L E G E N D
M-1
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
BELL AND SPIGOT
TRAP, ELECTRIC (INDICATE TYPE)
SOLVENT CEMENT
REDUCER, ECCENTRIC (STRAIGHT, INVERT)
REDUCER, ECCENTRIC (STRAIGHT, DOWN)
FIRE DEPARTMENT CONNECTION
M E C H A N I C A L M A T E R I A L I N D I C A T I O N S & S Y M B O L S
TEE, OUTLET DOWN
ANCHOR, MAIN
BUTTERFLY
AIR LINE
valves : (for selective actuators)
GATE, ANGLE
PLUG VALVE
GATE, GLOBE
THREE WAY
CONTROL
DPT DEWPOINT TEMPERATUREAMERICAN WIRE GAUGEAWG
CENTIGRADE
CAPACITY
BRAKE HORSEPOWER
BAROMETER(-TRIC)
BOILING POINT
PRESSURE, BAROMETRIC
COOLING LOAD
COEFFICIENT
CUBIC METER PER HOUR
COUNTER CLOCKWISE
CLASSIFICATION
CAST IRON PIPE
CHILLED WATER
CIRCUIT
CUBIC METER
COMPRESSOR
CONTINUE
CONNECTIONCONN
CONT
CU M
CPRSR
CLASS
CLG LOAD
COEF
CMH
CKT
CIP
CHW
CCW
C
CAP
BP
BARO PR
BARO
BHP
FA FACE AREA OR FRESH AIR
FHC
FLA
FHY FIRE HYDRANT
FULL LOAD AMPERES
FIRE HOSE CABINET
EFF
EWT
EXPJT
EVAP
EP
EQPT
ESP
ENT
ECON
EDR
EAT
ECC
DX
DPDT
DPV
EFFICIENCY
EXPANSION JOINT
EXTERNAL STATIC PRESSURE
EVAPORAT (-E,-ING,-ED,-OR)
ENTERING WATER TEMP
EXPLOSION PROOF
ENTERING
EQUIPMENT
DRY PIPE VALVE
DOUBLE POLE DOUBLE THROW
ENTERING AIR TEMPERATURE
EQUIVALENT DIRECT RADIATION
DIRECT EXPANSION
ECONOMIZER
ECCENTRIC
air conditioning and refrigeration
AIR COOLED
ALARM CHECK VALVE
AIR CONDITION UNIT (S)
AVERAGE
APPROXIMATE
AMPERE(AMP, AMPS)
AIR HANDLING UNIT
ALTITUDE
AMBIENT
ALUMINUM
APPARATUS DEW POINT
AIR CONDITION (-ING,-ED)
AIR COOLED CONDENSING UNIT
APPROX
AVG
AMP
AMB
AIR COND
ALT
AL
AHU
ACCU
ACLD
ACU
ACV
ADP
C/HWS
C/HWR
CHS
CHR
D
RS
RL
RD
(NAME)
M
CU MM
DIAG
DO
DIV
DIFF
DB
DIA or
DBT
CW
Cv
CWP
DECIBEL OR DRY BULB
DRY BULB TEMPERATURE
DIAGRAM
DIVISION
DIESEL OIL
DIFFERENCE
DIAMETER
DEGREE
o
CUBIC MILLIMETER
COEFFICIENT, VALVE FLOW
CLOCKWISE OR COLD WATER
CIRCULATING WATER PUMP
HOT/CHILLED WATER SUPPLY
HOT CHILLED WATER RETURN
CHILLED WATER RETURN
CHILLED WATER SUPPLY
DRAIN
REFRIGERANT SUCTION
REFRIGERANT LIQUID
CONTROL AIR MAIN
PIPE TO BE REMOVED
REFRIGERANT DISCHARGE
GLOBE
GATE
A
BALL
SQ
PLUMBING
LIQUID LINELL
PLMB
LINEAR METER
LITERS PER DAY
LITERS PER HOUR
LAUNDRY TRAY
LITERS PER SECOND
LEAVING WATER TEMPERATURE
NOT APPLICABLE
NOISE CRITERIA
NORMALLY CLOSED
METERS PER SECOND
METERS PER HOUR
MINIMUM OR MINUTE
NORMALLY OPEN
NATIONAL TAPER PIPE (THREAD)
NOT IN CONTRACTNICKG KILOGRAM
KILOGRAM PER SQ. CENTIMETER (ABSOLUTE)
KILOGRAM PER SQ. CENTIMETER
KILOGRAM PER SQ. CENTIMETER (GAUGE)KG/SQ CM G
KG/SQ CM A
KG/SQ CM
NO
N.O.
NPT
NUMBER
KILOCALORIE PER HOUR
THERMAL CONDUCTIVITY
JOULE
IRON PIPE SIZE
ISOMETRIC
DIAMETER, INSIDE
KCAL/HR
K
J
ISO
ID
IPS
HEAD
HERTZ
HORIZONTAL
HORSEPOWER
HOT WATER
HOT WATER HEATER
HOUR(S)
MERCURY
HORIZ
HZ
HW
HWH
HP
HR
HD
HG
MAX MAXIMUM
NC
N/A
N.C.
MM
MPH
MPS
MIN
MILLIMETER
M
LT
LWT
LM
LPH
LPS
LPD
METERS
SUPPLY AIRSA
SANITARY
SUBMERSIBLE
SCHEDULE
SAN
SCH
SBM
UH
UR
U
QUART
QUANTITY
PERCENT
PETROLEUM, OIL AND LUBRICANTS
POINT OF CONNECTION
PARTS PER MILLION
PRESSURE REDUCING VALVE
RADIATOR
REFRIGERANT (12, 22, ETC)
REVOLUTIONS PER MINUTE
REFRIGERATION TON
THERMAL RESISTANCE
RETURN AIR
RELATIVE HUMIDITY
RT
RH
RPM
R12, R22
R
RA
RDTR
QT
QTY
PPM
PRV
POC
POL
THERM
TONS
TYP
THK
TSTAT
TD
TEMP
SYM
STOR
SUCT
STD
STL
SSU
SSF
SST
ST
FLEXIBLE CONNECTOR
EXPANSION JOINT
EXPANSION LOOP
FLOWMETER, ORIFICE
KILOGRAM PER SQ. METER (GAUGE)
KILOGRAM PER SQ. METER (ABSOLUTE)
KILOGRAM PER SQ. METER
STRAINER, BLOW OFF
PUMP (INDICATE USE)
PRESSURE GAUGE AND COCK
PRESSURE SWITCH
KILOWATT HOUR
LATENT HEAT
LEAVING AIR TEMPERATURE
FLOWMETER, VENTURI
A B B R E V I A T I O N S
FIBERGLASS REINFORCED PLASTIC
FEMALE PIPE THREAD
GRAMS
HOSE BIBB
FACE VELOCITY
FEED WATER PUMP
GAGE OR GAUGE
GALVANIZED STEEL
FIXTURE
GA
GALVS
HB
GR
FXTR
FVEL
FWP
FLUSH VALVE
FREQUENCY
FUEL OILFO
FREQ
FRP
FPT
FV
LAT
LH
LG
LBS
L
LAV
KWH
LENGTH
POUNDS
LITERS
LAVATORY
KG/SM G
KG/SM A
KG/SM
KJ
KW
KILOJOULE
KILOWATT
P
PS
FS
STRAINER
FLOW SWITCH
OFM
VFM
EJ
BALL JOINT
(2-WAY SHOWN)
OUTSIDE AIR
NOT TO SCALE
OUTSIDE AIR INTAKE LOUVER
POLE
OXYGEN
PASCAL
PRESSURE DROP OR DIFFERENCE
PHASE (ELECTRIC)
PRESSURE GAGE
OUTSIDE SCREW & YOKE
DIAMETER, OUTSIDE
PH
PG
Pa
PD
P
OXY
OS&Y
NTS
OA
OD
OAIL
SPR
SP
SPEC
SPDT
SM
SLPD
SLPS
SLPH
SEC
SF
SG
SH
SL
sprinkler
DRY-PIPE VALVE
PRE-ACTION VALVE
SIDEWALL SPRINKLER
ALARM CHECK VALVE
PENDENT SPRINKLER
UNION, SCREWED
UNION, FLANGED
TEE, SINGLE SWEEP
UPRIGHT SPRINKLER
COLD WATER
HOT WATER SUPPLY
HOT WATER RETURN
CONDENSATE DRAIN ABOVE
SANITARY DRAIN
ACID WASTE
CHEMICAL SUPPLY PIPES
FLOOR DRAIN
CONDENSATE DRAIN BELOW
FLOOR OR GRADE
FUNNEL DRAIN, OPEN
SURFACE CLEANOUT
VENT THRU ROOF
FLOOR CLEANOUT
PIPE SLEEVE
HOSE BIBB
BACKFLOW PREVENTER
PIPE SLEEVE WITH FIRE STOPPING
FLOOR SINK (200mm x 200mm)
PITCH OR PIPE, UP(U), DOWN(D)
FLOOR OR GRADE
(NAME)E
VAC
A
HWS
MTWR
HWR
MTWS
CR
CS
FOG
FOR
FOS
FOV
FOD
MU
VPD
PC
BBD
MPC
LPC
LPS
MPS
JWS
JWR
FCO
LOW TEMPERATURE HOT WATER RETURN
LOW TEMPERATURE HOT WATER SUPPLY
MEDIUM TEMPERATURE HOT WATER RETURN
MEDIUM TEMPERATURE HOT WATER SUPPLY
VACUUM (AIR)
COMPRESSED AIR
EXISTING PIPE
FUEL OIL RETURN
FUEL OIL SUPPLY
CONDENSATE WATER RETURN
CONDENSATE WATER SUPPLY
FUEL OIL GAUGE
PLAN ELEV.
BFP
200mm x 200mm
SCO
FUEL OIL TANK VENT
PUMPED CONDENSATE
BOILER BLOW DOWN
VACUUM PUMP DISCHARGE
FUEL OIL DRAIN
MAKE UP WATER
LOW PRESSURE STEAM
JACKET WATER SUPPLY
JACKET WATER RETURN
LOW PRESSURE CONDENSATE
MEDIUM PRESSURE CONDENSATE
MEDIUM PRESSURE STEAM
ACID
(NAME)
FD
CD
G GAS
CD
VENT
PIPING
heating plumbing
MOTOR ELECTRIC
CHECK, NON-SLAM
QUICK CLOSING, FUSIBLE LINK
SQUARE HEAD BALANCING COCK
PRESSURE REDUCING
SQUARE HEAD BALANCING COCK
HOSE END DRAIN
CONTROL, PNEUMATIC-ELECTRIC
CONTROL, ELECTRIC-PNEUMATIC
ALIGNMENT GUIDE
ANCHOR, INTERMEDIATE
AIR VENT, AUTOMATIC
AIR VENT, MANUAL
W/ MEASURING TAP
MV
AVV
S AIR SEPARATOR
S
R
SAFETY
QUICK OPENING
RELIEF
PE
LOCK SHIELD
NEEDLE
valves, special duty :
EP
M
S
CHECK, SWING
SOLENOID
DIAPHRAGM
LATERAL
TEE, OUTLET UP
REDUCER, CONCENTRIC
TEE
CONNECTION, TOP
ELBOW, TURNED UP
CONNECTION, BOTTOM
ELBOW, TURNED DOWN
fitting :
FLANGED
WELDED
R
SOLDERED
CAP
BUSHING
THERMOMETER
SCREWED
THERMOSTAT, ELECTRIC
valve actuators dampers
SQUARE
WATTHOUR OR WATER HEATER
HEAT TRANSFER COEFFICIENT
UNIT HEATER
URINAL
TEMPERATURE DIFFERENCE
TONS OF REFRIGERATION
THERMOMETER
THERMOSTAT
TYPICAL
THICKNESS
TEMPERATURE
SYMBOL
STAINLESS STEEL
SAYBOLT SECONDS FUROL
SAYBOLT SECONDS UNIVERSAL
STORAGE
SUCTION
STANDARD
STEEL
STEAM
WIDTH
WEIGHT
WASHER
WATERPROOF
WATER CLOSET
WATER-COOLED
W/
WT
WTRPRF
WSHR
WITH
WD
WH
WC
WCLD
FIRE DAMPER (PROVIDE ACCESS DOOR)
ELECTRIC MOTOR OPERATED DAMPER
SMOKE DAMPER (PROVIDE ACCESS DOOR)
PRESSURE, DYNAMIC(VELOCITY)
WET BULB TEMPERATURE
STATIC PRESSURE
LPD, STANDARD CONDITIONS
LPS, STANDARD CONDITIONS
LPH, STANDARD CONDITIONS
SINGLE POLE DOUBLE THROW
SPECIFICATION
SPRINKLER
SQUARE METER
SPECIFIC GRAVITY
SECOND
SAFETY FACTOR
SENSIBLE HEAT
SENSIBLE LOAD
VOLUME
VERTICAL
VISCOSITY
WET BULB
VENTILATION
WB
WBT
W
VP
WATT
VOL
VISC
VENT
VERT
VACUUM
VALVE
VARIABLE AIR VOLUME
VELOCITY
VOLTV
VAC
VLV
VAV
VEL
SD
AD
M
VD
AD FD
S
BDD
PNEUMATIC OPERATED DAMPER
SPLITTER DAMPER
BACKDRAFT DAMPER
MANUAL VOLUME DAMPER
DUCT SECTION, POSITIVE PRESS., FIRST
EXHAUST AIR GRILLE OR REGISTER, CEILING
DUCT SECTION, NEGATIVE PRESS., FIRST
ACCESS DOOR, VERTICAL OR HORIZONTAL
CHANGE OF ELEVATION, RISE(R), DOWN(D)
COWL, (GOOSENECK) AND FLASHING
F S
FC
TRANSITION
DETECTORS, FIRE AND/OR SMOKE
TURNING VANES
FLEXIBLE CONNECTION
SOUND ATTENUATOR
FLEXIBLE DUCT
AD
R
810mm x 400mm
810mm x 400mm
810mm x 400mm
FIGURE IS ON TOP
ACOUSTICAL LINING
DIRECTION OF FLOW
FIGURE IS ON TOP
(600mm x 300mmH, 472 LPS)
TG 600/300
NECK DIAMETER)
DIFFUSER, LINEAR
CEILING DIFFUSER, ROUND TYPE (200mm
CEILING DIFFUSER, SQUARE TYPE
EXISTING WORK TO BE REMOVED
200mm NCD
SUPPLY AIR GRILLE OR REGISTER, CEILING
EXHAUST AIR GRILLE OR REGISTER, CEILING
SUPPLY AIR GRILLE OR REGISTER, SIDEWALL
RETURN AIR GRILLE OR REGISTER, CEILING
TRANSFER GRILLE ASSEMBLY
LOUVER, DOOR OR WALL
UNDERCUT DOOR (13mm, 47.2 LPS)
DOOR GRILLE (300mmx150mmH)
(500mmWx300mmH, 94.4 LPS)
500/300L
47.2
UC 13mm
300x150
DG
94.4
SR
RR
RG
SG
EG
ER
SR
SG
DUCT WORK
grilles, registers and diffusers :
RLA
LRA
RATED LOAD AMPS
LOCKED ROTOR AMPS
REMOVE EXIST WORK(R)
(E) EXISTING WORK TO REMAIN.
OR END OF DEMOLITION WORK
POINT OF CONNECTION NEW TO EXISTING
SYMBOLS
MECHANICAL MATERIAL INDICATIONS &
REPAIR FIRE ALARM SYSTEM / INSTALL
BUILDING TRANSMITTERS AND REPAIR
BUILDING S-81, CAMP CASEY(PH#1)CHONG,ST
185600
M-2
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
GENERAL NOTES & SCOPE OF WORK
GALVANIZED STEEL PIPE WITH CAST IRON DRAINAGE FITTINGS.
ABOVEGROUND VENT PIPING WILL BE HUBLESS CAST IRON PIPE AND FITTINGS OR
LAGGED COPPER PIPING. SOIL, WASTE, AND VENT PIPING WILL BE CAST IRON SOIL PIPE.
WITH TIN-ANTIMONY SOLDERED ENDS. HOT WATER PIPING WILL BE INSULATED AND
TYPE. WATER PIPING SHALL BE COPPER. FITTINGS SHALL BE CAST BRONZE OR COPPER
13. PLUMBING FIXTURES SHALL BE OF COMMERCIAL GRADE AND OF WATER CONSERVING
MAKING ALL NECESSARY DUCT CONNECTIONS FUNCTION AS ORIGINALLY INTENDED.
INSTALLATION, REMOVE THE EXISTING DUCTWORK AND REPLACE WITH NEW DUCTWORK,
EXISTING DUCTWORK ELEVATION AND LOCATION IS IN CONFLICT WITH THE NEW PIPING
MUST COORDINATE WITH THE EXISTING DUCTWORK ELEVATIONS AND LOCATION. IF THE
12. PRIOR TO THE INSTALLATION OF NEW HVAC AND PLUMBING PIPING, THE CONTRACTOR
CONTRACTING OFFICER FOR APPROVAL.
CONTRACTOR ACCORDING TO ACTUAL FIELD CONDITIONS AND SUBMITTED TO THE
FIELD CONDITIONS. SUCH DETAILS SHALL BE PREPARED IN THE FIELD BY THE
11. SOME DETAILS SHOWN ON THE CONTRACT DRAWINGS MAY NOT MATCH EXACTLY TO THE
SUCH AS ANCHORS, HANGERS/SUPPORTS, ETC.
10. ALL HVAC PIPING/DUCTWORK TO BE REMOVED SHALL INCLUDE ALL ITS ACCESSORIES,
PATCHED OR RESTORED TO MATCH THE ADJACENT SURFACE OR AREA.
9. ANY OPENING RESULT FROM THE REMOVAL WORK THAT IS NOT TO BE REUSED SHALL BE
DUCTWORK SHALL MEET THE REQUIREMENTS OF SEAL CLASS C.
ACCORDING TO SMACNA STATIC PRESSURE CONSTRUCTION CLASS 500PA AND
8. ALL SUPPLY, RETURN, AND EXHAUST AIR DUCTWORK SHALL BE CONSTRUCTED
AREA.
DUCTWORK SHALL BE PATCHED OR RESTORED TO MATCH THE ADJACENT SURFACE OR
7. ALL WALL/FLOOR/ROOF OPENINGS RESULTING FROM THE REMOVAL OF PIPING AND
SHOP DRAWING SHALL NOT BE THE EXACT DUPLICATION OF THE CONTRACT DRAWING.
6. NO MECHANICAL WORK CAN BE STARTED WITHOUT AN APPROVED SHOP DRAWING. A
5. CONCRETE REMOVAL AND RESTORATION SHALL CONFORM TO SPEC.
4. ANY PIPES THAT PENETRATE FIRE RATED WALLS (EXISTING/NEW) SHALL BE SEALED PER SPEC.
OR REPLACED BY THE CONTRACTOR.
DAMAGES DUE TO THE WORK PERFORMED UNDER THIS CONTRACT SHALL BE REPAIRED
DAMAGE THE EXISTING EQUIPMENT, NEW EQUIPMENT, DUCTWORK, PIPING, ETC.
3. CONNECTIONS TO EXISTING SYSTEMS SHALL BE DONE IN SUCH A MANNER AS NOT TO
APPROXIMATE AND SHALL BE VERIFIED AT THE JOB SITE.
2. LOCATION AND SIZES OF EXISTING EQUIPMENT, DUCTWORK, PIPING, ETC. ARE
CORRECTIONS FOR THE CONTRACTING OFFICER'S APPROVAL.
CONTRACTING OFFICER'S REPRESENTATIVE WITH RECOMMENDATIONS FOR PROPER
DISCREPANCY IS DETECTED, IT SHOULD BE BROUGHT TO THE ATTENTION OF THE
EXISTING CONDITIONS, EQUIPMENT, FINISHES, ETC., PRIOR TO START OF WORK. IF ANY
1. THE CONTRACTOR SHALL VISIT THE SITE AND SHALL FAMILIARIZE HIMSELF WITH THE
GENERAL NOTES
PLUMBING WORK
HVAC SYSTEM
SCOPE OF WORK
1.
REPAIR BY REPLACEMENT OF EXISTING DETERIORATED HOT/CHILLED WATER CIRCULATION PUMP, EXPANSION TANK, AIR SEPARATOR, AND
ASSOCIATED PIPING WITH NEW.
REPAIR BY REPLACEMENT OF EXISTING DETERIORATED DRAIN AND HOT/CHILLED WATER PIPING THROUGHOUT THE BUILDING WITH NEW.
REPAIR BY REPLACEMENT OF EXISTING MECHANICAL ROOM HEATING SYSTEM WITH NEW HOT WATER UNIT HEATERS.
ALL MECHANICAL SYSTEMS SHALL BE TESTED, ADJUSTED, AND BALANCED BY THE CONTRACTOR IN STRICT ACCORDANCE WITH
APPLICABLE SECTIONS OF DIVISION 15 - MECHANICAL O&MA STANDARD TECHNICAL SPECIFICATIONS FOR MISCELLANEOUS PROJECTS, KOREA.
THE HVAC TESTING, ADJUSTING, AND BALANCING (TAB) REPORT SHALL BE SUBMITTED TO THE PROJECT COR FOR GOVERNMENT REVIEW AND
APPROVAL.
2.
3.
4.
5.
6.
7.
8.
1.
2.
3.
4.
5.
6.
REPAIR BY REPLACEMENT OF EXISTING DETERIORATED BATHROOM PLUMBING FIXTURES, INCLUDING WATER CLOSETS, LAVATORIES, AND ASSOCIATED PIPING, WITH NEW.
FUEL OIL PIPING WITH NEW.
REPAIR BY REPLACEMENT OF EXISTING DETERIORATED HOT WATER BOILER, CONC PAD, CONTROL AND ASSOCIATED WATER AND
WITH NEW.
REPAIR BY REPLACEMENT OF EXISTING DETERIORATED FAN COIL UNITS, OUTSIDE AIR INTAKE BOXES, CONTROLS AND ASSOCIATED PIPING
REPAIR BY REPLACEMENT EXISTING BACK FLOW PREVENTER (BFP) AND PRESSURE REDUCING VALVE (PRV) ASSEMBLY, INCLUDING PIPE
SUPPORTS, HOSE BIBB AND WALL HYDRANT.
REPAIR BY REPLACEMENT OF EXISTING DETERIORATED OIL FIRED DOMESTIC HOT WATER HEATER, STORAGE TANK, AND CIRCULATION PUMPS
WITH NEW OIL FIRED DOMESTIC HOT WATER HEATER, WATER CIRCULATION PUMPS, CONC. PADS AND ASSOCIATED WATER, CONTROLS AND FUEL OIL PIPING.
REPAIR BY REPLACEMENT OF EXISTING DETERIORATED BATHROOM EXHAUST FANS AND DUCTS WITH NEW.
REPAIR BY REPLACEMENT OF EXISTING SINK AND VALVE BOX WITHIN THE LAUNDRY ROOM WITH NEW.
REPAIR BY REPLACEMENT OF EXISTING DETERIORATED EXHAUST FANS WITHIN THE MECHANICAL ROOM WITH NEW.
9.
10.
REPAIR BY REPLACEMENT OF EXISTING DETERIORATED ALL DOMESTIC HOT AND COLD WATER PIPING WITH NEW.
REPAIR BY REPLACEMENT OF EXISTING DETERIORATED ALL SEWER, VENT, FLOOR DRAIN AND CLEANOUT PIPING.
REPAIR BY REPLACEMENT OF EXISTING DETERIORATED WATER CHILLER, VALVE BOX AND ASSOCIATED PIPING WITH NEW.
REPAIR BY REPLACEMENT OF EXISTING ROOF GOOSENECK, SPLIT AIR CONDITIONING AND RANGE HOOD WITH NEW.
SPRINKLER WORK
REPAIR AND MAINTENANCE WORK(K-WORK)
CONTRUCTION WORK(L-WORK)
1. INSTALL FIRE PROTECTION SYSTEM.
REPAIR FIRE ALARM SYSTEM / INSTALL
BUILDING TRANSMITTERS AND REPAIR
M-3
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
MECHANICAL EQUIPMENT SCHEDULE - 1
P
MOTOR
VOLT/PH/HZ
ITEM NO Q'TY
PUMPS
SERVICE TYPE
CAPACITY
(LPS)
HEAD(kPa)
HP
RPM REMARKS
115/1/60
PIPE MOUNTED
INLINE CENTRIFUGAL TYPE
DOMESTIC HOT WATERP
1 0.76 44.9 1/4 1,725
CIRC PUMP
1,750200/3/6021.261 179.4
HOT/CHILLED WATER
TO INCLUDE NOTES7.5 kw x 1 EA
WATER CHILLER
CHILLER
NOTE:
Q'TY
AIR-COOLED SCROLL TYPE
WC
(LPS)
FLOW RATE
1.26BLDG COOLING SYSTEM
ITEM NO SERVICE TYPE
(TON)
COOLING CAP
6.8 TON 0.2 Kw
CONDENSER FANSCOMPRESSORS
(A-1)
DROP(KPa)
27.2
WATER PRESSURE
TEMP.
LEAVING WATER
POWERQTY
VOLT/PH/HZ
220/3/60
POWERQTY
2 220/3/60
VOLT/PH/HZ
REMARKS
REQUIRED
POWER
INPUT (Kw)
7.5
220/1/6020.0 82.16.723.9 16.9
3,130188.7 1,922 0.13 3,566 0.08 45
REMARKS
SUPPLY FAN
VOLT/PH/HZLPS
HEATING CAPACITY
(Watts)(DEG.C)
EWTEATHEAT CAP
(WATTS) (DEG.C)
LPS
COOLING CAPACITY
AIR
(LPS)
CAPACITY
FAN COIL UNIT
T Y P ESERVICEQTY.
WBDB
EWT
(WATTS)(WATTS)
TOTAL SENSIBLE
(DEG.C)
FCU
ITEM NO
7 EACH BEDROOM
VERTICAL CABINET
FLOOR MOUNTED TYPE
ESP
(Pa)
37.4
MAX
WPD
(Kpa)
28.4
MIN. OA
SETTING
(LPS)
28.3
FCU
2 FLOOR MOUNTED TYPE
VERTICAL CABINET
2 LAUNDRY & CORRIDOR
CHILLED/HOT WATER COIL
14.7 0.031,4150.101,495141.5 2,417 16.9
23.9 6.7 82.120.0 --
NOTES
220/1/60
POWER
B
82.1
BLDG HEATING
PRESS
WORKING
206.8
(kPa)
VOLT/PH/HZ
115/1/601/3 HP
OIL BURNER
TYPESERVICE
GROSS
(kW)
INPUT
77.6
Q'TY
ITEM NO
SUPPLY
TEMP
9.1
RATE
FIRING
(LPH)
PACKAGED OIL FIRED
FIRE-TUBE TYPE
REMARKS
SYSTEM
BLOWER MOTOR
NOTES:
REMARKS
4&2 3
HOOD SIZE
POWER VOLT/PH/HZ
12.0 AMPS
SERVICE
75.5
(LPS)
CAPACITY
FAN FAN MOTOR
ITEM NO Q'TY
RANGE HOOD
INCLUDE4
FE
3 BUILT-IN CONTROL SWITCH21 WASHABLE FILTER LIGHTING(75W)
115/1/60
RH
TYP MODULE &
STAINLESS STEEL
HOOD VENTED TYPE
W/BACKDRAFT DAMPER
TYPE
750Wx450D
(MM)
DAY ROOM
4 PREFABRICATED ROOF CURB.
BIRDSCREEN2
3 MANUAL BACKDRAFT DAMPER
DISCONNECT SWITCH1
NOTE :
REMARKSVOLT/PH/HZHP
RPM(Pa)
ESP FAN MOTOR
(LPS)
AIR CAP
TYPESERVICE
FANS
Q'TYITEM NO
EF
115/1/601/483262.3353.91
MECH ROOM
EACH BATH
115/1/60
67562.323.67 53
CENTRIFUGAL FAN
CEILING MOUNTED, DIRECT DRIVEN,
CEILING GRILLE
WATTROOM
(110)2
EF
RECIRC PUMP
PIPE MOUNTED
INLINE CENTRIFUGAL TYPE
CENTRIFUGAL FAN
ROOF MOUNTED BELT DRIVE
R-410a
TYPE
REFRIGERANT
PER MANUFACTURER RECOMMENDATIONS.
ALL AC UNITS REFRIGERANT PIPING SHALL BE INSTALLED 1 CAPACITY SHALL BE BASED ON 35 DEG CN O T E S :
SPLIT AIR CONDITIONING UNIT
QTY. REMARKS
CONDENSER FAN
VOLT/PH/HZ
POWERPOWER QTY
OUTDOOR UNIT
POWER VOLT/PH/HZ
QTY
(KW)
COOLING CAP
(LPS)
INDOOR EVAPORATOR UNIT
COMPRESSORSERVICEITEM NO T Y P E
AIR CAP.
SHALL BE PROVIDED WITH LOW AMBIENT KIT.3
EFFICIENCY
MIN.
(SEER)
PACKAGED SPLIT AIR COOLED TYPECOMM ROOM
ACU
1 152.8
2.7
(0.8 TON)
1.1 FLA 115/1/60 1
7.5 RLA
40.0 LRA
1 115/1/600.6 FLA 10.0
HIGH WALL DUCT FREE SPLIT COOLING SYSTEM
WITH REMOTE ELECTRONIC CONTROLLER.
21 43
RECOVERY
FIRED TYPE
PACKAGED OIL
1,035
(Kpa)
PRESSURE
WORKING
DWH
VOLT/PH/HZ
BURNER CAPACITY
115/1/601
ITEM NO Q'TY
HOT WATER SYSTEM
SERVICE
BUILDING DOMESTIC
TYPE
(LPH)
RATE
1/3HP9.1
POWER
RATE
(LPH)
FIRING
60.0 55.5
SUPPLY
TEMP RISE
TEMP
REMARKS
M E C H A N I C A L E Q U I P M E N T S C H E D U L E - 1
DOMESTIC HOT WATER HEATER(OFF-SHORE)
HOT WATER BOILERS(OFF-SHORE)
QUANTITIES ARE SHOWN FOR ESTIMATING PURPOSE ONLY, THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING
ACTUAL QUANTITIES BASED ON THE CONTRACT DOCUMENT REQUIREMENTS.
GENERAL NOTE
REPAIR FIRE ALARM SYSTEM / INSTALL
BUILDING TRANSMITTERS AND REPAIR
M-4
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
MECHANICAL EQUIPMENT SCHEDULE - 2
M E C H A N I C A L E Q U I P M E N T S C H E D U L E - 2
406 x 1,148
ET
206.8
HOT/CHILLED
ACCEPTANCE TANK CAP.
(LITS)
R E M A R K S
(kPa)
PRESSURE
WORKINGTANK SIZE
(mmDIAx mmHGT)
TYPESERVICE
Q'TYITEM NO
EXPANSION TANKS
BLADDER
VERTICAL TYPE
AIR SEPARATORS
ITEM NO Q'TY
PIPE MOUNTED
SERVICE TYPE
PIPE SIZE
INLET OUTLET
REMARKS
TYPE1
AS
MAX. WORKING
PRESSURE (KPa)
1,035 W/BUILT-IN STRAINER50DIA 50DIA
QUANTITIES ARE SHOWN FOR ESTIMATING PURPOSE ONLY, THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING
ACTUAL QUANTITIES BASED ON THE CONTRACT DOCUMENT REQUIREMENTS.
GENERAL NOTE
HOT/CHILLED
WATER SYSTEM
WATER SYSTEM
REPAIR FIRE ALARM SYSTEM / INSTALL
BUILDING TRANSMITTERS AND REPAIR
BUILDING S-81, CAMP CASEY(PH#1)CHONG,ST
185600
AIR CAP.(LPS) VOLT/PH/HZHPRPM
1,600 208/1/601/100256.7
FAN CAPACITYBLDG
DASCHARGE
T Y P E
HORIZONTAL
ELECTRIC UNIT HEATER
QTY
MECH ROOM
SERVICE
TYPE
REMARKS
208/1/60
VOLT/PH/HZ
HEATING ELEMENT CAP
POWER(KW)
PROVIDE UNIT MOUNTED DISCONNECT SWITCH
AND UNIT MTD. THERMOSTAT.
NO
EUH
M-5
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
SCALE : 1 / 100-
M5
GROUND FLOOR HVAC PLAN
GROUND FLOOR HVAC PLAN
C/HWR
C /H
W S
C /H
W R
C/HWR
C/HWS
C/HWS
C/HWR
C/HWS
C/HWS
C/HWR
E A
C /H
W S
E A
E A
E A
E A
E A
E A
E A
C/HWS
TTTT
T T TT
T
C /H
W S
C /H
W R
R L
R S
E A
E A
E A
E A
E A
E A
EF
SEE
150x150
FCU
FCU
FCU
150x150
ROOF GOOSENECK
(TYP) SEE DETAIL
THERMOSTAT FOR FCU (TYP)
(FOR BEDROOM)
300x50 O.A INTAKE WALL BOX (TYP OF 4)
300x50 O.A INTAKE WALL BOX (TYP OF 3)
(FOR BEDROOM)
THERMOSTAT FOR FCU (TYP)
FCU FCU
FCUFCU
FCU
FCU
EF
EF EF
ACU
OACU
RH
RH
RH
1 1
RH
RH
RH
RH
25 DIA COND. DRAIN CONNECT TO
DOWNSPOUT NOZZLE SEE DETAIL
(TYP)
150x150
150x150150x150150x150
(TYP)
DOWNSPOUT NOZZLE SEE DETAIL
25 DIA COND. DRAIN CONNECT TO
25 25
SPILL ON MECH ROOM
FLOOR DRAIN
FLOOR DRAIN
SPILL ON MECH ROOM
BEDROOM
LAUNDRY
MECH ROOM
CORRIDORVEST VEST
BEDROOM
BEDROOM
BEDROOM
VIP BEDROOM
101 BEDROOM
BEDROOM
112 109
CLOSET
COMM
150x150
20 20 20 20
202020
M20
M23
FUEL OIL TANK(E)
F O
S
UNDERGROUND
- M6
CONC. PAD
CONC. PAD 1
WC
M23
REPAIR FIRE ALARM SYSTEM / INSTALL
BUILDING TRANSMITTERS AND REPAIR
M-6
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
M6 SCALE : 1 / 50
MECH ROOM HVAC PARTIAL PLAN
SEE
SEE
SEE
WATER CHILLER
CHEMICAL FEEDER
W/REMOVABLE FUNNEL
OIL FILTER (TYP.)
AUTO SAFETY SHUT-OFF VALVE (TYP.)
MODULATING 3-WAY
CONTROL VALVE
AS
P
FOR UH-1
HEATING THERMOSTAT
EXHAUST FAN
EF
200 DIA SMOKE STACK
W/ BAROMETRIC DAMPER
WC
W/ BAROMETRIC DAMPER
200 DIA SMOKE STACK
LAUNDRY
VENTILATION THERMOSTAT
20 20
INTAKE LOUVER W/BIRDSCREEN
TOP & BOTTOM
OPENING (TYP OF 2)
600x300 COMBUSTION AIR INTAKE
& MOTORIZED DAMPER
INTAKE LOUVER
600x300 OUTSIDE AIRUNDERGROUND DOUBLE WALL PIPING
40mm CHS/CHR PREFABRICATED
SEE DETAIL
AIR SEPARATOR
B
HOT WATER BOILER
DWH
DOMESTIC HOT WATER HEATER
CIRC PUMP
HOT/CHILLED WATER
1/50SCALE
DETAIL "A"
100 DIA DRYER VENT
SEE DETAIL
ET
EXPANSION TANK
W/BIRDSCREEN AND MOTORIZED DAMPER
400x200 O.A INTAKE LOUVER
ROOM
MECH
ROOM
MECH
600x300 COMBUSTION AIR INTAKE
OPENING
& MOTORIZED DAMPER
INTAKE LOUVER
600x300 OUTSIDE AIR
600x600 OUTSIDE AIR
INTAKE LOUVER W/BIRDSCREEN
OPENING
600x300 COMBUSTION AIR INTAKE
M
OA
OA
OA
T V
FS
F O
S
E
C/HWR
C/HWR
OA
TH
C H
S
CHS
CHR CHR
CHS
C H
S C
H R
EA
M21
MECH ROOM HVAC PARTIAL PLAN
F O
S
(UNDERGROUND)
CONNECT TO EXISTING FUEL OIL TANK
- M5
- M5
- M5
CONC. PAD
C O
N C P
A D
CONC. PAD
CONC. PAD
CONC. PAD
M20
REPAIR FIRE ALARM SYSTEM / INSTALL
BUILDING TRANSMITTERS AND REPAIR
BUILDING S-81, CAMP CASEY(PH#1)CHONG,ST
185600
EUH
ELEC. UNIT HEAER
M-7
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
M7-
CHILLED/HOT WATER CONTROL DIAGRAM
CONTROL EQUIPMENT SCHEDULE AND NOTES
SEQUENCE OF OPERATION, BOILER SYSTEM
CHILLED/HOT WATER CONTROL DIAGRAM,
O
O
C1
CHEMICAL FEEDER
W/REMOVABLE FUNNEL
THERMOSTAT
OUTDOOR
(COOLING)
(HEATING)
T
TEMPERATURE WITH REMOTE SETPOINT POTENTIOMETER. RESET
ONE SENSOR FOR HEATING MEDIUM, THE OTHER SENSOR OUTDOOR AIR
MEDIUM CONTROL POINT AUTOMATICALLY AS OUTDOOR TEMPERATURE FALLS.
CONTROL FOR THE BOILER HOT WATER HEATING SYSTEM. RAISES HEATING
LOW VOLTAGE, ELECTRONIC TYPE SHALL PROVIDE PROPORTIONAL RESET
REMOTE BULB ELECTRIC TYPE THERMOSTAT, STANDARD RESPONSE, SPDT
SWITCH MAKES CIRCUIT ON TEMPERATURE RISE OR FALL AS INDICATED,
CONTROL RANGE -18 TO +38 DEG C., 6.1M COPPER CAPILLARY TUBING,
DIFF.= 1.7 TO 5.6 DEG.C. ADJ. AND 8 AMPS AT 120VAC.
BOILER SYSTEM CONTROL EQUIPMENT SCHEDULE
HW RESET CONTROLLER (RC):
O.A. THERMOSTAT:
RATIO: 1.0 TO 1.0.
RESET CONTROLLER
OUTDOOR AIR TEMP.
OUTDOOR
SENSOR
TEMP.
CHILLED/HOT WATER PUMP CONTROL CIRCUIT
V
OARC
P
SENSOR
TEMP.
SUPPLY WATER
120V. SEE ELECTRICAL DWG
SEE ELEC DWG
H
T
OUTDOOR
THERMOSTAT
HOLDING COIL
PUMP STARTER
HOA SWITCH
AUTO
OFF
HAND
N
O/L'S
CONTACT
AUTO
AUXILIARY
BOILER & CHILLER CONTROL
C1
FLOW
SWITCH
C2
HAND
PACKAGED
CONTROLS
CONTROLS
PACKAGED
CHILLER
BOILER
SWITCH
SEQUENCE OF OPERATION
SCHEDULE.
CLOSES THEIR RESPECTIVE CONTACTS. BUILT-IN CONTROL OF WATER CHILLER SHALL
CHILLED/HOT WATER CIRC. PUMP STARTS AND RUNS DURING SUMMER SEASON.
SUMMER SEASON
LOW WATER CUT-OFF (BUILT-IN CONTROL) STOPS BURNER OPERATION WHEN
WATER LEVEL DROPS TO CUT-OFF SETTING AND MUST BE MANUALLY RESET.
HIGH LIMIT CONTROLLER (BUILT-IN CONTROL) STOPS BURNER OPERATION WHEN
VARIABLE HOT WATER SUPPLY TEMPERATURE IN ACCORDANCE WITH THE FOLLOWING RESET
PUMP ARE ENERGIZED DURING WINTER SEASON.
THE HEATING BOILER B-1,AND HOT/CHILLED
WINTER SEASON
OUTDOOR RESET CONTROLLER SHALL MODULATE 3WAY CONTROL VALVE TO MAINTAIN A
AND HOT WATER BOILER SHALL BE DE-ENERGIZED.
B.
A.
II.
B.
(60
E.
D.
C.
(20
I.
A.
60.0
H.W. TEMP.
82.2
15.6
-6.7
O.A. TEMP.
(180
(140
P
P
OPEN H.W VALVES (V-1) AND CLOSE C.W. VALVES (V-2) MANUALLY.F.
C. CLOSE H.W. VALVES (V-1) AND OPEN C.W. VALVES (V-2) MANUALLY.
T H0
T C0
AIR COOLED LIQUID CHILLER IS ENERGIZED WHEN RELAY RC AND CHS FLOW SWITCH (FS)
MAKE UP
ASSEMBLY
BACK FLOW PREVENTER
SET AT 0.84KG/CM
PRESSURE REDUCING VALVE
H W
S
HOT WATER BOILER
OIL BURNER W/RELAY
HOT WATER BOILER
CONTROL PANEL
B
P
OUTDOOR AIR THERMOSTAT
W/REMOTE BULB
OA TEMP.
SENSOR
SUNSHIELD
SUNSHIELD
T
H
AIR COOLED
WATER CHILLER
CIRC.PUMP
CHILLED/HOT WATER
BOILER PACKAGE
VALVE, PART OF
PRESSURE RELIEF
CHR
CHS
C H
S
H W
R
C H
R
AS
WC
E.A.
P
C/HWR
SENSOR C/HWS
FROM/TO BLDG. HEATING
AND COOLING SYSTEM
CHILLED/HOT WATER
EXPANSION TANK
M
OARC
RESET CONTROLLER
OUTDOOR AIR
PIPING LINE
COLD WATER
CONTROL VALVE
MODULATING 3-WAY
0-100 DEG. RANGE
TO MAKE ON FALL IN TEMP
V-1
V-1
V-2 V-2
TO
OT
C
OUTDOOR AIR THERMOSTAT
W/ REMOTE BULB
WIRE TO MAKE ON RISE
RANGE)
IN TEMP(0-100 DEG. C
STARTER
CHILLER FLOW SWITCH PROVIDED
BY CHILLER MFG. AND CONTRACTOR
INSTALLED
PANEL
CHILLER CONTROL
FS
CLOSEDOPEN
CLOSED
SUMMER WINTER
OPEN
VALVE
V - 2
V - 1
POSITION
ET
DEG C.
DEG C.
DEG F.)
DEG F.)
DEG C.
DEG C.
DEG F.)
DEG F.)
WHEN O.A. THERMOSTAT DROPS TO IT'S SETPOINT OF 15.5 C(60 F),
WHEN O.A. TEMP. RISES ABOVE 15.5 C (60 F), HOT/CHILLED WATER CIRC. PUMP
HOT WATER TEMPERATURE REACHES 98.9 C (210 F). AND REQUIRES MANUAL RESET.
WHEN O.A. THERMOSTAT RISES TO IT'S SETPOINT OF 23.9 C(75 F)
MAINTAIN CHILLED WATER SUPPLY TEMPERATURE AT 6.7 C (44 F).
SET AT 15.5 C WIRE
REPAIR FIRE ALARM SYSTEM / INSTALL
BUILDING TRANSMITTERS AND REPAIR
M-8
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
M8-
FAN COIL UNIT CONTROL DIAGRAM
NOT TO SCALE
M8-
SPLIT A/C UNIT CONTROL DIAGRAM
NOT TO SCALE
M8- NOT TO SCALE
HEATER CONTROL
A/C UNIT CONTROL DIAGRAM AND UNIT
FAN COIL UNIT CONTROL DIAGRAM, SPLIT
FACTORY PROVIDED WALL MOUNTED
SPACE THERMOSTAT
SWITCH(OFF-HIGH-MEDIUM-LOW)
UNIT MOUNTED 3-SPEED
MAINTAIN ROOM TEMPERATURE AT 23.9 DEG.C
IN WINTER OPERATION :
PIPE MOUNTED CHANGEOVER SWITCH
IN SUMMER OPERATION :
MAINTAIN ROOM TEMPERATURE AT 20 DEG.C
SPACE COOLING THERMOSTAT SHALL CYCLE FCU FAN "ON"OR"OFF" TO
FAN OPERATION IS CONTROLLED BY OCCUPANT VIA 3-SPEED FAN
THE OPERATING MODE (HEATING OR COOLING) SHALL BE DETERMINED BY
SPACE HEATING THERMOSTAT SHALL CYCLE FCU FAN "ON"OR"OFF" TO
COOLING THERMOSTAT
COMBINATION TYPE HEATING &
(WALL MOUNTED)
FLOOR MOUNTED FCU CONTROL
T
FCU:
CHANGEOVER SWITCH
PIPE MOUNTED AUTO
R Y
B
RA
CH
C
SA
SEQUENCE OF OPERATION
FCU UNIT
BOUNDARY
3-SPEED SWITCH
UNIT MOUNTED
M
L
OFF
H M
W/O LOCKING DEVICE
OA
(ONLY FOR FCU-1)
THERMOSTAT CONTROLLER
T C
ACU
ACU
(INDOOR A/C UNIT)
BUILT-IN CONTROL
PACKAGED A/C UNIT
1.
RS
RL
SEQUENCE OF OPERATION
COMM RM
PACKAGED AIR CONDITIONER FOR LAUNDRY ROOM.
ACU-1 "ON-OFF"TO MAINTAIN IT'S SETPOINT OF 25.5 DEG C.
SET "FAN-OFF-COOL"SWITCH TO"COOL"POSITION, SPACE THERMOSTAT CONTROLS
(OUTDOOR A/C UNIT)
PACKAGED A/C UNIT
(CENTURY-ACE MODEL CAT-100A OR
APPROVED EQUAL)
OA INTAKE DAMPER
SWITCH WALL MOUNTED. WHEN FCU IS OPERATED OPEN OA INTAKE DAMPER.
REPAIR FIRE ALARM SYSTEM / INSTALL
BUILDING TRANSMITTERS AND REPAIR
BUILDING S-81, CAMP CASEY(PH#1)CHONG,ST
185600
T SW
ON-OFF SWITCH
UNIT MOUNTED
THERMOSTAT &
M
GENERAL:
TO 29.4 DEC. C.
SETPOINT. SET THE THERMOSTAT AT 12.7 DEG.C.
THE THERMOSTAT SHALL CYCLE WALL HEATER TO MAINTAIN THERMOSTAT
SEQUENCE OF OPERATION
MANUFACTURER SHALL FURNISH THE CONTROL SYSTEM TO
INCLUDE UNIT MOUNTED THERMOSTAT AND ON-OFF SWITCH.
THE THERMOSTAT SHALL HAVE A TEMPERATURE RANGE OF 12.7 DEC. C
ELECTRIC UNIT HEATER
ELEC. UNIT HEATER CONTROL
M-9
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
- NOT TO SCALE
MECH. RM VENT SYS CONTROL DIAGRAM (EF-2) 3
- NOT TO SCALE
EF-1 CONTROL CIRCUIT (EACH BATH RM)
- NOT TO SCALE
DOMESTIC HOT WATER SYSTEM CONTROL DIAGRAM
DIAGRAM AND EF-1 CONTROL CIRCUIT
DIAGRAM, MECH. RM VENT SYS CONTROL
DOMESTIC HOT WATER SYSTEM CONTROL
P
SENSOR STRAP ON
43.3 DEG.C
RECIRC PUMP
DOMESTIC HW
T-1 AQUASTAT
M
TSTACK
DWH
THERMOSTATIC MIXING VALVE
HOT WATER SENSOR
HOT WATER RETURN PIPING
MOUNT IN DOMESTIC
SEE ELECTRICAL DWGS
(TYPICAL)
WELL
FUSE
T-1 SHALL BE A REMOTE BULB
120V, 1PH, 60HZ
SEQUENCE OF OPERATION
AS FOLLOWS ;
GROUND
P
REMOTE BULB THERMOSTAT T-1 SHALL CONTROL PUMP P-2 TO MAINTAIN
ITS SETPOINT. T-1 SHALL BE PROVIDED WITH A COPPER CAPILLARY.
DIFFERENTIAL. AND SUITABLE FOR 8 FLA AT 120 VAC.
AQUASTAT SHALL CONTROL PUMP TO MAINTAIN ITS SET POINT.
AUTO
OFF
T-1
MOTOR STARTER
FOR P-2
LIGHT
HOLDING COIL
GREEN PILOT
1C
G
P
PUMP CONTROL
HAND
O/L
60.0 DEG.C
E.A.
T
T-1
EF-2
O.A. DM
N
F
G
M
OL'S
1PH 120VAC
DAMPER MOTOR
SET AT 35.0 DEG. C.
VENTILATION THERMOSTAT(T-1)
MAN. MTR STARTER
W/A.O.H. SEL. SW
ROOF EXH. FAN
GREEN PILOT LAMP
O.A.
A
OFF
H
H
VENT THERMOSTAT
MOTORIZED O.A.
DAMPER
FOR MECH.RM.
LOUVER W/BIRDSCREEN
OUTSIDE AIR INTAKE
SEQUENCE OF OPERATION
WHEN SPACE TEMP. RISES ABOVE 35 DEG.C, ROOF EXHAUST FAN
SHALL OPERATE AND OPEN O.A. INTAKE DAMPER AND MOTORIZED
BACKDRAFT DAMPER VENTILATION TO MAINTAIN T-1 SETPOINT.
EXHAUST FAN SHALL RUN WHENEVER LIGHTIHG SWITCH IS ON
MAG MTR STARTER
EXHAUST FAN EF-1
SEE ELECTRICAL DWGS
LIGHTING CONTACT
HAND
SEQUENCE OF OPERATION
EF-1
OFF
AUTO
H
C
L
CL
2C
RED
N
EF
T
M9
M9
M9
REPAIR FIRE ALARM SYSTEM / INSTALL
BUILDING TRANSMITTERS AND REPAIR
M-10
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
- NOT TO SCALE
MECH ROOM HVAC PIPING ISOMETRIC DIAGRAM
M10
ISOMETRIC DIAGRAM
MECH. ROOM HVAC PIPING
B
DW
H
ET
W
C W
ATE
R
CHI
LL
ER
CHS
AS AI
R
SEP
ARATOR
SEE
C/HW
S 40
P
HOT
W
ATE
R
CI
RC.
P
UPM
P
CHR
C/
HW
R
C/
HW
R
CHS
(U
NDERGROUND
PI
PI
NG)
FOR
CONT.
SEE
CI
VI
L
DW
G
CHR
E
E
OI
L
FI
LT
ER
(T
YP)
AUTO
SHUT-
OFF
FL
EXI
BLE
C
ONNECTOR
(T
YP)
SW
IT
CH
(T
YP)
SEE
SEE
C/
HW
R
CHS
CHEM
IC
AL
FE
DDER
W /F
UNNEL
FL
EXI
BLE
C
ONNECTOR
(T
YP)
HOT
W
ATE
R
BOI
LE
R
EXPANSI
ON
TANK
DOM
ES
TI
C
HOT
W
ATE
R
HEATE
R
M
ODULATI
NG
3-
W
AY
CONTROL
VALVE
BALANCI
NG
VALVE
(T
YP)
SEE
VALVE
BOX
DETAI
L
M
M
M
M
REPAIR FIRE ALARM SYSTEM / INSTALL
BUILDING TRANSMITTERS AND REPAIR
BUILDING S-81, CAMP CASEY(PH#1)CHONG,ST
185600
EUH ELE
C.
U
NI
T
HEATE
R
M-11
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
SCALE : 1 / 100
SCALE : 1 / 100
SCALE : 1 / 100
1.
NOTES:
CONTRACTOR SHALL VERIFY EXACT LOCATION, SIZE AND DIRECTION
2. CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR PLUMBING PIPING SYSTEM.
OF HW, CW, SEWER AND VENT PIPING IN FIELD(TYP)
M11
M11
GROUND FLOOR PLUMBING PIPING PLAN-1
GROUND FLOOR PLUMBING PIPING PLAN-2
SCHEDULE AND NOTES
PLAN-1 & 2, PLUMBING FIXTURE
GROUND FLOOR PLUMBING PIPING
SEE
SEESEE
40 50
50 40
25 50
BEDROOM
VEST
VIP BEDROOM
BEDROOM
BEDROOM
BEDROOM
VEST
CORRIDOR
BEDROOM
BEDROOM
COMM
CLOSET
MECH ROOM111
LAUNDRY
S S
SEE SEE
SEE
100 FCO100 FCO
100 FCO100
100 100
VIP BEDROOM
VEST
BEDROOM
BEDROOM
BEDROOM
BEDROOM
CORRIDOR
VEST
BEDROOM
BEDROOM
104MECH ROOM
CLOSET
COMM
LAUNDRY
,5
SEE CIVIL DWG
FOR CONT.
WALL HANG TYPE
W/ AERATOR SHALL BE KOSDO INC
MODEL KSAJ-515-24 OR APPROVED EQUAL.
MODEL KSAJ-100 OR APPROVED EQUAL.
SHALL BE KOSDO INC
5015 40 SINGLE BOWLP-9 LAUNDRY SINK1 15
20 40WASHER1 20
15SHOWER7P-10 15 40 50
FLUSH TANKE MOUNTED TYPE100
WASTE
15 40
PIPE CONNECTION
H.W. VENT
BACK
STAINLESS STEEL TYPE
R E M A R K S
RESPONSIBLE FOR VERIFYING ACTUAL QUANTITIES BASED ON THE CONTRACT DOCUMENTS
QUANTITIES ARE SHOWN FOR ESTIMATION PURPOSE ONLY, THE CONTRACTOR SHALL BE
PLUMBING FIXTURE SCHEDULE
C.W.
NOTES :
REQUIREMENTS.
QTY.
P-7
P-1
P-5
SYMBOL
KITCHEN SINK
SINGLE BOWL
F I X T U R E
LAVATORY
WATER CLOSET7
SEE
SEE
M12
2 2
M12
M12M12
M12
M12M12
1 1
-- M12
S
REPAIR FIRE ALARM SYSTEM / INSTALL
BUILDING TRANSMITTERS AND REPAIR
M-12
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
SCALE : 1 / 50
SCALE : 1 / 50
PLUMBING PIPING PARTIAL PLAN 4
SCALE : 1 / 50
PLUMBING PIPING PARTIAL PLAN
1.
NOTES:
CONTRACTOR SHALL VERIFY EXACT LOCATION, SIZE AND DIRECTION
2. CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR PLUMBING PIPING SYSTEM.
OF HW, CW, SEWER AND VENT PIPING IN FIELD(TYP)
M12
M12 M12
P-5
WATER HAMMER ARRESTOR
(PDI:"A" TYP) (TYP. OF 2)
BALL VALVE (TYP)
P-1
P-10
P-7
SEE
SEE
VALVE BOX, SEE DETAIL
ET
P
AS SEPARATOR
AS
DWH
B
WALL HYDRANT
20mm NON FREEZE TYPE
15mm HOSE BIBB
BACK FLOW PREVENTER
PRESSURE REDUCING VALVE
P-9
P-7
P-10
P-1
P-5
P-9
75 FCO
65 VTR
75 FD
W
100 FCO
100 FCO
50 FD
P-10
P-1
P-5 P-5
P-1
P-10
P-7 P-7
(PDI:"A" TYP) (TYP. OF 4)
WATER HAMMER ARRESTOR
BALL VALVE (TYP)
20 20
32 32
25 25
P-10
P-1
P-5
P-1
P-10
P-7P-7
P-5
65 VTR
100 FCO
50 TRANCH DRAIN
PP101A
SEE SEE
SEE
SEE
DOMESTIC
HOT WATER
HEATER
RECIRC PUMP
DOMESTIC HOT WATER
DRAIN
50 TRANCH 50 TRANCH
DRAIN
VIP BEDROOM
COMM
CLOSET
MECH ROOM
LAUNDRY
VIP BEDROOM
LAUNDRY
MECH ROOM
CLOSET
COMM
BEDROOM BEDROOM
BEDROOM BEDROOM
SEE
,5
50DIA DOMESTIC WATER
FOR CONT.
SEE CIVIL DWG
65 VTR
V
V
S S
S
S
S
V
S S
V
V
GROUND FLOOR HOT & COLD WATER GROUND FLOOR SEWER
BEDROOM HOT & COLD WATER
PLUMBING PIPING PARTIAL PLAN 2
SCALE : 1 / 50M12
PLUMBING PIPING PARTIAL PLAN
BEDROOM SEWER
PLAN AND NOTES
& SEWER PLUMBING PIPING PARTIAL
BEDROOM, FLOOR HOT & COLD, WATER
M11
M11
M21
M11
1M11
M11
M11
REPAIR FIRE ALARM SYSTEM / INSTALL
BUILDING TRANSMITTERS AND REPAIR
M-13
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
1.
NOTES:
CONTRACTOR SHALL VERIFY EXACT LOCATION, SIZE AND DIRECTION
2. CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR PLUMBING PIPING SYSTEM.
OF HW, CW, SEWER AND VENT PIPING IN FIELD(TYP)
DW
H
ET
B
AS
AI
R
SEP
ARATOR
SEE
CI
VI
L
DW
G
FOR
CONT
S
F
D
F
CO
P
BACK-
FL
OW
P
REVENTE
R
PREVENTE
R
ASS
EM
BLY
PRES
SURE
REDUCI
NG
VALVE
3- W
AY
M
ODULATI
NG
M
IX
V
ALVE
N
ON
FREEZE
D
TYPE
W
ALL
H
YDRANT
VALVE
BOX
SEE
DOM
ES
TI
C
HOT
W
ATE
R
HEATE
R
BOI
LE
R
HOT
W
ATE
R
EXPANSI
ON
TANK
S
V
TR
V
SEE
- M13
MECH ROOM PLUMBING PIPING ISOMETRIC DIAGRAM
NOT TO SCALE
ISOMETRIC DIAGRAM
MECH ROOM PLUMBING PIPING
M
M
REPAIR FIRE ALARM SYSTEM / INSTALL
BUILDING TRANSMITTERS AND REPAIR
M-14
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
1.
NOTES:
CONTRACTOR SHALL VERIFY EXACT LOCATION, SIZE AND DIRECTION
2. CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR PLUMBING PIPING SYSTEM.
OF HW, CW, SEWER AND VENT PIPING IN FIELD(TYP)
M14
DCW & DHW PIPING
P-
SEE
SEWER & VENT PIPING
FCO
S
S
V
V
V
SEE
V
TR
P-
P-
P-
BALL
V
ALVE
(T
YP)
W
ATE
R
HAM
M
ER
ARRES
TOR
(P .D .I:
"A
" T
YPE)
(T
YP
OF
4)
P-
P-
P-
P-
P-
P-
P-
V
P-
V
P-
P-
V
P-
V
P-
V
V
V
TYP UNIT PLUMBING PIPING ISOMETRIC DIAGRAM-1
NOT TO SCALE
- M14
TYP UNIT PLUMBING PIPING ISOMETRIC DIAGRAM-2
NOT TO SCALE
ISOMETRIC DIAGRAM-1 & 2
TYP UNIT PLUMBING PIPING
M
M
REPAIR FIRE ALARM SYSTEM / INSTALL
BUILDING TRANSMITTERS AND REPAIR
SP
D
FIRE PROTECTION LEGEND & ABBREVIATION
SPRINKLER
MAIN SUPPLY SPRINKLER
PENDENT SPRINKLER(K=5.6)
UPRIGHT SPRINKLER(K=5.6)
CUTTING POINT
CAP
FIRE DEPARTMENT CONNECTION
(2-WAY SHOWN)
VALVES
CHECK VALVE
FITTING
WALL MOUNTED TEST HEADER
CONNECTION, TOP
ELBOW, 90
ELBOW, TURNED UP
ELBOW, TURNED DOWN
TEE
TEE, OUTLET UP
TEE, OUTLET DOWN
CONNECTION, BOTTOM
RISER
TEST VALVE
DRAIN VALVE
TYPICALTYP.
NO
EXST EXISTING
ABBREVIATIONS
MAX MAXIMUM
MIN MINIMUM
DRAIN PIPE
NUMBER
DRAWINGDWG
CONN
CONT CONTINUE/CONTINUATION
CONNECTION
RM ROOM
W/ WITH
W/O WITHOUT
SCH SCHEDULE
RESIDENTIAL PENDENT SPRINKLER(K=4.9)
UPRIGHT SPRINKLER(K=8.0)
SPRINKLER Q'TY LIST
SPRINKLER HEAD TYPE
US/(METRIC)
"K" FACTOR
SIZE
A R E ASYMBOL
BED ROOM, VIP BED ROOM
THREAD
SPRINKLER Q'TY LIST
RESIDENTIAL PENDENT TYPE SPRINKLER HEAD 4.9/(68)1/2" NPT
TOTAL
105.6/(80)1/2" NPTQUICK RESPONSE PENDENT TYPE SPRINKLER HEAD
TOTAL NUMBER OF SPRINKLER OF SYSTEM 50
VEST, CORRIDOR
AUTOMATIC FIRE SUPPRESSION(S) GENERAL NOTES:
1. THE CONTRACTOR SHALL PROVIDE AND INSTALL AN AUTOMATIC WET PIPE SPRINKLER SYSTEM
TO FULLY PROTECT THIS FACILITY. THE FIRE SPRINKLER SYSTEM SHOWN THESE DRAWING IS
PERFORMANCE BASED WHICH MEANS CONCEPTUAL REQUIREMENT ONLY. THE SPRINKLER
CONTRACTOR SHALL SUBMIT A COMPLETE FIRE SPRINKLER SYSTEM SHOPDRAWINGS BASED ON
NFPA 13 AND SPECIFICATION REQUIREMENTS AND SUBMIT FOR APPROVAL PRIOR TO
INSTALLATION. THE EQUIPMENT SHOWN ARE SUGGESTED LOCATIONS HOWEVER FINAL LAYOUT
SHALL BE IN ACCORDANCE WITH APPLICABLE CODES, MANUFACTURER'S RECOMMENDATIONS, AND
EQUIPMENT LISTINGS. CONTRACTOR SHALL COORDINATE SPRINKLER HEADS LOCATIONS WITH,
CEILING PANELS, LIGHTING FIXTURES, AND HVAC AIR DEVICES. ALL EQUIPMENT SHALL BE UL
LISTED AND FM APPROVED IN ACCORDANCE WITH NFPA 13 AND THE PROJECT SPECIFICATION.
2. THE CONTRACTOR SHALL CONDUCT WATER SUPPLY HYDRANT TEST FOR THIS PROJECT BASED
ON NFPA 291 REQUIREMENTS AND UTILIZE THIS DATA TO DESIGN THE SPRINKLER SYSTEM.
THE HYDRANT LOCATIONS, FLOW TESTS, AND DATE SHALL BE INDICATED ON THE
SHOPDRAWINGS. AUTOMATIC SPRINKLER PROTECTION SYSTEM IS REQUIRED TO PROTECT THIS
ENTIRE FACILITY. A MINIMUM 10% SAFETY FACTOR IS REQUIRED BETWEEN THE AVAILABLE
WATER SUPPLY AND THE SPRINKLER SYSTEM DEMAND.
INSTALLED IN THE HORIZONTAL POSITION.
7. ALL AUTOMATIC SPRINKLER DRAIN VALVES FOR FIRE DEPARTMENT CONNECTIONS SHALL BE
BE INSTALLED ON THE EXTERIOR.
DRAINS, BUT MUST TERMINATE TO THE BUILDING EXTERIOR. SPRINKLER RISERS SHALL NOT
AND MAINTENANCE. TEST DRAINS ARE NOT TO BE TERMINATED AT WALL SINKS OR FLOOR
6. PROVIDE MINIMUM 1M X 2M SPACE FOR EACH FIRE SPRINKLER RISER FOR INSTALLATION
AS-BUILT DRAWINGS FOR THIS PROJECT.
CONTRACTOR SHALL CONFORM TO THE SYMBOLS INDICATED IN NFPA 170 TO DEVELOP THE
22-"PLANS AND CALCULATIONS" PRIOR TO SPRINKLER PIPING INSTALLATION. THE
5. CONTRACTOR SHALL SUBMIT HYDRAULIC CALCULATIONS AS REQUIRED BY NFPA 13 CHAPTER
4. FIRE PROTECTION PLANS SHOWN ARE USED FOR COST ESTIMATE PURPOSE ONLY.
WITH O-RINGS ARE NOT PERMITTED.
BRACING CALCULATION IN ACCORDANCE WITH NFPA 13 REQUIREMENTS; SPRINKLERS
3. PROVIDE EARTHQUAKE PROTECTION (SWAY BRACING), END OF BRANCH LINE AND SEISMIC
8. FLEXIBLE COUPLINGS SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 13, PAR 9.3.2.
9. ALL PIPING, SANITARY, VENT, WASTE, PLUMBING, OTHER PIPING, POWER OR CONTROL CIRCUTS, OR DUCT SHALL PENETRATE ANY STAIR OR EXIT PASSAGEWAY ENCLOSURE UNLESS IT SERVES
AN APPLIANCE WITHIN THE ENCLOSURE AND DEAD ENDS IN THE ENCLOSURE.
VERIFYING ACTUAL QUANTITIES BASED ON THE CONTRACT DOCUMENT REQUIRMENTS.
1. QUANTITIES ARE SHOWN FOR ESTIMATING PURPOSE ONLY, THE CONTRACTOR SHALL BE RESPONSIBLE FOR
NOTE
DRY SIDEWALL SPRINKLER(K=5.6)
OS&Y GATE VALVE(N.O.)
W/TAMPER SWITCH
OS&Y GATE VALVE(N.C.)
W/TAMPER SWITCH
28.0/(115)3/4" NPTQUICK RESPONSE PENDENT TYPE SPRINKLER HEAD LAUNDRY
MECH ROOM, COMM CLOSETQUICK RESPONSE UPRIGHT TYPE SPRINKLER HEAD 8.0/(115)3/4" NPT 3
M-15
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
NOTES SPRINKLER Q'TY LIST AND NOTE
AUTOMATIC FIRE SUPPRESSION GENERAL
FIRE PROTECTION LEGEND & ABBREVIATION
REPAIR FIRE ALARM SYSTEM / INSTALL
BUILDING TRANSMITTERS AND REPAIR
SCALE : 1 / 100
1 NEW GROUND FLOOR FIRE PROTECTION CLASSIFICATION PLAN
TTTT
T TT
T
BEDROOM
LAUNDRY
MECH ROOM
CORRIDORVEST VEST
BEDROOM
BEDROOM
BEDROOM
VIP BEDROOM
101 BEDROOM
BEDROOM
112 109
CLOSET
COMM
LIGHT HAZARD ORDINARY-II HAZARDRESIDENTIAL HAZARD
M-16
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
M16
CLASSIFICATION PLAN
NEW GROUND FLOOR FIRE PROTECTION
REPAIR FIRE ALARM SYSTEM / INSTALL
BUILDING TRANSMITTERS AND REPAIR
NEW GROUND FLOOR FIRE PROTECTION PIPING PLAN
SCALE : 1 / 100
M17
M-17
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
BEDROOM
LAUNDRY
MECH ROOM
CORRIDOR
VEST
VEST
BEDROOM
BEDROOM
BEDROOM
VIP BEDROOM
101 BEDROOM
BEDROOM
CLOSET
COMM
25 25 25
80 80 80 80 80 80 80
PENDENT TYPE SPRINKLER HEAD
15mm RESIDENTIAL CONCEALED
UPRIGHT TYPE SPRINKLER HEAD
20mm QUICK RESPONSE
PENDENT TYPE SPRINKLER HEAD
15mm QUICK RESPONSE CONCEALED
PENDENT TYPE SPRINKLER HEAD
20mm QUICK RESPONSE CONCEALED
PIPING PLAN
NEW GROUND FLOOR FIRE PROTECTION
REPAIR FIRE ALARM SYSTEM / INSTALL
BUILDING TRANSMITTERS AND REPAIR
MECH ROOM
WATER MOTOR ALARM GONG
80mm BACKFLOW PREVENTER
UL/FM APPROVED ASSEMBLY
N .O
N .O
80mm X 65mm
TEST VALVE HEADER
W/20mm BALL DRIP VALVE
80mm ALARM CHECK VALVE
80mm CHECK VALVE
80mm X 65mm
FIRE DEPARTMENT SIAMESE CONNECTION
W/20mm BALL DRIP VALVE
140 SM (1500 SF)
ORDINARY TEMPERATURE RATING
LIGHT HAZARD ORDINARY HAZARD
GROUP-II OCCUPANCY
BED ROOM
4.9M X 4.9M
(16FT X 16FT)
MAX. 4.9 M (16 FT)
MIN. 2.4 M (8 FT)
SPRINKLER NOZZLE
K-FACTOR OF
(8.0)
(4.9)
(5.6)
WET SPRINKLER
4.1 LPM/SM (0.10 GPM/SF)
QUICK RESPONSE
20.9 SM (225 SF)
950 LPM (250 GPM)
MAX. 4.6 M (15 FT)
MIN. 1.8 M (6 FT)
60 MIN.
(57°C-77°C / 135°F-170°F)
ORDINARY TEMPERATURE RATING
TYPE OF SYSTEM
SPRINKLER
SPRINKLER TYPE
MAX. COVERAGE PER
BETWEEN SPRINKLERS
MAX. & MIN. SPACE OF
RATING*
SPRINKLER TEMPERATURE
DESCRIPTION
HAZARD
FIRE PROTECTION REQUIREMENTS
DESIGN DENSITY
DURATION OF SUPPLY
HOSE STREAM
DESIGN AREA
APPLICATION AREA
WET SPRINKLER
8.2 LPM/SM (0.20 GPM/SF)
QUICK RESPONSE
12.1 SM (130 SF)
950 LPM (250 GPM)
MAX. 4.6 M (15 FT)
230 SM (2500 SF)
MIN. 1.8 M (6 FT)
60 MIN.
(57°C-77°C / 135°F-170°F)
WET SPRINKLER
2.1 LPM/SM (0.05 GPM/SF)
RESIDENTIAL
950 LPM (250 GPM)
MAX. 4 HEADS
60 MIN.
RESIDENTIAL
OCCUPANCY
(57°C-77°C / 135°F-170°F)
ORDINARY TEMPERATURE RATING
OCCUPANCY
MECH ROOM, LAUNDRY, CBRN,
ARMS ROOM, STORAGE
MADIC/AID STATION, SUPPLY ROOM
OFFICE, TOILET, STAIR, JAN,
DAY ROOM, CORRIDOR, VEST,
M-18
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
- M18
SCALE : 1 / 50
MECH ROOM FIRE PROTECTION PIPING PARTIAL PLAN
REQUIREMENT
PARTIAL PLAN AND FIRE PROTECTION
MECH ROOM FIRE PROTECTION PIPING
REPAIR FIRE ALARM SYSTEM / INSTALL
BUILDING TRANSMITTERS AND REPAIR
MAIN RISER CONNECTION(TYPICAL)
AND SPIGOT PIECE
DUCTILE IRON FLANGE
AND SPIGOT PIIPE
RODS NOT LESS
THAN 20Ø
DUCTILE IRON BELL
SERVICE
FROM FIRE
MAIN
G.L
GENERAL NOTE :
OR LEAVING THE SUBJECT BUILDINGS.
THIS DETAIL SHALL BE UTILIZED WHERE
.FIRE MAIN SERVICE LINES ARE ENTERINE
STEEL PIPE
THRUST BLOCK
CONC.
FL
BITUMASTIC COATED
BITUMASTIC COATED
SPRINKLER ALARM CHECK VALVE & MAIN RISER
W/TAMPER SWITCH
GATE VALVE
OS & Y
FIRST
PIPE SUPPORT
1 3
SEE
M10
FIRE DEPT CONNECTION
VALVE
BALL DROP
2 TAMPER SWITCH
BACKFLOW PREVENTER
TEST VALVE HEADER
TEST VALVE
OS & Y GATE VALVE
DESCRIPTION
ITEM
SPRINKLER MAIN RISER
PER NFPA 13
FLEXIBLE COUPLING
FOR EARTH QUAKE
(WITH TAMPER SWITCH)
SUPERVISORY VALVE
WATER MOTOR ALARM DRAIN
PRESSURE SWITCH
PIPE SUPPORT
RISER TO SPRINKLER SYSTEM
FIRST SUPPORT W/CROSS BRACING
RETARDING CHAMBER
WATER MOTOR ALARM GONG
MAIN DRAIN AND TEST VALVE
SWAY BRACING PER NFPA 13 FOR
FLEXIBLE COUPLERS PER NFPA 13
DESCRIPTION
ALARM CHECK VALVE
(2-REQUIRED)
PRESSURE GAGE
ZONE 1 EARTHQUAKE
ITEM
FOR EARTH QUAKE
SEE
M10
VALVE
BALL DROP
- M19
- M19
- M19
MAIN DRAIN
SYSTEM TEST CONNECTION
PIPE EXTENDS THROUGH WALL TO OUTSIDE.
2. THE TEST VALVE SHOULD BE LOCATED AT AN
ACCESSIBLE POINT AND PREFERABLY NOT
OVER 7FT (2.1M) ABOVE THE FLOOR.
PIPE IN WARM ROOM BEYOND VALVE WHERE
1. NOT LESS THAN 4FT (1.2M) OF EXPOSED TEST
NOTES :
ACCESSIBLE LOCATION
TEST VALVE IN READILY
BRANCH LINE
P.G.
- M19
SWAY BRACING4
- M19
CONC SLAB
SWAY BRACE FITTINGS
SCHEDULE 40 PIPE
PIPE CLAMP
CROSSMAIN
SPRINKLER
EXPANSION BOLT (TYP)
CONC SLAB
SWAY BRACE FITTINGS
SCHEDULE 40 PIPE
CROSS MAIN
SPRINKLER
EXPANSION BOLT
PIPE CLAMP
* PIPE SIZE SHALL BE DETERMINED BY CALCULATIONS
ON WET PIPE SYSTEM
M-19
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
DETAILS-1
REPAIR FIRE ALARM SYSTEM / INSTALL
BUILDING TRANSMITTERS AND REPAIR
M-20
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
DETAILS - 2
SEE ARCH. DWGS.
WOOD NAILER
ALL AROUND
GASKET SEAL
(SPECIFIED IN DIVISION 7)
ROOF CONSTR.
FLASHING
CURB HT.
12"(300) MIN.
DIVISION 7 WORK
ROOF CURB,
POWER ROOF VENTILATOR
MIN. 2 EACH SIDE
BY FAN MFR.,
RECOMMENDED
LAGBOLTS AS
SEE ARCH. DWGS.
WOOD BLOCKING,
SEE ARCH. DWGS.
MANUAL
BACKDRAFT DAMPER
EXHAUST DUCT WORK
AS EQUIPMENT SCHEDULE
POWER ROOF VENTILATOREXPANSION TANK & AIR SEPARATOR PIPING DETAIL
SEAMS AND JOINTS
WATERPROOF
SEE ARCH. DETAIL
FLASHING
M
IN
W
D U C T S
IZE
+25%
450 MIN.
R
R=
SCREEN
BOLT & NUT
ANGLE IRON REINFORCING
WHERE REQUIRED
15 SCREEN
METAL SCREEN FRAME
MESH SCREEN
(HEAVY
SNOW AREA)
ROOF
M
IN
ANGLE RIVETED OR
TACK WELDED
AS REQUIRED
ROOF GOOSENECK (RECTANGULAR DUCT)
AIR VENT
FLOOR OR PAD
GAUGE GLASS
SHOWN. ANGLE IRON LEGS
WITH DRAIN ACCESS OPENING
FLOOR MOUNTING BASE RING
MAY BE USED AS AN OPTION.
COLD WATER FILL LINE.
SCHEDULE FOR SIZE
FROM SYSTEM
SEE EXPANSION TANK
PREVENTER
BACK-FLOW
REMOVABLE STRAINER
EXPANSION
DRAIN
TANK
PRESSURE REDUCING
VALVE
EXPANSION TANK
MANUFACTURER'S
AIR VENT
FD ECA BG HF
HOT PIPE LINE
HGD FECBG H A
CG
MF
EXPOSED
CLINCHING STAPLE @ 100 O.C.
CG OR
MF
EXPOSED
WEATHER
A
C
D
B
CLASS II ADHESIVE
OVERLAP (40)
VAPOR-BARRIER JACKET
2. HOT WATER HEATING
3. HEATED OIL PIPE LINE
1. STEAM & CONDENSATE
5. REFRIGERATION SUCTION
4. A/C CONDENSATE DRAIN
LONGITUDINAL JOINTS
COLD WATER PIPE LINE
3. DUAL TEMP. WATER
2. CHILLED WATER
1. MAKE-UP WATER
DOWN TO SHED WATER
SHALL BE OVERLAPPED
ALUMINUM JACKET
H
G
NOTE :
BAPIPING
COLD PIPE LINE
HOT PIPE LINE
D EC
INSULATION
PIPE
AREA
ITEM
80 JACKET STRIPE
F
CONCEALED
VAPOR-BARRIER JACKET
(MIN. 40 JACKET OVERLAP)
VAPOR-BARRIER COATING
10 W x 0.5 THK @300 O.C.
ALUMINUM LOCK-TYPE BANDS
80 JACKET STRIP OR
MF - MINERAL FIBER SHALL BE USED FOR HOT PIPES
CG - CELLULAR GLASS SHALL BE USED FOR COLD PIPES
SEE SPECIFICATION FOR INSULATION THICKNESS
SECTIONFRONT VIEW
1.5 THK (MIN)
SST DRYER VENT CAP
SATIN FINISH
D U
C T D
IR
M E
T E
R P
L U
S
M
IN
(MIN)
D U
C T D
IR
M E
T E
R
DRYER VENT WALL CAP DETAIL1
- M20
PIPE INSULATION DETAIL 2
- M20
- M20
- M20
- M20
REPAIR FIRE ALARM SYSTEM / INSTALL
BUILDING TRANSMITTERS AND REPAIR
M-21
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
"H2"
375 FROM ROOF LINE
WEATHER CAP CONNECTION
WEATHER CAP #14GA.
STAINLESS STEEL
SMOKESTACK
WELD
SST. STEEL SHEET
SEE DETAIL "X"
(TYP. OF 4)
"D1"
FLASHING CAP
ROOF FLASHING
#14GA. SST. STEEL
SEE NOTE 1.
"D1" "D2" "D"DIA.
STACK
"D2"
"H2""H1"
(UNIT METRIC)