Attachment 2 Redlined Plans 8Mar24.pdf

PDF 16 MB Posted

Attached to
Greenhouse Construction, Blueberry and Cranberry Research Station, Chatsworth, New Jersey
Solicitation number
12305B24R0030
Issued by

About this file

This document is an attachment to a Request for Proposal (RFP) for the construction of two 30' x 100' (6,000 square foot total) aluminum framed greenhouses at the Blueberry and Cranberry Research Station in Chatsworth, New Jersey. The solicitation, identified as 12305B24R0030, is a requirement of the United States Department of Agriculture (USDA), Agricultural Research Service (ARS) with an estimated construction value between $1,000,000 and $5,000,000.

The project includes furnishing all labor, materials, and equipment to construct the greenhouses with 6 mil poly inflated film covering, shade cloth, polycarbonate panels, exhaust fans, louvers, propane fired furnaces, circulation fans, greenhouse controls system, domestic water main, irrigation system, propane tank and piping, and new electrical service. The solicitation includes a base bid and three optional contract line items for additional work. The period of performance is 180 days after the notice to proceed. The solicitation is a total small business set-aside with a size standard of $45.0 million. Site visits are scheduled for 07/24/2024 and the deadline for submitting requests for information is 08/01/2024.

View the file

Other files

Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NO SCALEVICINITY MAP

N

BLUEBERRY AND CRANBERRY RESEARCH CENTER

AGRICULTURAL RESEARCH SERVICE

U.S. DEPARTMENT OF AGRICULTURE

DRAWING NO.

INDEX OF DRAWINGS

SHEET NO. TITLE

LOCATION MAP NO SCALE

N

T100

C100

S100

S101

A100

A200

A300

M001

M100

M200

M600

E001

ES100

E100

E200

E600

E601

E700

TITLE SHEET

SITE LAYOUT

FOUNDATION PLAN

FOUNDATION DETAILS

FLOOR PLAN

ELEVATIONS

GREENHOUSE SECTION

MECHANICAL NOTES AND ABBREVIATIONS

MECHANICAL FLOOR PLAN

MECHANICAL ELEVATIONS

MECHANICAL SCHEDULE AND DETAILS

ELECTRICAL NOTES AND ABBREVIATIONS

SITE PLAN

FLOOR PLAN

ELEVATIONS

EXISTING PANEL SCHEDULES AND SINGLE LINE

NEW PANEL SCHEDULES

LIGHTING SLIDES

125 LAKE OSWEGO ROAD CHATSWORTH, NJ 08019

USDA

CRANBERRY BREEDING AND

GENETICS GREENHOUSE

PROJECT

LOCATION

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

C:\ Us ers

\JF

ER

GU

~1 \Ap pD ata

\Lo ca l\T em p\A cP ub lish

_1

\T1

.dw g M ar

, 2

4 - 2:

pm

P.A.

FIRMTHE

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

c

USDA AGRICULTURAL RESEARCH SERVICE

BLUEBERRY AND CRANBERRY RESEARCH CENTER

ADDITION TO CRANBERRY BREEDING AND GENETICS GREENHOUSE

CHATSWORTH, NEW JERSEY

TITLE SHEET

T100 1 1803/08/24

REH

REH

FEJ

10300 BALTIMORE AVE.

BELTSVILLE, MD 20705

XXX

6223-A

XXX

XXX

XXX

XXX

CHATSWORTH, NJ

PROJECT LOCATION:

125 LAKE OSWEGO ROAD

CHATSWORTH, NJ 08019

A-E CONTRACT #12305B21D0013 / 12305B22F0084

GREEN BANK

CHATSWORTH RD.

LAKE OSWEGO RD.

LA

KE

O

SW

EG

O

R D

PE

N

N P

L R

D

PENN PL RD.

PENN PL RD.

CONTRACTORS

HAUL ROUTE

100% DESIGN RE-SUBMITTAL

BID DESCRIPTION

BASE BID:

CONSTRUCTS A SINGLE GREENHOUSE STRUCTURE AS INDICATED AND SPECIFIED.

BID OPTION #1:

CONSISTS OF INSTALLATION OF EVAPORATIVE COOLING PADS FOR GREENHOUSE #1 AS DETAILED AND SPECIFIED.

BID OPTION #2:

CONSISTS OF CONSTRUCTING A SECOND GREENHOUSE STRUCTURE, GREENHOUSE #2, CONNECTED TO GREENHOUSE #1 AS DETAILED

AND SPECIFIED.

BID OPTION #3:

CONSISTS OF INSTALLATION OF EVAPORATIVE COOLING PADS FOR GREENHOUSE #2 AS DETAILED AND SPECIFIED.

NEW GRETNA

CHATSWORTH RD

CHATSWORTH

BARNEGAT RDTABERNACLE

CHATSWORTH RD

SAVOY RD

jferguson Stamp

EXISTING FUEL OIL TANK

EXISTING BOLLARDS

NEW 8" DIA. SCHEDULE 40

PIPE BOLLARDS (TYP. OF 5)

SEE DETAIL 3/C100

NEW PROPANE TANK N.I.C. INSTALLED

AND FURNISHED BY GOVERNMENT

8'-10"

1'-

2"

LINE OF OUTSIDE OF FOOTING

NEW CRANBERRY

RESEARCH GREENHOUSE

BASE BID

W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W

W W

W

EXISTING 2" WATER LINE

PROVIDE WET TAP AT EXISTING WATER LINE,

SEE DETAIL 2/C100.

PROVIDE NEW WATER LINE SEE MECHANICAL

'-0

EXISTING GREENHOUSE EXISTING GREENHOUSE

EXISTING HEADHOUSE

EXISTING HEADHOUSE

NEW CRANBERRY

RESEARCH GREENHOUSE

BID OPTION #2

6'

17'-4"

EQ. EQ. EQ.

7'

8'-2"

29'-10"

1'-

2"

29'-10"

'-6

W W

W

PROVIDE NEW WATER LINE SEE MECHANICAL

PROVIDE WET TAP AT EXISTING WATER LINE,

SEE DETAIL 2/C100.

1'-6"

61'-2"

EVAPORATIVE COOLING

PADS BID OPTION #3

EVAPORATIVE COOLING

PADS BID OPTION #1

BASE BIDBID OPTION #2

SCALE:

SITE PLAN

1" = 10'

C100

NORTH

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

P.A.

FIRMTHE

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

c

USDA AGRICULTURAL RESEARCH SERVICE

BLUEBERRY AND CRANBERRY RESEARCH CENTER

ADDITION TO CRANBERRY BREEDING AND GENETICS GREENHOUSE

CHATSWORTH, NEW JERSEY

SITE LAYOUT

C100 2 1803/08/24

REH

REH

FEJ

10300 BALTIMORE AVE.

BELTSVILLE, MD 20705

XXX

6223-A

XXX

XXX

XXX

XXX

20'

SCALE: 1"=10'-0"

0 10' 30'

FINISHED GRADE

AROUND COVER

HAND TAMP BACKFILL

PVC WATERLINE, TYP.

THRUST BLOCK

#4 BARS, TYP.

EXISTING PIPE,

MATERIAL TYPE

VARIES

MECHANICAL JOINT

TAPPING TEE

MECHANICAL JOINT

GATE VALVE

CAST IRON VALVE BOX (COVER

MARKED WATER)

20"x20"x4" CONCRETE PAD W/6x6, W2.9xW2.9 W.W.F.

" M

IN

IM

UM

1"

SCALE:

TYPICAL WET TAP DETAIL

NONE

C100

1'-8"

SQUARE

3'- 0"

4'- 0"

1"

3"

FINISHED GRADE

#5 REBAR THRU PIPE

8"Ø SCH 40 PIPE,

PAINT SAFETY YELLOW

FILL PIPE w/ CONCRETE

& ROUND OFF TOP

SCALE:

TYPICAL BOLLARD DETAIL

NONE

C100

EXISTING GRAVEL PAVEMENT

NEW GRAVEL

PAVEMENT SURFACE

LIMIT OF GRAVEL REMOVAL/REPLACEMENT

1' MIN. 1' MIN.

6" M

IN

HAUNCHING

4" BEDDING MIN.

FINAL BACKFILL

INITIAL BACKFILL

NOTES:

1. MATCH THICKNESS OF EXISTING GRAVEL OR

4" MIN. WHICHEVER IS GREATER.

TRENCH BACKFILL NOTES

1. BEDDING SHALL BE CLASS II (SW OR SP) WORKED BY HAND. IF GROUNDWATER IS ENCOUNTERED. THEN CLASS II (GP)

BEDDING SHALL BE USED. BEDDING SHALL BE HAND TAMPED.

2. HAUNCHING AND INITIAL BACKFILL SHALL BE CLASS II (GW OR GP). HAUNCHING SHALL BE WORKED AROUND THE PIPE BY

HAND TO ELIMINATE VOIDS, AND SHALL BE HAND TAMPED ADJACENT TO THE PIPE. INITIAL BACK FILL SHALL BE COMPACTED

TO 96% STANDARD PROCTOR DENSITY.

3. FINAL BACKFILL SHALL BE CLASS I, II, OR III COMPACTED TO 96% STANDARD PROCTOR DENSITY. MATERIAL EXCAVATED FROM THE TRENCH MAY BE USED AS CLASS III MATERIAL IN TURFED AREAS IF IT IS FREE OF LARGE ROCKS OR COBBLES. THE TOP 8" OF FINAL BACKFILL IN A TRENCH CUT THROUGH EXISTING GRAVEL ROADWAYS SHALL BE CLASS I. COMPACTED TO 98%

STANDARD PROCTOR DENSITY.

4. ALL MATERIALS ARE CLASSIFIED IN ACCORDANCE WITH ASTM D 2321.

5. ALL MATERIALS SHALL BE INSTALLED IN MAXIMUM 6" LOOSE LIFTS. INITIAL AND FINAL BACKFILL MATERIALS SHALL BE

COMPACTED NEAR OPTIMUM MOISTURE CONTENT.

6. ALL TRENCH EXCAVATIONS SHALL BE SLOPED, SHORED, SHEETED, BRACED OR OTHERWISE SUPPORTED IN COMPLIANCE

WITH OSHA REGULATIONS AND ANY LOCAL ORDINANCES.

SCALE:

TYPICAL TRENCH DETAIL

NONE

C100

N.I.C.

jferguson Stamp

Wayne.Shekailo Rectangle

Wayne.Shekailo Line

Wayne.Shekailo Line

1'-6"

98'-2"

1'-6"101'-2"

1'- 6"

1'- 6"

'-4

" B

AS

E

BI

D

6'

S101

S101

4" CONCRETE WALKWAY 4" COMPACTED CRUSHED STONE

4'-0" 6'-10"

'-2

6'

'-2

5'-3"

6'

5'-3"

6'

'-2

1'- 6"

'-4

" B

ID

O

PT

IO

N

#2

6'

S101

4" CONCRETE WALKWAY

4'-0" 6'-10"

'-2

6'

'-2

5'-3"

6'

5'-3"

6' 4" COMPACTED CRUSHED STONE

S101

GREENHOUSE #1

BASE BID

GREENHOUSE #2

BID OPTION #2

1'- 8"

1'- 8"

'-9

'-9

S101

S101

S101

S101

S101

S101

S101

S101

S101

S101

S101

BASE BID

BID OPTION #2

S101

4" REINFORCED CONCRETE

PAD SLOPED FROM FINISH

WALKWAY ELEVATION TO

FINISHED GRADE

4" REINFORCED CONCRETE

PAD SLOPED FROM FINISH

WALKWAY ELEVATION TO

FINISHED GRADE

S101

S101

S101

4" REINFORCED CONCRETE

PAD SLOPED FROM FINISH

WALKWAY ELEVATION TO

FINISHED GRADE

4" REINFORCED CONCRETE

PAD SLOPED FROM FINISH

WALKWAY ELEVATION TO

FINISHED GRADE

SCALE:

FOUNDATION PLAN

1/4" = 1'-0"

S100

8'0 2' 4' 12'

SCALE: 1/4"= 1'-0"

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

P.A.

FIRMTHE

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

c

USDA AGRICULTURAL RESEARCH SERVICE

BLUEBERRY AND CRANBERRY RESEARCH CENTER

ADDITION TO CRANBERRY BREEDING AND GENETICS GREENHOUSE

CHATSWORTH, NEW JERSEY

FOUNDATION PLAN

S100 3 1803/08/24

REH

REH

FEJ

10300 BALTIMORE AVE.

BELTSVILLE, MD 20705

XXX

6223-A

XXX

XXX

XXX

XXX

TRUE

NORTH

jferguson Stamp

Wayne.Shekailo Rectangle

Wayne.Shekailo Line

1'-6"

2'- 2"

4"

6'-0"

4"

4" COMPACTED

CRUSHED STONE

2" MIN.

2" M

IN

#4 @ 9" O.C.

1'-

1'-2"

SCALE:

FOUNDATION DETAIL

1-1/2" = 1'-0"

S101

SCALE:

SLAB ON GRADE DETAIL

1-1/2" = 1'-0"

S101

(4) #4 CONT. TOP AND BOTTOM

6" x 6" x 4.0 W.W.M. CONT. 4" COMPACTED CRUSHED

STONE

1" CHAMFER

COMPACTED EXISTING SOILS

COMPACTED EXISTING SOILS

TOP OF FOOTING

4'-0" A.F.G.

TOP OF CONCRETE

0'-4" A.F.G.

(2) #4 CONT.

1'-6"

2'- 2"

4"

4" INTERIOR SLAB ON GRADE

2" MIN.

2" M

IN

#4 @ 9" O.C.

1'-

1'-2"

(4) #4 CONT. TOP AND BOTTOM

COMPACTED EXISTING SOILS

TOP OF FOOTING

4" A.F.G.

(2) #4 CONT.

12" EXPANSION MATERIAL

SCALE:

FOUNDATION DETAIL

1-1/2" = 1'-0"

S101

SCALE:

FOUNDATION DETAIL

1-1/2" = 1'-0"

S101

4" SLAB ON GRADE

GREENHOUSE STRUCTURE

GREENHOUSE STRUCTURE

2'- 2"

4"

4" COMPACTED

CRUSHED STONE

2" MIN.

2" M

IN

#4 @ 9" O.C.

1'-

1'-2"

(4) #4 CONT. TOP AND BOTTOM

1" CHAMFER

COMPACTED EXISTING SOILS

TOP OF FOOTING

4" A.F.G.

(2) #4 CONT.

GREENHOUSE STRUCTURE

4"

5"5"

GREENHOUSE STRUCTURE

1'-6"

BASE BID ONLY BASE BID AND BID OPTION #2

2'- 2"

4"

4" COMPACTED

CRUSHED STONE

2" MIN.

2" M

IN

#4 @ 9" O.C.

1'-

1'-2"

1" CHAMFER

COMPACTED EXISTING SOILS

TOP OF FOOTING

4" A.F.G.

(2) #4 CONT.

GREENHOUSE STRUCTURE

5"

1'-6"

SCALE:

FOUNDATION DETAIL

1-1/2" = 1'-0"

S101

1" CHAMFER

1'-6"

2'- 2"

4"

4" INTERIOR SLAB ON GRADE

2" MIN.

2" M

IN

#4 @ 9" O.C.

1'-

1'-2"

(4) #4 CONT. TOP AND BOTTOM

COMPACTED EXISTING SOILS

(2) #4 CONT.

12" EXPANSION MATERIAL

GREENHOUSE STRUCTURE

TOP OF FOOTING

4" A.F.G.

TOP OF SLAB

AT GRADE

5'-3"

6" x 6" x 4.0 W.W.M. CONT. 4" SLAB ON GRADE

TOP OF SLAB

4" A.F.G.

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

P.A.

FIRMTHE

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

c

USDA AGRICULTURAL RESEARCH SERVICE

BLUEBERRY AND CRANBERRY RESEARCH CENTER

ADDITION TO CRANBERRY BREEDING AND GENETICS GREENHOUSE

CHATSWORTH, NEW JERSEY

FOUNDATION DETAILS

S101 4 1803/08/24

REH

REH

FEJ

10300 BALTIMORE AVE.

BELTSVILLE, MD 20705

XXX

6223-A

XXX

XXX

XXX

XXX

SCALE: 1 1/2"=1'-0"

0 6" 1' 2'

30" 30"

30"

30" jferguson Stamp

Wayne.Shekailo Line

Wayne.Shekailo Line

Wayne.Shekailo Line

Wayne.Shekailo Line

Wayne.Shekailo Line

Wayne.Shekailo Line

Wayne.Shekailo Line

Wayne.Shekailo Line

Wayne.Shekailo Line

Wayne.Shekailo Line

Wayne.Shekailo Line

Wayne.Shekailo Line

'-4

1/ 2"

6'

EXHAUST FAN

SEE MECHANICAL

EXHAUST FAN

SEE MECHANICAL

3'- 6"

CIRCULATOR FAN

HEAT DUCTS SEE MECHANICAL

HEAT DUCTS SEE MECHANICAL

LOUVER ABOVE PADS.

SEE MECHANICAL

VENT SYSTEM

BID OPTION #1

VENT CONTROL. PROVIDE

ANCHORING / FOOTING PER

MANUFACTURERS

RECOMMENDATIONS.A200

A200

DOOR BY GREENHOUSE

MANUFACTURER

A300

4" CONCRETE PAD SLOPED

FROM FINISH WALKWAY

ELEVATION TO FINISHED

GRADE

5'-3"

6' 4" REINFORCED CONCRETE WALKWAY

CIRCULATOR FAN

CIRCULATOR FAN CIRCULATOR FAN

3'- 6"

DOOR BY GREENHOUSE

MANUFACTURER

BID OPTION #1:

EVAPORATIVE COOLING PAD SYSTEM

HEATER SEE MECHANICAL

HEATER SEE MECHANICAL ALUMINUM FRAMING SYSTEM

6 MIL. ANTI-CONDENSATE, UV RESISTANT PLASTIC SHEETING AS SPECIFIED.

4'

6'-10"

5'-3"

6'

4" CONCRETE PAD SLOPED

FROM FINISH WALKWAY

ELEVATION TO FINISHED

GRADE

' B

AS

E

BI

D

'-4

1/ 2"

6'

EXHAUST FAN

SEE MECHANICAL

EXHAUST FAN

SEE MECHANICAL

3'- 6"

CIRCULATOR FAN

HEAT DUCTS SEE MECHANICAL

HEAT DUCTS SEE MECHANICAL

LOUVER ABOVE PADS.

SEE MECHANICAL

VENT SYSTEM

BID OPTION #3

VENT CONTROL. PROVIDE

ANCHORING / FOOTING PER

MANUFACTURERS

RECOMMENDATIONS.

DOOR BY GREENHOUSE

MANUFACTURER

4" CONCRETE PAD SLOPED

FROM FINISH WALKWAY

ELEVATION TO FINISHED

GRADE

5'-3"

6' 4" REINFORCED CONCRETE WALKWAY

CIRCULATOR FAN

CIRCULATOR FAN CIRCULATOR FAN

3'- 6"

DOOR BY GREENHOUSE

MANUFACTURER

BID OPTION #1:

EVAPORATIVE COOLING PAD SYSTEM

HEATER SEE MECHANICAL ALUMINUM FRAMING SYSTEM

6 MIL. ANTI-CONDENSATE, UV RESISTANT PLASTIC SHEETING AS SPECIFIED.

4'

6'-10"

5'-3"

6'

4" CONCRETE PAD SLOPED

FROM FINISH WALKWAY

ELEVATION TO FINISHED

GRADE

' B

ID

O

PT

IO

N #2

100'

100'

A200

A200

1 SIM.

GREENHOUSE #1

BASE BID

GREENHOUSE #2

BID OPTION #2

HEATER SEE MECHANICAL

POLYCARBONATE

END PANELS (TYP.)

SEE ELEVATIONS

POLYCARBONATE

END PANELS (TYP.)

SEE ELEVATIONS

F

INFLATION FAN SEE DETAIL 4/A200

AND ELECTRICAL DRAWINGS.

F

INFLATION FAN SEE DETAIL 4/A200

AND ELECTRICAL DRAWINGS.

BASE BID

BID OPTION #2

SCALE:

FLOOR PLAN

1/4" = 1'-0"

A100

8'0 2' 4' 12'

SCALE: 1/4"= 1'-0"

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

P.A.

FIRMTHE

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

c

USDA AGRICULTURAL RESEARCH SERVICE

BLUEBERRY AND CRANBERRY RESEARCH CENTER

ADDITION TO CRANBERRY BREEDING AND GENETICS GREENHOUSE

CHATSWORTH, NEW JERSEY

FLOOR PLAN

A100 5 1803/08/24

REH

REH

FEJ

10300 BALTIMORE AVE.

BELTSVILLE, MD 20705

XXX

6223-A

XXX

XXX

XXX

XXX

TRUE

NORTH

N.I.C.

WINDJAMMER 6000 WILL HAVE RIGID POLYCARBONATE WALLS

jferguson Stamp

Wayne.Shekailo Line

Wayne.Shekailo Line

Wayne.Shekailo Rectangle

SCALE:

SOUTH ELEVATION (TRUE NORTH)

1/4" = 1'-0"

A200

SCALE:

NORTH ELEVATION (TRUE NORTH)

1/4" = 1'-0"

A200

3' - 6" X 7' - 0" DOOR

EXHAUST FAN

SEE MECHANICAL

EXHAUST FAN

SEE MECHANICAL

VENT SYSTEM BY

GREENHOUSE

MANUFACTURER

BID OPTION #1

SCALE:

EAST ELEVATION (TRUE NORTH)

WEST ELEVATION (TRUE NORTH) MIRROR

1/4" = 1'-0"

A200

FINISHED GRADE

FOUNDATION. SEE S100

FOUNDATION. SEE S100

SHADE CLOTH AS SPECIFIED PROVIDE MANUFACTURERS

STANDARD ANCHORING SYSTEM

VENT CONTROL. PROVIDE

ANCHORING / FOOTING PER

MANUFACTURERS

RECOMMENDATIONS. SEE

BID OPTION #1 AND #3.

FURNACE VENT

EXHAUST FAN

FOUNDATION. SEE S100

FINISHED GRADE

ALUMINUM FRAMING SYSTEM. 6 MIL. DOUBLE WALL INFLATED ANTI-CONDENSATE,

UV RESISTANT PLASTIC SHEETING AS SPECIFIED.

8 MM. DOUBLE WALL POLYCARBONATE PANELS

FURNACE VENT

FINISHED GRADE

FOUNDATION. SEE S100

8 MM. DOUBLE WALL POLYCARBONATE PANELS

FINISHED GRADE

3' - 6" X 7' - 0" DOOREXHAUST FAN

SEE MECHANICAL

FINISHED GRADE

FOUNDATION. SEE S100

8 MM. DOUBLE WALL

POLYCARBONATE PANELSFURNACE VENT

VENT SYSTEM BY

GREENHOUSE

MANUFACTURER

BID OPTION #3

GREENHOUSE #2

BID OPTION #2 GREENHOUSE #1

BASE BID

GREENHOUSE #1

BASE BID

GREENHOUSE #2

BID OPTION #2

8'0 2' 4' 12'

SCALE: 1/4"= 1'-0"

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

P.A.

FIRMTHE

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

c

USDA AGRICULTURAL RESEARCH SERVICE

BLUEBERRY AND CRANBERRY RESEARCH CENTER

ADDITION TO CRANBERRY BREEDING AND GENETICS GREENHOUSE

CHATSWORTH, NEW JERSEY

ELEVATIONS

A200 6 1803/08/24

REH

REH

FEJ

10300 BALTIMORE AVE.

BELTSVILLE, MD 20705

XXX

6223-A

XXX

XXX

XXX

XXX

(2) AIR TRANSFER GASKETS

6 MIL. DOUBLE WALL

INFLATED ANTI-CONDENSATE,

UV RESISTANT PLASTIC

SHEETING AS SPECIFIED.

INFLATION MOUNT

STOP TAB

ROLL-FORM RAIL

GREENHOUSE END WALL 516" HEX NUT

AND WASHER

INFLATION FAN WITH AIR INLET DAMPER (ADJUSTABLE

FOR DESIRED ROOF / WALL TENSION)

SHALL INCLUDE:

(1) 60 CFM INFLATION BLOWER

(1) MOUNTING BRACKET

(1) PVC PLUG

(1) 4" HOSE CLAMP

(1) 3" x 5' FLEX TUBING

(2) AIR TRANSFER GASKETS

MOUNTING HARDWARE

NOTES:

1. INSTALL INFLATION MOUNT FIRMLY TO GREENHOUSE END WALL MEMBER.

2. PLACE (1) AIR TRANSFER GASKET ON THE 6 MIL. DOUBLE WALL ANTI-CONDENSATE, UV RESISTANT PLASTIC SHEETING TO BE INFLATED. CUT OUT THE SHEET

(ONE LAYER OF SHEETING ONLY) FROM THE GASKET TO ALLOW AIR TO PASS.

3. PLACE SECOND AIR TRANSFER GASKET ON THE INSIDE OF THE SHEETING. BE SURE TO ALIGN THE 2 GASKETS PRIOR TO PRESSING THE TWO TOGETHER. ST

THE TWO GASKETS TOGETHER USING AN ORDINARY OFFICE STAPLER.

4. INSERT THE 3"x5' FLEX TUBING THROUGH THE AIR TRANSFER GASKETS. ENSURE APPROXIMATELY 1" OF THE FLEX TUBING PASSES THROUGH THE GASKETS

ENSURE A TIGHT SEAL.MAKE SURE NO SHARP EDGES ARE EXPOSED TO PUNCTURE OUTER LAYER OF SHEETING.

SCALE:

SHEETING INFLATION KIT DETAIL

N.T.S.

A200

N.I.C.

N.I.C.

ELEVATION MAY CHANGE WITH WINDJAMMER 6000 MODEL

ELEVATION MAY CHANGE WITH WINDJAMMER 6000

MODEL

WINDJAMMER 6000 WILL HAVE RIGID POLYCARBONATE WALLS

N.I.C.

jferguson Stamp

Wayne.Shekailo Rectangle

Wayne.Shekailo Line

Wayne.Shekailo Line

Wayne.Shekailo Rectangle

Wayne.Shekailo Line

Wayne.Shekailo Rectangle

Wayne.Shekailo Line

Wayne.Shekailo Rectangle

GREENHOUSE STRUCTURE

BASIS OF DESIGN:

WINDJAMMER 5000 PROSPIANT

6'

4" THICK CONCRETE WALK WAY

SEE STRUCTURAL

4" COMPACTED

CRUSHED STONE

A300

FINISH GRADE

0'-0"

T. O. FOOTING

1'-0" A.F.G.

COMPACTED EXISTING SOILS

GREENHOUSE STRUCTURE

BASIS OF DESIGN:

WINDJAMMER 5000 PROSPIANT

6'4" THICK CONCRETE WALK WAY

SEE STRUCTURAL

PERIMETER FOOTING SEE STRUCTURAL

4" COMPACTED

CRUSHED STONE

COMPACTED EXISTING SOILS

GREENHOUSE #1

BASE BID GREENHOUSE #2

BID OPTION #2

GUTTER

14 GA.

GALVANIZED

GUTTER

GREENHOUSE

FRAMING

6 MIL. DOUBLE WALL

ANTI-CONDENSATE, UV RESISTANT

PLASTIC SHEETING AS SPECIFIED.

7'- 0"

TO

C

EN

TE

R

OF

B

EN

D

NEOPRENE GASKET

SELF DRILLING SCREW

WITH GASKET

WASHERS

A300

1'

GREENHOUSE STRUCTURE RECEPTOR

(2) 5 8" X 5" BOLTS PER COLUMN

(2) 5 8"x5" STAINLESS STEEL EXPANSION

ANCHORS PER RECEPTOR

PERIMETER FOOTING SEE STRUCTURAL

GREENHOUSE STRUCTURE BASIS

OF DESIGN: WINDJAMMER 5000

PROSPIANT

9"COMPACTED EXISTING SOILS

EXISTING SOILS

4" CRUSHED STONE

1'

GREENHOUSE STRUCTURE RECEPTOR

(2) 5 8" X 5" BOLTS PER COLUMN

(2) 5 8"x5" STAINLESS STEEL EXPANSION

ANCHORS PER RECEPTOR

PERIMETER FOOTING

SEE STRUCTURAL

GREENHOUSE STRUCTURE BASIS

OF DESIGN: WINDJAMMER 5000

PROSPIANT

COMPACTED

EXISTING

SOILS

#30 FELT UNDER BASE PLATE

SECTION ELEVATION

10 1/2"

#30 FELT UNDER BASE PLATE

1'

GREENHOUSE STRUCTURE RECEPTOR

(2) 5 8" X 5" BOLTS PER COLUMN

(2) 5 8"x5" STAINLESS STEEL EXPANSION

ANCHORS PER RECEPTOR

PERIMETER FOOTING SEE STRUCTURAL

GREENHOUSE STRUCTURE BASIS

OF DESIGN: WINDJAMMER 5000

PROSPIANT

9"COMPACTED EXISTING SOILS

4" CRUSHED STONE

#30 FELT UNDER BASE PLATE

BASE BID BASE BID AND BID OPTION #2

1'

GREENHOUSE STRUCTURE RECEPTOR

(2) 5 8" X 5" BOLTS PER COLUMN

(2) 5 8"x5" STAINLESS STEEL EXPANSION

ANCHORS PER RECEPTOR

PERIMETER FOOTING SEE STRUCTURAL

GREENHOUSE STRUCTURE BASIS

OF DESIGN: WINDJAMMER 5000

PROSPIANT

9"COMPACTED EXISTING SOILS

4" CRUSHED STONE

#30 FELT UNDER BASE PLATE

SCALE:

GREENHOUSE SECTION

1/2" = 1'-0"

A300

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

P.A.

FIRMTHE

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

c

USDA AGRICULTURAL RESEARCH SERVICE

BLUEBERRY AND CRANBERRY RESEARCH CENTER

ADDITION TO CRANBERRY BREEDING AND GENETICS GREENHOUSE

CHATSWORTH, NEW JERSEY

GREENHOUSE SECTION

A300 7 1803/08/24

REH

REH

FEJ

10300 BALTIMORE AVE.

BELTSVILLE, MD 20705

XXX

6223-A

XXX

XXX

XXX

XXX

4'

SCALE: 1/2"=1'-0"

0 1' 2' 8'

SCALE:

RECEPTOR DETAIL

1-1/2" = 1'-0"

A300 SCALE:

RECEPTOR DETAIL

1-1/2" = 1'-0"

A300

SCALE: 1 1/2"=1'-0"

0 6" 1' 2'

N.I.C.

N.I.C.

SECTION MAY CHANGE WITH WINDJAMMER 6000 MODEL

jferguson Stamp

Wayne.Shekailo Rectangle

Wayne.Shekailo Line

Wayne.Shekailo Rectangle

Wayne.Shekailo Line

Wayne.Shekailo Rectangle

Wayne.Shekailo Line

Wayne.Shekailo Line

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

P.A.

FIRMTHE

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

c

USDA AGRICULTURAL RESEARCH SERVICE

BLUEBERRY AND CRANBERRY RESEARCH CENTER

ADDITION TO CRANBERRY BREEDING AND GENETICS GREENHOUSE

CHATSWORTH, NEW JERSEY

MECHANICAL

NOTES AND ABBREVIATIONS

M001 8 1803/08/24

REH

DTC

FEJ

10300 BALTIMORE AVE.

BELTSVILLE, MD 20705

XXX

6223-A

XXX

XXX

XXX

XXX

1. INSTALLATION OF HVAC WORK SHALL BE COORDINATED WITH OTHER TRADES BEFORE ANY INSTALLATION IS DONE. DUCTWORK SHOWN

ON PLANS IS SCHEMATIC.

2. COORDINATE MECHANICAL AND ELECTRICAL SUCH THAT MECHANICAL PIPING, DUCTWORK AND EQUIPMENT IS NOT LOCATED OVER OR

ABOVE ANY ELECTRICAL.

3. AT START OF CONSTRUCTION, PREPARE TYPED LISTS OF EQUIPMENT THAT ARE SUPPLIED REQUIRING ELECTRICAL WORK AND SEND LISTS

TO THE ELECTRICAL CONTRACTOR FOR REVIEW AND COORDINATION.

4. EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S APPROVED CLEARANCE, AND INTERNATIONAL BUILDING CODE

/ INTERNATIONAL MECHANICAL CODE.

5. INSTALLATION OF EQUIPMENT SHALL PERMIT ACCESSIBILITY FOR SERVICE AND/OR REPLACEMENT WITHOUT NECESSITATING REMOVAL

OR MODIFICATION TO OTHER PIPING, WIRING, OR EQUIPMENT.

6. COORDINATE WALL, FLOOR AND ROOF PENETRATIONS WITH THE GENERAL CONTRACTOR.

7. SUPPLEMENTAL STEEL MEMBERS REQUIRED TO SUPPORT HVAC EQUIPMENT FROM MAIN STRUCTURE SHALL BE PROVIDED BY THE HVAC

CONTRACTOR UNLESS SPECIFICALLY NOTED OTHERWISE.

8. EXACT LOCATIONS OF THERMOSTATS, CO2 SENSORS, AND SENSORS SHALL BE COORDINATED WITH FINAL LOCATIONS OF WALL-MOUNTED ARCHITECTURAL AND ELECTRICAL EQUIPMENT. MOUNT THERMOSTATS AND CO2 SENSORS MINIMUM 48" AFF.

9. PROVIDE HOUSEKEEPING PADS FOR MECHANICAL EQUIPMENT.

10. INSTALL EXPOSED CONTROL WIRING IN CONDUIT. SEE DIVISION ELECTRICAL FOR REQUIREMENTS.

11. MANUFACTURER NAME AND MODEL NUMBERS ARE BASIS OF DESIGN AND ARE SHOWN FOR INFORMATION ONLY. REFER TO

SPECIFICATIONS FOR COMPLETE REQUIREMENTS.

12. PIPING INSULATION SHALL BE PROVIDED ON ALL PIPING SYSTEMS.

13. FURNACE VENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER INSTALLATION INSTRUCTIONS.

14. SPECIFICATIONS TAKE PRECEDENCE OVER DRAWINGS. HOWEVER, ITEMS SHOWN ON DRAWING BUT NOT IN THE SPECIFICATIONS ARE REQUIRED WITHIN THE PROJECT SCOPE. IN ADDITION, SPECIFIC ITEMS SHOWN ON THE DRAWINGS TAKE PRECEDENCE OVER

SPECIFICATIONS IN CASES WHERE THE SPECIFICATION HAS OPTIONS.

15. ALL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S APPROVED PUBLISHED LITERATURE.

16. ALL EQUIPMENT INSTALLED IN THIS PROJECT SHALL COMPLY WITH THE "BUY AMERICAN ACT". BASIS OF DESIGN SHOWN ON SCHEDULES IS TO ESTABLISH A STANDARD OF QUALITY, NOT TO LIMIT COMPETITION. EQUIVALENT EQUIPMENT FROM

ANOTHER MANUFACTURER IS ACCEPTABLE.

GENERAL PROJECT NOTES:ABBREVIATIONS:

@ AT

& ND

AHU AIR HANDLING UNIT

ARCH ARCHITECT, ARCHITECTURAL

AS AIR SEPARATOR

ASHRAE AMERICAN SOCIETY OF HEATING, REFRIGERATING,

AND AIR CONDITIONING ENGINEERS

ASTM AMERICAN SOCIETY FOR TESTING AND

MATERIALS

BDD BACKDRAFT DAMPER

BLDG BUILDING

BTU, BTUH BRITISH THERMAL UNITS, BTUs PER HOUR

CD CONDENSATE DRAIN

CFM CUBIC FEET PER MINUTE

CHWR CHILLED WATER RETURN

CHWS CHILLED WATER SUPPLY

CLG COOLING

CMU CONCRETE MASONRY UNIT

CO CLEANOUT

CO2 CARBON DIOXIDE

CONC CONCRETE

CONN CONNECT, CONNECTING, CONNECTION

CONT CONTINUED

COP COEFFICIENT OF PERFORMANCE

COR CONTRACTING OFFICER'S (OWNER'S)

REPRESENTATIVE

CT COOLING TOWER

CU CONDENSING UNIT

CWR CONDENSER WATER RETURN

CWS CONDENSER WATER SUPPLY

D DEPTH

DB, Tdb DRY BULB (TEMPERATURE) dBA DECIBELS

DCW DOMESTIC COLD WATER

DDC DIRECT DIGITAL CONTROLS

DEG. F (°F) DEGREES FAHRENHEIT

DF DESTRATIFICATION FAN

DFCU DUCTLESS FAN COIL UNIT

DH DEHUMIDIFIER

DIA, Ø DIAMETER

DIV DIVISION

DN DOWN

DP, PD DIFFERENTIAL PRESSURE, PRESSURE DROP

DSCU DUCTLESS SPLIT CONDENSING UNIT

DSHP DUCTLESS SPLIT HEAT PUMP

DWG DRAWING

DX DIRECT EXPANSION

EA EXHAUST AIR

EAG EXHAUST AIR GRILLE

EAT ENTERING AIR TEMPERATURE

EER ENERGY EFFICIENCY RATIO

EF EXHAUST FAN

EFF EFFICIENCY

ELEC ELECTRICAL

EMCS ENERGY MONITORING AND CONTROLS SYSTEM

ERU ENERGY RECOVERY UNIT

ERV ENERGY RECOVERY VENTILATOR

ET EXPANSION TANK

ESP EXTERNAL STATIC PRESSURE

EUH ELECTRIC UNIT HEATER

EWT ENTERING WATER TEMPERATURE

EXT EXTERIOR

EXH EXHAUST

EXST, (E) EXISTING

FCU FAN COIL UNIT

FD FIRE DAMPER

FFE FINISHED FLOOR ELEVATION

FLA FULL LOAD AMPS

FOB FLAT ON BOTTOM

FOT FLAT ON TOP

FPM FEET PER MINUTE

FSD FIRE SMOKE DAMPER

FT FOOT, FEET

FT WG FEET WATER GAUGE

FV FLUE VENT

GA GAGE

GC GENERAL CONTRACTOR

GPM GALLONS PER MINUTE

GWH GAS WATER HEATER

H HEIGHT

HR HOUR

HTG HEATING

HTR HEATER

HTW HEATING WATER

HVAC HEATING, VENTILATING, AND AIR CONDITIONING

HWR HEATING WATER RETURN

HWS HEATING WATER SUPPLY

HX HEAT EXCHANGER

HZ HERTZ

IMC INTERNATIONAL MECHANICAL CODE

IN INCH, INCHES

IN WC INCHES WATER COLUMN

IN WG INCHES WATER GAUGE

IPLV INTEGRATED PART LOAD VALUE

KW KILOWATTS

L LENGTH, LOUVER (WALL)

LAT LEAVING AIR TEMPERATURE

LBD LINEAR BAR DIFFUSER

LBS POUNDS

LWT LEAVING WATER TEMPERATURE

MAX MAXIMUM

MBH 1000 BRITISH THERMAL UNITS

MCA MINIMUM CIRCUIT AMPACITY

MERV MINIMUM EFFICIENCY REPORTING VALUE

MECH MECHANICAL

MFCR, MFCG MANUFACTURER, MANUFACTURING

MIN MINIMUM

MOCP, MOP MAXIMUM OVER CURRENT PROTECTION

MTWR MEDIUM TEMPERATURE WATER RETURN

MTWS MEDIUM TEMPERATURE WATER SUPPLY

NG NATURAL GAS

NC NOISE CRITERIA

N.C. NORMALLY CLOSED

NO. NUMBER

N.O. NORMALLY OPEN

NTS NOT TO SCALE

OA OUTSIDE AIR

OD OUTSIDE DAMPER

PD PRESSURE DROP

PH PHASE

PLBG PLUMBING

PPM PARTS PER MILLION

PRV PRESSURE RELIEF VALVE

PSI POUNDS PER SQUARE INCH

PCHWR PLANT CHILLED WATER RETURN

PCHWS PLANT CHILLED WATER SUPPLY

PMTWR PLANT MEDIUM TEMPERATURE WATER RETURN

PMTWS PLANT MEDIUM TEMPERATURE WATER SUPPLY

QTY QUANTITY

RA RETURN AIR

RAG RETURN AIR GRILLE

RH RELATIVE HUMIDITY, ROOF HOOD

RM ROOM

RPM REVOLUTIONS PER MINUTE

SA SUPPLY AIR

SAD SUPPLY AIR DIFFUSER

SAG SUPPLY AIR GRILLE

SD SMOKE DAMPER, SMOKE DETECTOR

SEER SEASONAL ENERGY EFFICIENCY RATIO

SF SUPPLY FAN

SMACNA SHEET METAL AND AIR CONDITIONING

CONTRACTOR'S NATIONAL ASSOCIATION

SP STATIC PRESSURE

SS STAINLESS STEEL

TSTAT THERMOSTAT

TEMP TEMPERATURE

TYP TYPICAL

UH UNIT HEATER

UL UNDERWRITER'S LABORATORY

UMCS UTILITY MONITORING AND CONTROL SYSTEM

V VOLTAGE, VOLTS

VAV VARIABLE AIR VOLUME

VD VOLUME DAMPER

VFD VARIABLE FREQUENCY DRIVE

VRF VARIABLE REFRIGERANT FLOW

WB, Twb WET BULB (TEMPERATURE)

SUMP PUMP

P

SYMBOLS

SUMP PUMP

EF-1

EF-1

POLY-TUBING DUCT

INSTALLED AT GRADE

POLY-TUBING DUCT

INSTALLED AT GRADE

VENT SYSTEM

VENT CONTROLCF-1

CF-1

M200

M200

BID OPTION #1:

ECP-1

F-1

F-1

CF-1 CONTROLLER

F-1 VENT

(TYP. 2)

F-1 VENT

(TYP. 2)

1" PVC BELOW

GRADE

2,000 GALLON PROPANE TANK. (NOT IN CONTRACT. SHALL BE

PROVIDED AND INSTALLED BY GOVERNMENT)

1" SCHEDULE 40 BLACK CARBON STEEL PIPE. (NOT IN CONTRACT.

SHALL BE PROVIDED AND INSTALLED BY GOVERNMENT)

1" SCHEDULE 40 BLACK CARBON STEEL PIPE. (NOT IN

CONTRACT. SHALL BE PROVIDED AND INSTALLED BY

GOVERNMENT)

1" DCW BELOW GRADE

SEE C100 FOR

CONTINUATION

CF-1 3

CF-13

KEYED NOTES:

1. PROVIDE PROPANE FIRED FURNACE. PROVIDE HOUSEKEEPING PAD

BENEATH FURNACE. SEE DETAIL 2/M600.

2. PROVIDE VENT FOR PROPANE FIRED FURNACE AND INSTALL IN

ACCORDANCE WITH FURNACE AND GREENHOUSE MANUFACTURER'S

INSTALLATION INSTRUCTIONS.

3. PROVIDE SUSPENDED CIRCULATOR FANS. FANS SHALL ALL BE

CONTROLLED BY A SINGLE CONTROLLER.

4. PROVIDE NEW WALL MOUNTED EXHAUST FAN. FAN SHALL BE

INTERLOCKED WITH GREENHOUSE MFG PROVIDED VENT.

5. PROVIDE FREEZE PROOF FAUCET IN ACCORDANCE WITH

SPECIFICATIONS.

6. EF-1 SHALL BE INTERLOCKED WITH VENT SYSTEM SO THAT EF-1 IS NOT

ENABLED UNTIL VENT IS IN THE FULLY OPEN POSITION.

7. SIZE POLY-DUCT TO MATCH HEATER OUTLET OPENING DIAMETER.

1" DCW UP FOR ECP-1

MAKEUP WATER

GREENHOUSE CONTROLLER

1" PVC BELOW

GRADE

1" PVC BELOW

GRADE (TYP. 4)

P

PECP-1 SUMP PUMP

(TYP.2)

EF-1

EF-1

POLY-TUBING DUCT

INSTALLED AT GRADE

POLY-TUBING DUCT

INSTALLED AT GRADE

VENT SYSTEM

VENT CONTROL

CF-1

CF-1

BID OPTION #1:

ECP-1

F-1

F-1

CF-1 CONTROLLER

F-1 VENT

(TYP. 2)

F-1 VENT

(TYP. 2)

1" PVC BELOW

GRADE5

1" SCHEDULE 40 BLACK CARBON STEEL PIPE. (NOT IN CONTRACT

SHALL BE PROVIDED AND INSTALLED BY GOVERNMENT)

1" DCW BELOW GRADE

SEE C100 FOR

CONTINUATION

CF-1 3

CF-13

1" DCW UP FOR ECP-1

MAKEUP WATER

GREENHOUSE CONTROLLER

1" PVC BELOW

GRADE

1" PVC BELOW

GRADE (TYP. 4)

P

P

ECP-1 SUMP PUMP

(TYP.2)

M200

M200

1 SIM.

1-1/2" SCHEDULE 40 BLACK CARBON STEEL PIPE. (NOT IN CONTRACT

SHALL BE PROVIDED AND INSTALLED BY GOVERNMENT)

1-1/2" SCHEDULE 40 BLACK CARBON STEEL PIPE. (NOT IN CONTRACT.

SHALL BE PROVIDED AND INSTALLED BY GOVERNMENT)

COORDINATE BOLLARD LOCATIONS WITH GOVERNMENT (SEE C100)

GREENHOUSE #1

BASE BID

GREENHOUSE #2

BID OPTION #2

BASE BID

BID OPTION #2

BID OPTION #3

COOLING PAD SYSTEM

FOR GREENHOUSE #2

BID OPTION #1

COOLING PAD SYSTEM

FOR GREENHOUSE #1

SCALE:

FLOOR PLAN

3/16" = 1'-0"

M100

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

P.A.

FIRMTHE

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

c

USDA AGRICULTURAL RESEARCH SERVICE

BLUEBERRY AND CRANBERRY RESEARCH CENTER

ADDITION TO CRANBERRY BREEDING AND GENETICS GREENHOUSE

CHATSWORTH, NEW JERSEY

MECHANICAL FLOOR PLAN

M100 9 1803/08/24

REH

DTC

FEJ

10300 BALTIMORE AVE.

BELTSVILLE, MD 20705

XXX

6223-A

XXX

XXX

XXX

XXX

0 4' 8' 16'

SCALE: 3/16"= 1'-0"

2'

PLAN

NORTH

TRUE

NORTH

N.I.C.

PROPANE LOCATION REMAINS UNCHANGED

jferguson Stamp

Wayne.Shekailo Rectangle

Wayne.Shekailo Line

Rectangle

KEYED NOTES:

1. PROVIDE VENT FOR PROPANE FIRED FURNACE AND INSTALL IN

ACCORDANCE WITH FURNACE AND GREENHOUSE MANUFACTURER'S

INSTALLATION INSTRUCTIONS.

2. PROVIDE NEW WALL MOUNTED EXHAUST FAN. FAN SHALL BE

INTERLOCKED WITH GREENHOUSE MFG PROVIDED VENT.

3. EF-1 SHALL BE INTERLOCKED WITH VENT SYSTEM SO THAT EF-1 IS NOT

ENABLED UNTIL VENT IS IN THE FULLY OPEN POSITION.

FINISHED GRADE

ECP-1

EF-1

EF-1

FINISHED GRADE

F-1 VENT1 F-1 VENT1

EF-12

F-1 VENT1

F-1 VENT1

EF-1 2

F-1 VENT

(TYP.2)

EF-1

FINISHED GRADE

ECP-1

GREENHOUSE #2

BID OPTION #2 GREENHOUSE #1

BASE BID

GREENHOUSE #1

BASE BID

GREENHOUSE #2

BID OPTION #2VENT SYSTEM BY

GREENHOUSE

MANUFACTURER

BID OPTION #1

VENT SYSTEM BY

GREENHOUSE

MANUFACTURER

BID OPTION #3

VENT CONTROL. PROVIDE

ANCHORING / FOOTING PER

MANUFACTURERS

RECOMMENDATIONS. SEE

BID OPTION #1 AND #3.

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

P.A.

FIRMTHE

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

c

USDA AGRICULTURAL RESEARCH SERVICE

BLUEBERRY AND CRANBERRY RESEARCH CENTER

ADDITION TO CRANBERRY BREEDING AND GENETICS GREENHOUSE

CHATSWORTH, NEW JERSEY

MECHANICAL ELEVATIONS

M200 10 1803/08/24

REH

DTC

FEJ

10300 BALTIMORE AVE.

BELTSVILLE, MD 20705

XXX

6223-A

XXX

XXX

XXX

XXX

SCALE:

SOUTH ELEVATION

1/4" = 1'-0"

M100

SCALE:

NORTH ELEVATION

1/4" = 1'-0"

M100

SCALE:

EAST ELEVATION

WEST ELEVATION MIRROR

1/4" = 1'-0"

M100

8'0 2' 4' 12'

SCALE: 1/4"= 1'-0"

N.I.C.

N.I.C.

WINDJAMMER 6000

ELEVATION MAY BE

DIFFERENT

WINDJAMMER 6000 ELEVATION

MAY BE DIFFERENT

jferguson Stamp

Wayne.Shekailo Rectangle

Wayne.Shekailo Line

Wayne.Shekailo Line

Wayne.Shekailo Rectangle

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

P.A.

FIRMTHE

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

c

USDA AGRICULTURAL RESEARCH SERVICE

BLUEBERRY AND CRANBERRY RESEARCH CENTER

ADDITION TO CRANBERRY BREEDING AND GENETICS GREENHOUSE

CHATSWORTH, NEW JERSEY

MECHANICAL

SCHEDULE AND DETAILS

M600 11 1803/08/24

REH

DTC

FEJ

10300 BALTIMORE AVE.

BELTSVILLE, MD 20705

XXX

6223-A

XXX

XXX

XXX

XXX

EVAPORATIVE COOLING PAD(BID OPTION #1 AND #3)

HEIGHT

(FT)

LENGTH

(FT)

BASIS OF DESIGNMODEL MEDIA

THICKNESS REMARKS

ECH600

NOTES:

1. PROVIDE MAKE-UP WATER AS RECOMMENDED BY MANUFACTURER TO EACH COOLING WALL.

2. PROVIDE WITH SUBMERSIBLE PUMP BY COOLING CELL MANUFACTURER, SIZED FOR COOLING CELL PRESSURE LOOP. PROVIDE A PUMP

FOR EACH COOLING WALL. SELECTED PUMPS SHALL NOT EXCEED 1 HP. COOLING CELL SHALL HAVE CELLULOSE-TYPE PADS. GPM & AIRFLOW VALUES SHOWN ARE APPROXIMATE. ACTUAL VALUES SHALL BE BASED ON MANUFACTURER'S RECOMMENDATIONS FOR SIZE

AND THICKNESS OF PADS.

3. PROVIDE COOLING WALLS WITH BOTTOM TROUGH TO DRAIN BACK TO SUMP TANK.

4. PROVIDE 2-WAY CONTROL VALVE FOR EACH COOLING WALL TO INTERFACE WITH GREENHOUSE CONTROL SYSTEM.

5. EVAPORATIVE COOLING PADS SHALL OPERATE BASED ON GREENHOUSE CONTROLLER SET POINT.

J & D MANUFACTURING 20 6 6"

AIRFLOW

(CFM)

E.S.P.

(IN W.G.)

NOTES:

1. PROVIDE WITH ALUMINUM CONSTRUCTION AND SLANT WALL HOUSING.

2. FAN SHALL BE RATED FOR GREENHOUSE APPLICATIONS.

3. PROVIDE WITH ALUMINUM BACKDRAFT SHUTTER AND INSECT SCREEN.

4. FANS SHALL BE TWO SPEED.

5. FANS SHALL OPERATE BASED ON GREENHOUSE CONTROLLER SET POINT.

EF-1 ACME OR EQUAL DCA24H-B SLANT WALL HOUSING 6336 949 0.15" 6.3 3/4 115/208/230 60 SEE NOTES

GREENHOUSE FAN SCHEDULE

MANUFACTURER MODEL TYPE

AIRFLOW

(CFM)

FAN

SIZE

NOTES:

1. FAN SHALL BE RATED FOR GREENHOUSE APPLICATIONS.

2. PROVIDE FAN WITH VARIABLE SPEED CONTROLLER INDEPENDENT OF GREENHOUSE CONTROLLER.

CF-1 ACME OR EQUAL HAF20A4 HORIZONTAL AIR FLOW 3,005 1626 20" 60 1/15 115/1 105.0 SEE NOTES

CIRCULATOR FAN SCHEDULE

MANUFACTURER MODEL TYPE

NOTES:

1. FURNACES SHALL OPERATE BASED ON GREENHOUSE CONTROLLER SET POINT.

2. PROVIDE WITH A CARBON MONOXIDE SENSOR AND CARBON MONOXIDE EXTRACTION FAN. FAN SHALL OPERATE UPON SIGNAL FROM CARBON MONOXIDE SENSOR. BASIS OF DESIGN

KIDDE CARBON MONOXIDE ALARM. SENSOR SHALL BE SET TO ACTIVATE HEATER WHEN CARBON MONOXIDE LEVELS REACH 50 PPM.

3. BASIS OF DESIGN IS SIEBRING MANUFACTURING ROYAL GAS HEATER RH240.

4. INSTALL FURNACE AND FLUE VENTING SYSTEM IN ACCORDANCE WITH MANUFACTURER'S INSTALLATION INSTRUCTIONS.

F-1 ROYAL HEAT RH240 HORIZONTAL BLOWER 240,000 11" 8" 640 32" SEE NOTES

FURNACE SCHEDULE

MANUFACTURER MODEL TYPE

48" 54"

VENT

PIPE

28003/4

MOTOR

HP

BLOWER

CFM

WEIGHT

(LBS)

LP-GAS

(W.C.)

MARK

ECP-1

MARK

MARK

MARK BTU DIMENSIONS

W L H

REMARKS

SEE NOTES

REMARKS

WATTS

MOTOR

VOLTSHP

HZRPM

RPM C/W

HP VOLTS HZ

MOTOR REMARKS

INSECT SCREEN

SCALE:

BID OPTION #1 AND #3

EVAPORATIVE COOLING PAD AND SUMP PUMP DETAIL

NTS

M600

SUMP TANK. PROVIDE WITH

COOLING PAD MANUFACTURER

PROVIDED WATER RE-CIRCULATION

SYSTEM

MEDIA

VENT SYSTEM

SEE ARCH.

COOLING PAD

COOLING: COOLING SHALL BE PROVIDED IN TWO STAGES. STAGE 1 - EXHAUST FANS SHALL ACTIVATE, VENT ACTUATORS SHALL OPEN THE VENTS TO CIRCULATE AIR AS REQUIRED TO MAINTAIN A TEMPERATURE SET POINT AS MEASURED BY THE SPACE TEMPERATURE AS DETERMINED BY THE GREENHOUSE MASTER CONTROLLER. STAGE 2 -EVAPORATIVE COOLING WALL PUMPS SHALL ENERGIZE.

EVAPORATIVE COOLING WALLS SHALL MAINTAIN A TEMPERATURE SET POINT AS MEASURED BY THE SPACE TEMPERATURE SENSORS AS

DETERMINED BY THE GREENHOUSE MASTER CONTROLLER.

HEATING: FURNACE SHALL ENERGIZE TO PROVIDE HEATING. HEATERS SHALL MAINTAIN A TEMPERATURE SET POINT AS MEASURED BY THE

SPACE TEMPERATURE SENSORS AS DETERMINED BY THE GREENHOUSE MASTER CONTROLLER.

CONTROL SYSTEM SHALL MONITOR INDOOR AIR TEMPERATURE BY SPACE TEMPERATURE SENSORS LOCATED IN EACH BAY. PROVIDE ALL WIRING AND CONTROLS FOR A COMPLETE OPERATIONAL SYSTEM. VERIFY SEQUENCE OF OPERATIONS WITH USDA PERSONNEL.

SEQUENCE OF OPERATION

GREENHOUSE

CONTROLLER INPUT/

OUTPUT SUMMARY

NOTES:

1. BASIS OF DESIGN: MICRO-GROW CONTROLS SYSTEM.

EVAPORATIVE COOLING WALL

AN

AL

OG

IN

PU

T

AN

AL

OG

O

UT

PU

T

BI

NA

RY

IN

PU

T

BI

NA

RY

O

UT

PU

T

EXHAUST FAN X

X

XTEMPERATURE SENSOR

FURNACE ENABLE X

VENT ACTUATOR X

VENT SYSTEM

SEE ARCH.

HOUSEKEEPING PADS MUST EXTEND A MINIMUM OF 6"

BEYOND ALL SIDES OF SUPPORTED EQUIPMENT UNLESS

OTHERWISE INDICATED. PADS MUST BE A MINIMUM OF 4"

THICK.

PROVIDE 3000 PSI CONCRETE HOUSEKEEPING

PADS FOR ALL GROUND AND/OR FLOOR

MOUNTED EQUIPMENT

EDGE OF SUPPORTED EQUIPMENT

CHAMFERED EDGED ALL

SIDES

FLOOR

ALL PADS INSTALLED ON CONCRETE FLOORS ARE TO BE PROVIDED WITH

#4 REBAR DOWEL RODS PENETRATING A MINIMUM OF 2" INTO BOTH THE

PAD AND THE SUPPORTING FLOOR. PROVIDE A MINIMUM OF FOUR (4)

DOWEL RODS PER PAD, WITH SPACING OF DOWEL RODS AT 18" ON

CENTER MAXIMUM BOTH WAYS.

#4 REINFORCEMENT MAX 4" ON CENTER EACH

WAY

SCALE:

HOUSEKEEPING PAD DETAIL

NTS

M600

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

P.A.

FIRMTHE

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

c

USDA AGRICULTURAL RESEARCH SERVICE

BLUEBERRY AND CRANBERRY RESEARCH CENTER

ADDITION TO CRANBERRY BREEDING AND GENETICS GREENHOUSE

CHATSWORTH, NEW JERSEY

ELECTRICAL

NOTES AND ABBREVIATIONS

E001 12 1803/08/24

REH

BSN

FEJ

10300 BALTIMORE AVE.

BELTSVILLE, MD 20705

XXX

6223-A

XXX

XXX

XXX

XXX

1. THE DRAWINGS INDICATE THE GENERAL EXTENT OF WORK. THE DRAWINGS ARE NOT

INTENDED TO INDICATE OR DESCRIBE ALL WORK REQUIRED FOR THE FULL PERFORMANCE

AND COMPLETION OF THE REQUIREMENTS OF THE CONTRACT.

2. THE CONTRACTOR IS RESPONSIBLE FOR THE COORDINATION OF ALL PARTS OF THE WORK SO THAT NO WORK SHALL BE LEFT IN AN UNFINISHED OR INCOMPLETE CONDITION. INSTALLATION

OF ELECTRICAL WORK SHALL BE COORDINATED WITH OTHER TRADES BEFORE ANY

INSTALLATION IS DONE. CONDUIT AND DEVICES SHOWN ON PLANS ARE SCHEMATIC.

3. ALL WORK SHALL CONFORM TO APPLICABLE INDUSTRY AND MANUFACTURER'S PUBLISHED

STANDARDS FOR QUALITY OF MATERIALS AND WORKMANSHIP, AS WELL AS, ALL

REQUIREMENTS IN THESE DRAWINGS AND SPECIFICATIONS. ANY CONFLICTING

REQUIREMENTS OF THE SOURCES LISTED ABOVE SHALL BE BROUGHT TO THE CONTACTING

OFFICER'S ATTENTION PRIOR TO PROCEEDING WITH THE WORK.

4. THE CONTRACTOR SHALL PROTECT ANY EXISTING, IN-PLACE, AND NEW WORK.

5. ONCE ON SITE, THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND SHALL VERIFY ALL

NEW AND EXISTING CONDITIONS SHOWN ON THESE DRAWINGS. THE CONTRACTOR SHALL

NOTIFY THE CONTRACTOR IN WRITING OF ANY DIFFERING CONDITIONS BEFORE

COMMENCEMENT OF WORK.

6. THE CONTRACTOR SHALL PLAN HIS/HER WORK TO PROVIDE ADEQUATE PROTECTION FOR

PERSONS AND PROPERTY AT ALL TIMES, AND EXECUTE THE WORK IN SUCH A MANNER TO

AVOID ANY HAZARD TO PERSONS AND PROPERTY AS NECESSARY.

7. MINIMUM RACEWAY SIZE SHALL BE 3/4-IN. INCREASE RACEWAY SIZE AS REQUIRED TO LIMIT

RACEWAY FILL RATIO TO LESS THAN 40% FULL.

8. ALL CONDUCTORS COPPER.

9. ALL FEEDERS AND BRANCH CIRCUITS SHALL INCLUDE A GREEN INSULATED GROUND

CONDUCTOR, SIZE PER NATIONAL ELECTRICAL CODE, OR AS SHOWN, CONNECTED TO EACH

DEVICE AND OUTLET BOX ON THE CIRCUIT AND TO THE PANELBOARD GROUND BUS. PROVIDE

A DEDICATED NEUTRAL CONDUCTOR FOR EACH BRANCH CIRCUIT. MULTTIPLE BRANCH

CIRCUITS IN ONE RACEWAY REQUIRE ONLY ONE GROUND CONDUCTOR.

10. ALL SAFETY DISCONNECTS SHALL BE HEAVY DUTY 240V NEMA 4 NON-FUSED TYPE.

11. PROVIDE SAFETY DISCONNECTS FOR ALL MECHANICAL EQUIPMENT.

12. NEW WORK SHALL BE MADE TO TIE INTO THE EXISTING IN A UNIFORM MANNER, SIMILAR ITEMS

OF NEW WORK SHALL BE CHECKED AGAINST EXISTING WORK.

13. REFER TO ONE-LINE DIAGRAMS, SCHEDULES, AND RISER DIAGRAMS FOR CONDUCTOR AND

CONDUIT SIZES NOT SHOWN ON PLANS.

14. PROVIDE LABELS ON ALL RECEPTACLES, WALL MOUNTED LIGHT SWITCHES AND JUNCTION

BOXES INDICATING THE SOURCE PANEL AND CIRCUIT(S). TEXT SHALL BE BLACK 1/4-IN IN

HEIGHT PRINTED ON A CLEAR LABEL. HANDWRITTEN LABELS ARE NOT PERMITTED.

15. COORDINATE WALL, FLOOR AND ROOF PENETRATIONS WITH THE CONTRACTOR.

16. SUPPLEMENTAL STEEL MEMBERS REQUIRED TO SUPPORT ELECTRICAL EQUIPMENT FROM

MAIN STRUCTURE SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR UNLESS

SPECIFICALLY NOTED OTHERWISE.

17. EXACT LOCATIONS OF PANELBOARDS, DISCONNECTS, TIMERS, AND SWITCHES SHALL BE

COORDINATED WITH FINAL LOCATIONS OF WALL-MOUNTED ARCHITECTURAL AND

MECHANICAL EQUIPMENT. MOUNT DISCONNECTS AND SWITCHES MINIMUM 48" AFF. MOUNT

TIMERS MINIMUM 40" AFF.

18. MANUFACTURER NAME AND MODEL NUMBERS ARE BASIS OF DESIGN AND ARE SHOWN

FOR INFORMATION ONLY. REFER TO SPECIFICATIONS FOR COMPLETE REQUIREMENTS.

19. SPECIFICATIONS TAKE PRECEDENCE OVER DRAWINGS. HOWEVER, ITEMS SHOWN ON

DRAWING BUT NOT IN THE SPECIFICATIONS ARE REQUIRED WITHIN THE PROJECT SCOPE.

IN ADDITION, SPECIFIC ITEMS SHOWN ON THE DRAWINGS TAKE PRECEDENCE OVER

SPECIFICATIONS IN CASES WHERE THE SPECIFICATION HAS OPTIONS.

20. ALL EQUIPMENT INSTALLED IN THIS PROJECT SHALL COMPLY WITH THE "BUY AMERICAN

ACT". BASIS OF DESIGN SHOWN ON SCHEDULES IS TO ESTABLISH A STANDARD OF

QUALITY, NOT TO LIMIT COMPETITION. EQUIVALENT EQUIPMENT FROM ANOTHER

MANUFACTURER IS ACCEPTABLE

21. PROVIDE GFCI PROTECTION AND FOR ALL NON-LIGHTING RECEPTACLES.

22. PROVIDE WEATHERPROOF IN USE COVERS FOR ALL RECEPTACLES.

23. PROVIDE WEATHERPROOF COVERS FOR ALL SWITCHES.

GENERAL PROJECT NOTES:ABBREVIATIONS:

DSHP

DSS

DWBP

DX

EC

EF

ELEC

EMH

EMT

E or EMER

EPA

EQUIP

ERV

ERU

EXIST or EX

A OR AMP AMPERE(S)

ACC

AC

AC

AF

AFF

AFG

AHU

AIC

AL

AM

ASYM

AT

ATS

AUTO

AWG

B

BC

BCW

BFF

BFG

BLDG

C

CAT

CB

CCT

CCTV

CFCI

CH

CHWCP

CHWP

CHWSP

CKT

CMH

CP

CPT

CRAC

CRI

CT

CT

CU

CWP

D

DC

DF

DH or DUH

DHWCP

DISC

DOAS

DPST

DPDT

DSCU

AIR COOLED CHILLER

ALTERNATING CURRENT

AIR CONDITIONING UNIT

CURTAIN

AMP FRAME

ABOVE FINISHED FLOOR

ABOVE FINISHED GRADE

AIR HANDLING UNIT

AMPERE INTERRUPTING

CAPACITY

ALUMINUM

AMMETER

ASYMMETRICAL

AMP TRIP

AUTOMATIC TRANSFER

SWITCH

AUTOMATIC

AMERICAN WIRE GAUGE

BOILER

BRANCH CONTROLLER

BARE COPPER WIRE

BELOW FINISHED FLOOR

BELOW FINISHED GRADE

BUILDING

CONDUIT

CATEGORY

CIRCUIT BREAKER

CORRELATED COLOR

TEMPERATURE

CLOSED CIRCUIT

TELEVISION

CONTRACTOR FURNISHED

CONTRACTOR INSTALLED

CHILLER

CHILLED WATER

CIRCULATING PUMP IN A

PRIMARY-SECONDARY

SYSTEM

CHILLED WATER PUMP

CHILLED WATER SUPPLY

PUMP IN A PRIMARY-

SECONDARY SYSTEM

CIRCUIT

COMMUNICATIONS

MANHOLE

CONDENSATE PUMP

CONTROL POWER

TRANSFORMER

COMPUTER ROOM AC UNIT

COLOR RENDERING INDEX

CURRENT TRANSFORMER

COOLING TOWER

COPPER OR CONDENSING

UNIT

CONDENSER WATER PUMP

DEPTH

DIRECT CURRENT

DESTRATIFICATION FAN

DUCT HEATERS

DOMESTIC HOT WATER

CIRCULATING PUMP

DISCONNECT SWITCH

DEDICATED OUTSIDE AIR

SYSTEM (UNIT)

DOUBLE POLE SINGLE

THROW

DOUBLE POLE DOUBLE

THROW

DUCTLESS SPLIT

CONDENSING UNIT

(POWERS THE DSS INDOOR

UNIT)

DUCTLESS SPLIT HEAT

PUMP (POWERS THE DSS

INDOOR UNIT)

DUCTLESS SPLIT SYSTEM

(INDOOR UNIT)

DOMESTIC WATER

BOOSTER PUMP

DIRECT EXPANSION (DX)

COOLING COIL

EMPTY CONDUIT

EXHAUST FAN

ELECTRICAL

ELECTRICAL MANHOLE

ELECTRICAL METALLIC

TUBING

EMERGENCY

EFFECTIVE PROJECTED

AREA

EQUIPMENT

ENERGY RECOVERY

VENTILATOR

ENERGY RECOVERY UNIT

EXISTING

NFPA

NC

NESC

NL

NO

NTS

P

PA

HWP

HWRP

HWSP

HWUH

HZ

IDS

IMC

IRH

J OR JB

K

KAIC

KEF

KH

KV

KVA

KW

KWHR

L

LA

LAN

LAV

LM

LTG

MAU

MAX

MCA

MCB or MB

MCC

MGB

MH

MIN

MLO

MOD

MT or MTD

MRS

N

NEC

NEMA

HT

HVU

HWCP

GUH

GWH

H or HT

HAC

HOA

HP

HP

EUH

EXP

EWC

EWH

F

FACP

FCU

FLEX

FWE

G OR GND

GFGI

GFCI

GRS

ELECTRIC UNIT HEATER

EXPLOSION PROOF

ELECTRIC WATER COOLER

ELECTRIC WATER HEATER

FUSE

FIRE ALARM CONTROL

PANEL

FAN COIL UNIT

FLEXIBLE

FURNISHED WITH

EQUIPMENT

GROUND

GOVERNMENT FURNISHED

GOVERNMENT INSTALLED

GROUND FAULT

INTERRUPTER

GALVANIZED RIGID STEEL

CONDUIT

GAS UNIT HEATER

GAS WATER HEATER

HEIGHT

HEATED AIR CURTAIN

HAND-OFF AUTOMATIC

HORSE POWER

HEAT PUMP (OUTDOOR

PORTION OF SPLIT SYSTEM

HEAT PUMP, USE CU FOR

STANDARD DX OUTDOOR

UNIT)

HEAT TRACKING

HEATING/VENTILATING UNIT

HEATING WATER

CIRCULATING PUMP IN A

PRIMARY-SECONDARY

SYSTEM

HEATING WATER SUPPLY IN

A PRIMARY-ONLY SYSTEM

HOT WATER

RECIRCULATION PUMP

HEATING WATER SUPPLY

PUMP IN A PRIMARY-

SECONDARY SYSTEM

HOT WATER UNIT HEATER

HERTZ

INTRUSION DETECTION

SYSTEM

INTERMEDIATE METAL

CONDUIT

INFRARED HEATER

JUNCTION BOX

KILO

THOUSAND AMPERE

INTERRUPTING CAPACITY

KCM OR KCMIL THOUSAND OF CIRCULAR

MILS

KITCHEN EXHAUST FAN

KITCHEN HOOD

KILOVOLT

KILOVOLT-AMPERES

KILOWATT

KILOWATT-HOUR

LENGTH

LIGHTNING ARRESTOR

LOCAL AREA NETWORK

LAVATORY

LOCKHEED MARTIN

LIGHTING

MAKE-UP AIR UNIT

MAXIMUM

MINIMUM CIRCUIT AMPACITY

MAIN CIRCUIT BREAKER

MOTOR CONTROL CENTER

MAIN GROUND BAR

MANHOLE or MOUNTING

HEIGHT

MINIMUM

MAIN LUGS ONLY

MOTOR OPERATED DAMPER

MOUNT or MOUNTED

MOTOR RATED SWITCH

NEUTRAL

NATIONAL ELECTRICAL

CODE

NATIONAL ELECTRICAL

MANUFACTURER'S

ASSOCIATION

NATIONAL FIRE

PROTECTION ASSOCIATION

NORMALLY CLOSED

NATIONAL ELECTRICAL

SAFETY CODE

NIGHT LIGHT

NORMALLY OPEN

NOT TO SCALE

POLE(S) or PUMP

PUBLIC ADDRESS

SPEC

SPST

SWBD

SWGR

TMGB

TOL

TP

TYP

U

UH

UG

UIO

UL

UTP

V

VA

VAV

VEF

VM

VRF

W

WC

WEF

WH

WHDM

WSHP

WP

XFMR

Z

PDU

PF

PH

PIU

PMT

PNL

PTAC

PVC

POWER DISTRIBUTION UNIT

POWER FACTOR

PHASE

VAV TERMINAL UNIT WITH

PARALLEL OR SERIES FAN

(PRIMARY INDUCTION UNIT)

PAD MOUNTED

TRANSFORMER

PANEL OR PANELBOARD

PACKAGED THRU-WALL AIR

CONDITIONER

POLYVINYL CHLORIDE

RECEPT or RECP RECEPTACLE

RF

RH

RETURN FAN

RADIANT HEATERS

(ELECTRIC)

RMC

RMS

RTU

RVNR

SA

SCCR

SD

SF

S/N

SP

SPD

SPDT

RIGID METAL CONDUIT

ROOT MEAN SQUARE

ROOF TOP UNIT

REDUCED VOLTAGE NON-

REVERSING

SURGE ARRESTOR

SHORT CIRCUIT CURRENT

RATING

SMOKE DAMPER

SUPPLY FAN

SOLID NEUTRAL

SUMP PUMP

SURGE PROTECTIVE DEVICE

SINGLE POLE DOUBLE

THROW

SPECIFICATIONS

SINGLE POLE SINGLE

THROW

SWITCHBOARD

SWITCHGEAR

TELECOMMUNICATIONS

MAIN GROUNDING BUSBAR

THERMAL OVERLOAD

TWISTED PAIR

TYPICAL

URINAL

UNIT HEATER

UNDERGROUND

UNLESS INDICATED

OTHERWISE

UNDERWRITERS

LABORATORY

UNSHIELDED TWISTED PAIR

VOLTS

VOLT AMPERES

VAV TERMINAL UNIT

VEHICLE EXHAUST FAN

VOLTMETER

VARIABLE REFRIGERANT

FLOW SYSTEM

WATTS or WIRE or WIDTH

WATER CLOSET

WELDING EXHAUST FAN

WATER HEATER

WATTHOUR DEMAND METER

WATER SOURCE HEAT

PUMP

WEATHERPROOF

TRANSFORMER

IMPEDANCE

NOTE: ABBREVIATIONS ABOVE

ARE FOR ELECTRICAL SHEETS

ONLY. NOT ALL ABBREVIATIONS

SHOWN WILL BE USED ON THIS

PROJECT.

MDP MAIN DISTRIBUTION PANEL

xx

PANELBOARD.

NAME OF PANELBOARD

GEAR

LA-1

LA-1 HOMERUN TO PANELBOARD. ARC DENOTES CONCEALED

CIRCUITRY. TEXT DENOTES PANELBOARD NAME WITH

CIRCUIT NUMBER. DEVICES HAVING CIRCUIT NUMBERS

LOCATED BESIDE THEM MAY NOT SHOW THE CIRCUIT

NUMBERS AT THE HOMERUN ARROWS.

PARTIAL HOMERUN TO PANELBOARD. COMBINE ALL

PARTIAL HOMERUNS THAT ARE ON THE SAME CIRCUIT IN

A JUNCTION BOX PRIOR TO ENTERING THE PANELBOARD.

10 THE TEXT INSIDE THE ARC INDICATES THE AWG SIZE OF

THE CONDUCTORS THAT SHALL BE RUN IN THE CONDUIT.

THE ABSENCE OF TEXT SIGNIFIES THAT THE

CONDUCTORS SHOULD BE #12 AWG.

CONDUIT AND WIRING

CONDUCTORS IN CONDUIT SURFACE MOUNTED TO WALL OR

CEILING. LONG TIC MARKS INDICATE NUMBER OF

CONDUCTORS. THE EQUIPMENT GROUNDING CONDUCTOR

IS SHOWN AS A SHORT TIC MARK. SIZE THE

EQUIPMENT GROUNDING CONDUCTOR AND THE CONDUIT

PER THE NEC. THE ABSENCE OF TIC MARKS SIGNIFIES

THAT TWO CONDUCTORS PLUS AN EQUIPMENT GROUNDING

CONDUCTOR SHOULD BE PROVIDED. FOR EXAMPLE, THE

MARKINGS TO THE LEFT SIGNIFY THAT THREE

CONDUCTORS PLUS AN EQUIPMENT GROUNDING

CONDUCTOR SHOULD BE PROVIDED.

UNDERGROUND DUCT. DASHED LINE INDICATES CONDUIT IS

TO BE TRENCHED AND BURIED. REFER TO ?/E-??? FOR

DETAIL.

ELECTRICAL LEGEND:

SIMPLEX NEMA L5-20R. PROVIDE WITH WEATHERPROOF IN USE COVER.

QUADRUPLEX NEMA 5-20R. PROVIDE WITH WEATHERPROOF IN USE COVER.

DUPLEX NEMA 5-20R. PROVIDE WITH WEATHERPROOF IN USE COVER.

EXISTING FUEL OIL TANK

NEW PROPANE TANK N.I.C. INSTALLED

AND FURNISHED BY GOVERNMENT

W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W

W W

W

EXISTING 2" WATER LINE

EXISTING GREENHOUSE EXISTING GREENHOUSE

EXISTING HEADHOUSE

EXISTING HEADHOUSE

W W

W

NEW CRANBERRY

RESEARCH GREENHOUSE

BASE BID

NEW CRANBERRY

RESEARCH GREENHOUSE

BID OPTION #2

EVAPORATIVE COOLING

PADS BID OPTION #3

EVAPORATIVE COOLING

PADS BID OPTION #1

BASE BIDBID OPTION #2

SCALE:

SITE PLAN

1" = 10'

ES100

NORTH

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

P.A.

FIRMTHE

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

c

USDA AGRICULTURAL RESEARCH SERVICE

BLUEBERRY AND CRANBERRY RESEARCH CENTER

ADDITION TO CRANBERRY BREEDING AND GENETICS GREENHOUSE

CHATSWORTH, NEW JERSEY

SITE PLAN

ES100

13 1803/08/24

REH

BSN

FEJ

10300 BALTIMORE AVE.

BELTSVILLE, MD 20705

XXX

6223-A

XXX

XXX

XXX

XXX

20'

SCALE: 1"=10'-0"

0 10' 30'

COMPACTED SAND BACKFILL

BACKFILL AND COMPACT IN

MAX 6" LAYERS

MARKER TAPE WITH

DETECTABLE FOIL BACKING.

MARKER TAPE MUST BE RED

AND CONTINUOUSLY

LABELED ELECTRIC

SCALE:

DUCTBANK DETAIL

NA

ES100

7 1/2"

MIN

3"

MIN

3" MI

N

3" MI

N

3"

MIN

1'

EMERGENCY POWER DUCT

THREE #4, #10GND IN

1.25-IN SCH 40 PVC

(TYPICAL OF TWO DUCTS)

NORMAL POWER DUCT

THREE 1/0, #6GND IN 1.5-IN

SCH 40 PVC

(TYPICAL OF TWO DUCTS)

KEYED NOTES:

1. PROVIDE NEW UNDERGROUND SERVICE FROM EXISTING 2-IN CONDUIT

STUBBED OUT 3-FT FROM PANEL MDP TO NEW PANEL GH1 CONSISTING

OF THREE 1/0, #6GND IN 1.5-IN SCH 40 PVC. REFER TO 2/ES100.

2. PROVIDE NEW UNDERGROUND SERVICE FROM EXISTING 2-IN CONDUIT

STUBBED OUT 3-FT FROM PANEL MDP TO NEW PANEL GH2 CONSISTING

OF THREE 1/0, #6GND IN 1.5-IN SCH 40 PVC. REFER TO 2/ES100.

3. PROVIDE NEW UNDERGROUND SERVICE FROM EXISTING 2-IN CONDUIT

STUBBED OUT 3-FT FROM PANEL EM TO NEW PANEL GH1 EM CONSISTING OF

THREE #4, #10GND IN 1.25-IN SCH 40 PVC. REFER TO 2/ES100.

4. PROVIDE NEW UNDERGROUND SERVICE FROM EXISTING 2-IN CONDUIT

STUBBED OUT 3-FT FROM PANEL EM TO NEW PANEL GH2 EM CONSISTING OF

THREE #4, #10GND IN 1.25-IN SCH 40 PVC. REFER TO 2/ES100.

5. EQUIPMENT IS BEING PROVIDED BY A DIFFERENT CONTRACT. CONFIRM

WORK MATCHES CONDITIONS SHOWN PRIOR TO START OF WORK.

X

COMPACTED SAND BACKFILL

BACKFILL AND COMPACT IN

MAX 6" LAYERS

MARKER TAPE WITH

DETECTABLE FOIL BACKING.

MARKER TAPE MUST BE RED

AND CONTINUOUSLY

LABELED ELECTRIC

SCALE:

DUCTBANK DETAIL

NA

ES100

7 1/2"

MIN

3"

MIN

3" MI

N

3" MI

N

3"

MIN

1'

EMERGENCY POWER DUCT

THREE #4, #10GND IN

1.25-IN SCH 40 PVC

NORMAL POWER DUCT

THREE 1/0, #6GND IN

1.5-IN SCH 40 PVC

7 1 /2"

MI

N

PANEL MDP

PANEL EM

GENERATOR

NEW PANEL GH1 EM

NEW UNDERGROUND SERVICE1 2

NEW PANEL GH11

ES100

ES100

3 4

NEW UNDERGROUND SERVICE1 3

NEW PANEL GH2 EM

NEW PANEL GH22

NEW UNDERGROUND SERVICE2 4

ES100

Stamp

CF-1 CF-1

A1

PANEL EM

PANEL GH

GL1 GL1 GL1 GL1 GL1 GL1 GL1 GL1 GL1 GL1 GL1

GH2:3 GH2:7

GL1GL1

GH2:11

GL1GL1

GL1GL1GL1

GH2:9

GL1GL1GL1 GL1 GL1 GL1 GL1 GL1 GL1 GL1 GL1 GL1

GH2:5GH2:1

GH2:15

GH2:13

GH2 EM:1

GH2 EM:1

GH2 EM:3

GH2 EM:3

GH2 EM:2

GH2 EM:7

GH2 EM:5

ENVIRONMENTAL

CONTROL PANEL

LIGHTING TIMERS

(TYP OF 6)

GH2:17

GH2:23

GH2 EM:4

CF-1 CF-1

A1

PANEL EM

PANEL GH

GL1 GL1 GL1 GL1 GL1 GL1 GL1 GL1 GL1 GL1 GL1

GH1:3 GH1:7

GL1GL1

GH1:11

GL1GL1

GL1GL1GL1

GH1:9

GL1GL1GL1 GL1 GL1 GL1 GL1 GL1 GL1 GL1 GL1 GL1

GH1:5GH1:1

GH1:15

GH1:13

GH1 EM:1

GH1 EM:1

GH1 EM:3

GH1 EM:3

GH1 EM:2

GH1

EM:7

GH1 EM:5

ENVIRONMENTAL

CONTROL PANEL

LIGHTING TIMERS

(TYP OF 6)

GH1:17

GH1:23

GH1 EM:4

A1 A1 A1

A1 A1 A1

CF-1 CF-1

CF-1 CF-1

EXHAUST FAN

SEE MECHANICAL

EXHAUST FAN

SEE MECHANICAL

F

F

GH1 EM:11

GH1 EM:9

GH1:21

EF-1

EF-1

EXHAUST FAN

SEE MECHANICAL

EXHAUST FAN

SEE MECHANICAL

F

F

GH2 EM:11

GH2 EM:9

GH2:21

EF-1

EF-1

VENT SYSTEM

VENT CONTROL

BID OPTION #1:

EVAPORATIVE COOLING PAD SYSTEM

P

GH1 EM:6

ECP-1

ECP-2

P

GH1 EM:8

GH1 EM:10

L

GH1:21

VENT SYSTEM

VENT CONTROL

BID OPTION #1:

EVAPORATIVE COOLING PAD SYSTEM

P

GH2 EM:6

ECP-1

ECP-2

P

GH2 EM:8

GH2 EM:10

L

GH2:21

HEAT DUCTS SEE MECHANICAL

HEAT DUCTS SEE MECHANICAL

GH1:19

GH2:19

HEAT DUCTS SEE MECHANICAL

F-1

F-1

F-1

E200

E200

E200

2 SIM.

GREENHOUSE #1

GREENHOUSE #2

F

F

GH1 EM:12

GH2 EM:12

INFLATION FAN

INFLATION FAN

F-1 HEAT DUCTS SEE MECHANICAL

BASE BID

BID OPTION #2

VENT SYSTEM

BID OPTION #1

VENT SYSTEM

BID OPTION #3

SCALE:

FLOOR PLAN

1/4" = 1'-0"

E100

8'0 2' 4' 12'

SCALE: 1/4"= 1'-0"

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

P.A.

FIRMTHE

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

c

USDA AGRICULTURAL RESEARCH SERVICE

BLUEBERRY AND CRANBERRY RESEARCH CENTER

ADDITION TO CRANBERRY BREEDING AND GENETICS GREENHOUSE

CHATSWORTH, NEW JERSEY

ELECTRICAL PLAN

E100 15 1803/08/24

REH

BSN

FEJ

10300 BALTIMORE AVE.

BELTSVILLE, MD 20705

XXX

6223-A

XXX

XXX

XXX

XXX

1 1

1 1

2 3

2 3 2 3

2 3 2 3

2 3

2 3 4

2 2

2 2

KEYED NOTES:

1. PROVIDE 30A SAFETY DISCONNECT.

2. SUPPORT DEVICE AND CONDUIT FROM

GREENHOUSE FRAME. PROVIDE ADDITIONAL

SUPPORT AS REQUIRED.

3. SUPPORT LIGHT FIXTURE AND DRIVER FROM

GREENHOUSE FRAME. PROVIDE ADDITIONAL

HANGERS AND SUPPORT AS

REQUIRED.CONNECT TO LIGHTING TIMER PER

DETAIL 1/E700.

4. PROVIDE MANUAL SWITCHING. LOCATE

THREE-WAY SWITCH ON GREENHOUSE

EXTERIOR AT EACH DOOR MOUNTED 48-IN AFF.

PROVIDE WEATHERPROOF SWITCH COVER.

TYPICAL FOR 2 GREENHOUSES.

5. BID OPTION #1: EVAPORATIVE COOLING SYSTEM.

6. BID OPTION #3: EVAPORATIVE COOLING SYSTEM.

1 1

1 1

2 3

2 3 2 3

2 3 2 3

2 3

2 3 4

2 2

2 2

PLAN

NORTH

TRUE

NORTH

GREENHOUSE #1

BASE BID

GREENHOUSE #2

BID OPTION #2

GL1

A1

GL1

GROW LIGHTS

AISLE LIGHTS

LIGHTING RECEPTACLE

8'- 2"

HEAT DUCTS SEE MECHANICAL

'-8

5'- 8"

CONVENIENCE RECEPTACLE

GROW LIGHTS

LIGHTING RECEPTACLE

CONVENIENCE RECEPTACLEGL1

A1

GL1

HEAT DUCTS SEE MECHANICALHEAT DUCTS SEE MECHANICAL

GROW LIGHTS

AISLE LIGHTS

LIGHTING RECEPTACLE

GROW LIGHTS

LIGHTING RECEPTACLE

CONVENIENCE RECEPTACLE

EF-1EF-1

LIGHTING TIMERS

LIGHT SWITCH

GH EM

RECEPTACLE

ENVIRONMENTAL

CONTROL PANEL

MECHANICAL EQUIPMENT

SAFETY DISCONNECTS

MECHANICAL EQUIPMENT

SAFETY DISCONNECTS

1 1

CONVENIENCE RECEPTACLE2

2 2

8'0 2' 4' 12'

SCALE: 1/4"= 1'-0"

PPM

REVISIONS

Agricultural

Service Research

DE…