100 Ton Temporary Chiller
Closed Solicitation Posted
This opportunity was awarded. See the award notice from .
- Solicitation number
- FA252123QB084
- Agency
- Air Force Space Command Air Force, Department of Defense
- Responses due
- Set-aside
- Woman-Owned Small Business
Opportunity facts
- NAICS code
- 333415 Air-Conditioning and Warm Air Heating Equipment and Commercial and Industrial Refrigeration Equipment Manufacturing
- Place of performance
- Patrick AFB, Florida 32925, United States
Notice details come from SAM.gov. Updated .
About this opportunity
The contract opportunity involves the provision and delivery of a 100-ton temporary Trane chiller to building 896. The chiller must meet various specifications including high efficiency, full factory refrigerant charge, factory installed freeze protection, and a 10-year parts/labor/refrigerant warranty among others. The contractor is also expected to provide a structural steel base with fork holes and lifting frame, a pump, isolation butterfly valves, gauges and thermometers, and other necessary components.
- Provision and delivery of a 100-ton temporary Trane chiller.
- Supply of a structural steel base with fork holes and lifting frame.
- Provision of a pump with TEFC motor.
- Supply of isolation butterfly valves.
- Provision of gauges and thermometers.
Notice text
2 versions
Update #2 · Latest ·
The purpose of this modification is to notified that we are posting the Q & As.
Please see new attachment.
All other items remain unchanged.
Provide and deliver 100 nominal ton temporary Trane chiller to building 896
The purpose of this combined synopsis and solicitation for one (1) 100 Ton Temporary Chiller Following are the salient characteristics among others:
100 Ton, 20-130 Ton Air Cooled
Model #CGAM100CANARIIS
The request is for the contractor to provide delivery of a 100-ton portable air-cooled chiller.
Government will offload chiller and start the chiller for operational testing.
Product
100 nominal tons
460 VAC, 3 phase, 60 Hz
High efficiency/performance
Full factory refrigerant charge (HFC-454B)
W/ Factory installed freeze protection
Refrigerant isolation valves (discharge valve)
UL listed to U.S. and Canadian safety standard
ASHRAE 90.1 compliance for all versions up to 2016
AHRI certified
Factory installed flow switch – set point 60 cm/s
Standard cooling (40-65 degrees Fahrenheit/4.44-18 degrees Celsius)
Grooved pipe connection
Factory insulation 1-1/4”-high humidity/low evaporator temperature
Performance based on water
High ambient (up to 125 degrees Fahrenheit/up to 52 degrees Celsius)
Complete Coat lanced aluminum fins with Blygold spray
Across the line starter/direct on line
Single point connection main line unit power-ancillary items require other power
Circuit breaker-high fault rated control panel
Enclosure type UL 1995 rated for outdoor applications
LonTalk/Tracer Summit interface
High A short circuit rating
Elastomeric isolators
W/ Water strainer factory installed
Architectural louvered panels
Chiller Warranty
10-year parts/labor/refrigerant warranty
Packaged Chiller Modification
Entire System UL Label
Structural steel base with fork holes and lifting frame
Galvanized base frame
Frame and piping painted black
Chiller painted white
(1) Pump (2.4 gpm/ton) with TEFC motor @ chiller flow and 100 ft TDH
Isolation butterfly valves
Pump bypass piping with valve
Gauges and thermometers
Fill/drain line
Vent line
Mount, pipe, and wire chiller
Supply/Return stickers
Rigging/Weight sticker
Electrical Information
Single point power connection 460-3-60
NEMA 3R enclosure
Quick connection terminals
Shore power connection
Auxiliary compressor heaters
System wiring
All wiring in EMT or liquid tight flexible metal conduit
Controls Information
Hand-Off pump switch
Phase fail and light
FS8W McDonell Miller flow switch
McCrometer meter
Testing
NIST Traceable Test Equipment
Hydrostatic Test to 150 psig or 50 psig over maximum system pressure (whichever is greater) for 2 hours.
Update #1 ·
Provide and deliver 100 nominal ton temporary Trane chiller to building 896
The purpose of this combined synopsis and solicitation for one (1) 100 Ton Temporary Chiller Following are the salient characteristics among others:
100 Ton, 20-130 Ton Air Cooled
Model #CGAM100CANARIIS
The request is for the contractor to provide delivery of a 100-ton portable air-cooled chiller.
Government will offload chiller and start the chiller for operational testing.
Product
100 nominal tons
460 VAC, 3 phase, 60 Hz
High efficiency/performance
Full factory refrigerant charge (HFC-454B)
W/ Factory installed freeze protection
Refrigerant isolation valves (discharge valve)
UL listed to U.S. and Canadian safety standard
ASHRAE 90.1 compliance for all versions up to 2016
AHRI certified
Factory installed flow switch – set point 60 cm/s
Standard cooling (40-65 degrees Fahrenheit/4.44-18 degrees Celsius)
Grooved pipe connection
Factory insulation 1-1/4”-high humidity/low evaporator temperature
Performance based on water
High ambient (up to 125 degrees Fahrenheit/up to 52 degrees Celsius)
Complete Coat lanced aluminum fins with Blygold spray
Across the line starter/direct on line
Single point connection main line unit power-ancillary items require other power
Circuit breaker-high fault rated control panel
Enclosure type UL 1995 rated for outdoor applications
LonTalk/Tracer Summit interface
High A short circuit rating
Elastomeric isolators
W/ Water strainer factory installed
Architectural louvered panels
Chiller Warranty
10-year parts/labor/refrigerant warranty
Packaged Chiller Modification
Entire System UL Label
Structural steel base with fork holes and lifting frame
Galvanized base frame
Frame and piping painted black
Chiller painted white
(1) Pump (2.4 gpm/ton) with TEFC motor @ chiller flow and 100 ft TDH
Isolation butterfly valves
Pump bypass piping with valve
Gauges and thermometers
Fill/drain line
Vent line
Mount, pipe, and wire chiller
Supply/Return stickers
Rigging/Weight sticker
Electrical Information
Single point power connection 460-3-60
NEMA 3R enclosure
Quick connection terminals
Shore power connection
Auxiliary compressor heaters
System wiring
All wiring in EMT or liquid tight flexible metal conduit
Controls Information
Hand-Off pump switch
Phase fail and light
FS8W McDonell Miller flow switch
McCrometer meter
Testing
NIST Traceable Test Equipment
Hydrostatic Test to 150 psig or 50 psig over maximum system pressure (whichever is greater) for 2 hours.
Attachments
| File | Type | Posted |
|---|---|---|
| Q and As FA252123QB084 100 TON CHILLER.pdf | ||
| FA252123QB084 CSS 20230817P.pdf | ||
| Brand Name J A.pdf |