This is a combined synopsis and solicitation for cooling tower installations at two buildings on Aberdeen Proving Ground in Maryland. The solicitation seeks firm fixed price proposals to deliver and install four cooling towers at Building 385 by October 2021 and December 2021, and to deliver and install two cooling towers at Building 384F by October 2021 and November 2021. Proposals are due by April 1, 2021 and award will be made to the lowest price technically acceptable offeror. The solicitation is issued by the Army Contracting Command and provides the statement of work, drawings, response instructions and applicable FAR clauses. Products and services required include delivery and installation of cooling towers, associated piping and equipment.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Combined Synopsis Solicitation
W91ZLK-21-R-0010
Questions and Answers
Q. The Solicitation drawings for Building 384F are showing additional work over/above the “Closed
Circuit Cooler” system. This work entails gas fired unit heaters/associated gas/flue piping and controls. It also shows ventilation upgrades in exhaust fans/ intake louvers/ controls for same. It shows a Gas Leak
Detection system as well as some compressed air piping. Is this aforementioned work to be part of this
Solicitation?
A. No, only the closed circuit cooler system and piping is part of the solicitation.
Q. At Bldg 384F is the new 4” underground sanitary and associated floor drains etc. to be part of this
Solicitation?
A. Sanitary drains are not part of the solicitation. They have been installed by facility contractor.
Q. Can we set up for site visit to Bldg 384F?
A. Yes, if this is appropriate for the solicitation we can host a site visit.
Q. At Building 385 are we to include “pipe support staunchions” for the “stacked 12”/10” glycol piping or will they be provided by others?
A. Yes/No, the only supports provided by Government will be the 24 stands placed between the hydraulic pumping units. Vendor will need supply supports for glycol piping at other locations.
Q. Prior pricing efforts had this/these projects Tax Exempt. Are these projects Tax Exempt?
A. Yes, EXEMPTION CERTIFICATE FROM MARYLAND RETAIL SALES AND USE TAX (Oct 2012)
Exemption certificate No. 30005004 covers exemption from Maryland Retail sales and Use tax.
No, only the closed circuit cooler system and piping is part of the solicitation.
Sanitary drains are not part of the solicitation. They have been installed by facility contractor.
Yes, if this is appropriate for the solicitation we can host a site visit.
Yes/No, the only supports provided by Government will be the 24 stands placed between the hydraulic pumping units. Vendor will need supply supports for glycol piping at other locations
5. I believe yes, but Lesha can you confirm.