061000RoughCarpentry.docx

DOCX document 29 KB Posted

Attached to
Z2PZ--907-MM-FY24-006: Committal Shelter/Columbarium/Perimeter Fence Repair
Solicitation number
36C78625R0006
Issued by

About this file

This document is a technical specification for Section 06 10 00 Rough Carpentry, which is part of a larger federal contract opportunity.

The specification outlines the requirements for wood blocking, sheathing, furring, nailers, and rough hardware to be used in the construction project. It provides details on the performance requirements, submittals, product delivery and handling, applicable industry standards, and installation procedures for the rough carpentry work. Key requirements include using lumber and plywood products that meet certain grading and moisture content standards, utilizing waterborne or boron-based wood preservatives, and following specified installation methods for sheathing, blocking, nailers, and furring. The specification also includes requirements for biobased content in the lumber and plywood products. This technical specification supports the broader federal contract opportunity to repair a Committal Shelter, Columbarium, and Perimeter Fence at a National Cemetery facility.

View the file

Other files

File Type Posted
36C78625R0006 0003.docx DOCX document
36C78625R0006 0002.docx DOCX document
36C78625R0006 0001.docx DOCX document
Photo Library.docx DOCX document
013323ShopDrawingsProductData.docx DOCX document
Drawings_Volume 1.pdf PDF
Drawings_Volume 2.pdf PDF
062000FinCarpentry.docx DOCX document
Lump Sum Division Spreadsheet.xlsx XLSX spreadsheet
SOW 907-MM-FY24-006 Repair Committal Shelter.doc DOC document
076000FlashSheetMetal.docx DOCX document
Drawings_Volume 3.pdf PDF
36C78625R0006_1.docx DOCX document
Wage Determination_Multnomah County OR.txt TXT text file
074113MetalRoof.docx DOCX document
Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

10-01-23

SECTION 06 10 00

ROUGH CARPENTRY

PART 1 - GENERAL

1.1 DESCRIPTION

A. Section specifies wood blocking, sheathing, furring, nailers, and rough hardware.

1.2 RELATED WORK

A. Milled Woodwork: Section 06 20 00, FINISH CARPENTRY.

1.3 PERFORMANCE REQUIREMENTS

A.Not used
B.Engineered Wood Products:
1.Provide products with no added urea formaldehyde; determine formaldehyde concentrations in air from wood products under test conditions of temperature and relative humidity in accordance with ASTM D6007 or E1333.
2.Not used

1.4 Not used

1.5 SUBMITTALS

A.Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.
B.Provide documentation of conformance with performance requirements of this section.
C.Prepare shop drawings showing framing connection details, fasteners, connections and dimensions.

1.6 PRODUCT DELIVERY, STORAGE, AND HANDLING

A.Protect lumber and other products from dampness both during and after delivery at site.
B.Pile lumber in stacks in such manner as to provide air circulation around surfaces of each piece.
C.Stack plywood and other board products so as to prevent warping.
D.Locate stacks on well drained areas, supported at least 150 mm (6 inches) above grade and cover with well-ventilated sheds having firmly constructed over hanging roof with sufficient end wall to protect lumber from driving rain.

1.7 APPLICABLE PUBLICATIONS

A.Publications listed below form a part of this specification to extent referenced. Publications are referenced in text by the basic designation only. Comply with applicable provisions and recommendations of the following, except as otherwise shown or specified.
B.American Forest and Paper Association (AF&PA):

Wood Structural Design Data C. American Lumber Standard Committee, Incorporated (ALSC):

ALSC Board of Review

D.American National Standards Institute (ANSI):
ANSI A190.1-2022Structural Glued Laminated Timber
E.American Plywood Association (APA):
E30-2019Engineered Wood Construction Guide
F.American Society of Mechanical Engineers (ASME):
B18.2.1-(R2021)Square, Hex, Heavy Hex and Askew Head Bolts and Hex, Heavy Hex, Hex Flange, Lobed Head, and Lag Screws
B18.2.2-2010Hex Nuts for General Applications
B18.6.1-81 (R2008)Wood Screws
B18.6.4-98(R2005)Thread Forming and Thread Cutting Tapping Screws and Metallic Drive Screws
G.American Society for Testing and Materials (ASTM):
A307-21Carbon Steel Bolts and Studs, 60,000 PSI Tensile Strength
C954-18Steel Drill Screws for the Application of Gypsum Panel Products or Metal Plaster Bases to Steel Studs from 0.033 in. (0.84 mm) to 0.112 in. (2.84 mm) in Thickness
C1002-22Steel Self-Piercing Tapping Screws for the Application of Gypsum Panel Products or Metal Plaster Bases to Wood Studs or Steel Studs
D6007-22Determining Formaldehyde Concentration in Air from Wood Products Using a Small-Scale Chamber
E1333-22Determining Formaldehyde Concentrations in Air and Emission Rates from Wood Products Using a Large Chamber
F844-19Washers, Steel, Plan (Flat) Unhardened for General Use
F1667-11ae1Nails, Spikes, and Staples
H.American Wood Protection Association (AWPA)
I.FM Global Group (FM):
FM 4435(2014)Approval Standard for Edge Systems Used with Low Slope Roofing Systems
J.Green Seal (GS):
GS-36(2013) Commercial Adhesives
K.South Coast Air Quality Management District (SCAQMD):
SCAQMD Rule 1168(1989; R2005) Adhesive and Sealant Applications
L.U.S. Department of Commerce/National Institute of Science and Technology:
PS 1-09Structural Plywood
PS 20-10American Softwood Lumber Standard

PART 2 - PRODUCTS

2.1 LUMBER

A.Unless otherwise specified, each piece of lumber to bear a grade mark, stamp, or other identifying marks indicating grades of material, and rules or standards under which produced.
1.Identifying marks in accordance with rule or standard under which material is produced, including requirements for qualifications and authority of the inspection organization, usage of authorized identification, and information included in the identification.
2.Inspection agency for lumber approved by the Board of Review, American Lumber Standards Committee, to grade species used.
B.Structural Members: Species and grade as listed in the AF&PA, National Design Specification for Wood Construction having design stresses as shown.
C.Lumber Other Than Structural:
1.Unless otherwise specified, species graded under the grading rules of an inspection agency approved by Board of Review, American Lumber Standards Committee.
2.Framing lumber: Minimum extreme fiber stress in bending of 1100.
3.Furring, blocking, nailers and similar items 100 mm (4 inches) and narrower Standard Grade; and members 150 mm (6 inches) and wider, Number 2 Grade.
D.Sizes:
1.Conforming to Prod. Std. PS20.
2.Size references are nominal sizes, unless otherwise specified, actual sizes within manufacturing tolerances allowed by standard under which produced.
E.Moisture Content:
1.At time of delivery and maintained at the site.
2.Boards and lumber 50 mm (2 inches) and less in thickness: 19 percent or less.
3.Lumber over 50 mm (2 inches) thick: 25 percent or less.
F.Preservative Treatment:
1.Do not treat Heart Redwood and Western Red Cedar.
2.Products containing chromium or arsenic will not be permitted.
3.Provide products with waterborne or boron-based preservatives.
G.Waterborne Wood Preservatives:
1.Treat wood products with waterborne wood preservatives listed in Section 4 of AWPA Standards U1, excluding those which contain arsenic and/or chromium.
2.Pressure treatment of wood products must conform to the requirements of AWPA Standards U1 and T1.
3.Retention of preservatives as prescribed in AWPA Standard U1 for the following Use Categories (material conforming to a higher AWPA Use Category may be specified):
a.UC1: Interior construction - above ground, dry conditions.
b.UC2: Interior construction - above ground, damp conditions.
c.UC3A: Exterior construction - above ground, coated and with rapid water runoff.
d.UC3B: Exterior construction - above ground, uncoated or poor water runoff.
e.UC4A: General purpose soil or freshwater contact - heavy duty above ground.
f.UC4B: Heavy duty soil or freshwater contact - critical or difficult to replace components.
g.UC4C: Extreme duty soil or freshwater contact - critical structural components.
H.Boron-based Preservatives: Impregnate lumber with preservative treatment conforming to AWPA Standard U1.
I.Fire-retardant Treatment:
1.Fire-retardant-treated wood products to be free of halogens, sulfates, ammonium phosphate and formaldehyde.
2.Fire retardant treatment of wood products to conform to the requirements of AWPA Standard U1, Commodity Specification H and AWPA Standard T1, Section H.

SPEC WRITER NOTES:

2.2 PLYWOOD

A.Comply with Prod. Std. PS 1 and APA E30.
B.Bear the mark of a recognized association or independent inspection agency that maintains continuing control over quality of plywood which identifies compliance by veneer grade, group number, span rating where applicable, and glue type.
C.Sheathing:
1.APA rated Exposure 1 or Exterior; panel grade CD or better.
2.Wall Sheathing:
a.Minimum 9 mm (11/32 inch) thick with supports 400 mm (16 inches) on center and 12 mm (15/32 inch) thick with supports 600 mm (24 inches) on center unless specified otherwise.
b.Minimum 1200 mm (48 inches) wide at corners without corner bracing of framing.
3.Roof Sheathing:
a.Minimum 9 mm (11/32 inch) thick with span rating 24/0 or 12 mm (15/32 inch) thick with span rating for supports 400 mm (16 inches) on center unless specified otherwise.
b.Minimum 15 mm (19/32 inch) thick or span rating of 40/20 or 18 mm (23/32 inch) thick or span rating of 48/24 for supports 600 mm (24 inches) on center.

SPEC WRITER NOTES:

1. Specify other manufactured lumber if used. Allow options where possible.

2.3 ROUGH HARDWARE

A.Anchor Bolts: ASTM A307, size as indicated, complete with nuts and washers.
B.Washers:
1.ASTM F844.
2.Use zinc or cadmium coated steel or cast iron for washers exposed to weather.
C.Screws:
1.Wood to Wood: ANSI B18.6.1 or ASTM C1002.
2.Wood to Steel: ASTM C954, or ASTM C1002.
D.Nails:
1.ASTM F1667:
a.Common: Type I, Style 10.
b.Concrete: Type I, Style 11.
c.Barbed: Type I, Style 26.
d.Underlayment: Type I, Style 25.
e.Masonry: Type I, Style 27.

2.4 BLOCKING

A.General: Provide miscellaneous lumber as indicated and lumber support or attachment for other construction, including the following:
1.Blocking.
2.Nailers.
3.Furring.
B.Provide Standard or No. 2 Grade lumber.

2.5 Rough Carpentry Products shall comply with following standards for biobased materials:

Material Type
Percent by Weight
Lumber
25 percent biobased material
plywood
55 percent biobased material

The minimum-content standards are based on the weight (not the volume) of the material in the insulating core only.

PART 3 - EXECUTION

3.1 INSTALLATION OF FRAMING AND MISCELLANEOUS WOOD MEMBERS

A.Conform to applicable requirements of the following:
1.Comply with APA standards for installation of plywood.
B.Not Used
C.Not used
D.Sheathing:
1.Lay panels with joints staggered, with edge and ends 3 mm (1/8 inch) apart and nailed over bearings as specified.
2.Set nails not less than 9 mm (3/8 inch) from edges.
3.Install 50 mm by 100 mm (2 inch by 4 inch) blocking spiked between studs to support edge or end joints of panels.
E.Wood Roof Nailers, Edge Strips, Crickets, Curbs, and Cants: Provide sizes and configurations indicated or specified and anchored securely to continuous construction.
1.Roof Edge Strips and Nailers: Provide at perimeter of roof, around openings through roof, and where roofs abut walls, curbs, and other vertical surfaces.
2.Except where indicated otherwise, nailers to be 150 mm (6 inches) wide and the same thickness as the insulation. Anchor nailers securely to underlying construction.
3.Not used
4.Not used
F.Wood Blocking: Provide proper sizes and shapes at proper locations for the installation and attachment of wood and other finish materials, fixtures, equipment, and items indicated or specified.
G.Wood Grounds: Provide for fastening wood trim, finish materials, and other items to plastered walls and ceilings. Install grounds in proper alignment and true with a 2400 mm (8 foot) straightedge.
H.Wood Furring:
1.Provide where shown and as necessary for facing materials specified.
2.Except as shown otherwise, furring strips to be nominal one by 3, continuous, and spaced 400 mm (16 inches) o.c. Erect furring vertically or horizontally as necessary.
3.Nail furring strips to masonry.
4.Do not use wood plugs.
5.Provide furring strips around openings, behind bases, and at angles and corners.
6.Furring to be plumb, rigid, and level and shimmed as necessary to provide a true, even plane with surfaces suitable to receive the finish required.

3.2 Protection

A.Protect rough carpentry from weather.
B.If rough carpentry becomes wet, apply EPA-registered borate treatment complying with EPA registered label.

- - - E N D - - -

ROUGH CARPENTRY

06 10 00 - 2