W045--Boiler Rental

Closed Solicitation Posted

Solicitation number
36C24227Q0042
Agency
Responses due
Set-aside
No set-aside

Opportunity facts

Place of performance
Department of Veterans Affairs Franklin Delano Roosevelt Hospital Montrose, New York 10548, United States

Notice details come from SAM.gov. Updated .

About this opportunity

The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 2 seeks a temporary 800 HP fire-tube boiler rental with maintenance and repair services for VA Hudson Valley Healthcare System Montrose Campus, with quotations due October 21, 2026 at 2:00 PM Eastern Time. A mandatory site visit is scheduled October 19, 2026 at 10:00 AM at Franklin Delano Roosevelt Hospital, Building 16 Engineering Conference Room, 2094 Albany Post Road, Montrose, NY 10548.

Place of performance is Montrose, NY. The boiler must be installed by November 1, 2026 and ready for service by December 1, 2026, positioned on the east side of the plant near Building 24. Historical peak steam load is 120,000 lb./hr; the boiler must operate at 95 PSI with 35,000 lbs./hr steam capacity at 212°F and a maximum fuel input of 33,000,000 BTU/hr. The unit must operate on both natural gas and #2 oil without burner modifications, meeting a 9 PPM NOx emissions requirement (though a 30 PPM unit is acceptable as a temporary solution). The Government furnishes fuel; the vendor provides the boiler, installation, and all necessary connections including 3-inch gas piping, 1-inch oil piping, electrical service to a 250-amp breaker approximately 200 feet away, 10-inch insulated steam piping with welding and pressure testing, and 6-inch feedwater piping with heat tracing maintained at minimum 225°F. Monthly maintenance includes minimum 10 hours per month with weekly checkups, two internal inspection reports, and training for boiler plant personnel. All work must comply with ASME standards, NFPA codes, VA specifications, and the VHA Safety Device and Testing Manual. The rental period runs through March 31, 2027 with an option to extend if the VA's boiler repair project extends beyond the expected completion date. NAICS code is 238220; PSC is W045. Evaluation weighs technical capability at 40%, past performance with three relevant federal or commercial references at 30%, and price at 30%. This is not a small business set-aside.

Notice text

3 versions

Update #3 · Latest ·

36C24227Q0042 Mod 2

Answers to questions submitted:

Q1: What is the observed historical peak steam load of the facility?

A1: 120,000 lb./hr.

Q2: Will the Montrose VAMC waive the requirements of the VHA Safety Device and Testing Manual?

A2: No.

Q3: Air permits for emissions are the responsibility of the entity operating/generating the emission, not the owner of the equipment. Please clarify.

A3: VA only, not the vendor.

Q4: Will the VA change the 9PPM NOx requirement to 30 PPM?

A4: No.

Q5: Please clarify the size of the Boiler.

A5: 800 HP

Q6: Will fuel for the rental boiler be furnished by the Government of the Contractor?

A6: Government

Q7: Confirm intended placement and connection routing if boiler placement is on the south end but connections are at the north end?

A7: East side of the plant (end near Boiler 1 near Building 24 hazmat storage area)

Q8: What is the required installation and ready for service date?

A8: Installation 11/1/2026. Ready for service 12/1/2026.

Q9. Is a rental unit rated at about 30ppm NOx on natural gas acceptable for the temporary heating period, given that it is a temporary rental operating under the facility s existing permit?

A9. Yes

Q10. If 9 ppm NOx is mandatory, will the Government accept a unit fitted with flue gas recirculation (FGR) or selective catalytic reduction (SCR) to meet it, and will any additional time be allowed for delivery?

A10. The most important factor is that the vendor make the delivery date, so the 9-ppm cis is not a deal breaker.

Q11. The requirement lists a 95 PSIG operating pressure but also references 35,000 lb./hr. at 212° F and a 15 PSIG code. What operating pressure should the rental boiler be size for?

A11. 95 PSI is sufficient.

Q12. Can a portable day tank with a capacity of 10,000 gallons be placed next to the portable boiler in lieu of installing a return line several hundred feet across to the opposite end of the boiler plant?

A12. No.

** Please acknowledge all amendments with your response**

Update #2 ·

The purpose of this amendment to 36C24227Q0042 is to do the following:

Remove the following clauses:

52.219-6, Notice of Total Small Business Set-Aside (DEVIATION) (NOV2025)

52.219-14, Limitations on Subcontracting (DEVIATION) (NOV 2025)

Sets a meeting place for the site visit on Monday, October 19, 2026 @10:00am as the following:

VA Hudson Valley Healthcare System

Montrose Campus Franklin Delano Roosevelt Hospital

2094 Albany Post Rd.

Montrose, NY 10548

Report to:

Building 16 Engineering Conference Room

Update #1 ·

This is a combined synopsis solicitation for commercial services prepared in accordance with part 12. This announcement constitutes the only solicitation. Offers are being requested and a separate written solicitation will not be issued.

Solicitation number 36C24227Q0042 is issued as a request for quotation (RFQ) for a temporary boiler rental (1000 HP Fire tube boiler) with boiler maintenance and repair services as needed.

This acquisition is not set-aside for small business concerns. This solicitation incorporates provisions and clauses by reference. The full text of provisions and clauses may be accessed electronically at www.acquision.gov.

Files

File Type Posted
36C24227Q0042 0002.docx DOCX document
36C24227Q0042 0001.docx DOCX document
36C24227Q0042.docx DOCX document
temp oil.jpg JPG image
temp water.jpg JPG image
2015-4187 05132026.pdf PDF
temp steam.jpg JPG image
temp gas.jpg JPG image
Temp electric.jpg JPG image

Similar open opportunities

Opportunity Agency Set-aside Responses due
16292 Steam Boiler Replacement Hill AFB, Utah 84056, United States · NAICS 238220 Air Force Sustainment Center Total Small Business
657-27-107JC, Replace Select Hot Water Heating System Saint Louis, Missouri 63103, United States · NAICS 238220 Veterans Integrated Service Network 15 Service-Disabled Veteran-Owned Small Business Sole Source
H212-- Fire Pump Test and Alarm support Hudson Valley VA Medical Center aEUR" Castle Point Campus Wappingers Falls, New York 12590, United States · NAICS 561621 Veterans Integrated Service Network 2 Service-Disabled Veteran-Owned Small Business
H945--Boiler Controls Inspection and Testing Department of Veterans Affairs Richard L. Roudebush VA Medical Center Indianapolis, Indiana 46202, United States · NAICS 541350 Veterans Integrated Service Network 10 Service-Disabled Veteran-Owned Small Business
White City, Oregon, Boiler Inspection Services Solicitation Base Year + Four Option Years (offers are now due on 11/13/2026) White City, Oregon 97503, United States · NAICS 561210 Veterans Integrated Service Network 20 Service-Disabled Veteran-Owned Small Business

On GovTribe

Work this opportunity

  • Track it in your pipeline
  • Find teaming partners
  • Similar opportunities
  • Ask GovTribe AI about this opportunity