WV NP NERI 107(3)_HYD_Memo_adv.pdf
PDF 2 MB Posted
- Attached to
- New River Gorge National Park and Preserve
- Solicitation number
- 693C73-26-B-000016
About this file
This is a storm drain system design memo prepared by the Federal Highway Administration (FHWA) for the Cunard River Access Road (NPS Route 107) project in Fayette, West Virginia, within the New River Gorge National Park and Preserve. The project addresses storm drainage for Stations 112+00-117+00 along a proposed soldier pile retaining wall.
The proposed storm drain system consists of two 24-inch diameter HDPE pipes (38 feet and 44 feet in length, respectively) with 2% slopes, designed to handle a 10-year design event with flow rates of 0.43 cfs and 5.22 cfs. The system includes Type 4D catch basin inlets at Stations 113+03 and 116+55, with inlet capture efficiencies of 69.5% and 65.6% respectively. Pipe velocities range from 4.09 to 9.61 feet per second, meeting the minimum 3 feet per second criteria while remaining below the 10 feet per second threshold. Outlet protection consists of riprap aprons (Class 2, D50 = 9 inches) at each outfall per standard detail E251-01. An asphalt paved parallel ditch (Detail E608-A) is recommended to accommodate a maximum flow of 13.8 cfs on a 6.6% slope. The design replaces four existing deteriorated 18-inch culverts, three of which are located within or near the proposed wall location. All recommendations comply with Project Development and Design Manual (PDDM) criteria, including minimum pipe cover of 3 feet, gutter spread limits of 6.5 feet, and watertight gasket specifications where hydraulic gradeline exceeds pipe soffit.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FHWA: S.Jurek:3549:JS:
\\fhfl15fileserve.flhd.fhwa.dot.gov\data\PROJECTS\neri\107(3)\Techserv\Hydra\Reports\Storm Drain System Memo\ WV NP NERI 107(3) Storm Drain System Memo - NEW.docx cc: PM, Hydraulics, Geotech, Env, HD Eng, TS Engineer
Form FHWA-201 U.S. DEPARTMENT OF TRANSPORTATION (Rev. 11-87) FEDERAL HIGHWAY ADMINISTRATION
MINUTE - MEMO
Use this form in lieu of transmittal slips within Dept. of Trans. when message comment is to be retained as file material. Do not prepare carbons. Not to be used in lieu of Form FHWA-121 for informal correspondence.
SUBJECT: WV NP NERI 107(3) Storm Drain System Memo
TO MESSAGE/COMMENT FROM/DATE
Yanina Kirtley Project Manager
Shoukat Nawaz Highway Design Manager
We have completed the preliminary storm drain system analysis for Cunard River Access Road (NPS Route 107), Stations 112+00-117+00, along the proposed soldier pile retaining wall. The project is located in Fayette West Virginia, within the New River Gorge National Park and Preserve.
The proposed storm drain system is designed to meet the Project Development and Design Manual (PDDM) criteria and guidance:
1. The design flow was analyzed for a 10-year design event.
2. Minimum pipe size and slope shall be such as will provide for a minimum velocity of 3 feet per second at the design flow rate to prevent deposition of sediment. Storm sewer slopes that produce velocities in excess of 10 feet per second when flowing full should be avoided. When full flow creates higher velocities the use of drop structures should be considered.
3. The limit of spread for a low standard road should be limited to half of one travel lane for gutter flow, both on grade and in roadway sags. The limit of spread for this road is 5 feet into the road. Including the width of the gutter, the total allowable spread is 6.5 feet.
4. The minimum size for storm drainpipe is 18”. However, short laterals less than 100ft in length a 12-in size may be used if required by limited cover space.
5. The minimum recommended capture efficiency for on-grade inlets is 70%.
6. Inlets located in a sag or sump point, should be designed for a 50% clogging factor.
7. Where a grate inlet is used at the low point of a sag vertical curve it is desirable to install a grate with twice the opening of the design requirement because of the vortices and the tendency to collect trash at these low points.
8. Minimum cover between the top of the pipe and the bottom of the pavement structure should be equal or greater than 3ft. Under no case should the cover of the pipe be less than 1 ft.
9. In storm drain sections where the hydraulic gradeline for the design flood must exceed the pipe soffit (i.e., the pipe flows under pressure), the hydraulic gradeline for the design flood will remain below the ground elevation at all inlets and access structures, and watertight gaskets should be specified for the pipe joints.
10. Water should not be carried across intersections and should not be allowed to overflow at driveway openings where the latter are on a descending grade from the gutter.
Samantha Jurek Hydraulic
THROUGH
Wendy Hiciano Hydraulics Team Leader
3/25/25
\\fhfl15fileserve.flhd.fhwa.dot.gov\data\PROJECTS\neri\107(3)\Techserv\Hydra\Reports\Storm Drain System Memo\ WV NP NERI 107(3) Storm Drain System Memo - NEW.docx cc: PM, Hydraulics, Geotech, Env, HD Eng, TS Engineer
Existing Conditions
Cunard Road has two failures sites within the project limits. There are four existing culverts near the site of the proposed soldier pile retaining wall: one 18”x44.4’ CMP at STA 112+20 that will remain undisturbed, two 18” CMP culverts that are within the proposed wall location at STA 113+90 and STA 115+30, respectively, and one 18”x42’ CMP after the proposed wall location at STA 116+85. The pipes are silted, and the outfalls are washed out. There is an existing V-shaped parallel ditch, 3ft wide.
Recommendations
A storm drain system consisting of two pipes and a gutter is proposed instead of a series of cross pipes due to the proposed soldier pile wall. The locations of the pipes through the wall would require much more complicated design and long term maintenance. Additionally, due to the sharply increasing slope of the existing terrain at the proposed pipe locations, storm drains with drop inlets will prevent an increased limit of disturbance for the project.
Hydrology (peak flow rates) was performed via Bentley Open Flow StormCAD software (ORD) using the Rational Method. The IDF curves were obtained from the NOAA Precipitation Frequency Data Server and imported into ORD. The drainage areas were delineated using georeferenced USGS quad maps within the software. Each drainage area contains a Catch Basin (CB) inlet. Table 1 shows the hydrology summary, and Table 5 shows the CB hydraulics summary.
Table 1: Drainage Area Hydrology Summary Hydrology Summary
Label Catch Basin
Station of CB (ft)
Area (ac)
Time of Concentration
(hours)
Runoff Coefficient
( C )
Catchment Intensity
Q10 (cfs)
DR-01 CB-01 113+03 0.766 0.26 0.207 3.874 0.62
DR-02 CB-02 116+55 9.623 0.28 0.213 3.770 7.78
Hydraulic design was performed via Bentley Open Flow StormCAD software (ORD) (2022 Release 3) using the HEC-22 (Urban Drainage Design Manual) headloss method, third edition.
Each pipe should have inlet 4D and a free end section (FES). The plan view for the system is shown in Attachment 2 and the profiles for the pipes are shown in Attachments 3 and 4. Table 2 shows the storm drain pipe summary, Table 3 shows the pipe summary, and Table 4 shows the summary of the inlet and outfalls.
\\fhfl15fileserve.flhd.fhwa.dot.gov\data\PROJECTS\neri\107(3)\Techserv\Hydra\Reports\Storm Drain System Memo\ WV NP NERI 107(3) Storm Drain System Memo - NEW.docx cc: PM, Hydraulics, Geotech, Env, HD Eng, TS Engineer
Table 2: Pipe and Gutter Hydraulics Summary Link Summary
Label Station (ft)
Q10 Flow (cfs)
Velocity (ft/s)
HGL In (ft)
HGL Out (ft)
Depth In (ft)
Depth Out (ft)
Pipe-01 113+03 0.43 4.09 1,110.42 1,109.65 0.22 0.15 Pipe-02 116+55 5.22 9.61 1,102.41 1,101.04 0.81 0.50
Gutter-01 113+03
116+55
0.19 (N/A) (N/A) (N/A) 0.21 0.17
Table 3: Storm Drain Pipe Summary
Pipe Summary
Label Station Diameter
(in) Length
(ft) Slope Invert
Start Invert Stop Material
(ft) (%) (ft) (ft)
Pipe-01 113+03 24 38 2% 1,110.20 1,109.50 HDPE
Pipe-02 116+55 24 44 2% 1,101.60 1,100.54 HDPE
Table 4: Inlet and Outlet Summary
Node Summary
Label Q10 Flow (Total In)
(cfs)
Q10 Flow (Total Out)
(cfs)
Elevation (Ground)
(ft)
Elevation
(RIM)
(ft)
Elevation (Invert)
(ft)
EGL In (ft)
EGL
Out (ft)
CB-01 0.43 0.43 1,113.79 1,113.79 1,110.54 1,110.54 1,110.52
FES-01 (N/A) 0.43 1,111.76 (N/A) 1109.5 1,109.65 1,109.65
CB-02 5.22 5.22 1,104.80 1,104.80 1,101.60 1,102.83 1,102.77
FES-02 (N/A) 2.64 1,102.80 (N/A) 1100.54 1,101.04 1,101.04
Table 5: Catch Basin Hydraulics Catch Basin Inlet Summary
Label Station (ft) Flow
(Captured) (cfs)
Flow (Total Bypassed)
(cfs)
Depth (Gutter)
(in)
Spread / Top Width
(ft)
CB-01 113+03 0.43 0.19 0.407 3.078
CB-02 116+55 5.22 2.74 2.014 3.882
\\fhfl15fileserve.flhd.fhwa.dot.gov\data\PROJECTS\neri\107(3)\Techserv\Hydra\Reports\Storm Drain System Memo\
The recommended inlet type is Type 4D. A modified Type 4D inlet is also recommended for CB-02. All inlets will be Type 4D, as shown in Attachment 5. The inlet summary is shown in table 6.
Table 6: Inlet Summary
We also recommend riprap at each outfall. The scour countermeasures were checked using the Riprap Analysis Hydraulic Toolbox V5.2, which is based on HEC-14 (Hydraulic Design of Energy Dissipators for Culverts and Channels, Third Edition). The standard riprap detail (E251-
01) will provide sufficient outlet protection for both pipes. Table 7 shows a summary of the riprap aprons.
Table 7: Scour Countermeasures – Riprap Summary Riprap Summary
Label Culvert Size (in)
Riprap Class D50 (in) Apron
Length (ft)
Width at End of
Apron (ft)
Apron Depth (ft)
Pipe-01 24 2 9 8 6.5 1.5 Pipe-02 24 2 9 8 6.5 1.5
To assist Highway Design determining the appropriate lining for the parallel ditch, HYD conducted a stability analysis using the Channel Analysis Hydraulic Toolbox (V5.2), based on HEC-15 (Design of Roadside Channels with Flexible Linings, Third Edition). Based on our analysis results, considering a slope of 6.6% and a maximum Q10 of 13.8cfs, we recommend an asphalt paved ditch as seen in EFLHD Detail E608-A. The larger ditch geometry will accommodate the spread of the flow. Please see attachment 8 for calculation details.
Please let us know should you have any questions.
Inlet Summary
Label Type of inlet Depth, H (ft) On-grade vs Sag % Clogging
CB-01 4D 2.92 On-grade N/A
CB-02 Modified 4D 3.20 On-grade N/A
\\fhfl15fileserve.flhd.fhwa.dot.gov\data\PROJECTS\neri\107(3)\Techserv\Hydra\Reports\Storm Drain System Memo\
Attachments:
• Attachment 1 – Storm Drain System Plan View
• Attachment 2 – Pipe-01 – Station 113+03 Profile View
• Attachment 3 – Pipe-02 – Station 116+55 Profile View
• Attachment 4 – Inlet 4D
• Attachment 5 – Paved Asphalt Waterway
• Attachment 6 – Calculation Detailed Summary
• Attachment 7 – Gutter Hydraulics
STA 116+55
Pipe-02
STA 113+03
Pipe-01
(Detail E251-01)
Riprap Apron at Outfall
Free End Section
Inlet 4D (Detail E604-02)
24" x 38' Circular HDPE
(Detail E251-01)
Riprap Apron at Outfall
Free End Section
(Detail E604-02A)
Modified Inlet 4D
24" x 44' Circular HDPE
Storm Drain System Plan View
Attachment 1
WV NP NERI 107(3) HYD Memo
-20 -10 0 10 20
1,100 1,100
1,110 1,110
1,120 1,120
1,130 1,130
Invert 1110.20' Invert 1109.50'
Slope 2%
38' Length
24" Round HDPE
Pipe-01
Inlet 4D
CB-01
Elev. 1113.79'
Inlet Ground
Free End Section
FES-01
1110.42'
HGL In
1109.65'
HGL Out
Attachment 2: Pipe-01
Profile View
STA 113+03
30 40
-30 -20 -10 0 10 20 30 40
1,090 1,090
1,100 1,100
1,110 1,110
1,120 1,120
1,130 1,130
Modified Inlet 4D
CB-02
Invert 1101.60' Invert 1100.54'
Free End Section
FES-02
Elev. 1104.80'
Inlet Ground
44' Length
24" Round HDPE
Pipe-02
Slope 2%
1101.04'
HGL Out
1102.41'
HGL In
Attachment 3: Pipe-02
Profile View
STA 116+55
1:6.1
3 -1.6% -1.6% -2.3%
Calculation Detailed Summary Element Details
110ID Notes Base AnalysisLabel
Hydraulic Summary
Backwater AnalysisFlow Profile Method Actual
Uniform Flow Velocity
Average Velocity Method
5Number of Flow Profile Steps ft0.00Minimum Structure Headloss ft0.00Hydraulic Grade Convergence Test hours0.083Minimum Time of
Concentration
Inlets
FalseNeglect Side Flow? Grate and Curb
Active Components for Combination Inlets In Sag
FalseNeglect Gutter Cross Slope For Side Flow?
Grate and Curb
Active Components for Combination Inlets on Grade
HEC-22 Energy Losses (Second Edition) ft0.50Elevations Considered Equal Within 1.000Depressed Unsubmerged
Factor
TrueConsider Non-Piped Plunging Flow?
0.950Half Bench Submerged Factor
1.000Flat Submerged Factor 0.150Half Bench Unsubmerged Factor
1.000Flat Unsubmerged Factor 0.750Full Bench Submerged Factor 1.000Depressed Submerged Factor 0.070Full Bench Unsubmerged
Factor
Headloss (AASHTO)
0.350Expansion, Ke 0.500Shaping Adjustment, Cs 0.250Contraction, Kc 1.300Non-Piped Flow Adjustment, Cn
Bend Angle vs. Bend Loss Curve
Bend Loss Coefficient, KbBend Angle (degrees)
0.0000.00 0.19015.00 0.35030.00 0.47045.00 0.56060.00 0.64075.00 0.70090.00
Gravity Hydraulics
Pipe with Maximum QV
Governing Upstream Pipe Selection Method
Page 1 of 376 Watertown Road, Suite 2D Thomaston, CT
06787 USA +1-203-755-1666
3/26/2025
Drainage and Utilities [10.12.02.04]
Bentley Systems, Inc. Haestad Methods Solution Center
03-WV_NP_NERI_107(3)_HYD_70%Updates -- Design IntlFt.stsw
Catchment Summary
Catchment CA (acres)
Runoff Coefficient (Rational)
Time of Concentration (hours)
Area (User Defined) (acres)
Label
0.1580.2070.2600.766DR-01
2.0470.2130.2839.623DR-02
Catchment Rational Flow (cfs)
Catchment Intensity (in/h)
0.623.874 7.783.770
Conduit Summary
Flow (cfs)
Subnetwork OutfallBranch IDSection TypeLabel
0.43FES-012CirclePipe-01 5.22FES-021CirclePipe-02
Depth (Out) (ft)
Depth (In) (ft)
Hydraulic Grade Line (Out) (ft)
Hydraulic Grade Line (In) (ft)
Velocity (ft/s)
0.150.221,109.651,110.424.09 0.500.811,101.041,102.419.61
Node Summary
Flow (Total Out) (cfs)
Flow (Total In) (cfs)
Subnetwork OutfallElement TypeLabel
0.430.43FES-01Catch BasinCB-01 5.225.22FES-02Catch BasinCB-02 5.21(N/A)(N/A)HeadwallFES-02 0.43(N/A)(N/A)HeadwallFES-01
Energy Grade Line (Out) (ft)
Energy Grade Line (In) (ft)
Elevation (Invert) (ft)
Elevation (Ground) (ft)
1,110.521,110.541,110.201,113.79 1,102.771,102.831,101.601,104.80 1,101.041,101.04(N/A)1,102.80 1,109.651,109.65(N/A)1,111.76
Inlet Summary
Flow (Captured) (cfs)
Catalog InletCatalog Inlet TypeInlet TypeLabel
0.43Inlet Generic DitchDitchDitchCB-01 5.22Inlet Generic DitchDitchDitchCB-02
Spread / Top Width (ft)
Depth (Gutter) (in)
Capture Efficiency (Calculated)
Bypass TargetFlow (Total Bypassed) (cfs)
3.0780.40769.5CB-020.19
3.8822.01465.6(N/A)2.74
Pond Summary
Page 2 of 376 Watertown Road, Suite 2D Thomaston, CT
06787 USA +1-203-755-1666
3/26/2025
Drainage and Utilities [10.12.02.04]
Bentley Systems, Inc. Haestad Methods Solution Center
Pond Summary
Flow (Total Out) (cfs)
Flow (Total In) (cfs)
Subnetwork OutfallElement TypeLabel
Volume (gal)
Hydraulic Grade (ft)
Page 3 of 376 Watertown Road, Suite 2D Thomaston, CT
06787 USA +1-203-755-1666
3/26/2025
Drainage and Utilities [10.12.02.04]
Bentley Systems, Inc. Haestad Methods Solution Center
Hydraulic Analysis Report
Project Data Project Title:
Designer:
Project Date: Wednesday, November 13, 2024
Project Units: U.S. Customary Units
Notes:
Channel Analysis: Channel Analysis Notes:
Input Parameters
Channel Type: Triangular
Side Slope 1 (Z1): 3.6000 ft/ft
Side Slope 2 (Z2): 3.6000 ft/ft
Longitudinal Slope: 6.6000 ft/ft
Manning's n: 0.0081
Flow 13.8000 cfs
Result Parameters
Depth 0.1976 ft
Area of Flow 0.1406 ft^2
Wetted Perimeter 1.4768 ft
Hydraulic Radius 0.0952 ft
Average Velocity 98.1491 ft/s
Top Width 1.4229 ft
Froude Number: 55.0239
Critical Depth 0.9819 ft
Critical Velocity 3.9760 ft/s
Critical Slope: 0.0013 ft/ft
Critical Top Width 7.07 ft
Calculated Max Shear Stress 81.3905 lb/ft^2
Calculated Avg Shear Stress 39.2106 lb/ft^2
Channel Lining Analysis: Channel Lining Design Analysis Notes:
Lining Input Parameters
Channel Lining Type: Riprap, Cobble, or Gravel
D50: 0.00 mm
Riprap Specific Weight: 165 lb/ft^3
Water Specific Weight: 62.4 lb/ft^3
Riprap Shape is Angular
Safety Factor: 1
Calculated Safety Factor: 1
Lining Results
Angle of Repose: 0 degrees
Relative Flow Depth: 9.7375e-312 ft
Manning's n method: Bathurst
Manning's n: 0
Channel Bottom Shear Results
V*: 0
Reynold's Number: 0
Shield's Parameter: 0
Shear stress on channel bottom: 0 lb/ft^2
Permissible shear stress for channel bottom: 0 lb/ft^2
Channel bottom is NOT stable
Stable D50: 0 mm
Channel Side Shear Results
K1: 0
K2: 0
Kb: 0
Shear stress on side of channel: 0 lb/ft^2
Permissible shear stress for side of channel: 0 lb/ft^2
Stable Side D50: 0 lb/ft^2
Side of channel is NOT stable
Channel Lining Stability Results 2
The channel is NOT stable
Channel Summary
Name of Selected Channel: Channel Analysis
Selected Profile: FHWA Profile (read‐only)
Culvert Assessment Profiles
Culvert Assessment Profile Name: Standard (read‐only)
Maximum Excavation Depth: 20.00 ft
Maximum Shallow Cover: 4.00 ft
Maximum Small Pipe Size: 36.00 ft
Minimum Manned Entry Size: 48.00 in
Riprap Classes
Riprap Class Name:CLASS I
Riprap Class Order:1
The following values are an 'average' of the size fraction range for the selected riprap class.
D100: 304.80 mm
D85: 228.60 mm
D50: 165.10 mm
D15: 114.30 mm
Riprap Class Name:CLASS II
Riprap Class Order:2
The following values are an 'average' of the size fraction range for the selected riprap class.
D100: 457.20 mm
D85: 330.20 mm
D50: 241.30 mm
D15: 177.80 mm
Riprap Class Name:CLASS III
Riprap Class Order:3
The following values are an 'average' of the size fraction range for the selected riprap class.
D100: 609.60 mm
D85: 431.80 mm
D50: 317.50 mm
D15: 228.60 mm
Riprap Class Name:CLASS IV
Riprap Class Order:4
The following values are an 'average' of the size fraction range for the selected riprap class.
D100: 762.00 mm
D85: 533.40 mm
D50: 393.70 mm
D15: 266.70 mm
Riprap Class Name:CLASS V
Riprap Class Order:5
The following values are an 'average' of the size fraction range for the selected riprap class.
D100: 914.40 mm
D85: 647.70 mm
D50: 469.90 mm
D15: 330.20 mm
Riprap Class Name:CLASS VI
Riprap Class Order:6
The following values are an 'average' of the size fraction range for the selected riprap class.
D100: 1066.80 mm
D85: 762.00 mm
D50: 546.10 mm
D15: 381.00 mm
Riprap Class Name:CLASS VII
Riprap Class Order:7
The following values are an 'average' of the size fraction range for the selected riprap class.
D100: 1257.30 mm
D85: 889.00 mm
D50: 647.70 mm
D15: 444.50 mm
Riprap Class Name:CLASS VIII
Riprap Class Order:8
The following values are an 'average' of the size fraction range for the selected riprap class.
D100: 1524.00 mm
D85: 1079.50 mm
D50: 800.10 mm
D15: 558.80 mm
Riprap Class Name:CLASS IX
Riprap Class Order:9
The following values are an 'average' of the size fraction range for the selected riprap class.
D100: 1828.80 mm
D85: 1295.40 mm
D50: 965.20 mm
D15: 660.40 mm
Riprap Class Name:CLASS X
Riprap Class Order:10
The following values are an 'average' of the size fraction range for the selected riprap class.
D100: 2133.60 mm
D85: 1511.30 mm
D50: 1130.30 mm
D15: 787.40 mm
| WV NP NERI 107(3) Final Storm Drain System Memo |
| 1 - Storm Drain System Plan View |
| 2 - Pipe-01 Station 113+03 Profile View |
| 3 - Pipe-02 Station 116+55 Profile View |
| 4 - Inlet4D |
| 5 - Paved Asphalt Waterway - Detail E608-A |
| 6 - Calculation Detailed Summary |
| 7 - Gutter Hydraulics |
| 2025-05-01T11:51:32-0400 | |
| SAMANTHA CAROL JUREK |
| 2025-05-01T11:58:30-0400 | |
| WENDY MERCEDES HICIANO |