H1_Drawing_files___185600___ARHC.PDF

PDF 3 MB Posted

Attached to
Replace fire alarm system and Building Transceiver (BT) for buildings on west side of Camp Casey.
Solicitation number
W91QVN-18-R-0137
Issued by

About this file

ARHC

View the file

Other files

File Type Posted
H1_Drawing_files___185600___CIVIL.PDF PDF
H1_Drawing_files___185600___STRU.PDF PDF
H1_Submittal_Register___185600.xls XLS spreadsheet
H1_Drawing_files___185600___ELEC.PDF PDF
RFP_for_W91QVN18R0137.docx DOCX document
H1_Drawing_files___185600___Title.pdf PDF
H1_Drawing_files___185600___MECH.PDF PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

A-1

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ARCHITECTURAL

MANUFACTURES INDICATED.

PURPOSES ONLY. AND NOT INTENDED TO LIMIT SELECTIONS TO PRODUCTS OF THE

COLORS AND PATTERNS LISTED BY MANUFACTURES ARE FOR BIDDING IDENTIFICATION 1.

ADJACENT AREAS AS DIRECTED BY THE CONTRACTING OFFICER REPRESENTATIVE (COR).

CAUSED BY THIS PROJECT AND SHALL REPAIR THE DAMAGES TO MATCH UP TO

CONTRACTOR SHALL BE RESPONSIBLE FOR ALL DAMAGES MADE TO EXISTING AREAS

FOR APPROVAL.

CONTRACTOR ACCORDING TO ACTUAL FIELD CONDITION AND SUBMITED TO COR

CONDITION. IN THAT CASE, SHOP DRAWINGS SHALL BE PREPARED AT THE SITE BY THE

SOME DETAILS SHOWN ON CONTRACT DRAWINGS MAY NOT COINCIDE WITH THE FIELD

8.

FOR APPROVAL.

CONTRACTOR SHALL SUBMIT MANUFACTURER'S INSTALLATION SHOP DRAWINGS TO COR

2.

3.

4.

5.

6.

7.

CONTRACTOR SHALL NOTIFY THE CONTRACTING OFFICER.

IF THERE ARE ANY CONFLICTS WITHIN THE CONTRACT DOCUMENT, THE GENERAL

AND DIMENSIONS PRIOR TO COMMENCING ANY CONSTRUCTION OR RENOVATION.

THE CONTRACTOR SHALL BE RESPONSIBLE IN VERIFYING ALL EXISTING CONDITION

OF THE LOAD BEARING WALLS TO PREVENT COLLAPSE OF THE STRUCTURE.

APPROPRIATE TEMPORARY SUPPORTS SHOULD BE CONSTRUCTED PRIOR TO DEMOLITION

9.

10.

11.

12.

13.

14.

NUMBERS ARE FROM TM-5-807-7 AND FEDERAL STANDARD NO. 595b, COLORS.

COLOR OF MATERIALS & PAINTS SHALL BE SELECTED BY USING AGENCY AND COLOR

DETAILS AND GET APPROVAL FROM COR. BEFORE FABRICATION AND INSTALLATION.

CONTRACTOR SHALL PREPARE SHOP DRAWINGS FOR ALL DOOR/WINDOW

ADDITIONAL COST TO THE GOVERNMENT.

EQUIPMENT, ETC), ELECTRICAL, TELEPHONE AND FIRE ALARM SYSTEM WITHOUT

THE INSTALLATION AND/OR REPLACEMENT OF MECHANICAL (PLUMBING, HEATING,

ITEMS, CUT, PATCH AND RESTORE WALLS, FLOORS AND CEILING WHERE REQUIRED FOR

THE CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVE/REINSTALL ANY OBSTRUCTED

GENERAL NOTES

SPECIFICATION 15181.

ITEMS REQUIRING MAINTENANCE/OPERATION IAW THE SECTION 3.1.14, OMA STD

PROVIDE ACCESS DOORS FOR ALL CONCEALED VALVES, VENTS, CONTROLS AND OTHER

COMMENCEMENT OF FLOOR TILE WORK AND AS PER FLOOR FINISH SCHEDULE.

ALL CONCRETE FLOOR SURFACES SHALL BE LEVELED AND SMOOTHED PRIOR TO

OFFICE, DPW. PER DIRECTION FROM THE INSPECTOR IN CHARGE OR COR.

SALVAGE OR SERVICEABLE MATERIALS SHALL BE RETURNED TO SUPPLY OR STORAGE

AND GENERAL NOTES

EXST & NEW GROUND FLOOR PLANS

1.67 K. SM/W

3.34 K. SM/W

AS FOLLOWS :

WALL

ROOF

"R" VALUE FOR INSULATION SHALL BE

& COATING.

REMOVE & CLEAN EXISTING PAINT BY SAND PAPER/ GRINDING FOR NEW PAINTING

FROM THE MANUFACTURE SHOWING THE PRODUCT IS LEAD FREE.

A CERTIFICATE OR MATERIAL SAFETY DATA SHEET (MSDS), WRITTEN IN ENGLISH,

SOLIDS) DURING THE EXECUTION OF THIS PROJECT. THE CONTRACTOR WILL PROVIDE

COATINGS WITH LESS THAN 0.05 PERCENT LEAD BY WEIGHT OF THE NON-VOLATILE

THE CONTRACTOR IS REQUIRED TO USE "LEAD FREE" COATINGS (LIQUID PAINTS OR

15.

16.

17.

18.

DOCUMENTATION TO 8 CES/CEAN.

THE CONTRACTOR SHALL PROVIDE THE NEW SURVEY REPORT AND ASBESTOS REMOVAL

ACCORDANCE WITH THE KOREA ENVIRONMENTAL GOVERNING STANDARD (KEGS).

PRIOR TO ANY WORK TO ASSURE THAT APPROPRIATE ASBESTOS CONTROL IS IN

AREA WILL NEED TO BE RESURVEYED AND ASBESTOS MATERIALS SHOULD BE REMOVED

WORK IN THE AFFECTED AREA AND NOTIFY THE CONTRACTING OFFICER. THE WORK

ASBESTOS CONTAINING MATERIAL ARE DISCOVERED, THE CONTRACTOR SHALL CEASE

IS NOT PRESENT IN THE AREAS AFFECTED BY THIS WORK: HOWEVER, IF SUSPECTED

VERIFYING THE PRODUCT IS ASBESTOS FREE. TESTS HAVE INDICATED THAT ASBESTOS

WILL PROVIDE A CERTIFICATE OR MSDS, WRITTEN IN ENGLISH, FROM THE MANUFACTURER

PERCENT BY WEIGHT) DURING THE EXECUTION OF THIS PROJECT. THE CONTRACTOR

THE CONTRACTOR IS REQUIRED TO USE "ASBESTOS FREE" MATERIALS (LESS THAN 0.1

BEDROOM

LAUNDRY

MECH ROOM

CORRIDOR

VEST

VEST

101 BEDROOM 102 BEDROOM 103 BEDROOM 104

107 BEDROOM 106 BEDROOM 105

L/S

W

D

FECB/B

DASHED LINE FOR

ROOF(ABOVE)

BED/LIV ROOM BED/LIV ROOM BED/LIV ROOM BED/LIV ROOM

BED/LIV ROOMLAUNDRY

MECH ROOM

CORRIDORVEST VEST

SCALE: 1 : 100

EXST GROUND FLOOR PLAN

SCALE: 1 : 100

NEW GROUND FLOOR PLAN

33,934

8,5858,3828,3828,585

,1

,8

,5

,8

33,934

8,5858,3828,3828,585

,8

,1

,8

,5

,8

8,5858,8903,8612,6429,957

BEDROOM

W1

L3

L1L2

D1 D3

D7

D8 D3 D1

D2

D4

D4 D4 D4 D4

D4D4

D5

D6

D6

D5

D5 D5 D5

D5D5

D6 D6

D6D6 D6

DAYROOMSTORAGE

SHALL BE AS A PART OF THE CONTRACT DOCUMENT OF THIS PROJECT.

STANDARD DETAIL DRAWINGS FOR O&MA PROJECT, KOREA, DATED NOVEMBER 2015

BED/LIV ROOM

W1 W1 W1 W1 W1 W1

W1 W1 W2 W1 W1 W1 W1

W

W/CMU, RE-BAR & EIFS

BLOCK UP DOOR OPNG

/CCTV

COMM CLOSET

YI, SC

185600

BUILDING S-81, CP CASEY

BUILDING TRANSMITTERS AND REPAIR

REPLACE FIRE ALARM SYSTEM / INSTALL

BEDROOM

LAUNDRY

MECH ROOM

CORRIDOR

VEST VEST

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

TYP

SB SB SB SB

SB

SB

SB

1 PER 2001 PER 200

GUTTER SLOPE

GUTTER EXPANSION JOINT

GUTTER SLOPE 6

DS

STANDING SEAM

METAL ROOFING

GEJ GEJDS DS DSDS GEJ

GEJDS DSGEJ

DS

DS GEJ DS

DS DS

F M

F M

F M

F M

F M

F M

A-2

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ARCHITECTURAL

CEILING ACCESS DOOR

DETECTOR

(SEE ELECTRICAL DRAWINGS)

CEILING EXHAUST FAN

(SEE MECHANICAL DRAWINGS)

(600x600 or 450x450)

ACST CLG

GWB CLG

PROTECTED METAL SOFFIT

1HR FIRE RATED WALL

(SEE ELECTRICAL DRAWINGS)

LIGHTING FIXTURE

FIRE ALARM SPEAKER

(SEE ELECTRICAL DRAWINGS)

LEGEND

VTR

GOOSENECK

(SEE MECH DWG)

SMOKE STACK

(SEE MECH DWG)

EXHAUST FAN

SB

F M

ROOF PLAN AND CEILING PLAN

60033,934600

,6

,8

,6

17,4753,86112,598

,1

,6

,8

,6

600 600

CURTAIN BOX

SCALE: 1 : 100

NEW ROOF PLAN

SCALE: 1 : 100

CEILING PLAN

BEDROOM

A-9

A-9

A-9

A-9

A-11

A-11

/CCTV

COMM CLOSET

YI, SC

185600

BUILDING S-81, CP CASEY

KEY PLAN

1ST FL

WORK POINT

1ST FL

WORK POINT

A-3

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ARCHITECTURAL

ELEVATIONS

STANDING SEAM

METAL ROOFING

PROTECTED

MET GUTTER

INSULATED BLAST

SLIDING AL WINDOW

(TYP)

THERMAL INSULATED

METAL DOOR

EIFS ON EXISTING

PROTECTED

MET FLASHING

EIFS ON EXISTING

CMU WALL

THERMAL INSULATED

PROTECTED

MET FLASHING

AIR INTAKE

LOUVER (TYP)

BUILDING

IDENTIFICATION

S-81

PROTECTED

MET FLASHING

STANDING SEAM

METAL ROOFING

PROTECTED

MET GUTTER

INSULATED BLAST

SLIDING AL WINDOW

(TYP)

EIFS ON EXISTING

CMU WALL

PROTECTED

MET FLASHING

EIFS ON EXISTING

CMU WALL

STANDING SEAM

METAL ROOFING

BUILDING

IDENTIFICATION

S-81

PROTECTED MET

DOWNSPOUT

SCALE:

1 : 100

NEW ELEVATION-1

SCALE:

1 : 100

NEW ELEVATION-2

SCALE:

1 : 100

NEW ELEVATION-4

SCALE:

1 : 100

NEW ELEVATION-3

CMU WALL (TYP)

A-11

BLAST METAL DOOR

A-11

YI, SC

185600

BUILDING S-81, CP CASEY

A-4

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ARCHITECTURAL

SCOPE OF WORKS (ARCHITECTURAL WORK)

REPAIR / MAINTENANCE (K) WORK

1.

2.

3.

4.

6.

7.

8.

9.

5.

SIGNAGE SCHEDULE.

REPLACE INTERIOR & EXTERIOR SIGNAGES WITH NEW FOR ALL ROOMS AS SHOWN ON

ON NEW FLOOR PLANS AND DETAIL DRAWING.

REPLACE DETERIORATED EXISTING FIRE EXTINGUISHER CABINET(FEC) WITH NEW AS SHOWN

11.

12.

13.

14.

15.

16.

17.

18.

HARDWARE SETS AS SHOWN ON NEW FLOOR PLANS AND DOOR SCHEDULE.

REPLACE DETERIORATED EXISTING DOORS AND DOOR FRAMES WITH NEW INCLUDING NEW

TYPE.

REPLACE DETERIORATED EXISTING WINDOW HORIZONTAL MINI BLINDS WITH NEWS, FIREPROOF

19.

20.

21.

22.

FLOOR PLANS AND FINISH SCHEDULE.

WATER RESISTANT OR 'X' TYPE) CEILING INCL. CEILING SUSPENSION SYSTEM AS SHOWN ON

REPLACE DETERIORATED EXISTING CEILING WITH NEW GYPSUM WALL BOARD (GWB, NORMAL,

SLAB IF NEEDED.

CORRECTED FOR NEW FLOORING. PROVIDE LEVELING CONCRETE FOR EXISTING CONCRETE

CONCRETE, LOW SPOTS, HIGH SPOTS, PAINTING, AND UNEVEN SURFACE SHALL HAVE BEEN

SHALL BE SMOOTH, TRUE, LEVEL PLANE WITH ALL DEFECTS SUCH AS ROUGH OR SCALING

ON FLOOR PLAN & INTERIOR FINISH SCHEDULE. THE EXISTING CONCRETE FLOORING

REPLACE DETERIORATED EXISTING FLOOR TILE WITH NEW PVCT INCLUDING VCB AS SHOWN

SCHEDULE.

PAINT ON ALL INTERIOR SURFACES INCL CEILING & WALL AS SHOWN ON INTERIOR FINISH

10.

SOUND PROOF INSULATIONS (STC 45) AS SHOWN ON FLOOR PLANS AND DETAIL DRAWINGS.

REPLACE DETERIORATED EXISTING ALL GWB WALLS WITH NEW INCLUDING METAL STUDS AND

REPLACE EXISTING CHAIR RAILS WITH NEW IN CORRIDOR AS SHOWN ON DETAIL DRAWING.

ROOM AS SHOWN ON FLOOR PLAN.

REPLACE DETERIORATED EXISTING METAL SHELF WITH MOP RACK WITH NEW IN LAUNDRY

SUSPENSION SYSTEMS AS SHOWN ON INTERIOR FINISH SCHEDULE.

REPLACE DETERIORATED EXISTING CEILING WITH NEW ACOUSTICAL CEILING TILE INCL. METAL

HARD & DETAIL MESHES AND FINISH COATING AS SHOWN ON FLOOR PLAN AND ELEVATIONS.

REPLACE DETERIORATED EXISTING EIFS ON EXST EXTERIOR CMU WALL WITH NEW INCLUDING

DETAIL DRAWINGS.

REPLACE EXISTING ALUMINUM LOUVERS WITH NEW AS SHOWN ON FLOOR PLANS AND

AS SHOWN ON FLOOR PLANS AND WINDOW SCHEDULE.

+ 12 THK AIR SPACE + 6 THK TINTED LOW-E TEMPERED GLASS ( SHGC : MAX 0.4 )

THERMAL BREAKER TYPE BLAST WINDOWS INCLUDING 8.75 THK CLEAR LAMINATED GLASS

REPLACE DETERIORATED EXISTING WINDOWS INCL INSECT SCREEN WITH NEW ALUMINUM

FLOOR PLAN AND ELEVATIONS.

REPLACE DETERIORATED EXISTING CONCRETE STOOPS AND STEPS WITH NEW AS SHOWN ON

AS SHOWN ON FLOOR PLAN AND DETAIL DRAWINGS.

REPLACE RAIN GUTTERS AND DOWNSPOUTS WITH NEW INCLUDING CONCRETE SPLASH BLOCKS

AND DETAIL DRAWINGS.

WATERPROOFING, MORTAR BEDS AND CEMENT BOARDS AS SHOWN ON FLOOR PLANS

REPLACE DETERIORATED EXISTING FCT AND GCWT(FULL HEIGHT) WITH NEW INCL.

WOODEN CURTAIN BOX WITH NEW AS SHOWN ON DETAILS. (NATURAL COLOR, OAK)

REPLACE DETERIORATED EXISTING WOODEN HEAD, JAMB & SILL FOR ALL WINDOWS AND

REPLACE DETERIORATED EXISTING SHELVE WITH NEW SST SHELVE IN LAUNDRY ROOM.

FLOOR PLAN AND DETAIL DRAWINGS.

REPLACE WOODEN CLOSET SHELF AND SST COAT ROD IN EACH CLOSET AS SHOWN ON

DETAIL DRAWINGS.

REPLACE EXISTING ALL TOILET ACCESSORIES WITH NEW AS SHOWN ON FLOOR PLAN AND

AND DETAIL DRAWINGS.

REPLACE DETERIORATED EXISTING ACCESS DOORS WITH NEW AS SHOWN ON CEILING PLAN

23.

24.

25.

26.

CABINET AS SHOWN ON FLOOR PLANS AND DETAIL DRAWINGS.

REPLACE EXISTING DETERIORATED KITCHENETTE INCLUDING BASE CABINET AND UPPER

AND DETAIL DRAWINGS.

REPLACE BULLETIN BOARD AND PLEXI-INFO HOLDER WITH NEW AS SHOWN ON CEILING PLAN

LINER PANEL AS SHOWN ON ROOF PLAN AND DETAIL DRAWINGS.

INCLUDING INSULATION, PROTECTED METAL FLASHING AND GALVANIZED METAL ROOF

REPLACE DETERIORATED EXISTING ROOF WITH NEW STANDING SEAM METAL ROOFING

LAUNDRY MECH ROOM

BEDROOM

BEDROOM

105111112

BATHRM BATHRM BATHRM

1ST FL

TOP OF CONC

CORR

109107 101

1ST FL

WORK POINT

CORR

109 102

MECH ROOM

KEY PLAN

6008,5858,8903,8612,6429,957600

6009,144600

3,8101,5243,810

,1

60010,994600

3,8101,2704,0641,850

,1

,5

STANDING SEAM

METAL ROOFING

W/ INSUL ON VR

EXTERIOR INSUL &

FINISH SYSTEM ON

EXISTING CMU WALL

PROTECTED

METAL

FLASHING

EXISTING CONC

SLAB TO REMAIN

(REMOVE EXISTING

FLOOR FINISH)-TYP

FILL NFSM W/ VB

(SEE STRL

DWG)-TYP

BEDROOM BEDROOM

STANDING SEAM

METAL ROOFING

W/ INSUL ON VR

PROTECTED

METAL GUTTER

PROTECTED

METAL

DOWNSPOUT

BEDROOM

STANDING SEAM

METAL ROOFING

W/ INSUL ON VR

COMM

NFSM 1200 HGT

(TYP)

SCALE:

1 : 100

LONGITUDINAL SECTION

SCALE:

1 : 100

CROSS SECTION-1

SCALE:

1 : 100

CROSS SECTION-2

BEDROOM

CMU GUARD WALL FOR CHILLER AS SHOWN ON PICTURES.

PAINT ON ALL EXISTING EXTERIOR EXPOSED SURFACES OF OTHER COMPONENTS SUCH AS

ACM REMOVAL NOTES

1.

2.

3.

REGION OFFICE.

THE ARMY, INSTALLATION MANAGEMENT AGENCY, KOREA

DATED 14 JANUARY 2014, ISSUED BY THE DEPARTMENT OF

TECHNICAL SPECFICATIONS FOR OMA PROJECTS, KOREA",

02 82 14/ASBESTOS HAZARD CONTROL ACTIVITIES, STANDARD

THE ASBESTOS REMOVAL WORKS SHALL CONFIRM TO "SECTION

ACM AT THE WORK SITE.

ENVIRONMENTAL OFFICE THRU COR TO COMPLETE REMOVAL

THE CONTRACTOR SHALL CONTACT AND VERIFY TO

WORK SITE.

LOAD ASBESTOS CONTAINING MATERIAL REMOVED FROM THE

EPA (ENVIRONMENTAL PROTECTION AGENCY) TO COR FOR EVERY

THE CONTRACTOR SHALL SUBMIT A CERTIFICATION OF DISPOSAL,

27.

- PIPE HANGING IN MECH ROOM, 1EA

- GASKET IN MECH ROOM, 1EA

- JOINT VERTICAL IN MECH ROOM, 1EA

REMOVE EXISTING ASBESTOS CONTAINING MATERIALS AS ACM REMOVAL NOTES.

AND ACM REMOVAL NOTES

SECTIONS, SCOPE OF WORK

CLOSET/CCTV

YI, SC

185600

BUILDING S-81, CP CASEY

A-5

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ARCHITECTURAL

152 MET STUD WALL

203 MET STUD WALL

LEGEND

92 MET STUD WALL

200 THK CONC WALL

EIFS ON EXISTING CMU WALL

SCALE: 1 : 50

15 THK GWB ON

C-100x50x20x2.3 @ 400 OC

92 MET STUD WALL

(1HR FIRE RATED & STC 50 W/ 90

THK SOUNDPROOF INSUL)

BEDROOM

LAUNDRY

MECH ROOM

CORRIDORVEST

VEST

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

108 109

FECB/B

BATH ROOM BATH ROOM

CLOSET

CLOSET

CLOSET CLOSET

CLOSETCLOSETCLOSET

REF REF REF

REF REFREF REF

BATH ROOM BATH ROOM

BATH ROOM BATH ROOM

BATH ROOM

DASHED LINE FOR

ROOF(ABOVE)

D

C

B

A

TYP

33,934

8,5858,3828,3828,585

6101,6262,0321,6267,1121,6262,8451,6261,6261,6265,6901,6262,0321,626610

,1

1,300

8,5858,8903,8612,6429,957

4061,4221005004,2771,6262,0321,626610 6101,6262,0321,6265,8931,6262,0321,626406

1,5851,0003,7003,7001,0003,6823,6821,0003,7003,7001,0001,5852,300

1,4111,9005501,4421,0002003,7041,0002,953

5001,900200700561

2,6001,261

,8

,5

,8

,6

2,300

COMM

15 THK GWB ON 38

FURRING CHANNEL ON

EXISTING CMU WALL

15 THK GWB ON 38

FURRING CHANNEL ON

EXISTING CMU WALL

15 THK GWB ON 38

FURRING CHANNEL ON

EXISTING CMU WALL

15 THK GWB ON 38

FURRING CHANNEL ON

EXISTING CMU WALL

15 THK GWB ON 38

FURRING CHANNEL ON

CONC WALL

DASHED LINE

FOR AIR INTAKE

LOUVER (TYP)

ENLARGED FLOOR PLAN

ENLARGED FLOOR PLAN

A-6

A-6

A-6

A-6

BEDROOM

A-11

L/S

W

D

W

CLOSET/CCTV

2003,461200

YI, SC

185600

BUILDING S-81, CP CASEY

REFREF

WCLAV

TB

SHD

SH

TTD

WCLAV

TB

SHD

SH

TTD

B

GCWT

SINKREF

(GFGI)

PAINT

GWB

MICRO WAVE

(GFGI)

GCWT

GCWT

PAINT GWB

REF

(GFGI)

D

C

B

A

D

C

B

A

D

C

B

A

D

C

B

A

SC/R

WC

SH

SHD

LAV

GCWT-1 (TYP)SHD

VCBA C D A B C D

TTD

B

4 1 3

GCWT

SINKREF

(GFGI)

PAINT

GWB

MICRO WAVE

(GFGI)

GCWT

PAINT GWB

REF

(GFGI)

VCBA C D

WC

SH

SHD

LAVA B C D

TTD TTD

SOAP HOLDERSH

WC WATER CLOSET

TOILET TISSUE DISPENSERTTD

TB TOWEL BAR

MG MIRROR GLASS

LAV LAVATORY

ABBREVIATION

SC/R SHOWER CURTAIN ROD

SHOWER HEADSHD

REF REFRIGERATOR

LIGHT SWITCH

203 MET STUD WALL

LEGEND

92 MET STUD WALL

VERIFY DIM.

GCWT

T B

TOWEL BAR

TOWEL BAR

SC/R

GCWT-1 (TYP)SHD

DOOR TO

CORRIDOR

A B

D L/S

DRYER(GFCI)

(TYP)

WASHER

(GFCI) (TYP)

GCWT

W

C D

FCU

GCWT

SHOWER CURB

MOP RACK

A-6

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ARCHITECTURAL

SHELF & ROD

200 1400

INTERIOR ELEVATIONS

TYPICAL PARTIAL PLANS AND

WC

780 960

750450450

1650800

780 1460 650

450 450 750

C L

G H

G T

VERIFY DIM

VERIFY DIM

C L

G H

G T

0 M

G

L A

V

S H

T T

D

S C /R

T B

C L

G H

G T

VERIFY DIM

VERIFY DIM

C L

G H

G T

0 M

G

L A

V

T T

D 0 S

H

T B

0S C /R

T T

D

C L

G H

G T

M O

P R

A C

K

ELECTRIC

RANGE

(GFGI)

HOOD

(SEE MECH

DWG)

DASHED LINE FOR

LIGHTING ON SSM

(SEE ELEC DWG)

SHOWER CURTAIN

W/ ROD

OPEN TO

BEDROOM

ELECTRIC

RANGE

(GFGI)

HOOD

OPEN TO

BEDROOM

SHOWER CURTAIN

W/ ROD

DASHED LINE FOR

LIGHTING ON SSM

(SEE ELEC DWG)

92 MET STUD WALL

(1HR FIRE RATED & STC 50 W/ 90

THK SOUNDPROOF INSUL)

SSM TRIM

SSM TRIM

SSM TRIM

SSM TRIM

SCALE: 1 : 50

TYP PARTIAL PLAN-BATHRM 2

SCALE: 1 : 50

TYP PARTIAL PLAN-BATHRM

A-6 A-6

SCALE: 1 : 50

CLOSET PARTIAL PLAN

A-5

SCALE: 1 : 50

SCALE: 1 : 50

INTERIOR ELEVATION (BED ROOM-1) INTERIOR ELEVATION (BATH ROOM-1)

A-6 A-6

SCALE: 1 : 50

INTERIOR ELEVATION (BED ROOM-2) 7

SCALE: 1 : 50

INTERIOR ELEVATION (BATH ROOM-2)

A-6 A-6

SCALE: 1 : 50

INTERIOR ELEVATION (LAUNDRY)

A-5

SST SHELF

A-6

A-6 A-6

A-6

A-12

A-11

A-10 A-10

A-12 A-12 A-12A-12

A-10

A-10

MC

TB MCTB

MC

MC

MC

TB

TB

SC

SC

(GFGI) (GFGI)

W

YI, SC

185600

BUILDING S-81, CP CASEY

1A

1B

1C

1D

1E

1ST FL

WORK POINT

MECH ROOM

BEDROOM

1ST FL

WORK POINT

CORRIDOR

V A

R

1ST FL 1ST FL

TOP OF CONC

VEST

CORRIDOR

1ST FL

A-7

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ARCHITECTURAL

SCALE: 1 : 30

WALL SECTIONS-1

WALL SECTIONS-1

C L

G H

G T

C L

G H

G T

C L

G H

G T

BEDROOM

STANDING SEAM

METAL ROOFING

W/ INSUL ON VR

FINISH PER

SCHEDULE

INSULATED

BLAST AL

WINDOW

PROTECTED

METAL GUTTER

PROTECTED

MET FLASHING

PROTECTED MET

SOFFIT

PAINT

15 THK GWB

ON C-100x50x20x2.3

@ 400 OC

FINISH PER

SCHEDULE

GALV METAL

ROOF LINER

THERMAL

INSULATED

METAL DOOR

GALV METAL

ROOF LINER

STANDING SEAM

METAL ROOFING

W/ INSUL

GALV METAL

ROOF LINER

FINISH PER

SCHEDULE

EIFS ON

CONC WALL

STANDING SEAM

METAL ROOFING

W/ INSUL ON VR

CONC

STOOP

FINISH PER

SCHEDULE

PAINT

15 THK GWB

ON 38 FURRING

CHANNEL @ 400 OC

HDR ON CONC

EXISTING CONC

SLAB TO

REMAIN(TYP)

2% SLOPE

NFSM

0.5 THK

COPPER

FLASHING

EIFS ON 12 THK

CEMENT BOARD

ON C-100x50x20x2.3

STL CHANNEL

@ 400 OC

PROTECTED

METAL FLASHING

STANDING SEAM

METAL ROOFING

W/ INSUL ON VR

GALV METAL

ROOF LINER

THERMAL INSULATED

BLAST METAL DOOR

12 THK GWB ON

C-100x50x20x2.3 STL

CHANNEL

@ 400 OC

FINISH PER

SCHEDULE

FINISH PER

SCHEDULE

CONC

STOOP

EIFS ON 12 THK

CEMENT BOARD

ON C-100x50x20x2.3

STL CHANNEL

@ 400 OC

PROTECTED

METAL FLASHING

VAPOR BARRIER

ON NFSM

(SEE STRL DWG)-TYP

SIDE WALK

(SEE CIVIL

DWG)

2% SLOPE

FINISH PER

CURTAIN BOX

STANDING SEAM

METAL ROOFING

W/ INSUL ON VR

PROTECTED

METAL GUTTER

PROTECTED

MET FLASHING

PROTECTED MET

SOFFIT

EIFS ON

EXISTING WALL

GALV METAL

ROOF LINER

BATHROOM

SHOWER

AREA

GCWT ON THINSET MORTAR

ON 12 THK CEMENT BOARD

ON 203 MET STUD @ 400 OC

(MAX)

PAINT 15 THK GWB ON BOTH SIDE OF

1HR FIRE RATED WALL(SEE NOTE)

(STC 50 MIN. W/ ACOUSTICAL/FIRE

SEALANT @ BOTTOM TOP OF WALL &

PENETRATIONS)

FINISH PER

SCHEDULE

PAINT 12 THK

WATER

RESISTANT

GWB

FINISH PER

90 THK GLASS FIBER INSUL

(30 kg/m²)

1A 1B 1C 1D

1E

A-9

A-11

A-10

A-9

NOTE :

1HR FIRE RATED WALL:

-15 THK TYPE "X" GWB OF BOTH SIDE

ON 92 MET STUD @ 400 OC (MAX)

WOOD SILL

OAK (TYP)

WOOD HEAD

OAK (TYP)THERMAL

SCHEDULE

SCHEDULE

NFSM

EIFS ON EXST

CMU WALL

PROTECTED MET

FLASHING

WOOD JAMB OAK

OAK (TYP)

GCWT ON THINSET MORTAR

(ON WATER PROOFING MEMBRANE,

FULL HEIGHT @ SHOWER AREA ONLY)

ON EXISTING CMU WALL(TCNA, W211-13)

FCT ON CEMENT MORTAR BED

(ON WATER PROOFING MEMBRANE

@ SHOWER AREA ONLY)

ON CONC SLAB (TCNA, F121-13)

GCWT ON THINSET MORTAR

(ON WATER PROOFING MEMBRANE, FULL

HEIGHT @ SHOWER AREA ONLY)

ON 12 THK CEMENT BOARD ON 203 MET STUD

(TCNA, W244C-13)

FM WP 45 (GA FILE NO WP1072)

YI, SC

185600

BUILDING S-81, CP CASEY

1B

1A

1C

1D

1B

CORR

109MECH ROOM

111 113

MECH ROOM

BEDROOM

BEDROOM

(S

C /R

MECH ROOM

BEDROOM

A-8

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ARCHITECTURALSCALE: 1 : 30

WALL SECTIONS-2

WALL SECTIONS-2

C L

G H

G T

C L

G H

G T

C L

G H

G T

C L

G H

G T

COMM

SHOWER

AREA

PAINT 12 THK

WATERRESISTANT

GWB

GALV METAL

ROOF LINER

FINISH PER SCHEDULE

HDR ON

CONC

BATH

ROOM

STANDING SEAM

METAL ROOFING

W/ INSUL ON VR

STANDING SEAM

METAL ROOFING

W/ INSUL ON VR

GALV METAL

ROOF LINER

GALV METAL

ROOF LINER

PAINT ON 15 THK GWB ON BOTH

SIDE OF 1 HR FIRE RATED WALL

(SEE NOTE)

(STC 45 MIN. W/ ACOUSTICAL/FIRE

SEALANT @ BOTTOM TOP OF WALL

& PENETRATIONS)

FINISH PER

SCHEDULE

STANDING SEAM

METAL ROOFING

W/ INSUL ON VR

FINISH PER

SCHEDULE

EXISTING CONC

SLAB TO

REMAIN(TYP)

VAPOR BARRIER

ON NFSM

(SEE STRL DWG)-TYP

FINISH PER

12 THK CEMENT

BOARD ON 1HR FIRE

RATED WALL

(SEE NOTE)

90 THK GLASS FIBER INSUL

(30 kg/m²)

FIRE STOPPING

W/ FIRE SEALANT

GALV METAL

ROOF LINERGALV METAL

ROOF LINER

FIRE STOPPING

W/ FIRE SEALANT

CONC WALL

(1 HR FIRE RATED WALL)

CONC WALL

(1 HR FIRE RATED WALL)

HDR ON

CONC

LAUNDRY

PAINT 15 THK GWB

ON 38 FURRING

CHANNEL @ 400 OC

FIRE STOPPING

W/ FIRE SEALANT

CONC WALL

(1 HR FIRE

RATED WALL)

HDR ON

CONC

PAINT ON 15 THK GWB

ON 92 METAL STUD @ 400 OC

(STC 45 MIN. W/ ACOUSTICAL/FIRE

SEALANT @ BOTTOM TOP OF WALL

& PENETRATIONS)

PAINT GALV

METAL ROOF

LINER

1A 1B 1C

1D

A-10

NOTE :

1HR FIRE RATED WALL:

-15 THK TYPE "X" GWB OF BOTH SIDE

ON 92 MET STUD @ 400 OC (MAX)

SCHEDULE

C L

G H

G T

FM WP 45 (GA FILE NO WP1072)

GCWT ON THINSET MORTAR

(ON WATER PROOFING MEMBRANE, FULL

HEIGHT @ SHOWER AREA ONLY)

ON 12 THK CEMENT BOARD

(TCNA, W244C-13)

ON 1 HR FIRE RATED WALL(SEE NOTE)

(STC 45 MIN. W/ ACOUSTICAL/FIRE SEALANT

@ BOTTOM TOP OF WALL & PENETRATIONS)

GCWT ON THINSET MORTAR

ON 12 THK CEMENT BOARD

(TCNA, W244C-13)

ON 152 METAL STUD @ 400 OC

FCT ON CEMENT MORTAR BED

ON WATER PROOFING MEMBRANE

ON CONC SLAB (TCNA, F121-13)

CLOSET/CCTV

YI, SC

185600

BUILDING S-81, CP CASEY

A-9

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ARCHITECTURAL

1.

NOTES :

0.25 THK POLYETHYLENE SHEET VAPOR RETARDER SHALL BE PROVIDED OVERLAP

& SEAL W/ SELF ADHESIVE AIR BARRIER AT JOINT & PENETRATION.

GALV

MET ROOF LINER

VAPOR RETARDER

INSULATION

GALV

SEALANT

SEALANT

MET F

LASHIN

G

MECH EQUIPMENT

(SEE MECH DWG)

OUTLINE OF

W/CRICKET

P.M FLASHING

M

IN

18 GA GALV MET CURB W/

100 FLANGE (ALL AROUND)

50x150 TREATED WOOD

P.M BASE FLASHING

P.M CAP FLASHIG

METAL ROOFING

STANDING SEAM

BLOCKING NAILER

CURB OPENING

(ALL AROUND OUTSIDE OF CURB)

RIGID INSULATIONCONNECT DUCT

INSUL ON VR

(TYP)

METAL ROOF LINER

METAL TRIM

CLOSURE

18 GA "Z"

CLOSURE

METAL ROOFING

STANDING SEAM

INSERT SCREEN

PROTECTED MET

W/MET FRAME

& FASTENERS

CAP FLASHING

FLASHING

EPDM PIPE

M

IN

VENT PIPE

GALV MET TRIM

INSUL OB VR

(SEE MECH DWG)

SEAM

STANDING

ROOF LINER

GALV MET

MET ROOFING

METAL ROOF LINER

INSUL ON VR

WORKING POINT

"Z" CLOSURE

GLAV

GLAV

PROTECTED METAL

RAKE FLASHING

MASTIC STANDING SEAM

MET ROOFING

INSULATION

GALV

METAL ROOF LINER

INSUL ON VR

STANDING SEAM

MET ROOFING

PROTECTED METAL

FLASHING

300300

EXTERIOR INSUL

& FNSH SYSTEM

PROTECTED MET

DOWNSPOUT

PAINT

15 THK GWB

ON C-100x50x20x2.3

@ 400 OC

25Wx3THK BRACKET

HANGER @ 900

OC(MAX)

(STAGGERED W/

STRAP HANGERS)

PROTECTED MET

WATER DRIP

PROTECTED MET SOFFIT

ON C- 100x50x20x2.3 W/

INSUL ON VR

SEALANT W/

BACKER ROD

PROTECTED MET GUTTER

(SEE INTO BRACKET

HANGER)

METAL STRAP HANGER @

900 OC (MAX)

(RIVER TO GUTTER EDGE)

CONTINUOUS METAL

EDGE STRIP

25 THK THERMAL

SPACER BLOCK

STANDING SEAM

MET ROOFING

PROTECTED MET

SOFFIT

ON C-100x50x20x2.3

@ 400 OC

SEALANT W/

BACKER ROD

PROTECTED MET

WATER DRIP

EXTERIOR INSUL &

FNSH SYSTEM

ON 12 THK CEMENT BOARD

ON C-100x50x20x2.3

@ 400 OC

CONC BOND BEAM

(SEE STRL DWG)-TYP

VAPOR

RETARDER

ON GALV MET

ROOF LINER

EIFS CONTROL JOINT W/

SEALANT & BACKER ROD

CEILING

(SEE FINISH SCHEDULE)

PAINT

15 THK GWB

ON 38 FURRING

CHANNEL @ 400 OC

CONC BOND BEAM

(SEE STRL DWG)-TYP

CEILING

(SEE FINISH

SCHEDULE)

"Z" CLOSURE

(MIN

http://youtu.be/hUNupHDgHa4

SCALE: 1 : 10A-2

ROOF EAVE DETAIL-1 2

SCALE: 1 : 10A-2

ROOF EAVE DETAIL-2

SCALE: 1 : 10A-2

METAL CURB DETAIL

SCALE: 1 : 10A-2

ROOF EDGE DETAIL 5

SCALE: 1 : 10A-2

VENT THRU ROOF DETAIL

SCALE: 1 : 10A-2

ROOF VALLEY DETAIL

EAVE FL

ASHING

25 200

MIN

150 150

EAVE FL

ASHING

ROOF DETAILS

YI, SC

185600

BUILDING S-81, CP CASEY

A-10

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ARCHITECTURAL

2A

2C

13 THK SOLID SURFACING

PLYWOOD (COUNTER TOP & BACK )

MATERIAL (SSM-1) ON 18 THK

SEALANT

20x100

WD SHIM

WD SHIM

20x100

2B

2D

C L

G

H

T

20X100 WD

(SEE ELEC DWG)

LIGHTING

MIRROR ON 7.5 THK PLYWD

POST-FORMED 13 THK

SOLID SURFACING MATERIAL

ON 7.5 THK PLYWD

MARINE EDGE

ON 18 THK PLYWOOD

PLASTIC LAMINATE (PL-1)

10 DIA POLISHED BRASS ROD

PULL @ EACH DOOR (B02011)

ON 7.5 THK PLYWOOD(FRONT)

PLASTIC LAMINATE (PL-2)

W/ HINGE (2PR-BO1602

@ EACH DOOR)

PLASTIC LAMINATE (PL-2)

ON 18 THK PLYWOOD

(TOP & EDGE)

(FRONT, BACK & EDGE)

1B

1C

1A SCALE : 1/10

LAV BOWL

(SEAMED UNDERMOUNT)

5B

5A

SECTION

P L A N

FEILD TILE )

( COLOR TO MATCH

PORCELAIN SOAP HOLDER

CERAMIC TILE

WATERPROOF MEMBRANE

SOAP HOLDER

CERAMIC TILE

PORCELAIN

WATERPROOFING MEMBRANE

CEMENT MORTAR

ON METAL LATH

W/6 DIA TOGGLE

ON WATERPROOFING

6 THK CEMENT BOARD

TOWEL BAR

FLANGE

TOWEL BAR

GCWT ON

BOLT

MEMBRANE ON

CONNECTED METAL

METAL CHANNEL

STUD

METAL STUD

@ 406 OC

4 THK BENT

W/ 6 DIA EXP BOLTS

@ 300 OC

SST BASE (WELDED)

R=5

12 THK SSM

SEALANT

WATER PROOFING

MEMBRANE

SHOWER AREABATH ROOM

SHOWER CURTAIN

2C

2B

2D

2A

L-50x50x6x50LG STL

PLASTIC LAMINATED (PL-2)

ON 18 THK PLYWD(TOP)

ON 7.5 THK PLYWD

PLASTIC LAMINATED (PL-2)

FIXED TO WD BLOCK &

50x100 WD

BLOCK

SILICONE SEALANT

30x50 HARDWD

18X18 HARDWD TRIM

W/ PLASTIC LAMINATED

POST-FORMED 13 THK

ON 18 THK PLYWOOD

MARINE EDGE

(FRONT, BACK & EDGE)

PLASTIC LAMINATED (PL-1)

ON 18 THK PLYWD

SOLID SURFACING (SSM-1) MATERIAL

50x100 WD BLOCK

WD BLOCK & TO

CONC SLAB W/

6DIA EXP BOLTS

@ 450 OC

L-50x50x6x50LG STL

CLIP FIXED TO

18 x 18

PLASTIC LAMINATED (PL-2)

ON 18 THK PLYWD

PLASTIC

PLYWD

& EDGE)

ON 7.5 THK PLYWOOD

PLASTIC LAMINATED

ON 18 THK PLYWOOD

POST-FORMED 13 THK

SOLID SURFACING (SSM-1) MATERIAL

(FRONT)

HARDWD TRIM

ON 18 THK

LAMINATED (PL-1)

(FRONT, BACK

W/ PLASTIC

LAMINATED (PL-1)

(TOP & EDGE)

MIRROR ON 7.5 THK PLYWD

WATER PROOFING

EXP BOLT @ 450 OC

TO CONC SLAB W/6 DIA

SEAL W/ BOLT

FOR WATER PROOFING

SEAL W/ BOLT

FOR WATER PROOFING

7.5 THK PLYWOOD

W/ GLUE

6 THK MIRROR ON

6 THK MIRROR ON

MATERIAL

SURFACING

13 THK SOLID

POST-FORMED

SEALANT

W/ GLUE

7.5 THK PLYWOOD

SST FRAME

12 THK CEMENT

BOARD

BOARD

12 THK CEMENT

SST FRAME

POST-FORMED

13 THK SOLID

SURFACING

MATERIAL

SEALANT

1C

1B SCALE : 1/2

SCALE : 1/2

SEALANT

BASE FLASHING

PROTECTED MET

PROTECTED

METAL

"Z" CLOSURE

T O

F

EIFS ON 12 THK

CEMENT BOARD

ON C-100x50x20x2.3

STL CHANNEL

@ 400 OC

100 THK TREATED

WD NAILER

80x80x7.0THK STEEL

ANGLE FRAME

@ 850 OC

METAL STRAP HANGER

@ 900 OC (MAX)

(RIVER TO GUTTER EDGE)

PROTECTED MET GUTTER

(SEE INTO BRACKET

HANGER)

25 W x 3 THK

BRACKET HANGER @

900 OC(MAX)

(STAGGERED W/

STRAP HANGERS)

PROTECTED MET

SOFFIT

C-100x50x20x2.3

W.P

STANDING SEAM

METAL ROOFING

CANOPY

EAVE FL

ASHING

SCALE:A-6

TYP LAVATORY COUNTER DETAIL

AS SHOWN

SCALE:A-6

SHOWER CURB DETAIL

1:5

SCALE:A-6 1:10

TOWEL BAR DETAIL 5

SCALE:A-6 1:10

SOAP HOLDER DETAILS

SCALE:A-10 1:5

D E T A I L S 6

SCALE:A-7 1:5

CANOPY DETAIL

A-10

A-10

A-10

A-10

A-10A-10

MISC DETAILS-1

12 THK CEMENT BOARD

12 THK CEMENT BOARD

COAT

THINSET MORTAR

THINSET MORTAR

BOND COAT

GCWT W/CEMENT

GCWT W/ CEMENT BOND

YI, SC

185600

BUILDING S-81, CP CASEY

A-11

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ARCHITECTURAL

THE GUTTER & TO MEET AT/FP REQUIREMENTS.

3. TO PREVENT LEAVES FROM COLLECTING IN

2. INSTALL REMOVABLE METAL SCREEN AT ALL GUTTERS.

SHOULD NOT BE EXCEEDED MAX 12,000mm.

1. DISTANCE BETWEEN GUTTER EXPANSION JOINTS

SECTION A-A

NOTE

SECTION A-A

MET. GUTTER

CONTINUOUS

A

CLEAT

MET. ROOFING

CLEAR

SLOPE

1:200

RIVET &

SOLDER

GUTTER

GUTTER LAP

ENDS

A

SLOPE

SLOPE

1:200

THAN BACK (MIN)

FRONT 12 LOWER

4B SECTION

& FINISH SYSTEM

EXT INSUL

FILL GROUT

FL LEVEL

& FINISH SYSTEM

EXT INSUL

AL SHEET FLASHING

SEALANT

SSTL PLATE

5 THK BENT

4B

4A ELEVATION

& FINISH SYSTEM

EXT INSUL

SSTL PLATE

5 THK BENT

FL LEVEL

DASHED LINE FOR

(BEYOND)

LOUVER

(SEE MECH DWG)

ELEVATION

O

U T S

ID

E

R

IM

D

IN

S

B

X

(INSIDE BOX DIM)

1B

(OUTSIDE TRIM DIM)

METAL

DOOR PULL

METAL FIRE

CABINET

EXTINGUISHER

PLEXIGLASS

METAL TRIM

L

IN

S

PULL

SIDE)

METAL DOOR

6 DIA METAL

SCREW (3-PER

SCHEDULE

FLAT TRIM

FINISH PER

(ALL AROUND)

WOOD SHIM

R

O U

P

E N

IN

G

1C SECTION

1A PLAN

(INSIDE BOX DIM)

(OUTSIDE TRIM DIM)

(INSIDE BOX DIM)

1C 1B

FLAT TRIM

IN

S

WOOD SHIM

(ALL AROUND)

DOOR PULL

CASING BEAD

(TYP)

(ROUGH OPENING)

1HR FIRE RATED

WALL

ON 92 MET STUD

15 THK GWB

@ 400 OC

3B

WOOD FRAME

EXSTING CMU WALL

EXP BOLTS

BULLETIN BOARD

RADIUS(3 MIN-TYP)

(HEAD, JAMB & SILL)

3 THK MET CLIP

@ 450 OC W/6 DIA

O O

R

SECTION

SCALE: 1/2

(NATURAL FINISH)

BULLETIN BOARD

WOOD FRAME

(NATURAL FINISH)

ELEVATION

SCALE: NONE

3A

FL

150 1910

T O

F F

L

(TYP)

(TYP)

@ 900 OC

METAL DS

(150 x 100)

1.5 THK X 50 W

DS STRAP HANGER

@ 900 OC (MAX)

PROTECTED METAL

EXT INSUL & FNSH SYSTEM

PROTECTED

9 DIA EXP BOLT

SST PLATE

3THKx50W

SST STRAP

75Wx150Hx5THK

CMU WALL

6 DIA CAP

W/WASHER (TYP)

CAP SCREW & NUT

RUST PROOF

SEALANT

PAINT 15 THK GWB

ON 92 METAL STUD

@ 400 OC

12 THK SSM

R=5

GCWT ON

ON 12 THK

CEMENT BOARD

25 THK WOOD TRIM

SEALANT

PAINT 15 THK GWB ON BOTH SIDE OF

(STC 45 MIN. W/ ACOUSTICAL/FIRE

SEALANT @ BOTTOM TOP OF WALL &

PENETRATIONS)

90 THK GLASS FIBER INSUL

(30 kg/m²)

L-150x150x6 THK

W/12 DIA BOLTS & NUTS

@ 450 OC

19 THK OAK WD

(NATURAL FINISH)

SEALANT(TYP)

30 300 30

4545 300

SCALE:A-5 1:10

FIRE EXTINGUISHER CABINET DETAIL

SCALE:A-7 1:2

CURTAIN BOX DETAILS

SCALE:A-5 1:2

BULLETIN BOARD DETAILS

SCALE:A-3 1:10

AIR INTAKE LOUVER DETAILS

SCALE:A-6 1:2

SSM TRIM DETAIL

SCALE:A-3 1:5

DOWNSPOUT HANGER DETAIL 6

SCALE:A-2 N/A

GUTTER EXPANSION JOINT DETAILS

MISC DETAILS-2

1HR FIRE RATED WALL

(SEE MATERIAL SCHEDULE

BB-1 , A-13)

CEMENT BOND COAT

CONC WALL

YI, SC

185600

BUILDING S-81, CP CASEY

CEILING LINE

PULL @ EACH DOOR

(B02011) 10 DIA POLISHED

C

T

20x100

(TYP)

WD SHIM

PLASTIC LAMINATE (PL-1)

(TOP,BOTTOM, & EDGE)

ON 18 THK PLYWOOD

REF (GFGI)

7.5 THK PLYWOOD (FRONT)

PLASTIC LAMINATE (PL-2)

(B04071 & B04081)

PLASTIC LAMINATE (PL-2)

PLASTIC LAMINATE (PL-2)

ON 18 THK PLYWOOD

ON 18 THK PLYWD

PLASTIC LAMINATE(PL-2)

MET ADJ SHELF HARDWARE

(TOP,BOTTOM & EDGE)-TYP

(BOTTOM & EDGE)-TYP

2PR - B01602 @ EACH DOOR)-TYP

(FRONT, BACK & EDGE W/HINGES

PLASTIC LAMINATE (PL-1) ON 18 THK PLYWD

ON 7.5 THK PLYWOOD (FRONT)-TYP

PLASTIC LAMINATE (PL-1)

PULL @ EACH DOOR

(TOP,BOTTOM, & EDGE)-TYP

ON 18 THK PLYWOOD

LIGHTING FIXTURE (SEE ELEC DWG)

(B02011) 10 DIA POLISHED BRASS ROD

18 THK PLYWOOD

ON METAL STUD WALL

ON 12 THK CEMENT BD

MARINE EDGE

13 THK SOLID SURFACE

MATERIAL (SSM-1) OVER

KITCHEN SINK

(SEE MECH DWG)

(COUNTERTOP, BACK &

SIDE SPLASH)

ON 18 THK PLYWOOD

PLASTIC LAMINATE (PL-1)

10 DIA POLISHED BRASS ROD

PULL @ EACH DOOR (B02011)

25X50 WD

VCB

ON 7.5 THK PLYWOOD(FRONT)

PLASTIC LAMINATE (PL-2)

W/ HINGE (2PR-BO1602

@ EACH DOOR)-TYP

PLASTIC LAMINATE (PL-2)

ON 18 THK PLYWOOD

BOLTS @600 OC

X50 LG W/ 12DIA EXP

50X100 WD & 50X50X6

(TOP & EDGE)-TYP

(FRONT, BACK & EDGE)

20x100

(TYP)

WD SHIM

5D

5C

PULL @ EACH DOOR

(B02011) 10 DIA POLISHED BRASS ROD

7.5 THK PLYWOOD (FRONT)

PLASTIC LAMINATE (PL-2)

ON 18 THK PLYWD

PLASTIC LAMINATE (PL-2)

(TOP,BOTTOM & EDGE)

MICROWAVE(GFGI)

PLASTIC LAMINATE (PL-1)

(TOP,BOTTOM, & EDGE)

ON 18 THK PLYWOOD

ON METAL STUD WALL

ON 12 THK CEMENT BD

BOLTS @600 OC

X50 LG W/ 12DIA EXP

50X100 WD & 50X50X6

C

T

20x100

(TYP)

WD SHIM

5D

VCB

5B

5A

18 THK PLYWOOD

(COUNTERTOP, BACK &

13 THK SOLID SURFACE

MATERIAL (SSM-1) OVER

SIDE SPLASH)

MARINE EDGE

@ EACH DOOR

PULL

PLASTIC LAMINATE (PL-2)

ON 7.5 THK PLYWOOD

(TOP, BOTTOM & EDGE)

METAL

ADJUSTABLE

25X50 WD

PLASTIC LAMINATE (PL-2)

ON 18 THK PLYWOOD

BRASS ROD

CEILING LINE

PLASTIC LAMINATE (PL-1)

ON 18 THK PLYWOOD (FRONT)-TYP

50x100 WD FRAME (TYP)CEILING LINE

PLASTIC LAMINATE (PL-1)

ON 18 THK PLYWOOD (FRONT)-TYP

50x100 WD FRAME (TYP)

C

T

(FRONT)

CEILING LINE

RANGE HOOD

(SEE MECH DWG)

PULL @ EACH DOOR

(B02011) 10 DIA POLISHED

C

T

20x100

(TYP)

WD SHIM

PLASTIC LAMINATE (PL-1)

(TOP,BOTTOM, & EDGE)

ON 18 THK PLYWOOD

ON METAL STUD WALL

ON 12 THK CEMENT BD

GCWT ON THINSET MORTAR

7.5 THK PLYWOOD (FRONT)

PLASTIC LAMINATE (PL-2)

BRASS ROD

50x100 WD FRAME (TYP)

PLASTIC LAMINATE (PL-1)

ON 18 THK PLYWOOD (FRONT)

ON METAL STUD WALL

ON 12 THK CEMENT BD

GCWT ON THINSET MORTAR

ON 12 THK CEMENT BD

5C

5B 5D

5A

L-50x50x6x50LG STL

PLASTIC LAMINATED (PL-2)

ON 18 THK PLYWD(TOP)

ON 7.5 THK PLYWD

PLASTIC LAMINATED (PL-2)

EXP BOLT @ 450 OC

FIXED TO WD BLOCK &

TO CONC SLAB W/6 DIA

50x100 WD

BLOCK

SILICONE SEALANT

30x50 HARDWD

18X18 HARDWD TRIM

W/ PLASTIC LAMINATED

POST-FORMED 13 THK

ON 18 THK PLYWOOD

MARINE EDGE

(FRONT, BACK & EDGE)

PLASTIC LAMINATED

ON 18 THK PLYWD

SOLID SURFACING (SSM-1)

DRAWER STOPPER

20x40 HARD WD

W/ PLASTIC

LAMINATED

(TOP)

ON 7.5 THK PLYWD

PLASTIC LAMINATED (PL-2)

50x100 WD BLOCK

WD BLOCK & TO

CONC SLAB W/

6DIA EXP BOLTS

@ 450 OC

L-50x50x6x50LG STL

CLIP FIXED TO

18 x 18

VCB

PLASTIC

PLYWD

& EDGE)

ON 7.5 THK PLYWOOD

ON 18 THK PLYWOOD

POST-FORMED 13 THK

SOLID SURFACING (SSM-1) MATERIAL

(FRONT)

HARDWD TRIM

ON 18 THK

LAMINATED (PL-1)

(FRONT, BACK

W/ PLASTIC

LAMINATED (PL-1)

(TOP & EDGE)

MATERIAL

(PL-1)

A-12

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ARCHITECTURAL

SCALE:A-6 1:10

CABINET DETAIL 2

SCALE:A-6 1:10

CABINET DETAIL

SCALE:A-6 1:10

UPPER CABINET DETAIL 4

SCALE:A-6 1:10

UPPER CABINET DETAIL

SCALE:A-12 1:5

D E T A I L S

SCALE:A-6 1:5

TYP SHELF & ROD DETAILS @ CLOSET

PLASTIC LAMINATED (PL-2)

A-12 A-12

A-12

A-12

A-12

CABINET DETAILS AND SHELF DETAIL

GCWT ON CEMENT BOND COAT GCWT ON CEMENT BOND COAT

GCWT ON CEMENT BOND COAT

PLASTIC LAMINATE (PL-1)

HANGING ROD

4 DIA HOLE (TYP)

CLOTHES

25 DIA SST PIPE

-25x25x2

2.5 THK SST

BRACKET

O O

R

HANGING ROD

SST BRACKET

CLOTHES

2.5 THK

25 DIA SST PIPE

-25x25x2 SST BRACKET

POSTFORM

22x200 WOOD

1.6 THK SST SOCKET

CLOTHES HANGING ROD

25 DIA SST PIPE

R

5 50

0 50

9 DIA TOGGLE BOLTS

PAINT GWB

PAINT CMU

BOTH SIDES-SHELF & SIDE PANEL

ON 18 THK PLYWD

PLASTIC LAMINATE (PL-1)

ON 18 THK PLYWD

@ 300 O.C

SEE DETAIL

@ 900 OC

@ 900 OC

100350

6A 6B

6C

@ 900 OC

6C

BOLTS

9 DIA TOGGLE

YI, SC

185600

BUILDING S-81, CP CASEY

O O

R

@ 600 O.C

20 THKx90

OAK CHAIR RAIL

CHAIR RAIL DETAIL

RADIUS

(3 MIN-TYP)

FACE OF WALL

SCALE : N/A

A-13

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ARCHITECTURAL

2.

1.

FOR SUBMITTAL REQUIREMENTS AND SPECIFIC ITEMS TO BE PAINTED.

SCHEDULE. SEE SPECIFICATION SECTION 09915 : EXTERIOR AND INTERIOR COLOR SCHEDULE

COLOR DESIGNATION SHALL BE AS INDICATED IN THE EXTERIOR AND INTERIOR FINISH COLOR

WITH THE CAMP CASEY EXTERIOR COLOR SCHEME AS APPROVED BY THE COR.

SELECTION OF EXTERIOR PAINT AND FACTORY APPLIED COLORS SHALL BE IN ACCORDANCE

MANUFACTURERS STANDARD MUST APPROACH.

COLOR IS NOT REQUIRED. THE SELECTIONS SERVE ONLY TO INDICATE THE COLOR WHICH THE

INTENDED TO LIMIT SELECTIONS OF PRODUCTS. AN EXACT MATCH OF THE MANUFACTURERS

MANUFACTURERS' COLORS LISTED ARE FOR IDENTIFICATION PURPOSES ONLY AND ARE NOT 3.

4.

ROOM NAMESROOM NOS

INTERIOR FINISH SCHEDULE

FLOOR BASE WALLS CEILING

REMARKS

FINISH COLOR FINISH COLOR FINISH COLOR FINISH COLOR HEIGHT

SURFACE

ROOFING

FLASHING

FASCIA

SOFFIT

DOOR & FRAME

HANDRAIL

MATERIAL

STEEL

STEEL PIPE

COLOR

CHOCOLATE

COLOR NO.

20095

CHOCOLATE

CHOCOLATE

CHOCOLATE

CHOCOLATE

CHOCOLATE

20095

20095

20095

20095

20095

REMARKS

WALL EIFS

WALL CMU

BEAM/COL CONC

CONC

SAND-STONE

SAND-STONE

SAND-STONE

SAND-STONE

23617

23617

23617

23617

PROTECTED METAL

EXTERIOR COLOR SCHEDULE-1

FS 595B

FS 595B

FS 595B

FS 595B

FS 595B

FS 595B

FS 595B

FS 595B

FS 595B

FS 595B

PT-1

MATERIAL & COLOR SCHEDULE

FLOOR MATERIAL/COLOR BASE MATERIAL/COLOR

WALL MATERIAL/COLOR

GCWT-1

PT-2

CEILING MATERIAL/COLOR

PVCT-1

OR APPROVED EQUAL

457.2MMx457.2MM, 3MM THK

KCC SENSE TILE, CERAMIC, TN2412C

PVC TILE

FCT-1

MAT'L

EXST

MAT'L

NEW

MAT'L

EXST

MAT'L

NEW

MAT'L

EXST

MAT'L

NEW

MAT'L

NEW

MAT'L

EXST

USER AGENCY.

SELECTION OF INTERIOR PAINT AND FACTORY APPLIED COLORS SHALL BE APPROVED BY

SHALL BE WATERPROOF TYPE GWB.GWB FOR TOILETS, AND OTHER WET AREAS 5.

101 THRU 107

BATH ROOM

BED ROOM VCBVCT PVCT

CMT FCT --

VCBF.F.

F.F.

PVCT-1

FCT-1 -

F.F.

VCB-1

GCWT

GWB PAINT

F.F.

PT-1

GWB GWB* PAINT

PAINT

PT-2

PT-2

GCWT GWB GWB* 2450

- - VAR

VCT GWB PAINT PT-1 GWB

F.F. PVCT-1 GWB GWB 2450

VCT

PVCT

PVCT

PVCT-1F.F.

VCB VCB F.F. VCB-1

VCB VCB F.F. VCB-1

F.F.

GWB

ACST

ACST

PAINT PT-2

GWB* : FIRE RETARDANT TYPE

FINISH SCHEDULE NOTES

VCT GWB PAINT PT-1PVCT PVCT-1F.F. VCB VCB F.F. VCB-1 GWB*

F.F. PVCT-1 CONC GWBVCT PVCT VCB VCB F.F. VCB-1 PAINT PT-1

WOOD

GWB* : WATERPROOF TYPE

GWB* : FIRE RETARDANT TYPE

GWB* : WATERPROOF TYPEFCT F.F. FCT-1 - - -

GWB* : FIRE RETARDANT TYPE

GWB* : FIRE RETARDANT TYPEF.F. ACST-1

ACST-1

OR APPROVED EQUAL

WHITE

MC 3102 (3S)

"KCC MITONE"

603MM x 603MM x 15MM THK

ACOUSTICAL CEILING TILE

STAIR WALLS

CORRIDOR

MECH ROOM

VEST

LAUNDRY

VEST

COMM CLOSET

112 -

HDR F.F. HDR-1

F.F. ACST-1

GWB 2450ACST F.F. ACST-1

GWB* PAINT PT-2 3000 GWB* : FIRE RETARDANT TYPE

CDA-300, CLEAR COATING

HDR-1

NOROO, DENSIL

OR APPROVED EQUAL

HARDENER

1200W x 900H

BB-1

MEDIUM GREY

POSTER PANEL: FABRICORK

FRAME: FINE WOOD

OR APPROVED EQUAL

MISC MATERIAL/COLOR

BULLETIN BOARD

PROTECTED METAL

PROTECTED METAL

PROTECTED METAL

OR APPROVED EQUAL

NON-SLIP, 300 x 300 x 8 THK

FG 7L67-1, MARON

DONGSEO, INUS

FLOOR CERAMIC TILE

OR APPROVED EQUAL

300 x 600 x 10 THK

LQR IN92-1, GLOSS

DONGSEO, INUS

GLAZED CERAMIC WALL TILE

GCWT-1

GCWT-1

KITCHEN CABINET NOTE

(PL-1).

PLYWD PANEL W/ PLASTIC LAMINATE

CONSTRUCTED OF SOLID WD TRIMS &

END PANEL AND ETC. SHALL BE

INCLUDING DOOR, DRAWER FRONTS, SIDE

ALL EXPOSED COUNTER CABINET FACES

5.

6.

(PL-2).

FINISHED W/ PLASTIC LAMINATE

ALL CABINET INSIDE SURFACE SHALL BE

7.

PL-1:

BY FORMICA OR APPROVED EQUAL.

7737-58, NATURAL CHERRY, MATTE

PLASTIC LAMINATE, COLOR:

PL-2:

BY FORMICA OR APPROVED EQUAL.

756-58, NATURAL MAPLE, MATTE

PLASTIC LAMINATE, COLOR:

SSM-1:

EQUAL.

MOSAIC BY FORMICA OR APPROVED

SOLID SURFACE, COLOR #651, CHICORY

FOR THE SOUND SILENCE.

EQUIPPED WITH RUBBER BUMPER

ALL CABINET DOORS SHALL BE

AND TO BE INSTALLED BY OTHER.

GOVERNMENT FURNISHED MATERIALS

MICROWAVE,RANGE AND REFRIGERATOR WILL BE 1.

2.

3.

4.

FINISHED W/ SOLID SURFACE MATERIAL (SSM-1).

ALL CABINET COUNTERTOP SHALL BE

8.

TWO (2) INCHES ACTURAL SIZE OF THE REF.)

JOB SITE, (REFRIGERATOR SPACE SHALL BE

AND CABINET SIZE WILL BE ADJUSTED ON THE

REFRIGERATOR DIMENSION IS APPROXIMATE SOLID SURFACE MATERIALS FOR APPROVAL.

OF HARDWARE, PLYWOOD, PLASTIC LAMINATE &

AND TEST REPORTS, CERTIFICATIONS

OF KITCHEN CABINETS WITH HARDWARE,

CONTRACTOR SHOULD SUBMIT SHOP DRAWING

& COLOR SCHEDULE AND NOTES

INTERIOR FINISH SCHEDULE, MATERIAL

NOROO, NR7066

OR APPROVE EQUAL

PAINT LATEX/ EGGSHELL

ARCHITECTURAL LATEX/ SEMIGLOSS

OR APPROVE EQUAL

NOROO, NR7066

PAINT HIGH PERFORMANCE

GCWT

SELECTED BY USING AGENCY.

PLASTIC LAMINATED COLOR TO BE

GCWT

PAINT PT-1GWB*

VCB-1

OR APPROVED EQUAL

DARK BROWN, 100 HGT, 3THK

LG HAUSYS

VINYL COVE BASE

: MOLD & MILDEW RESISTANT, STAIN PROOF

ANTIQUE WHITE

OR APPROVED EQUAL

ARDEX FG 4

* EPOXY GROUT COLOR FOR GCWT AND FT

GWB*

GWB*

GWB*

YI, SC

185600

BUILDING S-81, CP CASEY

A-14

ARCHITECTURAL

REMARKS

DOOR DIMENSION

WIDTH

MATERIAL

D1 B

DOOR

TYPE

DOOR

NOS.

ROUGH OPENING

WIDTH HEIGHT

HDW

SET

THICKHEIGHT NO (HR)

RATED

FIRE

LOUVERGLAZING

CUT

UNDER

FRAME

D2

D3

D4

D

D5

D - -

D6

D7

D

D8 E STEEL

STEEL 7

DOOR

12001626ALGLASSF - -------

STL HOLLOW CORE DOOR

C W/ STL FRAME

D

WOOD SOLID DOOR

BW/ STL FRAMEA

INSULATED STL DOOR

KEY BOX : WALL MOUNTED KEY BOX E83513.

COORDINATING WITH THE USER FOR APPROVAL BY COR.

THE CONTRACTOR SHALL SUBMIT MASTER KEYING CHART, 4.

5.

6.

8.

9.

7.

HEAT GAIN AND FIRERATED.

WHITE OR LIGHT BEIGE TO MAXIMIZE REFLECTANCE AND MINIMIZE

BE EQUIPPED WITH HORIZONTAL MINI BLINDS. COLOR SHALL BE

WINDOWS IN ALL AREAS WHERE FUNCTIONALLY WARRANTED SHALL

1.

2.

INSECT SCREEN SHOULD BE EQUIPPED TO ALL EXTERIOR WINDOWS.

NATURAL COLOR FINISH W/ QUARTER SLICED OAK.

ALL WOOD FLUSH DOORS SHALL BE FINISHED FACTORY COATED

10.

MANUFACTURER'S LISTED INSTRUCTIONS.

INSTALLED IN ACCORDANCE WITH NFPA 80 OR THE DOOR

INSTALLATION INSTRUCTIONS. FIRE RATED DOORS SHALL BE

TO BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER

DOOR FRAMES & FIRE RATED GLASS. FIRE RATED DOOR FRAMES

ALL FIRE RATED DOORS SHALL BE INSTALLED IN FIRE RATED

FABRICATION AND INSTALLATION

SHALL BE APPROVED BY THE CONTRACTING OFFICER BEFORE

DOORS AND ALUMINUM WINDOWS AS ACTUAL SIZE, AND DRAWINGS

THE CONTRACTOR SHALL PREPARE SHOP DRAWINGS FOR ALL

12.

2133STEEL STEEL 1000 2200 914 44.5 - -1

A STEEL 44.5 - -2

44.5 -3

E STEEL -6

STEEL -5

W/ STEEL FRAME

FACTORY FINISH

W/ QUARTER SLICED OAK

C

(2 EA)

P L A N

DOOR

S E C T I O N

STEEL TUBE

CONC STOOP

WELDED TO

STEEL PLATE

50 x 50 x 6THK

FOUNDATION

STEEL PLATE

STEEL TUBE

CONCRETE

170 x 170 x 6THK

WELDED TO

EYEBOLT

HOOK &

DOOR

HOOK & EYEBOLT

STEEL TUBE

CONC)

GALV STEEL

80x80x3.2 THK

50 x 50 x 6 THK STEEL

80x80x3.2 THK

WALL TYPE BUMPER L02101

GALV STEEL TUBE

(FILLED W/CONC)

PLATE WELDED TO

WALL TYPE BUMPER L02101

YELLOW STRIPS

BLACK BACKGROUND

TUBE (FILLED W/

1 DOOR STOP & HOLDER DETAILS

250X250

HARDWARE SCHEDULE & NOTES

DOOR / WINDOW SCHEDULE, ELEVATIONS,

GLASS VISION

PANEL AS

SCHEDULE

STEEL

W1

DOOR & WINDOW NOTES

HIGH QUALITY AND GRADE PRODUCTS WITH APPROVAL TO COR.

& QUALITY ARE NOT REQUIRED. BUT CONTRACTOR SHOULD INSTALL

AN EXACT MATCH OF THE MANUFACTURERS FUNCTION, GRADE, COLOR,

AND ARE NOT INTENDED TO LIMIT SELECTIONS OF PRODUCTS.

MANUFACTURERS LISTED ARE FOR IDENTIFICATION PURPOSES ONLY

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

DOOR / WINDOW / LOUVER SCHEDULE DOOR/ WINDOW / LOUVER ELEVATIONS

HARDWARE SCHEDULE

21331800 2200 1714STEEL

21331000 2200 914

STEEL

35.521331400 2200 1314

WOOD 2133800 2200 714

44.521331800 2200 1714

44.521331000 2200 914

44.521331000 2200 914

F

FIXED

HDW-4

THRESHOLD J32100

DOOR STOP L02161

KICK PLATE J102, SST

CLOSER CO2011

1 DOOR VIEWER LO3221

3 HINGES A5111 114X114, NRP

SOUND PROOF SEAL1

ROY 265 (FOR HEAD & JAMB)

WOOD

STEEL

G AL 300AL 700 - - - - - - - -L1

WOOD* 1/3 * SOUNDPROOF WOODEN DOOR, STC-25 MIN

G

HDW-1

WEATHER STRIP

THRESHOLD J321001

HINGES A5112, 114x114, NRP

1 DOOR CLOSER CO2021

EXIT DEVICE TYPE-3, F08

(ROY 154 FOR HEAD/JAMB)

ROY 414 FOR SILL)

1 KICK PLATE J102, SST

(LEVER TYPE HANDLE)

HINGES A5112 114x114, NRP

LOCKSET 1000-1, F07

FLUSH BOLTS L04081

1 ASTRAGAL

1 WEATHERSTRIP

(ROY 165 FOR HEAD/ JAMB,

ROY 415 FOR SILL)

HDW-2 (MECH)

HDW-3

DOOR STOP LO2161

KICK PLATE J102, SST1

HINGES A5112, 114x114, 1 DOOR CLOSER CO2011

THRESHOLD J321001

(INT ENT.)

AUTOMATIC DOOR BOTTOM ROY 3351

(UNIT ENT)

HDW-6

DOOR STOP LO21412

HINGES A5112, 114x114

2 MAGNETIC DOOR LATCH

ROD TYPE DOOR PULL

(CLOSET)

HINGES A5112 114X114

THRESHOLD

DOOR STOP L02161

HDW-5

(LEVER TYPE HANDLE)

(SOLID SURFACE MATERIAL)

(NEAR THE HINGE)

(BATHRM)

HINGES A5112 114x114

HDW-8

LOCK SET 1000-1, F071

2 DOOR STOP L02141

(LEVER TYPE HANDLE)

(COMM)

FLUSH BOLTS L040812

HDW-7

DOOR STOP LO2161

KICK PLATE J102, SST1

HINGES A5112, 114x114

1 DOOR CLOSER CO2011

LOCKSET 1000-1, F01

THRESHOLD J321001

(LEVER TYPE HANDLE)

(LAUNDRY)

WOOD

150x750

1)

E

WOOD SOLID DOOR

W/ STEEL FRAME

FACTORY FINISH

W/ QUARTER SLICED OAK

WOOD

3/4

- 1/3

150x750

1)

1) FIRE RATED / LAMINATED GLASS

44.5

150x750

1)

1) INSULATED / LAMINATED GLASS

1) LAMINATED GLASS

12001422ALGLASSF - -------W2

G AL 700AL 700 - - - - - - - -

G AL 200AL 400 - - - - - - - -

1DOOR STOP & HOLDER

1DOOR STOP & HOLDER

PULL PLATE J405

PUSH PLATE J301

19MM

LOCKSET F76

(EXT ENT)

GLASS VISION

PANEL AS

SCHEDULE

THERMAL INSULATED

BLAST METAL DOOR

W/ METAL FRAME

: 40.6 KPA

- PEAK IMPULSE

: 210 KPA-MS

PRESSURE

- PEAK REFLECTED

(ANODIZED DARK BRONZE)

AL BLAST WINDOW

(THERMAL BREAK TYPE)

SLIDING

W/ INSECT SCREEN

- PEAK REFLECTED PRESSURE

: 40.6 KPA

- PEAK IMPULSE

: 210 KPA-MS

( SHGC : MAX 0.4 )

+ 6 THK TINTED LOW-E TEMPERED GLASS

+ 12 THK AIR SPACE

: 8.75 THK CLEAR LAMINATED GLASS

TYPICAL INSULATED/LAMINATED GLASS FOR WINDOWS

MINI-BLIND AND INSECT SCREEN

MINI-BLIND AND INSECT SCREEN

( SHGC : MAX 0.4 )

+ 6 THK TINTED LOW-E TEMPERED GLASS

+ 12 THK AIR SPACE

8.75 THK CLEAR LAMINATED GLASS

W/ INSECT /BIRD SCREEN

AND FRAME

FIXED AL LOUVER (45° BLADES)

LAMINATED GLASS : 8.75 THK CLEAR LAMINATED GLASS

VERIFY FIRE RATED GLASS W/ LAMINATED GLASS.11.

L2

L3

-4EA OF AA BATTERIES PER EACH LOCKSET

INTO USING AGENCY

-ADDITIONALLY 20% OF BLANK CARD KEYS SHOULD BE TURNED

-O&M TRANING TO DPW BY MANUFACTURER

-MASTER KEY SYSTEM

-CARD KEYED TYPE WITH 3EA CARD KEYS & PROGRAM

-SELF LOCKING

ONITY, MAGSTRIPE HT24 OR APPROVED EQUAL

ELECTRONIC CARD KEYED LOCKSET,

ELECTRONIC CARD

KEYED LOCKSET WITH BATTERY

(LEVER TYPE HANDLE)

OR APPROVED EQUAL

- WDMA TM-8 HINGE LOADING TEST METHOD

- WDMA TM-7 CYCLE SLAM TEST METHOD

2014 O&MA SPECIFICATIONS.

INDICATED ON SECTION 08 14 00, WOOD DOORS,

SHALL SUBMIT CERTIFICATIONS AND TEST REPORTS FOR APPROVAL AS

ALL WOOD DOORS SHOULD BE TESTED AS FOLLOWING,AND CONTRACTOR 13.

YI, SC

185600

BUILDING S-81, CP CASEY

A-15

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ARCHITECTURAL

BUILDING IDENTIFICATION LAUNDRY

1A 2C 2B1C

M E S S A G E DETAILELEVATION QUANTITY R E M A R K S

ELEVATIONM E S S A G E R E M A R K SDETAIL QUANTITY

IDENTIFICATION

1B 2A,2B

COORDINATED WITH THE CONTRACTING

1. SIGN MESSAGE COPY WILL BE

OFFICER AND USING AGENCY

BY THE SITE ADAPT CONTRACTOR

NOTE

BROWN

BACKGROUND

LETTERS

WHITE

NOTE : ROOM NUMBERS SHALL BE AS

SHOWN ON FLOOR PLAN

FIN. FL

FINISH SYSTEM

EXT.INSUL &

STEEL BOLT

8 PER SIGN

ALUM. SLEEVE

MASTIC

COMPOUND

6 THK ALUM PLATE

WOOD NAILER W/

50 W x T, 1,200

Laundry

AND BULLETIN BOARD SCHEDULE

NOTE : FOR ALTERNATE MESSAGE SEE SIGNAGE

WHITE LETTERS

BACKGROUND

BROWN

FIN. FL

C A

P

1220012

75224

1220112

A1

A1

A1A1

A1

A1

BED ROOM

2B1C

A1 A1

CORRIDOR

SIGNAGE SCHEDULE AND DETAILS

1B1A

2B

BUILDING IDENTIFICATION

NOT TO SCALE

D E T A I LD E T A I L

SIZE, MOUNTING LOCATION & DETAILS OF SIGNAGE

1C

2C2A D E T A I L

A1 A1 A1

A1A1A1

1&2

DOUBLE EMULSION

FOAM TAPE

PICTOGRAPH

LETTERS &

ALL AROUND

POLISH EDGES

ACRYLIC BACKING

BOARD W/SCREW

@ WALL ONLY

(DO NOT USE

@ FIRE-RATED DOOR)

NOTE : CARD INSERTS PROVIDED

HOLDER

AL CARD

BY USING AGENCY

FOAM TAPE

DOUBLE EMULSION

W/ SCREW

BACKING BOARD

ACRYLIC

ROOM IDENTIFICATION MISC IDENTIFICATION

100225

1C 2B

A1 A1

MECH ROOM

DOOR VIEWER

2B1C

A1 A1

1COMM/ELEC ROOM

1 PER EACH

VIEWER

R20

DOUBLE EMULSION

FOAM TAPE

3B3A REAR VIEWFRONT VIEW

ACRYLIC

CLEAR 2THK

ACRYLIC

WHITE 2THK

ACRYLIC

CLEAR 2THK

3C SECTION

R20

INSIDE ROOM

4 4

3D

FLEXI-INFO

EQ220EQ

ACRYLIC

WHITE 2MM THK

ACRYLIC

CLEAR 2MM THK

222 2

3 3

A1 A1

PLEXI-INFO HOLDER

BED RM DOOR

DOOR ELEVATION

COLOR IS TO

BACKGROUND

ROOF COLOR

7070 760

MATCH

S - 81

A15 A15 A15

A15A15A15

A15 A15

A15 A15

A15 A15

A15A15

A15

A15

A15 A15

A15

A15

DOOR

S-81

1 PER EACH BEDROOM

NOT TO SCALE

DETAILS @ BED RM

PLEXI-INFO HOLDER

YI, SC

185600

BUILDING S-81, CP CASEY

185600-Repair bldg S-81, Cp Casey-A-1
185600-Repair bldg S-81, Cp Casey-A-2
185600-Repair bldg S-81, Cp Casey-A-3
185600-Repair bldg S-81, Cp Casey-A-4
185600-Repair bldg S-81, Cp Casey-A-5
185600-Repair bldg S-81, Cp Casey-A-6
185600-Repair bldg S-81, Cp Casey-A-7
185600-Repair bldg S-81, Cp Casey-A-8
185600-Repair bldg S-81, Cp Casey-A-9
185600-Repair bldg S-81, Cp Casey-A-10
185600-Repair bldg S-81, Cp Casey-A-11
185600-Repair bldg S-81, Cp Casey-A-12
185600-Repair bldg S-81, Cp Casey-A-13
185600-Repair bldg S-81, Cp Casey-A-14
185600-Repair bldg S-81, Cp Casey-A-15

File details come from the government source that posted it.