The document is a comprehensive set of electrical engineering and design drawings for the Orange County Corrections Switchgear Replacement project located in Orange County, Florida, involving Buildings D, E, and F. The drawings, dated 10-5-2023 and prepared by SGM (an engineering firm), provide detailed electrical plans, one-line diagrams, panel schedules, demolition plans, and electrical symbol legends for a significant electrical infrastructure upgrade. The project encompasses multiple floors of the corrections facilities, including power plans, demolition strategies, and replacement of existing electrical panels and switchgear across six floors of three buildings.
The project is estimated to cost $725,000.00 and is being competitively bid through the ProcureNow OpenGov e-Procurement Platform, with sealed bids due by 4:00 pm EST on Thursday, March 7, 2024. The technical specifications indicate a comprehensive electrical system replacement, with strict adherence to multiple electrical codes including NFPA 70 (National Electrical Code), NFPA 72 (National Fire Code), and the Florida Building Code. The drawings specify requirements for voltage drop, circuit tracing, ground and neutral segregation, and arc flash warning labels, suggesting a complex and highly technical electrical infrastructure modernization effort for the Orange County Corrections facility.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ORANGE COUNTY CORRECTIONS
3741 VISION BLVD, ORLANDO, FL 32839
ORANGE COUNTY CORRECTIONS SWITCHGEAR REPLACEMENT
BUILDINGS D, E & F
OWNER:
BOARD OF COUNTY COMMISSIONERS
ORANGE COUNTY, FLORIDA
MAYOR
JERRY L. DEMINGS
COMMISSIONER
NICOLE H. WILSON
DISTRICT 1
COMMISSIONER
MAYRA URIBE
DISTRICT 3
COMMISSIONER
CHRISTINE MOORE
DISTRICT 2
COMMISSIONER
MARIBEL GOMEZ CORDERO
DISTRICT 4
COMMISSIONER
MICHAEL SCOTT
DISTRICT 6
COMMISSIONER
EMILY BONILLA
DISTRICT 5
a. ALL ELECTRICAL WORK AND MATERIALS SHALL BE IN COMPLIANCE WITH ALL GOVERNING CODES
AND STANDARDS. THIS SHALL INCLUDE BUT NOT BE LIMITED TO THE FOLLOWING.
A. NFPA 70 NATIONAL ELECTRICAL CODE (2017)
B. NFPA 72 NATIONAL FIRE CODE (2016)
C. NFPA 101 - LIFE SAFETY CODE (2018)
D. FLORIDA FIRE PREVENTION CODE (7TH EDITION 2020)
E. FLORIDA BUILDING CODE (7TH EDITION 2020)
F. LOCAL REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION
TO REPLACE EXISTING SWITCHGEAR, AND PANELS IN BUILDING D,E,F.
THIS BRIEF DESCRIPTION OF THE SCOPE OF WORK IS NOT ALL INCLUSIVE AND IS COMPLIMENTED BY
THE SET OF CONSTRUCTION DOCUMENTS AND SPECIFICATIONS
BID/PERMIT SET
10-5-2023
Sheet List Table Sheet Number Sheet Title
T001 TITLE SHEET
E001 ELECTRICAL SYMBOLS LEGEND
ED301 DEMO POWER PLANS 1ST FLR BLDG D
ED302 DEMO POWER PLANS 1ST FLR BLDG E
ED303 DEMO POWER PLANS 1ST FLR BLDG F
ED304 DEMO POWER PLANS 2ND FLR BLDG D
ED305 DEMO POWER PLANS 2ND FLR BLDG E
ED306 DEMO POWER PLANS 2ND FLR BLDG F
ED307 DEMO POWER PLANS 3RD FLR BLDG D
ED308 DEMO POWER PLANS 3RD FLR BLDG E
ED309 DEMO POWER PLANS 3RD FLR BLDG F
ED310 DEMO POWER PLANS 4TH FLR BLDG D
ED311 DEMO POWER PLANS 4TH FLR BLDG E
ED312 DEMO POWER PLANS 4TH FLR BLDG F
ED313 DEMO POWER PLANS 5TH FLR BLDG E
ED314 DEMO POWER PLANS 6TH FLR BLDG E
ED501 ELECTRICAL DEMO ONE-LINE DIAGRAMS
E301 POWER PLANS 1ST FLR BLDG D
E302 POWER PLANS 1ST FLR BLDG E
E303 POWER PLANS 1ST FLR BLDG F
E304 POWER PLANS 2ND FLR BLDG D
E305 POWER PLANS 2ND FLR BLDG E
E306 POWER PLANS 2ND FLR BLDG F
E307 POWER PLANS 3RD FLR BLDG D
E308 POWER PLANS 3RD FLR BLDG E
E309 POWER PLANS 3RD FLR BLDG F
E310 POWER PLANS 4TH FLR BLDG D
E311 POWER PLANS 4TH FLR BLDG E
E312 POWER PLANS 4TH FLR BLDG F
E313 POWER PLANS 5TH FLR BLDG E
E314 POWER PLANS 6TH FLR BLDG E
E501 ELECTRICAL ONE-LINE DIAGRAMS
E701 ELECTRICAL PANEL SCHEDULES
E702 ELECTRICAL PANEL SCHEDULES
E703 ELECTRICAL PANEL SCHEDULES
E704 ELECTRICAL PANEL SCHEDULES
E801 ELECTRICAL DETAILS
ORANGE COUNTY
CORRECTIONS
SWITCHGEAR
REPLACEMENT
BUILDINGS D, E & F
ORANGE COUNTY
CAPITAL PROJECTS
DIVISION
400 E. SOUTH STREET
ORLANDO, FL 320801
2021-425
T001
TITLE SHEET
AutoCAD SHX Text
SITE MAP
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text O
AutoCAD SHX Text C
AutoCAD SHX Text Y
AutoCAD SHX Text T
AutoCAD SHX Text N
AutoCAD SHX Text U
AutoCAD SHX Text O
AutoCAD SHX Text C
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text D
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text O
AutoCAD SHX Text B
AutoCAD SHX Text U
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text O
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text L
AutoCAD SHX Text F
AutoCAD SHX Text Y
AutoCAD SHX Text T
AutoCAD SHX Text N
AutoCAD SHX Text D
AutoCAD SHX Text I
AutoCAD SHX Text
BUILDING LOCATION
AutoCAD SHX Text
SCOPE OF WORK
AutoCAD SHX Text N
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
APPLICABLE CODES
AutoCAD SHX Text Sheet Number:
AutoCAD SHX Text Issue:
AutoCAD SHX Text Description
AutoCAD SHX Text Date
AutoCAD SHX Text No.
AutoCAD SHX Text 2018 SGM ENGINEERING, INC. DRAWINGS, WRITTEN MATERIAL, AND DESIGN CONCEPTS SHALL NOT BE USED OR REPRODUCED IN WHOLE OR PART IN ANY FORM OR FORMAT WITHOUT PRIOR WRITTEN CONSENT OF SGM ENGINEERING, INC. DO NOT SCALE DRAWINGS. USE GIVEN DIMENSIONS ONLY. IF NOT SHOWN, VERIFY CORRECT DIMENSIONS WITH THE ENGINEER. CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND CONDITIONS AT JOB SITE.
AutoCAD SHX Text Seal:
AutoCAD SHX Text Sheet Name:
AutoCAD SHX Text Project Name:
AutoCAD SHX Text Client Name:
AutoCAD SHX Text
1200-T001-2021425.DWG
AutoCAD SHX Text Drawing File Name:
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Engineer of Record:
AutoCAD SHX Text License Number:
AutoCAD SHX Text Drawn By:
AutoCAD SHX Text Checked By:
AutoCAD SHX Text 2021-074
AutoCAD SHX Text Project Number:
AutoCAD SHX Text Scale:
AutoCAD SHX Text Design By:
AutoCAD SHX Text
AS SHOWN
AutoCAD SHX Text
10-5-2023 BID/PERMIT
AutoCAD SHX Text
STATE OF
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text I
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text D
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text L
AutoCAD SHX Text F
AutoCAD SHX Text No. 70700
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text S
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text C
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text P
AutoCAD SHX Text
FL-70700
TV
TV
LIGHTING FIXTURES
POWER DEVICES
SINGLE RECEPTACLE
JUNCTION BOX
DUPLEX RECEPTACLE
DISCONNECT SWITCH
DOOR BELL PUSH BUTTON
EQUIPMENT CONNECTION
SPECIAL PURPOSE RECEPTACLE
DOUBLE DUPLEX RECEPTACLE
MOTOR STARTER
SHUNT TRIP. MTD. AT 6'-5" AFF/AFG TO TOP OF ENCLOSURE
PHOTOCELL
DOOR BELL
TIMECLOCK
TRANSFORMER
DUPLEX RECEPTACLE, GROUND FAULT, ABOVE COUNTER
DUPLEX RECEPTACLE, GROUND FAULT
SINGLE 250V NON-LOCKING TYPE RECEPTACLE
ABOVE COUNTER DUPLEX RECEPTACLE
DUPLEX RECEPTACLE, HALF SWITCHED
MOTOR
120/208V PANELBOARD, SURFACE MOUNT
277/480V PANELBOARD, SURFACE MOUNT
POWER/DATA POLE
PULL BOX
CEILING MOUNTED RECEPTACLE
RECESSED FLOOR RECEPTACLE
FLOOR MOUNTED JUNCTION BOX
120/208V PANELBOARD, RECESSED
277/480V PANELBOARD, RECESSED
FEEDER OR BRANCH CIRCUIT CONCEALED IN WALL,
CEILING OR FLOOR
STARTER/DISCONNECT SWITCH
GENERATOR
CLOCK
LOCKBOX
DUPLEX RECEPTACLE, GROUND FAULT
WITH CAST ALUMINUM PADLOCKABLE (1
4" HASP) WEATHERPROOF
"IN USE" COVER. TAYMAC MX3200 OR EQUAL
DUPLEX RECEPTACLE, GROUND FAULT
LOCATE WITHIN ELECTRIC WATER COOLER PER
MANUFACTURER'S INSTRUCTIONS
DUPLEX RECEPTACLE FOR COMPUTER WORKSTATION
DUPLEX RECEPTACLE FOR TV LOCATED AT 18"AFF. LOCATE IN
COMMON BOX WITH CCTV
DUPLEX RECEPTACLE FOR TV LOCATED AT 84" AFF UNLESS
NOTED OTHERWISE.
AIR TERMINAL (ALUMINUM CLASS 1 MIN).
ROOFTOP MAIN CONDUCTOR, RUN EXPOSED ACROSS
ROOF.
DOWN CONDUCTOR, RUN CONCEALED IN STRUCTURE -
COPPER CLASS 1
COPPER-CLAD DRIVEN GROUND ROD AND TEST WELL.
SEE SPECIFICATIONS.
BOLTED 3-WAY SPLICE
BOLTED 4-WAY SPLICE
GROUND BUS BAR
GROUND ROD WITH TEST INSPECTION WELL. SEE
SPECIFICATIONS.
PIR-WALL SWITCH DECORATOR MOTION SENSOR, 120/277 VAC,
800/1200W. WATTSTOPPER PW-100 OR EQUAL.
DUAL ULTRASONIC/PIR-WALL SWITCH DECORATOR MOTION SENSOR,
120/277VAC, 800/1200W. WATTSTOPPER DW-100 OR EQUAL.
*DUAL ULTRASONIC/PIR-CEILING MOUNT SENSOR, 24 VDC/VAC,
35mA. WATTSTOPPER DT-305 OR EQUAL.
*DUAL ULTRASONIC/PIR-WALL MOUNT SENSOR, 24 VAC/VDC, 35mA.
WATTSTOPPER DT-205 OR EQUAL.
POWER PACK 120/277 VAC; 20 AMPS, 225mA SECONDARY.
WATTSTOPPER BZ-250 OR EQUAL.
*PIR-WALL MOUNT SENSOR, LOW TEMP, 24 VDC/AC, 20mA.
WATTSTOPPER CB-100 OR EQUAL.
*PIR-CEILING MOUNT SENSOR 24 VDC/VAC, 11mA, WATTSTOPPER
CI-205 OR EQUAL.
QUAD RECEPTACLE, GROUND FAULT
WITH CAST ALUMINUM PADLOCKABLE (1
4" HASP) WEATHERPROOF "IN USE"
COVER. TAYMAC MX 6200 OR EQUAL.
TRACK FIXTURE
CEILING MOUNTED RECESSED, DOWN LIGHT
EMERGENCY LIGHT FIXTURE
2'x4' FIXTURE
1'x4' FIXTURE
2'x2' FIXTURE
SURFACE MOUNTED LIGHTING FIXTURE
2'x4' FIXTURE, BATTERY/EMERGENCY
2'x2' FIXTURE, BATTERY/EMERGENCY
1'x4' FIXTURE, BATTERY/EMERGENCY
FLOOD LIGHT FIXTURE
BOLLARD OR PENDANT LIGHT FIXTURE
POWER DISTRIBUTION
LIGHTING CONTROL DEVICES
LIGHTNING PROTECTION
MISCELLANEOUS SYMBOL LEGEND
ABBREVIATIONS
AMPERES
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
BELOW FINISHED GRADE
ELECTRIC UNIT HEATER
ELECTRIC WATER COOLER
ELECTRIC WATER HEATER
ELECTRICAL METALLIC TUBING
BELOW FINISHED CEILING
EWH
FLUOR
FA
EXIST
EXH
EQUIP
EWC
EUH
EMT
EF
FLUORESCENT
FIRE ALARM
EXHAUST
EXISTING
EXHAUST FAN
EQUIPMENT
CLG
DISC
DWG
EA
CU
CL
CAB
CKT
BFG
CEILING
CENTERLINE
DISCONNECT(ING)
DRAWING(S)
EACH
COPPER
CABINET
CIRCUIT
CONDUIT
AFG
BFC
A
AFF
NATIONAL ELECTRICAL CODE
POLYVINYL CHLORIDE
UNLESS OTHERWISE NOTED
XFMR
V
WP
VA
TEL
UON
TRANSFORMER
TELEPHONE
VOLT-AMPERES
WEATHER PROOF
VOLTS
PVC
PNL
REC
NEC
MTR
MTG
MTD
MISC
MIN
RECEPTACLE
PANEL
MINIMUM
MISCELLANEOUS
MOUNTED
MOUNTING
MOTOR
HEATING/VENTILATING/
KILO-VOLTS-AMPERES
KILO-WATT-HOURS
MOTOR CONTROL CENTERMCC
MH
MFR
MAX
LTG
kVA kWH kW kV
JB
METAL HALIDE
LIGHTING
MANUFACTURER
MAXIMUM
JUNCTION BOX
KILO-VOLTS
KILO-WATTS
HVAC
HV
INC
HP HORSEPOWER
HIGH VOLTAGE
INCANDESCENT
FLA FULL LOAD AMPERES
ABOVE FINISHED CEILINGAFC
W WATTS
TYP TYPICAL
GFCI GROUND FAULT CIRCUIT
INTERRUPTER
CURRENT TRANSFORMERSCT's
KILO-VOLTS-AMPERES REACTIVEkVAR
RGS RIGID GALVANIZED STEEL
C m METER mm MILLIMETER
AIC AMPERES INTERUPTING
CAPACITY
MCB MAIN CIRCUIT BREAKER
MCP MOTOR CIRCUIT PROTECTOR
AIR CONDITIONING
HAND-OFF-AUTOMATIC
HIGH INTENSITY DISCHARGE
HIGH PRESSURE SODIUM
HID
HOA
HPS
GND
HGT
GROUND
HEIGHT
GFP GROUND FAULT PROTECTION
VFD VARIABLE FREQUENCY DRIVE
AMERICAN WIRE GAUGEAWG
PULL STATION INSIDEPSI
EXP EXPLOSION PROOFAUDIO ENHANCEMENTAE
1R1-1,3,5
1M1-1:3:5
1R1-1
1M1-1:3
1R1-1,3
4' WALL MOUNT FIXTURE
4' WALL MOUNT FIXTURE, EMERGENCY
CEILING MOUNTED RECESSED, EMERGENCY DOWN LIGHT
BOLLARD OR PENDANT LUMINAIRE, EMERGENCY
WALL MOUNTED SCONCE FIXTURE, BATTERY/EMERGENCY
POLE MOUNTED LUMINAIRE
SINGLE POLE MOUNT LUMINAIRE-RECTANGLES INDICATE
NUMBER OF FIXTURES
HOMERUN CONSISTING OF ONE SINGLE-PHASE, 1-POLE CIRCUIT, SEE
SPECIFICATIONS AND/OR FEEDER SCHEDULES FOR WIRE SIZES.
PANELBOARD AND CIRCUIT DESIGNATION ARE INDICATED.
HOMERUN CONSISTING OF THREE SINGLE-PHASE CIRCUITS: SEE
SPECIFICATIONS AND/OR FEEDER SCHEDULES FOR WIRE SIZES.
PANELBOARD AND CIRCUIT DESIGNATIONS ARE INDICATED.
HOMERUN CONSISTING OF ONE THREE-PHASE CIRCUITS: SEE
SPECIFICATIONS AND/OR FEEDER SCHEDULES FOR WIRE SIZES.
PANELBOARD AND CIRCUIT DESIGNATIONS ARE INDICATED.
HOMERUN CONSISTING OF ONE SINGLE-PHASE, 2-P0LE CIRCUIT:
SEE SPECIFICATIONS AND/OR FEEDER SCHEDULES FOR WIRE
SIZES. PANELBOARD AND CIRCUIT DESIGNATIONS ARE INDICATED.
HOMERUN CONSISTING OF TWO SINGLE-PHASE CIRCUITS: SEE
SPECIFICATIONS AND/OR FEEDER SCHEDULES FOR WIRE SIZES.
PANELBOARD AND CIRCUIT DESIGNATION ARE INDICATED.
E200
TITLE
SCALE: DETAIL TITLE REFERENCE
DETAIL NUMBER
SHEET NUMBER WHERE DETAIL IS REFERENCED
ADDITIONAL SHEET REFERENCES
E200
DETAIL NUMBER
SHEET NUMBER TO WHERE DETAIL IS REFERENCED
XX.XX
XX
WP
WP
EWC
CEILING MOUNTED RECESSED, WALL WASHER (ARROW
INDICATES DIRECTION OF WASH)
SINGLE FACE EXIT LIGHT FIXTURE ARROW INDICATES
DIRECTION OF EGRESS
DOUBLE FACE EXIT LIGHT FIXTURE ARROW INDICATES
DIRECTION OF EGRESS
POLE MOUNTED SITE LIGHTING FIXTURE RECTANGLES INDICATE
NUMBER OF FIXTURES
PC
TC
C
QUAD RECEPTACLE, GROUND FAULT
C
POWER POLE
J
J
PB
C
ST
DB
G
ALUMINUMAL
P
PD
PP
T
DN
SPD SURGE PROTECTION DEVICE, SEE SPECIFICATIONS.
SPD SURGE PROTECTION DEVICE
ECB
MMS
ENCLOSED CIRCUIT BREAKER
MANUAL MOTOR STARTER SWITCH
LT
R9
PP
W
CI
DT
S
D1
C
NOTIFICATION APPLIANCE CIRCUIT
*ULTRASONIC-CEILING CORRIDOR MOTION SENSOR, 24 VDC/VAC,
40mA. WATTSTOPPER WT-2250 OR EQUAL.
NAC
SWITCH, 1 POLE, LETTER INDICATES SWITCHLEG CONTROLLED.
SWITCH, KEYSWITCH
S3 4S
S
PS
2S
SWITCH
a
SWITCH, 2 POLE
S
SWITCH, 3-WAY
SWITCH, 4-WAY
KS
SWITCH - PILOT LIGHT
MS
S
MOTOR RATED SWITCH
S
SWITCH, 3-WAY, LETTER INDICATES SWITCHLEG CONTROLLED
SWITCH, KEYSWITCH, 3-WAY
NIGHT LIGHT, UNSWITCHEDNL
*FOR LOW VOLTAGE OCCUPANCY SENSORS, PROVIDE POWER
PACK(S) 120/277 VAC; 20 AMPS, 225mA SECONDARY AS NEEDED FOR
ZONE/AREA CONTROL. WATTSTOPPER BZ-250 OR EQUAL.
SWITCHES
SWITCH - LINE VOLTAGE TIMER, 120/277 VAC. WATTSTOPPER
TS-400 OR EQUAL.
DUAL ULTRASONIC/PIR-DUAL RELAY WALL SWITCH DECORATOR
MOTION SENSOR, 120/277VAC, 800/1200W. WATTSTOPPER DW-200 OR
EQUAL.
D2
S SWITCH, EXPLOSION PROOF
QUAD RECEPTACLE FOR COMPUTER WORKSTATION
C
4' STRIP FIXTURE
4' STRIP FIXTURE, BATTERY/EMERGENCY
4' STRIP FIXTURE, WALL MOUNTED
4' STRIP FIXTURE, WALL MOUNTED,
BATTERY/EMERGENCY
3a
3K
EXP
LB
VARIABLE FREQUENCY DRIVEVFD
UL 924 LISTED FAILSAFE EMERGENCY SWITCHING RELAY, LVS EPC-A
OR EQUAL. LOWER CASE LETTER NEXT TO DEVICE INDICATES
SWITCHLEG CONTROLLED.
LVS
S SWITCH, LOW VOLTAGE MOMENTARYL
TS
SWP
SWITCH, WEATHERPROOF
LIGHTING CONTACTORLC
ORANGE COUNTY
CORRECTIONS
SWITCHGEAR
REPLACEMENT
BUILDINGS D, E & F
ORANGE COUNTY
CAPITAL PROJECTS
DIVISION
400 E. SOUTH STREET
ORLANDO, FL 320801
2021-425
E001
ELECTRICAL SYMBOLS
LEGEND
ELECTRICAL SYMBOLS LEGEND
AutoCAD SHX Text Sheet Number:
AutoCAD SHX Text Issue:
AutoCAD SHX Text Description
AutoCAD SHX Text Date
AutoCAD SHX Text No.
AutoCAD SHX Text 2018 SGM ENGINEERING, INC. DRAWINGS, WRITTEN MATERIAL, AND DESIGN CONCEPTS SHALL NOT BE USED OR REPRODUCED IN WHOLE OR PART IN ANY FORM OR FORMAT WITHOUT PRIOR WRITTEN CONSENT OF SGM ENGINEERING, INC. DO NOT SCALE DRAWINGS. USE GIVEN DIMENSIONS ONLY. IF NOT SHOWN, VERIFY CORRECT DIMENSIONS WITH THE ENGINEER. CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND CONDITIONS AT JOB SITE.
AutoCAD SHX Text Seal:
AutoCAD SHX Text Sheet Name:
AutoCAD SHX Text Project Name:
AutoCAD SHX Text Client Name:
AutoCAD SHX Text
1600-E001-2021425.DWG
AutoCAD SHX Text Drawing File Name:
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Engineer of Record:
AutoCAD SHX Text License Number:
AutoCAD SHX Text Drawn By:
AutoCAD SHX Text Checked By:
AutoCAD SHX Text 2021-074
AutoCAD SHX Text Project Number:
AutoCAD SHX Text Scale:
AutoCAD SHX Text Design By:
AutoCAD SHX Text
AS SHOWN
AutoCAD SHX Text
10-5-2023 BID/PERMIT
AutoCAD SHX Text
STATE OF
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text I
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text D
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text L
AutoCAD SHX Text F
AutoCAD SHX Text No. 70700
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text S
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text C
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text P
AutoCAD SHX Text
FL-70700
AutoCAD SHX Text
JN
AutoCAD SHX Text
JN
AutoCAD SHX Text
BSB
JUSTIN L. MUNDELL
PUNCH
DOWN
BLOCK
RELAY
CABINET
LIGHTING
CONTROL
CABINET
FATCERC
PAC
LVR/BL
EA
RACK
RACK
RACK
EB
MSB-HV
MSB-LV
B B
LVR/BR
A A
1 1
GENERAL NOTES:
a. REFER TO SYMBOL LEGEND ON SHEET E001.
b. REFER TO BOOK SPECIFICATIONS.
c. REFER TO ARCHITECTURAL INTERIOR ELEVATIONS TO COORDINATE
EXACT PLACEMENT OF ALL DEVICES, EQUIPMENT, FIXTURES,
SWITCHES AND OUTLETS.
d. ALL COMPUTER CIRCUITS SHALL HAVE DEDICATED NEUTRAL FROM
LOAD TO SOURCE EQUIPMENT.
e. ALL FEEDERS ARE TO HAVE LESS THAN 2% TOTAL VOLTAGE DROP
AND ALL BRANCH CIRCUITS SHALL HAVE LESS THAN 3% VOLTAGE
DROP.
f. IF CIRCUITS ARE COMBINED AND RUN AS MULTI-WIRE BRANCH
CIRCUITS SHARING A COMMON NEUTRAL, THEN EACH UNGROUNDED
CONDUCTOR MUST BE DISCONNECTED SIMULTANEOUSLY BY A
COMMON TRIP CIRCUIT BREAKER. CONTRACTOR MAY, AT THEIR
OPTION, PROVIDE EITHER COMMON TRIP MULTI-POLE CIRCUIT
BREAKERS OR UTILIZE MANUFACTURERS LISTED HANDLE TIES IN
ORDER TO PROVIDE THE SIMULTANEOUS TRIP. THESE DEVICES ARE
NOT SHOWN IN THE PANEL SCHEDULES AND MUST BE PROVIDED BY
THIS SCOPE OF WORK. NO MORE THAN 3 CIRCUITS MAY BE
COMBINED IN A SINGLE RACEWAY WITHOUT PRIOR APPROVAL BY
THE ENGINEER.
g. CONTRACTOR SHALL PERFORM CIRCUIT TRACE ON ALL BRANCH
CIRCUITS IN PANEL BEING REPLACED AND PROVIDE AN UPDATED
TYPEWRITTEN PANEL SCHEDULE IDENTIFYING CIRCUITS FED AND
LOCATION AND/OR ROOM NUMBER.
h. CONTRACTOR TO SEGREGATE ALL GROUNDS AND NEUTRALS ONTO
THE CORRECT BUS.
i. CONTRACTOR TO CONFIRM THAT THERE IS A GROUND CONDUCTOR
FOR EACH LOAD OR THAT THE CONDUIT PATH GROUND IS
CONTINUOUS FOR EACH LOAD.
j. CONTRACTOR SHALL PROVIDE ARC FLASH WARNING LABELS FOR
ALL PANELS BEING REPLACED.
k. CONTRACTOR TO CHECK PHASE ROTATION PRIOR TO
DISCONNECTION AND AFTER RECONNECTION OF POWER.
l. CONTRACTOR TO IDENTIFY CONDUITS EXITING PANEL WITH CIRCUIT
NUMBER INFORMATION.
m. ENSURE ALL WIRES ARE TAGGED PER IDENTIFICATION
SPECIFICATION.
n. ENSURE NEW PANEL HEIGHT DOES NOT RESULT IN EXCEEDING 6'-7"
TO HIGHEST BREAKER.
PLAN KEY NOTES:
1. CONTRACTOR TO PROVIDE AND INSTALL NEW PANEL. REFER TO
SHEET E501 FOR PANEL SIZES. CONTRACTOR TO EXTEND EXISTING
WIRING AND CONDUIT AS REQUIRED. REFER TO SHEET
E701,E702,E703, AND E704 FOR BREAKER SIZES.
PHOENIX
VIDEO
VISITATION
BRC
GENESIS
HORIZON
MAIN
JAIL
BLDG B
BLDG A
ADMIN
NORTH
PERIMETER
SHERIFF
OPERATIONS
FDC
KEY PLAN
NTS
N
CASSADY
ORANGE COUNTY
CORRECTIONS
SWITCHGEAR
REPLACEMENT
BUILDINGS D, E & F
ORANGE COUNTY
CAPITAL PROJECTS
DIVISION
400 E. SOUTH STREET
ORLANDO, FL 320801
2021-425
E301
POWER PLANS 1ST FLR
BLDG D
POWER PLANS 1ST FLR BLDG D
00 8' 16'4'SCALE: 1/8"=1'-0"
N
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text
DN
AutoCAD SHX Text
DN
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text
DN
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text Sheet Number:
AutoCAD SHX Text Issue:
AutoCAD SHX Text Description
AutoCAD SHX Text Date
AutoCAD SHX Text No.
AutoCAD SHX Text 2018 SGM ENGINEERING, INC. DRAWINGS, WRITTEN MATERIAL, AND DESIGN CONCEPTS SHALL NOT BE USED OR REPRODUCED IN WHOLE OR PART IN ANY FORM OR FORMAT WITHOUT PRIOR WRITTEN CONSENT OF SGM ENGINEERING, INC. DO NOT SCALE DRAWINGS. USE GIVEN DIMENSIONS ONLY. IF NOT SHOWN, VERIFY CORRECT DIMENSIONS WITH THE ENGINEER. CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND CONDITIONS AT JOB SITE.
AutoCAD SHX Text Seal:
AutoCAD SHX Text Sheet Name:
AutoCAD SHX Text Project Name:
AutoCAD SHX Text Client Name:
AutoCAD SHX Text
1600-E301-2021425.DWG
AutoCAD SHX Text Drawing File Name:
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Engineer of Record:
AutoCAD SHX Text License Number:
AutoCAD SHX Text Drawn By:
AutoCAD SHX Text Checked By:
AutoCAD SHX Text 2021-074
AutoCAD SHX Text Project Number:
AutoCAD SHX Text Scale:
AutoCAD SHX Text Design By:
AutoCAD SHX Text
AS SHOWN
AutoCAD SHX Text
10-5-2023 BID/PERMIT
AutoCAD SHX Text
STATE OF
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text I
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text D
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text L
AutoCAD SHX Text F
AutoCAD SHX Text No. 70700
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text S
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text C
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text P
AutoCAD SHX Text
FL-70700
AutoCAD SHX Text
JN
AutoCAD SHX Text
JN
AutoCAD SHX Text
BSB
E
EF
MSB/A
MSB/A
F
GENERAL NOTES:
a. REFER TO SYMBOL LEGEND ON SHEET E001.
b. REFER TO BOOK SPECIFICATIONS.
c. REFER TO ARCHITECTURAL INTERIOR ELEVATIONS TO COORDINATE
EXACT PLACEMENT OF ALL DEVICES, EQUIPMENT, FIXTURES,
SWITCHES AND OUTLETS.
d. ALL COMPUTER CIRCUITS SHALL HAVE DEDICATED NEUTRAL FROM
LOAD TO SOURCE EQUIPMENT.
e. ALL FEEDERS ARE TO HAVE LESS THAN 2% TOTAL VOLTAGE DROP
AND ALL BRANCH CIRCUITS SHALL HAVE LESS THAN 3% VOLTAGE
DROP.
f. IF CIRCUITS ARE COMBINED AND RUN AS MULTI-WIRE BRANCH
CIRCUITS SHARING A COMMON NEUTRAL, THEN EACH UNGROUNDED
CONDUCTOR MUST BE DISCONNECTED SIMULTANEOUSLY BY A
COMMON TRIP CIRCUIT BREAKER. CONTRACTOR MAY, AT THEIR
OPTION, PROVIDE EITHER COMMON TRIP MULTI-POLE CIRCUIT
BREAKERS OR UTILIZE MANUFACTURERS LISTED HANDLE TIES IN
ORDER TO PROVIDE THE SIMULTANEOUS TRIP. THESE DEVICES ARE
NOT SHOWN IN THE PANEL SCHEDULES AND MUST BE PROVIDED BY
THIS SCOPE OF WORK. NO MORE THAN 3 CIRCUITS MAY BE
COMBINED IN A SINGLE RACEWAY WITHOUT PRIOR APPROVAL BY
THE ENGINEER.
g. CONTRACTOR SHALL PERFORM CIRCUIT TRACE ON ALL BRANCH
CIRCUITS IN PANEL BEING REPLACED AND PROVIDE AN UPDATED
TYPEWRITTEN PANEL SCHEDULE IDENTIFYING CIRCUITS FED AND
LOCATION AND/OR ROOM NUMBER.
h. CONTRACTOR TO SEGREGATE ALL GROUNDS AND NEUTRALS ONTO
THE CORRECT BUS.
i. CONTRACTOR TO CONFIRM THAT THERE IS A GROUND CONDUCTOR
FOR EACH LOAD OR THAT THE CONDUIT PATH GROUND IS
CONTINUOUS FOR EACH LOAD.
j. CONTRACTOR SHALL PROVIDE ARC FLASH WARNING LABELS FOR
ALL PANELS BEING REPLACED.
k. CONTRACTOR TO CHECK PHASE ROTATION PRIOR TO
DISCONNECTION AND AFTER RECONNECTION OF POWER.
l. CONTRACTOR TO IDENTIFY CONDUITS EXITING PANEL WITH CIRCUIT
NUMBER INFORMATION.
m. ENSURE ALL WIRES ARE TAGGED PER IDENTIFICATION
SPECIFICATION.
n. ENSURE NEW PANEL HEIGHT DOES NOT RESULT IN EXCEEDING 6'-7"
TO HIGHEST BREAKER.
PLAN KEY NOTES:
1. CONTRACTOR TO PROVIDE AND INSTALL NEW PANEL. REFER TO
SHEET E501 FOR PANEL SIZES. CONTRACTOR TO EXTEND EXISTING
WIRING AND CONDUIT AS REQUIRED. REFER TO SHEET
E701,E702,E703, AND E704 FOR BREAKER SIZES.
PHOENIX
VIDEO
VISITATION
BRC
GENESIS
HORIZON
MAIN
JAIL
BLDG B
BLDG A
ADMIN
NORTH
PERIMETER
SHERIFF
OPERATIONS
FDC
KEY PLAN
NTS
N
CASSADY
ORANGE COUNTY
CORRECTIONS
SWITCHGEAR
REPLACEMENT
BUILDINGS D, E & F
ORANGE COUNTY
CAPITAL PROJECTS
DIVISION
400 E. SOUTH STREET
ORLANDO, FL 320801
2021-425
E302
POWER PLANS 1ST FLR
BLDG E
POWER PLANS 1ST FLR BLDG E
00 8' 16'4'SCALE: 1/8"=1'-0"
N
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Sheet Number:
AutoCAD SHX Text Issue:
AutoCAD SHX Text Description
AutoCAD SHX Text Date
AutoCAD SHX Text No.
AutoCAD SHX Text 2018 SGM ENGINEERING, INC. DRAWINGS, WRITTEN MATERIAL, AND DESIGN CONCEPTS SHALL NOT BE USED OR REPRODUCED IN WHOLE OR PART IN ANY FORM OR FORMAT WITHOUT PRIOR WRITTEN CONSENT OF SGM ENGINEERING, INC. DO NOT SCALE DRAWINGS. USE GIVEN DIMENSIONS ONLY. IF NOT SHOWN, VERIFY CORRECT DIMENSIONS WITH THE ENGINEER. CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND CONDITIONS AT JOB SITE.
AutoCAD SHX Text Seal:
AutoCAD SHX Text Sheet Name:
AutoCAD SHX Text Project Name:
AutoCAD SHX Text Client Name:
AutoCAD SHX Text
1600-E301-2021425.DWG
AutoCAD SHX Text Drawing File Name:
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Engineer of Record:
AutoCAD SHX Text License Number:
AutoCAD SHX Text Drawn By:
AutoCAD SHX Text Checked By:
AutoCAD SHX Text 2021-074
AutoCAD SHX Text Project Number:
AutoCAD SHX Text Scale:
AutoCAD SHX Text Design By:
AutoCAD SHX Text
AS SHOWN
AutoCAD SHX Text
10-5-2023 BID/PERMIT
AutoCAD SHX Text
STATE OF
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text I
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text D
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text L
AutoCAD SHX Text F
AutoCAD SHX Text No. 70700
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text S
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text C
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text P
AutoCAD SHX Text
FL-70700
AutoCAD SHX Text
JN
AutoCAD SHX Text
JN
AutoCAD SHX Text
BSB
1M-9 1M-10 1M-11 1M-12 1M-13 1M-14 1M-15 1M-16
1N-9
1N-10
1N-11
1N-12
1N-13
1N-14
1N-15
1N-16
F135c
F135a
F135b
F-1K DORM
F-1L DORM
F-1M DORM
F-1N DORM
1M-1N TRAP
1K-3
1K-4
1L-4 1L-3
M
N
ER
GENERAL NOTES:
a. REFER TO SYMBOL LEGEND ON SHEET E001.
b. REFER TO BOOK SPECIFICATIONS.
c. REFER TO ARCHITECTURAL INTERIOR ELEVATIONS TO COORDINATE
EXACT PLACEMENT OF ALL DEVICES, EQUIPMENT, FIXTURES,
SWITCHES AND OUTLETS.
d. ALL COMPUTER CIRCUITS SHALL HAVE DEDICATED NEUTRAL FROM
LOAD TO SOURCE EQUIPMENT.
e. ALL FEEDERS ARE TO HAVE LESS THAN 2% TOTAL VOLTAGE DROP
AND ALL BRANCH CIRCUITS SHALL HAVE LESS THAN 3% VOLTAGE
DROP.
f. IF CIRCUITS ARE COMBINED AND RUN AS MULTI-WIRE BRANCH
CIRCUITS SHARING A COMMON NEUTRAL, THEN EACH UNGROUNDED
CONDUCTOR MUST BE DISCONNECTED SIMULTANEOUSLY BY A
COMMON TRIP CIRCUIT BREAKER. CONTRACTOR MAY, AT THEIR
OPTION, PROVIDE EITHER COMMON TRIP MULTI-POLE CIRCUIT
BREAKERS OR UTILIZE MANUFACTURERS LISTED HANDLE TIES IN
ORDER TO PROVIDE THE SIMULTANEOUS TRIP. THESE DEVICES ARE
NOT SHOWN IN THE PANEL SCHEDULES AND MUST BE PROVIDED BY
THIS SCOPE OF WORK. NO MORE THAN 3 CIRCUITS MAY BE
COMBINED IN A SINGLE RACEWAY WITHOUT PRIOR APPROVAL BY
THE ENGINEER.
g. CONTRACTOR SHALL PERFORM CIRCUIT TRACE ON ALL BRANCH
CIRCUITS IN PANEL BEING REPLACED AND PROVIDE AN UPDATED
TYPEWRITTEN PANEL SCHEDULE IDENTIFYING CIRCUITS FED AND
LOCATION AND/OR ROOM NUMBER.
h. CONTRACTOR TO SEGREGATE ALL GROUNDS AND NEUTRALS ONTO
THE CORRECT BUS.
i. CONTRACTOR TO CONFIRM THAT THERE IS A GROUND CONDUCTOR
FOR EACH LOAD OR THAT THE CONDUIT PATH GROUND IS
CONTINUOUS FOR EACH LOAD.
j. CONTRACTOR SHALL PROVIDE ARC FLASH WARNING LABELS FOR
ALL PANELS BEING REPLACED.
k. CONTRACTOR TO CHECK PHASE ROTATION PRIOR TO
DISCONNECTION AND AFTER RECONNECTION OF POWER.
l. CONTRACTOR TO IDENTIFY CONDUITS EXITING PANEL WITH CIRCUIT
NUMBER INFORMATION.
m. ENSURE ALL WIRES ARE TAGGED PER IDENTIFICATION
SPECIFICATION.
n. ENSURE NEW PANEL HEIGHT DOES NOT RESULT IN EXCEEDING 6'-7"
TO HIGHEST BREAKER.
PLAN KEY NOTES:
1. CONTRACTOR TO PROVIDE AND INSTALL NEW PANEL. REFER TO
SHEET E501 FOR PANEL SIZES. CONTRACTOR TO EXTEND EXISTING
WIRING AND CONDUIT AS REQUIRED. REFER TO SHEET
E701,E702,E703, AND E704 FOR BREAKER SIZES.
PHOENIX
VIDEO
VISITATION
BRC
GENESIS
HORIZON
MAIN
JAIL
BLDG B
BLDG A
ADMIN
NORTH
PERIMETER
SHERIFF
OPERATIONS
FDC
KEY PLAN
NTS
N
CASSADY
ORANGE COUNTY
CORRECTIONS
SWITCHGEAR
REPLACEMENT
BUILDINGS D, E & F
ORANGE COUNTY
CAPITAL PROJECTS
DIVISION
400 E. SOUTH STREET
ORLANDO, FL 320801
2021-425
E303
POWER PLANS 1ST FLR
BLDG F
POWER PLANS 1ST FLR BLDG F
00 8' 16'4'SCALE: 1/8"=1'-0"
N
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Sheet Number:
AutoCAD SHX Text Issue:
AutoCAD SHX Text Description
AutoCAD SHX Text Date
AutoCAD SHX Text No.
AutoCAD SHX Text 2018 SGM ENGINEERING, INC. DRAWINGS, WRITTEN MATERIAL, AND DESIGN CONCEPTS SHALL NOT BE USED OR REPRODUCED IN WHOLE OR PART IN ANY FORM OR FORMAT WITHOUT PRIOR WRITTEN CONSENT OF SGM ENGINEERING, INC. DO NOT SCALE DRAWINGS. USE GIVEN DIMENSIONS ONLY. IF NOT SHOWN, VERIFY CORRECT DIMENSIONS WITH THE ENGINEER. CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND CONDITIONS AT JOB SITE.
AutoCAD SHX Text Seal:
AutoCAD SHX Text Sheet Name:
AutoCAD SHX Text Project Name:
AutoCAD SHX Text Client Name:
AutoCAD SHX Text
1600-E301-2021425.DWG
AutoCAD SHX Text Drawing File Name:
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Engineer of Record:
AutoCAD SHX Text License Number:
AutoCAD SHX Text Drawn By:
AutoCAD SHX Text Checked By:
AutoCAD SHX Text 2021-074
AutoCAD SHX Text Project Number:
AutoCAD SHX Text Scale:
AutoCAD SHX Text Design By:
AutoCAD SHX Text
AS SHOWN
AutoCAD SHX Text
10-5-2023 BID/PERMIT
AutoCAD SHX Text
STATE OF
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text I
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text D
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text L
AutoCAD SHX Text F
AutoCAD SHX Text No. 70700
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text S
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text C
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text P
AutoCAD SHX Text
FL-70700
AutoCAD SHX Text
JN
AutoCAD SHX Text
JN
AutoCAD SHX Text
BSB
K
GENERAL NOTES:
a. REFER TO SYMBOL LEGEND ON SHEET E001.
b. REFER TO BOOK SPECIFICATIONS.
c. REFER TO ARCHITECTURAL INTERIOR ELEVATIONS TO COORDINATE
EXACT PLACEMENT OF ALL DEVICES, EQUIPMENT, FIXTURES,
SWITCHES AND OUTLETS.
d. ALL COMPUTER CIRCUITS SHALL HAVE DEDICATED NEUTRAL FROM
LOAD TO SOURCE EQUIPMENT.
e. ALL FEEDERS ARE TO HAVE LESS THAN 2% TOTAL VOLTAGE DROP
AND ALL BRANCH CIRCUITS SHALL HAVE LESS THAN 3% VOLTAGE
DROP.
f. IF CIRCUITS ARE COMBINED AND RUN AS MULTI-WIRE BRANCH
CIRCUITS SHARING A COMMON NEUTRAL, THEN EACH UNGROUNDED
CONDUCTOR MUST BE DISCONNECTED SIMULTANEOUSLY BY A
COMMON TRIP CIRCUIT BREAKER. CONTRACTOR MAY, AT THEIR
OPTION, PROVIDE EITHER COMMON TRIP MULTI-POLE CIRCUIT
BREAKERS OR UTILIZE MANUFACTURERS LISTED HANDLE TIES IN
ORDER TO PROVIDE THE SIMULTANEOUS TRIP. THESE DEVICES ARE
NOT SHOWN IN THE PANEL SCHEDULES AND MUST BE PROVIDED BY
THIS SCOPE OF WORK. NO MORE THAN 3 CIRCUITS MAY BE
COMBINED IN A SINGLE RACEWAY WITHOUT PRIOR APPROVAL BY
THE ENGINEER.
g. CONTRACTOR SHALL PERFORM CIRCUIT TRACE ON ALL BRANCH
CIRCUITS IN PANEL BEING REPLACED AND PROVIDE AN UPDATED
TYPEWRITTEN PANEL SCHEDULE IDENTIFYING CIRCUITS FED AND
LOCATION AND/OR ROOM NUMBER.
h. CONTRACTOR TO SEGREGATE ALL GROUNDS AND NEUTRALS ONTO
THE CORRECT BUS.
i. CONTRACTOR TO CONFIRM THAT THERE IS A GROUND CONDUCTOR
FOR EACH LOAD OR THAT THE CONDUIT PATH GROUND IS
CONTINUOUS FOR EACH LOAD.
j. CONTRACTOR SHALL PROVIDE ARC FLASH WARNING LABELS FOR
ALL PANELS BEING REPLACED.
k. CONTRACTOR TO CHECK PHASE ROTATION PRIOR TO
DISCONNECTION AND AFTER RECONNECTION OF POWER.
l. CONTRACTOR TO IDENTIFY CONDUITS EXITING PANEL WITH CIRCUIT
NUMBER INFORMATION.
m. ENSURE ALL WIRES ARE TAGGED PER IDENTIFICATION
SPECIFICATION.
n. ENSURE NEW PANEL HEIGHT DOES NOT RESULT IN EXCEEDING 6'-7"
TO HIGHEST BREAKER.
PLAN KEY NOTES:
1. CONTRACTOR TO PROVIDE AND INSTALL NEW PANEL. REFER TO
SHEET E501 FOR PANEL SIZES. CONTRACTOR TO EXTEND EXISTING
WIRING AND CONDUIT AS REQUIRED. REFER TO SHEET
E701,E702,E703, AND E704 FOR BREAKER SIZES.
PHOENIX
VIDEO
VISITATION
BRC
GENESIS
HORIZON
MAIN
JAIL
BLDG B
BLDG A
ADMIN
NORTH
PERIMETER
SHERIFF
OPERATIONS
FDC
KEY PLAN
NTS
N
CASSADY
ORANGE COUNTY
CORRECTIONS
SWITCHGEAR
REPLACEMENT
BUILDINGS D, E & F
ORANGE COUNTY
CAPITAL PROJECTS
DIVISION
400 E. SOUTH STREET
ORLANDO, FL 320801
2021-425
E304
POWER PLANS 2ND FLR
BLDG D
POWER PLANS 2ND FLR BLDG D
00 8' 16'4'SCALE: 1/8"=1'-0"
N
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
DN
AutoCAD SHX Text
DN
AutoCAD SHX Text
DN
AutoCAD SHX Text
DN
AutoCAD SHX Text
UP
AutoCAD SHX Text
DN
AutoCAD SHX Text
DN
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text
DN
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text
DN
AutoCAD SHX Text
DN
AutoCAD SHX Text
UP
AutoCAD SHX Text Sheet Number:
AutoCAD SHX Text Issue:
AutoCAD SHX Text Description
AutoCAD SHX Text Date
AutoCAD SHX Text No.
AutoCAD SHX Text 2018 SGM ENGINEERING, INC. DRAWINGS, WRITTEN MATERIAL, AND DESIGN CONCEPTS SHALL NOT BE USED OR REPRODUCED IN WHOLE OR PART IN ANY FORM OR FORMAT WITHOUT PRIOR WRITTEN CONSENT OF SGM ENGINEERING, INC. DO NOT SCALE DRAWINGS. USE GIVEN DIMENSIONS ONLY. IF NOT SHOWN, VERIFY CORRECT DIMENSIONS WITH THE ENGINEER. CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND CONDITIONS AT JOB SITE.
AutoCAD SHX Text Seal:
AutoCAD SHX Text Sheet Name:
AutoCAD SHX Text Project Name:
AutoCAD SHX Text Client Name:
AutoCAD SHX Text
1600-E301-2021425.DWG
AutoCAD SHX Text Drawing File Name:
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Engineer of Record:
AutoCAD SHX Text License Number:
AutoCAD SHX Text Drawn By:
AutoCAD SHX Text Checked By:
AutoCAD SHX Text 2021-074
AutoCAD SHX Text Project Number:
AutoCAD SHX Text Scale:
AutoCAD SHX Text Design By:
AutoCAD SHX Text
AS SHOWN
AutoCAD SHX Text
10-5-2023 BID/PERMIT
AutoCAD SHX Text
STATE OF
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text I
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text D
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text L
AutoCAD SHX Text F
AutoCAD SHX Text No. 70700
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text S
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text C
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text P
AutoCAD SHX Text
FL-70700
AutoCAD SHX Text
JN
AutoCAD SHX Text
JN
AutoCAD SHX Text
BSB
K2
GENERAL NOTES:
a. REFER TO SYMBOL LEGEND ON SHEET E001.
b. REFER TO BOOK SPECIFICATIONS.
c. REFER TO ARCHITECTURAL INTERIOR ELEVATIONS TO COORDINATE
EXACT PLACEMENT OF ALL DEVICES, EQUIPMENT, FIXTURES,
SWITCHES AND OUTLETS.
d. ALL COMPUTER CIRCUITS SHALL HAVE DEDICATED NEUTRAL FROM
LOAD TO SOURCE EQUIPMENT.
e. ALL FEEDERS ARE TO HAVE LESS THAN 2% TOTAL VOLTAGE DROP
AND ALL BRANCH CIRCUITS SHALL HAVE LESS THAN 3% VOLTAGE
DROP.
f. IF CIRCUITS ARE COMBINED AND RUN AS MULTI-WIRE BRANCH
CIRCUITS SHARING A COMMON NEUTRAL, THEN EACH UNGROUNDED
CONDUCTOR MUST BE DISCONNECTED SIMULTANEOUSLY BY A
COMMON TRIP CIRCUIT BREAKER. CONTRACTOR MAY, AT THEIR
OPTION, PROVIDE EITHER COMMON TRIP MULTI-POLE CIRCUIT
BREAKERS OR UTILIZE MANUFACTURERS LISTED HANDLE TIES IN
ORDER TO PROVIDE THE SIMULTANEOUS TRIP. THESE DEVICES ARE
NOT SHOWN IN THE PANEL SCHEDULES AND MUST BE PROVIDED BY
THIS SCOPE OF WORK. NO MORE THAN 3 CIRCUITS MAY BE
COMBINED IN A SINGLE RACEWAY WITHOUT PRIOR APPROVAL BY
THE ENGINEER.
g. CONTRACTOR SHALL PERFORM CIRCUIT TRACE ON ALL BRANCH
CIRCUITS IN PANEL BEING REPLACED AND PROVIDE AN UPDATED
TYPEWRITTEN PANEL SCHEDULE IDENTIFYING CIRCUITS FED AND
LOCATION AND/OR ROOM NUMBER.
h. CONTRACTOR TO SEGREGATE ALL GROUNDS AND NEUTRALS ONTO
THE CORRECT BUS.
i. CONTRACTOR TO CONFIRM THAT THERE IS A GROUND CONDUCTOR
FOR EACH LOAD OR THAT THE CONDUIT PATH GROUND IS
CONTINUOUS FOR EACH LOAD.
j. CONTRACTOR SHALL PROVIDE ARC FLASH WARNING LABELS FOR
ALL PANELS BEING REPLACED.
k. CONTRACTOR TO CHECK PHASE ROTATION PRIOR TO
DISCONNECTION AND AFTER RECONNECTION OF POWER.
l. CONTRACTOR TO IDENTIFY CONDUITS EXITING PANEL WITH CIRCUIT
NUMBER INFORMATION.
m. ENSURE ALL WIRES ARE TAGGED PER IDENTIFICATION
SPECIFICATION.
n. ENSURE NEW PANEL HEIGHT DOES NOT RESULT IN EXCEEDING 6'-7"
TO HIGHEST BREAKER.
PLAN KEY NOTES:
1. CONTRACTOR TO PROVIDE AND INSTALL NEW PANEL. REFER TO
SHEET E501 FOR PANEL SIZES. CONTRACTOR TO EXTEND EXISTING
WIRING AND CONDUIT AS REQUIRED. REFER TO SHEET
E701,E702,E703, AND E704 FOR BREAKER SIZES.
PHOENIX
VIDEO
VISITATION
BRC
GENESIS
HORIZON
MAIN
JAIL
BLDG B
BLDG A
ADMIN
NORTH
PERIMETER
SHERIFF
OPERATIONS
FDC
KEY PLAN
NTS
N
CASSADY
ORANGE COUNTY
CORRECTIONS
SWITCHGEAR
REPLACEMENT
BUILDINGS D, E & F
ORANGE COUNTY
CAPITAL PROJECTS
DIVISION
400 E. SOUTH STREET
ORLANDO, FL 320801
2021-425
E305
POWER PLANS 2ND FLR
BLDG E
POWER PLANS 2ND FLR BLDG E
00 8' 16'4'SCALE: 1/8"=1'-0"
N
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Sheet Number:
AutoCAD SHX Text Issue:
AutoCAD SHX Text Description
AutoCAD SHX Text Date
AutoCAD SHX Text No.
AutoCAD SHX Text 2018 SGM ENGINEERING, INC. DRAWINGS, WRITTEN MATERIAL, AND DESIGN CONCEPTS SHALL NOT BE USED OR REPRODUCED IN WHOLE OR PART IN ANY FORM OR FORMAT WITHOUT PRIOR WRITTEN CONSENT OF SGM ENGINEERING, INC. DO NOT SCALE DRAWINGS. USE GIVEN DIMENSIONS ONLY. IF NOT SHOWN, VERIFY CORRECT DIMENSIONS WITH THE ENGINEER. CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND CONDITIONS AT JOB SITE.
AutoCAD SHX Text Seal:
AutoCAD SHX Text Sheet Name:
AutoCAD SHX Text Project Name:
AutoCAD SHX Text Client Name:
AutoCAD SHX Text
1600-E301-2021425.DWG
AutoCAD SHX Text Drawing File Name:
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Engineer of Record:
AutoCAD SHX Text License Number:
AutoCAD SHX Text Drawn By:
AutoCAD SHX Text Checked By:
AutoCAD SHX Text 2021-074
AutoCAD SHX Text Project Number:
AutoCAD SHX Text Scale:
AutoCAD SHX Text Design By:
AutoCAD SHX Text
AS SHOWN
AutoCAD SHX Text
10-5-2023 BID/PERMIT
AutoCAD SHX Text
STATE OF
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text I
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text D
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text L
AutoCAD SHX Text F
AutoCAD SHX Text No. 70700
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text S
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text C
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text P
AutoCAD SHX Text
FL-70700
AutoCAD SHX Text
JN
AutoCAD SHX Text
JN
AutoCAD SHX Text
BSB
1M-1 1M-2 1M-3 1M-4 1M-5 1M-6 1M-7 1M-8
1N-1
1N-2
1N-3
1N-4
1N-5
1N-6
1N-7
1N-8
1K-1
1K-2
1L-2 1L-1
K3
GENERAL NOTES:
a. REFER TO SYMBOL LEGEND ON SHEET E001.
b. REFER TO BOOK SPECIFICATIONS.
c. REFER TO ARCHITECTURAL INTERIOR ELEVATIONS TO COORDINATE
EXACT PLACEMENT OF ALL DEVICES, EQUIPMENT, FIXTURES,
SWITCHES AND OUTLETS.
d. ALL COMPUTER CIRCUITS SHALL HAVE DEDICATED NEUTRAL FROM
LOAD TO SOURCE EQUIPMENT.
e. ALL FEEDERS ARE TO HAVE LESS THAN 2% TOTAL VOLTAGE DROP
AND ALL BRANCH CIRCUITS SHALL HAVE LESS THAN 3% VOLTAGE
DROP.
f. IF CIRCUITS ARE COMBINED AND RUN AS MULTI-WIRE BRANCH
CIRCUITS SHARING A COMMON NEUTRAL, THEN EACH UNGROUNDED
CONDUCTOR MUST BE DISCONNECTED SIMULTANEOUSLY BY A
COMMON TRIP CIRCUIT BREAKER. CONTRACTOR MAY, AT THEIR
OPTION, PROVIDE EITHER COMMON TRIP MULTI-POLE CIRCUIT
BREAKERS OR UTILIZE MANUFACTURERS LISTED HANDLE TIES IN
ORDER TO PROVIDE THE SIMULTANEOUS TRIP. THESE DEVICES ARE
NOT SHOWN IN THE PANEL SCHEDULES AND MUST BE PROVIDED BY
THIS SCOPE OF WORK. NO MORE THAN 3 CIRCUITS MAY BE
COMBINED IN A SINGLE RACEWAY WITHOUT PRIOR APPROVAL BY
THE ENGINEER.
g. CONTRACTOR SHALL PERFORM CIRCUIT TRACE ON ALL BRANCH
CIRCUITS IN PANEL BEING REPLACED AND PROVIDE AN UPDATED
TYPEWRITTEN PANEL SCHEDULE IDENTIFYING CIRCUITS FED AND
LOCATION AND/OR ROOM NUMBER.
h. CONTRACTOR TO SEGREGATE ALL GROUNDS AND NEUTRALS ONTO
THE CORRECT BUS.
i. CONTRACTOR TO CONFIRM THAT THERE IS A GROUND CONDUCTOR
FOR EACH LOAD OR THAT THE CONDUIT PATH GROUND IS
CONTINUOUS FOR EACH LOAD.
j. CONTRACTOR SHALL PROVIDE ARC FLASH WARNING LABELS FOR
ALL PANELS BEING REPLACED.
k. CONTRACTOR TO CHECK PHASE ROTATION PRIOR TO
DISCONNECTION AND AFTER RECONNECTION OF POWER.
l. CONTRACTOR TO IDENTIFY CONDUITS EXITING PANEL WITH CIRCUIT
NUMBER INFORMATION.
m. ENSURE ALL WIRES ARE TAGGED PER IDENTIFICATION
SPECIFICATION.
n. ENSURE NEW PANEL HEIGHT DOES NOT RESULT IN EXCEEDING 6'-7"
TO HIGHEST BREAKER.
PLAN KEY NOTES:
1. CONTRACTOR TO PROVIDE AND INSTALL NEW PANEL. REFER TO
SHEET E501 FOR PANEL SIZES. CONTRACTOR TO EXTEND EXISTING
WIRING AND CONDUIT AS REQUIRED. REFER TO SHEET
E701,E702,E703, AND E704 FOR BREAKER SIZES.
PHOENIX
VIDEO
VISITATION
BRC
GENESIS
HORIZON
MAIN
JAIL
BLDG B
BLDG A
ADMIN
NORTH
PERIMETER
SHERIFF
OPERATIONS
FDC
KEY PLAN
NTS
N
CASSADY
ORANGE COUNTY
CORRECTIONS
SWITCHGEAR
REPLACEMENT
BUILDINGS D, E & F
ORANGE COUNTY
CAPITAL PROJECTS
DIVISION
400 E. SOUTH STREET
ORLANDO, FL 320801
2021-425
E306
POWER PLANS 2ND FLR
BLDG F
POWER PLANS 2ND FLR BLDG F
00 8' 16'4'SCALE: 1/8"=1'-0"
N
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Sheet Number:
AutoCAD SHX Text Issue:
AutoCAD SHX Text Description
AutoCAD SHX Text Date
AutoCAD SHX Text No.
AutoCAD SHX Text 2018 SGM ENGINEERING, INC. DRAWINGS, WRITTEN MATERIAL, AND DESIGN CONCEPTS SHALL NOT BE USED OR REPRODUCED IN WHOLE OR PART IN ANY FORM OR FORMAT WITHOUT PRIOR WRITTEN CONSENT OF SGM ENGINEERING, INC. DO NOT SCALE DRAWINGS. USE GIVEN DIMENSIONS ONLY. IF NOT SHOWN, VERIFY CORRECT DIMENSIONS WITH THE ENGINEER. CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND CONDITIONS AT JOB SITE.
AutoCAD SHX Text Seal:
AutoCAD SHX Text Sheet Name:
AutoCAD SHX Text Project Name:
AutoCAD SHX Text Client Name:
AutoCAD SHX Text
1600-E301-2021425.DWG
AutoCAD SHX Text Drawing File Name:
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Engineer of Record:
AutoCAD SHX Text License Number:
AutoCAD SHX Text Drawn By:
AutoCAD SHX Text Checked By:
AutoCAD SHX Text 2021-074
AutoCAD SHX Text Project Number:
AutoCAD SHX Text Scale:
AutoCAD SHX Text Design By:
AutoCAD SHX Text
AS SHOWN
AutoCAD SHX Text
10-5-2023 BID/PERMIT
AutoCAD SHX Text
STATE OF
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text I
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text D
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text L
AutoCAD SHX Text F
AutoCAD SHX Text No. 70700
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text S
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text C
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text P
AutoCAD SHX Text
FL-70700
AutoCAD SHX Text
JN
AutoCAD SHX Text
JN
AutoCAD SHX Text
BSB
EQDHP-D
EHDP/D
ELDP-D
ED
D
EC
C
1 1
GENERAL NOTES:
a. REFER TO SYMBOL LEGEND ON SHEET E001.
b. REFER TO BOOK SPECIFICATIONS.
c. REFER TO ARCHITECTURAL INTERIOR ELEVATIONS TO COORDINATE
EXACT PLACEMENT OF ALL DEVICES, EQUIPMENT, FIXTURES,
SWITCHES AND OUTLETS.
d. ALL COMPUTER CIRCUITS SHALL HAVE DEDICATED NEUTRAL FROM
LOAD TO SOURCE EQUIPMENT.
e. ALL FEEDERS ARE TO HAVE LESS THAN 2% TOTAL VOLTAGE DROP
AND ALL BRANCH CIRCUITS SHALL HAVE LESS THAN 3% VOLTAGE
DROP.
f. IF CIRCUITS ARE COMBINED AND RUN AS MULTI-WIRE BRANCH
CIRCUITS SHARING A COMMON NEUTRAL, THEN EACH UNGROUNDED
CONDUCTOR MUST BE DISCONNECTED SIMULTANEOUSLY BY A
COMMON TRIP CIRCUIT BREAKER. CONTRACTOR MAY, AT THEIR
OPTION, PROVIDE EITHER COMMON TRIP MULTI-POLE CIRCUIT
BREAKERS OR UTILIZE MANUFACTURERS LISTED HANDLE TIES IN
ORDER TO PROVIDE THE SIMULTANEOUS TRIP. THESE DEVICES ARE
NOT SHOWN IN THE PANEL SCHEDULES AND MUST BE PROVIDED BY
THIS SCOPE OF WORK. NO MORE THAN 3 CIRCUITS MAY BE
COMBINED IN A SINGLE RACEWAY WITHOUT PRIOR APPROVAL BY
THE ENGINEER.
g. CONTRACTOR SHALL PERFORM CIRCUIT TRACE ON ALL BRANCH
CIRCUITS IN PANEL BEING REPLACED AND PROVIDE AN UPDATED
TYPEWRITTEN PANEL SCHEDULE IDENTIFYING CIRCUITS FED AND
LOCATION AND/OR ROOM NUMBER.
h. CONTRACTOR TO SEGREGATE ALL GROUNDS AND NEUTRALS ONTO
THE CORRECT BUS.
i. CONTRACTOR TO CONFIRM THAT THERE IS A GROUND CONDUCTOR
FOR EACH LOAD OR THAT THE CONDUIT PATH GROUND IS
CONTINUOUS FOR EACH LOAD.
j. CONTRACTOR SHALL PROVIDE ARC FLASH WARNING LABELS FOR
ALL PANELS BEING REPLACED.
k. CONTRACTOR TO CHECK PHASE ROTATION PRIOR TO
DISCONNECTION AND AFTER RECONNECTION OF POWER.
l. CONTRACTOR TO IDENTIFY CONDUITS EXITING PANEL WITH CIRCUIT
NUMBER INFORMATION.
m. ENSURE ALL WIRES ARE TAGGED PER IDENTIFICATION
SPECIFICATION.
n. ENSURE NEW PANEL HEIGHT DOES NOT RESULT IN EXCEEDING 6'-7"
TO HIGHEST BREAKER.
PLAN KEY NOTES:
1. CONTRACTOR TO PROVIDE AND INSTALL NEW PANEL. REFER TO
SHEET E501 FOR PANEL SIZES. CONTRACTOR TO EXTEND EXISTING
WIRING AND CONDUIT AS REQUIRED. REFER TO SHEET
E701,E702,E703, AND E704 FOR BREAKER SIZES.
PHOENIX
VIDEO
VISITATION
BRC
GENESIS
HORIZON
MAIN
JAIL
BLDG B
BLDG A
ADMIN
NORTH
PERIMETER
SHERIFF
OPERATIONS
FDC
KEY PLAN
NTS
N
CASSADY
ORANGE COUNTY
CORRECTIONS
SWITCHGEAR
REPLACEMENT
BUILDINGS D, E & F
ORANGE COUNTY
CAPITAL PROJECTS
DIVISION
400 E. SOUTH STREET
ORLANDO, FL 320801
2021-425
E307
POWER PLANS 3RD FLR
BLDG D
POWER PLANS 3RD FLR BLDG D
00 8' 16'4'SCALE: 1/8"=1'-0"
N
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Sheet Number:
AutoCAD SHX Text Issue:
AutoCAD SHX Text Description
AutoCAD SHX Text Date
AutoCAD SHX Text No.
AutoCAD SHX Text 2018 SGM ENGINEERING, INC. DRAWINGS, WRITTEN MATERIAL, AND DESIGN CONCEPTS SHALL NOT BE USED OR REPRODUCED IN WHOLE OR PART IN ANY FORM OR FORMAT WITHOUT PRIOR WRITTEN CONSENT OF SGM ENGINEERING, INC. DO NOT SCALE DRAWINGS. USE GIVEN DIMENSIONS ONLY. IF NOT SHOWN, VERIFY CORRECT DIMENSIONS WITH THE ENGINEER. CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND CONDITIONS AT JOB SITE.
AutoCAD SHX Text Seal:
AutoCAD SHX Text Sheet Name:
AutoCAD SHX Text Project Name:
AutoCAD SHX Text Client Name:
AutoCAD SHX Text
1600-E301-2021425.DWG
AutoCAD SHX Text Drawing File Name:
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .