Attachment 2 Redlined Plans 8Mar24.pdf
PDF 16 MB Posted
- Attached to
- Greenhouse Construction, Blueberry and Cranberry Research Station, Chatsworth, New Jersey
- Solicitation number
- 12305B24R0030
About this file
This document is an attachment to a Request for Proposal (RFP) for the construction of two 30' x 100' (6,000 square foot total) aluminum framed greenhouses at the Blueberry and Cranberry Research Station in Chatsworth, New Jersey. The solicitation, identified as 12305B24R0030, is a requirement of the United States Department of Agriculture (USDA), Agricultural Research Service (ARS) with an estimated construction value between $1,000,000 and $5,000,000.
The project includes furnishing all labor, materials, and equipment to construct the greenhouses with 6 mil poly inflated film covering, shade cloth, polycarbonate panels, exhaust fans, louvers, propane fired furnaces, circulation fans, greenhouse controls system, domestic water main, irrigation system, propane tank and piping, and new electrical service. The solicitation includes a base bid and three optional contract line items for additional work. The period of performance is 180 days after the notice to proceed. The solicitation is a total small business set-aside with a size standard of $45.0 million. Site visits are scheduled for 07/24/2024 and the deadline for submitting requests for information is 08/01/2024.
View the file
Other files
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NO SCALEVICINITY MAP
N
BLUEBERRY AND CRANBERRY RESEARCH CENTER
AGRICULTURAL RESEARCH SERVICE
U.S. DEPARTMENT OF AGRICULTURE
DRAWING NO.
INDEX OF DRAWINGS
SHEET NO. TITLE
LOCATION MAP NO SCALE
N
T100
C100
S100
S101
A100
A200
A300
M001
M100
M200
M600
E001
ES100
E100
E200
E600
E601
E700
TITLE SHEET
SITE LAYOUT
FOUNDATION PLAN
FOUNDATION DETAILS
FLOOR PLAN
ELEVATIONS
GREENHOUSE SECTION
MECHANICAL NOTES AND ABBREVIATIONS
MECHANICAL FLOOR PLAN
MECHANICAL ELEVATIONS
MECHANICAL SCHEDULE AND DETAILS
ELECTRICAL NOTES AND ABBREVIATIONS
SITE PLAN
FLOOR PLAN
ELEVATIONS
EXISTING PANEL SCHEDULES AND SINGLE LINE
NEW PANEL SCHEDULES
LIGHTING SLIDES
125 LAKE OSWEGO ROAD CHATSWORTH, NJ 08019
USDA
CRANBERRY BREEDING AND
GENETICS GREENHOUSE
PROJECT
LOCATION
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
C:\ Us ers
\JF
ER
GU
~1 \Ap pD ata
\Lo ca l\T em p\A cP ub lish
_1
\T1
.dw g M ar
, 2
4 - 2:
pm
P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
c
USDA AGRICULTURAL RESEARCH SERVICE
BLUEBERRY AND CRANBERRY RESEARCH CENTER
ADDITION TO CRANBERRY BREEDING AND GENETICS GREENHOUSE
CHATSWORTH, NEW JERSEY
TITLE SHEET
T100 1 1803/08/24
REH
REH
FEJ
10300 BALTIMORE AVE.
BELTSVILLE, MD 20705
XXX
6223-A
XXX
XXX
XXX
XXX
CHATSWORTH, NJ
PROJECT LOCATION:
125 LAKE OSWEGO ROAD
CHATSWORTH, NJ 08019
A-E CONTRACT #12305B21D0013 / 12305B22F0084
GREEN BANK
CHATSWORTH RD.
LAKE OSWEGO RD.
LA
KE
O
SW
EG
O
R D
PE
N
N P
L R
D
PENN PL RD.
PENN PL RD.
CONTRACTORS
HAUL ROUTE
100% DESIGN RE-SUBMITTAL
BID DESCRIPTION
BASE BID:
CONSTRUCTS A SINGLE GREENHOUSE STRUCTURE AS INDICATED AND SPECIFIED.
BID OPTION #1:
CONSISTS OF INSTALLATION OF EVAPORATIVE COOLING PADS FOR GREENHOUSE #1 AS DETAILED AND SPECIFIED.
BID OPTION #2:
CONSISTS OF CONSTRUCTING A SECOND GREENHOUSE STRUCTURE, GREENHOUSE #2, CONNECTED TO GREENHOUSE #1 AS DETAILED
AND SPECIFIED.
BID OPTION #3:
CONSISTS OF INSTALLATION OF EVAPORATIVE COOLING PADS FOR GREENHOUSE #2 AS DETAILED AND SPECIFIED.
NEW GRETNA
CHATSWORTH RD
CHATSWORTH
BARNEGAT RDTABERNACLE
CHATSWORTH RD
SAVOY RD
jferguson Stamp
EXISTING FUEL OIL TANK
EXISTING BOLLARDS
NEW 8" DIA. SCHEDULE 40
PIPE BOLLARDS (TYP. OF 5)
SEE DETAIL 3/C100
NEW PROPANE TANK N.I.C. INSTALLED
AND FURNISHED BY GOVERNMENT
8'-10"
1'-
2"
LINE OF OUTSIDE OF FOOTING
NEW CRANBERRY
RESEARCH GREENHOUSE
BASE BID
W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W
W W
W
EXISTING 2" WATER LINE
PROVIDE WET TAP AT EXISTING WATER LINE,
SEE DETAIL 2/C100.
PROVIDE NEW WATER LINE SEE MECHANICAL
'-0
EXISTING GREENHOUSE EXISTING GREENHOUSE
EXISTING HEADHOUSE
EXISTING HEADHOUSE
NEW CRANBERRY
RESEARCH GREENHOUSE
BID OPTION #2
6'
17'-4"
EQ. EQ. EQ.
7'
8'-2"
29'-10"
1'-
2"
29'-10"
'-6
W W
W
PROVIDE NEW WATER LINE SEE MECHANICAL
PROVIDE WET TAP AT EXISTING WATER LINE,
SEE DETAIL 2/C100.
1'-6"
61'-2"
EVAPORATIVE COOLING
PADS BID OPTION #3
EVAPORATIVE COOLING
PADS BID OPTION #1
BASE BIDBID OPTION #2
SCALE:
SITE PLAN
1" = 10'
C100
NORTH
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
c
USDA AGRICULTURAL RESEARCH SERVICE
BLUEBERRY AND CRANBERRY RESEARCH CENTER
ADDITION TO CRANBERRY BREEDING AND GENETICS GREENHOUSE
CHATSWORTH, NEW JERSEY
SITE LAYOUT
C100 2 1803/08/24
REH
REH
FEJ
10300 BALTIMORE AVE.
BELTSVILLE, MD 20705
XXX
6223-A
XXX
XXX
XXX
XXX
20'
SCALE: 1"=10'-0"
0 10' 30'
FINISHED GRADE
AROUND COVER
HAND TAMP BACKFILL
PVC WATERLINE, TYP.
THRUST BLOCK
#4 BARS, TYP.
EXISTING PIPE,
MATERIAL TYPE
VARIES
MECHANICAL JOINT
TAPPING TEE
MECHANICAL JOINT
GATE VALVE
CAST IRON VALVE BOX (COVER
MARKED WATER)
20"x20"x4" CONCRETE PAD W/6x6, W2.9xW2.9 W.W.F.
" M
IN
IM
UM
1"
SCALE:
TYPICAL WET TAP DETAIL
NONE
C100
1'-8"
SQUARE
3'- 0"
4'- 0"
1"
3"
FINISHED GRADE
#5 REBAR THRU PIPE
8"Ø SCH 40 PIPE,
PAINT SAFETY YELLOW
FILL PIPE w/ CONCRETE
& ROUND OFF TOP
SCALE:
TYPICAL BOLLARD DETAIL
NONE
C100
EXISTING GRAVEL PAVEMENT
NEW GRAVEL
PAVEMENT SURFACE
LIMIT OF GRAVEL REMOVAL/REPLACEMENT
1' MIN. 1' MIN.
6" M
IN
HAUNCHING
4" BEDDING MIN.
FINAL BACKFILL
INITIAL BACKFILL
NOTES:
1. MATCH THICKNESS OF EXISTING GRAVEL OR
4" MIN. WHICHEVER IS GREATER.
TRENCH BACKFILL NOTES
1. BEDDING SHALL BE CLASS II (SW OR SP) WORKED BY HAND. IF GROUNDWATER IS ENCOUNTERED. THEN CLASS II (GP)
BEDDING SHALL BE USED. BEDDING SHALL BE HAND TAMPED.
2. HAUNCHING AND INITIAL BACKFILL SHALL BE CLASS II (GW OR GP). HAUNCHING SHALL BE WORKED AROUND THE PIPE BY
HAND TO ELIMINATE VOIDS, AND SHALL BE HAND TAMPED ADJACENT TO THE PIPE. INITIAL BACK FILL SHALL BE COMPACTED
TO 96% STANDARD PROCTOR DENSITY.
3. FINAL BACKFILL SHALL BE CLASS I, II, OR III COMPACTED TO 96% STANDARD PROCTOR DENSITY. MATERIAL EXCAVATED FROM THE TRENCH MAY BE USED AS CLASS III MATERIAL IN TURFED AREAS IF IT IS FREE OF LARGE ROCKS OR COBBLES. THE TOP 8" OF FINAL BACKFILL IN A TRENCH CUT THROUGH EXISTING GRAVEL ROADWAYS SHALL BE CLASS I. COMPACTED TO 98%
STANDARD PROCTOR DENSITY.
4. ALL MATERIALS ARE CLASSIFIED IN ACCORDANCE WITH ASTM D 2321.
5. ALL MATERIALS SHALL BE INSTALLED IN MAXIMUM 6" LOOSE LIFTS. INITIAL AND FINAL BACKFILL MATERIALS SHALL BE
COMPACTED NEAR OPTIMUM MOISTURE CONTENT.
6. ALL TRENCH EXCAVATIONS SHALL BE SLOPED, SHORED, SHEETED, BRACED OR OTHERWISE SUPPORTED IN COMPLIANCE
WITH OSHA REGULATIONS AND ANY LOCAL ORDINANCES.
SCALE:
TYPICAL TRENCH DETAIL
NONE
C100
N.I.C.
jferguson Stamp
Wayne.Shekailo Rectangle
Wayne.Shekailo Line
Wayne.Shekailo Line
1'-6"
98'-2"
1'-6"101'-2"
1'- 6"
1'- 6"
'-4
" B
AS
E
BI
D
6'
S101
S101
4" CONCRETE WALKWAY 4" COMPACTED CRUSHED STONE
4'-0" 6'-10"
'-2
6'
'-2
5'-3"
6'
5'-3"
6'
'-2
1'- 6"
'-4
" B
ID
O
PT
IO
N
#2
6'
S101
4" CONCRETE WALKWAY
4'-0" 6'-10"
'-2
6'
'-2
5'-3"
6'
5'-3"
6' 4" COMPACTED CRUSHED STONE
S101
GREENHOUSE #1
BASE BID
GREENHOUSE #2
BID OPTION #2
1'- 8"
1'- 8"
'-9
'-9
S101
S101
S101
S101
S101
S101
S101
S101
S101
S101
S101
BASE BID
BID OPTION #2
S101
4" REINFORCED CONCRETE
PAD SLOPED FROM FINISH
WALKWAY ELEVATION TO
FINISHED GRADE
4" REINFORCED CONCRETE
PAD SLOPED FROM FINISH
WALKWAY ELEVATION TO
FINISHED GRADE
S101
S101
S101
4" REINFORCED CONCRETE
PAD SLOPED FROM FINISH
WALKWAY ELEVATION TO
FINISHED GRADE
4" REINFORCED CONCRETE
PAD SLOPED FROM FINISH
WALKWAY ELEVATION TO
FINISHED GRADE
SCALE:
FOUNDATION PLAN
1/4" = 1'-0"
S100
8'0 2' 4' 12'
SCALE: 1/4"= 1'-0"
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
c
USDA AGRICULTURAL RESEARCH SERVICE
BLUEBERRY AND CRANBERRY RESEARCH CENTER
ADDITION TO CRANBERRY BREEDING AND GENETICS GREENHOUSE
CHATSWORTH, NEW JERSEY
FOUNDATION PLAN
S100 3 1803/08/24
REH
REH
FEJ
10300 BALTIMORE AVE.
BELTSVILLE, MD 20705
XXX
6223-A
XXX
XXX
XXX
XXX
TRUE
NORTH
jferguson Stamp
Wayne.Shekailo Rectangle
Wayne.Shekailo Line
1'-6"
2'- 2"
4"
6'-0"
4"
4" COMPACTED
CRUSHED STONE
2" MIN.
2" M
IN
#4 @ 9" O.C.
1'-
1'-2"
SCALE:
FOUNDATION DETAIL
1-1/2" = 1'-0"
S101
SCALE:
SLAB ON GRADE DETAIL
1-1/2" = 1'-0"
S101
(4) #4 CONT. TOP AND BOTTOM
6" x 6" x 4.0 W.W.M. CONT. 4" COMPACTED CRUSHED
STONE
1" CHAMFER
COMPACTED EXISTING SOILS
COMPACTED EXISTING SOILS
TOP OF FOOTING
4'-0" A.F.G.
TOP OF CONCRETE
0'-4" A.F.G.
(2) #4 CONT.
1'-6"
2'- 2"
4"
4" INTERIOR SLAB ON GRADE
2" MIN.
2" M
IN
#4 @ 9" O.C.
1'-
1'-2"
(4) #4 CONT. TOP AND BOTTOM
COMPACTED EXISTING SOILS
TOP OF FOOTING
4" A.F.G.
(2) #4 CONT.
12" EXPANSION MATERIAL
SCALE:
FOUNDATION DETAIL
1-1/2" = 1'-0"
S101
SCALE:
FOUNDATION DETAIL
1-1/2" = 1'-0"
S101
4" SLAB ON GRADE
GREENHOUSE STRUCTURE
GREENHOUSE STRUCTURE
2'- 2"
4"
4" COMPACTED
CRUSHED STONE
2" MIN.
2" M
IN
#4 @ 9" O.C.
1'-
1'-2"
(4) #4 CONT. TOP AND BOTTOM
1" CHAMFER
COMPACTED EXISTING SOILS
TOP OF FOOTING
4" A.F.G.
(2) #4 CONT.
GREENHOUSE STRUCTURE
4"
5"5"
GREENHOUSE STRUCTURE
1'-6"
BASE BID ONLY BASE BID AND BID OPTION #2
2'- 2"
4"
4" COMPACTED
CRUSHED STONE
2" MIN.
2" M
IN
#4 @ 9" O.C.
1'-
1'-2"
1" CHAMFER
COMPACTED EXISTING SOILS
TOP OF FOOTING
4" A.F.G.
(2) #4 CONT.
GREENHOUSE STRUCTURE
5"
1'-6"
SCALE:
FOUNDATION DETAIL
1-1/2" = 1'-0"
S101
1" CHAMFER
1'-6"
2'- 2"
4"
4" INTERIOR SLAB ON GRADE
2" MIN.
2" M
IN
#4 @ 9" O.C.
1'-
1'-2"
(4) #4 CONT. TOP AND BOTTOM
COMPACTED EXISTING SOILS
(2) #4 CONT.
12" EXPANSION MATERIAL
GREENHOUSE STRUCTURE
TOP OF FOOTING
4" A.F.G.
TOP OF SLAB
AT GRADE
5'-3"
6" x 6" x 4.0 W.W.M. CONT. 4" SLAB ON GRADE
TOP OF SLAB
4" A.F.G.
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
c
USDA AGRICULTURAL RESEARCH SERVICE
BLUEBERRY AND CRANBERRY RESEARCH CENTER
ADDITION TO CRANBERRY BREEDING AND GENETICS GREENHOUSE
CHATSWORTH, NEW JERSEY
FOUNDATION DETAILS
S101 4 1803/08/24
REH
REH
FEJ
10300 BALTIMORE AVE.
BELTSVILLE, MD 20705
XXX
6223-A
XXX
XXX
XXX
XXX
SCALE: 1 1/2"=1'-0"
0 6" 1' 2'
30" 30"
30"
30" jferguson Stamp
Wayne.Shekailo Line
Wayne.Shekailo Line
Wayne.Shekailo Line
Wayne.Shekailo Line
Wayne.Shekailo Line
Wayne.Shekailo Line
Wayne.Shekailo Line
Wayne.Shekailo Line
Wayne.Shekailo Line
Wayne.Shekailo Line
Wayne.Shekailo Line
Wayne.Shekailo Line
'-4
1/ 2"
6'
EXHAUST FAN
SEE MECHANICAL
EXHAUST FAN
SEE MECHANICAL
3'- 6"
CIRCULATOR FAN
HEAT DUCTS SEE MECHANICAL
HEAT DUCTS SEE MECHANICAL
LOUVER ABOVE PADS.
SEE MECHANICAL
VENT SYSTEM
BID OPTION #1
VENT CONTROL. PROVIDE
ANCHORING / FOOTING PER
MANUFACTURERS
RECOMMENDATIONS.A200
A200
DOOR BY GREENHOUSE
MANUFACTURER
A300
4" CONCRETE PAD SLOPED
FROM FINISH WALKWAY
ELEVATION TO FINISHED
GRADE
5'-3"
6' 4" REINFORCED CONCRETE WALKWAY
CIRCULATOR FAN
CIRCULATOR FAN CIRCULATOR FAN
3'- 6"
DOOR BY GREENHOUSE
MANUFACTURER
BID OPTION #1:
EVAPORATIVE COOLING PAD SYSTEM
HEATER SEE MECHANICAL
HEATER SEE MECHANICAL ALUMINUM FRAMING SYSTEM
6 MIL. ANTI-CONDENSATE, UV RESISTANT PLASTIC SHEETING AS SPECIFIED.
4'
6'-10"
5'-3"
6'
4" CONCRETE PAD SLOPED
FROM FINISH WALKWAY
ELEVATION TO FINISHED
GRADE
' B
AS
E
BI
D
'-4
1/ 2"
6'
EXHAUST FAN
SEE MECHANICAL
EXHAUST FAN
SEE MECHANICAL
3'- 6"
CIRCULATOR FAN
HEAT DUCTS SEE MECHANICAL
HEAT DUCTS SEE MECHANICAL
LOUVER ABOVE PADS.
SEE MECHANICAL
VENT SYSTEM
BID OPTION #3
VENT CONTROL. PROVIDE
ANCHORING / FOOTING PER
MANUFACTURERS
RECOMMENDATIONS.
DOOR BY GREENHOUSE
MANUFACTURER
4" CONCRETE PAD SLOPED
FROM FINISH WALKWAY
ELEVATION TO FINISHED
GRADE
5'-3"
6' 4" REINFORCED CONCRETE WALKWAY
CIRCULATOR FAN
CIRCULATOR FAN CIRCULATOR FAN
3'- 6"
DOOR BY GREENHOUSE
MANUFACTURER
BID OPTION #1:
EVAPORATIVE COOLING PAD SYSTEM
HEATER SEE MECHANICAL ALUMINUM FRAMING SYSTEM
6 MIL. ANTI-CONDENSATE, UV RESISTANT PLASTIC SHEETING AS SPECIFIED.
4'
6'-10"
5'-3"
6'
4" CONCRETE PAD SLOPED
FROM FINISH WALKWAY
ELEVATION TO FINISHED
GRADE
' B
ID
O
PT
IO
N #2
100'
100'
A200
A200
1 SIM.
GREENHOUSE #1
BASE BID
GREENHOUSE #2
BID OPTION #2
HEATER SEE MECHANICAL
POLYCARBONATE
END PANELS (TYP.)
SEE ELEVATIONS
POLYCARBONATE
END PANELS (TYP.)
SEE ELEVATIONS
F
INFLATION FAN SEE DETAIL 4/A200
AND ELECTRICAL DRAWINGS.
F
INFLATION FAN SEE DETAIL 4/A200
AND ELECTRICAL DRAWINGS.
BASE BID
BID OPTION #2
SCALE:
FLOOR PLAN
1/4" = 1'-0"
A100
8'0 2' 4' 12'
SCALE: 1/4"= 1'-0"
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
c
USDA AGRICULTURAL RESEARCH SERVICE
BLUEBERRY AND CRANBERRY RESEARCH CENTER
ADDITION TO CRANBERRY BREEDING AND GENETICS GREENHOUSE
CHATSWORTH, NEW JERSEY
FLOOR PLAN
A100 5 1803/08/24
REH
REH
FEJ
10300 BALTIMORE AVE.
BELTSVILLE, MD 20705
XXX
6223-A
XXX
XXX
XXX
XXX
TRUE
NORTH
N.I.C.
WINDJAMMER 6000 WILL HAVE RIGID POLYCARBONATE WALLS
jferguson Stamp
Wayne.Shekailo Line
Wayne.Shekailo Line
Wayne.Shekailo Rectangle
SCALE:
SOUTH ELEVATION (TRUE NORTH)
1/4" = 1'-0"
A200
SCALE:
NORTH ELEVATION (TRUE NORTH)
1/4" = 1'-0"
A200
3' - 6" X 7' - 0" DOOR
EXHAUST FAN
SEE MECHANICAL
EXHAUST FAN
SEE MECHANICAL
VENT SYSTEM BY
GREENHOUSE
MANUFACTURER
BID OPTION #1
SCALE:
EAST ELEVATION (TRUE NORTH)
WEST ELEVATION (TRUE NORTH) MIRROR
1/4" = 1'-0"
A200
FINISHED GRADE
FOUNDATION. SEE S100
FOUNDATION. SEE S100
SHADE CLOTH AS SPECIFIED PROVIDE MANUFACTURERS
STANDARD ANCHORING SYSTEM
VENT CONTROL. PROVIDE
ANCHORING / FOOTING PER
MANUFACTURERS
RECOMMENDATIONS. SEE
BID OPTION #1 AND #3.
FURNACE VENT
EXHAUST FAN
FOUNDATION. SEE S100
FINISHED GRADE
ALUMINUM FRAMING SYSTEM. 6 MIL. DOUBLE WALL INFLATED ANTI-CONDENSATE,
UV RESISTANT PLASTIC SHEETING AS SPECIFIED.
8 MM. DOUBLE WALL POLYCARBONATE PANELS
FURNACE VENT
FINISHED GRADE
FOUNDATION. SEE S100
8 MM. DOUBLE WALL POLYCARBONATE PANELS
FINISHED GRADE
3' - 6" X 7' - 0" DOOREXHAUST FAN
SEE MECHANICAL
FINISHED GRADE
FOUNDATION. SEE S100
8 MM. DOUBLE WALL
POLYCARBONATE PANELSFURNACE VENT
VENT SYSTEM BY
GREENHOUSE
MANUFACTURER
BID OPTION #3
GREENHOUSE #2
BID OPTION #2 GREENHOUSE #1
BASE BID
GREENHOUSE #1
BASE BID
GREENHOUSE #2
BID OPTION #2
8'0 2' 4' 12'
SCALE: 1/4"= 1'-0"
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
c
USDA AGRICULTURAL RESEARCH SERVICE
BLUEBERRY AND CRANBERRY RESEARCH CENTER
ADDITION TO CRANBERRY BREEDING AND GENETICS GREENHOUSE
CHATSWORTH, NEW JERSEY
ELEVATIONS
A200 6 1803/08/24
REH
REH
FEJ
10300 BALTIMORE AVE.
BELTSVILLE, MD 20705
XXX
6223-A
XXX
XXX
XXX
XXX
(2) AIR TRANSFER GASKETS
6 MIL. DOUBLE WALL
INFLATED ANTI-CONDENSATE,
UV RESISTANT PLASTIC
SHEETING AS SPECIFIED.
INFLATION MOUNT
STOP TAB
ROLL-FORM RAIL
GREENHOUSE END WALL 516" HEX NUT
AND WASHER
INFLATION FAN WITH AIR INLET DAMPER (ADJUSTABLE
FOR DESIRED ROOF / WALL TENSION)
SHALL INCLUDE:
(1) 60 CFM INFLATION BLOWER
(1) MOUNTING BRACKET
(1) PVC PLUG
(1) 4" HOSE CLAMP
(1) 3" x 5' FLEX TUBING
(2) AIR TRANSFER GASKETS
MOUNTING HARDWARE
NOTES:
1. INSTALL INFLATION MOUNT FIRMLY TO GREENHOUSE END WALL MEMBER.
2. PLACE (1) AIR TRANSFER GASKET ON THE 6 MIL. DOUBLE WALL ANTI-CONDENSATE, UV RESISTANT PLASTIC SHEETING TO BE INFLATED. CUT OUT THE SHEET
(ONE LAYER OF SHEETING ONLY) FROM THE GASKET TO ALLOW AIR TO PASS.
3. PLACE SECOND AIR TRANSFER GASKET ON THE INSIDE OF THE SHEETING. BE SURE TO ALIGN THE 2 GASKETS PRIOR TO PRESSING THE TWO TOGETHER. ST
THE TWO GASKETS TOGETHER USING AN ORDINARY OFFICE STAPLER.
4. INSERT THE 3"x5' FLEX TUBING THROUGH THE AIR TRANSFER GASKETS. ENSURE APPROXIMATELY 1" OF THE FLEX TUBING PASSES THROUGH THE GASKETS
ENSURE A TIGHT SEAL.MAKE SURE NO SHARP EDGES ARE EXPOSED TO PUNCTURE OUTER LAYER OF SHEETING.
SCALE:
SHEETING INFLATION KIT DETAIL
N.T.S.
A200
N.I.C.
N.I.C.
ELEVATION MAY CHANGE WITH WINDJAMMER 6000 MODEL
ELEVATION MAY CHANGE WITH WINDJAMMER 6000
MODEL
WINDJAMMER 6000 WILL HAVE RIGID POLYCARBONATE WALLS
N.I.C.
jferguson Stamp
Wayne.Shekailo Rectangle
Wayne.Shekailo Line
Wayne.Shekailo Line
Wayne.Shekailo Rectangle
Wayne.Shekailo Line
Wayne.Shekailo Rectangle
Wayne.Shekailo Line
Wayne.Shekailo Rectangle
GREENHOUSE STRUCTURE
BASIS OF DESIGN:
WINDJAMMER 5000 PROSPIANT
6'
4" THICK CONCRETE WALK WAY
SEE STRUCTURAL
4" COMPACTED
CRUSHED STONE
A300
FINISH GRADE
0'-0"
T. O. FOOTING
1'-0" A.F.G.
COMPACTED EXISTING SOILS
GREENHOUSE STRUCTURE
BASIS OF DESIGN:
WINDJAMMER 5000 PROSPIANT
6'4" THICK CONCRETE WALK WAY
SEE STRUCTURAL
PERIMETER FOOTING SEE STRUCTURAL
4" COMPACTED
CRUSHED STONE
COMPACTED EXISTING SOILS
GREENHOUSE #1
BASE BID GREENHOUSE #2
BID OPTION #2
GUTTER
14 GA.
GALVANIZED
GUTTER
GREENHOUSE
FRAMING
6 MIL. DOUBLE WALL
ANTI-CONDENSATE, UV RESISTANT
PLASTIC SHEETING AS SPECIFIED.
7'- 0"
TO
C
EN
TE
R
OF
B
EN
D
NEOPRENE GASKET
SELF DRILLING SCREW
WITH GASKET
WASHERS
A300
1'
GREENHOUSE STRUCTURE RECEPTOR
(2) 5 8" X 5" BOLTS PER COLUMN
(2) 5 8"x5" STAINLESS STEEL EXPANSION
ANCHORS PER RECEPTOR
PERIMETER FOOTING SEE STRUCTURAL
GREENHOUSE STRUCTURE BASIS
OF DESIGN: WINDJAMMER 5000
PROSPIANT
9"COMPACTED EXISTING SOILS
EXISTING SOILS
4" CRUSHED STONE
1'
GREENHOUSE STRUCTURE RECEPTOR
(2) 5 8" X 5" BOLTS PER COLUMN
(2) 5 8"x5" STAINLESS STEEL EXPANSION
ANCHORS PER RECEPTOR
PERIMETER FOOTING
SEE STRUCTURAL
GREENHOUSE STRUCTURE BASIS
OF DESIGN: WINDJAMMER 5000
PROSPIANT
COMPACTED
EXISTING
SOILS
#30 FELT UNDER BASE PLATE
SECTION ELEVATION
10 1/2"
#30 FELT UNDER BASE PLATE
1'
GREENHOUSE STRUCTURE RECEPTOR
(2) 5 8" X 5" BOLTS PER COLUMN
(2) 5 8"x5" STAINLESS STEEL EXPANSION
ANCHORS PER RECEPTOR
PERIMETER FOOTING SEE STRUCTURAL
GREENHOUSE STRUCTURE BASIS
OF DESIGN: WINDJAMMER 5000
PROSPIANT
9"COMPACTED EXISTING SOILS
4" CRUSHED STONE
#30 FELT UNDER BASE PLATE
BASE BID BASE BID AND BID OPTION #2
1'
GREENHOUSE STRUCTURE RECEPTOR
(2) 5 8" X 5" BOLTS PER COLUMN
(2) 5 8"x5" STAINLESS STEEL EXPANSION
ANCHORS PER RECEPTOR
PERIMETER FOOTING SEE STRUCTURAL
GREENHOUSE STRUCTURE BASIS
OF DESIGN: WINDJAMMER 5000
PROSPIANT
9"COMPACTED EXISTING SOILS
4" CRUSHED STONE
#30 FELT UNDER BASE PLATE
SCALE:
GREENHOUSE SECTION
1/2" = 1'-0"
A300
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
c
USDA AGRICULTURAL RESEARCH SERVICE
BLUEBERRY AND CRANBERRY RESEARCH CENTER
ADDITION TO CRANBERRY BREEDING AND GENETICS GREENHOUSE
CHATSWORTH, NEW JERSEY
GREENHOUSE SECTION
A300 7 1803/08/24
REH
REH
FEJ
10300 BALTIMORE AVE.
BELTSVILLE, MD 20705
XXX
6223-A
XXX
XXX
XXX
XXX
4'
SCALE: 1/2"=1'-0"
0 1' 2' 8'
SCALE:
RECEPTOR DETAIL
1-1/2" = 1'-0"
A300 SCALE:
RECEPTOR DETAIL
1-1/2" = 1'-0"
A300
SCALE: 1 1/2"=1'-0"
0 6" 1' 2'
N.I.C.
N.I.C.
SECTION MAY CHANGE WITH WINDJAMMER 6000 MODEL
jferguson Stamp
Wayne.Shekailo Rectangle
Wayne.Shekailo Line
Wayne.Shekailo Rectangle
Wayne.Shekailo Line
Wayne.Shekailo Rectangle
Wayne.Shekailo Line
Wayne.Shekailo Line
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
c
USDA AGRICULTURAL RESEARCH SERVICE
BLUEBERRY AND CRANBERRY RESEARCH CENTER
ADDITION TO CRANBERRY BREEDING AND GENETICS GREENHOUSE
CHATSWORTH, NEW JERSEY
MECHANICAL
NOTES AND ABBREVIATIONS
M001 8 1803/08/24
REH
DTC
FEJ
10300 BALTIMORE AVE.
BELTSVILLE, MD 20705
XXX
6223-A
XXX
XXX
XXX
XXX
1. INSTALLATION OF HVAC WORK SHALL BE COORDINATED WITH OTHER TRADES BEFORE ANY INSTALLATION IS DONE. DUCTWORK SHOWN
ON PLANS IS SCHEMATIC.
2. COORDINATE MECHANICAL AND ELECTRICAL SUCH THAT MECHANICAL PIPING, DUCTWORK AND EQUIPMENT IS NOT LOCATED OVER OR
ABOVE ANY ELECTRICAL.
3. AT START OF CONSTRUCTION, PREPARE TYPED LISTS OF EQUIPMENT THAT ARE SUPPLIED REQUIRING ELECTRICAL WORK AND SEND LISTS
TO THE ELECTRICAL CONTRACTOR FOR REVIEW AND COORDINATION.
4. EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S APPROVED CLEARANCE, AND INTERNATIONAL BUILDING CODE
/ INTERNATIONAL MECHANICAL CODE.
5. INSTALLATION OF EQUIPMENT SHALL PERMIT ACCESSIBILITY FOR SERVICE AND/OR REPLACEMENT WITHOUT NECESSITATING REMOVAL
OR MODIFICATION TO OTHER PIPING, WIRING, OR EQUIPMENT.
6. COORDINATE WALL, FLOOR AND ROOF PENETRATIONS WITH THE GENERAL CONTRACTOR.
7. SUPPLEMENTAL STEEL MEMBERS REQUIRED TO SUPPORT HVAC EQUIPMENT FROM MAIN STRUCTURE SHALL BE PROVIDED BY THE HVAC
CONTRACTOR UNLESS SPECIFICALLY NOTED OTHERWISE.
8. EXACT LOCATIONS OF THERMOSTATS, CO2 SENSORS, AND SENSORS SHALL BE COORDINATED WITH FINAL LOCATIONS OF WALL-MOUNTED ARCHITECTURAL AND ELECTRICAL EQUIPMENT. MOUNT THERMOSTATS AND CO2 SENSORS MINIMUM 48" AFF.
9. PROVIDE HOUSEKEEPING PADS FOR MECHANICAL EQUIPMENT.
10. INSTALL EXPOSED CONTROL WIRING IN CONDUIT. SEE DIVISION ELECTRICAL FOR REQUIREMENTS.
11. MANUFACTURER NAME AND MODEL NUMBERS ARE BASIS OF DESIGN AND ARE SHOWN FOR INFORMATION ONLY. REFER TO
SPECIFICATIONS FOR COMPLETE REQUIREMENTS.
12. PIPING INSULATION SHALL BE PROVIDED ON ALL PIPING SYSTEMS.
13. FURNACE VENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER INSTALLATION INSTRUCTIONS.
14. SPECIFICATIONS TAKE PRECEDENCE OVER DRAWINGS. HOWEVER, ITEMS SHOWN ON DRAWING BUT NOT IN THE SPECIFICATIONS ARE REQUIRED WITHIN THE PROJECT SCOPE. IN ADDITION, SPECIFIC ITEMS SHOWN ON THE DRAWINGS TAKE PRECEDENCE OVER
SPECIFICATIONS IN CASES WHERE THE SPECIFICATION HAS OPTIONS.
15. ALL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S APPROVED PUBLISHED LITERATURE.
16. ALL EQUIPMENT INSTALLED IN THIS PROJECT SHALL COMPLY WITH THE "BUY AMERICAN ACT". BASIS OF DESIGN SHOWN ON SCHEDULES IS TO ESTABLISH A STANDARD OF QUALITY, NOT TO LIMIT COMPETITION. EQUIVALENT EQUIPMENT FROM
ANOTHER MANUFACTURER IS ACCEPTABLE.
GENERAL PROJECT NOTES:ABBREVIATIONS:
@ AT
& ND
AHU AIR HANDLING UNIT
ARCH ARCHITECT, ARCHITECTURAL
AS AIR SEPARATOR
ASHRAE AMERICAN SOCIETY OF HEATING, REFRIGERATING,
AND AIR CONDITIONING ENGINEERS
ASTM AMERICAN SOCIETY FOR TESTING AND
MATERIALS
BDD BACKDRAFT DAMPER
BLDG BUILDING
BTU, BTUH BRITISH THERMAL UNITS, BTUs PER HOUR
CD CONDENSATE DRAIN
CFM CUBIC FEET PER MINUTE
CHWR CHILLED WATER RETURN
CHWS CHILLED WATER SUPPLY
CLG COOLING
CMU CONCRETE MASONRY UNIT
CO CLEANOUT
CO2 CARBON DIOXIDE
CONC CONCRETE
CONN CONNECT, CONNECTING, CONNECTION
CONT CONTINUED
COP COEFFICIENT OF PERFORMANCE
COR CONTRACTING OFFICER'S (OWNER'S)
REPRESENTATIVE
CT COOLING TOWER
CU CONDENSING UNIT
CWR CONDENSER WATER RETURN
CWS CONDENSER WATER SUPPLY
D DEPTH
DB, Tdb DRY BULB (TEMPERATURE) dBA DECIBELS
DCW DOMESTIC COLD WATER
DDC DIRECT DIGITAL CONTROLS
DEG. F (°F) DEGREES FAHRENHEIT
DF DESTRATIFICATION FAN
DFCU DUCTLESS FAN COIL UNIT
DH DEHUMIDIFIER
DIA, Ø DIAMETER
DIV DIVISION
DN DOWN
DP, PD DIFFERENTIAL PRESSURE, PRESSURE DROP
DSCU DUCTLESS SPLIT CONDENSING UNIT
DSHP DUCTLESS SPLIT HEAT PUMP
DWG DRAWING
DX DIRECT EXPANSION
EA EXHAUST AIR
EAG EXHAUST AIR GRILLE
EAT ENTERING AIR TEMPERATURE
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN
EFF EFFICIENCY
ELEC ELECTRICAL
EMCS ENERGY MONITORING AND CONTROLS SYSTEM
ERU ENERGY RECOVERY UNIT
ERV ENERGY RECOVERY VENTILATOR
ET EXPANSION TANK
ESP EXTERNAL STATIC PRESSURE
EUH ELECTRIC UNIT HEATER
EWT ENTERING WATER TEMPERATURE
EXT EXTERIOR
EXH EXHAUST
EXST, (E) EXISTING
FCU FAN COIL UNIT
FD FIRE DAMPER
FFE FINISHED FLOOR ELEVATION
FLA FULL LOAD AMPS
FOB FLAT ON BOTTOM
FOT FLAT ON TOP
FPM FEET PER MINUTE
FSD FIRE SMOKE DAMPER
FT FOOT, FEET
FT WG FEET WATER GAUGE
FV FLUE VENT
GA GAGE
GC GENERAL CONTRACTOR
GPM GALLONS PER MINUTE
GWH GAS WATER HEATER
H HEIGHT
HR HOUR
HTG HEATING
HTR HEATER
HTW HEATING WATER
HVAC HEATING, VENTILATING, AND AIR CONDITIONING
HWR HEATING WATER RETURN
HWS HEATING WATER SUPPLY
HX HEAT EXCHANGER
HZ HERTZ
IMC INTERNATIONAL MECHANICAL CODE
IN INCH, INCHES
IN WC INCHES WATER COLUMN
IN WG INCHES WATER GAUGE
IPLV INTEGRATED PART LOAD VALUE
KW KILOWATTS
L LENGTH, LOUVER (WALL)
LAT LEAVING AIR TEMPERATURE
LBD LINEAR BAR DIFFUSER
LBS POUNDS
LWT LEAVING WATER TEMPERATURE
MAX MAXIMUM
MBH 1000 BRITISH THERMAL UNITS
MCA MINIMUM CIRCUIT AMPACITY
MERV MINIMUM EFFICIENCY REPORTING VALUE
MECH MECHANICAL
MFCR, MFCG MANUFACTURER, MANUFACTURING
MIN MINIMUM
MOCP, MOP MAXIMUM OVER CURRENT PROTECTION
MTWR MEDIUM TEMPERATURE WATER RETURN
MTWS MEDIUM TEMPERATURE WATER SUPPLY
NG NATURAL GAS
NC NOISE CRITERIA
N.C. NORMALLY CLOSED
NO. NUMBER
N.O. NORMALLY OPEN
NTS NOT TO SCALE
OA OUTSIDE AIR
OD OUTSIDE DAMPER
PD PRESSURE DROP
PH PHASE
PLBG PLUMBING
PPM PARTS PER MILLION
PRV PRESSURE RELIEF VALVE
PSI POUNDS PER SQUARE INCH
PCHWR PLANT CHILLED WATER RETURN
PCHWS PLANT CHILLED WATER SUPPLY
PMTWR PLANT MEDIUM TEMPERATURE WATER RETURN
PMTWS PLANT MEDIUM TEMPERATURE WATER SUPPLY
QTY QUANTITY
RA RETURN AIR
RAG RETURN AIR GRILLE
RH RELATIVE HUMIDITY, ROOF HOOD
RM ROOM
RPM REVOLUTIONS PER MINUTE
SA SUPPLY AIR
SAD SUPPLY AIR DIFFUSER
SAG SUPPLY AIR GRILLE
SD SMOKE DAMPER, SMOKE DETECTOR
SEER SEASONAL ENERGY EFFICIENCY RATIO
SF SUPPLY FAN
SMACNA SHEET METAL AND AIR CONDITIONING
CONTRACTOR'S NATIONAL ASSOCIATION
SP STATIC PRESSURE
SS STAINLESS STEEL
TSTAT THERMOSTAT
TEMP TEMPERATURE
TYP TYPICAL
UH UNIT HEATER
UL UNDERWRITER'S LABORATORY
UMCS UTILITY MONITORING AND CONTROL SYSTEM
V VOLTAGE, VOLTS
VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER
VFD VARIABLE FREQUENCY DRIVE
VRF VARIABLE REFRIGERANT FLOW
WB, Twb WET BULB (TEMPERATURE)
SUMP PUMP
P
SYMBOLS
SUMP PUMP
EF-1
EF-1
POLY-TUBING DUCT
INSTALLED AT GRADE
POLY-TUBING DUCT
INSTALLED AT GRADE
VENT SYSTEM
VENT CONTROLCF-1
CF-1
M200
M200
BID OPTION #1:
ECP-1
F-1
F-1
CF-1 CONTROLLER
F-1 VENT
(TYP. 2)
F-1 VENT
(TYP. 2)
1" PVC BELOW
GRADE
2,000 GALLON PROPANE TANK. (NOT IN CONTRACT. SHALL BE
PROVIDED AND INSTALLED BY GOVERNMENT)
1" SCHEDULE 40 BLACK CARBON STEEL PIPE. (NOT IN CONTRACT.
SHALL BE PROVIDED AND INSTALLED BY GOVERNMENT)
1" SCHEDULE 40 BLACK CARBON STEEL PIPE. (NOT IN
CONTRACT. SHALL BE PROVIDED AND INSTALLED BY
GOVERNMENT)
1" DCW BELOW GRADE
SEE C100 FOR
CONTINUATION
CF-1 3
CF-13
KEYED NOTES:
1. PROVIDE PROPANE FIRED FURNACE. PROVIDE HOUSEKEEPING PAD
BENEATH FURNACE. SEE DETAIL 2/M600.
2. PROVIDE VENT FOR PROPANE FIRED FURNACE AND INSTALL IN
ACCORDANCE WITH FURNACE AND GREENHOUSE MANUFACTURER'S
INSTALLATION INSTRUCTIONS.
3. PROVIDE SUSPENDED CIRCULATOR FANS. FANS SHALL ALL BE
CONTROLLED BY A SINGLE CONTROLLER.
4. PROVIDE NEW WALL MOUNTED EXHAUST FAN. FAN SHALL BE
INTERLOCKED WITH GREENHOUSE MFG PROVIDED VENT.
5. PROVIDE FREEZE PROOF FAUCET IN ACCORDANCE WITH
SPECIFICATIONS.
6. EF-1 SHALL BE INTERLOCKED WITH VENT SYSTEM SO THAT EF-1 IS NOT
ENABLED UNTIL VENT IS IN THE FULLY OPEN POSITION.
7. SIZE POLY-DUCT TO MATCH HEATER OUTLET OPENING DIAMETER.
1" DCW UP FOR ECP-1
MAKEUP WATER
GREENHOUSE CONTROLLER
1" PVC BELOW
GRADE
1" PVC BELOW
GRADE (TYP. 4)
P
PECP-1 SUMP PUMP
(TYP.2)
EF-1
EF-1
POLY-TUBING DUCT
INSTALLED AT GRADE
POLY-TUBING DUCT
INSTALLED AT GRADE
VENT SYSTEM
VENT CONTROL
CF-1
CF-1
BID OPTION #1:
ECP-1
F-1
F-1
CF-1 CONTROLLER
F-1 VENT
(TYP. 2)
F-1 VENT
(TYP. 2)
1" PVC BELOW
GRADE5
1" SCHEDULE 40 BLACK CARBON STEEL PIPE. (NOT IN CONTRACT
SHALL BE PROVIDED AND INSTALLED BY GOVERNMENT)
1" DCW BELOW GRADE
SEE C100 FOR
CONTINUATION
CF-1 3
CF-13
1" DCW UP FOR ECP-1
MAKEUP WATER
GREENHOUSE CONTROLLER
1" PVC BELOW
GRADE
1" PVC BELOW
GRADE (TYP. 4)
P
P
ECP-1 SUMP PUMP
(TYP.2)
M200
M200
1 SIM.
1-1/2" SCHEDULE 40 BLACK CARBON STEEL PIPE. (NOT IN CONTRACT
SHALL BE PROVIDED AND INSTALLED BY GOVERNMENT)
1-1/2" SCHEDULE 40 BLACK CARBON STEEL PIPE. (NOT IN CONTRACT.
SHALL BE PROVIDED AND INSTALLED BY GOVERNMENT)
COORDINATE BOLLARD LOCATIONS WITH GOVERNMENT (SEE C100)
GREENHOUSE #1
BASE BID
GREENHOUSE #2
BID OPTION #2
BASE BID
BID OPTION #2
BID OPTION #3
COOLING PAD SYSTEM
FOR GREENHOUSE #2
BID OPTION #1
COOLING PAD SYSTEM
FOR GREENHOUSE #1
SCALE:
FLOOR PLAN
3/16" = 1'-0"
M100
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
c
USDA AGRICULTURAL RESEARCH SERVICE
BLUEBERRY AND CRANBERRY RESEARCH CENTER
ADDITION TO CRANBERRY BREEDING AND GENETICS GREENHOUSE
CHATSWORTH, NEW JERSEY
MECHANICAL FLOOR PLAN
M100 9 1803/08/24
REH
DTC
FEJ
10300 BALTIMORE AVE.
BELTSVILLE, MD 20705
XXX
6223-A
XXX
XXX
XXX
XXX
0 4' 8' 16'
SCALE: 3/16"= 1'-0"
2'
PLAN
NORTH
TRUE
NORTH
N.I.C.
PROPANE LOCATION REMAINS UNCHANGED
jferguson Stamp
Wayne.Shekailo Rectangle
Wayne.Shekailo Line
Rectangle
KEYED NOTES:
1. PROVIDE VENT FOR PROPANE FIRED FURNACE AND INSTALL IN
ACCORDANCE WITH FURNACE AND GREENHOUSE MANUFACTURER'S
INSTALLATION INSTRUCTIONS.
2. PROVIDE NEW WALL MOUNTED EXHAUST FAN. FAN SHALL BE
INTERLOCKED WITH GREENHOUSE MFG PROVIDED VENT.
3. EF-1 SHALL BE INTERLOCKED WITH VENT SYSTEM SO THAT EF-1 IS NOT
ENABLED UNTIL VENT IS IN THE FULLY OPEN POSITION.
FINISHED GRADE
ECP-1
EF-1
EF-1
FINISHED GRADE
F-1 VENT1 F-1 VENT1
EF-12
F-1 VENT1
F-1 VENT1
EF-1 2
F-1 VENT
(TYP.2)
EF-1
FINISHED GRADE
ECP-1
GREENHOUSE #2
BID OPTION #2 GREENHOUSE #1
BASE BID
GREENHOUSE #1
BASE BID
GREENHOUSE #2
BID OPTION #2VENT SYSTEM BY
GREENHOUSE
MANUFACTURER
BID OPTION #1
VENT SYSTEM BY
GREENHOUSE
MANUFACTURER
BID OPTION #3
VENT CONTROL. PROVIDE
ANCHORING / FOOTING PER
MANUFACTURERS
RECOMMENDATIONS. SEE
BID OPTION #1 AND #3.
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
c
USDA AGRICULTURAL RESEARCH SERVICE
BLUEBERRY AND CRANBERRY RESEARCH CENTER
ADDITION TO CRANBERRY BREEDING AND GENETICS GREENHOUSE
CHATSWORTH, NEW JERSEY
MECHANICAL ELEVATIONS
M200 10 1803/08/24
REH
DTC
FEJ
10300 BALTIMORE AVE.
BELTSVILLE, MD 20705
XXX
6223-A
XXX
XXX
XXX
XXX
SCALE:
SOUTH ELEVATION
1/4" = 1'-0"
M100
SCALE:
NORTH ELEVATION
1/4" = 1'-0"
M100
SCALE:
EAST ELEVATION
WEST ELEVATION MIRROR
1/4" = 1'-0"
M100
8'0 2' 4' 12'
SCALE: 1/4"= 1'-0"
N.I.C.
N.I.C.
WINDJAMMER 6000
ELEVATION MAY BE
DIFFERENT
WINDJAMMER 6000 ELEVATION
MAY BE DIFFERENT
jferguson Stamp
Wayne.Shekailo Rectangle
Wayne.Shekailo Line
Wayne.Shekailo Line
Wayne.Shekailo Rectangle
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
c
USDA AGRICULTURAL RESEARCH SERVICE
BLUEBERRY AND CRANBERRY RESEARCH CENTER
ADDITION TO CRANBERRY BREEDING AND GENETICS GREENHOUSE
CHATSWORTH, NEW JERSEY
MECHANICAL
SCHEDULE AND DETAILS
M600 11 1803/08/24
REH
DTC
FEJ
10300 BALTIMORE AVE.
BELTSVILLE, MD 20705
XXX
6223-A
XXX
XXX
XXX
XXX
EVAPORATIVE COOLING PAD(BID OPTION #1 AND #3)
HEIGHT
(FT)
LENGTH
(FT)
BASIS OF DESIGNMODEL MEDIA
THICKNESS REMARKS
ECH600
NOTES:
1. PROVIDE MAKE-UP WATER AS RECOMMENDED BY MANUFACTURER TO EACH COOLING WALL.
2. PROVIDE WITH SUBMERSIBLE PUMP BY COOLING CELL MANUFACTURER, SIZED FOR COOLING CELL PRESSURE LOOP. PROVIDE A PUMP
FOR EACH COOLING WALL. SELECTED PUMPS SHALL NOT EXCEED 1 HP. COOLING CELL SHALL HAVE CELLULOSE-TYPE PADS. GPM & AIRFLOW VALUES SHOWN ARE APPROXIMATE. ACTUAL VALUES SHALL BE BASED ON MANUFACTURER'S RECOMMENDATIONS FOR SIZE
AND THICKNESS OF PADS.
3. PROVIDE COOLING WALLS WITH BOTTOM TROUGH TO DRAIN BACK TO SUMP TANK.
4. PROVIDE 2-WAY CONTROL VALVE FOR EACH COOLING WALL TO INTERFACE WITH GREENHOUSE CONTROL SYSTEM.
5. EVAPORATIVE COOLING PADS SHALL OPERATE BASED ON GREENHOUSE CONTROLLER SET POINT.
J & D MANUFACTURING 20 6 6"
AIRFLOW
(CFM)
E.S.P.
(IN W.G.)
NOTES:
1. PROVIDE WITH ALUMINUM CONSTRUCTION AND SLANT WALL HOUSING.
2. FAN SHALL BE RATED FOR GREENHOUSE APPLICATIONS.
3. PROVIDE WITH ALUMINUM BACKDRAFT SHUTTER AND INSECT SCREEN.
4. FANS SHALL BE TWO SPEED.
5. FANS SHALL OPERATE BASED ON GREENHOUSE CONTROLLER SET POINT.
EF-1 ACME OR EQUAL DCA24H-B SLANT WALL HOUSING 6336 949 0.15" 6.3 3/4 115/208/230 60 SEE NOTES
GREENHOUSE FAN SCHEDULE
MANUFACTURER MODEL TYPE
AIRFLOW
(CFM)
FAN
SIZE
NOTES:
1. FAN SHALL BE RATED FOR GREENHOUSE APPLICATIONS.
2. PROVIDE FAN WITH VARIABLE SPEED CONTROLLER INDEPENDENT OF GREENHOUSE CONTROLLER.
CF-1 ACME OR EQUAL HAF20A4 HORIZONTAL AIR FLOW 3,005 1626 20" 60 1/15 115/1 105.0 SEE NOTES
CIRCULATOR FAN SCHEDULE
MANUFACTURER MODEL TYPE
NOTES:
1. FURNACES SHALL OPERATE BASED ON GREENHOUSE CONTROLLER SET POINT.
2. PROVIDE WITH A CARBON MONOXIDE SENSOR AND CARBON MONOXIDE EXTRACTION FAN. FAN SHALL OPERATE UPON SIGNAL FROM CARBON MONOXIDE SENSOR. BASIS OF DESIGN
KIDDE CARBON MONOXIDE ALARM. SENSOR SHALL BE SET TO ACTIVATE HEATER WHEN CARBON MONOXIDE LEVELS REACH 50 PPM.
3. BASIS OF DESIGN IS SIEBRING MANUFACTURING ROYAL GAS HEATER RH240.
4. INSTALL FURNACE AND FLUE VENTING SYSTEM IN ACCORDANCE WITH MANUFACTURER'S INSTALLATION INSTRUCTIONS.
F-1 ROYAL HEAT RH240 HORIZONTAL BLOWER 240,000 11" 8" 640 32" SEE NOTES
FURNACE SCHEDULE
MANUFACTURER MODEL TYPE
48" 54"
VENT
PIPE
28003/4
MOTOR
HP
BLOWER
CFM
WEIGHT
(LBS)
LP-GAS
(W.C.)
MARK
ECP-1
MARK
MARK
MARK BTU DIMENSIONS
W L H
REMARKS
SEE NOTES
REMARKS
WATTS
MOTOR
VOLTSHP
HZRPM
RPM C/W
HP VOLTS HZ
MOTOR REMARKS
INSECT SCREEN
SCALE:
BID OPTION #1 AND #3
EVAPORATIVE COOLING PAD AND SUMP PUMP DETAIL
NTS
M600
SUMP TANK. PROVIDE WITH
COOLING PAD MANUFACTURER
PROVIDED WATER RE-CIRCULATION
SYSTEM
MEDIA
VENT SYSTEM
SEE ARCH.
COOLING PAD
COOLING: COOLING SHALL BE PROVIDED IN TWO STAGES. STAGE 1 - EXHAUST FANS SHALL ACTIVATE, VENT ACTUATORS SHALL OPEN THE VENTS TO CIRCULATE AIR AS REQUIRED TO MAINTAIN A TEMPERATURE SET POINT AS MEASURED BY THE SPACE TEMPERATURE AS DETERMINED BY THE GREENHOUSE MASTER CONTROLLER. STAGE 2 -EVAPORATIVE COOLING WALL PUMPS SHALL ENERGIZE.
EVAPORATIVE COOLING WALLS SHALL MAINTAIN A TEMPERATURE SET POINT AS MEASURED BY THE SPACE TEMPERATURE SENSORS AS
DETERMINED BY THE GREENHOUSE MASTER CONTROLLER.
HEATING: FURNACE SHALL ENERGIZE TO PROVIDE HEATING. HEATERS SHALL MAINTAIN A TEMPERATURE SET POINT AS MEASURED BY THE
SPACE TEMPERATURE SENSORS AS DETERMINED BY THE GREENHOUSE MASTER CONTROLLER.
CONTROL SYSTEM SHALL MONITOR INDOOR AIR TEMPERATURE BY SPACE TEMPERATURE SENSORS LOCATED IN EACH BAY. PROVIDE ALL WIRING AND CONTROLS FOR A COMPLETE OPERATIONAL SYSTEM. VERIFY SEQUENCE OF OPERATIONS WITH USDA PERSONNEL.
SEQUENCE OF OPERATION
GREENHOUSE
CONTROLLER INPUT/
OUTPUT SUMMARY
NOTES:
1. BASIS OF DESIGN: MICRO-GROW CONTROLS SYSTEM.
EVAPORATIVE COOLING WALL
AN
AL
OG
IN
PU
T
AN
AL
OG
O
UT
PU
T
BI
NA
RY
IN
PU
T
BI
NA
RY
O
UT
PU
T
EXHAUST FAN X
X
XTEMPERATURE SENSOR
FURNACE ENABLE X
VENT ACTUATOR X
VENT SYSTEM
SEE ARCH.
HOUSEKEEPING PADS MUST EXTEND A MINIMUM OF 6"
BEYOND ALL SIDES OF SUPPORTED EQUIPMENT UNLESS
OTHERWISE INDICATED. PADS MUST BE A MINIMUM OF 4"
THICK.
PROVIDE 3000 PSI CONCRETE HOUSEKEEPING
PADS FOR ALL GROUND AND/OR FLOOR
MOUNTED EQUIPMENT
EDGE OF SUPPORTED EQUIPMENT
CHAMFERED EDGED ALL
SIDES
FLOOR
ALL PADS INSTALLED ON CONCRETE FLOORS ARE TO BE PROVIDED WITH
#4 REBAR DOWEL RODS PENETRATING A MINIMUM OF 2" INTO BOTH THE
PAD AND THE SUPPORTING FLOOR. PROVIDE A MINIMUM OF FOUR (4)
DOWEL RODS PER PAD, WITH SPACING OF DOWEL RODS AT 18" ON
CENTER MAXIMUM BOTH WAYS.
#4 REINFORCEMENT MAX 4" ON CENTER EACH
WAY
SCALE:
HOUSEKEEPING PAD DETAIL
NTS
M600
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
c
USDA AGRICULTURAL RESEARCH SERVICE
BLUEBERRY AND CRANBERRY RESEARCH CENTER
ADDITION TO CRANBERRY BREEDING AND GENETICS GREENHOUSE
CHATSWORTH, NEW JERSEY
ELECTRICAL
NOTES AND ABBREVIATIONS
E001 12 1803/08/24
REH
BSN
FEJ
10300 BALTIMORE AVE.
BELTSVILLE, MD 20705
XXX
6223-A
XXX
XXX
XXX
XXX
1. THE DRAWINGS INDICATE THE GENERAL EXTENT OF WORK. THE DRAWINGS ARE NOT
INTENDED TO INDICATE OR DESCRIBE ALL WORK REQUIRED FOR THE FULL PERFORMANCE
AND COMPLETION OF THE REQUIREMENTS OF THE CONTRACT.
2. THE CONTRACTOR IS RESPONSIBLE FOR THE COORDINATION OF ALL PARTS OF THE WORK SO THAT NO WORK SHALL BE LEFT IN AN UNFINISHED OR INCOMPLETE CONDITION. INSTALLATION
OF ELECTRICAL WORK SHALL BE COORDINATED WITH OTHER TRADES BEFORE ANY
INSTALLATION IS DONE. CONDUIT AND DEVICES SHOWN ON PLANS ARE SCHEMATIC.
3. ALL WORK SHALL CONFORM TO APPLICABLE INDUSTRY AND MANUFACTURER'S PUBLISHED
STANDARDS FOR QUALITY OF MATERIALS AND WORKMANSHIP, AS WELL AS, ALL
REQUIREMENTS IN THESE DRAWINGS AND SPECIFICATIONS. ANY CONFLICTING
REQUIREMENTS OF THE SOURCES LISTED ABOVE SHALL BE BROUGHT TO THE CONTACTING
OFFICER'S ATTENTION PRIOR TO PROCEEDING WITH THE WORK.
4. THE CONTRACTOR SHALL PROTECT ANY EXISTING, IN-PLACE, AND NEW WORK.
5. ONCE ON SITE, THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND SHALL VERIFY ALL
NEW AND EXISTING CONDITIONS SHOWN ON THESE DRAWINGS. THE CONTRACTOR SHALL
NOTIFY THE CONTRACTOR IN WRITING OF ANY DIFFERING CONDITIONS BEFORE
COMMENCEMENT OF WORK.
6. THE CONTRACTOR SHALL PLAN HIS/HER WORK TO PROVIDE ADEQUATE PROTECTION FOR
PERSONS AND PROPERTY AT ALL TIMES, AND EXECUTE THE WORK IN SUCH A MANNER TO
AVOID ANY HAZARD TO PERSONS AND PROPERTY AS NECESSARY.
7. MINIMUM RACEWAY SIZE SHALL BE 3/4-IN. INCREASE RACEWAY SIZE AS REQUIRED TO LIMIT
RACEWAY FILL RATIO TO LESS THAN 40% FULL.
8. ALL CONDUCTORS COPPER.
9. ALL FEEDERS AND BRANCH CIRCUITS SHALL INCLUDE A GREEN INSULATED GROUND
CONDUCTOR, SIZE PER NATIONAL ELECTRICAL CODE, OR AS SHOWN, CONNECTED TO EACH
DEVICE AND OUTLET BOX ON THE CIRCUIT AND TO THE PANELBOARD GROUND BUS. PROVIDE
A DEDICATED NEUTRAL CONDUCTOR FOR EACH BRANCH CIRCUIT. MULTTIPLE BRANCH
CIRCUITS IN ONE RACEWAY REQUIRE ONLY ONE GROUND CONDUCTOR.
10. ALL SAFETY DISCONNECTS SHALL BE HEAVY DUTY 240V NEMA 4 NON-FUSED TYPE.
11. PROVIDE SAFETY DISCONNECTS FOR ALL MECHANICAL EQUIPMENT.
12. NEW WORK SHALL BE MADE TO TIE INTO THE EXISTING IN A UNIFORM MANNER, SIMILAR ITEMS
OF NEW WORK SHALL BE CHECKED AGAINST EXISTING WORK.
13. REFER TO ONE-LINE DIAGRAMS, SCHEDULES, AND RISER DIAGRAMS FOR CONDUCTOR AND
CONDUIT SIZES NOT SHOWN ON PLANS.
14. PROVIDE LABELS ON ALL RECEPTACLES, WALL MOUNTED LIGHT SWITCHES AND JUNCTION
BOXES INDICATING THE SOURCE PANEL AND CIRCUIT(S). TEXT SHALL BE BLACK 1/4-IN IN
HEIGHT PRINTED ON A CLEAR LABEL. HANDWRITTEN LABELS ARE NOT PERMITTED.
15. COORDINATE WALL, FLOOR AND ROOF PENETRATIONS WITH THE CONTRACTOR.
16. SUPPLEMENTAL STEEL MEMBERS REQUIRED TO SUPPORT ELECTRICAL EQUIPMENT FROM
MAIN STRUCTURE SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR UNLESS
SPECIFICALLY NOTED OTHERWISE.
17. EXACT LOCATIONS OF PANELBOARDS, DISCONNECTS, TIMERS, AND SWITCHES SHALL BE
COORDINATED WITH FINAL LOCATIONS OF WALL-MOUNTED ARCHITECTURAL AND
MECHANICAL EQUIPMENT. MOUNT DISCONNECTS AND SWITCHES MINIMUM 48" AFF. MOUNT
TIMERS MINIMUM 40" AFF.
18. MANUFACTURER NAME AND MODEL NUMBERS ARE BASIS OF DESIGN AND ARE SHOWN
FOR INFORMATION ONLY. REFER TO SPECIFICATIONS FOR COMPLETE REQUIREMENTS.
19. SPECIFICATIONS TAKE PRECEDENCE OVER DRAWINGS. HOWEVER, ITEMS SHOWN ON
DRAWING BUT NOT IN THE SPECIFICATIONS ARE REQUIRED WITHIN THE PROJECT SCOPE.
IN ADDITION, SPECIFIC ITEMS SHOWN ON THE DRAWINGS TAKE PRECEDENCE OVER
SPECIFICATIONS IN CASES WHERE THE SPECIFICATION HAS OPTIONS.
20. ALL EQUIPMENT INSTALLED IN THIS PROJECT SHALL COMPLY WITH THE "BUY AMERICAN
ACT". BASIS OF DESIGN SHOWN ON SCHEDULES IS TO ESTABLISH A STANDARD OF
QUALITY, NOT TO LIMIT COMPETITION. EQUIVALENT EQUIPMENT FROM ANOTHER
MANUFACTURER IS ACCEPTABLE
21. PROVIDE GFCI PROTECTION AND FOR ALL NON-LIGHTING RECEPTACLES.
22. PROVIDE WEATHERPROOF IN USE COVERS FOR ALL RECEPTACLES.
23. PROVIDE WEATHERPROOF COVERS FOR ALL SWITCHES.
GENERAL PROJECT NOTES:ABBREVIATIONS:
DSHP
DSS
DWBP
DX
EC
EF
ELEC
EMH
EMT
E or EMER
EPA
EQUIP
ERV
ERU
EXIST or EX
A OR AMP AMPERE(S)
ACC
AC
AC
AF
AFF
AFG
AHU
AIC
AL
AM
ASYM
AT
ATS
AUTO
AWG
B
BC
BCW
BFF
BFG
BLDG
C
CAT
CB
CCT
CCTV
CFCI
CH
CHWCP
CHWP
CHWSP
CKT
CMH
CP
CPT
CRAC
CRI
CT
CT
CU
CWP
D
DC
DF
DH or DUH
DHWCP
DISC
DOAS
DPST
DPDT
DSCU
AIR COOLED CHILLER
ALTERNATING CURRENT
AIR CONDITIONING UNIT
CURTAIN
AMP FRAME
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AIR HANDLING UNIT
AMPERE INTERRUPTING
CAPACITY
ALUMINUM
AMMETER
ASYMMETRICAL
AMP TRIP
AUTOMATIC TRANSFER
SWITCH
AUTOMATIC
AMERICAN WIRE GAUGE
BOILER
BRANCH CONTROLLER
BARE COPPER WIRE
BELOW FINISHED FLOOR
BELOW FINISHED GRADE
BUILDING
CONDUIT
CATEGORY
CIRCUIT BREAKER
CORRELATED COLOR
TEMPERATURE
CLOSED CIRCUIT
TELEVISION
CONTRACTOR FURNISHED
CONTRACTOR INSTALLED
CHILLER
CHILLED WATER
CIRCULATING PUMP IN A
PRIMARY-SECONDARY
SYSTEM
CHILLED WATER PUMP
CHILLED WATER SUPPLY
PUMP IN A PRIMARY-
SECONDARY SYSTEM
CIRCUIT
COMMUNICATIONS
MANHOLE
CONDENSATE PUMP
CONTROL POWER
TRANSFORMER
COMPUTER ROOM AC UNIT
COLOR RENDERING INDEX
CURRENT TRANSFORMER
COOLING TOWER
COPPER OR CONDENSING
UNIT
CONDENSER WATER PUMP
DEPTH
DIRECT CURRENT
DESTRATIFICATION FAN
DUCT HEATERS
DOMESTIC HOT WATER
CIRCULATING PUMP
DISCONNECT SWITCH
DEDICATED OUTSIDE AIR
SYSTEM (UNIT)
DOUBLE POLE SINGLE
THROW
DOUBLE POLE DOUBLE
THROW
DUCTLESS SPLIT
CONDENSING UNIT
(POWERS THE DSS INDOOR
UNIT)
DUCTLESS SPLIT HEAT
PUMP (POWERS THE DSS
INDOOR UNIT)
DUCTLESS SPLIT SYSTEM
(INDOOR UNIT)
DOMESTIC WATER
BOOSTER PUMP
DIRECT EXPANSION (DX)
COOLING COIL
EMPTY CONDUIT
EXHAUST FAN
ELECTRICAL
ELECTRICAL MANHOLE
ELECTRICAL METALLIC
TUBING
EMERGENCY
EFFECTIVE PROJECTED
AREA
EQUIPMENT
ENERGY RECOVERY
VENTILATOR
ENERGY RECOVERY UNIT
EXISTING
NFPA
NC
NESC
NL
NO
NTS
P
PA
HWP
HWRP
HWSP
HWUH
HZ
IDS
IMC
IRH
J OR JB
K
KAIC
KEF
KH
KV
KVA
KW
KWHR
L
LA
LAN
LAV
LM
LTG
MAU
MAX
MCA
MCB or MB
MCC
MGB
MH
MIN
MLO
MOD
MT or MTD
MRS
N
NEC
NEMA
HT
HVU
HWCP
GUH
GWH
H or HT
HAC
HOA
HP
HP
EUH
EXP
EWC
EWH
F
FACP
FCU
FLEX
FWE
G OR GND
GFGI
GFCI
GRS
ELECTRIC UNIT HEATER
EXPLOSION PROOF
ELECTRIC WATER COOLER
ELECTRIC WATER HEATER
FUSE
FIRE ALARM CONTROL
PANEL
FAN COIL UNIT
FLEXIBLE
FURNISHED WITH
EQUIPMENT
GROUND
GOVERNMENT FURNISHED
GOVERNMENT INSTALLED
GROUND FAULT
INTERRUPTER
GALVANIZED RIGID STEEL
CONDUIT
GAS UNIT HEATER
GAS WATER HEATER
HEIGHT
HEATED AIR CURTAIN
HAND-OFF AUTOMATIC
HORSE POWER
HEAT PUMP (OUTDOOR
PORTION OF SPLIT SYSTEM
HEAT PUMP, USE CU FOR
STANDARD DX OUTDOOR
UNIT)
HEAT TRACKING
HEATING/VENTILATING UNIT
HEATING WATER
CIRCULATING PUMP IN A
PRIMARY-SECONDARY
SYSTEM
HEATING WATER SUPPLY IN
A PRIMARY-ONLY SYSTEM
HOT WATER
RECIRCULATION PUMP
HEATING WATER SUPPLY
PUMP IN A PRIMARY-
SECONDARY SYSTEM
HOT WATER UNIT HEATER
HERTZ
INTRUSION DETECTION
SYSTEM
INTERMEDIATE METAL
CONDUIT
INFRARED HEATER
JUNCTION BOX
KILO
THOUSAND AMPERE
INTERRUPTING CAPACITY
KCM OR KCMIL THOUSAND OF CIRCULAR
MILS
KITCHEN EXHAUST FAN
KITCHEN HOOD
KILOVOLT
KILOVOLT-AMPERES
KILOWATT
KILOWATT-HOUR
LENGTH
LIGHTNING ARRESTOR
LOCAL AREA NETWORK
LAVATORY
LOCKHEED MARTIN
LIGHTING
MAKE-UP AIR UNIT
MAXIMUM
MINIMUM CIRCUIT AMPACITY
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
MAIN GROUND BAR
MANHOLE or MOUNTING
HEIGHT
MINIMUM
MAIN LUGS ONLY
MOTOR OPERATED DAMPER
MOUNT or MOUNTED
MOTOR RATED SWITCH
NEUTRAL
NATIONAL ELECTRICAL
CODE
NATIONAL ELECTRICAL
MANUFACTURER'S
ASSOCIATION
NATIONAL FIRE
PROTECTION ASSOCIATION
NORMALLY CLOSED
NATIONAL ELECTRICAL
SAFETY CODE
NIGHT LIGHT
NORMALLY OPEN
NOT TO SCALE
POLE(S) or PUMP
PUBLIC ADDRESS
SPEC
SPST
SWBD
SWGR
TMGB
TOL
TP
TYP
U
UH
UG
UIO
UL
UTP
V
VA
VAV
VEF
VM
VRF
W
WC
WEF
WH
WHDM
WSHP
WP
XFMR
Z
PDU
PF
PH
PIU
PMT
PNL
PTAC
PVC
POWER DISTRIBUTION UNIT
POWER FACTOR
PHASE
VAV TERMINAL UNIT WITH
PARALLEL OR SERIES FAN
(PRIMARY INDUCTION UNIT)
PAD MOUNTED
TRANSFORMER
PANEL OR PANELBOARD
PACKAGED THRU-WALL AIR
CONDITIONER
POLYVINYL CHLORIDE
RECEPT or RECP RECEPTACLE
RF
RH
RETURN FAN
RADIANT HEATERS
(ELECTRIC)
RMC
RMS
RTU
RVNR
SA
SCCR
SD
SF
S/N
SP
SPD
SPDT
RIGID METAL CONDUIT
ROOT MEAN SQUARE
ROOF TOP UNIT
REDUCED VOLTAGE NON-
REVERSING
SURGE ARRESTOR
SHORT CIRCUIT CURRENT
RATING
SMOKE DAMPER
SUPPLY FAN
SOLID NEUTRAL
SUMP PUMP
SURGE PROTECTIVE DEVICE
SINGLE POLE DOUBLE
THROW
SPECIFICATIONS
SINGLE POLE SINGLE
THROW
SWITCHBOARD
SWITCHGEAR
TELECOMMUNICATIONS
MAIN GROUNDING BUSBAR
THERMAL OVERLOAD
TWISTED PAIR
TYPICAL
URINAL
UNIT HEATER
UNDERGROUND
UNLESS INDICATED
OTHERWISE
UNDERWRITERS
LABORATORY
UNSHIELDED TWISTED PAIR
VOLTS
VOLT AMPERES
VAV TERMINAL UNIT
VEHICLE EXHAUST FAN
VOLTMETER
VARIABLE REFRIGERANT
FLOW SYSTEM
WATTS or WIRE or WIDTH
WATER CLOSET
WELDING EXHAUST FAN
WATER HEATER
WATTHOUR DEMAND METER
WATER SOURCE HEAT
PUMP
WEATHERPROOF
TRANSFORMER
IMPEDANCE
NOTE: ABBREVIATIONS ABOVE
ARE FOR ELECTRICAL SHEETS
ONLY. NOT ALL ABBREVIATIONS
SHOWN WILL BE USED ON THIS
PROJECT.
MDP MAIN DISTRIBUTION PANEL
xx
PANELBOARD.
NAME OF PANELBOARD
GEAR
LA-1
LA-1 HOMERUN TO PANELBOARD. ARC DENOTES CONCEALED
CIRCUITRY. TEXT DENOTES PANELBOARD NAME WITH
CIRCUIT NUMBER. DEVICES HAVING CIRCUIT NUMBERS
LOCATED BESIDE THEM MAY NOT SHOW THE CIRCUIT
NUMBERS AT THE HOMERUN ARROWS.
PARTIAL HOMERUN TO PANELBOARD. COMBINE ALL
PARTIAL HOMERUNS THAT ARE ON THE SAME CIRCUIT IN
A JUNCTION BOX PRIOR TO ENTERING THE PANELBOARD.
10 THE TEXT INSIDE THE ARC INDICATES THE AWG SIZE OF
THE CONDUCTORS THAT SHALL BE RUN IN THE CONDUIT.
THE ABSENCE OF TEXT SIGNIFIES THAT THE
CONDUCTORS SHOULD BE #12 AWG.
CONDUIT AND WIRING
CONDUCTORS IN CONDUIT SURFACE MOUNTED TO WALL OR
CEILING. LONG TIC MARKS INDICATE NUMBER OF
CONDUCTORS. THE EQUIPMENT GROUNDING CONDUCTOR
IS SHOWN AS A SHORT TIC MARK. SIZE THE
EQUIPMENT GROUNDING CONDUCTOR AND THE CONDUIT
PER THE NEC. THE ABSENCE OF TIC MARKS SIGNIFIES
THAT TWO CONDUCTORS PLUS AN EQUIPMENT GROUNDING
CONDUCTOR SHOULD BE PROVIDED. FOR EXAMPLE, THE
MARKINGS TO THE LEFT SIGNIFY THAT THREE
CONDUCTORS PLUS AN EQUIPMENT GROUNDING
CONDUCTOR SHOULD BE PROVIDED.
UNDERGROUND DUCT. DASHED LINE INDICATES CONDUIT IS
TO BE TRENCHED AND BURIED. REFER TO ?/E-??? FOR
DETAIL.
ELECTRICAL LEGEND:
SIMPLEX NEMA L5-20R. PROVIDE WITH WEATHERPROOF IN USE COVER.
QUADRUPLEX NEMA 5-20R. PROVIDE WITH WEATHERPROOF IN USE COVER.
DUPLEX NEMA 5-20R. PROVIDE WITH WEATHERPROOF IN USE COVER.
EXISTING FUEL OIL TANK
NEW PROPANE TANK N.I.C. INSTALLED
AND FURNISHED BY GOVERNMENT
W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W
W W
W
EXISTING 2" WATER LINE
EXISTING GREENHOUSE EXISTING GREENHOUSE
EXISTING HEADHOUSE
EXISTING HEADHOUSE
W W
W
NEW CRANBERRY
RESEARCH GREENHOUSE
BASE BID
NEW CRANBERRY
RESEARCH GREENHOUSE
BID OPTION #2
EVAPORATIVE COOLING
PADS BID OPTION #3
EVAPORATIVE COOLING
PADS BID OPTION #1
BASE BIDBID OPTION #2
SCALE:
SITE PLAN
1" = 10'
ES100
NORTH
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
c
USDA AGRICULTURAL RESEARCH SERVICE
BLUEBERRY AND CRANBERRY RESEARCH CENTER
ADDITION TO CRANBERRY BREEDING AND GENETICS GREENHOUSE
CHATSWORTH, NEW JERSEY
SITE PLAN
ES100
13 1803/08/24
REH
BSN
FEJ
10300 BALTIMORE AVE.
BELTSVILLE, MD 20705
XXX
6223-A
XXX
XXX
XXX
XXX
20'
SCALE: 1"=10'-0"
0 10' 30'
COMPACTED SAND BACKFILL
BACKFILL AND COMPACT IN
MAX 6" LAYERS
MARKER TAPE WITH
DETECTABLE FOIL BACKING.
MARKER TAPE MUST BE RED
AND CONTINUOUSLY
LABELED ELECTRIC
SCALE:
DUCTBANK DETAIL
NA
ES100
7 1/2"
MIN
3"
MIN
3" MI
N
3" MI
N
3"
MIN
1'
EMERGENCY POWER DUCT
THREE #4, #10GND IN
1.25-IN SCH 40 PVC
(TYPICAL OF TWO DUCTS)
NORMAL POWER DUCT
THREE 1/0, #6GND IN 1.5-IN
SCH 40 PVC
(TYPICAL OF TWO DUCTS)
KEYED NOTES:
1. PROVIDE NEW UNDERGROUND SERVICE FROM EXISTING 2-IN CONDUIT
STUBBED OUT 3-FT FROM PANEL MDP TO NEW PANEL GH1 CONSISTING
OF THREE 1/0, #6GND IN 1.5-IN SCH 40 PVC. REFER TO 2/ES100.
2. PROVIDE NEW UNDERGROUND SERVICE FROM EXISTING 2-IN CONDUIT
STUBBED OUT 3-FT FROM PANEL MDP TO NEW PANEL GH2 CONSISTING
OF THREE 1/0, #6GND IN 1.5-IN SCH 40 PVC. REFER TO 2/ES100.
3. PROVIDE NEW UNDERGROUND SERVICE FROM EXISTING 2-IN CONDUIT
STUBBED OUT 3-FT FROM PANEL EM TO NEW PANEL GH1 EM CONSISTING OF
THREE #4, #10GND IN 1.25-IN SCH 40 PVC. REFER TO 2/ES100.
4. PROVIDE NEW UNDERGROUND SERVICE FROM EXISTING 2-IN CONDUIT
STUBBED OUT 3-FT FROM PANEL EM TO NEW PANEL GH2 EM CONSISTING OF
THREE #4, #10GND IN 1.25-IN SCH 40 PVC. REFER TO 2/ES100.
5. EQUIPMENT IS BEING PROVIDED BY A DIFFERENT CONTRACT. CONFIRM
WORK MATCHES CONDITIONS SHOWN PRIOR TO START OF WORK.
X
COMPACTED SAND BACKFILL
BACKFILL AND COMPACT IN
MAX 6" LAYERS
MARKER TAPE WITH
DETECTABLE FOIL BACKING.
MARKER TAPE MUST BE RED
AND CONTINUOUSLY
LABELED ELECTRIC
SCALE:
DUCTBANK DETAIL
NA
ES100
7 1/2"
MIN
3"
MIN
3" MI
N
3" MI
N
3"
MIN
1'
EMERGENCY POWER DUCT
THREE #4, #10GND IN
1.25-IN SCH 40 PVC
NORMAL POWER DUCT
THREE 1/0, #6GND IN
1.5-IN SCH 40 PVC
7 1 /2"
MI
N
PANEL MDP
PANEL EM
GENERATOR
NEW PANEL GH1 EM
NEW UNDERGROUND SERVICE1 2
NEW PANEL GH11
ES100
ES100
3 4
NEW UNDERGROUND SERVICE1 3
NEW PANEL GH2 EM
NEW PANEL GH22
NEW UNDERGROUND SERVICE2 4
ES100
Stamp
CF-1 CF-1
A1
PANEL EM
PANEL GH
GL1 GL1 GL1 GL1 GL1 GL1 GL1 GL1 GL1 GL1 GL1
GH2:3 GH2:7
GL1GL1
GH2:11
GL1GL1
GL1GL1GL1
GH2:9
GL1GL1GL1 GL1 GL1 GL1 GL1 GL1 GL1 GL1 GL1 GL1
GH2:5GH2:1
GH2:15
GH2:13
GH2 EM:1
GH2 EM:1
GH2 EM:3
GH2 EM:3
GH2 EM:2
GH2 EM:7
GH2 EM:5
ENVIRONMENTAL
CONTROL PANEL
LIGHTING TIMERS
(TYP OF 6)
GH2:17
GH2:23
GH2 EM:4
CF-1 CF-1
A1
PANEL EM
PANEL GH
GL1 GL1 GL1 GL1 GL1 GL1 GL1 GL1 GL1 GL1 GL1
GH1:3 GH1:7
GL1GL1
GH1:11
GL1GL1
GL1GL1GL1
GH1:9
GL1GL1GL1 GL1 GL1 GL1 GL1 GL1 GL1 GL1 GL1 GL1
GH1:5GH1:1
GH1:15
GH1:13
GH1 EM:1
GH1 EM:1
GH1 EM:3
GH1 EM:3
GH1 EM:2
GH1
EM:7
GH1 EM:5
ENVIRONMENTAL
CONTROL PANEL
LIGHTING TIMERS
(TYP OF 6)
GH1:17
GH1:23
GH1 EM:4
A1 A1 A1
A1 A1 A1
CF-1 CF-1
CF-1 CF-1
EXHAUST FAN
SEE MECHANICAL
EXHAUST FAN
SEE MECHANICAL
F
F
GH1 EM:11
GH1 EM:9
GH1:21
EF-1
EF-1
EXHAUST FAN
SEE MECHANICAL
EXHAUST FAN
SEE MECHANICAL
F
F
GH2 EM:11
GH2 EM:9
GH2:21
EF-1
EF-1
VENT SYSTEM
VENT CONTROL
BID OPTION #1:
EVAPORATIVE COOLING PAD SYSTEM
P
GH1 EM:6
ECP-1
ECP-2
P
GH1 EM:8
GH1 EM:10
L
GH1:21
VENT SYSTEM
VENT CONTROL
BID OPTION #1:
EVAPORATIVE COOLING PAD SYSTEM
P
GH2 EM:6
ECP-1
ECP-2
P
GH2 EM:8
GH2 EM:10
L
GH2:21
HEAT DUCTS SEE MECHANICAL
HEAT DUCTS SEE MECHANICAL
GH1:19
GH2:19
HEAT DUCTS SEE MECHANICAL
F-1
F-1
F-1
E200
E200
E200
2 SIM.
GREENHOUSE #1
GREENHOUSE #2
F
F
GH1 EM:12
GH2 EM:12
INFLATION FAN
INFLATION FAN
F-1 HEAT DUCTS SEE MECHANICAL
BASE BID
BID OPTION #2
VENT SYSTEM
BID OPTION #1
VENT SYSTEM
BID OPTION #3
SCALE:
FLOOR PLAN
1/4" = 1'-0"
E100
8'0 2' 4' 12'
SCALE: 1/4"= 1'-0"
PPM
REVISIONS
Agricultural
Service Research
DESCRIPTION
SHEET
DATE
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
AGRICULTURAL RESEARCH SERVICE
OF
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
P.A.
FIRMTHE
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
c
USDA AGRICULTURAL RESEARCH SERVICE
BLUEBERRY AND CRANBERRY RESEARCH CENTER
ADDITION TO CRANBERRY BREEDING AND GENETICS GREENHOUSE
CHATSWORTH, NEW JERSEY
ELECTRICAL PLAN
E100 15 1803/08/24
REH
BSN
FEJ
10300 BALTIMORE AVE.
BELTSVILLE, MD 20705
XXX
6223-A
XXX
XXX
XXX
XXX
1 1
1 1
2 3
2 3 2 3
2 3 2 3
2 3
2 3 4
2 2
2 2
KEYED NOTES:
1. PROVIDE 30A SAFETY DISCONNECT.
2. SUPPORT DEVICE AND CONDUIT FROM
GREENHOUSE FRAME. PROVIDE ADDITIONAL
SUPPORT AS REQUIRED.
3. SUPPORT LIGHT FIXTURE AND DRIVER FROM
GREENHOUSE FRAME. PROVIDE ADDITIONAL
HANGERS AND SUPPORT AS
REQUIRED.CONNECT TO LIGHTING TIMER PER
DETAIL 1/E700.
4. PROVIDE MANUAL SWITCHING. LOCATE
THREE-WAY SWITCH ON GREENHOUSE
EXTERIOR AT EACH DOOR MOUNTED 48-IN AFF.
PROVIDE WEATHERPROOF SWITCH COVER.
TYPICAL FOR 2 GREENHOUSES.
5. BID OPTION #1: EVAPORATIVE COOLING SYSTEM.
6. BID OPTION #3: EVAPORATIVE COOLING SYSTEM.
1 1
1 1
2 3
2 3 2 3
2 3 2 3
2 3
2 3 4
2 2
2 2
PLAN
NORTH
TRUE
NORTH
GREENHOUSE #1
BASE BID
GREENHOUSE #2
BID OPTION #2
GL1
A1
GL1
GROW LIGHTS
AISLE LIGHTS
LIGHTING RECEPTACLE
8'- 2"
HEAT DUCTS SEE MECHANICAL
'-8
5'- 8"
CONVENIENCE RECEPTACLE
GROW LIGHTS
LIGHTING RECEPTACLE
CONVENIENCE RECEPTACLEGL1
A1
GL1
HEAT DUCTS SEE MECHANICALHEAT DUCTS SEE MECHANICAL
GROW LIGHTS
AISLE LIGHTS
LIGHTING RECEPTACLE
GROW LIGHTS
LIGHTING RECEPTACLE
CONVENIENCE RECEPTACLE
EF-1EF-1
LIGHTING TIMERS
LIGHT SWITCH
GH EM
RECEPTACLE
ENVIRONMENTAL
CONTROL PANEL
MECHANICAL EQUIPMENT
SAFETY DISCONNECTS
MECHANICAL EQUIPMENT
SAFETY DISCONNECTS
1 1
CONVENIENCE RECEPTACLE2
2 2
8'0 2' 4' 12'
SCALE: 1/4"= 1'-0"
PPM
REVISIONS
Agricultural
Service Research
DE…