Y26-743_Drawings.pdf
PDF 1 MB Posted
- Attached to
- Fredrick Douglas Window Replacement
- Solicitation number
- Y26-743
- Issued by
- Orange County, Orlando City, Florida
About this file
This is a set of architectural and structural bid documents for the Fredrick Douglass Day Care Center Window Replacement project prepared for Orange County Government, Florida. The project scope involves removing all existing exterior windows and installing new aluminum storefront windows with fixed glazing within existing masonry openings at the facility located at 3688 Day Care Center Road, Zellwood, Florida. The base bid specifies a non-impact rated storefront system using Kawneer Tri Fab Versa Glaze 451 frames (2 inches wide by 4.5 inches deep) with 1-inch insulated glazing (1/4-inch tempered glass, 1/2-inch air space, 1/4-inch tempered glass) in dark bronze finish, with Florida Product Approval #7237.2. A bid alternate is required for an impact-rated system using the Kawneer IR 501 model with impact-resistant glazing (Florida Product Approval #8787.2). The project includes demolition work to remove existing windows while preserving existing masonry openings, structural columns, and doors; interior finishes must be patched and repainted to match existing conditions after installation. The estimated project cost is $319,428.00, with sealed bids due by 4:00 p.m. EST on Tuesday, June 9, 2026. All submissions must be made electronically through the OpenGov e-Procurement Platform, with questions due by 5:00 p.m. EST on Tuesday, May 26, 2026.
The design incorporates multiple window elevations (identified as A through M) throughout the facility, with structural requirements based on 2023 Florida Building Code standards including ultimate wind speed of 139 miles per hour for Building Risk Category II. Window attachment fasteners are designated as a delegated design requiring compliance with component and cladding wind pressure requirements; fasteners must be capable of attaching to concrete masonry units, concrete, and structural steel up to 1/4-inch thickness, with stainless steel required for exterior use. The contractor is responsible for field verification of all existing conditions, site survey in the presence of the owner prior to demolition, and protection of items to remain during construction. Interior finishes require patching and repainting to match existing conditions, and existing wood sills are to be salvaged for reinstallation. The project design team includes Rhodes+Brito Architects (605 E. Robinson Street, Suite 750, Orlando, Florida), C & S Companies for structural engineering, and Carlson Construction Estimators for cost estimating.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BOARD OF COUNTY COMMISSIONERS
JERRY L. DEMMINGS
COUNTY MAYOR
NICOLE H. WILSON
District 1 Commissioner
CHRISTINE MOORE
District 2 Commissioner
MAYRA URIBE
District 3 Commissioner
MARIBEL GOMEZ CORDERO
District 4 Commissioner
KELLY MARTINEZ SEMRAD
District 5 Commissioner
MICHAEL SCOTT
District 6 Commissioner
REMOVE ALL EXISTING EXTERIOR WINDOWS. INSTALL
NEW ALUMINUM STOREFRONT WINDOWS WITH FIXED
GLAZING WITHIN EXISTING OPENINGS.
PROJECT SCOPE
PROJECT DESIGN TEAM
CARLSON CONSTRUCITON
ESTIMATORS
1000 SAVAGE COURT,SUITE 104
LONGWOOD, FL 32750
PH: (407) 792-9988
CONTACT: ANITA CARLSSON TROUT
COST ESTIMATING
A C CT T SEH IR
AR0014284
RHODES+BRITO ARCHITECTS
605 E. ROBINSON ST, SUITE 750
ORLANDO, FL 32801
PH. (407) 648-7288
CONTACT: MAXIMIANO BRITO
ARCHITECTURE STRUCTURE
C & S COMPANIES
255 E ROBINSON ST, SUITE 2145
ORLANDO, FL 32801
PH: (407) 422.1118
CONTACT: ANDREA CELLA
FREDRICK DOUGLASS DAY CARE CENTER
WINDOW REPLACEMENT
BID DOCUMENTS
12/11/2025
ORANGE COUNTY GOVERNMENT
G000
3688 DAY CARE CENTER RD, ZELLWOOD, FL 32757
400 EAST SOUTH STREET, SUITE 500
ORLANDO, FL 32801
VICINITY MAP
PROJECT LOCATION
D A
Y C
A R
E C
E N
T E
R R
O A
D
WILLOW STREET
DATE SUBMISSION / REVISION NO.
r h o d e s + b r i t o A R C H I T E C T S
A
A101
A2
A711
A2
A711
MATERIALS LEGEND
DRAWING FORMAT
DIMENSIONING SHEET NUMBERING
100 SF
A101
A711A scale:
drawn:
check:
date:
project no: 2001.001
01.01.01 date
Client Logo and
Project Title
ALL
REPRODUCTION
AND
INTELLECTUAL
PROPERTY
RIGHTS
RESERVED
CLIENT LOGO
HERE
A
B
C
D
E
F
G
H
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
19.02
TYP
TYP
G1
E1
C1
A1 A3
C3
E3
G3
A5 A7 A9
C5
EACH SHEET IS DIVIDED INTO A GRID. AN ALPHA-NUMERIC GRID COORDINATE SYSTEM IS USED TO ORGANIZE THE DRAWING TITLES
DRAWING TITLES ARE NUMBERED ACCORDING TO ITS LOCATION ON THE GRID. THE LOWER LEFT HAND CORNER GRID OF THE
DRAWING IS USED AS THE IDENTIFICATION NUMBER (SEE DIAGRAM).
COLUMN CENTERLINE
PARTITIONS ARE DIMENSIONED TO FACE OF STUDS, FACE OF CMU AND FACE OF
BLOCK UNLESS INDICATED OTHERWISE
DIMENSIONS ARE INDICATED ON DRAWINGS, DO NOT SCALE DRAWINGS
6.
7.
PARTITION
KEYNOTE
REFERENCE
ELEVATION
REFERENCE
REVISION
IDENTIFICATION
PARTITION TYPE
IDENTIFICATION
WINDOW TYPE
REVISION NUMBER
(REFER TO TITLE
BLOCK)
TARGET ELEVATION
TARGET DESCRIPTION
WINDOW DESIGNATION
(REFER TO WINDOW
SCHEDULE)
REFERENCE NUMBER
PARTITION TYPE
(REFER TO PARTITION
TYPE DETAILS)A
GRAPHIC
SCALE
INDICATES FEET
WHEN A ROOM/BUILDING/OBJECT CENTERLINE IS INDICATED, ONLY ONE SIDE OF
ELEMENT MAY BE DIMENSIONED
PARTITIONS WITH FINISH FACE FLUSH WITH FINISH FACE OF COLUMN WILL NOT BE
DRAWN ON SMALL SCALE PLANS BUT WILL BE DRAWN ACCORDINGLY ON LARGER
SCALE DRAWINGS.
COLUMN CENTERLINE
PARTITION FINISH FACE ON COLUMN OR GRID LINE WILL NOT BE DIMENSIONED ON
SMALL SCALE PLANS BUT WILL BE DRAWN ACCORDINGLY ON LARGER SCALE
DRAWINGS.
PARTITIONS CENTERED ON COLUMNS OR GRID LINES WILL NOT BE DIMENSIONED ON
SMALL SCALE PLANS BUT WILL BE DRAWN ACCORDINGLY ON LARGER SCALE
DRAWINGS.
5.
4.
PARTITION
3.
B. AS DIMENSIONED
COLUMN CENTERLINE
PARTITION
DOOR LOCATION
DOORS ARE LOCATED BY ONE OF THE FOLLOWING:
A. ONE JAMB FACE LOCATED BY A PARTITION AT RIGHT ANGLE.
2.
1.
PARTITION
DOOR
SINGLE INTERIOR
ELEVATION
REFERENCE
RESTROOM
ACCESSORY
IDENTIFICATION
DOOR NUMBER
SPOT
ELEVATION
REFERENCE
TRUE
NORTH ARROWDOOR NUMBER
(SEE DOOR SCHEDULE)
TARGET ELEVATION
ACCESSORY TYPE
(REFER TO RESTROOM
ACCESSORY SCHEDULE)A
ELEVATION DETAIL NUMBER
ELEVATION ORIENTATION
SHEET NUMBER ON WHICH
ELEVATION OCCURS
ROOM AREA
WALL SECTION
OR BUILDING
SECTION
REFERENCE
ROOM NUMBER
SHEET NUMBER ON
WHICH SECTION OCCURS
SECTION ORIENTATION
SECTION DETAIL NUMBER
ROOM NAME
COLUMN
IDENTIFICATION
B
CALLOUT DETAIL
REFERENCE
A501
A1
COLUMN CENTERLINE
DRAWING ON WHICH
DETAIL OCCURS
DETAIL NUMBER
REVISION SYMBOLS
REVISION AREA
REVISION DELTA
SUBCATEGORY
SHEET NUMBER
ITEM
CATEGORY
DISCIPLINE:
L - Landscape
S - Structural
A - Architectural
P - Plumbing
E - Electrical
M - Mechanical (HVAC)
C - Civil
RIGID INSULATION
POROUS FILL
GYPSUM BOARD /
GROUT FILL
BATT INSULATION
STEEL
PLYWOOD
(OR GLULAM)
CONTINUOUS
ROUGH LUMBER
DISCONTINUOUS
ROUGH LUMBER
CONCRETE MASONRY UNITSFINISH LUMBER
CONCRETE
EARTH
PROJECT
NORTH ARROW
DRAWING INDEX
BEXISTING COLUMN
IDENTIFICATION
LIST OF ABBREVIATIONS
MISCELLANEOUS CHANNEL
MECHANICAL/ELECTRICAL/PLUMBING
LAMINATED VENEER LUMBER
COMPT COMPARTMENT
BW
BVL
BOTH WAYS
BEVELED
BM
BSL
BS
BOT
BRK
BUR
BRG PL
BRG
BSMT
BO
BD
BLDG
BLK(G)
BIT
BET
BEL
BENCH MARK
BUILDING SETBACK LINE
BUILT UP ROOFING
BOTH SIDES
BEARING PLATE
BOTTOM OF
BASEMENT
BRICK
BEARING
BOTTOM
BITUMINOUS
BLOCK(ING)
BUILDING
BOARD
BETWEEN
BELOW
CP
CT
CYD
CORR
CRS
CR
CSMT
CENTER POINT
CUBIC YARD
COURSE(S)
CORRUGATED
CERAMIC TILE
CHROMIUM (PLATED)
CASEMENT
ADDENDUMADD
A/V
AUTO
ASPH
ASB
ARCH
APROX
ANOD
AP
AHU
A/E
ADD'D
ANC
ALUM
ALT
ADJ
ADH
AFF
ANCHOR(AGE)
AUDIO VISUAL
ACCESS PANEL
APPROXIMATE
ARCHITECT(URAL)
ANODIZED
ASBESTOS
ASPHALT
AUTOMATIC
AIR HANDLING UNIT
ARCHITECT/ENGINEER
ADDITIONAL
ABOVE FINISHED FLOOR
ADJUSTABLE
ADHESIVE
ALTERNATE
ALUMINUM
AD
AB
A/C
ACT
ACPL
AC
ACC
ABV
ACOUSTICAL
ACOUSTICAL PLASTER
ACOUSTICAL TILE
AIR CONDITIONING
ANCHOR BOLT
AREA DRAIN
ABOVE
ACCESS
CI CAST IRON
CNTRSNK
CO
CONN
CONT
CONTR
CONST
CONC
COL
CNTR
CLOS
CK
CJ
CMU
CLS
CLR
CIR
CLC
CIP
CONNECTION
COUNTERSINK
CONTRACT(OR)
CONTINUOUS
CONSTRUCTION
CLEAN OUT
CENTER
CONCRETE
COLUMN
CONTROL JOINT
CAST-IN-PLACE
CONC MASONRY UNIT
CLEAR(ANCE)
CLOSET
CAULK
CEILING
CLOSURE
CIRCLE
CG
C/C
CAT
CFT
CHAM
CHT
CB
CAB
CORNER GUARD
CENTER TO CENTER
CUBIC FOOT
CEILING HEIGHT
CAST BASIN
CATEGORY
CHAMFER
CABINET
MANHOLEMH
INVERTINV
FRP FIBERGLASS REINFORCED
PLASTICEJ EXPANSION JOINT
GALVANIZED STEEL SHEET
EQUIP
EXT
EXP
EX
EST
ESC
EWC
ENGR
EQ
ENCL
EMER
ELEV
EL
EP
ELEC
EQUIPMENT
EXPANDED(EXPANSION)
ELECTRIC WATER COOLER
EXTERIOR
EXISTING
ESTIMATE
ESCALATOR
ELECTRICAL POWERBOARD
ENGINEER
EQUAL
ENCLOSE(URE)
EMERGENCY
ELEVATOR
ELEVATION
ELECTRICAL
GKT GASKET(ED)
GP
GYP
GWB
GYPBD
GLAM
GL
GSS
GYPSUM WALL BOARD
GYPSUM BOARD
GLUE LAMINATED
GALVANIZED PIPE
GYPSUM
GLASS
GA
GI
GEN'L
GD
GB
GC
GALV
FURN
FT
FUT
FUR
FS
FTG
FRT
GALVANIZED IRON
GENERAL CONTRACTOR
GALVANIZED
GAUGE
GENERAL
GRADE
GRAB BAR
FURNITURE/FURNISHINGS
FIRE-RETARDANT
FOOT
FUTURE
FURRING
FULL SIZE
FOOTING
JT
KIT
KO
JC
JB
JF
JST
IPS
JOINT
KITCHEN
KNOCKOUT
JANITOR CLOSET
JUNCTION BOX
JOINT FILLER
IRON PIPE SIZE
JOIST
MIR
MISC
MIN
MTD
MO
MM
MT
MASONRY OPENING
MIRROR
MISCELLANEOUS
MILLIMETER
MINIMUM
METAL THRESHOLD
MOUNTED
FIRE-RESISTANT COATING
FIRE EXTINGUISHER CABINET
FINISHED FLOOR ELEVATION
EXTERIOR INSULATION & FINISH
SYSTEM
DISP DISPENSER
EB
EIFS
E
EA
DWR
DR
DN
DWG
DRB
DS
DIV DR
DTL
DL
DP
EXPANSION BOLT
EAST
EACH
DRAWER
DIVISION DOOR
DAMP PROOFING
DOOR
DOWN
DRAWING
DRAIN BOARD
DOWN SPOUT
DETAIL
DEAD LOAD
DEPT
DBL
DF
DH
DIM
DIA
DEP
DEMO
DRINKING FOUNTAIN
DEMOLISH, DEMOLITION
DEPARTMENT
DOUBLE
DIMENSION
DOUBLE HUNG
DIAGONAL
DEPRESSED
FF FACTORY FINISH
FR
FND
FPL
FRC
FP
FOS
FOF
FOM
FOC
FLUOR
FH
FJT
FLR
FLEX
FLG
FFE
FIN
FGL
FRAME(D)(ING)
FOUNDATION
FLOOR PLATE
FACE OF STUDS
FACE OF FINISH
FACE OF MASONRY
FACE OF CONCRETE
FIREPROOF
FLUORESCENT
FIRE HYDRANT
FLUSH JOINT
FIBERGLASS
FLOOR
FLEXIBLE
FLASHING
FINISH(ED)
FBO
FCO
FEC
FE
FA
FAS
FD
FB
FURNISHED BY OTHERS
FLOOR CLEAN OUT
FIRE EXTINGUISHER
FIRE ALARM
FASTEN, FASTENER
FLOOR DRAIN
FACE BRICK
INSULATED BY CONTRACTOR
HEATING/VENTILATING/AIR
CONDITIONING
HP HIGH POINT
INCL
INT
IBC
INFO
ID
INSUL
HR
HWH
HRDW
HWD
HD HT
HTG
HT
HVAC
HOT
WATER
HEATER
INCLUDE(D)(ING)
INFORMATION
INSIDE DIAMETER
INSULATION
INTERIOR
HARDWOOD
HEAD HEIGHT
HOUR
HARDWARE
HEATING
HEIGHT
HM
HB
HOR
HBD
HJT
HDR
HD
HC
HOLLOW METAL
HORIZONTAL
HARDBOARD
HEAD JOINT
HEAVY DUTY
HOLLOW CORE
HOSE BIBB
HEADER
LUMP SUMLS
MED
MEMB
MECH
MAS
MAT'L
MAX
MEP
MTL
MFR
LVR
LVL
MC
M
LT
MATERIAL
MECHANICAL
MEDIUM
MEMBRANE
MAXIMUM
MANUFACTURER
METAL
MASONRY
LOUVER
METER
LIGHT
LAV
LAM
LBL
LAB
LF
LH
LB
LL
LAVATORY
LAMINATE
LINEAR FOOT
LEFT HAND
LABORATORY
LAG BOLT
LIVE LOAD
LABEL
WROUGHT IRON
VINYL ASBESTOS TILE
WELDED WIRE FABRIC
WALL TO WALL
UNDERWRITERS
LABORATORY
UNLESS NOTED OTHERWISE
VAPOR BARRIER
VINYL COMPOSITION TILE
WHEEL BUMPER
WATER REPELLENT
WATERPROOFING
WATER CLOSET
WHB
STANDARDSTD
ROOMRM
PRE CAST CONCRETEPCC
ROUGH OPENING
REVERSE(SIDE)
RIGHT OF WAY
RAIN WATER CONDUCTOR
POLYVINYL CHLORIDE
POUNDS PER CUBIC FOOT
POUNDS PER LINEAL FOOT
POUNDS PER SQUARE FOOT
POINT/PRESSURE TREATED
POUNDS PER SQUARE INCH
PROPERTY LINE/PLATE
PREFABRICATE(D)
PRE FINISHED
PLASTIC LAMINATE
PAIR/PROPOSAL REQUEST
PRELIMINARYPRELIM
PVC
PSF
PT
PSI
PRF
PTN
PVMT
PERFORMED
PARTITION
PAVEMENT
PLF
PLYWD
PREFAB
PNT
PR
POL
PLBG
PNL
PNTD
PLYWOOD
PAINT
POLISHED
PLUMBING
PANEL
PAINTED
PCF
PG
PL
PERIM
PH
PFN
PJ
PLAM
PLAS
PLATE GLASS
PERIMETER
PHASE
PANEL JOINT
PLASTER
RO
ROW
RVS
RWC
TOP OF MASONRY
TONGUE AND GROOVE
TOILET PARTITION
TOILET PAPER DISPENSER
THRES THRESHOLD
TR TRANSOM
TYPICAL
TELEVISION
TYP
TV
TOLERANCE
TOP OF
TOP OF STEEL
TOP OF WALL
TOILET
TOL
TO
TOM
TOS
TOW
TLT
TPTN
TPD
TOWEL BAR
TREAD
THICK(NESS)
TEMPORARY
TERRAZZO
TELEPHONE
TB
T
T&G
THK
TEMP
TER
TEL
SYSTEM
SYNTHETIC
SYMMETRY(ICAL)
SUSPENDED
STRUCTURAL
STORAGE
STEEL
SYS
SYN
SYM
SUS
STR
STOR
STL
WTW
WWF
WI
WSCT
WO
WM
WIN
WTH
WS
WR
WP
WAINSCOT
WITHOUT
WIRED MESH
WINDOW
WIDTH
WATER STOP
RUBBER BASE
REQUEST FOR INFO
ROOF HATCH
REFLECTED CEILING PLAN
REVISION(S),(D)
REFLECT(ED),(ING)
REFRIGERATOR
RAIN LEADER
REINFORCE(D),(ING)
QUARRY TILE
VERTICAL DATUM
NATIONAL GEODETIC
NOT APPLICABLE
NOT IN CONTRACT
OUTSIDE DIAMETER
NOT TO SCALE
OVERFLOW ROOF DRAIN
OPPOSITE HAND
PC
OV
OPP
ORD
OS
PRE CAST
OVERALL
OPPOSITE
OUTSIDE
OC
OFC
OH
OD
OPG
OH/OPH
ON CENTER
OFFICE
OVERHEAD
OPENING
NGVD
N
NA
NIC
NO
NOM
NTS
NORTH
NUMBER
NOMINAL
RADIUSRAD
RFI
RFH
RFG
REV
RES
RET
RH
RFL
RL
ROOFING
RESILIENT
RETURN
RIGHT HAND
REQ'D
RD
RB
RCP
REM
REF
REFR
REG
REINF
REQUIRED
ROOF DRAIN
REMOVE
REFERENCE
REGISTER
RA
R
QTR
QT
RETURN AIR
RISER
QUARTER
SLAB ON GRADE
STAINLESS STEEL
SPECIFICATION(S)
SHELVINGSH
STATION
SQUARE YARD
SQUARE INCH
SQUARE
SPECIAL
SPEAKER
SPACER
STA
SQ/YD
SQ/IN
SS
SQ
SPEC
SPL
SPK
SPCR
SEALER
STEEL JOIST
SHELVING
SOUND PROOF
SLEEVE
SIMILAR
SHEET
SHEATHING
SOG
SLR
SJ
SHELV
SP
SL
SIM
SHT
SHTH
SQUARE FOOT
SOUTH
STORM DRAIN
SOLID CORE
SHEET GLASS
SECTION
SCHEDULE
SAFETY GLASS
SF
S
SD
SC
SG
SECT
SCHED
SFGL
W/
WH
WB
WD
WG
W
WC
WITH
WALL HUNG
WOOD BASE
WOOD
WIRED GLASS
WEST
VAT
VEST
VB
VCT
VAR
VERT
VESTIBULE
VARNISH
VERTICAL
UNF
UR
UL
UNO
UC
UNFINISHED
URINAL
UNDERCUT
OPCI OWNER PROVIDED
CONTRACTOR INSTALLED
OPOI OWNER PROVIDED
OWNER INSTALLED
CPCI CONTRACTOR PROVIDED
CONTRACTOR INSTALLED
RECEP RECEPTIONIST
SECRETARYSECR
SECURITYSECU
AHJ AUTHORITY HAVING JURISDICTION
VOL VOLUME
FV FIELD VERIFIED
UNO
4" TYP
SYMBOL LEGEND
ROOM
NAMEROOM
IDENTIFICATION
A711
MULTIPLE
INTERIOR
ELEVATION
REFERENCE
A1
A3
A2A4
ELEVATION DETAIL NUMBER
ELEVATION ORIENTATION
SHEET NUMBER ON WHICH
ELEVATION OCCURS
FIRST FLOOR
100' - 0"
SPECIALITY
EQUIPMENT
IDENTIFICATION
EQUIPMENT TYPE
(REFER TO EQUIPMENT
SCHEDULE)A
02 4 8134 no.revision
G - General
ID - Interior Design
FS - Food Service
FP - Fire Protection
T - Technology
SCALE:
DATE:
DRAWN BY:
CHECK BY:
PROJECT NUMBER:
1 2 3 4 5 6 7 8 9 10
H
G
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9 10
ALL REPRODUCTION AND INTELLECTUAL
PROPERTY RIGHTS RESERVED ©
Seal
Consultants
Client
A C CT T SEH IR
605 E. ROBINSON STREET, SUITE 750
ORLANDO, FL 32801
AR0014284
www.rbarchitects.com 407.648.7288
12" = 1'-0"
G001
GENERAL
INFORMATION
EW
JS
12/11/2025
18019-0077
FREDRICK DOUGLASS
DAY CARE CENTER
WINDOW
REPLACEMENT
ORANGE COUNTY
GOVERNMENT
BID DOCUMENTS
GENERAL
REV. NO. SHEET NAME
G000 COVER SHEET
G001 GENERAL INFORMATION
Grand total: 2
ARCHITECTURAL
REV. NO. SHEET NAME
A101 FLOOR PLAN & ELEVATIONS
A601 STOREFRONT ELEVATIONS & DETAILS
AD101 DEMOLITION FLOOR PLAN & ELEVATIONS
Grand total: 3
STRUCTURAL
REV. NO. SHEET NAME
S-001 STRUCTURAL GENERAL NOTES AND SCHEDULES
Grand total: 1
DATE SUBMISSION/REVISION NO.
A101
C1
A101
A1
AD101
C1
BABIES
ROOM
CLASSROOM
BATH
BATH
MEN
BATH
FOYER
WOMEN
LAUNDRY
OFFICE
CLOSET
FOYER
DRY
CLOSET
KITCHEN
DINING
ROOM
CLASSROOM
CLASSROOM
CLASSROOM
BATH
BATH
BATH
AD101
A1
D01D01
D01
D02D02
D02
D01D01D01D01 A601
C7
D01 D01
(TYP)(TYP)
Level 1
+0'-0"
D01
SCALE:
DATE:
DRAWN BY:
CHECK BY:
PROJECT NUMBER:
1 2 3 4 5 6 7 8 9 10
H
G
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9 10
ALL REPRODUCTION AND INTELLECTUAL
PROPERTY RIGHTS RESERVED ©
Seal
Consultants
Client
A C CT T SEH IR
605 E. ROBINSON STREET, SUITE 750
ORLANDO, FL 32801
AR0014284
www.rbarchitects.com 407.648.7288
1/8" = 1'-0"
AD101
DEMOLITION FLOOR
PLAN & ELEVATIONS
EW
JS
12/11/2025
18019-0077
FREDRICK DOUGLASS
DAY CARE CENTER
WINDOW
REPLACEMENT
ORANGE COUNTY
GOVERNMENT
BID DOCUMENTS
SCALE: 1/8" = 1'-0"AD101
D1 DEMOLITION FLOOR PLAN
SCALE: 1/8" = 1'-0"AD101
C1 SOUTH ELEVATION - DEMOLITION
SCALE: 1/8" = 1'-0"AD101
A1 NORTH ELEVATION - DEMOLITION
SCALE: 1/8" = 1'-0"AD101
A9 TYP. SIDE WALL ELEVATION
DEMOLITION KEYNOTE LEGEND
D01 REMOVE ALL EXISTING EXTERIOR WINDOWS. EXISTING MASONRY OPENING TO
REMAIN AS-IS.
D02 REMOVE EXISTING INTERIOR FINISHES ONLY AS REQUIRED FOR REMOVAL /
INSTLLATION OF WINDOWS.
GENERAL NOTES - DEMOLITION
A VERIFY ALL EXISTING CONDITIONS PRIOR TO START OF WORK. THE GENERAL
CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD VERIFICATION AND
COORDINATION OF ALL EXISTING CONDITIONS WITH CONTRACT DESIGN
DOCUMENTS. CONTRACTOR SHALL NOTIFY OWNER AND ARCHITECT IN WRITING
OF ANY DISCREPANCIES PRIOR TO THE START OF DEMOLITION WORK.
B GENERAL CONTRACTOR SHALL COORDINATE THE DEMOLITION WORK
DESCRIBED IN THE DEMOLITION DRAWINGS OF EACH DISCIPLINE WITHIN THE
CONTRACT DOCUMENTS.
C PRIOR TO START OF DEMOLITION, THE CONTRACTOR SHALL CREATE A SITE
SURVEY FOR THE AREA OF WORK IN THE PRESENCE OF THE OWNER, TO
IDENTIFY EXISTING ITEMS TO REMAIN, TO BE SALVAGED, TO BE
REMOVED/REINSTALLED DURING CONSTRUCTION, AND TO IDENTIFY DAMAGED
ITEMS NDICATED TO REMAIN. SITE SURVEY MUST BE ACCEPTED BY OWNER &
ARCHITECT.
D WHERE ITEMS ARE SCHEDULED TO REMAIN DURING CONSTRUCTION, GENERAL
CONTRACTOR MUST PROTECT THOSE ITEMS FROM DAMAGE. WHERE ITEMS
ARE SCHEDULED TO BE REMOVED AND REINSTALLED, THE GENERAL
CONTRACTOR IS RESPONSIBLE TO PROTECT AND STORE THOSE ITEMS DURING
CONSTRUCTION.
E CONTRACTOR SHALL NOT DAMAGE OR ALTER EXISTING STRUCTURAL COLUMNS
DURING DEMOLITION. REFER TO STRUCT DRAWINGS.
F ALL EXISTING DOORS ARE TO REMAIN.
REFER TO ELEVATION
A9/AD101 FOR WINDOW
DEMOLITION AT RETURN
WALL
REFER TO ELEVATION
A9/AD101 FOR WINDOW
DEMOLITION AT RETURN
WALL
REFER TO ELEVATION
A9/AD101 FOR WINDOW
DEMOLITION AT RETURN
WALL
REFER TO ELEVATION
A9/AD101 FOR WINDOW
DEMOLITION AT RETURN
WALL
BABIES
ROOM
CLASSROOM
BATH
MEN
BATH
FOYER
WOMEN
LAUNDRY
OFFICE
FOYER
DRY
CLOSET
KITCHEN
DINING
ROOM
D
CLASSROOM
CLASSROOM
CLASSROOM
BATH
H F
GM
J HJ
KH
ML
HK
A101
C1
A101
A1
A601
C7
01 01
01 01
A
B
DA
C
B
A
AA
AA A
H J J
D
G
H
FK L M
K
M
Level 1
+0'-0"
H
SCALE:
DATE:
DRAWN BY:
CHECK BY:
PROJECT NUMBER:
1 2 3 4 5 6 7 8 9 10
H
G
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9 10
ALL REPRODUCTION AND INTELLECTUAL
PROPERTY RIGHTS RESERVED ©
Seal
Consultants
Client
A C CT T SEH IR
605 E. ROBINSON STREET, SUITE 750
ORLANDO, FL 32801
AR0014284
www.rbarchitects.com 407.648.7288
1/8" = 1'-0"
A101
FLOOR PLAN &
ELEVATIONS
EW
JS
12/11/2025
18019-0077
FREDRICK DOUGLASS
DAY CARE CENTER
WINDOW
REPLACEMENT
ORANGE COUNTY
GOVERNMENT
BID DOCUMENTS
SCALE: 1/8" = 1'-0"A101
E1 FLOOR PLAN - NEW WORK
SCALE: 1/8" = 1'-0"A101
C1 SOUTH ELEVATION - NEW WORK
SCALE: 1/8" = 1'-0"A101
A1 NORTH ELEVATION - NEW WORK
SCALE: 1/8" = 1'-0"A101
A9 TYP. SIDE ELEVATION
GENERAL NOTES - FLOOR PLAN
A THESE DRAWINGS HAVE BEEN DEVELOPED FROM OBSERVED FIELD CONDITIONS
AND AS-BUILT DRAWINGS. THE DRAWINGS MAY NOT REFLECT ALL HIDDEN
CONDITIONS. THE CONTRACTOR SHALL VISIT THE PROJECT SITE AND SHALL
VERIFY THESE DRAWINGS WITH THE EXISTING FIELD CONDITIONS. THE
CONTRACTOR SHALL NOTIFY THE ARCHITECT IN WRITING OF ANY
DISCREPANCIES BETWEEN THE DRAWINGS AND EXISTING CONDITIONS.
B IT IS THE INTENT OF THIS FACILITY TO REMAIN OPERATIONAL FOR THE DURATION
OF THIS PROJECT. CONTRACTOR SHALL ENSURE SAFETY OF ALL OCCUPANTS.
ITEMS WHICH MAY CREATE DUST, NOISE, OR CIRCULATION PROBLEMS SHALL BE
COORDINATED WITH OWNER PRIOR TO START OF WORK.
C CONTRACTOR SHALL PROTECT ALL ITEMS INTENDED TO REMAIN IN PLACE
DURING CONSTRUCTION FROM DAMAGE DURING DEMOLITION WORK AND SHALL
BEAR ALL COSTS OF REPAIRING OR REPLACING EXISTING ITEMS DAMAGED
DURING CONSTRUCTION.
D ALL WORK SHALL CONFORM TO ALL APPLICABLE CODES AND REGULATIONS
ASSOCIATED WITH DEMOLITION AND NEW WORK. FOR ADDITIONAL GENERAL
NOTES, LEGENDS, AND SCHEDULES REFER TO SHEET G001.
E WHERE REQUIRED BY CONTRACT DOCUMENTS AND/OR AHJ, CONTRACTOR SHALL
PROVIDE ENGINEERED SHOP DRAWINGS AND FL PRODUCT APPROVALS FOR
REVIEW BY THE DESIGN TEAM PRIOR TO FABRICATION OF ALL ASSEMBLIES.
F ALL MATERIAL STORED ON SITE SHALL BE PROPERLY PROTECTED FROM INJURY
OR DETERIORATION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL COSTS
INCURRED TO CLEAN THE STORED MATERIAL TO THE SATISFACTION OF THE
OWNER AND DESIGNER.
G WHERE CONFLICT EXISTS AMONG THE VARIOUS PARTS OF THE CONTRACT
DOCUMENTS, DRAWINGS, GENERAL NOTES, AND SPECIFICATIONS, THE
STRICTEST REQUIREMENTS SHALL GOVERN.
H ARCHITECTUAL AND ENGINEERS DRAWINGS, AS PART OF THE CONTRACT
DOCUMENTS, INDICATE SUFFICIENT INFORMATION TO CONVEY DESIGN INTENT. IF
ERRORS, INCONSISTENCIES, OR OMISSIONS ARE DISCOVERED, PROMPTLY
NOTIFY THE ARCHITECT AND ENGINEERS IN WRITING.
J CONTRACTOR SHALL PATCH / REPAIR INTERIOR FINISHES AS NEEDED AFTER THE
STOREFRONT INSTALLATION IS COMPLETE. ALL PATCHED / REPAIRED AREAS
SHALL BE PAINTED TO MATCH EXISTING.
NOTE:
THIS ELEVATION OCCURS IN FOUR (4)
LOCATIONS
KEYNOTE LEGEND
01 NEW ALUMINUM STOREFRONT WINDOW WITH FIXED GLAZING.
06 LINE OF HIGH WINDOW. REFER TO EXTERIOR ELEVATIONS FOR CLARITY.
A9
A601
(3 EQ. SPACING)
11' - 10"
(3 EQ. SPACING)
11' - 10"
24' - 0" (MO)
(5 E
Q S
P A
C
IN
G
(M O
A A
A9
A601
16' - 0" (M0)
(2 EQ. SPACING)
7' - 10"
(2 EQ. SPACING)
7' - 10"
(5 E
Q S
P A
C
IN
G
(M O
B B
(5 E
Q S
P A
C
IN
G
(M O
(3 EQ. SPACING)
12' - 0" (MO)
C
(M O
21' - 0" (MO)
EQ EQ EQ EQ EQ EQ EQ
F
4' - 0" (MO)
(M O
EQ. EQ.
J
9' - 0" (MO)
2' - 0" 2' - 0"
(M O
G
(M O
5' - 0" (MO)
EQ EQ
M
2' - 3" (MO)
(M O
EQ EQ
H
5' - 8" (MO)
(M O
M
EQ EQ
EXISTING LINTEL
BACKER ROD AND
SEALANT AT PERIMETER
OF FRAME EACH SIDE
EXISTING CMU WALL
EXTERIOR
ALUM. STOREFRONT W/
FIXED GLAZING. REFER TO
STOREFRONT SYSTEM NOTES
WOOD SHIM
INTERIOR FRAMING AND
WALLBOARD SHALL BE
PATCHED / REPAIRED AND
REPAINTED TO MATCH
EXISTING AS NEEDED AFTER
INSTALLATION OF TOREFRONT
IS COMPLETE.
INTERIOR
EXISTING
CONCRETE SILL
TO REMAIN IN
PLACE
EXISTING CMU
WALL
SEALANT WITH
BACKER ROD
ALUM. STOREFRONT W/
FIXED GLAZING. REFER TO
STOREFRONT SYSTEM NOTES
EXISTING FURRING
AND WALLBOARD
TO REMAIN
(V.I.F.)
EXISTING WOOD SILL
TO BE REMOVED
AND SALVAGED
FOR REINSTALLATION.
CUT WIDTH OF SILL
AS NEEDED TO ACCOMODATE
NEW STOREFROMT
INTERIOR EXTERIOR
INTERIOR FRAMING AND
WALLBOARD SHALL BE
PATCHED / REPAIRED AND
REPAINTED TO MATCH AS
NEEDED AFTER INSTALLATION
OF STOREFRONT IS
COMPLETE.
BACKER ROD AND
SEALANT AT THE
PERIMETER OF THE
FRAME, EACH. SIDE
EXIST. CMU
WALL
ALUM. STOREFRONT
W/ FIXED GLAZING
EXTERIOR
INTERIOR
8' - 5" (MO)
(M O
2' - 0" 2' - 0"
L
EXISTING STL.
COLUMN TO
REMAIN.
ALUM. STOREFRONT
W/ FIXED GLAZING
BREAK METAL COLUMN
WRAP AT BOTH INTERIOR
AND EXTERIOR SIDES. COLOR
TO MATCH DARK BRONZE
STOREFRONT
WOOD BLOCKING
ADJUST SIZE AS
NEEDED. ATTACHED
TO STEEL COLUMN
BACKER ROD &
SEALANT - TYP
CONC. SILL
BELOW
EXTERIOR
INTERIOR
ALIGN
ALIGN
24' - 2" (MO)
(M O
EQ EQ EQ EQ EQ EQ EQ
K
SCALE:
DATE:
DRAWN BY:
CHECK BY:
PROJECT NUMBER:
1 2 3 4 5 6 7 8 9 10
H
G
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9 10
ALL REPRODUCTION AND INTELLECTUAL
PROPERTY RIGHTS RESERVED ©
Seal
Consultants
Client
A C CT T SEH IR
605 E. ROBINSON STREET, SUITE 750
ORLANDO, FL 32801
AR0014284
www.rbarchitects.com 407.648.7288
As indicated
A601
STOREFRONT
ELEVATIONS &
DETAILS
EW
JS
12/11/2025
18019-0077
FREDRICK DOUGLASS
DAY CARE CENTER
WINDOW
REPLACEMENT
ORANGE COUNTY
GOVERNMENT
BID DOCUMENTS
SCALE: 1/2" = 1'-0"A601
G1 STOREFRONT ELEVATION 'A'
SCALE: 1/2" = 1'-0"A601
G5 STOREFRONT ELVATION 'B'
SCALE: 1/2" = 1'-0"A601
G7 STOREFRONT ELEVATION 'C'
SCALE: 1/2" = 1'-0"A601
E1 WINDOW ELEVATION 'D'
SCALE: 1/2" = 1'-0"A601
E5 WINDOW ELEVATION 'F'
SCALE: 1/2" = 1'-0"A601
C5 WINDOW ELEVATION 'J'
SCALE: 1/2" = 1'-0"A601
C1 WINDOW ELEVATION 'G'
SCALE: 1/2" = 1'-0"A601
E3 WINDOW ELEVATION 'E'
SCALE: 1/2" = 1'-0"A601
C3 WINDOW ELEVATION 'H'
SCALE: 1/2" = 1'-0"A601
A1 WINDOW ELEVATION 'M'
SCALE: 3" = 1'-0"A601
A3 TYPICAL STROREFRONT HEAD DETAIL
SCALE: 3" = 1'-0"A601
A5 TYPICAL STOREFRONT SILL DETAIL
SCALE: 3" = 1'-0"A601
A7 TYPICAL STOREFRONT JAMB DETAIL
SCALE: 1/2" = 1'-0"A601
B1 WINDOW ELEVATION 'L'
GENERAL NOTES - STOREFRONTS
A ROUGH OPENINGS ARE EXISTING AND SHALL NOT BE MODIFIED.
B THE CONTRACTOR SHALL VISIT THE SITE AND VERIFY THE SIZE OF ALL EXISTING
OPENINGS.
C THE CONTRACTOR SHALL REVIEW ALL SHEETS WITHIN THE CONSTRUCTION
DOCUMENTS AND SPECIFICATIONS TO ENSURE THE FULL SCOPE OF WORK IS
COORDINATED.
D THE STOREFRONT BASE BID WILL BE A NON-IMPACT RATED STOREFRONT SYSTEM
WITH FIXED INSULATED GLAZING. THE CONTRACTOR SHALL PROVIDE A BID
ALTERNATE COST FOR AN IMPACT RATED STOREFRONT SYSTEM WITH IMPACT
RATED GLAZING. REFER TO SPECIFICATION FOR EACH SYSTEM.
E REFER TO SHEET S-001 FOR DESIGN WIND LOADS.
F CONTRACTOR SHALL REFER TO THE SPECIFICATIONS FOR EACH SYSTEM.
G ALL ALUMINUM FLASHINGS SHALL MATCH THE STOREFRONT IN COLOR.
H DIMENSIONS SHOWN ON THE WINDOW ELEVATIONS INDICATE THE SIZE OF THE
EXISTING MASONRY OPENING. STOREFRONT FRAME SIZES SHALL BE NOTED ON
THE REQUIRED SHOP DRAWINGS FOR REVIEW AND APPROVAL.
SCALE: 3" = 1'-0"A601
A9 STOREFRONT JAMB DETAIL AT COL.
BASE BID:
MANUFACTURER: KAWNEER OR EQUAL
MODEL: TRI FAB VERSA GLAZE 451; CENTER GLAZED
FRAME SIZE: 2" WIDE X 4 1/2" DEEP
FINISH: DARK BRONZE
GLAZING: 1" INSULATED (1/4" TEMPERED, 1/2" AIR SPACE, 1/4" TEMPERED)
FLORIDA PRODUCT APPROVAL: #7237.2
BID ALTERNATE:
MANUFACTURER: KAWNEER OR EQUAL
MODEL: IR 501
FRAME SIZE: 2 1/2" WIDE X 5" DEEP
FINISH: DARK BRONZE
GLAZING: 1 5/16" IMPACT RESISTANT / INSULATED
FLORIDA PRODUCT APPROVAL: #8787.2
STOREFRONT SYSTEMS
SCALE: 1/2" = 1'-0"A601
C7 STOREFRONT ELEVATION 'K'
DESIGN CRITERIA
ALL CONSTRUCTION SHALL CONFORM TO THE MORE RESTRICTIVE OF THE FOLLOWING CODES, THE MOST RECENT EDITIONS OF THE STANDARDS ADOPTED BY THE AUTHORITY HAVING JURISDICTION AS REFERENCED THROUGHOUT THE STRUCTURAL
GENERAL NOTES, AND THE FOLLOWING DESIGN CRITERIA:
BUILDING CODE: 2023 FLORIDA BUILDING CODE (FBC), 8TH EDITION
DESIGN DEAD LOADS: N/A
DESIGN LIVE LOADS: N/A
DESIGN SNOW LOADS: NOT APPLICABLE
DESIGN WIND LOADS:
BUILDING RISK CATEGORY : II
ULTIMATE WIND SPEED (V,ULT) 3 SEC GUST: 139 MILES PER HOUR
NOMINAL WIND SPEED (V,ASD) 3-SECOND GUST: 108 MILES PER HOUR
TORNADO WIND SPEED, (V,T): NOT APPLICABLE FOR SITE LOCATION
EFFECTIVE PLAN AREA FOR TORNADO DESIGN: NOT APPLICABLE FOR SITE LOCATION
WIND EXPOSURE: C
INTERNAL PRESSURE COEFFICIENT: +0.18, -0.18
WIND BORNE DEBRIS REGION: NOT APPLICABLE
COMPONENTS AND CLADDING: SEE WIND PRESSURE KEYPLAN
DESIGN SEISMIC LOADS: NOT APPLICABLE
FLOOD DESIGN DATA: SITE NOT WITHIN FLOOD HAZARD AREA THEREFORE NOT APPLICABLE
DESIGN RAIN LOAD DATA:
PRIMARY DRAINAGE SYSTEMS SHALL BE DESIGNED FOR A RAINFALL INTENSITY EQUAL TO OR GREATER THAN THE 60-MIN DURATION/ 100-YEAR RETURN PERIOD (FREQUENCY) STORM WITH A RAINFALL INTENSITY: “I” = 3.90 IN/HR
RAIN LOAD BASED ON A HYDRAULIC HEAD RAINFALL INTENSITY EQUAL TO OR GREATER THAN THE 15-MIN DURATION/100-YEAR
RETURN PERIOD (FREQUENCY) STORM WITH A RAINFALL INTENSITY: “I” = 7.37 IN/HR
MODIFICATIONS TO EXISTING CONSTRUCTION
THE EXISTING CONSTRUCTION SHOWN ON THESE DRAWINGS IS PROVIDED FOR REFERENCE ONLY. EXISTING CONSTRUCTION SHALL BE VERIFIED IN THE FIELD PRIOR TO FABRICATION AND ERECTION OF ALL NEW CONSTRUCTION.
ANY EXISTING FINISHES REMOVED OR DAMAGED TO ACCOMPLISH ANY STRUCTURAL MODIFICATIONS SHALL BE REINSTATED AT THE
COMPLETION OF MODIFICATION WORK, TYPICAL UNLESS NOTED OTHERWISE.
"a"
"a" "a"
"a"
COMPONENTS AND CLADDING DIAGRAM FOR ALL OTHER
BUILDINGS (FLAT ROOF 0° < θ ≤ 3°) a = 10% OF THE LEAST HORIZONTAL DIMENSION OR 0.4h, WHICHEVER IS SMALLER, BUT NOT LESS THAN EITHER 4% OF THE LEAST HORIZONTAL DIMENSION OR 3 FT (0.9m).
h = MEAN ROOF HEIGHT, FT (m), EXCEPT THAT EAVE HEIGHT SHALL BE USED FOR θ ≤ 10°.
2 2
3 31
"a"
"a"
1'1
DESIGN WIND PRESSURES FOR EXTERIOR COMPONENTS AND
CLADDING MATERIALS (FLAT ROOF)
ROOF SLOPE SURFACE
EFFECTIVE WIND
AREA (SF)
WIND PRESSURE
TOWARD FROM
SURFACE (+PSF)
WIND PRESSURE
AWAY FROM
SURFACE (-PSF)
ZONE 1'
ROOF CENTER
FLAT to 3°
ZONE 2
ROOF PERIMETER
ZONE 3
ROOF CORNER
ZONE 4
WALL
ZONE 5
WALL CORNERS
N/A
ZONE 1
ROOF INNER
PERIMETER
COMPONENTS AND CLADDING WIND PRESSURE NOTES:
1. THE COMPONENTS AND CLADDING WIND LOAD PRESSURES IN THE TABLES ARE BASED ON THE LATEST EDITION OF ASCE 7. THE WIND PRESSURES ARE ULTIMATE LOAD PRESSURES. REFER TO THE GENERAL
NOTES AND DESIGN DATA NOTES FOR WIND LOAD INFORMATION AND PARAMETERS.
2. THE PRESSURES IN THE TABLES BELOW ARE TO BE USED FOR WIND CONTRIBUTION TO THE TOTAL LOAD APPLIED TO ANY COMPONENTS AND CLADDING MEMBER OR MATERIAL WHICH IS PART OF A ROOF
OR EXTERIOR WALL ASSEMBLY.
3. REFER TO CHAPTER 16 OF FBC OR ASCE 7 FOR DEFINITION OF TERMS.
4. CONFIGUARTION OF END ZONES, EDGE STRIPS, AND CORNERS SHALL BE PER ASCE 7.
5. INTERPOLATION FOR EFFECTIVE WIND AREA BETWEEN 10 SF AND 100 SF FOR ROOFS, AND 10 SF AND
500 SF FOR WALLS IS PERMITTED.
6. PRESSURES ARE APPLIED NORMAL TO THE SURFACE OF THE COMPONENT OR CLADDING ELEMENT.
7. POSITIVE AND NEGATIVE PRESSURES ACT SIMULANEOUSLY AT PARAPETS.
8. THE WIDTH OF EDGE STRIP (a) SHALL BE PER THE DIAGRAMS PRESENTED.
38.6 34.6 31.2 28.9
38.6 34.6 31.2 28.9
41.8 37.8 34.4 32.2
51.5 43.5 36.7 32.2
N/A
N/AN/A
N/A
N/A
N/A N/A
N/A
WINDOW ATTACHMENT
FASTENERS SHALL BE A DELEGATED DESIGN, SEE COMPONENTS & CLADDING TABLE FOR WIND PRESSURE REQUIREMENTS.
FASTENERS USED SHALL BE CAPABLE OF ATTACHING TO CONCRETE MASONRY UNIT, CONCRETE AND STRUCTURAL STEEL UP
TO 1/4" THICKNESS.
PROVIDE STAINLESS STEEL FASTENERS FOR EXTERIOR USE OR WHEN EXPOSED TO WEATHER. PROVIDE GALVANIZED CARBON STEEL
ANCHORS AT OTHER LOCATIONS, UNLESS OTHERWISE NOTED.
IF REINFORCEMENT IS ENCOUNTERED DURING DRILLING, ABANDON AND SHIFT THE HOLE LOCATION TO AVOID THE REINFORCEMENT.
PROVIDE A MINIMUM OF 2 ANCHOR DIAMETERS OR 1 INCH, WHICHEVER IS LARGER, OF SOUND CONCRETE BETWEEN THE DOWEL AND THE ABANDONED HOLE. FILL THE ABANDONED HOLE WITH NON-SHRINK GROUT. IF THE ANCHOR OR DOWEL MAY NOT BE SHIFTED AS NOTED, THE ENGINEER WILL DETERMINE A NEW LOCATION. VERIFY BOLT SPACING BY GPR SCANNING (OR SIMILAR METHOD) PRIOR TO
STEEL FABRICATION AND BEGINNING CONSTRUCTION.
USE FASTENERS LESS THAN 1/2 INCH IN DIAMETER. DO NOT CUT OR DAMAGE EXISTING REINFORCING WITHIN THE EXISTING WALL.
ALL POST-INSTALLED ANCHORS SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER’S INSTALLATION INSTRUCTIONS AND
THE APPLICABLE ICC EVALUATION SERVICES REPORT.
WINDOW FRAME ATTACHMENT TO THE
EXISTING CMU OR CONCRETE WALL PER
THE WINDOW MANUFACTURER. WINDOW
MANUFACTURER TO PROVIDE FASTENERS
CAPABLE OF WITHSTANDING THE WIND
LOAD COMPONENTS AND CLADDING
PRESSURES SHOWN ON S-001
WINDOW REPLACEMENT INTO
EXISTING WALL OPENING
EXISTING MASONRY WALL
EXISTING WINDOW SILL, SEE ARCH DWGS
WINDOW ATTACHMENT,
SEE
WINDOW REPLACEMENT INTO
EXISTING WALL OPENING
EXISTING STEEL POST, SEE ARCH DRAWINGS FOR
LOCATION. WINDOW FRAME AND ATTACHMENT TO THE
EXISTING STEEL POST PER THE WINDOW MANUFACTURER.
WINDOW MANUFACTURER TO PROVIDE FASTENERS
CAPABLE OF WITHSTANDING THE WIND LOAD COMPONENTS
AND CLADDING PRESSURES SHOWN ON S-001
/D8 S-001
EXISTING MASONRY WALL
EXISTING WINDOW SILL, SEE ARCH DWGS
SCALE: NOT TO SCALEF9 GENERAL NOTES
SCALE:
DATE:
DRAWN BY:
CHECK BY:
PROJECT NUMBER:
1 2 3 4 5 6 7 8 9 10
H
G
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9 10
ALL REPRODUCTION AND INTELLECTUAL
PROPERTY RIGHTS RESERVED ©
Seal
Client
A C CT T SEH IR
605 E. ROBINSON STREET, SUITE 750
ORLANDO, FL 32801
AR0014284
www.rbarchitects.com 407.648.7288
225 E. Robinson Street. Suite 145 Orlando, Florida 32801 Phone: 407-422-1118
Fax: 407-841-9149 FL. L.B. No. 7513
COA No. 7602 www.cscos.com
As indicated
S-001
STRUCTURAL
GENERAL NOTES AND
WIND PRESSURES &
DETAILS
A. CELLA, PE
C. SIMMERSON
12/11/2025
L68087001
FREDRICK DOUGLASS
DAY CARE CENTER
WINDOW
REPLACEMENT
3688 DAY CARE CENTER RD,
ZELLWOOD, FL 32757
ORANGE COUNTY
GOVERNMENT
BID DOCUMENTS
SCALE: NOT TO SCALEF5 COMPONENTS AND CLADDING
SCALE: 3/4" = 1'-0"D8 TYPICAL WINDOW ATTACHMENT TO EXISTING STRUCTURE - ELEVATION VIEW SCALE: 1/2" = 1'-0"D5 TYPICAL WINDOW ATTACHMENT TO EXISTING STEEL POST - ELEVATION VIEW
| Sheets |
| A101 - FLOOR PLAN & ELEVATIONS |
| A601 - STOREFRONT ELEVATIONS & DETAILS |
| AD101 - DEMOLITION FLOOR PLAN & ELEVATIONS |
| G000 - COVER SHEET |
| G001 - GENERAL INFORMATION |
File details come from the government source that posted it. Updated .