121-071426JVC.pdf

PDF 2 MB Posted

Attached to
South Campus Building S202 Ceiling Tile Replacement & Corridors Re-Painting
Solicitation number
121-071426JVC-S202
Issued by
Cabarrus County, North Carolina

About this file

This is an Invitation to Bid (IFB #121-071426JVC) issued by Rowan-Cabarrus Community College in Concord, North Carolina, for ceiling tile replacement and corridor re-painting at the South Campus Building S202. The project encompasses partial demolition and replacement of existing ceiling tiles and grids across three building levels, verification and correction of above-ceiling infrastructure including support for IT cabling, HVAC ductwork, fire alarm devices, and lighting systems, and installation of new ceiling grid and tiles aligned with existing HVAC and lighting systems. The scope includes three distinct work areas: ceiling tile replacements only, ceiling tile and grid replacement, and alternate ceiling tile and grid replacement, with new corridor walls to be re-painted in College-specified eggshell finish across all three levels. A mandatory pre-bid conference is required on Wednesday, August 12, 2026, at 10:00 a.m. at the project site, with attendance mandatory to submit a bid. Sealed bids must be submitted via email in PDF format (maximum 20 MB) to collegeenvironment@rccc.edu no later than 2:00 p.m. local time on Thursday, August 27, 2026, with public opening via Zoom immediately thereafter. All inquiries for clarifications must be received by Monday, August 17, 2026, at 1:00 p.m., with answers provided via addendum by August 19, 2026.

Bid bonds equal to 5% of the total bid amount are required, with checks mailed separately to Rowan-Cabarrus Community College by the 2:00 p.m. deadline on August 27, 2026. All bidders must be licensed North Carolina contractors with owner-approved sub-contractors and must be registered with the North Carolina Electronic Vendor Portal (eVP) prior to proposal submission, with failure to register resulting in disqualification. The contract must incorporate and adhere to the State of North Carolina's General Terms and Conditions. Deliverables include a construction schedule, material and subcontractor submittals outlining planned use and staffing, and warranty information per College standards as specified in the Facilities Design Manual. The project must comply with the Rowan-Cabarrus Community College Facilities Design Manual specifications and North Carolina Building Code requirements, with construction phasing coordinated to maintain campus access and emergency routes and final acceptance contingent upon visual inspection and specification compliance. Scope is based on provided mark-ups with major changes resulting from concealed conditions addressed through Requests for Information and formal change order processes.

View the file

Other files

File Type Posted
Addendum_3_08.19.26.pdf PDF
Addendum_2_08.07.26.docx.pdf PDF
Addendum_1_07.27.26.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

IFB # 121-071426JVC

South Campus Building S202 Ceiling Tile Replacement & Corridors Re-Painting

ROWAN-CABARRUS COMMUNITY COLLEGE

1531 Trinity Church Rd.

Concord, NC

INVITATION TO BID

NOTICE TO BID

Sealed bids for the Rowan-Cabarrus Community College, South Campus Building S202 Ceiling Tile Replacement and Corridors Re-Painting Project will be received via email, (pdf format only, maximum 20 MG) at collegeenvironment@rccc.edu until, but no later than 2:00 pm, local prevailing time, Thursday, August. 27, 2026, and then publicly opened and read immediately thereafter via ZOOM. Bidders are encouraged to view the bid opening in real time via a ZOOM link that follows.

The Bid Name and IFB # 121-071426JVC shall be referenced as the subject line of all emails.

Bidders shall be Contractors licensed in North Carolina, with Owner approved sub-contractors as required. The General Contractor shall be the Prime Contractor, and the bid shall contain all work required to ensure complete and satisfactory installation as designed. Bidders will receive an email receipt notification that their bids have been received.

Bids received after the announced time and date for submittal will be rejected. Bidders are responsible for ensuring their bid is received before the deadline indicated. All firms must be registered with the North Carolina Electronic Vendor Portal (eVP and Purchase Orders) prior to presenting a proposal. Failure to register may result in disqualification. North Carolina Electronic Vendor Portal may be found at https://evp.nc.gov/

Contractual Requirement: All bidders must agree to execute a contract that incorporates and adheres to the State of North Carolina's General Terms and Conditions. These terms are available for review at: https://www.doa.nc.gov/north-carolina-general-terms-and-conditions-5-2025/open.

Bid bonds are required in the amount of 5% of the total bid submitted. If paying by check, send to:

Rowan-Cabarrus Community College PO Box 1595, (1333 Jake Alexander Blvd. S, for courier, etc.)

Salisbury, NC 28145 ATTN: Ronda Holland

Checks must be received by 2:00 pm, Thursday, August 27, 2026. Only Bid Bond checks can be mailed, bids and other items must be sent via email.

A Mandatory Pre-Bid Conference will be held at 10:00 am on Wednesday, August 12, 2026, at the South Campus Building S202, 1531 Trinity Church Rd., Concord, NC. Attendees to gather at the left side Stair Tower Entry as viewed from the parking Lot. The purpose of this meeting will be to review the areas for rework as highlighted in the marked-up existing drawings. Attendance at the meeting is required to submit a bid.

https://evp.nc.gov/ https://www.doa.nc.gov/north-carolina-general-terms-and-conditions-5-2025/open

SCOPE OF WORK

1. Partial demolition and replacement of existing ceiling tiles and grids per marked-up plans provided,

2. Verification / corrections as needed for existing above ceiling infrastructure and independent structural support for any non-compliant anchoring or support of IT cabling, HVAC ductwork, fire alarm devices, lighting, and any other miscellaneous concealed conditions for corrective work,

3. Installation of new ceiling grid and tiles where marked on plans to re-align with existing HVAC and lighting already in place, which may need additional support.

a. NOTE: New corridor ceiling tiles and grid on second and third floors to be re-worked to center sprinkler heads in 2x2 ACT. Verifications with Facilities and College Environment on site for any issues.

b. Three areas for different installations (ref. attached plans):

i. Ceiling Tile replacements only

ii. Ceiling Tile and Grid replacement

iii. Add Alternate Ceiling Tile and Grid Replacement

4. Compliance with Rowan-Cabarrus Community College Facilities Design Manual (FDM) Specifications, and North Carolina Building Code requirements.

5. Re-painting all corridor walls for all three levels with College specified and approved color as noted in the Facilities Design Manual in eggshell finish.

PROJECT OVERVIEW / Additional Details for Compliance

1. Construction Phasing and Access

• Maintain campus access and emergency routes at all times.

• Coordinate construction sequencing with the College to minimize disruption.

• Provide temporary pedestrian control, barricades, and signage as required.

2. Quality Control and Acceptance

• Final acceptance is contingent upon visual inspection, and compliance with specifications.

3. Deliverables

• Construction schedule.

• Material and Subcontractor Submittals of planned use and staffing.

• Warranty information per College standards. See FDM.

4. Assumptions and Exclusions

• Scope is based on the provided mark-ups attached below, and listings above.

• Any major scope changes resulting from concealed conditions shall be addressed through Requests for

Information and any formal Change Order processes, if required.

All inquiries for clarifications and questions must be received via email to john.cole@rccc.edu by Monday, August 17, 2026 at 1:00 pm and will be answered via Addendum no later than 5:00 PM, August 19, 2026.

ATTACHMENTS

1. Drawings - South S202 High-lighted Former Project Drawings AD201 – First Level Reflected Ceiling Plan – Demolition - dated April 08, 2024 AD202 – Second Level Reflected Ceiling Plan – Demolition - dated April 08, 2024 AD203 – Third Level Reflected Ceiling Plan – Demolition - dated 04-08-24

2. Facility Design Manual Standards -2024 – Part 3 Ceiling Grid & Tiles – 3.9.2 mailto:john.cole@rccc.edu

BID OPENING ZOOM LINK

Join Zoom Meeting https://rccc-edu.zoom.us/j/93147817418

Meeting chat link https://rccc-edu.zoom.us/launch/jc/93147817418

Meeting ID: 931 4781 7418

One tap mobile +16465588656,,93147817418# US (New York)

+16469313860,,93147817418# US

Join instructions https://rccc-edu.zoom.us/meetings/93147817418/invitations?signature=yLFGPa26hxbkrFX5umdPoyHVjMZ75TgGQ 3FCosP6giY

END OF INVITATION TO BID

https://rccc-edu.zoom.us/j/93147817418 https://rccc-edu.zoom.us/launch/jc/93147817418 https://rccc-edu.zoom.us/meetings/93147817418/invitations?signature=yLFGPa26hxbkrFX5umdPoyHVjMZ75TgGQ3FCosP6giY https://rccc-edu.zoom.us/meetings/93147817418/invitations?signature=yLFGPa26hxbkrFX5umdPoyHVjMZ75TgGQ3FCosP6giY https://rccc-edu.zoom.us/meetings/93147817418/invitations?signature=yLFGPa26hxbkrFX5umdPoyHVjMZ75TgGQ3FCosP6giY

S

S

S S S S S

S S

S

OS

OS

OS OS

OS

OS

OS

OS

OS OS

OS

OS OS

F

F

F

F

F

F

F

F

F

F

S

F

S

S

S

S

S S

S

PLAN

N

TRUE

N

A A

B B

C C

D D

E E

CLASSROOM

CLASSROOM

OFFICE

104A

CLASSROOM

CLASSROOM

OFFICE

110B

CORRIDOR

101B

MECH./ELEC.

ELEV.

ELEVATOR

LOBBY

101A

JANITOR

ELEV.

MACH.

180B

STAIR #1

STAIR #2

WOMEN

MEN

STORAGE

BOILER

180A

WELDING

LAB

OFFICE

110A

CORRIDOR

101C

CORRIDOR

101D

CORRIDOR

101E

OFFICE

104B

OPEN

OFFICE

CORRIDOR

101F

OFFICE

CLASSROOM

C.1 C.1

C.1

C.1

C.1

C.3

C.0

EXISTING GWB HEADER TO

REMAIN

C.1

C.1

C.7 C.8

C.1

C.1C.1 C.1

C.2

C.2 C.2

C.2

C.2 C.2

C.2 C.2

R R

R

R

R

R R

R

R

R

C.1

C.1

R

R

REMOVE PORTION OF EXISTING CEILING

GRID TO INSTALL NEW GWB HEADER

NO CEILING WORK IN AREAS

SHOWN SHADED, TYPICAL

EXISTING WINDOW SHADES

TO REMAIN, UNLESS NOTED

OTHERWISE

EXISTING GWB HEADER TO

REMAIN

REMOVE EXISTING WINDOW SHADES

DURING DEMOLITION AND NEW WORK,

AND REINSTALL IN SAME LOCATION AT

END OF PROJECT

REMOVE EXISTING WINDOW SHADES

DURING DEMOLITION AND NEW WORK,

AND REINSTALL IN SAME LOCATION AT

END OF PROJECT

EXISTING WINDOW SHADES

TO REMAIN, UNLESS NOTED

OTHERWISE

C.0

C.0

C.0

C.0

C.0

C.0

C.0

C.0R

C.2 C.2

C.2

C.2

C.2

C.2

REMOVE EXISTING CEILING

TILE, 2x2 GRID TO REMAIN

OTS

OTS

CLASSROOM

C.3 C.3 C.3 C.3

C.3 C.3 C.3 C.3

C.3

REMOVE EXISTING CEILING GRID AND

TILE SHOWN DOTTED

REMOVE EXISTING ROLL DOWN PROJECTION

SCREEN, PROJECTOR AND SPEAKERS AND

RETURN TO OWNER

REMOVE EXISTING LIGHT FIXTURES

SHOWN DOTTED AND RE-USE IN

ELSEWHERE IN NEW WORK, SEE SHEET

A102 AND ELECTRICAL DRAWINGS

REMOVE EXISTING SPRINKLER HEADS AND

RE-INSTALL IN NEW CEILING, SEE SHEET A102

REMOVE EXISTING CEILING GRID AND

TILE SHOWN DOTTED, TYPICAL

REMOVE EXISTING LIGHT FIXTURES

SHOWN DOTTED AND RE-USE IN NEW

WORK, SEE SHEET A201 AND ELECTRICAL

DRAWINGS

REMOVE EXISTING SPRINKLER HEADS

IN CEILINGS TO BE REMOVED, TYPICAL

SEE FIRE PROTECTION DRAWINGS

REMOVE EXISTING HVAC DIFFUSERS

IN CEILINGS TO BE REMOVED, TYPICAL

SEE MECHANICAL DRAWINGS

REMOVE EXISTING FIRE ALARM

DEVICES, SMOKE DETECTORS,

OCCUPANCY SENSORS ETC, IN

CEILINGS TO BE REMOVED, TYPICAL

SEE ELECTRICAL DRAWINGS

REFLECTED CEILING PLAN KEYED NOTES

NO WORKC.0

REMOVE EXISTING CEILING TILES, EXISTING GRID TO REMAINC.1

REMOVE EXISTING LIGHT FIXTURE, SEE ELECTRICAL DRAWINGSC.2

REMOVE EXISTING LIGHT FIXTURE AND RE-USE IN NEW WORK, SEE ELECTRICAL DRAWINGSC.3

INFILL NEW CEILING GRID TEES TO MATCH EXISTING FOR 2X2 LAYOUT AND PROVIDE NEW CEILING TILE

NEW LIGHT FIXTURE, SEE ELECTRICAL DRAWINGS

EXISTING LIGHT FIXTURE RE-USED IN NEW LOCATION, SEE ELECTRICAL DRAWINGS

C.4

C.5

C.6

EXISTING CEILING MOUNTED PROJECTOR TO REMAIN, RELOCATE MOUNT SLIGHTLY AS

NECESSARY TO INSTALL NEW CEILING GRID TEES

C.7

EXISTING WALL MOUNTED ROLL DOWN SCREEN TO REMAINC.8

REMOVE EXISTING WALL MOUNTED ROLL DOWN SCREEN AND RE-USE IN NEW WORK.C.9

EXISTING WALL TO BE REMOVED

EXISTING WALL TO REMAIN

WALL LEGEND

NEW WALL

EXISTING 2 HR RATED WALL TO REMAIN

NOTE: WALL SYMBOLOGY FOR GRAPHICAL PURPOSES ONLY.

REFER TO PARTITION TYPES AND WALL SECTIONS FOR ACTUAL

WALL CONSTRUCTION.

EXISTING 1 HR RATED WALL TO REMAIN

NEW 1 HR RATED WALL

CEILING LEGEND

RECESSED LED DOWN LIGHT

2x4 RECESSED LED FIXTURE

2x2 RECESSED LED FIXTURE

SMOKE DETECTOR

OCCUPANCY SENSOROS

CEILING MOUNTED LIGHT

S

EXIT SIGN

DIRECTIONAL EXIT SIGN

UPRIGHT SPRINKLER HEAD

SPRINKLER HEAD MOUNTED IN CEILING

SUPPLY AIR DIFFUSER

RETURN AIR DIFFUSER /

EXHAUST GRILLE

LINEAR SUPPLY AIR DIFFUSER

INDICATES CEILING MOUNTED DEVICES, SPRINKLER HEADS, ETC. TO BE REMOVED

INDICATES CEILING MOUNTED DEVICES, SPRINKLER HEADS, ETC. TO BE RELOCATED

LOCATED IN CENTER OF NEW CEILING TILE, TYPICAL

R

SPEAKER WITH GRILLES

FIRE ALARM DEVICEF

CAMERA

101C 101D 101E 104A 104B 105 106 107 107A 111 112 117A 117B 117C 118A 118B 118C

REFLECTED CEILING BASE BID / ALTERNATE

WORK SHOWN IN THE FOLLOWING ROOMS IS BASE BID.

ALL OTHER WORK SHOWN ON THE REFLECTED CEILING PLAN IS TO BE INCLUDED IN ALTERNATE #2

OWNERSHIP OF INSTRUMENTS OF SERVICE:

All reports, specifications, plans, computer files, field data, notes, and other documents and instruments of service shall remain the property of the Design Professional. The Design Professional shall retain all common law, statutory and other reserved rights, including the copyright thereto.

This drawing is the property of Yates - Chreitzberg - Hughes Architects and is not to be reproduced or copied in whole or any part. It is not to be used on any other project and is to be returned upon request.

© Copyright 2024

R C

C C

B ui dl in g S2

R en ov at io ns

T rin ity

C hu rc h

R d

C on co rd , N

C

CONSULTANT:

PROFESSIONAL SEALS:

CLIENT:

YCHA COM.#:

REVISIONS:

PHASE & DATE:

SHEET TITLE:

ARCHITECTURAL:

7035 NORTHWINDS DR NW

CONCORD, NC 28027

704.788.2000 www.ycharch.com

I T ZBERG - H UGH ES ARCH I TECTS

PA

O

DROCNC

, N. C.CAROL I NA

HTRON

O O

RE

GI

ST

ER

ED

ARCHI TECTURAL C

RP

RATION

CERT. NO.

YA

TE

S-

CH

RE

SCO #22-25351-02A

NCCCS #2692

S:

\R ev it

Lo ca l F ile s\

9.

R

C C

C B ui ld in g

S2

Re no va tio ns _b illh yc ha rc h.

co m

.rv t

4/

/2

6:

:1

PM

22219.00

FIRST LEVEL

REFLECTED CEILING

PLAN - DEMOLITION

AD201

CONSTRUCTION DOCUMENTS

04-08-24

AD201 3/16" = 1'-0"

1 FIRST LEVEL REFLECTED CEILING PLAN - DEMOLITION

disenhour Area Measurement

639.32 sf disenhour Typewritten Text New ACT Grid and Tile In Yellow Area disenhour Area Measurement

72.3 sf disenhour Area Measurement

83.08 sf disenhour Area Measurement

83.84 sf

SS S SS

SSS

S

OS

OS

OS

OS

OS

OS

OS

OS OS

OSOS

OS

OSOS

OS

OS

OS

OS

F

F

F F

F

F

F

F

F

FF

F

F

F

S

FOSOS

S S

S S

S

S

S

S S

S

SS

S S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

PLAN

N

TRUE

N

A A

B B

C C

D D

E E

OFFICE

STORAGE

212C

STORAGE

212B

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

MEN

WOMEN

CORRIDOR

201A

CORRIDOR

201C

OFFICE

212A

STOR.

ENTRANCE

200 ENTRANCE

STOR.

214A

STOR.

214B

STOR.

STOR.

217A

STOR.

216A

CORRIDOR

ELEC.

JANITOR

223 OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

ELEV.

ELEV.

LOBBY

VESTIBULE

201E

CORRIDOR

201B

CORRIDOR

201D

CLASSROOM

R R R R R R RRR R R

R R

R

RR

R

R

R

R

RR

R

EXISTING WINDOW SHADES

TO REMAIN, TYPICAL

EXISTING GWB HEADER TO

REMAIN

REMOVE EXISTING CEILING MOUNTED

PROJECTORS AND SPEAKERS, RE-USE

IN NEW WORK, SEE SHEET A203

REMOVE EXISTING CEILING MOUNTED

PROJECTORS AND SPEAKERS, RE-USE

IN NEW WORK, SEE SHEET A203 AND

ELECTRICAL DRAWINGS

REMOVE EXISTING CEILING GRID AND

TILE SHOWN DOTTEDREMOVE WALL MOUNTED ROLL DOWN

PROJECTION SCREENS AND RE-USE IN NEW

WORK, SEE SHEET A203

REMOVE EXISTING CEILING GRID AND

TILE SHOWN DOTTED

EXISTING GWB HEADER TO

REMAIN

EXISTING GWB HEADER TO REMAIN

EXISTING WINDOW SHADES

TO REMAIN, TYPICAL

REMOVE EXISTING CEILING

TILE, 2x2 GRID TO REMAIN

REMOVE EXISTING CEILING MOUNTED

PROJECTOR, CAMERA AND SPEAKERS,

AND RETURN TO OWNER

C.1

C.1

C.1

C.0

C.0 C.1

C.1

C.1 C.1

C.1 C.1

C.0 C.0 C.0 C.0

C.0

C.7 C.7

RRRRRR

R

R RRRRRR RRRRRRR RR

R

C.8C.8

R

R

C.1 C.1

C.1

C.1 C.1

C.1 C.1

C.1

R

R

R

R R R R R

R R R

R

R

R R

R R R

R R R

R R

R

R

OPEN TO ABOVE OPEN TO ABOVE

REMOVE EXISTING LIGHT FIXTURES

SHOWN DOTTED AND RE-USE IN NEW

WORK, SEE SHEET A202 AND ELECTRICAL

DRAWINGS

NO CEILING WORK IN AREAS

SHOWN SHADED, TYPICAL

C.0

C.0

C.0

C.0

C.1

C.1

C.2

C.2

R

C.1 C.2 C.2

C.2 C.2

R

C.0

C.0

REMOVE EXISTING WALL MOUNTED

ROLL DOWN PROJECTION SCREEN

AND RETURN TO OWNER

EXISTING CUBICLE CURTAIN

AND TRACK TO REMAIN

REFLECTED CEILING PLAN KEYED NOTES

NO WORKC.0

REMOVE EXISTING CEILING TILES, EXISTING GRID TO REMAINC.1

REMOVE EXISTING LIGHT FIXTURE, SEE ELECTRICAL DRAWINGSC.2

REMOVE EXISTING LIGHT FIXTURE AND RE-USE IN NEW WORK, SEE ELECTRICAL DRAWINGSC.3

INFILL NEW CEILING GRID TEES TO MATCH EXISTING FOR 2X2 LAYOUT AND PROVIDE NEW CEILING TILE

NEW LIGHT FIXTURE, SEE ELECTRICAL DRAWINGS

EXISTING LIGHT FIXTURE RE-USED IN NEW LOCATION, SEE ELECTRICAL DRAWINGS

C.4

C.5

C.6

EXISTING CEILING MOUNTED PROJECTOR TO REMAIN, RELOCATE MOUNT SLIGHTLY AS

NECESSARY TO INSTALL NEW CEILING GRID TEES

C.7

EXISTING WALL MOUNTED ROLL DOWN SCREEN TO REMAINC.8

REMOVE EXISTING WALL MOUNTED ROLL DOWN SCREEN AND RE-USE IN NEW WORK.C.9

EXISTING WALL TO BE REMOVED

EXISTING WALL TO REMAIN

WALL LEGEND

NEW WALL

EXISTING 2 HR RATED WALL TO REMAIN

NOTE: WALL SYMBOLOGY FOR GRAPHICAL PURPOSES ONLY.

REFER TO PARTITION TYPES AND WALL SECTIONS FOR ACTUAL

WALL CONSTRUCTION.

EXISTING 1 HR RATED WALL TO REMAIN

NEW 1 HR RATED WALL

CEILING LEGEND

RECESSED LED DOWN LIGHT

2x4 RECESSED LED FIXTURE

2x2 RECESSED LED FIXTURE

SMOKE DETECTOR

OCCUPANCY SENSOROS

CEILING MOUNTED LIGHT

S

EXIT SIGN

DIRECTIONAL EXIT SIGN

UPRIGHT SPRINKLER HEAD

SPRINKLER HEAD MOUNTED IN CEILING

SUPPLY AIR DIFFUSER

RETURN AIR DIFFUSER /

EXHAUST GRILLE

LINEAR SUPPLY AIR DIFFUSER

INDICATES CEILING MOUNTED DEVICES, SPRINKLER HEADS, ETC. TO BE REMOVED

INDICATES CEILING MOUNTED DEVICES, SPRINKLER HEADS, ETC. TO BE RELOCATED

LOCATED IN CENTER OF NEW CEILING TILE, TYPICAL

R

SPEAKER WITH GRILLES

FIRE ALARM DEVICEF

CAMERA

REFLECTED CEILING BASE BID / ALTERNATE

WORK SHOWN IN THE FOLLOWING ROOMS IS BASE BID.

204 205 207 210 218 219 220 221 222

ALL OTHER WORK SHOWN ON THE REFLECTED CEILING PLAN IS TO BE INCLUDED IN ALTERNATE #2

OWNERSHIP OF INSTRUMENTS OF SERVICE:

All reports, specifications, plans, computer files, field data, notes, and other documents and instruments of service shall remain the property of the Design Professional. The Design Professional shall retain all common law, statutory and other reserved rights, including the copyright thereto.

This drawing is the property of Yates - Chreitzberg - Hughes Architects and is not to be reproduced or copied in whole or any part. It is not to be used on any other project and is to be returned upon request.

© Copyright 2024

R C

C C

B ui dl in g S2

R en ov at io ns

T rin ity

C hu rc h

R d

C on co rd , N

C

CONSULTANT:

PROFESSIONAL SEALS:

CLIENT:

YCHA COM.#:

REVISIONS:

PHASE & DATE:

SHEET TITLE:

ARCHITECTURAL:

7035 NORTHWINDS DR NW

CONCORD, NC 28027

704.788.2000 www.ycharch.com

I T ZBERG - H UGH ES ARCH I TECTS

PA

O

DROCNC

, N. C.CAROL I NA

HTRON

O O

RE

GI

ST

ER

ED

ARCHI TECTURAL C

RP

RATION

CERT. NO.

YA

TE

S-

CH

RE

SCO #22-25351-02A

NCCCS #2692

S:

\R ev it

Lo ca l F ile s\

9.

R

C C

C B ui ld in g

S2

Re no va tio ns _b illh yc ha rc h.

co m

.rv t

4/

/2

6:

:2

PM

22219.00

SECOND LEVEL

REFLECTED CEILING

PLAN - DEMOLITION

AD202

CONSTRUCTION DOCUMENTS

04-08-24

AD202 3/16" = 1'-0"

1 SECOND LEVEL REFLECTED CEILING PLAN - DEMOLITION

disenhour Area Measurement 1,696.92 sf disenhour Area Measurement

90.03 sf disenhour Area Measurement

90.22 sf disenhour Typewritten Text New ACT Grid and Tile In Yellow Area disenhour Area Measurement

82.87 sf

OS

F

OS

F

OS

F

OS

F

OS

F

OSOS

OSOSOS

S

OS

OS

F

OS

F

OS

OS F

F

OS

OSF

OS

F

S S

S

SSSS

S

S

S

S

SS S

S

S

S

S

SS

S

S

S

S

S S

PLAN

N

TRUE

N

A A

B B

C C

D D

E E

EXISTING WINDOW SHADES

TO REMAIN, TYPICAL

EXISTING GWB HEADER TO

REMAIN

NO CEILING WORK IN AREAS

SHOWN SHADED, TYPICAL

R RR R RR R RRR

R

RRRRRRRRR RR

R

R R R

R

RR

R

R R R

RRR

R

RRRR

R R R

D

R

R

R R

R R

R

R

C.3

C.0

C.0

C.1

C.3

REMOVE EXISTING CEILING MOUNTED

PROJECTORS, SPEAKERS AND CAMERAS,

RE-USE IN NEW WORK, SEE SHEET A203

AND ELECTRICAL DRAWINGS

C.3 C.3

C.3 C.3

C.3C.3C.3

C.1

C.3 C.3

C.3C.3

C.3C.3C.3

C.3

D

C.3C.3

C.3C.3

C.3

RRR

C.7 C.7

C.7

C.7 C.7

C.1

R

C.1

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

MEN

WOMEN

CORRIDOR

301A

CORRIDOR

301C

IDF

381A

IDF

CORRIDOR

ELEC.

OFFICE

314A

OFFICE

314B

OFFICE

314C

OFFICE

314D

OFFICE

314E

OFFICE

ELEV.

STOR.

OFFICE

308A

OFFICE

309A

STOR.

308B

ELEVATOR

LOBBY

ENTRANCE

202ENTRANCE

VESTIBULE

301E

CORRIDOR

301B

CORRIDOR

301D

C.1 C.1

C.0

C.1

C.1

C.0

C.1

C.0

EXISTING GWB ON SHAFT AT

ROOF LADDER TO REMAIN

C.0

C.1

C.1

C.1

R

C.1 C.1 C.1

C.7 C.7 C.8

C.1

C.8

C.1

C.1

C.1

C.1

REMOVE WALL MOUNTED ROLL DOWN

PROJECTION SCREENS AND RE-USE IN NEW

WORK, SEE SHEET A203

REMOVE EXISTING CEILING GRID AND TILE

SHOWN DOTTED

C.3

C.1

C.1

C.1 C.1

C.8

C.1

C.2 C.2

C.2 C.2

C.2 C.2

C.2 C.2 C.2

C.2C.2C.2

EXISTING GWB HEADER TO

REMAIN

C.1

C.1

C.2C.2

C.2C.2

C.2C.2

C.2C.2C.2

C.2 C.2 C.2

EXISTING GWB HEADER TO

REMAIN

EXISTING WINDOW SHADES

TO REMAIN, TYPICAL

REMOVE EXISTING CEILING

TILE, 2x2 GRID TO REMAIN

REMOVE EXISTING CEILING

TILE, 2x2 GRID TO REMAIN

REMOVE EXISTING CEILING MOUNTED

PROJECTORS, SPEAKERS AND CAMERAS,

RE-USE IN NEW WORK, SEE SHEET A203

REMOVE EXISTING CEILING GRID AND

TILE SHOWN DOTTED

REMOVE EXISTING LIGHT FIXTURES

SHOWN DOTTED AND RE-USE IN NEW

WORK, SEE SHEET A202 AND ELECTRICAL

DRAWINGS

C.0

C.2

C.2

C.2

C.2

C.2 C.2

C.2 C.2

C.2C.2

C.2 C.2

C.2

C.2

REMOVE ALL EXISTING DOWNLIGHTS

IN EXTERIOR GWB SOFFIT

REMOVE ALL EXISTING DOWNLIGHTS

IN EXTERIOR GWB SOFFIT

R

R R R

R RR R

CLASSROOM

CLASSROOM

CLASSROOM

WORK IN THIS AREA TO BE ALTERNATE #1

REMOVE EXISTING CEILING SPEAKERS AND

CAMERAS, RE-USE IN NEW WORK, SEE ELEC.

DWGS., TYPICAL

C

BASE BID FOR EXISTING CLASSROOMS 202, 204 AND 206:

REMOVE EXISTING CEILING TILES, EXISTING GRID TO REMAIN

C

REFLECTED CEILING PLAN KEYED NOTES

NO WORKC.0

REMOVE EXISTING CEILING TILES, EXISTING GRID TO REMAINC.1

REMOVE EXISTING LIGHT FIXTURE, SEE ELECTRICAL DRAWINGSC.2

REMOVE EXISTING LIGHT FIXTURE AND RE-USE IN NEW WORK, SEE ELECTRICAL DRAWINGSC.3

INFILL NEW CEILING GRID TEES TO MATCH EXISTING FOR 2X2 LAYOUT AND PROVIDE NEW CEILING TILE

NEW LIGHT FIXTURE, SEE ELECTRICAL DRAWINGS

EXISTING LIGHT FIXTURE RE-USED IN NEW LOCATION, SEE ELECTRICAL DRAWINGS

C.4

C.5

C.6

EXISTING CEILING MOUNTED PROJECTOR TO REMAIN, RELOCATE MOUNT SLIGHTLY AS

NECESSARY TO INSTALL NEW CEILING GRID TEES

C.7

EXISTING WALL MOUNTED ROLL DOWN SCREEN TO REMAINC.8

REMOVE EXISTING WALL MOUNTED ROLL DOWN SCREEN AND RE-USE IN NEW WORK.C.9

EXISTING WALL TO BE REMOVED

EXISTING WALL TO REMAIN

WALL LEGEND

NEW WALL

EXISTING 2 HR RATED WALL TO REMAIN

NOTE: WALL SYMBOLOGY FOR GRAPHICAL PURPOSES ONLY.

REFER TO PARTITION TYPES AND WALL SECTIONS FOR ACTUAL

WALL CONSTRUCTION.

EXISTING 1 HR RATED WALL TO REMAIN

NEW 1 HR RATED WALL

CEILING LEGEND

RECESSED LED DOWN LIGHT

2x4 RECESSED LED FIXTURE

2x2 RECESSED LED FIXTURE

SMOKE DETECTOR

OCCUPANCY SENSOROS

CEILING MOUNTED LIGHT

S

EXIT SIGN

DIRECTIONAL EXIT SIGN

UPRIGHT SPRINKLER HEAD

SPRINKLER HEAD MOUNTED IN CEILING

SUPPLY AIR DIFFUSER

RETURN AIR DIFFUSER /

EXHAUST GRILLE

LINEAR SUPPLY AIR DIFFUSER

INDICATES CEILING MOUNTED DEVICES, SPRINKLER HEADS, ETC. TO BE REMOVED

INDICATES CEILING MOUNTED DEVICES, SPRINKLER HEADS, ETC. TO BE RELOCATED

LOCATED IN CENTER OF NEW CEILING TILE, TYPICAL

R

SPEAKER WITH GRILLES

FIRE ALARM DEVICEF

CAMERAREFLECTED CEILING BASE BID / ALTERNATES

WORK SHOWN IN THE FOLLOWING ROOMS IS BASE BID: 307 308A 309A 314 314A 314B 314C 314D 314E

ALL OTHER WORK SHOWN ON THE REFLECTED CEILING PLAN IS TO BE ALTERNATE #2

ALTERNATE #1 - REMOVE ALL CEILING GRID, TILE, LIGHTS, DIFFUSERS, ETC. IN ROOMS 302 304 306

BASE BID FOR EXISTING CLASSROOMS: 302 304 306

REMOVE EXISTING CEILING TILES, EXISTING GRID, LIGHTS, DIFFUSERS, ETC. TO REMAIN

OWNERSHIP OF INSTRUMENTS OF SERVICE:

All reports, specifications, plans, computer files, field data, notes, and other documents and instruments of service shall remain the property of the Design Professional. The Design Professional shall retain all common law, statutory and other reserved rights, including the copyright thereto.

This drawing is the property of Yates - Chreitzberg - Hughes Architects and is not to be reproduced or copied in whole or any part. It is not to be used on any other project and is to be returned upon request.

© Copyright 2024

R C

C C

B ui dl in g S2

R en ov at io ns

T rin ity

C hu rc h

R d

C on co rd , N

C

CONSULTANT:

PROFESSIONAL SEALS:

CLIENT:

YCHA COM.#:

REVISIONS:

PHASE & DATE:

SHEET TITLE:

ARCHITECTURAL:

7035 NORTHWINDS DR NW

CONCORD, NC 28027

704.788.2000 www.ycharch.com

I T ZBERG - H UGH ES ARCH I TECTS

PA

O

DROCNC

, N. C.CAROL I NA

HTRON

O O

RE

GI

ST

ER

ED

ARCHI TECTURAL C

RP

RATION

CERT. NO.

YA

TE

S-

CH

RE

SCO #22-25351-02A

NCCCS #2692

S:

\R ev it

Lo ca l F ile s\

9.

R

C C

C B ui ld in g

S2

Re no va tio ns _b illh yc ha rc h.

co m

.rv t

4/

/2

6:

:3

PM

22219.00

THIRD LEVEL

REFLECTED CEILING

PLAN - DEMOLITION

AD203

CONSTRUCTION DOCUMENTS

04-08-24

AD203 3/16" = 1'-0"

1 THIRD LEVEL REFLECTED CEILING PLAN - DEMOLITION

disenhour Area Measurement 2,399.63 sf disenhour Area Measurement

289.45 sf disenhour Area Measurement

289.5 sf disenhour Area Measurement

207.42 sf disenhour Area Measurement

884.93 sf disenhour Area Measurement

874.93 sf disenhour Area Measurement 1,008.76 sf disenhour Area Measurement

885.03 sf disenhour Area Measurement 1,032.15 sf disenhour Area Measurement 1,853.87 sf disenhour Typewritten Text New ACT Tile Only In Blue Area disenhour Typewritten Text New ACT Grid and Tile In Yellow Area disenhour Area Measurement

81.73 sf disenhour Area Measurement

583.59 sf disenhour Area Measurement

602.39 sf disenhour Typewritten Text Price Pink Rooms as an Alternate

Facility Design Manual

Issue: November 15, 2020 College Standards Page 3-21 Revised: February 1, 2024

Level 3 This gypsum board finish is typically specified in appearance areas that will receive heavy or medium texture finishes before final painting or in areas where heavy-duty commercial-grade wallcoverings will be applied as the final decoration. Level 3 is not recommended for smooth wall designs or applications where light textures; non-continuous textures or lightweight wallcoverings will be applied. After wiping joints with a joint knife, leaving a thin layer of compound over all joints and interior angles, add a separate coat of joint compound over all joints and interior angles.

Cover fastener heads and accessories with two layers of joint compound.

Make sure the surface is smooth and free of tool marks.

Level 4 Finish Level 4 is typically specified in appearance areas where smooth wall designs are going to be decorated with flat paints, light textures or non-continuous textures or where wallcoverings will be applied. This level of finish is not recommended in spaces where non-flat or dark/deep-tone paints are going to be applied. As in previous levels, all joints and interior angles have tape embedded in the joint compound. After wiping joints with a joint knife, leaving a thin layer of compound over all joints, add two coats of joint compound over all flat joints. After wiping interior angles with a joint knife, leaving a thin layer of compound, add one separate coat of joint compound over interior angles. Cover fastener heads and accessories with three layers of joint compound. Make sure the surface is smooth and free of tool marks. If finishing glass mat or fiber-reinforced gypsum panels, check with the manufacturer for finishing recommendations.

Level 5 Gypsum board finishing Level 5 is typically specified in appearance areas where smooth wall designs are decorated with non-flat paints, glossy or decorative finishes, or dark/deep-tone paints or where critical lighting conditions occur. Level 5 provides a uniform surface and minimizes the possibility of joint photographing and/or fasteners showing through the final decoration. In Level 5, all joints and interior angles have tape embedded in the joint compound. All joints are then wiped with a joint knife, leaving a thin layer of compound over all joints and interior angles. Add two coats of joint compound over all flat joints. Add one coat of joint compound over interior angles. Cover fastener heads and accessories with three coats of joint compound. Apply a skim coat of joint compound or material manufactured for this purpose to the entire surface. Make sure the surface is smooth and free of tool marks.

3.9.2. Acoustical Tile Ceilings

Acoustical tile ceilings shall be exposed grid, lay-in system. Acoustical tiles shall be two feet square (2’x2’) lay-in tiles composed of non-combustible materials.

3.9.2.1. The standard Acoustical ceiling tile suspension systems shall be wide faces, double web, steel which are hot-dip galvanized with prefinished 15/16” flanges. They shall be rated for intermediate duty. Color: White. Acceptable manufacturers are Armstrong, USG, and Chicago Metallic Corporation.

3.9.2.2. The standard acoustical ceiling tiles shall be ¾” thick, white, mineral based, treated with mold/mildew inhibitor. They shall have a reflectance of no less than LR 0.83, with a Noise Reduction Coefficient (NRC) of 0.70, and a Ceiling Attenuation Class on not less than 40 Armstrong Tundra, medium texture with tegular edge shall be the basis of design. Acceptable

Facility Design Manual

Issue: November 15, 2020 College Standards Page 3-22 Revised: February 1, 2024 manufacturers are Armstrong, USG, and CertainTeed. 3.9.2.1. USG Frost™ ClimaPlus™ #414, 2'x2'x3/4", Shadowline Edge with Bevel – Flat White 050.

3.9.2.3. Open Office and Collaboration spaces will have ceilings with high NRC and CAC characteristics.

3.9.2.4. Class A “Fire-Rated” materials shall be specified to complete a UL fire-rated ceiling system for fire protection of structural components, where fire-rated assembly is required by Code.

3.9.3. Flooring

The following materials are preferred at the locations indicated:

3.9.3.1. Terrazzo or non-slip porcelain tile – high traffic areas such as lobbies and corridors.

At ornamental stairs, treads and risers shall match the adjacent materials with non-slip nosings.

3.9.3.2. Luxury Vinyl Tile (LVT) – low traffic lobbies and corridors, general purpose rooms, labs, classrooms where appropriate.

3.9.3.3. Carpet Tile – offices, conference rooms, auditorium aisles (with permanent seating), lounges, classrooms as appropriate, music or language listening rooms.

3.9.3.4. Porcelain Tile – restroom, bathrooms and showers.

3.9.3.5. Quarry Tile or Anti-bacterial Cement – food service areas.

3.9.3.6. Sealed Concrete – mechanical rooms, storage rooms, custodial rooms.

3.9.3.7. Raised, Removable Panels supported on interconnecting grids and pedestals, providing an under-floor plenum for air distribution and utilities may be utilized in Server Rooms, and other appropriate spaces.

3.9.3.8. Steel Trowel Finish Concrete – treads and risers with non-slip nosings for service and egress stairs.

3.9.3.9. Walk- off Carpet Tiles - building entrances.

3.9.4. Tile Carpeting

All carpet shall be selected from the North Carolina Qualified Products List (QPL) established by the State Purchasing Department.

Light colors (such as white, yellow, or gold) and solid colors which immediately show all traffic patterns and any stain must be avoided.

All carpet to be 24” x 24” tiles to facilitate replacement of damaged carpet and storage of attic stock.

Use of broadloom carpet must be approved by the College.

All newly carpeted areas shall be appropriately covered with plastic or brown paper to protect the carpet from construction debris. Carpet shall be in clean, like new condition when turned over to the College.

Tile carpeting with a hard composition backing, but not containing PVC, is preferred for public spaces where floor access is desirable and for ease of repair. A mixed pattern with high soil and stain hiding capabilities is preferred.

3.9.4.1. Carpet Specification Requirements

File details come from the government source that posted it. Updated .