Y23-749_OC_CORRECTIONS_UPS_IV_REPLACEMENT_(30x42).pdf
PDF 5 MB Posted
- Solicitation number
- Y23-749
- Issued by
- Orange County, Orlando City, Florida
About this file
This is a comprehensive set of electrical engineering design documents for the Orange County Corrections Uninterrupted Power Supply (UPS) Systems Replacement project located at 2450 33rd Street, Orlando, Florida. The project involves replacing the existing UPS system at the Sheriff's Operations Building, with work scheduled to be completed as of September 23, 2022. The design documents include electrical site plans, demolition plans, one-line diagrams, electrical schedules, and detailed electrical specifications. The project scope encompasses installing a new 30kW UPS system, including mechanical, electrical, and fire protection components, with the existing UPS system to be removed.
The project is being managed by the Orange County Capital Projects Division and will adhere to multiple governing codes and standards, including NFPA 70 (National Electrical Code), NFPA 72 (National Fire Code), NFPA 101 (Life Safety Code), Florida Fire Prevention Code, and Florida Building Code. The electrical work involves complex system replacements, circuit relocations, and comprehensive grounding and electrical infrastructure modifications. The design emphasizes maintaining less than 2% voltage drop on feeders and 3% on branch circuits, with specific requirements for circuit breakers, neutrals, and equipment grounding. The project documents indicate careful planning for electrical system continuity, safety, and compliance with local and national electrical standards.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ORANGE COUNTY CORRECTIONS
2450 33RD STREET, ORLANDO, FL 32839
ORANGE COUNTY CORRECTIONS UPS REPLACEMENT
OWNER:
BOARD OF COUNTY COMMISSIONERS
ORANGE COUNTY, FLORIDA
MAYOR
JERRY L. DEMINGS
COMMISSIONER
BETSY VANDERLEY
DISTRICT 1
COMMISSIONER
MAYRA URIBE
DISTRICT 3
COMMISSIONER
CHRISTINE MOORE
DISTRICT 2
COMMISSIONER
MARIBEL GOMEZ CORDERO
DISTRICT 4
COMMISSIONER
VICTORIA P. SIPLIN
DISTRICT 6
COMMISSIONER
EMILY BONILLA
DISTRICT 5
a. ALL ELECTRICAL WORK AND MATERIALS SHALL BE IN COMPLIANCE WITH ALL GOVERNING CODES
AND STANDARDS. THIS SHALL INCLUDE BUT NOT BE LIMITED TO THE FOLLOWING.
A. NFPA 70 NATIONAL ELECTRICAL CODE (2014)
B. NFPA 72 NATIONAL FIRE CODE (2013)
C. NFPA 101 - LIFE SAFETY CODE (2015)
D. FLORIDA FIRE PREVENTION CODE (6TH EDITION 2017)
E. FLORIDA BUILDING CODE (6TH EDITION 2017)
F. LOCAL REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION
INSTALL NEW UPS SYSTEM, TO INCLUDE MECHANICAL, ELECTRICAL AND FIRE PROTECTION. EXISTING PS
TO BE REMOVED.
THIS BRIEF DESCRIPTION OF THE SCOPE OF WORK IS NOT ALL INCLUSIVE AND IS COMPLIMENTED BY
THE SET OF CONSTRUCTION DOCUMENTS AND SPECIFICATIONS
Sheet List Table Sheet Number Sheet Title
T001 COVER SHEET
E001 ELECTRICAL SYMBOLS LEGEND
ED301 DEMO 1ST LEVEL SHERIFF OPERATIONS
E301 1ST LEVEL SHERIFF OPERATIONS
ED501 DEMO ONE LINE DIAGRAM
E501 ONE LINE DIAGRAM
E701 ELECTRICAL SCHEDULES
E801 ELECTRICAL DETAILS
E101 ELECTRICAL SITE PLAN
S.100 GENERATOR NOTES & PAD DETAILS
SEPTEMBER 23, 2022
T001
COVER SHEET
COVER SHEET
ORANGE COUNTY
CORRECTIONS UPS
REPLACEMENT
Y19-824
SHERIFF'S OP BLDG
ORANGE COUNTY
CAPITAL PROJECTS
DIVISION
400 E. SOUTH STREET
ORLANDO, FL 320801
AutoCAD SHX Text
SITE MAP
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text O
AutoCAD SHX Text C
AutoCAD SHX Text Y
AutoCAD SHX Text T
AutoCAD SHX Text N
AutoCAD SHX Text U
AutoCAD SHX Text O
AutoCAD SHX Text C
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text D
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text O
AutoCAD SHX Text B
AutoCAD SHX Text U
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text O
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text L
AutoCAD SHX Text F
AutoCAD SHX Text Y
AutoCAD SHX Text T
AutoCAD SHX Text N
AutoCAD SHX Text D
AutoCAD SHX Text I
AutoCAD SHX Text
BUILDING LOCATION
AutoCAD SHX Text
SCOPE OF WORK
AutoCAD SHX Text N
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
APPLICABLE CODES
AutoCAD SHX Text Sheet Number:
AutoCAD SHX Text Issue:
AutoCAD SHX Text Description
AutoCAD SHX Text Date
AutoCAD SHX Text No.
AutoCAD SHX Text 2018 SGM ENGINEERING, INC. DRAWINGS, WRITTEN MATERIAL, AND DESIGN CONCEPTS SHALL NOT BE USED OR REPRODUCED IN WHOLE OR PART IN ANY FORM OR FORMAT WITHOUT PRIOR WRITTEN CONSENT OF SGM ENGINEERING, INC. DO NOT SCALE DRAWINGS. USE GIVEN DIMENSIONS ONLY. IF NOT SHOWN, VERIFY CORRECT DIMENSIONS WITH THE ENGINEER. CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND CONDITIONS AT JOB SITE.
AutoCAD SHX Text Seal:
AutoCAD SHX Text Sheet Name:
AutoCAD SHX Text Project Name:
AutoCAD SHX Text Client Name:
AutoCAD SHX Text
1200-T001-2019386.DWG
AutoCAD SHX Text Drawing File Name:
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Engineer of Record:
AutoCAD SHX Text License Number:
AutoCAD SHX Text Drawn By:
AutoCAD SHX Text Checked By:
AutoCAD SHX Text 2019-386
AutoCAD SHX Text Project Number:
AutoCAD SHX Text Scale:
AutoCAD SHX Text Design By:
AutoCAD SHX Text
AS SHOWN
AutoCAD SHX Text 09/23/2022 100%%%
TV
TV
LIGHTING FIXTURES
POWER DEVICES
SINGLE RECEPTACLE
JUNCTION BOX
DUPLEX RECEPTACLE
DISCONNECT SWITCH
DOOR BELL PUSH BUTTON
EQUIPMENT CONNECTION
SPECIAL PURPOSE RECEPTACLE
DOUBLE DUPLEX RECEPTACLE
MOTOR STARTER
SHUNT TRIP. MTD. AT 6'-5" AFF/AFG TO TOP OF ENCLOSURE
PHOTOCELL
DOOR BELL
TIMECLOCK
TRANSFORMER
DUPLEX RECEPTACLE, GROUND FAULT, ABOVE COUNTER
DUPLEX RECEPTACLE, GROUND FAULT
SINGLE 250V NON-LOCKING TYPE RECEPTACLE
ABOVE COUNTER DUPLEX RECEPTACLE
DUPLEX RECEPTACLE, HALF SWITCHED
MOTOR
120/208V PANELBOARD, SURFACE MOUNT
277/480V PANELBOARD, SURFACE MOUNT
POWER/DATA POLE
PULL BOX
CEILING MOUNTED RECEPTACLE
RECESSED FLOOR RECEPTACLE
FLOOR MOUNTED JUNCTION BOX
120/208V PANELBOARD, RECESSED
277/480V PANELBOARD, RECESSED
FEEDER OR BRANCH CIRCUIT CONCEALED IN WALL,
CEILING OR FLOOR
STARTER/DISCONNECT SWITCH
GENERATOR
CLOCK
LOCKBOX
DUPLEX RECEPTACLE, GROUND FAULT
WITH CAST ALUMINUM WEATHERPROOF "IN USE"
COVER
DUPLEX RECEPTACLE, GROUND FAULT
LOCATE WITHIN ELECTRIC WATER COOLER PER
MANUFACTURER'S INSTRUCTIONS
DUPLEX RECEPTACLE FOR COMPUTER WORKSTATION
DUPLEX RECEPTACLE FOR TV LOCATED AT 18"AFF. LOCATE IN
COMMON BOX WITH CCTV
DUPLEX RECEPTACLE FOR TV LOCATED AT 84" AFF UNLESS
NOTED OTHERWISE.
AIR TERMINAL (ALUMINUM CLASS 1 MIN).
ROOFTOP MAIN CONDUCTOR, RUN EXPOSED ACROSS
ROOF.
DOWN CONDUCTOR, RUN CONCEALED IN STRUCTURE -
COPPER CLASS 1
COPPER-CLAD DRIVEN GROUND ROD AND TEST WELL.
SEE SPECIFICATIONS.
BOLTED 3-WAY SPLICE
BOLTED 4-WAY SPLICE
ROOF DRAIN BOND
GROUND BUS BAR
GROUND ROD WITH TEST INSPECTION WELL. SEE
SPECIFICATIONS.
PIR-WALL SWITCH DECORATOR MOTION SENSOR, 120/277 VAC,
800/1200W. WATTSTOPPER PW-100 OR EQUAL.
DUAL ULTRASONIC/PIR-WALL SWITCH DECORATOR MOTION SENSOR,
120/277VAC, 800/1200W. WATTSTOPPER DW-100 OR EQUAL.
*DUAL ULTRASONIC/PIR-CEILING MOUNT SENSOR, 24 VDC/VAC,
35mA. WATTSTOPPER DT-305 OR EQUAL.
*DUAL ULTRASONIC/PIR-WALL MOUNT SENSOR, 24 VAC/VDC, 35mA.
WATTSTOPPER DT-205 OR EQUAL.
POWER PACK 120/277 VAC; 20 AMPS, 225mA SECONDARY.
WATTSTOPPER BZ-150 OR EQUAL.
*PIR-WALL MOUNT SENSOR, LOW TEMP, 24 VDC/AC, 20mA.
WATTSTOPPER CB-100 OR EQUAL.
*PIR-CEILING MOUNT SENSOR 24 VDC/VAC, 11mA, WATTSTOPPER
CI-205 OR EQUAL.
QUAD RECEPTACLE, GROUND FAULT
WITH CAST ALUMINUM WEATHERPROOF "IN USE"
COVER
TRACK FIXTURE
CEILING MOUNTED RECESSED, DOWN LIGHT
EMERGENCY LIGHT FIXTURE
2'x4' FIXTURE
1'x4' FIXTURE
2'x2' FIXTURE
SURFACE MOUNTED LIGHTING FIXTURE
2'x4' FIXTURE, BATTERY/EMERGENCY
2'x2' FIXTURE, BATTERY/EMERGENCY
1'x4' FIXTURE, BATTERY/EMERGENCY
FLOOD LIGHT FIXTURE
BOLLARD OR PENDANT LIGHT FIXTURE
POWER DISTRIBUTION
LIGHTING CONTROL DEVICES
LIGHTNING PROTECTION
MISCELLANEOUS SYMBOL LEGEND
ABBREVIATIONS
1R1-1,3,5
1M1-1:3:5
1R1-1
1M1-1:3
1R1-1,3
4' WALL MOUNT FIXTURE
4' WALL MOUNT FIXTURE, EMERGENCY
CEILING MOUNTED RECESSED, EMERGENCY DOWN LIGHT
BOLLARD OR PENDANT LUMINAIRE, EMERGENCY
WALL MOUNTED SCONCE FIXTURE, BATTERY/EMERGENCY
POLE MOUNTED LUMINAIRE
SINGLE POLE MOUNT LUMINAIRE-RECTANGLES INDICATE
NUMBER OF FIXTURES
HOMERUN CONSISTING OF ONE SINGLE-PHASE, 1-POLE CIRCUIT, SEE
SPECIFICATIONS AND/OR FEEDER SCHEDULES FOR WIRE SIZES.
PANELBOARD AND CIRCUIT DESIGNATION ARE INDICATED.
HOMERUN CONSISTING OF THREE SINGLE-PHASE CIRCUITS: SEE
SPECIFICATIONS AND/OR FEEDER SCHEDULES FOR WIRE SIZES.
PANELBOARD AND CIRCUIT DESIGNATIONS ARE INDICATED.
HOMERUN CONSISTING OF ONE THREE-PHASE CIRCUITS: SEE
SPECIFICATIONS AND/OR FEEDER SCHEDULES FOR WIRE SIZES.
PANELBOARD AND CIRCUIT DESIGNATIONS ARE INDICATED.
HOMERUN CONSISTING OF ONE SINGLE-PHASE, 2-P0LE CIRCUIT:
SEE SPECIFICATIONS AND/OR FEEDER SCHEDULES FOR WIRE
SIZES. PANELBOARD AND CIRCUIT DESIGNATIONS ARE INDICATED.
HOMERUN CONSISTING OF TWO SINGLE-PHASE CIRCUITS: SEE
SPECIFICATIONS AND/OR FEEDER SCHEDULES FOR WIRE SIZES.
PANELBOARD AND CIRCUIT DESIGNATION ARE INDICATED.
E200
TITLE
SCALE: DETAIL TITLE REFERENCE
DETAIL NUMBER
SHEET NUMBER WHERE DETAIL IS REFERENCED
ADDITIONAL SHEET REFERENCES
E200
DETAIL NUMBER
SHEET NUMBER TO WHERE DETAIL IS REFERENCED
XX.XX
XX
WP
WP
EWC
CEILING MOUNTED RECESSED, WALL WASHER (ARROW
INDICATES DIRECTION OF WASH)
SINGLE FACE EXIT LIGHT FIXTURE ARROW INDICATES
DIRECTION OF EGRESS
DOUBLE FACE EXIT LIGHT FIXTURE ARROW INDICATES
DIRECTION OF EGRESS
POLE MOUNTED SITE LIGHTING FIXTURE RECTANGLES INDICATE
NUMBER OF FIXTURES
PC
TC
C
QUAD RECEPTACLE, GROUND FAULT
C
POWER POLE
J
J
PB
C
ST
DB
G
P
PD
PP
T
DN
SPD SURGE PROTECTION DEVICE, SEE SPECIFICATIONS.
LT
R9
P
W
CI
DT
S
D1
C *ULTRASONIC-CEILING CORRIDOR MOTION SENSOR, 24 VDC/VAC,
40mA. WATTSTOPPER WT-2250 OR EQUAL.
SWITCH, 1 POLE, LETTER INDICATES SWITCHLEG CONTROLLED.
SWITCH, KEYSWITCH
S3 4S
S
PS
2S
SWITCH
a
SWITCH, 2 POLE
S
SWITCH, 3-WAY
SWITCH, 4-WAY
KS
SWITCH - PILOT LIGHT
MS
S
MOTOR RATED SWITCH
S
SWITCH, 3-WAY, LETTER INDICATES SWITCHLEG CONTROLLED
SWITCH, KEYSWITCH, 3-WAY
*FOR LOW VOLTAGE OCCUPANCY SENSORS, PROVIDE POWER
PACK(S) 120/277 VAC; 20 AMPS, 225mA SECONDARY AS NEEDED FOR
ZONE/AREA CONTROL. WATTSTOPPER BZ-250 OR EQUAL.
SWITCHES
SWITCH - LINE VOLTAGE TIMER, 120/277 VAC. WATTSTOPPER
TS-400 OR EQUAL.
DUAL ULTRASONIC/PIR-DUAL RELAY WALL SWITCH DECORATOR
MOTION SENSOR, 120/277VAC, 800/1200W. WATTSTOPPER DW-200 OR
EQUAL.
D2
S SWITCH, EXPLOSION PROOF
QUAD RECEPTACLE FOR COMPUTER WORKSTATION
C
4' STRIP FIXTURE
4' STRIP FIXTURE, BATTERY/EMERGENCY
4' STRIP FIXTURE, WALL MOUNTED
4' STRIP FIXTURE, WALL MOUNTED,
BATTERY/EMERGENCY
3a
3K
EXP
LB
VARIABLE FREQUENCY DRIVEVFD
UL 924 LISTED FAILSAFE EMERGENCY SWITCHING RELAY, LVS EPC-A
OR EQUAL. LOCATE IN ACCESSIBLE LOCATION ABOVE CEILING AT
ENTRY DOOR TO SPACE SERVED. PROVIDE LABEL ON CEILING GRID
OR ACCESS PANEL IDENTIFYING LOCATION. LOWER CASE LETTER
NEXT TO DEVICE INDICATES SWITCHLEG CONTROLLED.
LVS
S SWITCH, MOMENTARY, HUBBELL 1557-I OR EQUAL.L
TS
SWP
SWITCH, WEATHERPROOF
LIGHTING CONTACTORLC
A AMPERES
AE AUDIO ENHANCEMENT
AFC ABOVE FINISHED CEILING
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AIC AMPERES INTERUPTING
CAPACITY
AL ALUMINUM
AWG AMERICAN WIRE GAUGE
BFC BELOW FINISHED CEILING
BFG BELOW FINISHED GRADE
C CONDUIT
CAB CABINET
CKT CIRCUIT
CLG CEILING
CL CENTERLINE
CT's CURRENT TRANSFORMERS
CU COPPER
DISC DISCONNECT(ING)
DWG DRAWING(S)
EA EACH
ECB ENCLOSED CIRCUIT BREAKER
EF EXHAUST FAN
EMT ELECTRICAL METALLIC
TUBING
EQUIP EQUIPMENT
EUH ELECTRIC UNIT HEATER
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EXH EXHAUST
EXIST EXISTING
EXP EXPLOSION PROOF
FA FIRE ALARM
FLA FULL LOAD AMPERES
FLUOR FLUORESCENT
GFCI GROUND FAULT CIRCUIT
INTERRUPTER
GFP GROUND FAULT PROTECTION
GND GROUND
GRC GALVANIZED RIGID CONDUIT
HGT HEIGHT
HID HIGH INTENSITY DISCHARGE
HPS HIGH PRESSURE SODIUM
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HVAC HEATING/VENTILATING/ AIR
CONDITIONING
HV HIGH VOLTAGE
INC INCANDESCENT
JB JUNCTION BOX
kV KILO-VOLTS kVA KILO-VOLTS-AMPERES kVAR KILO-VOLTS-AMPERES
REACTIVE
kW KILO-WATTS KWh KILO-WATT-HOURS
LTG LIGHTING
m METER mm MILLIMETER
MAX MAXIMUM
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MCP MOTOR CIRCUIT PROTECTOR
MFR MANUFACTURER
MH METAL HALIDE
MIN MINIMUM
MISC MISCELLANEOUS
MMS MANUAL MOTOR STARTER
SWITCH
MTR MOTOR MOUNTED
MTD MOUNTING MTG
NAC NOTIFICATION APPLIANCE
CIRCUIT
NEC NATIONAL ELECTRICAL CODE
NL NIGHT LIGHT, UNSWITCHED
PNL PANEL
PSI PULL STATION INSIDE
PVC POLYVINYL CHLORIDE
REC RECEPTACLE
RGS RIGID GALVANIZED STEEL
SPD SURGE PROTECTION DEVICE
TEL TELEPHONE
TYP TYPICAL
UON UNLESS OTHERWISE NOTED
V VOLTS
VA VOLT-AMPERES
VFD VARIABLE FREQUENCY DRIVE
W WATTS
WP WEATHER PROOF
XFM TRRANSFORMER
RD
SD
DIMMER SWITCH, SLIDE, 0-10 VOLT, LUTRON OR EQUAL
MOUNTING 3" ABOVE COUNTER OR BACK SPLASH
C
1. DATA JACKS:
EACH RJ45 CAT6 JACK FOR DATA SHALL BE CONNECTED TO
A DEDICATED UTP 4 PR CAT6 CABLE
COMMUNICATIONS "INFORMATION OUTLET" MOUNTED. AT
RECEPTACLE HEIGHT UNLESS OTHERWISE NOTED. MODULE AND
FACEPLATE
NX
X = MOUNTING (F)LUSH, (S)URFACE, (M)ODULAR FURNITURE
ADAPTER (P)OLE, (R)ACEWAY, (D)OUBLE GANG FLUSH, (PD)
PEDESTAL
N = # OF DATA JACKS
SPECIAL NOTES:
PREMISE DISTRIBUTION SYSTEM
ECB ENCLOSED CIRCUIT BREAKER
E001
ELECTRICAL SYMBOLS
LEGEND
ELECTRICAL SYMBOLS LEGEND
ORANGE COUNTY
CORRECTIONS UPS
REPLACEMENT
Y19-824
SHERIFF'S OP BLDG
ORANGE COUNTY
CAPITAL PROJECTS
DIVISION
400 E. SOUTH STREET
ORLANDO, FL 320801
AutoCAD SHX Text Sheet Number:
AutoCAD SHX Text Issue:
AutoCAD SHX Text Description
AutoCAD SHX Text Date
AutoCAD SHX Text No.
AutoCAD SHX Text 2018 SGM ENGINEERING, INC. DRAWINGS, WRITTEN MATERIAL, AND DESIGN CONCEPTS SHALL NOT BE USED OR REPRODUCED IN WHOLE OR PART IN ANY FORM OR FORMAT WITHOUT PRIOR WRITTEN CONSENT OF SGM ENGINEERING, INC. DO NOT SCALE DRAWINGS. USE GIVEN DIMENSIONS ONLY. IF NOT SHOWN, VERIFY CORRECT DIMENSIONS WITH THE ENGINEER. CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND CONDITIONS AT JOB SITE.
AutoCAD SHX Text Seal:
AutoCAD SHX Text Sheet Name:
AutoCAD SHX Text Project Name:
AutoCAD SHX Text Client Name:
AutoCAD SHX Text
1600-E001-2019386.DWG
AutoCAD SHX Text Drawing File Name:
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Engineer of Record:
AutoCAD SHX Text License Number:
AutoCAD SHX Text Drawn By:
AutoCAD SHX Text Checked By:
AutoCAD SHX Text 2019-386
AutoCAD SHX Text Project Number:
AutoCAD SHX Text Scale:
AutoCAD SHX Text Design By:
AutoCAD SHX Text
AS SHOWN
AutoCAD SHX Text
JUSTIN L. MUNDELL
AutoCAD SHX Text
FL70700
AutoCAD SHX Text
BSB
AutoCAD SHX Text
BSB
AutoCAD SHX Text
BSB
SHERIFF'S OPS
1st FLOOR
U
PS
0K
W
NEW UPS
N
E101
ELECTRICAL
SITE PLAN
ELECTRICAL SITE PLAN
00 80' 160'40'SCALE: 1"=80'
ORANGE COUNTY
CORRECTIONS UPS
REPLACEMENT
Y19-824
SHERIFF'S OP BLDG
ORANGE COUNTY
CAPITAL PROJECTS
DIVISION
400 E. SOUTH STREET
ORLANDO, FL 320801
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text 101A
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text 101B
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text 101C
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text 101D
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text 101E
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text 101F
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text 101G
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text M100B
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text 123A
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text 105E
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
AutoCAD SHX Text
ELEVATOR
AutoCAD SHX Text
AutoCAD SHX Text
ELEVATOR
AutoCAD SHX Text
EQUIPMENT
AutoCAD SHX Text M100C
AutoCAD SHX Text
STAIR
AutoCAD SHX Text 198B
AutoCAD SHX Text
STAIR
AutoCAD SHX Text
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text 199C
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text 199B
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
BREAK
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
AutoCAD SHX Text
CONFERENCE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text 199G
AutoCAD SHX Text
OPEN
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text 199E
AutoCAD SHX Text
OPEN
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
TOILET
AutoCAD SHX Text R100B
AutoCAD SHX Text
TOILET
AutoCAD SHX Text R100C
AutoCAD SHX Text
JANITOR
AutoCAD SHX Text J100B
AutoCAD SHX Text
MEN
AutoCAD SHX Text R100H
AutoCAD SHX Text
WOMEN
AutoCAD SHX Text R100D
AutoCAD SHX Text
LOBBY
AutoCAD SHX Text
AutoCAD SHX Text
STAIR
AutoCAD SHX Text 198A
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text 105F
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text 199A
AutoCAD SHX Text
JANITOR
AutoCAD SHX Text J100A
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text
YARD
AutoCAD SHX Text M100A
AutoCAD SHX Text
GYMNASIUM
AutoCAD SHX Text
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text 116A
AutoCAD SHX Text
MEN
AutoCAD SHX Text R100G
AutoCAD SHX Text
WOMEN
AutoCAD SHX Text R100A
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text 199F
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text 105C
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text 105B
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text 105A
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text 105D
AutoCAD SHX Text
OPEN
AutoCAD SHX Text
AREA
AutoCAD SHX Text
AutoCAD SHX Text
WORK
AutoCAD SHX Text
AREA
AutoCAD SHX Text
AutoCAD SHX Text
MEN
AutoCAD SHX Text R100E
AutoCAD SHX Text
WOMEN
AutoCAD SHX Text R100F
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
AutoCAD SHX Text
OPEN
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
GUARD
AutoCAD SHX Text
STATION
AutoCAD SHX Text
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text 199D
AutoCAD SHX Text
VESTIBULE
AutoCAD SHX Text
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text N
AutoCAD SHX Text Sheet Number:
AutoCAD SHX Text Issue:
AutoCAD SHX Text Description
AutoCAD SHX Text Date
AutoCAD SHX Text No.
AutoCAD SHX Text 2018 SGM ENGINEERING, INC. DRAWINGS, WRITTEN MATERIAL, AND DESIGN CONCEPTS SHALL NOT BE USED OR REPRODUCED IN WHOLE OR PART IN ANY FORM OR FORMAT WITHOUT PRIOR WRITTEN CONSENT OF SGM ENGINEERING, INC. DO NOT SCALE DRAWINGS. USE GIVEN DIMENSIONS ONLY. IF NOT SHOWN, VERIFY CORRECT DIMENSIONS WITH THE ENGINEER. CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND CONDITIONS AT JOB SITE.
AutoCAD SHX Text Seal:
AutoCAD SHX Text Sheet Name:
AutoCAD SHX Text Project Name:
AutoCAD SHX Text Client Name:
AutoCAD SHX Text
1600-E101-2019386.DWG
AutoCAD SHX Text Drawing File Name:
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Engineer of Record:
AutoCAD SHX Text License Number:
AutoCAD SHX Text Drawn By:
AutoCAD SHX Text Checked By:
AutoCAD SHX Text 2019-386
AutoCAD SHX Text Project Number:
AutoCAD SHX Text Scale:
AutoCAD SHX Text Design By:
AutoCAD SHX Text
AS SHOWN
AutoCAD SHX Text
JUSTIN L. MUNDELL
AutoCAD SHX Text
FL70700
AutoCAD SHX Text
STATE OF
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text I
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text D
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text L
AutoCAD SHX Text F
AutoCAD SHX Text No. 70700
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text S
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text C
AutoCAD SHX Text S
AutoCAD SHX Text R
AutoCAD SHX Text P
AutoCAD SHX Text
BSB
AutoCAD SHX Text
BSB
AutoCAD SHX Text
BSB
SHERIFF'S OPS
1st FLOOR
MDP
XFR
DPL1
A EM1
ATS
EDPEM
L3
GENERAL NOTES:
a.
b.
c.
d.
e.
f.
g.
h.
i.
j.
k.
l.
m.
n.
o.
p.
PHOENIX
VIDEO
VISITATION
BRC
GENESIS
HORIZON
MAIN
JAIL
BLDG B
BLDG A
ADMIN
NORTH
PERIMETER
SHERIFF
OPERATIONS
FDC
KEY PLAN
NTS
N
CASSADY
PLAN KEY NOTES:
1. REMOVE EXISTING FEED.
GENERAL NOTES:
a. REFER TO SYMBOL LEGEND ON SHEET XXXX.
b. REFER TO BOOK SPECIFICATIONS.
c. REFER TO ARCHITECTURAL INTERIOR ELEVATIONS TO COORDINATE
EXACT PLACEMENT OF ALL DEVICES, EQUIPMENT, FIXTURES,
SWITCHES AND OUTLETS.
d. REFER TO EQUIPMENT SCHEDULES ON DRAWINGS XXX FOR
DISCONNECT, CONDUIT AND WIRE SIZES.
e. ALL COMPUTER CIRCUITS SHALL HAVE DEDICATED NEUTRAL FROM
LOAD TO SOURCE EQUIPMENT.
f. ALL FEEDERS ARE TO HAVE LESS THAN 2% TOTAL VOLTAGE DROP
AND ALL BRANCH CIRCUITS SHALL HAVE LESS THAN 3% VOLTAGE
DROP.
g. IF CIRCUITS ARE COMBINED AND RUN AS MULTI-WIRE BRANCH
CIRCUITS SHARING A COMMON NEUTRAL, THEN EACH UNGROUNDED
CONDUCTOR MUST BE DISCONNECTED SIMULTANEOUSLY BY A
COMMON TRIP CIRCUIT BREAKER. CONTRACTOR MAY, AT THEIR
OPTION, PROVIDE EITHER COMMON TRIP MULTI-POLE CIRCUIT
BREAKERS OR UTILIZE MANUFACTURERS LISTED HANDLE TIES IN
ORDER TO PROVIDE THE SIMULTANEOUS TRIP. THESE DEVICES ARE
NOT SHOWN IN THE PANEL SCHEDULES AND MUST BE PROVIDED BY
THIS SCOPE OF WORK. NO MORE THAN 3 CIRCUITS MAY BE
COMBINED IN A SINGLE RACEWAY WITHOUT PRIOR APPROVAL BY
THE ENGINEER.
h. CONTRACTOR IS RESPONSIBLE FOR CUTTING AND PATCHING
SIDEWALKS OR DIRECTIONAL BORING UNDER ALL SIDEWALKS AND
ROADS. UTILIZE 3000 PSI CONCRETE FOR ANY PATCHING OF
ROADWAY (BLACK CONCRETE) OR SIDEWALK. FINISH LOOK OF THE
CONCRETE SHALL MATCH THE EXISTING LOOK OF THE
SURROUNDING CONCRETE OR ASPHALT. CONTRACTOR SHALL
COMPACT ALL TRENCHES NOT UNDER CONCRETE TO 95% AND
UNDER CONCRETE TO 98% COMPACTION. MAINTAIN THE FLOW OF
TRAFFIC DOWN THE STREET AT ALL TIMES. PROVIDE A WRITTEN
MAINTENANCE OF TRAFFIC PLAN PRIOR TO BEGINNING ANY WORK
THAT WILL DISRUPT THE NORMAL FLOW OF TRAFFIC. PROVIDE ALL
SIGNAGE, FLAGMEN, ETC REQUIRED TO MAINTAIN THE TRAFFIC
FLOW. PLANT NEW GRASS WHERE WORK WAS DISTURBED. ALL
AREAS SHALL BE BROUGHT TO AN "AS FOUND" CONDITION.
i. CONTRACTOR SHALL PERFORM CIRCUIT TRACE ON ALL BRANCH
CIRCUITS IN PANEL BEING REPLACED AND PROVIDE AN UPDATED
TYPEWRITTEN PANEL SCHEDULE IDENTIFYING CIRCUITS FED AND
LOCATION AND/OR ROOM NUMBER.
j. CONTRACTOR TO SEGREGATE ALL GROUNDS AND NEUTRALS ONTO
THE CORRECT BUS.
k. CONTRACTOR TO CONFIRM THAT THERE IS A GROUND CONDUCTOR
FOR EACH LOAD OR THAT THE CONDUIT PATH GROUND IS
CONTINUOUS FOR EACH LOAD.
l. CONTRACTOR SHALL PROVIDE ARC FLASH WARNING LABELS FOR
ALL PANELS BEING REPLACED.
m. CONTRACTOR TO CHECK PHASE ROTATION PRIOR TO
DISCONNECTION AND AFTER RECONNECTION OF POWER.
n. CONTRACTOR TO IDENTIFY CONDUITS EXITING PANEL WITH CIRCUIT
NUMBER INFORMATION.
o. ENSURE ALL WIRES ARE TAGGED PER IDENTIFICATION
SPECIFICATION.
p. ENSURE NEW PANEL HEIGHT DOES NOT RESULT IN EXCEEDING 6'-7"
TO HIGHEST BREAKER.
ED301
DEMO 1ST LEVEL
SHERIFF OPERATIONS
DEMO 1ST LEVEL SHERIFF OPERATIONS
00 16' 32'8'SCALE: 1/16"=1'-0"
N
ORANGE COUNTY
CORRECTIONS UPS
REPLACEMENT
Y19-824
SHERIFF'S OP BLDG
ORANGE COUNTY
CAPITAL PROJECTS
DIVISION
400 E. SOUTH STREET
ORLANDO, FL 320801
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text 101A
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text 101B
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text 101C
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text 101D
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text 101E
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text 101F
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text 101G
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text M100B
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text 123A
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text 105E
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
AutoCAD SHX Text
ELEVATOR
AutoCAD SHX Text
AutoCAD SHX Text
ELEVATOR
AutoCAD SHX Text
EQUIPMENT
AutoCAD SHX Text M100C
AutoCAD SHX Text
STAIR
AutoCAD SHX Text 198B
AutoCAD SHX Text
STAIR
AutoCAD SHX Text
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text 199C
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text 199B
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
BREAK
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
AutoCAD SHX Text
CONFERENCE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text 199G
AutoCAD SHX Text
OPEN
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text 199E
AutoCAD SHX Text
OPEN
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
TOILET
AutoCAD SHX Text R100B
AutoCAD SHX Text
TOILET
AutoCAD SHX Text R100C
AutoCAD SHX Text
JANITOR
AutoCAD SHX Text J100B
AutoCAD SHX Text
MEN
AutoCAD SHX Text R100H
AutoCAD SHX Text
WOMEN
AutoCAD SHX Text R100D
AutoCAD SHX Text
LOBBY
AutoCAD SHX Text
AutoCAD SHX Text
STAIR
AutoCAD SHX Text 198A
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text 105F
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text 199A
AutoCAD SHX Text
JANITOR
AutoCAD SHX Text J100A
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text
YARD
AutoCAD SHX Text M100A
AutoCAD SHX Text
GYMNASIUM
AutoCAD SHX Text
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text 116A
AutoCAD SHX Text
MEN
AutoCAD SHX Text R100G
AutoCAD SHX Text
WOMEN
AutoCAD SHX Text R100A
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text 199F
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text 105C
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text 105B
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text 105A
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text 105D
AutoCAD SHX Text
OPEN
AutoCAD SHX Text
AREA
AutoCAD SHX Text
AutoCAD SHX Text
WORK
AutoCAD SHX Text
AREA
AutoCAD SHX Text
AutoCAD SHX Text
MEN
AutoCAD SHX Text R100E
AutoCAD SHX Text
WOMEN
AutoCAD SHX Text R100F
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
AutoCAD SHX Text
OPEN
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
GUARD
AutoCAD SHX Text
STATION
AutoCAD SHX Text
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text 199D
AutoCAD SHX Text
VESTIBULE
AutoCAD SHX Text
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text N
AutoCAD SHX Text Sheet Number:
AutoCAD SHX Text Issue:
AutoCAD SHX Text Description
AutoCAD SHX Text Date
AutoCAD SHX Text No.
AutoCAD SHX Text 2018 SGM ENGINEERING, INC. DRAWINGS, WRITTEN MATERIAL, AND DESIGN CONCEPTS SHALL NOT BE USED OR REPRODUCED IN WHOLE OR PART IN ANY FORM OR FORMAT WITHOUT PRIOR WRITTEN CONSENT OF SGM ENGINEERING, INC. DO NOT SCALE DRAWINGS. USE GIVEN DIMENSIONS ONLY. IF NOT SHOWN, VERIFY CORRECT DIMENSIONS WITH THE ENGINEER. CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND CONDITIONS AT JOB SITE.
AutoCAD SHX Text Seal:
AutoCAD SHX Text Sheet Name:
AutoCAD SHX Text Project Name:
AutoCAD SHX Text Client Name:
AutoCAD SHX Text
1600-ED301-2019386-SHERIFF OP.DWG
AutoCAD SHX Text Drawing File Name:
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Engineer of Record:
AutoCAD SHX Text License Number:
AutoCAD SHX Text Drawn By:
AutoCAD SHX Text Checked By:
AutoCAD SHX Text 2019-386
AutoCAD SHX Text Project Number:
AutoCAD SHX Text Scale:
AutoCAD SHX Text Design By:
AutoCAD SHX Text
AS SHOWN
AutoCAD SHX Text
JUSTIN L. MUNDELL
AutoCAD SHX Text
FL70700
AutoCAD SHX Text
BSB
AutoCAD SHX Text
BSB
AutoCAD SHX Text
BSB
PHOENIX
VIDEO
VISITATION
BRC
GENESIS
HORIZON
MAIN
JAIL
BLDG B
BLDG A
ADMIN
NORTH
PERIMETER
SHERIFF
OPERATIONS
FDC
KEY PLAN
NTS
N
CASSADY
SHERIFF'S OPS
1st FLOOR
MDP
XFR
DPL1
A EM1
ATS
EDPEM
L3
EDHP
ST
EM2 53
ECB
GENERAL NOTES:
a. REFER TO SYMBOL LEGEND ON SHEET XXXX.
b. REFER TO BOOK SPECIFICATIONS.
c. REFER TO ARCHITECTURAL INTERIOR ELEVATIONS TO COORDINATE
EXACT PLACEMENT OF ALL DEVICES, EQUIPMENT, FIXTURES,
SWITCHES AND OUTLETS.
d. REFER TO EQUIPMENT SCHEDULES ON DRAWINGS XXX FOR
DISCONNECT, CONDUIT AND WIRE SIZES.
e. ALL COMPUTER CIRCUITS SHALL HAVE DEDICATED NEUTRAL FROM
LOAD TO SOURCE EQUIPMENT.
f. ALL FEEDERS ARE TO HAVE LESS THAN 2% TOTAL VOLTAGE DROP
AND ALL BRANCH CIRCUITS SHALL HAVE LESS THAN 3% VOLTAGE
DROP.
g. IF CIRCUITS ARE COMBINED AND RUN AS MULTI-WIRE BRANCH
CIRCUITS SHARING A COMMON NEUTRAL, THEN EACH UNGROUNDED
CONDUCTOR MUST BE DISCONNECTED SIMULTANEOUSLY BY A
COMMON TRIP CIRCUIT BREAKER. CONTRACTOR MAY, AT THEIR
OPTION, PROVIDE EITHER COMMON TRIP MULTI-POLE CIRCUIT
BREAKERS OR UTILIZE MANUFACTURERS LISTED HANDLE TIES IN
ORDER TO PROVIDE THE SIMULTANEOUS TRIP. THESE DEVICES ARE
NOT SHOWN IN THE PANEL SCHEDULES AND MUST BE PROVIDED BY
THIS SCOPE OF WORK. NO MORE THAN 3 CIRCUITS MAY BE
COMBINED IN A SINGLE RACEWAY WITHOUT PRIOR APPROVAL BY
THE ENGINEER.
h. CONTRACTOR SHALL PERFORM CIRCUIT TRACE ON ALL BRANCH
CIRCUITS IN PANEL BEING REPLACED AND PROVIDE AN UPDATED
TYPEWRITTEN PANEL SCHEDULE IDENTIFYING CIRCUITS FED AND
LOCATION AND/OR ROOM NUMBER.
i. CONTRACTOR TO SEGREGATE ALL GROUNDS AND NEUTRALS ONTO
THE CORRECT BUS.
j. CONTRACTOR TO CONFIRM THAT THERE IS A GROUND CONDUCTOR
FOR EACH LOAD OR THAT THE CONDUIT PATH GROUND IS
CONTINUOUS FOR EACH LOAD.
k. CONTRACTOR SHALL PROVIDE ARC FLASH WARNING LABELS FOR
ALL PANELS BEING REPLACED.
l. CONTRACTOR TO CHECK PHASE ROTATION PRIOR TO
DISCONNECTION AND AFTER RECONNECTION OF POWER.
m. CONTRACTOR TO IDENTIFY CONDUITS EXITING PANEL WITH CIRCUIT
NUMBER INFORMATION.
n. ENSURE ALL WIRES ARE TAGGED PER IDENTIFICATION
SPECIFICATION.
o. ENSURE NEW PANEL HEIGHT DOES NOT RESULT IN EXCEEDING 6'-7"
TO HIGHEST BREAKER.
PLAN KEY NOTES:
1. PROVIDE AND INSTALL NEW ENCLOSED CIRCUIT BREAKER. REFER TO
ONE LINE DIAGRAM ON SHEET E501 FOR BREAKER SIZE. REFER TO
FEEDER SCHEDULE ON SHEET E701 FOR CONDUIT AND WIRE SIZE.
ALL ECB BREAKERS TO BE SHUNT TRIP BREAKER. INSTALL
DETENTION GRADE FENCING AROUND ECB MAINTAIN PROPER NEC
CLEARANCES.
2. INSTALL NEW EPO.
3. RELOCATE EXISTING CIRCUITS TO PANELS REFER TO ONE LINE FOR
MORE INFORMATION. .
4. PROVIDE AND INSTALL NEW TRANSFORMER FROM EXISTING PANEL
FEEDER TO EQUIPMENT FEEDER SCHEDULE ON SHEET E701 FOR
CONDUIT AND WIRE SIZES.
5. PROVIDE AND INSTALL NEW PANEL REFER TO PANEL FEEDER
SCHEDULE ON SHEET E701 FOR BREAKER, CONDUIT, AND WIRE SIZE.
E301
1ST LEVEL SHERIFF
OPERATIONS
1ST LEVEL SHERIFF OPERATIONS
00 8' 16'4'SCALE: 1/8"=1'-0"
N
ORANGE COUNTY
CORRECTIONS UPS
REPLACEMENT
Y19-824
SHERIFF'S OP BLDG
ORANGE COUNTY
CAPITAL PROJECTS
DIVISION
400 E. SOUTH STREET
ORLANDO, FL 320801
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text 101A
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text 101B
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text 101C
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text 101D
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text 101E
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text 101F
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text 101G
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text M100B
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text 123A
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text 105E
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
AutoCAD SHX Text
ELEVATOR
AutoCAD SHX Text
AutoCAD SHX Text
ELEVATOR
AutoCAD SHX Text
EQUIPMENT
AutoCAD SHX Text M100C
AutoCAD SHX Text
STAIR
AutoCAD SHX Text 198B
AutoCAD SHX Text
STAIR
AutoCAD SHX Text
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text 199C
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text 199B
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
BREAK
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
AutoCAD SHX Text
CONFERENCE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text 199G
AutoCAD SHX Text
OPEN
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text 199E
AutoCAD SHX Text
OPEN
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
TOILET
AutoCAD SHX Text R100B
AutoCAD SHX Text
TOILET
AutoCAD SHX Text R100C
AutoCAD SHX Text
JANITOR
AutoCAD SHX Text J100B
AutoCAD SHX Text
MEN
AutoCAD SHX Text R100H
AutoCAD SHX Text
WOMEN
AutoCAD SHX Text R100D
AutoCAD SHX Text
LOBBY
AutoCAD SHX Text
AutoCAD SHX Text
STAIR
AutoCAD SHX Text 198A
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text 105F
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text 199A
AutoCAD SHX Text
JANITOR
AutoCAD SHX Text J100A
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text
YARD
AutoCAD SHX Text M100A
AutoCAD SHX Text
GYMNASIUM
AutoCAD SHX Text
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text 116A
AutoCAD SHX Text
MEN
AutoCAD SHX Text R100G
AutoCAD SHX Text
WOMEN
AutoCAD SHX Text R100A
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text 199F
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text 105C
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text 105B
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text 105A
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text 105D
AutoCAD SHX Text
OPEN
AutoCAD SHX Text
AREA
AutoCAD SHX Text
AutoCAD SHX Text
WORK
AutoCAD SHX Text
AREA
AutoCAD SHX Text
AutoCAD SHX Text
MEN
AutoCAD SHX Text R100E
AutoCAD SHX Text
WOMEN
AutoCAD SHX Text R100F
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
AutoCAD SHX Text
OPEN
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
GUARD
AutoCAD SHX Text
STATION
AutoCAD SHX Text
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text 199D
AutoCAD SHX Text
VESTIBULE
AutoCAD SHX Text
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AutoCAD SHX Text N
AutoCAD SHX Text Sheet Number:
AutoCAD SHX Text Issue:
AutoCAD SHX Text Description
AutoCAD SHX Text Date
AutoCAD SHX Text No.
AutoCAD SHX Text 2018 SGM ENGINEERING, INC. DRAWINGS, WRITTEN MATERIAL, AND DESIGN CONCEPTS SHALL NOT BE USED OR REPRODUCED IN WHOLE OR PART IN ANY FORM OR FORMAT WITHOUT PRIOR WRITTEN CONSENT OF SGM ENGINEERING, INC. DO NOT SCALE DRAWINGS. USE GIVEN DIMENSIONS ONLY. IF NOT SHOWN, VERIFY CORRECT DIMENSIONS WITH THE ENGINEER. CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND CONDITIONS AT JOB SITE.
AutoCAD SHX Text Seal:
AutoCAD SHX Text Sheet Name:
AutoCAD SHX Text Project Name:
AutoCAD SHX Text Client Name:
AutoCAD SHX Text
1600-E301-2019386-SHERIFF OP.DWG
AutoCAD SHX Text Drawing File Name:
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Engineer of Record:
AutoCAD SHX Text License Number:
AutoCAD SHX Text Drawn By:
AutoCAD SHX Text Checked By:
AutoCAD SHX Text 2019-386
AutoCAD SHX Text Project Number:
AutoCAD SHX Text Scale:
AutoCAD SHX Text Design By:
AutoCAD SHX Text
AS SHOWN
AutoCAD SHX Text
JUSTIN L. MUNDELL
AutoCAD SHX Text
FL70700
AutoCAD SHX Text
BSB
AutoCAD SHX Text
BSB
AutoCAD SHX Text
BSB
EXISTING UTILITY
SWITCH GEAR IN
CEP
100A 3P
277/480V, 3PH, 4W
EXISTING
SWITCHBOARD "P"
480/277 VOLT, 4-WIRE,
1200A
3P GFST
60A 3P
100A 3P
100A 3P
PANEL
"L1"
SPD
200A 3P
200A 3P
PANEL
"LE"
SPD
60A 3P
30A 3P
60A 3P
100A 3P
100A 3P
PANEL
"L2"
SPD
100A 3P
200A 3P
200A 3P
PANEL
"L3"
SPD
400A 3P
30A 3P
20A 3P
P-CHW-1 P-CHW-2
3P,30A
30A 3P
PANEL
"FCU-1"
SPD
30A 3P
EDH-
400A 480/277V 4P ATS A
G EXISTING 500W GENERATOR
400A 3P
PANEL
"EDP"
SPD
TRANSFORMER
30KVA
480-120/208V
100A 3P
#2
PANEL
"EM1"
SPD
3P,30A
WATER
HEATER
3P,100A
WATER HEATER
PUMPS
AC IN GYMCHILLER
3P,30A3P,60A
ELEVATOR
3P,60A
100A 3P
100A 3P
PANEL
"ACC"
SPD
3P,400A
SWITCHBOARD "P1"
208/120 VOLT, 4-WIRE,
25,000AIC
250A 3P
60A 3P
TRANSFORMER
75KVA
480-120/208V
60A 3P
PANEL
"A"
SPD
100A 3P
100A 3P
PANEL
"B"
SPD
100A 3P
100A 3P
PANEL
"C"
SPD
125A 3P
125A 3P
PANEL
"D"
SPD
125A 3P
125A 3P
PANEL
"E"
SPD
125A 3P
125A 3P
PANEL
"F"
SPD
GENERAL NOTES:
a. REFER TO SYMBOL LEGEND AND GENERAL NOTES ON SHEET E001.
b. REFER TO BOOK SPECIFICATIONS.
c. REFER TO ARCHITECTURAL INTERIOR ELEVATIONS TO COORDINATE EXACT PLACEMENT OF
ALL DEVICES, EQUIPMENT, FIXTURES, SWITCHES AND OUTLETS.
d. REFER TO EQUIPMENT SCHEDULES ON SHEET E-701 FOR DISCONNECT, CONDUIT AND WIRE
SIZES.
e. ALL COMPUTER CIRCUITS SHALL HAVE DEDICATED NEUTRAL FROM LOAD TO SOURCE
EQUIPMENT.
f. ALL FEEDERS ARE TO HAVE LESS THAN 2% TOTAL VOLTAGE DROP AND ALL BRANCH
CIRCUITS SHALL HAVE LESS THAN 3% VOLTAGE DROP.
g. IF CIRCUITS ARE COMBINED AND RUN AS MULTI-WIRE BRANCH CIRCUITS SHARING A
COMMON NEUTRAL, THEN EACH UNGROUNDED CONDUCTOR MUST BE DISCONNECTED
SIMULTANEOUSLY BY A COMMON TRIP CIRCUIT BREAKER. CONTRACTOR MAY, AT THEIR
OPTION, PROVIDE EITHER COMMON TRIP MULTI-POLE CIRCUIT BREAKERS OR UTILIZE
MANUFACTURERS LISTED HANDLE TIES IN ORDER TO PROVIDE THE SIMULTANEOUS TRIP.
THESE DEVICES ARE NOT SHOWN IN THE PANEL SCHEDULES AND MUST BE PROVIDED BY
THIS SCOPE OF WORK. NO MORE THAN 3 CURRENT CARRYING CONDUCTORS MAY BE
COMBINED IN A SINGLE RACEWAY WITHOUT PRIOR APPROVAL BY THE ENGINEER OF RECORD
(EOR).
PLAN KEY NOTES:
1. DEMO EXISTING FEEDER AND CONDUIT BACK TO SOURCE AS INDICATED.
COORDINATE WITH NEW ONE LINE DIAGRAM FOR ADDITIONAL
INFORMATION.
ED501
DEMO ONE LINE
DIAGRAM
DEMO ONE LINE DIAGRAM
ORANGE COUNTY
CORRECTIONS UPS
REPLACEMENT
Y19-824
SHERIFF'S OP BLDG
ORANGE COUNTY
CAPITAL PROJECTS
DIVISION
400 E. SOUTH STREET
ORLANDO, FL 320801
AutoCAD SHX Text Sheet Number:
AutoCAD SHX Text Issue:
AutoCAD SHX Text Description
AutoCAD SHX Text Date
AutoCAD SHX Text No.
AutoCAD SHX Text 2018 SGM ENGINEERING, INC. DRAWINGS, WRITTEN MATERIAL, AND DESIGN CONCEPTS SHALL NOT BE USED OR REPRODUCED IN WHOLE OR PART IN ANY FORM OR FORMAT WITHOUT PRIOR WRITTEN CONSENT OF SGM ENGINEERING, INC. DO NOT SCALE DRAWINGS. USE GIVEN DIMENSIONS ONLY. IF NOT SHOWN, VERIFY CORRECT DIMENSIONS WITH THE ENGINEER. CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND CONDITIONS AT JOB SITE.
AutoCAD SHX Text Seal:
AutoCAD SHX Text Sheet Name:
AutoCAD SHX Text Project Name:
AutoCAD SHX Text Client Name:
AutoCAD SHX Text
1600-ED501-2019386.DWG
AutoCAD SHX Text Drawing File Name:
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Engineer of Record:
AutoCAD SHX Text License Number:
AutoCAD SHX Text Drawn By:
AutoCAD SHX Text Checked By:
AutoCAD SHX Text 2019-386
AutoCAD SHX Text Project Number:
AutoCAD SHX Text Scale:
AutoCAD SHX Text Design By:
AutoCAD SHX Text
AS SHOWN
AutoCAD SHX Text
JUSTIN L. MUNDELL
AutoCAD SHX Text
FL70700
AutoCAD SHX Text
BSB
AutoCAD SHX Text
BSB
AutoCAD SHX Text
BSB
EXISTING UTILITY
SWITCH GEAR IN
CEP
277/480V, 3PH, 4W
EXISTING
SWITCHBOARD "MDP"
480/277 VOLT, 4-WIRE,
1200A
3P GFST
60A 3P
100A 3P
100A 3P
PANEL
"L1"
SPD
200A 3P
200A 3P
PANEL
"LE"
SPD
60A 3P
30A 3P
60A 3P
100A 3P
100A 3P
PANEL
"L2"
SPD
100A 3P
200A 3P
200A 3P
PANEL
"L3"
SPD
400A 3P
30A 3P
20A 3P
P-CHW-1 P-CHW-2
3P,30A
30A 3P
PANEL
"FCU-1"
SPD
30A 3P
EDH-
400A 480/277V 4P ATS A
G EXISTING 500W GENERATOR
400A 3P
PANEL
"EDP"
SPD
3P,30A
WATER
HEATER
3P,100A
WATER HEATER
PUMPS
AC IN GYMCHILLER
3P,30A3P,60A
ELEVATOR
3P,60A
100A 3P
100A 3P
PANEL
"ACC"
SPD
3P,400A
SWITCHBOARD "DP"
208/120 VOLT, 4-WIRE,
25,000AIC
250A 3P
60A 3P
TRANSFORMER
75KVA
480-120/208V
60A 3P
PANEL
"A"
SPD
100A 3P
100A 3P
PANEL
"B"
SPD
100A 3P
100A 3P
PANEL
"C"
SPD
125A 3P
125A 3P
PANEL
"D"
SPD
125A 3P
125A 3P
PANEL
"E"
SPD
125A 3P
125A 3P
PANEL
"F"
SPD
TRANSFORMER
30KVA
480-120/208V
100A 3P
PANEL
"EM1"
SPD
40A 3P
PANEL
"EM3"
SPD
UPS
30KVA
480V 3P
#2
50A 3P
PANEL
"UPS-1"
SPD
100A 3P
GENERAL NOTES:
a. REFER TO SYMBOL LEGEND AND GENERAL NOTES ON SHEET E001.
b. REFER TO BOOK SPECIFICATIONS.
c. REFER TO ARCHITECTURAL INTERIOR ELEVATIONS TO COORDINATE EXACT PLACEMENT OF
ALL DEVICES, EQUIPMENT, FIXTURES, SWITCHES AND OUTLETS.
d. REFER TO EQUIPMENT SCHEDULES ON SHEET E-701 FOR DISCONNECT, CONDUIT AND WIRE
SIZES.
e. ALL COMPUTER CIRCUITS SHALL HAVE DEDICATED NEUTRAL FROM LOAD TO SOURCE
EQUIPMENT.
f. ALL FEEDERS ARE TO HAVE LESS THAN 2% TOTAL VOLTAGE DROP AND ALL BRANCH
CIRCUITS SHALL HAVE LESS THAN 3% VOLTAGE DROP.
g. IF CIRCUITS ARE COMBINED AND RUN AS MULTI-WIRE BRANCH CIRCUITS SHARING A
COMMON NEUTRAL, THEN EACH UNGROUNDED CONDUCTOR MUST BE DISCONNECTED
SIMULTANEOUSLY BY A COMMON TRIP CIRCUIT BREAKER. CONTRACTOR MAY, AT THEIR
OPTION, PROVIDE EITHER COMMON TRIP MULTI-POLE CIRCUIT BREAKERS OR UTILIZE
MANUFACTURERS LISTED HANDLE TIES IN ORDER TO PROVIDE THE SIMULTANEOUS TRIP.
THESE DEVICES ARE NOT SHOWN IN THE PANEL SCHEDULES AND MUST BE PROVIDED BY
THIS SCOPE OF WORK. NO MORE THAN 3 CURRENT CARRYING CONDUCTORS MAY BE
COMBINED IN A SINGLE RACEWAY WITHOUT PRIOR APPROVAL BY THE ENGINEER OF RECORD
(EOR).
PLAN KEY NOTES:
1. PROVIDE AND INSTALL NEW UPS INSTALL CONDUIT, WIRE, BREAKERS
PER EQUIPMENT FEEDER SCHEDULE ON SHEET E701.
2. NEW CONDUIT AND WIRE, REFER TO EQUIPMENT FEEDER SCHEDULE ON
SHEET E701.
3. PROVIDE AND INSTALL NEW PANELS , CONDUIT, WIRE, BREAKER PER
EQUIPMENT FEEDER SCHEDULE ON SHEET E701. PROVIDE ALL BREAKERS
FOR PANEL AS SHOWN ON THE PANEL FEEDER SCHEDULE ON SHEET
E601.
E501
ONE LINE DIAGRAM
ONE LINE DIAGRAM
ORANGE COUNTY
CORRECTIONS UPS
REPLACEMENT
Y19-824
SHERIFF'S OP BLDG
ORANGE COUNTY
CAPITAL PROJECTS
DIVISION
400 E. SOUTH STREET
ORLANDO, FL 320801
AutoCAD SHX Text Sheet Number:
AutoCAD SHX Text Issue:
AutoCAD SHX Text Description
AutoCAD SHX Text Date
AutoCAD SHX Text No.
AutoCAD SHX Text 2018 SGM ENGINEERING, INC. DRAWINGS, WRITTEN MATERIAL, AND DESIGN CONCEPTS SHALL NOT BE USED OR REPRODUCED IN WHOLE OR PART IN ANY FORM OR FORMAT WITHOUT PRIOR WRITTEN CONSENT OF SGM ENGINEERING, INC. DO NOT SCALE DRAWINGS. USE GIVEN DIMENSIONS ONLY. IF NOT SHOWN, VERIFY CORRECT DIMENSIONS WITH THE ENGINEER. CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND CONDITIONS AT JOB SITE.
AutoCAD SHX Text Seal:
AutoCAD SHX Text Sheet Name:
AutoCAD SHX Text Project Name:
AutoCAD SHX Text Client Name:
AutoCAD SHX Text
1600-E501-2019386.DWG
AutoCAD SHX Text Drawing File Name:
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Engineer of Record:
AutoCAD SHX Text License Number:
AutoCAD SHX Text Drawn By:
AutoCAD SHX Text Checked By:
AutoCAD SHX Text 2019-386
AutoCAD SHX Text Project Number:
AutoCAD SHX Text Scale:
AutoCAD SHX Text Design By:
AutoCAD SHX Text
AS SHOWN
AutoCAD SHX Text
JUSTIN L. MUNDELL
AutoCAD SHX Text
FL70700
AutoCAD SHX Text
BSB
AutoCAD SHX Text
BSB
AutoCAD SHX Text
BSB
E701
ELECTRICAL
SCHEDULES
ELECTRICAL SCHEDULES
ORANGE COUNTY
CORRECTIONS UPS
REPLACEMENT
Y19-824
SHERIFF'S OP BLDG
ORANGE COUNTY
CAPITAL PROJECTS
DIVISION
400 E. SOUTH STREET
ORLANDO, FL 320801
AutoCAD SHX Text Sheet Number:
AutoCAD SHX Text Issue:
AutoCAD SHX Text Description
AutoCAD SHX Text Date
AutoCAD SHX Text No.
AutoCAD SHX Text 2018 SGM ENGINEERING, INC. DRAWINGS, WRITTEN MATERIAL, AND DESIGN CONCEPTS SHALL NOT BE USED OR REPRODUCED IN WHOLE OR PART IN ANY FORM OR FORMAT WITHOUT PRIOR WRITTEN CONSENT OF SGM ENGINEERING, INC. DO NOT SCALE DRAWINGS. USE GIVEN DIMENSIONS ONLY. IF NOT SHOWN, VERIFY CORRECT DIMENSIONS WITH THE ENGINEER. CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND CONDITIONS AT JOB SITE.
AutoCAD SHX Text Seal:
AutoCAD SHX Text Sheet Name:
AutoCAD SHX Text Project Name:
AutoCAD SHX Text Client Name:
AutoCAD SHX Text
1600-E701-2019386-SHERIFF OP.DWG
AutoCAD SHX Text Drawing File Name:
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Engineer of Record:
AutoCAD SHX Text License Number:
AutoCAD SHX Text Drawn By:
AutoCAD SHX Text Checked By:
AutoCAD SHX Text 2019-386
AutoCAD SHX Text Project Number:
AutoCAD SHX Text Scale:
AutoCAD SHX Text Design By:
AutoCAD SHX Text
AS SHOWN
AutoCAD SHX Text
JUSTIN L. MUNDELL
AutoCAD SHX Text
FL70700
AutoCAD SHX Text
BSB
AutoCAD SHX Text
BSB
AutoCAD SHX Text
BSB
1' -1
AP
PR
O
X.
PANEL ELEVATION
2' -0
AP
PR
O
X.
BLOCKING (BOTH SIDES)6'-4" ABOVE
FINISHED GRADE
PANEL AND COVER
9"
(APPROX.)
CONTACTOR IN
NEMA 1 ENCLOSURE
12 POLE
FINISHED GRADE
2' -0
M
IN
U
M U
M
DETAIL NOTE:
SERVICE GROUND PER N.E.C. AND SPECIFICATIONS.
ALL CONNECTIONS TO GROUND RODS AND BUILDING STEEL SHALL
BE EXOTHERMIC TYPE. ALL OTHERS SHALL BE TORQUE BOLTED.
BUILDING STEEL
MAIN WATER SERVICE PIPE
(IF METAL) JUMPER AROUND WATER METER
BUILDING MAIN SERVICE ENTRANCE
EQUIPMENT GROUNDING BUS BAR
SIZE AS SHOWN ON DRAWINGS
EQUIPMENT GROUNDING BUS BAR
IN ELECTRICAL ROOM
EQUIPMENT GROUNDING BUS BAR
IN TELECOM ROOM
ENCASED ELECTRODE
(3) 3/4" DIAMETER x 30' LENGTH COPPER CLAD GROUND ROD
SPACED A MINIMUM 30'-" APART IN A DELTA CONFIGURATION
WITH TEST/INSPECTION WELL AT ALL GROUND ROD LOCATIONS
TO BUILDING LIGHTNING PROTECTION SYSTEM
TO CHILLED WATER PIPING FROM UNDERGROUND
RACEWAY COUNTERPOISE
#3/0 EQUAL POTENTIAL SERVICE BOND
480-120/208
TRANSFORMERBUILDING STEEL
UNDERGROUND METAL WATER PIPE
ENCASED ELECTRODE
GROUND ROD
NEUTRAL
BONDING JUMPER
EQUIPMENT BONDING JUMPER
NEUTRAL GROUND
UTILITY
TRANSFORMER
SERVICE GROUND CONDUCTOR
GROUNDING ELECTRODE CONDUCTOR
PANEL XXX
FED FROM XXXXX
AHU-XXX
FED FROM XXXXX
1/8" PREDRILLED HOLES FOR RIVET OR
MACHINE SCREW MOUNTING
A
A
A
480V 3Ø 3W, 60A
120/208V 3Ø 4W, 225A
E801
ELECTRICAL DETAILS
ELECTRICAL DETAILS
ORANGE COUNTY
CORRECTIONS UPS
REPLACEMENT
Y19-824
SHERIFF'S OP BLDG
ORANGE COUNTY
CAPITAL PROJECTS
DIVISION
400 E. SOUTH STREET
ORLANDO, FL 320801
AutoCAD SHX Text
AutoCAD SHX Text
GROUNDING ELECTRODE OVERVIEW
AutoCAD SHX Text No Scale
AutoCAD SHX Text
AutoCAD SHX Text
PHENOLIC LABEL DETAIL
AutoCAD SHX Text No Scale
AutoCAD SHX Text
AutoCAD SHX Text Sheet Number:
AutoCAD SHX Text Issue:
AutoCAD SHX Text Description
AutoCAD SHX Text Date
AutoCAD SHX Text No.
AutoCAD SHX Text 2018 SGM ENGINEERING, INC. DRAWINGS, WRITTEN MATERIAL, AND DESIGN CONCEPTS SHALL NOT BE USED OR REPRODUCED IN WHOLE OR PART IN ANY FORM OR FORMAT WITHOUT PRIOR WRITTEN CONSENT OF SGM ENGINEERING, INC. DO NOT SCALE DRAWINGS. USE GIVEN DIMENSIONS ONLY. IF NOT SHOWN, VERIFY CORRECT DIMENSIONS WITH THE ENGINEER. CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS AND CONDITIONS AT JOB SITE.
AutoCAD SHX Text Seal:
AutoCAD SHX Text Sheet Name:
AutoCAD SHX Text Project Name:
AutoCAD SHX Text Client Name:
AutoCAD SHX Text
1600-E801-2019386.DWG
AutoCAD SHX Text Drawing File Name:
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Engineer of Record:
AutoCAD SHX Text License Number:
AutoCAD SHX Text Drawn By:
AutoCAD SHX Text Checked By:
AutoCAD SHX Text 2019-386
AutoCAD SHX Text Project Number:
AutoCAD SHX Text Scale:
AutoCAD SHX Text Design By:
AutoCAD SHX Text
AS SHOWN
AutoCAD SHX Text
JUSTIN L. MUNDELL
AutoCAD SHX Text
FL70700
AutoCAD SHX Text
BSB
AutoCAD SHX Text
BSB
AutoCAD SHX Text
BSB
| Sheets and Views |
| T001 COVER SHEET |
| E001 ELECTRICAL SYMBOLS LEGEND |
| E101 ELECTRICAL SITE PLAN |
| ED301 DEMO 1ST LEVEL SHERIFF OPERATIONS |
| E301 1ST LEVEL SHERIFF OPERATIONS |
| ED501 DEMO ONE LINE DIAGRAM |
| E501 ONE LINE DIAGRAM |
| E701 ELECTRICAL SCHEDULES |
| E801 ELECTRICAL DETAILS |
File details come from the government source that posted it. Updated .