FY26 750kVA 3-Phase Transformer

Closed Solicitation Posted

Solicitation number
FA440726Q1000
Agency
Responses due
Set-aside
Total Small Business

Opportunity facts

Place of performance
Scott Air Force Base, Illinois 62225, United States

Notice details come from SAM.gov. Updated .

About this opportunity

The Department of the Air Force Air Mobility Command seeks quotations for a single 750 kVA 3-phase pad-mount transformer, with proposals due June 12, 2026 at noon CST. This is a total small-business set-aside procured under FAR Part 12 procedures.

Place of performance is Scott Air Force Base, Illinois. The transformer must be manufactured with copper windings, meet DOE 2016 efficiency standards, and utilize Envirotemp FR3 insulating fluid. High-voltage specifications include 12470GY/7200 volts at 15 kV class with 95 kV BIL, dead-front primary termination with loop feed, and a 5-position tap changer with 2.5% taps above and below nominal. The unit requires six 200-amp Cooper bushing wells with removable studs, six 15 kV load-break inserts, three 15-38 kV 300A 2-position loadbreak switches, and three Varistar elbow arresters at 15 kV class. Low-voltage specifications designate 480Y/277 volts at 1.2 kV class with 30 kV BIL, live-front secondary termination, and radial feed. Overcurrent protection includes bayonet fuses in series with partial-range current-limiting fuses. Cabinet construction requires 304L stainless steel for sill, sides, and tank base with Federal Spec Sherwin Williams 6006 black bean brown paint. No fixed delivery deadline is imposed; the transformer serves as backup equipment.

NAICS Code 335311 and PSC Code 6120 apply. Evaluation uses Lowest Price Technically Acceptable (LPTA) criteria with a single award. Delivery is FOB Destination. Offerors must maintain active SAM registration. The specification was updated June 4, 2026 to mandate copper windings, superseding prior winding material requirements.

Notice text

2 versions

Update #2 · Latest ·

Request the purchase of the product listed below. This acquisition is being procured utilizing NAICS Code 335311 Power, Distribution, and Specialty Transformer Manufacturing: Ballasts Lamp holders, and Starters Size Standard 600 Employees and PSC Code 6120, Transformers: Distribution and Power Station. This requirement will be a Small-Business Set-Aside. Using RFO Part 12 procedures, 375th CONS intends to evaluate submitted quotes using Lowest Price Technically Acceptable (LPTA) criteria, and a single award will be made.

To be considered for award, offerors must have an active registration in SAM. Please provide an offer for the product listed below by: 10:00 A.M. CST 5 June 2026.  (All RFQ info and Transformer Specs are attached)

Copper Windings Required - Updated 4Jun26

kVA - 750 kVA 3 Phase Pad-Mount Transformer

Insulating fluid - Envirotemp FR3

Efficiency Standard - DOE 2016

High Voltage - 12470GY/7200 Volts

High Voltage kV Class - 15 kV Class                                                                                

High Voltage kV BIL - 95 kV BIL

Primary Termination Style - Dead Front

Primary Feed Type - Loop Feed                                                                   

Taps -  2 - 2.5% taps above and 2 - 2.5% taps below nominal

Tap Changer - 5-position tap changer

Tap Changer Switch Location - Frontplate HV Compartment

High Voltage Bushings - 200 amp Cooper bushing wells with removable studs (Quantity: 6)

Primary Ground Bushing Selection - Combined H0X0 Bushing

High Voltage Inserts - 15 kV, 95 kV BIL load-break inserts (Quantity: 6)

Loadbreak Switch(es) - 15-38 kV, 300A 2-Position (Quantity: 3)

Loadbreak Switch Location - Frontplate HV Compartment

High Voltage Arresters - Varistar elbow arresters, 15 kV class, distribution class 15 kV (Quantity: 3)

Overcurrent Protection Bayonet Fuses in series with Partial-Range Current-Limiting Fuses (Quantity: 3)

Expulsion fuses Bayonet fuses - (Quantity: 3)

Bayonet Holder - Copper Bayonet Fuse Holder (Quantity: 3)

Low Voltage - 480Y/277 Volts

Low Voltage kV Class - 1.2 kV Class

Low Voltage kV BIL - 30 kV BIL

Secondary Termination Style - Live Front

Secondary Feed Type - Radial Feed

Low Voltage Bushing Location - LV Frontplate (seg 1)

Low Voltage Bushings - Integral aluminum 12-hole spade bushing(s) (Quantity: 4)

Bushing Supports - Standard LV Bushing Support Assembly

Cabinet hardware - Penta-head cabinet door bolts

Cabinet Types - IEEE/ANSI                                                                                                                                                             Infrared Viewing Windows - No Window Required                                                                                                                    Bushing Layout - K 4.5 Loop feed per IEEE C57.12.34-2022 Figure 11 minimum dimensions (without bails)                 Special Paint - Federal Spec Number Sherwin Williams 6006, Black Bean Brown                                                               Cabinet Sill Construction - 304L Stainless steel cabinet sill                                                                                                     Cabinet Sides Construction - 304L Stainless steel cabinet sides                                                                                                    Tank Base Construction - 304L Stainless steel tank base                                                                                                                 FM / UL Certifications - UL Listed                                                                                                                                                                          Liquid Level Gauge - Magnetic liquid level gauge                                                                                                                                         Pressure Vacuum Gauges - Pressure/vacuum gauge                                                                                                                                    Thermometer - Thermometer, dial-type                                                                                                                                                                                                                           Other Fittings - Schrader valve                                                                                                                                                                                                                                                       Drain Valve - Drain valve with sampler in LV Compartment (1")                                                                                                                                     Fill Valve - Fill plug in LV Compartment                                                                                                                                                                 Pressure Relief Device - Pressure relief device, 50 SCFM                                                                                                                                  Ground Pads - Two-hole ground pads (Quantity: 3)                                                                                                                                                         Nitrogen Blanket - Yes

Cover Bolted cover

Gauges Location Inside Main Cabinet on Front Plate

Update #1 ·

Request the purchase of the product listed below. This acquisition is being procured utilizing NAICS Code 335311 Power, Distribution, and Specialty Transformer Manufacturing: Ballasts Lamp holders, and Starters Size Standard 600 Employees and PSC Code 6120, Transformers: Distribution and Power Station. This requirement will be a Small-Business Set-Aside. Using RFO Part 12 procedures, 375th CONS intends to evaluate submitted quotes using Lowest Price Technically Acceptable (LPTA) criteria, and a single award will be made.

To be considered for award, offerors must have an active registration in SAM. Please provide an offer for the product listed below by: 10:00 A.M. CST 5 June 2026.  (All RFQ info and Transformer Specs are attached)

kVA - 750 kVA 3 Phase Pad-Mount Transformer

Insulating fluid - Envirotemp FR3

Efficiency Standard - DOE 2016

High Voltage - 12470GY/7200 Volts

High Voltage kV Class - 15 kV Class                                                                                

High Voltage kV BIL - 95 kV BIL

Primary Termination Style - Dead Front

Primary Feed Type - Loop Feed                                                                   

Taps -  2 - 2.5% taps above and 2 - 2.5% taps below nominal

Tap Changer - 5-position tap changer

Tap Changer Switch Location - Frontplate HV Compartment

High Voltage Bushings - 200 amp Cooper bushing wells with removable studs (Quantity: 6)

Primary Ground Bushing Selection - Combined H0X0 Bushing

High Voltage Inserts - 15 kV, 95 kV BIL load-break inserts (Quantity: 6)

Loadbreak Switch(es) - 15-38 kV, 300A 2-Position (Quantity: 3)

Loadbreak Switch Location - Frontplate HV Compartment

High Voltage Arresters - Varistar elbow arresters, 15 kV class, distribution class 15 kV (Quantity: 3)

Overcurrent Protection Bayonet Fuses in series with Partial-Range Current-Limiting Fuses (Quantity: 3)

Expulsion fuses Bayonet fuses - (Quantity: 3)

Bayonet Holder - Copper Bayonet Fuse Holder (Quantity: 3)

Low Voltage - 480Y/277 Volts

Low Voltage kV Class - 1.2 kV Class

Low Voltage kV BIL - 30 kV BIL

Secondary Termination Style - Live Front

Secondary Feed Type - Radial Feed

Low Voltage Bushing Location - LV Frontplate (seg 1)

Low Voltage Bushings - Integral aluminum 12-hole spade bushing(s) (Quantity: 4)

Bushing Supports - Standard LV Bushing Support Assembly

Cabinet hardware - Penta-head cabinet door bolts

Cabinet Types - IEEE/ANSI                                                                                                                                                             Infrared Viewing Windows - No Window Required                                                                                                                    Bushing Layout - K 4.5 Loop feed per IEEE C57.12.34-2022 Figure 11 minimum dimensions (without bails)                 Special Paint - Federal Spec Number Sherwin Williams 6006, Black Bean Brown                                                               Cabinet Sill Construction - 304L Stainless steel cabinet sill                                                                                                     Cabinet Sides Construction - 304L Stainless steel cabinet sides                                                                                                    Tank Base Construction - 304L Stainless steel tank base                                                                                                                 FM / UL Certifications - UL Listed                                                                                                                                                                          Liquid Level Gauge - Magnetic liquid level gauge                                                                                                                                         Pressure Vacuum Gauges - Pressure/vacuum gauge                                                                                                                                    Thermometer - Thermometer, dial-type                                                                                                                                                                                                                           Other Fittings - Schrader valve                                                                                                                                                                                                                                                       Drain Valve - Drain valve with sampler in LV Compartment (1")                                                                                                                                     Fill Valve - Fill plug in LV Compartment                                                                                                                                                                 Pressure Relief Device - Pressure relief device, 50 SCFM                                                                                                                                  Ground Pads - Two-hole ground pads (Quantity: 3)                                                                                                                                                         Nitrogen Blanket - Yes

Cover Bolted cover

Gauges Location Inside Main Cabinet on Front Plate

Files

Show all 12

Similar open opportunities

Opportunity Agency Set-aside Responses due
Transformer, power NAICS 334416 Naval Supply Systems Command No set-aside
Transformer NAICS 334416 Naval Supply Systems Command No set-aside
Transformer, power NAICS 334413 Land and Maritime Total Small Business
Transformer, psrl NAICS 334416 Land and Maritime No set-aside
Transformer, power NAICS 335311 Land and Maritime No set-aside

On GovTribe

Work this opportunity

  • Track it in your pipeline
  • Find teaming partners
  • Similar opportunities
  • Ask GovTribe AI about this opportunity