This document is a 100% Construction Document for a VA project to replace hot water generators in Buildings 24, 51, and 53 at the Jefferson Barracks VA Health Care System in St. Louis, Missouri. The project number is 657-24-109JB, and the construction documents are fully sprinklered. The drawings, prepared by Design-Are Engineering, Inc., include detailed mechanical specifications, site plans, construction area layouts, and technical details for replacing domestic hot water generators across three buildings.
The documents outline comprehensive logistics and construction requirements, including strict scheduling notes, construction debris management, security protocols, and infection control risk assessment (ICRA) guidelines. Specific technical details cover water heater control schematics, piping connections, temporary water heater setup, and engineering control center point lists for monitoring water temperatures, system status, and operational parameters. The project involves replacing existing hot water generators with new equipment, ensuring minimal disruption to the occupied VA healthcare facility during construction.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
JEFFERSON BARRACKS
Replace Hot Water Generators in Buildings 24, 51, & 53
US DEPARTMENT OF VETERANS AFFAIRS
ST. LOUIS VA HEALTH CARE SYSTEM
VA PROJECT NUMBER: 657-24-109JB
OVERALL CAMPUS SITE PLAN, BUILDING NUMBER, AND PROJECT LOCATOR
CONTACT INFORMATION
COR: Gene Kengovskiy, P.E.
Healthcare Engineer, Design & Construction, Facility Engineering Services
314-652-4100, EXT 68154
YEVGENIY.KENGOVSKIY@VA.GOV
DAE: DAVE HAUN, PROJECT MANAGER
317-464-9090
DHAUN@DAENGINEERING.COM
60T
51T
1CC
101T
1CC
3T
55G
52G
60G
52SG
1CC
56G
1CC
60T
51T
1G
1CC
101T
1CC
1CC
1CC
3T
55G
52G
60G
52SG
1CC
56G
1CC
53T
JEFFERSON DRIVE
SOUTH GATE ENTRANCE DRIVE
TO
IN
TER
STATE 255 →
NORTH GATE ENTRANCE DRIVE
KO
C
H R
O
AD
JEFFERSON
BARRACKS
NATIONAL
CEM
ETERY
I-255 LOT
JEFFERSON DRIVE
SOUTH GATE ENTRANCE DRIVE
TO
IN
TER
STATE 255 →
NORTH GATE ENTRANCE DRIVE
KO
C
H R
O
AD
KO
C
H R
O
AD
25T
CO
NSTRUCTIO
N
ZO
NE
CO
NST.
ZO
NE
CO
NST.
ZO
NE
TEM
PO
RARY CO
RRIDO
R
CO
NST. ZO
NE
53G
PROJECT BUILDING
LOCATIONS
GI-001
GENERAL COVER SHEET
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration
REPLACE HOT WATER GENERATORS IN
B24, B51, & B53
JEFFERSON BARRACKS CAMPUS
1 JEFFERSON BARRACKS DR - ST. LOUIS, MO 63125
657-24-109JB
10/04/2024 DEH DAE 17
2707 Rand Rd Indianapolis, IN 46241
(317) 646 - 9090
100% CONSTRUCTION DOCUMENTS - FOR BIDDING
FULLY SPRINKLERED
S
TATE
OF I L L
NO
I S
I
R
AutoCAD SHX Text
VAN
AutoCAD SHX Text
VAN
AutoCAD SHX Text
VAN
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ENGINEER
AutoCAD SHX Text 062-073724
AutoCAD SHX Text
REGISTERED
AutoCAD SHX Text
PROFESSIONAL
51T
53T
G10A
G15
G08
DN
CORR
H001
LINEN
GS08
IRM
ELECTRICAL
GS12
MECHANICAL
GS13
IRM
GS53
EMS
SERVICE
C O
R R
ID
O
R H
BA100 ROOM
BA100A
ELECTRICAL
ROOM
BA101
MECHANICAL
BA102
LAUNDRY
CHUTE
BA103
GJ-001
OVERALL BUILDING AND PROJECT
CONSTRUCTION AREAS
NOT TO SCALE
N
LOGISTICS NOTES:
CONSTRUCTION SCHEDULING NOTES:
1. THE PROJECT SHALL BE COMPLETED IN THE CALENDAR DAYS NOTED IN THE CONTRACT.
2. THE GENERAL CONTRACTOR WILL PREPARE A GRAPHIC SCHEDULE FOR FINAL APPROVAL BY THE COR PRIOR TO CONSTRUCTION START.
3. CONTRACTOR MUST COORDINATE SCHEDULE WITH THE COR AND OTHER CONTRACTORS WORKING UNDER SEPARATE CONTRACTS IN
ADJACENT SPACES OF THE BUILDING.
4. THE GENERAL CONTRACTOR WILL PREPARE A CONSTRUCTION STAGING AND SAFETY PLAN FOR FINAL APPROVAL BY THE COR PRIOR TO
CONSTRUCTION START.
CONSTRUCTION DEBRIS NOTES:
1. CONSTRUCTION DEBRIS MUST BE CONTAINED WITHIN THE BOUNDARY AREA AT ALL TIMES.
2. CONSTRUCTION DEBRIS MUST BE MONITORED AND SECURED AT ALL TIMES
3. VA MANDATED RECYCLING FORMS MUST BE KEPT UP TO DATE.
4. DUMPING OF DEMOLITION OR CONSTRUCTION LIQUIDS IS PROHIBITED IN EXISTING PLUMBING FIXTURES UNLESS DIRECTED OTHERWISE BY COR.
LOGISTICS KEY NOTES:X
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration
REPLACE HOT WATER GENERATORS IN
B24, B51, & B53
JEFFERSON BARRACKS CAMPUS
1 JEFFERSON BARRACKS DR - ST. LOUIS, MO 63125
657-24-109JB
10/04/2024 DEH DAE 17
2707 Rand Rd Indianapolis, IN 46241
(317) 646 - 9090
100% CONSTRUCTION DOCUMENTS - FOR BIDDING
FULLY SPRINKLERED
S
TATE
OF I L L
NO
I S
I
R
A. SELECTED CONTRACTOR TO OBTAIN REQUIRED SECURITY CLEARANCES AND BADGES WITH THE CONTRACTING OFFICER REPRESENTATIVE
(COR) DURING SUBMITTAL PHASE.
B. BUILDING WILL REMAIN OCCUPIED DURING CONSTRUCTION.
C. DEMOLITION AND CONSTRUCTION WORK SHALL NOT INTERFERE WITH OR REDUCE EXISTING BUILDING SECURITY. CONTRACTOR SHALL WORK
WITH COR FOR FINAL LOCATIONS AND TO SCHEDULE FOR BUILDING SECURITY.
D. CONTRACTOR IS TO PROVIDE TEMPORARY PATH OF EMERGENCY EGRESS FOR AREAS UNDER CONSTRUCTION, UNLESS DIRECTED OTHERWISE
BY THE COR.
E. CONTRACTOR TO PROVIDE A GRAPHIC PLAN OF PROPOSED TEMPORARY EGRESS AND PROTECTION OF STRUCTURES PRIOR TO COMMENCING WORK FOR VA APPROVAL. THE EGRESS PATH MUST HAVE PROTECTION FROM WORK ABOVE AND ADJACENT TO THE PATH.
F. BUILDING HOURS ARE CURRENTLY 7:00AM - 5:00PM MONDAY THRU FRIDAY. ANY CHANGES TO BUILDING HOURS WILL BE PROVIDED BY THE COR.
G. ALL CONSTRUCTION PERSONNEL MUST SIGN-IN EVERY DAY THAT THEY ARE ON SITE - COORDINATE DESIRED PROCEDURE WITH COR.
H. NOISY WORK AND WORK PRODUCING NOXIOUS ODOR SHALL BE SCHEDULED 48 HOURS IN ADVANCE AND COMPLETED OUTSIDE REGULAR BUILDING HOURS OR AS DIRECTED BY THE COR. PROTECT MECHANICAL DUCTS AND AIR INTAKE FROM DUST, DEBRIS AND NOXIOUS ODORS.
I. NO MATERIAL IS TO BE STAGED OR STORED IN THE BUILDING CORRIDORS AND CONTRACTOR IS RESPONSIBLE FOR MAINTAINING ALL EXISTING
PATHS OF EGRESS FROM THE BUILDING.
J. THE GENERAL CONTRACTOR MAY USE EXISTING STORAGE WITHIN THE BUILDING ONLY AS DIRECTED BY COR.
K. CONTRACTOR MAY HAVE ACCESS TO 110V ELECTRICITY, WATER, AND BUILDING RESTROOMS WHILE WORKING ON THE INTERIOR OF THE
BUILDING. (VERIFY WITH COR PRIOR TO USING INTERIOR FACILITIES)
L. CONTRACTOR PARKING TO BE IN PUBLIC LOTS OR AS DESIGNATED BY COR.
M. MATERIALS STORAGE LOCATIONS AS DESIGNATED BY COR.
N. SECURITY
1.1. CONTRACTOR SHALL NOT LEAVE DOORS PROPPED OPEN.
1.2. CONTRACTOR SHALL NOT LEAVE TOOLS OR LADDERS UNATTENDED.
1.3. CONTRACTOR SHALL NOT LEAVE ELECTRICAL OR DATA PANELS EXPOSED.
P. PHOTOGRAPHY
1.1. NO PHOTOGRAPHY OF VA PREMISES IS ALLOWED WITHOUT WRITTEN PERMISSION OF THE COR. IF PERMISSION IS GRANTED BY THE COR, NO PHOTOGRAPHY IS PERMITTED OF PERSONNEL, PATIENTS, COMPUTER SCREENS, LICENSE PLATES, OR ANY OTHER SENSITIVE MATERIAL
AS DETERMINED BY THE COR.
Q. BADGING
1.1. ALL CONTRACTOR PERSONNEL ARE REQUIRED TO DISPLAY VA BADGE WHEN WORKING ON STATION.
1.2. TWO-WEEK NOTICE IS REQUIRED FOR BADGING OF CONTRACTOR PERSONNEL REQUIRING A FLASH PASS/BADGE ABOVE WAIST.
R. KEYS
1.1. COORDINATE WITH VA COR FOR ACCESS AND ISSUING OF KEYS.
S. JOBSITE PLAN
1.1. JOBSITE PLAN MUST BE SUBMITTED PRIOR TO COMMENCEMENT OF WORK
a. INCLUDES a.1. ENTRANCES USED a.2. MATERIAL MOVEMENT PLAN a.3. RESTROOMS TO BE USED a.4. LIST OF SUBCONTRACTORS a.5. PERSONNEL ON SITE
T. TRAILER STORAGE
1.1. CONTRACTORS ARE REQUIRED TO COORDINATE TRAILER STORAGE LOCATION WITH COR.
U. CONTRACTOR SHALL NOTIFY COR OF ANY MATERIAL REMOVED CONTAINING EE# OR MAXIMO NUMBER.
1.1. CONTRACTOR SHALL NOTIFY COR OF ANY NEW EQUIPMENT AND/OR SPECIFIC REQUIREMENTS FOR EQUIPMENT (I.E. SPECIAL OUTLETS, ADEQUATE BREAKER SIZE, ETC.). (MAKE, MODEL, SERIAL NUMBER)
V. UTILITY SHUTDOWNS
1.1. MUST BE COORDINATED WITH COR 21 DAYS IN ADVANCE.
W. FIRESTOPPING
1.1. INSTALL TEMPORARY FIRESTOPPING IN ALL NEW CORE DRILLED PENETRATIONS IN FLOOR AND WALLS. ENSURE FIRESTOPPING IS
MAINTAINED THROUGHOUT
X. FIRE ALARM/SPRINKLER
1.1. IF FIRE ALARM AND/OR SPRINKLER SYSTEM IS DISABLED DURING CONSTRUCTION, HEAT DETECTION MUST BE PROVIDED. SIEMENS MUST
MAKE FINAL TERMINATIONS AND PROGRAM INTO EXISTING FIRE ALARM SYSTEM.
Y. ILSM
1.1. TEMPORARY FIRE EXTINGUISHERS SHALL BE APPROPRIATELY MOUNTED AND SPACED DURING CONSTRUCTION FOR HOUSEKEEPING AND
SAFETY REQUIREMENTS.
a.1. TRAVEL DISTANCE FROM ANY POINT OF THE PROTECTED AREA TO THE NEAREST FIRE EXTINGUISHER SHALL NOT EXCEED 100 FEET.
Z. EXIT PATHS MUST BE LITTER/DEBRIS FREE AND ALL WORK IN CORRIDORS HAVE TO BE REMOVED BEFORE 6:00AM EACH MORNING.
1. BUILDING ACCESS POINT; DOOR AND/OR DOCK.
2. APPROXIMATE LOCATION OF WORK IN BUILDING
3. SUGGESTED DUMPSTER LOCATIONS. VERIFY WITH COR, PRIOR TO START OF ON-SITE MOBILIZATION.
4. WASTE WILL HAVE TO BE TAKEN OUT ON A CART OR THROUGH WINDOW.
5. DOOR COVERING TO MEET/EXCEED JEFFERSON BARRACKS ICRA STANDARDS. VERIFY WITH COR.
6. DOOR WITH WALKOFF MAT.
7. CONSTRUCTION BARRIER LIMITS. PROVIDE A MINIMUM OF 5'-0" CLEARANCE IN HALLWAY, VERIFY WITH COR.
8. SUGGESTED PATH OF CONSTRUCTION DEBRIS REMOVAL.
9. ICRA NOT REQUIRED. ALL DUST TO BE KEPT AT A MINIMUM.
BUILDING 51 CONSTRUCTION AREABUILDING 24 CONSTRUCTION AREA BUILDING 53 CONSTRUCTION AREA
NOT TO SCALE
N
NOT TO SCALE
N
NOT TO SCALE
BUILDING 51 - BA102 CONSTRUCTION AND ICRA INFORMATIONBUILDING 24 - G15 CONSTRUCTION AND ICRA INFORMATION BUILDING 53 - GS13 CONSTRUCTION AND ICRA INFORMATION
NOT TO SCALE NOT TO SCALE
LEGEND:
ICRA BARRIER
CONSTRUCTION BARRIER ENCLOSURE
APPROXIMATE WORK BOUNDRY
7 5 6 4 8
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ENGINEER
AutoCAD SHX Text 062-073724
AutoCAD SHX Text
REGISTERED
4" RUBBER COVE
WITH 16 GA. METAL
STUDS AT 16" O.C.
BOARD EACH SIDE.
WITH 5/8" GYPSUM
AS SCHEDULED
ACOUSTICAL CEILING
2' X 4' SUSPENDED
WALL CONST. TYPES (DETAILS)
TYPE A
BASE @ BOTH SIDES
4" RUBBER COVE
3 5/8" 16 GA. METAL
STUDS AT 16" O.C.
BOARD EACH SIDE.
WITH 5/8" GYPSUM
W A
LL
H
EI
G H T
V
ER
IE
S
TYPE B
C
EI
LI
N G
H
EI
G H T
'-0
ON FLOOR PLAN.
FI
EL
D V
ER
IF
Y
C
EI
LI
N G
H
EI
G H T
'-0
4 7/8"4 7/8"
W A
LL
H
EI
G H T
V
ER
IE
S
FI
EL
D V
ER
IF
Y
TO MATCH EXISTING AREA TO MATCH EXISTING AREA
ROOF METAL DECKING
BASE @ BOTH SIDES
AS SCHEDULED
ACOUSTICAL CEILING
2' X 4' SUSPENDED
ON FLOOR PLAN.
3 5/8" INSULATED WALL
WALL TO EXTEND TO
ROOF METAL DECKING
GENERAL NOTES:
LOW RISK
OFFICE AREAS
PATIENT RISK GROUPS
MEDIUM RISK HIGH RISK HIGHEST RISK
CARDIOLOGY CCU ANY AREA CARING FOR
ECHOCARDIOGRAPHY
ENDOSCOPY
NUCLEAR MEDICINE
PHYSICAL THERAPY
RADIOLOGY/MRI
RESPIRATORY THERAPY
EMERGENCY ROOM
LABOR & DELIVERY
LABORATORY (SPECIMEN)
NEWBORN NURSERY
OUTPATIENT SURGERY
PEDIATRICS
IMMUNOCOMPROMISED PATIENTS
BURN UNIT
CARDIAC CATH LAB
CENTRAL STERILE SUPPLY
INTENSIVE CARE UNITS
MEDICAL UNIT
PHARMACY
POST ANESTHESIA CARE UNIT
SURGICAL UNITS
NEGATIVE PRESSURE ISOLATION ROOMS
ONCOLOGY
OPERATING ROOMS INCLUDING
C-SECTION ROOMS
LOW RISK GROUP
CONSTRUCTION PROJECT TYPE
MEDIUM RISK GROUP
HIGH RISK GROUP
HIGHEST RISK GROUP
RISK RELATED GROUP TYPE A TYPE B TYPE C TYPE D
I II II III/IV
II
II III/IV
III/IV
III
III/IV
IV
IV
IV
I
I
II
CONSTRUCTION PROJECT BY PATIENT RISK
IC MATRIX - CLASS OF PRECAUTIONS:
INFECTION CONTROL APPROVAL WILL BE REQUIRED WHEN THE CONSTRUCTION ACTIVITY AND RISK
NOTE:
LEVEL INDICATE THAT CLASS III OR CLASS IV CONTROL PROCEDURES ARE NECESSARY.
INSPECTION AND NON-INVASIVE ACTIVITIES
TYPE A
SMALL SCALE, SHORT DURATION ACTIVITIES
TYPE B
WHICH CREATES MINIMAL DUST.
WORK THAT GENERATES A MODERATE TO
TYPE C
HIGH LEVEL OF DUST OR REQUIRES DEMOLITION
OR REMOVAL OF ANY FIXED BUILDING
COMPONENTS OR ASSEMBLIES
MAJOR DEMOLITION AND CONSTRUCTION
TYPE D
PROJECTS
MATRIX OF PRECAUTIONS FOR
CONSTRUCTION & RENOVATION
I R AC (ICRA)
C
LA
SS
V
1. ISOLATE H.V.A.C. SYSTEM IN AREA WHERE WORK IS BEING DONE TO PREVENT
CONTAMINATION OF DUCT SYSTEM.
2. COMPLETE ALL CRITICAL BARRIERS IE. SHEETROCK, PLYWOOD, PLASTIC, TO SEAL
AREA FROM NON-WORK AREA OR IMPLEMENT CONTROL CUBE METHOD (CART WITH
PLASTIC COVERING AND SEALED CONNECTION TO WORK SITE WITH HEPA VACUUM FOR
VACUUMING PRIOR TO EXIT) BEFORE CONSTRUCTION BEGINS.
3. MAINTAIN NEGATIVE AIR PRESSURE WITHIN WORK SITE UTILIZING HEPA EQUIPPED AIR
FILTRATION UNITS IF INDICATED.
4. SEAL HOLES, PIPES, CONDUITS, AND PUNCTURES APPROPRIATELY.
5. CONSTRUCT ANTEROOM AND REQUIRE ALL PERSONNEL TO PASS THROUGH THIS ROOM
7. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT IS
INSPECTED BY THE OWNER'S SAFETY DEPARTMENT AND INFECTION CONTROL.
8. ROOM AND/OR SHALL BE THOROUGHLY CLEANED BY THE OWNER'S ENVIRONMENTAL
SERVICES DEPARTMENT.
2. REMOVE BARRIER MATERIALS CAREFULLY TO MINIMIZE SPREADING OF DIRT AND DEBRIS
ASSOCIATED WITH CONSTRUCTION.
5. VACUUM WORK AREA WITH HEPA FILTERED VACUUM.
6. WET MOP AREA WITH DISINFECTANT.
SO THEY CAN BE VACUUMED USING HEPA VACUUM CLEANER BEFORE LEAVING WORK
SITE OR THEY CAN WEAR CLOTH OR PAPER COVERALLS THAT ARE REMOVED EACH
TIME THEY LEAVE THE WORK SITE.
6. ALL PERSONNEL ENTERING WORK SITE ARE REQUIRED TO WEAR SHOE COVERS.
SHOE COVERS MUST BE CHANGED EACH TIME THE WORKER EXITS THE WORK AREA.
SITE OR THEY CAN WEAR CLOTH OR PAPER COVERALLS THAT ARE REMOVED EACH
TIME THEY LEAVE THE WORK SITE.
3. CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT IN TIGHTLY COVERED CONTAINERS.
7. REMOVE ISOLATION OF H.V.A.C. SYSTEM IN AREAS WHERE WORK IS BEING PERFORMED.
4. COVER TRANSPORT RECEPTACLES OR CARTS. TAPE COVERING UNLESS SOLID LID.
PRIOR TO ANY CONSTRUCTION
POST CONSTRUCTION
1. OBTAIN APPROVAL BY MCOT TEAM TO REMOVE BARRIERS.
TYPICAL IDEAL
CONSTRUCTION LAYOUT
CLASS IV
ELEVATION
TYPE B
TYPE A
CROSS-SECTION 'A-A' MOBILE CONTAINMENT CART
CLASS IV
ILSMICRA
MANOMETER
READING FORM
PROJECT
CONTACT
SHEET
POSTED ON THE CONTAINMENT DOOR IN CLEAR
PLASTIC SLEEVES
INTERIM LIFE SAFETY MEASURES:
INFECTION CONTROL RISK ASSESSMENT:
PICRA:
UTILITIES SHUT-DOWNS:
ICRA
ILSM
GJ-002
TYPE IV ICRA CONSTRUCTION DETAILS
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration
REPLACE HOT WATER GENERATORS IN
B24, B51, & B53
JEFFERSON BARRACKS CAMPUS
1 JEFFERSON BARRACKS DR - ST. LOUIS, MO 63125
657-24-109JB
10/04/2024 DEH DAE 17
2707 Rand Rd Indianapolis, IN 46241
(317) 646 - 9090
100% CONSTRUCTION DOCUMENTS - FOR BIDDING
FULLY SPRINKLERED
S
TATE
OF I L L
NO
I S
I
R
AutoCAD SHX Text
2. ALL APPLICABLE FORMS TO BE COMPLETED AND APPROVED PRIOR TO STARTING WORK.
AutoCAD SHX Text
3. PERMITS TO INCLUDE:
AutoCAD SHX Text
ICRA, ILSM, ABOVE CEILING, FIRE SPRINKLER SYSTEM, MEDICAL GASES,
AutoCAD SHX Text
UTILITY SHUT-DOWN, FIRE/SMOKE WALL, FIRE ALARM SYSTEM.
AutoCAD SHX Text
4. THE CONSTRUCTION AREA MUST MAINTAIN A NEGATIVE PRESSURE VENTILATION.
AutoCAD SHX Text NEGATIVE AIR UNIT TO BE MAINTAINED WITH FILTER(S) REPLACEMENT PER SPECIFICATIONS.
AutoCAD SHX Text
1. ALL PERSONNEL ENTERING THE CONSTRUCTION SITE AREA MUST WEAR A HARD HAT
AutoCAD SHX Text
AND SAFETY GLASSES ALONG WITH ANY OTHER PPE REQUIRED IN THAT AREA.
AutoCAD SHX Text
CLEAN ALL EXTERIOR SURFACES OF CARTS AND TOOLS AT THE END OF EACH SHIFT.
AutoCAD SHX Text
(WEEKLY REPLACEMENT OF PRE-FILTER OR AS NECESSARY. HEPA FILTER REPLACED MONTHLY.
AutoCAD SHX Text
NEGATIVE PRESSURE MACHINES MUST BE ON AND OPERATIONAL 24/7.
AutoCAD SHX Text
MONITOR NEGATIVE PRESSURE AND POST LOG AT THE END OF EACH SHIFT.
AutoCAD SHX Text
5. CONSTRUCTION CLASS WILL BE DETERMINED BY THE CONSTRUCTION SAFETY COMMITTEE
AutoCAD SHX Text
6. DURING CONSTRUCTION BE CERTAIN THAT:
AutoCAD SHX Text
BARRIERS ARE INTACT AND MAINTAINED.
AutoCAD SHX Text
PARTICAL COUNT METER IS AVAILABLE.
AutoCAD SHX Text
NEGATIVE INDICATOR IS AVAILABLE.
AutoCAD SHX Text
ICRA REQUIREMENTS ARE INTACT AND
AutoCAD SHX Text
VERIFY ARE BEING MAINTAINED.
AutoCAD SHX Text
INCLUDES, BUT IS NOT LIMITED TO:
AutoCAD SHX Text
REMOVABLE OF CEILING TILES FOR VISUAL INSPECTION LIMITED TO
AutoCAD SHX Text
1 TILE PER 50 SQUARE FEET.
AutoCAD SHX Text
PAINTING (BUT NOT SANDING).
AutoCAD SHX Text
WALL COVERING, ELECTRICAL TRIM, MINOR PLUMBING, AND
AutoCAD SHX Text
ACTIVITIES WHICH DO NOT GENERATE DUST OR REQUIRE CUTTING
AutoCAD SHX Text
OF WALLS OR ACCESS TO CEILINGS OTHER THAN FOR VISUAL
AutoCAD SHX Text
INSPECTION.
AutoCAD SHX Text
INCLUDES, BUT IS NOT LIMITED TO:
AutoCAD SHX Text
INSTALLATION OF TELEPHONE AND COMPUTER CABLING.
AutoCAD SHX Text
ACCESS TO CHASE SPACES.
AutoCAD SHX Text
CUTTING OF WALLS OR CEILING WHERE DUST MIGRATION
AutoCAD SHX Text
CAN BE CONTROLLED.
AutoCAD SHX Text
INCLUDES, BUT IS NOT LIMITED TO:
AutoCAD SHX Text
SANDING OF WALLS FOR PAINTING OR WALL COVERING.
AutoCAD SHX Text
REMOVAL OF FLOOR COVERINGS, CEILING TILES OR CASEWORK.
AutoCAD SHX Text
NEW WALL CONSTRUCTION.
AutoCAD SHX Text
MINOR DUCT WORK OR ELECTRICAL WORK ABOVE CEILINGS.
AutoCAD SHX Text
MAJOR CABLING ACTIVITIES.
AutoCAD SHX Text
ANY ACTIVITY WHICH CANNOT BE COMPLETED WITHIN A SINGLE
AutoCAD SHX Text
WORK SHIFT.
AutoCAD SHX Text
INCLUDES, BUT IS NOT LIMITED TO:
AutoCAD SHX Text
ACTIVITIES WHICH REQUIRE CONSECUTIVE WORK SHIFTS.
AutoCAD SHX Text
REQUIRES HEAVY DEMOLITION OR OR REMOVAL OF A
AutoCAD SHX Text
COMPLETE CABLING SYSTEM.
AutoCAD SHX Text
NEW CONSTRUCTION.
AutoCAD SHX Text
NFECTION
AutoCAD SHX Text
ONTROL
AutoCAD SHX Text
ISK
AutoCAD SHX Text
SSESSMENT
AutoCAD SHX Text
POST ICRA, ILSM, FIRE INSPECTION
AutoCAD SHX Text
TEMP. ANTE ROOM
AutoCAD SHX Text
HARD BARRIER
AutoCAD SHX Text
EITHER KEEP RUNNING
AutoCAD SHX Text
COVER ALL RETURNS
AutoCAD SHX Text
HEPA NEGATIVE AIR UNIT
AutoCAD SHX Text
TAPE ALL SERVICES
AutoCAD SHX Text
ABC TYPE FIRE EXTINGUISHER ON
AutoCAD SHX Text
FIRE RATED PLYWOOD
AutoCAD SHX Text A
AutoCAD SHX Text O
AutoCAD SHX Text V
AutoCAD SHX Text
WEEKLY CHANGED
AutoCAD SHX Text
(OR MORE AS NEEDED)
AutoCAD SHX Text
MONTHLY CHANGED
AutoCAD SHX Text
HEPA FILTER
AutoCAD SHX Text
PRE-FILTER
AutoCAD SHX Text
SUPPLY DUCTS
AutoCAD SHX Text
OR COVER WITH FIRE
AutoCAD SHX Text
AT THE GRATE/DIFFUSERS
AutoCAD SHX Text
TO PROTECT AGAINST
AutoCAD SHX Text
PORTABLE FLOOR BRACKET
AutoCAD SHX Text
SHEETS VISIBLE TO PUBLIC
AutoCAD SHX Text
CONTAMINATION
AutoCAD SHX Text
(REFER TO ELEVATION)
AutoCAD SHX Text
FLEX DUCT
AutoCAD SHX Text
EXISTING WINDOW FRAME
AutoCAD SHX Text
FIRE RATED PLYWOOD
AutoCAD SHX Text
(TEMP. REMOVE
AutoCAD SHX Text
HEPA NEGATIVE AIR UNIT
AutoCAD SHX Text
EXISTING FIRE
AutoCAD SHX Text
SPRINKLER SYSTEM
AutoCAD SHX Text
EXISTING CONCRETE SLAB FLOORING
AutoCAD SHX Text
FIRE/U.L. RATED PLASTIC
AutoCAD SHX Text
TO PREVENT DUST
AutoCAD SHX Text
GLASS PANEL)
AutoCAD SHX Text
FIRE/U.L. RATED PLASTIC
AutoCAD SHX Text
TO PREVENT DUST
AutoCAD SHX Text E
AutoCAD SHX Text
OPTIONAL EXHAUST DUCTS
AutoCAD SHX Text
(COVER THE GRATES
AutoCAD SHX Text
AND THE DIFFUSERS)
AutoCAD SHX Text
EXISTING WALL
AutoCAD SHX Text
EXISTING WALL
AutoCAD SHX Text
INDICATOR MUST BE AT -0.01 OR MORE NEGATIVE
AutoCAD SHX Text
(VERIFY DAILY), IF NOT VERIFY ALL OPENING
AutoCAD SHX Text
SUCH AS DOORS ARE CLOSED AND/OR CHANGE
AutoCAD SHX Text
OUT NEGATIVE AIR PRE-FILTER.
AutoCAD SHX Text
(LOCKED AT ALL TIMES)
AutoCAD SHX Text
BLUE CORE LOCKSET
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text
OUTSIDE OF BUILDING
AutoCAD SHX Text
AutoCAD SHX Text
FINISHED FLOORING TO BE KEPT CLEAN.
AutoCAD SHX Text
FLOORS NOT BEING REPLACED TO BE
AutoCAD SHX Text
WITH FIRE RATED PLASTIC
AutoCAD SHX Text
SHEETING AND SECURE
AutoCAD SHX Text
WITH DUCT TAPE.
AutoCAD SHX Text
RATED PLASTIC SHEETING
AutoCAD SHX Text
AND SECURE WITH DUCT
AutoCAD SHX Text
TAPE TO KEEP DUST OUT.
AutoCAD SHX Text
(ILSM MAY REQUIRE MORE
AutoCAD SHX Text
THAN ONE OR WALL MOUNTED).
AutoCAD SHX Text
PROVIDE STICKY MATS
AutoCAD SHX Text
(CHANGED END OF SHIFT
AutoCAD SHX Text
OR MORE IF NECESSARY
AutoCAD SHX Text
TO MAINTAIN CLEANLINESS).
AutoCAD SHX Text
(TYPICAL REGULATOR INSTALLATION).
AutoCAD SHX Text
(INSTALL PRIOR TO
AutoCAD SHX Text
CONSTRUCTION).
AutoCAD SHX Text
PRIOR TO CONSTRUCTION).
AutoCAD SHX Text
FLEX DUCT
AutoCAD SHX Text
CART WITH CANVAS/
AutoCAD SHX Text
1-1/4" SQUARE
AutoCAD SHX Text
TUBE FRAME AND
AutoCAD SHX Text
ZIPPER SIDE ENTRY
AutoCAD SHX Text
PLASTIC WINDOW
AutoCAD SHX Text
HEPA NEGATIVE AIR UNIT
AutoCAD SHX Text
MOBILE CONTAINMENT
AutoCAD SHX Text
FLEX DUCT
AutoCAD SHX Text
NEED INSPECTION TAG AND
AutoCAD SHX Text
MONTHLY INSPECTION).
AutoCAD SHX Text
(INITIALS/DATED).
AutoCAD SHX Text
INFILTRATION (INSTALL
AutoCAD SHX Text
(REFER TO
AutoCAD SHX Text
ELEV. DETAIL)
AutoCAD SHX Text
SCALE: 1/2"=1'-0"
AutoCAD SHX Text
SCALE: 1/2"=1'-0"
AutoCAD SHX Text
SCALE: 1/2"=1'-0"
AutoCAD SHX Text
PROTECTED OR COVERED WITH ROSEN
AutoCAD SHX Text
PAPER/FIRE RATED PLYWOOD.
AutoCAD SHX Text
THE REQUIRED INFECTION CONTROL RISK ASSESSMENT FORMS
AutoCAD SHX Text
MUST BE COMPLETED AND POSTED IN THE PROPER AREA.
AutoCAD SHX Text
THE REQUIRED INTERIM LIFE SAFETY MEASURES FORMS
AutoCAD SHX Text
MUST BE COMPLETED AND POSTED IN THE PROPER AREA.
AutoCAD SHX Text
DAILY FIRE WATCH INSPECTIONS MUST BE PROVIDED DAILY BY THE
AutoCAD SHX Text
PROJECT COR OR PERSON(S) ASSIGNED BY THE PROJECT
AutoCAD SHX Text
COR. THIS MUST BE LOGGED IN WITH DOCUMENTATION.
AutoCAD SHX Text
THE AREA. PROJECT COR TO HAVE DOCUMENTED PROOF OF
AutoCAD SHX Text
THE PROJECT COR SHALL NOTIFY THE PROPER SHOP
AutoCAD SHX Text
PERSONNEL AND STAFF MEMBERS WITH A MIN. OF 21 DAYS
AutoCAD SHX Text
IN ADVANCE FOR ANY UTILITIES SHUT-DOWN(S) THAT WILL EFFECT
AutoCAD SHX Text
REQUIREMENT. (NOT APPLICABLE ON SOME PROJECTS).
AutoCAD SHX Text
TO BE PROVIDED WHEN APPLICABLE WITH PROJECT
AutoCAD SHX Text
THIS ACTION.
AutoCAD SHX Text
LOGGED IN WITH DOCUMENTATION.
AutoCAD SHX Text
INTERIM LIFE SAFETY MEASURES FORM WILL BE SIGNED BY
AutoCAD SHX Text
THE COR AND SAFETY REPRESENTATIVE.
AutoCAD SHX Text
SITE TO BE INSPECTED ON A DAILY BASES AND MUST BE
AutoCAD SHX Text
SITE AREA PLASTIC WALL AND/OR ANTE ROOM ENCLOSURE WILL
AutoCAD SHX Text
BE INSPECTED BY INFECTION CONTROL PREVENTION COORDINATOR,
AutoCAD SHX Text
SAFETY REPRESENTATIVE AND CONTRACT OFFICER REPRESENTATIVE
AutoCAD SHX Text
(COR) FOR APPROVAL PRIOR TO PROJECT START/RELEASE DATE.
AutoCAD SHX Text
REMOVAL OF PLASTIC WALLS AND ENCLOSURES TO BE REMOVED
AutoCAD SHX Text
UPON THEIR APPROVAL.
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ENGINEER
AutoCAD SHX Text 062-073724
AutoCAD SHX Text
REGISTERED
CONSULTANTS: ARCHITECT/ENGINEERS:
Revisions: Date:
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration
REPLACE HOT WATER GENERATORS IN
B24, B51, & B53
JEFFERSON BARRACKS CAMPUS
1 JEFFERSON BARRACKS DR - ST. LOUIS, MO 63125
657-24-109JB
10/04/2024 DEH DAE 17
2707 Rand Rd Indianapolis, IN 46241
(317) 646 - 9090
100% CONSTRUCTION DOCUMENTS - FOR BIDDING
FULLY SPRINKLERED
S
TATE
OF I L L
NO
I S
I
R
MG-001
ABBREVIATIONS, LEGENDS, & NOTES -
MECHANICAL
CEILING DIFFUSER
EXIST..
ELEC.
EF
EP
ECC
DWG
DPT
DN
Db
DCP
CR
dB
CW
CP
CONN
COND
CHWR
CHWS
CFM
CC
BLDG
AHU
AFMS
ABV
AC
EXISTING
ELECTRICAL
EXHAUST FAN
ELECTRICAL/PNEUMATIC
ENGINEERING CONTROL CENTER
DRAWINGS
DIFFERENTIAL PRESSURE TRANSMITTER
DOWN
DECIBELS
DRY BULB TEMPERATURE, (DEGREES)
DISTRIBUTED CONTROL PANEL
CONDENSATE RETURN
COLD WATER
CONDENSATE PUMP
CONNECT
CONDENSATE
CHILLED WATER RETURN (PIPING)
CHILLED WATER SUPPLY (PIPING)
CUBIC FEET PER MINUTE
COOLING COIL
BUILDING
AIR HANDLING UNIT
AIR FLOW MEASURING STATION
ABOVE
AIR CONDITIONING UNIT
WFMD
WF
WC
Wb
VAV
VTR
VSMC
TYP
TEMP
T'STAT
SYS
SQ/FT
SPT
SPS
SPEC.
SP
SHT
RV
RM
RET
REQ'D
PRV
PSI
PL
PHC
PD
O.C.
N.O.
NO
O.L.
NC
WATER FLOW MEASURING DEVICE
WATER FILTER
WATER COLUMN
WET BULB
VARIABLE AIR VOLUME
VENT THROUGH ROOF
VARIABLE SPEED MOTOR CONTROLLER
TYPICAL
TEMPERATURE
THERMOSTAT
SYSTEM
SQUARE FEET
STATIC PRESSURE SENSOR
SPECIFICATION
STATIC PRESSURE (INCHES OF WATER)
STATIC PRESSURE TRANSMITTER
SHEET
RELIEF VENT
ROOM
RETURN
REQUIRED
PRESSURE REDUCING VALVE
POUNDS PER SQUARE INCH
PLACES
PREHEAT COIL
OVER LOAD
ON CENTERS
NORMALLY OPEN
PRESSURE DROP (FEETWATER)
NUMBER
NOISE CRITERIA
MT'D
MFG
MIN.
MECH
MAX.
MVD
LBS/HOUR
LTCP
LPS
LPR
KWH
IN
HWP
MOUNTED
KW
MANUFACTURER
MINIMUM
MECHANICAL
MAXIMUM
MANUAL VOLUME DAMPER
POUNDS PER HOUR
LOCAL TEMPERATURE CONTROL PANEL
LOW PRESSURE STEAM SUPPLY
LOW PRESSURE STEAM RETURN
KILOWATT HOUR
KILOWATT
INCHES
HOT WATER PUMP
HAND-OFF-AUTOHOA
O.A./OSA
SF
E
RAG
CD
R
S
HWR
HWS
HPR
HPS
HP
HORIZ.
HC
G.P.M.
FEET PER MINUTE
FLANGED (SEE DWG'S)
FLEXIBLE CONNECTOR
FD FLOOR DRAIN
FPM
FLNG'D
FLEX. CONN.
FLEX
FLR.
FF
EXH
FLEXIBLE
FLOOR
FINAL FILTER
EXHAUST AIR
GA.
F&T
FT
OUTDOOR AIR
SUPPLY FAN
EXHAUST CFM
RETURN AIR GRILLE
CEILING DIFFUSER
RETURN CFM
SUPPLY CFM
HEATING WATER RETURN
HEATING WATER SUPPLY
HIGH PRESSURE RETURN
HIGH PRESSURE STEAM
HORSEPOWER
HORIZONTAL
HEATING COIL
GALLONS PER MINUTE
GAGE
FLOAT AND THERMOSTATIC
FEET
VALVES
BALL VALVE
P/T TEST PLUG (PRESSURE/TEMPERATURE)
MANUAL AIR VENT
PRESSURE REDUCING VALVE
SAFETY OR PRESSURE RELIEF VALVE
THREE-WAY MODULATING CONTROL VALVE
STRAIGHT-THRU TWO POSITION CONTROL VALVE
STRAIGHT-THRU MODULATING CONTROL VALVE
CIRCUIT SETTER
BALANCING VALVE
BUTTERFLY-VALVE
CHECK VALVE
GATE VALVE WITH 3/4" HOSE ADAPTER
GLOBE VALVE
ANGLE GLOBE VALVE
GATE VALVE
ABBREVIATION LEGEND
FLAT OVAL DUCT DOWN
FLAT OVAL DUCT UP
CEILING SUPPLY DIFFUSER W/ CFM INDICATED (FOUR WAY THROW)
LD LINEAR DIFFUSER
WITH CFM INDICATED
6"
FC
D
R
EXHAUST CEILING REGISTER OR GRILLE
FLEXIBLE CONNECTION
INCLINED DROP, IN DIRECTION OF AIR FLOW
INCLINED RISE, IN DIRECTION OF AIR FLOW
EXHAUST OR RETURN TOP REGISTER OR GRILLE (WALL TYPE)
SUPPLY TOP REGISTER OR GRILLE (WALL TYPE)
VANE TURN ELBOW & AIR SPLIT TYPE DUCT TAKE-OFF
V.D.
MANUAL VOLUME DAMPER
LOUVER
SPIN-N-TAP WITH MVD DAMPER
DOUBLE WALL SOUND
STANDARD RADIUS ELBOW
VANED ELBOW (SHORT RADIUS)
ELBOWS WITH VANES EVEN IF SYMBOL IS MISSING)
VANED ELBOW (PROVIDE ALL SQUARE OR RECTANGULAR
DUCTWORK ELBOW UNLESS NOTED OTHERWISE.
THICKNESS VANES. VANES REQUIRED IN ALL
SQUARE TYPE ELBOW WITH DOUBLE
UP
UP
7:1 RATIO FOR HIGH PRESSURE.
TRANSITION. 4:1 RATIO FOR LOW PRESSURE,
ELBOW TURNED DOWN WITH TURNING VANES
ELBOW TURNED UP WITH TURNING VANES
RETURN AIR DUCT
EXHAUST AIR DUCTDOWN
OUTSIDE AIR DUCT
SUPPLY AIR DUCTDOWN
DUCTWORK LEGEND
12X10
6"0M.V.D.
RECTANGULAR DUCT (WXH)
RND DUCT TAKE OFF WITH SPIN-IN EXTRACTOR
MANUAL VOLUME DAMPER
FLEXIBLE DUCT (MAXIMUM 5'-0" IN LENGTH)
MOTORIZED DAMPER (OPPOSED BLADE) W/INTERLOCK
R
DN.
DIRECTION OF AIR FLOW
INCLINED RISE IN RESPECT TO
DIRECTION OF AIR FLOW
INCLINED DROP IN RESPECT TO
100S
MOTORIZED DAMPER (PARALLEL BLADE) W/INTERLOCK
ROOM CONTROL: THERMOSTAT, HUMIDISTATT H
T REMOTE BULB THERMOSTAT
DUCT OR PIPE THERMOSTAT (NOTE: PROVIDE 12" MINT
LENGTH IN DUCT WHEN SPACE PERMITS)
DUCT OR PIPE TEMP. SENSOR SEE NOTE ABOVE.T
H
DUCT STATIC PRESSURE SENSOR
DUCT HUMIDITY SENSOR
SP
F SMOKE DETECTOR (SEE ELECTRICAL DWGS)
SD
C HOLDING COIL IN MOTOR STARTER
CONTACT, NORMALLY OPEN (N.O.)
CONTACT, NORMALLY CLOSED (N.C.)
SWITCH
SIGNAL FROM ECC OR DCP
SIGNAL TO ECC OR DCP
SIGNAL TO FIRE ALARM SYSTEM
PRESSURE TRANSMITTERP
HIGH PRESSURE STEAM (60 PSIG & ABOVE)
HIGH PRESSURE STEAM CONDENSATE RETURN
MEDIUM PRESSURE STEAM (16 PSIG THRU 59 PSIG)
MEDIUM PRESSURE STEAM CONDENSATE RETURN
LOW PRESSURE STEAM (15 PSIG & BELOW)
LOW PRESSURE STEAM CONDENSATE RETURN
CONDENSATE PUMP DISCHARGE
HOT WATER HEATING SUPPLY
HOT WATER HEATING SUPPLY
VENT LINE
PIPING SYMBOLS
CONTROLS
OVERALL GENERAL NOTESGENERAL
EX. PIPE TO BE REMOVED
WATER FLOW MEASURING DEVICE
THERMOMETER
STRAINER
THERMOSTATIC TRAP
FLOAT & THERMOSTATIC TRAP SET INCLUDING PIPING
ACCESSORIES (SEE STD. DETAIL)
ACCESSORIES (SEE STD. DETAIL)
INVERTED BUCKET TRAP SET INCLUDING PIPING
NEW AND EXISTING WORK ON REVISED SHEETS
POINT OF CONNECTION BETWEEN NEW
UNION
RISE OR DROP IN PIPE
SIDE CONNECTION
BOTTOM CONNECTION, 45° OR 90°
TOP CONNECTION, 45° OR 90°
ECCENTRIC REDUCER
REDUCER OR INCREASER
ANCHOR (ALSO SEE "D" DWGS)
DIRECTION OF FLOW
DIRECTION OF PIPE PITCH (DOWN)
FLEXIBLE DUCT
ECCENTRIC REDUCER
CONCENTRIC REDUCER
UNION
FINISHED FLOORFIN.
NEGATIVE PRESSURE RELIEF VENTNPR
NEGATIVE PRESSURE RELIEF VENT
NPR
FIRE SMOKE DAMPERFSD
F.S.D. FIRE/SMOKE DAMPER
F.S.D.
ANCHORX
OR
NORMALLY CLOSEDN.C.
100S
10 X 8 NEW DUCT-WIDTH X DEPTH
ATTENUATING DUCT
CHILLED WATER RETURN
CHILLED WATER SUPPLY
F.D.
F.D. FIRE DAMPER
POINT OF WHERE DEMOLITION STOPS AND
EXISTING IS TO REMAIN ON DEMO SHEETS
INFORMATION CONCERNING THE LOCATION(S) AND SIZES OF EXISTING
EQUIPMENT AND PIPING WAS OBTAINED FROM EXISTING DRAWINGS AND
CURSORY FIELD OBSERVATION, HOWEVER, ACTUAL "ASBUILT" DRAWINGS WERE
NOT AVAILABLE, CERTAIN INFORMATION CONCERNING THE LOCATION OF THE
EXISTING CONDITIONS HAS BEEN ASSUMED IN THIS DRAWING. THE EXACT
LOCATION(S) AND DIRECTION OF FLOW OF ALL EXISTING EQUIPMENT, ETC., IS
UNKNOWN. REASONABLE EFFORT HAS BEEN MADE TO ACCURATELY DEPICT THE
EXISTING CONDITIONS, HOWEVER, ALL EXISTING WORK MUST BE VERIFIED IN
THE FIELD TO DETERMINE THE EXACT LOCATIONS, DIRECTIONS OF PIPE RUNS,
SIZE, ETC.. PRIOR TO STARTING CONSTRUCTION. ANY CONFLICT BETWEEN THESE
PLANS AND ACTUAL FIELD CONDITIONS SHALL BE REPORTED IMMEDIATELY TO
THE ENGINEER FOR VERIFICATION AND/OR CORRECTION.
PIPING FIELD VERIFY:
MECHANICAL FIELD VERIFY:
INFORMATION CONCERNING THE LOCATION(S) AND SIZES OF EXISTING
DUCTWORK AND DIFFUSERS WAS OBTAINED FROM EXISTING DRAWINGS AND
CURSORY FIELD OBSERVATION, HOWEVER, ACTUAL "ASBUILT" DRAWINGS WERE
NOT AVAILABLE, CERTAIN INFORMATION CONCERNING THE LOCATION OF THE
EXISTING CONDITIONS HAS BEEN ASSUMED IN THIS DRAWING. THE EXACT
LOCATION(S) AND DIRECTION OF FLOW OF ALL EXISTING EQUIPMENT, ETC., IS
UNKNOWN. REASONABLE EFFORT HAS BEEN MADE TO ACCURATELY DEPICT THE
EXISTING CONDITIONS, HOWEVER, ALL EXISTING WORK MUST BE VERIFIED IN
THE FIELD TO DETERMINE THE EXACT LOCATIONS, DIRECTIONS OF DUCT RUNS,
SIZE, ETC.. PRIOR TO STARTING CONSTRUCTION. ANY CONFLICT BETWEEN THESE
PLANS AND ACTUAL FIELD CONDITIONS SHALL BE REPORTED IMMEDIATELY TO
THE ENGINEER FOR VERIFICATION AND/OR CORRECTION.
MECHANICAL GENERAL NOTES:
FOR GENERAL DUCT CONSTRUCTION AND PIPING CONNECTIONS SEE DETAILS ON
ALL WORK SHALL BE IN ACCORDANCE WITH THE BEST QUALITY STANDARDS OF THE
TRADE, AND SHALL CONFORM WITH ALL FEDERAL, STATE, AND LOCAL CODES AND
STANDARDS.
CONSTRUCTION DOCUMENTS SHALL BE FOLLOWED AS CLOSELY AS POSSIBLE,
HOWEVER, SYSTEMS HAVE BEEN SHOWN DIAGRAMMATICALLY AND IN SOME CASES,
ENLARGED FOR CLARITY. ANY OFFSETS, ADDITIONAL FITTINGS, AND/OR
APPURTENANCES REQUIRED TO PROVIDE A COMPLETE AND COORDINATED SYSTEM
SHALL BE BORNE BY THE CONTRACTOR.
BALANCE DAMPERS SHALL BE LOCATED AT BRANCH CONNECTION TO THE MAIN.
ALL EQUIPMENT INCLUDING BUT NOT LIMITED TO DUCTWORK, PIPING, UNIT HEATERS,
ETC. SHALL BE HUNG FROM THE TOP CHORD OF THE STRUCTURAL STEEL OR BY HANGERS
EACH MAIN DUCT PASSING THROUGH FLOOR SPACES SHALL BE FIRE DAMPERED.
ALL EXTERIOR PENETRATIONS SHALL BE WEATHER AND WATER TIGHT.
CONTRACTORS ARE TO REVIEW EXISTING STRUCTURAL AND PLANS, WITH ACTUAL
LAYOUT OF BEAMS, JOISTS, ETC. TO AVOID CONFLICT BETWEEN DUCT. ADJUST DUCT
ROUTING TO ACCEPT STRUCTURAL CONDITIONS.
ALL EXHAUST DISCHARGES AND GAS FLUES WHERE INDICATED SHALL BE LOCATED A
MINIMUM OF 25'-0" AWAY FROM OUTSIDE AND COMBUSTION AIR INTAKES UNLESS LOCAL
AND STATE CODES MANDATE ADDITIONAL DISTANCE.
WHERE WALL TYPE LOUVERS ARE INDICATED, MECHANICAL CONTRACTOR SHALL SEAL
WATER-TIGHT ALL AROUND LOUVER WITH SILICON CAULKING. CONTRACTOR SHALL
COORDINATE PAINTING REQUIREMENTS FOR LOUVERS WITH GENERAL CONTRACTOR
PRIOR TO SUBMITTING BID.
A.
B.
C.
D.
E.
F.
H.
I.
J.
K.
G.
H4
H7
A
DETAIL NUMBER
DRAWING NUMBER WHERE SHOWN
SECTION LETTER
DRAWING NUMBER WHERE DRAWN
CROSS HATCHED AREAS ARE NOT IN
CONTRACT AND ARE EXISTING TO
REMAIN, UNLESS SPECIFICALLY NOTED
OR SHOWN OTHERWISE.
E.T.R.
THIS SYMBOL SHOWS THE APPROXIMATE POINT WHERE
NEW WORK STARTS AND EXISTING IS TO REMAIN.
CONTRACTOR SHALL VERIFY ELECTRICAL CHARACTERISTICS OF ALL MECHANICAL
EQUIPMENT WITH THE ELECTRICAL CONTRACTOR PRIOR TO PLACING EQUIPMENT ON
ORDER
MECHANICAL DETAILS SHEET.
CONNECTED TO CONCRETE SLAB ABOVE AS REQUIRED.
FOR DEMOLITION THIS SYMBOL SHOW THE
APPROXIMATE POINT WHERE DEMOLITION STOPS AND
EXISTING IS TO REMAIN FOR NEW WORK.
E.T.R. EXISTING TO REMAIN
RTU ROOF TOP UNIT
OR
1. ALL PIPING AND DUCTS IN FINISHED ROOMS OR SPACES SHALL BE
CONCEALED IN FURRED CHASE OR SUSPENDED CEILING.
2. THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION OF FACE SHOWN
OR INDICATED. DUCT SIZES ARE NET INSIDE DIMENSIONS.
3. ACCESS PANELS IN SUSPENDED CEILINGS ARE REQUIRED FOR ALL VALVES,
TRAPS, DAMPERS, CLEANOUTS, CONTROLS, ETC.,AND SHALL BE
FURNISHED AND INSTALLED UNDER ARCHITECTURAL SPECIFICATIONS.
4. TOTAL STATIC PRESSURE NOTED IN SCHEDULES INCLUDES DUCT SYSTEM,
TERMINAL UNITS, FILTERS, COILS, ETC.
5. FOR TYPICAL STEAM, WATER & PIPING CONNECTIONS TO EQUIPMENT SEE
STANDARD DETAILS.
6. CEILING DIFFUSER SIZES SHOWN ON FLOOR PLANS ARE NECK SIZES.
7. WATER PIPE CONNECTIONS TO AIR HEATING AND COOLING COILS SHALL
BE MADE SO THERE WILL BE COUNTER FLOW BETWEEN WATER AND AIR.
8. NOT ALL DUCT OFFSETS ARE SHOWN TO AVOID OBSTACLES OR PROVIDE
SUFFICIENT ACCESS CLEARANCE. PROVIDE COORDINATED SHOP DRAWING
FOR APPROVAL BEFORE CONSTRUCTION.
9. ALL AIR DEVICES SHALL BE PROVIDED WITH VOLUME DAMPERS
REGARDLESS OF WHETHER IT IS SHOWN ON THE DRAWING. ALL AIR
DEVICES SHALL HAVE A VOLUME DAMPER. PROVIDE CABLE ACTUATED
DAMPER OR ROOMSIDE ADJUSTABLE DAMPER WHERE EILING PLENUM IS
INACCESSIBLE.
DRAWING SYMBOLS
MPCR
MPS
MEDIUM PRESSURE CONDENSATE RETURN
MEDIUM PRESSURE STEAM
STEAM VENTSV
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ENGINEER
AutoCAD SHX Text 062-073724
AutoCAD SHX Text
REGISTERED
AutoCAD SHX Text
PROFESSIONAL
AutoCAD SHX Text
HWH
AutoCAD SHX Text
HWHR
AutoCAD SHX Text V
AutoCAD SHX Text V
AutoCAD SHX Text
CHR
CH
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration
REPLACE HOT WATER GENERATORS IN
B24, B51, & B53
JEFFERSON BARRACKS CAMPUS
1 JEFFERSON BARRACKS DR - ST. LOUIS, MO 63125
657-24-109JB
10/04/2024 DEH DAE 17
2707 Rand Rd Indianapolis, IN 46241
(317) 646 - 9090
100% CONSTRUCTION DOCUMENTS - FOR BIDDING
FULLY SPRINKLERED
S
TATE
OF I L L
NO
I S
I
R
MG-002
DETAILS - MECHANICAL
NOTE:
(FULL SIZE)
DIRT POCKET
6" MIN.
STEAM MAIN
BASE OF RISER DRIPS SIMILAR TO ABOVE
OF TRAP
FULL SIZE
5LB. DROP UNLESS OTHERWISE
BUCKET TRAP CAP 200LBS/HR @
INDICATED; DETAIL B6/MQ004
DRIP RETURN MAIN
NO SCALE
TYPICAL WATER PIPING
REDUCER, IF REQUIRED
PROVIDE HOSE CAP NUTELEVATION
WELDED PIPING
ELEVATION
THREADED PIPING
NOTES:
DRAIN ALL LOW POINTS AS INDICATED ABOVE.1.
2.
NO SCALE
REDUCER
CIRCULATING WATER
PIPING
IF AUTOMATIC AIR VENTS ARE USED,
PIPE DISCHARGE TO DRAIN.
VENT ALL HIGH POINTS AS INDICATED ABOVE.
2.
NOTES:
1.
WHERE SCALE POCKETS ARE SHOWN ON PIPE
RISER DIAGRAMS AND/OR PLANS, LOCATE
DRAIN AT BOTTOM OF SCALE POCKET.
NO SCALE
1/4" COPPER TUBING
3/8" GATE VALVE
3/8" 4" NIPPLE
ADAPTER TO 3/4" THREAD
3/4" GATE VALVE
NO SCALE
NO SCALE
LAST
CONNECTION ON
LINE
EXPANSION TANK PIPING DETAIL
MAKE-UP WATER AND TYPICAL WATER CONNECTIONS TO
H.W. HEATING CONVERTOR DETAIL
GATE VALVE (TYP)
TEMPERATURE SENSOR AND
TRANSMITTER
ASME RATED PRESSURE
RELIEF VALVE PIPE DISCHARGE
TO FLOOR DRAIN
HWS
GAUGE COCK (TYP)
CONVERTOR
UNION (TYP)
HWR
T
SEE DETAIL E/MQ006 FOR STEAM
AND CONDENSATE PIPING
TO FLOOR DRAIN
NO SCALE
HEATING CONVERTOR DETAIL
TYPICAL STEAM CONNECTIONS TO H.W.
CONVERTOR
CONTROL VALVE
SIZE AS
BUCKET TRAP
VACUUM BREAKER
AUTO AIR VENT
STRAINER (TYP); WITH HOSE END
BLOW DOWN VALVE; TYPICAL
ECCENTRIC REDUCER (TYP)GLOBE VALVE BYPASS SAME
STEAM MAIN
CONDENSATE
RETURN
(TYPICAL)
UNION
CONTROL VALVE
(TYPICAL)
GATE VALVE
1/3 CAPACITY
2/3 CAPACITY
2/3 CAPACITY
SEE DETAIL
K/MQ006
FOR WATER PIPING
NO SCALE
NO SCALE NO SCALE
FRONT VIEW
Auto
Pump
Off Hand
Pump
Hand Auto Off
ITT
Domestic
Domestic
ITT
Off Hand
Pump
AutoAuto Off
Hand
Pump
BACK VIEW
NO SCALE
b
CEM-TROL
Menu
Power On
Primary High Limit
Secondary High Limit
Temperature / Status
(Select) Silence Alarm
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ENGINEER
AutoCAD SHX Text 062-073724
AutoCAD SHX Text
REGISTERED
AutoCAD SHX Text
PROFESSIONAL
AutoCAD SHX Text
STEAM MAIN DRIP CONNECTION
AutoCAD SHX Text
%%UEND OF H.P. OR M.P.
AutoCAD SHX Text
VALVE CONNECTION
AutoCAD SHX Text %%uTYPICAL DRAIN
AutoCAD SHX Text
TYPICAL AIR VENT
AutoCAD SHX Text %%uELEVATION
AutoCAD SHX Text
ASSEMBLY
AutoCAD SHX Text
INVERTED BUCKET STEAM TRAP
AutoCAD SHX Text
NOTE: 1. 2.
AutoCAD SHX Text ALL DRIP POINTS ON STEAM MAINS SHALL BE PROVIDED WITH A 12" MINIMUM HIGH DRIP LEG FROM BOTTOM OF STEAM MAIN TO TRAP INLET. DRIP LEG SHALL HAVE 6" SCALE POCKET BELOW TRAP INLET. PROVIDE BYPASS PIPING.
AutoCAD SHX Text
SEE DRAWINGS FOR PIPE SIZES
AutoCAD SHX Text
TO RETURN MAIN
AutoCAD SHX Text
SCHEDULE 80 STEEL PIPE
AutoCAD SHX Text
PIPE SIZE SHALL BE SAME SIZE AS TRAP
AutoCAD SHX Text
INVERTED BUCKET TRAP. SEE PLANS, AND SCHEDULES
AutoCAD SHX Text
FLOW
AutoCAD SHX Text
SCHEDULE 80 STEEL PIPE
AutoCAD SHX Text BYPASS-INSTALL IN HORIZONTAL PLANE LEVEL WITH TRAP OR IN VERTICAL PLANE & BELOW TRAP
AutoCAD SHX Text
12" MIN.
AutoCAD SHX Text
6" MIN.
AutoCAD SHX Text DRIP LEG OR EQUIPMENT CONNECTION. MAKE THE SAME SIZE AS THE SUPPLY MAIN OR EQUIPMENT CONNECTION. SEE NOTE 1
AutoCAD SHX Text [300mm]
AutoCAD SHX Text [150mm]
AutoCAD SHX Text
1" GATE VALVE
AutoCAD SHX Text
DIELECTRIC FITTING WHERE RETURN IS COPPER PIPE
AutoCAD SHX Text
%%USTEAM TRAP ASSEMBLY
AutoCAD SHX Text
[6"] MIN.
AutoCAD SHX Text
[12"] MIN.
AutoCAD SHX Text
[6"] MIN.
AutoCAD SHX Text
[12"] MIN.
AutoCAD SHX Text
DRIP LEG (TYP.)
AutoCAD SHX Text 3/4" [20mm] DRAIN (ALTERNATE LOCATIONS) (TYPICAL)
AutoCAD SHX Text
STEAM LINE (TYPICAL)
AutoCAD SHX Text
CAP (TYPICAL)
AutoCAD SHX Text
PIPE T0 STEAM TRAP (TYPICAL)
AutoCAD SHX Text
NOTE: DRIP POCKET PIPE SIZE SAME AS STEAM MAIN UNLESS OTHERWISE NOTED.
AutoCAD SHX Text
STEAM LINE DRIP POCKET
AutoCAD SHX Text 3/4" [20mm] MIN.
AutoCAD SHX Text
FROM DRIP CONNECTION
AutoCAD SHX Text
DRIP RETURN
AutoCAD SHX Text 3/8" [10mm] TEST CONNECTION
AutoCAD SHX Text
STEAM TRAP ASSEMBLY
AutoCAD SHX Text
STEAM LINE DRIP POCKET
AutoCAD SHX Text A5
AutoCAD SHX Text E7
AutoCAD SHX Text A8
AutoCAD SHX Text A7
AutoCAD SHX Text C5
AutoCAD SHX Text
GAUGE WITH COCK AND SNUBBER
AutoCAD SHX Text
EXPANSION LINE;
AutoCAD SHX Text
PIPE TO SUCTION
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
OF PUMPS
AutoCAD SHX Text
LINE FULL SIZE
AutoCAD SHX Text
PIPE DISCHARGE
AutoCAD SHX Text 1/2"
AutoCAD SHX Text
TO DRAIN
AutoCAD SHX Text
GLOBE VALVE
AutoCAD SHX Text
EXPANSION TANK
AutoCAD SHX Text
RELIEF VALVE
AutoCAD SHX Text
BALL VALVE; TYPICAL
AutoCAD SHX Text
LIKE WILKINS SERIES 70
AutoCAD SHX Text
PRESSURE REDUCING VALVE,
AutoCAD SHX Text
DET108
AutoCAD SHX Text
STRAINER
AutoCAD SHX Text 1/2"
AutoCAD SHX Text
BACKFLOW PREVENTER
AutoCAD SHX Text
FROM DOMESTIC
AutoCAD SHX Text
WATER SUPPLY
AutoCAD SHX Text
UNION; TYPICAL
AutoCAD SHX Text
REDUCED PRESSURE
AutoCAD SHX Text A1
AutoCAD SHX Text E5
AutoCAD SHX Text A3
AutoCAD SHX Text
BUILDING 51 & 53 HOT WATER GENERATOR
AutoCAD SHX Text C1
AutoCAD SHX Text
BUILDING 24 HOT WATER GENERATOR
AutoCAD SHX Text C9
AutoCAD SHX Text
H6SEH636 - BASIS OF DESIGN
AutoCAD SHX Text 2"M.N.P.T. Hot Water Outlet
AutoCAD SHX Text Relief Valve
AutoCAD SHX Text Water Solenoid Safety Valve (DSSS) (optional)
AutoCAD SHX Text Pressure Gauge
AutoCAD SHX Text Cem-trol Control Panel
AutoCAD SHX Text 2" M.N.P.T. Cold Water Inlet
AutoCAD SHX Text Main Trap
AutoCAD SHX Text Intratank Circulator
AutoCAD SHX Text Auxilary Trap
AutoCAD SHX Text Steam Inlet
AutoCAD SHX Text Source Steam Pressure Gauge
AutoCAD SHX Text Cem-trol Control Panel
AutoCAD SHX Text Condensate Outlet (requires gravity drain)
AutoCAD SHX Text
CEMLINE CORPORATION
AutoCAD SHX Text
CONNECTIONS TO DOMESTIC WATER HEATER
AutoCAD SHX Text
NTS
AutoCAD SHX Text
12" MIN.
AutoCAD SHX Text [300mm]
AutoCAD SHX Text [150mm]
AutoCAD SHX Text
CONTROL VALVE BY MANUFACTURER OF DOMESTIC WATER HEATER
AutoCAD SHX Text
FLOAT & THERMOSTATIC TRAP ASSEMBLY
AutoCAD SHX Text
GRAVITY STEAM CONDENSATE RETURN
AutoCAD SHX Text
DIELECTRIC FITTING
AutoCAD SHX Text
SCALE POCKET
AutoCAD SHX Text
DOMESTIC WATER HEATER
AutoCAD SHX Text TRAP OR ORIFICED UNION FITTING FURNISHED BY MANUFACTURER OF DOMESTIC WATER HEATER, SEE PLUMBING DWGS.
AutoCAD SHX Text
FLOOR
AutoCAD SHX Text
NOTES:
AutoCAD SHX Text
1. VERTICAL COIL TYPE DOMESTIC WATER HEATER IS SHOWN. IF HORIZONTAL TUBE BUNDLE VERTICAL COIL TYPE DOMESTIC WATER HEATER IS SHOWN. IF HORIZONTAL TUBE BUNDLE TYPE IS FURNISHED, PIPING SHALL BE SIMILAR. 2. SEE PLUMBING DRAWINGS FOR PIPING CONNECTIONS. SEE PLUMBING DRAWINGS FOR PIPING CONNECTIONS. 3. PIPING TO UPPER HEATER HEAD SHOULD BE PROVIDED WITH UNION OR FLANGES, LOCATED PIPING TO UPPER HEATER HEAD SHOULD BE PROVIDED WITH UNION OR FLANGES, LOCATED OUTSIDE THE OUTER DIAMETER OF HEAD TO FACILITATE REMOVAL OF HEAD AND SHELL. 4. PIPING BETWEEN CONTROL VALVE AND HEATER CONNECTION SHOULD BE AS SHORT AS PIPING BETWEEN CONTROL VALVE AND HEATER CONNECTION SHOULD BE AS SHORT AS POSSIBLE. 5. PROVIDE INTEGRAL OR EXTERNAL HEAT TRAPS. PROVIDE INTEGRAL OR EXTERNAL HEAT TRAPS. 6. PROVIDE HOSE CONNECTION TO DRAIN.PROVIDE HOSE CONNECTION TO DRAIN.
AutoCAD SHX Text
DHW
AutoCAD SHX Text
DCW
AutoCAD SHX Text
DHWR
AutoCAD SHX Text
DRAIN
AutoCAD SHX Text TEMPERATURE & PRESSURE RELIEF VALVE BY MANUFACTURER OF DOMESTIC WATER HEATER ROUTE TO NEAREST FLOOR DRAIN
AutoCAD SHX Text
PRESSURE GAUGE
AutoCAD SHX Text
THERMOMETER
AutoCAD SHX Text
STEAM SUPPLY
AutoCAD SHX Text
CONNECTIONS TO DOMESTIC WATER BOOSTER HEATER
AutoCAD SHX Text
NTS
AutoCAD SHX Text ALL STEAM BOOSTER HEATERS REQUIRED BY EQUIPMENT SPECIFICATION SHALL BE PIPED AS SHOWN ABOVE. SEE EQUIPMENT SPECIFICATION AND PLUMBING DRAWINGS FOR PIPING CONNECTIONS.
AutoCAD SHX Text
NOTES: 1. 2.
AutoCAD SHX Text
BOOSTER HEATER SEE EQUIPMENT SPECIFICATION
AutoCAD SHX Text
STEAM SUPPLY
AutoCAD SHX Text
CONTROL VALVE BY MANUFACTURER OF BOOSTER HEATER.
AutoCAD SHX Text
FULL SIZE OF BOOSTER HEATER INLET
AutoCAD SHX Text
THERMOMETER
AutoCAD SHX Text
DHW
AutoCAD SHX Text
DHW
AutoCAD SHX Text
SCALE POCKET
AutoCAD SHX Text
FLOAT AND THERMOSTATIC TRAP ASSEMBLY
AutoCAD SHX Text [300mm]
AutoCAD SHX Text [150mm]
AutoCAD SHX Text F1
AutoCAD SHX Text F3
AutoCAD SHX Text
OVERFLOW LOOP
AutoCAD SHX Text
DUPLEX CONDENSATE PUMP PACKAGE DETAIL
AutoCAD SHX Text
LIQUID TIGHT CONDUIT(RIGID CONDUIT)
AutoCAD SHX Text
CONDENSATE PUMP RATED FOR 200F AND SCHEDULED CAPACITY
AutoCAD SHX Text
PILOT LIGHT(S)
AutoCAD SHX Text
2-POLE FLOAT SWITCH
AutoCAD SHX Text NEMA 2 - CONTROL PANEL (UL LISTED) (STARTERS, FUSED DISCONNECTS, CIRCUIT TRANSFORMER, & POWER CONTROL RELAY)
AutoCAD SHX Text
TO VENT
AutoCAD SHX Text
UNION
AutoCAD SHX Text
OVERFLOW
AutoCAD SHX Text
CAST IRON RECEIVER (W/ REQ'D NPT OPENINGS)
AutoCAD SHX Text
2-POLE FLOAT SWITCH
AutoCAD SHX Text
PLUGGED DRAIN
AutoCAD SHX Text
TO DRAIN
AutoCAD SHX Text
BALANCE VALVE
AutoCAD SHX Text
PUMP DISCHARGE
AutoCAD SHX Text
CHECK VALVE
AutoCAD SHX Text
SYSTEM CONDENSATE RETURN (SCHD 80)
AutoCAD SHX Text
GATE VALVE
AutoCAD SHX Text
TO DRAIN
AutoCAD SHX Text
TO DRAIN
AutoCAD SHX Text
LOOP FILL
AutoCAD SHX Text
H-O-A SELECTOR SWITCHES
AutoCAD SHX Text
DIAL THERMOMETER
AutoCAD SHX Text
CAST IRON INLET STRAINER
AutoCAD SHX Text
WATER LEVEL GAUGE GLASS (W/ SHUTOFF VALVE)
AutoCAD SHX Text
LIFTING EYE BOLT
AutoCAD SHX Text
PUMP DISCHARGE PRESSURE GAUGE
AutoCAD SHX Text
BUTTERFLY SUCTION VALVE
AutoCAD SHX Text
FULL SIZE VENT LINE PIPED TO ATMOSPHERE
AutoCAD SHX Text C3
AutoCAD SHX Text
THERMOMETER
AutoCAD SHX Text
STRAINER WITH BLOWDOWN
AutoCAD SHX Text
FRONT
AutoCAD SHX Text
SIDE
AutoCAD SHX Text
TOP
AutoCAD SHX Text 2-1/2" NPT Cold Water Inlet
AutoCAD SHX Text Steam Inlet
AutoCAD SHX Text 2-1/2" NPT Hot Water Outlet
AutoCAD SHX Text Drain
AutoCAD SHX Text Relief Valve
AutoCAD SHX Text V45SSH8XX - BASIS OF DESIGN Energy Source - Steam
AutoCAD SHX Text Cem-trol Control Panel
Condensate Outlet (requires gravity drain)
Drawing Title
VA Health Care System Approval:
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Drawing # of
Veterans Health
Administration
REPLACE HOT WATER GENERATORS IN
B24, B51, & B53
JEFFERSON BARRACKS CAMPUS
1 JEFFERSON BARRACKS DR - ST. LOUIS, MO 63125
657-24-109JB
10/04/2024 DEH DAE 17
2707 Rand Rd Indianapolis, IN 46241
(317) 646 - 9090
100% CONSTRUCTION DOCUMENTS - FOR BIDDING
FULLY SPRINKLERED
S
TATE
OF I L L
NO
I S
I
R
MG-003
DETAILS - MECHANICAL
NO SCALENO SCALE
PIPE/DUCT PENETRATION OF SMOKE BARRIERS
NO SCALE
WALL
PRESSURE PLATE
BOLT
BASIS OF DESIGN: LINK SEAL
ELASTOMERIC SEAL ELEMENT
LS MODEL (C, L, S-316, O, OS-316, T)
LS Model Seal Element Bolts/Nuts Pressure Plate C EPDM (Black) Zinc Dichromate/Organic Coated Carbon Steel Bolt Reinforced Nylon Polymer L EPDM (Blue) Zinc Dichromate/Organic Coated Carbon Steel Bolt Reinforced Nylon Polymer O Nitrile Zinc Dichromate/Organic Coated Carbon Steel Bolt Reinforced Nylon Polymer T Silicone Zinc Dichromate/Organic Coated Carbon Steel Bolt Steel Zinc Dichromate (C,L,O)+S-316 (see model options) 316 Stainless Steel Reinforced Nylon Polymer
Sleeve Model Description Material CS Century-Line Sleeve HDPE WS Steel Wall Sleeve Steel
CAST / CORE DRILLED HOLE
HEAT SHRINK
CARRIER
PIPE
NOTE:
STEEL END CAP WILL INCREASE
OUTSIDE DIAMETER OF HDPE
JACKET BY 1/2"
16" LG STEEL END CAP*
GENERAL NOTES:
1. FOR SYSTEMS WHICH ARE ANCHORED, A MECHANICAL
COMPRESSIVE SEAL ASSEMBLY CAN BE UTILIZED FOR
WATERPROOFING THE WALL PENETRATION.
2. IF EXPANSION THRU THE WALL IS ANTICIPATED, WE
RECOMMEND THE FOLLOWING SEALING MECHANISM:
OUTSIDE FACE
OF WALL
WALL SLEEVE AND SEAL
(BY INSTALLING CONTR.)
INSULATION
JACKET
1/2" X 3" NIPPLE
NIPPLE THREADED
1/4"-20 BOLT
w/LOCK NUT
FOR GROUND
9"
6"3"
A. WRAP THE EXTERIOR OF THE JACKET WITH AN
OILED OAKUM MATERIAL FROM THE INSIDE OF THE
WALL TO ABOUT HALFWAY THRU THE WALL.
B. WRAP THE EXTERIOR OF THE JACKET WITH
ARMAFLEX MATERIAL TO THE OUTER WALL.
C. COAT THE ARMAFLEX WITH A BITUMASTIC SEALANT.
TEMPORARY WATER HEATER SIDE ELEVATION
NO SCALE
TEMPORARY WATER HEATER FRONT ELEVATION
NO SCALE
SAND BAGS OR WEIGHTED
BLOCKS SIMILAR TYPICAL
EX. FLOOR
WOOD FRAME
3/4" PLYWOOD WATER HEATER(S)
TWH-1 TWH-2
MIN
6'-0"
1"Ø UNION; TYPICAL
PIPE TO HOSE CONNECTION; TYPICAL
EX. FLOOR
WYE CONNECTION
PEX HOSE; TYPICAL
WOOD STAND
MIN
36"
DCW - IN
DHW - OUT
DHW - OUT
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX…