These are 100% Construction Documents for the Santa Cruz Metro Bus Overflow Parking Project located at 809 W. Beach St. in Watsonville, California. The project involves comprehensive electrical and site improvements, specifically focusing on parking lot lighting, electrical infrastructure, and site electrical systems. The documents, prepared by Jacobs Engineering Group Inc., are dated March 21, 2025, and include detailed electrical site plans, photometric calculations, luminaire schedules, electrical site plans, conduit routing, and specific technical specifications for lighting pole installations, electrical equipment, and site electrical systems.
The project includes installing multiple 35'-0" aluminum lighting poles with LED luminaires arranged at various degrees of spacing, designed to provide controlled illumination with minimal offsite light spill. The electrical design incorporates features such as photocells, surge protectors, and specific mounting requirements, with careful attention to placement near the perimeter fenceline and coordination with potential security camera installations. The documents specify using bronze-finished equipment, concrete foundations, and careful routing of underground conduits, with provisions for future infrastructure like a potential PG&E transformer area. The electrical systems are designed to connect to an existing load center and include detailed voltage drop calculations, energy compliance documentation, and comprehensive technical specifications for installation and equipment.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
D
C
B
A
REUSE OF DOCUMENTS: THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE PROPERTY OF JACOBS AND IS NOT TO BE USED, IN WHOLE OR IN PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF JACOBS.
Drawing Sheet Number:
554321 www.jacobs.com
©Jacobs Engineering Group Inc. 2024 ALL RIGHTS RESERVED
Project Number:
Paper Size: ARCH E1
Drawing Sheet Title:
Drawing Status:
Graphic Scale :
Revisions:
Project Client:
Seals:
E
4 Embarcadero Center, Suite 3800 San Francisco, CA 94105
P: 415-728-0850
W8Y13601
SANTA CRUZ METRO
809 W. Beach St, Watsonville
100% CONSTRUCTION
DOCUMENTS
Number Description Date
Rev.
1970 BROADWAY ST STE 760
OAKLAND, CA 94612
TITLE SHEET
0.1
T-1
NO SCALE
NS
CIVIL
C
Exp.
E
TS AT
OF
G R E
No.
ANI
RL FOA
E
RE
S
D
TER
E
R EFO SP
E
LNAO
GN
94922
06/30/25
A. SEITZ
ISSUED FOR
CONSTRUCTION
2025-03-21
Rev.
Attachment A to IFB 26-02
C
B
A
REUSE OF DOCUMENTS: THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE PROPERTY OF JACOBS AND IS NOT TO BE USED, IN WHOLE OR IN PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF JACOBS.
Drawing Sheet Number:
554321 www.jacobs.com
©Jacobs Engineering Group Inc. 2024 ALL RIGHTS RESERVED
Project Number:
Paper Size: ARCH E1
Drawing Sheet Title:
Drawing Status:
Graphic Scale :
Revisions:
Project Client:
Seals:
E
4 Embarcadero Center, Suite 3800 San Francisco, CA 94105
P: 415-728-0850
W8Y13601
SANTA CRUZ METRO
809 W. Beach St, Watsonville
100% CONSTRUCTION
DOCUMENTS
Number Description Date
Rev.
1970 BROADWAY ST STE 760
OAKLAND, CA 94612
PAVEMENT
DELINEATION PLAN
0.1
PD-1
NS
CIVIL
C
Exp.
E
TS AT
OF
G R E
No.
ANI
RL FOA
E
RE
S
D
TER
E
R EFO SP
E
LNAO
GN
94922
06/30/25
A. SEITZ
ISSUED FOR
CONSTRUCTION
2025-03-21
Rev.
C
B
A
REUSE OF DOCUMENTS: THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE PROPERTY OF JACOBS AND IS NOT TO BE USED, IN WHOLE OR IN PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF JACOBS.
Drawing Sheet Number:
554321 www.jacobs.com
©Jacobs Engineering Group Inc. 2024 ALL RIGHTS RESERVED
Project Number:
Paper Size: ARCH E1
Drawing Sheet Title:
Drawing Status:
Graphic Scale :
Revisions:
Project Client:
Seals:
E
4 Embarcadero Center, Suite 3800 San Francisco, CA 94105
P: 415-728-0850
W8Y13601
SANTA CRUZ METRO
809 W. Beach St, Watsonville
100% CONSTRUCTION
DOCUMENTS
Number Description Date
Rev.
CIDH PILES DETAILS
S-001
ISSUED FOR
CONSTRUCTION
2025-03-21
1970 BROADWAY ST STE 760
OAKLAND, CA 94612
Rev.
C
B
A
REUSE OF DOCUMENTS: THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE
PROPERTY OF JACOBS AND IS NOT TO BE USED, IN WHOLE OR IN PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF JACOBS.
Drawing Sheet Number:
554321 www.jacobs.com
©Jacobs Engineering Group Inc. 2025 ALL RIGHTS RESERVED
Project Number:
Paper Size: ARCH E1
Drawing Sheet Title:
Drawing Status:
Graphic Scale :
Revisions:
Project Client:
Seals:
E
4 Embarcadero Center, Suite 3800
San Francisco, CA 94105
P: 415-728-0850
W8Y13601
SANTA CRUZ METRO
809 W. Beach St, Watsonville
100% CONSTRUCTION
DOCUMENTS
Number Description Date
Rev.
Project :
PARKING LOT
IMPROVEMENTS
E-001
E-401A
DUPLEX 20A RECEPTACLE, 120V
SPLIT 20A DUPLEX RECEPTACLE
(15)
TVSS
T
225AF
225AT
3P
ABBREVIATIONS
A AMPERE
AC ALTERNATING CURRENT, AIR
CONDITIONING
AF AMPERE FRAME, AMPERE
FUSE
AFC AVAILABLE FAULT CURRENT
AFG ABOVE FINISHED FLOOR
AHJ AUTHORITY HAVING
JURISDICTION
AIC AMPERE INTERRUPTING
CAPACITY
AHU AIR HANDLING UNIT
ANN ANNUCIATOR
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER
SWITCH
AV AUDIO/VISUAL
AVG AVERAGE
AWG AMERICAN WIRE GAUGE
BC BARE COPPER
BKR BREAKER
BLDG BUILDING
BMS BUILDING MANAGEMENT
SYSTEM
C CONDUIT
COND CONDUCTOR
CONN CONNECTION
CONT CONTINUOUS, CONTINUATION
CB CIRCUIT BREAKER
CCTV CLOSED CIRCUIT TELEVISION
CFCI CONTRACTOR FURNISHED
CONTRACTOR INSTALLED
CKT CIRCUIT
CO CONDUIT ONLY
CONV CONVENIENCE
CONTR CONTRACTOR
COMB COMBINATION
COMM COMMUNICATION
COMP COMPRESSOR
CPU CENTRAL PROCESSING UNIT
CT CURRENT TRANSFORMER
CU COPPER, CONDENSING UNIT
DC DIRECT CURRENT
DI DIGITAL INPUT
DIA DIAMETER
DISC DISCONNECT
DPDT DOUBLE POLE DOUBLE
THROW
DPNL,DP DISTRIBUTION PANEL
DPST DOUBLE POLE SINGLE THROW
DTC DIGITAL TIME CLOCK
(E) EXISTING TO REMAIN
E.C. EMPTY CONDUIT
EF EXHAUST FAN
EL ELECTRIC, ELECTRICAL
ELEV ELEVATION
EMT ELECTRICAL METALLIC
TUBING
ENCL ENCLOSURE
EHT ELECTRIC HEAT TRACE
EOL END OF LINE RESISTOR
EQ, EQUIPMENT
EQUIP
ER EQUIPMENT ROOM
EWC ELECTRIC WATER COOLER
(F) FUTURE
FAAP FIRE ALARM ANNUNCIATOR
PANEL
FACP FIRE ALARM CONTROL PANEL
FC FOOT CANDLE, FAN COIL
FLA FULL LOAD AMPS
FL FLUORESCENT
FO FIBER OPTIC
FPC FIRE PUMP CONTROLLER
FPP FIBER PATCH PANEL
FSD FIRE-SMOKE DAMPER
FV FULL VOLTAGE
FVNR FULL VOLTAGE,
NON-REVERSING
GA GAUGE
GEC GROUNDING ELECTRODE
CONDUCTOR
GFI GROUND FAULT INTERRUPTER
GFCI GROUND FAULT CIRCUIT
INTERRUPTER
GFP GROUND FAULT PROTECTION
G, GRD, GROUND
GND
HAZ HAZARDOUS
HID HIGH INTENSITY DISCHARGE
HH HANDHOLE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER, HEAT PUMP
HPF HIGH POWER FACTOR
HT HEIGHT
HV HIGH VOLTAGE
HVAC HEATING, VENTILATING AND
AIR CONDITIONING
HZ HERTZ
IC INTERMEDIATE CROSS
CONNECT
IDF INTERMEDIATE DISTRUBTION
FRAME
IDS INTRUSION DETECTION
SYSTEM
IES ILLUMINATING ENGINEERING
SOCIETY
IG ISOLATED GROUND
J, JB, JUNCTION BOX
J-BOX
KA KILOAMPERES
KCMIL THOUSAND CIRCULAR MILLS
KP KEYPAD
KV KILOVOLT
KVA KILOVOLT AMPERES
KVAR KILOVOLT
AMPERES-REACTIVE
KW KILOWATT
KWH KILOWATT HOURS
LRA LOCKED ROTOR AMPERE
LSIG LONG TIME, SHORT TIME,
INSTANTANEOUS , GROUND
FAULT
LTG LIGHTING
LV LOW VOLTAGE
MAX MAXIMUM
MCA MINIMUM CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MCP MOTOR CIRCUIT PROTECTOR
MDF MAIN DISTRIBUTION FRAME
MFR MANUFACTURER
MH MANHOLE
MIN MINIMUM
MLO MAIN LUGS ONLY
MM MULTIMODE
MNS MASS NOTIFICATION SYSTEM
MTG MOUNTING
MTS MANUAL TRANSFER SWITCH
N, NEUT NEUTRAL
NAC NOTIFICATION APPLIANCE
CIRCUIT
NC NONCOMBUSTIBLE
N/C NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NIC NOT IN CONTRACT
NO NUMBER
N/O NORMALLY OPEN
NP NAME PLATE
NR NON-REVERSING
NTS NOT TO SCALE
OH OVERHEAD
OC ON CENTER, OVERCURRENT
P POLE
PCMS POWER CONTROL
MONITORING SYSTEM
PF POWER FACTOR
PH PHASE
PIR PASSIVE INFARED
PIV POST INDICATING VALVE
PKGD PACKAGED
POS POSITIVE
PRI PRIMARY
PTZ PAN-TILT-ZOOM
PVC POLYVINYL CHLORIDE
QY,QTY QUANTITY
RCP REFLECTED CEILING PLAN
REC RECEPTACLE
RECT RECTIFIER
RFI RADIO FREQUENCY
INTERFERENCE
RGS RIGID GALVANIZED STEEL
RMS ROOT MEAN SQUARE
RTU ROOF TOP UNIT
SEC SECONDARY
SM SINGLE MODE
SP SINGLE POLE, SMOKE
PARTITION
SQFT SQUARE FEET
SSRV SOLID STATE REDUCED
VOLTAGE
S/S START-STOP
S-T SHUNT-TRIP
STBY STANDBY
STD STANDARD
STP SHIELDED TWISTED PAIR
SUB SUB PANEL
SW SWITCH
SWBD SWITCHBOARD
TD TIME DELAY
TE TELECOMMUNICATIONS
ENCLOSURE
TELE TELEPHONE
TERM TERMINAL
TR TELECOMMUNICATIONS ROOM
TV TELEVISION
TVSS TRANSIENT VOLTAGE SURGE
SUPPRESSOR
TYP TYPICAL
UNIV UNIVERSAL
UL UNDERWRITERS
LABORATORIES, INC.
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER
SUPPLY
V VOLT, VOLTAGE
VA VOLT AMPERE
VAV VARIABLE AIR VOLUME
VM VOLTMETER
VP VOICE PANEL
VFD VARIABLE FREQUENCY DRIVE
W WATT
WH WATER HEATER
WM WATTMETER
WP WEATHERPROOF
X, XP EXPLOSION PROOF
XFMR TRANSFORMER
Y-D WYE-DELTA
Y WYE
Z IMPEDANCE
NOTE: LIST IS NOT ALL INCLUSIVE AND
DOES NOT INCLUDE, AMONG OTHER,
MDST MEASUREMENTS AND INDUSTRY
STANDARDS.
SYMBOL DESCRIPTION
POWER
EQUIPMENT NO.
AC
REMARKS
ELECTRICAL SYMBOLS
NUMERAL INDICATES CIRCUIT
NUMBER (TYP.)
DUPLEX RECEPTACLES, 120V, L5-20R
JUNCTION BOX
JUNCTION BOX WALL MOUNTED
NON-FUSED DISCONNECT SWITCH
COMBINATION STARTER
FLUSH MOUNTED PANELBOARD
SURFACE MOUNTED PANELBOARD
TRANSFORMER (DRY TYPE)
TRANSIENT VOLTAGE SURGE
SUPPRESSION UNIT
MOLDED CASE 3-POLE CIRCUIT BREAKER
LOWER CASE SUBSCRIPT ADJACENT
TO LIGHT FIXTURE INDICATES WHICH
LIGHT FIXTURES THE SWITCH
CONTROLS.
SYMBOL DESCRIPTION REMARKS
LIGHTING
SINGLE POLE SWITCH
DOUBLE POLE SWITCH
THREE WAY SWITCH
TIME OPERATED
LOW VOLTAGE DIMMER CONTROL
MISCELLANEOUS
30 = SWITCH AMP RATING / (15) =
FUSE AMP RATING
FUSED DISCONNECT SWITCH
1 = NEMA STARTER SIZE
225 = AMP TRIP RATING (AT)
225 = AMP FRAME RATING (AF)
VFD
VARIABLE FREQUENCY DRIVE
EARTH GROUND
MOTOR LOAD. NUMBER INDICATES MOTOR
SIZE = 5 HP
OCCUPANCY SENSOR CEILING MOUNTED
OCCUPANCY SENSOR WALL MOUNTED
LUMINAIRE MOUNTED OCCUPANCY SENSOR
THERMOSTAT
GROUND ROD
GROUND WELL
GROUNDING BUS
CALLOUTS
NOTE CALLOUT PER
FLOOR PLAN
SHEET NO.
FLOOR
PLAN/DETAIL NO.
EQUIPMENT TYPE
SEE
ABBREVIATIONS
MECHANICAL
EQUIPMENT
DISCONNECT/
CONTROLLER
FURNISHED WITH
EQUIPMENT
FUTURE
EQUIPMENT
WORKING SPACE
CLEARANCE
ELECTRICAL
EQUIP
SPECIAL RECEPTACLE, 208V, 30A UON
DUPLEX 20A RECEPTACLE, 120V GFCI
GFCI
30 = SWITCH AMP RATING
ONE OUTLET IMPRINTED
"CONTROLLED"
ENCLOSED CIRCUIT BREAKER
(250)
EQUIPMENT ON
CONCRETE PAD
FUTURE
WALL MOUNT UNLESS SHOWN
WITH CONCRETE PAD
SINGLE POLE SWITCH
MANUAL MOTOR STARTER WITH THERMAL
OVERLOAD PROTECTION
M
S
OS
S
D
OS
S a
S
S
S
T
OCCUPANCY SENSOR WALL MOUNTED W/
DIMMER CONTROL
S
OS
D
PHOTOSENSOR
PS
LUMINAIRE MOUNTED OCCUPANCY AND
DAYLIGHT DIMMING PHOTOSENSOR
OS
OP
LOW VOLTAGE SWITCH
S a
L
CABLE RUNWAY (BASKET TRAY)
MAIN CABLE HANGER ROUTE
CONDUIT/CABLE TURNING UP
CONDUIT STUB OUT
CONDUIT/CABLE CONCEALED
CONDUIT/CABLE RUN, EXPOSED ON FLOORS, CEILING AND WALLS
RACEWAYS AND WIRES
HOMERUN TO PANEL LA, CIRCUITS #1,3,5 & 2 COMMA (,) INDICATES SHARED
NEUTRAL AMPERSAND (&) INDICATES SEPARATE NEUTRAL
LA-1,3,5&2
GROUND FAULT CIRCUIT INTERRUPTER
GFI
BLANK FACE WIRING DEVICE
WITHOUT RECEPTACLE
SIMPLEX 20A RECEPTACLE, 120V
HOMERUN TO PANEL LA, POLYPHASE CIRCUITS #1,3,5 WITHOUT NEUTRAL
LA-1/3/5
OCCUPANCY AND DAYLIGHT DIMMING
SENSOR CEILING MOUNTED
OP
20A PLUG LOAD RELAY CONTROLLER
PL
17 SWITCH CIRCUIT WITHIN ROOM.
LOWER CASE SUBSCRIPT ADJACENT
INDICATES WHICH RECEPTACLE
CIRCUIT IS CONTROLLED IF MORE
THAN ONE PRESENT.
DIMMER CONTROL
D
EXTENT OF DAYLIT ZONE
20A DUPLEX RECEPTACLE BOTH OUTLETS IMPRINTED
"CONTROLLED"
EXTERIOR PHOTOCELL
PC
RECESSED DUPLEX 20A "CLOCK STYLE"
RECEPTACLE, 120V
DISCONNECT SWITCH 30 = AMP RATING
3P=NUMBER OF POLES
30A
3P
GROUND CABLE RUN
CONDUIT/CABLE RUN, AERIAL OVERHEAD
G
FUSED DISCONNECT SWITCH30A
3P
(NOTE: NOT ALL SYMBOLS ARE USED)
HH
SITE LIGHTING POLE (REFER TO PLAN
IN-GRADE HANDHOLE
ELECTRICAL
SYMBOLS AND
ABBREVIATIONS
A
LC-5,7
SL102
"A" INDICATES LUMINAIRE AND POLE
TYPE PER LUMINAIRE SCHEDULE.
"LC-5,7" INDICATES BRANCH CIRCUIT
NUMBER.
"SL102" INDICATES IDENTIFICATION
TAG TO BE APPLIED TO STREET
LIGHTING POLE
FOR LUMINAIRE HEAD CONFIGURATION)
ISSUED FOR
CONSTRUCTION
2025-03-21
STATE OF CAL IFORNIA
RE
GI
ST
ER
ED
PROFESSIONAL ENGINEER
E16755
ELECTRICAL
S I M
ON PA U L J E
F
F
09/30/202167
03/21/2025
1970 BROADWAY ST STE 760
OAKLAND, CA 94612
C
B
A
REUSE OF DOCUMENTS: THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE
PROPERTY OF JACOBS AND IS NOT TO BE USED, IN WHOLE OR IN PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF JACOBS.
Drawing Sheet Number:
554321 www.jacobs.com
©Jacobs Engineering Group Inc. 2025 ALL RIGHTS RESERVED
Project Number:
Paper Size: ARCH E1
Drawing Sheet Title:
Drawing Status:
Graphic Scale :
Revisions:
Project Client:
Seals:
E
4 Embarcadero Center, Suite 3800
San Francisco, CA 94105
P: 415-728-0850
W8Y13601
SANTA CRUZ METRO
809 W. Beach St, Watsonville
100% CONSTRUCTION
DOCUMENTS
Number Description Date
Rev.
Project :
PARKING LOT
IMPROVEMENTS
0 ISSUED FOR
CONSTRUCTION
2025-03-21
E-002
ELECTRICAL
GENERAL NOTES
AND SPECIFICATIONS
P L O
T T
E t a y l o r p p r o j e c t s s a n t a c r u z m e t r o p a r c s w d i p r o d w o r k i n g c a d a d w g
1. SOME LEGEND SYMBOLS MAY NOT BE USED - SEE DRAWINGS FOR APPLICABLE DEVICES.
2. THE LATEST EDITION OF THE OWNER'S AND/OR ARCHITECT'S GENERAL, SPECIAL AND SUPPLEMENTARY
CONDITIONS AS WELL AS SEPARATE SPECIFICATIONS OR PROJECT MANUALS ARE PART OF THESE
CONSTRUCTIONS DOCUMENTS.
3. THE SCOPE OF WORK SHALL INCLUDE LABOR, MATERIALS, EQUIPMENT, TOOLS AND SERVICES REQUIRED
FOR THIS COMPLETE INSTALLATION OF THE ELECTRICAL SYSTEMS AS INDICATED AND SPECIFIED.
4. ELECTRICAL DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW OFFSETS, BENDS, ELBOWS, JUNCTION
BOXES OR OTHER SPECIFIC ELEMENTS WHICH MAY BE REQUIRED FOR PROPER INSTALLATION OF WORK.
SIZE AND LOCATION OF EQUIPMENT AND WIRING ARE SHOWN TO SCALE WHERE POSSIBLE BUT MAY BE
DISTORTED FOR CLARITY OF THE DRAWINGS. FINAL LOCATIONS OF OUTLETS AND EQUIPMENT SHALL BE
SHOWN IN ENLARGED DETAILS OR AS APPROVED BY THE ARCHITECT OR HIS REPRESENTATIVE. IT IS
NOT WITHIN THE SCOPE OF DRAWINGS TO SHOW NECESSARY BENDS, OFFSETS, JUNCTION & PULL
BOXES, AND OBSTRUCTIONS. CONTRACTOR SHALL PROVIDE AN INSTALLATION TO MAINTAIN HEADROOM, AND KEEP OPENINGS AND PASSAGEWAYS CLEAR.
a. JUNCTION AND PULL BOXES SHALL BE LOCATED WHERE ACCESSIBLE ABOVE MAIN PATHS OF
TRAVEL WHEN POSSIBLE, AND IN LOCATIONS WHERE MINIMAL DISRUPTION WOULD OCCUR
SHOULD SERVICING BE REQUIRED.
6. ELECTRICAL MATERIAL & EQUIPMENT SHALL BE NEW AND IN PERFECT CONDITION WHEN INSTALLED.
EQUIPMENT SHALL BE UL LISTED, AND MATERIALS SHALL BE MANUFACTURED IN ACCORDANCE WITH
APPLICABLE STANDARDS OF ANSI, NEMA & NBFU. REPLACE DEFECTIVE OR DAMAGED MATERIALS, OR
REPAIR IN A MANNER APPROVED BY THE OWNER. ALL PRODUCTS SHALL BE LISTED AND LABELED AS
DEFINED IN NFPA 70, BY A QUALIFIED TESTING AGENCY, AND MARKED FOR INTENDED LOCATION AND
APPLICATION.
7. INSTALLATION OF ELECTRICAL WORK : UNLESS MORE STRINGENT REQUIREMENTS ARE SPECIFIED IN THE
CONTRACT DOCUMENTS OR MANUFACTURERS' WRITTEN INSTRUCTIONS, COMPLY WITH NFPA 70 AND
NECA NEIS 1 FOR INSTALLATION OF WORK
8. DEFINITIONS:
a. "FURNISH": SUPPLY AND DELIVER TO PROJECT SITE, READY FOR UNLOADING, UNPACKING, ASSEMBLY, INSTALLATION, AND SIMILAR OPERATIONS.
b. "INSTALL": OPERATIONS AT PROJECT SITE INCLUDING UNLOADING, TEMPORARILY STORING, UNPACKING, ASSEMBLING, ERECTING, PLACING, ANCHORING, APPLYING, WORKING TO
DIMENSION, FINISHING, CURING, PROTECTING, CLEANING, AND SIMILAR OPERATIONS.
c. "PROVIDE": FURNISH AND INSTALL, COMPLETE AND READY FOR THE INTENDED USE.
d. “SHALL”: USED TO QUALIFY AN ACTION WHICH IS MANDATORY.
8. PROVIDE SEISMIC SUPPORT DEVICES, RESTRAINTS AND APPURTENANCES INCLUDING HANGERS, ANCHORS, SLEEVES, INSERTS, SEALS, AND ASSOCIATED FASTENERS USED FOR MOUNTING RACEWAYS, EQUIPMENT AND OTHER ELECTRICAL ITEMS IN ACCORDANCE WITH STATE, COUNTY, CITY, AND LOCAL
CODES. SEISMIC RESTRAINTS AND ATTACHMENTS FOR ELECTRICAL EQUIPMENT AND SYSTEM
COMPONENTS SHALL BE PROVIDED IN ACCORDANCE WITH CBC AND SMACNA REQUIREMENTS.
9. REFER TO ARCHITECTURAL AND STRUCTURAL DRAWINGS FOR EXACT LOCATIONS, DIMENSIONS, AND/OR
RATINGS OF FIRE RATED SEPARATIONS, EXPANSION JOINTS, AND SEISMIC JOINTS.
10. KEEP CONDUITS AND OTHER OPENINGS CLOSED TO PREVENT ENTRY OF FOREIGN MATTER. COVER
FIXTURES, EQUIPMENT AND APPARATUS AND PROTECT AGAINST DIRT, WATER, CHEMICAL OR
MECHANICAL DAMAGE BEFORE AND DURING THE CONSTRUCTION PERIOD UNTIL FINAL ACCEPTANCE.
RESTORE TO ORIGINAL CONDITION ANY FIXTURES, APPARATUS OR EQUIPMENT DAMAGED PRIOR TO
FINAL ACCEPTANCE, INCLUDING RESTORATION OF DAMAGED SHOP COATS OF PAINT. DELIVER
EQUIPMENT AND STORE AT THE SITE, PROPERLY PACKED AND CRATED, UNTIL FINALLY INSTALLED.
11. ANY INCONSISTENCY OR DISCREPANCY IN THE DRAWINGS OR SPECIFICATIONS SHALL BE CLEARED WITH
THE ENGINEER PRIOR TO ROUGH IN OR INSTALLATION. IT IS FURTHER UNDERSTOOD THAT THE
CONTRACTOR HAS READ AND FULLY UNDERSTANDS THE DRAWINGS, SPECIFICATIONS AND RELATED
DOCUMENTS FOR THIS PROJECT PRIOR TO THE COMMENCEMENT OF WORK, INCLUDING DOCUMENTS OF
OTHER DIVISIONS WHICH MAY INTERFERE OR OTHERWISE AFFECT THE WORK OF THIS DIVISION. NO
CONSIDERATION WILL BE GRANTED BY REASON OF LACK OF FAMILIARITY ON THE PART OF THIS DIVISION
WITH THOSE DOCUMENTS.
12. THE CONTRACTOR SHALL UNDERTAKE THE WORK IN ITS ENTIRETY IN ACCORDANCE WITH ITS DESIGN
AND PURPOSE. WORK SHALL BE CARRIED OUT IN A PROFESSIONAL MANNER WITH MAXIMUM
EFFICIENCY, EXCELLENT WORKMANSHIP AND SHALL MEET THE REQUIREMENTS OF THE FOLLOWING:
a. CALIFORNIA CODE OF REGULATIONS:
TITLE 8 - INDUSTRIAL RELATIONS (ELEVATOR SAFETY ORDERS)
TITLE 19 - PUBLIC SAFETY
TITLE 22 - SOCIAL SECURITY
TITLE 24 - 2022 CALIFORNIA BUILDING STANDARDS CODE, (PARTS 1 THRU 9)
b. CALIFORNIA STATE AND LOCAL FIRE MARSHAL.
c. AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI).
d. INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS (IEEE).
e. INSTITUTE OF CABLE ENGINEERS ASSOCIATION (ICEA).
f. NATIONAL ELECTRICAL CONTRACTORS ASSOCIATION STANDARDS FOR CONSTRUCTION (NECA).
g. UNDERWRITERS LABORATORIES, INC. (UL).
h. INSTRUMENT SOCIETY OF AMERICA (ISA).
i. STATE INDUSTRIAL ACCIDENT COMMISSION.
j. OCCUPATIONAL SAFETY AND HEALTH APPEALS BOARD (OSHA).
k. NATIONAL ELECTRICAL TESTING ASSOCIATION (NETA)
13. ELECTRICAL CONTRACTOR SHALL BE LICENSED IN THE STATE OF CALIFORNIA AND WORKERS SHALL BE
CERTIFIED IN ACCORDANCE WITH THE DEPARTMENT OF INDUSTRIAL RELATIONS, DIVISION OF
APPRENTICESHIP STANDARDS AND CALIFORNIA LABOR CODE SECTION 3099.
14. CONTRACTOR SHALL CAREFULLY LAY OUT WORK IN ADVANCE TO AVOID UNNECESSARY CUTTING, CHANNELING, CHASING OR DRILLING OF FLOORS, WALLS, PARTITIONS, CEILINGS OR OTHER SURFACES.
STRUCTURAL MEMBERS SHALL NOT BE CUT OR DRILLED WITHOUT THE APPROVAL OF THE ENGINEER
AND OWNER. HOWEVER, WHERE SUCH WORK IS NECESSARY PROVIDE CUTTING, CORING AND PATCHING
OF THE CONSTRUCTION WORK WHICH MAY BE REQUIRED FOR THE PROPER INSTALLATION OF THE
ELECTRICAL WORK. PATCHING SHALL BE OF THE SAME MATERIALS, WORKMANSHIP AND FINISH, AND
SHALL ACCURATELY MATCH SURROUNDING WORK. AFTER COMPLETION OF WORK, CLEAN UP
RESULTANT DEBRIS AND REMOVE FROM SITE.
15. NUMBER OF UNGROUNDED “HOT” CONDUCTORSAND GROUNDED NEUTRAL CONDUCTORS IS AS IMPLIED
BY THE CIRCUIT NUMBERS ADJACENT TO THE EQUIPMENT, DEVICE, OR OUTLET UNLESS NOTED
OTHERWISE. HOME RUNS MAY BE COMBINED IN A SINGLE CONDUIT HOME RUN WITH UP TO (3) BRANCH
CIRCUITS IN A CONDUIT WHERE PERMITTED BY CODE. MAINTAIN CONDUIT FILL BELOW 40%, AND DERATE
CONDUCTOR AMPACITIES TO 80% PER TABLE 310-15(b)(2)(a), FOR 4 THROUGH 6 CONDUCTORS.
16. UNLESS MORE STRINGENT REQUIREMENTS ARE SPECIFIED IN THE CONTRACT DOCUMENTS,PROVIDE
DATA SUBMITTAL FOR EACH TYPE OF PRODUCT TO BE INCORPORATED INTO THE WORK.
a. INCLUDE DATA ON FEATURES, ACCESSORIES, AND FINISHES, CLEARLY IDENTIFYING PRODUCT
AND OPTIONS PROPOSED.
b. INCLUDE PHYSICAL DESCRIPTION AND DIMENSIONS.
c. LAMPS, INCLUDE LIFE, OUTPUT (LUMENS, CCT, AND CRI), AND ENERGY-EFFICIENCY DATA.
d. PHOTOMETRIC DATA AND ADJUSTMENT FACTORS BASED ON LABORATORY TESTS, COMPLYING
WITH IES LIGHTING MEASUREMENTS TESTING AND CALCULATION GUIDES, OF EACH LUMINAIRE
TYPE. THE ADJUSTMENT FACTORS SHALL BE FOR LAMPS AND ACCESSORIES IDENTICAL TO
THOSE INDICATED FOR THE LUMINAIRE AS APPLIED IN THIS PROJECT.
e. WIRING DIAGRAMS FOR POWER, CONTROL, AND SIGNAL WIRING.
17. CONTRACTOR SHALL PROVIDE LUGS FOR TERMINATING OVERSIZED CONDUCTORS, OR MAKE
PROVISIONS FOR TERMINATING OVERSIZED CONDUCTORS TO EQUIPMENT OR DEVICES WHICH LUGS DO
NOT ACCEPT OVERSIZED CONDUCTORS. SUBMIT TO PROJECT ENGINEER FOR APPROVAL APPLICABLE
VOLTAGE DROP CALCULATIONS PRIOR TO REDUCING CONDUCTOR SIZE.
18. CONTRACTOR SHALL PROVIDE ELECTRICAL FINAL CONNECTIONS TO ELECTRICAL EQUIPMENT AND
OUTLETS FOR A COMPLETE AND OPERABLE SYSTEM.
19. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VISIT THE JOBSITE PRIOR TO SUBMITTING
THE PROPOSAL AND TO BECOME FAMILIARI WITH EXISTING CONDITIONS.
20. PROVIDE WIRING DEVICES WITH SOURCE PANEL NAME AND CIRCUIT NUMBER ENGRAVED ON THE FRONT.
IDENTIFY CIRCUIT NUMBERS AT THE TERMINATION POINT OF ALL CONDUCTORS USING HEAT SHRINK
SLEEVES. IDENTIFY THE CIRCUIT NUMBERS PRESENT WITHIN JUNCTION BOXES WITH INDELIBLE INK ON
THE COVER.
21. ELECTRICAL EQUIPMENT SHALL BE FULLY RATED FOR THE MAXIMUM AVAILABLE SHORT CIRCUIT
CURRENT. REFER TO PANEL SCHEDULES AND SINGLE LINE DIAGRAM FOR AIC RATINGS OF EQUIPMENT.
22. CONTRACTOR SHALL DETERMINE ACTUAL LENGTHS OF FEEDERS AND BRANCH CIRCUITS BASED ON
ROUTING AND FIELD CONDITIONS.
23. PROVIDE WIRING FOR EQUIPMENT FURNISHED BY OTHER DIVISIONS SHOWN ON DRAWINGS. THE TERM
"WIRING" AS USED HEREIN, INCLUDES FURNISHING AND INSTALLING CONDUIT, WIRE, JUNCTION BOXES, STARTERS, DISCONNECTS, ETC., AND MAKING CONNECTIONS TO THE EQUIPMENT. BE RESPONSIBLE FOR
PROPER WIRING AND NECESSARY ELECTRICAL ADJUSTMENTS TO EQUIPMENT TO CONFORM TO
SPECIFIED REQUIREMENTS OF THE EQUIPMENT. CONTRACTOR SHOULD OBTAIN AND REVIEW DRAWINGS
OF OTHER DISCIPLINES TO ASCERTAIN THE REQUIREMENTS OF EQUIPMENT BEING FURNISHED AND/OR
INSTALLED BY THAT DIVISION PRIOR BID. COORDINATE EXACT DETAILS AND LOCATIONS PRIOR TO
ROUGH IN WITH OTHER DIVISIONS.
29. ELECTRICAL EQUIPMENT SHALL BE BONDED AND GROUNDED IN ACCORDANCE WITH STATE, COUNTY, CITY, AND LOCAL CODES. APPLICABLE CODES AND JURISDICTIONS. ALL FEEDERS AND BRANCH CIRCUIT
CONDUITS SHALL BE PROVIDED WITH AN INSULATED EQUIPMENT BONDING CONDUCTOR.
30. PROVIDE A COMPLETE GROUNDED RACEWAY SYSTEM FOR POWER, LIGHTING AND FOR ALL LOW
VOLTAGE SIGNAL CABLING SYSTEMS NOT SPECIFICALLY SHOWN ON THESE ELECTRICAL DRAWINGS, INCLUDE BUT NOT LIMITED TO, DEVICE BACK BOXES, CONDUITS WITH PULL LINE, COUPLINGS, PULL
BOXES, BONDING WIRES, AND SUPPORTS FOR THE FOLLOWING:
a. SECURITY
CONTRACTOR SHALL REFER TO DESIGN DRAWINGS FOR THE ABOVE REFERENCED SYSTEMS FOR
DETAILS.
31. EQUIPMENT ENCLOSURES, J-BOXES, GUTTERS ETC. INSTALLED OUTSIDE OF BUILDING AND SUBJECT TO
WEATHER SHALL BE WEATHER PROOF METALLIC NEMA 3R (PROVIDE NEMA 4X STAINLESS STEEL WHERE
INDICATED). GFI TYPE RECEPTACLES LOCATED ON EXTERIOR SHALL HAVE “IN USE” TYPE WEATHER
PROOF ENCLOSURES.
32. PRIOR TO INSTALLING CABLES IN BELOW GRADE CONDUITS AND DUCTS, PULL LEATHER-WASHER-TYPE
DUCT CLEANER, WITH GRADUATED WASHER SIZES, THROUGH FULL LENGTH OF DUCT UNTIL DUCT
CLEANER INDICATES THAT DUCT IS CLEAR OF DIRT AND DEBRIS. FOLLOW WITH RUBBER DUCT SWAB FOR
FINAL CLEANING AND TO ASSIST IN SPREADING LUBRICANT THROUGHOUT DUCTS.
33. VACUUM OUT ALL ACCUMULATED DEBRIS FROM ENCLOSURES, PANELBOARDS AND JUNCTION BOXES
UTILIZED FOR THE PROJECT PRIOR TO HANDOVER.
37. CLEAN INTERNAL SURFACES OF IN-GRADE HANDHOLES, REMOVE FOREIGN MATERIAL.
38. PROVIDE A FUSED DISCONNECT SPLICE CONNECTOR IN EACH LIGHT POLE, READILY ACCESSIBLE AND
LEVEL WITH THE HAND HOLE, INSTALLED IN EACH UNGROUNDED CONDUCTOR BETWEEN THE LINE AND
THE LUMINAIRE. THE CONNECTOR SHALL BE A WATER TIGHT BUSSMAN “HEY” FUSEHOLDER OR EQUAL
WITH 5 AMPERE KTK FUSE.
39. PROVIDE EACH LIGHTING POLE WITH A UNIQUE IDENTIFIER USING LABELING IDENTIFIED ON THE
DRAWINGS. EQUIPMENT IDENTIFICATION CHARACTERS SHALL BE 2-1/2 INCH, SERIES D LETTERING, EXCEPT ON WOOD POLES, THEY MUST BE 3-INCH LETTERING. THE CHARACTERS MUST BE ON
SELF-ADHESIVE REFLECTIVE UV STABILIZED LABELS AFFIXED TO METALLIC POLES. EXCEPT ON WOOD
POLES, THE CHARACTERS MUST BE EMBOSSED ON ALUMINUM LABELS. LABELS MUST HAVE A WHITE
BACK GROUND, ALL BLACK CAPITAL CHARACTERS, AND MUST EXTEND BEYOND THE CHARACTER BY A
MINIMUM OF 1/4 INCH. SUBMIT PRODUCT DATA AND SAMPLE FOR LABEL. VERIFY EXACT REQUIREMENTS
WITH OWNER'S REPRESENTATIVE PRIOR TO MANUFACTURE OF LABELS.
40. ERECT ALL LIGHTING POLES STRAIGHT AND PLUMB ON CONCRETE FOUNDATIONS, INSTALL VENDOR'S
BOLT/NUT COVERS OVER ANCHOR BOLTS AND PROVIDE GROUT,WITH DRAIN PIPE, BETWEEN
FOUNDATION TOP AND LIGHTING POLE BASE PLATE . ALL PERIMETER LIGHTING POLE LUMINAIRES
SHALL FACE INWARDS AWAY FROM THE PROPERTY LINE, APPROXIMATELY PERPINDICULAR TO THE
PROPERTY LINE. PROVIDE HOUSE SIDE BACKLIGHT SHIELDING TO LIMIT LIGHTING SPILL OFF THE
PROPERTY.
41. PROVIDE ALL TRENCHING, CONDUIT BEDDING MATERIAL AND NATIVE MATERIAL BACKFILL FOR ALL
BURIED RACEWAYS. PROVIDE DETECTABLE WARNING MARKER TAPE BURIED ABOVE CONDUIT.
GENERAL NOTES
SECTION 260519 - LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND
CABLES
600V CONDUCTOR MATERIAL AND APPLICATIONS
A. BRANCH CIRCUITS: COPPER. SOLID FOR NO. 12 AWG AND SMALLER;
STRANDED FOR NO. 10 AWG AND LARGER.
B. EXPOSED BRANCH CIRCUITS: TYPE THHN/THWN-2 OR XHHW-2, SINGLE
CONDUCTORS IN RACEWAY.
C. BRANCH CIRCUITS CONCEALED IN CONCRETE, BELOW SLABS-ON-GRADE,
AND UNDERGROUND: TYPE THHN/THWN-2 OR XHHW-2 SINGLE
CONDUCTORS IN RACEWAY.
D. BRANCH CIRCUITS CONCEALED IN LIGHTING POLE: TYPE THHN/THWN-2
OR XHHW-2 SINGLE CONDUCTORS IN RACEWAY AND TYPE UF-B CABLE AS
INDICATED.
E. FUSED DISCONNECT SPLICE CONNECTOR: WATER TIGHT BUSSMAN “HEY”
FUSEHOLDER OR EQUAL WITH 5 AMPERE KTK FUSE.
SECTION 260526 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
EQUIPMENT GROUNDING
A. INSTALL INSULATED EQUIPMENT GROUNDING CONDUCTORS WITH ALL
BRANCH CIRCUITS AND FEEDERS.
POLES SUPPORTING OUTDOOR LIGHTING FIXTURES
A. INSTALL GROUNDING ELECTRODE AND A GROUNDING ELECTRODE
CONDUCTOR IN ADDITION TO EQUIPMENT GROUNDING CONDUCTOR
INSTALLED WITH BRANCH-CIRCUIT CONDUCTORS.
CONNECTIONS
A. USE UL APPROVED HIGH-PRESS GROUND CONNECTORS
(UNDERGROUND), OR UL APPROVED MECHANICAL GROUND CONNECTORS
(ACCESSIBLE LOCATIONS).
SECTION 26500 - LUMINAIRES
LUMINAIRES AND POLES
A. PRODUCT AND OPERATION AS INDICATED ON THE DRAWINGS.
POLE INSTALLATION
A. EXAMINE POLES, LUMINAIRE-MOUNTING DEVICES, LOWERING DEVICES,
AND POLE ACCESSORIES BEFORE INSTALLATION. COMPONENTS THAT
ARE SCRATCHED, DENTED, MARRED, WET, MOISTURE DAMAGED, OR
VISIBLY DAMAGED ARE CONSIDERED DEFECTIVE.
B. ALIGNMENT: ALIGN POLE FOUNDATIONS AND POLES FOR OPTIMUM
DIRECTIONAL ALIGNMENT OF LUMINAIRES AND THEIR MOUNTING
PROVISIONS ON POLE. ALIGN HANDHOLE TO BE ACCESSIBLE.
C. CONCRETE POLE FOUNDATIONS: SET ANCHOR BOLTS IN ACCORDANCE
WITH ANCHOR-BOLT TEMPLATES FURNISHED BY POLE MANUFACTURER.
D. MOUNT POLE WITH LEVELING NUTS AND TIGHTEN TOP NUTS TO TORQUE
LEVEL IN ACCORDANCE WITH POLE MANUFACTURER'S WRITTEN
INSTRUCTIONS.
E. GROUT VOID BETWEEN POLE BASE AND FOUNDATION. USE NONSHRINK
OR EXPANDING CONCRETE GROUT FIRMLY PACKED TO FILL SPACE.
F. INSTALL BASE COVERS UNLESS OTHERWISE INDICATED.
G. USE A SHORT PIECE OF 1/2 INCH DIAMETER PIPE TO MAKE A DRAIN HOLE
THROUGH GROUT. ARRANGE TO DRAIN CONDENSATION FROM INTERIOR
OF POLE.
H. RAISE AND SET POLE USING WEB FABRIC SLINGS (NOT CHAIN OR CABLE)
AT LOCATIONS INDICATED BY MANUFACTURER.
SECTION 260529 - HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS
SUPPORT, ANCHORAGE, AND ATTACHMENT COMPONENTS
A. MATERIAL FOR SLOTTED STEEL CHANNEL, FITTINGS, CONDUIT SUPPORTS
AND ACCESSORIES: STEEL, HOT-DIP GALVANIZED AFTER FABRICATION
AND APPLIED ACCORDING TO MFMA-4.
B. PROVIDE SUPPORTS IN ACCORDANCE WITH SMACNA.
SECTION 260533 - RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS
RACEWAY APPLICATION
A. OUTDOORS: APPLY RACEWAY PRODUCTS AS BELOW UNLESS OTHERWISE
INDICATED:
1.EXPOSED CONDUIT: STEEL GRC.
2.UNDERGROUND CONDUIT: RNC, TYPE EPC-40-PVC, DIRECT BURIED. USE
40 MIL PVC COATED GRC WHERE INDICATED.
3.SECURITY PATHWAY (WHERE INDICATED): FLEXIBLE NON METALLIC
LIQUID TIGHT ELECTRICAL CONDUIT
4.CONNECTION TO VIBRATING EQUIPMENT (INCLUDING TRANSFORMERS
AND HYDRAULIC, PNEUMATIC, ELECTRIC SOLENOID, OR MOTOR-DRIVEN
EQUIPMENT): LFMC.
5.BOXES AND ENCLOSURES, ABOVEGROUND: NEMA 250, TYPE 4. SHEET
METAL OUTLET AND DEVICE BOXES: COMPLY WITH NEMA OS 1 AND
UL 514A. CAST-METAL OUTLET AND DEVICE BOXES: COMPLY WITH
NEMA FB 1, FERROUS ALLOY OR ALUMINUM, TYPE FD, WITH GASKETED
COVER.
B. RACEWAYS BELOW GRADE:
1.CHANGE FROM PVC TO PVC COATED STEEL GRC BEFORE RISING ABOVE
FLOOR/GRADE.
2.ARRANGE STUB-UPS SO CURVED PORTIONS OF BENDS ARE NOT VISIBLE
ABOVE FINISHED SLAB/GRADE.
3.MINIMUM TRADE SIZE 1" DIAMETER.
SECTION 260553 - IDENTIFICATION FOR ELECTRICAL SYSTEMS
UNDERGROUND WARNING TAPE
A. FOIL-BACKED DETECTABLE TYPE TAPE: 3 INCHES WIDE, WITH MINIMUM
THICKNESS OF 5 MIL .
B. TYPE OF SERVICE, CONTINUOUSLY REPEATED OVER FULL LENGTH OF
TAPE "CAUTION BURIED ELECTRIC LINE BELOW” BLACK TEXT ON RED
BACKGROUND.
C. PRINTING ON TAPE SHALL BE PERMANENT AND SHALL NOT BE DAMAGED
BY BURIAL OPERATIONS OR DEGRADE WHEN EXPOSED TO ACIDS,
ALKALIS, AND OTHER DESTRUCTIVE SUBSTANCES COMMONLY FOUND IN
SOILS.
MARKERS FOR CONDUCTORS AND CABLES
A. USE WRAP-AROUND SELF-ADHESIVE VINYL CLOTH, WRAP-AROUND
SELF-ADHESIVE VINYL SELF-LAMINATING, HEAT-SHRINK SLEEVE, PLASTIC
SLEEVE, PLASTIC CLIP-ON, OR VINYL SPLIT SLEEVE TYPE MARKERS
SUITABLE FOR THE CONDUCTOR OR CABLE TO BE IDENTIFIED.
B. LEGEND: POWER SOURCE AND CIRCUIT NUMBER OR OTHER
DESIGNATION INDICATED.
C. TEXT: USE FACTORY PRE-PRINTED OR MACHINE-PRINTED TEXT, ALL
CAPITALIZED.
D. MINIMUM TEXT HEIGHT: 1/8 INCH.
E. COLOR: BLACK TEXT ON WHITE BACKGROUND
MARKERS FOR RECEPTACLES, BOXES AND EQUIPMENT ENCLOSURES.
A. SELF-ADHESIVE VINYL LABELS, PREPRINTED, FLEXIBLE LABEL LAMINATED
WITH A CLEAR, WEATHER- AND CHEMICAL-RESISTANT, UV-STABILIZED
COATING.
B. INSTALL CIRCUIT LABELING FOR RECEPTACLES UNDER WEATHERPROOF
HINGED COVER.
SECTION 260923 - LIGHTING CONTROL DEVICES
ELECTRONIC TIME SWITCHES
A. SOLID STATE, PROGRAMMABLE, WITH ALPHANUMERIC DISPLAY;
COMPLYING WITH UL 917. MARKED FOR INTENDED LOCATION AND
APPLICATION.
B. PRODUCT AND OPERATION AS INDICATED ON THE DRAWINGS.
SECTION 262416 - PANELBOARD/CIRCUIT BREAKERS
A. THERMAL-MAGNETIC CIRCUIT BREAKERS: CIRCUIT BREAKERS WITH TRIP
RATINGS 100 AMP AND SMALLER INVERSE TIME-CURRENT ELEMENT FOR
LOW-LEVEL OVERLOADS, AND INSTANTANEOUS MAGNETIC TRIP ELEMENT
FOR SHORT CIRCUITS. MINIMUM 75 DEG C RATED TERMINALS.
SECTION 270528 - PATHWAYS FOR COMMUNICATIONS/SECURITY/ACCESS
CONTROL SYSTEMS
A. CONFORM TO SECTION 260533 AND WITH THE FOLLOWING
REQUIREMENTS.
B. CONFORM TO INSTALLATION INSTRUCTIONS OF TIA/EIA-569-A AND BICSI
TDMM FOR PATHWAYS.
C. WHEN ROUTING CONDUIT, MAINTAIN A GRADUATED BEND RADIUS TO
MAINTAIN CONDUIT CAPACITY. TYPICALLY A MINIMUM OF SIX TIMES THE
CONDUIT DIAMETER. MAXIMUM THREE 90 DEGREE BENDS BETWEEN
PULLING POINTS.
SPECIFICATIONS
STATE OF CAL IFORNIA
RE
GI
ST
ER
ED
PROFESSIONAL ENGINEER
E16755
ELECTRICAL
S I M
ON PA U L J E
F
F
09/30/202167
03/21/2025
C
B
A
REUSE OF DOCUMENTS: THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE
PROPERTY OF JACOBS AND IS NOT TO BE USED, IN WHOLE OR IN PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF JACOBS.
Drawing Sheet Number:
554321 www.jacobs.com
©Jacobs Engineering Group Inc. 2025 ALL RIGHTS RESERVED
Project Number:
Paper Size: ARCH E1
Drawing Sheet Title:
Drawing Status:
Graphic Scale :
Revisions:
Project Client:
Seals:
E
4 Embarcadero Center, Suite 3800
San Francisco, CA 94105
P: 415-728-0850
W8Y13601
SANTA CRUZ METRO
809 W. Beach St, Watsonville
100% CONSTRUCTION
DOCUMENTS
Number Description Date
Rev.
Project :
PARKING LOT
IMPROVEMENTS
0 ISSUED FOR
CONSTRUCTION
2025-03-21
E-010
ELECTRICAL
ENERGY
COMPLIANCE
CALCULATIONS
P L O
T T y l p r o j e c t s s a n t a c r u z m e t r o p a r c s w d i p r o d w o r k i n g c a d a d w g
STATE OF CAL IFORNIA
RE
GI
ST
ER
ED
PROFESSIONAL ENGINEER
E16755
ELECTRICAL
S I M
ON PA U L J E
F
F
09/30/202167
03/21/2025
C
B
A
REUSE OF DOCUMENTS: THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE
PROPERTY OF JACOBS AND IS NOT TO BE USED, IN WHOLE OR IN PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF JACOBS.
Drawing Sheet Number:
554321 www.jacobs.com
©Jacobs Engineering Group Inc. 2025 ALL RIGHTS RESERVED
Project Number:
Paper Size: ARCH E1
Drawing Sheet Title:
Drawing Status:
Graphic Scale :
Revisions:
Project Client:
Seals:
E
4 Embarcadero Center, Suite 3800
San Francisco, CA 94105
P: 415-728-0850
W8Y13601
SANTA CRUZ METRO
809 W. Beach St, Watsonville
100% CONSTRUCTION
DOCUMENTS
Number Description Date
Rev.
Project :
PARKING LOT
IMPROVEMENTS
0 ISSUED FOR
CONSTRUCTION
2025-03-21
E-011
ELECTRICAL
ENERGY
COMPLIANCE
CALCULATIONS
P L O
T T y l p r o j e c t s s a n t a c r u z m e t r o p a r c s w d i p r o d w o r k i n g c a d a d w g
STATE OF CAL IFORNIA
RE
GI
ST
ER
ED
PROFESSIONAL ENGINEER
E16755
ELECTRICAL
S I M
ON PA U L J E
F
F
09/30/202167
03/21/2025
C
B
A
REUSE OF DOCUMENTS: THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE
PROPERTY OF JACOBS AND IS NOT TO BE USED, IN WHOLE OR IN PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF JACOBS.
Drawing Sheet Number:
554321 www.jacobs.com
©Jacobs Engineering Group Inc. 2025 ALL RIGHTS RESERVED
Project Number:
Paper Size: ARCH E1
Drawing Sheet Title:
Drawing Status:
Graphic Scale :
Revisions:
Project Client:
Seals:
E
4 Embarcadero Center, Suite 3800
San Francisco, CA 94105
P: 415-728-0850
W8Y13601
SANTA CRUZ METRO
809 W. Beach St, Watsonville
100% CONSTRUCTION
DOCUMENTS
Number Description Date
Rev.
Project :
PARKING LOT
IMPROVEMENTS
0 ISSUED FOR
CONSTRUCTION
2025-03-21
E-100
ELECTRICAL
SITE PLAN -
PHOTOMETRICS
A
A
A
A
A
A
A
A
A
B
B
A
A
A
A
STATE OF CAL IFORNIA
RE
GI
ST
ER
ED
PROFESSIONAL ENGINEER
E16755
ELECTRICAL
S I M
ON PA U L J E
F
F
09/30/202167
03/21/2025
C
B
A
REUSE OF DOCUMENTS: THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE
PROPERTY OF JACOBS AND IS NOT TO BE USED, IN WHOLE OR IN PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF JACOBS.
Drawing Sheet Number:
554321 www.jacobs.com
©Jacobs Engineering Group Inc. 2025 ALL RIGHTS RESERVED
Project Number:
Paper Size: ARCH E1
Drawing Sheet Title:
Drawing Status:
Graphic Scale :
Revisions:
Project Client:
Seals:
E
4 Embarcadero Center, Suite 3800
San Francisco, CA 94105
P: 415-728-0850
W8Y13601
SANTA CRUZ METRO
809 W. Beach St, Watsonville
100% CONSTRUCTION
DOCUMENTS
Number Description Date
Rev.
Project :
PARKING LOT
IMPROVEMENTS
1. REMOVE AND DISPOSE OF EXISTING LIGHTING POLES,
LUMINAIRES AND WIRING BACK TO SOURCE LOAD CENTER
PANEL. REMOVE EXISTING LIGHTING CONTROLS SYSTEM.
REFER TO DRAWING PD-1 FOR POLE LOCATIONS.
2. FIELD VERIFY AND COORDINATE FINAL LOCATION OF
FOUNDATIONS FOR LIGHTING POLES WITH ALL
SUBSURFACE AND AT GRADE UTILITIES AND ALL SITE
FEATURES AND IMPROVEMENTS. VERIFY BY POTHOLING
PRIOR TO EXCAVATION.
3. UNDERGROUND CONDUITS SHALL BE MINIMUM 1" UNLESS
NOTED OTHERWISE.
4. LIGHTING POWER CONDUITS SHALL TURN UP INTO
LIGHTING POLE CONCRETE BASES AND STUB ABOVE TOP
OF BASE INSIDE POLE. CONDUCTORS SHALL BE SPLICED
AT FIRST ACCESSIBLE HANDHOLE LOCATION IN POLE TO
#12 AWG TYPE UF -B (12-2) CABLE FOR CONNECTION TO
LUMINAIRE AT TOP OF POLE. VERIFY WITH VENDOR
SUBMITTALS.
5. ETHERNET POE SECURITY CONDUITS SHALL TURN UP INTO
LIGHTING POLE CONCRETE BASES AND STUB ABOVE TOP
OF BASE INSIDE POLE AT MID-POINT BETWEEN FIRST AND
SECOND ACCESSIBLE HANDHOLE TO MAINTAIN
SEPARATION BETWEEN POE CABLE AND SINGLE
INSULATED POWER CONDUCTORS. ETHERNET POE CABLE
TO BE INSTALLED BY SECURITY VENDOR.
6. PROVIDE IN-LINE FUSES AND LABELING OF POLES AS
IDENTIFIED ON SHEET E-002.
7. PROVIDE ALL LIGHTING POLES WITH CONCRETE
FOUNDATION THAT EXTENDS 5'-0" ABOVE FINISHED GRADE.
PROVIDE SMOOTH FINISHED GROUT BETWEEN POLE BASE
AND TOP OF FOUNDATION. PAINT ALL VISIBLE PARTS OF
LIGHTING POLE FOUNDATIONS "SAFETY YELLOW".
8. AT PERIMETER FENCELINE, ROUTE BELOW GRADE
CONDUITS AND PLACE CENTER OF LIGHTING POLES
TYPICALLY WITHIN 2 TO 5 FEET OF THE FENCE LINE.
ROUTING AND LOCATIONS SHOWN IS DIAGRAMMATIC.
9. MEET, SCHEDULE AND COORDINATE WORK RELATED TO
SECURITY INSTALLATION WITH OWNER'S SECURITY
VENDOR, INCLUDING DRILLING OF LIGHTING POLES FOR
CAMERA CABLING, ENCLOSURE MOUNTING AND POWER
CONNECTION AND RACEWAY INSTALLATION.
GENERAL NOTES
0 ISSUED FOR
CONSTRUCTION
2025-03-21
E-101
ROUTE LIGHTING CIRCUIT CONDUCTORS VIA AUTOMATIC
TIME CLOCK TO (E) PANEL "LC". REFER TO DETAIL ON
SHEET E-701 FOR CONTROLS DIAGRAM. PROVIDE STEEL
CHANNEL SUPPORT, FIELD VERIFY MOUNTING LOCATION.
PROVIDE H-20 RATED CONCRETE HANDHOLE "TRAFFIC
BOX" FLUSH WITH GRADE, NOMINAL 10" WIDTH X 17" LONG
X 12" DEEP INTERNAL DIMENSIONS, WITH GALVANIZED
STEEL CHECKER PLATE H-20 BOLT DOWN COVER. CHRISTY
B1017 OR EQUAL. IDENTIFY LID WITH "SECURITY" SERVICE.
INSTALL IN ACCORDANCE WITH MANUFACTURER'S
INSTRUCTIONS AND DETAIL ON DRAWING E-701.
FIELD VERIFY LOCATION OF (E) LOAD CENTER AND (E)
BRANCH CIRCUITS ORIGINATING AT LOAD CENTER.
PROVIDE TYPED CIRCUIT CHART DOCUMENTING (E)
CIRCUITS TO REMAIN AND ALL PROPOSED CIRCUITS.
PROVIDE CIRCUIT NUMBER IDENTIFICATION AT THE
EXISTING AND PROPOSED LOAD EQUIPMENT AND
RECEPTACLES.
WEATHERPROOF SECURITY ENCLOSURE "SEC1" .
ENCLOSURE SHALL BE PROVIDED (SUPPLIED AND
INSTALLED) BY CONTRACTOR FOR USE BY SECURITY
VENDOR. PROVIDE STEEL CHANNEL FRAME. ENCLOSURE
SHALL BE NEMA 3R, SIDE HINGED DOOR WITH FULL PIANO
HINGE, PADLOCKABLE WING LATCH WITH REAR MOUNTED
BACKPLATE, MODEL "M1-31" MANUFACTURED BY SUNWIZE.
APPROXIMATE DIMENSIONS 16"W X 20.75"H X 9.4"D.
TERMINATE CONDUITS FOR SECURITY AT A
WEATHERPROOF WIREWAY OR JUNCTION BOX MOUNTED
BELOW SECURITY ENCLOSURE. PROVIDE CONDUITS
BETWEEN WIREWAY/JUNCTION BOX AND SECURITY
ENCLOSURE KNOCK-OUTS. FIELD COORDINATE FINAL
POWER CONNECTION WITH SECURITY VENDOR.
PROVIDE 1" CONDUIT BELOW GRADE FOR POE CABLING BY
SECURITY VENDOR FROM PROPOSED SECURITY
ENCLOSURE "SEC1" TO SERVE CAMERAS ON LIGHTING
POLES. PROVIDE CONDUITS WITH PULL STRINGS FOR USE
BY SECURITY VENDOR.
AREA FOR FUTURE PG&E TRANSFORMER AND CUSTOMER
SWITCHBOARD, APPROX 20'-0" X 15'-0". DO NOT ROUTE
BELOW GRADE CONDUITS IN THIS AREA. STRIPE AREA
WITH MARKING PAINT FOR TEMPORARY IDENTIFICATION
OF KEEP-OUT ZONE AT COMPLETION OF PROJECT.
PROTECT AND RETAIN EXSITING LOAD CENTER "LC"
BRANCH CIRCUIT PANEL, OVERHEAD SERVICE ENTRANCE
CONDUCTORS, SERVICE POLE AND GUYING SYSTEM,
MOUNTING BACKBOARD/RACK, PULLCAN, METER,
GROUNDING, ASSOCIATED RACEWAYS, RECEPTACLES
AND BRANCH CIRCUITS MOUNTED ADJACENT TO LOAD
CENTER.
KEYED NOTES
ELECTRICAL
SITE PLAN
H
H
H
H
C
A
M
C
A
M
H
H
HH
C
A
M
C
A
M
C
A
M
(E)PNL "LC"
A
LC-9,11
SL101
A
LC-5,7
SL102
A
LC-5,7
SL103
A
LC-5,7
SL104
A
LC-5,7
SL105
A
LC-5,7
SL106
A
LC-5,7
SL107
A
LC-9,11
SL107
A
LC-9,11
SL108
A
LC-9,11
SL109
A
LC-9,11
SL110
A
LC-9,11
SL111
A
LC-9,11
SL112
B
LC-13,15
SL113
B
LC-13,15
SL114
AUTOMATIC TIME CLOCK
TYP.
SECURITY
ENCLOSURE
LC-8
LC-14
TYP.
OUTLINE OF FUTURE MOBILE
FUELING TRUCK AREA. SHOWN
PROVIDE MINIMUM 24" COVER
FOR REFERENCE
FENCELINE
PVC COATED RIGID STEEL
SL106 AND SL107 TO BE
CONDUIT BETWEEN POLES
CONDUIT ROUTING SHOWN
IS DIAGRAMMATIC.
REFER TO GENERAL NOTE 8
STATE OF CAL IFORNIA
RE
GI
ST
ER
ED
PROFESSIONAL ENGINEER
E16755
ELECTRICAL
S I M
ON PA U L J E
F
F
09/30/202167
03/21/2025
C
B
A
REUSE OF DOCUMENTS: THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE
PROPERTY OF JACOBS AND IS NOT TO BE USED, IN WHOLE OR IN PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF JACOBS.
Drawing Sheet Number:
554321 www.jacobs.com
©Jacobs Engineering Group Inc. 2025 ALL RIGHTS RESERVED
Project Number:
Paper Size: ARCH E1
Drawing Sheet Title:
Drawing Status:
Graphic Scale :
Revisions:
Project Client:
Seals:
E
4 Embarcadero Center, Suite 3800
San Francisco, CA 94105
P: 415-728-0850
W8Y13601
SANTA CRUZ METRO
809 W. Beach St, Watsonville
100% CONSTRUCTION
DOCUMENTS
Number Description Date
Rev.
Project :
PARKING LOT
IMPROVEMENTS
0 ISSUED FOR
CONSTRUCTION
2025-03-21
E-501
ELECTRICAL
SCHEDULES
LUMINAIRE SCHEDULE
SYMBOL
DESIG MANUFACTURER MODEL DESCRIPTION
TOTAL
INPUT
WATTS
VOLTS
REMARKS
MTG
S = SURFACE
R = RECESSED
P = POLE
PD = PENDANT
FL = FLUORESCENT
IN = INCANDESCENT
LAMP
WATTS TYP
QTY
MH = METAL HALIDE
LED = LIGHT EMITTING DIODE
A SIGNIFY
LUMINAIRE:
GARDCO GULLWING
POLE: GARDCO TRA
LUMINAIRE: TWO PER POLE
GL18-FAWS-**50LA-4835-NW-UNV-BRP-PC-IS-RPA2
** ROTATED OPTICS ONE 4-90
AND ONE 4-270
POLE:
TRA-CA-8/5-35-D2-DT2-BZ-VDA-AHH
LED POLE MOUNTED WET LOCATION LUMINAIRES, TWO LUMINAIRES ARRANGED AT 180 DEGREE SPACING WITH ROTATED
OPTICS TO ACHIEVE FORWARD THROW WITH TYPE 4 DISTRIBUTION, AND INTERNAL SHIELD TO LIMIT OFFSITE BACKLIGHT
SPILL. INCLUDE FIELD ADJUSTABLE WATTAGE SELECTOR TO LIMIT INDIVIDUAL LUMINAIRE OUTPUT TO 6,200 LUMENS MAX.
4000K CCT, 70 MIN. CRI. EQUIP EACH LUMINAIRE WITH PHOTOCELL AND SURGE PROTECTOR. PROVIDE ROUND POLE ADAPTER
FOR LUMINAIRE ATTACHMENT. LUMINAIRE TO BE ONE-PIECE DIE CAST ALUMINUM HOUSING WITH ELECTROSTATICALLY
APPLIED, THERMALLY CURED TEXTURED POLESTER POWDERCOAT FINISH. FINISH TO BE BRONZE TO MATCH POLE. LUMINAIRE
TO BE UL LISTED WITH WET LOCATION LABEL.
ROUND ALUMINUM TAPERED 35'-0" POLE WITH CAST ALUMINUM BASE. DRILL FOR TWO WAY LUMINAIRE MOUNTING AT 180°.
PROVIDE ONE HANDHOLE AT STANDARD +20" ABOVE BASE AND ADDITIONAL HANDHOLE AT APPROXIMATELY +36" ABOVE BASE.
INCLUDE POST TOP CAP, VIBRATION DAMPENER AND ACCESSIBLE GROUND LUG AT HANDHOLE. HANDHOLES TO BE COMPLETE
WITH ALUMINUM ACCESS DOOR COVER AND WEATHERPROOF GASKET. PROVIDE BASE COVER/NUT COVERS, ANCHOR BOLTS
AND TEMPLATE. FINISH WITH ELECTROSTATICALLY APPLIED, THERMALLY CURED POLYESTER POWDERCOAT. FINISH TO BE
BRONZE.
B
P105 W
PER LUMINAIRE
315W PER POLE
ASSEMBLY
-- LED
PROVIDE WITH 35'-0" POLE MOUNTED ON
CONCRETE BASE, 5'-0" AFG.
VERIFY ALL PART NUMBERS WITH VENDOR
PRIOR TO ORDERING EQUIPMENT.
PHOTOCELL, ADDITIONAL HANDHOLE
SIGNIFY
LUMINAIRE:
GARDCO GULLWING
POLE: GARDCO TRA
LUMINAIRE: THREE PER POLE
GL18-4-105LA-4870-NW-UNV-BRP-PC-RPA2
POLE:
TRA-CA-8/5-35-D3@120-DT2-BZ-VDA-AHH
LED POLE MOUNTED WET LOCATION LUMINAIRES, THREE LUMINAIRES ARRANGED AT 120 DEGREE SPACING WITH FORWARD
THROW TYPE 4 DISTRIBUTION. INDIVIDUAL LUMINAIRE OUTPUT 12802 LUMENS 4000K CCT, 70 MIN. CRI. EQUIP EACH LUMINAIRE
WITH PHOTOCELL AND SURGE PROTECTOR. PROVIDE ROUND POLE ADAPTERS FOR LUMINAIRE ATTACHMENT. LUMINAIRES TO
BE ONE-PIECE DIE CAST ALUMINUM HOUSING WITH ELECTROSTATICALLY APPLIED, THERMALLY CURED TEXTURED POLESTER
POWDERCOAT FINISH. FINISH TO BE BRONZE TO MATCH POLE. LUMINAIRE TO BE UL LISTED WITH WET LOCATION LABEL.
ROUND ALUMINUM TAPERED 35'-0" POLE WITH CAST ALUMINUM BASE. DRILL FOR THREE WAY LUMINAIRE MOUNTING AT 120°.
PROVIDE ONE HANDHOLE AT STANDARD +20" ABOVE BASE AND ADDITIONAL HANDHOLE AT APPROXIMATELY +36" ABOVE BASE.
INCLUDE POST TOP CAP, VIBRATION DAMPENER AND ACCESSIBLE GROUND LUG AT HANDHOLE. HANDHOLES TO BE COMPLETE
WITH ALUMINUM ACCESS DOOR COVER AND WEATHERPROOF GASKET. PROVIDE BASE COVER/NUT COVERS, ANCHOR BOLTS
AND TEMPLATE. FINISH WITH ELECTROSTATICALLY APPLIED, THERMALLY CURED POLYESTER POWDERCOAT. FINISH TO BE
BRONZE.
P
UNIVERSAL
120-277V
50 W MAX.
PER LUMINAIRE
100 W PER POLE
ASSEMBLY
-- LED
PROVIDE WITH 35'-0" POLE MOUNTED ON
CONCRETE BASE, 5'-0" AFG.
VERIFY ALL PART NUMBERS WITH VENDOR
PRIOR TO ORDERING EQUIPMENT.
ROTATED OPTICS, FIELD ADJUSTABLE
WATTAGE SELECTOR, PHOTOCELL,
ADDITIONAL HANDHOLE
REFER TO DETAIL 3/E-701
NOTE: ALL NEW CIRCUIT BREAKERS SHALL MATCH MAKE, MODEL AND AIC RATING OF EXISTING
PROVIDE CIRCUIT BREAKER AND WIRING
PROVIDE CIRCUIT BREAKER AND WIRING
PROVIDE WIRING TO (E) CIRCUIT BREAKER
PROVIDE WIRING TO (E) CIRCUIT BREAKER
PROVIDE CIRCUIT BREAKER AND WIRING
STATE OF CAL IFORNIA
RE
GI
ST
ER
ED
PROFESSIONAL ENGINEER
E16755
ELECTRICAL
S I M
ON PA U L J E
F
F
09/30/202167
03/21/2025
C
B
A
REUSE OF DOCUMENTS: THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE
PROPERTY OF JACOBS AND IS NOT TO BE USED, IN WHOLE OR IN PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF JACOBS.
Drawing Sheet Number:
554321 www.jacobs.com
©Jacobs Engineering Group Inc. 2025 ALL RIGHTS RESERVED
Project Number:
Paper Size: ARCH E1
Drawing Sheet Title:
Drawing Status:
Graphic Scale :
Revisions:
Project Client:
Seals:
E
4 Embarcadero Center, Suite 3800
San Francisco, CA 94105
P: 415-728-0850
W8Y13601
SANTA CRUZ METRO
809 W. Beach St, Watsonville
100% CONSTRUCTION
DOCUMENTS
Number Description Date
Rev.
Project :
PARKING LOT
IMPROVEMENTS
0 ISSUED FOR
CONSTRUCTION
2025-03-21
E-701
ELECTRICAL
DETAILS
STATE OF CAL IFORNIA
RE
GI
ST
ER
ED
PROFESSIONAL ENGINEER
E16755
ELECTRICAL
S I M
ON PA U L J E
F
F
09/30/202167
03/21/2025