Section 081113 SF - HOLLOW METAL DOORS AND FRAMES.docx

DOCX document 27 KB Posted

Attached to
Critical Housing Maintenance Construction at Lowman Ranger District, Boise National Forest, Idaho (GAOA)
Solicitation number
1240LT26Q0011
Issued by

About this file

This is a technical specification section for hollow metal doors and frames required as part of the Critical Housing Maintenance Construction project at Lowman Ranger District, Boise National Forest, Idaho. The specification establishes requirements for both interior and exterior hollow metal doors and frames, including materials, fabrication standards, installation procedures, and performance criteria. Interior doors and frames must comply with SDI A250.8 Level 2 heavy-duty standards with uncoated steel sheet minimum 0.053 inch thickness and prime finish. Exterior doors and frames must be 1-3/4 inches thick with metallic-coated steel sheet (minimum 0.042 inch thickness with A40 coating), polyurethane or polyisocyanurate core, and thermal-rated doors requiring R-value of at least 10 when tested per ASTM C 1363. Fire-rated assemblies must comply with NFPA 80 and applicable testing standards (NFPA 252, UL 10C, NFPA 257, or UL 9).

Approved manufacturers include Ceco Door, ASSA ABLOY, DKS Steel Door & Frame Systems, Mesker Door, Pioneer Industries, Rocky Mountain Metals, and Steelcraft. Fabrication requirements include rigid construction free of defects, proper welding of frame sections, weep-hole openings in exterior doors, and factory hardware preparation according to SDI A250.6 and BHMA A156.115 standards. Installation must achieve strict tolerances (±1/16 inch for squareness, alignment, twist, and plumb) and comply with SDI A250.11 or NAAMM-HMMA 840. Material specifications reference ASTM standards for cold-rolled steel, hot-rolled steel, metallic-coated steel, galvanized fasteners, and grout. The specification includes detailed requirements for frame anchors, floor anchors, glazing stops, and door silencers, with field adjustments and prime-coat touchup required immediately after erection.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

USDA FOREST SERVICE R-4

YOUR PROJECT NAME HER

SECTION 081113 - HOLLOW METAL DOORS AND FRAMES

GENERAL

SUMMARY

Section includes hollow-metal work.

DEFINITIONS

Minimum Thickness: Minimum thickness of base metal without coatings according to NAAMM-HMMA 803 or SDI A250.8.

ACTION SUBMITTALS

Product Data: For each type of product.

Shop Drawings: Include elevations, door edge details, frame profiles, metal thicknesses, preparations for hardware, and other details.

INFORMATIONAL SUBMITTALS

Product test reports.

MEASUREMENT AND PAYMENT

No separate payment will be made for the work included under this section; rather payment shall be considered to be included in the items of work listed in the Schedule of Items.

PRODUCTS

MANUFACTURERS

Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following:

Ceco Door; ASSA ABLOY.

DKS Steel Door & Frame Systems, Inc.

Mesker Door Inc.

Pioneer Industries.

Rocky Mountain Metals, Inc.

Steelcraft; an Allegion brand.

REGULATORY REQUIREMENTS

Fire-Rated Assemblies: Complying with NFPA 80 and listed and labeled by a qualified testing agency acceptable to authorities having jurisdiction for fire-protection ratings indicated, based on testing at positive pressure according to NFPA 252 or UL 10C.

Smoke- and Draft-Control Assemblies: Provide an assembly with gaskets listed and labeled for smoke and draft control by a qualified testing agency acceptable to authorities having jurisdiction, based on testing according to UL 1784 and installed in compliance with NFPA 105.

Fire-Rated, Borrowed-Lite Assemblies: Complying with NFPA 80 and listed and labeled by a testing and inspecting agency acceptable to authorities having jurisdiction for fire-protection ratings indicated, based on testing according to NFPA 257 or UL 9.

INTERIOR DOORS AND FRAMES

Heavy-Duty Frames: SDI A250.8, Level 2. At locations indicated in the Door and Frame Schedule.

Physical Performance: Level B according to SDI A250.4.

Doors:

Frames:

Materials: Uncoated, steel sheet, minimum thickness of 0.053 inch.

Sidelite Frames: Fabricated from same thickness material as adjacent door frame.

Construction: Full profile welded.

Exposed Finish: Prime.

EXTERIOR HOLLOW-METAL DOORS AND FRAMES

Heavy-Duty Doors and Frames: SDI A250.8, Level 2. At locations indicated in the Door and Frame Schedule.

Physical Performance: Level B according to SDI A250.4.

Doors:

Type: As indicated in the Door and Frame Schedule.

Thickness: 1-3/4 inches.

Face: Metallic-coated steel sheet, minimum thickness of 0.042 inch, with minimum A40 coating.

Edge Construction: Model 1, Full Flush.

Core: Polyurethane or Polyisocyanurate.

Thermal-Rated Doors: Provide doors fabricated with thermal-resistance value (R-value) of not less than 10 deg F x h x sq. ft./Btu when tested according to ASTM C 1363.

Frames:

Materials: Metallic-coated steel sheet, minimum thickness of 0.053 inch, with minimum A40 coating.

Construction: Full profile welded.

Exposed Finish: Prime.

BORROWED LITES

Hollow-metal frames of uncoated steel sheet, minimum thickness of 0.053 inch.

Construction: Full profile welded.

FRAME ANCHORS

Jamb Anchors:

Stud-Wall Type: Designed to engage stud, welded to back of frames; not less than 0.042 inch thick.

Compression Type for Drywall Slip-on Frames: Adjustable compression anchors.

Floor Anchors: Formed from same material as frames, minimum thickness of 0.042 inch, and as follows:

Monolithic Concrete Slabs: Clip-type anchors, with two holes to receive fasteners.

Separate Topping Concrete Slabs: Adjustable-type anchors with extension clips, allowing not less than 2-inch height adjustment. Terminate bottom of frames at finish floor surface.

MATERIALS

Cold-Rolled Steel Sheet: ASTM A 1008/A 1008M, Commercial Steel (CS), Type B; suitable for exposed applications.

Hot-Rolled Steel Sheet: ASTM A 1011/A 1011M, Commercial Steel (CS), Type B; free of scale, pitting, or surface defects; pickled and oiled.

Metallic-Coated Steel Sheet: ASTM A 653/A 653M, Commercial Steel (CS), Type B.

Frame Anchors: ASTM A 879/A 879M, Commercial Steel (CS), 04Z (12G) coating designation; mill phosphatized.

For anchors built into exterior walls, steel sheet complying with ASTM A 1008/A 1008M or ASTM A 1011/A 1011M, hot-dip galvanized according to ASTM A 153/A 153M, Class B.

Inserts, Bolts, and Fasteners: Hot-dip galvanized according to ASTM A 153/A 153M.

Power-Actuated Fasteners in Concrete: From corrosion-resistant materials.

Grout: ASTM C 476, except with a maximum slump of 4 inches (102 mm), as measured according to ASTM C 143/C 143M.

Mineral-Fiber Insulation: ASTM C 665, Type I (blankets without membrane facing).

Glazing: Section 088000 "Glazing."

FABRICATION

Fabricate hollow-metal work to be rigid and free of defects, warp, or buckle. Accurately form metal to required sizes and profiles, with minimum radius for metal thickness. Where practical, fit and assemble units in manufacturer's plant. To ensure proper assembly at Project site, clearly identify work that cannot be permanently factory assembled before shipment.

Hollow-Metal Doors:

Exterior Doors: Provide weep-hole openings in bottoms of exterior doors to permit moisture to escape. Seal joints in top edges of doors against water penetration.

Hollow-Metal Frames: Where frames are fabricated in sections due to shipping or handling limitations, provide alignment plates or angles at each joint, fabricated of same thickness metal as frames.

Provide countersunk, flat- or oval-head exposed screws and bolts for exposed fasteners unless otherwise indicated.

Floor Anchors: Weld anchors to bottoms of jambs with at least four spot welds per anchor; however, for slip-on drywall frames, provide anchor clips or countersunk holes at bottoms of jambs.

Jamb Anchors: Provide number and spacing of anchors as follows:

Stud-Wall Type: Locate anchors not more than 18 inches (457 mm) from top and bottom of frame. Space anchors not more than 32 inches (813 mm) o.c. and as follows:

Three anchors per jamb up to 60 inches (1524 mm) high.

Four anchors per jamb from 60 to 90 inches (1524 to 2286 mm) high.

Compression Type: Not less than two anchors in each frame.

Door Silencers: Except on weather-stripped frames, drill stops to receive door silencers.

Single-Door Frames: Drill stop in strike jamb to receive three door silencers.

Double-Door Frames: Drill stop in head jamb to receive two door silencers.

Hardware Preparation: Factory prepare hollow-metal work to receive templated mortised hardware; include cutouts, reinforcement, mortising, drilling, and tapping according to SDI A250.6, the Door Hardware Schedule, and templates.

Reinforce doors and frames to receive nontemplated, mortised, and surface-mounted door hardware.

Comply with applicable requirements in SDI A250.6 and BHMA A156.115 for preparation of hollow-metal work for hardware.

Stops and Moldings: Provide stops and moldings around glazed lites and louvers where indicated. Form corners of stops and moldings with butted or mitered hairline joints.

Single Glazed Lites: Provide fixed stops and moldings welded on secure side of hollow-metal work.

Multiple Glazed Lites: Provide fixed and removable stops and moldings so that each glazed lite is capable of being removed independently.

Provide fixed frame moldings on outside of exterior and on secure side of interior doors and frames.

Provide loose stops and moldings on inside of hollow-metal work.

Coordinate rabbet width between fixed and removable stops with glazing and installation types indicated.

STEEL FINISHES

Prime Finish: Clean, pretreat, and apply manufacturer's standard primer.

Shop Primer: SDI A250.10.

EXECUTION

INSTALLATION

Hollow-Metal Frames: Install hollow-metal frames for doors, borrowed lites, and other openings, of size and profile indicated. Comply with SDI A250.11 or NAAMM-HMMA 840 as required by standards specified.

Set frames accurately in position; plumbed, aligned, and braced securely until permanent anchors are set. After wall construction is complete, remove temporary braces, leaving surfaces smooth and undamaged.

At fire-rated openings, install frames according to NFPA 80.

Where frames are fabricated in sections because of shipping or handling limitations, field splice at approved locations by welding face joint continuously; grind, fill, dress, and make splice smooth, flush, and invisible on exposed faces.

Install frames with removable stops located on secure side of opening.

Install door silencers in frames before grouting.

Remove temporary braces necessary for installation only after frames have been properly set and secured.

Check plumb, square, and twist of frames as walls are constructed. Shim as necessary to comply with installation tolerances.

Field apply bituminous coating to backs of frames that will be filled with grout containing antifreezing agents.

Floor Anchors: Provide floor anchors for each jamb and mullion that extends to floor, and secure with postinstalled expansion anchors.

Floor anchors may be set with power-actuated fasteners instead of postinstalled expansion anchors if so indicated and approved on Shop Drawings.

In-Place Metal or Wood-Stud Partitions: Secure slip-on drywall frames in place according to manufacturer's written instructions.

Installation Tolerances: Adjust hollow-metal door frames for squareness, alignment, twist, and plumb to the following tolerances:

Squareness: Plus or minus 1/16 inch , measured at door rabbet on a line 90 degrees from jamb perpendicular to frame head.

Alignment: Plus or minus 1/16 inch, measured at jambs on a horizontal line parallel to plane of wall.

Twist: Plus or minus 1/16 inch measured at opposite face corners of jambs on parallel lines, and perpendicular to plane of wall.

Plumbness: Plus or minus 1/16 inch measured at jambs at floor.

Hollow-Metal Doors: Fit hollow-metal doors accurately in frames, within clearances specified below. Shim as necessary.

Non-Fire-Rated Steel Doors:

Between Door and Frame Jambs and Head: 1/8 inch (3.2 mm) plus or minus 1/32 inch (0.8 mm).

Between Edges of Pairs of Doors: 1/8 inch (3.2 mm) to 1/4 inch (6.3 mm) plus or minus 1/32 inch (0.8 mm).

At Bottom of Door: 3/4 inch (19.1 mm) plus or minus 1/32 inch (0.8 mm).

Between Door Face and Stop: 1/16 inch (1.6 mm) to 1/8 inch (3.2 mm) plus or minus 1/32 inch (0.8 mm).

Fire-Rated Doors: Install doors with clearances according to NFPA 80.

Smoke-Control Doors: Install doors and gaskets according to NFPA 105.

Glazing: Comply with installation requirements in Section 088000 "Glazing" and with hollow-metal manufacturer's written instructions.

Secure stops with countersunk flat- or oval-head machine screws spaced uniformly not more than 9 inches (230 mm) o.c. and not more than 2 inches (51 mm) o.c. from each corner.

ADJUSTING AND CLEANING

Final Adjustments: Check and readjust operating hardware items immediately before final inspection. Leave work in complete and proper operating condition. Remove and replace defective work, including hollow-metal work that is warped, bowed, or otherwise unacceptable.

Remove grout and other bonding material from hollow-metal work immediately after installation.

Prime-Coat Touchup: Immediately after erection, sand smooth rusted or damaged areas of prime coat and apply touchup of compatible air-drying, rust-inhibitive primer.

Metallic-Coated Surface Touchup: Clean abraded areas and repair with galvanizing repair paint according to manufacturer's written instructions.

Touchup Painting: Cleaning and touchup painting of abraded areas of paint are specified in painting Sections.

END OF SECTION 081113

FEBRUARY 2022

HOLLOW METAL DOORS AND FRAMES
081113 - 6