These are preliminary 30% review drawings for the Town of Frisco's Well 7 PFAS (Per- and Polyfluoroalkyl Substances) Mitigation Improvements project, prepared by Plummer Associates, Inc. in association with Atlos Architects, BCER, and Repella Consulting Engineers. The documents cover a comprehensive set of engineering and architectural drawings detailing the proposed water treatment facility, including site plans, building layouts, mechanical and electrical systems, process flow diagrams, and hydraulic profiles. The project involves constructing a new treatment building at the existing Well 7 location, featuring two treatment vessels, chemical storage rooms, associated piping and equipment, electrical and instrumentation systems, and site improvements.
The drawings indicate a treatment facility designed to mitigate PFAS contamination, with key components including a 15,000-gallon chlorine contact pressure vessel, treatment vessels, cartridge filters, pumps, chemical injection systems for sodium hypochlorite and sodium hydroxide, and supporting infrastructure. The facility will be located on a site near the Nordic Center Lodge in Frisco, Colorado, with an elevation around 9,075 feet. The design appears to be in the preliminary review stage, marked explicitly as "not intended for construction, bidding, or permit purposes," suggesting the project is still in the early design phase and will undergo further refinement before potential construction procurement.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Plummer Associates, Inc.
TAYLOR M. GERTIG, P.E., PROJECT MANAGERPATRICK J. O'BRIEN, P.E., PRINCIPAL
TOWN OF FRISCO
PRELIMINARY REVIEW DRAWINGS FOR:
WELL 7 PFAS MITIGATION IMPROVEMENTS
1221 AURARIA PKWY | DENVER, COLORADO 80204
303.300.3464 | www.plummer.com
Plummer Associates, Inc.
MAY 2024
IN ASSOCIATION WITH:
DATE:
CO P.E. NO.
TAYLOR M. GERTIG
57138
THESE DOCUMENTS ARE
FOR INTERIM REVIEW AND
ARE NOT INTENDED FOR
CONSTRUCTION, BIDDING,
OR PERMIT PURPOSES.
02/24/2023DATE:
CO P.E. NO.
PATRICK J. O'BRIEN
33925
THESE DOCUMENTS ARE
FOR INTERIM REVIEW AND
ARE NOT INTENDED FOR
CONSTRUCTION, BIDDING,
OR PERMIT PURPOSES.
02/24/2023
OWNER'S ADDRESS
102 SCHOOL ROAD
PO BOX 4100
FRISCO CO 80443
9057.59
RED CAP 15242
9053.66
RED CAP 15242
9054.61
RED CAP 1524216
9056.90
BLM S35/S36
9068.26
CDOT 1029
LPLPLP
UG
E
UGE
DU
M
PS
TE
R
GR
AT
E
LI
GH
TP
O
LE
BE
N
CH
SE
W
ER
M
AN
HO
LE
RI
M E
L.
=9
6.
2'
GA
S
GAS
GAS
GAS
U
GT
W W
O U
TL
ET
BO
LL
AR
D
N O
RD
IC
CE
N
TE
R
LO
DG
E
DE
CK
RAMP
HY
DR
AN
T
SE
W
ER
M
AN
HO
LE
RI
M E
L.
=9
6.
2'
SE
W
ER
M
AN
HO
LE
RI
M E
L.
=9
1.
3'
CONC.
DECK
W
EL
L
EDGE OF ASPHALT
EDGE OF ASPHALT
EDGE OF ASPHALT
EDGE OF ASPHALT
EDGE OF ASPHALT
CO
N
C.
RE
C
PA
TH
SI
GN
DI
SK
G O
LF
SI
GN
U
TI
LI
TY
PA
N
EL
RECREATION WAY
CO
N
CR
ET
E
CO
N
C.
W
W
SE
W
ER
M
AN
HO
LE
SE
W
ER
M
AN
HO
LE
LI
FT
ST
AT
IO
N
IN
VE
RT
IN
2.
IN
VE
RT
O U
T
.7
5'
IN
VE
RT
IN
2.
IN
VE
RT
O U
T
.1
3'
IN
VE
RT
IN
(S E)
3.
IN
VE
RT
IN
(S
W ) 9
3.
IN
VE
RT
O
U T
.4 7'
GR
AV
EL
P
AT
H
GRAVEL PATH
RECREATION PATH 21
M
ET
ER
S TR
AN
SF
O
RM
ER
3.
5'
M
ET
AL
LI
D 3.
5' L
ID
2.
5'
L
ID
CL
EA
N O
U T
TOP OF BANK
CONCRETE
M
ET
AL
GA
TE
TO
E
TO
P
O F
BA
N
K
TO
E O
F
BA
N K
GA
TE
VA
LV
ES
GR
AV
EL
R
O
AD
GR
AV
EL
P
AT
H
LP
LP
LP
W
W
W
W
W
W
UGE
UGE
UGE
UG
E
UG
E
UG
E
UG
E
U
GE
UG
E
UGE
UGE
UGE
UGE
UGE
DU
M
PS
TE
R
GR
AT
E
LI
GH
TP
O
LE
BE
N
CH
SE
W
ER
M
AN
HO
LE
RI
M E
L.
=9
6.
2'
GA
S
GA
S
GA
S
GA
S
GA
S
GAS
GASGAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
UG
E
UG
E
UGE
UGE
UGE
UGE
UGE
UGE
U
GE
UG
E
UGE
GA
S
GA
S
GAS
UGT
UGT
U
GT
UGT
UGT
UGT
W
W
W W W W W
W W
W W W W
W
W
O U
TL
ET
BO
LL
AR
D
N O
RD
IC
CE
N
TE
R
LO
DG
E
DE
CK
RAMP
HY
DR
AN
T
SE
W
ER
M
AN
HO
LE
RI
M E
L.
=9
6.
2'
SE
W
ER
M
AN
HO
LE
RI
M E
L.
=9
1.
3'
CONC.
DEC
K
W
EL
L
EDGE OF ASPHALT
EDGE OF ASPHALT
EDGE OF ASPHALT
EDGE OF ASPHALT
EDGE OF ASPHALT
CO
N
C.
RE
C
PA
TH
SI
GN
DI
SK
G O
LF
SI
GN
U
TI
LI
TY
PA
N
EL
RECREATION WAY
CO
N
CR
ET
E
CO
N
C.
UGE
UGE
U
GE
UGE
UGE
UGE
UGE
UGE
W W
W W
W
W
W W
W
W W
W W
W
IN
VE
RT
IN
2.
IN
VE
RT
O U
T
.7
5'
IN
VE
RT
IN
2.
IN
VE
RT
O U
T
.1
3'
IN
VE
RT
IN
(S E)
3.
IN
VE
RT
IN
(S
W ) 9
3.
IN
VE
RT
O
U T
.4 7'
GR
AV
EL
P
AT
H
GRAVEL PATH
RECREATION PATH
SS
SS
SS
SS
M
ET
ER
S TR
AN
SF
O
RM
ER
3.
5'
M
ET
AL
LI
D 3.
5' L
ID
2.
5'
L
ID
CL
EA
N O
U T
TOP OF BANK
CONCRETE
M
ET
AL
GA
TE
TO
E
TO
P
O F
BA
N
K
TO
E O
F
BA
N K
GA
TE
VA
LV
ES
GR
AV
EL
R
O
AD
GR
AV
EL
P
AT
H
UGE
UGE
G-001
GE
N
ER
AL
VI
CI
N
IT
Y M
AP
A
N D
SH
EE
T
IN
DE
X
M. FREYTAG
M. RAGAY
T. GERTIG
P. O'BRIEN
N
Dwg.
No.
Seq.
RE
VI
SI
O
N
BY
DA
TE
N O
TO
W
N O
F
FR
IS
CO
W
EL
L
PF
AS
M
IT
IG
AT
IO
N
IM
PR
O
VE
M
EN
TS
SC
HO
O L
RO
AD
PO
B
O X
FR
IS
CO
C
O
DESIGNED
CHECKED
REVIEWED
DRAWN
PR
IN
TE
D:
/1
0/
:2
PM
C
U se rs
\r pe m be rt on
\D C\
AC
CD
oc s\
Pl um m er
A ss oc ia te s\
-0
-0 9_
W
EL
L_ 7\
Pr oj ec t F ile s\
Pl um m er
\S he et s\
Ge ne ra l\G
-0
V
IC
IN
IT
Y M
AP
A
N D
SH
EE
T
IN
DE
X.
dw g
S
AV
ED
: 5
/9 /2
5:
P M
S
AV
ED
B
Y:
R pe m be rt on U
SE
R:
P em be rt on , R on
4131-002-09
IF THIS BAR DOES NOT
MEASURE ONE INCH,
DRAWING IS NOT TO
LABELED SCALE
N C
AP
IT
AL
O
F
TX
H W
Y, S
TE
A
U
ST
IN
, T
X
2.
2.
T
BP
E
RE
GI
ST
ER
ED
F
IR
M
N U
M
BE
R F-
DATE:
CO P.E. NO.
NICHOLAS E. TOUSSAINT
34211
THESE DOCUMENTS ARE
FOR INTERIM REVIEW AND
ARE NOT INTENDED FOR
CONSTRUCTION, BIDDING,
OR PERMIT PURPOSES.
04/24/2024
DATE:
CO P.E. NO.
TAYLOR M. GERTIG
57138
THESE DOCUMENTS ARE
FOR INTERIM REVIEW AND
ARE NOT INTENDED FOR
CONSTRUCTION, BIDDING,
OR PERMIT PURPOSES.
02/24/2023
INDEX OF DRAWINGS
SEQ # SHEET TITLE
GENERAL
1. G-000 COVER SHEET
2. G-001 SHEET LIST AND AND VICINITY MAP
3. G-002 GENERAL NOTES
4. G-003 CIVIL AND MECHANICAL SYMBOLS AND ABBREVIATIONS
5. G-004 PROCESS FLOW DIAGRAM AND HYDRAULIC PROFILE
6. G-005 HYDRAULIC PROFILE
7. G-006 PIPE SCHEDULE AND DESIGN CRITERIA
CIVIL
8. C-100 OVERALL EXISTING SITE PLAN
9. C-101 PROPOSED SITE PLAN PLAN
10. C-102 PROPOSED YARD PIPING PLAN
11. C-103 ENLARGED GRADING AND SITE COORDINATE PLAN
ARCHITECTURAL
12. A-001 ARCHITECTURAL GENERAL NOTES
13. A-100 BUILDING PLAN
14. A-101 BUILDING ELEVATIONS I
15. A-102 BUILDING ELEVATIONS II
STRUCTURAL
16. S-001 STRUCTURAL GENERAL NOTES
17. S-100 BUILDING STRUCTURAL PLAN
18. S-101 BUILDING SECTIONS I
19. S-102 BUILDING SECTIONS II
20. S-103 BUILDING SECTIONS III
21. S-104 BUILDING SECTIONS IV
MECHANICAL
22. M-100 TREATMENT BUILDING PLAN
23. M-101 TREATMENT BUILDING SECTIONS I
24. M-102 TREATMENT BUILDING SECTIONS II
25. M-103 PUMP AREA SECTIONS I
26. M-104 PUMP AREA SECTIONS II
HVAC
27. H-001 HVAC GENERAL NOTES
28. H-100 HVAC PLAN
29. H-101 HVAC SECTIONS I
30. H-102 HVAC SECTIONS II
ELECTRICAL
31. E-001 PROVISIONS AND NOTES
32. E-002 LEGEND
33. E-100 SITE PLAN
34. E-101 ONE-LINE DIAGRAM
35. E-102 SCHEDULES
36. E-103 POWER PLAN
37. E-104 LIGHTING PLAN
38. E-105 GROUNDING PLAN
INSTRUMENTATION
39. I-001 LEGEND AND SYMBOLS
40. I-100 EXISTING P&ID
41. I-101 PROPOSED TREATMENT SYSTEM P&ID
42. I-102 NETWORK ARCHITECTURE
43. I-103 INSTRUMENT PLAN
44.
STANDARD DETAILS
45. A-900 ARCHITECTURAL DETAILS I
46. A-901 ARCHITECTURAL DETAILS II
47. S-900 STRUCTURAL DETAILS I
48. S-901 STRUCTURAL DETAILS II
49. M-900 MECHANICAL DETAILS I
50. M-901 MECHANICAL DETAILS II
51. H-900 HVAC DETAILS I
52. H-901 HVAC DETAILS II
53. E-900 CONTROL SCHEMATICS
54. E-901 GROUNDING SCHEMATIC
55. E-902 ELECTRICAL STANDARD DETAILS I
56. E-903 ELECTRICAL STANDARD DETAILS II
VICINITY MAP
SCALE: 1"=100'
NORDIC CENTER LODGERECREATION
PATH
PENINSULA ROAD/
RECREATION WAY
PROJECT LOCATION
SUMMIT BLVD
SU
M
M
IT BLVD
E MAIN ST
LOCATION MAP
SCALE: 1"=500'
PEN
IN
SU
LA
RD/
REC
REA
TIO
N W
AY
PITKIN ST
DILLON
RESERVOIR
PENINSULA
RECREATION
AREA
N
PROPOSED TREATMENT
BUILDING
EXISTING WELL 7
BUILDING
* SHEET NOT INCLUDED IN 30% REVIEW SET
EMATICS
I-104 INSTRUMENT PLAN II*
Dwg.
No.
Seq.
RE
VI
SI
O
N
BY
DA
TE
N O
TO
W
N O
F
FR
IS
CO
W
EL
L
PF
AS
M
IT
IG
AT
IO
N
IM
PR
O
VE
M
EN
TS
SC
HO
O L
RO
AD
PO
B
O X
FR
IS
CO
C
O
DESIGNED
CHECKED
REVIEWED
DRAWN
PR
IN
TE
D:
/1
0/
:2
PM
C
U se rs
\r pe m be rt on
\D C\
AC
CD
oc s\
Pl um m er
A ss oc ia te s\
-0
-0 9_
W
EL
L_ 7\
Pr oj ec t F ile s\
Pl um m er
\S he et s\
Ge ne ra l\G
-0
G
EN
ER
AL
N O
TE
S.
dw g
S
AV
ED
: 5
/9 /2
5:
P M
S
AV
ED
B
Y:
R pe m be rt on U
SE
R:
P em be rt on , R on
4131-002-09
IF THIS BAR DOES NOT
MEASURE ONE INCH,
DRAWING IS NOT TO
LABELED SCALE
N C
AP
IT
AL
O
F
TX
H W
Y, S
TE
A
U
ST
IN
, T
X
2.
2.
T
BP
E
RE
GI
ST
ER
ED
F
IR
M
N U
M
BE
R F-
DATE:
CO P.E. NO.
NICHOLAS E. TOUSSAINT
34211
THESE DOCUMENTS ARE
FOR INTERIM REVIEW AND
ARE NOT INTENDED FOR
CONSTRUCTION, BIDDING,
OR PERMIT PURPOSES.
04/24/2024
DATE:
CO P.E. NO.
TAYLOR M. GERTIG
57138
THESE DOCUMENTS ARE
FOR INTERIM REVIEW AND
ARE NOT INTENDED FOR
CONSTRUCTION, BIDDING,
OR PERMIT PURPOSES.
02/24/2023
1. CONTRACTOR SHALL CONFINE CONSTRUCTION OPERATIONS WITHIN THE OWNER'S EXISTING
EASEMENTS AND RIGHTS-OF-WAY AND THE CONSTRUCTION LIMITS INDICATED ON THE DRAWINGS, AND SHALL USE DUE CARE IN PLACING CONSTRUCTION TOOLS, EQUIPMENT, EXCAVATED
MATERIALS, MATERIALS AND SUPPLIES, SO AS TO CAUSE NO DAMAGE TO PROPERTY OR
INTERFERENCE WITH OTHER CONSTRUCTION ACTIVITIES. CONTRACTOR SHALL BE RESPONSIBLE FOR
PROTECTION OF ALL EXISTING ASPHALT AND CONCRETE FROM CONSTRUCTION EQUIPMENT.
DAMAGED ASPHALT AND CONCRETE SHALL BE REPLACED IN KIND BY THE CONTRACTOR, AT HIS OR
HER EXPENSE.
2. CONTRACTOR SHALL LOCATE, POTHOLE AND VERIFY THE LOCATIONS OF ALL EXISTING PIPING
PRIOR TO START OF CONSTRUCTION. WHERE CONNECTIONS ARE TO BE MADE, CONTRACTOR
SHALL VERIFY THE EXISTING MATERIAL TYPE PRIOR TO ORDERING ANY CONNECTION FITTINGS OR APPURTENANCES REQUIRED FOR THE CONNECTIONS. ALL CONNECTIONS TO EXISTING UTILITIES SHALL BE DONE IN A WAY SO AS TO MINIMIZE DISRUPTION IN SERVICE TO EXISTING USERS.
3. ALL MATERIALS AND WORKMANSHIP SHALL BE SUBJECT TO INSPECTION BY THE OWNER. THE
OWNER RESERVES THE RIGHT TO ACCEPT OR REJECT ANY MATERIALS AND WORKMANSHIP THAT
DOES NOT CONFORM TO STANDARDS AND SPECIFICATIONS.
4. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE FOLLOWING:
(A) ALL LICENSES AND PERMITS REQUIRED FOR CONSTRUCTION.
(B) THE NOTIFICATION OF THE PROPER AUTHORITIES PRIOR TO CONSTRUCTION AND A
PRECONSTRUCTION MEETING WITH THE OWNER, AND ENGINEER OF RECORD.
5. ALL PAVEMENT SAW CUTS SHALL BE 90° TO ONE ANOTHER.
6. THE CONTRACTOR SHALL PROTECT, REPAIR OR REPLACE ANY UTILITY IN KIND INCLUDING BUT NOT LIMITED TO: RESIDENTIAL SERVICES, WATER LINES, SEWER LINES, STORM DRAINS, ETC., THAT WAS
REMOVED OR DAMAGED DURING CONSTRUCTION.
7. ALL MANHOLES/VALVE RINGS AND COVERS SHALL BE INSTALLED WITH CONCRETE COLLARS UNLESS
OTHERWISE NOTED.
8. ALL KNOWN SEWERS, WATER MAINS, GAS MAINS, TELEPHONE CONDUITS, ELECTRIC CABLES, AND
OTHER UNDERGROUND STRUCTURES ARE SHOWN ON THE DRAWINGS ONLY TO THE EXTENT SUCH
INFORMATION HAS BEEN MADE AVAILABLE TO OR DISCOVERED BY THE ENGINEER. IT IS EXPECTED
THAT THERE MAY BE DISCREPANCIES AND OMISSIONS IN THE LOCATION AND QUANTITIES OF
UTILITIES AND STRUCTURES SHOWN. THIS INFORMATION IS SHOWN FOR THE CONVENIENCE OF
THE CONTRACTOR BUT IS NOT GUARANTEED TO BE EITHER CORRECT OR COMPLETE AND ALL
RESPONSIBILITY FOR THE ACCURACY AND COMPLETENESS THEREOF IS EXPRESSLY DISCLAIMED.
CONTRACTOR SHALL MAKE SUCH INVESTIGATION AS HE OR SHE THINKS NECESSARY TO VERIFY ITS CORRECTNESS AND COMPLETENESS. CONTRACTOR SHALL, AHEAD OF EXCAVATION, AND PRIOR TO
ORDERING OF ANY PRODUCTS FOR THE PROJECT, LOCATE ALL UNDERGROUND UTILITIES AND
STRUCTURES SO THAT THEY WILL NOT BE ACCIDENTALLY CUT BY CONSTRUCTION ACTIVITIES.
CONTRACTOR SHALL CONTACT THE UTILITY INFORMATION CENTER AT 811 AT LEAST 48 HOURS
PRIOR TO ANY DIGGING.
9. THE CONTRACTOR SHALL BE SOLELY AND COMPLETELY RESPONSIBLE FOR CONDITIONS AT AND
ADJACENT TO THE JOB SITE, INCLUDING SAFETY OF ALL PERSONS AND PROPERTY DURING
PERFORMANCE OF THE WORK. THIS REQUIREMENT SHALL APPLY CONTINUOUSLY AND IS NOT
LIMITED TO NORMAL WORKING HOURS.
10. THE CONTRACTOR SHALL PROVIDE ALL LIGHTS, SIGNS, BARRICADES, FLAGMEN OR OTHER DEVICES
NECESSARY TO PROVIDE FOR PUBLIC SAFETY IN ACCORDANCE WITH THE CURRENT MANUAL ON
UNIFORM TRAFFIC CONTROL DEVICES (M.U.T.C.D.).
11. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL VEHICULAR AND PEDESTRIAN TRAFFIC
CONTROL DURING THE ENTIRE LENGTH OF THE PROJECT.
12. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL TRAFFIC CONTROL PLANS & PERMITTING.
13. THE CONTRACTOR SHALL CONTACT THE UTILITY NOTIFICATION CENTER OF COLORADO (UNCC) AT 1-800-922-1987, AT LEAST 2 WORKING DAYS PRIOR TO BEGINNING EXCAVATION OR GRADING, TO HAVE ALL REGISTERED UTILITY LOCATIONS MARKED. OTHER UNREGISTERED UTILITY ENTITIES ARE TO BE LOCATED BY CONTACTING THE RESPECTIVE REPRESENTATIVE. UTILITY SERVICE LATERALS ARE
ALSO TO BE LOCATED PRIOR TO BEGINNING EXCAVATION OR GRADING.
14. ALL DISTURBED SOIL, ON OR OFF-SITE, AND RELATED TO WORK AT THIS PROJECT SITE, IS REQUIRED
TO BE PROTECTED FROM WIND AND STORM WATER EROSION. THE CONTRACTOR IS RESPONSIBLE
FOR OBTAINING A STORMWATER MANAGEMENT PERMIT AND ABIDING BY THE PERMIT
OBLIGATIONS. THE CONTRACTOR IS RESPONSIBLE FOR INSTALLATION AND MAINTENANCE OF
STORMWATER BEST PRACTICES UNTIL FINAL STABILIZATION IS ACHIEVED.
15. ANY DISRUPTION OF UTILITY SERVICE THAT IS REQUIRED TO ADJUST, EXTEND, RELOCATE OR
OTHERWISE MODIFY ANY UTILITY WITHIN THE PROJECT AREA SHALL BE COORDINATED IN
ADVANCE WITH THE OWNER AND OWNER SHALL BE NOTIFIED 48 HOURS PRIOR TO THE START OF
DISRUPTION.
16. THE CONTRACTOR SHALL BE RESPONSIBLE FOR INSURING THAT NO MUD OR DEBRIS SHALL BE
TRACKED ONTO THE EXISTING PUBLIC STREET SYSTEM. MUD AND DEBRIS MUST BE REMOVED
IMMEDIATELY BY AN APPROPRIATE METHOD (I.E. MACHINE BROOM SWEEP, LIGHT DUTY
FRONT-END LOADER, HANDWORK, ETC.) AND APPROVED BY THE INSPECTOR.THE FREQUENCY AND
EFFORT OF STREET CLEANING OPERATIONS SHALL BE DIRECTLY RELATED TO THE AMOUNT OF
CONSTRUCTION TRAFFIC AND WEATHER CONDITIONS. THE CONTRACTOR SHALL IMMEDIATELY
ADDRESS ANY STREET CLEANING PROBLEMS IDENTIFIED BY THE OWNER.
17. CONTRACTOR SHALL COORDINATE ALL WORK WITH THE OWNER.
18. CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS, ELEVATIONS, MATERIALS, AND
CONDITIONS PRIOR TO INITIATING WORK.
19. CONTRACTOR SHALL SUPPORT AND PROTECT ALL EXISTING UTILITIES AND STRUCTURES
FROM DAMAGE THAT MAY OCCUR DURING CONSTRUCTION. CONTRACTOR SHALL
REPLACE ITEMS AND REPAIR STRUCTURES DAMAGED BY CONSTRUCTION AND/OR
DEMOLITION TO THE SATISFACTION OF THE OWNER AT NO ADDITIONAL COST TO THE
OWNER. CONTRACTOR SHALL TOUCH-UP ITEMS THAT ARE AFFECTED DURING
CONSTRUCTION. AREAS IMPACTED BY CONSTRUCTION ACTIVITIES INCLUDING BUT NOT
LIMITED TO GRASS AREAS, SIDEWALKS, ROADS, STRUCTURES,PIPING, AND EQUIPMENT
SHALL BE RETURNED TO A CONDITION EQUAL TO OR BETTER THAN EXISTING, AS
DETERMINED BY THE OWNER.
20. CONTRACTOR SHALL NOT OPERATE ANY EXISTING VALVES DURING CONSTRUCTION. ALL
EXISTING VALVE OPERATIONS SHALL BE COORDINATED WITH AND PERFORMED BY THE
OWNER.
21. CONTRACTOR SHALL COORDINATE ELECTRICAL, INSTRUMENTATION, AND PIPING.
22. EXISTING VALVES, PIPELINES, AND STRUCTURES WILL LEAK IN THE CLOSED POSITION.
CONTRACTOR SHALL PROVIDE WHATEVER MEANS AND EQUIPMENT NECESSARY TO
CONTROL WATER DURING CONSTRUCTION.
23. ALL ANCHOR BOLTS, EXPANSION ANCHORS, AND CONCRETE INSERTS SHALL BE 304
STAINLESS STEEL UNLESS OTHERWISE NOTED.
24. ALL SURFACES AND MATERIALS IN CONTACT WITH WATER SHALL COMPLY WITH THE
REQUIREMENTS OF THE SAFE DRINKING WATER ACT AND SHALL CONFORM TO NSF-61.
PRODUCT SHALL BEAR THE MARK OR SEAL OF AN ACCREDITED TESTING LABORATORY.
25. FURNISH AND INSTALL INSULATED BOLT AND GASKET SET AT CONNECTIONS BETWEEN
DISSIMILAR METALS.
26. PIPE SUPPORTS SHOWN ON THE DRAWINGS ARE FOR ILLUSTRATIVE PURPOSES AND DO
NOT SHOW ALL SUPPORTS AT THE REQUIRED SPACING.REFER TO SECTION 40 05 07
"HANGERS AND SUPPORTS FOR PROCESS SYSTEMS" FOR PIPE SUPPORT SPACING
REQUIREMENT.
27. ALL EQUIPMENT, VALVES, FITTINGS, MATERIALS, ETC., REMOVED IN CONJUNCTION WITH
THE CONTRACTORS ACTIVITIES ON THIS PROJECT ARE THE PROPERTY OF THE OWNER AND
SHALL BE OFFERED TO THEM FOR THEIR CONTINUED USE.
28. CONTRACTOR SHALL REMOVE DEMOLISHED MATERIAL FROM THE PROJECT AREA
INCLUDING DEMOLISHED VALVES, EQUIPMENT, AND PIPING, CONCRETE RUBBLE AND
DEBRIS RESULTING FROM DEMOLITION, TRASH, ETC. TO AN APPROPRIATE OFF SITE
LOCATION.
29. REFERENCE ELECTRICAL PLANS FOR ELECTRICAL CONDUIT, DUCT BANKS, RACEWAYS, LIGHT
POLES, AND MANHOLES.
GENERAL NOTES (CONTINUED):
G-002
GE
N
ER
AL
GE
N
ER
AL
N O
TE
S
M. FREYTAG
M. RAGAY
T. GERTIG
P. O'BRIEN
GENERAL NOTES
AT NO COST TO THE OWNER.
SEWER MANHOLE
SURVEY CATEGORY
CONTROL MONUMENT
SECTION CORNER
WATER MAIN
SEWER MAIN
SEWER FORCEMAIN
STORM DRAIN
W W
SS SS
FM FM
SD SD
PROPOSED FEATURES
RAW WATER MAIN RW RW
WATER VALVE
SURVEY MONUMENT
SEE DESCRIPTION
EASEMENT LINE
CONTOUR - MAJOR
CONTOUR - MINOR5541
FIRE HYDRANT
Dwg.
No.
Seq.
RE
VI
SI
O
N
BY
DA
TE
N O
TO
W
N O
F
FR
IS
CO
W
EL
L
PF
AS
M
IT
IG
AT
IO
N
IM
PR
O
VE
M
EN
TS
SC
HO
O L
RO
AD
PO
B
O X
FR
IS
CO
C
O
DESIGNED
CHECKED
REVIEWED
DRAWN
PR
IN
TE
D:
/1
0/
:3
PM
C
U se rs
\r pe m be rt on
\D C\
AC
CD
oc s\
Pl um m er
A ss oc ia te s\
-0
-0 9_
W
EL
L_ 7\
Pr oj ec t F ile s\
Pl um m er
\S he et s\
Ge ne ra l\G
-0
G
EN
ER
AL
S
YM
BO
LS
A N
D
AB
BR
EV
IA
TI
O N
S.
dw g S
AV
ED
: 5 /9
/2
5:
P
M S
AV
ED
B Y:
R pe m be rt on
U
SE
R:
P em be rt on
, R on
4131-002-09
IF THIS BAR DOES NOT
MEASURE ONE INCH,
DRAWING IS NOT TO
LABELED SCALE
N C
AP
IT
AL
O
F
TX
H W
Y, S
TE
A
U
ST
IN
, T
X
2.
2.
T
BP
E
RE
GI
ST
ER
ED
F
IR
M
N U
M
BE
R F-
DATE:
CO P.E. NO.
NICHOLAS E. TOUSSAINT
34211
THESE DOCUMENTS ARE
FOR INTERIM REVIEW AND
ARE NOT INTENDED FOR
CONSTRUCTION, BIDDING,
OR PERMIT PURPOSES.
04/24/2024
DATE:
CO P.E. NO.
TAYLOR M. GERTIG
57138
THESE DOCUMENTS ARE
FOR INTERIM REVIEW AND
ARE NOT INTENDED FOR
CONSTRUCTION, BIDDING,
OR PERMIT PURPOSES.
02/24/2023
G-003
GE
N
ER
AL
SY
M
BO
LS
A N
D
AB
BR
EV
IA
TI
O N
S
M. FREYTAG
M. RAGAY
T. GERTIG
P. O'BRIEN
AIR RELEASE/VACUUM RELIEF VALVE
BALL CHECK VALVE
BUTTERFLY VALVE
BALL VALVE
CHECK VALVE
GLOBE VALVE
GATE VALVE
PLUG VALVE
PUMP
SUMP PUMP
MOTOR OPERATOR
PNEUMATIC OPERATOR
SOLENOID
BLIND FLANGE
REDUCER
CHEMICAL INJECTOR
MIXER
PRESSURE GAUGE W/
DIAPHRAGM
SYMBOLS
VERTICAL TURBINE PUMP
FLOW METER
UV REACTOR
PIPING MATERIAL INDEX
ABS ACRYLONITRILE BUTADIENE STYRENE
BS BLACK STEEL
BR BRASS
CH CHROME IRON ALLOY
CIP CAST IRON PIPE (GRAY IRON)
CPVC CHLORINATED POLYVINYL CHLORIDE
CU COPPER TUBING
DIP DUCTILE IRON PIPE
DT DRAIN TILE
FRP FIBERGLASS REINFORCED PLASTIC
GL GLASS LINED PIPE
GS GALVANIZED STEEL PIPE
PE POLYETHYLENE PIPE
PET POLYETHYLENE TUBING
PP PERFORATED PVC PIPE
PVC POLYVINYL CHLORIDE (PVC PIPE)
RCP REINFORCED CONCRETE
RCCP REINFORCED CONCRETE CYLINDER
RS RUBBER LINED STEEL PIPE
STL STEEL PIPE
SS STAINLESS STEEL
SST STAINLESS STEEL TUBING
VCP VITRIFIED CLAY
PIPING CONNECTION INDEX
AFF ABOVE FINISH FLOOR
B BELL
BF BLIND FLANGE
BFV BUTTERFLY VALVE
BV BALL VALVE
BW BUTT WELD
C COUPLED
FCA FLANGED COUPLING ADAPTER
FLG FLANGE
G GROOVED
MJ MECHANICAL JOINT
PE PLAIN END
PO PUSH-ON JOINT
S SPIGOT
SC SCREWED
SV SOLVENT WELD
SW SOCKET WELD
T THREADED
WV WATER VALVE
PROCESS ABBREVIATION INDEX
BWS BACKWASH SUPPLY
BWW BACKWASH TO WASTE
BYP BYPASS
D DRAIN
FIL FILTERED WATER
FILL MEDIA INLET FILL
FW FINISHED WATER
NaOCI SODIUM HYPOCHLORITE NaOH CAUSTIC SODA
NC NORMALLY CLOSED
RW RAW WATER
TVE TREATMENT VESSEL EFFLUENT
V VENT
48/RCY/DIP
48/RCY/DIP
PIPE SIZE IN INCHES
PROCESS ABBREVIATION
NEW
EXISTING
PIPE CALLOUT FORMAT
PROCESS LINE TYPE
EXISTING
NEW
PIPE MATERIAL
BACK FLOW PREVENTER
RADAR LEVEL SENSOR
CONCRETE
GRAVEL
EARTH
GATE VALVE
EXISTING POWER POLE
SOIL BORING LOCATION
EXISTING LIGHT PEDESTAL
EXISTING BARBED WIRE FENCE
EXISTING UNDERGROUND GAS LINE
EXISTING UNDERGROUND TELEPHONE
EXISTING UNDERGROUND ELECTRIC LINE
DRAINAGE FLOWLINE
EXISTING GAS METER
EXISTING WATER METER
EXISTING WELL
ROCK/ RIPRAP
COORDINATE
PROPERTY LINE
PVC FITTING
WELDED FITTING
CUT PIPE
SILT FENCE
EXISTING STORM INLET
WATTLE/LOG SEDIMENT BARRIER
FINISHED MAJOR CONTOUR
EXISTING MAJOR CONTOUR
SURFACE FLOW DIRECTION
FINISHED MINOR CONTOUR
EXISTING MINOR CONTOUR
PROPOSED CHAIN LINK FENCE
PROPOSED WROUGHT IRON FENCE
UT
UGE
EXISTING UNDERGROUND FIBER OPTICFO
G
SAFETY GRATING
EXISTING TELEPHONE PEDESTAL
EXISTING TRANSFORMER
EXISTING VAULT
EXISTING ELECTRICAL BOX
EXISTING WATER BOX
EXISTING FIRE HYDRANT
FLANGED FITTING
MECHANICAL JOINT FITTING
EXISTING CLEANOUT
EXISTING VALVE BOX
SLIDE GATE
NEW FIRE HYDRANT
PLUG VALVE
EXISTING OVERHEAD ELECTRIC LINEOHE
EXISTING SANITARY SEWER LINESAN
EXISTING STORM SEWER LINE
EXISTING WATER LINEW
STRAW BALE SEDIMENT BARRIER
ROW LINE
ASPEN TREE
SPRUCE TREE
SEWER MANHOLE
SURVEY CONTROL POINT
UTILITY PEDISTAL
SPOT ELEVATION
LIMITS OF CONSTRUCTION
PINE TREE
STATIC MIXER
Seq.
RE
VI
SI
O
N
BY
DA
TE
N O
TO
W
N O
F
FR
IS
CO
W
EL
L
PF
AS
M
IT
IG
AT
IO
N
IM
PR
O
VE
M
EN
TS
SC
HO
O L
RO
AD
PO
B
O X
FR
IS
CO
C
O
DESIGNED
CHECKED
REVIEWED
DRAWN
PR
IN
TE
D:
/1
0/
:3
PM
C
U se rs
\r pe m be rt on
\D C\
AC
CD
oc s\
Pl um m er
A ss oc ia te s\
-0
-0 9_
W
EL
L_ 7\
Pr oj ec t F ile s\
Pl um m er
\S he et s\
Ge ne ra l\G
-0
P
RO
CE
SS
F
LO
W D
IA
GR
AM
.d w g
S
AV
ED
: 5
/9 /2
5:
P M
S
AV
ED
B
Y:
R pe m be rt on U
SE
R:
P em be rt on , R on
4131-002-09
IF THIS BAR DOES NOT
MEASURE ONE INCH,
DRAWING IS NOT TO
LABELED SCALE
N C
AP
IT
AL
O
F
TX
H W
Y, S
TE
A
U
ST
IN
, T
X
2.
2.
T
BP
E
RE
GI
ST
ER
ED
F
IR
M
N U
M
BE
R F-
DATE:
CO P.E. NO.
NICHOLAS E. TOUSSAINT
34211
THESE DOCUMENTS ARE
FOR INTERIM REVIEW AND
ARE NOT INTENDED FOR
CONSTRUCTION, BIDDING,
OR PERMIT PURPOSES.
04/24/2024
DATE:
CO P.E. NO.
TAYLOR M. GERTIG
57138
THESE DOCUMENTS ARE
FOR INTERIM REVIEW AND
ARE NOT INTENDED FOR
CONSTRUCTION, BIDDING,
OR PERMIT PURPOSES.
02/24/2023
G-004
GE
N
ER
AL
PR
O
CE
SS
F
LO
W D
IA
GR
AM
M. FREYTAG
M. RAGAY
T. GERTIG
P. O'BRIEN
WELL PUMP
15,000 GALLON
CHLORINE CONTACT
PRESSURE VESSEL
T-400
INSIDE
BUILDING
OUTSIDE
BUILDING
TO DISTRIBUTION
SYSTEM
CAM LOCK
8/RW/DIP
8/
RW
/D
IP
WELL 7 PROCESS FLOW DIAGRAM
INSIDE TREATMENT
BUILDING
OUTSIDE BUILDING
8/BWS 8/BWS
4/FILL
(TYP)
8/TVE
BACKWASH TO
WASTE/DRAIN TO
SEWER
8/BWW
8/
BW
W
SA
M
PL
E
SA
M
PL
E
8/RW
8/TVE/DIP
8/
BW
W
VENT VENT NaOH
INJECTION
NaOCI
INJECTION
TREATMENT VESSEL 1 TREATMENT VESSEL 2
SODIUM
HYPOCHLORITE
TANK
DISCHARGE
BLEED
PD
CHEMICAL PANEL
SODIUM HYPOCHLORITE
SODIUM
HYDROXIDE
TANK
DISCHARGE
BLEED
VENT
CHEMICAL PANEL
SODIUM HYDROXIDE
8/RW/BYPASS
VENT
Seq.
RE
VI
SI
O
N
BY
DA
TE
N O
TO
W
N O
F
FR
IS
CO
W
EL
L
PF
AS
M
IT
IG
AT
IO
N
IM
PR
O
VE
M
EN
TS
<C
LI
EN
T
AD
DR
ES
S>
DESIGNED
CHECKED
REVIEWED
DRAWN
PR
IN
TE
D:
/1
8/
:3
AM
C
U se rs
\r pe m be rt on
\D C\
AC
CD
oc s\
Pl um m er
A ss oc ia te s\
-0
-0 9_
W
EL
L_ 7\
Pr oj ec t F ile s\
Pl um m er
\S he et s\
Ge ne ra l\G
-0
H
YD
RA
U
LI
C
PR
O
FI
LE
.d w g S
AV
ED
: 4 /1
6/
:3
PM
S
AV
ED
B Y:
R pe m be rt on
U
SE
R:
P em be rt on
, R on
4131-002-09
IF THIS BAR DOES NOT
MEASURE ONE INCH,
DRAWING IS NOT TO
LABELED SCALE
N C
AP
IT
AL
O
F
TX
H W
Y, S
TE
A
U
ST
IN
, T
X
2.
2.
T
BP
E
RE
GI
ST
ER
ED
F
IR
M
N U
M
BE
R F-
DATE:
CO P.E. NO.
TAYLOR M. GERTIG
57138
THESE DOCUMENTS ARE
FOR INTERIM REVIEW AND
ARE NOT INTENDED FOR
CONSTRUCTION, BIDDING,
OR PERMIT PURPOSES.
02/24/2023
G-005
GE
N
ER
AL
HY
DR
AU
LI
C
PR
O
FI
LE
M. FREYTAG
M. RAGAY
T. GERTIG
P. O'BRIEN
Distribution System
FF EL 9061.5
HGL EL 9250.6
Treatment Vessel
Notes
1.WELL NO. 7 IS PERMITTED FOR AN INSTANTANEOUS PUMPING
RATE UP TO 650 GPM. THE ANNUAL AMOUNT OF
GROUNDWATER TO APPROPRIATED UNDER THE WELL PERMIT IS
UP TO 887 ACRE-FT (550 GPM). DRAWDOWN LEVEL ASSUME AN
AVERAGE OF THE TWO MAXIMUM PUMPING RATES.
HGL
EL 9098.7
HGL at 200 GPM HGL at 650 GPM HGL at 650 GPM (WITH BOOSTER PUMP)
HGL EL 9230.8
GR EL 9075.0
Treatment BuildingWell House Peninsula Storage
HGL EL 9279.0 89
N
C
AP
IT
AL
O F
TX
H
W Y, S
TE
A U
ST
IN
, T X
2.
2.
T
BP
E
RE
GI
ST
ER
ED
F
IR
M N
U M
BE
R
F-
SC
HO
O L
RO
AD
PO
B
O X
FR
IS
CO
C
O
LP
LP
LP
W
W
W
W
W
W
W
W
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
GAS
GAS GAS GAS GAS GAS GAS
GA
S
GA
S
GA
S
GA
S
GA
S
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
UGE
UGE
UGE
U
GE UG
E
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE UGE
UGE
UGE
GAS
GAS
GAS
GAS
UGT
UGT
UGT UGT
UGT
UGT
UGT
W
W
W
W W
W W
W W
W W
W W
W W
W W
W
W
W
UGE
UGE
UGE
UGE
UGE
UGE UGE UGE UGE UGE
UG
E
U
GE
UG
E
UGE
UGE
UGE
UGE
UGE
W
W W
W W
W
W
W
W W
W W
W
W W
W W
W W
SS
SS
SS
SS
SS
SS
SS
SS
U
GE
UGE
U
GE
NORDIC
CENTER
LODGE
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
Dwg.
No.
Seq.
RE
VI
SI
O
N
BY
DA
TE
N O
TO
W
N O
F
FR
IS
CO
W
EL
L
PF
AS
M
IT
IG
AT
IO
N
IM
PR
O
VE
M
EN
TS
SC
HO
O L
RO
AD
PO
B
O X
FR
IS
CO
C
O
DESIGNED
CHECKED
REVIEWED
DRAWN
PR
IN
TE
D:
/1
3/
:2
PM
C
U se rs
\r pe m be rt on
\D C\
AC
CD
oc s\
Pl um m er
A ss oc ia te s\
-0
-0 9_
W
EL
L_ 7\
Pr oj ec t F ile s\
Pl um m er
\S he et s\
CI
VI
L\ C-
O
VE
RA
LL
S
IT
E
PL
AN
.d w g
S
AV
ED
: 5
/1 3/
1:
A
M S
AV
ED
B Y:
R pe m be rt on
U
SE
R:
P em be rt on
, R on
4131-002-09
IF THIS BAR DOES NOT
MEASURE ONE INCH,
DRAWING IS NOT TO
LABELED SCALE
N C
AP
IT
AL
O
F
TX
H W
Y, S
TE
A
U
ST
IN
, T
X
2.
2.
T
BP
E
RE
GI
ST
ER
ED
F
IR
M
N U
M
BE
R F-
DATE:
CO P.E. NO.
TAYLOR M. GERTIG
57138
THESE DOCUMENTS ARE
FOR INTERIM REVIEW AND
ARE NOT INTENDED FOR
CONSTRUCTION, BIDDING,
OR PERMIT PURPOSES.
02/24/2023
C-100
CI
VI
L
O
VE
RA
LL
E
XI
ST
IN
G
SI
TE
P
LA
N
M. FREYTAG
M. RAGAY
T. GERTIG
P. O'BRIEN
N
GRAVEL
COMMUNITY
TRAIL
PAVED
COMMUNITY
TRAIL
ARV MH
CHLORINE CONTACT
PRESSURE VESEL
CHEMICAL
ROOM
US FOREST SERVICE
SEWER MANHOLE
4/D/PVC
CLEANOUT
WELL 7
BUILDING
8/RW/DIP
12/FW
METERS
BACKUP
GENERATOR
8" GATE VALVE
(TYP 2)
8/FW/DIP
TRANSFORMER
RECREATION WAY
RAMP
CONCRETE PAD
DUMPSTER
PARKING LOT
SIDEWALK
GRAVEL DRIVEWAY
CONCRETE PAD
GRAPHIC SCALE : 1" = 16'
8 3216016 000
NOTES
1. 1. REFER TO G-002 FOR ADDITIONAL NOTES.
2. PROJECT BENCHMARK HELD ELEVATION 9127.79 FT NGS
SURVEY CONTROL MONUMENT "B449". NAVD 88.
3. BASIS OF BEARINGS: THE FOUND MONUMENTS ALONG
THE EAST BOUNDARY LINE OF WOODEN CANOE AT
WATER DANCE ON LAKE DILLON, BEING N 00°08'04" W.
RECEPTION NUMBER 517527.
OVERALL EXISTING SITE PLAN
LP
LP
LP
W
W
W
W
W
W
W
W
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
GAS
GAS GAS GAS GAS GAS GAS
GA
S
GA
S
GA
S
GA
S
GA
S
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
UGE
UGE
UGE
UGE UG
E
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE UGE
UGE
UGE
GAS
GAS
GAS
GAS
UGT
UGT
UGT UGT
UGT
UGT
UGT
W
W
W
W W
W W
W W
W W
W W
W W
W W
W
W
W
UGE
UGE
UGE
UGE
UGE
UGE UGE UGE UGE UGE
UG
E
U
GE
UG
E
UGE
UGE
UGE
UGE
UGE
W
W W
W W
W
W
W
W W
W W
W
W W
W W
W W
SS
SS
SS
SS
SS
SS
SS
SS
U
GE
UGE
U
GE
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
Dwg.
No.
Seq.
RE
VI
SI
O
N
BY
DA
TE
N O
TO
W
N O
F
FR
IS
CO
W
EL
L
PF
AS
M
IT
IG
AT
IO
N
IM
PR
O
VE
M
EN
TS
SC
HO
O L
RO
AD
PO
B
O X
FR
IS
CO
C
O
DESIGNED
CHECKED
REVIEWED
DRAWN
PR
IN
TE
D:
/1
3/
:2
PM
C
U se rs
\r pe m be rt on
\D C\
AC
CD
oc s\
Pl um m er
A ss oc ia te s\
-0
-0 9_
W
EL
L_ 7\
Pr oj ec t F ile s\
Pl um m er
\S he et s\
CI
VI
L\ C-
1_
PR
O
P_
SI
TE
_P
LA
N
.d w g S
AV
ED
: 5 /1
3/
1:
A M
S
AV
ED
B
Y:
R pe m be rt on U
SE
R:
P em be rt on , R on
4131-002-09
IF THIS BAR DOES NOT
MEASURE ONE INCH,
DRAWING IS NOT TO
LABELED SCALE
N C
AP
IT
AL
O
F
TX
H W
Y, S
TE
A
U
ST
IN
, T
X
2.
2.
T
BP
E
RE
GI
ST
ER
ED
F
IR
M
N U
M
BE
R F-
DATE:
CO P.E. NO.
TAYLOR M. GERTIG
57138
THESE DOCUMENTS ARE
FOR INTERIM REVIEW AND
ARE NOT INTENDED FOR
CONSTRUCTION, BIDDING,
OR PERMIT PURPOSES.
02/24/2023
C-101
CI
VI
L
PR
O
PO
SE
D
SI
TE
P
LA
N
M. FREYTAG
M. RAGAY
T. GERTIG
P. O'BRIEN
N
GRAVEL
COMMUNITY
TRAIL
NORDIC
CENTER
LODGE
PAVED COMMUNITY TRAIL
ARV MH
CHLORINE CONTACT
PRESSURE VESEL
CHEMICAL
ROOM
4/D/PVC
CLEANOUT
WELL 7
8/RW/DIP
8/FW
12/FW
METERS
BACKUP
GENERATOR
8" GATE VALVE
(TYP 2)
8/FW/DIP
LIGHTPOLE
BOLLARD (TYP)
RAMPHYDRANT
CONC.
REC PATH
SIGN
UTILITY
PANEL
RECREATION W
AY
DUMPSTER
GRAVEL ROAD
MH
TRANSFORMER
US FOREST SERVICE
SEWER
US FOREST SERVICE SEWER
(ESTIMATED LOCATION)
MHSEWER MANHOLE
TREATMENT
BUILDING
GRAVEL
DRIVEWAY
BUILDING
XX
XXXX
GRAPHIC SCALE : 1" = 16'
8 3216016 000
SPLIT RAIL FENCE XX
XXXX
SIDEWALK
PARKING LOT
CONCRETE
PAD
PAVED
DRIVEWAY
XX
XXX
PROPOSED SITE PLAN
NOTES
1. REFER TO G-002 FOR ADDITIONAL NOTES.
2. REFER TO YARD PIPING PLAN FOR PROPOSED
UNDERGROUND PIPING.
3. REFER TO SITE COORDINATE AND GRADING PLAN
FOR SITE COORDINATES AND SITE IMPROVEMENTS.
LIMITS OF CONSTRUCTION
W
W
W
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE UGE UGE UGE
UGE
UGE
UGE
GAS
GAS
GAS
GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS
GA
S
GA
S
GA
S
GA
S
GA
S
GA
S
GA
S
GA
S
GA
S
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
W
W
W
W
W
W
W
W W
W W
W W
W W
W W
W W
W W
W
UGE
UGE UGE UGE UGE
UGE UGE UGE UGE UGE
UGE UGE UGE
UGE
UGE
UGE
UG
E
UG
E
U
GE
U
GE
U
GE
UGE
UG
E
UG
E
UGE
UGE
UGE
UGE
UGE
W W
W W
W W
W W
W W
W W
W W
W W
W
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
W
WU
GE
U
GE
UGE
UGE
U
GE
U
GE
U
GE
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
GRAVEL COMMUNITY TRAIL
ARV MH
CHLORINE CONTACT
PRESSURE VESEL
CHEMICAL
ROOM
4/D/PVC
CLEANOUT
WELL 7 BUILDING
8/RW/DIP
8/FW
12/FW
METERS
BACKUP
GENERATOR
8" GATE VALVE
(TYP 2)
8/FW/DIP
REC PATH
SIGN
UTILITY
PANEL
GRAVEL ROAD
TRANSFORMER
US FOREST SERVICE
SEWER
US FOREST SERVICE SEWER
(ESTIMATED LOCATION)
MH
SEWER MANHOLE
TREATMENT BUILDING
GRAVEL DRIVEWAY
Dwg.
No.
Seq.
RE
VI
SI
O
N
BY
DA
TE
N O
TO
W
N O
F
FR
IS
CO
W
EL
L
PF
AS
M
IT
IG
AT
IO
N
IM
PR
O
VE
M
EN
TS
SC
HO
O L
RO
AD
PO
B
O X
FR
IS
CO
C
O
DESIGNED
CHECKED
REVIEWED
DRAWN
PR
IN
TE
D:
/1
3/
:2
PM
C
U se rs
\r pe m be rt on
\D C\
AC
CD
oc s\
Pl um m er
A ss oc ia te s\
-0
-0 9_
W
EL
L_ 7\
Pr oj ec t F ile s\
Pl um m er
\S he et s\
CI
VI
L\ C-
2_
PR
O
P_
YP
_P
LA
N .d w g
S
AV
ED
: 5
/1 3/
1:
A
M S
AV
ED
B Y:
R pe m be rt on
U
SE
R:
P em be rt on
, R on
4131-002-09
IF THIS BAR DOES NOT
MEASURE ONE INCH,
DRAWING IS NOT TO
LABELED SCALE
N C
AP
IT
AL
O
F
TX
H W
Y, S
TE
A
U
ST
IN
, T
X
2.
2.
T
BP
E
RE
GI
ST
ER
ED
F
IR
M
N U
M
BE
R F-
DATE:
CO P.E. NO.
TAYLOR M. GERTIG
57138
THESE DOCUMENTS ARE
FOR INTERIM REVIEW AND
ARE NOT INTENDED FOR
CONSTRUCTION, BIDDING,
OR PERMIT PURPOSES.
02/24/2023
C-102
CI
VI
L
PR
O
PO
SE
D
YA
RD
P
IP
IN
G
PL
AN
M. FREYTAG
M. RAGAY
T. GERTIG
P. O'BRIEN
N
XX
XXX
GRAPHIC SCALE : 1" = 8'
4 16808 000NOTES
1. REFER TO G-002 FOR ADDITIONAL NOTES.
2. REFER TO SHEET C-103 FOR PAVING AND
GRADING IN THIS AREA
8/TVE/DIP
8/RW/DIP
8" GATE VALVE
AND VALVE BOX
(TYP 3)
XX
XXXX
8/D/PVC
MIN 2'-6"
PROPOSED YARD PIPING PLAN
LP
LP
LP
W
W
W
W
W
W
W
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE UGE
UGE
UGE
UGE
UGE
UGE
UGE
GAS
GAS GAS GAS GAS GAS GAS
GA
S
GA
S
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
UGE
UGE
UGE
UGE UG
E
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE
UGE UGE
UGE
UGE
GAS
GAS
GAS
GAS
UGT
UGT
UGT UGT
UGT
UGT
UGT
W
W
W
W
W
UGE
UGE
UGE
UGE
UGE
UGE UGE UGE UGE UGE
UG
E
UG
E
UGE
UGE
UGE
UGE
UGE
W
W W
W W
W
W
W
W W
W W
W
W W
W W
W
SS
SS
SS
SS
SS
SS
SS
SS
U
GE
UGE
U
GE
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
U
GE
UGE
U
GE
90759075
90759076
Dwg.
No.
Seq.
RE
VI
SI
O
N
BY
DA
TE
N O
TO
W
N O
F
FR
IS
CO
W
EL
L
PF
AS
M
IT
IG
AT
IO
N
IM
PR
O
VE
M
EN
TS
SC
HO
O L
RO
AD
PO
B
O X
FR
IS
CO
C
O
DESIGNED
CHECKED
REVIEWED
DRAWN
PR
IN
TE
D:
/1
3/
:2
PM
C
U se rs
\r pe m be rt on
\D C\
AC
CD
oc s\
Pl um m er
A ss oc ia te s\
-0
-0 9_
W
EL
L_ 7\
Pr oj ec t F ile s\
Pl um m er
\S he et s\
CI
VI
L\ C-
3_
PA
V_
GR
AD
IN
G_
PL
AN
.d w g S
AV
ED
: 5 /1
3/
1:
A M
S
AV
ED
B
Y:
R pe m be rt on U
SE
R:
P em be rt on , R on
4131-002-09
IF THIS BAR DOES NOT
MEASURE ONE INCH,
DRAWING IS NOT TO
LABELED SCALE
N C
AP
IT
AL
O
F
TX
H W
Y, S
TE
A
U
ST
IN
, T
X
2.
2.
T
BP
E
RE
GI
ST
ER
ED
F
IR
M
N U
M
BE
R F-
DATE:
CO P.E. NO.
TAYLOR M. GERTIG
57138
THESE DOCUMENTS ARE
FOR INTERIM REVIEW AND
ARE NOT INTENDED FOR
CONSTRUCTION, BIDDING,
OR PERMIT PURPOSES.
02/24/2023
CI
VI
L
M. FREYTAG
M. RAGAY
T. GERTIG
P. O'BRIEN
N
GRAVEL
COMMUNITY
TRAIL
NORDIC
CENTER
LODGE
PAVED COMMUNITY TRAIL
ARV MH
CHLORINE CONTACT
PRESSURE VESEL
CHEMICAL
ROOM
4/D/PVC
CLEANOUT
WELL 7
8/RW/DIP
12/FW
METERS
BACKUP
GENERATOR
8" GATE VALVE
(TYP 2)
8/FW/DIP
GRAPHIC SCALE : 1" = 16'
8 3216016
LIGHTPOLE
BOLLARD (TYP)
RAMPHYDRANT
CONC.
REC PATH
SIGN
UTILITY
PANEL
RECREATION W
AY
RELOCATE DUMPSTER
REFER TO SHEET C-XXXX
GRAVEL ROAD
TRANSFORMER
US FOREST SERVICE
SEWER
US FOREST SERVICE SEWER
(ESTIMATED LOCATION)
TREATMENT BUILDING
FFE, UPPER LEVEL 9075.0
FFE LOWER LEVEL 9061.50
GRAVEL
DRIVEWAY
BUILDING
C-103
EN
LA
RG
ED
S
IT
E
CO
O
RD
IN
AT
E
AN
D
GR
AD
IN
G
PL
AN
XX
XXX
SEWER MANHOLE
RIM EL.=9076.2'
NOTES
1. CONTRACTOR TO RESTORE SITE GRADING TO MATCH
EXISTING CONDITIONS UNLESS OTHERWISE NOTED.
SIDEWALK
PARKING LOT
PAVED
DRIVEWAY
XX
XXX
ENLARGED SITE COORDINATE AND GRADING PLAN
31' - 6"
/2
NaOH
STORAGE
ROOM
NaOCl
STORAGE
ROOM
8" STATIC MIXER
TO CHLORINE CONTACT TANK
(REFER TO YARD PIPING
PLAN FOR CONTINUATION)
FROM WELL 7 PUMP
(REFER TO YARD PIPING
PLAN FOR CONTINUATION)
WALL PENETRATION
XXX
60' - 2"
8" TEE (TYP )
CHEMICAL STORAGE TOTE
(TYP 5)
8" SWING
CHECK VALVE(TYP 2)
RFCA(TYP 2)
CENTRIFUGAL PUMP
(TYP 2)
8" 90° BEND
(TYP)
TO SEWER
(REFER TO YARD PIPING
PLAN FOR CONTINUATION)
TREATMENT
VESSEL NO. 1
TREATMENT
VESSEL NO. 2
CARTRIDGE FILTER
(TYP 4)
PLATFORM
(REF. TO STRUCTURAL)
12 FT OVERHEAD DOOR
PERSONNEL DOOR
(TYP 3)
8/TVE/DIP
8/BWW/DIP
STAIRS TO
OPERATING FLOOR
A M-102
B M
-1
HANDRAIL
(TYP )
12' - 0"
/2 " 9
/2
CMU BUILDING
(REF. TO STRUCTURAL)
8/RW/DIP
(BYPASS)
8" HANDWHEEL BFV
(TYP 5)
FRP GRATING
(REFER TO STRUCTURAL)
PIPE TRENCH
CONCRETE LANDING
(TYP)
(TYP )
ø 2' -
6"
52' - 6"
6' - 8"
4 FT ELECTRICAL
CLEARANCE AREA 4
ELECTRICAL EQUIPMENT AREA
8/RW/DIP
8/TVE/DIP
6' - 8"
8" STATIC MIXER
TO CHLORINE CONTACT TANK
(REFER TO YARD PIPING
PLAN FOR CONTINUATION)
FROM WELL 7 PUMP
(REFER TO YARD PIPING
PLAN FOR CONTINUATION)
WALL PENETRATION
XXXCMU BUILDING
(REF. TO STRUCTURAL)
8/RW/DIP
(BYPASS)
NN
DESIGNED
Dwg.
No.
DRAWN
CHECKED
REVIEWED
IF THIS BAR DOES NOT
MEASURE ONE INCH,
DRAWING IS NOT TO
LABELED SCALE
Seq. of
THESE DOCUMENTS ARE
FOR INTERIM REVIEW AND
ARE NOT INTENDED FOR
CONSTRUCTION, BIDDING
OR PERMIT PURPOSES.
TAYLOR M. GERTIG
CO P.E. NO. 57138
P R
IN
T
E D
M E
C H
A N
IC
A
L
/1
/2
:5
:3
P M
A u to d e sk
D o cs
/4
-0
-0
W E
LL
/N
W
T R
E A
T M
E N
T
V E
S
SE
L_ B
U
IL
D
IN
G
M .r v t
TO
W
N O
F
FR
IS
C
O W
EL
L
P
FA
S
M
IT
IG
A
TI
O
N
IM
P R
O V
EM
EN
TS
TR
EA
TM
E
N T
B U
IL
D
IN
G
P
LA
N
4131-002-09
M-100
P. O'BRIEN
W.DAGM
M. FREYTAG
T. GERTIG
S
C H
O O
L R
O A
D
P O
B O
X
F R
IS
C
O C
O
A U
R A
R
IA
P K
W Y
D
E N
V E
R
C O
-3
-3
T
B P
E R
E G
IS
T
E R
E D
F
IR
M N
U M
B E
R F
-1
SCALE: 3/8" = 1'-0"
TREATMENT BUILDING PLAN
N O
D A T E
R E V
IS
IO
N
B Y
DATE: 05/10/2024
4/FILL/DIP
C/L 9082.00
12 FT
OVERHEAD DOOR
TOC EL 9075.00
TOC EL 9061.50
8/TVE/DIP
C/L 9058.50
TOC EL 9075.00
CENTRIFUGAL PUMP
(TYP 2)
EQUIPMENT PAD
(TYP 2)
TREATMENT VESSEL 2TREATMENT VESSEL 1
6/RW/DIP
55 GAL DRUM
ARV(TYP )
NN
DESIGNED
Dwg.
No.
DRAWN
CHECKED
REVIEWED
IF THIS BAR DOES NOT
MEASURE ONE INCH,
DRAWING IS NOT TO
LABELED SCALE
Seq. of
THESE DOCUMENTS ARE
FOR INTERIM REVIEW AND
ARE NOT INTENDED FOR
CONSTRUCTION, BIDDING
OR PERMIT PURPOSES.
TAYLOR M. GERTIG
CO P.E. NO. 57138
P R
IN
T
E D
M E
C H
A N
IC
A
L
/1
/2
:5
:5
P M
A u to d e sk
D o cs
/4
-0
-0
W E
LL
/N
W
T R
E A
T M
E N
T
V E
S
SE
L_ B
U
IL
D
IN
G
M .r v t
TO
W
N O
F
FR
IS
C
O W
EL
L
P
FA
S
M
IT
IG
A
TI
O
N
IM
P R
O V
EM
EN
TS
TR
EA
TM
E
N T
B U
IL
D
IN
G
S
EC
TI
O
N I
4131-002-09
M-102
P. O'BRIEN
W.DAGM
M. FREYTAG
T. GERTIG
S
C H
O O
L R
O A
D
P O
B O
X
F R
IS
C
O C
O
A U
R A
R
IA
P K
W Y
D
E N
V E
R
C O
-3
-3
T
B P
E R
E G
IS
T
E R
E D
F
IR
M N
U M
B E
R F
-1
SCALE: 3/8" = 1'-0"
SECTION A
N O
D A T E
R E V
IS
IO
N
B
8/TVE/DIP
C/L/9068.82
8/BWW/DIP
C/L/9058.50
8/RW/DIP
C/L 9065.32
TOC EL 9061.50
8" HANDWHEEL
BFV
6" / 12"
6" / 12"
4/FILL/DIP
C/L 9082.00
CARTRIDGE FILTER
(TYP)
TREATMENT
VESSEL(TYP 2)
GRADE EL 9075.00
TOP OF MAS.
EL 9080.46
ARV(TYP )
NN
DESIGNED
Dwg.
No.
DRAWN
CHECKED
REVIEWED
IF THIS BAR DOES NOT
MEASURE ONE INCH,
DRAWING IS NOT TO
LABELED SCALE
Seq. of
THESE DOCUMENTS ARE
FOR INTERIM REVIEW AND
ARE NOT INTENDED FOR
CONSTRUCTION, BIDDING
OR PERMIT PURPOSES.
TAYLOR M. GERTIG
CO P.E. NO. 57138
P R
IN
T
E D
M E
C H
A N
IC
A
L
/1
/2
:5
:0
P M
A u to d e sk
D o cs
/4
-0
-0
W E
LL
/N
W
T R
E A
T M
E N
T
V E
S
SE
L_ B
U
IL
D
IN
G
M .r v t
TO
W
N O
F
FR
IS
C
O W
EL
L
P
FA
S
M
IT
IG
A
TI
O
N
IM
P R
O V
EM
EN
TS
TR
EA
TM
EN
T B
U
IL
D
IN
G S
EC
TI
O N
II
4131-002-09
M-103
P. O'BRIEN
W.DAGM
M. FREYTAG
T. GERTIG
S
C H
O O
L R
O A
D
P O
B O
X
F R
IS
C
O C
O
A U
R A
R
IA
P K
W Y
D
E N
V E
R
C O
-3
-3
T
B P
E R
E G
IS
T
E R
E D
F
IR
M N
U M
B E
R F
-1
SCALE: 3/8" = 1'-0"
SECTION B
N O
D A T E
R E V
IS
IO
N
B
BALL CHECK VALVE
SWING CHECK VALVE
DOUBLE DOOR CHECK VALVE
BALL VALVE
V-PORT BALL VALVE
SPRAY NOZZLE
HOSE STATION
YARD HYDRANT
EYE WASH STATION
CONE VALVE
DIAPHRAGM VALVE
SLEEVE OR PLUNGER VALVE
NEEDLE VALVE
3-WAY VALVE
PETCOCK VALVE
4-WAY VALVE
SPRING LOADED PRESSURE RELIEF
VALVE
SURGE RELIEF VALVE
PRESSURE REGULATING VALVE
FLOW CONTROL VALVE
SLIDE GATE
SLIDE GATE
SUBMERSIBLE PRESSURE/LEVEL
FLOAT SWITCH
WEIR GATE
STOP GATE
IN-LINE PRESSURE DIAPHRAGM
MAGNETIC FLOW METER - FULL
MAGNETIC FLOW METER - INSERT
ULTRASONIC FLOW METER
VENTURI TUBE FLOW METER
PARSHALL FLUME FLOW METER
EJECTOR
EDUCTOR
ULTRASONIC LEVEL
DIFFUSER
VENTED BALL VALVE
RADAR LEVEL
PROPELLER/TURBINE/PADDLEWHEEL
FLOW METER
EQUIPMENT SYMBOLS PROCESS LINE TYPESFIELD INSTRUMENT SYMBOLSVALVE SYMBOLSFITTING SYMBOLS
BACK PRESSURE VALVE
MUD VALVE
M MOTORIZED
P PNEUMATIC
E ELECTRIC
AIR/VACUUM RELEASE VALVE
PULSATION DAMPENER
FLAP GATE
FAIL OPENFO
FAIL CLOSEFC
FAIL INDETERMINATEFI
FAIL AS ISFAI
NORMALLY OPENNO
NORMALLY CLOSEDNC
LOCKED OPENLO
LOCKED OPENLC
MODULATINGM
TYPICAL VALVE ANNOTATIONS
UNION
BLIND FLANGE
CLEANOUT
PLUG
QUICK COUPLING
REDUCER
FLEXIBLE HOSE
FLEXIBLE COUPLING
SIGHT GLASS
OFF GAS DEMISTER
Y STRAINER
SLUICE GATE
ROTAMETER
RUPTURE DISK
DRAIN
SILENCER
AIR FILTER
CALIBRATION CHAMBER
FINE BUBBLE DIFFUSER
COURSE BUBBLE DIFFUSER
STATIC MIXER
ELLIPTICAL/DIAPHRAGM CONTROL
VALVE
KNIFE GATE VALVE
BUTTERFLY VALVE
PLUG VALVE
PINCH VALVE
GLOBE VALVE
GATE AND ACTUATOR SYMBOLS
THERMAL MASS FLOW METER
ORIFICE
UNDEFINED FLOW METER
UNDEFINED INSTRUMENT
INSTRUMENTATION IDENTIFICATION
INSTRUMENT
NUMBER
ANALYTICAL ELEMENTAE
ANALYTICAL INDICATING TRANSMITTERAIT
FLOW ELEMENTFE
FLOW INDICATING TRANSMITTERFIT
FLOW/LEVEL INDICATING TRANSMITTERF/LIT
FLOW SWITCHFS
FLOW SWITCH LOWFSL
FLOW TOTALIZER INDICATORFQI
LEVEL ELEMENTLE
LEVEL INDICATING TRANSMITTERLIT
LEVEL SWITCH HIGHLSH
LEVEL SWITCH HIGH HIGHLSHH
LEVEL SWITCH SWITCHESLSs
LEVEL TRANSMITTERLT
PRESSURE DIFFERENTIAL INDICATORPDI
PRESSURE INDICATORPI
PRESSURE INDICATING TRANSMITTERPIT
LEVEL SWITCH LOWLSL
LEVEL SWITCH LOW LOWLSLL
TEMPERATURE INDICATORTI
TEMPERATURE SWITCH HIGHTSH
WEIGHT INDICATORWI
WEIGHT INDICATING TRANSMITTERWIT
XXX
PROCESS AREA
INSTRUMENT
TYPE
ANALYTICAL TYPE
(IF USED)XX
CHLORINE RESIDUALCL2
DISSOLVED OXYGENDO
COMBUSTIBLE GASGAS
OXYGEN REDUCTION POTENTIALORP
ANALYTICAL TYPE IDENTIFIER
INSTRUMENT TYPE
pHpH
TURBIDITYTURB
ULTRAVIOLET TRANSMISSIVITYUVT
TEMPERATURE INDICATING TRANSMITTERTIT
PRESSURE SWITCH HIGHPSH
PRESSURE SWITCH LOWPSL
TOTAL ORGANIC CARBONTOC
TEMPERATURETEMP
ORTHOPHOSPHATEOP
AMMONIANH3
CONDUCTIVITYCOND
ANALYTICAL IDENTIFICATION
METERING PUMP
GENERIC PUMP
MAJOR PROCESS LINE, TYPICALLY
TREATED FLOW
MINOR PROCESS LINE, TYPICALLY
SECONDARY FLOW
UTILITY PROCESS LINE, TYPICALLY
SERVICE WATER OR DRAIN
EXISTING MINOR PROCESS LINE, AS
LABELED
EXISTING MAJOR PROCESS LINE, AS
LABELED
FUTURE MAJOR PROCESS LINE
EXISTING UTILITY PROCESS LINE,
AS LABELED
XXXXX
XXXXX
(Y-YYY)
XXXXX
XXXXX
(Y-YYY)
MAJOR OR MINOR
PROCESS LINE
DESCRIPTION
DRAWING
DESTINATION
LOCATION
MAJOR OR MINOR
PROCESS LINE
DESCRIPTION
XXXXX INCOMING UTILITY PROCESS
"XXXXX" INDICATES TYPE
XXXXX OUTGOING UTILITY PROCESS
"XXXXX" INDICATES TYPE
HAND-OFF-AUTOHOA
ON-OFF-AUTOOOA
ON-OFFOO
SWITCH TYPE IDENTIFIER
SWITCH
PLC DATA HIGHWAY
PNEUMATIC AIR LINE
D
D
WIRED SIGNAL
DISCRETE INPUT INTO PLC
DISCRETE OUTPUT FROM PLC
ANALOG INPUT INTO PLC
ANALOG OUTPUT FROM PLC
A
A
LOCAL-OFF-REMOTELOR
CROSS REFERENCE SYMBOLS
INSTRUMENTATION SIGNAL SYMBOLS
CONTROL PANEL SYMBOLS
FUTURE MINOR PROCESS LINE
FUTURE UTILITY PROCESS LINE
TIMER
R
RUNNING
RESET
ETM
INDICATOR LIGHT
PUSH BUTTON
ELAPSED TIME METER
KEYPAD
UNIT
NUMBERTRAIN NO.
EQUIPMENT IDENTIFICATION
####-AAA-1234
EQUIPMENT NUMBER
UNIT TRAIN NUMBER
TRAIN, BUILDING OR
EQUIPMENT
ABBREVIATION
PROCESS AREA
FOOT VALVE
DIFFERENTIAL PRESSURE SWITCH HIGHPDSH
TEMPERATURE ELEMENTTE
VELOCITY ELEMENT X AXISVEX
VELOCITY ELEMENT Y AXISVEY
COMPLEX NUMBER
PRESSURE DIFFERENTIAL INDICATING TRANSMITTERPDIT
GATE VALVE
DUCKBILL CHECK VALVE
FOUL AIR DUCT SYMBOLS
MANUAL BALANCING DAMPER
PRESSURE RELIEF DAMPER
INLET VANE DAMPER
BUBBLE TIGHT DAMPER
FLOW INDICATORFI
PRESSURE TRANSDUCERPT
H HYDRAULIC
HYDRAULIC HOSE
TEMPERATURE SWITCH
SILENT CHECK VALVE
V
K
SG
U U
U
Dwg.
No.
Seq.
RE
VI
SI
O
N
BY
DA
TE
N O
TO
W
N O
F
FR
IS
CO
W
EL
L
PF
AS
M
IT
IG
AT
IO
N
IM
PR
O
VE
M
EN
TS
<C
LI
EN
T
AD
DR
ES
S>
DESIGNED
CHECKED
REVIEWED
DRAWN
PR
IN
TE
D:
/1
3/
:5
AM
C
U se rs
\n to us sa in t\
DC
\A
CC
Do cs \P lu m m er
A ss oc ia te s\
-0
-0 9_
W
EL
L_ 7\
Pr oj ec t F ile s\
Pl um m er
\S he et s\
PI
D\
PI
D-
1.
dw g
S
AV
ED
: 5
/3 /2
:4
PM
S
AV
ED
B
Y:
N to us sa in t U
SE
R:
T ou ss ai nt , N ic k
4131-002-09
IF THIS BAR DOES NOT
MEASURE ONE INCH,
DRAWING IS NOT TO
LABELED SCALE
N C
AP
IT
AL
O
F
TX
H W
Y, S
TE
A
U
ST
IN
, T
X
2.
2.
T
BP
E
RE
GI
ST
ER
ED
F
IR
M
N U
M
BE
R F-
DATE:
CO P.E. NO.
NICHOLAS E. TOUSSAINT
34211
THESE DOCUMENTS ARE
FOR INTERIM REVIEW AND
ARE NOT INTENDED FOR
CONSTRUCTION, BIDDING,
OR PERMIT PURPOSES.
04/24/2024
A.GUDAL
N.TOUSSAINT
T.GERTIG
M.BARRERA
PID-001
EL
EC
TR
IC
AL
PI
D
LE
GE
N
D
IN
ST
RU
M
EN
TA
TI
O N
ID
SC
HO
O L
RO
AD
PO
B
O X
FR
IS
CO
C
O
N C
AP
IT
AL
O
F
TX
H W
Y, S
TE
A
U
ST
IN
, T
X
2.
2.
T
BP
E
RE
GI
ST
ER
ED
F
IR
M
N U
M
BE
R F-
WELL 7 PLC
(LOCATED IN WELL 7 BLDG)
FIELD
WELL PUMP
P-110
CV-120
HOA
MI-150
CL-420
CONNECTION TO EXISTING
DISTRIBUTION SYSTEM
RFBP-230
RFBP-220
BV-242
SAMPLE
TAP
SAMPLING
SODIUM
HYPOCHLORITE
TANK T-300
BV-111
BV-112
BV-141
DISCHARGE
BLEED
PD
PD-340
BV-333
BV-337
BV-334
BV-336
CHEMICAL PANEL
SODIUM HYPOCHLORITE
MP-310
BPV-341
BV-332
BV-335
ARV-113
ST-315
BV-338
GV-160
PRV (AS REQUIRED)
BV-244
HB-1
VENT
SAMPLE
TAP
HS
A
SP
EE
D
IN
DI
CA
TI
O
N
D
HO
A
IN
A
U
TO
D
FA
U
LT
D
RU
N
N
IN
G
ST
AR
T/
ST
O P
CO
M
M
AN
D
D
SP
EE
D
CO
M M
AN
D
A A
PR
ES
SU
RE
IN
DI
CA
TI
O N
SENSUS
TOTALIZING
FLOW METER
PIT
FE
FIT
A
FL
O
W R
AT
E
IN
DI
CA
TI
O N
PI
PI
SODIUM
HYDROXIDE
TANK T-500
DISCHARGE
BLEED
PRV-520
PD-540
BV-533
BV-537
BV-534
BV-536
MP-410
BPV-541
BV-532
BV-535
ST-515
BV-538
VENT
PI
CHEMICAL PANEL
SODIUM HYDROXIDE
A
SP
EE
D
IN
DI
CA
TI
O
N
D
HO
A
IN
A
U
TO
D
FA
U
LT
D
RU
N
N
IN
G
ST
AR
T/
ST
O P
CO
M
M
AN
D
D
SP
EE
D
CO
M M
AN
D
A
CHEMICAL METERING PANEL
(TYP. 2)
BV-531
PRV-320
BV-331
ZS
ZS
D
W
EL
L
BL
DG
IN
TR
U
SI
O
N
D
CH
EM
IC
AL
R O
O M
IN
TR
U
SI
O N
TIT
A
BU
IL
DI
N
G
TE
M
PE
RA
TU
RE
YS
D
PO
W
ER
F
AI
LU
RE
YS
D
U
PS
F
AI
LU
RE
YS
D
AT
S
IN
E
M
ER
GE
N
CY
P
O
SI
TI
O
N
YS
D
GE
N
ER
AT
O R
RU
N
N
IN
G
LSH
D
W
AT
ER
O
N F
LO
O
R
SW
IT
CH
ZS
D
CH
EM
IC
AL
R O
O M
T
EM
PE
RA
TU
RE
S W
8/RW/DIP 8/RW/DIP 8/RW/DIP 8/RW/DIP 8/RW/DIP
GV-412GV-241
GV-240
ARV-231
BV-245
15,000 GALLON
CHLORINE CONTACT
PRESSURE VESSEL
T-400
INSIDE WELL
BUILDING
OUTSIDE
BUILDING
GV-410 GV-411
ARV-401
INSIDE WELL BUILDING OUTSIDE WELL BUILDING
DRAIN
BV-243
AIT
AE
A
FR
EE
C
HL
O
RI
N E
IN
DI
CA
TI
O N
AE
A pH
IN
DI
CA
TI
O
N
CL2 pH
Dwg.
No.
Seq.
RE
VI
SI
O
N
BY
DA
TE
N O
TO
W
N O
F
FR
IS
CO
W
EL
L
PF
AS
M
IT
IG
AT
IO
N
IM
PR
O
VE
M
EN
TS
<C
LI
EN
T
AD
DR
ES
S>
DESIGNED
CHECKED
REVIEWED
DRAWN
PR
IN
TE
D:
/1
3/
:5
AM
C
U se rs
\n to us sa in t\
DC
\A
CC
Do cs \P lu m m er
A ss oc ia te s\
-0
-0 9_
W
EL
L_ 7\
Pr oj ec t F ile s\
Pl um m er
\S he et s\
PI
D\
PI
D-
2.
dw g
S
AV
ED
: 5
/3 /2
:4
PM
S
AV
ED
B
Y:
N to us sa in t U
SE
R:
T ou ss ai nt , N ic k
4131-002-09
IF THIS BAR DOES NOT
MEASURE ONE INCH,
DRAWING IS NOT TO
LABELED SCALE
N C
AP
IT
AL
O
F
TX
H W
Y, S
TE
A
U
ST
IN
, T
X
2.
2.
T
BP
E
RE
GI
ST
ER
ED
F
IR
M
N U
M
BE
R F-
DATE:
CO P.E. NO.
NICHOLAS E. TOUSSAINT
34211
THESE DOCUMENTS ARE
FOR INTERIM REVIEW AND
ARE NOT INTENDED FOR
CONSTRUCTION, BIDDING,
OR PERMIT PURPOSES.
04/24/2024
A.GUDAL
N.TOUSSAINT
T.GERTIG
M.BARRERA
PID-002
EL
EC
TR
IC
AL
M
IN
ST
RU
M
EN
TA
TI
O
N
EX
IS
TI
N
G P&
ID
ID
SC
HO
O L
RO
AD
PO
B
O X
FR
IS
CO
C
O
N C
AP
IT
AL
O
F
TX
H W
Y, S
TE
A
U
ST
IN
, T
X
2.
2.
T
BP
E
RE
GI
ST
ER
ED
F
IR
M
N U
M
BE
R
WELL 7 PLC
(LOCATED IN WELL 7 BLDG)
FIELD
WELL PUMP
P-110
CV-120
HOA
15,000 GALLON
CHLORINE CONTACT
PRESSURE VESSEL
T-400MI-150
INSIDE WELL
BUILDING
OUTSIDE
BUILDING
CL-420
CONNECTION TO EXISTING
DISTRIBUTION SYSTEM
RFBP-230
RFBP-220
BV-242
SODIUM
HYPOCHLORITE
TANK T-300
BV-111
BV-112 BV-141
DISCHARGE
BLEED
PD
PD-340
BV-333
BV-337
BV-334
BV-336
RELOCATED CHEMICAL PANEL
SODIUM HYPOCHLORITE
MP-310
BPV-341
BV-332
BV-335
ARV-113
ST-315
BV-338
GV-160
PRV (AS REQUIRED)
BV-244
HB-1
VENT
SAMPLE
TAP
HS
A
SP
EE
D
IN
DI
CA
TI
O
N
D
HO
A
IN
A
U
TO
D
FA
U
LT
D
RU
N
N
IN
G
ST
AR
T/
ST
O P
CO
M
M
AN
D
D
SP
EE
D
CO
M M
AN
D
A A
PR
ES
SU
RE
IN
DI
CA
TI
O N
PIT
FE
FIT
A
FL
O
W R
AT
E
IN
DI
CA
TI
O N
PI
PI
SODIUM
HYDROXIDE
TANK T-500
DISCHARGE
BLEED
PRV-520
PD-540
BV-533
BV-537
BV-534
BV-536
MP-410
BPV-541
BV-532
BV-535
ST-515
BV-538
VENT
PI
RELOCATED CHEMICAL PANEL
SODIUM HYDROXIDE
A
SP
EE
D
IN
DI
CA
TI
O
N
D
HO
A
IN
A
U
TO
D
FA
U
LT
D
RU
N
N
IN
G
ST
AR
T/
ST
O P
CO
M
M
AN
D
D
SP
EE
D
CO
M M
AN
D
A
CHEMICAL METERING PANEL
(TYP. 2)
BV-531
PRV-320
BV-331
ZS
ZS
D
W
EL
L
BL
DG
IN
TR
U
SI
O
N
D
CH
EM
IC
AL
R O
O M
IN
TR
U
SI
O N
TIT
A
BU
IL
DI
N
G
TE
M
PE
RA
TU
RE
YS
D
PO
W
ER
F
AI
LU
RE
YS
D
U
PS
F
AI
LU
RE
YS
D
AT
S
IN
E
M
ER
GE
N
CY
P
O
SI
TI
O
N
YS
D
GE
N
ER
AT
O R
RU
N
N
IN
G
LSH
D
W
AT
ER
O
N F
LO
O
R
SW
IT
CH
ZS
D
CH
EM
IC
AL
R O
O M
T
EM
PE
RA
TU
RE
S W
8/RW/DIP 8/RW/DIP 8/RW/DIP 8/RW/DIP 8/RW/DIP
GV-410 GV-411
GV-412GV-241
GV-240 ARV-401
ARV-231
SAMPLE
TAP
SAMPLING
BV-245
DRAIN
BV-243
AIT
AE
A
FR
EE
C
HL
O
RI
N E
IN
DI
CA
TI
O N
AE
A pH
IN
DI
CA
TI
O
N
CL2 pH
A
VE
SS
EL
P
RE
SS
U
RE
D
IF
FE
RE
N
TI
AL
IN
DI
CA
TI
O N
A
VE
SS
EL
P
RE
SS
U
RE
D
IF
FE
RE
N
TI
AL
IN
DI
CA
TI
O N
GV-611 GV-621
Dwg.
No.
Seq.
RE
VI
SI
O
N
BY
DA
TE
N O
TO
W
N O
F
FR
IS
CO
W
EL
L
PF
AS
M
IT
IG
AT
IO
N
IM
PR
O
VE
M
EN
TS
<C
LI
EN
T
AD
DR
ES
S>
DESIGNED
CHECKED
REVIEWED
DRAWN
PR
IN
TE
D:
/1
3/
:0
PM
C
U se rs
\n to us sa in t\
DC
\A
CC
Do cs \P lu m m er
A ss oc ia te s\
-0
-0 9_
W
EL
L_ 7\
Pr oj ec t F ile s\
Pl um m er
\S he et s\
PI
D\
PI
D-
3.
dw g
S
AV
ED
: 5
/1 3/
2:
P
M S
AV
ED
B Y:
N to us sa in t
U
SE
R:
T ou ss ai nt
, N ic k
4131-002-09
IF THIS BAR DOES NOT
MEASURE ONE INCH,
DRAWING IS NOT TO
LABELED SCALE
N C
AP
IT
AL
O
F
TX
H W
Y, S
TE
A
U
ST
IN
, T
X
2.
2.
T
BP
E
RE
GI
ST
ER
ED
F
IR
M
N U
M
BE
R F-
DATE:
CO P.E. NO.
NICHOLAS E. TOUSSAINT
34211
THESE DOCUMENTS ARE
FOR INTERIM REVIEW AND
ARE NOT INTENDED FOR
CONSTRUCTION, BIDDING,
OR PERMIT PURPOSES.
04/24/2024
A.GUDAL
N.TOUSSAINT
T.GERTIG
M.BARRERA
8/TVE/DIP
8/FW/DIP
PID-003
EL
EC
TR
IC
AL
PR
O
PO
SE
D P&
ID
INSIDE TREATMENT BUILDING
OUTSIDE TREATMENT
BUILDING
TREATMENT VESSEL
TNK-601
TREATMENT VESSEL 2
TNK-602
8/BWS 8/BWS
4/FILL
(TYP)
8/TVE
BACKWASH TO
WASTE/DRAIN TO SEWER
8/BWW
8/
BW
W
SA
M
PL
E
SA
M
PL
E
8/RW
8/
BW
W
ARV
BFV-613
BFV-615
BFV-612
PDIT PDIT
BFV-622
BFV-625
BFV-624
ARV
BFV-623
NC
NONO
NCNC
NC
BFV-611
NC
NC
NO NO
MI-600
INSIDE TREATMENT
BUILDING
OUTSIDE TREATMENT
BUILDING
SODIUM HYPOCHLORITE
SODIUM HYDROXIDE
BFV-610
NO
BFV-611
NO
U
PI
FI
P-610
BFV-621
NO
U
PI
FI
P-620
M
M
BOOSTER
PUMP
CONTROL
PANEL
VE
SS
EL
P
RE
SS
U
RE
D
IF
FE
RE
N
TI
AL
IN
DI
CA
TI
O N
BO
O
ST
ER
P U
M P
CO
N
TR
O
L
IN
FO
RM
AT
IO
N
ZS
ZS
D
W
EL
L
BL
DG
IN
TR
U
SI
O
N
D
CH
EM
IC
AL
R O
O M
IN
TR
U
SI
O N
TIT
A
BU
IL
DI
N
G
TE
M
PE
RA
TU
RE
YS
D
PO
W
ER
F
AI
LU
RE
BFV-612
NO
BFV-614
NC
BFV-613
NC
BFV-614
NO
BFV-620
NO
IN
ST
RU
M
EN
TA
TI
O
N
ID
SC
HO
O L
RO
AD
PO
B
O X
FR
IS
CO
C
O
N C
AP
IT
AL
O
F
TX
H W
Y, S
TE
A
U
ST
IN
, T
X
2.
2.
T
BP
E
RE
GI
ST
ER
ED
F
IR
M
N U
M
BE
R
Seq.
RE
VI
SI
O
N
BY
DA
TE
N O
TO
W
N O
F
FR
IS
CO
W
EL
L
PF
AS
M
IT
IG
AT
IO
N
IM
PR
O
VE
M
EN
TS
<C
LI
EN
T
AD
DR
ES
S>
DESIGNED
CHECKED
REVIEWED
DRAWN
PR
IN
TE
D:
/2
2/
:3
PM
C
U se rs
\n to us sa in t\
DC
\A
CC
Do cs \P lu m m er
A ss oc ia te s\
EI
C
Gr ou p\ Pr oj ec t F ile s\
FR
IS
CO
\A
CA
D\
El ec tr ic al \S
HE
ET
FI
LE
S\ E-
0.
dw g
S
AV
ED
: 4
/4 /2
1:
P M
S
AV
ED
B
Y:
N to us sa in t U
SE
R:
T ou ss ai nt , N ic k
4131-002-09
IF THIS BAR DOES NOT
MEASURE ONE INCH,
DRAWING IS NOT TO
LABELED SCALE
N C
AP
IT
AL
O
F
TX
H W
Y, S
TE
A
U
ST
IN
, T
X
2.
2.
T
BP
E
RE
GI
ST
ER
ED
F
IR
M
N U
M
BE
R F-
DATE:
CO P.E. NO.
NICHOLAS E. TOUSSAINT
34211
THESE DOCUMENTS ARE
FOR INTERIM REVIEW AND
ARE NOT INTENDED FOR
CONSTRUCTION, BIDDING,
OR PERMIT PURPOSES.
04/24/2024
ELECTRICAL GENERAL PROVISIONS
1. THE NOTES CONTAINED ON THIS SHEET ARE PROVIDED FOR THE CONVENIENCE OF THE CONTRACTOR WHEN WORKING IN THE FIELD AND CONTAIN EXCERPTS FROM THE SPECIFICATION SECTIONS. HOWEVER, THE CONTRACTOR IS HEREBY ADVISED THAT THE CONTRACT DOCUMENTS CONSIST OF BOTH THE DRAWINGS AND THE SPECIFICATIONS, AND THAT THE CONTRACTOR MUST COMPLY FULLY WITH BOTH THE BOUND DRAWINGS AND THE BOUND SPECIFICATIONS.
2. THE TERM “PROVIDE” USED IN THE DRAWINGS AND SPECIFICATIONS IMPLIES THE CONTRACTOR IS TO FURNISH, TRANSPORT, INSTALL, CONNECT, WARRANT AND START-UP, INCLUSIVELY.
3. WHERE NOTES ON THE DRAWING INDICATE THAT THE CONTRACTOR SHALL FIELD-VERIFY, THE INTENT IS FOR THE CONTRACTOR TO INVESTIGATE TO THE EXTENT NECESSARY TO PROVIDE THE WORK AND MATERIALS PRIOR TO BIDDING AND INCLUDE ALL COSTS IN THE BID PRICE. THE CONTRACT PRICE SHALL NOT BE INCREASED WHEN THE
CONTRACTOR HAS NOT INVESTIGATED PER THE NOTES DIRECTING THAT BE DONE.
4. CODES
4.1. ENTIRE INSTALLATION SHALL BE ACCORDANCE WITH THE FOLLOWING CODES AND STANDARDS
4.1.1. NFPA 70, NATIONAL ELECTRICAL CODE, 2020 EDITION.
4.1.2. NFPA 101, LIFE SAFETY CODE, 2021 EDITION.
4.1.3. NFPA 820, STANDARD FOR FIRE PROTECTION IN WASTEWATER TREATMENT AND COLLECTION FACILITIES, 2020 EDITION.
4.1.4. NFPA 780, LIGHTNING PROTECTION, 2020 EDITION.
4.1.5. NESC/IEEE C2: NATIONAL ELECTRIC SAFETY CODE, 2017 EDITION.
5. AREA CLASSIFICATION
5.1. THE FOLLOWING AREAS ARE RATED FOR THE STATED HAZARD CLASSIFICATION PER NFPA 820 AND TABLE 4.2.2;
5.1.1. WASTEWATER PUMPING STATION WETWELL, CLASS 1, DIVISION 1 - ENTIRE ROOM OR SPACE.
5.1.1.1. TABLE 4.2.2 ROW 14A.
5.1.2. WASTEWATER PUMPING STATION DRYWELL, CLASS 1, DIVISION 2 - ENTIRE ROOM OR SPACE.
5.1.2.1. TABLE 4.2.2 ROW 15B.
5.1.3. WASTEWATER PUMPING STATION METERING VAULT, CLASS 1, DIVISION 2 - ENCLOSED SPACE.
5.1.3.1. TABLE 4.2.2 ROW 34A.
5.1.4. WASTEWATER PUMPING STATION ELECTRICAL ROOM, UNCLASSIFIED
6. ENVIRONMENTAL RATINGS
6.1. THE FOLLOWING AREAS SHALL HAVE THE FOLLOWING ENVIRONMENTAL RATINGS;
6.1.1. ELECTRICAL ROOM - AIR-CONDITIONED
6.1.2. LIFT STATION AREAS - DAMP, VENTILATED, AND HEATED
7. ENCLOSURE RATINGS
7.1. PROVIDE ENCLOSURE FOR EQUIPMENT BASED UPON THE FOLLOWING CONDITIONS;
7.1.1. AIR-CONDITIONED AREAS, NEMA 12.
7.1.2. DRY, VENTILATED, AND HEATED AREAS, NEMA 12.
7.1.3. DAMP, VENTILATED, AND HEATED AREAS, NEMA 4 PAINTED STEEL.
7.1.4. WET, VENTILATED, AND HEATED AREAS, NEMA 4X 316 STAINLESS STEEL.
7.1.5. OUTDOORS, NEMA 4X 316 STAINLESS STEEL.
7.1.6. INDOOR CHEMICAL AREAS, NEMA 4X POLYCARBONATE.
7.1.7. OUTDOOR CHEMICAL AREAS, NEMA 4X 316 STAINLESS STEEL.
8. WORKMANSHIP
8.1. MATERIALS AND WORKMANSHIP SHALL COMPLY WITH THE CONTRACT DOCUMENTS, (INCLUDING BOTH
DRAWINGS AND SPECIFICATIONS), INDUSTRY STANDARDS, AND ALL APPLICABLE CODES.
8.2. ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR IN A PROFESSIONAL WORKMANLIKE MATTER. THE COMPLETED SYSTEM SHALL BE FULLY OPERATIVE AND ACCEPTED BY ENGINEER/OWNER.
8.3. CORRECTION OF ANY DEFECTS SHALL BE COMPLETE WITHOUT ADDITIONAL CHARGE AND SHALL INCLUDE REPLACEMENT OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION WHICH MANY HAVE BEEN DAMAGED.
8.4. ALL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S PUBLISHED RECOMMENDATIONS FOR SERVICE INTENDED AS INTERPRETED BY THE ENGINEER. THE INSTALLATION OF ALL EQUIPMENT SHALL BE MADE BY EXPERIENCED CRAFTSMAN IN A NEAT WORKMANLIKE MANNER. ALL MATERIALS, TOOLS, COSTS AND SERVICES NECESSARY TO COMPLETELY INSTALL ALL ELECTRICAL WORK SHALL BE FURNISHED
BY THE CONTRACTOR.
9. DOCUMENTATION
9.1. CONTRACTOR SHALL MAINTAIN A SET OF PRINTS AND MARK-UP DURING CONSTRUCTION TO REFLECT “AS-BUILT” CONDITIONS. PRINTS SHALL BE DELIVERED TO THE ENGINEER UPON COMPLETION OF THE PROJECT AS A
COMPLETE SET OF REQUIRED DRAWINGS.
EXISTING CONDITIONS
1. THE CONTRACTOR SHALL INSPECT THE SITE PRIOR TO BID TO EVALUATE EXISTING CONDITIONS. INSTALLATION OF THE NEW FACILITIES WILL REQUIRE FIELD COORDINATION WITH PLANT OPERATIONS TO PERMIT MAINTENANCE OR OPERATION DURING CONSTRUCTION. DURATION OF POWER OUTAGES SHALL BE MINIMUM REQUIRED FOR SAFE
INSTALLATION AND SHALL BE SCHEDULED WITH AND APPROVED BY THE OWNER.
2. THE CONTRACTOR SHALL TAKE PRECAUTIONS TO AVOID EXISTING UNDERGROUND UTILITIES INCLUDING PROCESS PIPING, WATER LINES, CHEMICAL FEED PIPING, ELECTRICAL CONDUITS, HAND EXCAVATION SHALL BE REQUIRED IN CONGESTED AREAS WHERE THE EXACT LOCATIONS OF ALL UTILITIES IN UNKNOWN. LOCATIONS SHOWN FOR THE EXISTING UNDERGROUND UTILIZES ARE APPROXIMATE ONLY. NOT ALL THE EXISTING UNDERGROUND UTILITIES ARE SHOWN. FIELD ADJUST LOCATIONS OF THE NEW FACILITIES TO ACCOMMODATE THE EXISTING SITE CONDITIONS AND
UNDERGROUND UTILITIES.
3. THE CONTRACTOR SHALL BE RESPONSIBLE TO LOCATE ALL UNDERGROUND UTILITIES BEFORE DIGGING. CONTRACTOR
SHALL COORDINATE THE EFFORT WITH THE OWNER.
SEQUENCING
1. EXISTING FACILITIES TO REMAIN IN OPERATION AT ALL TIMES. SEQUENCE WORK AND PROVIDE TEMPORARY SYSTEMS
AS REQUIRED TO MAINTAIN OPERATIONS.
2. PROVIDE TEMPORARY WIRING AND CONNECTIONS TO MAINTAIN EXISTING SYSTEMS IN SERVICE DURING CONSTRUCTION. WHEN WORK MUST BE PERFORMED ON ENERGIZED EQUIPMENT OR CIRCUITS, USE PERSONNEL
EXPERIENCED IN SUCH OPERATIONS.
DEMOLITION
1. THE CONTRACTOR SHALL REFER TO THE ARCHITECTURAL, STRUCTURAL, CIVIL, MECHANICAL AND PLUMBING DEMOLITION WORK DRAWINGS TO DETERMINE AND COORDINATE THE EXTENT OF THE DEMOLITION WORK REQUIRED
FOR THE PROJECT.
2. REMOVE ALL EXISTING BRANCH CIRCUITING AND EQUIPMENT (STARTERS, DISCONNECTS, DEVICES, WIRING, CABLES, AND CONDUIT), TO ALL LOADS THAT ARE BEING REMOVED BACK TO THE SOURCE OF SUPPLY UNLESS NOTED
OTHERWISE.
3. THE CONTRACTOR SHALL BE RESPONSIBLE TO CHECK THE FUNCTION OF EACH CONDUCTOR BEFORE REMOVING OR
DISCONNECTING.
4. GRIND ALL ANCHOR BOLTS FLUSH WITH SURFACE AND PATCH/FILL ALL CONDUIT OPENS IN SLAB AND/OR WALL.
MATERIALS
1. ALL MATERIALS SHALL BE NEW AND BEAR UNDERWRITERS LABELS WHERE APPLICABLE.
2. POWER CONDUCTORS AND CABLES
2.1. UNLESS NOTED OTHERWISE, CONDUCTOR SIZES INDICATED ARE BASED ON COPPER CONDUCTORS. DO NOT
PROVIDE CONDUCTORS SMALLER THAN THOSE INDICATED.
2.2. SMALLEST POWER WIRING SHALL BE 12 AWG.
2.3. SINGLE CONDUCTORS CONSTRUCTION:
2.3.1. UNLESS OTHERWISE INDICATED, ALL CONDUCTORS SHALL BE COPPER AND SHALL BE STRANDED. SOLID
CONDUCTORS SHALL BE ALLOWED ON 120-V LIGHTING AND RECEPTACLE CIRCUITS.
2.4. INSULATION REQUIREMENTS:
2.4.1. CONDUCTOR SIZES NO. 6 AND LARGER PROVIDE CONDUCTORS WITH TYPE RHH OR RHW.
2.4.2. CONDUCTOR SIZES SMALLER THAN NO. 6 PROVIDE CONDUCTORS WITH XHHW.
2.4.3. FOR LIGHTING AND RECEPTACLES, PROVIDE CONDUCTORS WITH THHN OR THWN.
2.5. WHERE FLEXIBLE CORDS AND CABLES ARE SPECIFIED, PROVIDE TYPE SO, 600 V WITH THE NUMBER AND SIZE OF
COPPER CONDUCTORS INDICATED.
2.6. WHERE MULTIPLE CONDUCTOR CABLES ARE SPECIFIED, PROVIDED CABLES THAT ARE UL CABLE TRAY RATED.
3. GROUNDING AND BONDING
3.1. CONTRACTOR SHALL PROVIDE A GROUNDING SYSTEM AS REQUIRED BY THE NEC AND IEEE GREEN BOOK. THE INSTALLED GROUNDING SYSTEM SHALL HAVE A RESISTANCE OF LESS THAN 5 OHMS TO GROUND. PROVIDE CONTINUOUS #4/0 TINNED COPPER GROUNDING SYSTEM. GROUND RODS SHALL BE COPPER CLAD STEEL 3/4”
DIAMETER X 10' LENGTH. CONNECTIONS SHALL BE EXOTHERMIC WELDS.
4. HANGERS AND SUPPORTS
4.1. ALL STRUT, SUPPORTING AND FASTENING DEVICES SHALL BE 316 STAINLESS STEEL.
4.2. PROVIDE LEVELING NUTS AND 3/4" GROUT UNDER ALL FLOOR MOUNTED BASE PLATES.
4.3. PROVIDE GROUNDING AT ALL OUTDOOR STRUT SWITCHRACKS.
5. RACEWAYS AND BOXES
5.1. ALL RACEWAY INSTALLATIONS SHALL BE INSTALLED IN A MANNER TO PREVENT CONFLICTS WITH EQUIPMENT AND STRUCTURAL COMPONENTS. ALL EXPOSED RACEWAY SHALL BE INSTALLED PARALLEL TO BEAMS, CEILINGS, FLOORS AND WALLS. SEE RACEWAY SPECIFICATION FOR ADDITIONAL REQUIREMENTS.
5.2. ALL CONDUITS SHALL BE INSTALLED PARALLEL AND PERPENDICULAR TO BUILDING STRUCTURE.
5.3. ALL RACEWAY INSTALLATIONS, CROSSING EXPANSION JOINTS OR TRANSITIONS FROM BELOW GRADE TO EXPOSED ABOVE GRADE, SHALL HAVE EXPANSION OR EXPANSION/DEFLECTION TYPE FITTINGS AS SPECIFIED FOR
THE APPLICATION
5.4. THREADED, INSULATED, AND GASKETED GALVANIZED STEEL HUBS RATED AS A RAIN-TIGHT CONNECTION SHALL BE USED FOR ALL CONDUITS PENETRATING ALL ENCLOSURES, PANELBOARDS, STARTERS, TERMINATION BOXES, MCC, PLC CABINETS, ETC. BUSHING SHALL BE GROUNDING OR NON-GROUNDING TYPE PER NFPA 70.
5.5. GALVANIZED STEEL CONDUIT SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE OR GROUT.
5.6. FLEXIBLE CONDUIT SHALL BE TYPE LFNC FLEXIBLE SEAL TIGHT CONDUIT FOR 3/4" AND 1" SIZES, CONNECTORS SHALL BE UL LISTED (1/2" LFNC FLEX SHALL BE ALLOWED FOR INSTRUMENTS WITH 1/2" THREADED HUB ENTRIES). USE GALVANIZED STEEL CORE LIGHT TIGHT FLEXIBLE METAL CONDUIT FOR SIZED 1 1/4" AND LARGER, CONNECTORS SHALL BE GALVANIZED STEEL. MAXIMUM LENGTH OF FLEX
CONDUIT SHALL BE 18".
5.7. CONDUIT APPLICATION
5.7.1. INDOORS-EXPOSED, RIGID GALVANIZED STEEL CONDUIT
5.7.2. OUTDOORS-EXPOSED, RIGID GALVANIZED STEEL CONDUIT
5.7.3. CONDUIT STUB-UPS THROUGH CONCRETE, PVC COATED RIGID GALVANIZED STEEL CONDUIT
5.7.4. CONDUIT CONCEALED IN CONCRETE SLABS OR WALLS, PVC SCHEDULE 80-EB
6. UNDERGROUND DUCTS AND RACEWAYS
6.1. THE DUCTBANK ROUTING SHOWN ON THE DRAWING(S) IS APPROXIMATE.