This is an Addendum No. 1 document issued November 12, 2025, for the Lillie B. Haynes Elementary School Roof Replacement project in East Lyme, Connecticut (Project #045-0064-RR, LAA#2745-01). The project involves the replacement of the existing built-up roof system with a modified bituminous membrane roofing system. The specification details a two-ply modified asphalt roofing system with multiple installation options, including hot-applied (Base Bid) and cold-applied (Alternate 1) methods, along with a 30-year warranty option (Alternate 2). The project includes installation of thermal insulation layers, vapor barriers, cover boards, edge treatment systems, and roof penetration flashings. The roofing system must achieve Class A fire ratings from Factory Mutual (FM), Underwriters Laboratory (UL), or equivalent testing facilities and must withstand design wind loads per ASCE 7-16 standards with uplift pressures ranging from 31.5 to 81.5 psf depending on roof zone. The contractor must maintain a full-time supervisor on-site during all roofing work and provide weekly progress reports with photographic documentation. The roofing system manufacturer must conduct minimum three site inspections per week at no additional cost and provide final completion certification.

The specification mandates prevailing wage rates effective October 30, 2025, with the Roofer (composition) classification established at $45.15 hourly rate plus $22.44 in benefits. All materials must be manufactured in the United States by an ISO 9001 certified manufacturer with documented 24 years of experience and cannot be private label products. The bidder must disclose the specific manufacturer and products at bid opening, and no material substitutions are permitted after that date. All submitted roofing systems must be accompanied by a report letter from a third-party licensed professional engineer confirming compliance with design and performance criteria. The manufacturer warranty covers 20 years for the Base Bid or 30 years for Alternate 2, with the installer providing a separate three-year warranty against defects in materials and workmanship. The project requires submission of shop drawings, design pressure calculations, manufacturer progress reports, verification samples, manufacturer's site supervision letter, and certification that the system meets LEED reflectivity and emissivity criteria for heat island reduction.

Text of this file

East Lyme Public Schools Lillie B. Haynes ES Roof Replacement 165 Boston Post Rd., PO Box 220 East Lyme, CT 06333 Project # 045-0064-RR

LAA# 2745-01

Date: November 12, 2025

ADDENDUM NO. 1

ATTACHMENT

This Addendum consists of 55 Page(s)

ADDNEDUM NO.1

East Lyme Public Schools Lillie B. Haynes ES Roof Replacement Project # 045-0064-RR

LAA# 2745-01

ADDENDUM 1 NOVEMBER 12, 2025

BLANK PAGE

CLASSIFICATION Hourly Rate Benefits

Lillie B. Haynes Elementary School: Roof ReplacementProject:

Minimum Rates and Classifications for Building Construction

ID#:

By virtue of the authority vested in the Labor Commissioner under provisions of Section 31-53 of the General Statutes of Connecticut, as amended, the following are declared to be the prevailing rates and welfare payments and will apply only where the contract is advertised for bid within 20 days of the date on which the rates are established. Any contractor or subcontractor not obligated by agreement to pay to the welfare and pension fund shall pay this amount to each employee as part of his/her hourly wages.

Project Number: 045-0064 RR State#:

Project:

FAP#:

Project Town:

Lillie B. Haynes Elementary School: Roof Replacement

East Lyme

Connecticut Department of Labor Wage and Workplace Standards Division

25-11143

1b) Asbestos/Toxic Waste Removal Laborers: Asbestos removal and encapsulation (except its removal from mechanical systems which are not to be scrapped), toxic waste removers, blasters.**See Laborers Group 7**

1c) Asbestos Worker/Heat and Frost Insulator 48.81 34.05

2) Boilermaker 48.21 30.01

3a) Bricklayer, Cement Mason, Concrete Finisher (including caulking), Stone Masons

42.61 34.89 + a

3b) Tile Setter 40.0 32.75

3c) Tile and Stone Finishers 33.0 27.43

3d) Marble & Terrazzo Finishers 34.2 26.23

3e) Plasterer 44.52 29.63

As of: October 30, 2025 ADDENDUM 1 NOVEMBER 12, 2025

3f) Terrazzo Mechanics & Marble Setters 40.6 34.93

------LABORERS------

4) Group 1: General laborers, carpenter tenders, concrete specialists, wrecking laborers and fire watchers.

35.7 28.85

4) Group 1a: Acetylene Burners (Hours worked with a torch) 36.7 28.85

4a) Group 2: Mortar mixers, plaster tender, power buggy operators, powdermen, fireproofer/mixer/nozzleman (Person running mixer and spraying fireproof only).

35.95 28.85

4b) Group 3: Jackhammer operators/pavement breaker, mason tender (brick), mason tender (cement/concrete), forklift operators and forklift operators (masonry).

36.2 28.85

4c) **Group 4: Pipelayers: Licensed P6 -P7 (one or two employees of the total crew who primary task is to perform mating of pipe sections).

36.7 28.85

4d) Group 5: Air track operator, sand blaster and hydraulic drills. 36.45 28.85

4e) Group 6: Blasters, nuclear and toxic waste removal. 38.7 28.85

4f) Group 7: Asbestos/lead removal and encapsulation (except it's removal from mechanical systems which are not to be scrapped).

38.7 28.85

4g) Group 8: Bottom men on open air caisson, cylindrical work and boring crew.

36.2 28.85

4h) Group 9: Top men on open air caisson, cylindrical work and boring crew. 35.7 28.85

4i) Group 10: Traffic Control Signalman 21.42 28.85

4j) Group 11: Toxic Waste Removers A or B With PPE 38.7 28.85

5) Carpenter, Acoustical Ceiling Installation, Soft Floor/Carpet Laying, Metal Stud Installation, Form Work and Scaffold Building, Drywall Hanging, Modular-Furniture Systems Installers, Lathers, Piledrivers, Resilient Floor Layers.

42.03 29.19

5a) Millwrights 43.25 29.13

5b) Carpenter - Welder 42.53 29.19

5c) Carpenter: Working with creosote lumber or acid 43.03 29.19

6) Electrical Worker (including low voltage wiring) (Trade License required:

E1,2 L-5,6 C-5,6 T-1,2 L-1,2 V-1,2,7,8,9)

46.4 36.66+3% of gross wage

7a) Elevator Mechanic (Trade License required: R-1,2,5,6) 66.72 38.435+a+b

-----OUTSIDE LINE CONSTRUCTION----

Groundman 32.1 13.95

Linemen/Cable Splicer 58.37 33.94

8) Glazier (Trade License required: FG-1,2) 43.13 26.50+ a

9) Ironworker, Ornamental, Reinforcing, Structural, and Precast Concrete Erection

45.25 43.62 + a

----OPERATORS----

Group 1: Crane Handling or Erecting Structural Steel or Stone; Hoisting Engineer (2 drums or over). (Trade License Required)

58.19 29.80 + a

Group 1a: Front End Loader (7 cubic yards or over); Work Boat 26 ft. and Over

53.33 29.80 + a

Group 2: Cranes (100 ton rate capacity and over); Bauer Drill/Caisson.

(Trade License Required)

57.78 29.80 + a

Group 2a: Cranes (under 100 ton rated capacity). 56.79 29.80 + a

Group 2b: Excavator over 2 cubic yards; Pile Driver ($3.00 premium when operator controls hammer)

52.92 29.80 + a

Group 3: Excavator; Gradall; Master Mechanic; Hoisting Engineer (all types of equipment where a drum and cable are used to hoist or drag material regardless of motive power of operation), Rubber Tire Excavator (Drott-1085 or similar);Grader Operator; Bulldozer Finegrade. (slopes, shaping, laser or GPS, etc.). (Trade License Required)

51.92 29.80 + a

Group 4: Trenching Machines; Lighter Derrick; CMI Machine or Similar;

Koehring Loader (Skooper); Goldhofer.

51.42 29.80 + a

Group 5: Specialty Railroad Equipment; Asphalt Spreader, Asphalt Reclaiming Machine; Line Grinder; Concrete Pumps; Drills with Self Contained Power Units; Boring Machine; Post Hole Digger; Auger; Pounder;

Well Digger; Milling Machine (over 24 mandrel).

50.63 29.80 + a

Group 5 continued: Side Boom; Combination Hoe and Loader; Directional Driller.

50.63 29.80 + a

Group 6: Front End Loader (3 up to 7 cubic yards); Bulldozer (rough grade dozer).

50.22 29.80 + a

Group 7: Asphalt Roller; Concrete Saws and Cutters (ride on types);

Vermeer Concrete Cutter; Stump Grinder; Scraper; Snooper; Skidder; Milling Machine (24" and under mandrel).

49.77 29.80 + a

Group 8: Mechanic; Grease Truck Operator; Hydroblaster; Barrier Mover;

Power Stone Spreader; Welding; Work Boat Under 26 ft.; Transfer Machine;

Rigger Foreman.

49.25 29.80 + a

Group 9: Front End Loader (under 3 cubic yards); Skid Steer Loader regardless of attachments; (Bobcat or Similar); Forklift, Power Chipper;

Landscape Equipment (including Hydroseeder); Vacuum Excavation Truck and Hydrovac Excavation Truck (27 HG pressure or greater).

48.67 29.80 + a

Group 10: Vibratory hammer; ice machine; diesel and air, hammer, etc. 45.96 29.80 + a

Group 11: Conveyor, earth roller, power pavement breaker (whiphammer), robot demolition equipment.

45.96 29.80 + a

Group 12: Wellpoint Operator. 45.87 29.80 + a

Group 13: Compressor Battery Operator. 45.12 29.80 + a

Group 14: Elevator Operator; Tow Motor Operator (solid tire no rough terrain). 43.6 29.80 + a

Group 15: Generator Operator; Compressor Operator; Pump Operator;

Welding Machine Operator; Heater Operator.

43.06 29.80 + a

Group 16: Maintenance Engineer. 42.2 29.80 + a

Group 17: Portable Asphalt Plant Operator; Portable Crusher Plant Operator;

Portable Concrete Plant Operator; Portable Grout Plant Operator; Portable Water Filtration Plant Operator.

47.91 29.80 + a

Group 18: Power Safety Boat; Vacuum Truck; Zim Mixer; Sweeper;

(Minimum for any job requiring a CDL license); Rigger; Signalman.

44.7 29.80 + a

Surveyor: Chief of Party 48.16 29.80 + a

Surveyor: Assistant Chief of Party 44.41 29.80 + a

Surveyor: Instrument Man 42.73 29.80 + a

Surveyor: Rodman or Chainman 36.78 29.80 + a

------PAINTERS (Including Drywall Finishing)------

10a) Brush and Roller 39.57 26.50

10b) Taping Only/Drywall Finishing 40.32 26.50

10c) Paperhanger and Red Label 40.07 26.50

10d) Spray 42.57 26.50

10e) Spray Helper 40.57 26.50

10f) Blast 44.57 26.50

10g) Blast Helper 40.57 26.50

11) Plumber (excluding HVAC pipe installation) (Trade License required: P-

1,2,6,7,8,9 J-1,2,3,4 SP-1,2)

50.58 36.30

12) Well Digger, Pile Testing Machine 37.26 24.05 + a

13) Roofer (composition) 45.15 22.44

14) Roofer (slate & tile) 45.65 22.44

15) Sheetmetal Worker (Trade License required for HVAC and Ductwork:

SM-1,SM-2,SM-3,SM-4,SM-5,SM-6)

44.7 44.38

16) Pipefitter (Including HVAC work) (Trade License required: S-1,2,3,4,5,6,7,8 B-1,2,3,4 D-1,2,3,4, G-1, G-2, G-8 & G- 9)

50.58 36.30

------TRUCK DRIVERS------

17) Block Truck 37.48 32.68 + a

17a) 2 Axle 36.16 32.68 + a

17ab) Helpers 34.66 32.68 + a

17b) 3 Axle, 2 Axle Mixer 36.27 32.68 + a

17c) 3 Axle Mixer 36.33 32.68 + a

17d) 4 Axle 36.39 32.68 + a

17e) 4 Axle Mixer 37.19 32.68 + a

17ef) 5 Axle 36.39 32.68 + a

17eg) 5 Axle Mixer 37.19 32.68 + a

17f) Heavy Duty Trailer (40 Tons and Over) 38.66 32.68 + a

17g) Euclids and Semi-Trailer 36.44 32.68 + a

17h) Heavy Duty Trailer up to 40 tons 37.39 32.68 + a

17i) Snorkle Truck 36.54 32.68 + a

17j) Swivel Dump and Tack Truck 36.39 32.68 + a

18) Sprinkler Fitter (Trade License required: F-1,2,3,4) 53.76 33.44 + a

19) Theatrical Stage Journeyman 25.76 7.34

Welders: Rate for craft to which welding is incidental.

Surveyors: Hazardous material removal: $3.00 per hour premium.

*Note: Hazardous waste removal work receives additional $1.25 per hour for truck drivers.

**Note: Hazardous waste premium $3.00 per hour over classified rate.

Truck Drivers: Trainers Premium: $3.00 over wage rate.

Truck Drivers: Night Premium - Mixer Drivers: $2.00 over wage rate.

Crane with 150 ft. boom (including jib) - $1.50 extra

Crane with 200 ft. boom (including jib) - $2.50 extra

Crane with 250 ft. boom (including jib) - $5.00 extra

Crane with 300 ft. boom (including jib) - $7.00 extra

Crane with 400 ft. boom (including jib) - $10.00 extra

All classifications that indicate a percentage of the fringe benefits must be calculated at the percentage rate times the "base hourly rate".

Apprentices duly registered under the Commissioner of Labor's regulations on "Work Training Standards for Apprenticeship and Training Programs" Section 31-51-d-1 to 12, are allowed to be paid the appropriate percentage of the prevailing journeymen hourly base and the full fringe benefit rate, providing the work site ratio shall not be less than one full-time journeyperson instructing and supervising the work of each apprentice in a specific trade.

The Prevailing wage rates applicable to this project are subject to annual adjustments each July 1st for the duration of the project.

Each contractor shall pay the annual adjusted prevailing wage rate that is in effect each July 1st, as posted by the Department of Labor.

It is the contractor's responsibility to obtain the annual adjusted prevailing wage rate increases directly from the Department of Labor's website.

The annual adjustments will be posted on the Department of Labor's Web page:

www.ct.gov/dol. For those without internet access, please contact the division listed below.

The Department of Labor will continue to issue the initial prevailing wage rate schedule to the Contracting Agency for the project.

All subsequent annual adjustments will be posted on our Web Site for contractor access.

Contracting Agencies are under no obligation pursuant to State labor law to pay any increase due to the annual adjustment provision.

Effective October 1, 2005 - Public Act 05-50: any person performing the work of any mechanic, laborer, or worker shall be paid prevailing wage

All Person who perform work ON SITE must be paid prevailing wage for the appropriate mechanic, laborer, or worker classification.

All certified payrolls must list the hours worked and wages paid to All Persons who perform work ON SITE regardless of their ownership i.e.: (Owners, Corporate Officers, LLC Members, Independent Contractors, et.

al)

Reporting and payment of wages is required regardless of any contractual relationship alleged to exist between the contractor and such person.

~~Unlisted classifications needed for work not included within the scope of the classifications listed may be added after award only as provided in the labor standards contract clause (29 CFR 5.5 (a) (1) (ii)).

Please direct any questions which you may have pertaining to classification of work and payment of prevailing wages to the Wage and Workplace Standards Division, telephone (860)263-6790.

EAST LYME PUBLIC SCHOOLS

LILLIE B. HAYNES ES ROOF REPLACEMENT

SECTION 075200

MODIFIED BITUMINOUS MEMBRANE

ROOFING

LAA PROJECT # 2745-01 PROJECT NO. 045-0064-RR

SECTION 075200

MODIFIED BITUMINOUS MEMBRANE ROOFING

PART 1 GENERAL

1.1 SECTION INCLUDES

A. Hot Applied 2-Ply Low VOC Asphalt Roofing.

B. Cold Applied 2-Ply Low VOC Asphalt Roofing.

C. Accessories.

D. Edge Treatment and Roof Penetration Flashings.

1.2 REFERENCE STANDARDS

A. ASCE 7 - Minimum Design Loads and Associated Criteria for Buildings and Other Structures;

Most Recent Edition Cited by Referring Code or Reference Standard.

B. ASCE 7-16 - Minimum Design Loads and Associated Criteria for Buildings and Other Structures; 2016.

C. ASTM C920 - Standard Specification for Elastomeric Joint Sealants; 2018.

D. ASTM D93 - Standard Test Methods for Flash Point by Pensky-Martens Closed Cup Tester;

2020.

E. ASTM D412 - Standard Test Methods for Vulcanized Rubber and Thermoplastic Elastomers-- Tension; 2016 (Reapproved 2021).

F. ASTM D523 - Standard Test Method for Specular Gloss; 2025.

G. ASTM D1002 - Standard Test Method for Apparent Shear Strength of Single-Lap-Joint Adhesively Bonded Metal Specimens by Tension Loading (Metal-to-Metal); 2010 (Reapproved 2019).

H. ASTM D1079 - Standard Terminology Relating to Roofing and Waterproofing; 2024.

I. ASTM D1876 - Standard Test Method for Peel Resistance of Adhesives (T-Peel Test); 2008 (Reapproved 2023).

J. ASTM D2240 - Standard Test Method for Rubber Property--Durometer Hardness; 2015 (Reapproved 2021).

K. ASTM D2794 - Standard Test Method for Resistance of Organic Coatings to the Effects of Rapid Deformation (Impact); 1993 (Reapproved 2024).

SECTION 075200

MODIFIED BITUMINOUS MEMBRANE

L. ASTM D3359 - Standard Test Methods for Rating Adhesion by Tape Test; 2023.

M. ASTM D3363 - Standard Test Method for Film Hardness by Pencil Test; 2022.

N. ASTM D4145 - Standard Test Method for Coating Flexibility of Prepainted Sheet; 2010 (Reapproved 2022).

O. ASTM E108 - Standard Test Methods for Fire Tests of Roof Coverings; 2020a.

P. ASTM E2178 - Standard Test Method for Determining Air Leakage Rate and Calculation of Air Permeance of Building Materials; 2021a.

Q. ISO 9001 - Quality Management Systems — Requirements; 2015, with Amendment (2024).

1.3 RELATED SECTIONS

A. Section 061000 - Rough Carpentry.

B. Section 061140 - Wood Blocking and Curbing: Wood nailers and cant strips.

C. Section 076200 - Sheet Metal Flashing and Trim: Weather protection for base flashings.

D. Section 077100 - Manufactured Roof Specialties: Counter flashing gravel stops, and fascia.

E. Section 221423 - Storm Drainage Piping Specialties.

1.4 REFERENCES

A. ASTM D 41 - Standard Specification for Asphalt Primer Used in Roofing, Dampproofing, and Waterproofing.

B. ASTM D 312 - Standard Specification for Asphalt used in Roofing.

C. ASTM D 451 - Standard Test Method for Sieve Analysis of Granular Mineral Surfacing for Asphalt Roofing Products.

D. ASTM D1079 Standard Terminology Relating to Roofing, Waterproofing and Bituminous Materials.

E. ASTM D 1863 Standard Specification for Mineral Aggregate Used as a Protective Coating for Roofing.

F. ASTM D 2178 Standard Specification for Asphalt Glass Felt Used in Roofing and Waterproofing.

G. ASTM D 4586 Standard Specification for Asphalt Roof Cement, Asbestos-Free.

H. ASTM D 4601 Standard Specification for Asphalt Coated Glass Fiber Base Sheet Used in Roofing.

I. ASTM D 5147 Standard Test Method for Sampling and Testing Modified Bituminous Sheet Materials.

SECTION 075200

MODIFIED BITUMINOUS MEMBRANE

J. ASTM D 6162 Standard Specification for Styrene Butadiene Styrene (SBS) Modified Bituminous Sheet Materials Using a Combination of Polyester and Glass Fiber Reinforcements.

K. ASTM D 6163 Standard Specification for Styrene Butadiene Styrene (SBS) Modified Bituminous Sheet Materials Using Glass Fiber Reinforcements.

L. ASTM D 6164 - Standard Specification for Styrene Butadiene Styrene (SBS) Modified Bituminous Sheet Materials Using Polyester Reinforcements.

M. ASTM E108 - Standard Test Methods for Fire Test of Roof Coverings

N. Factory Mutual Research (FM): Roof Assembly Classifications.

O. National Roofing Contractors Association (NRCA): Roofing and Waterproofing Manual.

P. Sheet Metal and Air Conditioning Contractors National Association, Inc. (SMACNA) - Architectural Sheet Metal Manual.

Q. Underwriters Laboratories, Inc. (UL): Fire Hazard Classifications.

R. Intertek/Warnock Hersey (WH): Fire Hazard Classifications.

S. ANSI-SPRI ES-1 Wind Design Standard for Edge Systems used with Low Slope Roofing Systems.

T. ASCE 7, Minimum Design Loads for Buildings and Other Structures

U. UL - Fire Resistance Directory.

V. FM Approvals - Roof Coverings and/or RoofNav assembly database.

1.5 SYSTEM DESCRIPTION

A. It is the intent of this specification to install a long-term, high-performance, redundant, two-ply, mineral modified bitumen roof system with NOx-Reducing Granules that meets or exceeds all current NRCA guidelines as stated in the most recent edition of the NRCA Roofing and Waterproofing Manual.

1.6 DESIGN / PERFORMANCE REQUIREMENTS

A. Perform work in accordance with all federal, state and local codes.

B. Exterior Fire Test Exposure: Roof system shall achieve a UL, FM or WH Class rating for roof slopes indicated on the Drawings as follows:

1. Factory Mutual Class A Rating.

2. Underwriters Laboratory Class A Rating.

C. Design Requirements:

1. Uniform Wind Uplift Load Capacity

a. Installed roof system shall withstand negative (uplift) design wind loading pressures complying with the following criteria.

SECTION 075200

MODIFIED BITUMINOUS MEMBRANE

1) Design Code: ASCE 7-16 ASD, Method 2 for Components and Cladding.

2) Importance Category:

a) IV

3) Importance Factor of:

a) 1.0

4) Wind Speed: 140 mph

5) Exposure Category:

a) C.

6) Design Roof Height: 15 feet (457.2 cm).

7) Minimum Building Width: 220 feet (6705.6 cm).

8) Roof Pitch: 1/4 :12”.

9) Roof Area Design Uplift Pressure:

a) Zone 1' Interior Field of Roof 31.5 psf

b) Zone 1 - Field of roof 48.9 psf

c) Zone 2 - Eaves, ridges, hips and rakes 61.9 psf

d) Zone 3 - Corners 81.5 psf

b. Over metal deck and SA VB, the insulation base layer of 4’x4’or 4'x8' 20 psi (137.90 kPa) polyisocyanurate shall be mechanically fastened at:

1) Z1 =11 (9ft Wide)

2) Z2 =17 (9ft Wide)

3) Z3 = 22 (3ft Wide x 9ft Length)

c. Over nailable deck, VB sheet layer shall be mechanically fastened (Nailed)with a minimum pull out value of 91 lbs. per fastener at:

1) Z1 = 9" o.c. through the 4" sheet lap with 2 rows of 9" o.c. in the field of the ply

2) Z2 = 7" o.c. through the 4" sheet lap with 3 rows of 7" o.c. in the field of the ply

3) Z3 = 6" o.c. through the 4" sheet lap with 4 rows of 6" o.c. in the field of the ply

2. Snow Load: 30 psf.

3. Live Load: 22.9 psf, or not to exceed original building design.

4. Dead Load:

a. Installation of new roofing materials shall not exceed the dead load capacity of the existing roof structure.

D. LEED: Roof system shall meet the reflectivity and emissivity criteria to qualify for one point under the LEED credit category, Credit 7.2, Landscape & Exterior Design to Reduce Heat Island - Roof.

E. Roof System membranes containing recycled or bio-based materials shall be third party certified through UL Environment.

F. Any roofing system submitted must be accompanied by a report letter signed by a third-party professional engineer licensed in the state in which the installation is to take place. This report letter shall show that the submitted system meets the Design and Performance criteria within this specification. Any roofing system submitted without a third-party licensed engineer approval letter will be rejected for non-conformance.

SECTION 075200

MODIFIED BITUMINOUS MEMBRANE

G. Roof system shall have been tested in compliance with the following codes and test requirements:

1. NRCA

2. FM Approvals:

a. RoofNav Website

1.7 SUBMITTALS

A. Submit under provisions of Section 013000.

B. Product Data: Manufacturer's data sheets on each product to be used, including:

1. Preparation instructions and recommendations.

2. Storage and handling requirements and recommendations.

3. Installation instructions.

4. Performance data that meets or exceeds specified schedule of values.

5. Warranty: A sample warranty specific to the specified system and project.

C. Shop Drawings: Submit shop drawings including installation details of roofing, flashing, fastening, insulation and vapor barrier, including notation of roof slopes and fastening patterns of insulation and base modified bitumen membrane, prior to job start.

D. Manufacturer’s Progress Report Letter: Provide a manufacturers letter stating that weekly progress reports, complete with pictures and descriptions of that week’s work, will be submitted to the Owner and Architect at the end of each week during the duration of the project. Failure to submit letter will result in an immediate rejection of the submittal.

E. Design Pressure Calculations: Submit design pressure calculations for the roof area in accordance with ASCE 7 and local CT Building Code requirements. Include a roof system attachment analysis report, certifying the system's compliance with applicable wind load requirements before Work begins.

F. Recycled or Bio-Based Materials: Provide third party certification through UL Environment of roof system membranes containing recycled or bio-based materials.

G. Verification Samples: For each modified bituminous membrane ply product specified, two samples, minimum size 6 inches (152.4 mm) square, representing actual product, color, and patterns.

H. Manufacturer's Site Supervision Letter: Provide a manufacturers letter stating that job site inspections will be provided by roofing manufacturer’s representative regular basis and at a minimum of three times per week during the duration of the project.

I. Manufacturer’s Certificate: Certify that materials are manufactured in the United States by an ISO 9001 certified company and conform to requirements specified herein, are chemically and physically compatible with each other, and are suitable for inclusion within the total roof system specified herein.

SECTION 075200

MODIFIED BITUMINOUS MEMBRANE

J. Closeout Submittals: Provide manufacturer's maintenance instructions that include recommendations for periodic inspection and maintenance of all completed roofing work.

Provide product warranty executed by the manufacturer.

K. Lifespan Inspection Certificate: Provide a manufacturer’s letter stating that yearly roof inspections will be made at no additional cost to the Owner upon the Owner’s request and shall be provided for the life of the warranty. Photographic inspection reports shall be provided to the Owner for the Owners records and outline any suggested maintenance, issues or deficiencies found. Any deficiencies in the roof system covered under warranty shall be corrected at no additional cost to the Owner (labor and material). Failure to submit letter will result in an immediate rejection of the submittal.

L. Test Reports: Submit test reports, prepared by an independent testing agency, for all modified bituminous sheet roofing, indicating compliance with ASTM D5147.

M. Manufacturer's Fire Compliance Certificate: Certify that the roof system furnished is approved by Factory Mutual (FM), Underwriters Laboratories (UL) or approved third party testing facility in accordance with ASTM E108, Class A for external fire and meets local or nationally recognized building codes.

N. Closeout Submittals: Provide manufacturer's maintenance instructions that include recommendations for periodic inspection and maintenance of all completed roofing work.

Provide product warranty executed by the manufacturer. Assist Owner in preparation and submittal of roof installation acceptance certification as may be necessary in connection with fire and extended coverage insurance on roofing and associated work.

1.8 QUALITY ASSURANCE

A. Perform Work in accordance with NRCA Roofing and Waterproofing Manual.

B. Manufacturer Qualifications:

1. Manufacturer Approval: This specification is based on the performance characteristics of the system identified in Part 2. Failure of a system manufacturer or product to meet all performance and warranty requirements of this specification will result in forfeiture of the bid award.

2. The manufacturer’s warranty must come directly from the company who physically manufactures the products. PLA’s or any other private labeled panel system will not be accepted.

3. Company specializing in manufacturing products specified with documented ISO 9001 certification and minimum of twenty-four years of documented experience and must not have been in Chapter 11 bankruptcy during the last ten years.

C. Installer's Field Supervision: Maintain a full-time Supervisor/Foreman on job site during all phases of roofing work while roofing work is in progress.

D. Product Certification: Provide manufacturer's certification that materials are manufactured in the United States and conform to requirements specified herein, are chemically and physically compatible with each other, and are suitable for inclusion within the total roof system specified herein.

SECTION 075200

MODIFIED BITUMINOUS MEMBRANE

E. Manufacturer's Field Supervision: A representative of the roof system manufacturer must be present three days per week at a minimum during the roof system installation.

F. Installer Qualifications:

1. Connecticut DAS Certified, an approved installer of the roofing system manufacturer.

2. Installer must perform Work in accordance with NRCA Roofing.

3. Company specializing in performing work of this section with minimum five years documented experience and a certified Pre-Approved Manufactures Contractor.

4. Company specializing in performing Work on this project shall have minimum ten years documented experience.

5. Successful contractor is required to maintain a full-time supervisor/foreman who is on the job-site at all times during installation of new roof system. Foreman must have a minimum of five (5) years experience with the installation of system similar to that specified.

G. Source Limitations: Obtain all waterproofing components of roof system from a single manufacturer. Secondary products that are required shall be recommended and approved in writing by the roofing system Manufacturer. Upon request of the Architect or Owner, submit Manufacturer's written approval of secondary components in list form, signed by an authorized agent of the Manufacturer.

1.9 PRE-INSTALLATION MEETINGS

A. Convene minimum two weeks prior to commencing Work of this section.

B. Review installation procedures and coordination required with related Work.

C. Inspect and make notes of job conditions prior to installation:

1. Record minutes of the conference and provide copies to all parties present.

2. Identify all outstanding issues in writing designating the responsible party for follow-up action and the timetable for completion.

3. Installation of roofing system shall not begin until all outstanding issues are resolved to the satisfaction of the Architect.

1.10 DELIVERY, STORAGE, AND HANDLING

A. Deliver and store products in manufacturer's unopened packaging with labels intact until ready for installation.

B. Store all roofing materials in a dry place, on pallets or raised platforms, out of direct exposure to the elements until time of application. Store materials at least 4 inches (101.6 mm) above ground level and covered with "breathable" tarpaulins.

C. Stored in accordance with the instructions of the manufacturer prior to their application or installation. Store roll goods on end on a clean flat surface. No wet or damaged materials will be used in the application.

D. Store at room temperature wherever possible, until immediately prior to installing the roll.

During winter, store materials in a heated location with a 50-degree F (10 degree C) minimum

SECTION 075200

MODIFIED BITUMINOUS MEMBRANE

temperature, removed only as needed for immediate use. Keep materials away from open flame or welding sparks.

E. Avoid stockpiling of materials on roofs without first obtaining acceptance from the Architect.

F. Adhesive storage shall be between the range of above 50-degree F (10 degree C) and below 80 degree F (27 degree C). Area of storage shall be constructed for flammable storage.

1.11 MANUFACTURER'S INSPECTIONS

A. It is required by the Owner that when the project is in progress, the roofing system manufacturer shall provide the following, carried out by a full-time employee of the warrantying roofing system manufacturer at no additional cost to the Owner, Architect or Contractor:

1. Weekly progress reports with digital photographic documentation and a summary of daily work completed the previous week, including all observations, progress, problems, quality or work and any obstacles overcome.

2. Report live progress and quality of the work observed while onsite prior to leaving the jobsite.

3. Provide onsite inspections a minimum of three days per week, excluding any project meetings. The project inspector(s) shall possess field and technical experience with the roof system being installed.

4. Progress reports must be made available to the Architect and Owner via a password secure on-line data base program.

5. Punch List: Provide a punch list with pictures and explanations of remedies that once completed will allow for final warranty.

6. Competition Report: Provide a final completion report stating that the manufacturer has observed no application procedures in conflict with these specifications other than those that may have been previously reported and corrected and that the roof has been filed for warranty.

1.12 COORDINATION

A. Coordinate Work with installing associated metal flashings as work of this section proceeds.

1.13 PROJECT CONDITIONS

A. Maintain environmental conditions (temperature, humidity, and ventilation) within limits recommended by manufacturer for optimum results. Do not install products under environmental conditions outside manufacturer's absolute limits.

1.14 WARRANTY

A. Upon completion of the work, provide the Manufacturer's written and signed Edge-To-Edge NDL System Warranty, warranting that, if a leak develops in the roof during the term of this warranty, due either to defective material or defective workmanship by the installer, the manufacturer shall provide the Owner, at the Manufacturer's expense, with the labor and material necessary to return the defective area to a watertight condition. This warranty shall

SECTION 075200

MODIFIED BITUMINOUS MEMBRANE

cover all roofing system components, including manufacturers metal, wall panels, underlayment and any ancillary products accepted by the manufacturer and utilized for this project.

1. Warranty Period:

a. 20 years from date of acceptance.(Base Bid)

b. 30 years from date of acceptance.(Alternate 2)

B. Installer is to guarantee all work against defects in materials and workmanship for a period indicated following final acceptance of the Work.

1. Warranty Period:

a. 3 years from date of acceptance.

PART 2 PRODUCTS

2.1 PRODUCT OPTIONS AND SUBMISSION

A. Submitted Manufacturer's Products and Systems will be accepted based upon meeting the requirements of this specification.

B. Any material/system submitted must include a list of five (5) projects where the proposed material has been used in a similar roofing system as that which is specified and is located within a thirty-mile radius from the location of the project. In addition, the five projects must be at least five (5) years old and be available for inspection by the Architect, Owner or Owner’s Representative.

C. The design criteria specified within are the minimum Standard of Quality for the products and performance required for this project. The bidder must disclose in the bid, the Manufacturer and the products that they intend to use on the Project.

D. The Products specified are intended as the Standard of Quality for the products required for this project. The bidder must disclose in the bid the manufacturer and the products that they intend to use on the Project. If no manufacturer and products are listed, the bid/bidder will be disqualified.

1. Bidder will not be allowed to change materials after the bid opening date.

2. The products and system submitted must be equal to or exceed the products specified.

Supporting technical data shall be submitted to the Architect/ Owner for approval prior to acceptance.

3. The Bidder/Roofing Contractor represents that it has:

a. Personally, investigated the submitted product or method, and determined that it is equal or superior in all respects to that specified.

b. Will provide the same guarantee as for the product and method specified.

c. Will coordinate installation of submitted manufacturer products in work, making such changes as may be required for work to be completed in all respects.

d. Will waive all claims for additional cost related to submitted manufacturer products and system, which consequently become apparent.

e. Cost data is complete and includes all related cost under his/her contract or other contracts, which may be affected by the submitted manufacturer products and system.

SECTION 075200

MODIFIED BITUMINOUS MEMBRANE

f. Will reimburse the Owner for all redesign costs by the Architect for accommodation of the submitted manufacturer products and system.

4. Architect/ Owner reserves the right to be the final authority on the acceptance or rejection of any or all bids, proposed roofing systems or materials that has met all specified requirement criteria.

5. Failure to submit manufacturer/ system package, or any portion thereof requested, will result in immediate disqualification and consideration for that particular contractor’s bid.

E. Material Country of Origin:

1. All rolled good, mastics, sealants, prefabricated and all metal components shall be 100% sourced and manufactured in the USA by one manufacturer. Raw materials sourced outside of the stated country of origin shall not be accepted. Upon request of the Architect or Owner, submit a Manufacturer's written letter as proof that all components in list form, signed by an authorized agent of the Manufacturer have been sourced and manufactured in the listed country of origin above.

F. Single ply roofing systems will not be considered or accepted.

2.2 ROOFING SYSTEM LAYERS – LILLIE B. HAYNES SCHOOL

A. Structural Deck Existing: Types

1. Metal Type B or similar

2. Gypsum

3. L.W. Concrete

B. Vapor Barrier(s)

1. Nailed – Pattern per wind up-lifts

2. Self-Adhering – Installed per manufacturer’s instructions

C. Thermal Insulation Layers

1. Base Layer(s) - Closed cell, Grade 2, 20PSI polyiso foam core laminated to a glass reinforced mat facer. ISOGARD by ELEVATE or approved equal

a. Mechanically fastened to metal deck

b. Chemically adhered gypsum and concrete deck’s

1) Type III Asphalt

2) Low Rise Foam Adhesive

2. Subsequent Insulation Layers and Tapered - Closed cell, Grade 2, 20PSI polyiso foam core laminated to a glass reinforced mat facer. ISOGARD by ELEVATE or approved equal

a. Chemically adhered

1) Type III Asphalt

2) Low Rise Foam Adhesive

3. Roof Protection Board or Coverboard - ½” HD Two-sided, Preprimed Fiberboard.

STRUCTODEK HD WITH PRIMED RED COATING by BLUE RIDGE FIBERBOARD, INC or approved equal

a. Chemically adhered

1) Type III Asphalt

SECTION 075200

MODIFIED BITUMINOUS MEMBRANE

2) Low Rise Foam Adhesive

D. Waterproofing Roofing Ply’s and Membranes

1. Base Ply: Chemically adhered

a. Type III Asphalt (Base Bid)

b. Cold-Applied Adhesive

2. Cap Ply: Chemically adhered

a. Type III Asphalt (Base Bid)

b. Cold-Applied Adhesive with hot-air heat welded seam

2.3 HOT APPLIED 2-PLY MODIFIED ASPHALT ROOFING (Base Bid)

A. Base Sheet (Vapor Barrier): One ply of either self-adhered over metal or mechanically fastened (nailed) over structural decking substrate.

B. Base (Ply) Sheet: One ply bonded to the prepared coverboard with Interply Adhesive.

C. Modified Cap (Ply) Sheet: One ply bonded to the prepared basesheet with Interply Adhesive

D. Interply Adhesive: Low odor, HPR, type III asphalt at 25 lbs per square.

E. Flashing Base (Ply) Sheet: One ply bonded to the prepared substrate with Interply Adhesive

F. Flashing Cap (Ply) Sheet: One ply bonded to the prepared substrate with Interply Adhesive

G. Flashing Ply Adhesive: Low odor, HPR, type III asphalt or Low VOC, cold-applied flashing adhesive at 5 Gal/Sq. Min

2.4 COLD APPLIED 2-PLY LOW VOC ASPHALT ROOFING (Alternate 1)

A. Base Sheet (Vapor Barrier): One ply of either self-adhered over metal or mechanically fastened (nailed) over structural decking substrate

B. Base (Ply) Sheet: One ply bonded to the prepared substrate with Interply Adhesive

C. Modified Cap (Ply) Sheet: One ply bonded to the prepared substrate with interplay adhesive

D. Interply Adhesive: Low VOC, cold-applied at 2.5 Gal/Sq.

E. Flashing Base (Ply) Sheet: One ply bonded to the prepared substrate with Interply Adhesive

F. Flashing Cap (Ply) Sheet: One ply bonded to the prepared substrate with Interply Adhesive

G. Flashing Ply Adhesive: Low VOC, cold-applied flashing adhesive at 5 Gal/Sq. Min.

H. Surfacing: Requires 45 days wait before applying.

SECTION 075200

MODIFIED BITUMINOUS MEMBRANE

2.5 ACCESSORlES:

A. Vapor Retarder SA: SBS modified, self-adhering membrane with woven polypropylene film and split release film on backside as recommended and furnished by the membrane manufacturer.

1. Install one layer of the self-adhering membrane to a properly prepared, primed (as required), clean and dry substrate in accordance with manufacturer's application instructions. Shingle in direction of slope or roof to shed water on each area of roof, can be utilized as a temporary roof.

a. Tensile Strength, ASTM D5147.

1) MD 125 lbf./in (21.89 kN/m).

2) XD 90 lbf./in. (15.76 kN/m).

b. Tear Strength, ASTM D 4073.

1) MD 175 lbf. (778 N).

2) XD 120 lbf. (534 N).

c. Thickness, ASTM D5147.

1) 45 mils 0.04 inch (1.14 mm).

d. Lap Adhesion, ASTM D1876.

1) 20 pli.

e. Water Permeance, ASTM E 96, Method B.

1) 0 perm (ng/Pa.s.m^2).

f. Air Permeability, ASTM E2178.

1) Less than 0.025 L/s*m^2.

B. Pitch Pocket Sealer: Two part, 100% solids, self-leveling, polyurethane sealant for filling pitch pans as recommended and furnished by the membrane manufacturer.

1. Durometer, ASTM D2240: 40-50 Shore

2. Elongation, ASTM D412: 250%

3. Tensile Strength, ASTM D412: 200 psi @ 100 mil (2.54001 mm)

C. Urethane Sealant Hybrid - One-part, non-sag sealant as approved and furnished by the membrane manufacturer for moving joints.

1. Tensile Strength, ASTM D412: 250 psi (1723.69 kPa)

2. Elongation, ASTM D412: 450%

3. Hardness, Shore A ASTM C920: 35

4. Adhesion-in-Peel, ASTM C 92: 30 pli

D. Sealant - Structural Adhesive: Single component, 100% solids structural adhesive as furnished and recommended by the membrane manufacturer.

1. Elongation, ASTM D412: 300%

2. Hardness, Shore A, ASTM C920: 50

3. Shear Strength, ASTM D1002: 300 psi (2068.43 kPa)

E. Walkway System: A one-component, moisture curing silicone rubberized coating system designed to enhance the impact resistance of the roof surface and also provide a non-skid walking surface when used with WG walkway granules as furnished and recommended by the membrane manufacturer.

SECTION 075200

MODIFIED BITUMINOUS MEMBRANE

1. Color: Safety Yellow

2. Width: Minimum 30”

F. Cover Board: Provide ½”, two-sided, pre-primed fiber board, Structodek HD Red or pre-approved equal.

1. 4’x4’ or 4’x8’ panel.

G. Liquid Flashing - An asphaltic-polyurethane, low odor, liquid flashing material designed for specialized details unable to be waterproofed with typical modified membrane flashings as furnished and recommended by the membrane manufacturer.

1. Tensile Strength, ASTM D412: 400 psi (2757.90 kPa)

2. Elongation, ASTM D412: 300%

3. Density @77 deg. F 8.5 lb/gal typical

H. Glass Fiber Cant - Glass Cant: Continuous triangular cross Section made of inorganic fibrous glass used as a cant strip as recommended by the membrane manufacturer.

2.6 EDGE TREATMENT AND ROOF PENETRATION FLASHINGS

A. Pre-Manufactured Edge Metal: Flash-less Snap-On Fascia Cover and Splice Plate.

1. Aluminum, ASTM B209, alloy 3105-H14, in thickness of .040" nom or .050" nom

B. Pre-Manufactured Edge Metal: Flash-less Snap-On Fascia Extruded Base Anchor and Components as furnished and recommended by the membrane manufacturer.

1. Base Anchor: 6005A-T61 extruded aluminum.

2. Compression Seal for top of anchor: TPE thermoplastic elastomer.

3. Sealant for Flange: Single-component high performance 100% solids, interior and exterior polyether joint sealant.

C. Pre-Manufactured Edge Metal Finishes:

1. Unexposed surfaces for mill finish flashing, fascia, and coping cap, as shipped from the mill

2. Exposed surfaces for fascia, coping cap and coated panels:

a. Finishes: fluorocarbon finish. Epoxy primer baked both sides, .2-.25 mils (0.00635 mm) thickness as approved by finish coat manufacturer.

Weathering finish as referred by National Coil Coaters Association (NCCA).

Provided with the following properties.

1) Pencil Hardness: ASTM D3363, HB-H / NCCA II-2.

2) Bend: ASTM D4145, O-T / NCCA II-19

3) Cross-Hatch Adhesion: ASTM D3359, no loss of adhesion

4) Gloss (60 deg. angle): ASTM D523, 25+/-5%

5) Reverse Bend: ASTM D2794, no cracking or loss of adhesion

6) Nominal Thickness: ASTM D1005

a) Primer: 0.2 mils (0.00508 mm)

b) Topcoat, 0.7 mils (0.01778 mm) min

c) Clear Coat (optional, only used with 22 ga. steel) 0.3 mils (0.00762 mm)

SECTION 075200

MODIFIED BITUMINOUS MEMBRANE

7) Color: Provide manufacturer's full range of standard, deluxe and premium colors for selection by architect and owner.

D. Pre-Manufactured Soffit Panels: Perimeter under edge flashing as furnished and recommended by the membrane manufacturer.

1. .032 aluminum in standard color with Kynar 500® Finish

2. Standard width is 12"

3. Vented and non-vented mechanically fastened

4. Color: Provide manufacturer's full range of standard, deluxe and premium colors for selection by architect and owner.

E. Pitch pans, Rain Collar 24 gauge stainless or 20oz (567gram) copper. All joints should be welded/soldered watertight.

F. Drain Flashings should be 4lb (1.8kg) sheet lead or polyvinyl butyral (PVB) foil formed and rolled.

G. Plumbing stacks should be 4lb (1.8kg) sheet lead or Pre-Manufactured polyvinyl butyral (PVB) foil boots formed and rolled.

H. Fabricated Flashings:

1. Fabricated flashings and trim shall conform to the detail requirements of SMACNA

"Architectural Sheet Metal Manual" and/or the CDA Copper Development Association "Copper in Architecture - Handbook" as applicable.

I. Manufactured Roof Specialties: Shop fabricated copings, fascia, gravel stops, control joints, expansion joints, joint covers and related flashings and trim are specified in Section 07710.

1. Manufactured roof specialties shall conform to the detail requirements of SMACNA

"Architectural Sheet Metal Manual" and/or the NRCA "Roofing and Waterproofing Manual" as applicable.

PART 3 EXECUTION

3.1 EXAMINATION

A. Do not begin installation until substrates have been properly prepared.

B. Inspect and approve the deck condition, slopes and fastener backing if applicable, parapet walls, expansion joints, roof drains, stack vents, vent outlets, nailers and surfaces and elements.

C. Verify that work penetrating the roof deck, or which may otherwise affect the roofing, has been properly completed.

D. If substrate preparation and other conditions are the responsibility of another installer, notify Architect of unsatisfactory preparation before proceeding.

3.2 PREPARATION

A. General: Clean surfaces thoroughly prior to installation.

SECTION 075200

MODIFIED BITUMINOUS MEMBRANE

1. Prepare surfaces using the methods recommended by the manufacturer for achieving the best result for the substrate under the project conditions.

2. Fill substrate surface voids that are greater than 1/4 inch (6.35 mm) wide with an acceptable fill material.

3. Roof surface to receive roofing system shall be smooth, clean, free from loose gravel, dirt and debris, dry and structurally sound.

4. Wherever necessary, all surfaces to receive roofing materials shall be power broom and vacuumed to remove debris and loose matter prior to starting work.

5. Do not apply roofing during inclement weather. Do not apply roofing membrane to damp, frozen, dirty, or dusty surfaces.

6. Fasteners and plates for fastening components mechanically to the substrate shall provide a minimum pull-out capacity of 300 lbs. (136 k) per fastener. Base or ply sheets attached with cap nails require a minimum pullout capacity of 91 lbs. per nail.

7. Prime decks where required, in accordance with requirements and recommendations of the primer and membrane manufacturer.

B. Metal Deck: deck shall be installed as specified in Section

1. Fastening of the deck should comply with the anticipated live and dead loads pertaining to the building as well as applicable Code.

2. When re-roofing over metal decks, any surface deflection and any needed repairs to severely corroded areas shall be reported to the Architect and Owner. Loose, compromised, rotted or inadequately secured decking shall be repaired, fastened, and irreparable or otherwise defective decking shall be replaced.

C. Poured reinforced concrete:

1. Shall be smooth, dry, clean, and free of ice/frost, projections, and depressions. Concrete shall be fully cured, and the surface shall be broom cleaned and free of release/curing agents prior to commencement of work.

2. Prepared concrete surfaces for roofing or insulation by priming with asphalt/concrete primer conforming to ASTM D 41. Apply at a rate of approx. 1 gallon/100 sq. ft. (.4 L/m2). All primed areas shall be fully dried before proceeding with the application of the roof system. Hold back bitumen at the joints approximately 4 inches (101.6 mm) to prevent bitumen drippage.

D. Gypsum:

1. Gypsum decks shall be smooth and free from deflections or ridges.

2. An average fastener withdrawal resistance as recommended by the fastener manufacturer shall be obtained; however, at no time shall it be less than 91 lbs. per fastener.

3. Wet or frozen poured gypsum decks are not suitable to receive a roof.

4. Poured-in-place gypsum roof decks contain a large percentage of moisture. All necessary precautions shall be taken to avoid the entrapment of moisture under the roofing system.

In addition to ventilation of the underside to allow for proper curing, topside and perimeter venting shall be implemented.

5. Install a mechanically attached base sheet prior to installation of insulation or roofing membrane. Base or ply sheets attached with cap nails require a minimum pullout capacity of 91 lbs. per nail.

SECTION 075200

MODIFIED BITUMINOUS MEMBRANE

3.3 INSTALLATION - GENERAL

A. Install modified bitumen membranes and flashings in accordance with manufacturer's instructions and with the recommendations provided by the National Roofing Contractors Association's Roofing & Waterproofing Manual, the Asphalt Roofing Manufacturers Association, and applicable codes.

B. General: Avoid installation of modified bitumen membranes at temperatures lower than 40-45 degrees Fahrenheit (7.22 degrees Celsius). When work at such temperatures unavoidable use the following precautions:

1. Take extra care during cold weather installation and when ambient temperatures are affected by wind or humidity, to ensure adequate bonding is achieved between the surfaces to be joined. Use extra care at material seam welds and where adhesion of the applied product to the appropriately prepared substrate as the substrate can be affected by such temperature constraints as well.

2. Unrolling of cold materials, under low ambient conditions must be avoided to prevent the likelihood of unnecessary stress cracking. Rolls must be at least 40 degrees Fahrenheit (4.44 degrees Celsius) at the time of application. If the membrane roll becomes stiff or difficult to install, it must be replaced with roll from a heated storage area.

C. Commence installation of the roofing system at the lowest point of the roof (or roof area), working up the slope toward the highest point. Lap sheets shingle fashion so as to constantly shed water

D. All slopes greater than 2:12 require back-nailing to prevent slippage of the ply sheets. Use ring or spiral-shank 1 inch (25.4 mm) cap nails, or screws and plates at a rate of 1 fastener per ply (including the membrane) at each insulation stop. Place insulation stops at 16 ft o.c for slopes less than 3:12 and 4 feet (121.92 cm) o.c for slopes greater than 3:12. On non-insulated systems, nail each ply directly into the deck at the rate specified above. When slope exceeds 2:12, install all plies parallel to the slope (strapping) to facilitate backnailing. Install 4 additional fasteners at the upper edge of the membrane when strapping the plies.

3.4 INSTALLATION HOT APPLIED ROOF SYSTEM (Base Bid)

A. Vapor Barrier Ply(s): Install a vapor barrier ply to properly prepared decking substrates prior to installing subsequent system layers. Metal deck substrates shall receive a self-adhering air barrier/vapor retarder for roof applications. Gypsum, concrete or other types of decking shall receive a nailable vapor barrier sheet, fastened or adhered according to manufacturer’s specifications and recommendations.

1. Overlap head laps a minimum of 6 inch (152.4 mm). Overlap side laps a minimum of 3 inch (76.2 mm). as indicated by the lap lines on the product.

2. If the ply has been used as a temporary roof and is expected to function as a air barrier in a finished roofing system, it must be inspected by the manufacturer and repaired as needed.

3. All damaged areas must be cut out and removed, and new membrane installed in those areas.

4. When the roof system is installed over the self-adhering sheet, the insulation must be attached by mechanically fastening it into the structural deck.

SECTION 075200

MODIFIED BITUMINOUS MEMBRANE

5. Install nailable base sheet plies in twenty-five (25) lbs (11.3kg) per square of bitumen shingled uniformly or nailed according to wind up-lifts.

B. Base/Felt Ply(s): Install base sheet or felt plies in twenty-five (25) lbs (11.3kg) per square of bitumen shingled uniformly to achieve one or more plies over the entire prepared substrate.

Shingle in direction of slope of roof to shed water on each area of roof. Do not step on base rolls until asphalt has cooled, fish mouths should be cut and patched.

1. Lap ply sheet ends 8 inches (203.2 mm). Stagger end laps 2 inches (50.8 mm) minimum.

2. Install base flashing ply…