00 01 15 Lincoln New Salem HVAC Upgrade Drawing Sheets Attachment B.pdf
PDF 3 MB Posted
- Attached to
- DNR-New Salem-HVAC Controls Upgrade
- Solicitation number
- 21-422DNR-DIREC-B-18089
- Issued by
- Madison County, Peoria City, Illinois
About this file
This document is an attachment to a state and local contract opportunity issued by the Illinois Department of Natural Resources (IDNR) for HVAC control upgrades at the Lincoln New Salem historic site. The project involves the demolition of existing HVAC controls and the installation of new DDC controls for the air handling units, boilers, chillers, and other HVAC equipment. The bid set includes drawings and specifications detailing the scope of work. Responses must be submitted electronically per CPO Notice 2020.06, with paper submissions not accepted. No site visit or pre-bid conference is mentioned.
The contract does not specify pricing terms, set asides, incumbent contractors, or funding sources. The bid documents indicate that the existing HVAC systems and controls at the historic site require upgrades, but do not provide details on the current environment or any budgetary requirements. The contract term is not explicitly stated.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT NO.: DATE:
PROFESSIONAL REGISTRATIONS
LOCATION MAP
PROJECT IMAGE
MAP DATA © 2017 GOOGLE
/1
/2
:2 :1
P
M
4-20-015
HVAC CONTROLS UPGRADE
ILLINOIS DEPT. OF NATURAL RESOURCES
LINCOLN'S NEW SALEM HISTORIC
SITE VISITORS CENTER - 15588
HISTORY LN, PETERSBERG, IL 62675
9/15/2020
IL
L
IN
O
IS
D
E P
T
O F
N A
T U
R A
L R
E S
O U
R C
E S
BID SET
H V
A C
C O
N T
R O
L S
U P
G R
A D
E
B
ID
S E
T
PAGES OR DIVISIONS COVERED:
LICENSE RENEWAL DATE:
DATE:
NAME:
SIGNATURE:
THE PORTION OF THIS TECHNICAL SUBMISSION DESCRIBED BELOW
WAS PREPARED BY ME OR UNDER MY DIRECT PERSONAL
SUPERVISION. I AM A DULY LICENSED ENGINEER UNDER THE
LAWS OF THE STATE OF ILLINOIS.
PAGES OR DIVISIONS COVERED:
LICENSE RENEWAL DATE:
DATE:
NAME:
SIGNATURE:
THE PORTION OF THIS TECHNICAL SUBMISSION DESCRIBED BELOW
WAS PREPARED BY ME OR UNDER MY DIRECT PERSONAL
SUPERVISION. I AM A DULY LICENSED ENGINEER UNDER THE
LAWS OF THE STATE OF ILLINOIS.
Jay D. Eman Sept 15, 2020
Nov 30, 2021
Electrical
JOSEPH M.
062-069758
GAIED
JOSEPH M. GAIED
Sep 15, 2020
Nov 30, 2021
Mechanical
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
G
H
I
J
K
1 2 3 4 5 6 7 8 9 10
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/1
/2
:2 :2
P
M MD1.1
CONTROLS
DEMOLITION PLAN
EPH
JMG
4-20-015
HVAC CONTROLS
UPGRADE
ILLINOIS DEPT. OF NATURAL
RESOURCES
LINCOLN'S NEW SALEM
HISTORIC SITE VISITORS
CENTER - 15588 HISTORY LN,
PETERSBERG, IL 62675
9/15/2020
9/15/2020
BID SET
EPH, JMG
KEYNOTES
1 VALVES TO REMAIN. DEMOLISH VALVE ACTUATORS AND ASSOCIATED PNEUMATIC
PIPING AND/OR WIRING BACK TO SOURCE CONTROL PANEL. TYPICAL.
2 DEMOLISH TEMPERATURE SENSOR, ELEMENT AND CONTROL WIRING TO SOURCE
CONTROL PANEL. TYPICAL.
3 DAMPERS TO REMAIN. DEMOLISH DAMPER ACTUATORS AND ASSOCIATED
PNEUMATIC PIPING BACK TO SOURCE CONTROL PANEL. TYPICAL.
4 DEMOLISH LOCAL CONTROL PANEL AND LOCAL CONTROL MODULES AND ALL
ASSOCIATED PNEUMATIC PIPING AND CONTROL WIRING.
5 ALL EXISTING MOTOR STARTERS ARE TO REMAIN.
SCALE: NOT TO SCALE
AHU-1 CONTROLS DEMOLITION
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
G
H
I
J
K
1 2 3 4 5 6 7 8 9 10
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/1
/2
:2 :2
P
M MD1.2
CONTROLS
DEMOLITION PLAN
EPH
JMG
4-20-015
HVAC CONTROLS
UPGRADE
ILLINOIS DEPT. OF NATURAL
RESOURCES
LINCOLN'S NEW SALEM
HISTORIC SITE VISITORS
CENTER - 15588 HISTORY LN,
PETERSBERG, IL 62675
9/15/2020
9/15/2020
BID SET
EPH, JMG
KEYNOTES
1 VALVES TO REMAIN. DEMOLISH VALVE ACTUATORS AND ASSOCIATED PNEUMATIC
PIPING AND/OR WIRING BACK TO SOURCE CONTROL PANEL. TYPICAL.
2 DEMOLISH AVERAGING TEMPERATURE SENSOR, ELEMENT AND CONTROL WIRING
TO SOURCE CONTROL PANEL. TYPICAL.
3 DAMPERS TO REMAIN. DEMOLISH DAMPER ACTUATORS AND ASSOCIATED
PNEUMATIC PIPING BACK TO SOURCE CONTROL PANEL. TYPICAL.
4 DEMOLISH LOCAL CONTROL PANEL AND LOCAL CONTROL MODULES AND ALL
ASSOCIATED PNEUMATIC PIPING AND CONTROL WIRING.
5 ALL EXISTING MOTOR STARTERS TO REMAIN.
SCALE: NOT TO SCALE
AHU-2 CONTROLS DEMOLOTION
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
G
H
I
J
K
1 2 3 4 5 6 7 8 9 10
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/1
/2
:2 :2
P
M MD1.3
CONTROLS
DEMOLITION PLAN
EPH
JMG
4-20-015
HVAC CONTROLS
UPGRADE
ILLINOIS DEPT. OF NATURAL
RESOURCES
LINCOLN'S NEW SALEM
HISTORIC SITE VISITORS
CENTER - 15588 HISTORY LN,
PETERSBERG, IL 62675
9/15/2020
9/15/2020
BID SET
EPH, JMG
KEYNOTES
1 VALVES TO REMAIN. DEMOLISH VALVE ACTUATORS AND ASSOCIATED PNEUMATIC
PIPING AND/OR WIRING BACK TO SOURCE CONTROL PANEL. TYPICAL.
2 DEMOLISH AVERAGING TEMPERATURE SENSOR, ELEMENT AND CONTROL WIRING
TO SOURCE CONTROL PANEL. TYPICAL.
3 DAMPERS TO REMAIN. DEMOLISH DAMPER ACTUATORS AND ASSOCIATED
PNEUMATIC PIPING BACK TO SOURCE CONTROL PANEL. TYPICAL.
4 DEMOLISH LOCAL CONTROL PANEL AND LOCAL CONTROL MODULES AND ALL
ASSOCIATED PNEUMATIC PIPING AND CONTROL WIRING.
5 ALL MOTOR STARTERS TO REMAIN.
SCALE: NOT TO SCALE
AHU-3 CONTROLS DEMOLITION
A. CONTRACTOR IS TO DEMOLISH EXISTING NON-OPERATIONAL HUMIDIFIER AND ALL
ASSOCIATED PNEUMATIC CONTROLS. NEW HUMIDIFIER IS TO BE INSTALLED IN SAME
LOCATION.
GENERAL NOTES
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
G
H
I
J
K
1 2 3 4 5 6 7 8 9 10
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/1
/2
:2 :2
P
M MD1.4
CONTROLS
DEMOLITION PLAN
EPH
JMG
4-20-015
HVAC CONTROLS
UPGRADE
ILLINOIS DEPT. OF NATURAL
RESOURCES
LINCOLN'S NEW SALEM
HISTORIC SITE VISITORS
CENTER - 15588 HISTORY LN,
PETERSBERG, IL 62675
9/15/2020
9/15/2020
BID SET
EPH, JMG
KEYNOTES
1 DEMOLISH PNEUMATIC PIPING, DAMPER ACTUATORS, AND CONTROL WIRING FOR
STAND ALONE EXHAUST FAN. TYPICAL.
2 VALVES TO REMAIN. DEMOLISH VALVE ACTUATORS AND ASSOCIATED PNEUMATIC
PIPING AND/OR WIRING BACK TO SOURCE CONTROL PANEL. TYPICAL.
3 DEMOLISH TEMPERATURE SENSOR, ELEMENT AND CONTROL WIRING TO SOURCE
CONTROL PANEL. TYPICAL.
4 DAMPERS TO REMAIN. DEMOLISH DAMPER ACTUATORS AND ASSOCIATED
PNEUMATIC PIPING BACK TO SOURCE CONTROL PANEL. TYPICAL.
5 ALL MOTOR STARTERS ARE TO REMAIN.
6 DEMOLISH LOCAL CONTROL PANEL AND LOCAL CONTROL MODULES AND ALL
ASSOCIATED PNEUMATIC PIPING AND CONTROL WIRING.
SCALE: NOT TO SCALE
AHU-4 CONTROLS DEMOLITION
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
G
H
I
J
K
1 2 3 4 5 6 7 8 9 10
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/1
/2
:2 :2
P
M MD1.5
CONTROLS
DEMOLITION PLAN
EPH
JMG
4-20-015
HVAC CONTROLS
UPGRADE
ILLINOIS DEPT. OF NATURAL
RESOURCES
LINCOLN'S NEW SALEM
HISTORIC SITE VISITORS
CENTER - 15588 HISTORY LN,
PETERSBERG, IL 62675
9/15/2020
9/15/2020
BID SET
EPH, JMG
SCALE: NOT TO SCALE
BOILER, CHILLER, FANS CONTROLS
DEMOLITION
KEYNOTES
1 DEMOLISH PNEUMATIC PIPING , DAMPER ACTUATORS, AND CONTROL WIRING FOR
STAND ALONE EXHAUST FAN. TYPICAL.
2 VALVES TO REMAIN. DEMOLISH VALVE ACTUATORS AND ASSOCIATED PNEUMATIC
PIPING AND/OR WIRING BACK TO SOURCE CONTROL PANEL. TYPICAL.
3 DAMPERS TO REMAIN. DEMOLISH DAMPER ACTUATORS AND ASSOCIATED
PNEUMATIC PIPING BACK TO SOURCE CONTROL PANEL. TYPICAL.
4 ALL MOTOR STARTERS ARE TO REMAIN.
5 DEMOLISH LOCAL CONTROL PANEL AND LOCAL CONTROL MODULES AND ALL
ASSOCIATED PNEUMATIC PIPING AND CONTROL WIRING.
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
G
H
I
J
K
1 2 3 4 5 6 7 8 9 10
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/1
/2
:2 :2
P
M MD1.6
CONTROLS
DEMOLITION PLAN
EPH
JMG
4-20-015
HVAC CONTROLS
UPGRADE
ILLINOIS DEPT. OF NATURAL
RESOURCES
LINCOLN'S NEW SALEM
HISTORIC SITE VISITORS
CENTER - 15588 HISTORY LN,
PETERSBERG, IL 62675
9/15/2020
9/15/2020
BID SET
EPH, JMG
SCALE: NOT TO SCALE
UNIT HEATERS, COMPRESSOR, FAN
COIL UNIT CONTROLS DEMOLITION
KEYNOTES
1 VALVES TO REMAIN. DEMOLISH VALVE ACTUATORS AND ASSOCIATED PNEUMATIC
PIPING AND/OR WIRING BACK TO SOURCE CONTROL PANEL. TYPICAL.
2 EXHAUST FAN 10 WAS NEVER INSTALLED. REMOVE ANY ASSOCIATED PNEUAMTIC
CONTROLS IF INSTALLED TO FACILITATE PLANNED FUTURE INSTALLATION.
3 DEMOLISH CENTRAL CONTROL PANEL AND ALL MODULES ASSOCIATED WITH
PNEUMATIC CONTROLS.
4 ALL MOTOR STARTERS ARE TO REMAIN.
AHU-3FCU-6
FCU-5
UH-3
UH-5
AHU-2
UH-4
H-3
AHU-4
FCU-6
EF-11
FCU-5
UH-3
UH-4
UH-5
UH-2
AHU-1A
AHU-1B
AHU-1C
UH-2
AHU-4
AHU-1AHU-3AHU-2
EF-12
EF-1
EF-2
P-2
P-1A
P-1
B-1
UH-1
H-3
COMBUSTION AIR
DAMPERS
WH
EXISTING CONTROL PANEL
LOCATIONS
PNEUMATIC
COMPRESSOR
UH-1
EF-4 & 4A
EXISTING CONTROL PANEL
SEWER EJECTOR
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
G
H
I
J
K
1 2 3 4 5 6 7 8 9 10
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/1
/2
:2 :2
P
M MD3.1
BUILDING LAYOUT
DEMOLITION
EPH
JMG
4-20-015
HVAC CONTROLS
UPGRADE
ILLINOIS DEPT. OF NATURAL
RESOURCES
LINCOLN'S NEW SALEM
HISTORIC SITE VISITORS
CENTER - 15588 HISTORY LN,
PETERSBERG, IL 62675
9/15/2020
9/15/2020
BID SET
EPH, JMG
SCALE: NOT TO SCALE
FIRST FLOOR LAYOUT DEMOLITION
SCALE: NOT TO SCALE
BASEMENT LAYOUT DEMOLITION
B. ALL THERMOSTATS ARE SHOWN FOR LOCATIONAL REFERENCE. ALL EXISTING
PNEUMATIC THERMOSTATS ARE TO BE DEMOLISHED. NEW THERMOSTATS ARE TO BE
LOCATED IN SAME LOCATION. SEE SHEET M3.1.
A. EXISTING BUILDING DRAWINGS ARE AVAILABLE UPON REQUEST FROM OWNER.
GENERAL NOTES
KEYNOTES
1 DEMOLISH EXISTING COMPRESSOR AND RETURN TO OWNER. DEMOLISH ALL
PIPING AND WIRING ASSOCIATED WITH PNEUMATIC CONTROLS.
2 MECHANICAL CONTRACTOR IS TO DEMOLISH EXISTING HUMIDIFIER, DISPERSION
TUBE, AND CONTROL WIRING. NEW HUMIDIFIER IS TO BE INSTALLED IN SAME
LOCATION. REFER TO SHEET M3.1.
3 DEMOLISH EXISITNG CONTROL PANELS ASSOCIATED WITH PNEUMATIC CONTROL
SYSTEM. CONTRACTOR IS TO VERIFY IN FIELD ALL LOCATIONS OF PANELS
NEEDING TO BE DEMOLISHED.
NC
NORA
EA
EF-1
EF
MOTOR
OA
NC
NO
C
C
TS-2
CHWR CHWS
SA
RH
C
HWS
HWR
DP-1
HC-1A, 1B, 1C
T-2
D4
D2
D3
TS-3
V-14A, B, C
V-1A
SF
AIR HANDLING UNIT 1
AO - RETURN AIR DAMPER
BI - RETURN AIR DAMPER STATUS
AO - EXHAUST AIR DAMPER
BI - EXHAUST AIR DAMPER STATUS
BI - FAN STATUS
BO - FAN START/STOP
M
CT
NC
D1
AO - OUTSIDE AIR DAMPER
BI - OUTSIDE AIR DAMPER STATUS
AI - MIXED AIR TEMP AO - COOLING VALVE
M
AO - HEATING VALVE
M
BI - F&BP DAMPER STATUS
AO - FACE & BYPASS DAMPER
AI - FAN DIFFERENTIAL PRESSURE
T-1
AI - ZONE SETPOINT ADJUST
AI - ZONE TEMP
BI - ZONE OVERRIDE
BI - FREEZE STAT
AI - DISCHARGE AIR TEMP
M CT
BI - FAN STATUS
BO - FAN START/STOP
TS-4
AI - DISCHARGE AIR TEMP
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
G
H
I
J
K
1 2 3 4 5 6 7 8 9 10
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/1
/2
:2 :2
P
M M1.1
CONTROLS DIAGRAM
EPH
JMG
4-20-015
HVAC CONTROLS
UPGRADE
ILLINOIS DEPT. OF NATURAL
RESOURCES
LINCOLN'S NEW SALEM
HISTORIC SITE VISITORS
CENTER - 15588 HISTORY LN,
PETERSBERG, IL 62675
9/15/2020
9/15/2020
BID SET
EPH, JMG
KEYNOTES
1 THERMOSTATS LOCATIONS ARE CALLED OUT ON SHEET M3.1. THERMOSTATS ARE
TO BE INSTALLED AT REMOVED PNEUMATIC THERMOSTAT HEIGHT AND LOCATION.
SCALE: NOT TO SCALE
AHU-1, EF-1 CONTROL DIAGRAM
1. AIR HANDLING UNIT AHU-1
a. GENERAL
1. AHU-1 IS A SINGLE ZONE DRAW THRU AIR HANDLING UNIT WITH FACE AND BYPASS
DAMPERS, CHILLED WATER COOLING COIL AND OUTDOOR, RETURN AND RELIEF AIR (EF-1)
MIXING DAMPERS.
2. DDC CONTROLLER SHALL PROVIDE AHU-1 CONTROL FUNCTIONS, CONTROLLER SHALL
ACCEPT ANALOG INPUTS FROM ELECTRONIC SENSORS OR BINARY INPUTS FROM
CONTACT CLOSURES. CONTROLLER PROVIDES ANALOG OUTPUTS TO THE VALVE AND
DAMPER ACTUATORS. BINARY OUTPUTS ARE PROVIDED FOR STARTING AND STOPPING
OF FANS AND RELATED SYSTEM DEVICES.
b. STARTING/STOPPING SEQUENCE
1. AHU-1 SUPPLY FAN IS STARTED AND STOPPED FROM THE DDC SYSTEM AND SHALL RUN
CONTINUOUSLY DURING THE DAY CYCLE TO MAINTAIN A SPACE SET POINT OF 75 DEG. F.
(ADJ.) DURING THE OCCUPIED SUMMER OPERATION AND 70 DEG. F. (ADJ.) DURING THE
OCCUPIED WINTER OPERATION. IT SHALL CYCLE TO MAINTAIN A REDUCED SETTING ON
NIGHT CYCLE TO MAINTAIN A SPACE SET POINT OF 80 DEG. F. (ADJ.) DURING THE
UNOCCUPIED SUMMER OPERATION AND 65 DEG. F. (ADJ.) DURING THE UNOCCUPPIED
WINTER OPERATION. THIS IS BASED ON USER PREDEFINED SCHEDULE. T-1 IS USED FOR
OPTIMAL START/STOP AND NIGHT CYCLE.
2. EF-1 IS STARTED AND STOPPED FROM THE DDC SYSTEM AND SHALL BE ENABLED TO RUN
WHENEVER AHU-1 RUNS ON DAY CYCLE AND REMAIN OFF DURING NIGHT CYCLE. (SEE
MIXED AIR/ECONOMIZER SEQUENCE BELOW).
3. DAY-AUTO-NIGHT SWITCH AT OPERATOR WORKSTATION SHALL OVERRIDE THE DDC
SYSTEM TIME CLOCK AND RETURN SYSTEM TO DAY OR NIGHT CYCLE IF DESIRED.
4. AUTO-OFF SWITCH AT OPERATOR WORKSTATION SHALL DETERMINE AHU-1 SYSTEM
OPERATION.
c. WARM-UP SEQUENCE
1. WHEN SYSTEM IS CHANGED FROM NIGHT TO DAY CYCLE, OA MD D-1 SHALL DELAY
OPENING UNTIL AREA REACHES DAY TEMPERATURE SETTING AT WHICH TIME THE OA MD
D-1 SHALL OPEN TO A 30% (ADJ.) MINIMUM POSITION. THE REL A MD D-3 SHALL FOLLOW
THE OA MD EXCEPT THEY SHALL DELAY OPENING BY 20% (ADJ.). THE RA MD D-2 SHALL
CLOSE IN OPPOSITE PROPORTION TO THE MA MD.
d. DUCT HEATING COIL/COOLING SEQUENCE
1. BAS SHALL MODULATE THE RESPECTIVE SPACE COIL VALVES V-14A, B, C TO MAINTAIN
SPACE TEMPERATURE SETPOINT BASED ON SIGNAL RECIEVED FROM TS-2, TS-4. THE OA
MD D-1, RA MD D-2, REL A MD D-3, FACE & BYPASS DAMPERS AND COOLING COIL 3-WAY
VALVE V-1A SHALL BE SEQUENCED BY THE ROOM THERMOSTAT CALLING FOR THE MOST
COOLING. (SEE MIXED AIR/ECONOMIZER SEQUENCE).
e. MIXED AIR/ECONOMIZER SEQUENCE
1. THE CONTROLLER SHALL MEASURE THE MIXED AIR TEMPERATURE AND MODULATE THE
ECONOMIZER DAMPERS IN SEQUENCE TO MAINTAIN A SETPOINT 2 DEG. F. (ADJ.) LESS
THAN THE SUPPLY AIR TEMPERATURE SETPOINT. THE OUTSIDE AIR DAMPERS SHALL
MAINTAIN A MINIMUM ADJUSTABLE POSITION OF 20% (ADJ.) OPEN WHENEVER OCCUPIED.
THE ECONOMIZER SHALL BE ENABLED WHENEVER:
- OUTSIDE AIR TEMPERATURE IS LESS THAN 65 DEG. F. (ADJ.).
- AND THE OUTSIDE AIR TEMPERATURE IS LESS THAN THE RETURN AIR
TEMPERATURE.
- AND THE SUPPLY FAN STATUS IS ON.
THE ECONOMIZER SHALL CLOSE WHENEVER:
- MIXED AIR TEMPERATURE DROPS FROM 40 DEG. F. TO 35 DEG. F. (ADJ.).
- OR THE FREEZESTAT (IF PRESENT) IS ON.
- OR ON LOSS OF SUPPLY FAN STATUS.
THE OUTSIDE AND EXHAUST AIR DAMPERS SHALL CLOSE AND THE RETURN AIR DAMPER
SHALL OPEN WHEN THE UNIT IS OFF. IF OPTIMAL START UP IS AVAILABLE THE MIXED AIR
DAMPER SHALL OPERATE AS DESCRIBED IN THE OCCUPIED MODE EXCEPT THAT THE
OUTSIDE AIR DAMPER SHALL MODULATE TO FULLY CLOSED.
2. MIXED AIR LOW LIMIT SENSOR TS-3 SHALL PREVENT TEMPERATURE FROM FALLING
BELOW 50 DEG. F. (ADJ.).
3. EXHAUST FAN EF-1 SHALL SEQUENCE FROM OFF TO LOW TO HIGH SPEED AS REL A MD
D-3 MODULATES OPEN.
f. INTERLOCK/SAFETY SEQUENCE
1. EXISTING SMOKE DETECTORS SHALL STOP SUPPLY FAN WHEN SMOKE IS DETECTED.
2. FREEZESTAT T-2, MANUAL RESET, SHALL STOP SUPPLY FAN WHEN TEMPERATURE FALLS
BELOW ITS SETTING.
3. OA MD D-1 AND REL A MD D-3 SHALL CLOSE AND RA MD D-2 SHALL OPEN DURING NIGHT
CYCLE OR ANYTIME FAN STOPS.
4. CHILLED WATER COIL 3-WAY VALVE V-2A SHALL GO TO FULL BYPASS WHEN SUPPLY FAN
STOPS.
5. DIFFERENTIAL PRESSURE SWITCH DP-1 SHALL PROVIDE FAN INTERLOCK AND “FAN ON”
INDICATION AT OPERATOR WORKSTATION.
6. AVERAGE SPACE TEMPERATURE INDICATION SHALL ALSO BE PROVIDED AT OPERATOR
WORKSTATION.
7. UNIT SHALL SHUT DOWN UPON RECEIVING SIGNAL FROM FIRE ALARM CONTROL PANEL.
FOR GUIDANCE ONLY. POINTS INDICATED ARE MINIMUM NUMBER OF POINTS. TEMPERATURE CONTROL CONTRACTOR IS RESPONSIBLE FOR PROVIDING ADDITIONAL POINTS AS NEEDED TO COMPLY WITH THE SEQUENCE OF OPERATION AND THE
DESIGN INTENT.
Fan in Hand x x
Fan Failure x x
Exhaust Air Damper in Hand x x
Exhaust Air Damper Failure x x
Exhaust Schedule x
Exhaust Air Damper x x x
Exhaust Fan Start/Stop x x x
Exhaust Fan Status x x x
Exhaust Air Damper Status x x x
Exhaust Fan Runtime Exceeded x x
Exhaust Fan in Hand x x
Exhaust Fan Failure x x
Low Discharge Air Temp x x
High Dischargbe Air Temp x x
Filter Change Required x x
Low Zone Temp x x
High Zone Temp x x
Heating Setpoint x x
Cooling Setpoint x x
Schedule x
Emergency Shutdown x x x x
Return Air Damper x x x
Outside Air Damper x x x
Supply Fan Start/Stop x x x
Return Air Damper Status x x x
Face and Bypass Damper Status x x x
Supply Fan Status x x x
Smoke Detector x x x x
Freezestat x x x x
Zone Override x x x
Outside Air Damper Status x x x
Heating Valve x x x
Cooling Valve x x x
Face and Bypass Dampers x x x
Mixed Air Temp x x x
Discharge Air Temp x x x
Fan Differential Pressure x x x
Zone Setpoint Adjust x x x
Zone Temp x x x
POINT NAME AI AO BI BO AV BV Loop Sched Trend Alarm Show on Graphic
HARDWARE POINTS SOFTWARE POINTS
NCNORA
EA
EF-2
EF
MOTOR
OA
NC
NO
C
C
CHWR CHWS
DP-1
D4
D1
D2
D3
TS-3
V-2A
SF
H
C
HWS
HWR
V-2
SA
T-1
EAEF-11
EF
MOTOR
D5
AIR HANDLING UNIT 2
BO - EXHAUST AIR DAMPER
BI - FAN STATUS
BO - FAN START/STOP
M
CT
BI - EXHAUST AIR DAMPER STATUS
BI - FAN STATUS
BO - FAN START/STOP
M
CT
AO - EXHAUST AIR DAMPER
BI - EXHAUST AIR DAMPER STATUS
AO - RETURN AIR DAMPER
BI - RETURN AIR DAMPER STATUS
AO - OUTSIDE AIR DAMPER
BI - OUTSIDE AIR DAMPER STATUS
AI - MIXED AIR TEMP
TS-2
AI - DISCHARGE AIR TEMP
AO - FACE & BYPASS DAMPER
BI - F&BP DAMPER STATUS
AI - ZONE SETPOINT ADJUST
AI - ZONE TEMP
BI - ZONE OVERRIDE
AO - HEATING VALVE
M
AO - COOLING VALVE
M
AI - FAN DIFFERENTIAL PRESSURE
T-2
BI - FREEZE STAT
M CT
BI - FAN STATUS
BO - FAN START/STOP
EF - 11
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
G
H
I
J
K
1 2 3 4 5 6 7 8 9 10
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/1
/2
:2 :2
P
M M1.2
CONTROLS DIAGRAM
EPH
JMG
4-20-015
HVAC CONTROLS
UPGRADE
ILLINOIS DEPT. OF NATURAL
RESOURCES
LINCOLN'S NEW SALEM
HISTORIC SITE VISITORS
CENTER - 15588 HISTORY LN,
PETERSBERG, IL 62675
9/15/2020
9/15/2020
BID SET
EPH, JMG
KEYNOTES
1 THERMOSTAT LOCATION IS CALLED OUT ON SHEET M3.1. THERMOSTAT IS TO BE
INSTALLED AT REMOVED PNEUMATIC THERMOSTAT HEIGHT AND LOCATION.
SCALE: NOT TO SCALE
AHU-2, EF-2, EF-11 CONTROL DIAGRAM
1. AIR HANDLING UNIT AHU-2
a. GENERAL
1. AHU-2 IS A SINGLE ZONE DRAW THRU AIR HANDLING UNIT WITH A HOT WATER
HEATING COIL, FACE AND BYPASS DAMPERS, CHILLED WATER COOLING COIL,
AND OUTDOOR, RETURN, AND RELIEF AIR (EF-2) MIXING DAMPERS.
2. DDC CONTROLLER SHALL PROVIDE AHU-2 CONTROL FUNCTIONS. CONTROLLER
SHALL ACCEPT ANALOG INPUTS FROM ELECTRONIC SENSORS OR BINARY
INPUTS FROM CONTACT CLOSURES. CONTROLLER PROVIDES ANALOG
OUTPUTS TO THE VALVE AND DAMPER ACTUATORS. BINARY OUTPUTS ARE
PROVIDED FOR STARTING AND STOPPING OF FANS AND RELATED SYSTEM
DEVICES.
b. STARTING/STOPPING SEQUENCE
1. AHU-2 SUPPLY FAN IS STARTED AND STOPPED FROM THE DDC SYSTEM AND
SHALL RUN CONTINUOUSLY DURING DAY CYCLE TO MAINTAIN A SPACE SET
POINT OF 75 DEG. F. (ADJ.) DURING THE OCCUPIED SUMMER OPERATION AND
70 DEG. F. (ADJ.) IT SHALL CYCLE TO MAINTAIN A REDUCED SETTING ON NIGHT
CYCLE TO MAINTAIN A SPACE SET POINT OF 80 DEG. F. (ADJ.) DURING THE
UNOCCUPIED SUMMER OPERATION AND 65 DEG. F. (ADJ.) DURING THE
UNOCCUPPIED WINTER OPERATION. THIS IS BASED ON USER PREDEFINED
SCHEDULE.
2. EF-11 SHALL RUN WHEN AHU-2 RUNS ON DAY CYCLE AND REMAIN OFF DURING
NIGHT CYCLE. EF-11 DAMPER D-5 SHALL OPEN WHEN EF-11 RUNS AND CLOSE
WHEN EF-11 STOPS.
3. EF-2 IS STARTED AND STOPPED FROM THE DDC SYSTEM AND SHALL BE
ENABLED TO RUN WHENEVER AHU-2 RUNS OF DAY CYCLE AND REMAIN OFF
DURING NIGHT CYCLE. (SEE MIXED AIR/ECONOMIZER SEQUENCE BELOW).
4. DAY-AUTO-NIGHT SWITCH AT OPERATOR WORKSTATION SHALL OVERRIDE THE
DDC SYSTEM TIME CLOCK AND RETURN SYSTEM TO DAY OR NIGHT CYCLE IF
DESIRED.
5. AUTO-OFF SPEED SWITCH AT OPERATOR WORKSTATION SHALL DETERMINE
AHU-2/EF-2 SYSTEM OPERATION.
c. WARM-UP SEQUENCE
1. WHEN SYSTEM IS CHANGED FROM NIGHT TO DAY CYCLE, OA MD D-1 SHALL
DELAY OPENING UNTIL AREA REACHES DAY TEMPERATURE SETTING AT WHICH
TIME THE OA MD D-1 SHALL OPEN TO A 30% (ADJ.) MINIMUM POSITION. THE REL
A MD D-3 SHALL FOLLOW THE OA MD EXCEPT THEY SHALL DELAY OPENING BY
20% (ADJ.). THE RA MD D-2 SHALL CLOSE IN OPPOSITE PROPORTION TO THE OA
MD.
d. MIXED AIR/ECONOMIZER SEQUENCE
1. THE CONTROLLER SHALL MEASURE THE MIXED AIR TEMPERATURE AND
MODULATE THE ECONOMIZER DAMPERS IN SEQUENCE TO MAINTAIN A
SETPOINT 2 DEG. F. (ADJ.) LESS THAN THE SUPPLY AIR TEMPERATURE
SETPOINT. THE OUTSIDE AIR DAMPERS SHALL MAINTAIN A MINIMUM
ADJUSTABLE POSITION OF 20% (ADJ.) OPEN WHENEVER OCCUPIED.
THE ECONOMIZER SHALL BE ENABLED WHENEVER:
- OUTSIDE AIR TEMPERATURE IS LESS THAN 65 DEG. F. (ADJ.).
- AND THE OUTSIDE AIR TEMPERATURE IS LESS THAN THE RETURN AIR
TEMPERATURE.
- AND THE SUPPLY FAN STATUS IS ON.
THE ECONOMIZER SHALL CLOSE WHENEVER:
- MIXED AIR TEMPERATURE DROPS FROM 40 DEG. F. TO 35 DEG. F.
(ADJ.).
- OR THE FREEZESTAT (IF PRESENT) IS ON.
- OR ON LOSS OF SUPPLY FAN STATUS.
THE OUTSIDE AND EXHAUST AIR DAMPERS SHALL CLOSE AND THE RETURN AIR
DAMPER SHALL OPEN WHEN THE UNIT IS OFF. IF OPTIMAL START UP IS
AVAILABLE THE MIXED AIR DAMPER SHALL OPERATE AS DESCRIBED IN THE
OCCUPIED MODE EXCEPT THAT THE OUTSIDE AIR DAMPER SHALL MODULATE
TO FULLY CLOSED.
2. MIXED AIR LOW LIMIT SENSOR TS-3 SHALL PREVENT TEMPERATURE FROM
FALLING BELOW 50 DEG. F. (ADJ.).
3. EXHAUST FAN EF-2 SHALL SEQUENCE FROM OFF TO LOW TO HIGH SPEED AS
REL A MD D-3 MODULATES OPEN.
e. HEATING SEQUENCE
1. ON A CALL FOR HEATING, SPACE SENSOR T-1 SHALL MODULATE HEATING COIL
2-WAY VALVE V-2 OPEN TO COIL AND F&BP MD D-4 OPEN TO COIL FACE TO
MAINTAIN SPACE TEMPERATURE.
2. WHEN OA TEMPERATURE FALLS BELOW 40 DEG. F. (ADJ.) V-2 SHALL REMAIN
OPEN AND THE F&BP MD D-4 SHALL MODULATE OPEN OR CLOSED TO MAINTAIN
SPACE TEMPERATURE.
3. LOW LIMIT DISCHARGE SENSOR TS-2 SHALL PREVENT TEMPERATURE FROM
FALLING BELOW 50 DEG. F. (ADJ.).
f. COOLING SEQUENCE
1. WHEN CHILLED WATER COOLING IS AVAILABLE, A CALL FOR COOLING FROM
SPACE SENSOR T-1 SHALL MODULATE THE 3-WAY COOLING VALVE V-2A TO
MAINTAIN SPACE TEMPERATURE, F&BP MD D-4 SHALL REMAIN OPEN TO THE
COIL FACE.
2. HEATING VALVE V-2 SHALL REMAIN CLOSED.
g. INTERLOCK/SAFETY SEQUENCE
1. EXISTING SMOKE DETECTOR SHALL STOP SUPPLY FAN WHEN SMOKE IS
DETECTED.
2. FREEZESTAT T-2, MANUAL RESET, SHALL STOP SUPPLY FAN WHEN
TEMPERATURE FALLS BELOW ITS SETTING.
3. OA MD D-1AND REL A MD D-3 SHALL CLOSE AND RA MD D-2 SHALL OPEN
DURING NIGHT OR ANYTIME FAN STOPS.
4. CHILLED WATER COIL 3-WAY VALVE V-2A SHALL GO TO FULL BYPASS WHEN
SUPPLY FAN STOPS.
5. DIFFERENTIAL PRESSURE SWITCH DP-1 SHALL PROVIDE FAN INTERLOCK AND
“FAN ON” INDICATION AT OPERATOR WORKSTATION.
6. ROOM SENSOR T-1 SHALL ALSO PROVIDE TEMPERATURE INDICATION AT
OPERATOR WORKSTATION.
7. UNIT SHALL SHUT DOWN UPON RECEIVING SIGNAL FROM FIRE ALARM
CONTROL PANEL.
FOR GUIDANCE ONLY. POINTS INDICATED ARE MINIMUM NUMBER OF POINTS. TEMPERATURE CONTROL CONTRACTOR IS RESPONSIBLE FOR PROVIDING ADDITIONAL POINTS AS NEEDED TO COMPLY WITH THE SEQUENCE OF OPERATION AND THE
DESIGN INTENT.
Fan in Hand x x
Fan Failure x x
Exhaust Air Damper in Hand x x
Exhaust Air Damper Failure x x
Schedule x
Exhaust Air Damper x x x
Fan Start/Stop x x x
Fan Status x x x
Exhaust Air Damper Status x x x
POINT NAME AI AO BI BO AV BV Loop Sched Trend Alarm Show on Graphic
HARDWARE POINTS SOFTWARE POINTS
FOR GUIDANCE ONLY. POINTS INDICATED ARE MINIMUM NUMBER OF POINTS. TEMPERATURE CONTROL CONTRACTOR IS RESPONSIBLE FOR PROVIDING ADDITIONAL POINTS AS NEEDED TO COMPLY WITH THE SEQUENCE OF OPERATION AND THE
DESIGN INTENT.
Fan in Hand x x
Fan Failure x x
Exhaust Air Damper in Hand x x
Exhaust Air Damper Failure x x
Exhaust Schedule x
Exhaust Air Damper x x x
Exhaust Fan Start/Stop x x x
Exhaust Fan Status x x x
Exhaust Air Damper Status x x x
Exhaust Fan Runtime Exceeded x x
Exhaust Fan in Hand x x
Exhaust Fan Failure x x
Low Discharge Air Temp x x
High Dischargbe Air Temp x x
Filter Change Required x x
Low Zone Temp x x
High Zone Temp x x
Heating Setpoint x x
Cooling Setpoint x x
Schedule x
Emergency Shutdown x x x x
Return Air Damper x x x
Outside Air Damper x x x
Supply Fan Start/Stop x x x
Return Air Damper Status x x x
Face and Bypass Damper Status x x x
Supply Fan Status x x x
Smoke Detector x x x x
Freezestat x x x x
Zone Override x x x
Outside Air Damper Status x x x
Heating Valve x x x
Cooling Valve x x x
Face and Bypass Dampers x x x
Mixed Air Temp x x x
Discharge Air Temp x x x
Fan Differential Pressure x x x
Zone Setpoint Adjust x x x
Zone Temp x x x
OA
RA
NC
NO
C
C
TS-2
CHWR CHWS
D2
D1
V-3A
SF
H
C
HWS
HWR
V-3
SA
NC
H-1
SS H
AIR HANDLING UNIT 3
AO - OUTSIDE AIR DAMPER
BI - OUTSIDE AIR DAMPER STATUS
H
AI - MIXED AIR HUMIDITY
TS-3
AI - MIXED AIR TEMP
AO - COOLING VALVE
M AO - HEATING VALVE
M
T-2
BI - FREEZE STAT
AO - FACE & BYPASS DAMPER
BI - F&BP DAMPER STATUS
AI - SUPPLY AIR HUMIDITY
AI - SUPPLY AIR SWITCH
AI - DISCHARGE AIR TEMP
M CT
BI - FAN STATUS
BO - FAN START/STOP
DP-1
AI - FAN DIFFERENTIAL PRESSURE
T-1
AI - ZONE SETPOINT ADJUST
AI - ZONE TEMP
BI - ZONE OVERRIDE
AI - ZONE HUMIDITY
H3
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
G
H
I
J
K
1 2 3 4 5 6 7 8 9 10
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/1
/2
:2 :2
P
M M1.3
CONTROLS DIAGRAM
EPH
JMG
4-20-015
HVAC CONTROLS
UPGRADE
ILLINOIS DEPT. OF NATURAL
RESOURCES
LINCOLN'S NEW SALEM
HISTORIC SITE VISITORS
CENTER - 15588 HISTORY LN,
PETERSBERG, IL 62675
9/15/2020
9/15/2020
BID SET
EPH, JMG
A. NEW HUMIDIFIER H-3 IS TO BE INSTALLED IN SAME LOCATION AS PREVIOUS
HUMIDIFIER.
GENERAL NOTES
KEYNOTES
1 THERMOSTAT AND HUMIDSTAT LOCATIONS ARE CALLED OUT ON SHEET M3.1.
THERMOSTAT AND HUMIDSTAT ARE TO BE INSTALLED AT REMOVED PNEUMATIC
THERMOSTAT AND HUMIDSTAT HEIGHT AND LOCATION.
SCALE: NOT TO SCALE
AHU-3 CONTROL DIAGRAM
1. AIR HANDLING UNIT AHU-3
a. GENERAL
1. AHU-3 IS A SINGLE ZONE DRAW THRU AIR HANDLING UNIT WITH A HOT WATER
HEATING COIL, FACE AND BYPASS DAMPERS, CHILLED WATER COOLING COIL,
ELECTRIC HUMIDIFIER AND OUTDOOR AIR DAMPER.
2. DDC CONTROLLER SHALL PROVIDE AHU-3 CONTROL FUNCTIONS. CONTROLLER
SHALL ACCEPT ANALOG INPUTS FROM ELECTRONIC SENSORS OR BINARY INPUTS
FROM CONTACT CLOSURES. CONTROLLER PROVIDES ANALOG OUTPUTS TO THE
VALVE AND DAMPER ACTUATORS. BINARY OUTPUTS ARE PROVIDED FOR STARTING
AND STOPPING OF FANS AND RELATED SYSTEM DEVICES.
b. STARTING/STOPPING SEQUENCE
1. AHU-3 SUPPLY FAN IS STARTED AND STOPPED FROM THE DDC SYSTEM AND SHALL
RUN CONTINUOUSLY DURING THE DAY CYCLE TO MAINTAIN A SPACE SET POINT OF
75 DEG. F. (ADJ.) DURING THE OCCUPIED SUMMER OPERATION AND 70 DEG. F. (ADJ.)
DURING THE OCCUPIED WINTER OPERATION. THIS IS BASED ON USER PREDEFINED
SCHEDULE.
2. DAY-AUTO-NIGHT SWITCH AT OPERATOR WORKSTATION SHALL OVERRIDE THE DDC
SYSTEM TIME CLOCK AND RETURN SYSTEM TO DAY OR NIGHT CYCLE IF DESIRED.
3. AUTO-OFF SPEED SWITCH AT OPERATOR WORKSTATION SHALL DETERMINE AHU-3
SYSTEM OPERATION.
4. ON NIGHT CYCLE ONLY CHANGE IS OA MD D-1 CLOSES. ROOM TEMPERATURE AND
HUMIDITY SETPOINTS SHALL REMAIN THE SAME DURING DAY AND NIGHT CYCLES.
c. HEATING SEQUENCE
1. ON A CALL FOR HEATING, SPACE SENSOR T-1 SHALL MODULATE 2-WAY HEATING COIL
VALVE V-3 OPEN AND F&BP MD D-2 OPEN TO FACE TO MAINTAIN SPACE
TEMPERATURE.
2. WHEN OA TEMPERATURE FALLS BELOW 40 DEG. F. (ADJ.) V-3 SHALL REMAIN 100%
OPEN AND THE F&BP MD D-2 SHALL MODULATE OPEN OR CLOSED TO MAINTAIN
SPACE TEMPERATURE.
3. LOW LIMIT DISCHARGE SENSOR TS-2 SHALL PREVENT TEMPERATURE FROM FALLING
BELOW 50 DEG. F. (ADJ.).
d. COOLING SEQUENCE
1. WHEN CHILLED WATER COOLING IS AVAILABLE, A CALL FOR COOLING FROM SPACE
SENSOR T-1 SHALL MODULATE THE 3-WAY COOLING VALVE V-3A TO MAINTAIN SPACE
TEMPERATURE. F&BP MD D-2 SHALL REMAIN OPEN TO THE COIL FACE.
2. HEATING VALVE V-3 SHALL REMAIN CLOSED.
e. HUMIDIFIER SEQUENCE
1. ELECTRIC HUMIDIFIER H-3 SHALL BE FURNISHED BY MECHANICAL CONTRACTOR.
SPACE HUMIDITY SENSOR H-1 IS USED FOR CONTROL. IT SHALL PROVIDE HUMIDITY
INDICATION TO THE DDC SYSTEM AND OPERATOR WORKSTATION. ROOM HUMIDITY IS
TO BE MAINTAINED AT 50% (ADJ.) WHENEVER OA TEMPERATURE IS BLOW 65 DEG. F.
(ADJ.) WHEN OA TEMPERATURE IS ABOVE 65 DEG. F. (ADJ.) AND CHILLED WATER IS
AVAILABLE, THE HUMIDIFIER SHALL NOT OPERATE UNTIL HUMIDITY DROPS TO 45%
(ADJ.), AT WHICH TIME THE HUMIDIFIER SHALL BE REACTIVATED. DUCT HUMIDITY
SENSOR SHALL BE USED TO CONTROL THE DUCT RELATIVE HUMIDITY NOT TO
EXCEED 75% (ADJ.).
f. INTERLOCK/SAFETY SEQUENCE
1. EXISTING SMOKE DETECTOR SHALL STOP SUPPLY FAN WHEN SMOKE IS DETECTED.
2. FREEZE STAT T-2, MANUAL RESET, SHALL STOP SUPPLY FAN WHEN TEMPERATURE
FALLS BELOW ITS SETTING.
3. OA MD D-1 SHALL CLOSE DURING NIGHT CYCLE OR ANYTIME FAN STOPS.
4. CHILLED WATER COIL 3-WAY V-3A SHALL GO TO FULL COIL BYPASS WHEN SUPPLY
FAN STOPS.
5. MIXED AIR SENSOR TS-3 SHALL PROVIDE TEMPERATURE INDICATION TO THE DDC
SYSTEM.
6. DIFFERENTIAL PRESSURE SWITCH DP-1 SHALL PROVIDE FAN INTERLOCKS AND “FAN
ON” INDICATION AT OPERATOR WORKSTATION.
7. HUMIDIFIER H-3 PARALLEL INTERLOCK SHALL PROVIDE “HUMIDIFIER H-3 ON”
INDICATION AT OPERATOR WORKSTATION.
8. ROOM SENSOR T-1 SHALL ALSO PROVIDE TEMPERATURE INDICATION AT OPERATOR
WORKSTATION.
9. UNIT SHALL SHUT DOWN UPON RECEIVING SIGNAL FROM FIRE ALARM CONTROL
PANEL.
FOR GUIDANCE ONLY. POINTS INDICATED ARE MINIMUM NUMBER OF POINTS. TEMPERATURE CONTROL CONTRACTOR IS RESPONSIBLE FOR PROVIDING ADDITIONAL POINTS AS NEEDED TO COMPLY WITH THE SEQUENCE OF OPERATION AND THE
DESIGN INTENT.
Duct Humidity Level x x x
Fan Runtime Exceeded x x
Fan in Hand x x
Fan Failure x x
Low Discharge Air Temp x x
High Dischargbe Air Temp x x
Filter Change Required x x
Low Zone Temp x x
High Zone Temp x x
Heating Setpoint x x
Cooling Setpoint x x
Schedule x
Emergency Shutdown x x x x
Return Air Damper x x x
Outside Air Damper x x x
Supply Fan Status x x x
Smoke Detector x x x x
Freezestat x x x x
Zone Override x x x
Heating Valve x x x
Cooling Valve x x x
Face and Bypass Dampers x x x
Mixed Air Humidity x x x
Zone Humidity x x x
Discharge Air Temp x x x
Fan Differential Pressure x x x
Zone Setpoint Adjust x x x
Zone Temp x x x
NORA
OA
NC
NO
C
C
TS-2
CHWR CHWS
SA
D4
D1
D2
TS-3
V-4A
SF
H
C
HWS HWR
V-4
EA
EF-4
EF
MOTOR
D5
EA
EF-4A
EF
MOTOR
D3
AIR HANDLING UNIT 4
AO - RETURN AIR DAMPER
BI - RETURN AIR DAMPER STATUS
AO - OUTSIDE AIR DAMPER
BI - OUTSIDE AIR DAMPER STATUS
AI - MIXED AIR TEMP
AO - FACE & BYPASS DAMPER
BI - F&BP DAMPER STATUS
AO - COOLING VALVE
M AO - HEATING VALVE
M
T-2
BI - FREEZE STAT
DP-1
AI - FAN DIFFERENTIAL PRESSURE
M CT
BI - FAN STATUS
BO - FAN START/STOP
AI - DISCHARGE AIR TEMP
T-1
AI - ZONE SETPOINT ADJUST
AI - ZONE TEMP
BI - ZONE OVERRIDE
BI - FAN STATUS
BO - FAN START/STOP
M
CT
BI - FAN STATUS
BO - FAN START/STOP
M
CT
AO - EXHAUST AIR DAMPER
BI - EXHAUST AIR DAMPER STATUS
AO - EXHAUST AIR DAMPER
BI - EXHAUST AIR DAMPER STATUS
EF - 4, 4A
CO2
AI - CO2 SENSOR2
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
G
H
I
J
K
1 2 3 4 5 6 7 8 9 10
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/1
/2
:2 :2
P
M M1.4
CONTROLS DIAGRAM
EPH
JMG
4-20-015
HVAC CONTROLS
UPGRADE
ILLINOIS DEPT. OF NATURAL
RESOURCES
LINCOLN'S NEW SALEM
HISTORIC SITE VISITORS
CENTER - 15588 HISTORY LN,
PETERSBERG, IL 62675
9/15/2020
9/15/2020
BID SET
EPH, JMG
KEYNOTES
1 THERMOSTAT LOCATION IS CALLED OUT ON SHEET M3.1. THERMOSTAT IS TO BE
INSTALLED AT REMOVED PNEUMATIC THERMOSTAT HEIGHT AND LOCATION.
2 NEW CO2 SENSOR. FURNISHED, INSTALLED AND WIRED BY CONTROLS
CONTRACTOR.
SCALE: NOT TO SCALE
AHU-4, EF-4, EF-4A CONTROL DIAGRAM
1. AIR HANDLING UNIT AHU-4
a. GENERAL
1. AHU-4 IS A SINGLE ZONE DRAW THRU AIR HANDLING UNIT WITH A HOT WATER
HEATING COIL, FACE AND BYPASS DAMPERS, CHILLED WATER COOLING COIL, AND
OUTDOOR, RETURN AND RELIEF AIR DAMPERS. (EF-4A)
2. DDC CONTROLLER SHALL PROVIDE AHU-4 CONTROL FUNCTIONS. CONTROLLER
SHALL ACCEPT ANALOG INPUTS FROM ELECTRONIC SENSORS OR BINARY INPUTS
FROM CONTACT CLOSURES. CONTROLLER PROVIDES ANALOG OUTPUTS TO THE
VALVE AND DAMPER ACTUATORS. BINARY OUTPUTS ARE PROVIDED FOR
STARTING AND STOPPING OF FANS AND RELATED SYSTEM DEVICES.
b. STARTING/STOPPING SEQUENCE
1. AHU-4 SUPPLY FAN IS STARTED AND STOPPED FROM THE DDC SYSTEM AND SHALL
RUN CONTINUOUSLY DURING DAY CYCLE TO MAINTAIN A SPACE SET POINT OF 75
DEG. F. (ADJ.) DURING THE OCCUPIED SUMMER OPERATION AND 70 DEG. F. (ADJ.)
DURING THE OCCUPIED WINTER OPERATION. IT SHALL CYCLE TO MAINTAIN A
REDUCED SETTING ON NIGHT CYCLE TO MAINTAIN A SPACE SET POINT OF 80 DEG.
F. (ADJ.) DURING THE UNOCCUPIED SUMMER OPERATION AND 65 DEG. F. (ADJ.)
DURING THE UNOCCUPPIED WINTER OPERATION. THIS IS BASED ON USER
PREDEFINED SCHEDULE.
2. EF-4 SHALL RUN WHEN AHU-4 RUNS ON DAY CYCLE IF VENTILATION CONTACT
CLOSURE AT OPERATOR WORKSTATION IS SET BEYOND ZERO. EF-4 SHALL REMAIN
OFF DURING NIGHT CYCLE.
3. EF-4A IS STARTED AND STOPPED FROM THE DDC SYSTEM AND SHALL BE ENABLED
TO RUN WHENEVER AHU-4 RUNS OF DAY CYCLE AND REMAIN OFF DURING NIGHT
CYCLE. (SEE MIXED AIR/ECONOMIZER SEQUENCE BELOW).
4. DAY-AUTO-NIGHT SWITCH AT OPERATOR WORKSTATION SHALL OVERRIDE THE
DDC SYSTEM TIME CLOCK AND RETURN SYSTEM TO DAY OR NIGHT CYCLE IF
DESIRED.
5. DDC CONTROL PROGRAM AT OPERATOR WORKSTATION SHALL DETERMINE
AHU-4/EF-4A SYSTEM OPERATION.
c. WARM-UP SEQUENCE
1. WHEN SYSTEM IS CHANGED FROM NIGHT TO DAY CYCLE, OA MD D-1 SHALL DELAY
OPENING UNTIL AREA REACHED DAY TEMPERATURE SETTING AT WHICH TIME THE
OA MD D-1 SHALL OPEN TO A 30% (ADJ.) MINIMUM POSITION. THE REL A MD D-3
SHALL FOLLOW THE OA MD EXCEPT THEY SHALL DELAY OPENING BY 20% (ADJ.).
THE RA MD D-2 SHALL CLOSE IN OPPOSITE PROPORTION TO THE OA MD.
d. MIXED AIR/ECONOMIZER SEQUENCE
1. THE CONTROLLER SHALL MEASURE THE MIXED AIR TEMPERATURE AND
MODULATE THE ECONOMIZER DAMPERS IN SEQUENCE TO MAINTAIN A SETPOINT 2
DEG. F. (ADJ.) LESS THAN THE SUPPLY AIR TEMPERATURE SETPOINT. THE OUTSIDE
AIR DAMPERS SHALL MAINTAIN A MINIMUM ADJUSTABLE POSITION OF 20% (ADJ.)
OPEN WHENEVER OCCUPIED.
THE ECONOMIZER SHALL BE ENABLED WHENEVER:
- OUTSIDE AIR TEMPERATURE IS LESS THAN 65 DEG. F. (ADJ.).
- AND THE OUTSIDE AIR TEMPERATURE IS LESS THAN THE RETURN AIR
TEMPERATURE.
- AND THE SUPPLY FAN STATUS IS ON.
THE ECONOMIZER SHALL CLOSE WHENEVER:
- MIXED AIR TEMPERATURE DROPS FROM 40 DEG. F. TO 35 DEG. F. (ADJ.).
- OR THE FREEZESTAT (IF PRESENT) IS ON.
- OR ON LOSS OF SUPPLY FAN STATUS.
THE OUTSIDE AND EXHAUST AIR DAMPERS SHALL CLOSE AND THE RETURN AIR
DAMPER SHALL OPEN WHEN THE UNIT IS OFF. IF OPTIMAL START UP IS AVAILABLE
THE MIXED AIR DAMPER SHALL OPERATE AS DESCRIBED IN THE OCCUPIED MODE
EXCEPT THAT THE OUTSIDE AIR DAMPER SHALL MODULATE TO FULLY CLOSED.
2. MIXED AIR LOW LIMIT SENSOR TS-3 SHALL PREVENT TEMPERATURE FROM FALLING
BELOW 50 DEG. F. (ADJ.).
3. EXHAUST FAN EF-4A SHALL SEQUENCE FROM OF TO LOW TO HIGHT SPEED AS REL
A MD D-3 MODULATES OPEN.
e. MINIMUM OUTSIDE AIR VENTILATION - CARBON DIOXIDE (CO2) CONTROL
1. WHEN IN THE OCCUPIED MODE, THE CONTROLLER SHALL MEASURE THE RETURN
AIR CO2 LEVELS AND MODULATE THE OUTSIDE AIR DAMPERS OPEN FROM THE
MINIMUM OPEN POSITION TO DELIVER MINIMUM VENTILATION AIRFLOW AS
DETERMINED BY THE TEST AND BALANCE CONTRACTOR ON RISING CO2
CONCENTRATIONS, OVERRIDING NORMAL DAMPER OPERATION TO MAINTAIN A
CO2 SET POINT OF 750 PPM (ADJ.).
f. HEATING SEQUENCE
1. ON A CALL FOR HEATING, SPACE SENSOR T-1 SHALL MODULATE HEATING COIL 2-
WAY VALVE V-4 OPEN TO COIL AND F&BP MD D-4 OPEN TO COIL FACE TO MAINTAIN
SPACE TEMPERATURE.
2. WHEN OA TEMPERATURE FALLS BELOW 40 DEG. F. (ADJ.) V-2 SHALL REMAIN OPEN
AND THE F&BP MD D-4 SHALL MODULATE OPEN OR CLOSED TO MAINTAIN SPACE
TEMPERATURE.
3. LOW LIMIT DISCHARGE SENSOR TS-2 WILL PREVENT TEMPERATURE FROM
FALLING BELOW 50 DEG. F. (ADJ.).
g. COOLING SEQUENCE
1. WHEN CHILLED WATER COOLING IS AVAILABLE, A CALL FOR COOLING FROM
SPACE SENSOR T-1 SHALL MODULATE THE 3-WAY COOLING VALVE V-4A TO
MAINTAIN SPACE TEMPERATURE. F&BP MD D-4 SHALL REMAIN OPEN TO THE COIL
FACE.
2. HEATING VALVE V-4 SHALL REMAIN CLOSED.
h. INTERLOCK/SAFETY SEQUENCE
1. EXISTING SMOKE DETECTORS SHALL STOP SUPPLY FAN WHEN SMOKE IS
DETECTED.
2. FREEZESTAT T-2, MANUAL RESET, SHALL STOP SUPPLY FAN WHEN TEMPERATURE
FALLS BELOW ITS SETTING.
3. OA AND REL A MD SHALL CLOSE AND RA MD SHALL OPEN DURING NIGHT CYCLE
OR ANYTIME FAN STOPS.
4. CHILLED WATER COIL 3-WAY CALCE V-4A SHALL GO TO FULL COIL BYPASS WHEN
SUPPLY FAN STOPS.
5. DIFFERENTIAL PRESSURE SWITCH DP-1 SHALL PROVIDE FAN INTERLOCKS AND
“FAN ON" INDICATION AT OPERATOR WORKSTATION.
6. ROOM SENSOR T-1 SHALL ALSO PROVIDE TEMPERATURE INDICATION AT
OPERATOR WORKSTATION.
7. UNIT SHALL SHUT DOWN UPON RECEIVING SIGNAL FROM FIRE ALARM CONTROL
PANEL.
FOR GUIDANCE ONLY. POINTS INDICATED ARE MINIMUM NUMBER OF POINTS. TEMPERATURE CONTROL CONTRACTOR IS RESPONSIBLE FOR PROVIDING ADDITIONAL POINTS AS NEEDED TO COMPLY WITH THE SEQUENCE OF OPERATION AND THE
DESIGN INTENT.
Fan in Hand x x
Fan Failure x x
Exhaust Air Damper in Hand x x
Exhaust Air Damper Failure x x
Schedule x
Exhaust Air Damper x x x
Fan Start/Stop x x x
Fan Status x x x
Exhaust Air Damper Status x x x
POINT NAME AI AO BI BO AV BV Loop Sched Trend Alarm Show on Graphic
HARDWARE POINTS SOFTWARE POINTS
FOR GUIDANCE ONLY. POINTS INDICATED ARE MINIMUM NUMBER OF POINTS. TEMPERATURE CONTROL CONTRACTOR IS RESPONSIBLE FOR PROVIDING ADDITIONAL POINTS AS NEEDED TO COMPLY WITH THE SEQUENCE OF OPERATION AND THE
DESIGN INTENT.
Fan Runtime Exceeded x x
Fan in Hand x x
Fan Failure x x
Low Discharge Air Temp x x
High Dischargbe Air Temp x x
Filter Change Required x x
Low Zone Temp x x
High Zone Temp x x
Heating Setpoint x x
Cooling Setpoint x x
Schedule x
Emergency Shutdown x x x x
Return Air Damper x x x
Outside Air Damper x x x
Supply Fan Status x x x
Smoke Detector x x x x
Freezestat x x x x
Zone Override x x x
Heating Valve x x x
Cooling Valve x x x
Face and Bypass Dampers x x x
CO2 Level x x x
Discharge Air Temp x x x
Fan Differential Pressure x x x
Zone Setpoint Adjust x x x
Zone Temp x x x
P-2
CHWS
TS-3
TS-4
CHWR
FS-2
CHILLER
CHILLER
THIS CHILLER INTERFACE SCHEMATIC MAY
NOT REFLECT THE ACTUAL SENSORS AND
POINTS AS SUPPLIED BY THE CHILLER
MANUFACTURER. ALL INTERFACE POINTS
SHALL BE COORDINATED WITH THE CHILLER
SUPPLIER.
CHILLER
BV - CHILLER STATUS
AV - CHILLER KW
AV - OPERATING HOURS
AV - CHILLED WATER SUPPLY TEMP SETPOINT
AV - OIL DIFFERENTIAL PRESSURE
AV - OIL TEMP
AV - CONDENSER REFRIGERANT PRESSURE
AV - EVAPORATOR REFRIGERANT PRESSURE
AV - CHILLED WATER SUPPLY TEMP
T
BI - CHILLED WATER FLOW STATUS
AV - CHILLED WATER RETURN TEMP
T
M
CT
BI - CHILLED WATER PUMP 1 STATUS
BO - CHILLED WATER PUMP 1 START/STOP
CHILLER PUMP
V-13
IN
OUT
BOILER
TS-2
TS-1
P-1
P-1A
HWS
HWR
TS-5
D1
D2
COMBUSTION AIR
COMBUSTION AIR
FS-1
BOILER / WATER HEATER
COMBUSTION AIR DAMPERS
THIS BOILER INTERFACE SCHEMATIC MAY NOT
REFLECT THE ACTUAL SENSORS AND POINTS
AS SUPPLIED BY THE BOILER
MANUFACTURER. ALL INTERFACE POINTS
SHALL BE COORDINATED WITH THE BOILER
SUPPLIER.
T
AV - HOT WATER SUPPLY TEMP
BI - HOT WATER FLOW STATUS
T
AV - HOT WATER RETURN TEMP
AO - BYPASS VALVE
M
BOILER
AV - OPERATING TEMP
AV - OPERATING PRESSURE
BV - BOILER STATUS
AV - BURNER CYCLES
AV - OPERATING HOURS
AV - HOT WATER SUPPLY TEMP SETPOINT
AI - OUTSIDE AIR TEMP
M
CT
BI - HOT WATER PUMP 1 STATUS
BO - HOT WATER PUMP 1 START/STOP
BI - HOT WATER PUMP 2 STATUS
BO - HOT WATER PUMP 2 START/STOP
M
CT
HOT WATER LOOP PUMPS
AO - OUTSIDE AIR DAMPER
BI - OUTSIDE AIR DAMPER STATUS
AO - OUTSIDE AIR DAMPER
BI - OUTSIDE AIR DAMPER STATUS
WATER HEATER
FS-2
BI - BOILER HOT WATER FLOW
EA
EF-12
EF
MOTOR
D3
EF-12
BI - FAN STATUS
BO - FAN START/STOP
M
CT
BO - EXHAUST AIR DAMPER
BI - EXHAUST AIR DAMPER STATUS
T-1
AI - ZONE SETPOINT ADJUST
AI - ZONE TEMP
BI - ZONE OVERRIDE
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
G
H
I
J
K
1 2 3 4 5 6 7 8 9 10
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/1
/2
:2 :2
P
M M1.5
CONTROLS DIAGRAM
EPH
JMG
4-20-015
HVAC CONTROLS
UPGRADE
ILLINOIS DEPT. OF NATURAL
RESOURCES
LINCOLN'S NEW SALEM
HISTORIC SITE VISITORS
CENTER - 15588 HISTORY LN,
PETERSBERG, IL 62675
9/15/2020
9/15/2020
BID SET
EPH, JMG
SCALE: NOT TO SCALE
CHILLER CONTROL DIAGRAM
a. GENERAL
1. DDC CONTOLLER SHALL PROVIDE HOT/CHILLED WATER SYSTEM CONTROL
FUNCTIONS. CONTROLLER SHALL ACCEPT ANALOG INPUTS FROM
ELECTRONIC SENSORS OR BINARY INPUTS FROM CONTACT CLOSURES.
CONTROLLER PROVIDES ANALOG OUTPUTS TO VALVE OR DAMPER
ACTUATORS. BINARY OUTPUTS ARE PROVIDED FROM STARTING AND
STOPPING OF BOILER, CHILLER, PUMPS AND RELATED SYSTEM DEVICES.
FOR GUIDANCE ONLY. POINTS INDICATED ARE MINIMUM NUMBER OF POINTS. TEMPERATURE CONTROL CONTRACTOR IS RESPONSIBLE FOR PROVIDING ADDITIONAL POINTS AS NEEDED TO COMPLY WITH THE SEQUENCE OF OPERATION AND THE
DESIGN INTENT.
Fan in Hand x x
Fan Failure x x
Exhaust Air Damper in Hand x x
Exhaust Air Damper Failure x x
Schedule x
Exhaust Air Damper x x x
Fan Start/Stop x x x
Fan Status x x x
Exhaust Air Damper Status x x x
POINT NAME AI AO BI BO AV BV Loop Sched Trend Alarm Show on Graphic
HARDWARE POINTS SOFTWARE POINTS
FOR GUIDANCE ONLY. POINTS INDICATED ARE MINIMUM NUMBER OF POINTS. TEMPERATURE CONTROL CONTRACTOR IS RESPONSIBLE FOR PROVIDING ADDITIONAL POINTS AS NEEDED TO COMPLY WITH THE SEQUENCE OF OPERATION AND THE
DESIGN INTENT.
Hot Water Flow Status x x x
Boiler Status x x x
Hot Water Return Temp x x x
Hot Water Supply Temp x x x
Hot Water Supply Temp Setpoint x x x
Operating Temp x x x
Operating Pressure x x x
Operating Hours x x
Burner Cycles x x
Water Heater OA Damper Status x
Boiler OA Damper Status x
Water Heater OA Damper x
Boiler OA Damper x
Outside Air Temp x
POINT NAME AI AO BI BO AV BV Loop Sched Trend Alarm Show on Graphic
HARDWARE POINTS SOFTWARE POINTS
FOR GUIDANCE ONLY. POINTS INDICATED ARE MINIMUM NUMBER OF POINTS. TEMPERATURE CONTROL CONTRACTOR IS RESPONSIBLE FOR PROVIDING ADDITIONAL POINTS AS NEEDED TO COMPLY WITH THE SEQUENCE OF OPERATION AND THE
DESIGN INTENT.
Low Hot Water Supply Temp x x
High Hot Water Supply Temp x x
Hot Water Pump 1A Runtime Exceeded x x
Hot Water Pump 1 Runtime Exceeded x x
Hot Water Pump 1A Running in Hand x x
Hot Water Pump 1 Running in Hand x x
Hot Water Pump 1A Failure x x
Hot Water Pump 1 Failure x x
Boiler Hot Water Flow x x x
Hot Water Flow Status x x x
Outside Air Temp x x
Hot Water Pump 1A Start/Stop x x x
Hot Water Pump 1 Start/Stop x x x
Hot Water Pump 1A Status x x x
Hot Water Pump 1 Status x x x
Hot Water Supply Temp x x x
Hot Water Return Temp x x x
POINT NAME AI AO BI BO AV BV Loop Sched Trend Alarm Show on Graphic
HARDWARE POINTS SOFTWARE POINTS
FOR GUIDANCE ONLY. POINTS INDICATED ARE MINIMUM NUMBER OF POINTS. TEMPERATURE CONTROL CONTRACTOR IS RESPONSIBLE FOR PROVIDING ADDITIONAL POINTS AS NEEDED TO COMPLY WITH THE SEQUENCE OF OPERATION AND THE
DESIGN INTENT.
Condenser Water Flow Status x x x
Chilled Water Flow Status x x x
Chiller Status x x x
Oil Temp x x x
Oil Differential Pressure x x x
Condenser Refrigerant Pressure x x x
Evaporator Refrigerant Pressure x x x
Condenser Water Return Temp x x x
Condenser Water Supply Temp x x x
Chilled Water Return Temp x x x
Chilled Water Supply Temp x x x
Operating Hours x x x
Chilled Water Supply Temp Setpoint x x x
Chiller kW x x x
POINT NAME AI AO BI BO AV BV Loop Sched Trend Alarm Show on Graphic
HARDWARE POINTS SOFTWARE POINTS
FOR GUIDANCE ONLY. POINTS INDICATED ARE MINIMUM NUMBER OF POINTS. TEMPERATURE CONTROL CONTRACTOR IS RESPONSIBLE FOR PROVIDING ADDITIONAL POINTS AS NEEDED TO COMPLY WITH THE SEQUENCE OF OPERATION AND THE
DESIGN INTENT.
Low Chilled Water Supply Temp x x
High Chilled Water Supply Temp x x
Chilled Water Pump 2 Runtime Exceeded x x
Chilled Water Pump 2 Running in Hand x x
Chilled Water Pump 2 Failure x x
Outside Air Temp x x
Chilled Water Pump 2 Start/Stop x x x
Chilled Water Pump 2 Status x x x
Chilled Water Return Temp x x x
Chilled Water Supply Temp x x x
POINT NAME AI AO BI BO AV BV Loop Sched Trend Alarm Show on Graphic
HARDWARE POINTS SOFTWARE POINTS
GENERAL NOTES
SCALE: NOT TO SCALE
BOILER, WATER HEATER, CA DAMPERS
CONTROL DIAGRAM
SCALE: NOT TO SCALE
EF-12 CONTROL DIAGRAM
a. EXHAUST FAN EF-12
1. 2 STAGE ROOM MECHANICAL ROOM THERMOSTAT T-1 SHALL SEQUENCE
EF-12 FROM OFF TO LOW TO HIGH AS SPACE TEMPERATURE INCREASES.
EF-12 MD D-3 AND BOTH COMBUSTION AIR MD D-1, 2 SHALL OPEN WHEN
FAN RUNS AND CLOSE WHEN FAN STOPS.
SEQUENCE OF OPERATION EF-12
a. CHILLER CH-1/ CHILLED WATER SYSTEM CONTROL
1. CHILLER IS CONTROLLED WITH ITS ON BOARD ORIGINAL EQUIPMENT
MANUFACTURER CONTROLLER. NEW BUILDING AUTOMATION SYSTEM
SHALL PROVIDE THE NECESSARY INTERFACE AS FOLLOWS TO ENABLE
AND DISABLE THE OPERATION OF THE EQUIPMENT AND PROVIDE ALARMS
AS SPECIFIED AT THE OPERATOR WORK STATION.
2. BAS SHALL DISABLE THE OPERATION OF THE CHILLER WHEN OA TEMP.
FALLS BELOW 55 DEG. F. (ADJ.).
3. CHILLER/CHW PUMP P-2 INTERLOCK WIRING SHALL BE PROVIDED BY
CONTRACTOR.
4. FS-2 FLOW SWITCH SHALL PREVENT CHILLER FROM OPERATING UNLESS
P-2 IS RUNNING.
5. CHILLER CH-1 IS ENABLED ANYTIME CHW PUMP P-2 RUNS.
6. CHW PUMP P-2 SHALL START ANYTIME AHU-1, 2, 3, 4 CHWS VALVES ARE
OPEN OVER 20% (ADJ.).
7. P-2 WILL NOT BE ALLOWED TO RUN IF OA TEMPERATURE IS LESS THAN 55
DEG. F. (ADJ.).
8. CHWS AND CHWR SENSORS TS-3, 4 SHALL PROVIDE TEMPERATURE
INDICATION TO DDC SYSTEM.
9. CHILLER INTERLOCK SHALL ALSO PROVIDE “CHILLER ON” INDICATION AT
OPERATOR WORKSTATION.
SEQUENCE OF OPERATION CHILLER
a. COMBUSTIONS AIR MOTORIZED DAMPERS
1. COMBUSTION AIR MD D-1 (BOILER) AND D-2 (WATER HEATER) SHALL BOTH
OPEN WHENEVER EITHER BURNER FIRES OR WHEN “OPEN-AUTO” IS
INDICATED “OPEN” AT OPERATOR WORKSTATION. WHEN DAMPERS ARE
CLOSED THEY SHALL STILL REMAIN OPEN 5% (ADJ. 0-15%). DAMPERS
SHALL CLOSE COMPLETELY IF BOILER FUEL BURNER SHUTS DOWN ON
SAFETY CONTROL (TO PREVENT BOILER ROOM FREEZE-UP). D-1 END
SWITCH SHALL CLOSE TO PROVE DAMPER IS OPEN BEFORE ALLOWING
BOILER TO COMPLETE ITS FIRING CIRCUIT.
a. BOILER B-1 / HOT WATER SYSTEM TEMPERATURE CONTROL
1. BOILER IS CONTROLLED WITH ITS ON BOARD ORIGINAL EQUIPMENT
MANUFACTURER CONTROLLER. NEW BUILDING AUTOMATION SYSTEM
SHALL PROVIDE THE NECESSARY INTERFACE AS FOLLOWS TO ENABLE
AND DISABLE THE OPERATION OF THE EQUIPMENT AND PROVIDE ALARMS
AS SPECIFIED AT THE OPERATOR WORK STATION
2. IMMERSION SENSOR TS-1 AND OUTDOOR SENSOR TS-5 SHALL RESET THE
HWS TEMPERATURE FROM 200 DEG. F. (ADJ.) TO 160 DEG. F (ADJ.) AS
OUTDOOR TEMPERATURE RISES FROM -10 DEG. F. (ADJ.) TO 70 DEG. F.
(ADJ.) BY MODULATING 3-WAY VALVE V-13 (FAIL SAFE IN FULL HEAT
POSITION).
3. AQUASTAT IN BOILER WILL CONTROL BOILER WATER TEMPERATURE AT
200 DEG. F. (ADJ.) CONSTANT.
4. FLOW SWITCH FS-2 SHALL PREVENT BOILER OPERATION UNLESS HW
PUMP. P-1 OR P-1A ARE OPERATING AND FLOW IS PROVEN BY FS-2.
5. BOILER AND PUMPS SHALL STOP WHEN OUTDOOR TEMPERATURE RISES
ABOVE 60 DEG. F. (ADJ.), (P-1A IS STANDBY).
6. HWR SENSOR TS-2 PROVIDES TEMPERATURE INDICTION TO THE DDC
SYSTEM.
7. OUTDOOR SENSOR TS-5 ALSO PROVIDES TEMPERATURE INDICATION AT
OPERATOR WORKSTATION.
8. BAS SHALL ISSUE AN ALARM AT OPERATOR WORKSTATION WHEN HOT
WATER PUMPS P-1, P-1A ARE COMMANDED ON AND FLOW IS NOT PROVEN
BY FS-1.
SEQUENCE OF OPERATION BOILER, WATER HEATER, CA DAMPERS
V-8, 9, 10 (UH-2, 3, 4)
H
C
FAN
V-11
H C
FAN
H
C
FAN
C
C
V-5A, 6A V-5, 6
HWS
HWSHWRCHWS
CHWR
H
C
V-7
HWSHWR
UH
MOTOR
UNIT HEATER-2, 3, 4 CABINET UNIT HEATER-5
PROPELLER UNIT HEATER-1
FAN COIL UNIT- 5, 6
T-1
AI - ZONE SETPOINT ADJUST
AI - ZONE TEMP
BI - ZONE OVERRIDE
M
CT
BI - FAN STATUS
BO - FAN START/STOP
AO - COOLING VALVE
M
AO - HEATING VALVE
M
AO - HEATING VALVE
M
T-1
AI - ZONE SETPOINT ADJUST
AI - ZONE TEMP
BI - ZONE OVERRIDE
M
CT
BI - FAN STATUS
BO - FAN START/STOP
M
CT
BI - FAN STATUS
BO - FAN START/STOP
T-1
AI - ZONE SETPOINT ADJUST
AI - ZONE TEMP
BI - ZONE OVERRIDE
AO - HEATING VALVE
M
T-2
AI - ZONE SETPOINT ADJUST
AI - ZONE TEMP
BI - ZONE OVERRIDE
AO - HEATING VALVE
M
M
CT
BI - FAN STATUS
BO - FAN START/STOP
PLAN NOTES
1. 115/1 BY EC.
2. 24/60 BY ECC.
3. SERVER.
4. OPERATOR WORK STATION (BY
ECC).
5. PROVIDE PROPER NUMBER OF
SUPERVISORY CONTROLLERS TO
ACCOMMODATE QUANTITY OF
FIELD LEVEL CONTROLLERS.
CAPACITY SHALL INCLUDE
EXPANSION FOR FUTURE. ECC
SHALL COORDINATE AND PROVIDE
ELECTRICAL POWER AND
NETWORK ACCESS TO ALL
SUPERVISORY CONTROLLERS.
6. OPERATOR WORKSTATION SHALL
BE LOCATED IN ROOM 022 -
MAINTENANCE OFFICE AREA.
COORDINATE WITH OWNER FOR
EXACT LOCATION.
7. EXISTING 115/1.
CHILLER
CONTROLLER
DDC
AHU-3
DDC
AHU-2
DDC
AHU-1
DDC
FCU DDC
ETHERNET
SWITCH
SUPERVISORY
NETWORK
CONTROLLER
SERVER
TO OWNERS
INTRANET
ETHERNET
INTERNET
CONNECTION
FIREWALL
FIELD LEVEL
NETWORK BY ECC
I/P
ETHERNET
I/P
I/P
I/P
PRT
LAN CONNECTION BY OWNER'S
IT PROVIDER-TYPICAL PER
SUPERVISORY CONTROLLER
EF-X
DDC
UH-X
DDC
AHU-4
DDC
HEATING PUMPS
CONTROLLER
DDC
COOLING PUMPS
CONTROLLER
DDC
SEWER PUMP
CONTROLLER
DDC
BOILER
CONTROLLER
DDC
M
CT
BI - SEWER EJECTOR PUMP ON
SEWER EJECTOR PUMP
BI -HIGH LEVEL ALARM
LEVEL MONITOR
BI - LOW LEVEL ALARM
BI -HIGH LEVEL ALARM
FIRE PROTECTION WATER TANK
TANK
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
G
H
I
J
K
1 2 3 4 5 6 7 8 9 10
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/1
/2
:2 :2
P
M M1.6
CONTROLS DIAGRAM
EPH
JMG
4-20-015
HVAC CONTROLS
UPGRADE
ILLINOIS DEPT. OF NATURAL
RESOURCES
LINCOLN'S NEW SALEM
HISTORIC SITE VISITORS
CENTER - 15588 HISTORY LN,
PETERSBERG, IL 62675
9/15/2020
9/15/2020
BID SET
EPH, JMG
SCALE: NOT TO SCALE
UNIT HEATERS, FAN COIL UNITS
CONTROL DIAGRAM
1. SEWAGE EJECTOR PUMP
a. SEWAGE EJECTION PUMP OPERATION SHALL BE CONTROLLED BY
SEWER EJECTOR PUMP CONTROL PANEL. BAS SHALL MONITOR
THE OPERATION OF THE SEWAGE EJECTION PUMP AND TANK
LEVELS.
2. FIRE PROTECTION WATER STORAGE TANK
a. BAS SHALL ISSUE AN ALARM AT OPERATOR WORKSTATION WHEN
TANK LEVEL FALLS BELOW 80% (ADJ.) OF FULL CAPACITY.
FOR GUIDANCE ONLY. POINTS INDICATED ARE MINIMUM NUMBER OF POINTS. TEMPERATURE CONTROL CONTRACTOR IS RESPONSIBLE FOR PROVIDING ADDITIONAL POINTS AS NEEDED TO COMPLY WITH THE SEQUENCE OF OPERATION AND THE
DESIGN INTENT.
Fan Runtime Exceeded x
Fan in Hand x
Fan Failure x
Low Discharge Air Temp x
High Discharge Air Temp x
Filter Required x
Low Zone Temp x
High Zone Temp x
Cooling Setpoint x x
Heating Setpoint x x
Schedule x
Fan Start/Stop x x x
Fan Status x x
Zone Override x x x
Heating Valve x x x
Cooling Valve x x x
Zone Setpoint Adjust x x
Zone Temp x x x
POINT NAME AI AO BI BO AV BV Loop Sched Trend Alarm Show on Graphic
HARDWARE POINTS SOFTWARE POINTS
FOR GUIDANCE ONLY. POINTS INDICATED ARE MINIMUM NUMBER OF POINTS. TEMPERATURE CONTROL CONTRACTOR IS RESPONSIBLE FOR PROVIDING ADDITIONAL POINTS AS NEEDED TO COMPLY WITH THE SEQUENCE OF OPERATION AND THE
DESIGN INTENT.
Fan Runtime Exceeded x
Fan in Hand x
Fan Failure x
Low Zone Temp x
Heating Setpoint x x
Schedule x
Fan Start/Stop x
Fan Status x x x
Zone Override x x x
Heating Valve x x x
Zone Setpoint Adjust x x
Zone Temp x x x
POINT NAME AI AO BI BO AV BV Loop Sched Trend Alarm Show on Graphic
HARDWARE POINTS SOFTWARE POINTS
FOR GUIDANCE ONLY. POINTS INDICATED ARE MINIMUM NUMBER OF POINTS. TEMPERATURE CONTROL CONTRACTOR IS RESPONSIBLE FOR PROVIDING ADDITIONAL POINTS AS NEEDED TO COMPLY WITH THE SEQUENCE OF OPERATION AND THE
DESIGN INTENT.
Fan Runtime Exceeded x
Fan in Hand x
Fan Failure x
Low Zone Temp x
Heating Setpoint x x
Schedule x
Fan Start/Stop x
Fan Status x x x
Zone Override x x x
Heating Valve x x x
Zone Setpoint Adjust x x
Zone Temp x x x
POINT NAME AI AO BI BO AV BV Loop Sched Trend Alarm Show on Graphic
HARDWARE POINTS SOFTWARE POINTS
FOR GUIDANCE ONLY. POINTS INDICATED ARE MINIMUM NUMBER OF POINTS. TEMPERATURE CONTROL CONTRACTOR IS RESPONSIBLE FOR PROVIDING ADDITIONAL POINTS AS NEEDED TO COMPLY WITH THE SEQUENCE OF OPERATION AND THE
DESIGN INTENT.
Fan Runtime Exceeded x
Fan in Hand x
Fan Failure x
Low Zone Temp x
Heating Setpoint x x
Schedule x
Fan Start/Stop x
Fan Status x x x
Zone Override x x x
Heating Valve x x x
Zone Setpoint Adjust x x
Zone Temp x x x
POINT NAME AI AO BI BO AV BV Loop Sched Trend Alarm Show on Graphic
HARDWARE POINTS SOFTWARE POINTS
SCALE: NOT TO SCALE
BAS SYSTEM ARCHITECTURE
FOR GUIDANCE ONLY. POINTS INDICATED ARE MINIMUM NUMBER OF POINTS. TEMPERATURE CONTROL CONTRACTOR IS RESPONSIBLE FOR PROVIDING ADDITIONAL POINTS AS NEEDED TO COMPLY WITH THE SEQUENCE OF OPERATION AND THE
DESIGN INTENT.
High Level Alarm x x
Pump Status "On" / "Off" x x x
POINT NAME AI AO BI BO AV BV Loop Sched Trend Alarm Show on Graphic
HARDWARE POINTS SOFTWARE POINTS
FOR GUIDANCE ONLY. POINTS INDICATED ARE MINIMUM NUMBER OF POINTS. TEMPERATURE CONTROL CONTRACTOR IS RESPONSIBLE FOR PROVIDING ADDITIONAL POINTS AS NEEDED TO COMPLY WITH THE SEQUENCE OF OPERATION AND THE
DESIGN INTENT.
High Level Alarm x x
Low Level Alarm x x
POINT NAME AI AO BI BO AV BV Loop Sched Trend Alarm Show on Graphic
HARDWARE POINTS SOFTWARE POINTS
SEQUENCE OF OPERATION SEWAGE PUMP AND FIRE TANK
1. CABINET UNIT HEATER (UH-2, 3, 4, 5)
a. ROOM THERMOSTAT T-1 SHALL MODULATE 2-WAY HWS VALVE AND CYCLE FAN
IN SEQUENCE THRU CONTROLLER TO MAINTAIN SPACE TEMPERATURE. THE
UNITS SHALL MAINTAIN REDUCED SETTINGS DURING NIGHT CYCLE.
2. PROPELLER UNIT HEATER (UH-1)
a. ROOM THERMOSTAT T-2 SHALL MODULATE 2-WAY HWS VALVE AND CYCLE FAN
IN SEQUENCE THRU CONTROLLER “AUTO” TO MAINTAIN SPACE TEMPERATURE.
THE UH FAN WILL RUN CONTINUOUS IN THE “ON” POSITION.
3. FAN COIL UNIT (FC-5, 6)
a. ROOM THERMOSTAT T-1 SHALL MODULATE 2-WAY HWS & CHWS VALVES IN
SEQUENCE TO MAINTAIN SPACE TEMPERATURE. CONTROLLER SHALL CYCLE
FAN OPERATION DURING DAY CYCLE OR CYCLE THE FAN TO MAINTAIN A
REDUCED SETTING DURING NIGHT CYCLE.
SEQUENCE OF OPERATION UNIT HEATERS, FAN COIL UNITS
SCALE: NOT TO SCALE
SEWAGE PUMP AND FIRE TANK
CONTROL DIAGRAM
HUMIDIFIER SCHEDULE
MARK MANUFACTURER MODEL SERVICE
DISPERSION
SYSTEM TYPE
CAP…