This is a combined synopsis and solicitation for cooling tower installation services. The U.S. Army Contracting Command at Aberdeen Proving Ground is seeking proposals for the delivery, installation, and integration of two cooling towers at Building 384F and 385 on Aberdeen Test Center in Aberdeen Proving Grounds, Maryland. Offerors must provide firm-fixed pricing for delivery and initial placement of the B385 tower within four months of award and installation completion within six months, and delivery and initial placement of the B384F tower within six months of award and installation completion within seven months. The period of performance is from May 15, 2021 to March 15, 2022. Proposals are due by April 1, 2021 and will be evaluated based on technical acceptability with the lowest price receiving award. The contractor will be responsible for all labor, equipment, and materials to install the cooling tower systems according to the performance work statement except for government furnished property and services.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
(1) ATWB 9-3I8-Z
Project Details
Project Name : APG Bldg 384F Location: TBD
Date: 2/12/2020 Customer:
Contact:
Contact Email:
Product Description The ATWB is a prime-surface steel coil only closed circuit cooler, featuring CrossCool™ Internal Tube Enhancement, designed around EVAPCO’s induced draft Advanced Technology (AT) tower. The ATWB line offers the most box size configurations in the industry while also providing nominal dry cooling capacity at reduced loads. This is not true for most evaporative closed circuit coolers in the industry! The ATWB is a maintenance friendly product, designed for all routine maintenance to be performed from outside the unit.
Selection Criteria Total Each Unit
Flow: 145.0 GPM 145.0 GPM
Fluid:
30%
Propylene Glycol
30% Propylene
Glycol Entering Fluid Temp: 95.0 F 95.0 F Leaving Fluid Temp: 85.0 F 85.0 F Entering Wet Bulb: 78.0 F 78.0 F
Required Capacity
689.77 MBH
45.98 Tons
Entering Dry Bulb Switchover: 31.9 F
Unit Selected One(1) EVAPCO ATWB 9-3I8-Z at 100.5% capacity (693.15 MBH) Product line is CTI/ECC certified for water, propylene glycol or ethylene glycol as process fluid. Selection is rated in accordance with CTI Standard 201 RS.
Physical Data Per Unit Overall Dimensions (WxLxH): 7'-5 7/8" x 8'-5 1/2" x 12'-1/4" Operating Weight: 10,400 lbs Shipping Weight: 6,980 lbs Heaviest Section: 5,680 lbs *weights and dimensions could vary depending on options selected
IBC Design Capability IBC Standard Structural Design
1.0 Importance Factor Specified
Seismic(Sᴅs): up to 1.6 g, z/h = 0 Wind Load(P): up to 288 psf
Fan Motor Data per Unit Number of Fans: 1 # of Fan Motors: 1 Nameplate Power (460/3/60): 10.00 HP Per Motor Typical Nameplate FLA: 12.4 Amps Per Motor *Nameplate FLA could vary
Pump Motor Data per Unit No.of Pumps: 1 Nameplate Power (460/3/60): 2 HP per pump motor Typical Nameplate FLA: 2.69 Amps Per Motor *Nameplate FLA could vary
Additional Details Per Unit Air Flow: 36,580 CFM Coil Volume: 144.1 gal per unit Coil Design Pressure: 250 psi Riser Pipe Diameter: 4"
Hydraulic Data Pressure Drop Through Coil: 2.3 psi Evaporated Water Rate: 1.10 GPM Spray Water Flow: 340 GPM
Layout Criteria From FACE B/D to wall: 3.00ft From FACE A/C to wall: 3.00ft Between FACE B/D ends: 6.00ft Between FACE A/C sides: 6.00ft
Sound Data(dB(A) @ 5'/50') Face A (Opp Mtr. Side): -∞/-∞ Face C (Motor Side): -∞/-∞ Face B (End): -∞/-∞ Face D (Opp End): -∞/-∞ Top: -∞/-∞ Notes: Sound Pressure Levels are according to CTI Standard ATC-128 and verified by an independent CTI-licensed sound test agency. Sound data is shown for 1 cell operating at full speed. The use of frequency inverters (Variable Frequency Drives) can increase sound levels. Sound Options: Super Low Sound Fan
Shipping Data 1 Basin Sections: (WxLxH): 101" x 101" x 53" ; 1300lbs each* | 1 Casing Sections: (WxLxH): 101" x 101" x 86" ; 5680lbs each* *dimensions and weights above include shipping skids
Closed Circuit Cooler Technical Data Sheet Chris Delp 425 McFarlan Road Suite 209 Kennett Square, Pennsylvania 19348
610-554-8863 chrisd@etshvac.com
Spectrum Version: 2.2020.130.2 February 12, 2020Page 1 of 15
Accessories
(1) IBC Standard Structural Design (1) 1.0 Importance Factor Specified (1) 304 Welded Stainless Steel Cold Water Basin
(1) CrossCool Coil (1) 5-Probe Electronic Water Level Control Package (1) Vibration Switch
(1) External Service Platform with Ladder (1) Safety Cage (1) Motor Davit with Base
(1) El. Heaters (0F / -18C ambient) (1) 6 kW;
460/3/60 (1) Smart Shield Package (FMF-6-4, BCF-10) (1) Smart Shield Startup and Service; 12 Months; 4.00
COC; 1 Boxes of biocide; 2 Box ET; IIL 1; IOL 1
(1) Fan Motor: Inverter Capable, Premium Efficient (1) Super Low Sound Fan (1) Fan Motor: Space Heaters
(1) Series Flow Operation (1) Corrosion Coupon Rack (1) Ethernet
Spectrum Version: 2.2020.130.2 February 12, 2020Page 2 of 15
REV.
NO. OF SHIPPING SECTIONSHEAVIEST SECTION
WEIGHT
UNIT
SCALE
DWG. #
SERIAL #MODEL #
SHIPPING
WEIGHT
DATE
DRAWN BY:OPERATING
WEIGHT
7'-5 7/8"
12'-1/4"
4'-1/4"
8'-0"
8'-5 1/2"
3" [80] MPT
OVERFLOW
2" [50] MPT
DRAIN
2" [50] MPT
MAKE-UP
4 1/4"
5 1/4"
5'-1 1/2"
1'-9 3/8"
6" 154 *
1'-10 1/8" 562 *3'-9 1/4"
1149 *
1'-11 1/8"
3"
1'-1 3/4"
ACCESS DOOR
1'-3"
2'-5 7/8"
NOTES:
1. (M)- FAN MOTOR LOCATION
2. HEAVIEST SECTION IS UPPER SECTION
3. MPT DENOTES MALE PIPE THREAD
FPT DENOTES FEMALE PIPE THREAD
BFW DENOTES BEVELED FOR WELDING
GVD DENOTES GROOVED
FLG DENOTES FLANGE
PE DENOTES PLAIN END
4. +UNIT WEIGHT DOES NOT INCLUDE
ACCESSORIES (SEE ACCESSORY DRAWINGS)
5. MAKE-UP WATER PRESSURE
20 psi MIN [137 kPa], 50 psi MAX [344 kPa]
6. *-APPROXIMATE DIMENSIONS DO NOT USE
FOR PRE-FABRICATION OF CONNECTING
PIPING
7. SERIES FLOW PIPING AND AUX. CROSSOVER
DRAIN BY OTHERS.
8. 3/4" [19MM] DIA. MOUNTING HOLES. REFER TO
RECOMMENDED STEEL SUPPORT DRAWING.
9. DIMENSIONS LISTED AS FOLLOWS:
ENGLISH FT-IN
METRIC [mm]
AUX. CROSSOVER DRAIN
(SEE NOTE 7)
SERIES FLOW PIPING
(SEE NOTE 7)
1'-7 1/2" 495 *
NTS
JLG
FACE AFACE B
FACE A
FACE B
FACE C
FACE D
PLAN VIEW
WB3090806-DRC-SLSFEVAPCO, INC.CLOSED CIRCUIT COOLER
ATWB 9-3I8-Z
2/12/2020
6980 lbs+ [3170] kg+ 10400 lbs+ [4720] kg+ 5680 lbs+ [2580] kg+ 2
(2) 1/2" [15]
FPT VENT
(2) 4" [100] BFW
(2) 4" [100] BFW
FLUID IN
FLUID OUT
Spectrum Version: 2.2020.130.2 February 12, 2020
Preliminary
TITLE
UNIT
SCALE
DWG. #
DRAWN BY
SLAW0908-DE
(8) O 3/4" [19mm]
MOUNTING HOLES
PLAN VIEW
UNIT OUTLINE 7'-5 7/8"
8'-5 1/2"
2"
2" 5113/16"
7'-4 1/4"
C/L OF MOUNTING HOLES
13/16"
2'-11 3/4"
TYPICAL END VIEW
UNIT
MOUNTING HOLE
13/16"
1 5/8"
C/L OF UNIT LOAD
2'-2"
2'-11 3/4"
N.T.S. JLGSTEEL SUPPORT CONFIGURATION
NOTES:
1. BEAMS SHOULD BE SIZED IN ACCORDANCE WITH ACCEPTED STRUCTURAL PRACTICES.
MAXIMUM DEFLECTION OF BEAM UNDER UNIT TO BE 1/360 OF UNIT LENGTH NOT TO
EXCEED 1/2" [13mm].
2. DEFLECTION MAY BE CALCULATED BY USING 55% OF THE OPERATING WEIGHT AS
A UNIFORM LOAD ON EACH BEAM. SEE CERTIFIED PRINT FOR OPERATING WEIGHT.
3. SUPPORT BEAMS AND ANCHOR HARDWARE ARE TO BE FURNISHED BY OTHERS.
ANCHOR HARDWARE TO BE ASTM A325 5/8" [16mm] BOLT OR EQUIVALENT.
4. BEAMS MUST BE LOCATED UNDER THE FULL LENGTH OF THE PAN SECTION.
5. SUPPORTING BEAM SURFACE MUST BE LEVEL. DO NOT LEVEL THE UNIT BY
PLACING SHIMS BETWEEN THE UNIT MOUNTING FLANGE AND THE SUPPORTING BEAM.
6. THE FACTORY RECOMMENDED STEEL SUPPORT CONFIGURATION IS SHOWN.
CONSULT THE FACTORY FOR ALTERNATE SUPPORT CONFIGURATIONS.
7. UNIT SHOULD BE POSITIONED ON STEEL SUCH THAT THE ANCHORING HARDWARE FULLY
PENETRATES THE BEAM'S FLANGE AND CLEARS THE BEAM'S WEB.
8. WHEN VIBRATION ISOLATION IS REQUIRED, THE VIBRATION ISOLATORS (BY OTHERS)
MUST BE LOCATED UNDER THE SUPPORTING BEAMS AND NOT BETWEEN THE SUPPORTING
STEEL BEAMS AND THE UNIT.
9. DIMENSIONS LISTED AS FOLLOWS: ENGLISH FT-IN
[METRIC] [mm]
EVAPCO, INC.ATWB 9-3I8-Z
Spectrum Version: 2.2020.130.2 February 12, 2020
SCALE
DWG. #
DRAWN BY
FAN MOTOR SPACE HEATERS
MHAU0000-DB
N.T.S. BLL
MOTOR
FAN
NOTE:
1. FAN MOTOR SPACE HEATERS SHOULD BE ENERGIZED WHEN MOTOR IS OFF TO PREVENT CONDENSATION IN THE MOTOR
2. FAN MOTOR SPACE HEATERS MUST BE SWITCHED OFF WHEN MOTOR IS RUNNING
L1/H1 L2/H2
HEATER 1
HEATER 2
ELECTRICAL DATA:
VOLTAGE: 120V
CURRENT: <2AMPS
EVAPCO, INC.ATWB 9-3I8-Z
Spectrum Version: 2.2020.130.2 February 12, 2020
SCALE
DWG. #
DRAWN BY
ELAW4MWML-DB
NOTES:
1. PIPING BY OTHERS.
2. LEVEL PROBE STANDPIPE ASSEMBLY, MAKE-UP VALVE AND Y-STRAINER TO SHIP LOOSE FOR FIELD MOUNTING BY OTHERS.
3. SEE CERTIFIED PRINT FOR MAKE-UP LOCATION.
4. STANDPIPE TO BE HEAT TRACED AND INSULATED FOR WINTER OPERATION (BY OTHERS).
5. THE ELECTRONIC WATER LEVEL CONTROL ON THIS UNIT WILL MAINTAIN THE PROPER OPERATING WATER LEVEL.
HOWEVER, BEFORE INITIAL START-UP THE UNIT MUST BE MANUALLY FILLED TO WITHIN 1" OF THE OVERFLOW.
6. FOR EASE OF MAINTENANCE, A SHUT-OFF VALVE IS RECOMMENDED UPSTREAM OF Y-STRAINER.
7. DIMENSIONS LISTED AS FOLLOWS: ENGLISH FT-IN
METRIC [mm]
LEVEL PROBE
STANDPIPE ASSEMBLY
(SEE CHART FOR QTY)
ELECTRIC MAKE-UP
VALVE WITH Y-STRAINER
UPSTREAM OF VALVE
(SEE CHART FOR SIZE & QTY)
CONN. END
X
Y
FACE C
JLGN.T.S.
INDUCED DRAFT CONDENSER/COOLER
ELECTRIC WATER LEVEL CONTROL LOCATION
QTY SIZE PART NO. QTY SIZE PART NO. QTY X Y
8.5x7.5 1 1" [25]
017-00153P 1 1" [25]
017-00280P 1 3' [914]
11" [279]
8.5,2.4M,7x9 8.5,2.4Mx10.5
1 1" [25]
017-00153P 1 1" [25]
017-00280P 1 3'-9 3/4" [1162]
11" [279]
8.5,2.4M,7x12 1 1" [25]
017-00153P 1 1" [25]
017-00280P 1 4'-7 1/2" [1410]
11" [279]
8.5,2.4Mx14 1 1 1/2" [40]
017-00154P 1 1 1/2" [40]
017-00281P 1 5'-6" [1676]
11" [279]
8.5,2.4M,7x18 1 1 1/2" [40]
017-00154P 1 1 1/2" [40]
017-00281P 1 8' [2438]
11" [279]
8.5,2.4Mx21 1 1 1/2" [40]
017-00154P 1 1 1/2" [40]
017-00281P 1 8'-9 3/4" [2686]
11" [279]
8.5,2.4M,7x24 2 1" [25]
017-00153P 2 1" [25]
017-00280P 1 4'-7 1/2" [1410]
11" [279]
8.5,2.4Mx28 2 1 1/2" [40]
017-00154P 2 1 1/2" [40]
017-00281P 1 5'-6" [1676]
11" [279]
2.4M,7x36 2 1 1/2" [40]
017-00154P 2 1 1/2" [40]
017-00281P 1 8' [2438]
11" [279]
2.4Mx42 2 1 1/2" [40]
017-00154P 2 1 1/2" [40]
017-00281P 1 8'-2 1/2" [2502]
11" [279]
12,3Mx12 1 1 1/2" [40]
017-00154P 1 1 1/2" [40]
017-00281P 1 9'-5" [2870]
11" [279]
12x14 1 1 1/2" [40]
017-00154P 1 1 1/2" [40]
017-00281P 1 4'-4" [1320]
11" [279]
12,3Mx18 1 2" [50]
017-00155P 1 2" [50]
017-00282P 1 6'-10" [2083]
11" [279]
12x20 1 2" [50]
017-00155P 1 2" [50]
017-00282P 1 7'-6" [2286]
11" [279]
12,3Mx24 2 1 1/2" [40]
017-00154P 2 1 1/2" [40]
017-00281P 1 9'-4" [2845]
11" [279]
12x28 2 1 1/2" [40]
017-00154P 2 1 1/2" [40]
017-00281P 1 16'-4" [4978]
11" [279]
12,3Mx36 2 2" [50]
017-00155P 2 2" [50]
017-00282P 1 6'-10" [2083]
11" [279]
12x40 2 2" [50]
017-00155P 2 2" [50]
017-00282P 1 7'-6" [2286]
11" [279]
UNIT
SELECTED BOX SIZE
VALVE Y-STRAINER STANDPIPE
EVAPCO, INC.
Spectrum Version: 2.2020.130.2 February 12, 2020
SCALE
DWG. #
DRAWN BY
MODEL # H FT-IN H [mm] eco-ATC 122A, 138A, 152A, 162A 5'-4 3/8 " [1635] eco-ATWB/eco-ATWB-E/ATWB-9-3G8, 3H8, 3I8, 3J8
ATW-64-3H, 3I
eco-ATC 168A, 186A, 198A eco-ATWB/eco-ATWB-E/ATWB-9-4G8, 4H8, 4I8, 4J8
ATW-64-4H, 4I
ATC-170E, 187E, 199E
eco-ATC 191A, 210A, 223A eco-ATWB/eco-ATWB-E/ATWB-9-5H8, 5I8, 5J8
ATW-64-5I, 5J
ATC-221E, 238E, 188E
eco-ATC 180A, 203A, 238A, 257A eco-ATWB/eco-ATWB-E/ATWB-9-6H8, 6I8, 6J8
ATW-64-6I, 6J
ATC-247E, 195E
eco-ATC 229A, 243A, 263A
ATWB-9-7H8, 7I8, 7J8 8'-4 1/8 " [2543]
5'-10 7/8 "
6'-7 3/8 "
7'-2 7/8 "
7'-10 3/8 "
[1825]
[2016]
[2207]
[2397]
FACE CFACE D
NOTES:
1. LADDER AND PLATFORM SHIP LOOSE. FIELD INSTALLATION BY OTHERS IS REQUIRED.
2. THE BOTTOM OF THE LADDER DOES NOT EXTEND PAST THE BASE OF THE UNIT.
IF THE UNIT IS ELEVATED THEN AN OPTIONAL EXTENDED LADDER PACKAGE
SHOULD BE CONSIDERED. (CONSULT FACTORY)
3. REFER TO RIGGING PACK FOR LADDER AND PLATFORM MOUNTING INSTRUCTIONS.
4. EACH PLATFORM AND LADDER ASSY. WEIGHS 580 LBS. [263KG]
5. FOR STANDARD UNITS, REFER TO UNIT CERTIFIED PRINT FOR PUMP LOCATION(S).
6. DIMENSIONS LISTED AS FOLLOWS: ENGLISH FT-IN
METRIC [mm]
H
3'-5"
5 3/8"
4 1/8"
7'-4 7/8"
EXTERNAL SERVICE PLATFORM
PLAW30908-DH
N.T.S. JLGEVAPCO, INC.ATWB 9-3I8-Z
Spectrum Version: 2.2020.130.2 February 12, 2020
SCALE
DWG. #
DRAWN BY HEATER LOCATION
HLAW09ST-DC
LWCO
017-00207PA
BULB WELL
017-00006P
LWCO COVER PLATE
(INSIDE UNIT)
THERMOSTAT
017-00005P
HEATER CONTROL PANEL
(OPTIONAL, SEE WIRING DIAGRAM)
IMMERSION
HEATER
2'-4 1/8"
6"
10 1/2"
9 3/4"
FACE D
JLGN.T.S.
NOTES:
OUTLET BOX AND THE NEAREST OBSTRUCTION FOR REMOVAL OF THE HEATER.
ALL NIPPLES ON UNIT ARE NOT SHOWN IN ORDER TO CLARIFY
ALL HEATER COMPONENTS BY EVAPCO ARE FACTORY MOUNTED WHEN POSSIBLE.
DIMENSIONS LISTED AS FOLLOWS: ENGLISH FT- IN
HEATER COMPONENT LOCATIONS.
A MINIMUM OF CLEARANCE IS REQUIRED BETWEEN THE HEATER
2.
4.
3.
1.
[METRIC] [mm]
3'-10"
4'-4"
EVAPCO, INC.ATWB 9-3I8-Z
Spectrum Version: 2.2020.130.2 February 12, 2020
SCALE
DWG. #
DRAWN BYN.T.S.SMART SHIELD ENGINEERING DATA
SS3AU0000-DC
MBG
FMF
H
W
BCF-10 BCF-20
H
W D
H
W D
D
D W H
FMF-6-3 1'-7" [480] 1'-1" [330] 3'-7" [1090] 44 [20] 111 [50] 3/4 [20]
FMF-6-4 1'-7" [480] 1'-2" [360] 3'-7" [1090] 49 [22] 116 [53] 3/4 [20]
FMF-10-6 1'-7" [480] 1'-4" [405] 4'-1" [1240] 75 [34] 165 [75] 3/4 [20]
FMF-10-8 1'-7" [480] 1'-6" [460] 4'-3" [1290] 95 [43] 185 [84] 1 [25]
BCF-10 1'-5" [430] 9" [230] 1' [305] 30 [14] 34 [15] NA
BCF-20 1'-5" [430] 2'-1" [630] 1' [305] 60 [27] 69 [31] NA
Smart Shield Component
Dimensions ft-in [mm]
FMF
Shipping Weight lb [kg]
Operating Weight lb [kg]
Blow Down Valve Size in [mm]
BCF
NOTES:
1. UNITS ARE DESIGNED FOR A MAXIMUM WATER TEMPERATURE OF 130°F [50°C]
2. THE FMF AND BCF MUST HAVE UNOBSTRUCTED RETURN PIPING TO BASIN.
3. DIMENSIONS ARE APPROXIMATE. DO NOT USE FOR PRE-FABRICATION OF PIPING.
EVAPCO, INC.ATWB 9-3I8-Z
Spectrum Version: 2.2020.130.2 February 12, 2020
SCALE
DWG. #
DRAWN BYN.T.S.SMART SHIELD/
CONDUCTIVITY WIRING DIAGRAM
SS1AU0000-DE
CAF
120/230 VOLT PANEL FACTORY WIRED
NOTES:
1. DASHED LINES INDICATE WIRING BY OTHERS.
2. INSTALLATION SHOULD COMPLY WITH NATIONAL, STATE, AND LOCAL CODES.
3. WIRE SECONDARY CONTACT FROM PUMP STARTER TO DIGITAL INPUT IN ORDER TO RECORD PUMP OPERATIONAL HOURS.
4. UNITS ARE STANDARD WITH NEMA 4X (EQUIVALENT TO IP65) ENCLOSURE. CE AND ETL LISTED, MEETING UL AND cUL SPECIFICATIONS.
4-20 mA
ANALOG
OUTPUT #2
(OPTIONAL)
SHIELD
TB2
4-20 mA
ANALOG
OUTPUT #1
(OPTIONAL)
SHIELD
H20 METER #2
(OPTIONAL)
POLARITY NOT CRITICAL
NEUTRAL
GROUND 6
W
HT
V
BL
U
0V
TB5
FLOW SW
POLARITY NOT CRITICAL
TB3
GR
N
0V
GR
N/
YE
L
0V
BLK 120V
BRN 240V
WHT 120V
BLU 240V
TB4
POWER
SUPPLY
N L
TB7
NC
NO
BLOWDOWN VALVE
R1
XMT + WHT
XMT - BLK
RCV - BLK
RCV + RED
X-SHLD (SHIELD)
TEMP - BLK
TEMP + GRN
R-SHLD (SHIELD)
CONDUCTIVITY
PROBE
TB1
H20 METER #1
(OPTIONAL)
POLARITY NOT CRITICAL
PANEL VIEW
RIBBON
CABLE
ETHERNET
(OPTIONAL)
4-20 mA
ANALOG
OUTPUT #1
(OPTIONAL)
CONDUCTIVITY
SENSOR CARD
LOCAL
AREA
NETWORK
(LAN)
RJ45 CONNECTOR
CA
T5
CA
BL
E
NC
NOR2
NC
NOR3
NC
NOR4
BL
K
V
BR
N
0V
DOOR VIEW
EVAPCO CONDUCTIVITY CONTROLLER 2
EVAPCO, INC.ATWB 9-3I8-Z
Spectrum Version: 2.2020.130.2 February 12, 2020
SCALE
DWG. #
DRAWN BY
NOTES:
SSAW09SU-DRC-ST
FACE B
PSJN.T.S.
FACTORY MOUNTED
FEEDER (FMF)
(SHIPS LOOSE
FOR FIELD
INSTALLATION)
EVAPCO
CONDUCTIVITY
CONTROLLER
BIO CONTROL
FEEDER (BCF)
CONDUCTIVITY
PROBE
BLOWDOWN VALVE
W/ WEATHER SHIELD
ISOLATION VALVE SHIPS LOOSE.
FIELD CONNECTION REQUIRED OVERFLOW AND BLOWDOWN CONNECTION,
SEE NOTE 3
FIELD CONNECTION TO DRAIN REQUIRED
1. BIO CONTROL FEEDER MAY EXTEND THE OVERALL LENGTH OF THE UNIT
BY UP TO 1' [305mm].
2. COIL CONNECTIONS NOT SHOWN FOR CLARITY.
3. REFER TO SMART SHIELD IOM FOR PROPER DRAIN CONNECTION.
4. ALL PVC RETURN CONNECTIONS INTO UNIT REQUIRE FIELD HAND TIGHTENING.
5. ALL PVC UNIONS REQUIRE FIELD HAND TIGHTENING.
6. PROVIDE 30" OF ACCESS IN FRONT OF SMART SHIELD FEEDERS AND CONTROL
EQUIPMENT FOR MAINTENANCE AND PRODUCT REPLENISHMENT.
7. THE INSTALLATION OF WATER TREATMENT EQUIPMENT MAY RESTRICT THE
REMOVAL OF AIR INLET LOUVERS.
SMART SHIELD ARRANGEMENT
FACE A
SEE NOTE 1
SEE NOTE 6
EVAPCO, INC.ATWB 9-3I8-Z
Spectrum Version: 2.2020.130.2 February 12, 2020
SCALE
DWG. #
DRAWN BY
A
A
FMF
VIEW A-A
CROSSOVER PIPING
(BY OTHERS)
FLUID OUT
FLUID IN
XPSAU0000-DRB-ST
6" [150] MINIMUM
*SEE NOTE 4
NOTES:
1. THIS DRAWING IS INTENDED TO PROVIDE CROSSOVER GUIDELINES ONLY.
2. FOR PIPE MATERIAL, REFERENCE BID SPECIFICATIONS.
3. REFERENCE CERTIFIED PRINT FOR COIL CONNECTION DIAMETER AND TYPE.
4. PUMP PIPING NOT INCLUDED IN REMOTE SUMP APPLICATIONS.
CROSSOVER PIPING SHOULD BE INSTALLED WITH ADEQUATE CLEARANCE
FROM OTHER PIPING, AS SHOWN.
5. SEE SMART SHIELD ARRANGEMENT DRAWING FOR CONDUCTIVITY
CONTROL AND BLOWDOWN PIPING DETAILS.
1/2" [15] HALF CPLG DRAIN
(BY OTHERS)
FACE B FACE B
SLRN.T.S.RECOMM.SERIES FLOW CROSSOVER PIPING W/ SMART SHIELD
6. DIMENSIONS LISTED AS FOLLOWS: ENGLISH FT-IN
[METRIC] [mm]
EVAPCO, INC.ATWB 9-3I8-Z
Spectrum Version: 2.2020.130.2 February 12, 2020
SCALE
DWG. #
DRAWN BY
B1AU0000-DC
N.T.S.3Ø HEATER WIRING DIAGRAM 1 HEATER SLR
IMMERSION HEATER BY:
LOW WATER CUTOFF/THERMOSTAT CONTROL BY:
AUXILIARY N.C. PUMP INTERLOCK BY:
HEATER CONTROL PANEL BY:
TRANSFORMER BY:
HEATER CONTACTOR BY:
FUSED DISCONNECT BY:
EVAPCO
EVAPCO
OTHERS
L1 L2
L1 L2
(H4) (H1)
(X2)(X1)
(H2) (H3)
120V
- REMOTE DEVICE
- TERMINAL POINT
RECOMMENDED POWER AND CONTROL WIRING
- ALL HEATERS AND CONTROLS NOT PROVIDED BY EVAPCO
TO BE INSTALLED AND WIRED BY OTHERS
- ALL POWER WIRING BY OTHERS
- ALL FIELD WIRING BY OTHERS
CON 1
J
LT1
G
BLUE RED
CR1 8
CR1
UNIT 1
HEATER
OFF AUTO
IF PUMP INTERLOCK
USED, REMOVE JUMPER
LOW WATER CUTOFF
THERMOSTAT
LINE VOLTAGE:
LINE VOLTAGE:
L3
CON 1
1H2
1H1
DISC
(1)
IMMERSION
HEATER
L3
1H3
1L2
1L1
1L3
NOTES:
1. DASHED LINES INDICATE FIELD WIRING.
2. THE HEATERS HAVE BEEN SIZED TO MAINTAIN
PAN WATER AT AN AMBIENT TEMPERATURE OF
3. ALL COMPONENTS BY EVAPCO HAVE TYPE 4 ENCLOSURES.
4. AUXILIARY N.C. CONTACT INTERLOCKS IMMERSION HEATERS WITH
SPRAY WATER CIRCULATING PUMP TO DE-ENERGIZE HEATERS WHEN
SPRAY PUMP IS RUNNING.
5. (1) CONTACTOR IS SUPPLIED FOR EVERY (2) HEATERS
- CONTACTOR SHOULD BE WIRED WITH SEPARATE SUPPLY
TERMINALS FOR EACH HEATER.
6. (1) CONTACTOR IS SUPPLIED PER CELL OF A MULTICELL UNIT
- PROVIDES FOR INDIVIDUAL CELL OPERATION.
EVAPCO, INC.ATWB 9-3I8-Z
0° F
OTHERS
OTHERS
OTHERS
OTHERS
40° F
460/3/60
460/3/60
Spectrum Version: 2.2020.130.2 February 12, 2020
2/12/2020ATWB 9-3I8-Z
TITLE DESCRIPTION:
EVAPCO, INC.
DWG. #VIBRATION SWITCH
ADJUSTMENT
ADJUST THE SWITCH SO THAT DURING FULL SPEED START-UP AND UNDER NORMAL CONDITIONS, THE CONTACTS DO NOT TRIP.
FIRST, WITH THE MOTOR OFF, TURN THE ADJUSTMENT SCREW COUNTER-CLOCKWISE (MORE SENSITIVE DIRECTION) UNTIL THE SWITCH TRIPS. NEXT, TURN THE ADJUSTMENT SCREW CLOCKWISE 1/8 TURN (LESS SENSITIVE DIRECTION). RESET THE SWITCH BY DEPRESSING THE PUSH-BUTTON RESET LOCATED ON TOP OF THE SWITCH. START THE MOTOR ON FULL SPEED. IF THE MOTOR TRIPS THE SWITCH, THEN TURN THE ADJUSTMENT SCREW CLOCKWISE AN ADDITIONAL 1/8 TURN. RESET THE SWITCH AND START THE
MOTOR AGAIN. REPEAT THE ABOVE PROCEDURE UNTIL THE MOTOR CONTINUES TO RUN.
SINGLE SPEED V1AU0000-EE
WIRING DIAGRAM:
DPDT
F
FAN
MOTOR
F
SUPPLIED VOLTAGE, 3 PHASE
INCOMING POWER
CIRCUIT
BREAKER
M1 OL1 1T1
1T2
1T3
SUPPLIED VOLTAGE
H1 H3 H2 H4
X1 X2
X2
OL1
M1
OPTIONAL
THERMOSTAT EVAPCO
SWITCH
HAND
OFF
DOX
AUTO
XDO
OFF
VIBRATION
017-00464P
MOTOR
(BY OTHERS)
CONTROL TRANSFORMER
CONTROL VOLTAGE
250 Vac; 1/2 AMP, 125 Vdc; 1/4 AMP, 250 Vdc.
15 AMPS, 125, OR 480 Vac; 1/8 HP, 125 Vac; 1/4 HP,
1. DASHED LINES INDICATE WIRING(BY OTHERS)
NOTES:
SWITCH CONTACT RATING:
F
F
F
F
Spectrum Version: 2.2020.130.2 February 12, 2020
SCALE
DWG. #
DRAWN BY
ELECTRIC WATER LEVEL CONTROL WIRING
D1AU0000-A
NOTES:
1. DASHED LINES INDICATE WIRING BY OTHERS.
2. TYPICAL WIRING PER PROBE.
120 VAC/60 Hz INTEGRAL LEVEL
PROBE/RELAY
IN A NEMA 4
POLYCARBONATE
ENCLOSURE
ELECTRIC MAKE-UP VALVE
(NORMALLY CLOSED)
120v POWER REQUIRED TO OPEN
L1 L2 NC C NO NC C NO NC C NO
L L
ALARM CIRCUIT
VOLTAGE
(AS DESIRED)
LOW ALARM HIGH ALARM
MWRN.T.S.
5 PROBE
EVAPCO, INC.ATWB 9-3I8-Z
Spectrum Version: 2.2020.130.2 February 12, 2020