12-Ticket and Gate Area Drawings.pdf

PDF 4 MB Posted

Attached to
Airport Common Use Passenger Processing System (CUPPS)
Solicitation number
025-26-AIR-RFP
Issued by
Cameron County, Texas

About this file

This file contains architectural and electrical drawings for the Brownsville South Padre Island International Airport (BRO) New Passenger Terminal project, specifically detailing ticket and gate area millwork and associated power infrastructure. The drawings include comprehensive plans, elevations, and sections for ticket counter millwork (IM4-510), gate counter millwork (IM4-511), and electrical power distribution for Level 1 and Level 2 of the terminal. The ticket counter design incorporates ADA-compliant stations, Parabit camera enclosures, and clear spaces for airline inserts, while the gate counter millwork includes stainless steel components, fire-retardant-treated plywood with plastic laminate, and monitor mounting provisions. The electrical drawings (EP1-113 and EP1-208) specify power requirements for ticketing and gate operations, including receptacles, conduit routing, panel connections, and dedicated circuits for equipment such as FIDS monitors, Parabit encoders, and various operational systems. The project involves coordination between multiple design disciplines including architecture, electrical, technology, and security systems.

The drawings reflect significant design development with multiple revisions issued between November 2018 and October 2020, including updates for Parabit equipment integration and other requested field modifications. The electrical infrastructure incorporates distributed power panels (1RP3B, 2RP2B, and specialized UPS and ATO panels) with detailed specifications for conduit sizing, circuit numbering, and mounting heights. The millwork specifications reference additional FF&E drawing packages and coordinate with manufacturer specifications for camera enclosures and related equipment. The project establishes infrastructure to support the Common Use Passenger Processing System (CUPPS) procurement objective, with integrated power and data provisions throughout the ticket and gate areas to accommodate future technology implementation and operational systems required for comprehensive passenger processing capabilities.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

6U

AL

6U

AL

6U

AL

6U

AL

3/ IM4-510

2/ IM4-510

/ I

M

-5

/ I

M

-5

IM4-510

CLEAR SPACE FOR ARILINE

INSERTS

CLEAR

7'-2 1/4"

'-3

/2

'-6

/2

/4

CLEAR SPACE FOR ARILINE

INSERTS

'-7

/4

'-0

STS-1

/ I

M

-5

/ I

M

-5

IM4-510

IM4-510

PARABIT

COUNTER-MOUNTED

CAMERA ENCLOSURE.

REFER

MANUFACTURER

SPECIFICATIONS AND

ELEC/TELECOM

DRAWINGS FOR

ADDITIONAL

REQUIREMENTS.

L1 - TICKETING LEVEL

FINISH FLOOR (3/8")

100' - 0 3/8"

IM4-510

IM4-510

CLEAR SPACE FOR INSERTS

1 1/2"

CLEAR

7'-4 1/4"1 1/2"

TYP

1"

7'-9 1/4"

C

LE

A R

'-6

/4

/4

'-6

/4

/2

'-0

/2

CLEAR SPACE FOR INSERTS

POWER AND DATA,

COORDINATE WITH

ELECTRICAL AND

TECHNOLOGY

2'-5 1/8" 2'-6" 2'-5 1/8"

STS-1

STS-1

SS-1

ALL EXPOSED

SURFACES ON AGENT

SIDE TO BE PL-7 U.N.O

'-6

/2

/2

'-0

3'-0"

TYP.

1"

SB-1

STS-1

SS-1

2'-10"

2'-7"

IM4-516

TICKETING SCALE.

REFERENCE FF&E

DRAWING PACKAGE

TICKETING SCALE.

REFERENCE FF&E

DRAWING PACKAGE

2'-11" 1'-6" 2'-11"

'-6

DEMO AND

INSTALL ACCESS

PANEL FOR

HUE/FA54 BOX

DEMO AND

INSTALL ACCESS

PANEL FOR

HUE/FA54 BOX

2'-11" 1'-6" 2'-11"

'-6

3 1/2" EQ EQ 3 1/2" EQ EQ

L1 - TICKETING LEVEL

FINISH FLOOR (3/8")

100' - 0 3/8"

/2

'-7

/2

/2

'-0

/2

'-2

/2

/2

'-8

/2

4"

2 1/2" 2'-7 1/2" 3 1/2"

3'-3 1/2"

3'-1 1/2"

SB-2

STS-1

SS-1

SS-1

L1 - TICKETING LEVEL

FINISH FLOOR (3/8")

100' - 0 3/8"

IM4-510

SS-1

STS-1

PL-4

SB-1

PL-4

SS-1

SS-1

PL-4

SB-2STS-1STS-1

2'-10"2'-6"7'-7 1/4"2'-6"7'-7 1/4"2'-6"

7'-4 1/4"

'-2

/2

'-1

T Y

P

/2

'-0

/2

'-1

/2

7'-9 1/4"

1"

IM4-510

IM4-510

OPEN TO BEYOND

3'-0"

'-0

/2

'-6

/2

2'-7"1 1/2"

TYP.

1"

IM4-516

/2

STS-1

L1 - TICKETING LEVEL

FINISH FLOOR (3/8")

100' - 0 3/8"

4"

/2

1"

TYP.

1" 1"

CLEAR FOR AIRLINE INSERTS

2'-2"

11 1/2" 1'-5" 9"

8"3 1/2"

4 3/4"3 1/2"

'-6

D E

M O

A N

D

IN

S T

A

LL

A

C C

E S

S P

A N

E L

F O

R

H U

E /F

A

B O

X

5 3/4"

(F A

L1 - TICKETING LEVEL

FINISH FLOOR (3/8")

100' - 0 3/8"

1'-10"

2'-0"

TYP.

1"

STS-1

STS-1

SS-1

'-1

/2

/2

'-0

L1 - TICKETING LEVEL

FINISH FLOOR (3/8")

100' - 0 3/8"

STS-1

2'-0"

1'-5 1/2"

'-1

/2

/2

'-0

5"

1 1/2"

AGENT SIDEPASSENGER SIDE

CORGAN ASSOCIATES, INC.

401 NORTH HOUSTON STREET

DALLAS, TEXAS 75202

SM

CH2M PROJECT NO.:

DRAWN:

DESIGNED:

APPROVED:

DATE ISSUED:

CH2M HILL ENGINEERS, INC.

12750 MERIT DRIVE SUITE 1100

DALLAS, TX 75251-1302

REGISTRATION #F-3699

A M

E L

IA

E A

R H

A R

T D

R

IV

E

B

O W

N S

V

IL

L E

T

E X

A S

B R

O W

N S

V

IL

L E

S O

U T

H P

A D

R E

I S

L A

N D

IN

T

E R

N A

T

IO

N A

L A

IR

P

O R

T

SHEET NUMBER:

ARCHITECTURAL

NEW PASSENGER

TERMINAL

CHECKED:

SCALE:

PROJECT TITLE:

SHEET TITLE:

/2 /2

:3

:1

P

M

1" = 1'-0"

Author

Designer

Approver

04/09/18

16102.0000

TICKET COUNTER

MILLWORK

IM4-510

Checker

1" = 1'-0"

AE1-113

1 TICKET COUNTER - ENLARGED PLAN

1" = 1'-0"

IM4-510

3 TICKET COUNTER - BACK ELEVATION

1" = 1'-0"

IM4-510

4 TICKET COUNTER - SIDE ELEVATION

1" = 1'-0"

IM4-510

2 TICKET COUNTER - FRONT ELEVATION

1" = 1'-0"

IM4-510

5 TICKET COUNTER - SECTION

1" = 1'-0"

IM4-510

7 ADA COUNTER - ELEVATION

1" = 1'-0"

IM4-510

6 ADA COUNTER - SECTION

NO. REVISION OR ISSUE DATE BY

0 ISSUE FOR CONSTRUCTION 11/26/2018

1 RFI 432 - PARABIT

EQUIPMENT

10/02/2020

10/02/2020

BR

O

6BR

O

L2 - DEPARTURES LEVEL

FINISH FLOOR (14'-0 3/8")

114' - 0 3/8"

IM4-510

IM4-510

IM4-516

ST-3

PL-4

SS-1

SS-1

7'-11 1/2"2'-1 1/2"

1 1/2" 1 1/2"7'-8 1/2"1 1/2"

TYP.

1"

'-2

/2

'-1

'-0

L2 - DEPARTURES LEVEL

FINISH FLOOR (14'-0 3/8")

114' - 0 3/8"

SS-1

7'-7 1/4"

CLEAR SPACE FOR INSERTS

7'-4 1/4"

/4

'-6

/4

POWER AND DATA,

COORDINATE WITH

ELECTRICAL AND

TECHNOLOGY

IM4-510

IM4-510

TYP.

1"

7'-9 1/4"

2'-5" 2'-6" 2'-5"

'-0

/2

'-0

'-0

/2

ST-3

SS-1

DEMO AND INSTALL

ACCESS PANEL

FOR HUE/FA54 BOX

'-6

2'-11" 1'-6" 2'-11"

3'-3 1/2"

EQ EQ

L2 - DEPARTURES LEVEL

FINISH FLOOR (14'-0 3/8")

114' - 0 3/8"

IM4-511

MILLWORK LOCK.

REFER TO SPEC FOR

TYPE

RECESSED PULL.

REFER TO SPEC FOR

TYPE

ST-3

PL-7

ST-3

ST-3

'-6

'-1

2'-0" 6"

1/4" -20 JOINT

CONNECTING NUTS

AND THREADED STUD

14 GA STAINLESS

STEEL ANGLE

MONITOR. REFER TO

ELECTRICAL AND

TECHNOLOGY

DRAWINGS

3/4"

FIRE-RETARDANT-TREATED

PLYWOOD WITH

PLASTIC LAMINATE ON

BOTH SIDES

L2 - DEPARTURES LEVEL

FINISH FLOOR (14'-0 3/8")

114' - 0 3/8"

IM4-511

IM4-511

ST-3

PL-7

PL-7

ST-3

/2

'-3

/2

'-7

8'-6"

L2 - DEPARTURES LEVEL

FINISH FLOOR (14'-0 3/8")

114' - 0 3/8"

IM4-511

IM4-511

ST-3

PL-7

ST-3

MONITOR. REFER TO

ELECTRICAL AND

TECHNOLOGY

DRAWINGS

'-6

'-9

/2

/2

'-7

L2 - DEPARTURES LEVEL

FINISH FLOOR (14'-0 3/8")

114' - 0 3/8"

IM4-511

PL-7

ST-3

ST-3

'-6

'-1

2'-0" 6"

IM4-511

V .I.

F

V A

R

IE

S

EQ EQ

'-0

IM4-511

2'-3" 2'-3"

14 GA STAINLESS

STEEL ANGLE

1/4" -20 JOINT

CONNECTING NUTS

AND THREADED STUD

#10 X 5/8" SELF

DRILLING SCREWS

4/ IM4-511

3/ IM4-511

MONITOR. REFER TO

ELECTRICAL AND

TECHNOLOGY

DRAWINGS

3 1/2"

CLEAR

7'-2 1/4" 3 1/2"

7'-9 1/4"

IM4-511

2/ IM4-511

SS-1

SS-1

/ I

M

-5

SS-1

ST-3

ST-3

PL-7

V

IF

V A

R

IE

S

PARABIT

COUNTER-MOUNTED

CAMERA ENCLOSURE.

REFER

MANUFACTURER

SPECIFICATIONS AND

ELEC/TELECOM

DRAWINGS FOR

ADDITIONAL

REQUIREMENTS.

CORGAN ASSOCIATES, INC.

401 NORTH HOUSTON STREET

DALLAS, TEXAS 75202

SM

CH2M PROJECT NO.:

DRAWN:

DESIGNED:

APPROVED:

DATE ISSUED:

CH2M HILL ENGINEERS, INC.

12750 MERIT DRIVE SUITE 1100

DALLAS, TX 75251-1302

REGISTRATION #F-3699

A M

E L

IA

E A

R H

A R

T D

R

O W

N S

V

IL

L E

T

E X

A S

B R

O W

N S

V

IL

L E

S O

U T

H P

A D

R E

I S

L A

N D

IN

T

E R

N A

T

IO

N A

L A

IR

P

O R

T

SHEET NUMBER:

ARCHITECTURAL

NEW PASSENGER

TERMINAL

CHECKED:

SCALE:

PROJECT TITLE:

SHEET TITLE:

/2 /2

:3

:1

P

M

As indicated

Author

Designer

Approver

04/30/18

16102.0000

GATE COUNTER

MILLWORK

IM4-511

Checker

1" = 1'-0"

IM4-511

2 GATE COUNTER ELEVATION

1" = 1'-0"

IM4-511

3 GATE COUNTER ELEVATION

1" = 1'-0"

IM4-511

7 GATE COUNTER WALL - ELEVATION

1" = 1'-0"

5 GATE COUNTER WALL - REAR ELEVATION

1" = 1'-0"

IM4-511

4 GATE COUNTER WALL - ELEVATION

1" = 1'-0"

IM4-511

8 GATE COUNTER WALL - SIDE ELEVATION

1" = 1'-0"

IM4-511

6 GATE COUNTER WALL - PLAN SECTION

NO. REVISION OR ISSUE DATE BY

0 ISSUE FOR CONSTRUCTION 11/26/2018

1 REV 1 - PERMIT REVIEW

COMMENTS

11/29/2018

2 RFI 432 - PARABIT

EQUIPMENT

10/02/2020

3" = 1'-0"

IM4-511

9 GATE COUNTER PARTITION DETAIL

1" = 1'-0"

AE1-207

1 GATECOUNTER - ENLARGED PLAN

10/02/2020

REF.

M

M

J

J

J

J

J

J

J

J

J

FIDS

10 9 8 7 6 5 4

C

E

J

E.7

H

G

EE4-001

EE4-001

AIRPORT

OPERATIONS

AIRLINE

OFFICES

ELECTRICAL

BADGING

OFFICE

IT ROOM

CIRCULATION

MAINTENANCE

OFFICE AND

WORKSTATION

MAINTENANCE

BREAKROOM

ATO

ADMIN/SUPER

OFFICE

1115D

TICKETING AND

CHECK-IN

AIRPORT IT

PLANTER

VESTIBULE

(TYP.)

PRIMARY

SCREENING

(TYP.)

F

CBIS

GENERAL

OFFICES

PORT

DIRECTOR'S

OFFICE

CBP

ELECTRICAL

EE4-001

EE4-001

1RP3B-22

1RP3B-22

1RP3B-23

1RP2B-7

1RP2A-15

1RP2B-10

+6"

1RP2A-11

+6"

1RP2A-13

+6"

1RP2A-13

+6"

1RP2A-15

+6"

1RP2A-15

1GRP2A-2

+80"

UPS-1RP1-9

+80"

UPS-1RP1-15

+80"

UPS-1RP1-19

1RP2B-3 1RP2B-3 1RP2B-3 1RP2B-3

24 26

1RP3B-20

1RP3B-18

1GRP2A-6

1GRP2A-4

+80"

UPS-1RP1-11

+80"

UPS-1RP1-13

+80"

UPS-1RP1-17

1GRP2A-2

1GRP2A-2

+6"

1RP2A-11

1RP2B-5

2#10, 1#10G - 3/4"C

1PP4-12

2#12, 1#12G - 3/4"C

1PP4-8

2#12, 1#12G - 3/4"C

1PP4-7,9,11

4#12,1#12G - 3/4"C

1PP4-1,3,5

4#12,1#12G - 3/4"C

1PP4-12

2#12, 1#12G - 3/4"C

1PP4-12

2#12, 1#12G - 3/4"C

1PP4-16

2#12, 1#12G - 3/4"C

1PP4-13,15,17

4#12,1#12G - 3/4"C

FCU-1-D9

FCU-1-B9

FCU-1-C8

FCU-1-C9

FCU-1-D11

FCU-1-D10

FCU-1-D8

FCU-1-E4

1GP2-5

2#12, 1#12G - 3/4"C

FCU-1-D4

WEAPON

STORAGE

AIRLINE

OFFICES

STORAGE

CIRCULATION

MAINTENANCE

STORAGE

WOMEN'S

RESTROOM

LOCKERS

AIRLINE

OFFICES

CIRCULATION

1RP2A-36

1RP2A-21

U P

S -1

R P

-2

U P

S -1

R P

-2

U P

S -1

R P

-2

U P

S -1

R P

-2

U P

S -1

R P

-3

U P

S -1

R P

-2

U P

S -1

R P

-2

U P

S -1

R P

-2

U P

S -1

R P

-2

U P

S -1

R P

-2

U P

S -1

R P

-3

U P

S -1

R P

-2

SF-1-F6

1RP3B-29

2#12, 1#12G - 3/4"C

+48"

31 31 27

1RP3B-22

+48"

FCU-1-C10

1RP3B-23

CIRCULATION

AIRLINE

OFFICES

+110"

CBP-1RP1-22

+110"

CBP-1RP1-22

+110"

CBP-1RP1-22

+110"

CBP-1RP1-24

+110"

CBP-1RP1-24

+110"

CBP-1RP1-24

D

+6"

1RP2A-11

+6"

1RP2A-11

+6"

1RP2A-13

+6"

1RP2A-13

1RP2A-23

1RP3B-24

1RP2B-7

1RP2B-71RP2B-7

1RP2B-9

GFI,+42"

1RP3A-6

1RP3B-21

MX LOCKER

1RP2B-11 1RP2B-11

1GRP1-12

1RP3B-15

2#12, 1#12G - 3/4"C

1RP2B-17

2#12, 1#12G - 3/4"C

1RP2B-18

2#6, 1#6G - 1"C

1RP2B-14

2#12, 1#12G - 3/4"C

1RP2B-16

2#6, 1#6G - 1"C

1GRP3-16

2#12, 1#12G - 3/4"C

17 17

1GP2-2,4,6

4#12,1#12G - 3/4"C

1RP2A-19

(TYP) (TYP) (TYP)

20 20 20 20 20

(TYP)

UPS-1RP1-33

CANOPY

GFI,+42"

1RP3A-6

FCU-1-B10

1GRP3-24

2#12, 1#12G - 3/4"C

1GRP2A-18

1GRP2A-18

1RP3A-8

1RP3A-8

1RP3A-8

1RP3A-8

CDP-1

ATO GM OFFICE

1115C

ATO BREAK

AREA

1115B

ATO STORAGE

AREA

1115F

ATO COMPUTER

WORKSTATION

1115E

ATO LOCKER

AREA

1115A

+66"

GFI

+42"

GFI

+42"

GFI

+48"

+48"

GFI

+48"

GFI

GFI

+48"

GFI

+48"

+66"

29 29

2 2

+66"

+66"

+42"

MICROWAVE

COFFEE

MACHINE

PRINTER

POWER FOR

SIGNAGE

TIME CLOCK

PANEL AA ATO

PANEL

UA ATO

HH

HH

2#10,1#10G IN 1"C FOR

POWER TO KIOSK FROM

PANEL 1RP3B, CKT #30

(1) 1"C TO KIOSK (COMM) (1) 1"C TO NORTH END OF

COMMERCIAL CANOPY (COMM)

(1) 1"C TO SOUTH END OF

COMMERCIAL CANOPY (COMM)

SOUTH KIOSK

COMMUNICATION HANDHOLE

REFER TO SITE PACKAGE

PHASE 2 DETAIL 2, DRAWING

ES2-201

POWER HANDHOLE REFER

TO SITE PACKAGE PHASE 2

DETAIL 2, DRAWING ES2-201

(1) 2"C FROM CANOPY TO

HANDHOLE FOR COMM

2#10,1#10G IN 1"C

FOR POWER TO

LIGHTING

2#10,1#10G IN 1"C

FOR POWER TO

LIGHTING

2#10,1#10G IN 1"C FOR

POWER TO KIOSK FROM

PANEL 1RP3B, CKT #30

(1) 1"C FROM CANOPY

COLUMN TO POWER

HANDHOLE

PRIMARY

SCREENING

S E

E S

H E

E T

E P

-1

S E

E S

H E

E T

E P

-1

S E

E S

H E

E T

E P

-1

S E

E S

H E

E T

E P

-1

S E

E S

H E

E T

E P

-1

UPS-1RP1-35

33 1RP2B-73

CBP-1RP1-1

34 34 34

UPS-1RP1-29UPS-1RP1-25UPS-1RP1-21

3 3 3

1RP2A-34

363636

CBP-1RP1-6

CBP-1RP1-2

CBP-1RP1-4

CBP-1RP1-20

CBP-1RP1-16

CBP-1RP1-18

1. REFER TO DWG. EE0-100 FOR

ABBREVIATIONS, LEGENDS AND

GENERAL NOTES.

2. UNO, CONTRACTOR TO USE 2#12, #

12G - 3/4"C FOR ALL GENERAL

PURPOSE RECEPTACLES SHOWN ON

THIS DWG.

3. UNO, ALL GENERAL PURPOSE

RECEPTACLES SHOWN ON THIS

SHEET SHALL BE MOUNTED AT 18"

AFF.

4. UNO, ALL GENERAL PURPOSE

RECEPTACLES SHOWN ON THIS DWG.

ARE TO PANEL 1RP3A.

GENERAL NOTES

LEGEND

1GRP1- 5

PANEL NAME

CIRCUIT

NUMBER

SM

N

CH2M PROJECT NO.:

DRAWN:

DESIGNED:

APPROVED:

DATE ISSUED:

CH2M HILL ENGINEERS, INC.

12750 MERIT DRIVE SUITE 1100

DALLAS, TX 75251-1302

REGISTRATION #F-3699

A

M E

L

IA

E A

R H

A R

T D

R

O W

N S

V

IL

L E

T

E X

A S

B R

O W

N S

V

IL

L E

S O

U T

H P

A D

R E

I S

L A

N D

IN

T

E R

N A

T

IO

N A

L A

IR

P

O R

T

SHEET NUMBER:

ELECTRICAL

01 02 03 04

KEY PLAN

NEW PASSENGER

TERMINAL

CHECKED:

SCALE:

PROJECT TITLE:

SHEET TITLE:

TRUE

NORTH

06 07 08 09

11 12 13 14

16 17 18 19

/5 /2

:4

:4

A

M C

A u to d e s k \1

-B

R O

-E L

-T E

-R

R E

B E

C C

A .S

O N

T H

E

IM

E R

.r v t

As indicated

T.ROOKER

R.LEAZURE

R.LEAZURE

12/30/19

423356

FLOOR PLAN LEVEL

1 SECTOR 13 POWER

EP1-113

C.ZARNAGHIAN

- 1/8" = 1'-0"

1 LEVEL 1 -SECTOR 13 - POWER

8 0 8

Scale: 1/8 INCH = 1 FOOT

KEYED NOTES

1 ALL GENERAL PURPOSE RECEPTACLE(S) IN

THE ROOM ARE TO PANEL 1GRP2A.

2 CONDUIT STUB-UPS FOR POWER AND DATA

TO TICKETING COUNTER MILLWORK.

COORDINATE EXACT LOCATION OF

STUB-UPS WITH MILLWORK PROVIDER.

3 DEMOLISH POWER AND DATA STUB UPS

AND PULL BACK CONDUCTORS TO THE

EDGE OF THE CONCRETE REMOVAL.

EXTEND NEW CONDUIT AND EXISTING

CONDUCTORS TO NEW FIS PODIUM

LOCATIONS. REFER TO KEYED NOTE 36 ON

THIS DRAWING.

4 6" FLOOR MOUNTED BOX WITH (1) DUPLEX

RECEPTACLE FOR POWER AND (1) GANG

SPACE WITH 6 PORTS FOR DATA. PROVIDE

3/4" POWER CONDUIT AND 1" DATA CONDUIT

FROM DESIGNATED SOURCES. REFER TO

TECHNOLOGY PACKAGE FOR DETAILS ON

DATA PORTS AND CABLES.

5 DEDICATED GFI RECEPTACLE. MOUNT AT

42" AFF.

6 BHS MCP-OB1.

7 FLOOR MOUNTED BOX FOR POWER AND

DATA TO INFORMATION DESK.

8 RECEPTACLE FOR MONITOR.

9 MANUAL SWITCH FOR GARBAGE DISPOSAL

MOUNTED AT +42" AFF.

10 MOTOR RATED SWITCH FURNISHED WITH

EQUIPMENT.

11 STUB UP CONDUITS INSIDE COLUMN AND

ROUTE INSIDE CANOPY SPACE TO FEED

LIGHTS AND SECURITY/TECH EQUIPMENT.

REFER TO DETAIL 3 ON STRUCTURAL DWG.

SE5-003 FOR DETAILS.

12 ALL GENERAL PURPOSE RECEPTACLE(S) IN

THE ROOM ARE TO PANEL 1RP3B.

13 RECEPTACLE FOR ADVERTISING BOARD

SIGN. MOUNT +60" AFF.

14 J-BOX FOR POWER TO AIRLINE OFFICES.

PROVIDE (1) 2" EMPTY CONDUIT ROUTED

OVERHEAD TO ELECTRICAL ROOM.

15 J-BOX ABOVE CEILING FOR POWER TO

DOOR OPERATOR. REFER TO DETAIL 3 ON

SECURITY DWG. TY5-100 FOR DETAILS.

COORDIANTE THE EXACT LOCATION OF

J-BOX WITH SECURITY CONTRACTOR.

16 RECEPTACLE TO BE MOUNTED ON

UNISTRUT SUPPORT AT 12" AFG.

COORDINATE WITH BHS EQUIPMENT

PROVIDER. SECURE SUPPORT TO FLOOR

USING 4-HOLE BASE PLATE AND EXPANSION

ANCHORS INTO FLOOR.

17 J-BOX FOR SAGEGLASS CONTROL PANEL.

18 J-BOX FOR POWER TO SLIDING DOORS.

19 J-BOX FOR POWER TO AIRLINE OFFICES.

PROVIDE (1) 1" EMPTY CONDUIT ROUTED

OVERHEAD TO ELECTRICAL ROOM.

20 3/4" POWER CONDUIT AND 1 1/2" DATA

CONDUIT ROUTED UNDER SLAB.

21 (1) 1" UNDERGROUND POWER CONDUIT AND

(1) 2" DATA/SECURITY UNDERGROUND

CONDUIT UNDER SLAB ROUTED TO

CANOPY.

22 DEDICATED RECEPTACLE FOR FIDS.

COORDINATE WITH MILLWORK PROVIDER

FOR RECEPTACLE MOUNTING LOCATION.

23 RECEPTACLE FOR POWER TO PAPER

TOWEL DISPENSER. MOUNT RECEPTACLE

RECESSED INTO THE WALL ADJACENT TO

UNIT. COORDINATE EXACT LOCATION

(INCLUDING MOUNTING HEIGHT) OF

RECEPTACLE WITH DISPENSER PROVIDER

PRIOR TO UNIT INSTALLATION.

24 REFER TO DETAIL 7 ON DWG. EE5-001 FOR

FAN CONTROL SCHEMATIC.

25 J-BOX FOR CONDENSATE PUMP

CONNECTION. REFER TO MH6-002 FOR

PUMP SCHEDULE.

26 RECEPTACLE FOR TV MONITOR.

27 RECEPTACLE FOR POWER FEED TO CBP

DISPLAY.

28 RECEPTACLE FOR CBIS FIELD DATA

REPORTING STATION (FDRS).

29 ALL GENERAL PURPOSE RECEPTACLE(S) IN

THE ROOM ARE TO PANEL UA ATO.

30 ALL GENERAL PURPOSE RECEPTACLE(S) IN

THE ROOM ARE TO PANEL AA ATO.

31 GFCI RECEPTACLE FOR REFRIGERATOR.

MOUNT AT +48" AFF.

32 PROVIDE LIGHTNING PROTECTION FOR THE

CANOPY PER SPECIFICATION SECTION 26 41

00.

33 2#12, 1#12G IN 3/4"C TO AXIS FA54 ENCODER

WALL-MOUNTED. COORDINATE LOCATION

WITH PARABIT.

34 2#12, 1#12G IN 3/4"C TO AXIS FA54 ENCODER

LOCATED AT THE TICKETING COUNTER.

COORDINATE LOCATION WITH PARABIT.

35 1/2" CONDUITS FROM DATA AND POWER

SIDES OF FLOOR BOX TO PARABIT BACK

WALL DISPLAY. EXTEND CONDUITS UP TO

DISPLAY JUNCTION BOXES. COORDINATE

JUNCTION BOX LOCATIONS WITH PARABIT

PRIOR TO INSTALLATION.

36 STUB UP 3/4" POWER AND 1 1/2" DATA

CONDUIT TO FIS PODIUM. REFER TO KEYED

NOTE 3 ON THIS DRAWING. COORDINATE

LOCATION WITH PARABIT.

NO. REVISION OR ISSUE DATE BY

0 ISSUE FOR CONSTRUCTION 11/26/18 REL

1 RFI 166 08/09/19 REL

2 PCR 04 UA/PCR 04A AA/PCR

05A CANOPY

01/20/20 REL

3 RFI 0432 PARABIT

EQUIPMENT

10/02/20 REL

10-02-2020

Additional ticket counter is here emmanuel.mena Text Box

RFI 0450_POWER TO TOWEL DISPENSERS TA-11

emmanuel.mena Cloud+ emmanuel.mena Cloud+

RFI 0451_ELECTRICAL REQUIREMENTS FOR ESCALATORS

emmanuel.mena Cloud+ emmanuel.mena Cloud+ RFI 0469_RM 1119 Food Waste Disposal emmanuel.mena Cloud+ emmanuel.mena Cloud+ RFI 0474_Power to Signage emmanuel.mena Cloud+ emmanuel.mena Cloud+ RFI 0474_Power to Signage

Lorena Cardona Rectangle

Lorena Cardona Rectangle

Lorena Cardona Rectangle

Lorena Cardona Rectangle

Lorena Cardona Oval

M

M

M

FIDS

GATE

FIDS

G A

T E

J

J

JJ

J

J

M

M

M

M

M M

M

J

G

ID

S

0.2

KVA

10 9 8 7 6 5 4

B

C

A

4.9

EE4-002

EE4-002

CIRCULATION

BREAKROOM

SHARED

OFFICES

CORRIDOR

ELECTRICAL

NURSING ROOM

CHASE

WOMEN'S

RESTROOM

PET RELIEF

JANITOR

MEN'S

RESTROOM

FAMILY

RESTROOM

CONCESSIONS

CIRCULATION

CIRCULATION

OUTBOUND

SEARCH

VERTICAL

CIRCULATION

CHASE

PRIVATE

SCREENING

ROOM

(TYP.)

FPTU-2-A9

FPTU-2-B9

2PP7-14,16,18

4#12,1#12G - 3/4"C

FPTU-2-A7 2PP2-8,10,12

4#10, 1#10G - 3/4"C

FPTU-2-B7

2PP2-13,15,17

4#12,1#12G - 3/4"C

FCU-2-B6

2PP2-19,21,23

4#12,1#12G - 3/4"C 2PP2-33

2#12, 1#12G - 3/4"C

FCU-2-C8

2PP5-4

2#12,1#12G - 3/4"C

2PP5-19,21,23

4#12,1#12G - 3/4"C

FCU-2-C10

2PP5-7,9,11

4#12,1#12G - 3/4"C

FPTU-2-B11

FPTU-2-A5

2PP2-20,22,24

4#10, 1#10G - 3/4"C

2RP1B-20

GFI,+42"

2RP4-21 21

+80"

2RP1A-11

2RP1B-20

2RP1B-20

2RP1B-20

GFI

GFI,+42"

+6"

2RP2A-22

2GRP1-15

GFI

+6"

2RP2A-22

2GRP1-15

2RP1A-10

2RP2A-26

2#12, 1#12G - 3/4"C

2RP2A-28

2#12,1#12G-3/4"C

2GRP1-9

2GRP1-5

2GRP1-5

GFI

FCU-2-B7

2PP2-31

2#12,1#12G-3/4"C

2RP2B-9

2RP1A-15

2#12, 1#12G - 3/4"C

2RP2B-9

CIRCULATION

HOLDROOM

IT

ELECTRICAL

ROOM

CONCESSIONS

GFI,+42"

9 12

FCU-2-C4

+48"

AHU-1

(TYP.)

2PP2-19,21,23

4#12,1#12G - 3/4"C

FCU-2-B4

FPTU-2-B5

2PP2-14,16,18

4#12,1#12G - 3/4"C

EE4-002

UPS-2RP2-16

2GRP1-12

2GRP1-10

EE4-002

STSO

2065A

COMM

STORAGE

OLC TRAINING

STSO

CHASE

2GRP1-13

2#12, 1#12G - 3/4"C

CHASE

2GRP1-6

2#12, 1#12G - 3/4"C

FCU-2-C9

GFI,+42"

18 GFI,+42"

GFI,+42"

GFI,+42"

23 23 23

13 13

2RP2B-15

2RP2B-18

2#12,1#12G-3/4"C

2RP2B-18

2#12,1#12G-3/4"C

2RP2B-17

2#12, 1#12G - 3/4"C

2RP2B-17

2#12,1#12G-3/4"C

G

R P

-1

GFI,+42"

GFI

EWC-1

2RP4-30

2PP7-7,9,11

4#12,1#12G-3/4"C

2PP7-13,15,17

4#12,1#12G-3/4"C

2GRP1-13

2#12, 1#12G - 3/4"C

2RP4-13

2RP4-15 2RP4-19

2RP4-17 2RP2A-1

2RP2A-3 2RP2A-7

2RP2A-5 2RP2A-9

2RP2A-11 2RP2A-15

2RP2A-13 2RP2A-17

2RP2A-19 2RP2A-23

2RP2A-21 2RP2A-25

2RP2A-27 2RP2A-31

2RP2A-29

2RP2A-35

2RP2A-33

2RP2A-2 2RP2A-4

2RP2A-12

2RP2A-10

2RP2A-16

2RP2A-14

2RP2B-11

11 11 26

11 11

UPS-2RP2-15

WH-2

SEE SHEET EP1-213

S E

E S

H E

E T

E P

-2

SEE SHEET EP1-207

SEE SHEET EP1-213SEE SHEET EP1-212 SEE SHEET EP1-213

SEE SHEET EP1-209

2RP2B-9

32 2

UPS-2RP1-11

EF-2-B3

2RP2A-22

UPS-2RP2-9

2RP2A-6

2GRP1-152

UPS-2RP1-3

UPS-2RP1-7

UPS-2RP1-9

LEGEND

1GRP1- 5

PANEL NAME

CIRCUIT

NUMBER

1. REFER TO DWG. EE0-100 FOR

ABBREVIATIONS, LEGENDS AND

GENERAL NOTES.

2. UNO, CONTRACTOR TO USE 2#12, #

12G - 3/4"C FOR ALL GENERAL

PURPOSE RECEPTACLES SHOWN ON

THIS DWG.

3. UNO, ALL GENERAL PURPOSE

RECEPTACLES SHOWN ON THIS

SHEET SHALL BE MOUNTED AT 18"

AFF.

4. UNO, ALL GENERAL PURPOSE

RECEPTACLES SHOWN ON THIS DWG.

ARE TO PANEL 2RP2B

GENERAL NOTES

SM

N

CH2M PROJECT NO.:

DRAWN:

DESIGNED:

APPROVED:

DATE ISSUED:

CH2M HILL ENGINEERS, INC.

12750 MERIT DRIVE SUITE 1100

DALLAS, TX 75251-1302

REGISTRATION #F-3699

A

M E

L

IA

E A

R H

A R

T D

R

O W

N S

V

IL

L E

T

E X

A S

B R

O W

N S

V

IL

L E

S O

U T

H P

A D

R E

I S

L A

N D

IN

T

E R

N A

T

IO

N A

L A

IR

P

O R

T

SHEET NUMBER:

ELECTRICAL

01 02 03 04

KEY PLAN

NEW PASSENGER

TERMINAL

CHECKED:

SCALE:

PROJECT TITLE:

SHEET TITLE:

TRUE

NORTH

06 07 08 09

11 12 13 14

16 17 18 19

/2 /2

:3

:4

A

M C

A u to d e s k \1

-B

R O

-E L

-T E

-R

R E

B E

C C

A .S

O N

T H

E

IM

E R

.r v t

As indicated

T.ROOKER

R.LEAZURE

R.LEAZURE

12/30/19

423356

FLOOR PLAN LEVEL

2 SECTOR 08 POWER

EP1-208

C.ZARNAGHIAN

- 1/8" = 1'-0"

1 LEVEL 2 - SECTOR 08 - POWER

8 0 8

Scale: 1/8 INCH = 1 FOOT

KEYED NOTES

1 SURFACE-MOUNTED MOTOR-RATED SNAP

SWITCH FOR WH-1.

2 SURFACE-MOUNTED MOTOR-RATED SNAP

SWITCH FOR WH-2.

3 POKE THROUGH WITH (2) NEMA 5-15R

RECEPTACLES FOR POWER TO HOLD ROOM

SEATS.

4 RECEPTACLE FOR MIXING CIRCULATING

STATION.

5 ALL CIRCUIT NUMBERS SHOWN FOR

RECEPTACLES IN THIS ROOM ARE TO

PANEL 2RP1A.

6 TO PANEL UPS-2RP2.

7 TO PANEL UPS-2RP1.

8 RECEPTACLE FOR FIDS MONITOR.

COORDINATE WITH MILLWORK PROVIDER

FOR RECEPTACLE MOUNTING LOCATION.

9 MANUAL SWITCH FOR GARBAGE DISPOSAL

MOUNTED AT +42" AFF.

10 MOTOR RATED SWITCH FURNISHED WITH

EQUIPMENT.

11 DISCONNECT SWITCH FOR OVERHEAD

DOOR. CONTRACTOR TO VERIFY WITH

OVERHEAD DOOR PROVIDER THE VOLTAGE

AND POWER REQUIREMENT FOR DOOR

PRIOR TO CIRCUITING. CONTRACTOR TO

ALSO PROVIDE APPROPRIATE

CONDUIT/WIRING FOR OVERHEAD DOORS

AS NECESSARY.

12 NOT USED.

13 RECEPTACLE FOR ADVERTISING BOARD

SIGN. MOUNT +60" AFF.

14 J-BOX FOR BMS CONTROL PANEL.

15 J-BOX FOR POWER TO RESTROOM

AUTOMATIC FAUCETS AND SOAP

DISPENSERS(S).

16 UNDER COUNTER J-BOX FOR POWER TO

RESTROOM AUTOMATIC FAUCETS AND

SOAP DISPENSERS(S).

17 RECEPTACLE FOR TV MONITOR.

18 GFI, MOUNT +42" AFF.

19 COORDINATE EXACT LOCATION OF

CONDUIT STUB-UPS WITH MILLWORK

PROVIDER.

20 3/4" UNDER SLAB POWER CONDUIT TO GIDS

ON GATE COUNTER.

21 1 1/4" UNDER SLAB DATA/SECURITY

CONDUIT FOR CONNECTION BETWEEN

COUNTERS.

22 1 1/4" UNDER SLAB CONDUIT FOR

DATA/SECURITY TO GATE

COUNTER/MILLWORK.

23 3/4" UNDER SLAB POWER CONDUIT TO

RECEPTACLES ON GATE

COUNTER/MILLWORK.

24 1" UNDER SLAB CONDUIT FOR

DATA/SECURITY TO GATE

COUNTER/MILLWORK.

25 POKE THROUGH WITH (2) NEMA 5-15R

RECEPTACLES FOR POWER TO PARABIT

CHARGING TABLE. PROVIDE FIRE-RATED

POKE THROUGH, HUBBELL CATALOG

#PT7FSDBLA.

26 RECEPTACLE FOR POWER TO PAPER

TOWEL DISPENSER. MOUNT RECEPTACLE

RECESSED INTO THE WALL ADJACENT TO

UNIT. COORDINATE EXACT LOCATION

(INCLUDING MOUNTING HEIGHT) OF

RECEPTACLE WITH DISPENSER PROVIDER

PRIOR TO UNIT INSTALLATION.

27 GENERAL PURPOSE RECEPTACLE

MOUNTED +48" AFF.

28 ALL CIRCUIT NUMBERS SHOWN FOR

RECEPTACLES IN THIS ROOM ARE TO

PANEL 2RP1B.

29 GFCI RECEPTACLE FOR REFRIGERATOR.

MOUNT AT +48" AFF.

30 480V, NEMA SIZE 1 STARTER FOR EXHAUST

FAN EF-3-C7 ON THE ROOF. REFER TO

DWG. EP1-300 FOR THE LOCATION OF

EXHAUST FAN. REFER TO DETAIL 6 ON

DWG. EE5-001 FOR EF CONTROL

SCHEMATIC.

31 CONNECT TO CKTS 35,37,39 IN PANEL 2PP2

USING 4#12,1#12G IN 3/4"C.

32 2#12, 1#12G IN 3/4"C TO AXIS FA54 ENCODER

LOCATED ABOVE THE CEILING.

COORDINATE LOCATION WITH PARABIT.

33 2#12, 1#12G IN 3/4"C TO AXIS FA54 ENCODER

LOCATED AT THE GATE PODIUM.

COORDINATE LOCATION WITH PARABIT.

34 2#12, 1#12G IN 3/4"C TO AXIS FA54 ENCODER

WALL-MOUNTED. COORDINATE LOCATION

WITH PARABIT.

NO. REVISION OR ISSUE DATE BY

0 ISSUE FOR CONSTRUCTION 11/26/18 REL

1 PCR 04 UA/PCR 04A AA/PCR

05A CANOPY

01/20/20 REL

2 RFI 0432 PARABIT

EQUIPMENT

10/02/20 REL

10-02-2020 emmanuel.mena Highlight emmanuel.mena Highlight emmanuel.mena Highlight emmanuel.mena Highlight emmanuel.mena Highlight emmanuel.mena Highlight emmanuel.mena Cloud emmanuel.mena Text Box

RFI 0170_MISSING POWER FOR LV-1 LV-2

emmanuel.mena Text Box

RFI 0450_POWER TO TOWEL DISPENSERS TA-11

emmanuel.mena Cloud+ emmanuel.mena Cloud+ RFI 0516_OH Grille 2053 Controls

Lorena Cardona Rectangle

Lorena Cardona Oval

Lorena Cardona Oval

Blank Page

File details come from the government source that posted it. Updated .