WESD - Yamhill Center - Addendum 2 - 03.10.23.pdf
PDF 8 MB Posted
- Attached to
- Willamette ESD Yamhill Center Remodel
- Solicitation number
- S-P27003-00005880
- Issued by
- Washington County, Mcminnville City, Oregon
About this file
This document is an addendum to the construction documents for the Willamette Education Service District (WESD) Yamhill Center Remodel project in McMinnville, Oregon. The addendum modifies the original construction documents dated February 20, 2023, including revisions to architectural drawings, mechanical drawings, and project specifications. The addendum notes several changes, such as replacing drawings, clarifying detail numbers, adding new sections, and accepting substitutions for certain light fixtures. A non-mandatory subcontractor open house will be held on March 2 and March 9 at the project site.
The addendum does not provide details on pricing, set asides, incumbents, funding sources, or other commercial terms. It focuses solely on the technical aspects of the construction project, including demolition, HVAC, and plumbing work. Contractors are responsible for verifying existing conditions, coordinating with other trades, and ensuring compliance with all applicable codes and regulations.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
503-390-0281 ● FAX 503-390-2459 ● 3095 RIVER ROAD NORTH ● SALEM, OREGON 97303
Addendum No. 2
Date: March 9, 2023
Project: WESD Yamhill Center Remodel
To: Prospective Bidders
This addendum forms a part of the Contract Documents and modifies the original Construction Documents dated 02-20-23 as noted below, and becomes a part of the Contract Documents.
This addendum consists of 2 pages, plus attachments.
ARCHITECTURAL DRAWINGS:
1. Sheet A-101: Replace this sheet in its entirety. Added sheet notes
2. Sheet A-102: Replace this sheet in its entirety. Added sheet notes
3. Sheet A-103: Replace this sheet in its entirety. Added sheet notes.
4. Sheet A-104: Replace this sheet in its entirety. Added sheet notes.
5. Sheet A-201: Replace this sheet in its entirety. Revised elevation notes.
6. Sheet A-401: Replace this sheet in its entirety. Revised elevation notes.
7. Sheet A-501: Replace this sheet in its entirety. Clarified detail numbers.
8. Sheet A-502: Replace this sheet in its entirety. Added reception details.
9. Sheet A-701: Replace this sheet in its entirety. Updated finish layout on plan.
MECHANICAL DRAWINGS:
1. Sheet MP-001: Replace this sheet in its entirety. Revised sheet notes.
2. Sheet M-101: Replace this sheet in its entirety. Revised sheet notes.
3. Sheet M-201: Replace this sheet in its entirety. Revised sheet notes.
4. Sheet M-202: Replace this sheet in its entirety. Revised sheet notes.
5. Sheet M-501: Replace this sheet in its entirety. Revised detail notes.
6. Sheet M-701: Replace this sheet in its entirety. Revised sheet notes.
PROJECT MANUAL:
1. Section 01 2300 Alternates: replace section in its entirety. Revised bid alternate language.
2. Section 06 64 00 Plastic Paneling: replace section in its entirety. Updated wall protection panels.
3. Section 09 29 00 Gypsum Board: replace section in its entirety. Added impact resistant gypsum board.
4. Section 10 14 00 Signage: add section in its entirety.
5. Section 28 13 00 Electronic Access Control: add section in its entirety.
ACCEPTED SUBSTITUTIONS:
1. Sheet E-003 Luminaire Schedule, accepted manufacturer/model:
a. Type D4: Lightolier Calculite.
b. Type RA2: Daybrite Fluxgrid.
c. Type RA4: Daybrite Fluxgrid.
d. Type RA4E: Daybrite Fluxgrid.
e. Type RL2: Daybrite TG Troffer.
f. Type RL4: Daybrite TG Troffer.
g. Type SW4: Daybrite Fluxstream Wrapround.
503-390-0281 ● FAX 503-390-2459 ● 3095 RIVER ROAD NORTH ● SALEM, OREGON 97303
h. Type V2: Brownlee 5178 Series
i. Type X1: Evenlite Telesis.
End of Addendum 2.
Attachments:
Drawing sheets:
A-101 A-102 A-103 A-104 A-201 A-401 A-501 A-502 A-701
MP-001
M-101 M-201 M-202 M-501 M-701 Specifications:
Section 01 2300 Alternates Section 06 64 00 Plastic Paneling Section 09 29 00 Gypsum Board Section 10 14 00 Signage Section 28 13 00 Electronic Access Control:
A
B
A D
E
C A
AA
A
A
A
C
C
C
B
A
B G
B
A A
B
B
B
F
F
B
C
B
B
A
B
A
G
A
F F
B
B A
A
A
G
A
M
B
A
C
A
A
A C
BB BA A
A
H
A
B
A
AA
BBB
J
K
A
L
E
A
C
TYP
TYP
2' -9
N
N N
N
N N
NN
N
N
N
N
N
N N
N
N
N
N
N N N
N
N
N
N
N
N N
N
N
N
N
N
N
A
N
N
N
N
N A
E
N
N
N
A
EXIST
EXIST
EXIST
EXIST
EXIST
EXIST
EXIST EXIST
EXIST EXIST
EXIST
EXIST
B
G
P R
P P P
P PA A
N
N
P
P
P P P
P
P
P
P
P
P
P
P
P
PP
P
P P
P
B
P P
S
S
P
TYP
ALL WALLS
P
TYP
ALL WALLS
P
P
S
TYP
P
TYP
ALL WALLS
N
P
TYP
ALL WALLS
N
P
TYP
ALL WALLS
P
TYP
ALL WALLS
FE
FD
FD
FD
FD
DS
DS
DS
DS
DS
DS
DS
W D
FE
C
FE
FEC
FEC
FEC
FE
FEC
S
P
TYP
ALL WALLS
P
TYP
ALL WALLS
DEMOLITION NOTES
A
B
GENERAL NOTES
C
D
E
F
G
H
J
K
L
M
N
1. PROTECT ALL EXISTING SURFACES TO REMAIN.
2. REPAIR GYP BD & FINISH TO MATCH ADJACENT SURFACES AS REQD,
AFTER DEMOLITION WORK.
3. WHERE PLUMBING IS REMOVED, CAP PIPING IN WALL OR ABV CLG AT
NEAREST FIXTURE. CAP WASTE IN SLAB.
4. EXISTING FLOOR IS CONCRETE SLAB ON GRADE, UON. WHERE
FLOORING IS REMOVED, GRIND SLAB TO REMOVE EXCESS ADHESIVE
AND PREP SLAB AS REQ'D FOR NEW FLG.
5. SEE SHEET A-103 FOR ADDITIONAL DEMOLITION.
REMOVE EXISTING WALL OR PORTION OF EXISTING WALL
REMOVE EXIST DOOR / FRAME ASSEMBLY, SALVAGE DOORS FOR
RELOCATION
REMOVE EXISTING CASEWORK
RELOCATE KITCHEN EQUIP TO NEW FOOD PREP AREA
REMOVE FIRE EXTINGUISHER/FEC & SALVAGE FOR REUSE
REMOVE PORTION OF EXISTING SHEAR WALL
REMOVE EXISTING DOOR AND FRAME, DISCARD FRAMME & SALVAGE
DOORS TO OWNER
CAREFULLY REMOVE WALL AROUND EXISTING ELEC PANEL. MAINTAIN
SUPPORT FOR PANEL DURING WORK. ELEC PANEL TO BE REUSED.
DISASSEMBLE SOUND BOOTH AND DISCARD
REMOVE COILING GRILLE AND DISCARD
REMOVE COILING DOOR AND DISCARD
WELD DOOR SHUT. REMOVE EXIST HDW AND PROVIDE BLANK PLATE
SEAL AROUND DOOR ON EXT SIDE.
REMOVE EXIST FLOORING AND WALL BASE, THIS ROOM
REMOVE GYP BD ENTIRE WALL AS REQ'D FOR NEW WORK, TYP
REMOVE TOILET ACCESSORIES & SALVAGE FOR REINSTALLATION
SAWCUT & REMOVE PORTION OF SLAB FOR PLUMBING WORK
P
R
S sheet:
of:
copyright c Carlson Veit Junge Architects PC checked by:
drawn by:
dwg file:
project:
date:
revisions:
pr oj ec t:
co ns ul ta nt s:
02-20-23 03022 A-101-X-03022-R1
KC
AMF
FLOOR PLAN -
DEMOLITION
A-101
W
IL
LA
M
ET
TE
E D
U C
AT
IO
N S
ER
VI
C E
D
IS
TR
IC
T
YA
M H
IL
L
C
EN
TE
R
R
EM
O D
EL
S
W H
IG
H
W
AY
M C
M
IN
N
VI
LL
E, O R
03-09-23
ADDENDUM #2
FLOOR PLAN - DEMOLITION
1/8" = 1'-0"
AutoCAD SHX Text
PP
AutoCAD SHX Text
PP
AutoCAD SHX Text
PP
AutoCAD SHX Text
OPEN
AutoCAD SHX Text I
AutoCAD SHX Text H
AutoCAD SHX Text R
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text R
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text
SALEM, OREGON
AutoCAD SHX Text
ANGELA M. FLORES
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text T
CONSTRUCTION NOTES
GENERAL NOTES
3'-0" X 7'-0" OPENING, WRAP W/ GYP BD AND PROVIDE U-SHAPE CORNER GUARDS,
FULL HT
NEW CASEWORK
INFILL EXIST OPENING W/ STUDS TO MATCH EXIST WIDTH AND GYP BD' TO MATCH
EXIST WIDTH, AND FINISH TO MATCH ADJ SURFACES
ALIGN NEW FACE OF FINISH W/ EXIST FACE OF FINISH
INFILL EXIST OPENING W/ STUDS, GYP BD, PLYWD AS REQ'D FOR SHEAR WALL &
FINISH TO MATCH ADJ SURFACES
PROVIDE WP-1 FULL HT, THIS ROOM
FREEZER, OFOI
REFRIGERATOR, OFOI
FOOD WARMER, OFOI
MOP SINK. PROVIDE 4'-0" x 4'-0" FRP AT ADJ WALLS
PROVIDE WP-1 UP TO 4'-0" AFF,THIS ROOM
2x6 WD STUD WALL
PROVIDE NEW GYP BD AND FINISH TO MATCH ADJ SURFACES. PAINT WALL
CORNER TO CORNER
THIS ROOM TO RECEIVE 6" RUBBER BASE
INFILL EXIST OPENING W/ 2x6 STUDS, R-21 BATT INSUL, WRB & CMU VENEER TO
MATCH EXISTING
REINSTALL EXISTING TOILET ACCESSORIES
1. ALL DIMENSIONS ARE TO FACE OF STUDS, UON
2. PATCH / REPAIR ALL WALLS AFFECTED BY DEMO
3. 48" CORNER GUARDS TO BE INSTALLED AT ALL OUTSIDE CORNERS
4. PROVIDE TEMP FLOOR PROTECTION AT MULTI-PURPOSE 194 & MEETING 126,
SUCH AS RAMBOARD, OR SIMILAR. INSTALL IN ACCORDANCE W/
MANUFACTURER'S INSTRUCTIONS.
5. ALL NEW WALLS ARE 2X4 WD STUDS W/ (1) LAYER OF GYP BD EA SIDE, UON.
REFER TO STRUCTURAL DWGS FOR SHEAR WALL LOCATIONS ASSEMBLY.
6. SEE DETAIL 2/A-501 FOR ROOF PATCH/REPAIR.
RELOCATED FE/FEC
OFOI COPIER
NEW WALL UP TO EXIST SOFFIT, SEE DETAIL 4/A-501
OFOI DOUBLE MICROWAVE CART
PROVIDE IMPACT RESISTANT GYP BD UP TO 8'-0", ENTIRE ROOM
PATCH/REPAIR CONC SLAB & VAPOR RETARDER, SEE DTL 1/A-501
WALL TYPES
AC1
AC2
ACOUSTIC WALL TYPE 1 SEE DTL 5/A-501
ACOUSTIC WALL TYPE 2 SEE DTL 6/A-501
AC1
102B
2A
9C
1A
9B
9A
111B
163A
9A
8A
0A
1A
8A
6A
6A
7A
2A
1A
0A
8A
7A
6A
205A
195A
A
A
B
B
D
195B
215A
4A
184A
182E
182D
182C
182B
182A
A-201
A
5A
A-201
D
C
2 2 2
C
A-401
1 1
1 1
33 3
3 3
5' -0
15'-4" 10'-2"
6' -7
5'-6"
8' -0
5'-3" 6'-10"
27'-6" 30'-7"
'-8
'-1
8'-3"
1' -1
0"
3' -0
1'-5"
6'-0"
3' -1
8'
-3
9'-11" 9'-11" 9'-11" 2'-0"
5' -0
13'-4" 9'-10"
'-6
'-6
6' -5
4' -4
9'-7"
'-0
27'-11" 27'-7" 6'-7"
9' -6
5'-6"
3' -0
3' -0
5'-7" 6'-2"
6'-0"
6' -0
A-201L N
M
A-201
2'-7"
2'-7"2'-0"
2'-7" 2'-0" 2'-7"
A-201
B
EXIST
EXIST
EXIST
EXIST
EXIST
EXIST
EXIST EXIST
EXIST EXIST
EXIST
EXIST
9'-10"
5"
5' -0
5' -4
A-201
B
A-201
B
A-201
A
A-201
A
11 11 11
111111
1111 11
3' -5
3'
-2
193A
7A
203A
A-401
13 13 13
13 13
AC1
AC1
AC1AC1
AC1 AC1AC1
AC1
AC2AC2
AC2
AC2
AC2
AC2AC2
AC2AC2
AC2
AC1AC1
AC1AC1
AC1
AC1 AC1 AC1
AC1
AC1
AC1
AC1 AC1
21 21 21
21 21 21
21 21 21
21 21 21
21 21
A-501
TYP
TYP
FE
FD
FD
FD
FD
FD
FD
FD
DS
RD
DS
DS
DS
DS
DS
DS
DS
W D
FD
FD
OFFICE
OFFICE
OFFICE
OPEN OFFICE
OFFICE
COATS
STORAGE
MECH
OFFICE
OFFICE
OFFICE
OFFICE
HALL
SENSORY
HALL
OFFICE
OFFICE
OFFICE
OFFICE
STAFF LOUNGE
HALL
OFFICE
OFFICE
OFFICE
CONFERENCE
OFFICE
OFFICE
HALL
HALL
OFFICE
WORKROOM
WORKROOM
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
VESTIBULE
OFFICE
HALL
HALL
KITCHEN
FOOD STORAGE
MEN
WOMEN
HALL
HALL
STORAGE
MEETING
MEETING
MEETING
COFFEE
STORAGE
STORAGE
HALL
VESTIBULE
GALLERY
EQUIP STOR
EQUIP STOR
106 SERVER
CLASSROOM
CLASSROOM
WOMEN
MEN
HALL
CLASSROOM 1
CLASSROOM 2
CLASSROOM 3
STORAGE
IT OFFICE
RESET
RESET
RESET
STORAGE
RR
RR
HALL
COATS
HALL
HALL
COACH OFFICE
CAFETERIA
MULTI-PURPOSE
STORAGE
OFFICE
196 OFFICE
OFFICE
JANITOR
199 OFFICE
OFFICE
HALL
HALL
CLEAR / MEETING
CLASSROOM 4
CLASSROOM 5
RESET
RESET
RESET
HALL
HALL
STORAGE
CLASSROOM 6
HALL
EXIST RR
ELEC
OFFICE
109 WORKROOM
AUD STOR
111A
AUDIOLOGY
STORAGE
109A
STORAGE
HALL
RESET
FIRE
LOBBY
FE
C
FEC
FEC
FE
FEC
FEC
FE
A-501
TYP
A-501
A-501
DOOR SCHEDULE
DOOR
MARK SIZE W X H X THK
DOOR FRAME
R
AT
IN
G
(7
H
AR
D W
AR
E
(8
REMARKS (9)
TY
PE
(2
C O
N
ST
(3
FI
N
IS
H
(4
G
LA
SS
(5
C O
N
ST
(3
FI
N
IS
H
(4
FR
AM
E D
ET
AI
LS
(6
102A 3'-0" X 7'-0" X 1-3/4" B SC WT 1
4" T HS ME 1/A-501 - 1 NOTE 1, 2
102B 3'-0" X 7'-0" X 1-3/4" B SC WT 1
4" T HS ME 1/A-501 - 1 NOTE 1, 2, 3
109A 3'-0" X 7'-0" X 1-3/4" B SC WT 1
4" T HS ME 1/A-501 - 2 NOTE 1, 2
109B 3'-0" X 7'-0" X 1-3/4" B SC WT 1
4" T HS ME 1/A-501 - 2 NOTE 1, 2, 3
109C 3'-0" X 7'-0" X 1-3/4" A SC WT - HS ME 1/A-501 - 3 NOTE 1, 2
111A 3'-0" X 7'-0" X 1-3/4" C SC WT 1
4" T HS ME 1/A-501 - 4 NOTE 1, 2
111B 3'-0" X 7'-0" X 1-3/4" A SC WT - HS ME 1/A-501 - 3 NOTE 1, 2
135A 3'-0" X 7'-0" X 1-3/4" B SC WT 1
4" T HS ME 1/A-501 - 2 NOTE 1, 2
163A 3'-0" X 7'-0" X 1-3/4" A SC WT - HS ME 1/A-501 - 3 NOTE 1, 2
178A 3'-0" X 7'-0" X 1-3/4" C SC WT 1
4" T HS ME 1/A-501 - 4 NOTE 1, 2
179A 3'-0" X 7'-0" X 1-3/4" C SC WT 1
4" T HS ME 1/A-501 - 4 NOTE 1, 2
180A 3'-0" X 7'-0" X 1-3/4" C SC WT 1
4" T HS ME 1/A-501 - 4 NOTE 1, 2
181A 3'-0" X 7'-0" X 1-3/4" A SC WT - HS ME 1/A-501 - 3 NOTE 1, 2
182A 3'-0" X 7'-0" X 1-3/4" A SC WT - HS ME 1/A-501 - 6 NOTE 4
182B 3'-0" X 7'-0" X 1-3/4" A SC WT - HS ME 1/A-501 - 6 NOTE 4
182C 3'-0" X 7'-0" X 1-3/4" A SC WT - HS ME 1/A-501 - 6 NOTE 4
182D 3'-0" X 7'-0" X 1-3/4" A SC WT - HS ME 1/A-501 - 6 NOTE 4
182E 3'-0" X 7'-0" X 1-3/4" A SC WT - HS ME 1/A-501 - 6 NOTE 4
184A 3'-0" X 7'-0" X 1-3/4" A SC WT - HS ME 1/A-501 - 6 NOTE 1, 4
186A 3'-0" X 7'-0" X 1-3/4" C SC WT 1
4" T HS ME 1/A-501 - 4 NOTE 1, 2
187A 3'-0" X 7'-0" X 1-3/4" A SC WT - HS ME 1/A-501 - 3 NOTE 1, 2
193A 3'-0" X 7'-0" X 1-3/4" C SC WT 1
4" T HS ME 1/A-501 - 7 NOTE 1, 3
195A 3'-0" X 7'-0" X 1-3/4" A SC WT - HS ME 1/A-501 - 3 NOTE 1, 2
195B 3'-6" X 7'-0" X 1-3/4" B SC WT EX HS ME 1/A-501 - 7 NOTE 1
196A 3'-0" X 7'-0" X 1-3/4" B SC WT 1
4" T HS ME 1/A-501 - 4 NOTE 1, 2, 3
197A 3'-0" X 7'-0" X 1-3/4" B SC WT 1
4" T HS ME 1/A-501 - 4 NOTE 1, 2, 3
198A 3'-0" X 7'-0" X 1-3/4" B SC WT 1
4" T HS ME 1/A-501 - 4 NOTE 1, 2
200A 3'-0" X 7'-0" X 1-3/4" A SC WT - HS ME 1/A-501 - 3 NOTE 1, 2
201A 3'-0" X 7'-0" X 1-3/4" B SC WT 1
4" T HS ME 1/A-501 - 4 NOTE 1, 2, 3
202A 3'-0" X 7'-0" X 1-3/4" B SC WT 1
4" T HS ME 1/A-501 - 4 NOTE 1, 2
203A 6'-0" X 7'-0" X 1-3/4" BB HS ME 1" T/N HS ME 9,14,19/A-501 - 5 NOTE 5
205A 3'-0" X 7'-0" X 1-3/4" C SC WT 1
4" T HS ME 1/A-501 - 4 NOTE 1, 2
206A 3'-0" X 7'-0" X 1-3/4" C SC WT 1
4" T HS ME 1/A-501 - 4 NOTE 1, 2
207A 3'-0" X 7'-0" X 1-3/4" C SC WT 1
4" T HS ME 1/A-501 - 4 NOTE 1, 2, 3
208A 3'-0" X 7'-0" X 1-3/4" C SC WT 1
4" T HS ME 1/A-501 - 4 NOTE 1, 2
214A 3'-0" X 7'-0" X 1-3/4" B SC WT 1
4" T HS ME 1/A-501 - 3 NOTE 1, 2
215A 3'-0" X 7'-0" X 1-3/4" A SC WT - HS ME 1/A-501 - 4 NOTE 1, 2
7 RATING
6 ELEVATION2 TYPE
SEE DOOR TYPES
3 CONSTRUCTION
EX = EXISTING DOOR
HS = HOLLOW STEEL
SC = SOLID CORE WOOD
4 FINISH
FF = FACTORY FINISH
ME = METAL ENAMEL
WT = WOOD TRANSPARENT
5 GLASS
T = TEMPERED
T/IN = TEMPERED/INSULATING
SEE FRAME ELEVATIONS
20, 45, 60, 90 INDICATES
FIRE RATING IN MINUTES
8 HARDWARE
NUMBER REFERS TO
HARDWARE GROUP IN
HARDWARE SCHEDULE IN
SPECIFICATIONS
1. EXIST DOOR & HDW TO BE
REUSED, UON. PROVIDE NEW
DOOR FRAME
2. PROVIDE SALVAGED LOCKSET PER
SECTION 087100.
3. AT EXIST DOOR, MODIFY DOOR TO
PROVIDE NEW RELITE GLAZING
KIT. PROVIDE GLAZING PER
SCHEDULE.
4. 1" UNDERCUT
5. CARD READER
9 REMARKS
DOOR TYPES
6"
6" 6"
6"
8" 6"
A C DB 10
sheet:
of:
copyright c Carlson Veit Junge Architects PC checked by:
drawn by:
dwg file:
project:
date:
revisions:
pr oj ec t:
co ns ul ta nt s:
02-20-2023 03022 A-101-X-03022-R1
KC
AMF
FLOOR PLAN
A-102
W
IL
LA
M
ET
TE
E D
U C
AT
IO
N S
ER
VI
C E
D
IS
TR
IC
T
YA
M H
IL
L
C
EN
TE
R
R
EM
O D
EL
S
W H
IG
H
W
AY
M C
M
IN
N
VI
LL
E, O R
03-09-23
ADDENDUM #2
FLOOR PLAN
1/8" = 1'-0"
AutoCAD SHX Text
PP
AutoCAD SHX Text
PP
AutoCAD SHX Text
PP
AutoCAD SHX Text
OPEN
AutoCAD SHX Text I
AutoCAD SHX Text H
AutoCAD SHX Text R
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text R
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text
SALEM, OREGON
AutoCAD SHX Text
ANGELA M. FLORES
AutoCAD SHX Text I
AutoCAD SHX Text G
DEMOLITION LEGEND
EXIST CLG GRID TO BE REMOVED
EXIST CLG GRID TO REMAIN
EXIST GYP BD CLG TO BE REMOVED
EXIST GYP BD CLG TO REMAIN
EXIST EMERGENCY EGRESS SIGN TO BE REMOVED,
RELOCATED
EXIST EMERGENCY EGRESS SIGN
EXIST 2X4 LIGHT FIXTURE TO BE REMOVED
EXIST 2X4 LIGHT FIXTURE TO REMAIN
NEW 2X4 LED LIGHT FIXTURE CENTERED IN ROOM
EXIST 1X4 LIGHT TO REMAIN
EXIST 1X4 LIGHT TO BE REMOVED
EXIST LIGHT TO REMAIN
EXIST LIGHT TO BE REMOVED
EXIST TRACK LIGHT TO REMAIN
EXIST TRACK LIGHT TO BE REMOVED
EXIST 2X2 LED LIGHT FIXTURE TO REMAIN
EXIST 2X2 LED LIGHT FIXTURE TO BE REMOVED
EXIST RECESSED DOWN LIGHT TO REMAIN
EXIST RECESSED DOWN LIGHT TO BE REMOVED
EXIST WALL MOUNT LIGHT FIXTURE
EXIST SUPPLY TO REMAIN
EXIST SUPPLY TO BE REMOVED
EXIST RETURN TO REMAIN
EXIST RETURN TO BE REMOVED
EXIST EXHAUST TO REMAIN
EXIST EXHAUST TO BE REMOVED
DEMO
A REMOVE EXISTING EXHAUST DUCT, DISCARD
REMOVE CEILING MOUNTED UNIT HEATER, SALVAGE
TO OWNER
REMOVE EXISTING SUSP CLG GRID & TILES, THIS RM
REMOVE EXISTING GYP BD CLG, THIS RM
REMOVE EXIST GYP BD SOFFIT
REMOVE PORTION OF SUSP ACOUS CLG AS REQ'D
FOR NEW WORK
REMOVE PORTION OF GYP BD CLG AS REQ'D FOR
NEW WORK
B
C
DEMOLITION NOTES
D
E
F
G
1. CONTRACTOR IS RESPONSIBLE TO FIELD VERIFY
LOCATION OF ALL HVAC EQUIPMENT
2. REMOVE CEILING TILES AS REQ'D FOR DUCT
ACCESS/CLEANING
GENERAL NOTES
A
B
10'-0"
9'-0"
10'-0"
10'-0" 10'-0"
9'-0" 9'-0"
9'-0"
9'-0" 10'-0"
9'-0"
10'-0"
10'-0"
9"-0"
8'-0"
9'-4"
9'-0"
10'-0"
9'-0"
9'-0"
DEMO
DEMO
DEMO
DEMO
10'-0"
9'-0" 9'-0" 9'-0" 9'-0"
9'-0"
9'-0" 9'-0" 9'-0" 9'-0"
9'-0"
9'-0"
9'-0"
9'-0"
9'-0"
9'-0"
10'-0"
9'-0"
9'-0" 9'-0" 9'-0"
9'-0"9'-0"
9'-0" 9'-0"
9'-0"
9'-0"9'-0"
9'-0"
9'-0"
9'-0"
9'-0"
9'-0"
9'-0"
9'-0"
9'-0"
9'-0"
10'-0" 10'-0"
10'-0"
9'-0"
16'-8"
GABLE
10'-0"
10'-0"
8'-10"
8'-10"
8'-10"
9'-0"9'-0"9'-0" 9'-0"9'-0"
10'-0"
9'-0"
10'-0"
9'-0"
9'-0"
STRUCT
STRUCT
9"-0"
9"-0"
9'-0"
10'-0"
9'-0"9'-0"9'-0"
9'-0"
9'-0" 9'-0"
9'-0"9'-0"
9'-0"
9'-4"8'-10"
9'-4"9'-4"
9'-4"
9'-4"
9'-0"
9'-0" 9'-0"
9'-0"
8'-10"
9'-0"
9'-0"
9'-0"
9'-0"
8'-10"
9'-0"
10'-0"
D
E
D C C C
C C
C
C
C
C
C
C
C
C
C
C C
C
C
C
C
C
C
C
CC
C
C
C
C C
C C C C C
C
D
DEMO
DEMO
DEMO
G G
D
G G
F F F
FE
C
FE
FEC
FEC
FEC
FE
FEC
G sheet:
of:
copyright c Carlson Veit Junge Architects PC checked by:
drawn by:
dwg file:
project:
date:
revisions:
pr oj ec t:
co ns ul ta nt s:
02-20-23 03022 A-101-X-03022-R1
KC
AMF
REFLECTED CEILING
PLAN - DEMOLITION
A-103
W
IL
LA
M
ET
TE
E D
U C
AT
IO
N S
ER
VI
C E
D
IS
TR
IC
T
YA
M H
IL
L
C
EN
TE
R
R
EM
O D
EL
S
W H
IG
H
W
AY
M C
M
IN
N
VI
LL
E, O R
03-09-23
ADDENDUM #2
REFLECTED CEILING PLAN - DEMOLITION
1/8" = 1'-0"
AutoCAD SHX Text
PP
AutoCAD SHX Text
PP
AutoCAD SHX Text
PP
AutoCAD SHX Text
OPEN
AutoCAD SHX Text I
AutoCAD SHX Text H
AutoCAD SHX Text R
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text R
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text
SALEM, OREGON
AutoCAD SHX Text
ANGELA M. FLORES
AutoCAD SHX Text I
AutoCAD SHX Text G
1 EXIST SKYLIGHT TO REMAIN
PROVIDE NEW SUSP CLG GRID & TILES TO MATCH
LAYOUT OF ADJ SPACE
EXIST ACCESS DOOR ABOVE SUSP CLG @ GYP BD
CLG OR WALL TO REMAIN
OPEN TO STRUCTURE ABOVE
PATCH/REPAIR GYP BD CLG & FINISH TO MATCH ADJ
SURFACES
PROVIDE NEW SUSP CLG GRID & TILES, THIS RM
PROVIDE NEW GYP BD CEILING, THIS RM
CONSTRUCTION NOTES
1. NEW CEILING GRIDS TO BE CENTERED IN ROOMS, UON
2. CONTRACTOR IS RESPONSIBLE TO FIELD VERIFY
LOCATION OF ALL HVAC EQUIPMENT
GENERAL NOTES
10'-0"
10'-0"
9'-0"
10'-0"
10'-0"
10'-0"10'-0"
10'-0"
9'-0" 9'-0" 9'-0"
10'-0"
9'-0" 9'-0"
9'-0" 9'-0"
9'-0"
10'-0" 10'-0"
10'-0"
9'-0" 9'-0"
9'-0"
8'-10"
9'-0"
9'-4"
9'-0"
10'-0"
9'-0"
9'-0"
9'-0"
9'-0"
9'-0" 9'-0"
1 1
10'-0"
9'-0"
9'-0"
10'-0"
9'-0" 9'-0" 9'-0" 9'-0"
9'-0"
9'-0" 9'-0" 9'-0" 9'-0"
9'-0"
9'-0"
9'-0"
9'-0"
9'-0"
9'-0"
10'-0"
9'-0"
9'-0" 9'-0" 9'-0"
9'-0"9'-0"
9'-0" 9'-0"
9'-0"
9'-0"9'-0"
9'-0"
9'-0"
9'-0"
9'-0"
9'-0"
9'-0"
9'-0"
9'-0"
9'-0"
9'-0"
9'-0"
9'-0"
10'-0" 10'-0"
10'-0"
9'-0"
9'-0"
16'-8"
GABLE
10'-0"
10'-0"
9'-0"
8'-0"
9'-4"
8'-10"
8'-10"
8'-10" 8'-10"
9'-0"
8'-10"
8'-10"9'-0" 9'-0" 9'-0" 9'-0" 9'-0" 9'-0"
8'-10"
9'-0"
9'-0"9'-0"9'-0" 9'-0"9'-0"
10'-0"
9'-4"
10-0"
9-0"
9'-0"
10'-0"
D
D
D
D
C
C
C
C
C
C
C
C
C
C
C
C
A
A
A
A
A A
A A
A A
A A A
A
A
A
A
A
AA
A
AA
A A
A A A
A
A
A
C C
A
A A A
A
A
A
AAA
A
A A
A A
A A
A
A
A
A
AAAAAAA
C C C
A
AA
A
A
A
AA
AA
A
A A A A
AAAAA
A
A
A
A A
A
A
AA
AA A
B B
A
A
AA
A
A
A
A A
A
A
A
A C
AA
A
A
10'-0"
A
A
A
A
AA
A
A A
10'-0"
A A
A
AA
A
A
A
A A
A
AA
A
A
A
A A
A
AA
A
AB
A
A A
AA
A
AA B
5 5
6 6 6
6 6 6 6 6
6 6
6 6
6 6 6
B
LEGEND
NEW CLG GRID
EXIST CLG GRID TO REMAIN
EXIST GYP BD CLG TO REMAIN
NEW GYP BD CLG
EXIST EMERGENCY EGRESS SIGN TO REMAIN
NEW EMERGENCY EGRESS SIGN
EXIST 2X4 LIGHT FIXTURE TO REMAIN
NEW 2X4 LED LIGHT FIXTURE CENTERED IN ROOM
EXIST 1X4 LIGHT TO REMAIN
EXIST LIGHT TO REMAIN
EXIST TRACK LIGHT TO REMAIN
C
EXIST 2X2 LED LIGHT FIXTURE
NEW 2X2 LED LIGHT FIXTURE
EXIST RECESSED DOWN LIGHT
NEW RECESSED DOWN LIGHT
EXIST WALL MOUNT LIGHT FIXTURE TO REMAIN
NEW WALL MOUNT LED LIGHT FIXTURE
EXIST SUPPLY TO REMAIN
NEW SUPPLY
EXIST RETURN TO REMAIN
NEW RETURN
EXIST EXHAUST TO REMAIN
NEW EXHAUST
B
A
D
MAX
8"
TRAPEZE TYPE HANGER @ DUCTWORK OR
OTHER LARGE OBSTRUCTIONS
ACOUSTIC LAY-IN TILE
(4) HEAVY DUTY MAIN RUNNERS @ 4'-0" OC
ATTACHED TO (2) ADJACENT WALLS
MIN 12 GA WIRE LATERAL BRACING PERPENDICULAR
TO EACH OTHER, SECURE TO STRUCTURE WITH
EXPANSION ANCHOR RATED FOR 200# LATERAL LOAD
MIN 12 GA
SUPPORT WIRE 100
LBS CAPACITY TYP
@ MAX 4'-0" OC
45 M
AX.
BERC CLIP @ NON-ATTACHED WALLS.
PERIMETER SUPPORT WIRE 8" MAX FROM
WALL MAX 6:1 OUT OF PLUMB AT ALL
TERMINATING MEMBERS
COUNTERSLOPE HANGERS IF MORE THAN
6:1 OUT OF PLUMB
NOTE:
1. HEAVY DUTY CROSS TEES @ ALL LIGHT FIXTURES & MECHANICAL SERVICES PER
CISCA 3-4 STANDARDS.
2. NOT ALL REQUIREMENTS ARE SHOWN. CONTRACTOR TO VERIFY WITH SITE
CONDITIONS AND CODE REFERENCES.
3. ATTACH CEILING GRID TO TWO ADJACENT WALLS. DO NOT ATTACH OPPOSITE
WALLS.
4. PROVIDE SEISMIC JOINTS ACCOMODATING 3 4" MOVEMENT AT CEILING AREAS
GREATER THAN 2,500 SQ FT.
VERTICAL STRUT @ MAX 12'-0" OC FROM
MAIN RUNNER TO STRUCTURE MAX 2" FROM
NEAREST CROSS MEMBER MAIN RUNNER/
CROSS TEE INTERSECTIONS. MUST LIMIT
MOVEMENT TO LESS THAN 1/4" @ POINT OF
ATTACHMENT. LATERAL FORCE BRACING
REQUIRED FOR CEILING AREAS OVER 1,000
SQ FT.
STRUCTURAL
FRAMING
CONSTRUCT SUSPENDED CEILINGS IN ACCORDANCE WITH NORTHWEST WALL & CEILING
BUREAU - TECHNICAL BULLETIN 401.
6'-0" MAX
MIN 12 GA
SLACK SUPPORT
WIRE @ FIXT <10
LBS - (2) WIRES
@ FIXT >10 LBS
1 SUSPENDED CEILING DETAIL
1/2" = 1'-0" sheet:
of:
copyright c Carlson Veit Junge Architects PC checked by:
drawn by:
dwg file:
project:
date:
revisions:
pr oj ec t:
co ns ul ta nt s:
02-20-23 03022 A-101-X-03022-R1
KC
AMF
REFLECTED CEILING
PLAN
A-104
W
IL
LA
M
ET
TE
E D
U C
AT
IO
N S
ER
VI
C E
D
IS
TR
IC
T
YA
M H
IL
L
C
EN
TE
R
R
EM
O D
EL
S
W H
IG
H
W
AY
M C
M
IN
N
VI
LL
E, O R
03-09-23
ADDENDUM #2
REFLECTED CEILING PLAN
1/8" = 1'-0"
AutoCAD SHX Text I
AutoCAD SHX Text H
AutoCAD SHX Text R
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text R
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text
SALEM, OREGON
AutoCAD SHX Text
ANGELA M. FLORES
AutoCAD SHX Text I
AutoCAD SHX Text G
WINDOW SCHEDULE
WDW
MARK
NOMINAL WINDOW
SIZE (W X H)
O
PE
R
AT
IO
N
TY
PE
(A
FR
AM
E M
AT
ER
IA
L
(B
FR
AM
E
FI
N
IS
H (C
FR
AM
E
EL
EV
AT
IO
N
(D
G
LA
SS
TH
IC
KN
ES
S
(E
G
LA
SS
T
YP
E
(F
G
LA
SS
C
O
LO
R (G
REMARKS (H)
A 5'-0" x 3'-0" F HS ME SEE WINDOW
ELEVATIONS
4" T C
B 3'-4" x 5'-0" F/AW AL AN SEE WINDOW
ELEVATIONS 1" T/IN E
C 5'-0" x 3'-6" F HS ME SEE WINDOW
ELEVATIONS
4" T C
D 3'-6" x 3'-0" F HS ME SEE WINDOW
ELEVATIONS
4" T C
F = FIXED
AW = AWNING
AL = ALUMINUM
HS = HOLLOW STEEL
AN = ANODIZED
ME = METAL ENAMEL
C FRAME FINISH
B FRAME MATERIAL
A OPERATION TYPE D FRAME ELEVATIONS
SEE WINDOW TYPES
E GLASS THICKNESS
G GLASS COLOR
C = CLEAR
E = LOW-E COATED
H REMARKSNUMBER REFERS TO OVERALL
GLAZING THICKNESS
T = TEMPERED
T/IN = TEMPERED / INSULATING
F GLASS TYPE
1.
PL-1
COUNTER
AND 4"
BACKSPLASH
WIRE PULLS,
TYP
6'-0"
(4) EQ PANELS
RB-1, TYP
FIXED SHELF
PL-4
CHROMEBOOK SLOT
STORAGE W/ POWER
PORTION OF
CABINET BACK OPEN
ADJ SHELVES,
TYP
PL-4
INDUST STRENGTH
EXHAUST GRILL
4'-0"
(2) EQ PANELS
2' -1
0"
PL-1
COUNTER
AND 4"
BACKSPLASH
WIRE PULLS,
TYP
6'-0"
(4) EQ PANELS
RB-1, TYP
ADJ SHELVES,
TYP
PL-4
4'-0"
(2) EQ PANELS
1' -0
"2' -1
0" 1'
-1 1"
3' -3
1' -1
1" 3'
-3
A-502
A-502
1' -0
PL-3PL-4
A-201
E
A-201
J
G
H
A-201F
A-201
K
3' -7
1'
-5
6' -8
1' -1
2'
-5
100°
5'-0"
8'-0"
A-502
A-502
A-502
2' -6
3' -8
8'-10"
2' -6
2' -1
0"
3'-11"5'-0"
1' -2
2' -6
3' -8
1' -2
9' -4
9' -4
MATCH ADJ
SURFACES
2' -1
0"
(6) EQ CUBBIES
1'-3"SS-2
PL-2
SS-1
PL-2
SS-2
PL-2
SS-3
SS-1
PL-2
SS-2
PL-2
RB-1RB-1RB-1
SS-2
PL-2 61
2"
A-502
MATCH ADJ
SURFACES
7'-7" RB-1
TACK BD
SS-2
(2 ) E
Q
P-1 P-1
P-1
P-1
CASEWORK
PARTIAL HT WALL
WITH DOOR PL-2
SS-2
PL-2
SS-1
RB-1
2' -1
0"
ADJ SHELVES,
TYP
PL-3
WIRE PULLS,
TYP
RB-1, TYP
COPIER
2' -1
0" 1'
-1 1"
3' -3
1'-0"
2'-0"
PL-1 COUNTERTOP
AND 4" BACKSPLASH
4'-0"
(2) EQ PANELS
ADJ SHELVES, TYP
PL-3
WIRE PULLS, TYP
RB-1, TYP
2' -1
0" 1'
-1 1"
3' -3
1'-0"
2'-0"
PL-1, COUNTERTOP
AND 4" BACKSPLASH
4'-0"
(2) EQ PANELS
1'-0"4'-0"
(2) EQ PANELS
PL-4
WIRE PULLS,
TYP
RB-1, TYP
PL-1 COUNTERTOP
AND 4" BACKSPLASH
10'-0"
(5) EQ PANELS
PL-4 PL-4 5'-0"
CLR MIN
1'-7"
A-502
A-502
4'-0"
(2) EQ PANELS
2'-0"
3'-0"
(2) EQ PANELS
2' -1
0"
CASEWORK
PARTIAL HT WALL
WITH DOOR PL-2
PL-2
SS-2
RB-1
2' -6
1'
-2
A-502
P-1 P-1
P-1
WINDOW ELEVATIONS
A BA
3' -0
3'
-0
5'-0"
2' -8
3'
-8
3'-4"
1' -4
5' -0
FIXED PANEL
OPERABLE
SASH
C
3' -8
3'
-6
5'-0"
D
3' -0
3'
-0
3'-6"
A-501 10
A-501
A-501
A-501
A-501
A-501
16" DEEP PL-5
SHELVES
PL-1,
COUNTERTOP
W/ 6"
BACKSPLASH
4" WIRE PULLS,
TYP
RB-2
FRP
PL-6
3'-1" 16" DEEP PL-5
SHELF
PL-1,
COUNTERTOP
W/ 6"
BACKSPLASH
4" WIRE PULLS,
TYP
PL-6
1'-8"
DW DW
2'-9" 1'-4" 2'-3"
2' -1
0" 1'
-1 1"
1' -6
2'-0"
VFY
2'-0"
VFY
2'-6"
VFY
2'-7"
VFY
RB-1
2' -1
0" 1'
-1 1"
1' -6
A-502
A-502
A-502
3'-3"
TYP
1'-6"
RB-2
2'-3"
FRP
PL-5 FIXED PANEL
sheet:
of:
copyright c Carlson Veit Junge Architects PC checked by:
drawn by:
dwg file:
project:
date:
revisions:
pr oj ec t:
co ns ul ta nt s:
02-20-2023 03022 A-201-03022-R1
KC
AMF
WINDOW SCHEDULE
AND ELEVATIONS
A-201
W
IL
LA
M
ET
TE
E D
U C
AT
IO
N S
ER
VI
C E
D
IS
TR
IC
T
YA
M H
IL
L
C
EN
TE
R
R
EM
O D
EL
S
W H
IG
H
W
AY
M C
M
IN
N
VI
LL
E, O R
03-09-23
ADDENDUM #2
A TYP CLASSROOM
1/4" = 1'-0"
B TYP CLASSROOM
1/4" = 1'-0"
C KITCHEN 113
1/4" = 1'-0"
D KITCHEN 113
1/4" = 1'-0"
1 RECPTION DESK
1/4" = 1'-0"
E LOBBY 101
1/4" = 1'-0"
F LOBBY 101
1/4" = 1'-0" G LOBBY 101
1/4" = 1'-0"
H LOBBY 101
1/4" = 1'-0"
J LOBBY 101
1/4" = 1'-0"
L WORKROOM 102
1/4" = 1'-0"
M WORKROOM 102
1/4" = 1'-0"
N WORKROOM 102
1/4" = 1'-0"
K LOBBY 101
1/4" = 1'-0"
AutoCAD SHX Text I
AutoCAD SHX Text H
AutoCAD SHX Text R
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text R
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text
SALEM, OREGON
AutoCAD SHX Text
ANGELA M. FLORES
AutoCAD SHX Text I
AutoCAD SHX Text G
FD
FD
10'-0"
HWC
TPD
GB
GB
TSCD
TSCD
TSCD
TSCD
TSCD
TSCD
HWC
WC
WC
WC
WC
TPD
TPD
TPD
TPD
TPD
1' -1
5' -0
'-6
5' -0
1' -3
EQ
EQ
3' -3
LAV
MI
PTD PTD
PTD PTD
SD
SD
SD
SD
MI
MI
MI
MI
LAV
LAV
LAV
LAV
A-401
E
A D
A-401
P
Q S
R
HALL
HALL
RR
HALL
RR
6' -1
0"
2'-0"
GB
GB
GB
GB
SD PTD
SND
3' -3
3'
-3
4' -4
4'
-4
4' -4
4'
-4
5'-7"
A-401
K
L N
M
A-401
B
C
A-401
G
H K
J
2'-4"
A-401F
A-401
G
H K
J
A-401
G
H K
J
A-401
G
H K
J
1'-4"
SNR
SNR
SNR
SNR
SNR
6' -0
6"
T-1, 6" BASE
T-2
E.Q.E.Q.E.Q.
7' -0
2' -1
0"
SS-1
T-1
T-2
T-2
P-5P-5 P-5 MI 30"x48", TYP
SS-1
P-5
T-1
T-2
TS-1, TYP
TS-2, TYP
WBT-1, TYP T-3
TS-1, TYP TS-1, TYP TS-1, TYPTS-3
TS-3, TYP
TS-3, TYP
T-2
P-5
TS-1, TYP
TS-3, TYP
TS-3, TYP
TS-2, TYP
TS-3
2'-0"
T-2
2' -5
5"
A-502
TPD
GRAB BARS
GRAB BARS
T-2
T-1
T-2
T-1
P-5
T-1
T-2 T-2
T-1 T-2
T-1
P-5 P-5
TSCD
P-5
TPD
TSCD
SNR
SNR
TS-1 TS-1, TYP TS-1, TYP TS-1, TYP TS-1
TS-2 TS-2 TS-2, TYP TS-2
P-5
TPD
TSCD
TS-2
WDT-1
PAPER TOWELDRINKING FOUNTAIN (DF)
OR ELECTRIC WATER
COOLER (EWC) LOW
M
AX
DRINKING FOUNTAIN (DF)
COOLER (EWC) HIGH-LOW
OR ELECTRIC WATER
SPOUT
" 39
DRINKING FOUNTAIN/
CUSPIDOR (DF/C) DISPENSER
ACCESSIBLE WATER
CLOSET (HWC)CLOSET (HWC)
ACCESSIBLE WATER
SANITARY NAPKIN
TYPICAL UNLESS OTHERWISE NOTED
ALL DIMENSIONS ARE CLEAR FINISH
DISPENSER (SND)
FIRE EXTINGUISHER
CABINET (FEC) /
FIRE EXTINGUISHER (FE)
FEC
FE
SIGN
15"
MIN
INSULATE
WALL-HUNG LAVATORY
M
IN 34
M
AX
PIPES
(LAV)
4"
LAVATORY COUNTER
LAVATORY (LAV) AND
PIPES
INSULATE
BACKSPLASH
" M
AX
6" M
IN
" M
IN
54" MIN
42"
MIN
12"
MAX
BAR (GB)
GRAB
M
IN
39"-41"
16"-18"
36" MIN
" (GB)
24"
MIN
12"
MIN
" M
AX
(TSCD)
M
IN
42"
MAX
24"
MIN
1ï
M
IN
" M
AX
M
IN
36"
MAX
(MI)
" M
AX
AB
V
LA
V
24"
" 15"
MIN
(MI)
" M
AX
AB
V
LA
V
24"
M
IN 34
M
AX
4"
LOCATE SIGN
ON LATCH
SIDE OF DOOR
OR NEAREST
ADJACENT WALL
5"
MAX
15"
MIN
SIDE FRONT
M
AX
SPOUT
8"
MIN 27
M
IN11"
MIN9" M
IN
2" MAX
SPOUT
RECESS
FIXTURE MOUNTING HEIGHTS
NTS
PTD
2'-0"
VANITY LIGHT
24" X 36" MIRROR
WALL MOUNT LAV
TPD
GRAB BARS
WALL
MOUNT
LAV
SD
T-1
T-2
GRAB BARS
T-2
TS-1
T-2
TS-1
T-2
TS-1
P-5 P-5 P-5P-5
TSCD
TPD
TSCD
SNR
TS-2
TS-1
TS-2
T-1 T-1
TS-2
WDT-5
TS-2
T-1
TSCD
HWC
TPD
GB
SNR
PTD SD
LAV
MI
A-401
T
W U
V
RR
EXIST VANITY LIGHT
EXIST MIRROR
EXIST WALL
MOUNT LAV EXIST
GRAB BAR
T-1
P-5
EXIST TSCD
EXIST TPD
EXIST RECESSED
PTD/R
EXIST WALL
MOUNT LAV
EXIST SD
T-1
T-2
P-5
T-2
T-1
TSCD
EXIST GRAB
BAR
EXIST TPD
EXIST
SNR
TS-1 TS-1 TS-1, TYP
TS-2
WDT-1
TS-2
T-2
P-5
TS-2
sheet:
of:
copyright c Carlson Veit Junge Architects PC checked by:
drawn by:
dwg file:
project:
date:
revisions:
pr oj ec t:
co ns ul ta nt s:
20223
02-20-2023 03022 A-401-03022-R1
KC
AMF
LARGE SCALE
PLANS AND
ELEVATONS
A-401
W
IL
LA
M
ET
TE
E D
U C
AT
IO
N S
ER
VI
C E
D
IS
TR
IC
T
YA
M H
IL
L
C
EN
TE
R
R
EM
O D
EL
S
W H
IG
H
W
AY
M C
M
IN
N
VI
LL
E, O R
03-09-23
ADDENDUM #2
1 LARGE SCALE RR PLAN
1/4" = 1'-0"
A RR 182
1/4" = 1'-0" B RR 182
1/4" = 1'-0"
C RR 182
1/4" = 1'-0"
D RR 182
1/4" = 1'-0"
E RR 182
1/4" = 1'-0"
H RR 182, TYP
1/4" = 1'-0"
J RR 182, TYP
1/4" = 1'-0"
F HALL 183
1/4" = 1'-0"
K RR 182, TYP
1/4" = 1'-0"
L RR 182, ADA
1/4" = 1'-0"
M RR 182, ADA
1/4" = 1'-0"
N RR 182, ADA
1/4" = 1'-0"
P RR 182, ADA
1/4" = 1'-0"
Q RR 184
1/4" = 1'-0"
R RR 184
1/4" = 1'-0"
S RR 184
1/4" = 1'-0"
T RR 184
1/4" = 1'-0"
2 LARGE SCALE RR PLAN
1/4" = 1'-0"
U RR 216
1/4" = 1'-0"
V RR 216
1/4" = 1'-0"
W RR 216
1/4" = 1'-0"
X RR 216
1/4" = 1'-0"
G RR 182, TYP
1/4" = 1'-0"
1 1 1
1 1 1 1
DOOR
HEADER
GYPSUM BOARD
HS FRAME
WALL TYPE
ACCORDING TO
VARIES
2"
STUDS
CONC SLAB1/2" MAX
FINISH PER
SCHEDULE
THRESHOLD
SET IN
SEALANT
INTERIOREXTERIOR
HS DOOR FRAME
HS DOOR
DOOR SWEEP
7 WALL INFILL AT HEAD
3" = 1'-0"
12 WALL INFILL AT JAMB
3" = 1'-0"
17 WALL INFILL AT FOOTING
3" = 1'-0"
8 EXTERIOR ALUM WINDOW HEAD
3" = 1'-0"
13 EXTERIOR ALUM WINDOW JAMB
3" = 1'-0"
18 EXTERIOR ALUM WINDOW SILL
3" = 1'-0"
9 EXTERIOR HS DOOR HEAD
3" = 1'-0"
14 EXTERIOR HS DOOR JAMB
3" = 1'-0"
19 EXTERIOR HS DOOR THRESHOLD
3" = 1'-0"
11 INTERIOR HS DOOR HEAD / JAMB SIM
3" = 1'-0"
16 INTERIOR HS DOOR THRESHOLD
3" = 1'-0"
10 INTERIOR HS WINDOW HEAD / JAMB / SILL
3" = 1'-0"
REMOVE EXIST INT
PLYWD, 2X10 NAILER,
OH DOOR, STL
TRACK/COVER
EXIST CMU
VENEER
EXTERIOR INTERIOR
EXIST PLYWD
SHTHG
EXIST MAS
FLASHING
EXIST STL
LINTEL
BACKER ROD
& SANDED
SEALANT
JOINT
CMU VENEER
TO MATCH
EXIST
WRB OVER
PLYWD
SHTHG
EXIST STL HDR TO
REMAIN
SHIM AS REQD
NEW 2X6 WD
STUD WALL
W/ R-21 BATT
INSUL &
VAPOR
RETARDER
GYP BD
EXTERIOR INTERIOR
NEW 2X6 WD STUD
WALL W/ R-21 BATT
INSUL & VAPOR
RETARDER
GYP BD
PT PLATE
RUBBER BASE &
FINISH FLG PER PLAN
EXIST CONC
FOUNDATION & SLAB
ON GRADE
WRB
EXIST CONC
WALK
WEEP HOLES
@ 32" OC
THRU WALL
MAS FLASHING,
CUT FLUSH @
EXT VENEER
FACE
PLYWD SHTHG
FLEX
FLASHING
EXTERIOR
INTERIOR
NEW 2X6 WD STUD
WALL W/ R-21 BATT
INSUL & VAPOR
RETARDER
GYP BD
REMOVE EXIST
BLKG, OH DOOR
TRACK/COVER
3" WIDE, 24 GA GALV SHT
MTL W/ HEMMED EDGES.
LAP OVER EXIST BLDG
PAPER & SET IN SEALANT
EXIST STL
TUBE
SUPPORT
TO REMAIN
EXIST CMU VENEER
EXIST BLDG PAPER
OVER PLYWD SHTHG
CMU VENEER TO
MATCH EXIST
WRB OVER PLYWD
SHTHG
4"
EXTERIOR INTERIOR
PLYWD SHTHGCMU VENEER
FLEX FLASHING
OVER FLEX MAS
FLASHING
5 X 5 X 0.25 STL
LINTEL
WRB, WRAP
INTO OPENING
WEEP HOLES
2-PIECE PREFIN
HEAD FLASHING
NEW ALUM WINDOW
W/ INSUL GLAZING
BACKER ROD &
SEALANT
INTERIOR AIR
SEAL, MUST BE
IN CONTACT W/
WRB
GYP BD
2X6 STUD
WALL W/ R-21
BATT INSUL &
VAPOR
RETARDER
4X8 WD
HEADER
2"
2X6 STUD
WALL W/ R-21
BATT INSUL &
VAPOR
RETARDER
GYP BD
M
AT
C H
EX
IS
T
3/4" PLYWD W/
PLAM TO
MATCH EXIST,
ALL EXPOSED
EDGES & ENDS
EXTERIOR INTERIOR
STRUCTURAL
BACK DAM
ANGLE
SEALANT
NEW ALUM WINDOW
W/ INSUL GLAZING,
SHIM AS REQD
PREFIN SHT MTL
FLASHING
FLEX FLASHING,
EXTEND UP & OVER
WRB
BRICK SILL TO
MATCH EXIST
WRB OVER PLYWD
SHTHG
CMU VENEER
EXTERIOR
INTERIOR
PREFIN SHT MTL JAMB
FLASHING, BED TO WRB
NEW ALUM
WINDOW W/ INSUL
GLAZING, SHIM AS
REQD
PLAM SILL BELOW
BACKER ROD &
SEALANT
INTERIOR AIR
SEAL, MUST BE IN
CONTACT W/ WRB
BRICK SILL BELOW
CMU VENEER
PLYWD SHTHG
SANDED
SEALANT JOINT
GYP BD2X6 STUD WALL W/
R-21 BATT INSUL &
VAPOR RETARDER
FLEX FLASHING
OVER SHT MTL
WRB, WRAP
INTO JAMB
15 CASED OPENING SILL
3" = 1'-0"
NEW HARDWOOD CAP
RECESSED SS
FLAT-HEAD
SCREWS @ 9" OC
HARDWOOD PLUGS
FLUSH W/ TRIM
2"
LAP TRIM OVER EXIST
GYP BD & CAULK
JOINT, TYP
DOUBLE 2X6 PLATE
2"
WALL PER PLAN
4"
WALL TYPE
VARIES
ACCORDING TO
2"
HEADER
GYP BD
HS FRAME
ANCHOR
GLAZING PER
SCHEDULE
1/ 2"
M
AX
DOOR
TRANSITION STRIP
PER FINISH
CONDITIONS HOLLOW
STEEL FRAME
FINISH PER
SCHEDULE
FINISH PER
SCHEDULE
EXTERIOR INTERIOR
CMU VENEER
OVER BLDG
PAPER OVER
PLYWD
SHTHG
EXIST STL
LINTEL
2-PIECE PREFIN
HEAD FLASHING
HS INSUL DOOR
GYP BD
EXIST 2X6
STUD WALL
EXIST WD
HEADER
2"
BACKER ROD &
SEALANT HS DOOR
FRAME, BACK
PLASTER, TYP
EXTERIOR
INTERIOR
EXIST CMU VENEER
OVER BLDG PAPER
OVER PLYWD SHTHG
SANDED
SEALANT JOINT
GYP BDEXIST 2X6 STUD
WALL
2"
PREFIN SHT MTL JAMB
FLASHING, BED TO WRB
BACKER ROD &
SEALANT
HS DOOR FRAME, BACK
PLASTER, TYP
HS INSUL DOOR
INSTALL WINDOW SHIM & ADJ TO
ACHIEVE PLUMB & SQ PER MFR
RECOMMENDATIONS,USE CORROSION
RESISTANT FASTENERS
WINDOW OPENING
BEYOND BLDG WRAP
20 WINDOW FLASHING INSTALLATION
1/2" = 1'-0"
INSTALL FLEX
FLASH CORNER TABS
TO SEAL WEATHER
RESISTANT BARRIER &
SILL FLASH
MAKE (4) CUTS IN
BLDG WRAP AT WINDOW
OPENING AS INDICATED
DIAGRAM 4DIAGRAM 1
SEAL WDW HEAD & INSTALL
DRIP FLASHING W/ VERT
LEG UNDER WRAP
FOLD BLDG WRAP FLAPS
AROUND JAMBS &
FASTEN TO BACK OF
FRAMING
APPLY BLDG WRAP
OVER SHTHG STARTING
FROM BOTTOM OF WALL
(OVERLAP EACH COURSE
VERT & HORIZ - MIN 6",
SEAL OR TAPE)
DIAGRAM 2
WALL SHEATHING, TYP.
INSTALL FLEX FLASH PAN
OVER BLDG WRAP - TURN
UP @ ENDS & SILL STOP
INSTALL FLASHING STOP
ANGLE
INSTALL FLEX FLASH @
JAMBS & ADHERE TO
WDW FRAME
CUT & REMOVE TABS
INSTALL SHIM BLOCKS PER
WDW MFR RECOMMENDATIONS
INSTALL 12" STRIP OF
FLEX FLASH OVER TOP
OF WDW - SEAL TO
DRIP & JAMB FLASHING
DIAGRAM 5
6"
4"
FOLD BOTTOM FLAP OF
BLDG WRAP OVER SILL &
FASTEN TO INSIDE OF
FRAMING
FOLD BACK SIDE FLAPS
OF BLDG WRAP &
TEMPORARILY SECURE
IN PLACE
DIAGRAM 3
6" MIN
6" MIN
4 WALL CONNECTION @ EXIST SOFFIT
1-1/2" = 1'-0"
EXISTING SOFFIT
FRAMING
NEW WALL PER PLAN
EXIST T-BAR
CONTROL JOINT
1 NEW SLAB CONNECTION AT EXIST SLAB
1 1/2" = 1'-0"
REPAIR / REPLACE
VAPOR RETARDER
± 2'-0"
PLUMBING DEMO
COMPACTED NATIVE
STRATA ON
STRUCTURAL FILL
NEW CONC SLAB TO
MATCH EXIST DEPTH,
4" MIN
EXIST 4" CONC
SLAB W/ #4 @ 16"
OC EA WAY
DRILL & DRIVE #4 X 16"
DOWEL INTO EXIST SLAB
@ 32" OC, EMB = 3"
(2) #4 LONG
5 ACOUSTICAL WALL - TYPE 1
1-1/2" = 1'-0"
AC1
SIMPSON STC TRUSS
CLIP
EXISTING FLR JOIST
OR ROOF STRUCTURE
TO REMAIN
ACOUSTIC SEALANT
BLKG BTWN
JOISTS OR
TRUSSES
(1) LAYER GWB EACH
SIDE W/ ABUSE
RESTRICTIVE GWB
@ LOWER 48"
NOTE: LIBERALLY
BUTTER ALL
FACES OF
UTILITY BOXES,
PERIMETER
EDGES, & GAPS
W/ ACOUSTIC
SEALANT
SUSPENDED
CEILING
ACOUSTIC SEALANT
MINERAL WOOL
ACOUSTIC INSULATION,
FULL HEIGHT OF WALL
2X WD STUDS @ 24"
OC, UON
6 ACOUSTICAL WALL - TYPE 2
1-1/2" = 1'-0"
AC2
SIMPSON STC TRUSS
CLIP
EXISTING FLR JOIST
OR ROOF STRUCTURE
TO REMAIN
BLKG BTWN
JOISTS OR
TRUSSES
(1) LAYER GWB EACH
SIDE W/ ABUSE
RESTRICTIVE GWB
@ LOWER 48"
NOTE: LIBERALLY
BUTTER ALL
FACES OF
UTILITY BOXES,
PERIMETER
EDGES, & GAPS
W/ ACOUSTIC
SEALANT
SUSPENDED
CEILING, TYP
ACOUSTIC SEALANT
MINERAL WOOL
ACOUSTIC INSULATION,
TO 6" ABV CLG
2X WD STUDS @ 24"
OC, UON
3 TYPICAL WALL
1-1/2" = 1'-0"
EXIST CONC SLAB ON
GRADE
2X PT PLATE, SECURE
W/ PAF TO FLOOR @
32" OC
BLOCKING
SUSP ACOUS TILE
CLG PER PLAN
DBL TOP PLATE
SIMPSON STC TRUSS
CLIP @ EA BLKG
EXIST ROOF JOIST
BLOCKING @
4'-0" OC,
CONTRACTOR
OPTION TO
PROVIDE
ALTERNATING
DIAG BRACING
@ 4'-0" OC
CURB BY HVAC
STRUCTURAL SYSTEM MFR
FRAMING AS REQ'D BY
ADDITIONAL JOISTS OR
EQUIP MFR
0' -5
ROOF SHTHG
RIGID INSUL
2 HVAC UNIT CURB
1" = 1'-0"
COUNTERFLASHING
BASE FLASHING
CANT
CURB AS REQ'D
BY STRUC
SEALANT
0' -8
"BUILT-UP RFG W/
APPLIED COATING
NOTE: ROOFING HAS AN APPLIED
COATING THAT IS UNDER
WARRANTY. CONTACT LARRY,
LEHRKE, 253-355-4000, TREMCO
ROOFING AND MAINTENANCE FOR
ANY ROOF PATCHING
sheet:
of:
copyright c Carlson Veit Junge Architects PC checked by:
drawn by:
dwg file:
project:
date:
revisions:
pr oj ec t:
co ns ul ta nt s:
02-20-2023 03022 A-501-03022
KC
AMF
DETAILS
A-501
W
IL
LA
M
ET
TE
E D
U C
AT
IO
N S
ER
VI
C E
D
IS
TR
IC
T
YA
M H
IL
L
C
EN
TE
R
R
EM
O D
EL
S
W H
IG
H
W
AY
M C
M
IN
N
VI
LL
E, O R
03-09-23
ADDENDUM #2
AutoCAD SHX Text I
AutoCAD SHX Text H
AutoCAD SHX Text R
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text R
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text
SALEM, OREGON
AutoCAD SHX Text
ANGELA M. FLORES
AutoCAD SHX Text I
AutoCAD SHX Text G
1' -7
2'
-1 0"
1'-1"
4"
2"
2"
2'-1"
PL-4 TOP OVER 1/2"
PLYWD, DOOR TYP
RB-1
ADJ SHELVES,
TYP
ADJ SHELVES,
TYP
PL-3 TOP OVER 3/4" PLYWD
TYP
PL-3 TOP OVER 1/2"
PLYWD, DOOR TYP
PL-1 OVER 3/4" PLYWD
TYP
8' -0
4"
RB-1, TOEKICK
ATTACHED TO CAB
DOOR
ADJ SHELVES,
TYP
FIXED
SHELVES, TYP
PL-4 TOP OVER 1/2"
PLYWD, DOOR TYP
2'-0"
PL-4 TOP OVER 3/4" PLYWD
TYP
1 CLASSROOM
3/4" = 1'-0"
2 CASEWORK, TYP
3/4" = 1'-0"
3' -3
4"
3' -8
1'-4"
RECEPTACLE,
TYP
PORTION OF
CABINET
BACK OPEN
TO ALLOW
FOR
ELECTRICAL
SUPPLY TO
CHROME-
BOOKS
PL-4 TOP OVER 1/2"
PLYWD, DOOR TYP
1' -7
2'
-1 0"
1'-1"
4"
2"
2"
2'-1"
PL-4 TOP OVER 1/2"
PLYWD, DOOR TYP
RB-1
ADJ SHELVES,
TYP
PL-3 TOP OVER 3/4" PLYWD
TYP
PL-3 TOP OVER 1/2"
PLYWD, DOOR TYP
PL-1 OVER 3/4" PLYWD
TYP
3 CASEWORK, TYP
3/4" = 1'-0"
3' -3
4"
2' -1
0"
4"
2"
2"
2'-1"
PL-6 TOP OVER 1/2"
PLYWD, DOOR TYP
RB-1
PL-1 OVER 3/4" PLYWD
TYP
5 KITCHEN
3/4" = 1'-0"
6"
(2) LAYERS 3/4" PLYWD
FACED WITH PL-5
1'-1"
1' -5
1'
-6
FRP
2' -1
0"
4"
2"
2'-1"
RB-1
PL-1 OVER 3/4" PLYWD
TYP
4 KITCHEN
3/4" = 1'-0"
6"
(2) LAYERS 3/4" PLYWD
FACED WITH PL-5
1'-1"
1' -5
1'
-6
FRP
ADJ SHELVES,
TYP
4" WIRE PULL
PL-6 VERT
FACE TYP
7 COUNTERTOP DETAIL
1 1/2" = 1'-0"
SCRIBE TO WALL
3/4" X 4" OR 3/4" X 6"
BACKSPLASH, SELF-EDGED
PLAM, UON
4"
4"
2"
18"/24"/28"
CABINET
CONTRACTOR OPTION TO PROVIDE
2X WOOD BLK BETWEEN STUDS
6"X18 GA. MTL STRAP @ EACH STUD.
SPAN MIN 3 STUDS OR ONE STUD
SPACE BEYOND HUNG ITEM.
3 #10 TEK SCREWS AT EACH STUD
METAL STUD AS PER
FLOOR PLAN
NOTE: CONTRACTOR TO PROVIDE
ANCHORAGE OF MIN 250 LBS AT ALL GRAB
BAR LOCATIONS
CABINET PER INTERIOR ELEVATIONS
1X3 CONT. CABINET FRAME
6"x18 GA MTL STRAP @ EACH STUD.
SPAN MIN 3 STUDS OR ONE STUD
SPACE BEYOND HUNG ITEM
WALL ASSEMBLY PER FLOOR PLAN, UON
6" X18 GA MTL STRAP @ EACH STUD
(SPAN MIN OF 3 STUDS) OR ONE
STUD SPACE BEYOND HUNG ITEM
2 1/2" #10 MTL SCREWS AT MAX 32"
OC TYP
1 1/4" SQ STL TUBE BOLT TO WALL,
PROVIDE END CAPS, WELD & GRIND
SMOOTH COUNTERTOP
BLOCKING @ ALL BRACES
6"
6" A
FF
(T
YP
9 BACKING PLATE
1 1/2" = 1'-0"
8 CABINET ANCHORAGE
1 1/2" = 1'-0"
10 TYPICAL BRACE
1 1/2" = 1'-0"
11 RECEPTION COUNTER
1 1/2" = 1'-0"
RUBBER
BASE
FINISHED
FLOOR
2' -1
0"
SS-1 OVER 3 4"
PLYWD
PL-2 VERT FACE
TYP ON 3 4" PLYWD
1'-5"
CLR
2"
2'-5"
2X4 STUDS @ 24"
OC, PROVIDE
PATHWAY FOR
CABLES/CONDUITS
12 RECEPTION COUNTER
1 1/2" = 1'-0"
RUBBER
BASE
FINISHED
FLOOR
3' -8
SS-1 OVER 3 4"
PLYWD
PL-2 VERT FACE
TYP ON 3 4" PLYWD
1'-4"
CLR
2"
2'-0"
2X4 STUDS @ 24"
OC, PROVIDE
PATHWAY FOR
CABLES/CONDUITS
2' -6
SS-2 OVER 3 4"
PLYWD
FIXED 12" PLYWD
SHELVES
PLAM ALL EXPOSED
FACES
1' -2
13 RECEPTION COUNTER
1 1/2" = 1'-0"
RUBBER
BASE
FINISHED
FLOOR
3' -8
PL-2 VERT FACE
TYP ON 3 4" PLYWD
2X4 STUDS @ 24"
OC, PROVIDE
PATHWAY FOR
CABLES/CONDUITS
2' -6
SS-2 OVER 3 4"
PLYWD
2' -1
0"
PL-1
PL-6 VERT
FACE TYP
4" WIRE PULL
2"
2"
4"
3" RB-12'-0"
DROP IN SINK
FAUCET
(2) LAYERS 3/4" PLYWD
FACED WITH PL-5
1'-1"
6 SINK
3/4" = 1'-0"
1' -5
1'
-6
6"
FRP
MIRROR
CORIAN OVER
PLYWD
STL SUPPORT
TILE PER SCHEDULE
ALUM SCHLUTER COVE
PER SCHEDULE
TILE FLOORING PER
SCHEUDLE
5" 2'
-1 0"
2'-0"FO
S
ADA TRAP
COVER
14 VANITY SECTION
3/4" = 1'-0"
1/4" STL
BRACKET @
4'-0" O.C. MAX
W/ 3/8" DIA.
M.B. @ CNTR
FRAMING &
STUDS
TILE PER SCHEDULE
sheet:
of:
copyright c Carlson Veit Junge Architects PC checked by:
drawn by:
dwg file:
project:
date:
revisions:
pr oj ec t:
co ns ul ta nt s:
02-20-2023 03022 A-501-X-03022
KC
MJ
DETAILS
A-502
W
IL
LA
M
ET
TE
E D
U C
AT
IO
N S
ER
VI
C E
D
IS
TR
IC
T
YA
M H
IL
L
C
EN
TE
R
R
EM
O D
EL
S
W H
IG
H
W
AY
M C
M
IN
N
VI
LL
E, O R
03-09-23
ADDENDUM #2
AutoCAD SHX Text I
AutoCAD SHX Text H
AutoCAD SHX Text R
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text R
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text
SALEM, OREGON
AutoCAD SHX Text
ANGELA M. FLORES
AutoCAD SHX Text I
AutoCAD SHX Text G
CPT-1
CPT-1
CPT-1
LVT-1
LVT-1LVT-1 LVT-1 LVT-1
T-1
RB-1
T-1
CPT-1
LVT-1
LVT-1
CPT-1
RB-1
RB-1RB-1RB-1
RB-1
RB-1
LVT-2
RB-1
RB-1
RB-1
RB-1
RB-1
RB-1
RB-1
RB-1
RB-1
RB-1
RB-1
RB-1
LVT-1
RB-1
LVT-1RB-1
RB-1
LVT-1
LVT-1
RB-1
FE
FD
FD
FD
FD
FD
FD
FD
DS
RD
DS
DS
DS
DS
DS
DS
DS
W D
FD
FD
OFFICE
OFFICE
OFFICE
OPEN OFFICE
OFFICE
COATS
STORAGE
MECH
OFFICE
OFFICE
OFFICE
OFFICE
HALL
SENSORY
HALL
OFFICE
OFFICE
OFFICE
OFFICE
STAFF LOUNGE
HALL
OFFICE
OFFICE
OFFICE
CONFERENCE
OFFICE
OFFICE
HALL
HALL
OFFICE
WORKROOM
WORKROOM
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
VESTIBULE
OFFICE
HALL
HALL
KITCHEN
FOOD STORAGE
MEN
WOMEN
HALL
HALL
STORAGE
MEETING
MEETING
MEETING
COFFEE
STORAGE
STORAGE
HALL
VESTIBULE
GALLERY
EQUIP STOR
EQUIP STOR
106 SERVER
CLASSROOM
CLASSROOM
WOMEN
MEN
HALL
CLASSROOM 1
CLASSROOM 2
CLASSROOM 3
STORAGE
IT OFFICE
RESET
RESET
RESET
STORAGE
RR
RR
HALL
COATS
HALL
HALL
COACH OFFICE
CAFETERIA
MULTI-PURPOSE
STORAGE
OFFICE
196 OFFICE
OFFICE
JANITOR
199 OFFICE
OFFICE
HALL
HALL
CLEAR / MEETING
CLASSROOM 4
CLASSROOM 5
RESET
RESET
RESET
HALL
HALL
STORAGE
CLASSROOM 6
HALL
EXIST RR
ELEC
OFFICE
109 WORKROOM
AUD STOR
111A
AUDIOLOGY
STORAGE
109A
STORAGE
HALL
RESET
FIRE
LOBBY
FE
C
FEC
FEC
FE
FEC
FEC
FE
CPT-1
CPT-1
T-1
FRP-1
FRP-1
FRP-1
FRP-1
LVT-1
RB-1
T-1
FRP-1
RB-1
CPT-1
RB-1
RB-1
LVT-1
RB-1
LVT-1
CPT-1
RB-1
CPT-1
RB-1
CPT-1
RB-1
CPT-1
RB-1
LVT-1
RB-1
P-1
RB-1
P-1
EXIST
RB-1RB-1
RB-1
LVT-1
RB-1
LVT-1
LVT-1 LVT-1
LVT-1
LVT-1
EXIST EXIST
EXIST
3 7' -6
6'-0"
LVT-1 RB-1 LVT-1 RB-1
WO-1
P-1
P-2
RB-2
LVT-1
RB-2
LVT-1
LVT-1
LVT-1RB-1LVT-1
LVT-1
P-1
P-1
P-1
EXISTEXIST
LVT-1
LVT-1LVT-1
1 1 1
4 4 4
3 3
3 3
P-2
3P-2
3 3
EXIST
A-701
TYP
P-2
LVT-2
LVT-2
LVT-2
LVT-2LVT-2
LVT-2
LVT-2
5'-0"
LVT-2
LVT-2
LVT-2
LVT-2LVT-1
RB-1
LVT-2
LVT-2
LVT-2
FINISH LEGEND
ITEM CODE MATERIAL TYPE MANUFACTURER STYLE/COLOR NOTES
ACT-1 ACOUSTIC CEILING TILE
FL
O
O R
IN
G
CPT-1 CARPET TILE MANNINGTON PHILADELPHIA LAURELHURST INSTALLATION: VERTICAL ASHLAR
WO-1 WALK OFF MAT INTERFACE STEP RETREAT SR699 - MIDNIGHT INSTALLATION: QUARTER TURN
T-4 PORCELAIN TILE ARIZONA TILE 12X24 ANTHEA EARTH RESTROOMS
LVT-1 LUXURY VINYL TILE TARKETT CONTOUR, RAYS, COLOR: ORE
12"x36" INSTALLATION: VERTICAL ASHLAR
LVT-2 LUXURY VINYL TILE TARKETT CONTOUR, RAYS, COLOR: AZURE
12"x36" INSTALLATION: VERTICAL ASHLAR
RB-1 RUBBER BASE JOHNSONITE CHARCOAL #20 4" RUBBER BASE
RB-1 RUBBER BASE JOHNSONITE CHARCOAL #20 6" RUBBER BASE
C
AS
EW
O
R K
PL-1 PLASTIC LAMINATE WILSONART 4623-00 GRAPHITE NEBULA HORIZONTAL SURFACES
PL-2 PLASTIC LAMINATE LAMINART SILVER ASH 3071- I FINE-GRAIN
FINISH
LOCATION: RECEPTION DESK
VERTICAL SURFACES
PL-3 PLASTIC LAMINATE WILSONART PEWTER VELVET - TRACELESS
LOCATION: CLASSROOM /
WORKROOM UPPER VERTICAL
SURFACES
PL-4 PLASTIC LAMINATE WILSONART SILVER ALCHEMY
LOCATION: CLASSROOM /
WORKROOM LOWER VERTICAL
SURFACES
PL-5 PLASTIC LAMINATE WILSONART D327-60 PEPPERDUST LOCATION: FOOD PREP/KITCHEN -
UPPER VERTICAL SURFACES
PL-6 PLASTIC LAMINATE WILSONART D96-60 SHADOW LOCATION: FOOD PREP/KITCHEN -
LOWER VERTICAL SURFACES
SS-1 SOLID SURFACE CORIAN ASH CONCRETE
SS-2 SOLID SURFACE PENTAL QUARTZ CINZA POLISHED LOCATION: RECEPTION
W
AL
LS
T-1 PORCELAIN TILE ARIZONA TILE DIGITALART BIANCO - 12X24, CUT 6"
HT RESTROOMS
T-2 PORCELAIN TILE ARIZONA TILE DIGITALART BIANCO - 12X24 RESTROOMS
T-3 PORCELAIN TILE ARIZONA TILE DIGITALART BLEND STRAIGHT
STACK WALL TILE BASE
TS-1 TRANSITION SCHLUTER DILEX-AHK, SATIN ANODIZED
ALUMINUM WALL TILE BASE TO FLOOR TILE
TS-2 TRANSITION SCHLUTER SCHIENE, SATIN ANODIZED
ALUMINUM WALL TILE TO PAINT
TS-3 TRANSITION SCHLUTER QUADEC, SATIN ANNODIZED
ALUMINUM OUTSIDE EDGES OF WALL TILE
WDT-1 WOOD TRIM 1X3 - CLEAR COAT
FRP-1 FIBER-REINFORCED
PLASTIC CRANE COMPOSITES WHITE (85) - SMOOTH FINISH FLOOR TO CEILING
WP-1 WALL PROTECTION PANEL INPRO RICOCHET HARMONY- GLADIATOR /
RC-HAR-R308
P-1 PAINT MLLER 0210 HIDDEN COVE - SEMI GLOSS FIELD COLOR
P-2 PAINT MLLER 0508 MIDNIGHT MAGIC - SEMI GLOSS HOLLOW METAL DOORS & FRAMES
P-3 PAINT MILLER 0011 SUGAR DUST - EGGSHELL CEILING
P-4 PAINT MILLER 0507 DEEP LAGOON - SEMI-GLOSS ACCENT WALL
P-5 PAINT MILLER 0210 HIDDEN COVE - EPOXY EPOXY PT @ RR
EDGE REDUCER STRIP
TOP OF SLAB
CARPET
DOOR SWING
DIRECTION
DOOR SWING
DIRECTION
RESILIENT FLOORING
1 CARPET TRANSITION
3" = 1'-0"
GENERAL NOTES
1. PAINT ALL DOOR FRAMES IN AREA OF WORK TO BE PAINTED MILLER - 0508 MIDNIGHT
MAGIC, SEMI-GLOSS, UON.
3. ALL AREAS OF WORK TO GET RUBBER BASE - JOHNSONITE #20 CHARCOAL, 4" COVED,
UON
EXISTING FLOORING TO REMAIN
PATCH EXIST CARPET
PAINT ALL WALLS IN THIS ROOM MILLER PAINT - HIDDEN COVE 0210 - SEMI-GLOSS,
UON.
THIS ROOM TO RECEIVE RB-1 AT NEW WALLS
CONSTRUCTION NOTES
FINISH PLAN LEGEND
DIRECTIONAL FLOORING
INSTALLATION, 3-STEP ASHLAR
FINISH MATERIAL TAGX-X
FLOOR FINISH INSTALL DIRECTION
DIRECTIONAL FLOORING
INSTALLATION, QUARTER TURN
sheet:
of:
copyright c Carlson Veit Junge Architects PC checked by:
drawn by:
dwg file:
project:
date:
revisions:
pr oj ec t:
co ns ul ta nt s:
02-20-2023 03022 A-701-X-03022
KC
MJ
FINISH PLAN
A-701
W
IL
LA
M
ET
TE
E D
U C
AT
IO
N S
ER
VI
C E
D
IS
TR
IC
T
YA
M H
IL
L
C
EN
TE
R
R
EM
O D
EL
S
W H
IG
H
W
AY
M C
M
IN
N
VI
LL
E, O R
03-09-23
ADDENDUM #2
FINISH PLAN
1/8" = 1'-0"
AutoCAD SHX Text I
AutoCAD SHX Text H
AutoCAD SHX Text R
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text R
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text
SALEM, OREGON
AutoCAD SHX Text
ANGELA M. FLORES
AutoCAD SHX Text I
AutoCAD SHX Text G
RACI ENGINEERING
MECHANICAL,
CONTROLS, AND
PLUMBING DESIGN
raci-engineering.com
C
D
S
E T sheet:
of:
copyright c
Carlson Veit Junge Architects PC checked by:
drawn by:
dwg file:
project:
date:
revisions:
p r o j e c t c o n s u l t a n t s
02/20/2023
YD
AW
W I L
L A
M E
T T
E
E
D U
C A
T I O
N
S
E R
V I C
E
D
I S
T R
I C
T
Y A
M H
I L
L
C
E N
T E
R
R
E M
O D
E L
S
W
H
I G
H W
Y
M C
M I N
N V
I L L E
O
R
ARCH E1 42x30
WILLAMETTE EDUCATION SERVICE DISTRICT
YAMHILL CENTER REMODEL
MECHANICAL AND PLUMBING
GENERAL:
THE WORK UNDER THIS CONTRACT IS TO REZONE THE AIR DISTRIBUTION SYSTEMS SERVING THE
REMODEL AREAS. CONTRACTOR WILL DEMO AND REPLACE DUCTING, DIFFUSERS, AND GRILLES.
CONTRACTOR WILL DEMO, REPLACE, AND ADD VVT TERMINAL AIR VOLUME BOXES. CONTRACTOR
WILL ADD PROLON VVT CONTROLS FOR TWO EXISTING ROOFTOP AIRHANDLERS THAT DO NOT
CURRENTLY HAVE PROLON CONTROLS. CONTRACTOR WILL REPLACE ALL EXISTING ROOF
MOUNTED EXHAUST FANS AND ADD TWO NEW ROOF MOUNTED EXHAUST FANS. CONTRACTOR WILL
PROVIDE AND INSTALL A DUCTLESS SPLIT SYSTEM FOR SEVER ROOM COOLING. CONDENSING UNIT
WILL BE MOUNTED ON A CONTRACTOR PROVIDED ROOF CURB. CONTRACTOR WILL PROVIDE AND
INSTALL A NEW DRYER EXHAUST SYSTEM WHICH TERMINATES ABOVE ROOF. CONTRACTOR WILL
PROVIDE AND INSTALL PLUMBING AND FIXTURES FOR A NEW RESTROOM AND A REMODELED
RESTROOM. CONTRACTOR WILL PROVIDE AND INSTALL A NEW DRINKING FOUNTAIN. CONTRACTOR
WILL PROVIDE AND INSTALL A WALL MOUNTED WASHER BOX. CONTRACTOR WILL PROVIDE AN
INSTALL A KITCHEN SINK. CONTRACTOR WILL PROVIDE AN INSTALL A JANITOR UTILITY SINK.
CONTRACTOR WILL PROVIDE AND INSTALL A RESIDENTIAL STYLE RANGE EXHAUST HOOD.
THE WORK UNDER THIS CONTRACT IS TO PROVIDE THE LABOR, MATERIAL, AND EQUIPMENT FOR
THE COMPLETE INSTALLATION OF THE HVAC, AND PLUMBING SYSTEMS DESCRIBED. CONTRACTOR
IS RESPONSIBLE FOR INCIDENTAL MATERIALS, EQUIPMENT, INSTALLATION, STARTUP, TESTING, BALANCING, AND OPERATIONAL CHECKOUT FOR A FULLY FUNCTIONAL SYSTEM.
THE DRAWINGS AND WORK SCOPE ARE NOT INTENDED TO BE COMPREHENSIVE OF ALL WORK TO BE
DONE UNDER THIS CONTRACT. SPECIFICATIONS, DRAWINGS, AND WORK SCOPE MUST BE USED IN
THEIR ENTIRETY TO DEVELOP FULL UNDERSTANDING OF THE WORK TO BE DONE UNDER THIS
CONTRACT.
EXISTING FACILITIES ARE DRAWN AS ACCURATELY AS CAN BE DETERMINED FROM EXISTING
DRAWINGS AND ON-SITE INSPECTIONS. CONTRACTOR IS RESPONSIBLE FOR VERIFYING EXISTING
CONDITIONS. EXISTING CONDITIONS MAY REQUIRE FIELD ADJUSTMENT OF DESIGN AS SHOWN ON
THE CONSTRUCTION DOCUMENTS. CONTRACTOR SHALL CONFIRM UTILITY CONNECTION POINTS
AND STRUCTURAL OBSTRUCTIONS. CONTRACTOR WILL NOT BE REIMBURSED FOR UNANTICIPATED
WORK REQUIRED TO PROVIDE A FULLY FUNCTIONAL SYSTEM.
MINOR MODIFICATIONS TO DUCT PROFILE AND ROUTE ARE EXPECTED AND MAY BE MADE AT THE
CONTRACTORS OPTION WITHOUT APPROVAL. MAINTAIN AS-BUILT DRAWINGS OF DUCTING AS
INSTALLED.
WHERE SIGNIFICANT MODIFICATIONS TO THE DESIGN, AS DEPICTED ON THE CONSTRUCTION
DOCUMENTS, ARE REQUIRED, THE CONTRACTOR SHALL NOTIFY THE ARCHITECT AND ENGINEER OF
THE ISSUE AND ANY PROPOSED SOLUTION BEFORE PROCEEDING. EXAMPLES OF SIGNIFICANT
MODIFICATIONS INCLUDE SIGNIFICANT INCREASES IN DUCT LENGTH, DECREASE IN DUCT FREE
AREA, HIGH ASPECT DUCTING, NON SMACMA FITTINGS, A SIGNIFICANT ADDITIONAL NUMBER OF
DUCT ELBOWS, SIGNIFICANT CHANGES TO EQUIPMENT LOCATIONS AND ORIENTATIONS.
CONTRACTOR WILL NOT BE REIMBURSED FOR FIELD MODIFICATION THAT WERE NOT APPROVED BY
THE ARCHITECT AND ENGINEER PRIOR TO PURCHASING OR INSTALLING MATERIALS OR EQUIPMENT.
DEMO:
PROTECT ROOFTOP AHUS, VVT TERMINAL BOXES, AND DUCTING FROM DEMO DIRT, DUST, AND
DEBRIS. CAP DUCTING AND BAG EQUIPMENT FOR PROTECTION. MAINTAIN PROTECTIVE MEASURES
THROUGH CONSTRUCTION.
REMOVE AND PROPERLY DISPOSE OF DUCTING, DIFFUSER, GRILLES, VVT TERMINAL BOXES, AND
ROOFTOP EXHAUST FANS AS DESIGNATED ON THE DEMO FLOOR PLAN AND CALLED OUT IN
EQUIPMENT SCHEDULES.
CONTRACTOR SHALL ONLY DEMO DUCTING CALLED OUT FOR REMOVAL OR REPLACEMENT.
REPLACEMENT OF DUCTING NOT CALLED OUT FOR DEMO WILL BE REPLACED AT CONTRACTORS
EXPENSE.
CONTRACTOR SHALL NOTIFY ENGINEER AND ARCHITECT IF ANY REMAINING DUCTING OR
EQUIPMENT ARE DAMAGED OR IN POOR CONDITION REQUIRING REMEDIATION BEFORE START OF
CONSTRUCTION.
CONTRACTOR SHALL PROTECT PROLON TERMINAL BOX CONTROLS AND PROLON WALL SPACE
TEMPERATURE SENSORS FOR REUSE AND TURN OVER ANY UNUSED PROLON CONTROLS TO THE
OWNER FOR SPARES.
MECHANICAL:
DUCTING DESIGN IS SCHEMATIC. EXISTING EQUIPMENT AND DUCTING LOCATIONS WERE TAKEN
FROM ORIGINAL DESIGN DOCUMENTS, WHICH MAY NOT BE ACCURATE. AS SHOWN ON DRAWINGS,
EQUIPMENT LOCATIONS AND DUCT ROUTES DO NOT ACCOUNT FOR SEISMIC SHEAR WALLS,
TRUSSING OBSTRUCTIONS OR OBSTRUCTIONS DUE TO, PLUMBING SYSTEMS, EXISTING ELECTRIC
CONDUIT, SPRINKLER LINES, SPRINKLER HEADS, LIGHTING, AND EXISTING LOW VOLTAGE WIRE.
CONTRACTOR IS RESPONSIBLE FOR LOCATING EQUIPMENT AND ROUTING DUCTING TO AVOID
OBSTRUCTIONS AND, WHERE NECESSARY, CONTRACTOR IS RESPONSIBLE FOR MOVING WIRE AND
CONDUIT; FRAMING OPENINGS IN WALLS AND ROOFS; MOVING AND ADDING SPRINKLER HEADS; AND
MOVING LIGHTING. CONTRACTOR IS RESPONSIBLE FOR STRUCTURAL AND SEISMIC DESIGN OF
EQUIPMENT SUPPORTS INCLUDING ROOF CURBS AND SHEAR WALL PENETRATIONS.
CONTRACTOR SHALL MAINTAIN DUCT FREE AREA AND USE SMACNA FITTINGS WHEREVER POSSIBLE.
RIGHT ANGLE LATERAL BRANCHES SHALL USE BOOT T FITTINGS. BRANCH FITTINGS AT OTHER
ANGLES SHALL USE 45 DEGREE FITTINGS. USE 90 DEGREE FITTINGS WITH TURNING VANES OR PAIR
OF PANTS FITTING INSTEAD OF BULL NOSE TS. WHERE SMACNA FITTINGS CANNOT BE USED, THE
CONTRACTOR SHALL PROVIDE SCALE DIMENSIONED SHOP DRAWINGS OF THE INTENDED DESIGN
FOR APPROVAL BY THE ENGINEER PRIOR TO CONSTRUCTION. CONTRACTOR IS FREE TO ADJUST
DUCTING ROUTE AND PROFILE AS NECESSARY FOR SUCCESSFUL DUCT INSTALLATION. INSTALL
BALANCE DAMPERS AS REQUIRED FOR SYSTEM BALANCE. LOCATE BALANCE DAMPERS WHERE
ACCESSIBLE TO BALANCER OR INSTALL REMOTE OPERATOR.
CONTRACTOR SHALL KEEP AS-BUILT DRAWINGS OF ACTUAL DUCT SIZE, DUCT ROUTE, AND
EQUIPMENT LOCATIONS.
EXISTING DUCTING TO REMAIN HAS NOT BEEN FIELD VERIFIED. CONTRACTOR IS RESPONSIBLE FOR
CONFIRMING EXISTING DUCTING PRIOR TO BID AND SHALL PROVIDE NEW DUCTING WHERE EXISTING
DUCTING IS MISSING, IN POOR CONDITION, OR UNDERSIZED. PROVIDE AND INSTALL NEW BALANCE
DAMPERS ON ANY OUTLET OR INLET BRANCH THAT REQUIRES BALANCING BUT NOT EQUIPPED WITH
A BALANCE DAMPER. IN REMODEL AREAS, CONTRACTOR SHALL REPLACE EXISTING FLEXIBLE DUCT
RUNS OF MORE THAN 8 FEET OR MORE THAN 135° TOTAL BEND ANGLE WITH HARD DUCTING AND
FLEX DUCTING NOT LONGER THAN 4' HAVING A TOTAL BEND ANGLE OF NOT MORE THAN 90°.
THE MAXIMUM SUPPLY OR RETURN FLEX DUCT LENGTH SHALL BE LIMITED TO 4' AND HAVE A
MAXIMUM TOTAL BEND ANGLE OF 90°. WHERE SPACE ALLOWS, FLEX DUCT SHALL NOT ATTACH
DIRECTLY TO SUPPLY OR RETURN DIFFUSERS. FLEX DUCT LONGER THAN 2' SHALL HAVE AN
INTERMEDIATE WEBBING SUPPORT TO PREVENT SAGGING.
CONTRACTOR SHALL CLEAN, REPAIR, AND SEAL ANY REUSED EXISTING DUCTING SERVING
REMODEL SPACES. DUCT CLEANING AND REPAIR IS REQUIRED FOR PART OR ALL OF THE AHU-3, 8, 9, 10, 11, 12, 13, AND 14 SUPPLY AND RETURN DUCTING SYSTEMS. DUCT CLEANING AND REPAIR IS NOT
REQUIRED FOR OTHER SYSTEMS. FOR AHU-3, 8, 9, 10, 11, 12, 13, AND 14, DUCT CLEANING IS
REQUIRED FOR THE DUCTING PATH FROM THE AHU TO EACH NEW SUPPLY DIFFUSER AND EACH
NEW RETURN GRILLE.