1-2 Attachment A - WBS - 100% Plans.pdf

PDF 7 MB Posted

Attached to
Bus Overflow Parking Project at 809 W. Beach Street, Watsonville, CA
Solicitation number
26-02
Issued by
Newton County, California

About this file

These are 100% Construction Documents for the Santa Cruz Metro Bus Overflow Parking Project located at 809 W. Beach St. in Watsonville, California. The project involves comprehensive electrical and site improvements, specifically focusing on parking lot lighting, electrical infrastructure, and site electrical systems. The documents, prepared by Jacobs Engineering Group Inc., are dated March 21, 2025, and include detailed electrical site plans, photometric calculations, luminaire schedules, electrical site plans, conduit routing, and specific technical specifications for lighting pole installations, electrical equipment, and site electrical systems.

The project includes installing multiple 35'-0" aluminum lighting poles with LED luminaires arranged at various degrees of spacing, designed to provide controlled illumination with minimal offsite light spill. The electrical design incorporates features such as photocells, surge protectors, and specific mounting requirements, with careful attention to placement near the perimeter fenceline and coordination with potential security camera installations. The documents specify using bronze-finished equipment, concrete foundations, and careful routing of underground conduits, with provisions for future infrastructure like a potential PG&E transformer area. The electrical systems are designed to connect to an existing load center and include detailed voltage drop calculations, energy compliance documentation, and comprehensive technical specifications for installation and equipment.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

D

C

B

A

REUSE OF DOCUMENTS: THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE PROPERTY OF JACOBS AND IS NOT TO BE USED, IN WHOLE OR IN PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF JACOBS.

Drawing Sheet Number:

554321 www.jacobs.com

©Jacobs Engineering Group Inc. 2024 ALL RIGHTS RESERVED

Project Number:

Paper Size: ARCH E1

Drawing Sheet Title:

Drawing Status:

Graphic Scale :

Revisions:

Project Client:

Seals:

E

4 Embarcadero Center, Suite 3800 San Francisco, CA 94105

P: 415-728-0850

W8Y13601

SANTA CRUZ METRO

809 W. Beach St, Watsonville

100% CONSTRUCTION

DOCUMENTS

Number Description Date

Rev.

1970 BROADWAY ST STE 760

OAKLAND, CA 94612

TITLE SHEET

0.1

T-1

NO SCALE

NS

CIVIL

C

Exp.

E

TS AT

OF

G R E

No.

ANI

RL FOA

E

RE

S

D

TER

E

R EFO SP

E

LNAO

GN

94922

06/30/25

A. SEITZ

ISSUED FOR

CONSTRUCTION

2025-03-21

Rev.

Attachment A to IFB 26-02

C

B

A

REUSE OF DOCUMENTS: THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE PROPERTY OF JACOBS AND IS NOT TO BE USED, IN WHOLE OR IN PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF JACOBS.

Drawing Sheet Number:

554321 www.jacobs.com

©Jacobs Engineering Group Inc. 2024 ALL RIGHTS RESERVED

Project Number:

Paper Size: ARCH E1

Drawing Sheet Title:

Drawing Status:

Graphic Scale :

Revisions:

Project Client:

Seals:

E

4 Embarcadero Center, Suite 3800 San Francisco, CA 94105

P: 415-728-0850

W8Y13601

SANTA CRUZ METRO

809 W. Beach St, Watsonville

100% CONSTRUCTION

DOCUMENTS

Number Description Date

Rev.

1970 BROADWAY ST STE 760

OAKLAND, CA 94612

PAVEMENT

DELINEATION PLAN

0.1

PD-1

NS

CIVIL

C

Exp.

E

TS AT

OF

G R E

No.

ANI

RL FOA

E

RE

S

D

TER

E

R EFO SP

E

LNAO

GN

94922

06/30/25

A. SEITZ

ISSUED FOR

CONSTRUCTION

2025-03-21

Rev.

C

B

A

REUSE OF DOCUMENTS: THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE PROPERTY OF JACOBS AND IS NOT TO BE USED, IN WHOLE OR IN PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF JACOBS.

Drawing Sheet Number:

554321 www.jacobs.com

©Jacobs Engineering Group Inc. 2024 ALL RIGHTS RESERVED

Project Number:

Paper Size: ARCH E1

Drawing Sheet Title:

Drawing Status:

Graphic Scale :

Revisions:

Project Client:

Seals:

E

4 Embarcadero Center, Suite 3800 San Francisco, CA 94105

P: 415-728-0850

W8Y13601

SANTA CRUZ METRO

809 W. Beach St, Watsonville

100% CONSTRUCTION

DOCUMENTS

Number Description Date

Rev.

CIDH PILES DETAILS

S-001

ISSUED FOR

CONSTRUCTION

2025-03-21

1970 BROADWAY ST STE 760

OAKLAND, CA 94612

Rev.

C

B

A

REUSE OF DOCUMENTS: THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE

PROPERTY OF JACOBS AND IS NOT TO BE USED, IN WHOLE OR IN PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF JACOBS.

Drawing Sheet Number:

554321 www.jacobs.com

©Jacobs Engineering Group Inc. 2025 ALL RIGHTS RESERVED

Project Number:

Paper Size: ARCH E1

Drawing Sheet Title:

Drawing Status:

Graphic Scale :

Revisions:

Project Client:

Seals:

E

4 Embarcadero Center, Suite 3800

San Francisco, CA 94105

P: 415-728-0850

W8Y13601

SANTA CRUZ METRO

809 W. Beach St, Watsonville

100% CONSTRUCTION

DOCUMENTS

Number Description Date

Rev.

Project :

PARKING LOT

IMPROVEMENTS

E-001

E-401A

DUPLEX 20A RECEPTACLE, 120V

SPLIT 20A DUPLEX RECEPTACLE

(15)

TVSS

T

225AF

225AT

3P

ABBREVIATIONS

A AMPERE

AC ALTERNATING CURRENT, AIR

CONDITIONING

AF AMPERE FRAME, AMPERE

FUSE

AFC AVAILABLE FAULT CURRENT

AFG ABOVE FINISHED FLOOR

AHJ AUTHORITY HAVING

JURISDICTION

AIC AMPERE INTERRUPTING

CAPACITY

AHU AIR HANDLING UNIT

ANN ANNUCIATOR

AT AMPERE TRIP

ATS AUTOMATIC TRANSFER

SWITCH

AV AUDIO/VISUAL

AVG AVERAGE

AWG AMERICAN WIRE GAUGE

BC BARE COPPER

BKR BREAKER

BLDG BUILDING

BMS BUILDING MANAGEMENT

SYSTEM

C CONDUIT

COND CONDUCTOR

CONN CONNECTION

CONT CONTINUOUS, CONTINUATION

CB CIRCUIT BREAKER

CCTV CLOSED CIRCUIT TELEVISION

CFCI CONTRACTOR FURNISHED

CONTRACTOR INSTALLED

CKT CIRCUIT

CO CONDUIT ONLY

CONV CONVENIENCE

CONTR CONTRACTOR

COMB COMBINATION

COMM COMMUNICATION

COMP COMPRESSOR

CPU CENTRAL PROCESSING UNIT

CT CURRENT TRANSFORMER

CU COPPER, CONDENSING UNIT

DC DIRECT CURRENT

DI DIGITAL INPUT

DIA DIAMETER

DISC DISCONNECT

DPDT DOUBLE POLE DOUBLE

THROW

DPNL,DP DISTRIBUTION PANEL

DPST DOUBLE POLE SINGLE THROW

DTC DIGITAL TIME CLOCK

(E) EXISTING TO REMAIN

E.C. EMPTY CONDUIT

EF EXHAUST FAN

EL ELECTRIC, ELECTRICAL

ELEV ELEVATION

EMT ELECTRICAL METALLIC

TUBING

ENCL ENCLOSURE

EHT ELECTRIC HEAT TRACE

EOL END OF LINE RESISTOR

EQ, EQUIPMENT

EQUIP

ER EQUIPMENT ROOM

EWC ELECTRIC WATER COOLER

(F) FUTURE

FAAP FIRE ALARM ANNUNCIATOR

PANEL

FACP FIRE ALARM CONTROL PANEL

FC FOOT CANDLE, FAN COIL

FLA FULL LOAD AMPS

FL FLUORESCENT

FO FIBER OPTIC

FPC FIRE PUMP CONTROLLER

FPP FIBER PATCH PANEL

FSD FIRE-SMOKE DAMPER

FV FULL VOLTAGE

FVNR FULL VOLTAGE,

NON-REVERSING

GA GAUGE

GEC GROUNDING ELECTRODE

CONDUCTOR

GFI GROUND FAULT INTERRUPTER

GFCI GROUND FAULT CIRCUIT

INTERRUPTER

GFP GROUND FAULT PROTECTION

G, GRD, GROUND

GND

HAZ HAZARDOUS

HID HIGH INTENSITY DISCHARGE

HH HANDHOLE

HOA HAND-OFF-AUTOMATIC

HP HORSEPOWER, HEAT PUMP

HPF HIGH POWER FACTOR

HT HEIGHT

HV HIGH VOLTAGE

HVAC HEATING, VENTILATING AND

AIR CONDITIONING

HZ HERTZ

IC INTERMEDIATE CROSS

CONNECT

IDF INTERMEDIATE DISTRUBTION

FRAME

IDS INTRUSION DETECTION

SYSTEM

IES ILLUMINATING ENGINEERING

SOCIETY

IG ISOLATED GROUND

J, JB, JUNCTION BOX

J-BOX

KA KILOAMPERES

KCMIL THOUSAND CIRCULAR MILLS

KP KEYPAD

KV KILOVOLT

KVA KILOVOLT AMPERES

KVAR KILOVOLT

AMPERES-REACTIVE

KW KILOWATT

KWH KILOWATT HOURS

LRA LOCKED ROTOR AMPERE

LSIG LONG TIME, SHORT TIME,

INSTANTANEOUS , GROUND

FAULT

LTG LIGHTING

LV LOW VOLTAGE

MAX MAXIMUM

MCA MINIMUM CIRCUIT AMPACITY

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MCP MOTOR CIRCUIT PROTECTOR

MDF MAIN DISTRIBUTION FRAME

MFR MANUFACTURER

MH MANHOLE

MIN MINIMUM

MLO MAIN LUGS ONLY

MM MULTIMODE

MNS MASS NOTIFICATION SYSTEM

MTG MOUNTING

MTS MANUAL TRANSFER SWITCH

N, NEUT NEUTRAL

NAC NOTIFICATION APPLIANCE

CIRCUIT

NC NONCOMBUSTIBLE

N/C NORMALLY CLOSED

NEC NATIONAL ELECTRICAL CODE

NIC NOT IN CONTRACT

NO NUMBER

N/O NORMALLY OPEN

NP NAME PLATE

NR NON-REVERSING

NTS NOT TO SCALE

OH OVERHEAD

OC ON CENTER, OVERCURRENT

P POLE

PCMS POWER CONTROL

MONITORING SYSTEM

PF POWER FACTOR

PH PHASE

PIR PASSIVE INFARED

PIV POST INDICATING VALVE

PKGD PACKAGED

POS POSITIVE

PRI PRIMARY

PTZ PAN-TILT-ZOOM

PVC POLYVINYL CHLORIDE

QY,QTY QUANTITY

RCP REFLECTED CEILING PLAN

REC RECEPTACLE

RECT RECTIFIER

RFI RADIO FREQUENCY

INTERFERENCE

RGS RIGID GALVANIZED STEEL

RMS ROOT MEAN SQUARE

RTU ROOF TOP UNIT

SEC SECONDARY

SM SINGLE MODE

SP SINGLE POLE, SMOKE

PARTITION

SQFT SQUARE FEET

SSRV SOLID STATE REDUCED

VOLTAGE

S/S START-STOP

S-T SHUNT-TRIP

STBY STANDBY

STD STANDARD

STP SHIELDED TWISTED PAIR

SUB SUB PANEL

SW SWITCH

SWBD SWITCHBOARD

TD TIME DELAY

TE TELECOMMUNICATIONS

ENCLOSURE

TELE TELEPHONE

TERM TERMINAL

TR TELECOMMUNICATIONS ROOM

TV TELEVISION

TVSS TRANSIENT VOLTAGE SURGE

SUPPRESSOR

TYP TYPICAL

UNIV UNIVERSAL

UL UNDERWRITERS

LABORATORIES, INC.

UON UNLESS OTHERWISE NOTED

UPS UNINTERRUPTIBLE POWER

SUPPLY

V VOLT, VOLTAGE

VA VOLT AMPERE

VAV VARIABLE AIR VOLUME

VM VOLTMETER

VP VOICE PANEL

VFD VARIABLE FREQUENCY DRIVE

W WATT

WH WATER HEATER

WM WATTMETER

WP WEATHERPROOF

X, XP EXPLOSION PROOF

XFMR TRANSFORMER

Y-D WYE-DELTA

Y WYE

Z IMPEDANCE

NOTE: LIST IS NOT ALL INCLUSIVE AND

DOES NOT INCLUDE, AMONG OTHER,

MDST MEASUREMENTS AND INDUSTRY

STANDARDS.

SYMBOL DESCRIPTION

POWER

EQUIPMENT NO.

AC

REMARKS

ELECTRICAL SYMBOLS

NUMERAL INDICATES CIRCUIT

NUMBER (TYP.)

DUPLEX RECEPTACLES, 120V, L5-20R

JUNCTION BOX

JUNCTION BOX WALL MOUNTED

NON-FUSED DISCONNECT SWITCH

COMBINATION STARTER

FLUSH MOUNTED PANELBOARD

SURFACE MOUNTED PANELBOARD

TRANSFORMER (DRY TYPE)

TRANSIENT VOLTAGE SURGE

SUPPRESSION UNIT

MOLDED CASE 3-POLE CIRCUIT BREAKER

LOWER CASE SUBSCRIPT ADJACENT

TO LIGHT FIXTURE INDICATES WHICH

LIGHT FIXTURES THE SWITCH

CONTROLS.

SYMBOL DESCRIPTION REMARKS

LIGHTING

SINGLE POLE SWITCH

DOUBLE POLE SWITCH

THREE WAY SWITCH

TIME OPERATED

LOW VOLTAGE DIMMER CONTROL

MISCELLANEOUS

30 = SWITCH AMP RATING / (15) =

FUSE AMP RATING

FUSED DISCONNECT SWITCH

1 = NEMA STARTER SIZE

225 = AMP TRIP RATING (AT)

225 = AMP FRAME RATING (AF)

VFD

VARIABLE FREQUENCY DRIVE

EARTH GROUND

MOTOR LOAD. NUMBER INDICATES MOTOR

SIZE = 5 HP

OCCUPANCY SENSOR CEILING MOUNTED

OCCUPANCY SENSOR WALL MOUNTED

LUMINAIRE MOUNTED OCCUPANCY SENSOR

THERMOSTAT

GROUND ROD

GROUND WELL

GROUNDING BUS

CALLOUTS

NOTE CALLOUT PER

FLOOR PLAN

SHEET NO.

FLOOR

PLAN/DETAIL NO.

EQUIPMENT TYPE

SEE

ABBREVIATIONS

MECHANICAL

EQUIPMENT

DISCONNECT/

CONTROLLER

FURNISHED WITH

EQUIPMENT

FUTURE

EQUIPMENT

WORKING SPACE

CLEARANCE

ELECTRICAL

EQUIP

SPECIAL RECEPTACLE, 208V, 30A UON

DUPLEX 20A RECEPTACLE, 120V GFCI

GFCI

30 = SWITCH AMP RATING

ONE OUTLET IMPRINTED

"CONTROLLED"

ENCLOSED CIRCUIT BREAKER

(250)

EQUIPMENT ON

CONCRETE PAD

FUTURE

WALL MOUNT UNLESS SHOWN

WITH CONCRETE PAD

SINGLE POLE SWITCH

MANUAL MOTOR STARTER WITH THERMAL

OVERLOAD PROTECTION

M

S

OS

S

D

OS

S a

S

S

S

T

OCCUPANCY SENSOR WALL MOUNTED W/

DIMMER CONTROL

S

OS

D

PHOTOSENSOR

PS

LUMINAIRE MOUNTED OCCUPANCY AND

DAYLIGHT DIMMING PHOTOSENSOR

OS

OP

LOW VOLTAGE SWITCH

S a

L

CABLE RUNWAY (BASKET TRAY)

MAIN CABLE HANGER ROUTE

CONDUIT/CABLE TURNING UP

CONDUIT STUB OUT

CONDUIT/CABLE CONCEALED

CONDUIT/CABLE RUN, EXPOSED ON FLOORS, CEILING AND WALLS

RACEWAYS AND WIRES

HOMERUN TO PANEL LA, CIRCUITS #1,3,5 & 2 COMMA (,) INDICATES SHARED

NEUTRAL AMPERSAND (&) INDICATES SEPARATE NEUTRAL

LA-1,3,5&2

GROUND FAULT CIRCUIT INTERRUPTER

GFI

BLANK FACE WIRING DEVICE

WITHOUT RECEPTACLE

SIMPLEX 20A RECEPTACLE, 120V

HOMERUN TO PANEL LA, POLYPHASE CIRCUITS #1,3,5 WITHOUT NEUTRAL

LA-1/3/5

OCCUPANCY AND DAYLIGHT DIMMING

SENSOR CEILING MOUNTED

OP

20A PLUG LOAD RELAY CONTROLLER

PL

17 SWITCH CIRCUIT WITHIN ROOM.

LOWER CASE SUBSCRIPT ADJACENT

INDICATES WHICH RECEPTACLE

CIRCUIT IS CONTROLLED IF MORE

THAN ONE PRESENT.

DIMMER CONTROL

D

EXTENT OF DAYLIT ZONE

20A DUPLEX RECEPTACLE BOTH OUTLETS IMPRINTED

"CONTROLLED"

EXTERIOR PHOTOCELL

PC

RECESSED DUPLEX 20A "CLOCK STYLE"

RECEPTACLE, 120V

DISCONNECT SWITCH 30 = AMP RATING

3P=NUMBER OF POLES

30A

3P

GROUND CABLE RUN

CONDUIT/CABLE RUN, AERIAL OVERHEAD

G

FUSED DISCONNECT SWITCH30A

3P

(NOTE: NOT ALL SYMBOLS ARE USED)

HH

SITE LIGHTING POLE (REFER TO PLAN

IN-GRADE HANDHOLE

ELECTRICAL

SYMBOLS AND

ABBREVIATIONS

A

LC-5,7

SL102

"A" INDICATES LUMINAIRE AND POLE

TYPE PER LUMINAIRE SCHEDULE.

"LC-5,7" INDICATES BRANCH CIRCUIT

NUMBER.

"SL102" INDICATES IDENTIFICATION

TAG TO BE APPLIED TO STREET

LIGHTING POLE

FOR LUMINAIRE HEAD CONFIGURATION)

ISSUED FOR

CONSTRUCTION

2025-03-21

STATE OF CAL IFORNIA

RE

GI

ST

ER

ED

PROFESSIONAL ENGINEER

E16755

ELECTRICAL

S I M

ON PA U L J E

F

F

09/30/202167

03/21/2025

1970 BROADWAY ST STE 760

OAKLAND, CA 94612

C

B

A

REUSE OF DOCUMENTS: THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE

PROPERTY OF JACOBS AND IS NOT TO BE USED, IN WHOLE OR IN PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF JACOBS.

Drawing Sheet Number:

554321 www.jacobs.com

©Jacobs Engineering Group Inc. 2025 ALL RIGHTS RESERVED

Project Number:

Paper Size: ARCH E1

Drawing Sheet Title:

Drawing Status:

Graphic Scale :

Revisions:

Project Client:

Seals:

E

4 Embarcadero Center, Suite 3800

San Francisco, CA 94105

P: 415-728-0850

W8Y13601

SANTA CRUZ METRO

809 W. Beach St, Watsonville

100% CONSTRUCTION

DOCUMENTS

Number Description Date

Rev.

Project :

PARKING LOT

IMPROVEMENTS

0 ISSUED FOR

CONSTRUCTION

2025-03-21

E-002

ELECTRICAL

GENERAL NOTES

AND SPECIFICATIONS

P L O

T T

E t a y l o r p p r o j e c t s s a n t a c r u z m e t r o p a r c s w d i p r o d w o r k i n g c a d a d w g

1. SOME LEGEND SYMBOLS MAY NOT BE USED - SEE DRAWINGS FOR APPLICABLE DEVICES.

2. THE LATEST EDITION OF THE OWNER'S AND/OR ARCHITECT'S GENERAL, SPECIAL AND SUPPLEMENTARY

CONDITIONS AS WELL AS SEPARATE SPECIFICATIONS OR PROJECT MANUALS ARE PART OF THESE

CONSTRUCTIONS DOCUMENTS.

3. THE SCOPE OF WORK SHALL INCLUDE LABOR, MATERIALS, EQUIPMENT, TOOLS AND SERVICES REQUIRED

FOR THIS COMPLETE INSTALLATION OF THE ELECTRICAL SYSTEMS AS INDICATED AND SPECIFIED.

4. ELECTRICAL DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW OFFSETS, BENDS, ELBOWS, JUNCTION

BOXES OR OTHER SPECIFIC ELEMENTS WHICH MAY BE REQUIRED FOR PROPER INSTALLATION OF WORK.

SIZE AND LOCATION OF EQUIPMENT AND WIRING ARE SHOWN TO SCALE WHERE POSSIBLE BUT MAY BE

DISTORTED FOR CLARITY OF THE DRAWINGS. FINAL LOCATIONS OF OUTLETS AND EQUIPMENT SHALL BE

SHOWN IN ENLARGED DETAILS OR AS APPROVED BY THE ARCHITECT OR HIS REPRESENTATIVE. IT IS

NOT WITHIN THE SCOPE OF DRAWINGS TO SHOW NECESSARY BENDS, OFFSETS, JUNCTION & PULL

BOXES, AND OBSTRUCTIONS. CONTRACTOR SHALL PROVIDE AN INSTALLATION TO MAINTAIN HEADROOM, AND KEEP OPENINGS AND PASSAGEWAYS CLEAR.

a. JUNCTION AND PULL BOXES SHALL BE LOCATED WHERE ACCESSIBLE ABOVE MAIN PATHS OF

TRAVEL WHEN POSSIBLE, AND IN LOCATIONS WHERE MINIMAL DISRUPTION WOULD OCCUR

SHOULD SERVICING BE REQUIRED.

6. ELECTRICAL MATERIAL & EQUIPMENT SHALL BE NEW AND IN PERFECT CONDITION WHEN INSTALLED.

EQUIPMENT SHALL BE UL LISTED, AND MATERIALS SHALL BE MANUFACTURED IN ACCORDANCE WITH

APPLICABLE STANDARDS OF ANSI, NEMA & NBFU. REPLACE DEFECTIVE OR DAMAGED MATERIALS, OR

REPAIR IN A MANNER APPROVED BY THE OWNER. ALL PRODUCTS SHALL BE LISTED AND LABELED AS

DEFINED IN NFPA 70, BY A QUALIFIED TESTING AGENCY, AND MARKED FOR INTENDED LOCATION AND

APPLICATION.

7. INSTALLATION OF ELECTRICAL WORK : UNLESS MORE STRINGENT REQUIREMENTS ARE SPECIFIED IN THE

CONTRACT DOCUMENTS OR MANUFACTURERS' WRITTEN INSTRUCTIONS, COMPLY WITH NFPA 70 AND

NECA NEIS 1 FOR INSTALLATION OF WORK

8. DEFINITIONS:

a. "FURNISH": SUPPLY AND DELIVER TO PROJECT SITE, READY FOR UNLOADING, UNPACKING, ASSEMBLY, INSTALLATION, AND SIMILAR OPERATIONS.

b. "INSTALL": OPERATIONS AT PROJECT SITE INCLUDING UNLOADING, TEMPORARILY STORING, UNPACKING, ASSEMBLING, ERECTING, PLACING, ANCHORING, APPLYING, WORKING TO

DIMENSION, FINISHING, CURING, PROTECTING, CLEANING, AND SIMILAR OPERATIONS.

c. "PROVIDE": FURNISH AND INSTALL, COMPLETE AND READY FOR THE INTENDED USE.

d. “SHALL”: USED TO QUALIFY AN ACTION WHICH IS MANDATORY.

8. PROVIDE SEISMIC SUPPORT DEVICES, RESTRAINTS AND APPURTENANCES INCLUDING HANGERS, ANCHORS, SLEEVES, INSERTS, SEALS, AND ASSOCIATED FASTENERS USED FOR MOUNTING RACEWAYS, EQUIPMENT AND OTHER ELECTRICAL ITEMS IN ACCORDANCE WITH STATE, COUNTY, CITY, AND LOCAL

CODES. SEISMIC RESTRAINTS AND ATTACHMENTS FOR ELECTRICAL EQUIPMENT AND SYSTEM

COMPONENTS SHALL BE PROVIDED IN ACCORDANCE WITH CBC AND SMACNA REQUIREMENTS.

9. REFER TO ARCHITECTURAL AND STRUCTURAL DRAWINGS FOR EXACT LOCATIONS, DIMENSIONS, AND/OR

RATINGS OF FIRE RATED SEPARATIONS, EXPANSION JOINTS, AND SEISMIC JOINTS.

10. KEEP CONDUITS AND OTHER OPENINGS CLOSED TO PREVENT ENTRY OF FOREIGN MATTER. COVER

FIXTURES, EQUIPMENT AND APPARATUS AND PROTECT AGAINST DIRT, WATER, CHEMICAL OR

MECHANICAL DAMAGE BEFORE AND DURING THE CONSTRUCTION PERIOD UNTIL FINAL ACCEPTANCE.

RESTORE TO ORIGINAL CONDITION ANY FIXTURES, APPARATUS OR EQUIPMENT DAMAGED PRIOR TO

FINAL ACCEPTANCE, INCLUDING RESTORATION OF DAMAGED SHOP COATS OF PAINT. DELIVER

EQUIPMENT AND STORE AT THE SITE, PROPERLY PACKED AND CRATED, UNTIL FINALLY INSTALLED.

11. ANY INCONSISTENCY OR DISCREPANCY IN THE DRAWINGS OR SPECIFICATIONS SHALL BE CLEARED WITH

THE ENGINEER PRIOR TO ROUGH IN OR INSTALLATION. IT IS FURTHER UNDERSTOOD THAT THE

CONTRACTOR HAS READ AND FULLY UNDERSTANDS THE DRAWINGS, SPECIFICATIONS AND RELATED

DOCUMENTS FOR THIS PROJECT PRIOR TO THE COMMENCEMENT OF WORK, INCLUDING DOCUMENTS OF

OTHER DIVISIONS WHICH MAY INTERFERE OR OTHERWISE AFFECT THE WORK OF THIS DIVISION. NO

CONSIDERATION WILL BE GRANTED BY REASON OF LACK OF FAMILIARITY ON THE PART OF THIS DIVISION

WITH THOSE DOCUMENTS.

12. THE CONTRACTOR SHALL UNDERTAKE THE WORK IN ITS ENTIRETY IN ACCORDANCE WITH ITS DESIGN

AND PURPOSE. WORK SHALL BE CARRIED OUT IN A PROFESSIONAL MANNER WITH MAXIMUM

EFFICIENCY, EXCELLENT WORKMANSHIP AND SHALL MEET THE REQUIREMENTS OF THE FOLLOWING:

a. CALIFORNIA CODE OF REGULATIONS:

TITLE 8 - INDUSTRIAL RELATIONS (ELEVATOR SAFETY ORDERS)

TITLE 19 - PUBLIC SAFETY

TITLE 22 - SOCIAL SECURITY

TITLE 24 - 2022 CALIFORNIA BUILDING STANDARDS CODE, (PARTS 1 THRU 9)

b. CALIFORNIA STATE AND LOCAL FIRE MARSHAL.

c. AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI).

d. INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS (IEEE).

e. INSTITUTE OF CABLE ENGINEERS ASSOCIATION (ICEA).

f. NATIONAL ELECTRICAL CONTRACTORS ASSOCIATION STANDARDS FOR CONSTRUCTION (NECA).

g. UNDERWRITERS LABORATORIES, INC. (UL).

h. INSTRUMENT SOCIETY OF AMERICA (ISA).

i. STATE INDUSTRIAL ACCIDENT COMMISSION.

j. OCCUPATIONAL SAFETY AND HEALTH APPEALS BOARD (OSHA).

k. NATIONAL ELECTRICAL TESTING ASSOCIATION (NETA)

13. ELECTRICAL CONTRACTOR SHALL BE LICENSED IN THE STATE OF CALIFORNIA AND WORKERS SHALL BE

CERTIFIED IN ACCORDANCE WITH THE DEPARTMENT OF INDUSTRIAL RELATIONS, DIVISION OF

APPRENTICESHIP STANDARDS AND CALIFORNIA LABOR CODE SECTION 3099.

14. CONTRACTOR SHALL CAREFULLY LAY OUT WORK IN ADVANCE TO AVOID UNNECESSARY CUTTING, CHANNELING, CHASING OR DRILLING OF FLOORS, WALLS, PARTITIONS, CEILINGS OR OTHER SURFACES.

STRUCTURAL MEMBERS SHALL NOT BE CUT OR DRILLED WITHOUT THE APPROVAL OF THE ENGINEER

AND OWNER. HOWEVER, WHERE SUCH WORK IS NECESSARY PROVIDE CUTTING, CORING AND PATCHING

OF THE CONSTRUCTION WORK WHICH MAY BE REQUIRED FOR THE PROPER INSTALLATION OF THE

ELECTRICAL WORK. PATCHING SHALL BE OF THE SAME MATERIALS, WORKMANSHIP AND FINISH, AND

SHALL ACCURATELY MATCH SURROUNDING WORK. AFTER COMPLETION OF WORK, CLEAN UP

RESULTANT DEBRIS AND REMOVE FROM SITE.

15. NUMBER OF UNGROUNDED “HOT” CONDUCTORSAND GROUNDED NEUTRAL CONDUCTORS IS AS IMPLIED

BY THE CIRCUIT NUMBERS ADJACENT TO THE EQUIPMENT, DEVICE, OR OUTLET UNLESS NOTED

OTHERWISE. HOME RUNS MAY BE COMBINED IN A SINGLE CONDUIT HOME RUN WITH UP TO (3) BRANCH

CIRCUITS IN A CONDUIT WHERE PERMITTED BY CODE. MAINTAIN CONDUIT FILL BELOW 40%, AND DERATE

CONDUCTOR AMPACITIES TO 80% PER TABLE 310-15(b)(2)(a), FOR 4 THROUGH 6 CONDUCTORS.

16. UNLESS MORE STRINGENT REQUIREMENTS ARE SPECIFIED IN THE CONTRACT DOCUMENTS,PROVIDE

DATA SUBMITTAL FOR EACH TYPE OF PRODUCT TO BE INCORPORATED INTO THE WORK.

a. INCLUDE DATA ON FEATURES, ACCESSORIES, AND FINISHES, CLEARLY IDENTIFYING PRODUCT

AND OPTIONS PROPOSED.

b. INCLUDE PHYSICAL DESCRIPTION AND DIMENSIONS.

c. LAMPS, INCLUDE LIFE, OUTPUT (LUMENS, CCT, AND CRI), AND ENERGY-EFFICIENCY DATA.

d. PHOTOMETRIC DATA AND ADJUSTMENT FACTORS BASED ON LABORATORY TESTS, COMPLYING

WITH IES LIGHTING MEASUREMENTS TESTING AND CALCULATION GUIDES, OF EACH LUMINAIRE

TYPE. THE ADJUSTMENT FACTORS SHALL BE FOR LAMPS AND ACCESSORIES IDENTICAL TO

THOSE INDICATED FOR THE LUMINAIRE AS APPLIED IN THIS PROJECT.

e. WIRING DIAGRAMS FOR POWER, CONTROL, AND SIGNAL WIRING.

17. CONTRACTOR SHALL PROVIDE LUGS FOR TERMINATING OVERSIZED CONDUCTORS, OR MAKE

PROVISIONS FOR TERMINATING OVERSIZED CONDUCTORS TO EQUIPMENT OR DEVICES WHICH LUGS DO

NOT ACCEPT OVERSIZED CONDUCTORS. SUBMIT TO PROJECT ENGINEER FOR APPROVAL APPLICABLE

VOLTAGE DROP CALCULATIONS PRIOR TO REDUCING CONDUCTOR SIZE.

18. CONTRACTOR SHALL PROVIDE ELECTRICAL FINAL CONNECTIONS TO ELECTRICAL EQUIPMENT AND

OUTLETS FOR A COMPLETE AND OPERABLE SYSTEM.

19. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VISIT THE JOBSITE PRIOR TO SUBMITTING

THE PROPOSAL AND TO BECOME FAMILIARI WITH EXISTING CONDITIONS.

20. PROVIDE WIRING DEVICES WITH SOURCE PANEL NAME AND CIRCUIT NUMBER ENGRAVED ON THE FRONT.

IDENTIFY CIRCUIT NUMBERS AT THE TERMINATION POINT OF ALL CONDUCTORS USING HEAT SHRINK

SLEEVES. IDENTIFY THE CIRCUIT NUMBERS PRESENT WITHIN JUNCTION BOXES WITH INDELIBLE INK ON

THE COVER.

21. ELECTRICAL EQUIPMENT SHALL BE FULLY RATED FOR THE MAXIMUM AVAILABLE SHORT CIRCUIT

CURRENT. REFER TO PANEL SCHEDULES AND SINGLE LINE DIAGRAM FOR AIC RATINGS OF EQUIPMENT.

22. CONTRACTOR SHALL DETERMINE ACTUAL LENGTHS OF FEEDERS AND BRANCH CIRCUITS BASED ON

ROUTING AND FIELD CONDITIONS.

23. PROVIDE WIRING FOR EQUIPMENT FURNISHED BY OTHER DIVISIONS SHOWN ON DRAWINGS. THE TERM

"WIRING" AS USED HEREIN, INCLUDES FURNISHING AND INSTALLING CONDUIT, WIRE, JUNCTION BOXES, STARTERS, DISCONNECTS, ETC., AND MAKING CONNECTIONS TO THE EQUIPMENT. BE RESPONSIBLE FOR

PROPER WIRING AND NECESSARY ELECTRICAL ADJUSTMENTS TO EQUIPMENT TO CONFORM TO

SPECIFIED REQUIREMENTS OF THE EQUIPMENT. CONTRACTOR SHOULD OBTAIN AND REVIEW DRAWINGS

OF OTHER DISCIPLINES TO ASCERTAIN THE REQUIREMENTS OF EQUIPMENT BEING FURNISHED AND/OR

INSTALLED BY THAT DIVISION PRIOR BID. COORDINATE EXACT DETAILS AND LOCATIONS PRIOR TO

ROUGH IN WITH OTHER DIVISIONS.

29. ELECTRICAL EQUIPMENT SHALL BE BONDED AND GROUNDED IN ACCORDANCE WITH STATE, COUNTY, CITY, AND LOCAL CODES. APPLICABLE CODES AND JURISDICTIONS. ALL FEEDERS AND BRANCH CIRCUIT

CONDUITS SHALL BE PROVIDED WITH AN INSULATED EQUIPMENT BONDING CONDUCTOR.

30. PROVIDE A COMPLETE GROUNDED RACEWAY SYSTEM FOR POWER, LIGHTING AND FOR ALL LOW

VOLTAGE SIGNAL CABLING SYSTEMS NOT SPECIFICALLY SHOWN ON THESE ELECTRICAL DRAWINGS, INCLUDE BUT NOT LIMITED TO, DEVICE BACK BOXES, CONDUITS WITH PULL LINE, COUPLINGS, PULL

BOXES, BONDING WIRES, AND SUPPORTS FOR THE FOLLOWING:

a. SECURITY

CONTRACTOR SHALL REFER TO DESIGN DRAWINGS FOR THE ABOVE REFERENCED SYSTEMS FOR

DETAILS.

31. EQUIPMENT ENCLOSURES, J-BOXES, GUTTERS ETC. INSTALLED OUTSIDE OF BUILDING AND SUBJECT TO

WEATHER SHALL BE WEATHER PROOF METALLIC NEMA 3R (PROVIDE NEMA 4X STAINLESS STEEL WHERE

INDICATED). GFI TYPE RECEPTACLES LOCATED ON EXTERIOR SHALL HAVE “IN USE” TYPE WEATHER

PROOF ENCLOSURES.

32. PRIOR TO INSTALLING CABLES IN BELOW GRADE CONDUITS AND DUCTS, PULL LEATHER-WASHER-TYPE

DUCT CLEANER, WITH GRADUATED WASHER SIZES, THROUGH FULL LENGTH OF DUCT UNTIL DUCT

CLEANER INDICATES THAT DUCT IS CLEAR OF DIRT AND DEBRIS. FOLLOW WITH RUBBER DUCT SWAB FOR

FINAL CLEANING AND TO ASSIST IN SPREADING LUBRICANT THROUGHOUT DUCTS.

33. VACUUM OUT ALL ACCUMULATED DEBRIS FROM ENCLOSURES, PANELBOARDS AND JUNCTION BOXES

UTILIZED FOR THE PROJECT PRIOR TO HANDOVER.

37. CLEAN INTERNAL SURFACES OF IN-GRADE HANDHOLES, REMOVE FOREIGN MATERIAL.

38. PROVIDE A FUSED DISCONNECT SPLICE CONNECTOR IN EACH LIGHT POLE, READILY ACCESSIBLE AND

LEVEL WITH THE HAND HOLE, INSTALLED IN EACH UNGROUNDED CONDUCTOR BETWEEN THE LINE AND

THE LUMINAIRE. THE CONNECTOR SHALL BE A WATER TIGHT BUSSMAN “HEY” FUSEHOLDER OR EQUAL

WITH 5 AMPERE KTK FUSE.

39. PROVIDE EACH LIGHTING POLE WITH A UNIQUE IDENTIFIER USING LABELING IDENTIFIED ON THE

DRAWINGS. EQUIPMENT IDENTIFICATION CHARACTERS SHALL BE 2-1/2 INCH, SERIES D LETTERING, EXCEPT ON WOOD POLES, THEY MUST BE 3-INCH LETTERING. THE CHARACTERS MUST BE ON

SELF-ADHESIVE REFLECTIVE UV STABILIZED LABELS AFFIXED TO METALLIC POLES. EXCEPT ON WOOD

POLES, THE CHARACTERS MUST BE EMBOSSED ON ALUMINUM LABELS. LABELS MUST HAVE A WHITE

BACK GROUND, ALL BLACK CAPITAL CHARACTERS, AND MUST EXTEND BEYOND THE CHARACTER BY A

MINIMUM OF 1/4 INCH. SUBMIT PRODUCT DATA AND SAMPLE FOR LABEL. VERIFY EXACT REQUIREMENTS

WITH OWNER'S REPRESENTATIVE PRIOR TO MANUFACTURE OF LABELS.

40. ERECT ALL LIGHTING POLES STRAIGHT AND PLUMB ON CONCRETE FOUNDATIONS, INSTALL VENDOR'S

BOLT/NUT COVERS OVER ANCHOR BOLTS AND PROVIDE GROUT,WITH DRAIN PIPE, BETWEEN

FOUNDATION TOP AND LIGHTING POLE BASE PLATE . ALL PERIMETER LIGHTING POLE LUMINAIRES

SHALL FACE INWARDS AWAY FROM THE PROPERTY LINE, APPROXIMATELY PERPINDICULAR TO THE

PROPERTY LINE. PROVIDE HOUSE SIDE BACKLIGHT SHIELDING TO LIMIT LIGHTING SPILL OFF THE

PROPERTY.

41. PROVIDE ALL TRENCHING, CONDUIT BEDDING MATERIAL AND NATIVE MATERIAL BACKFILL FOR ALL

BURIED RACEWAYS. PROVIDE DETECTABLE WARNING MARKER TAPE BURIED ABOVE CONDUIT.

GENERAL NOTES

SECTION 260519 - LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND

CABLES

600V CONDUCTOR MATERIAL AND APPLICATIONS

A. BRANCH CIRCUITS: COPPER. SOLID FOR NO. 12 AWG AND SMALLER;

STRANDED FOR NO. 10 AWG AND LARGER.

B. EXPOSED BRANCH CIRCUITS: TYPE THHN/THWN-2 OR XHHW-2, SINGLE

CONDUCTORS IN RACEWAY.

C. BRANCH CIRCUITS CONCEALED IN CONCRETE, BELOW SLABS-ON-GRADE,

AND UNDERGROUND: TYPE THHN/THWN-2 OR XHHW-2 SINGLE

CONDUCTORS IN RACEWAY.

D. BRANCH CIRCUITS CONCEALED IN LIGHTING POLE: TYPE THHN/THWN-2

OR XHHW-2 SINGLE CONDUCTORS IN RACEWAY AND TYPE UF-B CABLE AS

INDICATED.

E. FUSED DISCONNECT SPLICE CONNECTOR: WATER TIGHT BUSSMAN “HEY”

FUSEHOLDER OR EQUAL WITH 5 AMPERE KTK FUSE.

SECTION 260526 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS

EQUIPMENT GROUNDING

A. INSTALL INSULATED EQUIPMENT GROUNDING CONDUCTORS WITH ALL

BRANCH CIRCUITS AND FEEDERS.

POLES SUPPORTING OUTDOOR LIGHTING FIXTURES

A. INSTALL GROUNDING ELECTRODE AND A GROUNDING ELECTRODE

CONDUCTOR IN ADDITION TO EQUIPMENT GROUNDING CONDUCTOR

INSTALLED WITH BRANCH-CIRCUIT CONDUCTORS.

CONNECTIONS

A. USE UL APPROVED HIGH-PRESS GROUND CONNECTORS

(UNDERGROUND), OR UL APPROVED MECHANICAL GROUND CONNECTORS

(ACCESSIBLE LOCATIONS).

SECTION 26500 - LUMINAIRES

LUMINAIRES AND POLES

A. PRODUCT AND OPERATION AS INDICATED ON THE DRAWINGS.

POLE INSTALLATION

A. EXAMINE POLES, LUMINAIRE-MOUNTING DEVICES, LOWERING DEVICES,

AND POLE ACCESSORIES BEFORE INSTALLATION. COMPONENTS THAT

ARE SCRATCHED, DENTED, MARRED, WET, MOISTURE DAMAGED, OR

VISIBLY DAMAGED ARE CONSIDERED DEFECTIVE.

B. ALIGNMENT: ALIGN POLE FOUNDATIONS AND POLES FOR OPTIMUM

DIRECTIONAL ALIGNMENT OF LUMINAIRES AND THEIR MOUNTING

PROVISIONS ON POLE. ALIGN HANDHOLE TO BE ACCESSIBLE.

C. CONCRETE POLE FOUNDATIONS: SET ANCHOR BOLTS IN ACCORDANCE

WITH ANCHOR-BOLT TEMPLATES FURNISHED BY POLE MANUFACTURER.

D. MOUNT POLE WITH LEVELING NUTS AND TIGHTEN TOP NUTS TO TORQUE

LEVEL IN ACCORDANCE WITH POLE MANUFACTURER'S WRITTEN

INSTRUCTIONS.

E. GROUT VOID BETWEEN POLE BASE AND FOUNDATION. USE NONSHRINK

OR EXPANDING CONCRETE GROUT FIRMLY PACKED TO FILL SPACE.

F. INSTALL BASE COVERS UNLESS OTHERWISE INDICATED.

G. USE A SHORT PIECE OF 1/2 INCH DIAMETER PIPE TO MAKE A DRAIN HOLE

THROUGH GROUT. ARRANGE TO DRAIN CONDENSATION FROM INTERIOR

OF POLE.

H. RAISE AND SET POLE USING WEB FABRIC SLINGS (NOT CHAIN OR CABLE)

AT LOCATIONS INDICATED BY MANUFACTURER.

SECTION 260529 - HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS

SUPPORT, ANCHORAGE, AND ATTACHMENT COMPONENTS

A. MATERIAL FOR SLOTTED STEEL CHANNEL, FITTINGS, CONDUIT SUPPORTS

AND ACCESSORIES: STEEL, HOT-DIP GALVANIZED AFTER FABRICATION

AND APPLIED ACCORDING TO MFMA-4.

B. PROVIDE SUPPORTS IN ACCORDANCE WITH SMACNA.

SECTION 260533 - RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS

RACEWAY APPLICATION

A. OUTDOORS: APPLY RACEWAY PRODUCTS AS BELOW UNLESS OTHERWISE

INDICATED:

1.EXPOSED CONDUIT: STEEL GRC.

2.UNDERGROUND CONDUIT: RNC, TYPE EPC-40-PVC, DIRECT BURIED. USE

40 MIL PVC COATED GRC WHERE INDICATED.

3.SECURITY PATHWAY (WHERE INDICATED): FLEXIBLE NON METALLIC

LIQUID TIGHT ELECTRICAL CONDUIT

4.CONNECTION TO VIBRATING EQUIPMENT (INCLUDING TRANSFORMERS

AND HYDRAULIC, PNEUMATIC, ELECTRIC SOLENOID, OR MOTOR-DRIVEN

EQUIPMENT): LFMC.

5.BOXES AND ENCLOSURES, ABOVEGROUND: NEMA 250, TYPE 4. SHEET

METAL OUTLET AND DEVICE BOXES: COMPLY WITH NEMA OS 1 AND

UL 514A. CAST-METAL OUTLET AND DEVICE BOXES: COMPLY WITH

NEMA FB 1, FERROUS ALLOY OR ALUMINUM, TYPE FD, WITH GASKETED

COVER.

B. RACEWAYS BELOW GRADE:

1.CHANGE FROM PVC TO PVC COATED STEEL GRC BEFORE RISING ABOVE

FLOOR/GRADE.

2.ARRANGE STUB-UPS SO CURVED PORTIONS OF BENDS ARE NOT VISIBLE

ABOVE FINISHED SLAB/GRADE.

3.MINIMUM TRADE SIZE 1" DIAMETER.

SECTION 260553 - IDENTIFICATION FOR ELECTRICAL SYSTEMS

UNDERGROUND WARNING TAPE

A. FOIL-BACKED DETECTABLE TYPE TAPE: 3 INCHES WIDE, WITH MINIMUM

THICKNESS OF 5 MIL .

B. TYPE OF SERVICE, CONTINUOUSLY REPEATED OVER FULL LENGTH OF

TAPE "CAUTION BURIED ELECTRIC LINE BELOW” BLACK TEXT ON RED

BACKGROUND.

C. PRINTING ON TAPE SHALL BE PERMANENT AND SHALL NOT BE DAMAGED

BY BURIAL OPERATIONS OR DEGRADE WHEN EXPOSED TO ACIDS,

ALKALIS, AND OTHER DESTRUCTIVE SUBSTANCES COMMONLY FOUND IN

SOILS.

MARKERS FOR CONDUCTORS AND CABLES

A. USE WRAP-AROUND SELF-ADHESIVE VINYL CLOTH, WRAP-AROUND

SELF-ADHESIVE VINYL SELF-LAMINATING, HEAT-SHRINK SLEEVE, PLASTIC

SLEEVE, PLASTIC CLIP-ON, OR VINYL SPLIT SLEEVE TYPE MARKERS

SUITABLE FOR THE CONDUCTOR OR CABLE TO BE IDENTIFIED.

B. LEGEND: POWER SOURCE AND CIRCUIT NUMBER OR OTHER

DESIGNATION INDICATED.

C. TEXT: USE FACTORY PRE-PRINTED OR MACHINE-PRINTED TEXT, ALL

CAPITALIZED.

D. MINIMUM TEXT HEIGHT: 1/8 INCH.

E. COLOR: BLACK TEXT ON WHITE BACKGROUND

MARKERS FOR RECEPTACLES, BOXES AND EQUIPMENT ENCLOSURES.

A. SELF-ADHESIVE VINYL LABELS, PREPRINTED, FLEXIBLE LABEL LAMINATED

WITH A CLEAR, WEATHER- AND CHEMICAL-RESISTANT, UV-STABILIZED

COATING.

B. INSTALL CIRCUIT LABELING FOR RECEPTACLES UNDER WEATHERPROOF

HINGED COVER.

SECTION 260923 - LIGHTING CONTROL DEVICES

ELECTRONIC TIME SWITCHES

A. SOLID STATE, PROGRAMMABLE, WITH ALPHANUMERIC DISPLAY;

COMPLYING WITH UL 917. MARKED FOR INTENDED LOCATION AND

APPLICATION.

B. PRODUCT AND OPERATION AS INDICATED ON THE DRAWINGS.

SECTION 262416 - PANELBOARD/CIRCUIT BREAKERS

A. THERMAL-MAGNETIC CIRCUIT BREAKERS: CIRCUIT BREAKERS WITH TRIP

RATINGS 100 AMP AND SMALLER INVERSE TIME-CURRENT ELEMENT FOR

LOW-LEVEL OVERLOADS, AND INSTANTANEOUS MAGNETIC TRIP ELEMENT

FOR SHORT CIRCUITS. MINIMUM 75 DEG C RATED TERMINALS.

SECTION 270528 - PATHWAYS FOR COMMUNICATIONS/SECURITY/ACCESS

CONTROL SYSTEMS

A. CONFORM TO SECTION 260533 AND WITH THE FOLLOWING

REQUIREMENTS.

B. CONFORM TO INSTALLATION INSTRUCTIONS OF TIA/EIA-569-A AND BICSI

TDMM FOR PATHWAYS.

C. WHEN ROUTING CONDUIT, MAINTAIN A GRADUATED BEND RADIUS TO

MAINTAIN CONDUIT CAPACITY. TYPICALLY A MINIMUM OF SIX TIMES THE

CONDUIT DIAMETER. MAXIMUM THREE 90 DEGREE BENDS BETWEEN

PULLING POINTS.

SPECIFICATIONS

STATE OF CAL IFORNIA

RE

GI

ST

ER

ED

PROFESSIONAL ENGINEER

E16755

ELECTRICAL

S I M

ON PA U L J E

F

F

09/30/202167

03/21/2025

C

B

A

REUSE OF DOCUMENTS: THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE

PROPERTY OF JACOBS AND IS NOT TO BE USED, IN WHOLE OR IN PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF JACOBS.

Drawing Sheet Number:

554321 www.jacobs.com

©Jacobs Engineering Group Inc. 2025 ALL RIGHTS RESERVED

Project Number:

Paper Size: ARCH E1

Drawing Sheet Title:

Drawing Status:

Graphic Scale :

Revisions:

Project Client:

Seals:

E

4 Embarcadero Center, Suite 3800

San Francisco, CA 94105

P: 415-728-0850

W8Y13601

SANTA CRUZ METRO

809 W. Beach St, Watsonville

100% CONSTRUCTION

DOCUMENTS

Number Description Date

Rev.

Project :

PARKING LOT

IMPROVEMENTS

0 ISSUED FOR

CONSTRUCTION

2025-03-21

E-010

ELECTRICAL

ENERGY

COMPLIANCE

CALCULATIONS

P L O

T T y l p r o j e c t s s a n t a c r u z m e t r o p a r c s w d i p r o d w o r k i n g c a d a d w g

STATE OF CAL IFORNIA

RE

GI

ST

ER

ED

PROFESSIONAL ENGINEER

E16755

ELECTRICAL

S I M

ON PA U L J E

F

F

09/30/202167

03/21/2025

C

B

A

REUSE OF DOCUMENTS: THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE

PROPERTY OF JACOBS AND IS NOT TO BE USED, IN WHOLE OR IN PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF JACOBS.

Drawing Sheet Number:

554321 www.jacobs.com

©Jacobs Engineering Group Inc. 2025 ALL RIGHTS RESERVED

Project Number:

Paper Size: ARCH E1

Drawing Sheet Title:

Drawing Status:

Graphic Scale :

Revisions:

Project Client:

Seals:

E

4 Embarcadero Center, Suite 3800

San Francisco, CA 94105

P: 415-728-0850

W8Y13601

SANTA CRUZ METRO

809 W. Beach St, Watsonville

100% CONSTRUCTION

DOCUMENTS

Number Description Date

Rev.

Project :

PARKING LOT

IMPROVEMENTS

0 ISSUED FOR

CONSTRUCTION

2025-03-21

E-011

ELECTRICAL

ENERGY

COMPLIANCE

CALCULATIONS

P L O

T T y l p r o j e c t s s a n t a c r u z m e t r o p a r c s w d i p r o d w o r k i n g c a d a d w g

STATE OF CAL IFORNIA

RE

GI

ST

ER

ED

PROFESSIONAL ENGINEER

E16755

ELECTRICAL

S I M

ON PA U L J E

F

F

09/30/202167

03/21/2025

C

B

A

REUSE OF DOCUMENTS: THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE

PROPERTY OF JACOBS AND IS NOT TO BE USED, IN WHOLE OR IN PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF JACOBS.

Drawing Sheet Number:

554321 www.jacobs.com

©Jacobs Engineering Group Inc. 2025 ALL RIGHTS RESERVED

Project Number:

Paper Size: ARCH E1

Drawing Sheet Title:

Drawing Status:

Graphic Scale :

Revisions:

Project Client:

Seals:

E

4 Embarcadero Center, Suite 3800

San Francisco, CA 94105

P: 415-728-0850

W8Y13601

SANTA CRUZ METRO

809 W. Beach St, Watsonville

100% CONSTRUCTION

DOCUMENTS

Number Description Date

Rev.

Project :

PARKING LOT

IMPROVEMENTS

0 ISSUED FOR

CONSTRUCTION

2025-03-21

E-100

ELECTRICAL

SITE PLAN -

PHOTOMETRICS

A

A

A

A

A

A

A

A

A

B

B

A

A

A

A

STATE OF CAL IFORNIA

RE

GI

ST

ER

ED

PROFESSIONAL ENGINEER

E16755

ELECTRICAL

S I M

ON PA U L J E

F

F

09/30/202167

03/21/2025

C

B

A

REUSE OF DOCUMENTS: THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE

PROPERTY OF JACOBS AND IS NOT TO BE USED, IN WHOLE OR IN PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF JACOBS.

Drawing Sheet Number:

554321 www.jacobs.com

©Jacobs Engineering Group Inc. 2025 ALL RIGHTS RESERVED

Project Number:

Paper Size: ARCH E1

Drawing Sheet Title:

Drawing Status:

Graphic Scale :

Revisions:

Project Client:

Seals:

E

4 Embarcadero Center, Suite 3800

San Francisco, CA 94105

P: 415-728-0850

W8Y13601

SANTA CRUZ METRO

809 W. Beach St, Watsonville

100% CONSTRUCTION

DOCUMENTS

Number Description Date

Rev.

Project :

PARKING LOT

IMPROVEMENTS

1. REMOVE AND DISPOSE OF EXISTING LIGHTING POLES,

LUMINAIRES AND WIRING BACK TO SOURCE LOAD CENTER

PANEL. REMOVE EXISTING LIGHTING CONTROLS SYSTEM.

REFER TO DRAWING PD-1 FOR POLE LOCATIONS.

2. FIELD VERIFY AND COORDINATE FINAL LOCATION OF

FOUNDATIONS FOR LIGHTING POLES WITH ALL

SUBSURFACE AND AT GRADE UTILITIES AND ALL SITE

FEATURES AND IMPROVEMENTS. VERIFY BY POTHOLING

PRIOR TO EXCAVATION.

3. UNDERGROUND CONDUITS SHALL BE MINIMUM 1" UNLESS

NOTED OTHERWISE.

4. LIGHTING POWER CONDUITS SHALL TURN UP INTO

LIGHTING POLE CONCRETE BASES AND STUB ABOVE TOP

OF BASE INSIDE POLE. CONDUCTORS SHALL BE SPLICED

AT FIRST ACCESSIBLE HANDHOLE LOCATION IN POLE TO

#12 AWG TYPE UF -B (12-2) CABLE FOR CONNECTION TO

LUMINAIRE AT TOP OF POLE. VERIFY WITH VENDOR

SUBMITTALS.

5. ETHERNET POE SECURITY CONDUITS SHALL TURN UP INTO

LIGHTING POLE CONCRETE BASES AND STUB ABOVE TOP

OF BASE INSIDE POLE AT MID-POINT BETWEEN FIRST AND

SECOND ACCESSIBLE HANDHOLE TO MAINTAIN

SEPARATION BETWEEN POE CABLE AND SINGLE

INSULATED POWER CONDUCTORS. ETHERNET POE CABLE

TO BE INSTALLED BY SECURITY VENDOR.

6. PROVIDE IN-LINE FUSES AND LABELING OF POLES AS

IDENTIFIED ON SHEET E-002.

7. PROVIDE ALL LIGHTING POLES WITH CONCRETE

FOUNDATION THAT EXTENDS 5'-0" ABOVE FINISHED GRADE.

PROVIDE SMOOTH FINISHED GROUT BETWEEN POLE BASE

AND TOP OF FOUNDATION. PAINT ALL VISIBLE PARTS OF

LIGHTING POLE FOUNDATIONS "SAFETY YELLOW".

8. AT PERIMETER FENCELINE, ROUTE BELOW GRADE

CONDUITS AND PLACE CENTER OF LIGHTING POLES

TYPICALLY WITHIN 2 TO 5 FEET OF THE FENCE LINE.

ROUTING AND LOCATIONS SHOWN IS DIAGRAMMATIC.

9. MEET, SCHEDULE AND COORDINATE WORK RELATED TO

SECURITY INSTALLATION WITH OWNER'S SECURITY

VENDOR, INCLUDING DRILLING OF LIGHTING POLES FOR

CAMERA CABLING, ENCLOSURE MOUNTING AND POWER

CONNECTION AND RACEWAY INSTALLATION.

GENERAL NOTES

0 ISSUED FOR

CONSTRUCTION

2025-03-21

E-101

ROUTE LIGHTING CIRCUIT CONDUCTORS VIA AUTOMATIC

TIME CLOCK TO (E) PANEL "LC". REFER TO DETAIL ON

SHEET E-701 FOR CONTROLS DIAGRAM. PROVIDE STEEL

CHANNEL SUPPORT, FIELD VERIFY MOUNTING LOCATION.

PROVIDE H-20 RATED CONCRETE HANDHOLE "TRAFFIC

BOX" FLUSH WITH GRADE, NOMINAL 10" WIDTH X 17" LONG

X 12" DEEP INTERNAL DIMENSIONS, WITH GALVANIZED

STEEL CHECKER PLATE H-20 BOLT DOWN COVER. CHRISTY

B1017 OR EQUAL. IDENTIFY LID WITH "SECURITY" SERVICE.

INSTALL IN ACCORDANCE WITH MANUFACTURER'S

INSTRUCTIONS AND DETAIL ON DRAWING E-701.

FIELD VERIFY LOCATION OF (E) LOAD CENTER AND (E)

BRANCH CIRCUITS ORIGINATING AT LOAD CENTER.

PROVIDE TYPED CIRCUIT CHART DOCUMENTING (E)

CIRCUITS TO REMAIN AND ALL PROPOSED CIRCUITS.

PROVIDE CIRCUIT NUMBER IDENTIFICATION AT THE

EXISTING AND PROPOSED LOAD EQUIPMENT AND

RECEPTACLES.

WEATHERPROOF SECURITY ENCLOSURE "SEC1" .

ENCLOSURE SHALL BE PROVIDED (SUPPLIED AND

INSTALLED) BY CONTRACTOR FOR USE BY SECURITY

VENDOR. PROVIDE STEEL CHANNEL FRAME. ENCLOSURE

SHALL BE NEMA 3R, SIDE HINGED DOOR WITH FULL PIANO

HINGE, PADLOCKABLE WING LATCH WITH REAR MOUNTED

BACKPLATE, MODEL "M1-31" MANUFACTURED BY SUNWIZE.

APPROXIMATE DIMENSIONS 16"W X 20.75"H X 9.4"D.

TERMINATE CONDUITS FOR SECURITY AT A

WEATHERPROOF WIREWAY OR JUNCTION BOX MOUNTED

BELOW SECURITY ENCLOSURE. PROVIDE CONDUITS

BETWEEN WIREWAY/JUNCTION BOX AND SECURITY

ENCLOSURE KNOCK-OUTS. FIELD COORDINATE FINAL

POWER CONNECTION WITH SECURITY VENDOR.

PROVIDE 1" CONDUIT BELOW GRADE FOR POE CABLING BY

SECURITY VENDOR FROM PROPOSED SECURITY

ENCLOSURE "SEC1" TO SERVE CAMERAS ON LIGHTING

POLES. PROVIDE CONDUITS WITH PULL STRINGS FOR USE

BY SECURITY VENDOR.

AREA FOR FUTURE PG&E TRANSFORMER AND CUSTOMER

SWITCHBOARD, APPROX 20'-0" X 15'-0". DO NOT ROUTE

BELOW GRADE CONDUITS IN THIS AREA. STRIPE AREA

WITH MARKING PAINT FOR TEMPORARY IDENTIFICATION

OF KEEP-OUT ZONE AT COMPLETION OF PROJECT.

PROTECT AND RETAIN EXSITING LOAD CENTER "LC"

BRANCH CIRCUIT PANEL, OVERHEAD SERVICE ENTRANCE

CONDUCTORS, SERVICE POLE AND GUYING SYSTEM,

MOUNTING BACKBOARD/RACK, PULLCAN, METER,

GROUNDING, ASSOCIATED RACEWAYS, RECEPTACLES

AND BRANCH CIRCUITS MOUNTED ADJACENT TO LOAD

CENTER.

KEYED NOTES

ELECTRICAL

SITE PLAN

H

H

H

H

C

A

M

C

A

M

H

H

HH

C

A

M

C

A

M

C

A

M

(E)PNL "LC"

A

LC-9,11

SL101

A

LC-5,7

SL102

A

LC-5,7

SL103

A

LC-5,7

SL104

A

LC-5,7

SL105

A

LC-5,7

SL106

A

LC-5,7

SL107

A

LC-9,11

SL107

A

LC-9,11

SL108

A

LC-9,11

SL109

A

LC-9,11

SL110

A

LC-9,11

SL111

A

LC-9,11

SL112

B

LC-13,15

SL113

B

LC-13,15

SL114

AUTOMATIC TIME CLOCK

TYP.

SECURITY

ENCLOSURE

LC-8

LC-14

TYP.

OUTLINE OF FUTURE MOBILE

FUELING TRUCK AREA. SHOWN

PROVIDE MINIMUM 24" COVER

FOR REFERENCE

FENCELINE

PVC COATED RIGID STEEL

SL106 AND SL107 TO BE

CONDUIT BETWEEN POLES

CONDUIT ROUTING SHOWN

IS DIAGRAMMATIC.

REFER TO GENERAL NOTE 8

STATE OF CAL IFORNIA

RE

GI

ST

ER

ED

PROFESSIONAL ENGINEER

E16755

ELECTRICAL

S I M

ON PA U L J E

F

F

09/30/202167

03/21/2025

C

B

A

REUSE OF DOCUMENTS: THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE

PROPERTY OF JACOBS AND IS NOT TO BE USED, IN WHOLE OR IN PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF JACOBS.

Drawing Sheet Number:

554321 www.jacobs.com

©Jacobs Engineering Group Inc. 2025 ALL RIGHTS RESERVED

Project Number:

Paper Size: ARCH E1

Drawing Sheet Title:

Drawing Status:

Graphic Scale :

Revisions:

Project Client:

Seals:

E

4 Embarcadero Center, Suite 3800

San Francisco, CA 94105

P: 415-728-0850

W8Y13601

SANTA CRUZ METRO

809 W. Beach St, Watsonville

100% CONSTRUCTION

DOCUMENTS

Number Description Date

Rev.

Project :

PARKING LOT

IMPROVEMENTS

0 ISSUED FOR

CONSTRUCTION

2025-03-21

E-501

ELECTRICAL

SCHEDULES

LUMINAIRE SCHEDULE

SYMBOL

DESIG MANUFACTURER MODEL DESCRIPTION

TOTAL

INPUT

WATTS

VOLTS

REMARKS

MTG

S = SURFACE

R = RECESSED

P = POLE

PD = PENDANT

FL = FLUORESCENT

IN = INCANDESCENT

LAMP

WATTS TYP

QTY

MH = METAL HALIDE

LED = LIGHT EMITTING DIODE

A SIGNIFY

LUMINAIRE:

GARDCO GULLWING

POLE: GARDCO TRA

LUMINAIRE: TWO PER POLE

GL18-FAWS-**50LA-4835-NW-UNV-BRP-PC-IS-RPA2

** ROTATED OPTICS ONE 4-90

AND ONE 4-270

POLE:

TRA-CA-8/5-35-D2-DT2-BZ-VDA-AHH

LED POLE MOUNTED WET LOCATION LUMINAIRES, TWO LUMINAIRES ARRANGED AT 180 DEGREE SPACING WITH ROTATED

OPTICS TO ACHIEVE FORWARD THROW WITH TYPE 4 DISTRIBUTION, AND INTERNAL SHIELD TO LIMIT OFFSITE BACKLIGHT

SPILL. INCLUDE FIELD ADJUSTABLE WATTAGE SELECTOR TO LIMIT INDIVIDUAL LUMINAIRE OUTPUT TO 6,200 LUMENS MAX.

4000K CCT, 70 MIN. CRI. EQUIP EACH LUMINAIRE WITH PHOTOCELL AND SURGE PROTECTOR. PROVIDE ROUND POLE ADAPTER

FOR LUMINAIRE ATTACHMENT. LUMINAIRE TO BE ONE-PIECE DIE CAST ALUMINUM HOUSING WITH ELECTROSTATICALLY

APPLIED, THERMALLY CURED TEXTURED POLESTER POWDERCOAT FINISH. FINISH TO BE BRONZE TO MATCH POLE. LUMINAIRE

TO BE UL LISTED WITH WET LOCATION LABEL.

ROUND ALUMINUM TAPERED 35'-0" POLE WITH CAST ALUMINUM BASE. DRILL FOR TWO WAY LUMINAIRE MOUNTING AT 180°.

PROVIDE ONE HANDHOLE AT STANDARD +20" ABOVE BASE AND ADDITIONAL HANDHOLE AT APPROXIMATELY +36" ABOVE BASE.

INCLUDE POST TOP CAP, VIBRATION DAMPENER AND ACCESSIBLE GROUND LUG AT HANDHOLE. HANDHOLES TO BE COMPLETE

WITH ALUMINUM ACCESS DOOR COVER AND WEATHERPROOF GASKET. PROVIDE BASE COVER/NUT COVERS, ANCHOR BOLTS

AND TEMPLATE. FINISH WITH ELECTROSTATICALLY APPLIED, THERMALLY CURED POLYESTER POWDERCOAT. FINISH TO BE

BRONZE.

B

P105 W

PER LUMINAIRE

315W PER POLE

ASSEMBLY

-- LED

PROVIDE WITH 35'-0" POLE MOUNTED ON

CONCRETE BASE, 5'-0" AFG.

VERIFY ALL PART NUMBERS WITH VENDOR

PRIOR TO ORDERING EQUIPMENT.

PHOTOCELL, ADDITIONAL HANDHOLE

SIGNIFY

LUMINAIRE:

GARDCO GULLWING

POLE: GARDCO TRA

LUMINAIRE: THREE PER POLE

GL18-4-105LA-4870-NW-UNV-BRP-PC-RPA2

POLE:

TRA-CA-8/5-35-D3@120-DT2-BZ-VDA-AHH

LED POLE MOUNTED WET LOCATION LUMINAIRES, THREE LUMINAIRES ARRANGED AT 120 DEGREE SPACING WITH FORWARD

THROW TYPE 4 DISTRIBUTION. INDIVIDUAL LUMINAIRE OUTPUT 12802 LUMENS 4000K CCT, 70 MIN. CRI. EQUIP EACH LUMINAIRE

WITH PHOTOCELL AND SURGE PROTECTOR. PROVIDE ROUND POLE ADAPTERS FOR LUMINAIRE ATTACHMENT. LUMINAIRES TO

BE ONE-PIECE DIE CAST ALUMINUM HOUSING WITH ELECTROSTATICALLY APPLIED, THERMALLY CURED TEXTURED POLESTER

POWDERCOAT FINISH. FINISH TO BE BRONZE TO MATCH POLE. LUMINAIRE TO BE UL LISTED WITH WET LOCATION LABEL.

ROUND ALUMINUM TAPERED 35'-0" POLE WITH CAST ALUMINUM BASE. DRILL FOR THREE WAY LUMINAIRE MOUNTING AT 120°.

PROVIDE ONE HANDHOLE AT STANDARD +20" ABOVE BASE AND ADDITIONAL HANDHOLE AT APPROXIMATELY +36" ABOVE BASE.

INCLUDE POST TOP CAP, VIBRATION DAMPENER AND ACCESSIBLE GROUND LUG AT HANDHOLE. HANDHOLES TO BE COMPLETE

WITH ALUMINUM ACCESS DOOR COVER AND WEATHERPROOF GASKET. PROVIDE BASE COVER/NUT COVERS, ANCHOR BOLTS

AND TEMPLATE. FINISH WITH ELECTROSTATICALLY APPLIED, THERMALLY CURED POLYESTER POWDERCOAT. FINISH TO BE

BRONZE.

P

UNIVERSAL

120-277V

50 W MAX.

PER LUMINAIRE

100 W PER POLE

ASSEMBLY

-- LED

PROVIDE WITH 35'-0" POLE MOUNTED ON

CONCRETE BASE, 5'-0" AFG.

VERIFY ALL PART NUMBERS WITH VENDOR

PRIOR TO ORDERING EQUIPMENT.

ROTATED OPTICS, FIELD ADJUSTABLE

WATTAGE SELECTOR, PHOTOCELL,

ADDITIONAL HANDHOLE

REFER TO DETAIL 3/E-701

NOTE: ALL NEW CIRCUIT BREAKERS SHALL MATCH MAKE, MODEL AND AIC RATING OF EXISTING

PROVIDE CIRCUIT BREAKER AND WIRING

PROVIDE CIRCUIT BREAKER AND WIRING

PROVIDE WIRING TO (E) CIRCUIT BREAKER

PROVIDE WIRING TO (E) CIRCUIT BREAKER

PROVIDE CIRCUIT BREAKER AND WIRING

STATE OF CAL IFORNIA

RE

GI

ST

ER

ED

PROFESSIONAL ENGINEER

E16755

ELECTRICAL

S I M

ON PA U L J E

F

F

09/30/202167

03/21/2025

C

B

A

REUSE OF DOCUMENTS: THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE

PROPERTY OF JACOBS AND IS NOT TO BE USED, IN WHOLE OR IN PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF JACOBS.

Drawing Sheet Number:

554321 www.jacobs.com

©Jacobs Engineering Group Inc. 2025 ALL RIGHTS RESERVED

Project Number:

Paper Size: ARCH E1

Drawing Sheet Title:

Drawing Status:

Graphic Scale :

Revisions:

Project Client:

Seals:

E

4 Embarcadero Center, Suite 3800

San Francisco, CA 94105

P: 415-728-0850

W8Y13601

SANTA CRUZ METRO

809 W. Beach St, Watsonville

100% CONSTRUCTION

DOCUMENTS

Number Description Date

Rev.

Project :

PARKING LOT

IMPROVEMENTS

0 ISSUED FOR

CONSTRUCTION

2025-03-21

E-701

ELECTRICAL

DETAILS

STATE OF CAL IFORNIA

RE

GI

ST

ER

ED

PROFESSIONAL ENGINEER

E16755

ELECTRICAL

S I M

ON PA U L J E

F

F

09/30/202167

03/21/2025

File details come from the government source that posted it. Updated .