The document is a comprehensive set of architectural and engineering drawings for the Orange County Sheriff's Sector IV Electrical & Lighting Upgrades project located at 2400 West 33rd Street in Orlando, Florida. The project involves extensive electrical infrastructure improvements, including the installation of a new utility service, construction of a new shield wall for an outdoor electrical equipment courtyard, and replacement of the existing emergency generator. The project includes a base bid and an alternate bid option, with the alternate bid featuring replacement of interior lighting fixtures with LED luminaires and a potential switch from a diesel to a natural gas generator. The project is scheduled for bid submission on October 17, 2024, with an estimated total project cost of $1,600,000.00.
The electrical upgrades encompass multiple key components, including removing the existing building standby generator, fuel tank, and automatic transfer switch, and constructing a new emergency electrical equipment closet. The project will implement a new emergency power system with an automatic transfer switch, emergency power panelboard, and new conduit and wiring throughout the building. The alternate bid offers additional flexibility with options for LED lighting and generator fuel type. The project will be conducted using electronic bid submissions through the OpenGov e-Procurement Platform, with technical support available for potential bidders. Questions about the solicitation must be submitted by September 19, 2024, through the platform's question and answer module.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
G-1
COVER SHEET
Engineering | Planning | Allied Services
Offices Nationwide www.hanson-inc.com
Hanson Professional Services Inc.
2300 Maitland Center Pkwy.
Maitland, FL 32751
(407) 790-7397
CONSULTANTS
EB0007061
AA0003116
IB0001058
ORANGE COUNTY
SHERIFF'S SECTOR IV
ELECTRICAL &
LIGHTING UPGRADES
2400 West 33rd Street Orlando, FL 32839
SHEET TITLE
REVIEWED BY:
DRAWN BY:
DESIGN BY:
PROJECT NO:
ISSUE:
© Copyright Hanson Professional Services Inc. 2024
06/10/2024 17G0191A
9/
/2
:3 1:
A
M Fi le P at h
54321 6
E
D
C
B
A
54321 6
BID DOCUMENTS
MARK DATE DESCRIPTION
Suite 310
SEAL
This item has been digitally signed and sealed by Austin J. Thompson P.E. on the date listed using a digital signature.
Printed copies of this document are not considered sign and sealed and the SHA authentication code must be verified on any electronic copies.DRAWING INDEX
2400 West 33rd Street Orlando, FL 32804
BID DOCUMENTS
JUNE 10, 2024
ORANGE COUNTY SHERIFF'S SECTOR IV BUILDING
ELECTRICAL & LIGHTING UPGRADES
HANSON PROFESSIONAL SERVICES INC.
2300 Maitland Center Parkway, Suite 310
Maitland, FL 32751
(407) 790-7397
CODES IN EFFECT AT TIME OF DRAWING SUBMITTAL
FLORIDA BUILDING CODE, EIGHTH EDITION (2023)
FLORIDA ENERGY CONSERVATION CODE, EIGHTH EDITION (2023)
NEC (NFPA 70) 2020 EDITION
TO THE BEST OF THE ENGINEER'S KNOWLEDGE, THE PLANS AND
SPECIFICATIONS COMPLY WITH THE 2023 FLORIDA BUILDING CODE WITH ALL
CURRENT AMENDMENTS.
MEP ENGINEERS
ORANGE COUNTY MAYOR
Jerry L. Demings
DISTRICT 1 COMMISSIONER
Nicole Wilson
DISTRICT 2 COMMISSIONER
Christine Moore
DISTRICT 5 COMMISSIONER
Emily Bonilla
DISTRICT 6 COMMISSIONER
Michael "Mike" Scott
DISTRICT 4 COMMISSIONER
Maribel Gomez Cordero
DISTRICT 3 COMMISSIONER
Mayra Uribe
PROJECT LOCATION
N
G-1
ARCH. GENERAL INFORMATIONA-001
A-002
ABBREVIATIONS SYMBOLS & SHEET INDEXS-001
STRUCTURAL GENERAL NOTESS-002
LEGEND AND ABBREVIATIONSE-001
FIRST FLOOR POWER DEMOLITION PLANE-010
SECOND FLOOR POWER DEMOLITION PLAN
ELECTRICAL DETAILS
E-011
E-201
E-202
E-101 E-102 E-110
E-201A
E-202A E-211 E-212 E-501
ONE-LINE DIAGRAM - WORK SEQUENCE NO. 1
E-601 E-602 E-603 E-604
EXISTING PANELBOARD SCHEDULESE-610
EXISTING PANELBOARD SCHEDULESE-611
PROPOSED PANELBOARD SCHEDULESE-620
COVER SHEET
FIRST FLOOR LIGHTING PLAN - BASE BID
SECOND FLOOR LIGHTING PLAN - BASE BID
FIRST FLOOR POWER PLAN
SECOND FLOOR POWER PLAN
FIRST FLOOR LIGHTING PLAN - ALTERNATE BID
SECOND FLOOR LIGHTING PLAN - ALTERNATE BID
PARTIAL FIRST FLOOR PLAN
FIRST FLOOR LIGHTING CONTROLS PLAN
SECOND FLOOR LIGHTING CONTROLS PLAN
EXISTING AND PROPOSED ONE-LINE DIAGRAMS
A-003
LIFE SAFETYA-100
DEMOLITION AND RENOVATION FLOOR PLANSA-110
FOUNDATION PLAN
SECTIONS AND DETAILS
S-101 S-301
RCP - DEMOLITION
A-211
MISC. SCHEDULES AND DETAILSA-310
DEMO PLANSD-101
ARCH. SPECIFICATIONS
ARCH. SPECIFICATIONS
A-210
A-006 A-005 A-004
ARCH. SPECIFICATIONS
UL 2 HR WALL ASSEMBLY
UL 2 HR WALL ASSEMBLY
RCP - RENOVATION
MECHANICAL NOTES, LEGENDS, AND ABBREVIATIONSM-001
1214 East Concord Street Orlando, FL 32803
(407) 377-7227
ARCHITECT
STRUCTURAL
ENGINEERS
FIRST FLOOR MECHANICAL PLAN - ENLARGED - DEMOLITIONMD-301
FIRST FLOOR MECHANICAL PLAN - OVERALLM-100
FIRST FLOOR MECHANICAL PLAN - ENLARGED - RENOVATIONM-301
DETAILSM-501
SCHEDULESM-601
ONE-LINE DIAGRAM - WORK SEQUENCE NO. 2
ONE-LINE DIAGRAM - WORK SEQUENCE NO. 3
SCOPE OF WORK - SUMMARY
1. NEW UTILITY SERVICE FOR BUILDING.
2. NEW SHIELD WALL SURROUNDING NEW OUTDOOR ELECTRICAL EQUIPMENT
COURTYARD.
3. NEW EMERGENCY GENERATOR, OUTDOOR RATED GENERATOR SWITCHBOARD,
AND OUTDOOR RATED AUTOMATIC TRANSFER SWITCH. GENERATOR SHALL BE
DIESEL WITH SUB-BASE TANK.
4. MODIFICATIONS TO EXISTING BUILDING EXTERIOR WALL AND MAIN DISTRIBUTION
PANEL MDP AS REQUIRED FOR NEW AUTOMATIC TRANSFER SWITCH.
5. REMOVAL OF EXISTING BUILDING STANDBY GENERATOR, FUEL TANK, AUTOMATIC
TRANSFER SWITCH, AND STANDBY POWER DISTRIBUTION PANELBOARDS.
6. CONSTRUCTION OF NEW EMERGENCY ELECTRICAL EQUIPMENT CLOSET IN
CORNER OF EXISTING FIRST FLOOR BREAK ROOM.
7. NEW EMERGENCY POWER SYSTEM FOR BUILDING CONSISTING OF AUTOMATIC
TRANSFER SWITCH, EMERGENCY POWER PANELBOARD, EMERGENCY POWER
TRANFORMER/LOAD CENTER, AND NEW EMERGENCY POWER CONDUIT AND WIRE
THROUGHOUT THE BUILDING TO SUPPLY EXISTING AND NEW LOADS DESIGNATED
AS EMERGENCY LOADS.
8. NEW 208Y/120V DISTRIBUTION PANELBOARD AND FEEDERS FROM NEW
DISTRIBUTION PANELBOARD TO EXISTING BUILDING BRANCH CIRCUIT
PANELBOARDS.
9. REMOVAL AND MODIFICATION OF EXISTING BUILDING BRANCH PANELBOARD
INTERIORS AND PROVIDING NEW PANELBOARD INTERIORS INSIDE EXISTING
PANELBOARD ENCLOSURES.
10. HVAC MODIFICATIONS TO SUPPORT THE ELECTRICAL CHANGES.
BID ALTERNATE - REFER TO SPECIFICATION SECTION 01 23 00:
1. REPLACEMENT OF EXISTING INTERIOR LIGHTING FIXTURES THROUGHOUT THE
BUILDING WITH NEW LED INTERIOR LUMINAIRES. NEW ADDRESSABLE LIGHTING
CONTROL SYSTEM THROUGHOUT THE BUILDING.
2. IN LIEU OF DIESEL GENERATOR, PROVIDE NATURAL GAS GENERATOR. PROVIDE
NATURAL GAS PIPING AND ACCESSORIES FROM EXISTING CAPPED NATURAL GAS
LINE.
PROPOSED PANEL EM & TLC-EM SCHEDULES - ALTERNATE BIDE-620A
A-007 UL 2 HR FLOOR-CEILING ASSEMBLY
GTR
AJT
BM/CRB
FIXTURE SCHEDULESE-630
PROPOSED PANELBOARD SCHEDULESE-621
FIRST FLOOR LIGHTING DEMOLITION PLAN - ALTERNATE BIDE-020A
SECOND FLOOR LIGHTING DEMOLITION PLAN - ALTERNATE BIDE-021A
* FRAMING INSPECTION: ALL PLUMBING,
ELECTRICAL AND MECHANICAL ROUGH-INS MUST BE
COMPLETED, INSPECTED AND APPROVED BEFORE
REQUESTING THE FRAMING INSPECTIONS.
FBC INSPECTIONS
SITE GRADE ELEVATIONS WILL REMAIN AS EXISTING
UNLESS NOTED OTHERWISE.
GRADE ELEVATIONS
THE MAIN ARCHITECTURAL SCOPE OF WORK CONSISTS OF :
1- THERE IS NO CHANGE OF USE WITHIN THE SCOPE OF THIS WORK.
2- THERE IS NO ARCHITECTURAL SCOPE OF WORK AT 2ND FLOOR NOR ROOF FLOOR.
3- PROVIDE DEMOLITION AS REQUIRED TO CREATE A NEW 8' X 3' ELECTRICAL EQUIPMENT CLOSET/ROOM
WITHIN AN EXISTING BREAKROOM. FINISH TO MATCH EXISTING SPACE.
4- NEW ACOUSTIC PANELS CEILING ON EXISTING BREAK ROOM.
5- ALL EXISTING LIGHT FIXTURES TO BE REPLACED BY LED LIGHT FIXTURES, INCLUDING LIFE SAFETY FIXTURES AND EXIT SIGNS.
6- RELOCATE EXISTING AIR SUPPLY GRILL. CUT AND PATCH OPENINGS AS REQUIRED.
FINISH TO MATCH ADJACENT SURFACES.
7- DEMOLISH TWO EXTERIOR "WING" DETAILS ON THE FRONT ELEVATION OF THE EXISTING BUILDING.
8. PROVIDE NEW GENERATOR AREA BE ENCLOSED BY A CMU WALL. REFER TO STRUCTURAL SHEETS FOR DETAILS.
FINISH TO MATCH EXISTING BUILDING. ADD NEW 12'-0" FENCE W/PRIVACY SLATS AND SWING GATES.
9. THE PROJECT SCOPE INCLUDES MECHANICAL RENOVATION IN OTHER AREAS. PROVIDE NECESSARY REPAIR AND FINSHES TO
MATCH EXISTING. REFER TO MECHANICAL DRAWINGS.
10. THE PROJECT SCOPE INCLUDES ELECTRICAL RENOVATION IN OTHER AREAS. PROVIDE NECESSARY REPAIR AND FINSHES TO
MATCH EXISTING. REFER TO ELECTRICAL DRAWINGS.
A-001
INFORMATION
ARCH. GENERAL
54321 6
E
D
C
B
A
54321 6
Engineering | Planning | Allied Services
Offices Nationwide www.hanson-inc.com
Hanson Professional Services Inc.
2300 Maitland Center Pkwy.
Maitland, FL 32751
(407) 790-7397
CONSULTANTS
EB0007061
AA0003116
IB0001058
ORANGE COUNTY
SHERIFF'S SECTOR IV
ELECTRICAL &
LIGHTING UPGRADES
2400 West 33rd Street
Orlando, FL 32839
SHEET TITLE
REVIEWED BY:
DRAWN BY:
DESIGN BY:
PROJECT NO:
ISSUE:
© Copyright Hanson Professional Services Inc. 2020
05/24/24
17G0191A
BID DOCUMENTS
MARK DATE DESCRIPTION
Suite 310
DAT
SF
DOMINGO R. FORNOLES AR 94278
A
M
F i l e
P a t h
ABBREVIATIONS DIMENSIONING
SYMBOLS ARCHITECTURAL GENERAL NOTESMATERIALS LEGEND ARCHITECTURAL GENERAL NOTESMATERIALS LEGEND
ABBREVIATIONS DIMENSIONING
SYMBOLS MATERIALS LEGEND
SCOPE OF WORK
A-002
SPECIFICATIONS
ARCHITECTURAL
D
C
B
A
54321 6
Engineering | Planning | Allied Services
Offices Nationwide www.hanson-inc.com
Hanson Professional Services Inc.
2300 Maitland Center Pkwy.
Maitland, FL 32751
(407) 790-7397
CONSULTANTS
EB0007061
AA0003116
IB0001058
ORANGE COUNTY
SHERIFF'S SECTOR IV
ELECTRICAL &
LIGHTING UPGRADES
2400 West 33rd Street
Orlando, FL 32839
SHEET TITLE
REVIEWED BY:
DRAWN BY:
DESIGN BY:
PROJECT NO:
ISSUE:
© Copyright Hanson Professional Services Inc. 2020
05/24/24
17G0191A
BID DOCUMENTS
MARK DATE DESCRIPTION
Suite 310
DAT
SF
DOMINGO R. FORNOLES AR 94278
A
M
F i l e
P a t h
D.
B.
C.
DIVISION 8 - OPENINGS
SECTION 08 12 13 - HOLLOW METAL FRAMES
A. GENERAL: COMPLY WITH SDI A250.8.-2017 (ANSI/SDI-100) AND WITH
DETAILS INDICATED FOR TYPE AND PROFILE.
1.
2.
3.
INTERIOR FRAMES: FABRICATED FROM COLD-ROLLED
STEEL SHEET FOR LEVEL 3
HARDWARE REINFORCEMENT: FABRICATE ACCORDING TO
ANSI/SDI A250.6 WITH REINFORCEMENT PLATES FROM SAME
MATERIAL AS FRAMES.
EXISTING FRAMES SHALL BE CLEANED, PREPARED, AND
RELOCATED TO NEW OPENINGS AS DIRECTED BY THE OWNER
FROM THE EXISTING PROJECT.
COORDINATE ANCHORAGE INSTALLATION FOR HOLLOW-METAL
FRAMES. FURNISH SETTING DRAWINGS, TEMPLATES, AND
DIRECTIONS FOR INSTALLING ANCHORAGES INTO EXISTING STEEL.
DELIVER SUCH ITEMS TO PROJECT SITE IN TIME FOR INSTALLATION.
MANUFACTURERS:
OBTAIN HOLLOW-METAL WORK FROM SINGLE SOURCE FROM
SINGLE MANUFACTURER. SUBJECT TO COMPLIANCE WITH
REQUIREMENTS, AVAILABLE MANUFACTURERS OFFERING
PRODUCTS THAT MAY BE INCORPORATED INTO THE WORK
INCLUDE, BUT ARE NOT LIMITED TO, THE FOLLOWING:
1.
2.
3.
4.
STEELCRAFT; AN INGERSOLL-RAND COMPANY.
FIREDOOR CORPORATION OF FLORIDA.
CECO DOOR PRODUCTS; AN ASSA ABLOY GROUP COMPANY.
REPUBLIC BUILDER PRODUCTS COMPANY
EXTERIOR FRAMES: FABRICATED FROM METALLIC-COATED
STEEL SHEET FOR LEVEL 3 STEEL DOORS, 0.060-INCH-THICK
STEEL SHEET BASE METAL PRIOR TO GALVANIZING;
FABRICATE FRAMES WITH MITERED OR COPED CORNERS.
DIVISION 8 - OPENINGS
b.
N.
M.
L.
ANCHORS AS FOLLOWS:
a. STUD-WALL TYPE: LOCATE ANCHORS NOT MORE
THAN 18 INCHES FROM TOP AND BOTTOM OF FRAME.
SPACE ANCHORS NOT MORE THAN 32 INCHES O.C.
AND AS FOLLOWS:
1. TWO ANCHORS PER JAMB UP TO 60 INCHES
HIGH.
2.
3.
THREE ANCHORS PER JAMB FROM 60 TO 90
INCHES HIGH.
FOUR ANCHORS PER JAMB FROM 90 TO 96
INCHES HIGH.
POSTINSTALLED EXPANSION TYPE: LOCATE
ANCHORS NOT MORE THAN 6 INCHES (152 MM) FROM
TOP AND BOTTOM OF FRAME. SPACE ANCHORS NOT
MORE THAN 26 INCHES (660 MM) O.C.
PRIME FINISH: CLEAN, PRETREAT, AND APPLY MANUFACTURER'S
STANDARD PRIMER.
1. SHOP PRIMER: MANUFACTURER'S STANDARD, FAST-CURING,
LEAD- AND CHROMATE-FREE PRIMER COMPLYING WITH SDI
A250.10 ACCEPTABLE CRITERIA; RECOMMENDED BY PRIMER
MANUFACTURER FOR SUBSTRATE; COMPATIBLE WITH
SUBSTRATE AND FIELD-APPLIED COATINGS DESPITE
PROLONGED EXPOSURE.
INSTALLATION: INSTALL HOLLOW-METAL WORK PLUMB, RIGID,
PROPERLY ALIGNED, AND SECURELY FASTENED IN PLACE. COMPLY
WITH DRAWINGS AND MANUFACTURER'S WRITTEN INSTRUCTIONS.
1.
2.
3.
SOLIDLY PACK MINERAL-FIBER INSULATION INSIDE FRAMES
OF METAL STUD PARTITIONS.
INSTALLATION SHALL REQUIRE ADJUSTMENT OF HOLLOW-
METAL DOOR FRAMES FOR PROPER FUNCTIONING
HARDWARE: REQUIRE FLOOR SHIPPING SPACER TO REMAIN
UNTIL DOOR IS INSTALLED. COORDINATE FOR
UNDERCUTTING PER DIVISION 15.
4.
5.
DOUBLE STUDS SHALL BE REQUIRED AT JAMBS FOR WIDTHS
OF 36 INCHES OR GREATER.
STANDARD HEIGHT OF DOOR OPENING IS 7’-0”.
FINAL ADJUSTMENTS: REMOVE AND REPLACE DEFECTIVE WORK,
INCLUDING HOLLOW-METAL WORK THAT IS WARPED, BOWED, OR
OTHERWISE UNACCEPTABLE; PRIME-COAT TOUCHUP: IMMEDIATELY
AFTER ERECTION, SAND SMOOTH RUSTED OR DAMAGED AREAS OF
PRIME COAT AND APPLY TOUCHUP OF COMPATIBLE AIR-DRYING,
RUST-INHIBITIVE PRIMER.
END OF SECTION 08 12 13
SECTION 08 14 16 - FLUSH WOOD DOORS
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
1.3
A.
B.
1.4
A.
A.
1.2
A.
DRAWINGS AND GENERAL PROVISIONS OF THE CONTRACT,
INCLUDING GENERAL AND SUPPLEMENTARY CONDITIONS AND
DIVISION 01 SPECIFICATION SECTIONS, APPLY TO THIS SECTION.
SUMMARY
SECTION INCLUDES:
1.
2.
3.
SOLID-CORE FLUSH WOOD-VENEER DOORS.
FACTORY FINISHING FLUSH WOOD DOORS.
FACTORY FITTING FLUSH WOOD DOORS TO FRAMES AND
FACTORY MACHINING FOR HARDWARE.
ACTION SUBMITTALS
PRODUCT DATA: FOR EACH TYPE OF PRODUCT. INCLUDE DETAILS
OF CORE AND EDGE CONSTRUCTION AND TRIM OPENINGS. INCLUDE
FACTORY-FINISHING SPECIFICATIONS.
SAMPLES FOR INITIAL SELECTION: FOR FACTORY-FINISHED DOORS.
QUALITY ASSURANCE
MANUFACTURER'S CERTIFICATION: LICENSED PARTICIPANT IN AWI'S
QUALITY CERTIFICATION PROGRAM.
HOLLOW-METAL FRAMES: INSTALL HOLLOW-METAL FRAMES
OF SIZE AND PROFILE INDICATED. COMPLY WITH SDI A250.11
OR NAAMM-HMMA 840 AS REQUIRED BY STANDARDS
SPECIFIED.
2.2
B.
A.
2.
3.
1.5
A.
B.
C.
1.6
A.
B. VENDOR QUALIFICATIONS: A VENDOR THAT IS CERTIFIED FOR CHAIN
OF CUSTODY BY FORESTRY STEWARDSHIP COUNCIL FSC-
ACCREDITED CERTIFICATION BODY (FSC) FOR CERTIFIED WOOD
PRODUCTS. VENDOR COMPANIES WILL BE CONSIDERED AND
EVALUATED USING THE FSC CERTIFIED DATABASE:
HTTPS://US.FSC.ORG/FSC-CERTIFICATE-DATABASE.311.HTM.
DELIVERY, STORAGE, AND HANDLING
COMPLY WITH REQUIREMENTS OF REFERENCED STANDARD AND
MANUFACTURER'S WRITTEN INSTRUCTIONS.
PACKAGE DOORS INDIVIDUALLY IN PLASTIC BAGS OR CARDBOARD
CARTONS.
MARK EACH DOOR ON BOTTOM RAIL WITH OPENING NUMBER USED
ON SHOP DRAWINGS.
FIELD CONDITIONS
ENVIRONMENTAL LIMITATIONS: DO NOT DELIVER OR INSTALL
DOORS UNTIL SPACES ARE ENCLOSED AND WEATHERTIGHT, WET-
WORK IN SPACES IS COMPLETE AND DRY, AND HVAC SYSTEM IS
OPERATING AND MAINTAINING AMBIENT TEMPERATURE AND
RELATIVE HUMIDITY CONDITIONS AT OCCUPANCY LEVELS
DESIGNED FOR BUILDING OCCUPANTS FOR THE REMAINDER OF
CONSTRUCTION PERIOD.
1.7
A.
WARRANTY
SPECIAL WARRANTY: MANUFACTURER AGREES TO REPAIR OR
REPLACE DOORS THAT FAIL IN MATERIALS OR WORKMANSHIP
WITHIN SPECIFIED WARRANTY PERIOD.
1. FAILURES INCLUDE, BUT ARE NOT LIMITED TO, THE
FOLLOWING:
a.
b.
DELAMINATION OF VENEER.
WARPING (BOW, CUP, OR TWIST) MORE THAN 1/4
INCH IN A 42-BY-84-INCH SECTION.
c. TELEGRAPHING OF CORE CONSTRUCTION IN FACE
VENEERS EXCEEDING 0.01 INCH IN A 3-INCH SPAN.
WARRANTY SHALL ALSO INCLUDE INSTALLATION AND
FINISHING THAT MAY BE REQUIRED DUE TO REPAIR OR
REPLACEMENT OF DEFECTIVE DOORS.
WARRANTY PERIOD FOR SOLID-CORE INTERIOR DOORS: LIFE
OF INSTALLATION.
PART 2 - PRODUCTS
2.1
A.
MANUFACTURERS
SOURCE LIMITATIONS: OBTAIN FLUSH WOOD DOORS FROM SINGLE
MANUFACTURER; SUBJECT TO COMPLIANCE REQUIREMENTS,
PROVIDE PRODUCTS BY THE FOLLOWING:
1.
2.
MARSHFIELD-ALGOMA, SIGNATURE SERIES OR EQUAL.
ALTERNATIVE MANUFACTURER BY OWNER.
VENEER-FACED DOORS FOR TRANSPARENT FINISH
QUALITY STANDARD: IN ADDITION TO REQUIREMENTS SPECIFIED,
COMPLY WITH AWI/AWMAC/WI “ARCHITECTURAL WOODWORK
STANDARDS”.
1.
INTERIOR SOLID-CORE DOORS
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
AWI PREMIUM GRADE, WITH GRADE AA FACES.
VENEER SHALL BE CLEAR AND WITHOUT DARK SPOTS OR
STREAKS.
SPECIES: TYPE/CUT TO MATCH THAT OF EXISTING PROJECT
BUILDING INTERIOR WOOD DOORS.
CUT: RIFT CUT.
MATCH BETWEEN VENEER LEAVES: BOOK MATCH.
ASSEMBLY OF VENEER LEAVES ON DOOR FACES: RUNNING
MATCH.
ROOM MATCH: MATCH DOOR FACES WITHIN EACH
SEPARATE ROOM OR AREA OF BUILDING. CORRIDOR DOOR
FACES DO NOT NEED TO MATCH WHERE THEY ARE
SEPARATED BY 10 FEET OR MORE.
ROOM MATCH: PROVIDE DOOR FACES OF COMPATIBLE
COLOR AND GRAIN WITHIN EACH SEPARATE ROOM OR AREA
OF BUILDING.
EXPOSED VERTICAL AND TOP EDGES: SAME SPECIES AS
FACE OR COMPATIBLE SPECIES EDGE TYPE A.
CORE: GLUED WOOD STAVE; ADHESIVES: TYPE I IN
ACCORDANCE WITH WDMA T.M. 6.
CONSTRUCTION: FIVE PLIES, HOT-PRESSED BONDED
(VERTICAL AND HORIZONTAL EDGING IS BONDED TO CORE),
WITH ENTIRE UNIT ABRASIVE PLANED BEFORE VENEERING.
PROVIDE AWI QUALITY CERTIFICATION LABELS INDICATING
THAT DOORS COMPLY WITH REQUIREMENTS OF GRADE
SPECIFIED.
DIVISION 8 - OPENINGS
REFER TO HARDWARE SCHEDULE ON SHEET A-310.
END OF SECTION 08 14 16
SECTION 087100 ï DOOR HARDWARE
DIVISION 09 - FINISHES
2.
B.
C.
2.
3.
4.
5.
2.02 METAL FRAMING MATERIALS
A. NON-LOADBEARING FRAMING SYSTEM COMPONENTS: ASTM C645;
GALVANIZED SHEET STEEL, OF SIZE AND PROPERTIES NECESSARY
TO COMPLY WITH ASTM C754 FOR THE SPACING INDICATED, WITH
MAXIMUM DEFLECTION OF WALL FRAMING OF L/240 AT 5 PSF.
1. EXCEPTION: THE MINIMUM METAL THICKNESS AND SECTION
PROPERTIES REQUIREMENTS OF ASTM C 645 ARE WAIVED
PROVIDED STEEL OF 40 KSI MINIMUM YIELD STRENGTH IS
USED, THE METAL IS CONTINUOUSLY DIMPLED, THE
EFFECTIVE THICKNESS IS AT LEAST TWICE THE BASE METAL
THICKNESS, AND MAXIMUM STUD HEIGHTS ARE
DETERMINED BY TESTING IN ACCORDANCE WITH ASTM E 72
USING ASSEMBLIES SPECIFIED BY ASTM C 754.
STUDS: "C" SHAPED WITH FLAT OR FORMED WEBS WITH
KNURLED FACES.
RUNNERS: U SHAPED, SIZED TO MATCH STUDS.
CEILING CHANNELS: C SHAPED.
FURRING: HAT-SHAPED SECTIONS, MINIMUM DEPTH AS
NOTED ON THE DRAWINGS.
CEILING HANGERS: TYPE AND SIZE AS SPECIFIED IN ASTM C754 FOR
SPACING REQUIRED.
PARTITION HEAD TO STRUCTURE CONNECTIONS: PROVIDE
MECHANICAL ANCHORAGE DEVICES THAT ACCOMMODATE
DEFLECTION USING SLOTTED HOLES, SCREWS AND ANTI-FRICTION
BUSHINGS, PREVENTING ROTATION OF STUDS WHILE MAINTAINING
STRUCTURAL PERFORMANCE OF PARTITION.
1. STRUCTURAL PERFORMANCE: MAINTAIN LATERAL LOAD
RESISTANCE AND VERTICAL MOVEMENT CAPACITY
REQUIRED BY APPLICABLE CODE, WHEN EVALUATED IN
ACCORDANCE WITH AISI NORTH AMERICAN SPECIFICATION
FOR THE DESIGN OF COLD-FORMED STEEL STRUCTURAL
MEMBERS.
MATERIAL: ASTM A653/A653M STEEL SHEET, SS GRADE
PART 2 - PRODUCTS
2.01 GYPSUM BOARD ASSEMBLIES
A.
B.
D.
K.
L.
M.
N.
O.
P.
Q.
R.
S.
T.
U.
I.
J.
DIVISION 9 - FINISHES
SECTION 09 2913 GYPSUM BOARD ASSEMBLIES
PART 1 - GENERAL
1.01 SECTION INCLUDES
A.
B.
C.
D.
E.
METAL CHANNEL CEILING FRAMING.
GYPSUM WALLBOARD.
JOINT TREATMENT AND ACCESSORIES.
1.03 REFERENCE STANDARDS
A.
B.
C.
D.
E.
F.
G.
H.
AISI SG02-1 - NORTH AMERICAN SPECIFICATION FOR THE DESIGN OF
COLD-FORMED STEEL STRUCTURAL MEMBERS; AMERICAN IRON
AND STEEL INSTITUTE; 2001 WITH 2004 SUPPLEMENT. (REPLACED
SG-971)
ANSI A108.11 - AMERICAN NATIONAL STANDARD FOR INTERIOR
INSTALLATION OF CEMENTITIOUS BACKER UNITS; 2013.1.
ANSI A118.9 - AMERICAN NATIONAL STANDARD SPECIFICATIONS FOR
TEST METHODS AND SPECIFICATIONS FOR CEMENTITIOUS BACKER
UNITS; 2013.1.
ASTM A653/A653M - STANDARD SPECIFICATION FOR STEEL SHEET,
ZINC-COATED (GALVANIZED) OR ZINC-IRON ALLOY-COATED
(GALVANNEALED) BY THE HOT-DIP PROCESS; 2013.
ASTM C475/C475M - STANDARD SPECIFICATION FOR JOINT
COMPOUND AND JOINT TAPE FOR FINISHING GYPSUM BOARD; 2012.
ASTM C645 - STANDARD SPECIFICATION FOR NONSTRUCTURAL
STEEL FRAMING MEMBERS; 2013.
ASTM C665 - STANDARD SPECIFICATION FOR MINERAL-FIBER
BLANKET THERMAL INSULATION FOR LIGHT FRAME CONSTRUCTION
AND MANUFACTURED HOUSING; 2012.
ASTM C754 - STANDARD SPECIFICATION FOR INSTALLATION OF
STEEL FRAMING MEMBERS TO RECEIVE SCREW-ATTACHED GYPSUM
PANEL PRODUCTS; 2011.
ASTM C840 - STANDARD SPECIFICATION FOR APPLICATION AND
FINISHING OF GYPSUM BOARD; 2013.
ASTM C954 - STANDARD SPECIFICATION FOR STEEL DRILL SCREWS
FOR THE APPLICATION OF GYPSUM PANEL PRODUCTS OR METAL
PLASTER BASES TO STEEL STUDS FROM 0.033 IN. (0.84 MM) TO 0.112
IN. (2.84 MM) IN THICKNESS; 2011.
ASTM C1002 - STANDARD SPECIFICATION FOR STEEL SELF-PIERCING
TAPPING SCREWS FOR THE APPLICATION OF GYPSUM PANEL
PRODUCTS OR METAL PLASTER BASES TO WOOD STUDS OR STEEL
STUDS; 2007 (REAPPROVED 2013).
ASTM C1047 - STANDARD SPECIFICATION FOR ACCESSORIES FOR
GYPSUM WALLBOARD AND GYPSUM VENEER BASE; 2010A.
ASTM C1177/C1177M - STANDARD SPECIFICATION FOR GLASS MAT
GYPSUM SUBSTRATE FOR USE AS SHEATHING; 2013.
ASTM C1280 - STANDARD SPECIFICATION FOR APPLICATION OF
GYPSUM SHEATHING; 2013.
ASTM C1325 - STANDARD SPECIFICATION FOR NON-ASBESTOS
FIBER-MAT REINFORCED CEMENT SUBSTRATE SHEETS; 2008B.
ASTM C1396/C1396M - STANDARD SPECIFICATION FOR GYPSUM
BOARD; 2014.
ASTM D3273 - STANDARD TEST METHOD FOR RESISTANCE TO
GROWTH OF MOLD ON THE SURFACE OF INTERIOR COATINGS IN AN
ENVIRONMENTAL CHAMBER; 2012.
ASTM E72 - STANDARD TEST METHODS OF CONDUCTING STRENGTH
TESTS OF PANELS FOR BUILDING CONSTRUCTION; 2010.
GA-216 - APPLICATION AND FINISHING OF GYPSUM BOARD; GYPSUM
ASSOCIATION; 2013.
GA-600 - FIRE RESISTANCE DESIGN MANUAL; GYPSUM ASSOCIATION;
2012.
UL (FRD) - FIRE RESISTANCE DIRECTORY; UNDERWRITERS
LABORATORIES INC.; CURRENT EDITION.
1.04 SUBMITTALS
A.
B.
C.
SEE SECTION 01 3000 FOR SUBMITTAL PROCEDURES.
PRODUCT DATA: PROVIDE DATA ON METAL FRAMING, GYPSUM
BOARD ACCESSORIES, AND JOINT FINISHING SYSTEM.
PRODUCT DATA: PROVIDE MANUFACTURER'S DATA ON PARTITION
HEAD TO STRUCTURE CONNECTORS, SHOWING COMPLIANCE WITH
REQUIREMENTS.
TEST REPORTS: FOR ALL STUD FRAMING PRODUCTS THAT DO NOT
COMPLY WITH ASTM C645 OR C754, PROVIDE INDEPENDENT
LABORATORY REPORTS SHOWING MAXIMUM STUD HEIGHTS AT
REQUIRED SPACINGS AND DEFLECTIONS.
1.05 QUALITY ASSURANCE
A. INSTALLER QUALIFICATIONS: COMPANY SPECIALIZING IN
PERFORMING GYPSUM BOARD APPLICATION AND FINISHING, WITH
MINIMUM 5 YEARS OF DOCUMENTED EXPERIENCE.
PERFORMANCE CRITERIA FOR GYPSUM BOARD ASSEMBLIES.
METAL STUD WALL FRAMING.
PROVIDE COMPLETED ASSEMBLIES COMPLYING WITH ASTM C840
AND GA-216.
FIRE RATED ASSEMBLIES: PROVIDE WHERE INDICATE, COMPLETED
ASSEMBLIES AS FOLLOWS:
1. UL ASSEMBLY NUMBERS: PROVIDE CONSTRUCTION
EQUIVALENT TO THAT LISTED FOR THE PARTICULAR
ASSEMBLY IN THE CURRENT UL FIRE RESISTANCE
DIRECTORY.
50/340, WITH G60/Z180 HOT DIPPED GALVANIZED COATING.
END OF SECTION 08 71 00
3.05
B.
C.
2.
3.
A.
B.
C.
3.06
A.
3.
D.
E.
E.
F.
G.
H.
D.
3.
4.
PROVIDE COMPONENTS UL-LISTED FOR USE IN UL-LISTED
FIRE-RATED HEAD OF PARTITION JOINT SYSTEMS INDICATED
ON DRAWINGS.
DEFLECTION AND FIRESTOP TRACK:
a. PROVIDE MECHANICAL ANCHORAGE DEVICES AS
DESCRIBED ABOVE THAT ACCOMMODATE
DEFLECTION WHILE MAINTAINING THE FIRE-RATING
OF THE WALL ASSEMBLY.
2.03 BOARD MATERIALS
A. GYPSUM WALLBOARD: ASTM C 1396/C 1396M. SIZES TO MINIMIZE
JOINTS IN PLACE; ENDS SQUARE CUT
1. REGULAR TYPE:
a.
b.
c.
APPLICATION: USE FOR VERTICAL SURFACES,
UNLESS OTHERWISE INDICATED.
THICKNESS: 5/8 INCH
EDGES: TAPERED.
2.04 ACCESSORIES
A.
B.
C.
ACOUSTIC INSULATION: ASTM C665; PREFORMED GLASS FIBER,
FRICTION FIT TYPE, UNFACED. THICKNESS: 3 INCH MINIMUM.
ACOUSTIC SEALANT: NON-HARDENING, NON-SKINNING, FOR USE IN
CONJUNCTION WITH GYPSUM BOARD.
FINISHING ACCESSORIES: ASTM C1047, GALVANIZED STEEL OR
ROLLED ZINC, UNLESS OTHERWISE INDICATED.
1. TYPES: AS DETAILED OR REQUIRED FOR FINISHED
APPEARANCE.
2. SPECIAL SHAPES: IN ADDITION TO CONVENTIONAL
CORNERBEAD AND CONTROL JOINTS, PROVIDE U-BEAD AT
EXPOSED PANEL EDGES.
JOINT MATERIALS: ASTM C475 AND AS RECOMMENDED BY GYPSUM
BOARD MANUFACTURER FOR PROJECT CONDITIONS
1.
2.
3. READY-MIXED VINYL-BASED JOINT COMPOUND.
SCREWS FOR ATTACHMENT TO STEEL MEMBERS LESS THAN 0.03
INCH IN THICKNESS, TO WOOD MEMBERS, AND TO GYPSUM BOARD:
ASTM C1002; SELF-PIERCING TAPPING TYPE; CADMIUM-PLATED FOR
EXTERIOR LOCATIONS.
SCREWS FOR ATTACHMENT TO STEEL MEMBERS FROM 0.033 TO
0.112 INCH IN THICKNESS: ASTM C954; STEEL DRILL SCREWS FOR
APPLICATION OF GYPSUM BOARD TO LOADBEARING STEEL STUDS.
SCREWS: ASTM C 1002; SELF-PIERCING TAPPING TYPE; CADMIUM-
PLATED FOR EXTERIOR LOCATIONS.
SCREWS: ASTM C 954; STEEL DRILL SCREWS FOR APPLICATION OF
GYPSUM BOARD TO LOADBEARING STEEL STUDS.
PART 3 - EXECUTION
3.01 EXAMINATION
A.
TAPE: 2 INCH WIDE, COATED GLASS FIBER TAPE FOR JOINTS
AND CORNERS, EXCEPT AS OTHERWISE INDICATED.
TAPE: 2 INCH WIDE, CREASED PAPER TAPE FOR JOINTS AND
CORNERS, EXCEPT AS OTHERWISE INDICATED.
VERIFY THAT PROJECT CONDITIONS ARE APPROPRIATE FOR WORK
OF THIS SECTION TO COMMENCE.
3.02 FRAMING INSTALLATION
A.
B.
C.
METAL FRAMING: INSTALL IN ACCORDANCE WITH ASTM C754 AND
MANUFACTURER'S INSTRUCTIONS.
SUSPENDED CEILINGS AND SOFFITS: SPACE FRAMING AND FURRING
MEMBERS AS INDICATED.
STUDS: SPACE STUDS AS PERMITTED BY STANDARD.
1.
2.
EXTEND PARTITION FRAMING TO STRUCTURE WHERE
INDICATED AND TO CEILING IN OTHER LOCATIONS.
PARTITIONS TERMINATING AT CEILING: ATTACH CEILING
RUNNER SECURELY TO CEILING TRACK IN ACCORDANCE
WITH MANUFACTURER'S INSTRUCTIONS.
PARTITIONS TERMINATING AT STRUCTURE: ATTACH TOP
RUNNER TO STRUCTURE, MAINTAIN CLEARANCE BETWEEN
TOP OF STUDS AND STRUCTURE, AND CONNECT STUDS TO
TRACK USING SPECIFIED MECHANICAL DEVICES IN
ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS;
VERIFY FREE MOVEMENT OF TOP OF STUD DEVICES IN
ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS;
VERIFY FREE MOVEMENT OF TOP OF STUD CONNECTIONS;
DO NOT LEAVE STUDS UNATTACHED TO TRACK.
OPENINGS: REINFORCE OPENINGS AS REQUIRED FOR WEIGHT OF
DOORS OR OPERABLE PANELS, USING NOT LESS THAN DOUBLE
STUDS AT JAMBS.
STANDARD WALL FURRING: INSTALL AS SCHEDULED TO RECEIVE
GYPSUM BOARD, NOT MORE THAN 4 INCHES FROM FLOOR AND
CEILING LINES AND ABUTTING WALLS. SECURE IN PLACE ON
ALTERNATE CHANNEL FLANGES AT MAXIMUM 24 INCHES ON
CENTER.
F.
G.
FURRING FOR FIRE RATINGS: INSTALL AS REQUIRED FOR FIRE
RESISTANCE RATINGS INDICATED AND TO GA-600 REQUIREMENTS.
BLOCKING: INSTALL WOOD BLOCKING FOR SUPPORT OF:
1.
2.
3.
4.
FRAMED OPENINGS.
WALL MOUNTED CABINETS.
PLUMBING FIXTURES.
WALL MOUNTED DOOR HARDWARE.
3.04 BOARD INSTALLATION
A.
B.
COMPLY WITH ASTM C 840, GA-216, AND MANUFACTURER'S
INSTRUCTIONS. INSTALL TO MINIMIZE BUTT END JOINTS,
ESPECIALLY IN HIGHLY VISIBLE LOCATIONS.
INSTALLATION ON METAL FRAMING: USE SCREWS FOR
ATTACHMENT OF ALL GYPSUM BOARD EXCEPT FACE LAYER OF
NON-RATED DOUBLE-LAYER ASSEMBLIES, WHICH MAY BE
INSTALLED BY MEANS OF ADHESIVE LAMINATION.
INSTALLATION OF TRIM AND ACCESSORIES
CONTROL JOINTS: PLACE CONTROL JOINTS CONSISTENT WITH
LINES OF BUILDING SPACES AND AS INDICATED.
CORNER BEADS: INSTALL AT EXTERNAL CORNERS, USING LONGEST
PRACTICAL LENGTHS.
EDGE TRIM: INSTALL AT LOCATIONS WHERE GYPSUM BOARD ABUTS
DISSIMILAR MATERIALS AND AS INDICATED.
JOINT TREATMENT
FINISH GYPSUM BOARD IN ACCORDANCE WITH LEVELS DEFINED IN
ASTM C840, AS FOLLOWS:
1. KNOCK-DOWN PROCEDURE: APPLY AS SPATTER TEXTURED
PATTERN TO ACHIEVE DESIRED EFFECT. AFTER SPATTERING
SURFACE, WAIT ABOUT 10-15 MIN., THEN VERY LIGHTLY
FLATTEN ONLY TOPS OF SPATTERS WITH FLAT BLADE OR
FLAT HAND TROWEL. AGAIN, SIZE OF SPATTERS DEPENDS
ON PRESSURES USED. MATCH EXISTING.
LEVEL 2: IN UTILITY AREAS, BEHIND CABINETRY, AND ON
BACKING BOARD TO RECEIVE TILE FINISH.
LEVEL 1: FIRE RATED WALL AREAS ABOVE FINISHED
CEILINGS, WHETHER OR NOT ACCESSIBLE IN THE
COMPLETED CONSTRUCTION.
TAPE, FILL, AND SAND EXPOSED JOINTS, EDGES, AND CORNERS TO
PRODUCE SMOOTH SURFACE READY TO RECEIVE FINISHES.
1. FEATHER COATS OF JOINT COMPOUND SO THAT CAMBER IS
MAXIMUM 1/32 INCH.
FILL AND FINISH JOINTS AND CORNERS OF CEMENTITIOUS BACKING
BOARD AS RECOMMENDED BY MANUFACTURER.
END OF SECTION 09 29 13
B.
1.5
A.
SECTION 09 51 23 - ACOUSTICAL TILE CEILINGS
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A.
B.
C.
1.2
A.
1.3
A.
B.
C.
DRAWINGS AND GENERAL PROVISIONS OF THE CONTRACT,
INCLUDING GENERAL AND SUPPLEMENTARY CONDITIONS AND
DIVISION 01 SPECIFICATION SECTIONS, APPLY TO THIS SECTION.
BASIS OF DESIGN; ARMSTRONG CIRRUS 584B, ANGLED TEGULAR,
HUMIGUARD, PLUS (WHITE), TO MATCH EXISTING.
PREPARATION AND WORKMANSHIP: COMPLY WITH REQUIREMENTS
OF THE BASIS OF DESIGN FOR PRODUCTS INDICATED
SUMMARY
SECTION INCLUDES: ACOUSTICAL TILES FOR INTERIOR CEILINGS;
FULLY CONCEALED, DIRECT-HUNG, SUSPENSION SYSTEMS.
ACTION SUBMITTALS
PRODUCT DATA: FOR EACH TYPE OF PRODUCT.
SAMPLES: FOR EACH EXPOSED PRODUCT AND FOR EACH COLOR
AND TEXTURE SPECIFIED, 6 INCHES IN SIZE.
SAMPLES FOR INITIAL SELECTION: FOR COMPONENTS WITH
FACTORY-APPLIED FINISHES.
1.4 MAINTENANCE MATERIAL SUBMITTALS
A. FURNISH EXTRA MATERIALS, FROM THE SAME PRODUCT RUN, THAT
MATCH PRODUCTS INSTALLED AND THAT ARE PACKAGED WITH
PROTECTIVE COVERING FOR STORAGE AND IDENTIFIED WITH
LABELS DESCRIBING CONTENTS.
1. ACOUSTICAL CEILING UNITS: FULL-SIZE TILES EQUAL TO
TWO (2) PERCENT OF QUANTITY INSTALLED.
2. SUSPENSION-SYSTEM COMPONENTS: QUANTITY OF EACH
CONCEALED GRID AND EXPOSED COMPONENT EQUAL TO
TWO (2) PERCENT OF QUANTITY INSTALLED.
DELIVERY, STORAGE, AND HANDLING
DELIVER ACOUSTICAL TILES, SUSPENSION-SYSTEM COMPONENTS,
AND ACCESSORIES TO PROJECT SITE AND STORE THEM IN A FULLY
ENCLOSED, CONDITIONED SPACE WHERE THEY WILL BE
PROTECTED AGAINST DAMAGE FROM MOISTURE, HUMIDITY,
TEMPERATURE EXTREMES, DIRECT SUNLIGHT, SURFACE
CONTAMINATION, AND OTHER CAUSES.
BEFORE INSTALLING ACOUSTICAL TILES, PERMIT THEM TO REACH
ROOM TEMPERATURE AND A STABILIZED MOISTURE CONTENT.
PART 2 - PRODUCTS
2.1
A.
B.
C.
C.
B.
5.
3.
2.3
A.
ACCOUSTICAL CEILING TILE
SUSPENDED ACOUSTICAL TILE CEILINGS: OBTAIN EACH TYPE OF
ACOUSTICAL CEILING TILE AND ITS SUSPENSION SYSTEM FROM
SINGLE SOURCE FROM SINGLE MANUFACTURER.
USG OLYMPIA MICRO, CLIMAPLUS.
SURFACE-BURNING CHARACTERISTICS: COMPLY WITH ASTM E84;
TESTING BY A QUALIFIED TESTING AGENCY. IDENTIFY PRODUCTS
WITH APPROPRIATE MARKINGS OF APPLICABLE TESTING AGENCY.
1.
2.
3.
4.
5.
ASTM E1264 CLASSIFICATION: TYPE III, FORM 1 PATTERN E.
EDGES: TEGULAR
SIZE: ACT-1: 24 X 24 X 3/4 INCH.
NRC: 0.70 AND CAC: 35
FIRE PERFORMANCE UL 723 (ASTM E 84) FLAME-SPREAD: 25;
CLASS A ACCORDING TO ASTM E1264
6.
7.
SMOKE-DEVELOPED INDEX: 50 OR LESS.
LIGHT REFLECTANCE: 0.85
2.2 METAL SUSPENSION SYSTEM
A. METAL SUSPENSION-SYSTEM STANDARD: PROVIDE
MANUFACTURER'S STANDARD, DIRECT-HUNG, FULLY CONCEALED,
METAL SUSPENSION SYSTEM AND ACCESSORIES OF TYPE,
STRUCTURAL CLASSIFICATION, AND FINISH INDICATED THAT
COMPLIES WITH APPLICABLE REQUIREMENTS AS FOLLOWS:
1. STRUCTURAL CLASSIFICATION:
SYSTEM, ASTM C635.
2.
3.
4.
5.
INTERMEDIATE DUTY
FACE DESIGN: SIMILAR TO ARMSTRONG SILHOUETTE XL,
BOLTS LOT WITH REVEAL.
CAP MATERIAL: STEEL COLD-ROLLED SHEET.
CAP FINISH: FACTORY PAINTED WHITE COLOR.
GRID TYPE: AS INDICATED ON DRAWINGS.
ACCESSORIES
ATTACHMENT DEVICES: SIZE FOR FIVE TIMES THE DESIGN LOAD
INDICATED IN ASTM C635, TABLE 1, "DIRECT HUNG," UNLESS
OTHERWISE INDICATED. COMPLY WITH SEISMIC DESIGN
REQUIREMENTS PER STRUCTURAL DRAWINGS OR AS REQUIRED BY
THE AUTHORITY HAVING JURISDICTION.
1. CORROSION PROTECTION: CARBON-STEEL COMPONENTS
ZINC PLATED ACCORDING TO ASTM B633, CLASS SC 1 (MILD)
SERVICE CONDITION.
B. WIRE HANGERS, BRACES, AND TIES: PROVIDE WIRES AS FOLLOWS:
1. ZINC-COATED, CARBON-STEEL WIRE: ASTM A641/A641M,
CLASS 1 ZINC COATING, SOFT TEMPER.
2. SIZE: WIRE DIAMETER SUFFICIENT FOR ITS STRESS AT
THREE TIMES HANGER DESIGN LOAD (ASTM C635, TABLE 1,
"DIRECT HUNG") WILL BE LESS THAN YIELD STRESS OF WIRE,
BUT NOT LESS THAN 0.106-INCH- DIAMETER WIRE.
SEISMIC STABILIZER BARS: MANUFACTURER'S STANDARD
PERIMETER STABILIZERS DESIGNED TO ACCOMMODATE SEISMIC
FORCES.
PART 3 - EXECUTION
3.1
A.
INSTALLATION OF SUSPENDED ACOUSTICAL TILE CEILINGS
INSTALL SUSPENDED ACOUSTICAL TILE CEILINGS ACCORDING TO
ASTM C636 AND MANUFACTURER'S WRITTEN INSTRUCTIONS.
SUSPEND CEILING HANGERS FROM BUILDING'S STRUCTURAL
MEMBERS AND AS FOLLOWS:
1.
2.
DO NOT SUPPORT FROM PIPING, DUCTWORK, CONDUIT, OR
ROOF DECK.
INSTALL HANGERS PLUMB AND FREE FROM CONTACT WITH
INSULATION OR OTHER OBJECTS WITHIN CEILING PLENUM
THAT ARE NOT PART OF SUPPORTING STRUCTURE OR OF
CEILING SUSPENSION SYSTEM.
SPLAY HANGERS ONLY WHERE REQUIRED TO MISS
OBSTRUCTIONS, BUT NOT MORE THAN 60 DEGREE ANGLE
TO VERTICAL; OFFSET RESULTING HORIZONTAL FORCES BY
BRACING, COUNTER-SPLAYING, OR OTHER EQUALLY
EFFECTIVE MEANS.
4. WHERE WIDTH OF DUCTS AND OTHER CONSTRUCTION
WITHIN CEILING PLENUM PRODUCES HANGER SPACINGS
THAT INTERFERE WITH LOCATION OF HANGERS AT
SPACINGS REQUIRED TO SUPPORT STANDARD
SUSPENSION-SYSTEM MEMBERS, INSTALL SUPPLEMENTAL
SUSPENSION MEMBERS AND HANGERS IN FORM OF
TRAPEZES OR EQUIVALENT DEVICES.
SECURE WIRE HANGERS TO CEILING SUSPENSION
MEMBERS AND TO SUPPORTS ABOVE WITH A MINIMUM OF
THREE TIGHT TURNS. CONNECT HANGERS DIRECTLY TO
STRUCTURE OR TO INSERTS, EYE SCREWS, OR OTHER
DEVICES THAT ARE SECURE AND APPROPRIATE FOR
SUBSTRATE AND THAT WILL NOT DETERIORATE OR
OTHERWISE FAIL DUE TO AGE, CORROSION, OR ELEVATED
TEMPERATURES.
8.
B.
3.
2.
B.
E.
4.
4.
5.
6.
7.
8.
E.
D.
C.
7.
6. SECURE FLAT, ANGLE, CHANNEL, AND ROD HANGERS TO
STRUCTURE, INCLUDING INTERMEDIATE FRAMING
MEMBERS, BY ATTACHING TO INSERTS, EYE SCREWS, OR
OTHER DEVICES THAT ARE SECURE AND APPROPRIATE FOR
BOTH THE STRUCTURE TO WHICH HANGERS ARE ATTACHED
AND THE TYPE OF HANGER INVOLVED. INSTALL HANGERS IN
A MANNER THAT WILL NOT CAUSE THEM TO DETERIORATE
OR FAIL DUE TO AGE, CORROSION, OR ELEVATED
TEMPERATURES.
SPACE HANGERS NOT MORE THAN 48 INCHES O.C. ALONG
EACH MEMBER SUPPORTED DIRECTLY FROM HANGERS
UNLESS OTHERWISE INDICATED; PROVIDE HANGERS NOT
MORE THAN 8 INCHES FROM ENDS OF EACH MEMBER.
SIZE SUPPLEMENTAL SUSPENSION MEMBERS AND HANGERS
TO SUPPORT CEILING LOADS WITHIN PERFORMANCE LIMITS
ESTABLISHED BY REFERENCED STANDARDS.
SECURE BRACING WIRES TO CEILING SUSPENSION MEMBERS AND
TO SUPPORTS WITH A MINIMUM OF FOUR TIGHT TURNS. SUSPEND
BRACING FROM BUILDING'S STRUCTURAL MEMBERS AS REQUIRED
FOR HANGERS WITHOUT ATTACHING TO PERMANENT METAL
FORMS, STEEL DECK, OR STEEL DECK TABS. FASTEN BRACING
WIRES INTO CONCRETE WITH CAST-IN-PLACE OR POST-INSTALLED
ANCHORS.
INSTALL EDGE MOLDINGS AND TRIM OF TYPE INDICATED AT
PERIMETER OF ACOUSTICAL CEILING AREA AND WHERE
NECESSARY TO CONCEAL EDGES OF ACOUSTICAL TILES.
1.
2.
3.
APPLY ACOUSTICAL SEALANT IN A CONTINUOUS RIBBON
CONCEALED ON BACK OF VERTICAL LEGS OF MOLDINGS
BEFORE THEY ARE INSTALLED.
SCREW ATTACH MOLDINGS TO SUBSTRATE AT INTERVALS
NOT MORE THAN 16 INCHES O.C. AND NOT MORE THAN 3
INCHES FROM ENDS. MITER CORNERS ACCURATELY AND
CONNECT SECURELY.
DO NOT USE EXPOSED FASTENERS, INCLUDING POP RIVETS,
ON MOLDINGS AND TRIM.
INSTALL SUSPENSION-SYSTEM RUNNERS SO THEY ARE SQUARE
AND SECURELY INTERLOCKED WITH ONE ANOTHER. REMOVE AND
REPLACE DENTED, BENT, OR KINKED MEMBERS.
END OF SECTION 09 51 23
SECTION 09 65 00 - RESILIENT WALL BASE
PART 1 - GENERAL
1.01 SUMMARY
A.
1.02 REFERENCED DOCUMENTS
A. ASTM INTERNATIONAL:
1.
2.
3.
F 1861 STANDARD SPECIFICATION FOR RESILIENT WALL
BASE
E 84 STANDARD TEST METHOD FOR SURFACE BURNING
CHARACTERISTICS OF BUILDING MATERIALS
F 386 STANDARD TEST METHOD FOR THICKNESS OF
RESILIENT FLOORING MATERIALS HAVING FLAT SURFACES
E 648 STANDARD TEST METHOD FOR CRITICAL RADIANT
FLUX OF FLOORING SYSTEMS USING A RADIANT
ENERGYSOURCE.
E 662 TEST METHOD FOR SPECIFIC DENSITY OF SMOKE
GENERATED BY SOLID MATERIALS.
F 925 STANDARD TEST METHOD FOR RESISTANCE TO
CHEMICALS OF RESILIENT FLOORING.
F 137 STANDARD TEST METHOD FOR FLEXIBILITY OF
RESILIENT FLOORING MATERIALS WITH CYLINDRICAL
MANDREL APPARATUS
F 1515 STANDARD TEST METHOD FOR MEASURING LIGHT
STABILITY OF RESILIENT VINYL FLOORING BY COLOR
CHANGE
OTHER REFERENCED DOCUMENTS
1.
2.
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA): NFPA
255, TEST METHOD FOR CRITICAL RADIANT FLUX OF FLOOR
COVERING SYSTEMS USING A RADIANT ENERGY SOURCE
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) 258 TEST
METHOD FOR SPECIFIC DENSITY OF SMOKE GENERATED BY
SOLID MATERIALS.
CALIFORNIA SAFE DRINKING WATER AND TOXIC
ENFORCEMENT ACT OF 1986 (PROPOSITION 65).
THE COLLABORATIVE FOR HIGH PERFORMANCE SCHOOLS
(CHPS)
1.03 SUBMITTALS
A.
B.
C.
D.
PRODUCT DATA: SUBMIT PRODUCT DATA, INCLUDING
MANUFACTURER'S SPECIFICATION SUMMARY SHEET FOR SPECIFIED
PRODUCTS
SHOP DRAWINGS: SUBMIT SHOP DRAWINGS SHOWING LAYOUT,
FINISH COLORS, PATTERNS AND TEXTURES.
SAMPLES: SUBMIT SELECTION AND VERIFICATION SAMPLES FOR
FINISHES, COLORS, AND TEXTURES.
QUALITY ASSURANCE SUBMITTALS: SUBMIT THE FOLLOWING:
1. TEST REPORTS: CERTIFIED TEST REPORTS SHOWING
COMPLIANCE WITH SPECIFIED PERFORMANCE
CHARACTERISTICS AND PHYSICAL PROPERTIES.
2. MANUFACTURER'S INSTRUCTIONS: MANUFACTURER'S
INSTALLATION AND MAINTENANCE INSTRUCTIONS.
SUBMIT THE FOLLOWING:
1. MAINTENANCE DATA: MAINTENANCE DATA FOR INSTALLED
PRODUCTS IN ACCORDANCE WITH DIVISION 1 SECTIONS.
INCLUDE METHODS FOR MAINTAINING INSTALLED
PRODUCTS, AND PRECAUTIONS AGAINST CLEANING
MATERIALS AND METHODS DETRIMENTAL TO FINISHES AND
PERFORMANCE.
WARRANTY: WARRANTY DOCUMENTS SPECIFIED HEREIN.
1.04 QUALITY ASSURANCE
A. INSTALLER QUALIFICATIONS: INSTALLER EXPERIENCED IN
PERFORMING WORK OF THIS SECTION WHO HAS SPECIALIZED IN
INSTALLING WORK SIMILAR TO THAT REQUIRED FOR THIS PROJECT.
REGULATORY REQUIREMENTS
1. FIRE PERFORMANCE CHARACTERISTICS: PROVIDE
RESILIENT SHEET VINYL FLOOR COVERING WITH THE
FOLLOWING FIRE PERFORMANCE CHARACTERISTICS AS
DETERMINED BY TESTING PRODUCTS IN ACCORDANCE WITH
ASTM METHOD (AND) NFPA METHOD) INDICATED BELOW BY
A CERTIFIED TESTING LABORATORY OR ANOTHER TESTING
AND INSPECTING AGENCY ACCEPTABLE TO AUTHORITIES
HAVING JURISDICTION.
a. ASTM E 648 (NFPA 253), CRITICAL RADIANT FLUX OF
FLOOR COVERING SYSTEMS: CLASS 1, > 1.0 W/CM2
b.
c.
C.
D.
ASTM E 662 (NFPA 258), SPECIFIC OPTICAL DENSITY
OF SMOKE GENERATED BY SOLID MATERIALS:
PASSES, <450
ASTM E 84 (NFPA 255), SURFACE BUILDING
CHARACTERISTICS OF BUILDING MATERIALS: CLASS
C
SINGLE-SOURCE RESPONSIBILITY: OBTAIN RESILIENT WALL BASE
AND MANUFACTURER’S RECOMMENDED ADHESIVE FROM A SINGLE
SUPPLIER.
PRE-INSTALLATION MEETINGS: CONDUCT PRE-INSTALLATION
MEETING TO VERIFY PROJECT REQUIREMENTS, SUBSTRATE
CONDITIONS & MANUFACTURER’S RECOMMENDED SUBSTRATES
AND REQUIRED PREPARATION MANUFACTURER' INSTALLATION
INSTRUCTIONS AND MANUFACTURER'S WARRANTY REQUIREMENTS.
COMPLY WITH REQUIREMENTS IN DIVISION 1.
1.05
A.
B.
C.
DELIVERY, STORAGE, AND HANDLING
GENERAL: COMPLY WITH REQUIREMENTS IN DIVISION 1.
ORDERING: COMPLY WITH MANUFACTURER'S ORDERING
INSTRUCTIONS AND LEAD-TIME REQUIREMENTS TO AVOID
CONSTRUCTION DELAYS.
DELIVERY: DELIVER MATERIALS IN MANUFACTURER'S ORIGINAL,
UNOPENED, UNDAMAGED CONTAINERS WITH IDENTIFICATION
LABELS INTACT.
SECTION INCLUDES: RESILIENT WALL BASE
C.
C.
B.
3.
B.
D. STORAGE AND PROTECTION: STORE MATERIALS PROTECTED FROM
EXPOSURE TO HARMFUL WEATHER CONDITIONS AND ACCLIMATED
TO SITE CONDITIONS AT TEMPERATURE AND HUMIDITY CONDITIONS
RECOMMENDED BY MANUFACTURER.
1.06 PROJECT CONDITIONS
A. ENVIRONMENTAL REQUIREMENTS/CONDITIONS: IN ACCORDANCE
WITH MANUFACTURER'S RECOMMENDATIONS, AREAS TO RECEIVE
RESILIENT WALL BASE SHALL BE CLEAN, FULLY ENCLOSED,
WEATHER TIGHT WITH THE PERMANENT HVAC SET AT A UNIFORM
TEMPERATURE OF 65-85 DEGREES F FOR 48 HOURS PRIOR TO
DURING, AND THEREAFTER INSTALLATION OF RESILIENT WALL
BASE. RESILIENT WALL BASE AND ADHESIVE SHALL BE
CONDITIONED IN THE SAME MANNER. RESILIENT WALL BASE MUST
BE UNBOXED ACCLIMATED IN AREA OF USE AT LEAST 48 HOURS
PRIOR TO INSTALLATION. MINIMUM TEMPERATURE SHALL BE A 65
DEGREES F AFTER INSTALLATION.
EXISTING CONDITIONS: ENSURE ALL EXISTING WALLS ARE SUITABLE
FOR RESILIENT BASE INSTALLATION. BRING ALL UNACCEPTABLE
AREAS TO OWNER’S ATTENTION PRIOR TO COMMENCEMENT OF
WORK.
1.07 SEQUENCING AND SCHEDULING
A.
1.08 WARRANTY
A.
FINISHING OPERATIONS: INSTALL RESILIENT WALL BASE AFTER
FINISHING OPERATIONS, INCLUDING FLOOR COVERING PAINTING
AND CEILING OPERATIONS ETC., HAVE BEEN COMPLETED.
MANUFACTURER'S MATERIALS WARRANTY: SUBMIT, FOR OWNER'S
ACCEPTANCE, MANUFACTURER'S STANDARD WARRANTY
DOCUMENT. MANUFACTURER'S WARRANTY IS IN ADDITION TO, AND
NOT A LIMITATION OF, OTHER RIGHTS OWNER MAY HAVE UNDER
CONTRACT DOCUMENTS.
1. WARRANTY PERIOD: 1 YEAR LIMITED WARRANTY
COMMENCING ON DATE OF SUBSTANTIAL COMPLETION.
NOTICE OF ANY DEFECT MUST BE MADE IN WRITING TO
MANUFACTURER WITHIN THIRTY (30) DAYS AFTER BUYER
LEARNS OF THE DEFECT.
2. LIMITED WEAR WARRANTY: 3 YEAR LIMITED WEAR
WARRANTY.
1.09 MAINTENANCE
A. EXTRA MATERIALS: DELIVER TO OWNER EXTRA MATERIALS FROM
SAME PRODUCTION RUN AS PRODUCTS INSTALLED. PACKAGE
PRODUCTS WITH PROTECTIVE COVERING AND IDENTIFY WITH
DESCRIPTIVE LABELS. COMPLY WITH DIVISION ONE CLOSEOUT
SUBMITTALS (MAINTENANCE MATERIALS) SECTION.
1. QUANTITY: FURNISH QUANTITY OF RESILIENT WALL BASE
EQUAL TO 5% OF AMOUNT INSTALLED.
2. DELIVERY, STORAGE AND PROTECTION: COMPLY WITH
OWNER'S REQUIREMENTS FOR DELIVERY, STORAGE AND
PROTECTION OF EXTRA MATERIALS.
MAINTENANCE OF FINISHED FLOOR COVERING TO BE
CONDUCTED PER MANUFACTURER’S MAINTENANCE GUIDE.
PART 2 - PRODUCTS
2.01
A.
RESILIENT WALL BASE
MANUFACTURER:
1.
435-1056
2.
ARCHITECT AND OWNER PRE-APPROVED EQUAL
TEST RESULTS:
1.
2.
3.
4.
5.
6.
7.
8.
THICKNESS TOLERANCE: COMPLIES WITH ASTM F-386
FLEXIBILITY: COMPLIES WITH ASTM F-137
RESISTANCE TO HEAT AGING: COMPLIES WITH ASTM F-1515
RESISTANCE TO DETERGENTS: COMPLIES WITH ASTM F-925
RESISTANCE TO ALKALIS: NO FADING OR SOFTENING
DIMENSIONAL STABILITY: COMPLIES WITH ASTM F 186
SQUARENESS: 90 DEGREES +/- 0.5 DEGREES
DOES DO NOT CONTAIN ANY OF THE HAZARDOUS
CHEMICALS LISTED IN CALIFORNIA PROPOSITION 65
COLLABORATIVE FOR HIGH PERFORMANCE SCHOOLS
(CHPS) 01350 LOW-EMITTING MATERIAL CRITERIA: PASS
PROPRIETARY PRODUCT:
1.
b.
c.
d.
e.
ROPPE PINNACLE RUBBER BASE
a. COMPLIES WITH ASTM F-1861 TYPE TS (THERMOSET
VULCANIZED RUBBER), GROUP 1 (SOLID)
CONTAINS 10% NATURAL RUBBER
THICKNESS: 1/8” ( 3.175 MM) NOMINAL
COLOR: AS SPECIFIED ON FINISH MATERIAL LIST
PROFILE: STANDARD TOE (COVE BASE)
1.
2.
3.
NOMINAL HEIGHT: 4"
LENGTHS: 120' COILS
CORNERS: FACTORY PRE-FORMED OUTSIDE
CORNERS (6")
2.02 PRODUCT SUBSTITUTIONS
A. SUBSTITUTIONS: SUBSTITUTIONS PERMITTED PER OWNER'S
CRITERIA.
PART 3 - EXECUTION
3.01 MANUFACTURER'S INSTRUCTIONS
A.
B.
ROPPE CORPORATION CONTACT: P.O. BOX 1158 FOSTORIA,
OHIO USA 44830-1158. PHONE: (419) 435-8546 FAX: (419)
COMPLIANCE: COMPLY WITH MANUFACTURER’S INSTRUCTIONS FOR
INSTALLATION.
ADHESIVE: (SELECT ONE) ROPPE 205 WALL BASE ADHESIVE OR 210
WHITE ACRYLIC WALL BASE ADHESIVE
CAULKING: ROPPE COLORED CAULK
DIVISION 09 - FINISHES DIVISION 09 - FINISHES DIVISION 09 - FINISHES
B.
C.
3.02 EXAMINATION
A.
B.
SITE VERIFICATION OF CONDITIONS: VERIFY SUBSTRATE
CONDITIONS ARE ACCEPTABLE FOR INSTALLING PRODUCT IN
ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.
MATERIAL INSPECTION: IN ACCORDANCE WITH MANUFACTURER'S
INSTALLING REQUIREMENTS, VISUALLY INSPECT MATERIALS PRIOR
TO INSTALLING. MATERIAL WITH VISUAL DEFECTS SHALL NOT BE
INSTALLED.
3.03 PREPARATION
A. ADJACENT SURFACES PROTECTION: PROTECT ADJACENT WORK
AREAS AND FINISH SURFACES FROM DAM AGE DURING
PRODUCT INSTALLATION.
SURFACE PREPARATION, GENERAL: PREPARE SUBSTRATE IN
ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.
SUBSTRATE: PREPARE MANUFACTURER’S RECOMMENDED
SUBSTRATES TO BE SMOOTH, RIGID, FLAT, LEV EL,
PERMANENTLY DRY, CLEAN AND FREE OF FOREIGN MATERIALS
SUCH AS PAINT, DUST, GREASE, OILS, SOLVENT, OLD ADHESIVE
RESIDUE, VINYL WALL COVERINGS, NON-POROUS SURFACES AND
ALL OTHER CONTAMINANTS THAT MAY INTERFERE WITH ADHESIVE
BOND.
INSTALLATION
A.
B.
C.
D.
MANUFACTURER’S INSTRUCTIONS FOR SPECIFICATIONS ON
INSTALLING RESILIENT WALL BASE.
RESILIENT WALL BASE COLORS, HEIGHTS AND PROFILES: AS
SELECTED BY ARCHITECT.
ROPPE ADHESIVE
ROPPE COLORED CAULK
3.05 FIELD QUALITY REQUIREMENT
A. MANUFACTURER'S FIELD SERVICES: UPON OWNER'S REQUEST AND
WITH MINIMUM 72 HOURS NOTICE, PROVIDE MANUFACTURER'S
FIELD SERVICE CONSISTING OF PRODUCT USE RECOMMENDATIONS
AND PERIODIC SITE VISITS TO CONFIRM INSTALLING OF PRODUCT IS
IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.
1. SITE VISITS ON SITE VISIT SHALL OCCUR ON THE FIRST DAY
OF RESILIENT WALL BASE INSTALLATION.
3.06 CLEANING
A. CLEANING: REPAIR OR REPLACE DAMAGED INSTALLED PRODUCTS.
CLEAN INSTALLED PRODUCTS IN ACCORDANCE WITH
MANUFACTURER'S INSTRUCTIONS PRIOR TO OWNER'S
ACCEPTANCE. REMOVE CONSTRUCTION DEBRIS FROM PROJECT
SITE AND LEGALLY DISPOSE OF DEBRIS.
END OF SECTION 09 65 00
SECTION 09 65 19 - RESILIENT TILE FLOORING
PART 1 GENERAL
1.01 SUMMARY
A. Section Includes: Resilient vinyl tile flooring.
B. Related Sections: Sections related to this section include:
1.
2.
3.
Procurement and Contracting Requirements: Division 00 General
Conditions.
General Requirements: Division 01 Specification Sections.
Concrete: Division 03 Concrete Sections.
1.02 REFERENCES
A. American Concrete Institute (ACI):
1.
2.
B. ASTM International:
1.
2.
3.
4.
5.
6.
7.
8.
9.
ACI 302.1 Guide for Concrete Floor and Slab Construction.
ACI SP-15 Field Reference Manual - Standard Specifications for
Structural Concrete.
ASTM D2047 Standard Test Method for Static Coefficient of Friction of
Polish-Coated Floor Surfaces as Measured by the James Machine.
ASTM E648 Standard Test Method for Critical Radiant Flux of Floor-
Covering Systems Using a Radiant Heat Energy Source.
ASTM E662 Standard Test Method for Specific Optical Density of
Smoke Generated by Solid Materials.
ASTM E1643 Standard Practice for Installation of Water Vapor
Retarders Used in Contact with Earth or Granular Fill Under Concrete
Slabs.
ASTM E1745 Standard Specification for Water Vapor Retarders Used in
Contact with Soil or Granular Fill Under Concrete Slabs.
ASTM F137 Standard Test Method for Flexibility of Resilient Flooring
Materials with Cylindrical Mandrel Apparatus.
ASTM F386 Standard Test Method for Thickness of Resilient Flooring
Materials Having Flat Surfaces.
ASTM F536 Test Method for Size of Resilient Floor Coverings. (This test method was withdrawn by ASTM in 2004).
ASTM F540 Test Method for Squareness of Resilient Floor Tile by Dial
Gage Method. (This test method was withdrawn by ASTM in 2004).
10. ASTM F710 Standard Practice for Preparing Concrete Floors to Receive
Resilient Flooring.
11. ASTM F925 Standard Test Method for Resistance to Chemicals of
Resilient Flooring.
12. ASTM F970 Standard Test Method for Static Load Limit.
13. ASTM F1482 Standard Guide to Wood Underlayment Products
Available for Use Under Resilient Flooring.
14. ASTM F1514 Standard Test Method for Measuring Heat Stability of
Resilient Vinyl Flooring by Color Change.
15. ASTM F1515 Standard Test Method for Measuring Light Stability of
Resilient Vinyl Flooring by Color Change.
16. ASTM F1700 Standard Specification for Solid Vinyl Floor Tile.
17. ASTM F1869 Standard Test Method for Measuring Moisture Vapor
Emission Rate of Concrete Subfloor Using Anhydrous Calcium Chloride.
18. ASTM F1914 Standard Test Method for Short-Term Indentation and
Residual Indentation of Resilient Floor Covering.
19. ASTM F2170 Standard Test Method for Determining Relative Humidity in Concrete Floor Slabs Using in situ Probes.
C. Americans with Disabilities Act (ADA) of 1990.
A-003
D
C
B
A
54321 6
Engineering | Planning | Allied Services
Offices Nationwide www.hanson-inc.com
Hanson Professional Services Inc.
2300 Maitland Center Pkwy.
Maitland, FL 32751
(407) 790-7397
CONSULTANTS
EB0007061
AA0003116
IB0001058
ORANGE COUNTY
SHERIFF'S SECTOR IV
ELECTRICAL &
LIGHTING UPGRADES
2400 West 33rd Street
Orlando, FL 32839
SHEET TITLE
REVIEWED BY:
DRAWN BY:
DESIGN BY:
PROJECT NO:
ISSUE:
© Copyright Hanson Professional Services Inc. 2020
05/24/24
17G0191A
BID DOCUMENTS
MARK DATE DESCRIPTION
Suite 310
DAT
SF
DOMINGO R. FORNOLES AR 94278
A
M
F i l e
P a t h
DIVISION 9 - FINISHES
B.
C.
D.
SECTION 099123 ï INTERIOR PAINTING
PART 1 - GENERAL
1.1 SECTION INCLUDES
A.
B.
1.2
A.
B.
C.
D.
E.
F.
G.
H.
I.
1.3
A.
SURFACE PREPARATION BY CONTRACTOR.
PAINT AND COATING APPLICATION BY OWNERS VENDOR.
RELATED SECTIONS
SECTION 03300 - CONCRETE: SURFACE COORDINATION AND CURING
PROVISIONS.
SECTION 05120 - STRUCTURAL STEEL: SHOP PRIMING STRUCTURAL
STEEL.
SECTION 05500 - METAL FABRICATIONS: SHOP PRIMING FERROUS
METAL.
SECTION 06200 - FINISH CARPENTRY: SHOP PRIMING
ARCHITECTURAL WOODWORK.
SECTION 06400 - ARCHITECTURAL WOODWORK: SHOP-APPLIED
STAINS AND TRANSPARENT FINISHES.
SECTION 08110 - STEEL DOORS AND FRAMES: FACTORY PRIMING
STEEL DOORS AND FRAMES.
SECTION 09260 - GYPSUM BOARD ASSEMBLIES: SURFACE
PREPARATION OF GYPSUM BOARD.
SECTION 15050 - BASIC MECHANICAL MATERIALS AND METHODS:
MECHANICAL IDENTIFICATION.
SECTION 16050 - BASIC ELECTRICAL MATERIALS AND METHODS:
MECHANICAL IDENTIFICATION.
REFERENCES
B.
STEEL STRUCTURES PAINTING COUNCIL (SSPC):
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
SSPC-SP 1 - SOLVENT CLEANING.
SSPC-SP 2 - HAND TOOL CLEANING.
SSPC-SP 3 - POWER TOOL CLEANING.
SSPC-SP5/NACE NO. 1, WHITE METAL BLAST CLEANING.
SSPC-SP6/NACE NO. 3, COMMERCIAL BLAST CLEANING.
SSPC-SP7/NACE NO. 4, BRUSH-OFF BLAST CLEANING.
SSPC-SP10/NACE NO. 2, NEAR-WHITE BLAST CLEANING.
SSPC-SP11, POWER TOOL CLEANING TO BARE METAL.
SSPC-SP12/NACE NO. 5, SURFACE PREPARATION AND
CLEANING OF METALS BY WATERJETTING PRIOR TO
RECOATING.
SSPC-SP 13 / NACE NO. 6 SURFACE PREPARATION FOR
CONCRETE.
ENVIRONMENTAL PROTECTION AGENCY (EPA): METHOD 24 -
DETERMINATION OF VOLATILE MATTER CONTENT, WATER CONTENT,
DENSITY, VOLUME SOLIDS, AND WEIGHT SOLIDS OF SURFACE
COATINGS.
SOUTH COAST AIR QUALITY MANAGEMENT DISTRICT (SCAQMD):
RULE 113 - ARCHITECTURAL COATINGS.(JANUARY 1, 2004)
GREEN SEAL, INC.:
1.
2.
GS-11 STANDARD FOR PAINTS AND COATINGS.(1ST EDITION,
MAY 20,1993)
GC-03 - ENVIRONMENTAL CRITERIA FOR ANTI-CORROSIVE
PAINTS.
C.
D.
E.
2.4
A.
2.
2.3
A.
2.
PAINT MATERLALS - GENERAL
PAINTS AND COATINGS.
1. UNLESS OTHERWISE INDICATED, PROVIDE FACTORY-MIXED
COATINGS. WHEN REQUIRED, MIX COATINGS TO CORRECT
CONSISTENCY IN ACCORDANCE WITH MANUFACTURER'S
INSTRUCTIONS BEFORE APPLICATION. DO NOT REDUCE,
THIN, OR DILUTE COATINGS OR ADD MATERIALS TO
COATINGS UNLESS SUCH PROCEDURE IS SPECIFICALLY
DESCRIBED IN MANUFACTURER'S PRODUCT INSTRUCTIONS.
FOR OPAQUE FINISHES, TINT EACH COAT INCLUDING PRIMER
COAT AND INTERMEDIATE COATS, ONE-HALF SHADE
LIGHTER THAN SUCCEEDING COAT, WITH FINAL FINISH COAT
AS BASE COLOR. OR FOLLOW MANUFACTURES PRODUCT
INSTRUCTIONS FOR OPTIMAL COLOR CONFORMANCE.
PRIMERS: WHERE THE MANUFACTURER OFFERS OPTIONS ON
PRIMERS FOR A PARTICULAR SUBSTRATE, USE PRIMER
CATEGORIZED AS "BEST" BY THE MANUFACTURER.
COATING APPLICATION ACCESSORIES: PROVIDE ALL PRIMERS,
SEALERS, CLEANING AGENTS, CLEANING CLOTHS, SANDING
MATERIALS, AND CLEAN-UP MATERIALS REQUIRED, PER
MANUFACTURER'S SPECIFICATIONS.
COLOR: AS SELECTED BY THE OWNER.
REFER TO THE CURRENT MSDS/EDS FOR EXACT VOCS. VOCS MAY
VARY BY BASE. SOME COLORS MAY NOT BE 0 VOC AFTER TINTING
WITH CONVENTIONAL COLORANTS.
INTERIOR PAINT SYSTEMS
METAL - (STRUCTURAL STEEL COLUMNS, JOISTS, TRUSSES, BEAMS,
MISCELLANEOUS AND ORNAMENTAL IRON, STRUCTURAL IRON,
FERROUS METAL)
1. ALKYD SYSTEM
a.
2.
SEMI-GLOSS FINISH (WATER BASE):
1. 1ST COAT: S-W PRO INDUSTRIAL PRO-CRYL
UNIVERSAL PRIMER, B66-310 SERIES (5-10
MILS WET, 2-4 MILS DRY).
2ND COAT: S-W PROMAR 200 WATERBASED
ACRYLIC/ALKYD SEMI-GLOSS, B34-8200
SERIES.
5.
1.6
A.
B.
DELIVERY: DELIVER MANUFACTURER'S UNOPENED CONTAINERS TO
THE WORK SITE. PACKAGING SHALL BEAR THE MANUFACTURER'S
NAME, LABEL, AND THE FOLLOWING LIST OF INFORMATION.
1.
2.
3.
4.
5.
6.
7.
PRODUCT NAME, AND TYPE (DESCRIPTION).
APPLICATION AND USE INSTRUCTIONS.
SURFACE PREPARATION.
VOC CONTENT.
ENVIRONMENTAL ISSUES.
BATCH DATE.
COLOR NUMBER.
STORAGE: STORE AND DISPOSE OF SOLVENT-BASED MATERIALS,
AND MATERIALS USED WITH SOLVENT-BASED MATERIALS, IN
ACCORDANCE WITH REQUIREMENTS OF LOCAL AUTHORITIES
HAVING JURISDICTION.
B.
E.
F.
C.
D.
3.
2.
1.5
A.
C.
D.
1.4
A.
B.
SUBMITTALS
SUBMIT UNDER PROVISIONS OF SECTION 01300.
PRODUCT DATA: FOR EACH PAINT SYSTEM INDICATED, INCLUDING.
1. PRODUCT CHARACTERISTICS.
2.
3.
4.
5.
6.
SURFACE PREPARATION INSTRUCTIONS AND
RECOMMENDATIONS.
PRIMER REQUIREMENTS AND FINISH SPECIFICATION.
STORAGE AND HANDLING REQUIREMENTS AND
RECOMMENDATIONS.
APPLICATION METHODS.
CAUTIONS FOR STORAGE, HANDLING AND INSTALLATION.
SELECTION SAMPLES: SUBMIT A COMPLETE SET OF COLOR CHIPS
THAT REPRESENT THE FULL RANGE OF MANUFACTURER'S
PRODUCTS, COLORS AND SHEENS AVAILABLE.
VERIFICATION SAMPLES: FOR EACH FINISH PRODUCT SPECIFIED,
SUBMIT SAMPLES THAT REPRESENT ACTUAL PRODUCT, COLOR,
AND SHEEN.
QUALITY ASSURANCE
INSTALLER QUALIFICATIONS: A FIRM OR INDIVIDUAL EXPERIENCED
IN APPLYING PAINTS AND COATINGS SIMILAR IN MATERIAL, DESIGN,
AND EXTENT TO THOSE INDICATED FOR THIS PROJECT, WHOSE
WORK HAS RESULTED IN APPLICATIONS WITH A RECORD OF
SUCCESSFUL IN-SERVICE PERFORMANCE.
B.
C.
D.
PAINT EXPOSED SURFACES. IF A COLOR OF FINISH, OR A SURFACE
IS NOT SPECIFICALLY MENTIONED, ARCHITECT WILL SELECT FROM
STANDARD PRODUCTS, COLORS AND SHEENS AVAILABLE.
DO NOT PAINT PREFINISHED ITEMS, CONCEALED SURFACES,
FINISHED METAL SURFACES, OPERATING PARTS, AND LABELS
UNLESS INDICATED.
MOCK-UP: PROVIDE A MOCK-UP FOR EVALUATION OF SURFACE
PREPARATION TECHNIQUES AND APPLICATION WORKMANSHIP.
1. FINISH SURFACES FOR VERIFICATION OF PRODUCTS,
COLORS AND SHEENS.
2.
3.
4.
FINISH AREA DESIGNATED BY ARCHITECT.
PROVIDE SAMPLES THAT DESIGNATE PRIMER AND FINISH
COATS.
DO NOT PROCEED WITH REMAINING WORK UNTIL THE
ARCHITECT APPROVES THE MOCK-UP.
DELIVERY, STORAGE, AND HANDLING
3.2
A.
B.
2.
3.
2.
3. 3RD COAT: S-W PROMAR 200 WATERBASED
ACRYLIC/ALKYD SEMI-GLOSS, B34-8200
SERIES (4 MILS WET, 1.7 MILS DRY PER COAT).
EPOXY SYSTEM (WATER BASE)
a. SEMI-GLOSS FINISH:
1. 1ST COAT: S-W PRO INDUSTRIAL PRO-CRYL
UNIVERSAL PRIMER, B66-310 SERIES (5-10
MILS WET, 2-4 MILS DRY).
2ND COAT: S-W WATERBASED CATALYZED
EPOXY, B70W211/ B60V25.
3RD COAT: S-W WATERBASED CATALYZED
EPOXY, B70W211/ B60V25 (2.5 - 3 MILS DRY
PER COAT).
DRYWALL - (WALLS,…