00 01 15 Lincoln New Salem HVAC Upgrade Drawing Sheets Attachment B.pdf

PDF 3 MB Posted

Attached to
DNR-New Salem-HVAC Controls Upgrade
Solicitation number
21-422DNR-DIREC-B-18089
Issued by
Madison County, Peoria City, Illinois

About this file

This document is an attachment to a state and local contract opportunity issued by the Illinois Department of Natural Resources (IDNR) for HVAC control upgrades at the Lincoln New Salem historic site. The project involves the demolition of existing HVAC controls and the installation of new DDC controls for the air handling units, boilers, chillers, and other HVAC equipment. The bid set includes drawings and specifications detailing the scope of work. Responses must be submitted electronically per CPO Notice 2020.06, with paper submissions not accepted. No site visit or pre-bid conference is mentioned.

The contract does not specify pricing terms, set asides, incumbent contractors, or funding sources. The bid documents indicate that the existing HVAC systems and controls at the historic site require upgrades, but do not provide details on the current environment or any budgetary requirements. The contract term is not explicitly stated.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PROJECT NO.: DATE:

PROFESSIONAL REGISTRATIONS

LOCATION MAP

PROJECT IMAGE

MAP DATA © 2017 GOOGLE

/1

/2

:2 :1

P

M

4-20-015

HVAC CONTROLS UPGRADE

ILLINOIS DEPT. OF NATURAL RESOURCES

LINCOLN'S NEW SALEM HISTORIC

SITE VISITORS CENTER - 15588

HISTORY LN, PETERSBERG, IL 62675

9/15/2020

IL

L

IN

O

IS

D

E P

T

O F

N A

T U

R A

L R

E S

O U

R C

E S

BID SET

H V

A C

C O

N T

R O

L S

U P

G R

A D

E

B

ID

S E

T

PAGES OR DIVISIONS COVERED:

LICENSE RENEWAL DATE:

DATE:

NAME:

SIGNATURE:

THE PORTION OF THIS TECHNICAL SUBMISSION DESCRIBED BELOW

WAS PREPARED BY ME OR UNDER MY DIRECT PERSONAL

SUPERVISION. I AM A DULY LICENSED ENGINEER UNDER THE

LAWS OF THE STATE OF ILLINOIS.

PAGES OR DIVISIONS COVERED:

LICENSE RENEWAL DATE:

DATE:

NAME:

SIGNATURE:

THE PORTION OF THIS TECHNICAL SUBMISSION DESCRIBED BELOW

WAS PREPARED BY ME OR UNDER MY DIRECT PERSONAL

SUPERVISION. I AM A DULY LICENSED ENGINEER UNDER THE

LAWS OF THE STATE OF ILLINOIS.

Jay D. Eman Sept 15, 2020

Nov 30, 2021

Electrical

JOSEPH M.

062-069758

GAIED

JOSEPH M. GAIED

Sep 15, 2020

Nov 30, 2021

Mechanical

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

G

H

I

J

K

1 2 3 4 5 6 7 8 9 10

DATE:

DRAWN:

REVIEWED:

SHEET TITLE:

SHEET NUMBER:

PROJECT NO.:

PROJECT:

ISSUE:

# DATE: DESCRIPTION:

DESIGNED:

/1

/2

:2 :2

P

M MD1.1

CONTROLS

DEMOLITION PLAN

EPH

JMG

4-20-015

HVAC CONTROLS

UPGRADE

ILLINOIS DEPT. OF NATURAL

RESOURCES

LINCOLN'S NEW SALEM

HISTORIC SITE VISITORS

CENTER - 15588 HISTORY LN,

PETERSBERG, IL 62675

9/15/2020

9/15/2020

BID SET

EPH, JMG

KEYNOTES

1 VALVES TO REMAIN. DEMOLISH VALVE ACTUATORS AND ASSOCIATED PNEUMATIC

PIPING AND/OR WIRING BACK TO SOURCE CONTROL PANEL. TYPICAL.

2 DEMOLISH TEMPERATURE SENSOR, ELEMENT AND CONTROL WIRING TO SOURCE

CONTROL PANEL. TYPICAL.

3 DAMPERS TO REMAIN. DEMOLISH DAMPER ACTUATORS AND ASSOCIATED

PNEUMATIC PIPING BACK TO SOURCE CONTROL PANEL. TYPICAL.

4 DEMOLISH LOCAL CONTROL PANEL AND LOCAL CONTROL MODULES AND ALL

ASSOCIATED PNEUMATIC PIPING AND CONTROL WIRING.

5 ALL EXISTING MOTOR STARTERS ARE TO REMAIN.

SCALE: NOT TO SCALE

AHU-1 CONTROLS DEMOLITION

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

G

H

I

J

K

1 2 3 4 5 6 7 8 9 10

DATE:

DRAWN:

REVIEWED:

SHEET TITLE:

SHEET NUMBER:

PROJECT NO.:

PROJECT:

ISSUE:

# DATE: DESCRIPTION:

DESIGNED:

/1

/2

:2 :2

P

M MD1.2

CONTROLS

DEMOLITION PLAN

EPH

JMG

4-20-015

HVAC CONTROLS

UPGRADE

ILLINOIS DEPT. OF NATURAL

RESOURCES

LINCOLN'S NEW SALEM

HISTORIC SITE VISITORS

CENTER - 15588 HISTORY LN,

PETERSBERG, IL 62675

9/15/2020

9/15/2020

BID SET

EPH, JMG

KEYNOTES

1 VALVES TO REMAIN. DEMOLISH VALVE ACTUATORS AND ASSOCIATED PNEUMATIC

PIPING AND/OR WIRING BACK TO SOURCE CONTROL PANEL. TYPICAL.

2 DEMOLISH AVERAGING TEMPERATURE SENSOR, ELEMENT AND CONTROL WIRING

TO SOURCE CONTROL PANEL. TYPICAL.

3 DAMPERS TO REMAIN. DEMOLISH DAMPER ACTUATORS AND ASSOCIATED

PNEUMATIC PIPING BACK TO SOURCE CONTROL PANEL. TYPICAL.

4 DEMOLISH LOCAL CONTROL PANEL AND LOCAL CONTROL MODULES AND ALL

ASSOCIATED PNEUMATIC PIPING AND CONTROL WIRING.

5 ALL EXISTING MOTOR STARTERS TO REMAIN.

SCALE: NOT TO SCALE

AHU-2 CONTROLS DEMOLOTION

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

G

H

I

J

K

1 2 3 4 5 6 7 8 9 10

DATE:

DRAWN:

REVIEWED:

SHEET TITLE:

SHEET NUMBER:

PROJECT NO.:

PROJECT:

ISSUE:

# DATE: DESCRIPTION:

DESIGNED:

/1

/2

:2 :2

P

M MD1.3

CONTROLS

DEMOLITION PLAN

EPH

JMG

4-20-015

HVAC CONTROLS

UPGRADE

ILLINOIS DEPT. OF NATURAL

RESOURCES

LINCOLN'S NEW SALEM

HISTORIC SITE VISITORS

CENTER - 15588 HISTORY LN,

PETERSBERG, IL 62675

9/15/2020

9/15/2020

BID SET

EPH, JMG

KEYNOTES

1 VALVES TO REMAIN. DEMOLISH VALVE ACTUATORS AND ASSOCIATED PNEUMATIC

PIPING AND/OR WIRING BACK TO SOURCE CONTROL PANEL. TYPICAL.

2 DEMOLISH AVERAGING TEMPERATURE SENSOR, ELEMENT AND CONTROL WIRING

TO SOURCE CONTROL PANEL. TYPICAL.

3 DAMPERS TO REMAIN. DEMOLISH DAMPER ACTUATORS AND ASSOCIATED

PNEUMATIC PIPING BACK TO SOURCE CONTROL PANEL. TYPICAL.

4 DEMOLISH LOCAL CONTROL PANEL AND LOCAL CONTROL MODULES AND ALL

ASSOCIATED PNEUMATIC PIPING AND CONTROL WIRING.

5 ALL MOTOR STARTERS TO REMAIN.

SCALE: NOT TO SCALE

AHU-3 CONTROLS DEMOLITION

A. CONTRACTOR IS TO DEMOLISH EXISTING NON-OPERATIONAL HUMIDIFIER AND ALL

ASSOCIATED PNEUMATIC CONTROLS. NEW HUMIDIFIER IS TO BE INSTALLED IN SAME

LOCATION.

GENERAL NOTES

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

G

H

I

J

K

1 2 3 4 5 6 7 8 9 10

DATE:

DRAWN:

REVIEWED:

SHEET TITLE:

SHEET NUMBER:

PROJECT NO.:

PROJECT:

ISSUE:

# DATE: DESCRIPTION:

DESIGNED:

/1

/2

:2 :2

P

M MD1.4

CONTROLS

DEMOLITION PLAN

EPH

JMG

4-20-015

HVAC CONTROLS

UPGRADE

ILLINOIS DEPT. OF NATURAL

RESOURCES

LINCOLN'S NEW SALEM

HISTORIC SITE VISITORS

CENTER - 15588 HISTORY LN,

PETERSBERG, IL 62675

9/15/2020

9/15/2020

BID SET

EPH, JMG

KEYNOTES

1 DEMOLISH PNEUMATIC PIPING, DAMPER ACTUATORS, AND CONTROL WIRING FOR

STAND ALONE EXHAUST FAN. TYPICAL.

2 VALVES TO REMAIN. DEMOLISH VALVE ACTUATORS AND ASSOCIATED PNEUMATIC

PIPING AND/OR WIRING BACK TO SOURCE CONTROL PANEL. TYPICAL.

3 DEMOLISH TEMPERATURE SENSOR, ELEMENT AND CONTROL WIRING TO SOURCE

CONTROL PANEL. TYPICAL.

4 DAMPERS TO REMAIN. DEMOLISH DAMPER ACTUATORS AND ASSOCIATED

PNEUMATIC PIPING BACK TO SOURCE CONTROL PANEL. TYPICAL.

5 ALL MOTOR STARTERS ARE TO REMAIN.

6 DEMOLISH LOCAL CONTROL PANEL AND LOCAL CONTROL MODULES AND ALL

ASSOCIATED PNEUMATIC PIPING AND CONTROL WIRING.

SCALE: NOT TO SCALE

AHU-4 CONTROLS DEMOLITION

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

G

H

I

J

K

1 2 3 4 5 6 7 8 9 10

DATE:

DRAWN:

REVIEWED:

SHEET TITLE:

SHEET NUMBER:

PROJECT NO.:

PROJECT:

ISSUE:

# DATE: DESCRIPTION:

DESIGNED:

/1

/2

:2 :2

P

M MD1.5

CONTROLS

DEMOLITION PLAN

EPH

JMG

4-20-015

HVAC CONTROLS

UPGRADE

ILLINOIS DEPT. OF NATURAL

RESOURCES

LINCOLN'S NEW SALEM

HISTORIC SITE VISITORS

CENTER - 15588 HISTORY LN,

PETERSBERG, IL 62675

9/15/2020

9/15/2020

BID SET

EPH, JMG

SCALE: NOT TO SCALE

BOILER, CHILLER, FANS CONTROLS

DEMOLITION

KEYNOTES

1 DEMOLISH PNEUMATIC PIPING , DAMPER ACTUATORS, AND CONTROL WIRING FOR

STAND ALONE EXHAUST FAN. TYPICAL.

2 VALVES TO REMAIN. DEMOLISH VALVE ACTUATORS AND ASSOCIATED PNEUMATIC

PIPING AND/OR WIRING BACK TO SOURCE CONTROL PANEL. TYPICAL.

3 DAMPERS TO REMAIN. DEMOLISH DAMPER ACTUATORS AND ASSOCIATED

PNEUMATIC PIPING BACK TO SOURCE CONTROL PANEL. TYPICAL.

4 ALL MOTOR STARTERS ARE TO REMAIN.

5 DEMOLISH LOCAL CONTROL PANEL AND LOCAL CONTROL MODULES AND ALL

ASSOCIATED PNEUMATIC PIPING AND CONTROL WIRING.

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

G

H

I

J

K

1 2 3 4 5 6 7 8 9 10

DATE:

DRAWN:

REVIEWED:

SHEET TITLE:

SHEET NUMBER:

PROJECT NO.:

PROJECT:

ISSUE:

# DATE: DESCRIPTION:

DESIGNED:

/1

/2

:2 :2

P

M MD1.6

CONTROLS

DEMOLITION PLAN

EPH

JMG

4-20-015

HVAC CONTROLS

UPGRADE

ILLINOIS DEPT. OF NATURAL

RESOURCES

LINCOLN'S NEW SALEM

HISTORIC SITE VISITORS

CENTER - 15588 HISTORY LN,

PETERSBERG, IL 62675

9/15/2020

9/15/2020

BID SET

EPH, JMG

SCALE: NOT TO SCALE

UNIT HEATERS, COMPRESSOR, FAN

COIL UNIT CONTROLS DEMOLITION

KEYNOTES

1 VALVES TO REMAIN. DEMOLISH VALVE ACTUATORS AND ASSOCIATED PNEUMATIC

PIPING AND/OR WIRING BACK TO SOURCE CONTROL PANEL. TYPICAL.

2 EXHAUST FAN 10 WAS NEVER INSTALLED. REMOVE ANY ASSOCIATED PNEUAMTIC

CONTROLS IF INSTALLED TO FACILITATE PLANNED FUTURE INSTALLATION.

3 DEMOLISH CENTRAL CONTROL PANEL AND ALL MODULES ASSOCIATED WITH

PNEUMATIC CONTROLS.

4 ALL MOTOR STARTERS ARE TO REMAIN.

AHU-3FCU-6

FCU-5

UH-3

UH-5

AHU-2

UH-4

H-3

AHU-4

FCU-6

EF-11

FCU-5

UH-3

UH-4

UH-5

UH-2

AHU-1A

AHU-1B

AHU-1C

UH-2

AHU-4

AHU-1AHU-3AHU-2

EF-12

EF-1

EF-2

P-2

P-1A

P-1

B-1

UH-1

H-3

COMBUSTION AIR

DAMPERS

WH

EXISTING CONTROL PANEL

LOCATIONS

PNEUMATIC

COMPRESSOR

UH-1

EF-4 & 4A

EXISTING CONTROL PANEL

SEWER EJECTOR

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

G

H

I

J

K

1 2 3 4 5 6 7 8 9 10

DATE:

DRAWN:

REVIEWED:

SHEET TITLE:

SHEET NUMBER:

PROJECT NO.:

PROJECT:

ISSUE:

# DATE: DESCRIPTION:

DESIGNED:

/1

/2

:2 :2

P

M MD3.1

BUILDING LAYOUT

DEMOLITION

EPH

JMG

4-20-015

HVAC CONTROLS

UPGRADE

ILLINOIS DEPT. OF NATURAL

RESOURCES

LINCOLN'S NEW SALEM

HISTORIC SITE VISITORS

CENTER - 15588 HISTORY LN,

PETERSBERG, IL 62675

9/15/2020

9/15/2020

BID SET

EPH, JMG

SCALE: NOT TO SCALE

FIRST FLOOR LAYOUT DEMOLITION

SCALE: NOT TO SCALE

BASEMENT LAYOUT DEMOLITION

B. ALL THERMOSTATS ARE SHOWN FOR LOCATIONAL REFERENCE. ALL EXISTING

PNEUMATIC THERMOSTATS ARE TO BE DEMOLISHED. NEW THERMOSTATS ARE TO BE

LOCATED IN SAME LOCATION. SEE SHEET M3.1.

A. EXISTING BUILDING DRAWINGS ARE AVAILABLE UPON REQUEST FROM OWNER.

GENERAL NOTES

KEYNOTES

1 DEMOLISH EXISTING COMPRESSOR AND RETURN TO OWNER. DEMOLISH ALL

PIPING AND WIRING ASSOCIATED WITH PNEUMATIC CONTROLS.

2 MECHANICAL CONTRACTOR IS TO DEMOLISH EXISTING HUMIDIFIER, DISPERSION

TUBE, AND CONTROL WIRING. NEW HUMIDIFIER IS TO BE INSTALLED IN SAME

LOCATION. REFER TO SHEET M3.1.

3 DEMOLISH EXISITNG CONTROL PANELS ASSOCIATED WITH PNEUMATIC CONTROL

SYSTEM. CONTRACTOR IS TO VERIFY IN FIELD ALL LOCATIONS OF PANELS

NEEDING TO BE DEMOLISHED.

NC

NORA

EA

EF-1

EF

MOTOR

OA

NC

NO

C

C

TS-2

CHWR CHWS

SA

RH

C

HWS

HWR

DP-1

HC-1A, 1B, 1C

T-2

D4

D2

D3

TS-3

V-14A, B, C

V-1A

SF

AIR HANDLING UNIT 1

AO - RETURN AIR DAMPER

BI - RETURN AIR DAMPER STATUS

AO - EXHAUST AIR DAMPER

BI - EXHAUST AIR DAMPER STATUS

BI - FAN STATUS

BO - FAN START/STOP

M

CT

NC

D1

AO - OUTSIDE AIR DAMPER

BI - OUTSIDE AIR DAMPER STATUS

AI - MIXED AIR TEMP AO - COOLING VALVE

M

AO - HEATING VALVE

M

BI - F&BP DAMPER STATUS

AO - FACE & BYPASS DAMPER

AI - FAN DIFFERENTIAL PRESSURE

T-1

AI - ZONE SETPOINT ADJUST

AI - ZONE TEMP

BI - ZONE OVERRIDE

BI - FREEZE STAT

AI - DISCHARGE AIR TEMP

M CT

BI - FAN STATUS

BO - FAN START/STOP

TS-4

AI - DISCHARGE AIR TEMP

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

G

H

I

J

K

1 2 3 4 5 6 7 8 9 10

DATE:

DRAWN:

REVIEWED:

SHEET TITLE:

SHEET NUMBER:

PROJECT NO.:

PROJECT:

ISSUE:

# DATE: DESCRIPTION:

DESIGNED:

/1

/2

:2 :2

P

M M1.1

CONTROLS DIAGRAM

EPH

JMG

4-20-015

HVAC CONTROLS

UPGRADE

ILLINOIS DEPT. OF NATURAL

RESOURCES

LINCOLN'S NEW SALEM

HISTORIC SITE VISITORS

CENTER - 15588 HISTORY LN,

PETERSBERG, IL 62675

9/15/2020

9/15/2020

BID SET

EPH, JMG

KEYNOTES

1 THERMOSTATS LOCATIONS ARE CALLED OUT ON SHEET M3.1. THERMOSTATS ARE

TO BE INSTALLED AT REMOVED PNEUMATIC THERMOSTAT HEIGHT AND LOCATION.

SCALE: NOT TO SCALE

AHU-1, EF-1 CONTROL DIAGRAM

1. AIR HANDLING UNIT AHU-1

a. GENERAL

1. AHU-1 IS A SINGLE ZONE DRAW THRU AIR HANDLING UNIT WITH FACE AND BYPASS

DAMPERS, CHILLED WATER COOLING COIL AND OUTDOOR, RETURN AND RELIEF AIR (EF-1)

MIXING DAMPERS.

2. DDC CONTROLLER SHALL PROVIDE AHU-1 CONTROL FUNCTIONS, CONTROLLER SHALL

ACCEPT ANALOG INPUTS FROM ELECTRONIC SENSORS OR BINARY INPUTS FROM

CONTACT CLOSURES. CONTROLLER PROVIDES ANALOG OUTPUTS TO THE VALVE AND

DAMPER ACTUATORS. BINARY OUTPUTS ARE PROVIDED FOR STARTING AND STOPPING

OF FANS AND RELATED SYSTEM DEVICES.

b. STARTING/STOPPING SEQUENCE

1. AHU-1 SUPPLY FAN IS STARTED AND STOPPED FROM THE DDC SYSTEM AND SHALL RUN

CONTINUOUSLY DURING THE DAY CYCLE TO MAINTAIN A SPACE SET POINT OF 75 DEG. F.

(ADJ.) DURING THE OCCUPIED SUMMER OPERATION AND 70 DEG. F. (ADJ.) DURING THE

OCCUPIED WINTER OPERATION. IT SHALL CYCLE TO MAINTAIN A REDUCED SETTING ON

NIGHT CYCLE TO MAINTAIN A SPACE SET POINT OF 80 DEG. F. (ADJ.) DURING THE

UNOCCUPIED SUMMER OPERATION AND 65 DEG. F. (ADJ.) DURING THE UNOCCUPPIED

WINTER OPERATION. THIS IS BASED ON USER PREDEFINED SCHEDULE. T-1 IS USED FOR

OPTIMAL START/STOP AND NIGHT CYCLE.

2. EF-1 IS STARTED AND STOPPED FROM THE DDC SYSTEM AND SHALL BE ENABLED TO RUN

WHENEVER AHU-1 RUNS ON DAY CYCLE AND REMAIN OFF DURING NIGHT CYCLE. (SEE

MIXED AIR/ECONOMIZER SEQUENCE BELOW).

3. DAY-AUTO-NIGHT SWITCH AT OPERATOR WORKSTATION SHALL OVERRIDE THE DDC

SYSTEM TIME CLOCK AND RETURN SYSTEM TO DAY OR NIGHT CYCLE IF DESIRED.

4. AUTO-OFF SWITCH AT OPERATOR WORKSTATION SHALL DETERMINE AHU-1 SYSTEM

OPERATION.

c. WARM-UP SEQUENCE

1. WHEN SYSTEM IS CHANGED FROM NIGHT TO DAY CYCLE, OA MD D-1 SHALL DELAY

OPENING UNTIL AREA REACHES DAY TEMPERATURE SETTING AT WHICH TIME THE OA MD

D-1 SHALL OPEN TO A 30% (ADJ.) MINIMUM POSITION. THE REL A MD D-3 SHALL FOLLOW

THE OA MD EXCEPT THEY SHALL DELAY OPENING BY 20% (ADJ.). THE RA MD D-2 SHALL

CLOSE IN OPPOSITE PROPORTION TO THE MA MD.

d. DUCT HEATING COIL/COOLING SEQUENCE

1. BAS SHALL MODULATE THE RESPECTIVE SPACE COIL VALVES V-14A, B, C TO MAINTAIN

SPACE TEMPERATURE SETPOINT BASED ON SIGNAL RECIEVED FROM TS-2, TS-4. THE OA

MD D-1, RA MD D-2, REL A MD D-3, FACE & BYPASS DAMPERS AND COOLING COIL 3-WAY

VALVE V-1A SHALL BE SEQUENCED BY THE ROOM THERMOSTAT CALLING FOR THE MOST

COOLING. (SEE MIXED AIR/ECONOMIZER SEQUENCE).

e. MIXED AIR/ECONOMIZER SEQUENCE

1. THE CONTROLLER SHALL MEASURE THE MIXED AIR TEMPERATURE AND MODULATE THE

ECONOMIZER DAMPERS IN SEQUENCE TO MAINTAIN A SETPOINT 2 DEG. F. (ADJ.) LESS

THAN THE SUPPLY AIR TEMPERATURE SETPOINT. THE OUTSIDE AIR DAMPERS SHALL

MAINTAIN A MINIMUM ADJUSTABLE POSITION OF 20% (ADJ.) OPEN WHENEVER OCCUPIED.

THE ECONOMIZER SHALL BE ENABLED WHENEVER:

- OUTSIDE AIR TEMPERATURE IS LESS THAN 65 DEG. F. (ADJ.).

- AND THE OUTSIDE AIR TEMPERATURE IS LESS THAN THE RETURN AIR

TEMPERATURE.

- AND THE SUPPLY FAN STATUS IS ON.

THE ECONOMIZER SHALL CLOSE WHENEVER:

- MIXED AIR TEMPERATURE DROPS FROM 40 DEG. F. TO 35 DEG. F. (ADJ.).

- OR THE FREEZESTAT (IF PRESENT) IS ON.

- OR ON LOSS OF SUPPLY FAN STATUS.

THE OUTSIDE AND EXHAUST AIR DAMPERS SHALL CLOSE AND THE RETURN AIR DAMPER

SHALL OPEN WHEN THE UNIT IS OFF. IF OPTIMAL START UP IS AVAILABLE THE MIXED AIR

DAMPER SHALL OPERATE AS DESCRIBED IN THE OCCUPIED MODE EXCEPT THAT THE

OUTSIDE AIR DAMPER SHALL MODULATE TO FULLY CLOSED.

2. MIXED AIR LOW LIMIT SENSOR TS-3 SHALL PREVENT TEMPERATURE FROM FALLING

BELOW 50 DEG. F. (ADJ.).

3. EXHAUST FAN EF-1 SHALL SEQUENCE FROM OFF TO LOW TO HIGH SPEED AS REL A MD

D-3 MODULATES OPEN.

f. INTERLOCK/SAFETY SEQUENCE

1. EXISTING SMOKE DETECTORS SHALL STOP SUPPLY FAN WHEN SMOKE IS DETECTED.

2. FREEZESTAT T-2, MANUAL RESET, SHALL STOP SUPPLY FAN WHEN TEMPERATURE FALLS

BELOW ITS SETTING.

3. OA MD D-1 AND REL A MD D-3 SHALL CLOSE AND RA MD D-2 SHALL OPEN DURING NIGHT

CYCLE OR ANYTIME FAN STOPS.

4. CHILLED WATER COIL 3-WAY VALVE V-2A SHALL GO TO FULL BYPASS WHEN SUPPLY FAN

STOPS.

5. DIFFERENTIAL PRESSURE SWITCH DP-1 SHALL PROVIDE FAN INTERLOCK AND “FAN ON”

INDICATION AT OPERATOR WORKSTATION.

6. AVERAGE SPACE TEMPERATURE INDICATION SHALL ALSO BE PROVIDED AT OPERATOR

WORKSTATION.

7. UNIT SHALL SHUT DOWN UPON RECEIVING SIGNAL FROM FIRE ALARM CONTROL PANEL.

FOR GUIDANCE ONLY. POINTS INDICATED ARE MINIMUM NUMBER OF POINTS. TEMPERATURE CONTROL CONTRACTOR IS RESPONSIBLE FOR PROVIDING ADDITIONAL POINTS AS NEEDED TO COMPLY WITH THE SEQUENCE OF OPERATION AND THE

DESIGN INTENT.

Fan in Hand x x

Fan Failure x x

Exhaust Air Damper in Hand x x

Exhaust Air Damper Failure x x

Exhaust Schedule x

Exhaust Air Damper x x x

Exhaust Fan Start/Stop x x x

Exhaust Fan Status x x x

Exhaust Air Damper Status x x x

Exhaust Fan Runtime Exceeded x x

Exhaust Fan in Hand x x

Exhaust Fan Failure x x

Low Discharge Air Temp x x

High Dischargbe Air Temp x x

Filter Change Required x x

Low Zone Temp x x

High Zone Temp x x

Heating Setpoint x x

Cooling Setpoint x x

Schedule x

Emergency Shutdown x x x x

Return Air Damper x x x

Outside Air Damper x x x

Supply Fan Start/Stop x x x

Return Air Damper Status x x x

Face and Bypass Damper Status x x x

Supply Fan Status x x x

Smoke Detector x x x x

Freezestat x x x x

Zone Override x x x

Outside Air Damper Status x x x

Heating Valve x x x

Cooling Valve x x x

Face and Bypass Dampers x x x

Mixed Air Temp x x x

Discharge Air Temp x x x

Fan Differential Pressure x x x

Zone Setpoint Adjust x x x

Zone Temp x x x

POINT NAME AI AO BI BO AV BV Loop Sched Trend Alarm Show on Graphic

HARDWARE POINTS SOFTWARE POINTS

NCNORA

EA

EF-2

EF

MOTOR

OA

NC

NO

C

C

CHWR CHWS

DP-1

D4

D1

D2

D3

TS-3

V-2A

SF

H

C

HWS

HWR

V-2

SA

T-1

EAEF-11

EF

MOTOR

D5

AIR HANDLING UNIT 2

BO - EXHAUST AIR DAMPER

BI - FAN STATUS

BO - FAN START/STOP

M

CT

BI - EXHAUST AIR DAMPER STATUS

BI - FAN STATUS

BO - FAN START/STOP

M

CT

AO - EXHAUST AIR DAMPER

BI - EXHAUST AIR DAMPER STATUS

AO - RETURN AIR DAMPER

BI - RETURN AIR DAMPER STATUS

AO - OUTSIDE AIR DAMPER

BI - OUTSIDE AIR DAMPER STATUS

AI - MIXED AIR TEMP

TS-2

AI - DISCHARGE AIR TEMP

AO - FACE & BYPASS DAMPER

BI - F&BP DAMPER STATUS

AI - ZONE SETPOINT ADJUST

AI - ZONE TEMP

BI - ZONE OVERRIDE

AO - HEATING VALVE

M

AO - COOLING VALVE

M

AI - FAN DIFFERENTIAL PRESSURE

T-2

BI - FREEZE STAT

M CT

BI - FAN STATUS

BO - FAN START/STOP

EF - 11

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

G

H

I

J

K

1 2 3 4 5 6 7 8 9 10

DATE:

DRAWN:

REVIEWED:

SHEET TITLE:

SHEET NUMBER:

PROJECT NO.:

PROJECT:

ISSUE:

# DATE: DESCRIPTION:

DESIGNED:

/1

/2

:2 :2

P

M M1.2

CONTROLS DIAGRAM

EPH

JMG

4-20-015

HVAC CONTROLS

UPGRADE

ILLINOIS DEPT. OF NATURAL

RESOURCES

LINCOLN'S NEW SALEM

HISTORIC SITE VISITORS

CENTER - 15588 HISTORY LN,

PETERSBERG, IL 62675

9/15/2020

9/15/2020

BID SET

EPH, JMG

KEYNOTES

1 THERMOSTAT LOCATION IS CALLED OUT ON SHEET M3.1. THERMOSTAT IS TO BE

INSTALLED AT REMOVED PNEUMATIC THERMOSTAT HEIGHT AND LOCATION.

SCALE: NOT TO SCALE

AHU-2, EF-2, EF-11 CONTROL DIAGRAM

1. AIR HANDLING UNIT AHU-2

a. GENERAL

1. AHU-2 IS A SINGLE ZONE DRAW THRU AIR HANDLING UNIT WITH A HOT WATER

HEATING COIL, FACE AND BYPASS DAMPERS, CHILLED WATER COOLING COIL,

AND OUTDOOR, RETURN, AND RELIEF AIR (EF-2) MIXING DAMPERS.

2. DDC CONTROLLER SHALL PROVIDE AHU-2 CONTROL FUNCTIONS. CONTROLLER

SHALL ACCEPT ANALOG INPUTS FROM ELECTRONIC SENSORS OR BINARY

INPUTS FROM CONTACT CLOSURES. CONTROLLER PROVIDES ANALOG

OUTPUTS TO THE VALVE AND DAMPER ACTUATORS. BINARY OUTPUTS ARE

PROVIDED FOR STARTING AND STOPPING OF FANS AND RELATED SYSTEM

DEVICES.

b. STARTING/STOPPING SEQUENCE

1. AHU-2 SUPPLY FAN IS STARTED AND STOPPED FROM THE DDC SYSTEM AND

SHALL RUN CONTINUOUSLY DURING DAY CYCLE TO MAINTAIN A SPACE SET

POINT OF 75 DEG. F. (ADJ.) DURING THE OCCUPIED SUMMER OPERATION AND

70 DEG. F. (ADJ.) IT SHALL CYCLE TO MAINTAIN A REDUCED SETTING ON NIGHT

CYCLE TO MAINTAIN A SPACE SET POINT OF 80 DEG. F. (ADJ.) DURING THE

UNOCCUPIED SUMMER OPERATION AND 65 DEG. F. (ADJ.) DURING THE

UNOCCUPPIED WINTER OPERATION. THIS IS BASED ON USER PREDEFINED

SCHEDULE.

2. EF-11 SHALL RUN WHEN AHU-2 RUNS ON DAY CYCLE AND REMAIN OFF DURING

NIGHT CYCLE. EF-11 DAMPER D-5 SHALL OPEN WHEN EF-11 RUNS AND CLOSE

WHEN EF-11 STOPS.

3. EF-2 IS STARTED AND STOPPED FROM THE DDC SYSTEM AND SHALL BE

ENABLED TO RUN WHENEVER AHU-2 RUNS OF DAY CYCLE AND REMAIN OFF

DURING NIGHT CYCLE. (SEE MIXED AIR/ECONOMIZER SEQUENCE BELOW).

4. DAY-AUTO-NIGHT SWITCH AT OPERATOR WORKSTATION SHALL OVERRIDE THE

DDC SYSTEM TIME CLOCK AND RETURN SYSTEM TO DAY OR NIGHT CYCLE IF

DESIRED.

5. AUTO-OFF SPEED SWITCH AT OPERATOR WORKSTATION SHALL DETERMINE

AHU-2/EF-2 SYSTEM OPERATION.

c. WARM-UP SEQUENCE

1. WHEN SYSTEM IS CHANGED FROM NIGHT TO DAY CYCLE, OA MD D-1 SHALL

DELAY OPENING UNTIL AREA REACHES DAY TEMPERATURE SETTING AT WHICH

TIME THE OA MD D-1 SHALL OPEN TO A 30% (ADJ.) MINIMUM POSITION. THE REL

A MD D-3 SHALL FOLLOW THE OA MD EXCEPT THEY SHALL DELAY OPENING BY

20% (ADJ.). THE RA MD D-2 SHALL CLOSE IN OPPOSITE PROPORTION TO THE OA

MD.

d. MIXED AIR/ECONOMIZER SEQUENCE

1. THE CONTROLLER SHALL MEASURE THE MIXED AIR TEMPERATURE AND

MODULATE THE ECONOMIZER DAMPERS IN SEQUENCE TO MAINTAIN A

SETPOINT 2 DEG. F. (ADJ.) LESS THAN THE SUPPLY AIR TEMPERATURE

SETPOINT. THE OUTSIDE AIR DAMPERS SHALL MAINTAIN A MINIMUM

ADJUSTABLE POSITION OF 20% (ADJ.) OPEN WHENEVER OCCUPIED.

THE ECONOMIZER SHALL BE ENABLED WHENEVER:

- OUTSIDE AIR TEMPERATURE IS LESS THAN 65 DEG. F. (ADJ.).

- AND THE OUTSIDE AIR TEMPERATURE IS LESS THAN THE RETURN AIR

TEMPERATURE.

- AND THE SUPPLY FAN STATUS IS ON.

THE ECONOMIZER SHALL CLOSE WHENEVER:

- MIXED AIR TEMPERATURE DROPS FROM 40 DEG. F. TO 35 DEG. F.

(ADJ.).

- OR THE FREEZESTAT (IF PRESENT) IS ON.

- OR ON LOSS OF SUPPLY FAN STATUS.

THE OUTSIDE AND EXHAUST AIR DAMPERS SHALL CLOSE AND THE RETURN AIR

DAMPER SHALL OPEN WHEN THE UNIT IS OFF. IF OPTIMAL START UP IS

AVAILABLE THE MIXED AIR DAMPER SHALL OPERATE AS DESCRIBED IN THE

OCCUPIED MODE EXCEPT THAT THE OUTSIDE AIR DAMPER SHALL MODULATE

TO FULLY CLOSED.

2. MIXED AIR LOW LIMIT SENSOR TS-3 SHALL PREVENT TEMPERATURE FROM

FALLING BELOW 50 DEG. F. (ADJ.).

3. EXHAUST FAN EF-2 SHALL SEQUENCE FROM OFF TO LOW TO HIGH SPEED AS

REL A MD D-3 MODULATES OPEN.

e. HEATING SEQUENCE

1. ON A CALL FOR HEATING, SPACE SENSOR T-1 SHALL MODULATE HEATING COIL

2-WAY VALVE V-2 OPEN TO COIL AND F&BP MD D-4 OPEN TO COIL FACE TO

MAINTAIN SPACE TEMPERATURE.

2. WHEN OA TEMPERATURE FALLS BELOW 40 DEG. F. (ADJ.) V-2 SHALL REMAIN

OPEN AND THE F&BP MD D-4 SHALL MODULATE OPEN OR CLOSED TO MAINTAIN

SPACE TEMPERATURE.

3. LOW LIMIT DISCHARGE SENSOR TS-2 SHALL PREVENT TEMPERATURE FROM

FALLING BELOW 50 DEG. F. (ADJ.).

f. COOLING SEQUENCE

1. WHEN CHILLED WATER COOLING IS AVAILABLE, A CALL FOR COOLING FROM

SPACE SENSOR T-1 SHALL MODULATE THE 3-WAY COOLING VALVE V-2A TO

MAINTAIN SPACE TEMPERATURE, F&BP MD D-4 SHALL REMAIN OPEN TO THE

COIL FACE.

2. HEATING VALVE V-2 SHALL REMAIN CLOSED.

g. INTERLOCK/SAFETY SEQUENCE

1. EXISTING SMOKE DETECTOR SHALL STOP SUPPLY FAN WHEN SMOKE IS

DETECTED.

2. FREEZESTAT T-2, MANUAL RESET, SHALL STOP SUPPLY FAN WHEN

TEMPERATURE FALLS BELOW ITS SETTING.

3. OA MD D-1AND REL A MD D-3 SHALL CLOSE AND RA MD D-2 SHALL OPEN

DURING NIGHT OR ANYTIME FAN STOPS.

4. CHILLED WATER COIL 3-WAY VALVE V-2A SHALL GO TO FULL BYPASS WHEN

SUPPLY FAN STOPS.

5. DIFFERENTIAL PRESSURE SWITCH DP-1 SHALL PROVIDE FAN INTERLOCK AND

“FAN ON” INDICATION AT OPERATOR WORKSTATION.

6. ROOM SENSOR T-1 SHALL ALSO PROVIDE TEMPERATURE INDICATION AT

OPERATOR WORKSTATION.

7. UNIT SHALL SHUT DOWN UPON RECEIVING SIGNAL FROM FIRE ALARM

CONTROL PANEL.

FOR GUIDANCE ONLY. POINTS INDICATED ARE MINIMUM NUMBER OF POINTS. TEMPERATURE CONTROL CONTRACTOR IS RESPONSIBLE FOR PROVIDING ADDITIONAL POINTS AS NEEDED TO COMPLY WITH THE SEQUENCE OF OPERATION AND THE

DESIGN INTENT.

Fan in Hand x x

Fan Failure x x

Exhaust Air Damper in Hand x x

Exhaust Air Damper Failure x x

Schedule x

Exhaust Air Damper x x x

Fan Start/Stop x x x

Fan Status x x x

Exhaust Air Damper Status x x x

POINT NAME AI AO BI BO AV BV Loop Sched Trend Alarm Show on Graphic

HARDWARE POINTS SOFTWARE POINTS

FOR GUIDANCE ONLY. POINTS INDICATED ARE MINIMUM NUMBER OF POINTS. TEMPERATURE CONTROL CONTRACTOR IS RESPONSIBLE FOR PROVIDING ADDITIONAL POINTS AS NEEDED TO COMPLY WITH THE SEQUENCE OF OPERATION AND THE

DESIGN INTENT.

Fan in Hand x x

Fan Failure x x

Exhaust Air Damper in Hand x x

Exhaust Air Damper Failure x x

Exhaust Schedule x

Exhaust Air Damper x x x

Exhaust Fan Start/Stop x x x

Exhaust Fan Status x x x

Exhaust Air Damper Status x x x

Exhaust Fan Runtime Exceeded x x

Exhaust Fan in Hand x x

Exhaust Fan Failure x x

Low Discharge Air Temp x x

High Dischargbe Air Temp x x

Filter Change Required x x

Low Zone Temp x x

High Zone Temp x x

Heating Setpoint x x

Cooling Setpoint x x

Schedule x

Emergency Shutdown x x x x

Return Air Damper x x x

Outside Air Damper x x x

Supply Fan Start/Stop x x x

Return Air Damper Status x x x

Face and Bypass Damper Status x x x

Supply Fan Status x x x

Smoke Detector x x x x

Freezestat x x x x

Zone Override x x x

Outside Air Damper Status x x x

Heating Valve x x x

Cooling Valve x x x

Face and Bypass Dampers x x x

Mixed Air Temp x x x

Discharge Air Temp x x x

Fan Differential Pressure x x x

Zone Setpoint Adjust x x x

Zone Temp x x x

OA

RA

NC

NO

C

C

TS-2

CHWR CHWS

D2

D1

V-3A

SF

H

C

HWS

HWR

V-3

SA

NC

H-1

SS H

AIR HANDLING UNIT 3

AO - OUTSIDE AIR DAMPER

BI - OUTSIDE AIR DAMPER STATUS

H

AI - MIXED AIR HUMIDITY

TS-3

AI - MIXED AIR TEMP

AO - COOLING VALVE

M AO - HEATING VALVE

M

T-2

BI - FREEZE STAT

AO - FACE & BYPASS DAMPER

BI - F&BP DAMPER STATUS

AI - SUPPLY AIR HUMIDITY

AI - SUPPLY AIR SWITCH

AI - DISCHARGE AIR TEMP

M CT

BI - FAN STATUS

BO - FAN START/STOP

DP-1

AI - FAN DIFFERENTIAL PRESSURE

T-1

AI - ZONE SETPOINT ADJUST

AI - ZONE TEMP

BI - ZONE OVERRIDE

AI - ZONE HUMIDITY

H3

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

G

H

I

J

K

1 2 3 4 5 6 7 8 9 10

DATE:

DRAWN:

REVIEWED:

SHEET TITLE:

SHEET NUMBER:

PROJECT NO.:

PROJECT:

ISSUE:

# DATE: DESCRIPTION:

DESIGNED:

/1

/2

:2 :2

P

M M1.3

CONTROLS DIAGRAM

EPH

JMG

4-20-015

HVAC CONTROLS

UPGRADE

ILLINOIS DEPT. OF NATURAL

RESOURCES

LINCOLN'S NEW SALEM

HISTORIC SITE VISITORS

CENTER - 15588 HISTORY LN,

PETERSBERG, IL 62675

9/15/2020

9/15/2020

BID SET

EPH, JMG

A. NEW HUMIDIFIER H-3 IS TO BE INSTALLED IN SAME LOCATION AS PREVIOUS

HUMIDIFIER.

GENERAL NOTES

KEYNOTES

1 THERMOSTAT AND HUMIDSTAT LOCATIONS ARE CALLED OUT ON SHEET M3.1.

THERMOSTAT AND HUMIDSTAT ARE TO BE INSTALLED AT REMOVED PNEUMATIC

THERMOSTAT AND HUMIDSTAT HEIGHT AND LOCATION.

SCALE: NOT TO SCALE

AHU-3 CONTROL DIAGRAM

1. AIR HANDLING UNIT AHU-3

a. GENERAL

1. AHU-3 IS A SINGLE ZONE DRAW THRU AIR HANDLING UNIT WITH A HOT WATER

HEATING COIL, FACE AND BYPASS DAMPERS, CHILLED WATER COOLING COIL,

ELECTRIC HUMIDIFIER AND OUTDOOR AIR DAMPER.

2. DDC CONTROLLER SHALL PROVIDE AHU-3 CONTROL FUNCTIONS. CONTROLLER

SHALL ACCEPT ANALOG INPUTS FROM ELECTRONIC SENSORS OR BINARY INPUTS

FROM CONTACT CLOSURES. CONTROLLER PROVIDES ANALOG OUTPUTS TO THE

VALVE AND DAMPER ACTUATORS. BINARY OUTPUTS ARE PROVIDED FOR STARTING

AND STOPPING OF FANS AND RELATED SYSTEM DEVICES.

b. STARTING/STOPPING SEQUENCE

1. AHU-3 SUPPLY FAN IS STARTED AND STOPPED FROM THE DDC SYSTEM AND SHALL

RUN CONTINUOUSLY DURING THE DAY CYCLE TO MAINTAIN A SPACE SET POINT OF

75 DEG. F. (ADJ.) DURING THE OCCUPIED SUMMER OPERATION AND 70 DEG. F. (ADJ.)

DURING THE OCCUPIED WINTER OPERATION. THIS IS BASED ON USER PREDEFINED

SCHEDULE.

2. DAY-AUTO-NIGHT SWITCH AT OPERATOR WORKSTATION SHALL OVERRIDE THE DDC

SYSTEM TIME CLOCK AND RETURN SYSTEM TO DAY OR NIGHT CYCLE IF DESIRED.

3. AUTO-OFF SPEED SWITCH AT OPERATOR WORKSTATION SHALL DETERMINE AHU-3

SYSTEM OPERATION.

4. ON NIGHT CYCLE ONLY CHANGE IS OA MD D-1 CLOSES. ROOM TEMPERATURE AND

HUMIDITY SETPOINTS SHALL REMAIN THE SAME DURING DAY AND NIGHT CYCLES.

c. HEATING SEQUENCE

1. ON A CALL FOR HEATING, SPACE SENSOR T-1 SHALL MODULATE 2-WAY HEATING COIL

VALVE V-3 OPEN AND F&BP MD D-2 OPEN TO FACE TO MAINTAIN SPACE

TEMPERATURE.

2. WHEN OA TEMPERATURE FALLS BELOW 40 DEG. F. (ADJ.) V-3 SHALL REMAIN 100%

OPEN AND THE F&BP MD D-2 SHALL MODULATE OPEN OR CLOSED TO MAINTAIN

SPACE TEMPERATURE.

3. LOW LIMIT DISCHARGE SENSOR TS-2 SHALL PREVENT TEMPERATURE FROM FALLING

BELOW 50 DEG. F. (ADJ.).

d. COOLING SEQUENCE

1. WHEN CHILLED WATER COOLING IS AVAILABLE, A CALL FOR COOLING FROM SPACE

SENSOR T-1 SHALL MODULATE THE 3-WAY COOLING VALVE V-3A TO MAINTAIN SPACE

TEMPERATURE. F&BP MD D-2 SHALL REMAIN OPEN TO THE COIL FACE.

2. HEATING VALVE V-3 SHALL REMAIN CLOSED.

e. HUMIDIFIER SEQUENCE

1. ELECTRIC HUMIDIFIER H-3 SHALL BE FURNISHED BY MECHANICAL CONTRACTOR.

SPACE HUMIDITY SENSOR H-1 IS USED FOR CONTROL. IT SHALL PROVIDE HUMIDITY

INDICATION TO THE DDC SYSTEM AND OPERATOR WORKSTATION. ROOM HUMIDITY IS

TO BE MAINTAINED AT 50% (ADJ.) WHENEVER OA TEMPERATURE IS BLOW 65 DEG. F.

(ADJ.) WHEN OA TEMPERATURE IS ABOVE 65 DEG. F. (ADJ.) AND CHILLED WATER IS

AVAILABLE, THE HUMIDIFIER SHALL NOT OPERATE UNTIL HUMIDITY DROPS TO 45%

(ADJ.), AT WHICH TIME THE HUMIDIFIER SHALL BE REACTIVATED. DUCT HUMIDITY

SENSOR SHALL BE USED TO CONTROL THE DUCT RELATIVE HUMIDITY NOT TO

EXCEED 75% (ADJ.).

f. INTERLOCK/SAFETY SEQUENCE

1. EXISTING SMOKE DETECTOR SHALL STOP SUPPLY FAN WHEN SMOKE IS DETECTED.

2. FREEZE STAT T-2, MANUAL RESET, SHALL STOP SUPPLY FAN WHEN TEMPERATURE

FALLS BELOW ITS SETTING.

3. OA MD D-1 SHALL CLOSE DURING NIGHT CYCLE OR ANYTIME FAN STOPS.

4. CHILLED WATER COIL 3-WAY V-3A SHALL GO TO FULL COIL BYPASS WHEN SUPPLY

FAN STOPS.

5. MIXED AIR SENSOR TS-3 SHALL PROVIDE TEMPERATURE INDICATION TO THE DDC

SYSTEM.

6. DIFFERENTIAL PRESSURE SWITCH DP-1 SHALL PROVIDE FAN INTERLOCKS AND “FAN

ON” INDICATION AT OPERATOR WORKSTATION.

7. HUMIDIFIER H-3 PARALLEL INTERLOCK SHALL PROVIDE “HUMIDIFIER H-3 ON”

INDICATION AT OPERATOR WORKSTATION.

8. ROOM SENSOR T-1 SHALL ALSO PROVIDE TEMPERATURE INDICATION AT OPERATOR

WORKSTATION.

9. UNIT SHALL SHUT DOWN UPON RECEIVING SIGNAL FROM FIRE ALARM CONTROL

PANEL.

FOR GUIDANCE ONLY. POINTS INDICATED ARE MINIMUM NUMBER OF POINTS. TEMPERATURE CONTROL CONTRACTOR IS RESPONSIBLE FOR PROVIDING ADDITIONAL POINTS AS NEEDED TO COMPLY WITH THE SEQUENCE OF OPERATION AND THE

DESIGN INTENT.

Duct Humidity Level x x x

Fan Runtime Exceeded x x

Fan in Hand x x

Fan Failure x x

Low Discharge Air Temp x x

High Dischargbe Air Temp x x

Filter Change Required x x

Low Zone Temp x x

High Zone Temp x x

Heating Setpoint x x

Cooling Setpoint x x

Schedule x

Emergency Shutdown x x x x

Return Air Damper x x x

Outside Air Damper x x x

Supply Fan Status x x x

Smoke Detector x x x x

Freezestat x x x x

Zone Override x x x

Heating Valve x x x

Cooling Valve x x x

Face and Bypass Dampers x x x

Mixed Air Humidity x x x

Zone Humidity x x x

Discharge Air Temp x x x

Fan Differential Pressure x x x

Zone Setpoint Adjust x x x

Zone Temp x x x

NORA

OA

NC

NO

C

C

TS-2

CHWR CHWS

SA

D4

D1

D2

TS-3

V-4A

SF

H

C

HWS HWR

V-4

EA

EF-4

EF

MOTOR

D5

EA

EF-4A

EF

MOTOR

D3

AIR HANDLING UNIT 4

AO - RETURN AIR DAMPER

BI - RETURN AIR DAMPER STATUS

AO - OUTSIDE AIR DAMPER

BI - OUTSIDE AIR DAMPER STATUS

AI - MIXED AIR TEMP

AO - FACE & BYPASS DAMPER

BI - F&BP DAMPER STATUS

AO - COOLING VALVE

M AO - HEATING VALVE

M

T-2

BI - FREEZE STAT

DP-1

AI - FAN DIFFERENTIAL PRESSURE

M CT

BI - FAN STATUS

BO - FAN START/STOP

AI - DISCHARGE AIR TEMP

T-1

AI - ZONE SETPOINT ADJUST

AI - ZONE TEMP

BI - ZONE OVERRIDE

BI - FAN STATUS

BO - FAN START/STOP

M

CT

BI - FAN STATUS

BO - FAN START/STOP

M

CT

AO - EXHAUST AIR DAMPER

BI - EXHAUST AIR DAMPER STATUS

AO - EXHAUST AIR DAMPER

BI - EXHAUST AIR DAMPER STATUS

EF - 4, 4A

CO2

AI - CO2 SENSOR2

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

G

H

I

J

K

1 2 3 4 5 6 7 8 9 10

DATE:

DRAWN:

REVIEWED:

SHEET TITLE:

SHEET NUMBER:

PROJECT NO.:

PROJECT:

ISSUE:

# DATE: DESCRIPTION:

DESIGNED:

/1

/2

:2 :2

P

M M1.4

CONTROLS DIAGRAM

EPH

JMG

4-20-015

HVAC CONTROLS

UPGRADE

ILLINOIS DEPT. OF NATURAL

RESOURCES

LINCOLN'S NEW SALEM

HISTORIC SITE VISITORS

CENTER - 15588 HISTORY LN,

PETERSBERG, IL 62675

9/15/2020

9/15/2020

BID SET

EPH, JMG

KEYNOTES

1 THERMOSTAT LOCATION IS CALLED OUT ON SHEET M3.1. THERMOSTAT IS TO BE

INSTALLED AT REMOVED PNEUMATIC THERMOSTAT HEIGHT AND LOCATION.

2 NEW CO2 SENSOR. FURNISHED, INSTALLED AND WIRED BY CONTROLS

CONTRACTOR.

SCALE: NOT TO SCALE

AHU-4, EF-4, EF-4A CONTROL DIAGRAM

1. AIR HANDLING UNIT AHU-4

a. GENERAL

1. AHU-4 IS A SINGLE ZONE DRAW THRU AIR HANDLING UNIT WITH A HOT WATER

HEATING COIL, FACE AND BYPASS DAMPERS, CHILLED WATER COOLING COIL, AND

OUTDOOR, RETURN AND RELIEF AIR DAMPERS. (EF-4A)

2. DDC CONTROLLER SHALL PROVIDE AHU-4 CONTROL FUNCTIONS. CONTROLLER

SHALL ACCEPT ANALOG INPUTS FROM ELECTRONIC SENSORS OR BINARY INPUTS

FROM CONTACT CLOSURES. CONTROLLER PROVIDES ANALOG OUTPUTS TO THE

VALVE AND DAMPER ACTUATORS. BINARY OUTPUTS ARE PROVIDED FOR

STARTING AND STOPPING OF FANS AND RELATED SYSTEM DEVICES.

b. STARTING/STOPPING SEQUENCE

1. AHU-4 SUPPLY FAN IS STARTED AND STOPPED FROM THE DDC SYSTEM AND SHALL

RUN CONTINUOUSLY DURING DAY CYCLE TO MAINTAIN A SPACE SET POINT OF 75

DEG. F. (ADJ.) DURING THE OCCUPIED SUMMER OPERATION AND 70 DEG. F. (ADJ.)

DURING THE OCCUPIED WINTER OPERATION. IT SHALL CYCLE TO MAINTAIN A

REDUCED SETTING ON NIGHT CYCLE TO MAINTAIN A SPACE SET POINT OF 80 DEG.

F. (ADJ.) DURING THE UNOCCUPIED SUMMER OPERATION AND 65 DEG. F. (ADJ.)

DURING THE UNOCCUPPIED WINTER OPERATION. THIS IS BASED ON USER

PREDEFINED SCHEDULE.

2. EF-4 SHALL RUN WHEN AHU-4 RUNS ON DAY CYCLE IF VENTILATION CONTACT

CLOSURE AT OPERATOR WORKSTATION IS SET BEYOND ZERO. EF-4 SHALL REMAIN

OFF DURING NIGHT CYCLE.

3. EF-4A IS STARTED AND STOPPED FROM THE DDC SYSTEM AND SHALL BE ENABLED

TO RUN WHENEVER AHU-4 RUNS OF DAY CYCLE AND REMAIN OFF DURING NIGHT

CYCLE. (SEE MIXED AIR/ECONOMIZER SEQUENCE BELOW).

4. DAY-AUTO-NIGHT SWITCH AT OPERATOR WORKSTATION SHALL OVERRIDE THE

DDC SYSTEM TIME CLOCK AND RETURN SYSTEM TO DAY OR NIGHT CYCLE IF

DESIRED.

5. DDC CONTROL PROGRAM AT OPERATOR WORKSTATION SHALL DETERMINE

AHU-4/EF-4A SYSTEM OPERATION.

c. WARM-UP SEQUENCE

1. WHEN SYSTEM IS CHANGED FROM NIGHT TO DAY CYCLE, OA MD D-1 SHALL DELAY

OPENING UNTIL AREA REACHED DAY TEMPERATURE SETTING AT WHICH TIME THE

OA MD D-1 SHALL OPEN TO A 30% (ADJ.) MINIMUM POSITION. THE REL A MD D-3

SHALL FOLLOW THE OA MD EXCEPT THEY SHALL DELAY OPENING BY 20% (ADJ.).

THE RA MD D-2 SHALL CLOSE IN OPPOSITE PROPORTION TO THE OA MD.

d. MIXED AIR/ECONOMIZER SEQUENCE

1. THE CONTROLLER SHALL MEASURE THE MIXED AIR TEMPERATURE AND

MODULATE THE ECONOMIZER DAMPERS IN SEQUENCE TO MAINTAIN A SETPOINT 2

DEG. F. (ADJ.) LESS THAN THE SUPPLY AIR TEMPERATURE SETPOINT. THE OUTSIDE

AIR DAMPERS SHALL MAINTAIN A MINIMUM ADJUSTABLE POSITION OF 20% (ADJ.)

OPEN WHENEVER OCCUPIED.

THE ECONOMIZER SHALL BE ENABLED WHENEVER:

- OUTSIDE AIR TEMPERATURE IS LESS THAN 65 DEG. F. (ADJ.).

- AND THE OUTSIDE AIR TEMPERATURE IS LESS THAN THE RETURN AIR

TEMPERATURE.

- AND THE SUPPLY FAN STATUS IS ON.

THE ECONOMIZER SHALL CLOSE WHENEVER:

- MIXED AIR TEMPERATURE DROPS FROM 40 DEG. F. TO 35 DEG. F. (ADJ.).

- OR THE FREEZESTAT (IF PRESENT) IS ON.

- OR ON LOSS OF SUPPLY FAN STATUS.

THE OUTSIDE AND EXHAUST AIR DAMPERS SHALL CLOSE AND THE RETURN AIR

DAMPER SHALL OPEN WHEN THE UNIT IS OFF. IF OPTIMAL START UP IS AVAILABLE

THE MIXED AIR DAMPER SHALL OPERATE AS DESCRIBED IN THE OCCUPIED MODE

EXCEPT THAT THE OUTSIDE AIR DAMPER SHALL MODULATE TO FULLY CLOSED.

2. MIXED AIR LOW LIMIT SENSOR TS-3 SHALL PREVENT TEMPERATURE FROM FALLING

BELOW 50 DEG. F. (ADJ.).

3. EXHAUST FAN EF-4A SHALL SEQUENCE FROM OF TO LOW TO HIGHT SPEED AS REL

A MD D-3 MODULATES OPEN.

e. MINIMUM OUTSIDE AIR VENTILATION - CARBON DIOXIDE (CO2) CONTROL

1. WHEN IN THE OCCUPIED MODE, THE CONTROLLER SHALL MEASURE THE RETURN

AIR CO2 LEVELS AND MODULATE THE OUTSIDE AIR DAMPERS OPEN FROM THE

MINIMUM OPEN POSITION TO DELIVER MINIMUM VENTILATION AIRFLOW AS

DETERMINED BY THE TEST AND BALANCE CONTRACTOR ON RISING CO2

CONCENTRATIONS, OVERRIDING NORMAL DAMPER OPERATION TO MAINTAIN A

CO2 SET POINT OF 750 PPM (ADJ.).

f. HEATING SEQUENCE

1. ON A CALL FOR HEATING, SPACE SENSOR T-1 SHALL MODULATE HEATING COIL 2-

WAY VALVE V-4 OPEN TO COIL AND F&BP MD D-4 OPEN TO COIL FACE TO MAINTAIN

SPACE TEMPERATURE.

2. WHEN OA TEMPERATURE FALLS BELOW 40 DEG. F. (ADJ.) V-2 SHALL REMAIN OPEN

AND THE F&BP MD D-4 SHALL MODULATE OPEN OR CLOSED TO MAINTAIN SPACE

TEMPERATURE.

3. LOW LIMIT DISCHARGE SENSOR TS-2 WILL PREVENT TEMPERATURE FROM

FALLING BELOW 50 DEG. F. (ADJ.).

g. COOLING SEQUENCE

1. WHEN CHILLED WATER COOLING IS AVAILABLE, A CALL FOR COOLING FROM

SPACE SENSOR T-1 SHALL MODULATE THE 3-WAY COOLING VALVE V-4A TO

MAINTAIN SPACE TEMPERATURE. F&BP MD D-4 SHALL REMAIN OPEN TO THE COIL

FACE.

2. HEATING VALVE V-4 SHALL REMAIN CLOSED.

h. INTERLOCK/SAFETY SEQUENCE

1. EXISTING SMOKE DETECTORS SHALL STOP SUPPLY FAN WHEN SMOKE IS

DETECTED.

2. FREEZESTAT T-2, MANUAL RESET, SHALL STOP SUPPLY FAN WHEN TEMPERATURE

FALLS BELOW ITS SETTING.

3. OA AND REL A MD SHALL CLOSE AND RA MD SHALL OPEN DURING NIGHT CYCLE

OR ANYTIME FAN STOPS.

4. CHILLED WATER COIL 3-WAY CALCE V-4A SHALL GO TO FULL COIL BYPASS WHEN

SUPPLY FAN STOPS.

5. DIFFERENTIAL PRESSURE SWITCH DP-1 SHALL PROVIDE FAN INTERLOCKS AND

“FAN ON" INDICATION AT OPERATOR WORKSTATION.

6. ROOM SENSOR T-1 SHALL ALSO PROVIDE TEMPERATURE INDICATION AT

OPERATOR WORKSTATION.

7. UNIT SHALL SHUT DOWN UPON RECEIVING SIGNAL FROM FIRE ALARM CONTROL

PANEL.

FOR GUIDANCE ONLY. POINTS INDICATED ARE MINIMUM NUMBER OF POINTS. TEMPERATURE CONTROL CONTRACTOR IS RESPONSIBLE FOR PROVIDING ADDITIONAL POINTS AS NEEDED TO COMPLY WITH THE SEQUENCE OF OPERATION AND THE

DESIGN INTENT.

Fan in Hand x x

Fan Failure x x

Exhaust Air Damper in Hand x x

Exhaust Air Damper Failure x x

Schedule x

Exhaust Air Damper x x x

Fan Start/Stop x x x

Fan Status x x x

Exhaust Air Damper Status x x x

POINT NAME AI AO BI BO AV BV Loop Sched Trend Alarm Show on Graphic

HARDWARE POINTS SOFTWARE POINTS

FOR GUIDANCE ONLY. POINTS INDICATED ARE MINIMUM NUMBER OF POINTS. TEMPERATURE CONTROL CONTRACTOR IS RESPONSIBLE FOR PROVIDING ADDITIONAL POINTS AS NEEDED TO COMPLY WITH THE SEQUENCE OF OPERATION AND THE

DESIGN INTENT.

Fan Runtime Exceeded x x

Fan in Hand x x

Fan Failure x x

Low Discharge Air Temp x x

High Dischargbe Air Temp x x

Filter Change Required x x

Low Zone Temp x x

High Zone Temp x x

Heating Setpoint x x

Cooling Setpoint x x

Schedule x

Emergency Shutdown x x x x

Return Air Damper x x x

Outside Air Damper x x x

Supply Fan Status x x x

Smoke Detector x x x x

Freezestat x x x x

Zone Override x x x

Heating Valve x x x

Cooling Valve x x x

Face and Bypass Dampers x x x

CO2 Level x x x

Discharge Air Temp x x x

Fan Differential Pressure x x x

Zone Setpoint Adjust x x x

Zone Temp x x x

P-2

CHWS

TS-3

TS-4

CHWR

FS-2

CHILLER

CHILLER

THIS CHILLER INTERFACE SCHEMATIC MAY

NOT REFLECT THE ACTUAL SENSORS AND

POINTS AS SUPPLIED BY THE CHILLER

MANUFACTURER. ALL INTERFACE POINTS

SHALL BE COORDINATED WITH THE CHILLER

SUPPLIER.

CHILLER

BV - CHILLER STATUS

AV - CHILLER KW

AV - OPERATING HOURS

AV - CHILLED WATER SUPPLY TEMP SETPOINT

AV - OIL DIFFERENTIAL PRESSURE

AV - OIL TEMP

AV - CONDENSER REFRIGERANT PRESSURE

AV - EVAPORATOR REFRIGERANT PRESSURE

AV - CHILLED WATER SUPPLY TEMP

T

BI - CHILLED WATER FLOW STATUS

AV - CHILLED WATER RETURN TEMP

T

M

CT

BI - CHILLED WATER PUMP 1 STATUS

BO - CHILLED WATER PUMP 1 START/STOP

CHILLER PUMP

V-13

IN

OUT

BOILER

TS-2

TS-1

P-1

P-1A

HWS

HWR

TS-5

D1

D2

COMBUSTION AIR

COMBUSTION AIR

FS-1

BOILER / WATER HEATER

COMBUSTION AIR DAMPERS

THIS BOILER INTERFACE SCHEMATIC MAY NOT

REFLECT THE ACTUAL SENSORS AND POINTS

AS SUPPLIED BY THE BOILER

MANUFACTURER. ALL INTERFACE POINTS

SHALL BE COORDINATED WITH THE BOILER

SUPPLIER.

T

AV - HOT WATER SUPPLY TEMP

BI - HOT WATER FLOW STATUS

T

AV - HOT WATER RETURN TEMP

AO - BYPASS VALVE

M

BOILER

AV - OPERATING TEMP

AV - OPERATING PRESSURE

BV - BOILER STATUS

AV - BURNER CYCLES

AV - OPERATING HOURS

AV - HOT WATER SUPPLY TEMP SETPOINT

AI - OUTSIDE AIR TEMP

M

CT

BI - HOT WATER PUMP 1 STATUS

BO - HOT WATER PUMP 1 START/STOP

BI - HOT WATER PUMP 2 STATUS

BO - HOT WATER PUMP 2 START/STOP

M

CT

HOT WATER LOOP PUMPS

AO - OUTSIDE AIR DAMPER

BI - OUTSIDE AIR DAMPER STATUS

AO - OUTSIDE AIR DAMPER

BI - OUTSIDE AIR DAMPER STATUS

WATER HEATER

FS-2

BI - BOILER HOT WATER FLOW

EA

EF-12

EF

MOTOR

D3

EF-12

BI - FAN STATUS

BO - FAN START/STOP

M

CT

BO - EXHAUST AIR DAMPER

BI - EXHAUST AIR DAMPER STATUS

T-1

AI - ZONE SETPOINT ADJUST

AI - ZONE TEMP

BI - ZONE OVERRIDE

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

G

H

I

J

K

1 2 3 4 5 6 7 8 9 10

DATE:

DRAWN:

REVIEWED:

SHEET TITLE:

SHEET NUMBER:

PROJECT NO.:

PROJECT:

ISSUE:

# DATE: DESCRIPTION:

DESIGNED:

/1

/2

:2 :2

P

M M1.5

CONTROLS DIAGRAM

EPH

JMG

4-20-015

HVAC CONTROLS

UPGRADE

ILLINOIS DEPT. OF NATURAL

RESOURCES

LINCOLN'S NEW SALEM

HISTORIC SITE VISITORS

CENTER - 15588 HISTORY LN,

PETERSBERG, IL 62675

9/15/2020

9/15/2020

BID SET

EPH, JMG

SCALE: NOT TO SCALE

CHILLER CONTROL DIAGRAM

a. GENERAL

1. DDC CONTOLLER SHALL PROVIDE HOT/CHILLED WATER SYSTEM CONTROL

FUNCTIONS. CONTROLLER SHALL ACCEPT ANALOG INPUTS FROM

ELECTRONIC SENSORS OR BINARY INPUTS FROM CONTACT CLOSURES.

CONTROLLER PROVIDES ANALOG OUTPUTS TO VALVE OR DAMPER

ACTUATORS. BINARY OUTPUTS ARE PROVIDED FROM STARTING AND

STOPPING OF BOILER, CHILLER, PUMPS AND RELATED SYSTEM DEVICES.

FOR GUIDANCE ONLY. POINTS INDICATED ARE MINIMUM NUMBER OF POINTS. TEMPERATURE CONTROL CONTRACTOR IS RESPONSIBLE FOR PROVIDING ADDITIONAL POINTS AS NEEDED TO COMPLY WITH THE SEQUENCE OF OPERATION AND THE

DESIGN INTENT.

Fan in Hand x x

Fan Failure x x

Exhaust Air Damper in Hand x x

Exhaust Air Damper Failure x x

Schedule x

Exhaust Air Damper x x x

Fan Start/Stop x x x

Fan Status x x x

Exhaust Air Damper Status x x x

POINT NAME AI AO BI BO AV BV Loop Sched Trend Alarm Show on Graphic

HARDWARE POINTS SOFTWARE POINTS

FOR GUIDANCE ONLY. POINTS INDICATED ARE MINIMUM NUMBER OF POINTS. TEMPERATURE CONTROL CONTRACTOR IS RESPONSIBLE FOR PROVIDING ADDITIONAL POINTS AS NEEDED TO COMPLY WITH THE SEQUENCE OF OPERATION AND THE

DESIGN INTENT.

Hot Water Flow Status x x x

Boiler Status x x x

Hot Water Return Temp x x x

Hot Water Supply Temp x x x

Hot Water Supply Temp Setpoint x x x

Operating Temp x x x

Operating Pressure x x x

Operating Hours x x

Burner Cycles x x

Water Heater OA Damper Status x

Boiler OA Damper Status x

Water Heater OA Damper x

Boiler OA Damper x

Outside Air Temp x

POINT NAME AI AO BI BO AV BV Loop Sched Trend Alarm Show on Graphic

HARDWARE POINTS SOFTWARE POINTS

FOR GUIDANCE ONLY. POINTS INDICATED ARE MINIMUM NUMBER OF POINTS. TEMPERATURE CONTROL CONTRACTOR IS RESPONSIBLE FOR PROVIDING ADDITIONAL POINTS AS NEEDED TO COMPLY WITH THE SEQUENCE OF OPERATION AND THE

DESIGN INTENT.

Low Hot Water Supply Temp x x

High Hot Water Supply Temp x x

Hot Water Pump 1A Runtime Exceeded x x

Hot Water Pump 1 Runtime Exceeded x x

Hot Water Pump 1A Running in Hand x x

Hot Water Pump 1 Running in Hand x x

Hot Water Pump 1A Failure x x

Hot Water Pump 1 Failure x x

Boiler Hot Water Flow x x x

Hot Water Flow Status x x x

Outside Air Temp x x

Hot Water Pump 1A Start/Stop x x x

Hot Water Pump 1 Start/Stop x x x

Hot Water Pump 1A Status x x x

Hot Water Pump 1 Status x x x

Hot Water Supply Temp x x x

Hot Water Return Temp x x x

POINT NAME AI AO BI BO AV BV Loop Sched Trend Alarm Show on Graphic

HARDWARE POINTS SOFTWARE POINTS

FOR GUIDANCE ONLY. POINTS INDICATED ARE MINIMUM NUMBER OF POINTS. TEMPERATURE CONTROL CONTRACTOR IS RESPONSIBLE FOR PROVIDING ADDITIONAL POINTS AS NEEDED TO COMPLY WITH THE SEQUENCE OF OPERATION AND THE

DESIGN INTENT.

Condenser Water Flow Status x x x

Chilled Water Flow Status x x x

Chiller Status x x x

Oil Temp x x x

Oil Differential Pressure x x x

Condenser Refrigerant Pressure x x x

Evaporator Refrigerant Pressure x x x

Condenser Water Return Temp x x x

Condenser Water Supply Temp x x x

Chilled Water Return Temp x x x

Chilled Water Supply Temp x x x

Operating Hours x x x

Chilled Water Supply Temp Setpoint x x x

Chiller kW x x x

POINT NAME AI AO BI BO AV BV Loop Sched Trend Alarm Show on Graphic

HARDWARE POINTS SOFTWARE POINTS

FOR GUIDANCE ONLY. POINTS INDICATED ARE MINIMUM NUMBER OF POINTS. TEMPERATURE CONTROL CONTRACTOR IS RESPONSIBLE FOR PROVIDING ADDITIONAL POINTS AS NEEDED TO COMPLY WITH THE SEQUENCE OF OPERATION AND THE

DESIGN INTENT.

Low Chilled Water Supply Temp x x

High Chilled Water Supply Temp x x

Chilled Water Pump 2 Runtime Exceeded x x

Chilled Water Pump 2 Running in Hand x x

Chilled Water Pump 2 Failure x x

Outside Air Temp x x

Chilled Water Pump 2 Start/Stop x x x

Chilled Water Pump 2 Status x x x

Chilled Water Return Temp x x x

Chilled Water Supply Temp x x x

POINT NAME AI AO BI BO AV BV Loop Sched Trend Alarm Show on Graphic

HARDWARE POINTS SOFTWARE POINTS

GENERAL NOTES

SCALE: NOT TO SCALE

BOILER, WATER HEATER, CA DAMPERS

CONTROL DIAGRAM

SCALE: NOT TO SCALE

EF-12 CONTROL DIAGRAM

a. EXHAUST FAN EF-12

1. 2 STAGE ROOM MECHANICAL ROOM THERMOSTAT T-1 SHALL SEQUENCE

EF-12 FROM OFF TO LOW TO HIGH AS SPACE TEMPERATURE INCREASES.

EF-12 MD D-3 AND BOTH COMBUSTION AIR MD D-1, 2 SHALL OPEN WHEN

FAN RUNS AND CLOSE WHEN FAN STOPS.

SEQUENCE OF OPERATION EF-12

a. CHILLER CH-1/ CHILLED WATER SYSTEM CONTROL

1. CHILLER IS CONTROLLED WITH ITS ON BOARD ORIGINAL EQUIPMENT

MANUFACTURER CONTROLLER. NEW BUILDING AUTOMATION SYSTEM

SHALL PROVIDE THE NECESSARY INTERFACE AS FOLLOWS TO ENABLE

AND DISABLE THE OPERATION OF THE EQUIPMENT AND PROVIDE ALARMS

AS SPECIFIED AT THE OPERATOR WORK STATION.

2. BAS SHALL DISABLE THE OPERATION OF THE CHILLER WHEN OA TEMP.

FALLS BELOW 55 DEG. F. (ADJ.).

3. CHILLER/CHW PUMP P-2 INTERLOCK WIRING SHALL BE PROVIDED BY

CONTRACTOR.

4. FS-2 FLOW SWITCH SHALL PREVENT CHILLER FROM OPERATING UNLESS

P-2 IS RUNNING.

5. CHILLER CH-1 IS ENABLED ANYTIME CHW PUMP P-2 RUNS.

6. CHW PUMP P-2 SHALL START ANYTIME AHU-1, 2, 3, 4 CHWS VALVES ARE

OPEN OVER 20% (ADJ.).

7. P-2 WILL NOT BE ALLOWED TO RUN IF OA TEMPERATURE IS LESS THAN 55

DEG. F. (ADJ.).

8. CHWS AND CHWR SENSORS TS-3, 4 SHALL PROVIDE TEMPERATURE

INDICATION TO DDC SYSTEM.

9. CHILLER INTERLOCK SHALL ALSO PROVIDE “CHILLER ON” INDICATION AT

OPERATOR WORKSTATION.

SEQUENCE OF OPERATION CHILLER

a. COMBUSTIONS AIR MOTORIZED DAMPERS

1. COMBUSTION AIR MD D-1 (BOILER) AND D-2 (WATER HEATER) SHALL BOTH

OPEN WHENEVER EITHER BURNER FIRES OR WHEN “OPEN-AUTO” IS

INDICATED “OPEN” AT OPERATOR WORKSTATION. WHEN DAMPERS ARE

CLOSED THEY SHALL STILL REMAIN OPEN 5% (ADJ. 0-15%). DAMPERS

SHALL CLOSE COMPLETELY IF BOILER FUEL BURNER SHUTS DOWN ON

SAFETY CONTROL (TO PREVENT BOILER ROOM FREEZE-UP). D-1 END

SWITCH SHALL CLOSE TO PROVE DAMPER IS OPEN BEFORE ALLOWING

BOILER TO COMPLETE ITS FIRING CIRCUIT.

a. BOILER B-1 / HOT WATER SYSTEM TEMPERATURE CONTROL

1. BOILER IS CONTROLLED WITH ITS ON BOARD ORIGINAL EQUIPMENT

MANUFACTURER CONTROLLER. NEW BUILDING AUTOMATION SYSTEM

SHALL PROVIDE THE NECESSARY INTERFACE AS FOLLOWS TO ENABLE

AND DISABLE THE OPERATION OF THE EQUIPMENT AND PROVIDE ALARMS

AS SPECIFIED AT THE OPERATOR WORK STATION

2. IMMERSION SENSOR TS-1 AND OUTDOOR SENSOR TS-5 SHALL RESET THE

HWS TEMPERATURE FROM 200 DEG. F. (ADJ.) TO 160 DEG. F (ADJ.) AS

OUTDOOR TEMPERATURE RISES FROM -10 DEG. F. (ADJ.) TO 70 DEG. F.

(ADJ.) BY MODULATING 3-WAY VALVE V-13 (FAIL SAFE IN FULL HEAT

POSITION).

3. AQUASTAT IN BOILER WILL CONTROL BOILER WATER TEMPERATURE AT

200 DEG. F. (ADJ.) CONSTANT.

4. FLOW SWITCH FS-2 SHALL PREVENT BOILER OPERATION UNLESS HW

PUMP. P-1 OR P-1A ARE OPERATING AND FLOW IS PROVEN BY FS-2.

5. BOILER AND PUMPS SHALL STOP WHEN OUTDOOR TEMPERATURE RISES

ABOVE 60 DEG. F. (ADJ.), (P-1A IS STANDBY).

6. HWR SENSOR TS-2 PROVIDES TEMPERATURE INDICTION TO THE DDC

SYSTEM.

7. OUTDOOR SENSOR TS-5 ALSO PROVIDES TEMPERATURE INDICATION AT

OPERATOR WORKSTATION.

8. BAS SHALL ISSUE AN ALARM AT OPERATOR WORKSTATION WHEN HOT

WATER PUMPS P-1, P-1A ARE COMMANDED ON AND FLOW IS NOT PROVEN

BY FS-1.

SEQUENCE OF OPERATION BOILER, WATER HEATER, CA DAMPERS

V-8, 9, 10 (UH-2, 3, 4)

H

C

FAN

V-11

H C

FAN

H

C

FAN

C

C

V-5A, 6A V-5, 6

HWS

HWSHWRCHWS

CHWR

H

C

V-7

HWSHWR

UH

MOTOR

UNIT HEATER-2, 3, 4 CABINET UNIT HEATER-5

PROPELLER UNIT HEATER-1

FAN COIL UNIT- 5, 6

T-1

AI - ZONE SETPOINT ADJUST

AI - ZONE TEMP

BI - ZONE OVERRIDE

M

CT

BI - FAN STATUS

BO - FAN START/STOP

AO - COOLING VALVE

M

AO - HEATING VALVE

M

AO - HEATING VALVE

M

T-1

AI - ZONE SETPOINT ADJUST

AI - ZONE TEMP

BI - ZONE OVERRIDE

M

CT

BI - FAN STATUS

BO - FAN START/STOP

M

CT

BI - FAN STATUS

BO - FAN START/STOP

T-1

AI - ZONE SETPOINT ADJUST

AI - ZONE TEMP

BI - ZONE OVERRIDE

AO - HEATING VALVE

M

T-2

AI - ZONE SETPOINT ADJUST

AI - ZONE TEMP

BI - ZONE OVERRIDE

AO - HEATING VALVE

M

M

CT

BI - FAN STATUS

BO - FAN START/STOP

PLAN NOTES

1. 115/1 BY EC.

2. 24/60 BY ECC.

3. SERVER.

4. OPERATOR WORK STATION (BY

ECC).

5. PROVIDE PROPER NUMBER OF

SUPERVISORY CONTROLLERS TO

ACCOMMODATE QUANTITY OF

FIELD LEVEL CONTROLLERS.

CAPACITY SHALL INCLUDE

EXPANSION FOR FUTURE. ECC

SHALL COORDINATE AND PROVIDE

ELECTRICAL POWER AND

NETWORK ACCESS TO ALL

SUPERVISORY CONTROLLERS.

6. OPERATOR WORKSTATION SHALL

BE LOCATED IN ROOM 022 -

MAINTENANCE OFFICE AREA.

COORDINATE WITH OWNER FOR

EXACT LOCATION.

7. EXISTING 115/1.

CHILLER

CONTROLLER

DDC

AHU-3

DDC

AHU-2

DDC

AHU-1

DDC

FCU DDC

ETHERNET

SWITCH

SUPERVISORY

NETWORK

CONTROLLER

SERVER

TO OWNERS

INTRANET

ETHERNET

INTERNET

CONNECTION

FIREWALL

FIELD LEVEL

NETWORK BY ECC

I/P

ETHERNET

I/P

I/P

I/P

PRT

LAN CONNECTION BY OWNER'S

IT PROVIDER-TYPICAL PER

SUPERVISORY CONTROLLER

EF-X

DDC

UH-X

DDC

AHU-4

DDC

HEATING PUMPS

CONTROLLER

DDC

COOLING PUMPS

CONTROLLER

DDC

SEWER PUMP

CONTROLLER

DDC

BOILER

CONTROLLER

DDC

M

CT

BI - SEWER EJECTOR PUMP ON

SEWER EJECTOR PUMP

BI -HIGH LEVEL ALARM

LEVEL MONITOR

BI - LOW LEVEL ALARM

BI -HIGH LEVEL ALARM

FIRE PROTECTION WATER TANK

TANK

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

G

H

I

J

K

1 2 3 4 5 6 7 8 9 10

DATE:

DRAWN:

REVIEWED:

SHEET TITLE:

SHEET NUMBER:

PROJECT NO.:

PROJECT:

ISSUE:

# DATE: DESCRIPTION:

DESIGNED:

/1

/2

:2 :2

P

M M1.6

CONTROLS DIAGRAM

EPH

JMG

4-20-015

HVAC CONTROLS

UPGRADE

ILLINOIS DEPT. OF NATURAL

RESOURCES

LINCOLN'S NEW SALEM

HISTORIC SITE VISITORS

CENTER - 15588 HISTORY LN,

PETERSBERG, IL 62675

9/15/2020

9/15/2020

BID SET

EPH, JMG

SCALE: NOT TO SCALE

UNIT HEATERS, FAN COIL UNITS

CONTROL DIAGRAM

1. SEWAGE EJECTOR PUMP

a. SEWAGE EJECTION PUMP OPERATION SHALL BE CONTROLLED BY

SEWER EJECTOR PUMP CONTROL PANEL. BAS SHALL MONITOR

THE OPERATION OF THE SEWAGE EJECTION PUMP AND TANK

LEVELS.

2. FIRE PROTECTION WATER STORAGE TANK

a. BAS SHALL ISSUE AN ALARM AT OPERATOR WORKSTATION WHEN

TANK LEVEL FALLS BELOW 80% (ADJ.) OF FULL CAPACITY.

FOR GUIDANCE ONLY. POINTS INDICATED ARE MINIMUM NUMBER OF POINTS. TEMPERATURE CONTROL CONTRACTOR IS RESPONSIBLE FOR PROVIDING ADDITIONAL POINTS AS NEEDED TO COMPLY WITH THE SEQUENCE OF OPERATION AND THE

DESIGN INTENT.

Fan Runtime Exceeded x

Fan in Hand x

Fan Failure x

Low Discharge Air Temp x

High Discharge Air Temp x

Filter Required x

Low Zone Temp x

High Zone Temp x

Cooling Setpoint x x

Heating Setpoint x x

Schedule x

Fan Start/Stop x x x

Fan Status x x

Zone Override x x x

Heating Valve x x x

Cooling Valve x x x

Zone Setpoint Adjust x x

Zone Temp x x x

POINT NAME AI AO BI BO AV BV Loop Sched Trend Alarm Show on Graphic

HARDWARE POINTS SOFTWARE POINTS

FOR GUIDANCE ONLY. POINTS INDICATED ARE MINIMUM NUMBER OF POINTS. TEMPERATURE CONTROL CONTRACTOR IS RESPONSIBLE FOR PROVIDING ADDITIONAL POINTS AS NEEDED TO COMPLY WITH THE SEQUENCE OF OPERATION AND THE

DESIGN INTENT.

Fan Runtime Exceeded x

Fan in Hand x

Fan Failure x

Low Zone Temp x

Heating Setpoint x x

Schedule x

Fan Start/Stop x

Fan Status x x x

Zone Override x x x

Heating Valve x x x

Zone Setpoint Adjust x x

Zone Temp x x x

POINT NAME AI AO BI BO AV BV Loop Sched Trend Alarm Show on Graphic

HARDWARE POINTS SOFTWARE POINTS

FOR GUIDANCE ONLY. POINTS INDICATED ARE MINIMUM NUMBER OF POINTS. TEMPERATURE CONTROL CONTRACTOR IS RESPONSIBLE FOR PROVIDING ADDITIONAL POINTS AS NEEDED TO COMPLY WITH THE SEQUENCE OF OPERATION AND THE

DESIGN INTENT.

Fan Runtime Exceeded x

Fan in Hand x

Fan Failure x

Low Zone Temp x

Heating Setpoint x x

Schedule x

Fan Start/Stop x

Fan Status x x x

Zone Override x x x

Heating Valve x x x

Zone Setpoint Adjust x x

Zone Temp x x x

POINT NAME AI AO BI BO AV BV Loop Sched Trend Alarm Show on Graphic

HARDWARE POINTS SOFTWARE POINTS

FOR GUIDANCE ONLY. POINTS INDICATED ARE MINIMUM NUMBER OF POINTS. TEMPERATURE CONTROL CONTRACTOR IS RESPONSIBLE FOR PROVIDING ADDITIONAL POINTS AS NEEDED TO COMPLY WITH THE SEQUENCE OF OPERATION AND THE

DESIGN INTENT.

Fan Runtime Exceeded x

Fan in Hand x

Fan Failure x

Low Zone Temp x

Heating Setpoint x x

Schedule x

Fan Start/Stop x

Fan Status x x x

Zone Override x x x

Heating Valve x x x

Zone Setpoint Adjust x x

Zone Temp x x x

POINT NAME AI AO BI BO AV BV Loop Sched Trend Alarm Show on Graphic

HARDWARE POINTS SOFTWARE POINTS

SCALE: NOT TO SCALE

BAS SYSTEM ARCHITECTURE

FOR GUIDANCE ONLY. POINTS INDICATED ARE MINIMUM NUMBER OF POINTS. TEMPERATURE CONTROL CONTRACTOR IS RESPONSIBLE FOR PROVIDING ADDITIONAL POINTS AS NEEDED TO COMPLY WITH THE SEQUENCE OF OPERATION AND THE

DESIGN INTENT.

High Level Alarm x x

Pump Status "On" / "Off" x x x

POINT NAME AI AO BI BO AV BV Loop Sched Trend Alarm Show on Graphic

HARDWARE POINTS SOFTWARE POINTS

FOR GUIDANCE ONLY. POINTS INDICATED ARE MINIMUM NUMBER OF POINTS. TEMPERATURE CONTROL CONTRACTOR IS RESPONSIBLE FOR PROVIDING ADDITIONAL POINTS AS NEEDED TO COMPLY WITH THE SEQUENCE OF OPERATION AND THE

DESIGN INTENT.

High Level Alarm x x

Low Level Alarm x x

POINT NAME AI AO BI BO AV BV Loop Sched Trend Alarm Show on Graphic

HARDWARE POINTS SOFTWARE POINTS

SEQUENCE OF OPERATION SEWAGE PUMP AND FIRE TANK

1. CABINET UNIT HEATER (UH-2, 3, 4, 5)

a. ROOM THERMOSTAT T-1 SHALL MODULATE 2-WAY HWS VALVE AND CYCLE FAN

IN SEQUENCE THRU CONTROLLER TO MAINTAIN SPACE TEMPERATURE. THE

UNITS SHALL MAINTAIN REDUCED SETTINGS DURING NIGHT CYCLE.

2. PROPELLER UNIT HEATER (UH-1)

a. ROOM THERMOSTAT T-2 SHALL MODULATE 2-WAY HWS VALVE AND CYCLE FAN

IN SEQUENCE THRU CONTROLLER “AUTO” TO MAINTAIN SPACE TEMPERATURE.

THE UH FAN WILL RUN CONTINUOUS IN THE “ON” POSITION.

3. FAN COIL UNIT (FC-5, 6)

a. ROOM THERMOSTAT T-1 SHALL MODULATE 2-WAY HWS & CHWS VALVES IN

SEQUENCE TO MAINTAIN SPACE TEMPERATURE. CONTROLLER SHALL CYCLE

FAN OPERATION DURING DAY CYCLE OR CYCLE THE FAN TO MAINTAIN A

REDUCED SETTING DURING NIGHT CYCLE.

SEQUENCE OF OPERATION UNIT HEATERS, FAN COIL UNITS

SCALE: NOT TO SCALE

SEWAGE PUMP AND FIRE TANK

CONTROL DIAGRAM

HUMIDIFIER SCHEDULE

MARK MANUFACTURER MODEL SERVICE

DISPERSION

SYSTEM TYPE

CAP…