Attachment 8 Horticultural Research Lab Hazardous Material Survey Report - compressed.pdf
PDF 22 MB Posted
- Attached to
- Tornado Damage Repairs at the USDA-ARS U. S. Horticultural Research Laboratory, Ft. Pierce, Florida
- Solicitation number
- 1232SA26R0020
About this file
This is a Hazardous Material Survey Report for the Horticultural Research Lab located at 2001 South Rock Road in Fort Pierce, Florida. The survey was conducted on February 17, 2026, by Terracon Consultants Inc., an AHERA-accredited firm, to identify asbestos-containing materials (ACM), lead-based paint, polychlorinated biphenyls (PCBs), and universal/hazardous waste prior to planned demolition of the Clean Greenhouse and Regular Greenhouse, as well as HVAC duct replacement in the Pilot Plant and Micro Lab buildings.
The survey encompassed 65 bulk asbestos samples collected from thirteen homogeneous areas across four structures, eight paint chip samples, and eight caulk samples analyzed for PCBs. Laboratory analysis results indicate that asbestos was not detected in any of the 65 samples analyzed via Polarized Light Microscopy. Lead was not detected above laboratory reporting limits in any of the eight paint chip samples tested via Flame Atomic Absorption Spectrometry. Detectable PCB concentrations above the method detection limit were not identified in the seven collected caulk samples, with none exceeding the 50 ppm regulatory threshold. The survey identified universal waste items requiring proper disposal or recycling consideration, including 18 fluorescent light fixtures per greenhouse, electrical ballasts, space heaters, ceiling fans, and other equipment. The report notes that other building materials in the Pilot Plant and Micro Lab were not fully sampled and should be assumed to contain asbestos until proven otherwise through appropriate testing. No evidence of spills or leakage was observed from fertilizer solution reservoirs, though these should be drained and relocated or recycled prior to demolition.
View the file
Other files
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
3347 NW 55th Street Fort Lauderdale, Florida 33319
P (954) 741-8282 Terracon.com
Facilities | Environmental | Geotechnical | Materials I
March 6, 2026
The Johnson McAdams Firm, P.A.
108 West Market Street Greenwood, MS 38930
Attn: Rebecca P. Palmer P: (662) 455-4945 E: becky.palmer@jmcfirm.com
Re: Hazardous Material Survey Report Horticultural Research Lab 2001 South Rock Road Fort Pierce, Florida 34945 Terracon Project No. 34267020
Dear Ms. Palmer:
The purpose of this report is to present the results of the hazardous material survey performed on February 17, 2026, of the structures located at 2001 South Rock Road in Fort Pierce, Florida. This survey was conducted in general accordance with Terracon proposal number P34267020, dated January 26, 2026. We understand that these services were requested due to the planned demolition of the Clean Greenhouse, Regular Greenhouse and the planned renovation of the HVAC duct replacement within the Pilot Plant and Micro Lab buildings.
At the client’s direction, no additional interior or exterior building materials were sampled in the Pilot Plant or Micro Lab buildings beyond the grey mastic on the HVAC metal ducts observed at the time of Survey. Consequently, other building materials within these structures are assumed to contain asbestos until proven otherwise through appropriate sampling and laboratory analysis.
At the client’s request, the Clean Greenhouse and Regular Greenhouse were surveyed throughout the interior, exterior, and roof of the facility.
Asbestos was not detected in samples collected from the structures.
Lead was not detected above the detection Limit in the paint chip samples collected from the structures.
Polychlorinated biphenyls (PCBs) were not detected above the method detection limit in the samples collected from the structures.
Items with proper disposal or recycling considerations, such as ballasts and fluorescent light tubes, were observed. Please refer to the attached report for details
Terracon appreciates the opportunity to provide these services to The Johnson McAdams Firm, P.A. If you have any questions regarding this report, please contact the undersigned at (954) 703-1865.
Sincerely, Terracon Consultants Inc.
Florida Asbestos Consulting Business License No. ZA337
Sergio A. Adasme
Project Industrial Hygienist
Michael W. Schrum, P.E.
Licensed Asbestos Consultant AX078
3347 NW 55th Street Fort Lauderdale, Florida 33319
P (954) 741-8282 Terracon.com
Facilities | Environmental | Geotechnical | Materials I
Hazardous Material Survey Report Horticultural Research Lab
2001 South Rock Road
Fort Pierce, Florida 34945
March 6, 2026 | Terracon Project No. 34267020
Hazardous Material Survey Report Horticultural Research Lab | Fort Pierce, Florida 34945 March 6, 2026 | Terracon Project No. 34267020
Facilities | Environmental | Geotechnical | Materials i
Table of Contents
Page No.
1.0 INTRODUCTION
2.0 BUILDING DESCRIPTION
3.0 FIELD ACTIVITIES
3.1 Asbestos
3.2 Lead Paint
3.3 PCBs
3.4 Universal and Hazardous Waste
4.0 REGULATORY OVERVIEW
4.1 ASBESTOS
4.2 LEAD IN CONSTRUCTION
4.3 PCBS
4.4 UNIVERSAL AND HAZARDOUS WASTE
5.0 FINDINGS AND RECOMMENDATIONS
5.1 ASBESTOS
5.2 LEAD PAINT
5.3 PCB EVALUATION
5.4 UNIVERSAL AND HAZARDOUS WASTE
6.0 GENERAL COMMENTS
Appendices Appendix A Asbestos Survey Sample Results Summary Appendix B Asbestos Laboratory Analytical Report Appendix C Lead Paint Laboratory Analytical Report Appendix D PCBs Laboratory Analytical Report Appendix E Photographs Appendix F Licenses and Certifications Appendix G Sample Location Diagram
March 6, 2026 | Terracon Project No. 34267020
Facilities | Environmental | Geotechnical | Materials 1
1.0 Introduction
Terracon Consultants, Inc. (Terracon) conducted a hazardous material survey of the structures at 2001 South Rock Road in Fort Pierce, Florida 34945. The survey was conducted on February 17, 2026, by an AHERA-accredited Asbestos Building Inspectors in general accordance with Terracon proposal number. P34267020, dated January 26, 2026.
Building components were visually assessed, and homogeneous areas of suspect asbestos-containing materials (ACM) were identified and documented. Paint chip samples were collected to determine the presence or absence of lead-containing paint. Caulk samples were collected and analyzed for the presence of Polychlorinated Biphenyls (PCBs) and the buildings were visually evaluated for the presence of potential universal and hazardous waste that would likely be disturbed or impacted during the planned demolition. Asbestos sampling was performed in general accordance with EPA Asbestos Hazard Emergency Response Act (AHERA) sampling protocols, National Emission Standards for Hazardous Air Pollutants (NESHAP) regulations, and sampling methods outlined in the Occupational Safety and Health Administration (OSHA) standards 29 Code of Federal Regulations (CFR) 1910 and 29 CFR 1926. Suspect ACM samples were delivered to an accredited laboratory for analysis by Polarized Light Microscopy (PLM). Lead samples were analyzed by Flame Atomic Absorption Spectrometry Method SW846-3050B/7000B and PCBs were analyzed by EPA Method 3540C and 8082A.
1.1 Project Objective
Based on information provided by the client, we understand the purpose of this evaluation was to identify the presence and location of accessible friable and nonfriable ACM, lead-containing paints, PCBs in caulk, and potential universal or hazardous waste that would likely be disturbed/impacted during the planned upcoming demolition/renovation of the structures.
EPA regulation 40 CFR 61, Subpart M, National Emission Standards for Hazardous Air Pollutants (NESHAP), prohibits the release of asbestos fibers to the atmosphere during demolition activities. The asbestos NESHAP requires that potentially regulated asbestos-containing building materials be identified, classified, and quantified prior to planned disturbances or demolition activities.
The project objective also included a survey and testing of surface coatings for the presence of lead that may impact worker exposure to these materials (OSHA) as well as the potential for waste materials to become hazardous waste or regulated material with regulated disposal requirements. PCB and Universal Waste were also evaluated for proper disposal.
March 6, 2026 | Terracon Project No. 34267020
Facilities | Environmental | Geotechnical | Materials 2
1.2 General Conditions and Limitations
The hazardous material survey encompassed the following areas:
Clean Greenhouse
Regular Greenhouse Pilot Plant Building Mirco Lab Building
At the direction of The Johnson McAdams Firm, P.A. (Client), other areas of the facility and their associated materials were not included in the scope of this survey. The level of effort and associated tasks performed for this service was limited to the scope of services outlined in Terracon Proposal number P34267020. Terracon did not attempt to identify every potential exposure or hazard present in the structures.
1.3 Reliance
This report is prepared for the exclusive use and reliance of the Client. Use or reliance by any other party is prohibited without the written authorization of the Client and Terracon.
Reliance on the report by the client and all authorized parties will be subject to the terms, conditions, and limitations stated in Terracon Proposal number P34267020, dated January 26, 2026.
2.0 Building Description
The facility was constructed between 1960 and 1970. The clean greenhouse encompasses approximately 11,500 square feet and features a plexiglass-sheeted roof and exterior wall covering on metal frame, supported by interior and exterior concrete block walls on a concrete slab. The regular greenhouse measures approximately 19,000 square feet and is constructed with a plexiglass-sheeted roof and exterior wall covering on metal frame, similarly, mounted on interior and exterior concrete block walls on a concrete slab. The pilot plant building is approximately 1,800 square feet and consists of a metal-sheeted roof and exterior wall covering, supported by a metal frame and concrete slab. The micro lab building also measures approximately 1,800 square feet and is constructed with a metal-sheeted roof and exterior wall covering, mounted on a metal frame and concrete slab.
March 6, 2026 | Terracon Project No. 34267020
Facilities | Environmental | Geotechnical | Materials 3
3.0 Field Activities
The survey was conducted by Mr. Ryan Nanan (AHERA-accredited Asbestos Building Inspector Number 200206) and Mr. Jesse Beckles (AHERA-accredited Asbestos Building Inspector Number 0091-004-45969). Copies of the asbestos inspector’s certificates are attached in Appendix E. The survey was conducted in general accordance with the sample collection protocols established in EPA regulation 40 CFR 763 (AHERA). A summary of survey activities is provided below.
3.1 Asbestos
3.1.1 Visual Assessment
Our survey activities began with visual observation of the interior, exterior, and roof finishes of the structures likely to be impacted by planned demolition/renovation. A homogeneous area (HA) consists of building materials that appear similar throughout in terms of color, texture, and date of application. The assessment was conducted throughout visually accessible areas of the subject property. Building materials identified as glass, wood, or metal were not considered suspect ACM.
3.1.2 Physical Assessment
A physical assessment of each homogeneous area of suspect ACM was conducted to assess the friability and condition of the materials. A friable material is defined by the EPA as a material, which can be crumbled, pulverized, or reduced to powder by hand pressure when dry. Friability was assessed by physically touching suspect materials.
3.1.3 Sample Collection
Based on results of the visual observation, bulk samples of suspect ACM were collected in general accordance with AHERA sampling protocols. Random samples of suspect materials were collected in each homogeneous area. Bulk samples were collected using wet methods as applicable to reduce the potential for fiber release. Samples were placed in sealable containers and labeled with unique sample numbers using an indelible marker.
Terracon collected 65 bulk samples from thirteen homogeneous areas of suspect ACM. A summary of suspect ACM samples collected during the survey is included as Appendix A.
3.1.4 Sample Analysis
Bulk samples were submitted under chain of custody to Eurofins Built Environment Testing East, LLC (Eurofins) in Chantilly, Virginia for analysis by PLM with dispersion staining techniques per EPA methodology (EPA Method 600/R-93/116). The percentage of asbestos, where applicable, was determined by microscopic visual estimation. Eurofins is accredited under the National Voluntary Laboratory Accreditation Program (NVLAP Accreditation No.
600331-0).
March 6, 2026 | Terracon Project No. 34267020
Facilities | Environmental | Geotechnical | Materials 4
3.2 Lead Paint
The lead paint sampling was conducted by Mr. Ryan Nanan of Terracon. Paint chip samples were collected from homogenous painted surfaces identified to determine its lead content, measured by parts per million (ppm). Suspect lead paint samples were collected in general accordance with the EPA’s work practice standards for conducting lead paint activities (40 CFR 745.227). Currently, proposed renovation and demolition activities that could potentially disturb lead paint are subject to the OSHA regulations (29 CFR 1926.62 – Lead).
The lead paint sampling began with the Terracon representative walking the subject structures, observing painted surfaces, and selecting sample locations. After the sampling strategy was determined, Terracon collected eight paint chip samples from homogeneous surfaces.
Paint chip samples were submitted under a chain of custody to Eurofins of Fort Lauderdale, Florida. Paint chip samples were analyzed by Flame Atomic Absorption Spectrophotometry method SW846-3050B/7000B. Eurofins is an American Industrial Hygiene Association (AIHA) Environmental Lead Laboratory Accreditation (ELLAP) accredited laboratory (ELLAP Lab Code 200738-0), to perform Flame Atomic Absorption Spectrophotometry analysis. The lead paint laboratory analytical report is provided in Appendix C.
3.3 PCBs
In addition, Terracon collected eight bulk caulk samples for laboratory analysis of PCBs by EPA Methods 3540C and 8082A. A summary of the PCB in caulk samples collected and the laboratory results are included in Appendix D.
3.4 Universal and Hazardous Waste
Terracon performed a visual assessment of miscellaneous or hazardous materials which may be impacted during the planned demolition/renovation to attempt to identify materials that may impact worker exposure to these materials (OSHA) as well as the potential for waste materials to become a hazardous waste or regulated material with regulated disposal requirements. Testing of the suspect hazardous materials identified was specifically excluded from this assessment. These miscellaneous hazardous or regulated materials may include batteries, mercury-containing equipment, such as thermostats and fluorescent light bulbs, ballasts, fire exit lighting, and smoke detectors.
4.0 Regulatory Overview
4.1 Asbestos
The following sections provide a general overview to the applicable asbestos regulations.
Please refer to the complete current regulation in order to verify compliance before any actions are initiated on an ACM.
March 6, 2026 | Terracon Project No. 34267020
Facilities | Environmental | Geotechnical | Materials 5
4.1.1 NESHAP
The asbestos NESHAP (40 CFR Part 61, Subpart M) regulates asbestos fiber emissions and asbestos waste disposal practices. The NESHAP regulation also requires the identification and classification of existing ACM according to friability prior to renovation or demolition activity.
Under NESHAP, asbestos-containing building materials are classified as:
1. Friable ACM,
2. Category I Non-Friable ACM, or
3. Category II Non-Friable ACM.
Friable materials are those that, when dry, may be crumbled, pulverized, or reduced to powder by hand pressure. Category I Non-Friable ACM includes packings, gaskets, resilient floor coverings, and asphalt roofing products containing more than 1% asbestos. Category II Non-Friable ACM are any materials other than Category I Non-Friable ACM that contain more than 1% asbestos. Under NESHAP, Regulated Asbestos-Containing Materials (RACM) are classified as:
4. Friable ACM, or
5. Category I Non-Friable ACM that is in poor condition and/or has become friable, or
6. Category I Non-Friable ACM that will be or has been subjected to sanding, grinding, cutting, or abrading, or
7. Category II Non-Friable ACM that has a high probability of becoming or will become crumbled, pulverized, or reduced to powder by the forces expected to act upon the material in the course of renovation or demolition operations.
In the State of Florida, asbestos activities are regulated by the Florida Department of Environmental Protection (FDEP). Some counties have developed an enforcement division to carry out the responsibilities of the FDEP and have developed environmental and asbestos ordinances in which additional compliance is required. Since the facility is located in St.
Lucie County, Florida, the NESHAP regulations are under the jurisdiction of the St. Lucie County Florida Department of Health (561-837-5900).
Per the NESHAP, RACM must be removed prior to renovation or demolition activities that will disturb the materials. Any removal of ACM or RACM must be conducted by a State of Florida-licensed asbestos abatement contractor, in compliance with Florida Statute (F.S) 469.001-014.
March 6, 2026 | Terracon Project No. 34267020
Facilities | Environmental | Geotechnical | Materials 6
4.1.2 OSHA
OSHA’s general industry asbestos standard (29 CFR 1910.1001) requires employers to exercise due diligence in complying with the requirements to inform their employees and affected contractors working in the facility about the presence and location of both ACM and materials assumed to contain asbestos.
The OSHA Asbestos standard for construction (29 CFR 1926.1101) regulates workplace exposure to asbestos during construction and maintenance activities. The standard classifies construction and maintenance activities which could disturb ACM and specifies work practices and precautions which employers must follow when engaging in each class of regulated work. States which administer their own federally approved state OSHA programs may require additional precautions.
A full copy of the OSHA asbestos standard for general and construction industry may be found at OSHA’s website (www.osha.gov) and should be referenced for specific information.
4.2 Lead in Construction
Lead is regulated by the EPA, U.S. Department of Housing and Urban Development (HUD), FDEP and OSHA. The EPA and FDEP regulate lead use, removal, and disposal, and OSHA regulates lead exposure to workers. The EPA and HUD, with their small child-safety focus, define Lead-Based Paint (LBP) as paint, varnish, stain, or other applied coating that contains lead equal to or greater than 1.0 mg/cm2, 5,000 ppm, or 0.5% by dry weight as determined by laboratory analysis.
However, for the purpose of the OSHA lead standard, with its focus on the safety/exposure of construction workers, lead-containing paint or LCP includes any detectable concentrations of metallic lead, all inorganic lead compounds, and organic lead soaps. A synopsis of the OSHA regulations (29 CFR 1926.62) and the applicability are as follows:
The OSHA Lead Standard for Construction (29 CFR 1926.62) applies to all construction work where an employee may be occupationally exposed to lead. All work related to construction, alteration, or repair (including painting and decorating) is included. The lead-in-construction standard applies to any detectable concentration of lead in paint, as even small concentrations of lead can result in unacceptable employee exposures depending on the method of removal and other workplace conditions. The OSHA standard requires employee exposure to airborne lead be maintained below the PEL of 50 micrograms per cubic meter of air (ug/m3) over an 8-hour TWA.
Under this standard, construction includes, but is not limited to, the following:
Demolition or salvage of structures where lead or materials containing lead are present
Removal or encapsulation of materials containing lead
March 6, 2026 | Terracon Project No. 34267020
Facilities | Environmental | Geotechnical | Materials 7
New construction, alteration, repair, or renovation of structures, substrates, or portions containing lead, or materials containing lead
Installation of products containing lead
Lead contamination/emergency clean-up
Transportation, disposal, storage, or containment of lead or materials containing lead on the site or location at which construction activities are performed
Maintenance operations associated with construction activities described above
4.3 PCBS
Total PCB concentrations in excess of 50 ppm in caulks and coatings, and adjacent building surfaces (such as masonry) may be considered PCB-contaminated and must be properly managed during renovation and demolition projects under the EPA 40 CFR 761, Polychlorinated Biphenyls (PCBs) Manufacturing, Processing, Distribution in Commerce, and Use Prohibitions regulations. However, applied dried paint and caulking are considered PCB bulk waste products, which may be disposed of in a facility permitted, licensed, or registered by the State as a municipal or non-municipal non-hazardous waste disposal site.
4.4 Universal and Hazardous Waste
Universal waste (UW) are specific hazardous waste streams (batteries, pesticides, mercury containing equipment and bulbs) that a generator can choose to manage in an alternative manner in place of the more complex hazardous waste requirements. These wastes are generated by numerous businesses, typically in small quantities. The Universal Waste Rules (UWR) are intended to promote recycling as well as proper disposal by easing certain regulatory requirements. The federal UWRs are located at 40 CFR 261. Waste must be a hazardous waste before it can be a universal waste. If a hazardous waste stream is not managed as a universal waste, then the waste must be managed as a hazardous waste under the applicable hazardous waste regulations.
It should be noted that any materials resulting from the release or clean-up of spills or breakage of any universal waste is not itself universal waste. It must be determined whether or not such materials are a hazardous waste as identified in 40 CFR 261, and the material must then be managed and disposed of in accordance with applicable hazardous or solid waste regulations.
The potential exists for PCB-containing ballasts that do not have a “No PCBs” label. If ballasts are not marked "No PCBs", they must be treated as containing PCBs. In 1978, EPA issued a ban on manufacturing equipment using PCBs, which most ballasts manufactured before 1978 contained, due to it being hazardous to both human health and the environment.
PCBs are regulated under the Toxic Substance Control Act (TSCA) through the EPA. The EPA regulates the specifics on proper management of PCBs. If the generator determines that the
March 6, 2026 | Terracon Project No. 34267020
Facilities | Environmental | Geotechnical | Materials 8 ballasts do not contain hazardous constituents and do not contain PCBs then they can be disposed of as solid waste; however, they must first be evaluated to determine if they are hazardous. If they are hazardous and will be disposed of, they must be managed as hazardous waste and cannot be disposed of in a solid waste dumpster or landfill. The EPA and state recommendations for management of non-leaking ballasts is recycling. Ballasts that are leaking and are determined, or assumed, to contain PCBs must be disposed properly at an EPA-approved facility.
The potential mercury-containing equipment category was added to the Federal Rule at 40 CFR 273 on August 5, 2005. It includes devices, items, or articles which contain elemental mercury that is integral to their functions, and which would otherwise be regulated as a hazardous waste when discarded by virtue of exhibiting the toxicity characteristic (TC) for mercury (hazardous waste code D009). Some examples of such items include mercury-containing thermostats (formerly a separate universal waste category in the original rule), thermometers, barometers, mercury switches, and certain types of meters, regulators, and gauges, in which elemental mercury is contained in ampules or otherwise enclosed and can be managed intact. This category does not include cathode ray tubes or other types of electronic equipment in which elemental mercury is not integral to function, nor does it include mercury waste that is generated as a by-product through the process of manufacturing or treatment.
4.4.1 Hazardous Waste Disposal
A waste material has the characteristic of “toxicity” if it can leach specific toxic substances into the soil or groundwater. A toxicity characteristic leachate procedure (TCLP) is used to determine the leachability of waste materials.
TCLP testing was not performed as part of our work scope; however, the results of paint testing can be used to determine whether TCLP testing may be needed or not. If analytical results from paint testing are equal to or more than 20 times the TCLP regulatory limit, the waste may be hazardous. Likewise, if the total concentration of a chemical is less than 20 times the TCLP regulatory limit, then the sample is not likely to leach a sufficient quantity of that constituent to exceed the TCLP limit.
5.0 Findings and Recommendations
5.1 Asbestos
Asbestos was not identified in the samples collected during the February 17, 2026, asbestos survey.
If additional suspect materials are found during demolition activities, they should be assumed to contain asbestos until laboratory analysis can confirm or deny their asbestos content. A summary of suspect materials sampled is provided in Appendix A. Laboratory analytical reports are provided in Appendix B. Photographs are provided in Appendix D.
March 6, 2026 | Terracon Project No. 34267020
Facilities | Environmental | Geotechnical | Materials 9
5.2 Lead Paint
Lead was not detected above laboratory reporting limits in the samples collected during this site survey. An analytical summary of the paint chips samples and the laboratory analytical report and chain of custody are included in Appendix C. Representative Photographs are included in Appendix E.
5.3 PCB EVALUATION
Detectable PCB concentrations above the method detection limit were not identified in the 7 collected caulk samples. None of the caulk samples exceeded the regulatory threshold of 50 ppm. Applied dried paint and caulking are considered PCB bulk waste products, which may be disposed of in a facility permitted, licensed, or registered by the State as a municipal or non-municipal non-hazardous waste disposal site.
An analytical summary of the suspect caulk samples and the laboratory analytical report for PCBs is included in Appendices D. Representative photographs are included in Appendix E.
5.4 Universal and Hazardous Waste
Wall thermostats housing mercury-containing switches were not observed during this assessment. No electrical transformers potentially containing PCBs were observed during this assessment. A visual count of light fixtures and light tubes was conducted, and a count of potential mercury vapor-containing fluorescent tubes was obtained. Fixtures were assumed to contain one ballast each, which due to the age of the building are not likely to contain PCBs.
Suspect waste items of concern included:
18 fluorescent light fixtures were observed in each greenhouse unit.
One sunroof motor was observed in each greenhouse unit Two Space heaters were observed in each greenhouse bay Two ceiling mounted fans were observed in each greenhouse bay One wall vent fan was observed in each greenhouse bay Six grow lights were observed in the Clean Greenhouse section of the facility Seven Electrical Panel Boxes were observed in the hallways outside of the greenhouse bays Four fertilizer solution reservoir pumps and irrigation timers were observed in the hallway outside clean greenhouse section of the facility Four LED security light fixtures were observed on the pilot plant and micro-lab building Six fluorescent light fixtures were observed in the pilot plant building Six fluorescent light fixtures were observed in the micro-lab building Four Exit lights were observed in the pilot plant and micro-lab building Two garage door motors were observed in the pilot plant and micro-lab building
March 6, 2026 | Terracon Project No. 34267020
Facilities | Environmental | Geotechnical | Materials 10
No evidence of spills or leakage was observed from the fertilizer solution reservoirs observed in the greenhouse bays and hallways of the facility. chemicals on shelves in the building.
These reservoirs should be drained and relocated or recycled if no longer in use prior to building demolition or renovations.
6.0 General Comments
The hazardous material survey was conducted in a manner consistent with the level of care and skill ordinarily exercised by members of the profession currently practicing under similar conditions in the same locale. The results, findings, conclusions, and recommendations expressed in this report are based on conditions observed during our survey of the structures.
This report has been prepared on behalf of and exclusively for use by The Johnson McAdams Firm, P.A. for specific application to their project as discussed. This report is not a bidding document. Contractors or consultants reviewing this report must draw their own conclusions regarding further investigation or remediation deemed necessary. Terracon does not warrant the work of regulatory agencies, laboratories or other third parties supplying information which may have been used in the preparation of this report. No warranty expressed or implied is made.
Pre-Demolition Hazardous Material Survey Report
March 6, 2026 | Terracon Project No. 34267020
Facilities | Environmental | Geotechnical | Materials
Appendix A
Asbestos Survey Sample Results Summary
HA
Sample Number
Description Sample Location Lab Results
1 1A Interior/Exterior Concrete Block nad Mortar
Wall East - Clean Greenhouse
Gray Concrete: None Detected Gray Mortar: None Detected
1 1B Interior/Exterior Concrete Block nad Mortar
Wall Southeast - Clean Greenhouse
Gray Concrete: None Detected Gray Mortar: None Detected
1 1C Interior/Exterior Concrete Block nad Mortar
Wall West - Clean Greenhouse
Gray Concrete: None Detected Gray Mortar: None Detected
1 1D Interior/Exterior Concrete Block nad Mortar
Wall Southwest - Clean
Greenhouse Gray Concrete: None Detected Gray Mortar: None Detected
1 1E Interior/Exterior Concrete Block nad Mortar
Wall Northwest - Clean
Greenhouse Gray Concrete: None Detected Gray Mortar: None Detected
1 1F Interior/Exterior Concrete Block nad Mortar
Wall Northeast - Clean Greenhouse
Gray Concrete: None Detected Gray Mortar: None Detected
1 1G Interior/Exterior Concrete Block nad Mortar
Wall South - Clean Greenhouse
Gray Concrete: None Detected Gray Mortar: None Detected
2 2A Interior/Extrior Concrete Slab Southeast - Clean Greenhouse Gray Concrete: None Detected
2 2B Interior/Extrior Concrete Slab South - Clean Greenhouse Gray Concrete: None Detected
2 2C Interior/Extrior Concrete Slab Center - Clean Greenhouse Gray Concrete: None Detected
2 2D Interior/Extrior Concrete Slab Southwest - Clean
Greenhouse Gray Concrete: None Detected
2 2E Interior/Extrior Concrete Slab North - Clean Greenhouse Gray Concrete: None Detected
2 2F Interior/Extrior Concrete Slab East - Clean Greenhouse Gray Concrete: None Detected
2 2G Interior/Extrior Concrete Slab Northeast - Clean Greenhouse Gray Concrete: None Detected
3 3A White Wrap and Yellow Insulation on Pipe Southast - Clean Greenhouse
White Wrap: None Detected Silver Foil: None Detected
Beige Mastic: None Detected Yellow Insulation: None Detected
3 3B White Wrap and Yellow Insulation on Pipe East - Clean Greenhouse
White Wrap: None Detected Silver Foil: None Detected
Yellow Mastic: None Detected Off-White Compound: None Detected
Yellow Insulation: None Detected
3 3C White Wrap and Yellow Insulation on Pipe Center - Clean Greenhouse
White Wrap: None Detected Silver Foil: None Detected
Yellow Mastic: None Detected Yellow Insulation: None Detected
Appendix A
Asbestos Survey Sample Results Summary Horticultural Research Lab
2001 South Roack Road
Terracon Project No. 34267020
A-1
Number
Description Sample Location Lab Results
Appendix A
Asbestos Survey Sample Results Summary Horticultural Research Lab
2001 South Roack Road
Terracon Project No. 34267020 Fort Pierce, Florida 34945
3 3D White Wrap and Yellow Insulation on Pipe West- Clean Greenhouse
White Wrap: None Detected Silver Foil: None Detected
Yellow Mastic: None Detected Yellow Insulation: None Detected
3 3E White Wrap and Yellow Insulation on Pipe West - Clean Greenhouse
White Wrap: None Detected Silver Foil: None Detected
Yellow Mastic: None Detected Yellow Insulation: None Detected
4 4A Interior Grey Wall Caulking Center- Clean Greenhouse Gray Caulk: None Detected
4 4B Interior Grey Wall Caulking Center- Clean Greenhouse Gray Caulk: None Detected
4 4C Interior Grey Wall Caulking West - Clean Greenhouse Gray Caulk: None Detected
5 5A Roof/Exterior Clear Caulking East - Clean Greenhouse Transparent Caulk: None Detected
5 5B Roof/Exterior Clear Caulking West - Clean Greenhouse Transparent Caulk: None Detected
5 5C Roof/Exterior Clear Caulking Southwest - Clean
Greenhouse Transparent Caulk: None Detected
6 6A Interior White Door Frame Caulking West - Clean Greenhouse White Caulk: None Detected
6 6B Interior White Door Frame Caulking West - Clean Greenhouse White Caulk: None Detected
6 6C Interior White Door Frame Caulking West - Clean Greenhouse White Caulk: None Detected
7 7A Interior/Exterior Concrete Block nad Mortar
Wall East - Regular Greenhouse
Gray Concrete: None Detected Gray Mortar: None Detected
7 7B Interior/Exterior Concrete Block nad Mortar
Wall Northeast - Regular
Greenhouse Gray Concrete: None Detected Gray Mortar: None Detected
7 7C Interior/Exterior Concrete Block nad Mortar
Wall South - Regular Greenhouse
Gray Concrete: None Detected Gray Mortar: None Detected
7 7D Interior/Exterior Concrete Block nad Mortar
Wall Southeast - Regular
Greenhouse Gray Concrete: None Detected Gray Mortar: None Detected
7 7E Interior/Exterior Concrete Block nad Mortar
Wall Southwest - Regular
Greenhouse Gray Concrete: None Detected Gray Mortar: None Detected
7 7F Interior/Exterior Concrete Block nad Mortar
Wall Northwest - Regular
Greenhouse Gray Concrete: None Detected Gray Mortar: None Detected
7 7G Interior/Exterior Concrete Block nad Mortar
Wall Southwest - Regular
Greenhouse Gray Concrete: None Detected Gray Mortar: None Detected
A-2
Number
Description Sample Location Lab Results
Appendix A
Asbestos Survey Sample Results Summary Horticultural Research Lab
2001 South Roack Road
Terracon Project No. 34267020 Fort Pierce, Florida 34945
7 7H Interior/Exterior Concrete Block nad Mortar
Wall Northwest - Regular
Greenhouse Gray Concrete: None Detected Gray Mortar: None Detected
7 7I Interior/Exterior Concrete Block nad Mortar
Wall West - Regular Greenhouse
Gray Concrete: None Detected Gray Mortar: None Detected
8 8A Interior/Extrior Concrete Slab East - Regular Greenhouse Gray Concrete: None Detected
8 8B Interior/Extrior Concrete Slab Sotuheast - Regular
Greenhouse Gray Concrete: None Detected
8 8C Interior/Extrior Concrete Slab Center - Regular Greenhouse Gray Concrete: None Detected
8 8D Interior/Extrior Concrete Slab Center - Regular Greenhouse Gray Concrete: None Detected
8 8E Interior/Extrior Concrete Slab North - Regular Greenhouse Gray Concrete: None Detected
8 8F Interior/Extrior Concrete Slab Northwest - Regular
Greenhouse Gray Concrete: None Detected
8 8G Interior/Extrior Concrete Slab West - Regular Greenhouse Gray Concrete: None Detected
8 8H Interior/Extrior Concrete Slab West - Regular Greenhouse Gray Concrete: None Detected
8 8I Interior/Extrior Concrete Slab Southwest - Regular
Greenhouse Gray Concrete: None Detected
9 9A White Wrap and Yellow Insulation on Pipe East - Regular Greenhouse
White Wrap with Paint: None Detected Silver Foil: None Detected
Yellow Mastic: None Detected Yellow Insulation: None Detected
9 9B White Wrap and Yellow Insulation on Pipe Northeast - Regular
Greenhouse
White Wrap with Paint: None Detected Silver Foil: None Detected
Yellow Mastic: None Detected Yellow Insulation: None Detected
9 9C White Wrap and Yellow Insulation on Pipe Center - Regular Greenhouse
White Wrap with Paint: None Detected Silver Foil: None Detected
Yellow Mastic: None Detected Yellow Insulation: None Detected
9 9D White Wrap and Yellow Insulation on Pipe West - Regular Greenhouse
White Wrap with Paint: None Detected Silver Foil: None Detected
Yellow Mastic: None Detected Yellow Insulation: None Detected
9 9E White Wrap and Yellow Insulation on Pipe West - Regular Greenhouse
White Wrap with Paint: None Detected Silver Foil: None Detected
Yellow Mastic: None Detected Yellow Insulation: None Detected
10 10A Grey Interior Wall Caulking North - Regular Greenhouse Gray Caulk: None Detected
A-3
Number
Description Sample Location Lab Results
Appendix A
Asbestos Survey Sample Results Summary Horticultural Research Lab
2001 South Roack Road
Terracon Project No. 34267020 Fort Pierce, Florida 34945
10 10B Grey Interior Wall Caulking West - Regular Greenhouse Gray Caulk: None Detected
10 10C Grey Interior Wall Caulking East - Regular Greenhouse Gray Caulk: None Detected
Gray Compound: None Detected
11 11A Roof/Exterior Clear Caulknig Center - Regular Greenhouse Transparent Caulk: None Detected
11 11B Roof/Exterior Clear Caulknig West - Regular Greenhouse Transparent Caulk: None Detected
11 11C Roof/Exterior Clear Caulknig Sothuwest - Regular
Greenhouse Transparent Caulk: None Detected
11 11D Roof/Exterior Clear Caulknig Southeast - Regular
Greenhouse Transparent Caulk: None Detected
11 11E Roof/Exterior Clear Caulknig East - Regular Greenhouse Transparent Caulk: None Detected
12 12A Grey Mastic on Metal HVAC Duct North - Pilot Plant Building Gray Mastic: None Detected
12 12B Grey Mastic on Metal HVAC Duct Sotuthwest - Pilot Plant
Building Gray Mastic: None Detected
12 12C Grey Mastic on Metal HVAC Duct Center - Pilot Plant Building Gray Mastic: None Detected Silver Paint: None Detected
13 13A Grey Mastic on Metal HVAC Duct Center - Micro Lab Building Gray Mastic: None Detected Silver Foil: None Detected
13 13B Grey Mastic on Metal HVAC Duct North - Micro Lab Building Gray Mastic: None Detected Silver Foil: None Detected
13 13C Grey Mastic on Metal HVAC Duct South - Micro Lab Building Gray Mastic: None Detected
*Highlighted and bolded samples indicate materials with >1% asbestos.
*Bolded samples indicate materials with <1% asbestos.
A-4
March 6, 2026 | Terracon Project No. 34267020
Facilities | Environmental | Geotechnical | Materials
Appendix B
Asbestos Laboratory Analytical Report
Approved by:
Approved Signatory Alexis Starrett
Report for:
3347 NW 55th Street Fort Lauderdale, FL 33309
Regarding:
Eurofins Built Environment Testing East, LLC Project: Horticultural Research Lab; 2001 South Rock Road Fort Pierce, FL
EML ID: 4419123
All samples were received in acceptable condition unless noted in the Report Comments portion in the body of the report. The results relate only to the samples as received and tested. The results include an inherent uncertainty of measurement associated with estimating percentages by polarized light microscopy. Measurement uncertainty data for sample results with >1% asbestos concentration can be provided when requested.
Eurofins Built Environment Testing East, LLC ("the Company"), a member of the Eurofins Built Environment Testing group of companies, shall have no liability to the client or the client's customer with respect to decisions or recommendations made, actions taken or courses of conduct implemented by either the client or the client's customer as a result of or based upon the Test Results. In no event shall the Company be liable to the client with respect to the Test Results except for the Company's own willful misconduct or gross negligence nor shall the Company be liable for incidental or consequential damages or lost profits or revenues to the fullest extent such liability may be disclaimed by law, even if the Company has been advised of the possibility of such damages, lost profits or lost revenues. In no event shall the Company's liability with respect to the Test Results exceed the amount paid to the Company by the client therefor.
Dates of Analysis:
Asbestos PLM: 02-19-2026 and 02-20-2026
Service SOPs: Asbestos PLM (EPA 40CFR App E to Sub E of Part 763 & EPA 600/R-93-116, EBET-PLM-SOP83921) NVLAP Lab Code 600331-0
EMLab ID: 4419123, Page 1 of 18
March 6, 2026 | Terracon Project No. 34267020
Facilities | Environmental | Geotechnical | Materials
Appendix C
Lead Paint Laboratory Analytical Report
Sample ID Color Substrate Sample Location Paint Condition Test Result
(Lead in PPM)
L1 Brown Metal Door Clean Greenhouse Good < 47
L2 Brown Metal Door Frame Clean Greenhouse Good < 120
L3 Yellow Metal Pipe Clean Greenhouse Good <39
L4 Green Metal Pipe Clean Greenhouse Good < 39
L5 Yellow Metal Pipe Regular Greenhouse Good < 39
L6 Green Metal Pipe Regular Greenhouse Good < 39
L7 Red Metal Beam Pilot Plant Building Good < 39
L8 Red Metal Beam Micro-Lab Building Good < 390
Terracon Project No. 34267020
PPM = Parts Per Million
< = Not detected above the analytical method’s reporting limit.
Bold: Analytical results indicate detectable lead concentrations above the analytical method’s reporting limit.
Appendix C Table 2
Lead Paint Chips Sample Results Summary Horticultural Research Lab
2001 South Roack Road
A-1
Philip Newton
Report for:
3347 NW 55th Street Fort Lauderdale, FL 33309
Regarding:
Eurofins Built Environment Testing West, LLC Project: Horticultural Research Lab; 2001 South Rock Road Fort Pierce, FL
EML ID: 4419123
All samples were received in acceptable condition unless noted in the Report Comments portion in the body of the report. Due to the nature of the analyses performed, field blank correction of results is not applied. The results relate only to the samples as received and tested. Sample size, as it relates to Wipe samples only, is supplied by the client.
Eurofins Built Environment Testing West, LLC ("the Company"), a member of the Eurofins Built Environment Testing group of companies, shall have no liability to the client or the client's customer with respect to decisions or recommendations made, actions taken or courses of conduct implemented by either the client or the client's customer as a result of or based upon the Test Results.
In no event shall the Company be liable to the client with respect to the Test Results except for the Company's own willful misconduct or gross negligence nor shall the Company be liable for incidental or consequential damages or lost profits or revenues to the fullest extent such liability may be disclaimed by law, even if the Company has been advised of the possibility of such damages, lost profits or lost revenues. In no event shall the Company's liability with respect to the Test Results exceed the amount paid to the Company by the client therefor.
Dates of Analysis:
Lead - Flame AA: 02-20-2026
Service SOPs: Lead - Flame AA (EB-BC-S-8443) AIHA LAP, LLC accredited service, Lab ID #178697
Eurofins Built Environment Testing West, LLC's LabServe® reporting system includes automated fail-safes to ensure that all AIHA LAP, LLC quality requirements are met and notifications are added to reports when any quality steps remain pending.
EMLab ID: 4419123, Page 1 of 4
March 6, 2026 | Terracon Project No. 34267020
Facilities | Environmental | Geotechnical | Materials
Appendix D
PCB Laboratory Analytical Report
APPENDIX D
PCBS IN CAULK SAMPLE SUMMARY TABLE
HORTICULTURAL RESEARCH LAB
TERRACON PROJECT NO. 34267020
ND = None Detected
1 mg/kg = 1 ppm
Sample
ID
Material Description Material Location PCB Analyte PCB Content (mg/kg)
PCB1 Clean Greenhouse Exterior Wall Seams ND ND
PCB2 Clean Greenhouse Bathroom Fixtures ND ND
PCB3 Clean Greenhouse Conduit Penetrations Through Walls ND ND
PCB4 Regular Greenhouse Concrete Columns ND ND
PCB5 Regular Greenhouse Base of Metal Columns ND ND
PCB6 Regular Greenhouse Exterior Doors ND ND
PCB7 Regular Greenhouse Exterior Windows ND ND
Philip Newton
Report for:
3347 NW 55th Street Fort Lauderdale, FL 33309
Regarding:
Eurofins Built Environment Testing West, LLC Project: Horticultural Research Lab; 2001 South Rock Road Fort Pierce, FL
EML ID: 4419123
All samples were received in acceptable condition unless noted in the Report Comments portion in the body of the report. Due to the nature of the analyses performed, field blank correction of results is not applied. The results relate only to the samples as received and tested. Sample size, as it relates to Wipe samples only, is supplied by the client.
Eurofins Built Environment Testing West, LLC ("the Company"), a member of the Eurofins Built Environment Testing group of companies, shall have no liability to the client or the client's customer with respect to decisions or recommendations made, actions taken or courses of conduct implemented by either the client or the client's customer as a result of or based upon the Test Results.
In no event shall the Company be liable to the client with respect to the Test Results except for the Company's own willful misconduct or gross negligence nor shall the Company be liable for incidental or consequential damages or lost profits or revenues to the fullest extent such liability may be disclaimed by law, even if the Company has been advised of the possibility of such damages, lost profits or lost revenues. In no event shall the Company's liability with respect to the Test Results exceed the amount paid to the Company by the client therefor.
Dates of Analysis:
Lead - Flame AA: 02-20-2026
Service SOPs: Lead - Flame AA (EB-BC-S-8443) AIHA LAP, LLC accredited service, Lab ID #178697
Eurofins Built Environment Testing West, LLC's LabServe® reporting system includes automated fail-safes to ensure that all AIHA LAP, LLC quality requirements are met and notifications are added to reports when any quality steps remain pending.
EMLab ID: 4419123, Page 1 of 4
March 6, 2026 | Terracon Project No. 34267020
Facilities | Environmental | Geotechnical | Materials
Appendix E
Photographs
March 6, 2026 | Terracon Project No. 34267020
Facilities | Environmental | Geotechnical | Materials
Photo #1 HA-1 Interior/Exterior Concrete Block and Mortar Wall – Clean Greenhouse
Photo #2 HA-2 Interior/Exterior Concrete Slab – Clean Greenhouse
Photo #3 HA-3 White Wrap and Yellow Insulation on Pipe – Clean Greenhouse
Photo #4 HA-4 Grey Interior Wall Caulking – Clean Greenhouse
Photo #5 HA-5 Clear Roof Caulking – Clean Greenhouse
Photo #6 HA-6 Interior White Door Frame Caulking – Clean Greenhouse
March 6, 2026 | Terracon Project No. 34267020
Facilities | Environmental | Geotechnical | Materials
Photo #7 HA-7 Interior/Exterior Concrete Block and Mortar Wall – Regular Greenhouse
Photo #8 Interior/Exterior Concrete Slab Wall – Regular Greenhouse
Photo #9 HA-9 White Wrap and Yellow Insulation on Pipe – Regular Greenhouse
Photo #10 HA- 10 Grey Interior Wall Caulking – Regular Greenhouse
Photo #11 HA- 11 Clear Roof Caulking – Regular Greenhouse
Photo #12 HA-12 Grey Mastic on Metal HAVC Duct
March 6, 2026 | Terracon Project No. 34267020
Facilities | Environmental | Geotechnical | Materials
Photo #13 HA- 13Grey Mastic on Metal HAVC Duct
March 6, 2026 | Terracon Project No. 34267020
Facilities | Environmental | Geotechnical | Materials
Appendix F
Licenses and Certifications certifies
Jesse Beckles 5504 NW 51st Avenue, Tamarac, FL, 33319
Having passed a 25-question exam with a score of 70% or higher has successfully met training requirements for
Asbestos Refresher: Inspector Online FDBPR Asbestos Licensing Unit: Provider #0000995; Course #FL49-0006389 (½ Day; 3.40 Contact Hours)
(Reaccreditation for Inspector under TSCA Title II/AHERA) Conducted
2/27/2026
Certificate #: 0091 - 004-45969 Exam Date: 2/27/2026 EPA accreditation expires: 2/27/2027 Principal Instructor: Brian Duchene, PE, LAC CEUs: 0.4 FBPR LAC: #0000995; Course ## 0006389 FBPE CEHs: #0004021; Course #0009083/Educational Institutions: 4 CEHs
March 6, 2026 | Terracon Project No. 34267020
Facilities | Environmental | Geotechnical | Materials
Appendix G
Sample Location Diagram
Horticultural Research Lab
Scale: Not to Scale 2001 South Rock Road
Fort Pierce, Florida 34945 Project Number:34267020
N
2FPCB1
PCB2
PCB3
PCB4
PCB5
PCB6
PCB7
L1 L2
L3
L4 L5
L6
Horticultural Research Lab
Scale: Not to Scale 2001 South Rock Road
Fort Pierce, Florida 34945 Project Number:34267020
12A
12B
L7
12C
13A
13B
13C
L8
N N
Pilot Plant Building
Micro Lab Building
L7
L8
File details come from the government source that posted it. Updated .