J045--Eddy Current Test and Cleaning of (4) 900 Ton York Chillers Loma Linda VA Health Care System
Closed Pre-Solicitation Posted
Not the latest version. See the latest solicitation from .
- Solicitation number
- 36C26224Q0357
- Agency
-
Veterans Integrated Service Network 22
Veterans Health Administration, Department of Veterans Affairs
- Responses due
- Set-aside
- No set-aside
Opportunity facts
- NAICS code
- 238220 Plumbing, Heating, and Air-Conditioning Contractors
- Place of performance
- Department of Veterans Affairs Loma Linda CA 92357, United States
Notice details come from SAM.gov. Updated .
About this opportunity
This pre-solicitation notice seeks a contractor to perform eddy current testing and cleaning of four 900-ton York chillers at the VA Loma Linda Health Care System in Loma Linda, California. The Department of Veterans Affairs aims to address scaling issues affecting chiller performance. Interested offerors must have an OSHA 30-hour safety card and C-38 refrigeration license, and respond by December 28, 2023 with company registration details and a capability statement. The selected contractor will be responsible for testing and cleaning the evaporator and condenser sides of all four chillers over a 30-day period according to the detailed statement of work, including chemical circulation, tube brushing, waste disposal and reporting of test results.
No set-aside designation was specified. The primary NAICS code is 238220 for steam and air conditioning supply with a size standard of $16.5 million. The contractor must perform work on four 900-ton York chillers within 30 days of the start date according to the detailed statement of work provided. The government estimates a response deadline of December 28, 2023 but does not specify an anticipated award value or budget range.
Notice text
This is a SOURCES SOUGHT ANNOUNCEMENT ONLY. It is neither a solicitation announcement nor a request for proposals or quotes and does not obligate the Government to award a contract. Requests for a solicitation will not receive a response. Responses to this source sought must be in writing. The purpose of this sources sought announcement is for market research to make appropriate acquisition decisions and to gain knowledge of potential qualified Service Disabled Veteran Owned Small Businesses, Veteran Owned Small Businesses, 8(a), HubZone and other Small Businesses interested and capable of providing the services described below. Documentation of technical expertise must be presented in sufficient detail for the Government to determine that your company possesses the necessary functional area expertise and experience to compete for this acquisition. Responses to this notice shall include the following: (a) company name (b) address (c) point of contact (d) phone, fax, and email (e) Unique Entity ID (f) Cage Code (g) Tax ID Number (h) Type of small business, e.g. Services Disabled Veteran Owned small Business, Veteran-owned small business, 8(a), HUBZone, Women Owned Small Business, Small disadvantaged business, or Small Business HUBZone business and (i) must provide a capability statement that addresses the organizations qualifications and ability to perform as a contractor for the work described below.
Eddy Current Test and Cleaning of (4) 900 Ton York Chillers.
Important information: The Government is not obligated to nor will it pay for or reimburse any costs associated with responding to this sources sought synopsis request. This notice shall not be construed as a commitment by the Government to issue a solicitation or ultimately award a contract, nor does it restrict the Government to a particular acquisition approach. The Government will in no way be bound to this information if any solicitation is issued. The VA is mandated by Public Law 109-461 to consider a total set-aside for Service Disabled Veteran Owned Small Business set aside. However, if response by Service Disabled Veteran Owned Small Business firms proves inadequate, an alternate set-aside or full and open competition may be determined. No sub-contracting opportunity is anticipated. The North American Classification System (NAICS) code for this acquisition is 238220/ $16.5m.
Notice to potential offerors: All offerors who provide goods or services to the United States Federal Government must be registered in the System for Award Management (SAM) at www.sam.gov. Additionally, all Service Disabled Veteran Owned Businesses or Veteran Owned Businesses who respond to a solicitation on this project must be registered with the Department of Veterans Affairs Center for Veterans Enterprise VetBiz Registry located at Veteran Small Business Certification (sba.gov). All interested Offerors should submit information by e-mail to freddy.osuna@va.gov. All information submissions to be marked Attn: Freddy Osuna, Contract Specialist and should be received no later than 15:00 MST on 28, December 2023.
STATEMENT OF WORK
TITLE:
Perform Eddy Current Testing on Both the Evaporator and Condenser Sides on all Four, 900 Ton York Chillers
BACKGROUND INFORMATION:
During the recent preventive maintenance schedule some of our split temperatures taking from all (4) chillers were too low. identifying that all chillers condenser barrels could be cover with scale. Making the chillers not operate properly. our cooling demand is harder to meet due to the scaling of the condenser tubes. Chemically and brushing the tubes to remove the scaling shall benefit the operation of the chillers.
PART and EQUIPMENT LIST
Equipment
Model
Serial Number
900-ton YORK Chiller
YKM2MRH9-CWGS
699900
900-ton YORK Chiller
YKM2MRH9-CWGS
700130
900-ton YORK Chiller
YKM2MRH9-CWGS
537130
900-ton YORK Chiller
YJJPK4H9-CWX
782200
OBJECTIVES:
Contractor shall furnish all supervision, labor, equipment, tools, materials, and transportation to perform the installation of the steam safety relief valve and the steam reducing station pressure regulated valve.
Contractor shall provide a working schedule.
Contract shall commence when all parts have been received.
Contractor shall provide a 2 week notice for shut down of chillers.
Contractor shall provide a Safety Data Sheet (SDS) of chemicals being used to clean chillers barrels.
Contractor shall provide a Hazmat spill kit around working area.
Contractor and VA employees shall perform proper lockout and tagout on each chiller electrical energy.
Contractor and VA employees shall lockout and lockout all electrical to chiller #1.
Contractor and VA employees shall lockout the chill water supply and chill water return.
Contractor and VA employees shall lockout the condenser water supply and the condenser water return.
Contractor shall remove and replace the end bells to commence the eddy current testing on the evaporating and condenser of chiller#1.
Contractor shall circulate the rydlyme chemical through the condenser tubes.
Contractor shall drain all rydlyme from condenser tube barrels into their 55gallon chemical disposable barrel.
Contractors shall brush all the condenser tubes in the chiller.
Contractor shall put chiller back online.
Contractor and VA employees shall remove all lockout tagout from chiller.
Contractor shall inspect barrel covers for leaks.
Contractors shall check for proper operation of chiller.
Contractor and VA employees shall lockout and lockout all electrical to chiller #2.
Contractor and VA employees shall lockout the chill water supply and chill water return.
Contractor and VA employees shall lockout the condenser water supply and the condenser water return.
Contractor shall remove and replace the end bells to commence the eddy current testing on the evaporating and condenser of chiller#2.
Contractor shall circulate the rydlyme chemical through the condenser tubes.
Contractor shall drain all rydlyme from condenser tube barrels into their 55gallon chemical disposable barrel.
Contractors shall brush all the condenser tubes in the chiller.
Contractor shall put chiller back online.
Contractor and VA employees shall remove all lockout tagout from chiller.
Contractor shall inspect barrel covers for leaks.
Contractors shall check for proper operation of chiller.
Contractor and VA employees shall lockout and lockout all electrical to chiller #3.
Contractor and VA employees shall lockout the chill water supply and chill water return.
Contractor and VA employees shall lockout the condenser water supply and the condenser water return.
Contractor shall circulate the rydlyme chemical through the condenser tubes.
Contractor shall drain all rydlyme from condenser tube barrels into their 55gallon chemical disposable barrel.
Contractor shall remove and replace the end bells to commence the eddy current testing on the evaporating and condenser of chiller#3.
Contractors shall brush all the condenser tubes in the chiller.
Contractor shall circulate the rydlyme chemical through the condenser tubes.
Contractor shall drain all rydlyme from condenser tube barrels into their 55gallon chemical disposable barrel.
Contractors shall brush all the condenser tubes in the chiller.
Contractor shall put chiller back online.
Contractor and VA employees shall remove all lockout tagout from chiller.
Contractor shall inspect barrel covers for leaks.
Contractors shall check for proper operation of chiller.
Contractor and VA employees shall lockout and lockout all electrical to chiller #4.
Contractor and VA employees shall lockout the chill water supply and chill water return.
Contractor and VA employees shall lockout the condenser water supply and the condenser water return.
Contractor shall remove and replace the end bells to commence the eddy current testing on the evaporating and condenser of chiller#4.
Contractor shall circulate the rydlyme chemical through the condenser tubes.
Contractor shall drain all rydlyme from condenser tube barrels into their 55gallon chemical disposable barrel.
Contractors shall brush all the condenser tubes in the chiller.
Contractor shall put chiller back online.
Contractor and VA employees shall remove all lockout tagout from chiller.
Contractor shall inspect barrel covers for leaks.
Contractors shall check for proper operation of chiller.
Contractors shall dispose of all chemical waste.
Contractor shall inspect for any steam leaks.
Contractor shall provide eddy current results to the VA.
Contractor shall provide warranty documents for work perform.
PERIOD OF PERFORMANCE:
30 days from performance start date. Work may be scheduled during the day, Monday thru Friday.
Daytime hours: 5 am to 4 pm
Contractor shall initiate work within 2 weeks of being contacted by the designated Contracting Officer s Point of Contact (POC) or designee. Work shall be scheduled through the POC or designee, who will coordinate with VALLHCS staff. Timelines are subject to change due to VALLHCS operational requirements.
PLACE OF PERFORMANCE:
VA Loma Linda
11201 Benton St
Loma Linda, CA 92357
LICENSING REQUIREMENTS:
Offeror must possess a 30-hour Occupational Safety and Health Administration (OSHA) safety card.
C-38- Refrigeration License.
SPECIFIC REQUIREMENTS:
Contractor shall schedule start date with POC or designee five (5) business days in advance.
Contactor personnel don t require a Loma Linda PIV badge.
Contractor shall coordinate energy source LOCK OUT /TAG OUT procedures with VALLHCS Utilities System Supervisor before starting work. When work is complete, Contractor shall notify the VALLHCS Utilities System Supervisor that energy sources will be restored and require verification.
Contractor s supervisor or lead technician are to check in with VALLHCS Graphics Control prior to work each day
Contractor shall conform to the following standards, policies, regulations, governing agency, and any other local, state, or Federal guidelines that are not listed here
OSHA Regulations, www.osha.gov
NFPA, www.nfpa.org
RECOGNIZED HOLIDAYS:
The following is a list of all Government recognized holidays:
New Year s Day Labor Day
Martin Luther King Jr. s Birthday Columbus Day
President s Day Veteran s Day
Memorial Day Thanksgiving Day
Juneteenth Christmas Day
Independence Day
If a holiday falls on Sunday, the following Monday shall be observed as the legal holiday. When a
holiday falls on a Saturday, the preceding Friday is observed as a legal holiday by U.S. Government
agencies. Also included, would be any other day specifically declared by the President of the
United States of America to be a National Holiday.
CONTRACTOR EMPLOYEES:
Contractor personnel shall present a neat appearance and be easily recognized as a Contractor
employees. Examples: wearing of distinctive clothing such as uniform, badges, patches, etc.
Contractor personnel shall wear identification (I.D.) badges during the entire time they are on the VA Loma Linda Healthcare System grounds. I.D. badges must have identification picture, name of the individual, and the represented company depicted on it.
XI. SMOKING AND VAPING POLICIES:
Smoking and vaping are prohibited on Government property
.
X11. SAFETY AND PPE EQUIPMENT:
Personal Protective Equipment shall be provided for each Contractor employee by the Contractor.
Possession of weapons are prohibited.
XIII. PARKING:
It is the responsibility of Contractor personnel to park only in designated parking areas. Parking information is available from the VA Security Service. The VA shall not invalidate or make reimbursement for parking violations of the Contractor's personnel under any circumstances.
Files
| File | Type | Posted |
|---|---|---|
| 36C26224Q0357.docx | DOCX document |
Notice history
| Notice | Type | Posted |
|---|---|---|
| J045--Eddy Current Test and Cleaning of (4) 900 Ton York Chillers Loma Linda VA Health Care System | Solicitation | |
| This notice | Pre-Solicitation |
Similar open opportunities
| Opportunity | Agency | Set-aside | Responses due |
|---|---|---|---|
| Rental of two chillers for one year | Veterans Integrated Service Network 6 | Service-Disabled Veteran-Owned Small Business | |
| J041--RFQ SDVOSB Set-Aside CHILLER TUBE CLEANING SERVICES | Veterans Integrated Service Network 7 | Service-Disabled Veteran-Owned Small Business | |
| C221--402-27-001 Repair Chiller 3 (AE) | Veterans Integrated Service Network 1 | Service-Disabled Veteran-Owned Small Business | |
| Z2NZ--Turn Key Chiller Equipment (Purchase and Install) | Veterans Integrated Service Network 16 | No set-aside | |
| Chiller | Land and Maritime | No set-aside |
On GovTribe
Work this opportunity
- Track it in your pipeline
- Find teaming partners
- Similar opportunities
- Ask GovTribe AI about this opportunity