This document outlines preventative maintenance tasks for facilities at USAG Humphreys in South Korea. It includes a list of over 70 items requiring routine inspection and service on a daily, weekly, monthly, quarterly, or annual basis. Tasks cover systems like roofs, structures, mechanical equipment, electrical systems, plumbing fixtures, kitchen appliances, and more. The solicitation number provided is for a total maintenance contract at USAG Humphreys to perform the preventative maintenance tasks described. The contracting agency is the Department of the Army Materiel Command Army Contracting Command. The document contains detailed specifications but no pricing, response date, or award date information.

TE-02

View the file

Other files

Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ARCHITECT

* Architect * All the required tasks that are following TB 5-610. Preventitive Maintenece * D: daily / W: weekly / M: monthly Q: quarterly / SA: semi-annually A: annually

NO.ITEMTASKCHECKMAINTAINREFERENCESREMARKS
DWMQSAWMQSAA
1Roofing ElementCheck State and Tile roofsXTB 5-610Repair is required if deficiency found
Check Metal roofsXRepair is required if deficiency found
Check Asphalt strips and roll roofingXRepair is required if deficiency found
Check Cement AsbestosXRepair is required if deficiency found
Check Built-up roofsXRepair is required if deficiency found
Check FlashingsXRepair is required if deficiency found
Check Roof DeckingXRepair is required if deficiency found
Check Parapets and CopingsXRepair is required if deficiency found
Check Lighting Rods and Grounds (Elec.)XRepair is required if deficiency found
Check Roof Vents (Elec.)XRepair is required if deficiency found
Check Installed Equipment on RoofXRepair is required if deficiency found
Check Gutters and DownspoutsXRepair is required if deficiency found
2StructureFoundations and Exterior Walls: Check concrete, masonryXTB 5-610Repair is required if deficiency found
Foundations and Exterior Walls: Check timberXRepair is required if deficiency found
Foundations and Exterior Walls: Check ventsXRepair is required if deficiency found
Foundations and Exterior Walls: Check drainageXRepair is required if deficiency found
Foundations and Exterior Walls: Check stuccoXRepair is required if deficiency found
Foundations and Exterior Walls: Check cement-asbestosXRepair is required if deficiency found
Foundations and Exterior Walls: Check aluminum and shet steel sidingXRepair is required if deficiency found
Foundations and Exterior Walls: Check exterior trimXRepair is required if deficiency found
Interior walls and ceilings: Check woodXRepair is required if deficiency found
Interior walls and ceilings: Check wallboard, plasterboard, fiberboardXRepair is required if deficiency found
Interior walls and ceilings: Check plasterXRepair is required if deficiency found
Interior walls and ceilings: Check ceramic tileXRepair is required if deficiency found
Interior walls and ceilings: Check synthetic coverings and wallpaperXRepair is required if deficiency found
Interior walls and ceilings: Check wainscotsXRepair is required if deficiency found
Interior walls and ceilings: Check metal grillsXRepair is required if deficiency found
Chimnetys and Stacks: Check masonry and concreteXRepair is required if deficiency found
Chimnetys and Stacks: Check linings and bafflesXRepair is required if deficiency found
Chimnetys and Stacks: CheckladdersXRepair is required if deficiency found
Porches and Decks: Check columnsXRepair is required if deficiency found
Porches and Decks: Check fire escapesXRepair is required if deficiency found
Porches and Decks: Check rails-wood and metalXRepair is required if deficiency found
Porches and Decks: Check decking and stepsXRepair is required if deficiency found
Doors: Check woodXRepair is required if deficiency found
Doors: Check metal (Including auto door, turnstile gate)XRepair is required if deficiency found
Doors: Check stormXRepair is required if deficiency found
Doors: Check frames and jambsXRepair is required if deficiency found
Doors: Check door hardwareXRepair is required if deficiency found
Doors: Check casings, baseboards and moldingsXRepair is required if deficiency found
Doors: Check doorstopsXRepair is required if deficiency found
Loading Ramps and Platforms: Check warehouse platformsXRepair is required if deficiency found
Loading Ramps and Platforms: Check retaining wallsXRepair is required if deficiency found
Exterior and Interior Stairs: Check no obstructionsXRepair is required if deficiency found
Exterior and Interior Stairs: Check woodXRepair is required if deficiency found
Exterior and Interior Stairs: Check concreteXRepair is required if deficiency found
Exterior and Interior Stairs: Check steelXRepair is required if deficiency found
Exterior and Interior Stairs: Check finishXRepair is required if deficiency found
Exterior and Interior Stairs: Check railings and balustradesXRepair is required if deficiency found
Sub floors: Check loadingsXRepair is required if deficiency found
Sub floors: Check woodXRepair is required if deficiency found
Sub floors: CheckconcreteXRepair is required if deficiency found
Sub floors: ChecksteelXRepair is required if deficiency found
Window: Check wood sashXRepair is required if deficiency found
Window: Check metal sashXRepair is required if deficiency found
Window: Check storm windowsXRepair is required if deficiency found
Window: Check shtters, awnings and canopiesXRepair is required if deficiency found
Window: Check insect screensXRepair is required if deficiency found
Window: Check louvres and venetian blindsXRepair is required if deficiency found
Window: CheckshadesXRepair is required if deficiency found
Window: Check window hardwareXRepair is required if deficiency found
Window: Check glassXRepair is required if deficiency found
Glazing: Check fixed single and double glazing, insulating glassXRepair is required if deficiency found
Glazing: Check interior glass panelsXRepair is required if deficiency found
Glazing: Check roof lightsXRepair is required if deficiency found
3Flooring CoveringCheck wood FlooringXTB 5-610Repair is required if deficiency found
Check ConcreteXRepair is required if deficiency found
Check Oxychloride/CementitiousXRepair is required if deficiency found
Check TerrazzoXRepair is required if deficiency found
Check Clay and Masonry TileXRepair is required if deficiency found
Check Vinyl-asbestos TileXRepair is required if deficiency found
Check Asphalt tileXRepair is required if deficiency found
Check Resilient Flooring CoveringXRepair is required if deficiency found
Check MasticXRepair is required if deficiency found
Check Carpets and RugsXRepair is required if deficiency found
4Exterior PaintingCheck Peeling, efflorescenceXTB 5-610Repair is required if deficiency found
Check Rust, Corrosion, Absence of PaintXRepair is required if deficiency found
Check Weather DmageXRepair is required if deficiency found
Check DetriorationXRepair is required if deficiency found
Check Excessive Chalking or mildewXRepair is required if deficiency found
5Interior PaintingCheck Scuffs, AbrasionsXTB 5-610Repair is required if deficiency found
Check DeteriorationXRepair is required if deficiency found
Check Absence of PaintXRepair is required if deficiency found
6Rolling Counter doorCurtain & Bottom Bar: Check curtain components damaged (slats, endlocks, etc.)XO&M Manual

* MFG & MDL: WAYNE DALTON &

SERIES 500, SERIES 800, SERIES 700C

* MFG & MDL: CORNELL & MBD 5F 22GP

www.wayne-dalton.comRepair is required if deficiency found
Curtain & Bottom Bar: Check bottom bar damagedXRepair is required if deficiency found
Curtain & Bottom Bar: Check bottom bar fastenersXRepair is required if deficiency found
Curtain & Bottom Bar: Check fasteners attaching curtain to the barrelXRepair is required if deficiency found
Curtain & Bottom Bar: Check obstacles( any hang-ups, jammiing or other problems
preventing the door from moving smoothly throught the opening)XRepair is required if deficiency found
Curtain & Bottom Bar: Check any odd or excessive noiseXRepair is required if deficiency found
Curtain & Bottom Bar: Check bottom sealXRepair is required if deficiency found
Curtain & Bottom Bar: Check locking function properlyXRepair is required if deficiency found
Brackets: Check brackets plumb and perpendicular with wallXRepair is required if deficiency found
Brackets: Check bracket fastenersXRepair is required if deficiency found
Brackets: Check signs of excessive wear on the bearings (i.e. binding, excessive noise, etc.)XRepair is required if deficiency found
Brackets: Check adjusting wheel & pinXRepair is required if deficiency found
Brackets: Check lubrication of drive chainXRepair is required if deficiency found
Brackets: Check drive chain in need of tighteningXRepair is required if deficiency found
Brackets: Check drive or driven sprocket damagedXRepair is required if deficiency found
Guides: Check fastenersXRepair is required if deficiency found
Guides: Check guide assembly fastenersXRepair is required if deficiency found
Guides: Check guide gap dimension correctXRepair is required if deficiency found
Guides: Check guide parts bent or damagedXRepair is required if deficiency found
Guides: Check stoppers loose, damaged, or missingXRepair is required if deficiency found
Guides: Check hood/fascia dented or damagedXRepair is required if deficiency found
Hood and FasciaIs : Check hood/fascia dented or damagedXRepair is required if deficiency found
Hood and FasciaIs : Check curtain rubbing against the hood/fasciaXRepair is required if deficiency found
Hood and FasciaIs : Check level of hood/fasciaXRepair is required if deficiency found
Hood and FasciaIs : Check guide assembly fastenersXRepair is required if deficiency found
Hood and FasciaIs : Check hood support levelXRepair is required if deficiency found
Door operation: Check door require excessive force to openXRepair is required if deficiency found
Door operation: Check door contains locking (locking mechanism function properly
and securely hold the door in the closed position)XRepair is required if deficiency found
Door operation: Check sensing edge functionXRepair is required if deficiency found
Motor Operator: Check fasteners attaching the motor-to-the mounting bracket,
and mounting bracket-to-the door bracket secureXRepair is required if deficiency found
Motor Operator: Check sprockets properly alignedXRepair is required if deficiency found
Motor Operator: Check sprocket keys properly alighed with sprockets
and securely fastened with the set screwsXRepair is required if deficiency found
Motor Operator: Check door stopping correctly at the open (before bottom bar contact the stoppers) and closed (as soon as the bottom bar contacts the floor) positionsXRepair is required if deficiency found
Motor Operator: Check operator functioningXRepair is required if deficiency found
7Roll up doorDrive Chain: Check for excessive slack.

Drive Chain: Check & adjust as required.

Drive Chain: LubricateXMFG Maintenance Schedule
* MFG & MDL: Liftmaster* Inspect and service whenever a malfunciton is observed or suspected.

Every 3 months or 5,000 cycles Every 12 months or 20,000 cycles (Repeat All procedures) Sprockets: Check set screw tightness X Every 3 months or 5,000 cycles Every 12 months or 20,000 cycles (Repeat All procedures) Clutch: Check & adjust as required X Every 3 months or 5,000 cycles Every 6 months or 10,000 cycles Every 12 months or 20,000 cycles (Repeat All procedures) Belt: Check condition & tension X Every 3 months or 5,000 cycles Every 6 months or 10,000 cycles Every 12 months or 20,000 cycles (Repeat All procedures) Fasteners: Check & tighten as required X Every 3 months or 5,000 cycles Every 6 months or 10,000 cycles Every 12 months or 20,000 cycles (Repeat All procedures) Manual Disconnect: Check & Operate X Every 3 months or 5,000 cycles Every 6 months or 10,000 cycles Every 12 months or 20,000 cycles (Repeat All procedures) Bearing & Shafts: Check for wear & Lubricate X Every 3 months or 5,000 cycles Every 12 months or 20,000 cycles (Repeat All procedures) 8 Full/Half height turnstile One bottom of each rotor, re-grease the bearing that the rotor rests on X X Google search

* MFG & MDL: Designed Security , Inc. & 6500 Series control head

* To ensure long life on any turnstile, the follwing maintenance is recommende.

Note: Figures are assuming a miximu 75,000 passages per year.

Turnstiles with heavier traffic should be maintained more frequently.

Secure all nuts & bolts in clude concret anchors, carriage boltsXX
Clean any loose debris/Apply grease on the control head and inside of the castingXX
Lubricate to the brone bushing on the locking barsXX
9Auto door* MFG & MDL: LCN & 9550

&20TECHNICAL EXHIBIT 02

PM TASK LIST

ELECTRICAL

* Electrical * All the required tasks that are not here will be done as following EPM programs at NFPA 70B * D: daily / W: weekly / M: monthly Q: quarterly / SA: semi-annually A: annually

NO.ITEMTASKCHECKMAINTAINREFERENCESREMARKS
DWMQSAWMQSAA
1Emergency generatorFuel system: Fuel level in tankx*Cummins 1750DQKAD

*QSK60 Engine with PowerCommand control *Table 6-1 at UFC 3-540-07

Fuel system: Fuel lines, hoses & leaksx
Fuel system: Bedframe fluid containmentx
Fuel system: Drain waterx
Fuel system: Replace water separator elementx
Fuel system: Replace fuel system secondary filterx
Fuel system: Fuel injectorsCheck every 3,000hrs of operation
Lubrication system: Check Engine oil levelx
Lubrication system: Replace engine oil & filterx
Cooling system: Check Coolant level in radiatorx
Cooling system: Check Cooling fan bladesx
Cooling system: Check Drive beltsx
Cooling system: Check Coolant lines and radiator hosesx
Cooling system: Check Aftercooler corex
Cooling system: Check Water jacket corex
Cooling system: Check Water pumpx
Cooling system: Clean radiator matrixx
Cooling system: Replace cooling system coolantx
Air/Exhaust system: Check exhaust leaks & componentsx
Air/Exhaust system: Check air intake system for leaksx
Air/Exhaust system: Air cleaner resriction indicatorx
Air/Exhaust system: Air cleaner elementx
Battery system: Check battery electrolyte levelx
Battery system: Check Electrical connectionx
Electrical system: Check operation of control P/Lx
Electrical system: Check operation of emergency stop buttonx
Prime mover system: Check engine valve lashx
Prime mover system: Check engine mountsx
Prime mover system: Check starting motorx
Prime mover system: Check turbochargerx
Generator system: Check alternatorx
Generator system: Check engine groundx
Generator system: Check alternator stator(Record ohm value)x
Generator system: Check alternator bearings,housing & vibrationx
Generator system: Check connections in terminal boxx
Generator system: Clean/Regrease alternator bearingsx
2Auto Transfer swichOverall visual inspection & cleaning to meet NFPA 110x*ATS PM SOW from General Electric

*Table 7-1 at UFC 3-540-07

Vacuum accumulated dust form switches & P/Lx
Inspect moisture or signs of wetness or drippingx
Verify generator is in automatic position &
may be started and operated under loadxIf an generator is a secondary source
Verify equipment ground connectionx
Torque main lug terminals for S1 and S2x
Verify that phase rotations of both sources are matchedx
Measure & record S1 & S2 voltage and frequencyx
Review communications to external SCADA or Building systemsx
Lubricate any necessary moving linkages, bearings, etc.x
Adjust mechanical limit switches if necessaryx
Perform no load test of transfer S/Wx
Perform fast load/load test of transfer S/Wx
Adjust time delay if necessary and review sequencex
Perform second load test of transfer S/Wx
Record values of all measurement takenx
3Pad MTD TREnergized state: Safety locking devicex*Technical instruction manual

from Dongbang Electric Ind. Co., Ltd.

Energized state: Painting and corrosion of tank surfacex
Energized state: Noisex
Energized state: Temperature and oil levelx
Energized state: Oil leakage of filtering V/V and D/Vx
Energized state: Oil leakage of tankx
Energized state: Elbow connector & terminalx
Energized state: Ground terminalx
Energized state: Radius of cable curvaturex
Energized state: Insulation of terminalx
Energized state: Grounding of elbow connectorx
Energized state: Operation of pressure relief V/Vx
Energized state: Looseness corrosion of boltsx
Energized state: Damage of foundationx
Energized state: Number plate/Labelx
Energized state: Taping of connection partx
Energized state: Overheat and induced voltage of elbow connectorx
De-energized state: Check on secondary short circuitx
De-energized state: Insulation resistancex
De-energized state: Pressure rise and swelling of the tankx
De-energized state: Capacity of bay-o-net fusex
De-energized state: Closing condition of fuse holderx
De-energized state: Rubber gasketsx
De-energized state: Traces of arc at contact point of fuse holderx
De-energized state: Tightness between fuse holder & linkx
De-energized state: Insertion condition of elbow connectorx
De-energized state: Check overlapping between elbow and cablex
De-energized state: Coupling condition of elbow connectorx
4Dry TRFunction of fans and fan control if there isx*Technical instruction manual

from Dongbang Electric Ind. Co., Ltd.

*DPW PM check list

Pollution of transformer surfacesx
Clean any dust surface using vaccuum cleaner of blowing wity airxx
Recording frequency, S1/S2 voltage, X-frm ratiod & temperaturex
Function of temperature control by interrupting thermistor rowxx
5Lighting protection
Grounding systemNo loose connections that might result in high-resistance jointx*Appendix B at NFPA 780-29
No part of system has been weakened by corrosion or vibrationx
All down conductors and ground terminals are intactx
All components are securely fastened to their mounting surfacesx
Protected against accidental mechanical displacement as requiredx
Additions or alterations to the protected structurex
No damage to surge suppression devicesx
MNT: Inspect all conductors and system componentsx
MNT: Tightening of all clamps and splicersx
MNT: Measurement of lightning protection system resistancex
MNT: Measurement of resistance of ground terminalsx
MNT: Inspection/Testing of surge suppression devicesx
MNT: Refastening and tightening of components and conductorx
MNT: Maintenance recordx
6Panelboard

Switchboard

Circuit breakerCheck loose bolts and connection or overloadingx*GE Switchboard maintenance guide
Remove any accumlation of dirt or other foreign matterx
Retighten lugs and joints to eliminate possible heating pointx
Transmission of vibrations through the building and conduitsx
Check ambient temperatures and circuit loadingx
Mechanical damage to conductors, insulation or equipmentx
Arcing damage to insulationx
No water soaked equipmentx
7Surge protective devicesCheck the state of the status indicatorsx*EATON & APC SPD operation manualMaintenance free, Only replacement

available

Check inoperative modules by built-in diagnosticsx
8Uninterruptible Power SupplyComponent inspection/testingx*DA FORM 7475-R
Installation inspection/testingx
Wiring visual verificationx
Generator control functions as site conditionx
Loading UPS testx
Disconnect rectifiers & inverters separately.
Does system operate correctly?x
Energize and test systemx
Utility trip testx
Loaded transfer test(Normal, Emergency & Return)x
Tightness of bolted connectionsx
Battery discharge testx
Test all UPS diagnostic fault indicatorsx
Electrical Test & record: UPS input, UPS output, UPS THDx
9Obstruction light with controllerOperation of lampsx*Table 5-13 at FAA AC 150/5340-26C
Check flash ratex
Check operation of photocellx
Check insulation resistance and ground resistancex
Check wire and connectionsx
Check voltage at lamp socketx
Check weatherproofing of the fixturex
Check lightning protection systemx
Check power meterx
Service lowering device and other supporting hardwarex
Check changeover relay in dual fixturex
Clean and recondition obstruction lightx
Replace new lamp after 80% of rated lifex
10Lighting fixtureGroup relamping when lamps begin to failx*www. grainger.com
*www.buildings.comIf fail, relamping as grouping plan
Transformer, control gear, spread lense, glare baffle or color filterx
Ex. Light or vapor proof type: all screws, gasket or watertight sealx
Any burned-out lamps consider group relampingxIf fail, relamping as grouping plan
Same color temperature at same zonex
Re-aim adjustable lighting if necessaryx
Dust lamps & clean lens surface to enhance lighting performancex
11Lighting control panel & contactorsInspect each relay load wiringx*Leviton lighting relay cabinet checklist
Inspect each relay's load wiring for terminalsx
Relay in "off" position, check voltage btwn line & load terminalsx
Inspect all low voltage wiringx
Inspect control power wiringx
Confirm that cabinet boots properly and return to normal statusx
Set the time & date form the menuAs site condition
Update system software with the latest avilableIf updated is existed as requirments
Proceed to panel programming if necessaryIf updated is existed as requirments
12Illumination for emergency & signsSelf Test position: Test monthly 30 sec and annually for 30 min
(Be at least 1.5hrs of emergency light if the building lighting fails)x*7.9.2.1/7.9.3.1/7.10.6.3 at NFPA101

*6.3.2.2.11.5 at NFPA99

Minimum of 5fc on the illuminated surfacex
Battery replacement if necessaryx
Written record testing result & battery replacementxx
13Motor control/starter device
Switching deviceSurroundings: Dust, grease, oil, high Temp., rust, damage & gasketxx*Table 16.2.2 at NFPA 70B
Interior: excess vibration, loosened nuts/bolt and connections2 years interval maintenance
Contactor/solenoids: Control volage, excess heating, insulationsx
Contactor/solenoids: Discoloration, greedom of moving partsx
Contact tips: excessive pitting, copper oxidex
Springs/Flex. Leads: contact pressure, frayed trand, brittlex
Arc chutes: breaks or burningxx
Bearing: Freedom of movementxx
Coils: Evidence of overheating, charred insulationx
Magnets: Clean faces, shading coil, misalignment, bondingx
Fuse/clips: Proper rating, snug fit, fuseclip pressurex
Overload relays: Proper heater size, trip by hand, connectionx
Pushbutton/pilot lamp: Check contacts, grease and corrosionx
Resistors: Check signs of overheating, connection, tighten slidersx
Connection: Tighten main line and control conductor2 years interval maintenance
Control operation: Sequence of operation, check sensing devicesxx
Circuit breaker: case damage, exercise by opening/closingx
Disconnect and switching device: Excess heating/pittingxx
Disconnect and switching device: Roughness on switch bladex
Disconnect and switching device: Exercise by opening and closingxx
14Receptacles with cover platesFloor receptacle: Clean inside of floor boxesx*13.2 & 24.3/6/8 at NFPA 70B
Floor receptacle: Check cover hinge, seals, obstacles to damage cordx
Check cracked or broken, if contacts are exposed, replace receptaclex
Hold and retain inserted plug firmlyx
Arc tracking or evidence of burning of devicex
Wall plates or covers for suitable for environment and locationx
Damaged wall plates or spring doorsx
All gaskets, if usedx
Covers and threaded openings should be installed and tightx
GFCI: Tripping test by test button or tripping operationx
GFCI: Factory seal damagex
GFCI: Check miswiring, if have difference between tester & integral testx

&26TECHNICAL EXHIBIT 02

PM TASK LIST

MECHANICAL

* Mechanic D: daily / W: weekly / M: monthly Q: quarterly / SA: semi-annually A: annually

NO.ITEMTASKCHECKMAINTAINREFERENCESREMARKS
DWMQSAWMQSAA
1AHU
(AIR HANDLING UNIT, RF: RETURN FANS)BEARING: lubricate bearingsXXLG MODEL BAB0836HFA0, O & M manual, MECHANICAL DRAWING on S-12400
BEARING: check screws for tightnessXX
BEARING: check fasteners attaching bearingsXX
MOTOR: clean motor without water and solventsX
MOTOR: lubricate motorXX
WHEEL AND FASTENER: clean wheelXX
WHEEL AND FASTENER: check all fastener including screwXX
WHEEL AND FASTENER: Tighten wheel hub or bearing collarsXrepair as required
WHEEL AND FASTENER: check correct rotationX
WHEEL AND FASTENER: check bladeX
WHEEL AND FASTENER: check piping and valvesX
WHEEL AND FASTENER: check duct leakage and seal offX
BELT: Check belt for tension and breakdownXreplace as required
BELT: Check loosen pulleysX
ELECTRICAL SUPPLY: Check fuses, circuit breakers, switches, correct voltageXrepair as required
ELECTRICAL SUPPLY: Check/adjust automatic off/on timersX
Filter: check filtersXXclean or replace as required
Coil: check coil with drip panX
Check A/H for proper operation before and after PMX
Check for corrosionX
Inspect water piping & valves for leaksX
Inspect piping & valves for freon gas leaksX
Visually inspect coilX
Check operation of damper motorX
Lubricate damperX
Check computer for DDC systemX
Check DDC control communication panelX
Clean up area around unit and mechanical roomX
2CT(COOLING TOWER)Belt: Check and Lubriate fan shaft bearingXXO & M manual (Marley-AV Cooling Tower),

Drawing for S-12400,

Belt: Check and tighten support fastenersXrepair as required
Belt: Check shaft, sheave and belt aligmentX
Belt: Check belt tension and conditionX
Belt: Check sheave bushing fastener torqueX
Fan: Check and tighten blade and hub fastenersXrepair as required
Fan: Check fan blade pitch and tip clearanceX
Fan: Check fan cylinder for loose fastenersX
Motor: Lubricate (grease as required)X
Motor: Check mounting bolts for tightnessXrepair as required
Motor: Operate as leastXX
Motor: Check fan motor exteriorXrepair as required
Basin heater: Check temp/low water level sensorXX
Basin heater: Check/clean buildup of contaminant from sensorXX
Basin heater: Check water basin levelXrepair as required
Basin heater: Adjust blowdown as requiredX
Structure: Check/tighten all fastenersXX
Structure: Check and touch up all metal surfacesXX
Body: Check general condition and operationXrepair as required
Body: Check makeup valve (if equipped)X
Body: Check for unusual noise or vibrationX
Body: Check and clean air inletX
Body: Check and clean PVC drift eliminatorsX
Body: Check and clean distribution basin, nozzles and collection basinX
Body: Check mechanical-motor, fan and drive mechanismX
Check electrical wiring & connections 전기배선 점검X
Visually check fill and fan 육안으로 필 & 팬 점검X
Clean condensing fill , drip pan 콘덴싱 필, 드립팬 청소X
Inspect water piping & valves for leaks 물 배관과 밸브가 새지않나 점검X
Check Chilled Water as required 냉방수 양 확인X
Clean up area around unit and mechanical room 작업공간 주변청소X
Clean pan strainer 수조 스트레이너를 청소X
Clean and flush pan 수조를 청소하고 물로 세척X
Check bleed-off valve to make sure it is operative 배출수 밸브를 점검하여 작동여부 확인X
Lubricate pump and pump motor according to manufacturer's instructionsX
Check operating level in pan and adjust float valve 수조 운전수위 점검및 플로트밸부 조절X
Check water distribution system and spray pattem 수분배 시스템과 분사형태 점검X
Check drift eliminators 비산 엘리미네이터 점검X
Check the fan blades for cracks, missing, balancing weights, and vibrations 팬 날개의 균열 발생 여부, 무게 균형, 진동여부 점검X
Lubricate fan shaft bearings 팬 샤프트베어링 윤활유 주입X
Lubricate fan motor bearings 팬 모터베어링에 윤활유 주입X
Check belt tension and adjust 벨트 장력 점검및 조정X
Inspect and grease sliding motor base 슬라이딩 모터 베이스 검사, 구리스 도포X
Check fan screens, inlet louvers, fans and dry cooler coil (eco-ATC, eco-ATW, eco-ATWE) Remove any dirt or debris 팬 스크린, 입구 루버, 팬을 점검하고 오염이나 먼지를 제거X
Check water quality for biological contamination 생물학적 오염점검, 필요시 청소하고 수처리 전문회사에 연락하여 수처리 프로그램을 활용X
Regiorea disinfectant input 레지오렐라 살균제를 정기적으로 투입한다X
Coupling / shaft - inspect flex elements and hardware for tightness, proper torque & crack / deterioration 플렉시블과 적당한 토크로 조여졌는지, 금/부식등이 없는지 검사X
Heater controller - inspect controller and clean probe ends 히터조절기를 검사하여 탐지기 끝부분을 청소한다X
Heater - inspect junction box for loose wiring and moisture 히터 배선 결속, 습기가 있는지 단자대 검사X
Heater - inspect element for scale build up 히터 부품에 산화물이 축적되어 있는지 검사X
Electronic water level controller - inspect junction box for loose wiring and moisture 전자수위조절기의 배선이 느슨한지, 습기가 있는지 단자대를 검사X
Electronic water level controller - clean probe ends of scale build up 전자수위조절기의 물때가 낀 탐지기 끝부분 청소X
Electronic water level controller - clean inside the standpipe 전자수위조절기 내부 스탠드 파이프 청소X
Solenoid make-up valve - inspect and clean valve of debris 전자식 보급수밸브 이물질을 청소하고 작동여부 검사X
Vibration switch - inspect enclosure for loose wiring and moisture 진동스위치의 배선이 느슨한지, 습기가 찼는지 검사X
Vibration switch - adjust the sensitivity 진동스위치의 감도를 조절한다X
Sump sweeper piping - inspect and clean strainer and piping of debris 스트레이너와 배관을 검사하여 부스러기 조각을 제거한다X
3CO2 SENSORCheck proper operation/ calibrationXMOD# EX-5175 MANUALInitial calibration or replace as reqired
4HWHB & DHWH
(HOT WATER BOILER AND HEATER)Boiler Body: Check abrasions, wear, misalignmentXBurnham manual_4FPW-563A-50-GO-PF2016,

O&M manual

Drawing for S-12400repair as required
Boiler body: Check breaks in thermal insulation on pipeX
Boiler body: Check leakage of gases or oilX
Boiler body: Check insufficient oil or gas pressuresX
Boiler body: Check weathertightness of seams and jointsX
Boiler body: Check missing or damaged connectionsX
Boiler body: Check clogged jets, valves, fuel supply linesX
Boiler body: Check leaks, air-binding or water hammerX
Boiler body: Check/ clean boiler surfacesXX
Boiler body: Check/ clean dust, scaling, corrosion, other deposits, cloggingXX
Boiler body: Check/ clean boiler firetubes(soot, rust)XX
Boiler body: Check/ clean or replace firetube turbulatorsXX
Boiler body: Check drain water to remove scal and prevent freezing if not used during winter monthsXX
Boiler body: Check/clean and repair burner and controlsXX
Boiler body: Check/ lubricate boiler components(burner and circulator)XX
Boiler body: Check/ repair safety valveXX
Boiler body: Check/water treatment (chemical treatment)XX
Burner: Check misalignment, nonuniform flame or heat spreadXX
Burner: Check wrong fuel-air mixtureXX
Burner: Check incorrect position of pilot lightXX
Burner: Check pilot turndown testXX
Burner: Check low fire start interlockXX
Burner: Check/ remove oil drawer assemblyXXremove and clean
Burner: Check blower motor and blower wheelXX
Burner: Check/ clean burner componentsXX
Burner: Check/ clean gas pilot assemblyXX
Low water cutoff device: Check proper operationXX
Low water cutoff device: Check all visible wiring for brittle or worn insulationXX
Low water cutoff device: Check/ clean cutoff device(scal or sediment)XX
Low water cutoff device: Check/ clean the probe in cutoff deviceXX
Flue: Check/ clean obstructions, sootXX
Flue: Check/ repair pipe for damage and condesationXX
Flue: Check/ repair on proper support no sagsXX
Flue: Check/ repair on tightness of jointsXX
Flue: Check/ check proper operation of damperXrepair or replace as required
Electricity: Check loose connectionsXX
Electricity: Check charred, frayed, broken or wet insulationXX
Electricity: Check low voltageXX
Electricity: Check high limit safety controlXX
Electricity: Check operating controlXX
Electricity: Check fuel valve interlock switchXX
Electricity: Check purge switchXX
Check, report, and adjust boiler efficiencyX
5HYDROGEN DETECTORCheck proper operation/calibrationXMOD# EX-5175 MANUALInitial calibration or replace as reqired
6PUMPS
(INCLUDING CIRC. PUMP, SUMP PUMP)Pump body: Check for leaksXTACO base mounted pump manual
Drawing for S-12400repair as required
Pump body: Check for lubricationXlubicate as required
Pump body: Check/ monitor bearing temperatureXrepair as required
Pump body: Check and record pressure gage readingsX
Pump body: Check the seal for leakageXX
Pump body: Check wear ring clearancesXX
Pump body: Check/ measure total dynamic suction and discharge headXX
Motor: Check alignment of pump and motorXX
Motor: Check holding down bolts for tightnessXX
Motor: Check coupling for wearXX
7ACU
(SPLIT AIR CONDITIONING UNIT)Filter: Check/ clean or replace filtersXXO & M manual(carrier mod#38HDR030)

Drawing for S-12400

Indoor Unit: Check/ clean drain pipeXX
Indoor Unit: Check/ clean condensate drain panXX
Indoor Unit: Check/ clean indoor coilXX
Indoor Unit: Check/ clean indoor unit front panelXX
Outdoor unit: Check/ clean the fins from outsideXX
Outdoor unit: Check/ clean fins insideXX
Outdoor unit: Check/ remove dust from electrical partsXX
Outdoor unit: Check electrical connectionsXXrepair/tighten as required
Outdoor unit: Check/ clean outdoor fan and coilXX
Outdoor unit: Check outdoor fan assemblyXX
Outdoor unit: Check/ clean drain panXX
8FCU
(FAN COIL UNITS)FCU body: Check/ clean coil finsXXO & M manual, Drawing for S-12400
FCU body: Check/ clean drain trap and lineXX
FCU body: Check/ replace or clean filterXX
Valves and piping: Check leakage on valve-packageXreplace broken part as required
Electricity: Check electrical componentsXXreplace as required
9THERMOSTATIC MIXING VALVEValve body: Check/ clean valve bodyXX
Valve body: Check temperature adjustmentXXstandard setting is 110 deg F.
Valve body: Check hot water shut-offXX
Valve body: Check cold water shut-offXX
Connection: Check leakage on connectionXX
10HPU(HEAT PUMP, SPLIT SYSTEM UNITHeat pump body: Check/ clean filtersXXO & M manual, manual for 40QAC/38HDR
Drawing for S-12400replace as required
Heat pump body: Check leaks on refrigerant lineXreplace as required
Heat pump body: Check liquid line pressure tabsXreplace as required
Heat pump body: Check suction and discharge pressure tabsXreplace as required
Heat pump body: Check/ clean dust inside indoor unitXXX
Electricity: Check proper operation on control boxXXreplace as required
Electricity: Check electrical elementXXreplace as required
11CRAC
(COMPUTER ROOM AIR CONDITIONING UNIT)Air filters: Check/ replace air filtersXXO & M manual(Mini-Plus Ceiling manual)

Drawing for S-12400

Air filters: Check/ grille area and ensure unrestrictedX
Air filters: Check dirty filter sensor with alarmX
Blower section: Check belt tension and pulleys/sheave misalignedX
Blower section: Check blower wheel movement and clear of any debrisX
Blower section: Check motor mount/alignmentX
Humidifier(steam generator): Check drain valve/trap/drain lineX
Humidifier(steam generator): Check for leaks(make-up water/hoses)X
Humidifier(steam generator): Check humidifier canisterXreplace as required
Humidifier(steam generator): Check/clean strainerXclean as required
Humidifier(steam generator): Check proper operationXtake action as required
Refrigeration piping: Check for lines(leaks/lines secure)Xreplace as required
Refrigeration piping: Check capillary linesXreplace as required
Compressor: Check for oil leaksX
Compressor: Check comperssor mountingX
Compressor: Check wire connectionX
Compressor: Check pressure, superheat, sub-coolingX
Compressor: Check high/low pressure cut-in/outX
(air)cooler, dry cooler and condensers: Check for leaksX
(air)cooler, dry cooler and condensers: Check for water temperaturesX
(air)cooler, dry cooler and condensers: Check for debris on condensate panX
(air)cooler, dry cooler and condensers: Check float/pump operationX
(air)cooler, dry cooler and condensers: Check coilsX
(air)cooler, dry cooler and condensers: Check motor/motor mounts/fan bladeX
(air)cooler, dry cooler and condensers: Check wiringX
(air)cooler, dry cooler and condensers: Check piping for leaksX
Electricity: Check fuse/wire/contactorsXreplace as required
Electricity: Check unit control operation(high water alarm/pressure differential switch/air flow switch)Xreplace as required
Electricity: Check element/wiring/ampsXreplace as required
12FUEL OIL STORAGE TANKCheck leak detector for indication of fluid in intersticeXXO&M Manual
\\humpa710N501003\DPW_O&M\UTILITY & ENERGY BRANCH\O&M Manual\SPT040, One Stop Building and Bus Station, O&M Manuala. Item No : 33 56 10 - 4, 5

b. MFR & Model : DAEHYUN E&I

FRANKLIN FUELING SYSTEM #706-420-01

MORRISON BROS. CO. #539AS0400 AD

MORRISON BROS. CO. #910-1100AV, #910-2100AV

MORRISON BROS. CO. #534BDI0150AV

MORRISON BROS. CO. #285DI-5400 AS

MORRISON BROS. CO. #244OI-0060 AV

REDERAL SIGNAL CORP. #350-120-30

PANALARM LTD. #MODERL 57 ANNUNCIATOR

DWYER INSTRUMENTS INC. #F-7-MLK

FRANKLIN FUELING SYSTEM #706-420-01

c. Address : DAEHYUN E&I 383-1, Daejeong-ri, Samseong-myeon, Eumseong-gun, Chungcheongbuk-do, Korea Tel : 043-882-4391 www.dheni.co.kr

MORRISON BROS.

24th and Elm Street Dubuque, lowa 52001 Phone: 800-553-4840 Fax: 319-583-5028 www.morbros.com

d. POU : FACTORY-FABRICATED FUEL STORAGE TANKS AND PIPING

e. Actual Data : SECONDARY CONTAINED CONCRETE ENCASED ABOVE GROUND

TANK ASSEMBLY SHALL BE IN

ACCORDANCE WITH NEFA 30 AND NEFA 30A

PRIMARY STORAGE TANK SHALL BE

FACTORY-WELDED, STEEL THAT CONFORMS TO UL 142 CONCRETE SHALL HAVE A MINIMUM

20.7Mpa(3,000psi) STRENGTH

THE ENTIRE TANK ASSEMBLE SHALL CONFORM TO UL 2085

Check for leaks on the pumps, filters, hoses, nozzles, joints and fittingsXX
Check piping and fittings for rust (Include nipple, spill containment and manhole)XX
Check pump meter and reset buttonXX
Check fuel gauge or at a glance guageXX
Check spill containment for debrisXX
Check cracks in concreteXX
Check readability of signs and decalsXX
Check for water in the primary tank bottom under the fuelXX
Check the tank, including under the tank for any signs of leakageXX
Check detection device inluding leak indicator, leak detector tube capXX
Check all nozzles, hoses and fittingsXX
Check trigger mechanism on nozzleXX
Check pump motor for signs of over-heating or excessive wearXX
Check body of tank for cleanliness, need of paint, or rusting
Check slab and supports of unit for structural soundnessXX
Check grounding wiresXX
Check/ Replace the dispenser filterXX
Check fuel for bacterial infestation or microbial growthXX
Check all electrical wiringXX
check ventXX
Check the emergency relief ventXX
Check over-fill prevention valve and high-level alarmXX
Check the calibration of the fuel gaugeXX
13FTD
( FUEL OIL DAY TANK W/ASSEMBLY)Check deterioration on the tank, tank coating, piping, foundation, drainage, supports, ladder, platform, or safety equipmentXXO&M Manual
\\humpa710N501003\DPW_O&M\UTILITY & ENERGY BRANCH\O&M Manual\SPT040, One Stop Building and Bus Station, O&M Manuala. Item No : 33 56 10 - 7

b. MFR & Model : TRAMONT #TRS SERIES

c. Address : Tramont Corporation 3701 N. Humboldt Boulevard Milwaukee, Wisconsin 53212 Phone: 414-967-8800 Fax: 414-967-8811 e-mail : sales@tramont.com Internet: www.tramont.com

d. POU : FACTORY-FABRICATED FUEL STORAGE TANKS AND PIPING

e. Actual Data : UTRS-500 500GALLON DIESEL FUEL DAY TANK SYSTEM, UL-142

Check cracked and worn areas and delamination for molded plastic tanksXX
Check water at the lowest possible point within the primary tank (fuel tanks only) and remove any water foundXX
Check any chemical degradation for tanks containing other products.XX
Check any evidence of liquid (product or water) in the interstitial space (double-walled tanks) or containment areaXX
Check all drain valves secured in the closed position when not in use and all tank openings properly sealedXX
Check the piping connections tight and alignedXX
Check the spill basket clean and functionXX
Check the liquid level gauge readable and in good conditionXX
Check any obstructions or restrictions and emergency ventsXX
Check any operational malfunctions of ancillary equipment (pumps, gauges, etc.)XX
Check any release from the tank – includes visible signs of leakage around the tank, concrete pad, containment area, ring wall, or groundXX
Check a clear path to the tank and containment area, and are gates/doors to the containment area operable and in good conditionXX
Check a complete spill kit availableXX
Check any conditions that may be a fire or safety hazard, or pose an environmental hazardXXX
14DUCT
(DS-DUCT SILENCERS)Chcek cleaning conditionXXGoogle searching
Check and remove using wire brush and recoat with zinc-rich spray paintXX
Check waterproofing sealant on all seamsXX
Check the deteriaration and replace silencer 10-year intervalsXX
15ROOM THERMOSTAT FOR VAV CONTROLCheck temperature displayXXO&M Manual
\\humpa710N501003\DPW_O&M\UTILITY & ENERGY BRANCH\O&M Manual\SPT040, One Stop Building and Bus Station, O&M Manuala. Item No :23 09 23 - 148

b. MFR & Model : JOHNSON CONTROLS MODEL # LN-VSTAT-1

c. Address : Johnson Controls Inc.

Business Unit: Building Efficiency Location Type: Industrial/Commercial 9610 Ridgehaven Court Suite C San Diego, CA 92123 USA Phone: 858-268-0770 Fax: 858-268-4385 www.johnsoncontrols.com/

Check damage on surfaceXX
Check Temperature devision functionlly. (± 2° F differencial)XX
Check communication with VAVXX
Check seting point ChangeXX
Check occupancy OverrideXX
16Finned Tube Radiator
Check Hot water circulationXXXXO&M Manual
\\humpa710N501003\DPW_O&M\UTILITY & ENERGY BRANCH\O&M Manual\SPT040, One Stop Building and Bus Station, O&M Manuala. Item No : 23 52 00 - 74

b. MFR & Model : SEIL AIR CONDITION CO.,LTD

c. Address : 518-1, Songmun-ri, Yangji-myeon, Cheoin-gu, Yongin-si, Gyeonggi-do, Korea

TEL : 031-337-0961

E-MAIL : master@seilsac.co.kr www.seilsac.co.kr

d. POU : HEATING BOILERS

Check Valve opening/closing conditionXXXXX
Check/ remove AirXX
Check Horizontal levelXX
Check Other exterior conditionsXXX
Check Air inlet conditionsXXXXXX
17CALIBRATED TRIPLE DUTY VALVECheck valve, including painting, gasket and sealentXMFR & Model: TACO #MPV 040-4 TACO #SD030025repair as required
18Damper
(Outside Air intake Louver W/Birdscreen & motorized Damper with panel filter, STAINLESS STEEL BACKDRAFT DAMPER W/STAINLESS STEEL COUNTER WEIGHT)Check Trunion bearings, shafts, cleaned, etcXX1. OUTSIDE AIR DAMPER ACTUATOR; MFG: Honeywell Johnson Controls, Model # MS7505A2130, O&M Manual.

2. MOTORIZED DAMPER, VARIOUS SIZE, MFG: Sangmi Air tech, Model: AT-4166-SS-0, O&M Manual.

Check blades & adjustmentsXX
Check damper motors cycle, anchorageXX
19ET
(EXPANSION TANK)Check pre-charge is within the valve indicated on the labelXXMFR & Model: #1000-L, d. POU: tem #ET-2

MFG: AMTROL, Model: ST-20VC. O&M Manual.

Check damage, corrosionXX
Check/ clean the external portions of tankXX
20ES
(EMERGENCY SHOWER & EYE WASH )Check/ replace defective equipment (push paddle, etc)XMFR & Model: ACORN SAFETY - #S2320-HFC-AL1 /#TMV33

O&M Manual

Check/ clean strainerXReplace as required
Check eye wash spray nozzle caps with ball valve, actuating assemblyX
Check inlet pressureX
21CIRCUIT SETTER BALANCING VALVECheck/ clean inlet strainersXXMFG: Bell & Gosstt, Mode: Circuit Setter Plus, O&M Manual.
22RANGE HOODCheck/ replace the charcoal filterXXMFR & Model: Broan / # 40000, POU: For Equipment RH-1 (barracks Kitchen rm), O&M Manual.
23VD
(VOLUME DAMPER)Check damper motors, actuators, and mounting boltXXMFG: DAEHAN KIUP, Model: DH-Volume Damper(VDP).

O&M Manual.

Check linkages from actuatorsXX
Check/ adjust Blades operation (Dirt, soot lint, etc.)XXReplace blade, if needed
Check/ replace blade edge and side sealsXX
Check pins, straps, bushings (bearings) for wear, rust or corrosionXX
Check/ lubricate all mechanisms and moving partsXX
Check caulking conditionXX
24Refrigerent Leak Defection SystemCheck/ calibrate sensorXXB#12410/ O&M MANUAL #3-3303

MFG & MDL: Honeywell & #301-EM-RFSA-US3/#301-EMRP-RFSA/ #301-IRFS-R-134A/#301-C-DLC-BIP/PS-24-150-N12/#83219/#888888 https://honeywell.com

25LAVATORY, SINK AND BASINS, BATHTUBES AND SHOWERS, URINALlavatory: check unsanitaryXTM 5-610, Drawing for S-12400repair or replace as required
lavatory: check broken, leaks, missing, material defectsX
lavatory: check insecurely fastenedX
lavatory: check splinteredX
lavatory: check paint or protective coatingX
lavatory: check flush valve for improper functioningX
Sinks and basins: check unsanitary, odorsXrepair or replace as required
Sinks and basins: check broken and leaksX
Sinks and basins: check faucet for worn washersX
Sinks and basins: check traps and drains for dirty, clogged, corrosion, greaseX
Sinks and basins: check stopper for missing or deterioratedX
Bathtubs and showers: check hazards, leaks and unsanitary conditionsXrepair or replace as required
Bathtubs and showers:check insecurely fastenedX
Urinals: check unsanitary, leaks, broken and insecurely fastenedXrepair or replace as required
Urinals: check missing strainerX
Urinals: check flush valve for improper functioning, broken and damagedX
Piping: check external rust, leakage, clogging, loose connectionsXrepair or replace as required
Piping: check insufficient water flowX
Piping: check water hammerX
Piping: check solid accumulation in strainersX