12-LNAA-CO-002 Technical Drawings.pdf
PDF 9 MB Posted
- Attached to
- Cooling Tower Replacement
- Solicitation number
- US.258403
- Issued by
- Lehigh County, Pennsylvania
About this file
This file contains technical drawings and bid plans for a cooling tower replacement project at Lehigh Valley International Airport in Allentown, Pennsylvania, prepared by the Lehigh-Northampton Airport Authority. The project includes demolition of the existing cooling tower and associated equipment, installation of a new cooling tower unit (EVAPCO AT-28-3GI77 with 8,595 GPM capacity and 61,600 MBH design basis), replacement of two split-system condensing units (Hitachi PAS-24BUUFASDQ1) with associated indoor units, installation of new structural steel framing including HSS5X5X1/4 columns and beams with L4X4X1/4 bracing, new aluminum louver walls, new overhead and insulated galvanized doors, and comprehensive mechanical and electrical system modifications. The project also involves demolition of existing brick screen walls, installation of new galvanized steel angle lintels, roof and flashing work, and coordination with existing building systems. A non-mandatory virtual pre-bid meeting is scheduled for 1:00 p.m. on Tuesday, October 20, 2026, via Microsoft Teams. Questions must be submitted by 4:00 p.m. on Tuesday, October 27, 2026, through www.PennBid.net. Sealed proposals are due at 2:00 p.m. on Friday, November 13, 2026, via www.PennBid.net and will be opened publicly at 2:00 p.m. the same day at the Lehigh-Northampton Airport Authority Boardroom, 2nd Floor, Main Terminal, 3311 Airport Road, Allentown, PA 18109. Proposals must remain valid for 120 days.
The technical drawings indicate construction to comply with the 2021 International Building Code, ASCE 7-16 wind loading standards (120 MPH ultimate basic wind speed, Wind Exposure Category D), AISC 360 structural steel specifications, and all applicable Pennsylvania state and local codes. All structural steel exposed to weather, water, or chemicals shall be hot-dipped galvanized. The project design basis includes EVAPCO cooling tower operating parameters with 8,595-pound unit weight, 205.5 CFM fan capacity, and design specifications for 152 GPH flow and 10,020 MBH capacity. New electrical work includes 480-volt, three-phase, 30-ampere NEMA 3R disconnects for cooling tower fans, 7.5-horsepower variable frequency drives, and 208-volt, single-phase condensing unit connections. The Authority reserves the right to accept or reject any and all proposals, re-advertise, or award the contract in a manner determined to be in its best interest. No specific set-aside programs are identified in the bidding documents.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LOCATION MAP
LEHIGH VALLEY
INTERNATIONAL
AIRPORT
VICINITY MAP
PREPARED BY:
IT IS A VIOLATION OF THE LAW FOR ANY PERSON, UNLESS ACTING UNDER THE DIRECTION OF
A LICENSED PROFESSIONAL ENGINEER, ARCHITECT, LANDSCAPE ARCHITECT, OR LAND
SURVEYOR, TO ALTER AN ITEM IN ANY WAY. IF AN ITEM BEARING THE STAMP OF A LICENSED
PROFESSIONAL IS ALTERED, THE ALTERING ENGINEER, ARCHITECT, LANDSCAPE ARCHITECT,
OR LAND SURVEYOR SHALL STAMP THE DOCUMENT AND INCLUDE THE NOTATION "ALTERED
BY" FOLLOWED BY THEIR SIGNATURE, THE DATE OF SUCH ALTERATION, AND A SPECIFIC
DESCRIPTION OF THE ALTERATION.
LEHIGH
PREPARED FOR:
COOLING TOWER REPLACEMENT
BID PLANS
ALLENTOWN
PENNSYLVANIA
MJ PROJECT NO. 01.19181.12
LEHIGH VALLEY INTERNATIONAL AIRPORT
OCTOBER 2026
LEHIGH-NORTHAMPTON AIRPORT AUTHORITY
3311 AIRPORT ROAD
ALLENTOWN, PA 18109
1-800-FLY-LVIA
WWW.FLYABE.COM
1650 MARKET STREET
SUITE 3613, PHILADELPHIA, PA
PENNSYLVANIA 19103
PENNSYLVANIA
DEVIN A. SHAPLEY, PE
PA LIC. NO. PE095339
DATE: 10/13/2026
A2.2 PROPOSED WORK
A2.1 EXISTING CONDITIONS AND DEMOLITION
S1.0 STANDARD NOTES
DRAWING SHEET INDEX
DRAWING NUMBER DRAWING TITLE
S2.0 FRAMING PLANS
S3.0 SECTIONS
S4.0 WALL ELEVATIONS
M000 LEGEND, AND NOTES
M100 MECHANICAL PLANS AND SCHEDULES
E000 ELECTRICAL GENERAL INFORMATION
E100 ELECTRICAL COOLING TOWER PLANS
A2.3 SECTION DETAILS
LVY
PE
SNN AI
NA
NE.J H I
TE
AH
N A -R
X
A S
GI
ER
DERET ITECT
RCH
UP
PR
O
JE
CT
NO
RT
H
A2.14
A2.1 2
A2.1
A2.1
F11
F11
F12
F12
F13
F13
FB FB
FC FC
FD FD
FE FE
FF FF
10"
EXISTING MECHANICAL ROOM
EXISTING OPEN ROOF AREA
LOWER ROOF
-3' - 9"
FINISHED FLOOR
0' - 0"
ROOF
12' - 3 7/8"
A2.16
A2.1
A2.21
A2.2
F11
F11
F12
F12
F13
F13
FB FB
FC FC
FD FD
FE FE
FF FF
CUT AND PATCH EXISTING BRICK WALL AND
ROOFING DURING NEW COLUMN INSTALLATION
EXISTING MECHANICAL ROOM
EXISTING OPEN ROOF AREA
EXISTING
LOWER ROOF
EXISTING ROOF
EXISTING
LOWER ROOF
6' -0
5'-0"
7' -4
5'-8"
FB FC FD FE FF
5 2
F11 F12 F13
C
LI
EN
T:
PR
O
JE
C
T:
DRAWN
NO.
DRAWING TITLE
DRAWING NUMBER
DATE REVISIONS
IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS
THEY ARE ACTING UNDER THE DIRECT DIRECTION OF A
LICENSED PROFESSIONAL ENGINEER, ARCHITECT,
LANDSCAPE ARCHITECT, OR LAND SURVEYOR, TO
ALTER AN ITEM IN ANY WAY. IF AN ITEM BEARING THE
STAMP OF A LICENSED PROFESSIONAL IS ALTERED,
THE ALTERING ENGINEER, ARCHITECT, LANDSCAPE
ARCHITECT, OR LAND SURVEYOR SHALL STAMP THE
DOCUMENT AND INCLUDE THE NOTATION "ALTERED BY"
FOLLOWED BY THEIR SIGNATURE, THE DATE OF SUCH
ALTERATION, AND SPECIFIC DESCRIPTION OF THE
ALTERATION.
DESIGNED
CHECKED
SCALE
DATE
PROJECT
AS NOTED
SEAL
49 Court Street, Suite 240 Binghamton, NY 13901 www.mjinc.com
ARCHITECTS
1741 KIWANIS TR. DUBOIS, PA 15801
814-371-1541 ktharch.com
Au to de sk
D oc s:
//A
B E
C oo lin g
To w er /K
TH
M od el
.rv t
A2.1
EXISTING
CONDITIONS
AND
DEMOLITON
KTH: 26065A
Author
OCTOBER 13, 2026
LE
H
IG
H
V A
LL
E
Y
IN
T A
IR
P
O R
T
A irp or t R oa d, A lle nt ow n, P A
. 1
C O
O
LI
N G
T O
W E
R R
E P
LA
C
E M
E N
T
Designer
Checker
SCALE: 3/16" = 1'-0"
EXISTING FLOOR PLAN
SCALE: 3/16" = 1'-0"A2.1
4 EXISTING EAST ELEVATION
SCALE: 3/16" = 1'-0"A2.1
2 EXISTING WEST ELEVATION
SCALE: 3/16" = 1'-0"A2.1
3 EXISTING NORTH ELEVATION
SCALE: 3/16" = 1'-0"A2.1
5 EXISTING SOUTH ELEVTION
SCALE: 3/16" = 1'-0"
DEMOLITION FLOOR PLAN
SCALE: 3/16" = 1'-0"A2.1
6 DEMOLITION EAST ELEVATION
SCALE: 3/16" = 1'-0"A2.1
7 DEMOLITION SOUTH ELEVTION
DEMOLITION KEY NOTES
1 GENERAL CONTRACTOR TO DEMOLISH EXISTING DOOR, FRAME, AND ALL ASSOCIATED HARDWARE AND
MODIFY OPENNING SIZE FOR NEW DOOR FRAME.
2 GENERAL CONTRACTOR TO DEMOLISH EXISTING BRICK SCREEN WALL AND EXPOSE EXISTING STEEL BEAM
BELOW FOR NEW STEEL COLUMN CONNECTIONS PER STRUCTURAL
3 GENERAL CONTRACTOR TO DEMOLISH EXISTING BRICK WALL.
4 GENERAL CONTRACTOR TO COMPLETELY REMOVE EXISTING METAL LOUVER AND MODIFY OPENNING SIZE FOR
NEW OVERHEAD DOOR.
5 GENERAL CONTRACTOR TO REMOVE PORTION OF EXISTING STONE LINTEL AND WALL CAPS.
CONTRACTOR TO EXPOSE STEEL BEAM
WHEN SCREEN WALL IS REMOVED
CONTRACTOR TO EXPOSE STEEL BEAM
WHEN SCREEN WALL IS REMOVED
REMOVE EXISTING BRICK AND
CMU FOR LARGER OPENING
EXISTING CONDITIONS DEMOLITION
NOTE: 3D RENDERINGS ARE FOR REFERENCE ONLY
DEMO LOUVER AND OPENING
FOR NEW OVERHEAD DOOR
DEMO DOOR, FRAMING AND
OPENING FOR NEW DOOR
DEMO BRICK SCREEN WALLS
FOR NEW ALUMINUM LOUVER
WALL INSTALLATION
EXISTING ROOF MEMBRANE EXTENDS
UP EXISTING MASONRY WALLS
EXISTING ROOF MEMBRANE EXTENDS
UP EXISTING MASONRY WALLS
EXISTING BRICK SCREEN WALLS
OPENING TO COOLING TOWER
EXISTING BRICK WALLS
http://www.mjinc.com
SNN AI
NA
NE.J H I
TE
AH
N A -R
X
A S
GIER
DERET ITECT
RCH
101B
101A
A2.21
A2.2
A2.3
F11
F11
F12
F12
F13
F13
FB FB
FC FC
FD FD
FE FE
FF FF
1' -1
1"
'-1
'-5
/8
1'
-6
/8
1'-9" 27'-8"
NEW OVERHEAD DOOR
NEW INSULATED, GALVANIZED
DOOR AND FRAME
NEW EXTRUDED ALUMINUM LOUVER WALL
NEW GALVANIZED STEEL COLUMNS AT SUB
FRAMING PER STRUCTURAL DRAWINGS
NEW GALVANIZED W10X49 STEEL
COLUMN PER STRUCTURAL DRAWINGS
CUT AND PATCH EXISTING BRICK WALL AND
ROOFING DURING NEW COLUMN INSTALLATION
CUT AND PATCH EXISTING BRICK WALL AND
ROOFING DURING NEW COLUMN INSTALLATION
NEW EXTRUDED ALUMINUM LOUVER WALL
OPENING AT EXISTING STEEL STAIR
EXISTING MECHANICAL ROOM
EXISTING OPEN ROOF AREA
SEE MECHANICAL FOR COOLING TOWER REPLACEMENT
COORDINATE LOUVER OPENING FOR
EXISTING WATER PIPING
UP
101A
FB FC FD FE
NEW EXTRUDED ALUMINUM LOUVER WALL
OPENING AT EXISTING STEEL STAIR
COORDINATE LOUVER OPENING FOR
EXISTING WATER PIPING
NEW EXTRUDED ALUMINUM LOUVER WALL
NEW EXTRUDED ALUMINUM LOUVER WALL
NEW GALVANIZED W10X49 STEEL
COLUMN PER STRUCTURAL DRAWINGS
LOUVER END CAPS
LOUVER JOINTS
17'-5 7/8"
'-5
/2
EXISTING STEEL STEPS
F11 F12 F13
NEW EXTRUDED ALUMINUM LOUVER WALL
NEW GALVANIZED W10X49 STEEL
COLUMN PER STRUCTURAL DRAWINGS
LOUVER END CAPS
LOUVER JOINTS
'-5
/2
27'-3"
A2.3
FINISHED
FLOOR
TYPE: D1
FINISHED
FLOOR
TYPE: D2
1' -0
7'
-0
2' -0
6'
-0
LINE OF EXISTING
LOUVER OPENING
5'-8"
REMOVE EXISTING
BRICK AND CMU FOR
LARGER OPENING
NEW CONCRETE DOOR SILLS
BY GENERAL CONTRACTOR
5"
INSTALL NEW GALV.
STEEL ANGLE LINTELS
FINISHED
FLOOR
TYPE: F1
5" 7'
-0
4"
4'-0"
2" 3'-8" 2"
7' -4
NEW CONCRETE DOOR SILLS BY
GENERAL CONTRACTOR
REMOVE EXISTING PRECAST
CONCRETE HEADER
INSTALL NEW GALV.
STEEL ANGLE LINTELS
7' -2
OVERHEAD DOOR STEEL
JAMB PER MANUFACTURER
4" BRICK VENEER
J1
4" CMU
5/
8"
4" BRICK VENEER
J2
4" CMU
8"
3/
4"
CAULK (BOTH SIDES)
PAINTED, GALVANIZED HOLLOW
METAL FRAME - GROUT SOLID
PREFINISHED META JAMB FLASHING AT
NEW OVERHEAD DOOR
REMOVE AND REINSTALL EXISTING CMU
AND BRICK AT DOOR OPENINGS
NEW DBL. 4X4X1/4 GALVANIZED STEEL ANGLE
LINTELS PER STRUCTURAL
NEW PVC HEAD FLASHING WITH WEEP
VENTS @ 24" O.C.
NEW PVC SILL FLASHING
EXISTING ROOFING UP WALL
EXISTING MASONRY WALL
CONCRETE FLOOR OF MECHANICAL ROOM
PLACE NEW CONCRETE SILL AT BOTTOME
OF THE NEW DOORS (OVERHEAD DOOR
SILL SHOWN)
1' -0
4" 8"
4" 9 1/2"
CONTINUOUS DRIP GROOVE
1/2" CHAMPFERS
C
LI
EN
T:
PR
O
JE
C
T:
DRAWN
NO.
DRAWING TITLE
DRAWING NUMBER
DATE REVISIONS
IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS
THEY ARE ACTING UNDER THE DIRECT DIRECTION OF A
LICENSED PROFESSIONAL ENGINEER, ARCHITECT,
LANDSCAPE ARCHITECT, OR LAND SURVEYOR, TO
ALTER AN ITEM IN ANY WAY. IF AN ITEM BEARING THE
STAMP OF A LICENSED PROFESSIONAL IS ALTERED,
THE ALTERING ENGINEER, ARCHITECT, LANDSCAPE
ARCHITECT, OR LAND SURVEYOR SHALL STAMP THE
DOCUMENT AND INCLUDE THE NOTATION "ALTERED BY"
FOLLOWED BY THEIR SIGNATURE, THE DATE OF SUCH
ALTERATION, AND SPECIFIC DESCRIPTION OF THE
ALTERATION.
DESIGNED
CHECKED
SCALE
DATE
PROJECT
AS NOTED
SEAL
49 Court Street, Suite 240 Binghamton, NY 13901 www.mjinc.com
ARCHITECTS
1741 KIWANIS TR. DUBOIS, PA 15801
814-371-1541 ktharch.com
Au to de sk
D oc s:
//A
B E
C oo lin g
To w er /K
TH
M od el
.rv t
A2.2
PROPOSED
WORK
KTH: 26065A
Author
OCTOBER 13, 2026
LE
H
IG
H
V A
LL
E
Y
IN
T A
IR
P
O R
T
A irp or t R oa d, A lle nt ow n, P A
. 1
C O
O
LI
N G
T O
W E
R R
E P
LA
C
E M
E N
T
Designer
Checker
SCALE: 1/4" = 1'-0"
PROPOSED FLOOR PLAN
SCALE: 1/4" = 1'-0"A2.2
1 PROPOSED EAST ELEVATION
SCALE: 1/4" = 1'-0"A2.2
2 PROPOSED SOUTH ELEVTION
SCALE: 1/2" = 1'-0"
DOOR TYPES
SCALE: 1/2" = 1'-0"
FRAME TYPES
DOOR SCHEDULE
DOOR
NUMBER
PANEL FRAME
JAMB TYPE FIRE RATING HARDWARE SET # COMMENTSTYPE MATERIAL FINISH WIDE HEIGHT THICK TYPE MATERIAL FINISH
101A D2 METAL PREFINISHED 5'-8" 7'-4" 1" - STEEL PREFINISHED J1 NONE SLIDE BOLT INSULATED COILING DOOR 101B D1 HOLLOW METAL PAINTED 3'-8" 7'-0" 1 3/4" F1 HOLLOW METAL PAINTED J2 NONE PASSAGE INSULATED, GALVANIZED DOOR & FRAME
SCALE: 1 1/2" = 1'-0"
DOOR JAMBS
PROPOSED 3D VIEW
NOTE: 3D RENDERINGS ARE FOR REFERENCE ONLY
SCALE: 1 1/2" = 1'-0"
DOOR SECTION
NEW OVERHEAD DOOR
NEW METAL DOOR
NEW LOUVER WALLS
NOTE: CONTRACTOR SHALL FIELD VERIFY
ALL EXISITNG AND NEW CONDITIONS FOR
LOUVER AND DOOR SHOP DRAWINGS
SNN AI
NA
NE.J H I
TE
AH
N A -R
X
A S
GI
ER
DERET ITECT
RCH
4 1/2"
NEW 6" DEEP ALUMINUM LOUVERS, SPACED AT 5"
CLIP ANGLE ATTACHMENT POINT DESIGNED AND FURNISHED BY LOUVER MANUFACTURER
NEW 5" X 5" X 1/4" GALVANIZED H.S.S.
SECOND FLOOR
FRAMING PLAN
EL. 394'-0"
PENTHOUSE ROOF
FRAMING PLAN
EL. 405'-10 1/2"
LOUVER FRAMING
PLAN
EL. 407'-5"
FBFC
LOWER ROOF
-3' - 9"
LOWER ROOF
-3' - 9"
NEW 4" X 4" X 1/4" GALVANIZED ANGLE BRACES
EXISTING LOWER ROOF TO BE REPLACED UNDER SEPARATE CONTRACT
EXISTING BRICK WALL ON STEEL "Z" LEDGE TO REMAIN
NEW WOOD BLOCKING
SELF ADHERED PVC ROOFING LAPPED OVER PARAPET
NEW, REMOVABLE, PREFINISHED METAL COPING
SELF ADHERED PVC ROOF FLASHING EXTENDED UP EXISTING
WALL AND NEW STEEL COLUMN POST PENETRATIONS
EXISTING ROOF TO BE REPLACED UNDER SEPARATE CONTRACT
APPROXIMATE LINE OF NEW ROOF UNDER SEPARATE CONTRACT
EXISTING W33X 118 STEEL BEAM BELOW
EXISTING INSULATION BELOW
EXISTING METAL DECK
EXISTING METAL DECK
LINE OF EXISTING BRICK SCREEN WALL REMOVED
SELF ADHERED PVC AND LIQUID ROOF FLASHING AT ALL NEW STEEL
COLUMN PENETRATIONS
NEW COLUMN BEARING PLATES ON EXISTING BEAMS
(SEE STRUCTURAL)
CUT PORTION OF EXISTING BRICK WALL AND ROOF
DECK DURING NEW COLUMN INSTALLATION AND PATCH
WALL AND ROOF AFTER COLUMN INSTALLATION.
'-3
/2
4' -0
4'
-0
3' -8
1'
-9
COLUMN WATERPROOFING DETAILS
TYPICAL LOUVER DETAILSROOF TO WALL DETAILS
C
LI
EN
T:
PR
O
JE
C
T:
DRAWN
NO.
DRAWING TITLE
DRAWING NUMBER
DATE REVISIONS
IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS
THEY ARE ACTING UNDER THE DIRECT DIRECTION OF A
LICENSED PROFESSIONAL ENGINEER, ARCHITECT,
LANDSCAPE ARCHITECT, OR LAND SURVEYOR, TO
ALTER AN ITEM IN ANY WAY. IF AN ITEM BEARING THE
STAMP OF A LICENSED PROFESSIONAL IS ALTERED,
THE ALTERING ENGINEER, ARCHITECT, LANDSCAPE
ARCHITECT, OR LAND SURVEYOR SHALL STAMP THE
DOCUMENT AND INCLUDE THE NOTATION "ALTERED BY"
FOLLOWED BY THEIR SIGNATURE, THE DATE OF SUCH
ALTERATION, AND SPECIFIC DESCRIPTION OF THE
ALTERATION.
DESIGNED
CHECKED
SCALE
DATE
PROJECT
AS NOTED
SEAL
49 Court Street, Suite 240 Binghamton, NY 13901 www.mjinc.com
ARCHITECTS
1741 KIWANIS TR. DUBOIS, PA 15801
814-371-1541 ktharch.com
Au to de sk
D oc s:
//A
B E
C oo lin g
To w er /K
TH
M od el
.rv t
A2.3
SECTION
DETAILS
KTH: 26065A
EJH
OCTOBER 13, 2026
LE
H
IG
H
V A
LL
E
Y
IN
T A
IR
P
O R
T
A irp or t R oa d, A lle nt ow n, P A
. 1
C O
O
LI
N G
T O
W E
R R
E P
LA
C
E M
E N
T
EJH
JB
SCALE: 1 1/2" = 1'-0"A2.3
1 LOUVERED WALL SECTION
ROOF AND LOUVER DETAILS
NOTE: CONTRACTOR SHALL FIELD VERIFY
ALL EXISITNG AND NEW CONDITIONS FOR
LOUVER SHOP DRAWINGS
C
LI
EN
T:
PR
O
JE
C
T:
DRAWN
NO.
DRAWING TITLE
DRAWING NUMBER
DATE REVISIONS
IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS
THEY ARE ACTING UNDER THE DIRECT DIRECTION OF A
LICENSED PROFESSIONAL ENGINEER, ARCHITECT,
LANDSCAPE ARCHITECT, OR LAND SURVEYOR, TO
ALTER AN ITEM IN ANY WAY. IF AN ITEM BEARING THE
STAMP OF A LICENSED PROFESSIONAL IS ALTERED,
THE ALTERING ENGINEER, ARCHITECT, LANDSCAPE
ARCHITECT, OR LAND SURVEYOR SHALL STAMP THE
DOCUMENT AND INCLUDE THE NOTATION "ALTERED BY"
FOLLOWED BY THEIR SIGNATURE, THE DATE OF SUCH
ALTERATION, AND SPECIFIC DESCRIPTION OF THE
ALTERATION.
DESIGNED
CHECKED
SCALE
DATE
PROJECT
AS NOTED
SEAL
49 Court Street, Suite 240 Binghamton, NY 13901 www.mjinc.com
ARCHITECTS
1741 KIWANIS TR. DUBOIS, PA 15801
814-371-1541 ktharch.com
Au to de sk
D oc s:
//A
BE
C oo lin g To w er
/1
.1
AB
E C oo lin g To w er
_S _V
.rv t
S1.0
STANDARD
NOTES
01.19181.12
LMV
OCTOBER 13, 2026
LE
H
IG
H
V A
LL
E
Y
IN
T A
IR
P
O R
T
A irp or t R oa d, A lle nt ow n
P A
. 1
C O
O
LI
N G
T O
W E
R R
E P
LA
C
E M
E N
T
CEP
CEP
1.
1.
1.
A.
B.
C.
A.
1.
A.
1.
1.
2.
1.
1.
2.
1.
1.
DESIGN BASISDESIGN BASIS
BUILDING CODE
THE CONSTRUCTION DOCUMENTS ARE BASED ON THE REQUIREMENTS OF THE 2021 INTERNATIONAL BUILDING CODE IN ACCORDANCE WITH PENNSYLVANIA STATE
BUILDING RISK CATEGORY (PER IBC)
ABE COOLING TOWER: lll
WIND LOADS
BUILDING WIND LOADING HAS BEEN DETERMINED PER ASCE 7-16, CHAPTERS 26 AND 28. CRITERIA IS AS FOLLOWS:
WIND EXPOSURE CATEGORY: D
ULTIMATE BASIC WIND SPEED, V: 120 MPH
INTERNAL PRESSURE COEFFICIENT, GCpi: ±0.55
2. COMPONENTS AND CLADDING WIND PRESSURES HAVE BEEN DETERMINED PER ASCE 7-16, CHAPTER 30, ON AN ELEMENT BY ELEMENT BASIS.
DESIGNERS OF ELEMENTS ENGINEERED AS PART OF A DEFERRED SUBMITTAL THAT ARE SUBJECT TO WIND LOADING, ARE TO DETERMINE COMPONENT AND CLADDING WIND PRESSURES SPECIFIC TO THOSE ELEMENTS PER ASCE 7-16, CHAPTER 30 OR ANOTHER RELEVANT WIND LOADING PROCEDURE.
ELEMENT DEFLECTIONS AND BUILDING MOVEMENT
DESIGN OF STRUCTURAL ELEMENTS FOR SERVICEABILITY IS BASED ON GUIDANCE FROM IBC CHAPTER 16 AND IS TO INCLUDE MANUFACTURER CRITERIA FOR SPECIFIC FINISHES. DESIGNERS OF ELEMENTS AS PART OF A DEFERRED SUBMITTAL THAT ARE SUPPORTING FINISHES, ARE TO DESIGN FOR THE MINIMUM OF THE DESIGN CRITERIA OUTLINED BELOW OR THE SPECIFIC MANUFACTURER REQUIREMENTS FOR THOSE FINISHES. MINIMUM DESIGN CRITERIA IS AS FOLLOWS:
TYPICAL BEAM/GIRDER DEFLECTION
SUPPORTING TYPICAL CEILINGS AND FLOOR FINISHES INCLUDING SHEETROCK, DROPPED CEILINGS, CARPET, VINYL AND HARDWOOD FLOORS:
TOTAL LOAD: LENGTH/240
LIVE/SNOW LOAD: LENGTH/360
B. HOT-ROLLED WALL ELEMENTS
AT FLEXIBLE CLADDING:
0.6*WIND LOAD (ULTIMATE): HEIGHT/240
AT BRITTLE CLADDING:
0.6*WIND LOAD (ULTIMATE): HEIGHT/600
FUTURE VERTICAL EXPANSION
THE BUILDING DESIGN AS PART OF THIS SET OF DOCUMENTS DOES NOT INCLUDE ANY ALLOWANCES FOR FUTURE VERTICAL BUILDING EXPANSION.
1.
A.
B.
C.
D.
E.
A.
STRUCTURAL STEELSTRUCTURAL STEEL
THE STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH THE SITE, ARCHITECTURAL, MECHANICAL, ELECTRICAL AND PLUMBING DRAWINGS AND THE
SPECIFICATIONS.
2. ALL STRUCTURAL STEEL WORK SHALL COMPLY WITH THE FOLLOWING CODES AND STANDARDS AND ANY OTHER CODES, STANDARDS, OR OTHER DOCUMENTS REFERENCED THEREIN. VERSIONS OR EDITIONS SHALL BE AS REFERENCED BY THE BUILDING CODE INDICATED IN THE DESIGN BASIS.
AISC (AMERICAN INSTITUTE OF STEEL CONSTRUCTION) SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS – AISC 360
AISC CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES – AISC 303
AISC SEISMIC PROVISIONS FOR STRUCTURAL STEEL BUILDINGS – AISC 341
RCSC (RESEARCH COUNCIL ON STRUCTURAL CONNECTIONS) SPECIFICATION FOR STRUCTURAL JOINTS USING HIGH-STRENGTH BOLTS
AWS (AMERICAN WELDING SOCIETY) STRUCTURAL WELDING CODE – STEEL – AWS D1.1
3. ALL WELDING SHALL CONFORM TO THE "STRUCTURAL WELDING CODE - ANSI/AWS D1.1" OF THE AMERICAN WELDING SOCIETY.
4. STEEL MATERIALS SHALL CONFORM TO THE FOLLOWING:
STRUCTURAL SHAPES
ASTM A992, FY = 50,000 PSI (WIDE FLANGE SHAPES)
ASTM A36, FY = 36,000 PSI (ANGLES, CHANNELS,S-SHAPES, ETC.)
B. BOLTS
ASTM A325
C. NUTS
ASTM A563
D. WASHERS
ASTM F436
E. STRUCTURAL TUBING
ASTM A500, GRADE B, FY = 46,000 PSI FOR RECTANGULAR SQUARE SECTIONS, FY=42,000 PSI FOR ROUND SECTIONS.
5. ALL SHOP CONNECTIONS SHALL BE BOLTED OR WELDED. ALL FIELD CONNECTIONS SHALL BE BOLTED EXCEPT WHERE WELDING IS SPECIFICALLY CALLED FOR.
BOLTS SHALL BE 3/4" DIA. MINIMUM WITH OPEN HOLES 1/16" LARGER, EXCEPT FOR COLUMN GROUT PLATES WHICH ARE 3/16" LARGER AND COLUMN BASE
PLATES WHICH ARE 5/16" LARGER.
6. TIGHTEN ALL BOLTS PER THE REQUIREMENTS OF RCSC'S "SPECIFICATION FOR STRUCTURAL JOINTS USING HIGH STRENGTH BOLTS". THE JOINT TYPE FOR ALL
JOINTS IS SNUG-TIGHTENED UNLESS NOTED OTHERWISE.
7. THE DESIGN OF ALL CONNECTIONS SHALL BE THE RESPONSIBILITY OF THE STEEL FABRICATOR. COMPLETE CALCULATIONS SHALL BE PREPARED BY A REGISTERED PROFESSIONAL ENGINEER AND SHALL BE SUBMITTED TO THE ENGINEER FOR REVIEW PRIOR TO ANY FABRICATION. CONNECTIONS NOT DETAILED SHALL BE DESIGNED FOR THE LOADS INDICATED ON THE DRAWINGS, LOADS GIVEN IN THE AISC UNIFORM LOAD TABLES OR AS INDICATED IN THE MINIMUM CONNECTION DETAILS,WHICHEVER IS GREATER. THE CONNECTION DESIGN SHALL INCLUDE EXTERIOR TUBE COLUMN REINFORCEMENT OR PLATE DIAPHRAGMS TO TRANSFER THE LOADS TO THE TUBE COLUMNS WITHOUT INDUCING LOCAL BUCKLING OF THE TUBE WALLS AND WITHOUT EXCESSIVE DEFORMATION.
8. 8. ALL STEEL WHICH IS EXPOSED TO WEATHER, WATER, OR CHEMICALS IS TO BE HOT DIPPED GALVANIZED.ALL STEEL WHICH IS EXPOSED TO WEATHER, WATER, OR CHEMICALS IS TO BE HOT DIPPED GALVANIZED.
9. THE STRUCTURAL STEEL CONTRACTOR SHALL PROVIDE ALL NECESSARY GUYING AND BRACING REQUIRED TO ERECT AND HOLD THE STEEL FRAME PLUMB AND
SQUARE UNTIL THE ROOF DECK AND WALLS ARE INSTALLED.
10. THERE WILL BE NO FIELD BURNING, CUTTING OR OTHER ALTERATIONS OF PRIMARY STRUCTURAL STEEL, BAR JOISTS OR LONGSPAN JOISTS WITHOUT THE WRITTEN
PERMISSION OF THE ENGINEER.
11. NO MASONRY CONSTRUCTION SHALL BE ALLOWED IN AN AREA WHERE THE STRUCTURAL STEEL WORK IS NOT COMPLETE, SPECIFICALLY INCLUDING PLUMBING AND
ALIGNMENT.
12. THE CONTRACTOR SHALL SUBMIT SHOP DRAWINGS TO THE ENGINEER FOR REVIEW PRIOR TO FABRICATION FOR THE FOLLOWING ITEMS:
STRUCTURAL STEEL
IT IS REQUIRED THAT THE STRUCTURAL STEEL SUBCONTRACTOR PREPARE COMPLETE ERECTION DRAWINGS. REVISING OR PHOTOCOPYING OF THESE STRUCTURAL
DRAWINGS WILL NOT BE PERMITTED
13. ALL STRUCTURAL STEEL FABRICATION AND ERECTION MUST COMPLY WITH THE LATEST REQUIREMENTS OF OSHA 29 CFR PART 1926.
1.
COLD WEATHER CONSTRUCTION PROCEDURESCOLD WEATHER CONSTRUCTION PROCEDURES
IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO CONTINUOUSLY PROTECT SOILS, CONCRETE, MASONRY AND OTHER BUILDING MATERIALS FROM DAMAGE DUE TO COLD TEMPERATURES UNTIL THE BUILDING HAS BEEN TURNED OVER TO THE OWNER. THIS SHALL INCLUDE TEMPORARY ENCLOSURES, INSULATED BLANKETS
AND TEMPORARY HEATING.
2. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO REPAIR AND/OR REPLACE ANY DAMAGED OR DEFECTIVE WORK, IN A MANNER APPROVED BY THE ENGINEER.
3. ALL PROTECTIVE AND CORRECTIVE WORK SHALL BE AT THE EXPENSE OF THE CONTRACTOR.
SAFETY AND PROTECTIONSAFETY AND PROTECTION
CONTRACTOR SHALL BE RESPONSIBLE FOR INITIATING, MAINTAINING AND SUPERVISING ALL SAFETY PRECAUTIONS AND PROGRAMS IN CONNECTION WITH THE WORK.
CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS FOR THE SAFETY OF, AND SHALL PROVIDE THE NECESSARY PROTECTION TO PREVENT DAMAGE INJURY OR LOSS TO
1. ALL EMPLOYEES ON THE WORK AND OTHER PERSONS WHO MAY BE AFFECTED THEREBY.
2. ALL THE WORK AND ALL MATERIALS OR EQUIPMENT TO BE INCORPORATED THEREIN, WHETHER IN STORAGE ON OR OFF, THE SITE, AND
3. OTHER PROPERTY AT THE SITE OR ADJACENT THERETO, INCLUDING TREES, SHRUBS, LAWNS, WALKS, PAVEMENTS, ROADWAYS, STRUCTURES AND UTILITIES NOT
DESIGNATED FOR REMOVAL, RELOCATION OR REPLACEMENT IN THE COURSE OF CONSTRUCTION.
CONTRACTOR SHALL COMPLY WITH ALL APPLICABLE STANDARDS (SPECIFICALLY INCLUDING OSHA, AND ANY OTHER STATE ADOPTED OSHA PROGRAM), LAWS, ORDINANCES, RULES, REGULATIONS AND ORDERS OF ANY PUBLIC BODY HAVING JURISDICTION FOR THE SAFETY OF PERSONS OR PROPERTY OR TO PROTECT THEM FROM DAMAGE, INJURY OR LOSS; AND SHALL ERECT AND MAINTAIN ALL NECESSARY SAFEGUARDS FOR SUCH SAFETY AND PROTECTION. CONTRACTOR SHALL NOTIFY OWNERS OF ADJACENT
PROPERTY AND UTILITIES WHEN EXECUTION OF THE WORK MAY AFFECT THEM.
CONTRACTOR SHALL BE RESPONSIBLE FOR ALL REPAIRS AND OTHER COSTS ARISING FROM ANY DAMAGE AT THE SITE OR ADJACENT THERETO.
CONTRACTOR'S DUTIES AND RESPONSIBILITIES FOR THE SAFETY AND PROTECTION OF THE WORK SHALL CONTINUE UNTIL SUCH TIME AS ALL THE WORK IS COMPLETED.
F12F12
FEFE
F13F13
FDFD
S3.0S3.0
EXIST. W18X45EXIST. W18X45
EXIST. W18X45EXIST. W18X45
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
FCFC
W X
W X
S3.0S3.0
W12X19W12X19
W12X19W12X19
W12X19W12X19
W12X19W12X19
S3.0S3.0
29'-1 1/2"29'-1 1/2"
S4.0S4.0
S4.0S4.0
S3.0S3.0
S3.0S3.0
(0'-3")(0'-3")
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0'-2")(0'-2") (0'-2")(0'-2")
(0'-1")(0'-1") (0'-1")(0'-1")
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0
S
LO
P E D
S
LO
P E D
S
LO
P E D
S
LO
P E D
(-0'-5/8")(-0'-5/8")
(0'-0")(0'-0")
L4X4X1/4L4X4X1/4
S3.0S3.0
S3.0S3.0
S3.0S3.0
L4 X X
L4 X X
S3.0S3.0
10' MIN10' MIN
M
IN
M
IN
W14X22W14X22
(1
(1
(1'-6 1/2")(1'-6 1/2")
(2) L4X4X1/4(2) L4X4X1/4
(2 L4 X X
(2 L4 X X
F12F12
FEFE
F13F13
27'-8"27'-8"
FDFD
S3.0S3.0 E X
IS
T.
W X
E X
IS
T.
W X
EXIST. W24X68EXIST. W24X68
EXIST. W24X61EXIST. W24X61
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
FCFC
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
EXIST.
EXIST.
W 10X49
W 10X49
EXIST. 10X49 BELOW
EXIST. 10X49 BELOW
NEW
W
10X33 ABOVE
NEW
W
10X33 ABOVE
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
E X
IS
T.
W X
EXIST. W8X10EXIST. W8X10 EXIST. W8X10EXIST. W8X10
EXIST. W8X10EXIST. W8X10EXIST. W8X10EXIST. W8X10
EXIST. W8X10EXIST. W8X10 EXIST. W8X10EXIST. W8X10
NE
W
NE
W
HS
S5 X5 X1 /4
HS
S5 X5 X1 /4
NE
W
NE
W
HS
S5 X5 X1 /4
HS
S5 X5 X1 /4
HS
S5 X5 X1 /4
HS
S5 X5 X1 /4
S3.0S3.0
S3.0S3.0
EXIST. W24X61EXIST. W24X61
HS
S5 X5 X1 /4
HS
S5 X5 X1 /4
NE
W
NE
W
NE
W
NE
W
E X
IS
T.
W X
E X
IS
T.
W X
NE
W
NE
W
HS
S5 X5 X1 /4
HS
S5 X5 X1 /4
HS
S5 X5 X1 /4
HS
S5 X5 X1 /4
NE
W
NE
W
HSS5X5X1/4
HSS5X5X1/4
NEW
NEW
S4.0S4.0
S4.0S4.0
NE
W
NE
W
HS
S5 X5 X1 /4
HS
S5 X5 X1 /4
5 1/2"5 1/2" 6'-9 1/2"6'-9 1/2" 6'-7"6'-7" 6'-7"6'-7" 7'-3"7'-3"
S3.0S3.0
(0'-3")(0'-3")
(0'-3")(0'-3")
(0'-3")(0'-3")
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0
S
LO
P E D
S
LO
P E D
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0
(0
EXIST. W33X118EXIST. W33X118
CONTRACTOR SHALL FIELD VERIFY CONTRACTOR SHALL FIELD VERIFY
EXISTING TOP OF COLUMN EXISTING TOP OF COLUMN
CONNECTION DETAILS. DETAILED CONNECTION DETAILS. DETAILED
BOLTED CONNECTION INFORMATION BOLTED CONNECTION INFORMATION
SHALL BE PROVIDED UPON SHALL BE PROVIDED UPON
COMPLETION OF FIELD COMPLETION OF FIELD
VERIFICATION.VERIFICATION.
C
LI
EN
T:
PR
O
JE
C
T:
DRAWN
NO.
DRAWING TITLE
DRAWING NUMBER
DATE REVISIONS
IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS
THEY ARE ACTING UNDER THE DIRECT DIRECTION OF A
LICENSED PROFESSIONAL ENGINEER, ARCHITECT,
LANDSCAPE ARCHITECT, OR LAND SURVEYOR, TO
ALTER AN ITEM IN ANY WAY. IF AN ITEM BEARING THE
STAMP OF A LICENSED PROFESSIONAL IS ALTERED,
THE ALTERING ENGINEER, ARCHITECT, LANDSCAPE
ARCHITECT, OR LAND SURVEYOR SHALL STAMP THE
DOCUMENT AND INCLUDE THE NOTATION "ALTERED BY"
FOLLOWED BY THEIR SIGNATURE, THE DATE OF SUCH
ALTERATION, AND SPECIFIC DESCRIPTION OF THE
ALTERATION.
DESIGNED
CHECKED
SCALE
DATE
PROJECT
AS NOTED
SEAL
49 Court Street, Suite 240 Binghamton, NY 13901 www.mjinc.com
ARCHITECTS
1741 KIWANIS TR. DUBOIS, PA 15801
814-371-1541 ktharch.com
Au to de sk
D oc s:
//A
BE
C oo lin g To w er
/1
.1
AB
E C oo lin g To w er
_S _V
.rv t
S2.0
FRAMING
PLANS
01.19181.12
LMV
OCTOBER 13, 2026
LE
H
IG
H
V A
LL
E
Y
IN
T A
IR
P
O R
T
A irp or t R oa d, A lle nt ow n
P A
. 1
C O
O
LI
N G
T O
W E
R R
E P
LA
C
E M
E N
T
CEP
CEP
SCALE:SCALE: 1/4" = 1'-0" 1/4" = 1'-0"
PENTHOUSE ROOF FRAMING PLANPENTHOUSE ROOF FRAMING PLAN
SCALE:SCALE: 1/4" = 1'-0" 1/4" = 1'-0"
SECOND FLOOR FRAMING PLANSECOND FLOOR FRAMING PLAN
1.1.
2.2.
3.3.
4.4.
ELEVATION OF TOP OF EXISTING STEEL: 394'-0" UNLESS NOTED OTHERWISE.ELEVATION OF TOP OF EXISTING STEEL: 394'-0" UNLESS NOTED OTHERWISE.
ALL FRAMING IS NEW UNLESS NOTED AS EXISTING.ALL FRAMING IS NEW UNLESS NOTED AS EXISTING.
ALL NEW EXTERIOR STEEL TO BE HOT DIPPED GALVANIZED.ALL NEW EXTERIOR STEEL TO BE HOT DIPPED GALVANIZED.
SEE WALL SECTIONS FOR HSS BEAMS AND ANGLE BRACING DIMENSIONS.SEE WALL SECTIONS FOR HSS BEAMS AND ANGLE BRACING DIMENSIONS.
1.1.
2.2.
3.3.
ELEVATION OF TOP OF STEEL: 405'-10 1/2" UNLESS NOTED OTHERWISE.ELEVATION OF TOP OF STEEL: 405'-10 1/2" UNLESS NOTED OTHERWISE.
ALL NEW EXTERIOR STEEL TO BE HOT DIPPED GALVANIZED.ALL NEW EXTERIOR STEEL TO BE HOT DIPPED GALVANIZED.
SEE WALL ELEVATIONS FOR HSS BEAMS AND ANGLE BRACING DIMENSIONS.SEE WALL ELEVATIONS FOR HSS BEAMS AND ANGLE BRACING DIMENSIONS.
N O
RT
H
N O
RT
H
N O
RT
H
N O
RT
H
SECOND FLOORSECOND FLOOR
FRAMING PLANFRAMING PLAN
EL. 394'-0"EL. 394'-0"
FCFC
1/41/4
EXISTING W33x118 EXISTING W33x118
BEAMBEAM
11 1/2" X 1/2" X 11 1/2" X 1/2" X
11 1/2" STEEL 11 1/2" STEEL
PLATE WITH (4) PLATE WITH (4)
THROUGH BOLTSTHROUGH BOLTS
1/41/4
11" X 1/2" X 8" 11" X 1/2" X 8"
STEEL PLATE WITH STEEL PLATE WITH
(4) THROUGH BOLTS(4) THROUGH BOLTS
W14x22 BEAMW14x22 BEAM
4 1/4"4 1/4"1 1/2"1 1/2"
TYP.TYP.
1 1/2"1 1/2"
1"1"
7 3/8"7 3/8"
5"5"
1/41/4
7 3/8" X 1/4" X 7 3/8" X 1/4" X
4" X 2" STEEL 4" X 2" STEEL
STIFFENER PLATE STIFFENER PLATE
5" X 1/4" X 2" 5" X 1/4" X 2"
STEEL PLATE WITH STEEL PLATE WITH
(2) THROUGH BOLTS(2) THROUGH BOLTS
F13F13
PENTHOUSE ROOFPENTHOUSE ROOF
FRAMING PLANFRAMING PLAN
EL. 405'-10 1/2"EL. 405'-10 1/2"
1/41/4
(2) 1/2"Ø THREADED RODS, (2) 1/2"Ø THREADED RODS,
CENTERED IN ADJACENT BRICKS, CENTERED IN ADJACENT BRICKS,
DRILLED INTO BOTH WYTHES OF DRILLED INTO BOTH WYTHES OF
BRICK AND ANCHOR WITH HILTI BRICK AND ANCHOR WITH HILTI
HY270 ADHESIVE.HY270 ADHESIVE.
L5X5X5/16 X 1'-0 AT 4'-0" L5X5X5/16 X 1'-0 AT 4'-0"
o/c FIELD VERIFY BEAM TO o/c FIELD VERIFY BEAM TO
WALL OFFSET AND ADJUST WALL OFFSET AND ADJUST
HORIZONTAL LEG AS REQUIRED HORIZONTAL LEG AS REQUIRED
TO OBTAIN 3" OF WELD ALONG TO OBTAIN 3" OF WELD ALONG
SIDE OF ANGLE (TYPICAL).SIDE OF ANGLE (TYPICAL).
EXIST W14EXIST W14
EXIST W14EXIST W14
F13F13
PENTHOUSE ROOFPENTHOUSE ROOF
FRAMING PLANFRAMING PLAN
EL. 405'-10 1/2"EL. 405'-10 1/2"
EXIST W14EXIST W14 EXIST W14EXIST W14
W12X19W12X19
(2)L4X4X3/8 w/(3) 3/4"Ø BOLTS.(2)L4X4X3/8 w/(3) 3/4"Ø BOLTS.
L4X4X1/4 X 4" LONG WITH L4X4X1/4 X 4" LONG WITH
(1) THROUGH BOLT(1) THROUGH BOLT
1/41/4
TYP.TYP.
HSS5X5 COLUMNHSS5X5 COLUMN
1 1/2"1 1/2"
8" X 6" X 1/4" X 0'-4" 8" X 6" X 1/4" X 0'-4"
LONG BENT PLATELONG BENT PLATE
1/4" STEEL 1/4" STEEL
PLATE CENTEREDPLATE CENTERED
HSS5X5 BEAMHSS5X5 BEAM
L4X4X1/4 BRACE TYP.L4X4X1/4 BRACE TYP.
1 1/2"1 1/2"
SECOND FLOORSECOND FLOOR
FRAMING PLANFRAMING PLAN
EL. 394'-0"EL. 394'-0"
F13F13
1 1/2"1 1/2" 1 1/2"1 1/2"7"7"
EXISTING W27X84 BEAMEXISTING W27X84 BEAM
1/41/4
HSS5X5 COLUMNHSS5X5 COLUMN
10" X 1/2" X 10" 10" X 1/2" X 10"
STEEL PLATESTEEL PLATE
PENTHOUSE ROOFPENTHOUSE ROOF
FRAMING PLANFRAMING PLAN
EL. 405'-10 1/2"EL. 405'-10 1/2"
10' MIN10' MIN
1 1/2"1 1/2"
3" MIN3" MIN3" MIN3" MIN
TYP.TYP.
8"8"
9 1/2"9 1/2"
1/41/4
1/4" X 4" SQUARE PLATE1/4" X 4" SQUARE PLATE
L4X4X1/4L4X4X1/4
1/2"Ø THREADED RODS, 1/2"Ø THREADED RODS,
CENTERED IN ADJACENT BRICKS, CENTERED IN ADJACENT BRICKS,
DRILLED INTO BOTH WYTHES OF DRILLED INTO BOTH WYTHES OF
BRICK AND ANCHOR WITH HILTI BRICK AND ANCHOR WITH HILTI
HY270 ADHESIVE.HY270 ADHESIVE.
F13F13
FCFC
1'-3 3/4"1'-3 3/4"
8"8" 9 3/4"9 3/4"
W14X22 BEAMSW14X22 BEAMS
1/2" STEEL PLATE WITH 1/2" STEEL PLATE WITH
(4) THROUGH BOLTS(4) THROUGH BOLTS
2"2"
SECOND FLOORSECOND FLOOR
FRAMING PLANFRAMING PLAN
EL. 394'-0"EL. 394'-0"
CONTRACTOR SHALL FIELD VERIFY CONTRACTOR SHALL FIELD VERIFY
HSS COLUMN PLACEMENT HSS COLUMN PLACEMENT
RELATIVE TO THE WALL AND RELATIVE TO THE WALL AND
EXISTING BEAM. ACTUAL FIELD EXISTING BEAM. ACTUAL FIELD
CONDITIONS MAY REQUIRE CONDITIONS MAY REQUIRE
ADJUSTMENT OF PLATE ADJUSTMENT OF PLATE
DIMENSIONS.DIMENSIONS.
8" X 4" X 1/4" X 0'-4" LONG 8" X 4" X 1/4" X 0'-4" LONG
BENT PLATE WITH (1) THROUGH BENT PLATE WITH (1) THROUGH
BOLTBOLT
11"11"
1/2" STEEL PLATE1/2" STEEL PLATE
1/41/4
TYP.TYP.
L4X4 BRACINGL4X4 BRACINGHSS5X5HSS5X5
ADJUST AS REQUIRED FOR ADJUST AS REQUIRED FOR
FLASHING HEIGHT AND ROOF FLASHING HEIGHT AND ROOF
THICKNESSTHICKNESS
F13F13
1 1/2"1 1/2"
W14X22 BEAMW14X22 BEAM
L4X4 BRACINGL4X4 BRACING
8" X 6" X 1/4" X 0'-6" 8" X 6" X 1/4" X 0'-6"
LONG BENT PLATELONG BENT PLATE
1/4" STEEL PLATE CENTERED1/4" STEEL PLATE CENTERED
1/2" STEEL TOP PLATE1/2" STEEL TOP PLATE
1/41/4
1 1/2"1 1/2"
(2) L6X4X5/16 LLV ANGLE (2) L6X4X5/16 LLV ANGLE
LINTEL ABOVE OPENING, EMBED LINTEL ABOVE OPENING, EMBED
12" EACH SIDE OF OPENING.12" EACH SIDE OF OPENING.
EXISTING BRICK MASONRY EXISTING BRICK MASONRY
WALLS, REPLACE BRICKS AS WALLS, REPLACE BRICKS AS
NEEDED TO CONSTRUCT.NEEDED TO CONSTRUCT.
C
LI
EN
T:
PR
O
JE
C
T:
DRAWN
NO.
DRAWING TITLE
DRAWING NUMBER
DATE REVISIONS
IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS
THEY ARE ACTING UNDER THE DIRECT DIRECTION OF A
LICENSED PROFESSIONAL ENGINEER, ARCHITECT,
LANDSCAPE ARCHITECT, OR LAND SURVEYOR, TO
ALTER AN ITEM IN ANY WAY. IF AN ITEM BEARING THE
STAMP OF A LICENSED PROFESSIONAL IS ALTERED,
THE ALTERING ENGINEER, ARCHITECT, LANDSCAPE
ARCHITECT, OR LAND SURVEYOR SHALL STAMP THE
DOCUMENT AND INCLUDE THE NOTATION "ALTERED BY"
FOLLOWED BY THEIR SIGNATURE, THE DATE OF SUCH
ALTERATION, AND SPECIFIC DESCRIPTION OF THE
ALTERATION.
DESIGNED
CHECKED
SCALE
DATE
PROJECT
AS NOTED
SEAL
49 Court Street, Suite 240 Binghamton, NY 13901 www.mjinc.com
ARCHITECTS
1741 KIWANIS TR. DUBOIS, PA 15801
814-371-1541 ktharch.com
Au to de sk
D oc s:
//A
BE
C oo lin g To w er
/1
.1
AB
E C oo lin g To w er
_S _V
.rv t
S3.0
SECTIONS
01.19181.12
LMV
OCTOBER 13, 2026
LE
H
IG
H
V A
LL
E
Y
IN
T A
IR
P
O R
T
A irp or t R oa d, A lle nt ow n
P A
. 1
C O
O
LI
N G
T O
W E
R R
E P
LA
C
E M
E N
T
CEP
CEP
SECTIONSECTION
SCALE:SCALE: 3/4" = 1'-0" 3/4" = 1'-0"S3.0S3.0
33SECTIONSECTION
SCALE:SCALE: 3/4" = 1'-0" 3/4" = 1'-0"S3.0S3.0
11 SECTIONSECTION
SCALE:SCALE: 3/4" = 1'-0" 3/4" = 1'-0"S3.0S3.0
SECTIONSECTION
SCALE:SCALE: 3/4" = 1'-0" 3/4" = 1'-0"S3.0S3.0
44 SECTIONSECTION
SCALE:SCALE: 3/4" = 1'-0" 3/4" = 1'-0"S3.0S3.0
SECTIONSECTION
SCALE:SCALE: 3/4" = 1'-0" 3/4" = 1'-0"S3.0S3.0
99SECTIONSECTION
SCALE:SCALE: 3/4" = 1'-0" 3/4" = 1'-0"S3.0S3.0
SECTIONSECTION
SCALE:SCALE: 3/4" = 1'-0" 3/4" = 1'-0"S3.0S3.0
55 SECTIONSECTION
SCALE:SCALE: 3/4" = 1'-0" 3/4" = 1'-0"S3.0S3.0
SECTIONSECTION
SCALE:SCALE: 3/4" = 1'-0" 3/4" = 1'-0"S3.0S3.0
SECOND FLOORSECOND FLOOR
FRAMING PLANFRAMING PLAN
EL. 394'-0"EL. 394'-0"
FCFC
TO
D E
TE
R M
IN
E
D O O R
H E A D E R
H E
IG
H T
TO
D E
TE
R M
IN
E
D O O R
H E A D E R
H E
IG
H T
C O N
TR
A C
TO
R
TO
V E R
IF
Y
R O O F
S Y S
TE
M
TH
IC
K N E S S
C O N
TR
A C
TO
R
TO
V E R
IF
Y
R O O F
S Y S
TE
M
TH
IC
K N E S S
EXIST. W27X84EXIST. W27X84
W14X22W14X22
HSS5X5X1/4HSS5X5X1/4
HSS5X5X1/4HSS5X5X1/4
HSS5X5X1/4HSS5X5X1/4
HSS5X5X1/4HSS5X5X1/4HSS5X5X1/4HSS5X5X1/4
HSS5X5X1/4HSS5X5X1/4HSS5X5X1/4HSS5X5X1/4
W X
W X
H S S X X
H S S X X
H S S X X
H S S X X
H S S X X
H S S X X
H S S X X
H S S X X
1'-7 1/2"1'-7 1/2" 4'-4"4'-4" 6'-1"6'-1" CONTRACTOR TO FIELD VERIFY DISTANCE TO WALLCONTRACTOR TO FIELD VERIFY DISTANCE TO WALL
6'-1"6'-1"
S3.0S3.0
18'-4"18'-4"
S3.0S3.0
2 1/2"2 1/2"
E X
IS
T.
W X
E X
IS
T.
W X
L4 X4 X1 /4
L4 X4 X1 /4 L4
X4 X1 /4
L4 X4 X1 /4
L4X4X1/4
L4X4X1/4
L4 X4 X1 /4
L4 X4 X1 /4
M A X
M A X
DESIGN BRACE CONNECTION FOR DESIGN BRACE CONNECTION FOR
A COMPRESSION AND TENSION A COMPRESSION AND TENSION
LOAD OF 15 KIPS ASD LOAD OF 15 KIPS ASD
(TYPICAL).(TYPICAL).
HSS5X5X1/4HSS5X5X1/4
HSS5X5X1/4HSS5X5X1/4
HSS5X5X1/4HSS5X5X1/4
SECOND FLOORSECOND FLOOR
FRAMING PLANFRAMING PLAN
EL. 394'-0"EL. 394'-0"
F12F12 F13F13
S3.0S3.0
6'-7"6'-7"6'-7"6'-7"6'-9 1/2"6'-9 1/2"5 1/2"5 1/2"
E X
IS
T.
W X
E X
IS
T.
W X
W X
W X
H S S X X
H S S X X
H S S X X
H S S X X
H S S X X
H S S X X
H S S X X
H S S X X
W14X22W14X22
EXIST. W33X118EXIST. W33X118
S3.0S3.0
L4 X4 X1 /4
L4 X4 X1 /4
L4X4X1/4
L4X4X1/4
L4X 4X1
/4
L4X 4X1
/4
L4 X4 X1 /4
L4 X4 X1 /4
L4X4X1/4
L4X4X1/4
L4X 4X 1/
L4X 4X 1/
TYP.TYP.
E X
IS
T.
W X
E X
IS
T.
W X
27'-8"27'-8"
7'-3"7'-3"
S3.0S3.0
HSS5X5X1/4HSS5X5X1/4 HSS5X5X1/4HSS5X5X1/4 HSS5X5X1/4HSS5X5X1/4
HSS5X5X1/4HSS5X5X1/4
HSS5X5X1/4HSS5X5X1/4
HSS5X5X1/4HSS5X5X1/4 HSS5X5X1/4HSS5X5X1/4
HSS5X5X1/4HSS5X5X1/4 HSS5X5X1/4HSS5X5X1/4 HSS5X5X1/4HSS5X5X1/4HSS5X5X1/4HSS5X5X1/4
HSS5X5X1/4HSS5X5X1/4
DESIGN BRACE CONNECTION FOR DESIGN BRACE CONNECTION FOR
A COMPRESSION AND TENSION A COMPRESSION AND TENSION
LOAD OF 15 KIPS ASD LOAD OF 15 KIPS ASD
(TYPICAL).(TYPICAL).
C
LI
EN
T:
PR
O
JE
C
T:
DRAWN
NO.
DRAWING TITLE
DRAWING NUMBER
DATE REVISIONS
IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS
THEY ARE ACTING UNDER THE DIRECT DIRECTION OF A
LICENSED PROFESSIONAL ENGINEER, ARCHITECT,
LANDSCAPE ARCHITECT, OR LAND SURVEYOR, TO
ALTER AN ITEM IN ANY WAY. IF AN ITEM BEARING THE
STAMP OF A LICENSED PROFESSIONAL IS ALTERED,
THE ALTERING ENGINEER, ARCHITECT, LANDSCAPE
ARCHITECT, OR LAND SURVEYOR SHALL STAMP THE
DOCUMENT AND INCLUDE THE NOTATION "ALTERED BY"
FOLLOWED BY THEIR SIGNATURE, THE DATE OF SUCH
ALTERATION, AND SPECIFIC DESCRIPTION OF THE
ALTERATION.
DESIGNED
CHECKED
SCALE
DATE
PROJECT
AS NOTED
SEAL
49 Court Street, Suite 240 Binghamton, NY 13901 www.mjinc.com
ARCHITECTS
1741 KIWANIS TR. DUBOIS, PA 15801
814-371-1541 ktharch.com
Au to de sk
D oc s:
//A
BE
C oo lin g To w er
/1
.1
AB
E C oo lin g To w er
_S _V
.rv t
S4.0
WALL
ELEVATIONS
01.19181.12
LMV
OCTOBER 13, 2026
LE
H
IG
H
V A
LL
E
Y
IN
T A
IR
P
O R
T
A irp or t R oa d, A lle nt ow n
P A
. 1
C O
O
LI
N G
T O
W E
R R
E P
LA
C
E M
E N
T
CEP
CEP
SECTIONSECTION
SCALE:SCALE: 3/4" = 1'-0" 3/4" = 1'-0"S4.0S4.0
SECTIONSECTION
SCALE:SCALE: 3/4" = 1'-0" 3/4" = 1'-0"S4.0S4.0
1. ALL HSS5X5X1/4 BEAMS SHALL HAVE BOLTED CONNECTIONS ON EACH END.1. ALL HSS5X5X1/4 BEAMS SHALL HAVE BOLTED CONNECTIONS ON EACH END.
2. ALL L4X4X1/4 BRACING SHALL HAVE BOLTED CONNECTIONS ON EACH END AND SHALL BE DESIGNED BY THE STEEL FABRICATOR.2. ALL L4X4X1/4 BRACING SHALL HAVE BOLTED CONNECTIONS ON EACH END AND SHALL BE DESIGNED BY THE STEEL FABRICATOR.
1. ALL HSS5X5X1/4 BEAMS SHALL HAVE BOLTED CONNECTIONS ON EACH END.1. ALL HSS5X5X1/4 BEAMS SHALL HAVE BOLTED CONNECTIONS ON EACH END.
2. ALL L4X4X1/4 BRACING SHALL HAVE BOLTED CONNECTIONS ON EACH END AND SHALL BE DESIGNED BY THE STEEL FABRICATOR.2. ALL L4X4X1/4 BRACING SHALL HAVE BOLTED CONNECTIONS ON EACH END AND SHALL BE DESIGNED BY THE STEEL FABRICATOR.
MV
AV
M
T
DN
HVAC LEGEND
DESCRIPTIONABBREVIATIONABBREVIATION DESCRIPTIONDESCRIPTIONABBREVIATIONABBREVIATION DESCRIPTION
AAD AUTOMATIC DAMPER
ACU AIR CONDITIONING UNIT
AD ACCESS DOOR
AFF ABOVE FINISH FLOOR
AHU AIR HANDLING UNIT
APD AIR PRESSURE DROP IN. WG
ATU AIR TERMINAL UNIT
AWT AVERAGE WATER TEMPERATURE
BAS BUILDING AUTOMATION SYSTEM
BDD BACK DRAFT DAMPER
BFS BOILER FEED STATION
BHP BRAKE HORSEPOWER
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNITS PER HOUR
CFM CUBIC FEET PER MINUTE
CU CONDENSING UNIT
CUH CABINET UNIT HEATER
D DIFFUSER
db DRY BULB (°F)
DDC DIRECT DIGITAL CONTROL
DHW DOMESTIC HOT WATER
DIA, ø DIAMETER
DN DOWN
DWG DRAWING
DX DIRECT EXPANSION
(E) EXISTING
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE (°F)
EC ELECTRICAL CONTRACTOR
EDB ENTERING DRY BULB
EFF EFFICIENCY
ESP EXTERNAL STATIC PRESSURE
EWB ENTERING WET BULB (°F)
EWT ENTERING WATER TEMPERATURE (°F)
F FAN
° F DEGREES FAHRENHEIT
FA FREE AREA (SQ. FT.)
FCU FAN COIL UNIT
FD FIRE DAMPER (WITH ACCESS DOOR)
FLA FULL LOAD AMPS
FPI FINS PER INCH
FPM FEET PER MINUTE
FSD FIRE-SMOKE DAMPER (WITH ACCESS DOOR)
FT or ' FEET (OF HEAD)
FTR FIN TUBE RADIATION
G GRILLE
GAL GALLONS
GC GENERAL CONSTRUCTION CONTRACTOR
GPH GALLONS PER HOUR
HP HORSEPOWER
HWR HOT WATER RETURN
HWS HOT WATER SUPPLY
KW KILOWATTS
L LOUVER
LAT LEAVING AIR TEMPERATURE (°F)
LBS POUNDS
LD LOUVER/DAMPER
LDB LEAVING DRY BULB
LWB LEAVING WET BULB
LWT LEAVING WATER TEMPERATURE (°F)
MAX MAXIMUM
MBH THOUSAND BTUH
MC MECHANICAL CONTRACTOR
MCA MINIMUM CIRCUIT AMPACITY
MIN MINIMUM
NC NORMALLY CLOSED
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NTS NOT TO SCALE
OA OUTDOOR AIR
PC PLUMBING CONTRACTOR
PD PRESSURE DROP
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
UNIT HEATER
VIBRATION ISOLATOR
PIPING SYMBOLDESCRIPTIONPIPING SYMBOL
2-WAY CONTROL VALVE
GLOBE VALVE
TRIPLE DUTY VALVE
OPEN BUTTERFLY VALVE
GATE VALVE
SOLENOID - ELECTRIC - ON/OFF
DESCRIPTION
PIPING RISE
UNION CONNECTION
BOTTOM PIPE CONNECTION
TOP PIPE CONNECTION
FLANGE CONNECTION
PIPING DROP
PIPING SYMBOL
PRESSURE REDUCING VALVE
CLOSED BUTTERFLY VALVE
STRAINER
BALANCE VALVE
FUSIBLE LINK VALVE
CIRCULATING PUMP
PRESSURE GAUGE
PRESSURE SENSOR
AQUASTAT
DESCRIPTIONMISC. SYMBOLS
DIAL THERMOMETER
PRESSURE SWITCH
PIPE ANCHOR
PIPE GUIDE
PREMANUFACTURED EXPANSION LOOP
FLEXIBLE CONNECTOR
DIRECTION OF FLUID FLOW
PITCH PIPING DOWN
PIPE CAP/ PLUG
PIPING REDUCER - CONCENTRIC
PIPING REDUCER - ECCENTRIC
VACUUM BREAKER
MISC. SYMBOLS
THERMOSTAT
POINT OF CONNECTION/DISCONNECTION
THERMOMETER
CEILING GRILLE (G)
CEILING DIFFUSER (D)
REGISTER (R)
LINEAR DIFFUSER (D)
DESCRIPTION
DOOR LOUVER OR UNDERCUT
REMOVE EXISTING EQUIPMENT
FIN TUBE RADIATION WITH ENCLOSURE
FIN TUBE RADIATION BARE ELEMENT
PRESSURE/TEMPERATURE PLUG
MANUAL AIR VENT
FLOW METER
TEMPERATURE WELL
BACKFLOW PREVENTER
STEAM TRAP
AUTOMATIC AIR VENT
3-WAY CONTROL VALVE
(MIXING APPLICATION)
(DIVERTING APPLICATION)
3-WAY CONTROL VALVE
RELIEF VALVE
CHECK VALVE
BALL VALVE - CLOSED
BALL VALVE - OPEN
FLOW SWITCH
DESCRIPTION
AIR FLOW
WALL REGISTER OR GRILLE -
ROOF EXHAUST FAN
NON-POWERED ROOF VENTILATOR
DUCT SYMBOL DESCRIPTION
MAKE UP WATER
PUMPED DISCHARGE
REFRIGERANT LIQUID
CONDENSER WATER SUPPLY
CONDENSER WATER RETURN
REFRIGERANT SUCTION
MU
PD
RL
CWS
DESCRIPTIONDUCT SYMBOL
PIPING SYMBOLS
ATV
CD
BBD
ATMOSPHERIC VENT
BOILER BLOW DOWN
CONDENSATE DRAIN
DESCRIPTION
CHILLED WATER SUPPLY
CHILLED WATER RETURN
CHWS
G
HWS
NATURAL GAS
HOT WATER SUPPLY
HOT WATER RETURN
CAST IRON RADIATIONCIR
GPM GALLONS PER MINUTE
RV ROOF VENT
SL SKYLIGHT
UH UNIT HEATER
RTU ROOF TOP UNIT
MAU MAKE UP AIR UNIT
UV UNIT VENTILATOR
V VENT
RA RETURN AIR / RELIEF AIR
EF EXHAUST FAN
MA MIXED AIR
SCCV SELF CONTAINED CONTROL VALVE
TEMPERATURE SENSOR
HWR
RS
CWR
CHWR
EXISTING EQUIPMENT TO REMAIN
NEW EQUIPMENT
SD
FSD
OR
X"xX"
D S
FD
CAPPED DUCT
DUCT TRANSITION FROM
RECTANGULAR TO ROUND
FIRE/SMOKE DAMPER
SMOKE DAMPER
SQUARE TO ROUND BRANCH DUCT
RADIUS ELBOW (MIN R/W = 1.5)
RECTANGULAR ELBOW WITH
TURNING VANES
DUCT - DOWN - NEGATIVE PRESSURE
DUCT - UP - NEGATIVE PRESSURE
DUCT - DOWN - POSITIVE PRESSURE
DUCT SIZE - FIRST FIGURE IS SIZE
DUCT - UP - POSITIVE PRESSURE
DUCT - UP THRU ROOF - POSITIVE PRESSURE
DUCT - UP THRU ROOF - NEGATIVE PRESSURE
SHOWN
FLEXIBLE CONNECTION
ACOUSTICALLY LINED DUCTWORK
FLEXIBLE DUCT
FIRE DAMPER
VOLUME DAMPER
DUCT SMOKE DETECTOR
DUCT TRANSITION FROM
RECTANGULAR TO RECTANGULAR
N.O.
N.C.
C
N.C.
C
N.O.
T
S
1. THESE GENERAL MECHANICAL NOTES SHALL APPLY TO ALL M SERIES DRAWINGS, IN COORDINATION WITH DIVISION 23 SECTIONS, AND FRONT END (DIVISION 0 AND 1) REQUIREMENTS. ALL WORK ASSOCIATED WITH THE M SERIES DRAWINGS SHALL BE COORDINATED WITH ALL OTHER TRADES TO AVOID CONFLICTS.
2. ALL WORK SHALL BE PERFORMED IN COOPERATION WITH THE OWNER (AND/OR OWNER'S REPRESENTATIVE) AND THE ARCHITECT/ENGINEER THE CONTRACTOR SHALL COORDINATE ALL WORK WITH THE CONSTRUCTION SCHEDULE ESTABLISHED BY THE OWNER AND ARCHITECT, AND SHALL IMMEDIATELY
REPORT ANY DELAYS IN MATERIALS RECEIPT INCLUDING CIRCUMSTANCES CAUSING DELAYS.
3. CONTRACT DRAWINGS FOR THE MECHANICAL WORK ARE DIAGRAMMATIC, INTENDED TO CONVEY THE SCOPE OF WORK AND TO INDICATE THE GENERAL ARRANGEMENT AND APPROXIMATE LOCATION OF EQUIPMENT, DUCTWORK, PIPING, AND ACCESSORIES. THE INSTALLING CONTRACTOR SHALL BE RESPONSIBLE FOR CHECKING AND VERIFYING ALL CONDITIONS, DIMENSIONS, AND LOCATIONS PRIOR TO BIDDING PROJECT. CHECK PROJECT DRAWINGS PRIOR TO INSTALLATION FOR INTERFERENCES WITH OTHER TRADES. SHOULD THE CONTRACTOR FIND SUCH INTERFERENCES, THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING HIS WORK WITH OTHERS. THE OWNER RESERVES THE RIGHT TO MAKE REASONABLE CHANGES PRIOR TO ROUGH-IN WITHOUT ADDED EXPENSE.
DIMENSIONS INDICATED ARE SUBJECT TO VERIFICATION OF EXACT SITE CONDITIONS AT THE TIME OF INSTALLATION.
• THE CONTRACTOR SHALL INSTALL ALL DUCTWORK, PIPING, EQUIPMENT, ETC. IN A WORKMANLIKE MANNER WITH QUALIFIED CONTRACTORS.
4. ALL MECHANICAL WORK SHALL BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE MECHANICAL CODE, PLUMBING CODE, HEALTH CODE, FIRE CODE, ENERGY CONSERVATION CODE, AND BUILDING CODE. ALL WORK SHALL COMPLY WITH LOCAL, STATE AND FEDERAL REGULATIONS AND OTHER AUTHORITIES
HAVING JURISDICTION.
5. CONTRACTOR RESPONSIBLE FOR PAYING FOR ALL FEES ASSOCIATED WITH OBTAINING PERMITS, INSPECTIONS, ETC.
6. THE MECHANICAL CONTRACTOR SHALL BE LICENSED IN THE LOCAL JURISDICTION PRIOR TO BIDDING ON PROJECT. CONTRACTOR TO CONTACT
CITY/TOWNSHIP TO VERIFY LICENSE TO ENSURE THEY ARE CURRENT.
7. ALL MECHANICAL EQUIPMENT SHALL BE INSTALLED PER MANUFACTURER RECOMMENDATIONS. ANY CONFLICTS WITH INSTALLATION AND MANUFACTURER
RECOMMENDATIONS SHALL BE REPORTED TO ENGINEER.
8. CUTTING AND PATCHING
• CONTRACTOR IS RESPONSIBLE FOR ALL CUTTING AND PATCHING THROUGH WALLS, CEILINGS, ETC. AND FINISHING OF AFFECTED SURFACES, UNLESS
OTHERWISE NOTED. CONTRACTOR IS RESPONSIBLE FOR COORDINATING THEIR SUBCONTRACTORS.
• IF, AFTER WORK COMPLETION, AN OPENING IS REQUIRED IN A FINISHED SURFACE DUE TO LACK OF COORDINATION, CONTRACTOR SHALL BE
RESPONSIBLE FOR ANY CUTTING AND PATCHING AND FOR RESTORING THE FINISHED SURFACE TO ITS PREVIOUS CONDITION.
• CONTRACTOR IS RESPONSIBLE FOR CUTTING OPENINGS REQUIRED FOR REMOVAL OF EXISTING EQUIPMENT OR INSTALLATION OF NEW EQUIPMENT
SUPPLIED UNDER THE CONTRACT AND PATCHING AND RESTORING THE FINISHED SURFACE TO ITS PREVIOUS CONDITION.
9. FURNISH AND INSTALL ALL NEW EQUIPMENT AND MATERIALS AS DESCRIBED HEREIN. ANY MATERIAL, OPERATION, METHOD, OR DEVICE MENTIONED, LISTED OR NOTED WITHIN THIS SPECIFICATION SHALL BE FURNISHED BY THIS CONTRACTOR UNLESS SPECIFICALLY MENTIONED AS BEING FURNISHED OR INSTALLED BY
OTHERS.
10. ALL PIPING AND DUCT PENETRATING ALL FIRE-RATED WALLS, CEILINGS, FLOORS, ROOFS, ETC. SHALL BE FIRE STOPPED IN ACCORDANCE WITH DIVISION 7.
11. THE CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE COMPLETE AND OPERABLE SYSTEMS, INCLUDING OPERATIONAL PROPERTIES TO THE EXTEND NECESSARY TO LINK MULTIPLE COMPONENTS OF THE SYSTEMS TOGETHER AND TO INTERFACE WITH SYSTEMS PROVIDED BY OTHERS. THE MECHANICAL CONTRACTOR SHALL GUARANTEE ALL SYSTEMS AND WORKMANSHIP FOR A PERIOD OF ONE YEAR FROM DATE OF FINAL ACCEPTANCE.
• THE CONTRACTOR SHALL PROVIDE OWNER WITH ALL NECESSARY OPERATION AND MAINTENANCE MANUALS, SHOP DRAWINGS, WIRING DIAGRAMS, AS-
BUILT DRAWINGS, AND WARRANTY PAPERWORK UPON COMPLETION OF THE PROJECT.
12. THE CONTRACTOR IS RESPONSIBLE FOR TESTING, AND ADJUSTING ALL MECHANICAL EQUIPMENT INDICATED IN THE MECHANICAL DRAWINGS.
13. ALL PIPING PENETRATIONS THROUGH EXPOSED WALLS SHALL BE PROVIDED WITH CHROME ESCUTCHEONS AND SEAL TO WALL OR CEILING.
14. EQUIPMENT CONNECTIONS:
• ALL EQUIPMENT SHALL BE PROVIDED WITH UNIONS AND SHUT-OFF VALVES WHETHER DETAILED OR NOT.
• ALL MECHANICAL HYDRONIC OR REFRIGERANT EQUIPMENT SHALL BE PROVIDED WITH SHUT OFF VALVES.
15. ALL PENETRATIONS THROUGH ROOFING MEMBRANE AND ROOF DECKING SHALL BE PERFORMED BY AN INSTALLER CERTIFIED BY THE ROOFING SYSTEM
MANUFACTURER TO MAINTAIN ROOF SYSTEM WARRANTY.
16. NATURAL GAS REGULATOR VENT PIPING SHALL EXTEND TO THE EXTERIOR OF THE BUILDING AND TERMINATE IN ACCORDANCE WITH NFPA 54 AND/OR NFPA
58. ALL EXTERIOR GAS PIPING SHALL BE PAINTED WITH TWO COATS OF PRIMER AND ONE COAT OF FINISH PAINT. COLOR TO BE DETERMINED BASED COLOR OF
SURROUNDING SURFACES.
17. RODENT PROOFING - IN OR ON STRUCTURES WHERE OPENINGS HAVE BEEN MADE IN FLOORS CEILINGS, OR WALLS FOR THE PASSAGE OF DUCT OR PIPE, SUCH OPENINGS SHALL BE CLOSED AND PROTECTED WITH APPROVED METAL COLLARS THAT ARE SECURELY FASTENED TO THE ADJOINING STRUCTURE.
18. STRUCTURAL SAFETY - IN THE PROCESS OF INSTALLING OR REPAIRING ANY PART OF A MECHANICAL SYSTEM, THE FINISHED FLOOR, WALLS, CEILINGS, TILE OR ANY OTHER PART OF THE BUILDING OR PREMISES THAT MUST BE CHANGED OR REPLACED SHALL REMAIN IN A STRUCTURALLY SAFE CONDITION IN
ACCORDANCE WITH THE REQUIREMENTS OF THE BUILDING CODE OF PENNSYLVANIA.
19. PROTECTION OF DUCTS, PIPES AND MECHANICAL SYSTEM COMPONENTS - PIPING, DUCT AND OTHER SYSTEM COMPONENTS SHALL BE INSTALLED IN SUCH A MANNER SO AS TO PREVENT CORROSION, BREAKAGE, FREEZING, AND PHYSICAL DAMAGE BY OTHER BUILDING COMPONENTS IN ACCORDANCE WITH THE
REQUIREMENTS OF THE BUILDING CODE.
20. CONTROL CONTRACTOR RESPONSIBLE FOR ALL ELECTRICAL CIRCUITS TO POWER ALL CONTROL PANELS AND DEVICES.
GENERAL NOTES:
C L
IE
N T
P R
O J E
C T
DRAWN
NO.
DRAWING TITLE
DRAWING NUMBER
DATE REVISIONS
IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS
THEY ARE ACTING UNDER THE DIRECT DIRECTION OF A
LICENSED PROFESSIONAL ENGINEER, ARCHITECT,
LANDSCAPE ARCHITECT, OR LAND SURVEYOR, TO
ALTER AN ITEM IN ANY WAY. IF AN ITEM BEARING THE
STAMP OF A LICENSED PROFESSIONAL IS ALTERED,
THE ALTERING ENGINEER, ARCHITECT, LANDSCAPE
ARCHITECT, OR LAND SURVEYOR SHALL STAMP THE
DOCUMENT AND INCLUDE THE NOTATION "ALTERED BY"
FOLLOWED BY THEIR SIGNATURE, THE DATE OF SUCH
ALTERATION, AND SPECIFIC DESCRIPTION OF THE
ALTERATION.
DESIGNED
CHECKED
SCALE
DATE
PROJECT
AS NOTED
SEAL
49 Court Street, Suite 240 Binghamton, NY 13901 www.mjinc.com
ARCHITECTS
1741 KIWANIS TR. DUBOIS, PA 15801
814-371-1541 ktharch.com
A u to d e s k D o c s /A
B E
C o o lin g T o w e r/
.1
A
B E
C o o lin g T o w e r_
M V
.r v t
M000
LEGEND, AND
NOTES
19181.12
WH
OCTOBER 13, 2026
L E
H
IG
H V
A L L E
Y I N
T A
IR
P
O R
T
A ir p o rt
R o a d
A lle n to w n P
A
C O
O L
IN
G T
O W
E R
R E
P L A
C E
M E
N T
MRM
MRM
D1
10" CWS (E)
& 6" CWR (E) DN.
10" CWS (E) 6" CWR (E)
CT-1(E)
CU-1(E)
CU-2(E)
D5
D5
D2
D3
REMOVE
ACCESS/SERVICE
PLATFORM
MAINTAIN ISOLATION
VALVES (TYP)
REMOVE WALL MOUNTED
PIPE SUPPORTS
CONTROL CONDUIT
LB HIGH ON WALL
D4
R1R1
10" CWS (E)
& 6" CWR (E) DN.
10" CWS (E)
6" CWR (E)
CT-1
R8
R8
CU-1
CU-2
R5
R3
R4 R4
R3
R3
R6
R7
R2R2
PROVIDE NEW
NON-PENETRATING
PIPE SUPPORTS.
MINIMUM OF 4.
R9
8804400 61,6005 10,020 152
UNIT MCA
460/3 EVAPCO AT-28-3GI77 1, 2, 3
OPERATING
NOTE:
COOLING TOWER SCHEDULE
UNIT NO.
NOTES
LOCATION
DESIGN BASIS
DIMENSIONS
length" width" height"
E.W.T.
(degrees F)
L.W.T.
(degrees F)
WEIGHT (lbs.)
FAN
(HP EA.)
FAN FLOW
G.P.M.
FLOWCAPACITY
(mbh) (C.F.M.)
205.5 132CT-1 ROOF
ELECTRICAL
UNIT MOP CONN. POINTSPHASE
VOLTS /
FAN
QUANTITY
1. PROVIDE EXTERNAL WALKWAY, HANDRAILS AND LADDER.
2. PROVIDE DAVIT AT EACH UNIT FOR FAN MOTOR REPLACEMENT.
3. MAINTAIN EXISTING WATER TREATMENT SYSTEM AND CONTROLS
C.F.M
AREA SERVEDUNIT NO. SUPPLY
TOTAL
NOTESDESIGN BASIS
SPLIT SYSTEM INDOOR UNIT SCHEDULE
LOCATION
VOLTS/PHASE CONN. POINTS
ELECTRICAL PHYSICAL PROPERTIES
LENGTH" DEPTH" HEIGHT" WEIGHT LBS.
MAX.
COOLING
CAPACITY
(MBH)
MCA MOP
SS-1 DATA RM A126 DATA ROOM 735 1 15 208/1 1 22 54 11.625 14.375 54 HITACHI PPK-B24UFA1DQ 1
SS-2 DATA RM A126 DATA ROOM 735 208/11 15 1 22
SEER2
21.5
21.5
EER2
13 54 11.625 14.375 54 1
NOTES: 1. INDOOR UNIT POWERED FROM OUTDOOR UNIT.
HITACHI PPK-B24UFA1DQ
SYSTEM SERVEDLOCATIONUNIT NO. NOMINAL
CAPACITY
(MBH)
NOTES
VOLTS/PHASE UNIT MCA UNIT MOP
ELECTRICAL PHYSICAL PROPERTIES
CONN. POINT LENGTH" DEPTH" HEIGHT" WEIGHT LBS.
DESIGN BASIS
SPLIT SYSTEM OUTDOOR UNIT SCHEDULE
EER2SEER2
CU-1 ROOF SS-1 21.5 13 24 208/1 14.3 20 1 35.5 12.5 26.25 104 HITACHI PAS-24BUUFASDQ1 1
CU-1 ROOF SS-2 2421.5 13 208/1 14.3 20 1 1
NOTES: 1. UNIT CONTROLS SHALL BE STAND ALONE
35.5 12.5 26.25 104 HITACHI PAS-24BUUFASDQ1
D4
D2
D1
D3
R1
R3
R4
R5
D5 D5
DATA ROOM
A126
SS-1(E)
SS-2(E)
2" COND.(E) DN.
DATA ROOM
A126
SS-1
SS-2
5/8" RS/3/8" RL
UP TO CU-1 ON ROOF
5/8" RS/3/8" RL
UP TO CU-2 ON ROOF
1" COND. TO
EXISTING PIPE IN WALL
1" COND. TO
EXISTING PIPE IN WALL
2" COND.(E) DN.
T T
SS-1 SS-2
C L
IE
N T
P R
O J E
C T
DRAWN
NO.
DRAWING TITLE
DRAWING NUMBER
DATE REVISIONS
IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS
THEY ARE ACTING UNDER THE DIRECT DIRECTION OF A
LICENSED PROFESSIONAL ENGINEER, ARCHITECT,
LANDSCAPE ARCHITECT, OR LAND SURVEYOR, TO
ALTER AN ITEM IN ANY WAY. IF AN ITEM BEARING THE
STAMP OF A LICENSED PROFESSIONAL IS ALTERED,
THE ALTERING ENGINEER, ARCHITECT, LANDSCAPE
ARCHITECT, OR LAND SURVEYOR SHALL STAMP THE
DOCUMENT AND INCLUDE THE NOTATION "ALTERED BY"
FOLLOWED BY THEIR SIGNATURE, THE DATE OF SUCH
ALTERATION, AND SPECIFIC DESCRIPTION OF THE
ALTERATION.
DESIGNED
CHECKED
SCALE
DATE
PROJECT
AS NOTED
SEAL
49 Court Street, Suite 240 Binghamton, NY 13901 www.mjinc.com
ARCHITECTS
1741 KIWANIS TR. DUBOIS, PA 15801
814-371-1541 ktharch.com
A u to d e s k D o c s /A
B E
C o o lin g T o w e r/
.1
A
B E
C o o lin g T o w e r_
M V
.r v t
M100
MECHANICAL
PLANS AND
SCHEDULES
19181.12
WH
OCTOBER 13, 2026
L E
H
IG
H V
A L L E
Y I N
T A
IR
P
O R
T
A ir p o rt
R o a d
A lle n to w n P
A
C O
O L
IN
G T
O W
E R
R E
P L A
C E
M E
N T
MRM
MRM
1/4" = 1'-0"
FINISHED FLOOR MECHANICAL DEMOLITION PLAN
1/4" = 1'-0"
FINISHED FLOOR MECHANICAL RENOVATION PLAN
MECHANICAL DEMOLITION NOTES
D1 DISCONNECT AND REMOVE EXISTING COOLING TOWER. MAINTAIN EXISTING PIPING FOR
NEW WORK.
D2 DISCONNECT PIPING FOR TOWER AND REMOVE TO FIRST COUPLING. (TYP.)
D3 DISCONNECT AND REMOVE PIPING AT SCREEN WALL PENETRATION TO FACILITATE WALL
REMOVAL. TEMPORARILY SUPPORT PIPING LEFT FROM REMOVALS. RETAIN PIPING FOR
REINSTALLATION.
D4 REMOVE SENSOR, WIRE AND CONDUIT FROM PIPING SYSTEM AND MAINTAIN FOR
REINSTALLATION.
D5 REMOVE WALL MOUNTED CONDENSING UNIT, RS/RL PIPING TO DATA ROOM ON FIRST
FLOOR AND ASSOCIATED INDOOR UNIT, CONTROLS AND CONDENSATE PIPING. MAINTAIN
CONDENSING UNIT WALL BRACKETS FOR NEW UNIT INSTALLATION.
MECHANICAL RENOVATION NOTES
R1 PROVIDE NEW COOLING TOWER. RECONNECT TO EXISTING PIPING LEFT FROM
REMOVALS.
R2 PROVIDE NEW SPRING ISOLATOR MOUNTS (TYP. 8)
R3 PROVIDE NEW PIPING AND COUPLINGS. CONNECT EXISTING PIPING TO NEW TOWE (TYP.).
R4 PROVIDE NEW SPOOL PIPE WITH SENSOR WELL. REINSTALL EXISTING SENSORS AND
CONDUIT AT NEW UNIT.
R5 REINSTALL PIPING THROUGH NEW SCREEN WALL. COORDINATE SIZE AND LOCATION OF
OPENING WITH GENERAL CONSTRUCTION CONTRACTOR.
R6 PROVIDE REMOVABLE DAVIT TO BE USED FOR FAN MOTOR REPLACEMENT. (TYP. 2)
R7 PROVIDE EXTERNAL EQUIPMENT SERVICE PLATFORM. BASED ON EVAPCO MODEL.
R8 PROVIDE WALL MOUNTED CONDENSING UNIT, 5/8" RS/3/8" RL PIPING TO DATA ROOM ON
FIRST FLOOR.
R9 PROVIDE NEW SENSOR WELLS AND RE-INSTALL TEMPERATURE SENSORS, CONDUIT AND
WIRING (TYP.).
DEMOLITION MECH ISO
RENOVATION MECH ISO
1/4" = 1'-0"
FIRST FLOOR MECHANICAL DEMOLITION
1/4" = 1'-0"
FIRST FLOOR MECHANICAL RENOVATION
DOOR CONTACT
CARD READER
LOCAL ALARM/SIREN (AUDIBLE)
REQUEST-TO-EXIT MOTION SENSOR
FIXED DOME IP CAMERA
PTZ IP CAMERA
SECURITY LEGEND
DC
CR
LA
REX
G
POWER LEGEND
G
WP
J
DATA JACK - SINGLE PORT
DATA JACK - (#) = NUMBER OF PORTS
WIRELESS ACCESS POINT
TELEPHONE JACK - WALL MOUNT
FLOOR BOX ASSEMBLY - DATA JACK (#) PORTS
CLOCK
LOW-VOLTAGE LEGEND
WAP
SPRINKLER FLOW SWITCH
SPRINKLER TAMPER SWITCH
PRESSURE SWITCH
ADDRESSABLE INPUT MODULE (MONITORING)
ADDRESSABLE OUTPUT MODULE (RELAY)
MAGNETIC HOLD OPEN
MANUAL PULL STATION
NOTIFICATION DEVICE - SPEAKER/STROBE
NOTIFICATION DEVICE - STROBE
NOTIFICATION DEVICE - CARBON MONOXIDE STROBE
SMOKE DETECTOR (L = LOBBY SMOKE DETECTOR)
HEAT DETECTOR
DUCT SMOKE DETECTOR
CARBON MONOXIDE DETECTOR
SPRINKLER ALARM BELL
FIRE ALARM OSID - OPEN AREA SMOKE IMAGE
DETECTOR - EMITTER
FIRE ALARM OSID - OPEN AREA SMOKE IMAGE
DETECTOR - IMAGER, # = FIELD OF VIEW RANGE
FIRE ALARM LEGEND
TS
FS
M
AIM
AOM
F
F
S
H
CO
C
S
V
PS
LIGHT FIXTURE, REFER TO LIGHT FIXTURE
SCHEDULE
CEILING MOTION SENSOR - DUAL TECH.
CORNER MOUNT MOTION SENSOR - DUAL TECH.
SINGLE POLE LIGHT SWITCH
3-WAY LIGHT SWITCH
DIMMER SWITCH
MOTION SENSOR SWITCH (DUAL TECH.)
MOTION SENSOR SWITCH (INFRARED)
DIMMING MOTION SENSOR SWITCH (DUAL TECH.)
DIGITAL NETWORK MULTI-BUTTON SWITCH
PILOT LIGHT SWITCH
EXIT SIGN - SINGLE SIDED
EXIT SIGN - DOUBLE SIDED
EXIT SIGN - TRIANGLES INDICATE DIRECTION
ARROWS
TIME CLOCK
PHOTOCELL
LIGHTING LEGEND
D
M
P
LD
MI
M
MS
MD
W
P
PC
TC
C
B
I
E
NEMA 5-20 DUPLEX RECEPTACLE
NEMA 5-20 DUPLEX RECEPTACLE - GFI
NEMA 5-20 DUPLEX RECEPTACLE -
WEATHERPROOF, GFI
NEMA 5-20 DUPLEX RECEPTACLE, ABOVE
COUNTER
NEMA 5-20 DUPLEX RECEPTACLE, ABOVE
COUNTER, GFI
SPECIAL PURPOSE RECEPTACLE, REFER TO
PLANS FOR CONFIGURATION
QUADRUPLEX RECEPTACLE
MANUAL…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .