11-Attachment D SCTA Reading Unleaded Fuel and OWS Drawings.pdf
PDF 14 MB Posted
- Solicitation number
- Not on record
- Issued by
- Berks County, Richland Borough, Pennsylvania
About this file
This is a Scope of Work document and technical drawings prepared by KCI for the South Central Transit Authority (SCTA) regarding the replacement of an unleaded fuel tank and oil-water separator system at the Reading Operations Center in Reading, Pennsylvania. The project encompasses the removal of one existing 10,000-gallon gasoline underground storage tank (UST) and its associated piping system, installation of one new 10,000-gallon gasoline aboveground storage tank (AST) with a dispenser system and below-ground piping, and replacement of one 3,000-gallon flow-through oil/water separator (OWS) system. Additional work includes installation of a new concrete support pad for the AST, relocation of one light pole, and pavement resurfacing. All work is scheduled to occur outdoors on SCTA's property within the existing security fence at 1701 N. 10th Street, Reading, PA 19604, with construction to comply with NFPA 30 and 30A standards. The project is divided into two separate contracts: Contract No. 1 addresses all prime/mechanical construction activities, and Contract No. 2 covers electrical system installation and rehabilitation. Sealed bids are due electronically via PennBid by 2:00 PM prevailing time on Wednesday, April 29, 2026, with a non-mandatory pre-bid meeting scheduled for Thursday, March 19, 2026, at 9:30 AM at the Reading Operations Center.
The project work sequence requires careful coordination to maintain continuous operations, with provisions to preserve vehicle access to a minimum of two maintenance bays at all times during construction. The contractor must obtain all necessary local and state permits, coordinate with Pennsylvania One Call at 1-800-242-1776 at least three working days prior to beginning work, and comply with applicable codes including the Pennsylvania Uniform Construction Code, International Building Code 2018, International Fire Code 2018, NFPA 30 (2024) Flammable and Combustible Liquids Code, and NFPA 30A Code for Motor Fuel Dispensing Facilities. All work and contracts are subject to applicable state and federal laws, including Buy America provisions, Non-Discrimination and Non-Collusion requirements, and compliance with the Comptroller General's list of ineligible contractors. Funding is provided through a financial assistance contract between SCTA and the Pennsylvania Department of Transportation and Federal Transit Administration. SCTA encourages disadvantaged business enterprise (DBE) participation, though no specific DBE goal has been established for this project.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SITE DATA
1. MUNICIPALITY: CITY OF READING
2. COUNTY: BERKS COUNTY
3. EXISTING ZONING: M-C MANUFACTURING COMMERCIAL
4. TOTAL AREA OF SITE: 5.36 ACRES
5. TOTAL DISTURBED AREA: ~3,100.00 S.F.
6. THE PROPERTY SHOWN HEREON IS OWNED BY BARTA BERKS AREA READING TRANSPORTATION AUTH BY DEED DATED 01/01/1900, RECORDED AMONG THE LAND RECORDS OF BERKS COUNTY DEED BOOK 1702 PAGE 0047.
7. PARCEL ID: 17531721098735
8. THE LOCATION OF THE EXISTING UTILITIES SHOWN HEREON ARE APPROXIMATE ONLY. CONTRACTOR SHALL VERIFY THE EXISTENCE, LOCATION, AND DEPTH OF ANY EXISTING UTILITIES AND SHALL NOTIFY THE ENGINEER
OF ANY DISCREPANCIES PRIOR TO BEGINNING WORK.
9. THE CONTRACTOR SHALL CALL "PENNSYLVANIA ONE CALL" AT (1-800-242-1776) THREE WORKING PRIOR TO
BEGINNING ANY WORK IN THE VICINITY OF EXISTING UTILITIES.
10. THE CONTRACTOR SHALL NOTE THAT IN CASE OF A DISCREPANCY BETWEEN THE SCALED AND FIGURED
DIMENSIONS SHOWN ON THESE PLANS, THE FIGURED DIMENSIONS SHALL GOVERN.
GENERAL NOTES
1. ALL DISTURBED AREAS TO BE RESTORED TO EXISTING CONDITIONS OR IN ACCORDANCE WITH DESIGN FOR NEW
WORK.
2. CONTRACTOR TO VERIFY EXISTING UTILITIES PRIOR TO ANY CONSTRUCTION.
3. CONTRACTOR RESPONSIBLE FOR OBTAINING ALL NECESSARY PERMITS.
APPLICABLE CODES AND STANDARDS
PENNSYLVANIA UNIFORM CONSTRUCTION CODE (UCC)
INTERNATIONAL BUILDING CODE 2018 (IBC)
INTERNATIONAL ENERGY CONSERVATION CODE 2018 (IBC)
INTERNATIONAL FIRE CODE 2018
INTERNATIONAL MECHANICAL CODE 2018
INTERNATIONAL PLUMBING CODE 2018
NATIONAL ELECTRIC CODE 2017 (NFPA 70)
NFPA 101 LIFE SAFETY CODE 2021
INTERNATIONAL EXISTING BUILDING CODE 2018
INTERNATIONAL FUEL GAS CODE 2018
2018 INTERNATIONAL WILDLAND-URBAN INTERFACE CODE
2024 NFPA 30 FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE
2024 NFPA 30A CODE FOR MOTOR FUEL DISPENSING
FACILITIES AND REPAIR GARAGES
PROJECT DESCRIPTION
1. REMOVE (1) EXISTING 10,000 GALLON GASOLINE UNDERGROUND STORAGE TANK (UST) AND PIPING SYSTEM.
2. INSTALL ONE (1) NEW 10,000 GALLON GASOLINE ABOVEGROUND STORAGE TANK (AST) AND DISPENSER SYSTEM
WITH BELOW GROUND PIPING.
3. REPLACE ONE (1) 3,000 GALLON FLOW THROUGH OIL/WATER SEPARATOR (OWS) SYSTEM.
4. ALL WORK EXCEPT ELECTRICAL CONNECTIONS TO EXISTING EQUIPMENT WILL OCCUR OUTDOORS. NEW WORK ALSO INCLUDES INSTALLATION OF A NEW CONCRETE SUPPORT PAD FOR THE NEW AST, RELOCATION OF ONE (1) LIGHT POLE, AND PAVEMENT RESURFACING. ALL NEW CONSTRUCTION WILL BE IN ACCORDANCE WITH NFPA 30 AND 30A. ALL WORK TO OCCUR ON SCTA'S PROPERTY INSIDE THE EXISTING SECURITY FENCE.
SEQUENCE OF WORK
1. PERFORM SUBSURFACE UTILITY MARKOUT
2. INSTALL EROSION AND SEDIMENT CONTROL MEASURES.
3. INSTALL NEW CONCRETE PAD AND PREP FOR NEW AST. EXISTING GAS DISPENSERS STILL IN OPERATION.
4. INSTALL NEW AST AND ALL TANK TOP EQUIPMENT. EXISTING GAS DISPENSERS STILL IN OPERATION.
5. TAKE DISPENSERS OUT OF SERVICE AND INSTALL NEW PIPE TRENCH, NEW DISPENSERS AND ISLANDS, AND ELECTRIC. DRAIN, CLEAN AND TAKE EXISTING GASOLINE UST SYSTEM OUT OF SERVICE. REMOVE FUEL FROM THE UNDERGROUND TANK AND PIPING AND TAKE IT OUT OF SERVICE, BUT UST TO REMAIN TEMPORARILY IN THE
GROUND.
6. COMPLETE NEW GASOLINE AST AND DISPENSER SYSTEM AND OPEN FOR SERVICE.
7. REMOVE EXISTING GAS UST AND PIPING. BACKFILL AND STABILIZE PIPE TRENCH AREA TO MAINTAIN VEHICLE ACCESS TO A MINIMUM OF 2 MAINTENANCE BAYS AT ALL TIMES. GASOLINE UST EXCAVATION AND REMOVAL TO OCCUR AFTER PIPE TRENCH HAS BEEN RESTORED TO ALLOW ACCESS TO ALL NORTHERN MAINTENANCE BAYS.
THE UST EXCAVATION AREA TO BE STABILIZED AND VEHICLE ACCESS TO BAYS RESTORED WITHIN 1 WEEK OF
WORK IN THIS AREA IN ADVANCE OF PAVING.
8. REMOVE EXISTING OWS AND INSTALL NEW OWS AND PIPING CONNECTIONS.
9. REPAVE AND RESTORE SITE.
LEGEND
PROPERTY BOUNDARY
MAJOR CONTOUR
MINOR CONTOUR
EX. SIDEWALK
EX. EDGE OF PAVED ROAD
EX. WATER LINE
EX. FIRE HYDRANT
EX. BOLLARD
EX. STORM DRAIN PIPE
EX. STORM DRAIN MANHOLE
EX. STORM DRAIN INLET
EX. LIGHT FIXTURE
EX. BUILDING
LEGEND
VICINITY MAP
SCALE: 1"=2000'
SOUTH CENTRAL TRANSIT AUTHORITY
UNLEADED FUEL TANK AND OIL / WATER SEPARATOR REPLACEMENT PLAN
READING OPERATIONS CENTER
1701 N. 10TH STREET
READING, PA 19604
SHEET INDEX
SHEET NUMBER DESCRIPTION
C-1 COVER SHEET
C-2 EXISTING CONDITIONS PLAN
C-3 DEMOLITION PLAN
C-4 SITE PLAN
C-5 DETAILS
S-1 STRUCTURAL GENERAL NOTES
S-2 STRUCTURAL GENERAL PLANS, SECTIONS AND DETAILS
FM-0 MECHANICAL COVER SHEET
FM-1 MECHANICAL NEW WORK PLAN
FM-2 MECHANICAL TANK DETAILS
FM-3 MECHANICAL DETAILS I
FM-4 MECHANICAL DETAILS II
FE-0 ELECTRICAL COVER SHEET
FE-1 ELECTRICAL NEW WORK PLAN
FE-2 ELECTRICAL DETAILS I
FE-3 ELECTRICAL DETAILS II
SITE
DIAL 8-1-1 OR 1-800-242-1776 NOT LESS THAN 3
BUSINESS DAYS NOR MORE THAN 10 BUSINESS
DAYS PRIOR TO THE START OF EXCAVATION.
COORDINATE YOUR PROJECTS VIA
COORDINATE PA AT WWW.PAONECALL.ORG.
SHEET DATE
SHEET NAME
SHEET NUMBER
DRAWN BY
DESIGNED BY
KCI PROJECT NUMBER
00034570_002
02/23/2026
BE
R
KS
C
O U
N
TY
REV DATE DESCRIPTION BY
C
IT
Y O
F R
EA
D
IN
G
SO
UT
H
CE
NT
RA
L T
RA
NS
IT
A
UT
HO
RI
TY
U N
LE
A
D
ED
F U
EL
T
A N
K A
N D
O
IL
W
A
TE
R
SE
PA
R
A
TO
R R
EP
LA
C
EM
EN
T
PL
A
N
N
. 1 0T
H S
TR
EE
T, R
EA
D
IN
G
, P A
BI
D
S
ET
936 RIDGEBROOK ROAD
SPARKS, MD 21152
PHONE: (410) 316-7800
Fax: (410) 316-7868
WWW.KCI.COM
BID SET
C-1
COVER SHEET
seth.cheney Text Box
PROJECT #01-2026
' F
R O
N T
SE
TB
AC
K
6' B
U
FF
ER
' F
R O
N T
SE
TB
AC
K
0.
0.
480.00'
480.00'
6' B
U
FF
ER
15' FRONT
SETBACK
15' FRONT SETBACK
6' BUFFER
MERCEDES RONALD
1011 MOSS ST READING PA 19604-2213
PROPERTY ID/UPI: 17531721094836
LOCATION ADDRESS: 1722 N 10TH ST
MUNICIPALITY: READING
TAX DISTRICT: CITY OF READING
DEED #: 2017048285
DEED DATE: 20171228
PROPERTY CLASS: COMMERCIAL
LAND USE CODE: 2307
NET ACREAGE: ±1.39
A F HOLDING INC
PO BOX 15045 READING PA 19612-5045
PROPERTY ID/UPI: 17531721094597
LOCATION ADDRESS: 1700 N 10TH ST
MUNICIPALITY: READING
TAX DISTRICT: CITY OF READING
DEED # / DATE: 20261497 / 19000101
PROPERTY CLASS: COMMERCIAL
LAND USE CODE: 3326 NET ACREAGE: ±0.23
A F HOLDING INC
PO BOX 15045 READING PA 19612
PROPERTY ID/UPI: 17531721094698
LOCATION ADDRESS: 1712 N 10TH ST
MUNICIPALITY: READING
TAX DISTRICT: CITY OF READING
DEED # / DATE: 227120740 / 19960320
PROPERTY CLASS: INDUSTRIAL
LAND USE CODE: 3426
NET ACREAGE: ±0.30
BARTA BERKS AREA READING TRANSPORTATION AUTHORITY
10TH & EXETER STS READING, PA 19604 USA
PROPERTY ID/UPI: 17531721098735
LOCATION ADDRESS: 1701 N 10TH STREET
MUNICIPALITY: READING TAX DISTRICT: CITY OF READING
DEED # / DATE: 17020047 / 19000101
PROPERTY CLASS: EXEMPT LAND USE CODE: 9940
NET ACREAGE: ±5.36 (LOT ±230,400 SQ. FT.)
1-STORY CONCRETE BLOCK AND BRICK STRUCTURE
SANDRA J. WALTERS
PO BOX 14591 READING PA 19612
PROPERTY ID/UPI: 17531721096455
LOCATION ADDRESS: 1665 N 10TH ST
MUNICIPALITY: READING
TAX DISTRICT: CITY OF READING
DEED #: 2014005261
DEED DATE: 20140220
PROPERTY CLASS: COMMERCIAL
LAND USE CODE: 4241
NET ACREAGE: ±0.04
RODRIGUEZ BRYAN CASTILLO &
CASTILLO RAFAEL
4011 8TH AVE TEMPLE PA 19560
PROPERTY ID/UPI: 17531721097465
LOCATION: 1668 MULBERRY ST
MUNICIPALITY: READING
TAX DISTRICT: CITY OF READING
DEED #: 2018043957
DEED DATE: 20181221
PROPERTY CLASS: RESIDENTIAL
LAND USE CODE: 121A
NET ACREAGE: ±0.03
2 1/2 STORY BRICK/MASONRY
TUTTO MIO INC
96 COMMERCE DR # 153
WYOMISSING, PA 19610
PROPERTY ID/UPI: 17531721099401
LOCATION: 1639 MULBERRY ST
MUNICIPALITY: READING
TAX DISTRICT: CITY OF READING
DEED #: 2019042951
DEED DATE: 20191206
PROPERTY CLASS: COMMERCIAL
LAND USE CODE: 4101
NET ACREAGE: ±0.23
BEILER JOHN
3427 COMPASS RD GAP, PA 17527
PROPERTY ID/UPI: 17531721190434
LOCATION: 1632 N 11TH ST
MUNICIPALITY: READING
TAX DISTRICT: CITY OF READING
DEED #: 2022015354
DEED DATE: 20220412
PROPERTY CLASS: RESIDENTIAL
LAND USE CODE: 133
NET ACREAGE: ±0.09
2-STORY BRICK/MASONRY
EX. GATE BUTTON &
BOLLARD
VISITOR PARKING
SPACE (TYP OF 3)
EX. STOP SIGN
SIGN: NO PARKING OVER 5 TONS"
EX. TRANSF & ELECTRICAL
EQUIPMENT
FENCE 8' WROUGHT IRON
6' BUFFER
EXETER ST
BERN ST
N
0T H
S T
N
1T H
S T
UST OVERFILL
ALARM AND ESO
UNDERGROUND GASOLINE PIPING
AND ELECTRICAL CONDUIT TRENCH
U E
U E
U
EU
E
U E
C S-
C
S-
C S-
C
S-
C S-
C
S-
3,000 GALLON
OIL/WATER SEPARATOR
10,000 GALLON GASOLINE
UNDERGROUND TANK
N
( IN FEET )
1 inch = 30ft.
15 3030 60
EXISTING CONDITION PLAN NOTES
1. EXISTING FEATURES SHOWN ON THIS SITE PLAN WERE TAKEN FROM A SURVEY
PREPARED FOR THE BARTA BERKS AREA REGIONAL TRANSPORTATION
AUTHORITY "PARKING LOT IMPROVEMENTS / REFURBISHMENT AND SOLAR PANEL
CANOPY PROJECT #06-2024" DATED AUGUST 29TH, 2023.
SHEET DATE
SHEET NAME
SHEET NUMBER
DRAWN BY
DESIGNED BY
KCI PROJECT NUMBER
00034570_002
02/23/2026
BE
R
KS
C
O U
N
TY
REV DATE DESCRIPTION BY
C
IT
Y O
F R
EA
D
IN
G
SO
UT
H
CE
NT
RA
L T
RA
NS
IT
A
UT
HO
RI
TY
U N
LE
A
D
ED
F U
EL
T
A N
K A
N D
O
IL
W
A
TE
R
SE
PA
R
A
TO
R R
EP
LA
C
EM
EN
T
PL
A
N
N
. 1 0T
H S
TR
EE
T, R
EA
D
IN
G
, P A
BI
D
S
ET
936 RIDGEBROOK ROAD
SPARKS, MD 21152
PHONE: (410) 316-7800
Fax: (410) 316-7868
WWW.KCI.COM
BID SET
C-2
EXISTING
CONDITIONS
PLAN
R O
N T
SE
TB
AC
K
6' B
U
FF
ER
' F
R O
N T
SE
TB
AC
K
0.
0.
480.00'
480.00'
6' B
U
FF
ER
15' FRONT
SETBACK
15' FRONT SETBACK
6' BUFFER
MERCEDES RONALD
1011 MOSS ST READING PA 19604-2213
PROPERTY ID/UPI: 17531721094836
LOCATION ADDRESS: 1722 N 10TH ST
MUNICIPALITY: READING
TAX DISTRICT: CITY OF READING
DEED #: 2017048285
DEED DATE: 20171228
PROPERTY CLASS: COMMERCIAL
LAND USE CODE: 2307
NET ACREAGE: ±1.39
A F HOLDING INC
PO BOX 15045 READING PA 19612-5045
PROPERTY ID/UPI: 17531721094597
LOCATION ADDRESS: 1700 N 10TH ST
MUNICIPALITY: READING
TAX DISTRICT: CITY OF READING
DEED # / DATE: 20261497 / 19000101
PROPERTY CLASS: COMMERCIAL
LAND USE CODE: 3326 NET ACREAGE: ±0.23
A F HOLDING INC
PO BOX 15045 READING PA 19612
PROPERTY ID/UPI: 17531721094698
LOCATION ADDRESS: 1712 N 10TH ST
MUNICIPALITY: READING
TAX DISTRICT: CITY OF READING
DEED # / DATE: 227120740 / 19960320
PROPERTY CLASS: INDUSTRIAL
LAND USE CODE: 3426
NET ACREAGE: ±0.30
BARTA BERKS AREA READING TRANSPORTATION AUTHORITY
10TH & EXETER STS READING, PA 19604 USA
PROPERTY ID/UPI: 17531721098735
LOCATION ADDRESS: 1701 N 10TH STREET
MUNICIPALITY: READING TAX DISTRICT: CITY OF READING
DEED # / DATE: 17020047 / 19000101
PROPERTY CLASS: EXEMPT LAND USE CODE: 9940
NET ACREAGE: ±5.36 (LOT ±230,400 SQ. FT.)
1-STORY CONCRETE BLOCK AND BRICK STRUCTURE
SANDRA J. WALTERS
PO BOX 14591 READING PA 19612
PROPERTY ID/UPI: 17531721096455
LOCATION ADDRESS: 1665 N 10TH ST
MUNICIPALITY: READING
TAX DISTRICT: CITY OF READING
DEED #: 2014005261
DEED DATE: 20140220
PROPERTY CLASS: COMMERCIAL
LAND USE CODE: 4241
NET ACREAGE: ±0.04
RODRIGUEZ BRYAN CASTILLO &
CASTILLO RAFAEL
4011 8TH AVE TEMPLE PA 19560
PROPERTY ID/UPI: 17531721097465
LOCATION: 1668 MULBERRY ST
MUNICIPALITY: READING
TAX DISTRICT: CITY OF READING
DEED #: 2018043957
DEED DATE: 20181221
PROPERTY CLASS: RESIDENTIAL
LAND USE CODE: 121A
NET ACREAGE: ±0.03
2 1/2 STORY BRICK/MASONRY
TUTTO MIO INC
96 COMMERCE DR # 153
WYOMISSING, PA 19610
PROPERTY ID/UPI: 17531721099401
LOCATION: 1639 MULBERRY ST
MUNICIPALITY: READING
TAX DISTRICT: CITY OF READING
DEED #: 2019042951
DEED DATE: 20191206
PROPERTY CLASS: COMMERCIAL
LAND USE CODE: 4101
NET ACREAGE: ±0.23
BEILER JOHN
3427 COMPASS RD GAP, PA 17527
PROPERTY ID/UPI: 17531721190434
LOCATION: 1632 N 11TH ST
MUNICIPALITY: READING
TAX DISTRICT: CITY OF READING
DEED #: 2022015354
DEED DATE: 20220412
PROPERTY CLASS: RESIDENTIAL
LAND USE CODE: 133
NET ACREAGE: ±0.09
2-STORY BRICK/MASONRY
EX. GATE BUTTON &
BOLLARD
VISITOR PARKING
SPACE (TYP OF 3)
EX. STOP SIGN
SIGN: NO PARKING OVER 5 TONS"
EX. TRANSF & ELECTRICAL
EQUIPMENT
FENCE 8' WROUGHT IRON
6' BUFFER
EXETER ST
BERN ST
N
0T H
S T
N
1T H
S T
U E
U E
U
EU
E
U E
C S-
C
S-
C S-
C
S-
C S-
C
S-
REMOVE LIGHT POLE FOUNDATION -
PREPARE FOR NEW TANK AND PAD
REMOVE OVERFILL ALARM,
ESO, TROUGHS, AND CONDUIT
PREPARE FOR NEW UNDERGROUND
PIPING AND CONDUIT
EXISTING DRAIN PIPING
(TO REMAIN)
REMOVE GASOLINE DISPENSERS,
ISLANDS, SUMPS, AND BOLLARDS -
PREPARE FOR NEW DISPENSERS
REMOVE EXISTING UNDERGROUND
GASOLINE PIPING, VENT PIPING,
AND ELECTRICAL CONDUIT
PREPARE FOR NEW
TANK AND PAD
REMOVE EXISTING OIL/WATER
SEPARATOR INLET PIPING
10,000 GALLON GASOLINE TANK, PAD,
TANK EQUIPMENT, AND MONITORING PIPES
(TO BE REMOVED)
3,000 GALLON
OIL/WATER SEPARATOR
(TO BE REMOVED)
EXISTING OIL/WATER
SEPARATOR OUTLET PIPING
(TO REMAIN)
EXISTING OIL/WATER SEPARATOR
OUTLET PIPING (TO BE REMOVED)
MILL ASPHALT
PAVEMENT - 1.5" DEPTH
(330 S.Y.)
GASOLINE UST EXCAVATION TO OCCUR AFTER PIPE TRENCH HAS BEEN
RESTORED TO ALLOW ACCESS TO ALL NORTHERN MAINTENANCE BAYS.
THE UST EXCAVATION AREA TO BE STABILIZED AND VEHICLE ACCESS
TO BAYS RESTORED WITHIN ONE WEEK OF WORK IN THIS AREA
PIPE TRENCH EXCAVATION MUST BE COORDINATED WITH SCTA
TO MAINTAIN ACCESS TO A MINIMUM OF TWO MAINTENANCE
BAYS AT ALL TIMES. TRENCH AREAS SHALL BE BACKFILLED
AND COVERED WITH STEEL PLATES TO MAINTAIN ACCESS.
REPLACEMENT OF OIL / WATER SEPARATOR
SYSTEM TO OCCUR AFTER THE GASOLINE UST
AND PIPE TRENCH HAVE BEEN RESTORED.
DEMOLITION PLAN NOTES
1. THE CONTRACTOR IS RESPONSIBLE FOR OBTAINING ALL LOCAL AND STATE PERMITS REQUIRED FOR
DEMOLITION WORK.
2. THE CONTRACTOR SHALL INDEMNIFY AND HOLD HARMLESS THE OWNER AND/OR ENGINEER FOR ANY AND ALL INJURIES AND/OR DAMAGES TO PERSONNEL, EQUIPMENT AND/OR EXISTING FACILITIES IN THE
DEMOLITION AND CONSTRUCTION DESCRIBED IN THE PLANS AND SPECIFICATIONS.
3. EXISTING CONDITIONS AS DEPICTED ON THESE PLANS ARE GENERAL AND ILLUSTRATIVE IN NATURE AND DO NOT INCLUDE MECHANICAL, ELECTRICAL AND MISCELLANEOUS STRUCTURES. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO EXAMINE THE SITE AND BE FAMILIAR WITH EXISTING CONDITIONS PRIOR TO BIDDING ON THE DEMOLITION WORK FOR THIS PROJECT. IF CONDITIONS ENCOUNTERED DURING EXAMINATION ARE SIGNIFICANTLY DIFFERENT THAN THOSE SHOWN, THE CONTRACTOR SHALL NOTIFY THE ENGINEER
IMMEDIATELY.
4. ALL DEMOLITION WASTE AND CONSTRUCTION DEBRIS SHALL BE REMOVED BY THE CONTRACTOR AND DISPOSED OF IN A STATE APPROVED WASTE SITE AND IN ACCORDANCE WITH ALL LOCAL AND STATE CODES
AND PERMIT REQUIREMENTS.
5. ALL UTILITY REMOVAL, RELOCATION, CUTTING, CAPPING AND/OR ABANDONMENT SHALL BE COORDINATED
WITH THE APPROPRIATE UTILITY COMPANY.
6. THE BURNING OF CLEARED MATERIAL AND DEBRIS SHALL NOT BE ALLOWED UNLESS CONTRACTOR GETS
WRITTEN AUTHORIZATION FROM THE LOCAL AUTHORITIES AND LANDOWNER.
7. EROSION AND SEDIMENTATION CONTROL MEASURES AROUND AREAS OF DEMOLITION SHALL BE INSTALLED
PRIOR TO INITIATION OF DEMOLITION ACTIVITIES. REFER TO E&S PLAN FOR DETAILS.
8. ASBESTOS OR HAZARDOUS MATERIALS, IF FOUND ON SITE, SHALL SHALL BE REMOVED BY A LICENSED HAZARDOUS MATERIALS CONTRACTOR. CONTRACTOR SHALL NOTIFY OWNER IMMEDIATELY IF HAZARDOUS
MATERIALS ARE ENCOUNTERED.
9. CONTRACTOR SHALL ADHERE TO ALL LOCAL, STATE, FEDERAL, AND OSHA REGULATIONS WHEN OPERATING
DEMOLITION EQUIPMENT AROUND UTILITIES.
10. CONTRACTOR SHALL PROTECT AT ALL TIMES ADJACENT PROPERTY FROM DAMAGE DUE TO DEMOLITION
ACTIVITIES.
11. DEMOLITION CONTRACTOR SHALL COORDINATE EXISTING FACILITIES UTILITY DISCONNECTS WITH THE
OWNER A MINIMUM 7 DAYS PRIOR TO ANTICIPATED DEMOLITION OF STRUCTURES.
12. THE CONTRACTOR IS RESPONSIBLE FOR MAINTAINING ALL CURB, SIDEWALK, PAVING, UTILITIES, STORM SEWER, LANDSCAPING, AND OTHER ITEMS NOT SCHEDULED FOR DEMOLITION. DAMAGES TO THESE ITEMS SHALL BE REPAIRED BY THE CONTRACTOR TO THE SATISFACTION OF THE OWNER AND ARE INCIDENTAL TO
THE WORK.
13. WHERE EXISTING PAVING AND CONCRETE IS TO REMAIN, THE CONTRACTOR SHALL NEATLY SAWCUT THE
PAVING PRIOR TO REMOVAL OF PAVING/CONCRETE SCHEDULED FOR DEMOLITION.
14. CONTRACTOR IS TO COORDINATE WITH SCTA PRIOR TO TAKING THE EXISTING OIL / WATER SEPARATOR SYSTEM OUT OF SERVICE. CONTRACTOR TO PROVIDE TEMPORARY WATER STORAGE FOR MINIMAL WATER USAGE WITHIN THE MAINTENANCE BAY UNTIL THE NEW OIL / WATER SEPARATOR IS OPERATIONAL.
15. CONTRACTOR SHALL PROVIDE CONSTRUCTION FENCING TO SEPARATE WORK AREA FROM OPERATION OF
EXISTING FACILITY.
16. CONTRACTOR SHALL COORDINATE ANY CLOSED OFF WORK AREAS WITH OWNER IN ADVANCE.
DEMOLITION HATCH LEGEND:
MILL ASPHALT PAVEMENT 1.5" DEPTH
(330 S.Y.)
SAW CUT AND REMOVE ASPHALT PAVEMENT
(100 S.Y.)
SAW CUT AND REMOVE CONCRETE PAVEMENT
(15 S.Y.)
SHEET DATE
SHEET NAME
SHEET NUMBER
DRAWN BY
DESIGNED BY
KCI PROJECT NUMBER
00034570_002
02/23/2026
BE
R
KS
C
O U
N
TY
REV DATE DESCRIPTION BY
C
IT
Y O
F R
EA
D
IN
G
SO
UT
H
CE
NT
RA
L T
RA
NS
IT
A
UT
HO
RI
TY
U N
LE
A
D
ED
F U
EL
T
A N
K A
N D
O
IL
W
A
TE
R
SE
PA
R
A
TO
R R
EP
LA
C
EM
EN
T
PL
A
N
N
. 1 0T
H S
TR
EE
T, R
EA
D
IN
G
, P A
BI
D
S
ET
936 RIDGEBROOK ROAD
SPARKS, MD 21152
PHONE: (410) 316-7800
Fax: (410) 316-7868
WWW.KCI.COM
BID SET
C-3
DEMOLITION PLAN
N
( IN FEET )
1 inch = 30ft.
15 3030 60
R O
N T
SE
TB
AC
K
6' B
U
FF
ER
' F
R O
N T
SE
TB
AC
K
0.
0.
480.00'
480.00'
6' B
U
FF
ER
15' FRONT
SETBACK
15' FRONT SETBACK
6' BUFFER
MERCEDES RONALD
1011 MOSS ST READING PA 19604-2213
PROPERTY ID/UPI: 17531721094836
LOCATION ADDRESS: 1722 N 10TH ST
MUNICIPALITY: READING
TAX DISTRICT: CITY OF READING
DEED #: 2017048285
DEED DATE: 20171228
PROPERTY CLASS: COMMERCIAL
LAND USE CODE: 2307
NET ACREAGE: ±1.39
A F HOLDING INC
PO BOX 15045 READING PA 19612-5045
PROPERTY ID/UPI: 17531721094597
LOCATION ADDRESS: 1700 N 10TH ST
MUNICIPALITY: READING
TAX DISTRICT: CITY OF READING
DEED # / DATE: 20261497 / 19000101
PROPERTY CLASS: COMMERCIAL
LAND USE CODE: 3326 NET ACREAGE: ±0.23
A F HOLDING INC
PO BOX 15045 READING PA 19612
PROPERTY ID/UPI: 17531721094698
LOCATION ADDRESS: 1712 N 10TH ST
MUNICIPALITY: READING
TAX DISTRICT: CITY OF READING
DEED # / DATE: 227120740 / 19960320
PROPERTY CLASS: INDUSTRIAL
LAND USE CODE: 3426
NET ACREAGE: ±0.30
BARTA BERKS AREA READING TRANSPORTATION AUTHORITY
10TH & EXETER STS READING, PA 19604 USA
PROPERTY ID/UPI: 17531721098735
LOCATION ADDRESS: 1701 N 10TH STREET
MUNICIPALITY: READING TAX DISTRICT: CITY OF READING
DEED # / DATE: 17020047 / 19000101
PROPERTY CLASS: EXEMPT LAND USE CODE: 9940
NET ACREAGE: ±5.36 (LOT ±230,400 SQ. FT.)
1-STORY CONCRETE BLOCK AND BRICK STRUCTURE
SANDRA J. WALTERS
PO BOX 14591 READING PA 19612
PROPERTY ID/UPI: 17531721096455
LOCATION ADDRESS: 1665 N 10TH ST
MUNICIPALITY: READING
TAX DISTRICT: CITY OF READING
DEED #: 2014005261
DEED DATE: 20140220
PROPERTY CLASS: COMMERCIAL
LAND USE CODE: 4241
NET ACREAGE: ±0.04
RODRIGUEZ BRYAN CASTILLO &
CASTILLO RAFAEL
4011 8TH AVE TEMPLE PA 19560
PROPERTY ID/UPI: 17531721097465
LOCATION: 1668 MULBERRY ST
MUNICIPALITY: READING
TAX DISTRICT: CITY OF READING
DEED #: 2018043957
DEED DATE: 20181221
PROPERTY CLASS: RESIDENTIAL
LAND USE CODE: 121A
NET ACREAGE: ±0.03
2 1/2 STORY BRICK/MASONRY
TUTTO MIO INC
96 COMMERCE DR # 153
WYOMISSING, PA 19610
PROPERTY ID/UPI: 17531721099401
LOCATION: 1639 MULBERRY ST
MUNICIPALITY: READING
TAX DISTRICT: CITY OF READING
DEED #: 2019042951
DEED DATE: 20191206
PROPERTY CLASS: COMMERCIAL
LAND USE CODE: 4101
NET ACREAGE: ±0.23
BEILER JOHN
3427 COMPASS RD GAP, PA 17527
PROPERTY ID/UPI: 17531721190434
LOCATION: 1632 N 11TH ST
MUNICIPALITY: READING
TAX DISTRICT: CITY OF READING
DEED #: 2022015354
DEED DATE: 20220412
PROPERTY CLASS: RESIDENTIAL
LAND USE CODE: 133
NET ACREAGE: ±0.09
2-STORY BRICK/MASONRY
EX. GATE BUTTON &
BOLLARD
VISITOR PARKING
SPACE (TYP OF 3)
EX. STOP SIGN
SIGN: NO PARKING OVER 5 TONS"
EX. TRANSF & ELECTRICAL
EQUIPMENT
FENCE 8' WROUGHT IRON
6' BUFFER
EXETER ST
BERN ST
N
0T H
S T
N
1T H
S T
U E
U E
U
EU
E
U E
PROPOSED 10,000 GAL GASOLINE
ABOVE GROUND TANK
(REFER TO MECHANICAL PLANS)
RELOCATED LIGHT POLE
TIE NEW OIL / WATER SEPARATOR
INTO EXISTING OUTLET PIPING
NEW 1.5 " ASPHALT OVERLAY
(760 S.Y.)
(REFER TO DETAIL)
NEW 3,000 GALLON OIL / WATER SEPARATOR
(REFER TO DETAIL AND MECHANICAL PLANS)
INSTALL NEW 4" DRAIN / INLET PIPING AND
CONNECT TO THE OIL / WATER SEPARATOR
INSTALL NEW VENT PIPING PER
MANUFACTURER'S INSTRUCTIONS. EXTEND
EXTERNAL VENTS ABOVE THE ROOF LINE.
PROPOSED LIMIT
OF DISTURBANCE
(3,100 S.F)
PROPOSED 6" BOLLARDS
INSTALL NEW CONCRETE OVER OIL / WATER SEPARATOR
(REFER TO SHEET C-5 FOR DETAILS)
5" BASE COURSE (PG64-22. 0.0 TO 0.3 MILLION ESAL'S, 25 MM MIX)
NOT TO SCALE
COMPACTED SUBGRADE
6" PENNDOT 2A STONE BASE COURSE
3" WEARING COURSE (PG64-22. 0.0 TO 0.3 MILLION ESAL'S, 9.5 MM MIX)
ASPHALT PAVEMENT DETAIL
HATCH LEGEND:
NEW 1.5" ASPHALT OVERLAY
(290 S.Y.)
BACKFILL AND FULL DEPTH
ASPHALT RECONSTRUCTION
(200 S.Y.)
BACKFILL AND FULL DEPTH CONCRETE
PAVEMENT RECONSTRUCTION
(55 S.Y.)
CONT. 6" X 6" - W2 X W2 W.W.M. WITH 6' LAP AT EDGES
NOT TO SCALE
COMPACTED SUBGRADE
6" PENNDOT 2A STONE BASE COURSE
10" THICK 4000 PSI CONC. PAD (MEDIUM BROOM FINISH)
CONCRETE PAVEMENT DETAIL
XXXXXXX X
SHEET DATE
SHEET NAME
SHEET NUMBER
DRAWN BY
DESIGNED BY
KCI PROJECT NUMBER
00034570_002
02/23/2026
BE
R
KS
C
O U
N
TY
REV DATE DESCRIPTION BY
C
IT
Y O
F R
EA
D
IN
G
SO
UT
H
CE
NT
RA
L T
RA
NS
IT
A
UT
HO
RI
TY
U N
LE
A
D
ED
F U
EL
T
A N
K A
N D
O
IL
W
A
TE
R
SE
PA
R
A
TO
R R
EP
LA
C
EM
EN
T
PL
A
N
N
. 1 0T
H S
TR
EE
T, R
EA
D
IN
G
, P A
BI
D
S
ET
936 RIDGEBROOK ROAD
SPARKS, MD 21152
PHONE: (410) 316-7800
Fax: (410) 316-7868
WWW.KCI.COM
BID SET
C-4
SITE PLAN
N
( IN FEET )
1 inch = 30ft.
15 3030 60
GENERAL SPECIFICATIONS
NO REQ'D: (1)
CAPACITY: 3000 GALLONS
TYPE: HTC-G, HIGHGUARD, SINGLE WALL
MATERIAL: MILD CARBON STEEL
FLOW RATE: 300 GPM
GAUGE: BASED ON 60" MAX BURIAL
SHELL - 7 GA.
HEADS - 7 GA.
SURFACE PREP:
SSPC NO. 6 BLAST ALL EXTERIOR SURFACES
SSCP NO. 10 BLAST ALL INTERIOR SURFACES
COATING: MATERIAL THICKNESS
EXTERIOR HIGHGUARD (75 MILS)
INTERIOR CHEMLINE 4200 PW (15 MILS)
CONSTRUCTION:
LAP FIT & WELD ALL EXTERIOR SEAMS
OPERATING PRESSURE: ATMOSPHERIC
NOTES:
1. POLYURETHANE HIGHGUARD TANK IS NOT APPROVED FOR
THE STORAGE OF HEATED PRODUCTS
2. ALL VENT PIPING BY INSTALLER
3. 15,000 VOLT SPARK TEST PROVIDED AT FACTORY
PROVIDED EQUIPMENT (BY VENDOR)
1. 150# R.F.S.O. FLANGE W/ 2" FNPT FOR VENT
2. 4" Ø FNPT FOR GAUGE WITH PLUG
3. VELOCITY HEAD DIFFUSION BAFFLE
4. WEAR PLATE
5. SEDIMENT CHAMBER
6. UNDERFLOW BAFFLE (REMOVABLE)
7. SLUDGE BAFFLE
8. STRIKER PLATES
9. PARALLEL CORRUGATED PLATE COALESCER. CORELLA PVC PLATES
(3" PLATE SPACING)
10. OIL / WATER SEPARATOR CHAMBER
11. 6" THICK PETROSCREEN COALESCER MATERIAL INSTALLED W / PULL
ROD SHIPPED LOOSE
12. STEEL OUTLET DOWNCOMER
13. 24" Ø MANWAY WITH BOLT-ON EXTENSION SHIPPED LOOSE
14. 4" Ø FNPT FOR OIL PUMP-OUT WITH INTERNAL PVC PIPE INSTALLED
& RISER PIPE SHIPPED LOOSE
15. 2" Ø FNPT FOR LEVEL SENSOR WITH RISER PIPE SHIPPED LOOSE
16. LIFTING LUG
17. 2" Ø FNPT FOR VENT
18. SLUDGE CHAMBER
19. STEEL TRANSFER PIPING
20. 7 GA. BULKHEAD
21. GLM-48 ROUND GRADE LEVEL MANWAY
22. GLM-36 ROUND GRADE LEVEL MANWAY
ANCILLARY PROVIDED EQUIPMENT:
(4) 24" FIBREFLEX MANWAY GASKETS
(4) SETS OF NUTS / BOLTS / WASHERS FOR 24" MANWAY
OIL / WATER SEPARATOR
DETAIL
MANWAY
DETAIL
Warranty The subject manway is warranted by Highland Tank & Mfg. Co. to be free from defects in manufacturing, workmanship and materials. Highland Tank will repair or replace, at its sole discretion F.O.B. factory, within a period of one year after date of shipment, any item of our manufacture. All other items shall be warranted by their respective manufacturers. Liability hereunder is limited, as stated above, and does not include labor, installation costs, indirect or consequential damages of any kind. Manways must be returned to the factory and if found to be defective upon examination, will be repaired, replaced or credit will be issued at our option.
Approved Manufacturer Tank to be manufactured by Highland Tank at one of the following locations:
Stoystown, PA, Manheim, PA, Watervliet, NY, or Greensboro, NC.
Concrete Anchors 1.5" x 2" x 3"
Manway Skirt
.375" Checkered Plate
Recessed “D” Ring for Lifting as
Needed
Manway Lid Lid Collar
Manway Skirt
Diameter
Aluminum Lid
Steel Lid
.50" x 3"
.50" x 1.5"
Round
Nominal Manway Diameters Model Manway Skirt Manway Lid
Number Thickness I.D. Collar I.D. O.D.
GLM-36 7ga 36” 38.5” 38”
GLM-48 .25” 48” 50.5” 50”
ELEVATION
PLAN
2" (MIN.)
STOP 50% OF REBAR AT
NOTE
TOOLED JOINT. EXTEND
REMAINING REBAR THROUGH
JOINT.JOINTS
X X X
MATCH
EXISTING GRADE
X X
MATCH EXISTING GRADE
X X X XXXX X XX X X XXXX X X XXXXX
MATCH EXISTING GRADE
XX
MATCH EXISTING GRADE MATCH EXISTING GRADE MATCH EXISTING GRADE MATCH EXISTING GRADE
END VIEW
OIL / WATER SEPARATOR DETAIL NOTE
1. INSTALL OIL / WATER SEPARATOR IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.
SHEET DATE
SHEET NAME
SHEET NUMBER
DRAWN BY
DESIGNED BY
KCI PROJECT NUMBER
00034570_002
02/23/2026
BE
R
KS
C
O U
N
TY
REV DATE DESCRIPTION BY
C
IT
Y O
F R
EA
D
IN
G
SO
UT
H
CE
NT
RA
L T
RA
NS
IT
A
UT
HO
RI
TY
U N
LE
A
D
ED
F U
EL
T
A N
K A
N D
O
IL
W
A
TE
R
SE
PA
R
A
TO
R R
EP
LA
C
EM
EN
T
PL
A
N
N
. 1 0T
H S
TR
EE
T, R
EA
D
IN
G
, P A
BI
D
S
ET
936 RIDGEBROOK ROAD
SPARKS, MD 21152
PHONE: (410) 316-7800
Fax: (410) 316-7868
WWW.KCI.COM
BID SET
C-5
DETAILS
SHEET DATE
SHEET NAME
SHEET NUMBER
DRAWN BY
DESIGNED BY
KCI PROJECT NUMBER
00034570_002
02/23/2026
BE
R
KS
C
O U
N
TY
REV DATE DESCRIPTION BY
C
IT
Y O
F R
EA
D
IN
G
SO
UT
H C
EN
TR
AL
TR
AN
SIT
AU
TH
OR
ITY
U N
LE
A
D
ED
F U
EL
T
A N
K A
N D
O
IL
W
A
TE
R
SE
PA
R
A
TO
R R
EP
LA
C
EM
EN
T
PL
A
N
N
. 1 0T
H S
TR
EE
T, R
EA
D
IN
G
, P A
BI
D
S
ET
BID SET
MECHANICAL ABBREVIATIONS
AST ABOVEGROUND STORAGE TANK
CS CONTAINMENT SUMP
ESO EMERGENCY SHUT-OFF
ETR EXISTING TO REMAIN
EX EXISTING
FFS FUEL FILTER SKID
FFSCP FUEL FILTER SKID CONTROL PANEL
FILL TANK FILL PIPING
FOR FUEL OIL RETURN PIPING
FOR(P) FUEL OIL RETURN PIPING (PRIMARY)
FOR(R) FUEL OIL RETURN PIPING (REDUNDANT)
GAL GALLON
L.C. LOCK CLOSED
L.O. LOCK OPEN
N.C. NORMALLY CLOSED
N.O. NORMALLY OPEN
RX REMOVE EXISTING
STP SUBMERSIBLE TURBINE PUMP
TFS TRUCK FILL SKID
TFSCP TRUCK FUEL SKID CONTROL PANEL
TS TRANSITION SUMP
TYP. TYPICAL
UST UNDERGROUND STORAGE TANK
MECHANICAL SHEET LIST
FM-0 - MECHANICAL COVER SHEET
FM-1 - MECHANICAL NEW WORK PLAN
FM-2 - MECHANICAL TANK DETAILS I
FM-3 - MECHANICAL DETAILS I
FM-4 - MECHANICAL DETAILS II
MECHANICAL PIPING LEGEND
NEW PIPE
DEMOLISHED
PIPE TURNED UP/DOWN
BREAK LINE
EXISTING LINEWORK
EXTENT OF DEMOLITION
CONNECT TO EXISTING
AUTOMATIC AIR VENT
AUTOMATIC CONTROL VALVE
CHECK VALVE
MANUAL BALL VALVE
RELIEF VALVE
BASKET STRAINER
SOLENOID VALVE
PRESSURE DIFFERENTIAL FLOW METER
PUMP
SIGHT GUAGE
AIR ELIMINATOR
DIFFERENTIAL PRESSURE GUAGE
FLOW SWITCH
PRESSURE GAUGE
PIPE REDUCER
SG
AE
DP
FS
MECHANICAL GENERAL NOTES
THESE NOTES APPLY TO ALL MECHANICAL DRAWINGS:
1. ALL EXISTING UNDERGROUND UTILITY LOCATIONS SHOWN ON THE PLANS ARE
APPROXIMATE. CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING ALL
UNDERGROUND UTILITIES PRIOR TO START OF EXCAVATION.
2. PRIOR TO DEMOLITION OF ANY PIPING SYSTEMS, PIPES SHALL BE CLEANED AND
PURGED OF ALL LIQUIDS AND VAPORS. ALL LIQUIDS SHALL BE COLLECTED AND
PROPERLY DISPOSED. CONTRACTOR SHALL FOLLOW THE APPROVED PIPING
REMOVAL ABANDONMENT AND DISPOSAL PLAN AND API RP 1604 GUIDANCE.
3. PROVIDE NON-METALLIC TAGS ON ALL TANKS AND NEW VALVES.
4. DUE TO THE SCALE OF THE DRAWINGS, NOT ALL EXISTING OR REQUIRED
OFFSETS, FITTINGS, APPURTENANCES, VALVES, OR PIPING ACCESSORIES ARE
SHOWN.
MECHANICAL
COVER SHEET
FM-0
S. CHENEY
I. STURGEON
936 RIDGEBROOK ROAD
SPARKS, MD 21152
PHONE: (410) 316-7800
Fax: (410) 316-7868
WWW.KCI.COM
U E
U E
U E
UE
UE
C S-
C
S-
C S-
C
S-
C S-
C
S-
C S-
C
S-
C S-
C
S-
C S-
C
S-
C S-
C
S-
C S-
C
S-
C S-
INSTALL NEW GASOLINE
DISPENSERS, DISPENSER
ISLANDS AND BOLLARDS
INSTALL NEW 3,000
GALLON OIL/WATER
SEPARATOR. (SEE CIVIL
PLANS FOR DETAILS)
INSTALL (1) 10,000 GALLON
UL 2085 FIREGUARD
GASOLINE AST (27'-3" x 8'-6"
DIAMETER) WITH ACCESS
STAIRS/PLATFORM DESIGN
REMOTE FILL
NEW CONCRETE PAD,
10'-6" x 34'-0", TO BE
INSTALLED PARALLEL TO
EXISTING CONCRETE PAD
SS SS
SS
SS
CONNECT NEW SEWER
PIPING TO EXISTING
SEWER PIPING
CONNECT NEW SEWER
PIPING TO OWS
CONNECT EXISTING
SEWER PIPE TO NEW
OWS OUTLET
NEW UNDERGROUND PIPENEW PIPE
TRANSITION SUMP
EXISTING OWS INLET
FROM THE WASH BAY
SHEET DATE
SHEET NAME
SHEET NUMBER
DRAWN BY
DESIGNED BY
KCI PROJECT NUMBER
00034570_002
02/23/2026
BE
R
KS
C
O U
N
TY
REV DATE DESCRIPTION BY
C
IT
Y O
F R
EA
D
IN
G
SO
UT
H C
EN
TR
AL
TR
AN
SIT
AU
TH
OR
ITY
U N
LE
A
D
ED
F U
EL
T
A N
K A
N D
O
IL
W
A
TE
R
SE
PA
R
A
TO
R R
EP
LA
C
EM
EN
T
PL
A
N
N
. 1 0T
H S
TR
EE
T, R
EA
D
IN
G
, P A
BI
D
S
ET
BID SET
1"=20'-0"1 MECHANICAL NEW WORK PLAN
GENERAL NOTES:
SEQUENCE OF NEW WORK:
1. THE CONTRACTOR SHALL INSTALL A NEW CONCRETE AST SUPPORT PAD, NEW 10,000 GALLON DOUBLE WALL AST, NEW ABOVEGROUND AND UNDERGROUND PIPING, NEW PIPING
TRANSITION SUMP, MONITORING AND OVERFILL ALARM SYSTEMS.
2. THE INSTALLATION OF THE UNDERGROUND PIPING WILL REQUIRE THE EXCAVATION OF THE EXISTING DRIVELANE. THE CONTRACTOR SHALL ENSURE ALL TRENCHES ARE BACKFILLED AND DRIVEABLE/ACCESSIBLE AT THE END OF THE EACH WORK DAY. FOLLOWING THE COMPLETION OF THE PIPING, THE CONTRACTOR SHALL RETURN THE TRENCHED AREA TO MATCH THE
EXISTING DRIVELANE.
NEW WORK PLAN NOTES:
NOT TO SCALE2 DISPENSER TANK ISOMETRIC
1. THE CONTRACTOR SHALL COORDINATE ALL EQUIPMENT LOCATIONS WITH STRUCTURAL, PLUMBING, ELECTRICAL AND FIRE PROTECTION EQUIPMENT AS MAY BE REQUIRED IN THE FIELD.
2. INSTALL ALL EQUIPMENT AND MATERIALS IN STRICT ACCORDANCE WITH RESPECTIVE MANUFACTURERS WRITTEN INSTRUCTIONS.
3. THIS CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AT THE SITE BEFORE FABRICATING OR ORDERING ANY INSTALLATION MATERIALS.
4. THE WORK SHOWN IS INTENDED TO INCLUDE COMPLETE AND PROPER SYSTEMS, ALL AS SHOWN ON PLANS AND AS SPECIFIED. ALL LABOR, EQUIPMENT, MATERIALS AND ACCESSORIES FOR A COMPLETE AND PROPER INSTALLATION, AND AS MAY BE REQUIRED FOR A PROPER SYSTEM, SHALL BE FURNISHED UNDER THIS CONTRACT.
5. ALL MATERIALS MUST BE INSTALLED BY SKILLED PERSONNEL IN ACCORDANCE WITH BEST PRACTICES OF THE INDUSTRY. ALL UNDERGROUND PIPING, SUMPS AND OTHER FUEL SYSTEM
COMPONENTS MUST BE INSTALLED BY MDE CERTIFIED TANK INSTALLERS.
6. THE DRAWINGS ARE DIAGRAMMATIC AND INDICATIVE OF THE WORK TO BE PERFORMED. HOWEVER IT IS NOT INTENDED THAT THEY SHOW EVERY FITTING OR APPURTENANCES REQUIRED
FOR A COMPLETE INSTALLATION.
7. THE CONTRACTOR SHALL CAREFULLY INVESTIGATE THE WORK SITE CONDITIONS THAT WOULD AFFECT THE WORK TO BE PERFORMED AND SHALL ARRANGE SUCH WORK ACCORDINGLY, FURNISHING REQUIRED OFFSETS, FITTINGS, AND ACCESSORIES TO MEET SUCH CONDITIONS.
8. THE DRAWINGS MUST BE FOLLOWED AS CLOSELY AS CIRCUMSTANCES WILL PERMIT. SHOULD IT BE FOUND THAT ANY SYSTEM OR EQUIPMENT CANNOT BE INSTALLED AS SHOWN ON THE DRAWINGS, THE ENGINEER SHALL BE CONSULTED BEFORE INSTALLING OR MAKING CHANGES TO THE LAYOUT.
9. THIS CONTRACTOR MUST COMPLY WITH ALL LAWS, ORDINANCES, AND REGULATIONS OF ALL AUTHORITIES HAVING JURISDICTION.
10. NOTHING CONTAINED ON THESE DRAWINGS OR THE SPECIFICATIONS SHALL BE CONSTRUED TO BE IN CONFLICT WITH ANY STATE OR LOCAL CODES, ORDINANCES, OR REGULATIONS
GOVERNING THE INSTALLATION OF WORK SPECIFIED AND INDICATED ON THE DRAWINGS.
11. CONTRACTOR SHALL PATCH, REPAIR AND PAINT TO MATCH ADJACENT SURFACES, ALL SURFACES DAMAGED OR OTHERWISE MARKED DUE TO REMOVAL OF EXISTING, AND INSTALLATION OF
NEW EQUIPMENT, PIPING AND RELATED APPURTENANCES.
12. WASTE MATERIALS, DEBRIS, AND RUBBISH SHALL BE REMOVED FROM THE JOB SITE AND LEGALLY DISPOSED OF IN ACCORDANCE WITH ALL APPLICABLE REGULATIONS. CONTRACTOR SHALL
THOROUGHLY CLEAN UP WORK AREAS AFTER WORK IS COMPLETE ON A DAILY BASIS.
1. PERFORM SUBSURFACE UTILITY MARKOUT.
2. INSTALL EROSION AND SEDIMENT CONTROL MEASURES.
3. INSTALL NEW CONCRETE PAD AND PREP FOR NEW AST. EXISTING GAS DISPENSERS STILL IN OPERATION.
4. INSTALL NEW AST AND ALL TANK TOP EQUIPMENT. EXISTING GAS DISPENSERS STILL IN OPERATION.
5. TAKE DISPENSERS OUT OF SERVICE AND INSTALL NEW PIPE TRENCH, NEW DISPENSERS AND ISLANDS, AND ELECTRIC. DRAIN, CLEAN AND TAKE EXISTING GASOLINE UST SYSTEM OUT OF
SERVICE. REMOVE FUEL FROM THE UNDERGROUND TANK AND PIPING AND TAKE IT OUT OF SERVICE, BUT UST TO REMAIN TEMPORARILY IN GROUND.
6. COMPLETE NEW GASOLINE AST AND DISPENSER SYSTEM AND OPEN FOR SERVICE.
7. REMOVE EXISTING GAS UST AND PIPING. BACKFILL AND STABILIZE PIPE TRENCH AREA TO MAINTAIN VEHICLE ACCESS TO A MINIMUM OF 2 MAINTENANCE BAYS AT ALL TIMES. GASOLINE UST
EXCAVATION AND REMOVAL TO OCCUR AFTER PIPE TRENCH HAS BEEN RESTORED TO ALLOW ACCESS TO ALL NORTHERN MAINTENANCE BAYS. THE UST EXCAVATION AREA TO BE STABILIZED AND VEHICLE ACCESS TO BAYS RESTORED WITHIN 1 WEEK OF WORK IN THIS AREA IN ADVANCE OF PAVING.
8. REMOVE EXISTING OWS AND INSTALL NEW OWS AND PIPING CONNECTIONS.
9. REPAVE AND RESTORE SITE.
FUEL LINES
SUBMERSIBLE PUMP
GASOLINE
TRANSITION SUMP
PROPOSED
GASOLINE AST
SYSTEM
EXISTING DIESEL
AST SYSTEM
MECHANICAL NEW
WORK PLAN
FM-1
S. CHENEY
I. STURGEON
936 RIDGEBROOK ROAD
SPARKS, MD 21152
PHONE: (410) 316-7800
SHEET NUMBER
DRAWN BY
DESIGNED BY
KCI PROJECT NUMBER
00034570_002
02/23/2026
BE
R
KS
C
O U
N
TY
REV DATE DESCRIPTION BY
C
IT
Y O
F R
EA
D
IN
G
SO
UT
H C
EN
TR
AL
TR
AN
SIT
AU
TH
OR
ITY
U N
LE
A
D
ED
F U
EL
T
A N
K A
N D
O
IL
W
A
TE
R
SE
PA
R
A
TO
R R
EP
LA
C
EM
EN
T
PL
A
N
N
. 1 0T
H S
TR
EE
T, R
EA
D
IN
G
, P A
BI
D
S
ET
BID SET
NOT TO SCALE1 TANK FIELD ENLARGED PLAN
CONCRETE TANK PAD
NEW GALVANIZED
STEEL STAIR AND
CATWALK PACKAGE
REMOTE FILL
WITH OPV
REMOTE FILL
STAGE I VR
INTERSTITIAL
MONITOR
NORMAL VENT
PRIMARY
E-VENT
SECONDARY
E-VENT
ATG PROBE STP
EXISTING DIESEL TANKS
AND PIPING TO REMAIN
NEW TRANSITION SUMP
NEW GASOLINE
REMOTE FILL
MECHANICAL
TANK
DETAILS
FM-2
S. CHENEY
I. STURGEON
936 RIDGEBROOK ROAD
SPARKS, MD 21152
PHONE: (410) 316-7800
SHEET NUMBER
DRAWN BY
DESIGNED BY
KCI PROJECT NUMBER
00034570_002
02/23/2026
BE
R
KS
C
O U
N
TY
REV DATE DESCRIPTION BY
C
IT
Y O
F R
EA
D
IN
G
SO
UT
H C
EN
TR
AL
TR
AN
SIT
AU
TH
OR
ITY
U N
LE
A
D
ED
F U
EL
T
A N
K A
N D
O
IL
W
A
TE
R
SE
PA
R
A
TO
R R
EP
LA
C
EM
EN
T
PL
A
N
N
. 1 0T
H S
TR
EE
T, R
EA
D
IN
G
, P A
BI
D
S
ET
BID SET
NOT TO SCALE1 10K GALLON GASOLINE TANK
MECHANICAL
DETAILS I
FM-3
S. CHENEY
I. STURGEON
936 RIDGEBROOK ROAD
SPARKS, MD 21152
PHONE: (410) 316-7800
SHEET NUMBER
DRAWN BY
DESIGNED BY
KCI PROJECT NUMBER
00034570_002
02/23/2026
BE
R
KS
C
O U
N
TY
REV DATE DESCRIPTION BY
C
IT
Y O
F R
EA
D
IN
G
SO
UT
H C
EN
TR
AL
TR
AN
SIT
AU
TH
OR
ITY
U N
LE
A
D
ED
F U
EL
T
A N
K A
N D
O
IL
W
A
TE
R
SE
PA
R
A
TO
R R
EP
LA
C
EM
EN
T
PL
A
N
N
. 1 0T
H S
TR
EE
T, R
EA
D
IN
G
, P A
BI
D
S
ET
BID SET
FUEL TANK
GROUND LEVEL
TRANSITION
SUMP
1-1/2" FLEX UNDERGROUND
DOUBLE-WALLED PIPING
DISPENSER
NO SMOKING
CONTENT LABEL
TANK #
PRODUCT
WORKING CAPACITY
TANK CAPACITY
CHECK GAUGE AND CHART
DO NOT OVERFILL
NFPA 704 M PLACARD
(DIAMOND LABEL WITH
NUMBERS 1,3,0 FOR
GASOLINE10000-GALLONS
FLAMMABLE
GASOHOL
TANK 1
VOLUME LABEL
TANK IDENTIFICATION LABEL
FUEL TYPE LABEL
HAZARD
STATEMENT LABEL
18" BURIAL
DEPTH MINIMUM
NOT TO SCALE1 10K GASOLINE AST SIGNAGE DETAIL
NOT TO SCALE9 FUEL DISPENSING PIPE DETAIL
TANK
DISPENSER (TYP.)
M
PRODUCT PIPING
MOTOR
BALL VALVE
FIRE VALVE
SOLENOID VALVE
S
S
TANK
WORKING
VENT
D
SUBMERSIBLE
PUMP
3" VENT
PIPING
M
S
D
STAGE I VAPOR RECOVERY
PIPING FROM GASOLINE
TANK
ARFP S.S REMOTE
FILL & VAPOR
RECOVERY BOX
(GASOLINE)
NOT TO SCALE2 PIPING PLAN
NOT TO SCALE3 GASOLINE REMOTE FILL
6"
NOT TO SCALE4 PIPING TRANSITION SUMP
4" SCHEDULE-40 GALVANIZED
STEEL PIPE
PRESSURE/VACUUM VENT
CAP FOR GASOLINE
NOT TO SCALE7 AST VENT DETAIL
NOT TO SCALE6 DISPENSER SUMP
NOT TO SCALE
DISPENSER SUMP
GALLONS0 0 0 0 000
SHEAR VALVE SECURELY FASTENED
TO SUMP WITH STABILIZER BAR KIT
SHEAR VALVE
MOUNTING PLATE
VEEDER-ROOT
SUMP SENSOR
FLEX CONNECTOR
HH RETRACTOR BASE PLATE
LOCATE RETRACTOR
POSTS IN THE FIELD
STAINLESS STEEL ISLAND
FORMS OPW 6013 SS
8 DISPENSER DETAIL
SHEAR VALVE
NOZZLE
VENT
LEAK DETECTOR
TO 6K
GASOLINE
TO 6K
GASOLINE
3" STAGE 1 VAPOR RECOVERY
ADAPTER
3" CHECK VALVE ON
TANK FILL PIPING
BEYOND BOX
3" REMOTE FILL ADAPTER
& 3" BALL VALVE INSIDE
FILL/SPILL BOX
DOUBLE WALL
UNDERGROUND
GASOLINE PIPE
STEEL GAS PIPE
VEEDER-ROOT
SUMP SENSOR
NEW
COUNTERWEIGHT
HOSE RETRIEVER
SWIVEL HEAD
AND BASE KIT
NEW WAYNE SINGLE HOSE,
SINGLE PRODUCT ISLAND
ORIENTED DISPENSER
NOT TO SCALE5 PIPING ISOMETRIC DETAIL
GASOLINE
TRANSITION SUMP
FUEL LINES
PROPOSED NEW
GASOLINE AST SYSTEM
SUBMERSIBLE PUMP
41"
46.5"
27"
EXISTING DIESEL
AST SYSTEM
BREAKAWAY
HOSE SWIVEL
AND NOZZLE
MECHANICAL
DETAILS II
FM-4
S. CHENEY
I. STURGEON
936 RIDGEBROOK ROAD
SPARKS, MD 21152
PHONE: (410) 316-7800
SHEET NUMBER
DRAWN BY
DESIGNED BY
KCI PROJECT NUMBER
00034570_002
02/23/2026
BE
R
KS
C
O U
N
TY
REV DATE DESCRIPTION BY
C
IT
Y O
F R
EA
D
IN
G
SO
UT
H C
EN
TR
AL
TR
AN
SIT
AU
TH
OR
ITY
U N
LE
A
D
ED
F U
EL
T
A N
K A
N D
O
IL
W
A
TE
R
SE
PA
R
A
TO
R R
EP
LA
C
EM
EN
T
PL
A
N
N
. 1 0T
H S
TR
EE
T, R
EA
D
IN
G
, P A
BI
D
S
ET
BID SET
ELECTRICAL
COVER SHEET
FE-0
1. PROVIDE MATERIALS THAT ARE NEW AND WITHOUT IMPERFECTIONS OR BLEMISHES, AND PROTECTED FROM THE ELEMENTS PRIOR TO CONSTRUCTION.
2. COMPLY WITH OWNER'S USE OF PREMISES AND SAFETY REGULATIONS.
3. COORDINATE LOCATIONS OF ALL ELECTRICAL EQUIPMENT AND ROUTINGS OF ALL ELECTRICAL FEEDERS (AND ASSOCIATED PULLBOXES) AND BRANCH CIRCUITS WITH ALL OTHER
UTILITIES (EXISTING AND NEW), WITH STRUCTURE, AND WITH BUILDING ELEMENTS.
4. UNLESS NOTED OTHERWISE, EVERY CONDUIT CONTAINING 120V RATED WIRING AND GREATER, SHALL CONTAIN A SEPARATE INSULATED GROUND WIRE RATED FOR 600V.
5. PROVIDE SEPARATE UNSHARED NEUTRAL CONDUCTOR(S) FOR ALL BRANCH CIRCUITS UTILIZING A NEUTRAL (I.E. 120V, 208V, ETC). PROVIDE SEPARATE UNSHARED NEUTRAL CONDUCTOR(S) FOR ALL FEEDERS REQUIRING A NEUTRAL (I.E. 1 PHASE-3 WIRE, 3 PHASE-4 WIRE FEEDERS). SHARING OF NEUTRAL CONDUCTORS BETWEEN ANY CIRCUIT (BRANCH OR
FEEDER) IS NOT PERMITTED. MULTI-WIRE BRANCH CIRCUITS ARE NOT PERMITTED.
6. PROVIDE ALL CUTTING, PATCHING, AND ACCESS PANELS REQUIRED FOR ELECTRICAL WORK. REPAIR AND REFINISH DISTURBED FINISH MATERIALS AND OTHER SURFACES TO MATCH
ADJACENT UNDISTURBED SURFACES.
7. ALL WORK AND EQUIPMENT SHALL COMPLY WITH ALL AUTHORITIES HAVING JURISDICTION, INCLUDING BUT NOT LIMITED TO THE INTERNATIONAL MECHANICAL CODE, THE LOCAL FIRE MARSHALL UNDERWRITERS LABORATORY (UL), INTERNATIONAL FUEL GAS CODE, FIRE CODE, LIFE SAFETY CODE, FIRE ALARM CODE, AND THE NATIONAL ELECTRICAL CODE.
MODIFICATIONS REQUIRED BY THE ABOVE SAID AUTHORITIES TO BRING THE SPACE UNDER CONTRACT UP TO CODE SHALL BE MADE WITHOUT ADDITIONAL CHARGE WHERE CONTRACT DOCUMENT REQUIREMENTS ARE IN EXCESS OF CODE REQUIREMENTS, THE CONTRACT DOCUMENTS SHALL GOVERN. DEVIATIONS FROM THE CONTRACT DOCUMENTS REQUIRED BY THE
ABOVE AUTHORITIES SHALL BE SUBMITTED TO THE ENGINEER FOR REVIEW.
8. CONTRACTOR SHALL VERIFY ALL POINTS OF CONNECTION BEFORE COMMENCING WORK. CONTRACTOR SHALL REMOVE ALL WASTE MATERIALS, `DEBRIS, AND RUBBISH FROM THE SITE
AND LEGALLY DISPOSE OF IT.
9. A SET OF ELECTRICAL RECORD/COORDINATION DRAWINGS SHALL BE MAINTAINED AT THE JOB SITE. ACTUAL LOCATIONS OF ALL EQUIPMENT, CONDUIT, ETC., AND ALL DEVIATIONS OF THE WORK FROM THAT SHOWN ON THE CONTRACT DOCUMENTS SHALL BE MARKED ON THE RECORD/COORDINATION DRAWINGS. EACH TRADE SHALL REVIEW THE COORDINATION DRAWINGS AND RESOLVE ANY POTENTIAL CONFLICTS WITH OTHER TRADES PRIOR TO INSTALLING ANY PORTION OF THERE WORK. AS BUILT DOCUMENTS SHALL BE TURNED OVER TO
THE OWNER.
10. WORK SHALL BE EXECUTED IN A GOOD WORKMANLIKE MANNER USING MECHANICS SKILLED IN THEIR RESPECTIVE TRADES. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR ALL CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES AND PROCEDURES FOR ALL COORDINATION OF WORK UNDER THIS CONTRACT. MAINTAIN THE CONSTRUCTION PREMISES
IN A NEAT AND ORDERLY CONDITION AT THE END OF EACH WORKING DAY.
11. CONTRACTOR SHALL MAKE ALL FINAL EQUIPMENT CONNECTIONS AND PROVIDE THE NECESSARY DEVICES, ETC. FOR A COMPLETE AND OPERABLE SYSTEM.
12. ARRANGE CONDUIT, WIRING, EQUIPMENT AND OTHER WORK GENERALLY AS SHOWN, PROVIDING PROPER CLEARANCE AND ACCESS. CAREFULLY EXAMINE ALL CONTRACT DRAWINGS AND COORDINATE THE WORK WITH ALL TRADES. WHERE DEPARTURES ARE PROPOSED BECAUSE OF FIELD CONDITIONS OR OTHER CAUSES, PREPARE AND SUBMIT DETAILED DRAWINGS
FOR ACCEPTANCE.
13. THE CONTRACT DRAWINGS ARE DIAGRAMMATIC. ALL OFFSETS, BENDS, FITTINGS AND ACCESSORIES ARE NOT NECESSARILY SHOWN. PROVIDE ALL SUCH ITEMS AS REQUIRED FOR
COMPLETE OPERATIONAL SYSTEM.
14. CONTRACTOR SHALL OBTAIN AND PAY FOR ALL PERMITS, PLAN REVIEWS AND CERTIFICATES OF INSPECTION REQUIRED BY THE AUTHORITIES HAVING JURISDICTION OVER THIS WORK.
15. COST INCURRED FROM DAMAGES AS A RESULT OF THE CONTRACTOR'S WORK WILL BE THE RESPONSIBILITY OF THE CONTRACTOR. DAMAGES WILL NOT WARRANT COST OR DELAY
CLAIMS.
16. CONTRACTOR SHALL COMPLY WITH LOCAL AND APPLICABLE CODES. IN THE EVENT OF A CONFLICT, THE MOST STRINGENT SHALL GOVERN. SHOULD A CONFLICT ARISE BETWEEN CONSTRUCTION DOCUMENTS AND APPLICABLE CODES, WORK SHALL COMPLY WITH THE REQUIREMENTS OF THE ENFORCING CODE AUTHORITIES.
17. WHERE EVER POSSIBLE, THE CONTRACTOR SHALL OBTAIN ACTUAL ROUGH-IN DRAWINGS FOR THE ACTUAL ITEM OF EQUIPMENT TO BE INSTALLED PRIOR TO ROUGH-IN. THIS SHALL APPLY TO ALL EQUIPMENT, WHETHER IT IS TO BE INSTALLED BY THE CONTRACTOR OR BY OTHERS.
18. ANY EXISTING ELECTRICAL WORK SHOWN ON THESE DRAWINGS IS INDICATED FOR THE CONVENIENCE OF THE CONTRACTOR ONLY. THE OWNER AND ENGINEER IN NO WAY WARRANT OR GUARANTEE EITHER THE ACCURACY OR COMPLETENESS OF THIS INFORMATION. FINAL LOCATIONS AND QUANTITIES SHALL BE FIELD VERIFIED BY THE CONTRACTOR TO THEIR OWN
SATISFACTION.
19. THE CONTRACTOR SHALL VISIT THE SITE AND FIELD VERIFY EXISTING CONDITIONS PRIOR TO BEGINNING WORK. ROUTINGS SHOWN ON DRAWINGS ARE DIAGRAMMATIC. CONTRACTOR SHALL VERIFY THAT INTERFERENCES WILL NOT BE ENCOUNTERED. IF ANY DISCREPANCY IS DETECTED, THE CONTRACTOR SHALL BRING IT TO THE OWNER'S ATTENTION WITH
RECOMMENDATIONS FOR OWNER'S APPROVAL.
20. ALL WORK SHALL BE GUARANTEED FOR ONE YEAR AGAINST FAULTY LABOR, MATERIALS AND WORKMANSHIP. TIME FOR THIS GUARANTEE SHALL BEGIN FROM THE DATE OF ACCEPTANCE
OF THE COMPLETED WORK BY THE OWNER OR HIS APPOINTED REPRESENTATIVE.
21. THE CONTRACTOR SHALL REMOVE AND REINSTALL OR RELOCATE ANY MOVEABLE OBSTRUCTIONS THAT MAY IMPEDE WORK UNDER THIS CONTRACT, AT NO ADDITIONAL COST. THESE SHALL INCLUDE, BUT ARE NOT LIMITED TO EQUIPMENT, PIPING, ANY SUPPORTING APPURTENANCES, CONDUIT, ETC. ANY CONSTRUCTION REQUIRING WORK STATED HEREIN, SHALL BE RECONNECTED AFTER THE END OF CONSTRUCTION TO PROVIDE A FULLY FUNCTIONAL SYSTEM(S), AS FOUND PRIOR TO COMMENCING CONTRACT WORK.
ELECTRICAL GENERAL NOTES:
NOT ALL ABBREVIATIONS ARE REFLECTED ON DRAWING DOCUMENTS
A AMPERE
AF AMPERE FRAME
ABOVE FINISHED FLOORAFF
ABOVE FINISHED GRADEAFG
AIC AMPERE INTERRUPTING CAPACITY
ATS AUTOMATIC TRANSFER SWITCH
C CONDUIT
EX EXISTING
FLA FULL LOAD AMPS
FVNR FULL VOLTAGE NON-REVERSING
GFI GROUND FAULT INTERRUPTING
HORSEPOWERHP
KILOVOLT AMPEREKVA
KILOWATTKW
MINIMUM CIRCUIT AMPACITYMCA
MAIN CIRCUIT BREAKERMCB
NATIONAL ELECTRICAL CODENEC
NATIONAL FIRE PROTECTION ASSOCIATIONNFPA
POLEP
PH OR Ø PHASE
PSI POUNDS PER SQUARE INCH
SECONDARYSEC
UNDERWRITER'S LABORATORIESU.L.
V VOLTS
WIREW
AWG AMERICAN WIRE GAUGE
MIN MINIMUM
MAXIMUM OVERCURRENT PROTECTIVE DEVICEMOPD
VA VOLTAMPERES
KILOVOLTKV
ELBOW FITTINGLB
DWG DRAWINGS
ELEC ELECTRICAL
EMT ELECTRIC METALLIC TUBING
GROUNDG, GND, GRD
THOUSAND CIRCULAR MILSKCMIL
NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATIONNEMA
CB CIRCUIT BREAKER
ELECTRICAL ABBREVIATIONS
CT CURRENT TRANSFORMER
XFMR TRANSFORMER
ACT ABOVE COUNTER TOP
DP DISTRIBUTION PANEL
LOCKED ROTOR AMPSLRA
RIGID GALVANIZED STEELRGS
LIGHTNING PROTECTION AIR TERMINAL
PC
PLUG AND CORD CONNECTION
UNDERGROUND CONDUIT ROUTING: ELECTRICAL
SYMBOL DESCRIPTION
CIRCUIT BREAKER
GROUNDING CONNECTION
EQUIPMENT (SURFACE MOUNTED AND RECESSED)
N
L E
TRANSFER SWITCH
G GENERATOR
SYMBOL DESCRIPTION
CURRENT TRANSFORMER CONNECTIONS
DELTA-WYE POWER TRANSFORMER
SURGE PROTECTION DEVICE
GFI
WP
RACEWAY-CONDUIT TURNED UP
RACEWAY-CONDUIT TURNED DOWN
FV
ELECTRICAL SYMBOLS
DISCONNECT SWITCH
FULL VOLTAGE MAGNETIC, NON-REVERSING,
3 PHASE MOTOR STARTER
DISCONNECT SWITCH AND COMBINATION
MOTOR STARTER/DISCONNECT SWITCH
MOTORIZED EQUIPMENT
SPD
E
DUPLEX RECEPTACLE, 20A, NEMA 5-20R
GFI: GROUND FAULT CIRCUIT INTERRUPTER
WP: WEATHER PROOF COVER
LIGHT FIXTURE, SEE LIGHT FIXTURE SCHEDULE
UTILITY POLE
A
J JUNCTION BOX
RACEWAY-CHANGE IN ELEVATIONBELOW GRADEABOVE GRADE
AT PHASE CONDUCTORS
CT'S
PHOTOCELL
E
NOT ALL SYMBOLS ARE REFLECTED ON DRAWING DOCUMENTS
ELECTRICAL AND EMERGENCY MANHOLES
C UNDERGROUND CONDUIT ROUTING: CONTROL
UNDERGROUND ELECTRICAL UTILITY ROUTING
UNDERGROUND TELEPHONE UTILITY ROUTING
UGE
UGT
T TELEPHONE MANHOLE
LOD LIMIT OF DISTURBANCE
POLE MOUNTED LIGHT FIXTURES
PROTECTION BOLLARD
BUILDING INTERIOR CONDUIT ROUTING
EM
GROUND ROD
20A, SINGLE POLE, 120V, MANUAL MOTOR
STARTER WITH THERMAL OVERLOAD
ELEMENT
Sm
ELECTRICAL SHEET LIST
FE-0 - ELECTRICAL COVER SHEET
FE-1 - ELECTRICAL NEW WORK PLAN
FE-2 - ELECTRICAL DETAILS I
FE-3 - ELECTRICAL DETAILS II
S. CHENEY
I. STURGEON
936 RIDGEBROOK ROAD
SPARKS, MD 21152
PHONE: (410) 316-7800
U E
U E
U E
UE
UE
C S-
C
S-
C S-
C
S-
C S-
C
S-
C S-
C
S-
C S-
C
S-
C S-
C
S-
C S-
C
S-
C S-
C
S-
C S-
INSTALL NEW 3,000 GALLON
OIL/WATER SEPARATOR. (SEE
CIVIL PLANS FOR DETAILS)
INSTALL (1) 10,000 GALLON
UL 2085 FIREGUARD
GASOLINE AST (27'-3" x 8'-6"
DIAMETER) WITH ACCESS
STAIRS/PLATFORM DESIGN
NEW CONCRETE PAD,
10'-6" x 34'-0", TO BE
INSTALLED PARALLEL TO
EXISTING CONCRETE PAD
REMOTE FILL
EXISTING ELECTRICAL
PANELS TO REMAIN
(APPROXIMATE LOCATION)
PROPOSED
TRENCH LOCATION
INSTALL NEW GASOLINE
DISPENSERS, DISPENSER
ISLAND AND BOLLARDS
ROUTE NEW CONDUITS THROUGH
EXISTING WIREWAY. IF WIREWAY CANNOT
HANDLE NEW CONDUITS, PROVIDE NEW
WIREWAY TO ACCOMMODATE THE
ADDITIONAL CONDUITS
EX ATS
EX SBP1
EX FUEL PANEL
EX PB1 (RIGHT)
EX PB1 (LEFT)
EX PA1 (RIGHT)
EX PA1 (LEFT)
1 2
8 A
A
ROUTE NEW CONDUIT THROUGH EXISTING
WIREWAY. IF WIREWAY CANNOT HANDLE
NEW CONDUITS, PROVIDE NEW WIREWAY TO
ACCOMMODATE THE ADDITIONAL CONDUITS
EXISTING
VEEDER-ROOT TLS
450 CONSOLE
NEW OWS
CONTROL PANEL
SHEET DATE
SHEET NAME
SHEET NUMBER
DRAWN BY
DESIGNED BY
KCI PROJECT NUMBER
00034570_002
02/23/2026
BE
R
KS
C
O U
N
TY
REV DATE DESCRIPTION BY
C
IT
Y O
F R
EA
D
IN
G
SO
UT
H C
EN
TR
AL
TR
AN
SIT
AU
TH
OR
ITY
U N
LE
A
D
ED
F U
EL
T
A N
K A
N D
O
IL
W
A
TE
R
SE
PA
R
A
TO
R R
EP
LA
C
EM
EN
T
PL
A
N
N
. 1 0T
H S
TR
EE
T, R
EA
D
IN
G
, P A
BI
D
S
ET
BID SET
1"=20'-0"1 ELECTRICAL NEW WORK PLAN
GENERAL NOTES:
KEYED NOTES:
1. THE CONTRACTOR SHALL COORDINATE ALL EQUIPMENT LOCATIONS WITH STRUCTURAL, PLUMBING, ELECTRICAL AND FIRE PROTECTION EQUIPMENT AS MAY BE REQUIRED IN THE FIELD.
2. INSTALL ALL EQUIPMENT AND MATERIALS IN STRICT ACCORDANCE WITH RESPECTIVE MANUFACTURERS WRITTEN INSTRUCTIONS.
3. THIS CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AT THE SITE BEFORE FABRICATING OR ORDERING ANY INSTALLATION MATERIALS.
4. THE WORK SHOWN IS INTENDED TO INCLUDE COMPLETE AND PROPER SYSTEMS, ALL AS SHOWN ON PLANS AND AS SPECIFIED. ALL LABOR, EQUIPMENT, MATERIALS AND ACCESSORIES FOR A COMPLETE AND PROPER INSTALLATION, AND AS MAY BE REQUIRED FOR A PROPER SYSTEM, SHALL BE FURNISHED UNDER THIS CONTRACT.
5. ALL MATERIALS MUST BE INSTALLED BY SKILLED PERSONNEL IN ACCORDANCE WITH BEST PRACTICES OF THE INDUSTRY. ALL UNDERGROUND PIPING, SUMPS AND OTHER FUEL SYSTEM
COMPONENTS MUST BE INSTALLED BY MDE CERTIFIED TANK INSTALLERS.
6. THE DRAWINGS ARE DIAGRAMMATIC AND INDICATIVE OF THE WORK TO BE PERFORMED. HOWEVER IT IS NOT INTENDED THAT THEY SHOW EVERY FITTING OR APPURTENANCES
REQUIRED FOR A COMPLETE INSTALLATION.
7. THE CONTRACTOR SHALL CAREFULLY INVESTIGATE THE WORK SITE CONDITIONS THAT WOULD AFFECT THE WORK TO BE PERFORMED AND SHALL ARRANGE SUCH WORK ACCORDINGLY, FURNISHING REQUIRED OFFSETS, FITTINGS, AND ACCESSORIES TO MEET SUCH CONDITIONS.
8. THE DRAWINGS MUST BE FOLLOWED AS CLOSELY AS CIRCUMSTANCES WILL PERMIT. SHOULD IT BE FOUND THAT ANY SYSTEM OR EQUIPMENT CANNOT BE INSTALLED AS SHOWN ON THE DRAWINGS, THE ENGINEER SHALL BE CONSULTED BEFORE INSTALLING OR MAKING CHANGES TO THE LAYOUT.
9. THIS CONTRACTOR MUST COMPLY WITH ALL LAWS, ORDINANCES, AND REGULATIONS OF ALL AUTHORITIES HAVING JURISDICTION.
10. NOTHING CONTAINED ON THESE DRAWINGS OR THE SPECIFICATIONS SHALL BE CONSTRUED TO BE IN CONFLICT WITH ANY STATE OR LOCAL CODES, ORDINANCES, OR REGULATIONS
GOVERNING THE INSTALLATION OF WORK SPECIFIED AND INDICATED ON THE DRAWINGS.
11. CONTRACTOR SHALL PATCH, REPAIR AND PAINT TO MATCH ADJACENT SURFACES, ALL SURFACES DAMAGED OR OTHERWISE MARKED DUE TO REMOVAL OF EXISTING, AND INSTALLATION
OF NEW EQUIPMENT, PIPING AND RELATED APPURTENANCES.
12. WASTE MATERIALS, DEBRIS, AND RUBBISH SHALL BE REMOVED FROM THE JOB SITE AND LEGALLY DISPOSED OF IN ACCORDANCE WITH ALL APPLICABLE REGULATIONS. CONTRACTOR
SHALL THOROUGHLY CLEAN UP WORK AREAS AFTER WORK IS COMPLETE ON A DAILY BASIS.
1 EXISTING ELECTRICAL PANELS LOCATED IN GARAGE/SHOP SHALL REMAIN AND NEW CIRCUITS/FEEDERS FOR NEW EQUIPMENT TO BE PULLED FROM THIS LOCATION.
2 PROVIDE THE FOLLOWING CIRCUITS AND FEEDERS:
(1) 20A/2P BREAKER. PROVIDED 2#12, 1#12 GRD. - 1" C. TO TANK SUBMERSIBLE PUMP IN NEAREST EXISTING 120/208V PANEL. PROVIDE WIRING AND CONDUIT FROM TANK TO NEW SUBMERSIBLE PUMP CONTROLLER. BREAKERS SHOULD MATCH EXISTING BREAKER MANUFACTURER AND EXISTING PANEL AIC RATING.
(1) 20A/1P BREAKER. PROVIDE 1#12, 1#12 GRD. - 1"C. TO NEW OVERFILL ALARM IN NEAREST EXISTING 120/208V PANEL. NEW BREAKERS SHOULD MATCH EXISTING BREAKER
MANUFACTURER AND EXISTING PANEL AIC RATING.
(2) 3/4" CONDUIT FOR LOW VOLTAGE CABLING.
3 NEW CONDUITS TO FOLLOW EXISTING CONDUIT ROUTING.
4 PROVIDE REQUIRED CONDUIT SEAL OFFS PER NFPA 30.
5 REUSE EXISTING CONDUIT, WIRING AND CIRCUITS FOR NEW FUEL DISPENSERS.
6 DISCONNECT EXISTING LIGHT FIXTURE. REMOVE EXISTING POLE AND LIGHT FIXTURE. REMOVE EXISTING POLE BASE. EXISTING WIRING AND CONDUIT TO BE INTERCEPTED AND REUSED IN
NEW LOCATION OF EXISTING LIGHT FIXTURE.
7 PROVIDE NEW POLE BASE AND REINSTALL RELOCATED LIGHT POLE AND FIXTURE. REFER TO STRUCTURAL DRAWINGS FOR POLE BASE DESIGN.
8 THE INSTALLATION OF THE UNDERGROUND PIPING WILL REQUIRE THE EXCAVATION OF THE EXISTING DRIVELANE. THE CONTRACTOR SHALL ENSURE ALL TRENCHES ARE BACKFILLED AND DRIVEABLE/ACCESSIBLE AT THE END OF EACH WORK DAY. FOLLOWING THE COMPLETION OF THE PIPING, THE CONTRACTOR SHALL RETURN THE TRENCHED AREA TO MATCH THE
EXISTING DRIVELANE.
9 EXTEND LOW VOLTAGE CONDUIT FOR TANK PROBE AND SENSORS AND CONNECT TO EXISTING VEEDER-ROOT TLS 450.
INTEGRATE EXISTING ESTOP AND OVERFILL ALARM WITH NEW GASOLINE TANK AND DISPENSER WIRING. THE INTENT OF THE DESIGN IS TO MAKE ONE COMPLETE ALARM AND
EMERGENCY SHUT-OFF SYSTEM.
REUSE 120V CIRCUIT FROM EXISTING OWS ALARM FOR NEW OWS CONTROL PANEL.
EXTEND NEW LOW VOLTAGE CONDUIT AND WIRING FROM THE NEW OWS PANEL LOCATION TO OWS SENSORS.
RECONNECT EXISTING COEN CORP PEDESTALS AND RFID READER TO CONTROL DISPENSERS.
ELECTRICAL NEW
WORK PLAN
FE-1
S. CHENEY
I. STURGEON
936 RIDGEBROOK ROAD
SPARKS, MD 21152
PHONE: (410) 316-7800
SHEET NUMBER
DRAWN BY
DESIGNED BY
KCI PROJECT NUMBER
00034570_002
02/23/2026
BE
R
KS
C
O U
N
TY
REV DATE DESCRIPTION BY
C
IT
Y O
F R
EA
D
IN
G
SO
UT
H C
EN
TR
AL
TR
AN
SIT
AU
TH
OR
ITY
U N
LE
A
D
ED
F U
EL
T
A N
K A
N D
O
IL
W
A
TE
R
SE
PA
R
A
TO
R R
EP
LA
C
EM
EN
T
PL
A
N
N
. 1 0T
H S
TR
EE
T, R
EA
D
IN
G
, P A
BI
D
S
ET
BID SET
1 HAZARDOUS AREA CLASSIFICATION ZONE
SCALE: NONE
HAZARDOUS AREA CLASSIFICATION DRAWING NOTES:
2 HAZARDOUS AREA CLASSIFICATION ZONE
SCALE: NONE
FIELD VERIFY EXISTING
WALL THICKNESS
5 WALL-FLOOR PENETRATION DETAIL
SCALE: NONE 4 EXTERIOR EQUIPMENT MOUNTING DETAIL AT ABOVE GROUND FUEL TANKS
SCALE: NONE
3 TYPICAL TANK GROUNDING DETAIL
SCALE: NONE
12'-0" 12'-0"
VENT AREA,
CLASS 1, DIV. 1
VENT AREA,
CLASS 1, DIV. 2
GASOLINE TANK AREA,
CLASS 1, DIV. 2
GASOLINE TANK,
CLASS 1, DIV. 1
DISPENSER ISLAND
GASOLINE DISPENSERS
CLASS 1, DIV. 1
GASOLINE DISPENSER AREA
(TYP OF 4), CLASS 1 DIV. 2
EXTERIOR METAL
FUEL TANK
TANK SUPPORT
SADDLE (TYPICAL)
GROUNDING HOLE IN
SADDLE (TYPICAL)
CONCRETE PAD
FINISHED GRADE
OR PAVEMENT
EXOTHERMIC WELD
(TYPICAL)
3/4" DIAMETER X 10 FOOT LONG
COPPER CLAD STEEL GROUND
ROD DRIVEN 12 INCHES BELOW
FINISHED GRADE (TYPICAL OF 3)
TO GROUNDING HOLE
AT SADDLE ON OTHER
SIDE OF TANK
TO GROUNDING HOLE
AT SADDLE ON OTHER
SIDE OF TANK
STAINLESS STEEL, EXPANSION
TYPE ANCHOR BOLT WITH NUT
AND WASHER (TYPICAL)
RGS SLOTTED UNISTRUT
CHANNELS (3"W X 1.5"D X
1/4" THICK)
RGS BOLT WITH NUT AND
WASHER (TYPICAL)
RGS UNISTRUT POST BASE
SUPPORT (TYPICAL)
FINISHED PAVEMENT
ENTIRE SPACE WITHIN DISPENSERS
WITHIN 18" OF DISPENSER ENCLOSURE OR THAT
PORTION OF DISPENSER ENCLOSURE
CONTAINING LIQUID HANDLING COMPONENTS,
EXTENDING HORIZONTALLY 20' IN ALL DIRECTIONS
AND DOWN TO GRADE LEVEL
WITHIN 5' OF OPEN END VENT, EXTENDING IN ALL DIRECTIONS
BETWEEN 5' AND 10' FROM OPEN END OF VENT, EXTENDING IN ALL
DIRECTIONS.
WITHIN 10' OF SHELL ENDS, AND TOP OF TANK
ENTIRE VOLUME OF INSIDE OF TANK
PIPE SLEEVE - SIZE AS
REQUIRED
CONCRETE WALL OR
FLOOR SLAB
CONDUIT
PACKING MATERIAL: 3"
DEPTH, 4PCF, MINERAL
WOOL 1/2" FROM SURFACE
3M FIREDAM 150
CAULK 1/2" DEPTH
1" MAXIMUM
ANNULAR SPACE
1" MAXIMUM
ANNULAR SPACE
8" X 8"
WIREWAY
8" X 8"
WIREWAY
EXISTING
DIESEL TANK
EXISTING
DIESEL TANK
ELE…
This is the start of the file's text. The full file is on GovTribe.