GENERAL NOTES
1.
2.MOUNTING HEIGHTS ABOVE FLOOR SHALL BE AS FOLLOW UNLESS OTHERWISE
NOTED ON THE DRAWING.
LIGHTING FIXTURE SEE LIGHTING FIXTURE SCHEDULE
PANELBOARD SEE SPECIFICATION
SAFETY SWITCH 1524mm TO CENTER OF THE ENCL
1105mm TO CENTER OF THE ENCL
MOTOR CONTROLLER 1524mm TO CENTER OF THE ENCL
3.
4.
6.THE SOIL RESISTANCE TO GROUND FOR THE ELECTRICAL AND COMMMUNICATION
SYSTEMS SHALL BE 25 OHMS OR LESS. THE SOIL RESISTANCE TEST SHALL BE
7.
5.
CONDUCTED BY THE CONTRACTOR TO OBTAIN THE REQUIRED SOIL RESISTANCE.
INDICATEDS 2 #12AWG IN 16C
INDICATEDS 3 #12AWG IN 16C
INDICATEDS 4 #12AWG IN 16C
A GREATER NUMBER OF WIRES ARE INDICATED AS FOLLOWS;
1219mm TO CENTER OF THE ENCLWALL SWTICH
CONDUIT UNLESS OTHERWISE INDICATED.
ALL EQUIPMENT CONTROL WIRING SHALL BE #14 AWG. "TW" IN 16C
AND LOCATION OF THE F/A ANTENNA WITH THE CENTRAL FIRE DEPARTMENT
THE CONTRACTOR SHALL SUBMIT THE SHOP DRAWING FOR THE MOUNTING
TO TRANSMIT THE ALARM RADIO SIGNAL WAVE WITHOUT ANY OBSTRUCTION.
DETAIL OF THE F/A ANTENNA, AND COORDINATE THE MOUNTING HEIGHT
F/A EQUIPMENT IN THE CENTRAL FIRE DEPARTMENT.
THE EQUIPMENT SHOULD BE COMPATIBLE WITH THE MAIN EXISTING
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
SCOPE OF WORKS
LEGEND, GENERAL NOTES AND
E-1
12.
13.
14.
10.
11.
8.
9.
15.
SINGLE POLE TOGGLE SWITCH, 15A-125V
L E G E N D
FLEXIBLE CONDUIT W/CONNECTORS
LIGHTING
WIRING
POWER
INTERIOR
S
SYMBOL DESCRIPTION
DESCRIPTION
DESCRIPTION
T
J
THERMOSTAT (UNDER MECH. ITEM)
JUNCTION BOX
SYMBOL
SYMBOL
F FAN MOTOR (UNDER MECH. ITEM)
SAFETY SWITCH
C CONTROL CIRCUIT
3-WAY SWITCH, 15A-125V
AND GOVERNMENT INSTALLED
GOVERNMENT FURNISHED
GFGI
WEATHERPROOFWP
LA LIGHTNING ARRESTER
EXPLOSIONPROOFEP
DISTRIBUTIONDIST
GROUND FAULT PROTECTIONGFP
A AMPERE
AC ALTERNATING CURRENT
AF/AT AMPERE FRAME/AMPERE TRIP
AWG AMERICAN WIRE GAUGE
BC BARE COPPER
BLDG BUILDING
BRKR BREAKER
C CONDUIT
CB CIRCUIT BREAKER
CKT CIRCUIT
CONN CONNECTION
CT CURRENT TRANSFORMER
DET(S) DETAIL(S)
DIAG DIAGRAM
DISC DISCONNECT
DWG(S) DRAWING(S)
EA EACH
EM EMERGENCY
ENCL ENCLOSURE
EXST EXISTING
F/A FIRE ALARM
FL FLOOR
FLUOR FLUORESCENT
FXTR FIXTURE
GEN GENERATOR
GND GROUND
HP HORSE POWER
HZ HERTZ
INCAND INCANDESCENT
INSTL INSTALLATION
J-BOX JUNCTION BOX
K KILO
KV KILO VOLT
KVA KILO VOLT AMPERE
LTG LIGHTING
MAG MAGNETIC
MAX MAXIMUM
MIN MINIMUM OR MINUTE
MTG MOUNTING
NO NUMBER
O/H OVER HEAD
PH PHASE
PNLBD PANELBOARD
PRIM PRIMARY
PWR POWER
Q'TY QUANTITY
RCPT RECEPTACLE
REQ'D REQUIRED
SCHED SCHEDULE
SEC SECONDARY
SPEC SPECIFICATION
STD STANDARD
SW SWITCH
TEL TELEPHONE
TYP TYPICAL
U/G UNDERGROUND
V VOLT
VA VOLT AMPERE
W WATT
W/ WITH
XFMR TRANSFORMER
& AND
CABNET TYPE, RATED WATT ON LTG SCHEDULE
LED LIGHTING FIXTURE, WALL MOUNTED OR UNDER
ON LTG SCHEDULE, WET LOCATION
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
FAULT PROTECTED TYPE
DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDED
PANELBOARD
HOMERUN CIRCUIT TO PANELBOARD
TYPE OF MTG ON LTG SCHEDULE
EXTERIOR LED LIGHTING FIXTURE, RATED WATT &
TYPE
DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDING
ABBREVIATION
THE COTNRACTOR SHALL SUBMIT A SHOP DRAWING OF HVAC SYSTEM
IN ACCORDANCE WITH SEQUENCE OF OPERATION INDICATED ON THE
MECHANICAL DRAWINGS.
ANY CIRCUIT WITHOUT FURTHER DESIGNATION INDICATES 2-#12AWG
WIRES IN 16C CONDUIT UNLESS OTHERWISE INDICATED.
THE GROUNDING CONDUCTORS SHALL BE SEPARATELY PROVIDED FOR
ELECTRICAL EQUIPMENT UNLESS OTHERWISE INDICATED ON THE DRAWING.
CATV BEFORE CONSTRUCTION.
CONTRACTOR SHALL COORDINATE WITH AREA MP, DO IMO, SIGNAL BRIGADE,
AND GOVERNMENT ACCEPTANCE.
PANELBOARD DOOR, REQUIRED BEFORE FINAL BUILDING INSPECTION
CONTRACTOR SHALL MAKE CIRCUIT CHARTS AND ATTACH THEM TO
FIRE CODE AND SPECIFICATIONS.
OF THE NATIONAL ELECTRICAL CODE, NATIONAL ELECTRICAL SAFETY CODE,
ALL ELECTRICAL WORK SHALL CONFORM TO THE CURRENT REQUIREMENTS
OR RENOVATION.
CONDITION AND DIMENSIONS PRIOR TO COMMENCING ANY CONSTRUCTION
THE CONTRACTOR SHALL BE RESPONSIBLE IN VERIFING ALL EXISTING
FIXTURE A MINIMUM DISTANCE OF 458mm.
FIRE ALARM DETECTORS SHALL BE LOCATED TO CLEAR ANY LIGHTING
FACP
FTR
AUXILIARY
DESCRIPTIONSYMBOL
STROBES
WALL MOUNTED SPEAKER /COMBO. (FA+MNS)VISUAL
BUILDING TRANSMITTER UNIT FOR FIRE ALARM
SYSTEM
L
PHOTOCELL
WP
FAULT PROTECTED TYPE, WEATHER PROOF
DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDED
TYPE
SINGLE RECEPTACLE, 2P-3W-20A-125V, GROUNDING
TYPE WITH PLUG
SINGLE RECEPTACLE, 3P-4W-30A-125/250V, GROUNDING
TYPE WITH PLUG
SINGLE RECEPTACLE, 3P-4W-50A-125/250V, GROUNDING
L
L
ON LTG SCHEDULE
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
ON LTG SCHEDULE
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
W/EMERGENCY BATTERY UNIT
L
W/EMERGENCY UNIT TYPE
QUADPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDING
ON LTG SCHEDULE
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
ON LTG SCHEDULE
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
L
L
UNITS.
CERTIFICATE FROM MANUFACTURER FOR LED LIGHTING FIXTURES AND POWER
CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE 10YEARS WARRANTY
16.
THE GRADING LINE OF NEW DUCTS WILL BE LIMITED TO THE
WIDTH OF DUCT EXCAVATION.
AND AFTER INSTALLATION OF ELECTRICAL SYSTEM.
TO THEIR ORIGINAL CONDITION AND OPERATION DURING
ALL DAMAGED AREA INCLUDING SODDING, UTILITIES, STRUCTURES
THE CONTRACTOR SHALL BE RESPONSIBLE FOR RESTORING
LIGHTING CONTACTOR, SEL SW (H-O-A)
THE MANUFACTURER AND MODEL OF NEW BUILDING TRANSMITTER EQUIPMENT
IN THE CENTRAL FIRE DEPARTMENT.
THE EQUIPMENT SHOULD BE TESTED WITH THE RECEIVING SYSTEM(D21)
SHALL BE COORDINATED WITH THE CENTRAL FIRE DEPARTMENT.
RECEPTACLE
TYPE
DUPLEX RECEPTACLE, 2P-3W-20A-220V, GROUNDING
FIRE ALARM CONTROL PANEL
AND WALL
WIRING CONCEALED OR EXPOSED IN/ON THE CEILING
CEILING OR CONCEALED IN NEW WALL.
ALL WIRING SHALL BE CONCEALED ABOVE CEILING WHEN THE ROOM HAS
SCOPE OF WORK
1.
A. REPAIR/MAINTENANCE ( K )
4.
2.
6.
5.
3.
7.
8.
3S
642, 654, 655)
AND CONDUIT FOR 11 BUILDINGS (BUILDING NO. 1, 17, 47, 48, 50, 62, 68, 72,
BUILDING TRANSMITTERS SETS(11 SETS) AND ASSOCIATED WIRING
REPAIR EXIST FIRE ALARM CONTROL SYSTEM WITH NEW FIRE ALARM
185600
TAK, YS
9.
10.
CONDUITS WITH NEW FOR BUILDING NO 81.
EXTERIOR LIGHTS, TOGGLE SWITCHES, 3-WAY SWITCHES, WIRES AND
REPLACE DETERIORATED EXISTING LIGHTING FIXTURES, EXIT LIGHTS,
ASSOCIATED WIRING & CONDUITS WITH NEW FOR BUILDING NO 81.
ENCLOSED CIRCUIT BREAKER, RECEPTACLES W/COVER PLATES
REPLACE EXISTING PANEL BOARDS, WATTHOUR METER W/CT'S,
NEW FOR BUILDING NO 81.
POWER WIRES AND CONDUITS FOR MECHANICAL HVAC SYSTEM WITH
STARTERS, MANUAL MOTOR STARTER, JUNCTION BOXES, CONTROL/
REPLACE DETERIORATED EXISTING SAFETY SWTICH, MAGNETIC MOTOR
AND ASSOCIATED WIRING AND CONDUIT FOR BUILDING NO 81.
75 CANDELA), MICROPHONE, SPEAKER (WATTAGE AS REQ'D) DEVICE
BUILDING TRANSMITTER, ANTENNA, VISUAL/SIGNAL STROBES (15 OR
PANEL, MANUAL PULL STATION, SMOKE DETECTOR & RELAY MODULE,
ADDRESSABLE FIRE ALARM CONTROL AND MASS NOTIFICATION SYSTEM
REPLACE DETERIORATED FIRE ALARM CONTROL SYSTEM WITH NEW
& CONDUIT WITH NEW FOR BUILDING NO 81.
PLATES, TERMINAL BLOCKS, ACCESSOREIS AND ASSOCIATED WIRE
TELEPHONE TERMINAL BOARD, TELEPHONE OUTLETS W/COVER
REPLACE DETERIORATED EXISTING TELEPHONE SYSTEM INCLUDING
FOR BUILDING NO 81.
CATV OUTLETS W/ COVER PLATE & CABLE AND CONDUIT WITH NEW
REPLACE EXISTING CATV CABINETS AND ACCESSORIES, PULL BOXES,
NO 81.
CAP AND SECONDARY RACKS AND ACCESSORIES WITH NEW FOR BUILDING
REPLACE EXISTING EXTERIOR OVER HEAD SECONDARY LINE, ENTRANCE
ACCESSORIES WITH NEW FOR BUILDING NO 81.
REPLACE EXISTING EXTERIOR UNDERGROUND TELEPHONE LINE AND
SYSTEM WITH ASSOCIATED WIRING AND CONDUIT FOR BUILDING NO 81.
REMOVE AND REINSTALL EXISTING CCTV CEMARAS AND MONITORING
BUILDING S-81, CP CASEY
BUILDING TRANSMITTERS AND REPAIR
REPLACE FIRE ALARM SYSTEM / INSTALL
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
NEW GROUND FL LIGHTING PLAN
SCALE : 1/100
REMARKSMOUNTING METHODQ'TY
NO
SHT
WATTSTYPE
LAMP
NAME
ROOM
TYPE
LIGHT FIXTURE SCHEDULE
OCE STD DET 40-06-04
NO
LED101~107 BED ROOM
BATH ROOM
NS-6a
NS-6b
2-
1-
CEILING RECESSED
CEILING RECESSED W/"EM" UNIT
NS-7
NS-8
1-
1-
CEILING RECESSED
WALL MOUNTED ABOVE THE MIRROR TOP
112 LAUNDRY NS-4a
NS-4b
1-
1-
111 MECH ROOM NS-9a
NS-9b
- EXIT
EXTERIOR
ABOVE THE DOOR TOPNS-3 2- WALL MOUNTED4.99
NS-10 3-
110 VEST
113 COMM CLOSET
PENDNAT MOUNTED +2700mm AFF
+2700mm AFF, W/ "EM" UNITPENDNAT MOUNTED
NS-9b - 1 +2700mm AFF, W/ "EM" UNITPENDNAT MOUNTED
CEILING RECESSED
CEILING RECESSED W/"EM" UNIT
ABOVE THE DOOR TOPWALL MOUNTED
LED
108 VEST
109 CORRIDOR
NS-5b 25 1 CEILING RECESSED
NS-5a
NS-5b
CEILING RECESSED
CEILING RECESSED W/"EM" UNIT
W/"EM" UNIT-
5-
5-
NS-5b 25 1 CEILING RECESSED W/"EM" UNIT-
LED
S S
S
SSS SS
S S
"MP"
S3S
S
BED ROOM
BED ROOM
BED ROOM
BED ROOM
VEST
BED ROOM
BED ROOM
VIP BEDROOM
VEST
LAUNDRY
S S
CORRIDOR
3S S
S
S
3S
S S
S
S
S S
S3S
S
3S
S S
S
S
S
3SS
S S
S S
S3S
S
P2-1
P2-3
S
P2-5
COMM
ROOM
MECH
NIGHT LIGHT
(TYPICAL)
CONN TO NEW EXH FAN
SEE PLAN EP101
(TYPICAL)
"P1""P2"
L L L L L LLLLLLL
L L L L
LLL
L L L L
LLL
L
L
L
L L
L L
L L
L
L
LL
L
L
L
L L L L
LLL
E-2
ELECTRICAL
LIGHTING FIXTURE SCHEDULE
NEW GROUND FL LIGHTING PLAN &
LED 45
LED
LED
L
L
L
CLOSET/CCTV
TAK, YS
185600
BUILDING S-81, CP CASEY
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
DIODE(LED) EXIT LIGHT FIXTURE 1PH, 120V, 4.99W
WALL SURFACE MOUNTED LIGHT EMITTING
(MAX. INPUT), BATTERY BACK-UP WITH BATTERY CHARGER
NS-3
NS-7
NS-4a & 4b
NS-9a & 9b
NS-8
NS-10
245mm
254mm
CEILING RECESSED MOUNTED LIGHT EMITTING DIODE (LED)
NS-6a & 6bNS-5a & 5b
WALL
NON-STANDARD LIGHT FIXTURE DETAILS
ELECTRICAL
E-3
FIXTURE, 1PH, 120V, 25W, UL LISTED WITH CONVERTER &
ACCESSORIES (NS-5a) & WITH EM UNIT (NS-5b) AS REQUIRED
CEILING SURFACE/PENDANT MOUNTED LIGHT EMITTING DIODE (LED)
FIXTURE, 1PH, 120V, 45W, UL LISTED, WITH CONVERTER AND
ACCESSORIES AS REQUIRED, (NS-9a) & EM UNIT(NS-9b)
CEILING RECESSED MOUNTED LIGHT EMITTING DIODE (LED)
FIXTURE, 1PH, 120V, 45W, UL LISTED, WITH CONVERTER &
ACCESSORIES AS REQUIRED, (NS-4a) & WITH EM UNIT (NS-4b)
FIXTURE, 1PH, 120V, 18W, WITH CONVERTER & ACCESSORIES,
CEILING SURFACE MOUNTED LIGHT EMITTING DIODE (LED)
WET LOCATION SHOWER LIGHT TRIM, UL LISTED POWER UNIT
FIXTURE, 1PH, 120V, 18W, WITH CONVERTER & ACCESSORIES
WALL SURFACE MOUNTED LIGHT EMITTING DIODE (LED)
AS REQUIRED, UL LISTED POWER UNIT
WALL MOUNTED LED LIGHT FIXTURE, 1PH, 120V, 22W LED
LAMP, CONVERTER & ACCESSORIES AS REQUIRED,
WET LOCATION TYPE, UL LISTED POWER UNIT
CEILING RECESSED MOUNTED LIGHT EMITTING DIODE (LED)
FIXTURE, 1PH, 120V, 50W, UL LISTED, WITH CONVERTER &
ACCESSORIES, (NS-6a) & WITH EM UNIT (NS-6b) AS REQUIRED
TAK, YS
185600
BUILDING S-81, CP CASEY
R
P1-23
"EM"
2#10 & 1#10(G) IN 21C
RA
HD
"P1""P2"
CTC
CTC
D
P1-25
P1-19 P1-24
P1-22
P1-1 P1-21P1-2
P1-14 P1-13 P1-4
P1-11
P1-10
P1-3
P1-15
P1-17
P1-6
P1-5
P1-9 P1-16
P1-18
P1-8
P1-12
P1-7
R P2-2 P2-6
P2-20
P2-24 P2-16
P2-4R
P2-17 P2-7
P2-25 P2-21
P2-9
P2-11
R
P2-10
P2-15 P2-14
P2-23
R
RP2-27
P2-19
P2-13
P2-12
P2-22
P2-30
HDRA HD
P2-8 P2-18
"MP"
WP
W H
M
W
MP-7
MP-8
MP-9
MP-11
BED ROOM
BED ROOM
BED ROOM
BED ROOM
VEST
BED ROOM
BED ROOM
VIP BEDROOM
VEST
LAUNDRY
CORRIDOR
109113
COMM
ROOM
MECH
R
MM
P1-27
P1-29
P1-31
HD
RA
MM
HD
RA
HD
RA
P2-29
P2-30
P2-32 P2-26
M MM
RA
RA HD
MP-3
J
CONN TO NEW LIGHT
(TYPICAL)
J
DWH
J
P-1
J
B
J
J
EF-2
JP-2
EF-1
ACU1
(IN)
SB
A C
U
(OUT)
3#10 & 1#10(G) IN 21C
WC
"P1""P2"
"MP"
FCU-1 FCU-1
FCU-1
FCU-1 FCU-1
FCU-1 FCU-1
JEF-1 J EF-1 JEF-1
J EF-1 JEF-1J EF-1
F C
U
MP-15
MP-4
MP-14
P1-20
P2-28
P1-26
MP-12
MP-10
MP-13
BED ROOM
BED ROOM
BED ROOM
BED ROOM
VEST
BED ROOM
BED ROOM
VIP BEDROOM
VEST
LAUNDRY
CORRIDOR
109113
COMM
ROOM
MECH
MC
MB
MA
FCU-2
SA
NEW GROUND FL GENERAL POWER PLAN
SCALE : 1/100
NOTES
1. FOR ABBREVIATION, LEGEND AND GENERAL NOTES
* ADDITIONAL LEGEND(THIS SHEET ONLY)
SINGLE RECEPTACLE (3P-4W-50A-125/250V,
GROUNDING TYPE) W/PLUG FOR RANGE
1PH-120/208V-6470W
(LOCATED INSIDE HOOD CABINET)
AND LIGHT(1PH-120V-18W)
FOR RANGE HOOD FAN(1PH-115V-2.0A)
SINGLE RECEPTACLE (2P-3W-20A-125V
GROUNDING TYPE) W/CORD-SET
RA
(MH : +140mm TO TOP OF RCPT)
(MH: +900mm TO CENTER OF RCPT)
REFRIGERATOR, 1PH-115V-1/4HP
GROUNDING TYPE) W/PLUG
SINGLE RECEPTACLE (2P-3W-20A-125V
SINGLE RECEPTACLE (2P-3W-20A-125V
GROUNDING TYPE) W/PLUG FOR
WASHER (1PH-115V-1/2HP)
(1PH-120/208V-24A)
GROUNDING TYPE) W/PLUG FOR DRYER
SINGLE RECEPTACLE (3P-4W-30A-125/250V
ENCLOSED CIRCUIT BREAKER
(1P-100AF-20AT, 120VAC,
DEVICE, NEMA 1 ENCL
10,000AIC SYM) W/LOCKING
MAGNETIC MOTOR STARTER, 2P-120V
NEMA SIZE "00" W/O.L RELAYS,
PILOT LAMP(GREEN), AND 3-POSITION
SELECTOR SWITCH (H-O-A)
MA,MC
NEMA 1 ENCL
FCU1 FAN COIL UNIT-1
SUPPLY FAN: 1PH-220V-45W
W/BUILT-IN CONTROLLER
(UNDER MECH ITEM)
FCU2 FAN COIL UNIT-2
SUPPLY FAN: 1PH-220V-35W
W/BUILT-IN CONTROLLER
(UNDER MECH ITEM)
WATER CHILLER-1
COMP: 3PH-220V-7.5KW x1EA
W/BUILT-IN CONTROLLER
(UNDER MECH ITEM)
COND. FAN: 3PH-220V-0.2KW x2EA
J
(UNDER MECH ITEM)
EXHAUST FAN-1
1PH-115V-45W
J
EF-1
(UNDER MECH ITEM)
HOT/CHILLED
3PH-200V-2HP
J
P-1
(UNDER MECH ITEM)
DOMESTIC HOT
1PH-115V-1/4HP
J
P-2
(UNDER MECH ITEM)
MAGNETIC MOTOR STARTER, 3P-208V
NEMA SIZE "0" W/O.L RELAYS,
PILOT LAMP(GREEN), AND 3-POSITION
SELECTOR SWITCH(H-O-A) AND
CONTROL TR, NEMA 1 ENCL
HD
R
D
W
WATER CIRC PUMP-1
WATER CIRC PUMP-2
DOMESTIC HOT
1PH-115V-1/3HP
J
DWH
W/BUILT-IN CONTROLLER
WATER HEATER
(UNDER MECH ITEM)
SAFETY SWITCH, 3PST, 240V, 60A
W/40A FUSE, NEMA 3R ENCL
GROUND FAULT PROTECTED
DUPLEX RECEPTACLE (2P-3W-20A-125VAC,
GROUNDING TYPE)
"WP" TYPE, GROUND FAULT PROTECTED
DUPLEX RECEPTACLE (2P-3W-20A-125VAC,
GROUNDING TYPE)
WP
WC
EF-2
EXHAUST FAN-2
1PH-115V-1/4HP
W/DISCONNECT SWITCH
(UNDER MECH ITEM)
J
BOILER-1
W/BUILT-IN CONTROLLER
J
B
(UNDER MECH ITEM)
1PH-115V-1/3HP
MB
"EM"
WHM
WATTHOUR METER
SEE POWER ONE-LINE DIAGRMA EP601
SINGLE RECEPTACLE (2P-3W-20A-250VAC,
GROUNDING TYPE) FOR TRUNK BRIDGER
AMPLIFIER, SHALL BE INSTALLED INSIDE
CTC
THE CATV CABINET
DUPLEX RECEPTACLE (2P-3W-20A-125VAC,
GROUNDING TYPE) FOR TRUNK BRIDGER
AMPLIFIER, SHALL BE INSTALLED INSIDE
CTC
THE CATV CABINET
SINGLE RECEPTACLE (2P-3W-20A-250VAC,
GROUNDING TYPE) W/CORD-SET
FOR FAN COIL UNIT (UNDER MECH ITEM)
2.
INSIDE OR BEHIND THE FCU.
POWER CONNECTION OUTLET SHALL BE LOCATED
ACU SPLIT AIR CONDITIONING UNIT
INDOOR UNIT: 1PH-115V-1.1A(IN)
W/BUILT-IN CONTROLLER
(UNDER MECH ITEM)
ACU SPLIT AIR CONDITIONING UNIT
COMP: 1PH-115V-7.5A(OUT)
W/BUILT-IN CONTROLLER
(UNDER MECH ITEM)
COND. FAN: 1PH-115V-0.6A
SAFETY SWITCH, 2PST, 240V, 30A
W/20A FUSE, NEMA 3R ENCL
SA
SB
SEE NOTE 2 BELOW
(MH: +955mm TO BOTTOM OF ENCL)
(MH: +955mm TO BOTTOM OF ENCL)
NEW GROUND FL MECH POWER PLAN
SCALE : 1/100
(MH: +150mm ABOVE THE COUNTER TOP)
SINGLE RECEPTACLE (2P-3W-20A-125V
GROUNDING TYPE) W/PLUG FOR MICROWAVE,
1PH-120V-1100W (LOCATED INSIDE
CABINET WHERE MICROWAVE IS PLACED)
M
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMYSEE SHEET NO E-1.
SEE PLAN E-2
ELECTRICAL
NEW GROUND FL POWER PLANS
E-4
CCTV
CLOSET/CCTV
CLOSET/CCTV
TAK, YS
185600
1PH-115V, 1KW
EUH
EUH
ELECTRIC UNIT HEATER-1
BUILDING S-81, CP CASEY
225AT
225AF
90AT
100AF
3P
3P
100AF
3P
CONDUCTOR, #2(G) IN 21C
NEW GROUNDING
3PH, 4W, 120/208V, 60HZ
SYSTEM, NEMA 1 ENCL
CU BUS, 225A
10,000AIC SYM
G
S/NGND
2#12 & 1#12(G) IN 16C
10,000AIC SYM) W/LOCKING
(1P-100AF-20AT, 120VAC,
ENCLOSED CIRCUIT BREAKER "EM"
MAIN PANELBOARD "MP"
WHM
TR TYPE, W/CT'S 225/5Ax3EA
120/208V, 60Hz SYSTEM, NEMA 3R ENCL.
AND 15MIN DEMAND REGISTER FOR 3PH, 4W,
WITH NEW ADVANCED DIGITAL WATTHOUR METER,
"EM"
321 21
"P2"
FOR ABBREVIATION, LEGEND, AND GENERAL NOTES1.
NOTES
PROVIDE A LABEL WITH THE FOLLOWING INSCRIPTION
"FIRE PROTECTION/LIFE SAFETY EQUIPMENT" CONSTRUCT
AND FASTEN THE LABEL IDENTICAL TO THE PANEL
NAMEPLATE, EXCEPT THE LABEL MUST BE RED LAMINATED
PLASTIC WITH THE WHITE CENTER CORE.
2.
3. ENCLOSURE OF FIRE PANEL SHALL BE PAINTED WITH RED.
EXIST/NEW POWER ONE-LINE DIAGRAM
NOT TO SCALE
4#2 &
1#8(G)
IN 41C
REPLACE THE DETERIORATED EXISTING WHM
4#1/0 "WP"
NEW O/H SEC LINE,
SPARE
SEE NOTE 2 & 3 BELOW.
DEVICE, NEMA 1 ENCL
CONN TO FIRE ALARM/MASS
2#12 & 1#12(G) IN 16C
NOTIFICATION CONTROL PANEL
100AT
4#2 &
1#8(G)
IN 41C
100AF
3P
40AT
100AF
3P
20AT
100AF
1P
20AT
NEW SEC RACK (4-SPOOL)
AND ENTRANCE CAP
(103dia-4 HOLES)
NEMA 1 ENCL
SURGE SUPPRESSOR
TRANSIENT VOLTAGE
"P1"
TVSS
4#4/0 IN 103C
NEW SEC LINE,
WC
3#10 &
1#10(G)
IN 21C
EXT
COMP: 3PH-220V-7.5KW x1EA
COND. FAN: 3PH-220V-0.2KW x2EA
WATER CHILLER-1
W/BUILT-IN CONTROLLER
SAFETY SWITCH, 3PST, 240V, 60A
W/40A FUSE, NEMA 3R ENCL
EXT
SPARE
EXIST FUSE CUTOUT SWITCH,
EXIST GROUNDING WIRE
TO REMAIN
(3PH, 4W, 11.4KV,
EXIST O/H PRIM LINE
60HZ SYSTEM)
G
G
EXIST LIGHTNING ARRESTER
TO REMAIN
NEW SEC RACK (4-SPOOL)
W/WELDING CONNECTION
NEW GROUND ROD, COPPER
CLAD STEEL, 19diax3000LG
(TYPICAL)
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
SEE SHEET NO. E-1.
EXIST CON'C POLE
ELECTRICAL
E-5
EXIST/NEW POWER ONE-LINE DIAGRAM
NEW POLE MOUNTED TRANSFORMER,
1PH, 11.4KV-120/240V, 60HZ, 50KVAX3EA
NEW O/H SEC BUS WIRE
NEW GROUNDING WIRE, AWG#3/0"BC"
W/WELDING CONNECTION
NEW GROUND ROD, COPPER
CLAD STEEL, 19diax3000LG
(TYPICAL)
TAK, YS
185600
NEW O/H PRI LINE,
3- #2/0, 24KV & 1-#2/0, 600V
BUILDING S-81, CP CASEY
2 SETS OF (4#4/0)
TOTAL DEMAND LOAD ; 74,968 (VA)
TOTAL LOAD 122240 40840 40675
LOAD
TOTAL
MAIN PANELBOARD "MP" LOAD SCHEDULE
LOAD DESCRIPTION
NO.
CKT
GND
S/N
DIAGRAM
CONNECTION
CIRCUIT BREAKER
PHASE LOAD
A B PC AT
SIZE
AF AIC
B CA N G
REMARK
MAIN 3P-225AF-225AT CIRCUIT BREAKER
MTD TYPE, NEMA 1 ENCL.
60HZ, SN & GND, SURFACE
3PHASE ,4WIRE, 120/208V,
40725
PANELBOARD "P1"
RCPT FOR CATV EQUIPMENT
TVSS 30 4#10&1#10(G)
3 10000100 90
SPARE
4#2 & 1#8(G)
TOTAL DEMAND LOAD ; 32,958 (VA)
TOTAL LOAD 49617 16849 15767
LOAD
TOTAL
PANELBOARD "P2" LOAD SCHEDULE
LOAD DESCRIPTION
NO.
CKT
GND
S/N
DIAGRAM
CONNECTION
CIRCUIT BREAKER
PHASE LOAD
A B PC AT
SIZE
AF AIC
B CA N G
REMARK
MAIN 3P-100AF-100AT CIRCUIT BREAKER
17001
924 924
300 300
1 10000100 2#12&1#12(G)
HOOD FAN & LIGHT 2.5A
300300
670 670
ARC-FAULT
RCPTS 360VAx1, 180VAx2
2#12&1#12(G)
ARC-FAULT
PANELBOARD "P2"
25 26
32356470
300 300
MICROWAVE, 1100VA
REF, 1/4HP
REF, 1/4HP
REF, 1/4HP
REF, 1/4HP
2#12&1#12(G)
90FCU-1 (45W) x4 180
1000SPARE 1000
1000SPARE 1000
4#2&1#8(G)
4#2&1#8(G)
4#2 & 1#8(G)
TOTAL DEMAND LOAD ; 30,896 (VA)
TOTAL LOAD 43903 14211 14992
LOAD
TOTAL
PANELBOARD "P1" LOAD SCHEDULE
LOAD DESCRIPTION
NO.
CKT
GND
S/N
DIAGRAM
CONNECTION
CIRCUIT BREAKER
PHASE LOAD
A B PC AT
SIZE
AF AIC
B CA N G
REMARK
MAIN 3P-100AF-90AT CIRCUIT BREAKER
MTD TYPE, NEMA 1 ENCL.
60HZ, SN & GND, FLUSH
3PHASE ,4WIRE, 120/208V,
14700
720 720
1000 1000
1 10000100 20
720 720
2#12&1#12(G)
ARC-FAULT
10002000
1000 1000
REF, 1/4HP
REF, 1/4HP
REF, 1/4HP
2#12&1#12(G)
1000SPARE 1000
1000SPARE 1000
540 3 4
RCPTS 360VAx1, 180VAx2
RCPTS 360VAx1, 180VAx2
RCPTS 180VAx3
540RCPTS 180VAx3
RCPTS 360VAx1, 180VAx2
RCPTS 360VAx1, 180VAx2
RCPTS 180VAx3 540
RCPTS 360VAx1, 180VAx3
RCPTS 360VAx1, 180VAx3 900
ELEC RANGE, 6470W
ELEC RANGE, 6470W
ELEC RANGE, 6470W
HOOD FAN & LIGHT 2.5A
HOOD FAN & LIGHT 2.5A
50 2#8&1#10(G)
RCPTS 180VAx3
MTD TYPE, NEMA 1 ENCL.
60HZ, SN & GND, FLUSH
3PHASE ,4WIRE, 120/208V,
5 6
2FL 1/32W x2
LIGHT, LED 25W x12, 4.99W x2, FL 1/32W x2, EXH FAN-1 45Wx3
LIGHT, LED 50W x9, 18W x6, 45W x2
720 720
RCPTS 360VAx1, 180VAx2 720 720
RCPTS 180VAx3 540
RCPTS 180VAx3
RCPTS 360VAx1, 180VAx2
RCPTS 360VAx1, 180VAx2 720
RCPTS 360VAx1, 180VAx2
RCPTS 360VAx1, 180VAx2
RCPTS 180VAx3
RCPTS 180VAx3
RCPTS 360VAx1, 180VAx2
RCPTS 360VAx1, 180VAx2
436 436
997 997 7 8
2#12&1#12(G)
2#12&1#12(G)
ELEC RANGE, 6470W
ELEC RANGE, 6470W
ELEC RANGE, 6470W
ELEC RANGE, 6470W
50 2#8&1#10(G)
HOOD FAN & LIGHT 2.5A
HOOD FAN & LIGHT 2.5A
HOOD FAN & LIGHT 2.5A
HOOD FAN & LIGHT 2.5A
1 20
COND. FAN: 0.2KW x2EA
WC, COMP: 7.5KW x1EA, PUMP-1, 2HP
SPACE
EXH FAN-1 45Wx4
LIGHT, LED 50W x12, 18W x8, FCU-1 (45W) x3, FCU-2 (35W) x2 2
20 2#12&1#12(G)
RCPT FOR COMM EQUIPMENT
1RCPT FOR COMM EQUIPMENT
RCPT FOR CATV EQUIPMENT
RCPTS 180VAx1
SPARE
35 SPARE
1 20
10811081
11001100
10001000
10001000
1000SPARE 1000
1100MICROWAVE, 1100VA 1100
1100MICROWAVE, 1100VA 1100
1100MICROWAVE, 1100VA 1100
COMP:7.5A, COND. FAN: 0.6A
ACU-1, IN DOOR: 1.1A
2#12&1#12(G)
7900 2633 2633 2634
2703 901 901 901
3000 1000 10001000 20
3#12&1#12(G)
3#10&1#10(G)
DWH-1, 1/3HP 830
PUMP-2, 1/4HP 670
BOILER-1, 1/3HP 830
EXH FAN-2, 1/4HP 670
1000 20
10001000
1000 1000SPARE
SPARE
--------SPACE
--------SPACE
SPACE
1 20100 10000
RCPTS 180VAx2
RCPTS 180VAx4 720 720
WASHER, 1/2HP
360 360
1130 1130
11 DRYER, 24A 4992 2
20 10000 2#12&1#12(G)
2#10&1#10(G)
2496 112496
12 13
2#12&1#12(G)
17 20
19 22
21 24
--------SPACE
10001000
SPACE 10001000
SPACE 10001000
W/PULL WIRE FOR FUTURE USE.
NOTE
1. FOR FLUSH MOUNTED PANELBOARD, CONTRACTOR SHALL PROVIDE EMPTY CONDUITS
FOR FUTURE POWER CKTS.
PANELBOARD
J
W/PULL WIRES
(3EA OF 16C)
PROVIDE EMPTY CONDUITS
FLUSH MOUNTED
(100x100x50D)(3EA)
W/BLANK COVER
TYPICAL FLUSH MTD PANELBOARD INSTALL DETAIL
NOT TO SCALE
PROVIDE JUNCTION BOX
180 180
11001100
SPARE 1000100037
MICROWAVE, 1100VA
MICROWAVE, 1100VA
MICROWAVE, 1100VA 2#12&1#12(G)
1000SPARE 1000
1000SPARE 1000
11001100
43903 14211 1499214700
49617 16849 1576717001
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
LOAD SCHEDULE & DETAIL
E-6
TAK, YS
185600
ELECTRIC UNIT HEATER-1, 1KW
BUILDING S-81, CP CASEY
81 80
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
1/200SCALE :
NOTES
1. FOR ABBREVIATION, LEGEND AND GENERAL NOTES
SEE SHEET NO. E-1.
NEW ELEC & TEL EXTERIOR DISTRIBUTION PLAN
PS
S
S
S
P
P
P
EXIST O/H CATV LINE
(TYPICAL)
EXIST O/H PRI LINE
(TYPICAL)
WITH NEW O/H SEC LINE, 4#1/0
REPLACE EXIST O/H SEC LINE
S-81 (TYPICAL)
ACCESSORIES FOR BLDG.
"WP" , SEC. RACKS (4-SPOOL) &
(TYPICAL)
EXISTING EXTERIOR LIGHT
ELECTRICAL
DISTRIBUTION PLAN
NEW EXTERIOR ELEC & COMMUNICATION
E-7
EXISTING TELEPHONE PEDESTAL TO REMAIN
"TTB"
MECH ROOM
COMM CLOSET
103dia PVC CONDUIT
1WAY: 1-25PAIR #24AWG TEL CABLE
NEW U/G COMM LINE ONE WAY OF
FOR EXIST EXTERIOR LIGHT
NEW O/H SEC LINE, 2-AWG"8", "WP"
120/240V, 60HZ, 50KVAx3EA
REPLACE EXIST POLE MOUNTED TRANSFORMER,
WITH NEW, SELF-COOLED, OIL-FILLED, 1PH, 11.4KV-
TO NEW TRANSFORMERS
EXIST O/H SEC LINE/ RE-CONNECT
QUAD SHIELDED IN 35C
COAXIAL CABLE RG 11/U
TAK, YS
185600
BUILDING S-81, CP CASEY
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
NEW GROUND FL FIRE ALARM/MASS NOTIFICATION SYSTEM PLAN
SCALE : 1/100
FIRE ALARM/MASS NOTIFICATION SYSTEM SEQUENCE OF OPERATION
NOT TO SCALE
THE SWITCH FOR THE MANUAL OVERRIDE OF THE FIRE ALARM EVACUATION OCCUPANT NOTIFICATION APPLIANCES
SHALL BE LOCATED AT THE BLDG MASS NOTIFICATION SYSTEM AUTONOMOUS CONTROL UNIT AND SHALL BE LABELED
WITH AN ID PLATE: "FIRE ALARM SYSTEM OVERRIDE"
NOTE:
SYSTEM OUTPUT
OPEN CIRCUIT X
E
ACTIVATION OF A MANUAL PULL STATION X X
FIRE ALARM SYSTEM SEQUENCE OF OPERATIONS
SYSTEM INPUT
D
C
B
A
BLDG. #81
A N
N U
N C
IA
T E A
LA
R
M Z
O N E A
T C
O M
B
IN
E D F
IR
E A
LA
R
M
T R
A N S
M
IT
S
U P E R
V
IS
O R
Y S
IG
N A L
T O F
IR
E D
E P A R T
M E N T
T R
A N S
M
IT
T
R O
U B
LE
S
IG
N A L
T O F
IR
E D
E P A R T
M E N T
A N
N U
N C
IA
T E S
U P E R
V
IS
O R
Y Z
O N E A
T C
O M
B
IN
E D F
IR
E
A N
N U
N C
IA
T E T
R O
U B
LE
Z
O N E A
T F
IR
E A
LA
R
M
1 2 3
F
X
T R
A N S
M
IT
A
LA
R
M S
IG
N A L
T O F
IR
E D
E P A R T
M E N T
G
4 5 6 7
X
/M A S S N
O T
IF
IC
A T
IO
N C
O N T R
O L P A N E L
A
LA
R M /M
A S S N
O T
IF
IC
A T
IO
N C
O N T R
O L P A N E L
/M A S S N
O T
IF
IC
A T
IO
N C
O N T R
O L P A N E L
MASS SYSTEM ACTIVATION BY PRE-RECORDED MESSAGE OR MICROPHONE BUTTON ACTIVATION
MANUAL MASS OVERRIDE SWITCH
RESET MASS NOTIFICATION SYSTEM DURING FIRE ALARM CONDITION
X
X
ACTIVATION OF SMOKE DETECTOR WITH SOUNDER BASE IN BED ROOM XX
A C T
IV
A T E S
M O
K E D
E T E C T O
R S
O U
N D E R B
A S E
X
H
A C T
IV
A T E V
IS
IB
LE
A
N D A
U D
IB
LE
A
LA
F
IR
E A
LA
R
M N
O T
IF
IC
A T
IO
N D
E V
IC
E S
X
10 11
A C T
IV
A T E V
IS
IB
LE
A
N D A
U D
IB
LE
A
LA
N S N
O T
IF
IC
A T
IO
N D
E V
IC
E S
X X
GROUND FAULT
NOTIFICATION APPLIANCE CIRCUIT SHORT
X X
X X
M A S S M
E S S A G E S A
R E D
IS
C O
N T
IN
U E D
IM
M E D
IA
T E
LY
U P O
N A
C T
IV
A T
IO
N O
F M
A S S O
V E R R
ID
E S
W
IT
C H T
H E
T E
M P O
R A R
IL
Y A
N D
IM
M E D
IA
T E
LY
O
V E R R
ID
E F
IR
E
A
LA
R M N
O T
IF
IC
A T
IO
N S
Y S T E
M
X X X
IN
B
E D R
O O
M
COMBINED ADDRESSABLE FIRE ALARM/
FTR BUILDING TRANSMITTER W/BATTERY &
BATTERY CHARGER, NEMA 1 ENCL
W/MOUNTING BARCKET
OMNI-DIRECTION TYPE
FIRE ALARM ANTENNA
DIGITAL VOICE PANEL W/AMPLIFIER & BACK
SYNCHRONIZATION CONTROL MODULE,
24VDC, BUILT-IN ADDRESSABLE POINTS
UP AMPLIFIER (AS REQ'D) & MICROPHONE,
POWER MODULES PANEL(AS REQ'D) AND
MICROPHONE, BATTERY, BATTERY CHAREGER,
MODULE & RELAYS LCD ANNUNCIATOR,
MODULES AS REQ'D, PROGRAMMABLE
MASS NOTIFICATION CONTROL PANEL,
POWER SUPPLY, DIGITAL VOICE MODULE,
FMCP
W/WORDS "FIRE" + MNS-AMBER STROBE
AS REQ'D)/COMBO. (FA-CLEAR STROBE
WALL MOUNTED SPEAKER (WATTAGE
F M
SPEAKER (WATTAGE AS REQ'D)
FIRE ALARM/MASS NOTIFICATION
CEILING MOUNTED TYPE,
WP
F ADDRESSABLE MANUAL PULL STATION
SPEAKER (WATTAGE AS REQ'D)
FIRE ALARM/MASS NOTIFICATION
WALL MOUNTED "WP" TYPE,
* ADDITIONAL LEGEND (THIS SHEET ONLY)
(FA-CLEAR STROBE W/WORDS "FIRE" +
WALL MOUNTED COMBO.
NEMA 1 ENCL
W/WORDS "FIRE" + MNS-AMBER STROBE
AS REQ'D)/COMBO. (FA-CLEAR STROBE
WALL MOUNTED SPEAKER (WATTAGE
MNS-AMBER STROBE W/WORDS "ALERT")
VISUAL SIGNAL STROBES (75 CANDELA
MINIMUM, AMBER STROBE SHALL BE
DE-RATED AS REQUIRED)
(15 CANDELA MINIMUM, AMBER STROBE
W/WORDS "ALERT") VISUAL SIGNAL STROBES
SHALL BE DE-RATED AS REQUIRED)
(75 CANDELA MINIMUM, AMBER STROBE
W/WORDS "ALERT") VISUAL SIGNAL STROBES
SHALL BE DE-RATED AS REQUIRED)
NOTES
FOR ABBREVIATION, LEGEND, AND GENERAL NOTES,1.
IT SHALL BE COORDINATED WITH THE BUILDING
FOR THE LOCATION OF OUTDOOR MNS DEVICES,3.
EXTERIOR AESTHETICALLY.
IN THE CORRIDOR 109 NEARBY MAIN ENTRANCE , ONLY
POWER BOOSTER PANELS AND FIRE ALARM PERIPHERAL
INSTALL BATTERY CABINET, BUILDING TRANSMITTER, 4.
FMCP IS INSTALLED FOR AESTHETICAL CONCEDE.
2. FIRE ALARM AND MASS NOTIFICATION SYSTEM LAYOUT
IS CONCEPTUAL. FINAL DESIGNER SHALL COMPLETE
DESIGN IN ACCORDANCE WITH THE APPLICABLE CODE,
SPECIFICATIONS AND MANUFACTURER'S EQUIPMENT
LISTING.
BED ROOM
101 BED ROOM
BED ROOM
BED ROOM
VEST
BED ROOM
BED ROOM
VIP BEDROOM
VEST
LAUNDRY
CORRIDOR
SB
FMCP
SB SB SB
SB
SB
F
F
WP
F
F M
M F
F M
F M
F M
F M
F M
FTR
SB
FFF
F
FFF
F
F
F F
F
F F F F
F/M
F/MF/M
F/M
F/M
F/M
F/MF/MF/M
F/M
F/M
F/M F/M
F/M
F/M
F/M F/M
F/M
F/M
ROOM
MECH
COMM
FM
F
SEE SHEET NO. E-1.
ELECTRICAL
NOTIFICATION SYSTEM PLAN
NEW GROUND FL FIRE ALARM/MASS
E-8
FMCPTO
EQUIPMENT IN VEST 110 .
TS
PS
J
J
TS
J
TS
J
CO
FMCPTO
TAMPER SWITCH
(UNDER MECH ITEM) (TYPICAL)
FOR SPRINKLER SYSTEM
W/ADDRESSABLE MODULE
W/ ADDRESSABLE MODULE
CARBON MONOXIDE DETECTOR
CO
PS
J
TS
J
(UNDER MECH ITEM)
FOR SPRINKLER SYSTEM
W/ADDRESSABLE MODULE
PRESSURE SWITCH
CLOSET/CCTV
BUILDING S-81, CP CASEY (PHASE#1)
BUILDING TRANSMITTERS AND REPAIR
REPLACE FIRE ALARM SYSTEM / INSTALL
TAK, YS
185600
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
FIRE ALARM/MASS NOTIFICATION SYSTEM DIAGRAM
NOT TO SCALE
24VDC, BUILT-IN ADDRESSABLE POINTS MODULES AS REQ'D,
(AS REQ'D) & MICROPHONE. NEMA 1 ENCL
DIGITAL VOICE PANEL W/AMPLIFIER & BACK UP AMPLIFIER
BATTERY CHAREGER, POWER MODULES PANEL (AS REQ'D) AND
SYNCHRONIZATION CONTROL MODULE, POWER SUPPLY,
PROGRAMMABLE MODULE & RELAYS, LCD ANNUNCIATOR,
FIRE ALARM/MASS NOTIFICATION CONTROL PANEL (FMCP),
COMBINED ADDRESSABLE
DIGITAL VOICE MODULE, MICROPHONE, BATTERY,
FIRE ALARM/MASS NOTIFICATION
CONTROL PANEL (FMCP)
1st FL.
FTR
12#14 IN 21C(FOR SIGNAL)
2#12 IN 16C(FOR POWER)
(PROGRAM OF D-21 MONACO
BUILDING TRANSMITTER
BT-XM AT LEAST 16 ZONES)
#6 "BC" IN 21C
GROUND CONDUCTOR
COAXIAL CABLE
W/CONNECTORS IN 16C
OMNI-DIRECTION TYPE
FIRE ALARM ANTENNA
W/MOUNTING BRACKET
GROUND ROD, COPPER CLAD
WITH WELDING CONNECTION
STEEL, 19mmdia x 3000mmLG
"EM"SG
G ~
G
CONTROL PANEL & BOOSTER PANEL)
(INSTALLED BESIDE FIRE ALARM
(RATED AS REQ'D) (TYPICAL)
SURGE PROTECTOR
2#12 & 1#12(G) IN 16C
GROUND ROD, COPPER CLAD
GROUNDING SYSTEM #6, "BC" IN 21C
CONN TO BLDG ELECTRODE
STEEL, 19mmdiax3000mmLG
WITH WELDING CONNECTION AND
ENCLOSURE
LIGHTNING ARRESTER
W/WEATHER-PROOF
ROOF FL.
SB
F
104 112
F M
EXT
106 111
NOTES:
W/BATTERY & BATTERY
CHARGER, NEMA 1 ENCL
NFPA 72, 2013 EDITION.
PRERECORDED MESSAGES ARE IN ENGLISH AND HANGUL AT
CONTRACTOR SUBMITS SHOP DRAWINGS.
THE VOLTAGE DROP AND POWER SUPPLY CALCULATION
SHALL BE PROVIDED BY THE CONTRACTOR WHEN THE
4.
(3-FEET) FROM HVAC, HOT & COLD WATER PIPING.
ALSO CONDUITS SHALL BE RUN AWAY AT LEAST 900mmTHE FIRE ALARM SYSTEM IS CONCEPTUAL. THE
MANUFACTURER'S EQUIPMENT LISTING.
SHOP SUBMITTAL TO SHOW DETAILED INSTALLATION
MANUFACTURER'S LISTED INSTALLATION
2.
CONTRACTOR SHALL COMPLETE DESIGN AND INSTALL
13.
12.
11.
9.
SYSTEM SHALL BE DESIGNED IN ACCORDANCE WITH
AND THE MASS MESSAGE NEEDS TO HAVE PRE ALERT
PATTERN IS REQUIRED FOR FIRE ALARM EVACUATION
VOICE EVACUATION SYSTEM IN LIEU OF TEMPORAL
ALL DEVICES AND EQUIPMENT SHALL BE UL LISTED
ELECTRICAL AND MECHANICAL SYSTEM EQUIPMENT
COORDINATE THE EXACT DEVICE LOCATIONS WITH
SWITCHES AND NON-ADDRESSABLE INITIATION
ALL TAMPER SWITCHES, FLOW SWITCHES, PRESSURE
PROHIBITED FOR ALL IDC, NAC AND SLC.
ALL CLASS "B" EXCEPTIONS IN NFPA 72, 23.4.2.2 ARE8.
7. CLASS "B" RACEWAY OF FA SYSTEM SHALL BE
SEPARATED BY A MINIMUM OF 1220mm HORIZONTAL
10. COAXIAL CABLE SHALL BE ONE PIECE BETWEEN
3.
5.
6. THE POWER CIRCUIT NUMBER DEDICATED TO FIRE
ALARM CIRCUIT AND ROOM LOCATION OF PANEL
LETTER "FIRE ALARM CIRCUIT" ON THE DEDICATED
FIRE ALARM CIRCUIT SHALL BE IDENTIFIED BY A RED
THE FIRE ALARM/MASS NOTIFICATION SYSTEM
CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING
FIRE ALARM INTELLIGIBILITY/AUDIBILITY CALCULATION,
WIRE SIZE, CONDUIT SIZE, NO. OF WIRES FOR THE FIRE
POWER CIRCUIT BREAKER AND/OR DISCONNECT SWITCH.
SHALL BE INDICATED ON THE FIRE ALARM/MASS
BUILDING TRANSMITTER AND ANTENNA.
AND 305mm VERTICALLY.
DEVICES SHALL BE PROVIDED WITH CLASS "B"
THE SYSTEM FOR READY TO USE. THE NUMBER OF
DEVICES SHOWN IS THE MINIMUM REQUIRED AND THE
FINAL QUANTITY SHALL BE IN ACCORDANCE WITH THE
DEVICE LOCATIONS IN ACCORDANCE WITH THE
AND BUILDING ARCHITECTURAL FEATURES.
OR FM APPROVED.
SPECIFICATION SECTION 28.31.76.00.31 (FA) AND
HAVE PRE ALERT TEMPORAL PATTERN MIN 2 CYCLES
PROVIDE ADDITIONAL RELAYS AS REQUIRED.14.
18.
19.
20.
PER UFC 4-021-01.
17. THE MASS NOTIFICATION SYSTEM IS CONCEPTUAL. THE
NUMBER OF DEVICES SHOWN IS THE MINIMUM REQUIRED
AND THE FINAL QUANTITY SHALL BE IN ACCORDANCE
MANUFACTURER'S EQUIPMENT LISTING.
SHOP SUBMITTAL TO SHOW DETAILED INSTALLATION
THE MASS NOTIFICATION SYSTEM SHALL BE ENSURED THAT
LEAST FOR THE FOLLOWING ITEMS.
FOR ABBREVIATION, LEGEND, AND GENERAL NOTES
STROBES FOR MASS NOTIFICATION SHALL BE MARKED
STROBES FOR FIRE ALARM SHALL BE MARKED "FIRE"
"ALERT" IN RED LETTER AND W/AMBER LENS.
SYSTEM SHALL BE DESIGNED IN ACCORDANCE WITH
1.
AND W/CLEAR LENS.
15.
CONTINUOUS 3-10 SECOND TONE, NFPA 72, 24.4.1.2.2
& 24.4.1.8.2.
THE MASS SYSTEM ACTIVATION MUST OVERRIDE THE FIRE
ALARM NOTIFICATION APPLIANCES THE MASS SYSTEM
ON THE PANEL BY SWITCH.
THIS SEQUENCE IS REQUIRED FOR BOTH PRE-RECORDED
MASS MESSAGE IS REQUIRED TO BE ANNOUNCED
IMMEDIATELY UNTIL SHUTDOWN MANUALLY.
SPECIFICATION SECTION 28.31.76.00.31 (MNS)
THE CONTRACTOR SHALL PROVIDE THE REQUIRED
TESTING TO ACHIEVE A MINIMUM CIS SCORE 0.8 AS
16.
DEVICE LOCATIONS IN ACCORDANCE WITH THE
MANUFACTURER'S LISTED INSTALLATION
AND NFPA 72, 2013 EDITION.
APPLIANCES UNTIL MASS ALERT IS CANCELED MANUALLY
ACTIVATION MUST OVERRIDE THE FIRE ALARM NOTIFICATION
MESSAGES AND MANUAL MICROPHONE INITIATED MESSAGES.
ARE IDENTICAL TO FIRE ALARM VISUAL APPLIANCES.
23.
MASS VISUAL APPLIANCE LOCATION REQUIREMENTS
AS SHOP DRAWING SUBMITTALS.
CONTRACT DRAWINGS SHALL NOT BE SUBMITTED
ARMY AND AIR FORCE PROJECTS.
WITH ANY FIRE ALARM VISUAL APPLIANCES ON
MASS VISUAL APPLIANCES SHALL NOT BE COMBINED24.
25.
22. FIRE ALARM SYMBOLS FROM NEPA 170 SHALL BE
AND ALL VISUAL APPLIANCES WITHIN THE SAME ROOM
ALL AUDIBLE APPLIANCES WITHIN THE BUILDING21.
SHALL BE SYNCHRONIZED.
VOICE EVACUATION SPEAKERS, NEPA 72.
AUDIBLE APPLIANCES SHALL PROVIDE THE STANDARD
TEMPORAL PATTERN UNLESS NFPA 101 REQUIRES
USED.
26. SHOW WEATHERPROOF EXTERIOR SPEAKERS AT ALL
EXTERIOR DOORS OR EXTERIOR GATHERING AREAS.
SHALL BE UL LISTED OFF-THE-SHELF-EQUIPMENT AND
ALL BACK-UP AMPLIFIERS WIRING AND ARRANGEMENT27.
SHALL BE TESTED TO THE STANDARDS OF UL OR RM AS
REQUIRED BY UFC 4-21-01, PARAGRAPH 4-4.3.
BOTH KOREAN AND ENGLISH.
THE MAN SHALL HAVE PRERECORDED MASSAGES IN28.
APPLICABLE CODE, SPECIFICATIONS AND
REQUIREMENTS AND WIRE COUNT.
ALARM AND DETECTION SYSTEM.
NOTIFICATION CONTROL PANEL COVER.
MODULES.
SYSTEM. VOICE EVACUATION MESSAGE NEEDS TO
REQUIRED.
WITH THE APPLICABLE CODE, SPECIFICATIONS AND
REQUIREMENTS AND WIRE COUNT.
OF 20% SPARE ADDRESSES FOR FUTURE USE.
FIRE ALARM SYSTEM OF EACH SLC TO HAVE A MINIMUM29.
VISUAL SIGNAL STROBES (75 CANDELA
MINIMUM, AMBER STROBE SHALL BE
MNS-AMBER STROBE W/WORDS "ALERT")
(FA-CLEAR STROBE W/WORDS "FIRE" +
DE-RATED AS REQUIRED) (TYPICAL)
WALL MOUNTED COMBO.
ADDRESSABLE SMOKE
DETECTOR W/SOUNDER
BASE (TYPICAL)
M F
F
M
EXT
WP
F
M
EXT
WP
M
F
M
F
M
F
M
F
102103109 M
F
M
F
MINIMUM, AMBER STROBE SHALL BE
DE-RATED AS REQUIRED)
VISUAL SIGNAL STROBES (75 CANDELA
W/WORDS "FIRE" + MNS-AMBER STROBE
W/WORDS "ALERT") VISUAL SIGNAL STROBES
AS REQ'D)/COMBO. (FA-CLEAR STROBE
WALL MOUNTED SPEAKER (WATTAGE
MNS-AMBER STROBE W/WORDS "ALERT")
ADDRESSABLE MANUAL
PULL STATION (TYPICAL)
WALL MOUNTED "WP" TYPE,
NOTIFICATION SPEAKER
FIRE ALARM/MASS
(WATTAGE AS REQ'D) (TYPICAL)
(TYPICAL)
FIRE ALARM/MASS NOTIFICATION
SPEAKER (WATTAGE AS REQ'D)
CEILING MOUNTED TYPE,
(FA-CLEAR STROBE W/WORDS "FIRE" +
(WATTAGE AS REQ'D)/COMBO.
WALL MOUNTED SPEAKER
SHALL BE DE-RATED AS REQUIRED) (TYPICAL)
(15 CANDELA MINIMUM, AMBER STROBE
SEE SHEET NO. E-1.
SYSTEM DIAGRAM
FIRE ALARM/MASS NOTIFICATION
ELECTRICAL
E-9
ADDRESSABLE SMOKE
DETECTOR
TS
J
TS
J
TS
J
PS
J CO
111 111 111 111 111
TAMPER SWITCH
(UNDER MECH ITEM) (TYPICAL)
FOR SPRINKLER SYSTEM
W/ADDRESSABLE MODULE
(UNDER MECH ITEM)
FOR SPRINKLER SYSTEM
W/ADDRESSABLE MODULE
PRESSURE SWITCH
W/ ADDRESSABLE MODULE
CARBON MONOXIDE DETECTOR
2) INTRUDER/HOSTILE PERSON SIGHTED WITHIN/AROUND THE BUILDING
1) BOMB THREAT OR ACTUAL BOMB WITHIN/AROUND THE BUILDING
3) OCCUPANTS DIRECTED TO TAKE COVER WITHIN THE BUILDING
6) "ALL CLEAR" MESSAGE
TEST8)
THE BUILDING
CARBON MONOXIDE GAS DETECTION MESSAGE WITHIN/AROUND 7)
THE LOCAL AREA
5) EMERGENCY WEATHER CONDITIONS APPROPRIATE FOR
NORMAL MAIN ENTRANCE/EXIT
4) EVACUATION OF THE BUILDING USING EXITS OTHER THAN THE
TAK, YS
185600
BUILDING S-81, CP CASEY
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
NEW GROUND FL TEL/CATV SYSTEM PLAN
SCALE : 1/100
SCALE: 1:100
0 1000 2000 4000
NOTES
1. FOR ABBREVIATION, LEGEND, AND GENERAL NOTES
2.
IN THE BUILDING SHALL BE DONE BY THE CONTRACTOR
THE INTERIOR CATV CABLES TO CATV EQUIPMENT
UNDER SUPERVISION OF CATV OFFICE.
"TTB"
TV
CTC
+1350
T
COAXIAL CABLE RG 6/U QUAD
SHIELDED IN 16C (TYPICAL)
CAT-6, 2-4PAIR, #24AWG IN 27C
TO BE TERMINATED AT PATCH
PANEL (TYPICAL)
DUAL MODULAR JACK
CAT-6, 8-PIN (RJ45 TYPE)
W/COVER PLATE (TYPICAL)
WALL MOUNTED TYPE TV OUTLET
W/"0.0"dB LOSS FACE PLATE &
F-81 BARREL TYPE CONNECTOR
CAT-6, 1-4PAIR, #24AWG IN 27C
TO BE TERMINATED AT PATCH
PANEL (TYPICAL)
SINGLE MODULAR JACK
CAT-6, 8-PIN (RJ45 TYPE)
W/COVER PLATE & LUG
(TYPICAL)
TV TV TV
TVTVTV
T
T
T
T
CTV
CTV
CTV
T
T
T
T
T
CTV CTV
CTV CTV
T
T
T
T
BED ROOM
BED ROOM
BED ROOM
BED ROOM
VEST
BED ROOM
BED ROOM
VIP BEDROOM
VEST
LAUNDRY
CORRIDOR
COMM
ROOM
MECH
T
TELEPHONE TERMINAL BOARD (TTB)
SEE DIAGRAM 1
CATV DISTRIBUTION CABINET "CTC"
SEE DIAGRAM 2
SEE SHEET NO E-1.
E11
E11
ELECTRICAL
NEW GROUND FL TEL/CATV SYSTEM PLAN
E-10
CCTV
PRIOR TO CONSTRUCTION.
LOCATION OF CCTV CAMERAS WITH DPW, USING AGENCY
AND WIRING/CONDUIT. CONTRACTOR SHALL CONFIRM
AND MONITORING SYSTEM WITH ASSOCIATED ACCESSORIES
SHALL REMOVE/REINSTALL EXISTING CCTV CAMERAS
EXIST CCTV MONITORING SYSTEM/ CONTRACTOR
CLOSET/CCTV
TAK, YS
185600
BUILDING S-81, CP CASEY
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
(TYPICAL)
CABLE SUPPORT
QUADPLEX RECEPTACLE
2P-3W-20A-125V
GROUNDING TYPE
EXOTHERMIC WELDING, LISTED COMPRESSION TWO-
1. THE CONNECTIONS OF THE BONDING CONDUCTOR FOR
TELECOMMUNITIONS TO THE TMGB SHALL UTILIZE
HOLE LUGS, SUITABLE AND EQUIVALENT TWO-HOLE
G
2. THREE WALLS SHALL BE COVERED WITH PLYWOOD.
FINISHED FLOOR AND SHALL BE PLACED WITHIN 75mm
3. ENTRANCE CONDUITS SHALL EXTEND 150mm ABOVE
PLYWOOD SHALL BE FIRE-RATED.
NOTES:
CROSS CONNECTING
PATCH CORD AS REQ'D
(1-100PAIR) (TYPICAL)
110 TYPE TERMINAL BLOCK
G
(1-100PAIR)
PTB
G
1-25PAIR, #24AWG TEL CABLE
TELEPHONE TERMINAL BOARD (TTB)
2500x2400x19THK PLYWOODx1EA
SEE NOTE 2 BELOW.
CONDUIT STUB-UP W/SEALING
(150mm AFF) (TYPICAL)
COMM CLOSET 113 ENTRANCE TERMINAL BLOCK
110 TYPE PROTECTED
G
"MP" GROUNDING BUS BAR
1#6 "BC" IN 21C
CONN TO MAIN PANELBOARD
GROUNDING BUSBAR (TMGB)
(100mm(W) x6.4mm(D) x450mmLG)
GROUND WIRE
TELECOMMUNICATION MAIN
CONDUCTOR #6AWG
P1-24
TEL SYSTEM DIAGRAM
NOT TO SCALE
SEE SITE PLAN
CONDUIT COUPLING
(TYPICAL)
WALL TYPE 1-24 PORT
PATCH PANEL "B"
STAMP FACING OUT" TO ENSURE THAT THEY CAN BE
"PLYWOOD WILL BE INSTALLED WITH FIRE RATED
4. TEST RESULTS WILL BE PROVIDED IAW THE MOST RECENT
REVISION OF THE ANSI/TIA/EIA-568.
5. LABEL ALL DROPS IAW TIA/EIA-606-A.
6. LABEL ALL GROUNDS IAW I3A.
LUGS ARE PREFERRED.
FIELD VERIFIED.
OF A WALL.
1st FL.
ROOF
T T
T T
101 102 102
T
T
WALL MOUNTED TYPE TV OUTLET
W/"0"dB LOSS FACE PLATE &
F-81 BARREL TYPE CONNECTOR
(TYPICAL)
P1-25
#6 "BC" IN 21C
GROUNDING BUSBAR
CONN TO MAIN PANELBOARD "MP"
SINGLE RECEPTACLE, 2P-3W-
FOR TRUNK BRIDGER AMPLIFIER
20A-250VAC, GROUNDING TYPE
2-WAY SPLITTER, 8-WAY TAP OFF x2EA, P1-23
RECEPTACLE, AIR VENTS AND
LOCKING DEVICE, NEMA 1 ENCL
BACKBOARD LINE EXTENDER AMPLIFIERS,
CATV DISTRIBUTION CABINET
WITH 610x610 W/19THK PLYWOOD
762mm(W)x610mm(H)x254mm(D)
AMP
20A-125VAC, GROUNDING TYPE
CTC
FOR TRUNK BRIDGER AMPLIFIER 113
G
DUPLEX RECEPTACLE, 2P-3W-
1st FL.
CEILING FOR THE MAINTENANCE.
INSTALLED ABOVE THE CEILING SHALL BE MARKED ON THE
THE LOCATION OF PULL BOX WITH COUPLERS WHICH IS
8.
THE CONTRACTOR TO MEET THE REQUIREMENT OF CATV dB.
INITIAL TESTING OF CATV SYSTEM SHALL BE PERFORMED BY7.
6.
5.
4.
CATV PANEL; ONE VENT HIGH AND ONE VENT LOW.
PROVIDE DIAGONAL VENTS ON OPPOSITE SIDE OF3.
RETURN PATH(2-WAY) CAPABILITIES.
ALL CATV MATERIAL AND EQUIPMENT MUST HAVE2.
CABLE, etc. SHALL BE COMPATIBLE WITH THE
EXISTING BASE CATV SYSTEM. IT SHALL BE
THE SPECIFICATION OF MATERIALS SUCH AS CATV
OUTLET TAP UNITS, SPLITTERS, AMPLIFIER, COAXIAL
COORDINATED WITH BASE CATV PERSONNEL.
COORDINATE LOCATION OF "NODE EQUIPMENT" WITH
SPLITTERS, AND TAP-OFF'S ARE TO BE 2WAY AND
C-COR LINE EXTENDER, DIRECTIONAL COUPLERS,
RETURN PATH 5-42MHZ, TO INCLUDE ALL
OPERATE IN THE RANGE FROM 5 TO 860MHZ,
30 DAYS PRIOR TO PERFORMING FINAL ACCEPTANCE TESTING.
CONTRACTORS WILL COORDINATE WITH BASE CATV PERSONNEL
RESULTS WILL BE RECORDED AND AVAILABLE AT THE FINAL
PROJECTS ON USFK INSTALLATIONS FOR QUALITY ASSURANCE.
THEN, BASE CATV PERSONNEL WILL INSPECT/TEST ALL
COORDINATION WITH BASE CATV PERSONNEL ON THE TYPE OF
CABLE MATERIAL AND PASSIVE DEVICES TO BE USED MUST
BE AGREED UPON BY BASE CATV PERSONNEL, CONTRACTOR,
AND ANY QUALITY ASSURANCE BRANCH PERSONNEL i.e.
BASE CONTRACTOR PRIOR TO START OF WORK.
ATTENUATION'S TO COMPENSATE FOR dbMV LEVELS.
ACCEPTANCE INSPECTION.
CORPS OF ENGINEERS, KORO, BASE CATV PERSONNEL PRIOR
1.
NOTES
9.
WHICH DEVICE IS
LOCATED (TYPICAL)
ROOM NUMBER
(TYPICAL)
QUAD SHIELDED IN 16C
COAXIAL CABLE RG 6/U
TV
TV
TV
TV
TV
TV
TV
CATV SYSTEM DIAGRAM
NOT TO SCALE
ROOF
GROUND BONDING
TO ORDERING.
P1-22
ENTRANCE CAP (35dia-1 HOLE)
WALL TYPE 1-24 PORT
PATCH PANEL "C"
T
T
T
W/COVER PLATE & LUG
CAT-6, 8-PIN (RJ45 TYPE)
SINGLE MODULAR JACK
PANEL "A"
TO BE TERMINATED AT PATCH
CAT-6, 1-4PAIR, #24AWG IN 27C
W/COVER PLATE (TYPICAL)
CAT-6, 8-PIN (RJ45 TYPE)
DUAL MODULAR JACK
CAT-6, 2-4PAIR, #24AWG IN 27C
(1-4PAIR TO BE TERMINATED AT
PATCH PANEL "A" AND OTHER
(TYPICAL)
WALL TYPE 1-24 PORT
PATCH PANEL "D"
WALL TYPE 1-24 PORT
PATCH PANEL "A"
1-4PAIR TO BE TERMINATED AT
PATCH PANEL "C") (TYPICAL)
T T
103 103
T
T
T
T
E7
ELECTRICAL
TEL & CATV SYSTEM DIAGRAM
E-11
(TYPICAL)
QUAD SHIELDED IN 35C
COAXIAL CABLE RG 11/U
NEWSEC RACK (1-SPOOL) &
EXIST CATV INCOMING LINE
TAK, YS
185600
BUILDING S-81, CP CASEY
65-A
12 CM
ST
STREAM
S T
S T
P V C
227.5
J-4
ST
CM
.5
.9
W A
L L
W A
L L
W A
L L
WALL
W A
L L
WALL
228.4
ST
GAL27
.8
.5
S T
R C
6 PVC
ST
T
C
S T
268.6
STREAM
DISCHARGE TO
65-A
12 CM
ST
STREAM
GRAVES
GRAVES
B A
S K
E T
B A
L L
O
U R
T
T E
N N I
U R
T
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
LAYOUT PLAN
BUILDING TRANSMITTER LOCATION
E-12
MATCH LINE 'C'
MATCH LINE 'C'
00-49341
3-48PN
00-49341
4-200PN
00-49341
4-200PN
01-49550
00-49341
LAUNDRY
KSC
PEST
647667
UTIL
B&G
WH-1
WH-2
DPW HQ
A
B
629 685
651A
833T
808 811
746 715 726
A B
00-49341
A
B
1149 1151
10291144
A
B
1918 1879
A
B
A
B
A
B
2372A
2373T
A C
2451 2400
A
B
A
B
2648 2605
2609T
2514 2540
8008T
2540T
26462645
1991 1963
A B
18331832
1962 1812
456A
CCTT
CCTT
SIMNET
463Z
SSSC
TSAK MILES 2000
549 546
8114T
560G
A B
86M
48T
A
B
39 55
134 133
186 192
202A
208 215 214
213 212
258252
249 262
1785 235
237 238
FOOT BR
VEH BR
FOOT BR
VEH BR
VEH BR
VEH BR
VEH BR
VEH BR 1821
VEH BR
VEH BR
VEH BR
VEH BR
FOOT BR
VEH BR
VEH BR
FOOT BR
FOOT BR
VEH BR
VEH BR
VEH BR
FOOT BR
FOOT BR
VEH BR
VEH BR
VEH BR
VEH BR
FOOT BR
1158A
1158B
RAILHEAD
MATCH LINE 'C'
MATCH LINE 'C'
447A
F
F
497A
497B
458Z
2372?
QA00894-0J
QA00893-0J
QA00892-0J
ADMIN
EXER W/LAT
EXER W/LAT
QA00138-9J
QA01300-8J
00-54151 BUP 020122
00-54152 BUP 020122
00-54132 BUP 010801
00-54127 BUP 040430
00-54158 BUP 030104
00-54129 BUP 011109
00-54157 BUP AFTER 2026
00-54156 BUP 031030
00-54130 BUP 020330
00-54131 BUP 020929
00-54155 BUP 030506
03-57200 REPAIR 041007
99-47353
4-200PN
01-QA00604 BUP
XX-QA00606 BUP 0310XX
95-44142
4-184PN
95-44066
4-184PN
96-QA00466 BUP
95-44066
4-184PN
95-44066
4-184PN
95-44066
4-184PN
01-55893 BUP
99-QA00603 BUP
XX-QA00602 BUP 0310XX
99-47353
4-200PN
96-43269
4-184PN
97-44592
4-200PN
XX-QA00287 BUP
01-55894 BUP
99-51682
4-200PN
99-51820
3-48PN
97-44592
4-200PN
99-51682
4-200PN
99-51682
4-200PN
01-55882 BUP
A
B
A B
2022(?)
VEH BR
VEH BR
472?
455?
1839T
1840T
BARRIER
1564 1566
635A
2002B
A B
48A
A
B
A B
A B
A
B
A
B
A
B
174 Z
706(707A)
(2298)
1071?
A B
1760?
KS-124
VEH BR?
VEH BR?
BARRIER
BARRIER
FLAG
FO
TBALL FIELD
(SYN
TH
ETIC
TU
RF AREA)
1919LIFT STATION
BUILDING TRANSMITTER LOCATION LAYOUT PLAN
TAK, YS
185600
: PROJECTED BUILDING
BUILDING S-81, CP CASEY
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
1-#6 AWG (G)
BUSHING
GROUND CLAMP
21mm STEEL CONDUIT
MOUNTING BRACKET
21mm DIA BOLT (TYP)
FIN GRADE
CONNECTOR BOTH END
COAXIAL CABLE W/
25mmx25mmx3mm THK
HOT-DIPPED GALV.
ANGLE STEEL
RIGID STEEL
35mm DIA.
ANTENNA MAST
SERVICE HEAD
21mm DIA.
ANTENNA
OMNI DIRECTIONAL
915mm APART (MIN)
STRAP STEEL (TYP)
35mm DIA RSC
U-BOLT FOR
CONDUIT AS REQ'D
SEAL END OF
(M
IN
GND WIRE
#6 AWG "BC"
NOT TO SCALE
SEE SPECS
COPPER CLAD STL
GROUND ROD
KIT, NEMA 3R ENCL
LIGHTNING ARRESTER
WEATHERPROOF SEAL
P
C
G
FA ANTENNA
OMNIDIRECTIONAL
KIT IN NEMA 3R ENCL
LIGHTNING ARRESTER
CABLE IN 21mm C
ANTENNA COAXIAL
IN 21mm C
1-#6 AWG (G)
FA ANTENNA MOUNTING DETAIL
S
EXIST SIGNALING LINE CIRCUIT
D
MEET WIRING REQUIREMENT FOR FACP OR MNS
POWER AND CONTROL LINES AS REQUIRED TO
EXIST FIRE ALARM DETECTOR (TYPICAL)
NOT TO SCALE
CONNECTION DIAGRAM
TYPICAL BUILDING TRANSMITTER
NOTE
1.
COR FOR LOCATION SELECTION.
SHALL COORDINATE WITH FIRE DEPARTMENT AND
BE NEXT TO EXIST "FACP" OR "MNS". CONTRACTOR
WITH BATTERY & CHARGER/ LOCATION SHALL
BUILDING TRANSMITTER (BT-XM)
E-13
TRANSMITTER
TO FA BUILDING
FTR
(FACP)
CONTROL PANEL
EXIST FIRE ALARM
BUILDING S-81, CP CASEY (PHASE#1)
BUILDING TRANSMITTERS AND REPAIR
REPLACE FIRE ALARM SYSTEM / INSTALL
TAK, YS
185600
BUILDING NO. ITEMS
WITH CONNECTORS
COAXIAL CABLE (CLASS I&II)
W/ RAIN PROOF ENCL.,
LIGHTNING ARRESTER
AND MOUNTING SET,
FIRE ALARM ANTENNA
WITH BATTERY & CHARGER,
TRANSMITTER (BT-XM)
11 SETS OF BUILDING
TOTAL 11 BUIDLINGS
NOT TO SCALE
BT SYSTEM BUILDING SCHEDULE
TRANSMITTER CONNECTION DIAGRAM
FA ANTENNA MOUNTING DETAIL & BUILDING
BT SYSTEM BUILDING SCHEDULE TYPICAL
2.
LISTED BUILDINGS.
IF MASS NOTIFICATION SYSTEM IS NOT INSTALLED IN
SYSTEM OR ADDRESSABLE FIRE ALARM CONTROL PANEL
TRANSMITTER SHALL BE CONNECTED MASS NOTIFICATION
CONTROL LINES OF FIRE ALARM BUILDING
FIRE ALARM AND/ OR MASS NOTIFICATION SYSTEM POWER.
CONTRACTOR SHALL VERIFY EXISTING CONDITION OF
ATENNA, LIGHTNING ARRESTER, ETC BY BUILDING.
FOR INSTALLATION PLAN AND LOCATION OF BUILDING TRANSMITTER,
CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE SHOP DRAWING