M-1

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

MECHANICAL

SYMBOLS AND ABBREVIATIONS

heating

ACCU AIR COOLED CONDENSING UNIT

ACLD AIR COOLED

ACU AIR CONDITION UNIT (S)

ACV ALARM CHECK VALVE

ADP APPARATUS DEW POINT

AHU AIR HANDLING UNIT

AIR COND AIR CONDITION (-ING,-ED)

AL ALUMINUM

ALT ALTITUDE

AMB AMBIENT

AMP AMPERE(AMP, AMPS)

APPROX APPROXIMATE

AVG AVERAGE

AWG AMERICAN WIRE GAUGE

BARO BAROMETER(-TRIC)

BARO PR PRESSURE, BAROMETRIC

BHP BRAKE HORSEPOWER

BP BOILING POINT

CAP CAPACITY

CCW COUNTER CLOCKWISE

CHW CHILLED WATER

CIP CAST IRON PIPE

CKT CIRCUIT

CLASS CLASSIFICATION

CLG LOAD COOLING LOAD

COEF COEFFICIENT

CONN CONNECTION

CONT CONTINUE

CPRSR COMPRESSOR

JACKET WATER RETURN

MEDIUM PRESSURE STEAM

MEDIUM PRESSURE CONDENSATE

LOW PRESSURE STEAM

LOW PRESSURE CONDENSATE

BOILER BLOW DOWN

PUMPED CONDENSATE

VACUUM PUMP DISCHARGE

MAKE UP WATER

FUEL OIL DRAIN

FUEL OIL TANK VENT

FUEL OIL GAUGE

FUEL OIL SUPPLY

FUEL OIL RETURN

CONDENSATE WATER SUPPLY

CONDENSATE WATER RETURN

COMPRESSED AIR

VACUUM (AIR)

EXISTING PIPE

PIPE TO BE REMOVED

CONTROL AIR MAIN

REFRIGERANT DISCHARGE

REFRIGERANT SUCTION

REFRIGERANT LIQUID

DRAIN

CHILLED WATER SUPPLY

CHILLED WATER RETURN

HOT/CHILLED WATER SUPPLY

HOT CHILLED WATER RETURN

air conditioning and refrigeration

THREE WAY

PLUG VALVE

GATE, GLOBE

GATE, ANGLE

CONTROL

BUTTERFLY

BALL

AIR LINE

PIPE SLEEVE

BACKFLOW PREVENTER

PITCH OR PIPE, UP(U), DOWN(D)

VENT THRU ROOF

FUNNEL DRAIN, OPEN

SURFACE CLEANOUT

FLOOR CLEANOUT

FLOOR DRAIN

CHEMICAL SUPPLY PIPES

ACID WASTE

GAS

CONDENSATE DRAIN BELOW

CONDENSATE DRAIN ABOVE

SANITARY DRAIN

VENT

HOT WATER RETURN

HOT WATER SUPPLY

COLD WATER

plumbing valves : (for selective actuators)

PIPE SLEEVE WITH FIRE STOPPING

EXPANSION LOOP

EXPANSION JOINT

BALL JOINT

ANCHOR, MAIN

ANCHOR, INTERMEDIATE

ALIGNMENT GUIDE

AIR SEPARATOR

AIR VENT, MANUAL

AIR VENT, AUTOMATIC

SQUARE HEAD BALANCING COCK

SQUARE HEAD BALANCING COCK

SAFETY

RELIEF

QUICK CLOSING, FUSIBLE LINK

QUICK OPENING

PRESSURE REDUCING

NEEDLE

LOCK SHIELD

HOSE END DRAIN

CONTROL, ELECTRIC-PNEUMATIC

CHECK, NON-SLAM

CHECK, SWING

DIAPHRAGM

SOLENOID

MOTOR ELECTRIC

valve actuators

EXPANSION JOINTEXPJT

ENTERING WATER TEMPEWT

EVAPORAT (-E,-ING,-ED,-OR)EVAP

EXTERNAL STATIC PRESSUREESP

EXPLOSION PROOFEP

EQUIPMENTEQPT

ENTERINGENT

EFFICIENCYEFF

EQUIVALENT DIRECT RADIATIONEDR

ECONOMIZERECON

ECCENTRICECC

ENTERING AIR TEMPERATUREEAT

DIRECT EXPANSIONDX

DRY PIPE VALVEDPV

DOUBLE POLE DOUBLE THROWDPDT

DEWPOINT TEMPERATUREDPT

DIESEL OIL

DIVISIONDIV

DIFFERENCEDIFF

DIAGRAMDIAG

DIAMETER

DEGREEDEG or °

DRY BULB TEMPERATUREDBT

DECIBEL OR DRY BULBDB

CIRCULATING WATER PUMPCWP

CLOCKWISE OR COLD WATERCW

COEFFICIENT, VALVE FLOWCv

CU MM

HERTZHZ

HORIZONTALHORIZ

HOT WATER HEATERHWH

HOT WATERHW

HOUR(S)HR

HORSEPOWERHP

MERCURYHG

HEADHD

HOSE BIBBHB

GALVANIZED STEELGALVS

GAGE OR GAUGEGA

FIXTUREFXTR

FEED WATER PUMPFWP

FACE VELOCITYFVEL

FLUSH VALVEFV

FRP

FREQUENCYFREQ

FEMALE PIPE THREADFPT

FUEL OILFO

SUBMERSIBLESBM

SANITARYSAN

SUPPLY AIRSA

REFRIGERATION TONRT

REVOLUTIONS PER MINUTERPM

RELATIVE HUMIDITYRH

RADIATORRDTR

RETURN AIRRA

THERMAL RESISTANCER

QUANTITYQTY

QUARTQT

PERCENT

PRESSURE REDUCING VALVEPRV

PARTS PER MILLIONPPM

POL

POINT OF CONNECTIONPOC

PLUMBINGPLMB

PHASE (ELECTRIC)PH

PRESSURE GAGEPG

PD

POLEP

URINALUR

UNIT HEATERUH

HEAT TRANSFER COEFFICIENTU

TYPICALTYP

THERMOSTATTSTAT

TONS OF REFRIGERATIONTONS

THICKNESSTHK

THERMOMETERTHERM

TEMPERATURETEMP

TEMPERATURE DIFFERENCETD

SYMBOLSYM

SUCTIONSUCT

STORAGESTOR

STEELSTL

STANDARDSTD

STEAMST

SAYBOLT SECONDS UNIVERSALSSU

STAINLESS STEELSST

SAYBOLT SECONDS FUROLSSF

SQUARESQ

SPRINKLERSPR

SPECIFICATIONSPEC

SINGLE POLE DOUBLE THROWSPDT

SM

WATERPROOFWTRPRF

WEIGHTWT

WSHR

WITHW/

WATTHOUR OR WATER HEATERWH

WIDTHWD

WATER-COOLEDWCLD

WATER CLOSETWC

WET BULB TEMPERATUREWBT

WET BULBWB

WATTW

PRESSURE, DYNAMIC(VELOCITY)VP

VOLUMEVOL

VISCOSITYVISC

VERTICALVERT

VENTILATIONVENT

VELOCITYVEL

VARIABLE AIR VOLUMEVAV

LAV LAVATORY

LAT LEAVING AIR TEMPERATURE

LBS POUNDS

LG LENGTH

LH LATENT HEAT

LT LAUNDRY TRAY

LWT LEAVING WATER TEMPERATURE

NUMBERNO

NORMALLY OPENN.O.

NOT IN CONTRACTNIC

NORMALLY CLOSEDN.C.

NOISE CRITERIANC

NOT APPLICABLEN/A

MAX

WASHER

PETROLEUM, OIL AND LUBRICANTS

PRESSURE DROP OR DIFFERENCE

FIBERGLASS REINFORCED PLASTIC

valves, special duty :

FLEXIBLE CONNECTOR

FLOWMETER, ORIFICE

FLOWMETER, VENTURI

FLOW SWITCH

PRESSURE GAUGE AND COCK

PRESSURE SWITCH

PUMP (INDICATE USE)

STRAINER

STRAINER, BLOW OFF

FIRE DEPARTMENT CONNECTION

PRE-ACTION VALVE

DRY-PIPE VALVE

ALARM CHECK VALVE

SIDEWALL SPRINKLER

PENDENT SPRINKLER

UPRIGHT SPRINKLER

fitting :

THERMOMETER

THERMOSTAT, ELECTRIC

TRAP, ELECTRIC (INDICATE TYPE)

BUSHING

CAP

CONNECTION, BOTTOM

CONNECTION, TOP

ELBOW, 90°

ELBOW, 45°

ELBOW, TURNED UP

ELBOW, TURNED DOWN

REDUCER, CONCENTRIC

REDUCER, ECCENTRIC (STRAIGHT, INVERT)

REDUCER, ECCENTRIC (STRAIGHT, DOWN)

TEE

TEE, OUTLET UP

TEE, OUTLET DOWN

TEE, SINGLE SWEEP

UNION, SCREWED

UNION, FLANGED

DIFFUSER, LINEAR

DUCT SECTION, POSITIVE PRESS., FIRST

DIRECTION OF FLOW

ACCESS DOOR, VERTICAL OR HORIZONTAL

CHANGE OF ELEVATION, RISE(R), DOWN(D)

COWL, (GOOSENECK) AND FLASHING

ACOUSTICAL LINING

FLEXIBLE DUCT

SOUND ATTENUATOR

FLEXIBLE CONNECTION

FIGURE IS ON TOP

FIGURE IS ON TOP

DUCT SECTION, NEGATIVE PRESS., FIRST

R

AD

FC

TRANSITION

TURNING VANES

S DETECTORS, FIRE AND/OR SMOKEF

dampers

BACKDRAFT DAMPER

BDD

S

ELECTRIC MOTOR OPERATED DAMPER

MANUAL VOLUME DAMPER

FD

FIRE DAMPER (PROVIDE ACCESS DOOR)

AD

PNEUMATIC OPERATED DAMPER

SMOKE DAMPER (PROVIDE ACCESS DOOR)

SPLITTER DAMPER

VD

AD

SD

M

SG

SR

SG

SR

EG

ER

RG

RR

UC 13mm

47.2

94.4

DG

TG

grilles, registers and diffusers :

(2-WAY SHOWN)

sprinkler

LATERAL

FLOOR OR GRADE

FLOOR OR GRADE

W/ MEASURING TAP

R

PS

P

FS

VFM

OFM

EJ

S

MV

AVA

S

R

PE

EP

S

M

GLOBE

CONTROL, PNEUMATIC-ELECTRIC

HOSE BIBB

A

PLAN ELEV.

BFP

(NAME)

ACID

G

CD

CD

JWS

JWR

MPS

MPC

LPS

LPC

BBD

PC

VPD

MU

FOD

FOV

FOG

FOS

FOR

CS

CR

MTWS

MTWR

HWS

HWR

A

VAC

(NAME)E

(NAME)

RD

M

RS

RL

D

CHWS

CHWR

CH/HWS

CH/HWR

SCO

FCO

FD

JACKET WATER SUPPLY

FLANGED

PIPING

DUCT WORK

WELDED

SCREWED

SOLVENT CEMENT

BELL AND SPIGOT

VAC VACUUM

LIQUID LINELL

200mm x 200mm

FLOOR SINK (200mm x 200mm)

60°C HOT WATER (60°C)

82.22°C HOT WATER (82.22°C)

810mm x 400mm

810mm x 400mm

810mm x 400mm

200mm NCD

(600mm x 300mmH, 472 LPS)

TRANSFER GRILLE ASSEMBLY

600/300

300x150

DOOR GRILLE (300mmx150mmH)

500/300L

(500mmWx300mmH, 94.4 LPS)

LOUVER, DOOR OR WALL

CUBIC MILLIMETER

C CENTIGRADE

DIA or o

CMH CUBIC METER PER HOUR

CU M CUBIC METER

FA FACE AREA OR FRESH AIR

FHC FIRE HOSE CABINET

FHY FIRE HYDRANT

FLA FULL LOAD AMPERES

GR GRAMS

DIAMETER, INSIDEID

ISOMETRICISO

IRON PIPE SIZEIPS

J JOULE

KG

K THERMAL CONDUCTIVITY

KCAL/HR KILOCALORIE PER HOUR

KILOGRAM

KG/SQ CM KILOGRAM PER SQ. CENTIMETER

KG/SQ CM A KILOGRAM PER SQ. CENTIMETER (ABSOLUTE)

KG/SQ CM G KILOGRAM PER SQ. CENTIMETER (GAUGE)

KW KILOWATT

KWH KILOWATT HOUR

KG/SM KILOGRAM PER SQ. METER

KG/SM A KILOGRAM PER SQ. METER (ABSOLUTE)

KG/SM G KILOGRAM PER SQ. METER (GAGE)

KJ KILOJOULE

L LITERS

Pa PASCAL

OS&Y

OXY OXYGEN

OUTSIDE SCREW & YOKE

OD DIAMETER, OUTSIDE

LPD LITERS PER DAY

LPH LITERS PER HOUR

LPS

LM LINEAR METER

LITERS PER SECOND

LPH, STANDARD CONDITIONSSLPH

LPS, STANDARD CONDITIONSSLPS

SG

SLPD LPD, STANDARD CONDITIONS

SL SENSIBLE LOAD

SH SENSIBLE HEAT

SPECIFIC GRAVITY

VLV VALVE

V VOLT

SF SAFETY FACTOR

SEC SECOND

OAIL OUTSIDE AIR INTAKE LOUVER

OA OUTSIDE AIR

NOT TO SCALENTS

MIN

MPH

M METERS

MAXIMUM

MINIMUM OR MINUTE

METERS PER HOUR

MPS METERS PER SECOND

MM MILLIMETER

NPT NATIONAL TAPER PIPE (THREAD) SCH SCHEDULE

SP STATIC PRESSURE

SQUARE METER

SOLDERED/BRAZED

M E C H A N I C A L M A T E R I A L I N D I C A T I O N S & S Y M B O L S

A B B R E V I A T I O N S

HOT WATER SUPPLY

MEDIUM TEMPERATURE

HOT WATER RETURN

MEDIUM TEMPERATURE

HOT WATER SUPPLY

LOW TEMPERATURE

HOT WATER RETURN

LOW TEMPERATURE

(810mm WIDTH x 400mm DEPTH)

DUCT SIZES SHOWN

REGISTER, CEILING

EXHAUST AIR GRILLE OR

REGISTER, SIDEWALL

SUPPLY AIR GRILLE OR

REGISTER, CEILING

SUPPLY AIR GRILLE OR

REGISTER, CEILING

RETURN AIR GRILLE OR

(13mm, 47.2 LPS)

UNDERCUT DOOR

(200mm NECK DIAMETER)

CEILING DIFFUSER, ROUND TYPE

SQUARE TYPE

CEILING DIFFUSER,

GATE, NORMALLY CLOSED

REFRIGERANT (134A, 22, ETC)R134A,R22

GATE, NORMALLY OPEN

DFW

MECHANICAL MATERIAL INDICATIONS &

BLDG NO. 261

REPAIR TRANSIENT LIVING QUARTER,

WARRIOR BASECHU, HC

107387

M-2

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

MECHANICAL

5. CONCRETE REMOVAL AND RESTORATION SHALL CONFORM TO SPECIFICATION.

NECESSARY DUCT CONNECTION(S) TO FUNCTION AS ORIGINALLY INTENDED.

12. PRIOR TO INSTALLING NEW HVAC AND PLUMBING PIPING CONTRACTOR MUST

COORDINATE WITH EXISTING DUCTWORK AND PIPING ELEVATION/LOCATION.

IF EXISTING DUCT ELEVATION IS CONFLICTED WITH NEW PIPING INSTALLATION,

REMOVE EXISTING DUCTWORK AND INSTALL NEW DUCTWORK AND MAKE ALL

CONTRACTING OFFICER FOR APPROVAL.

CONTRACTOR ACCORDING TO ACTUAL FIELD CONDITIONS AND SUBMITTED TO THE

FIELD CONDITIONS. SUCH DETAILS SHALL BE PREPARED IN THE FIELD BY THE

11. SOME DETAILS SHOWN ON THIS CONTRACT DRAWINGS MAY NOT MATCH EXACT

SUCH AS ANCHORS, HANGERS/SUPPORT, ETC.

10. ALL HVAC PIPING/DUCTWORK TO BE REMOVED SHALL INCLUDE ALL IT'S ACCESSORIES

9. ANY OPENING RESULT FROM THE REMOVAL WORK THAT'S NOT TO BE RE-USED

SHALL BE PATCHED OR RESTORED TO MATCH ADJACENT SURFACE OR AREA.

GENERAL NOTES

PER SPEC.

THIS CONTRACTOR.

AND SHALL BE VERIFIED AT THE JOB SITE.

CORRECTIONS FOR CONTRACTING OFFICER'S APPROVAL.

7. ALL WALL/FLOOR/ROOF OPENINGS RESULTED FROM THE REMOVAL OF PIPING AND

4. ANY PIPES THAT PENETRATE FIRE RATED WALL (EXISTING/ NEW) SHALL BE SEALED

6. NO MECHANICAL WORK CAN BE STARTED WITHOUT AN APPROVED SHOP DRAWINGS.

SHOP DRAWING SHALL NOT BE THE EXACT DUPLICATION OF THE CONTRACT DRAWING.

2. LOCATION AND SIZES OF EXISTING EQUIPMENT, DUCTWORK, PIPING, ETC. APPROXIMATE

OFFICER'S REPRESENTATIVE ATTENTION WITH RECOMMENDATIONS FOR PROPER

IF ANY DISCREPANCY IS DETECTED, IT SHOULD BE BROUGHT TO THE CONTRACTING

THE EXISTING CONDITIONS, EQUIPMENT, FINISHES, ETC., PRIOR TO START OF WORK.

1. THE CONTRACTOR SHALL VISIT THE SITE AND SHALL FAMILIARIZE HIMSELF WITH

THE WORK PERFORMED UNDER THIS CONTRACT SHALL BE REPAIRED OR REPLACED BY

THE EXISTING EQUIPMENT ANY EQUIPMENT, DUCT WORK, PIPING ETC. DAMAGED DUE TO

3. CONNECT TO EXISTING SYSTEM SHALL BE DONE IN SUCH A MANNER AS NOT DAMAGE

THE REQUIREMENTS OF SEAL CLASS C.

8. ALL SUPPLY, RETURN AND EXHAUST AIR DUCTWORK SHALL BE CONSTRUCTED

ACCORDING TO SMACNA STATIC PRESSURE CALSS 500PA AND DUCTWORK SHALL MEET

DUCTWORK SHALL BE PATCHED OR RESTORED TO MATCH ADJACENT SURFACE OR AREAS.

SCOPE OF WORK

13.

CHANGES REQUIRED TO MAKE THIS

CONTRACTOR SHALL PROVIDE NECESSARY SHOP DRAWINGS FOR ANY

REQUIREMENT FOR GAS ONLY BURNERS MAY BE JUSTIFIABLE. THE

PACKAGE, PRIOR TO THE START OF CONSTRUCTION, THEREFORE THE

PROVIDE NATURAL GAS ACCESS TO THE BUILDING UNDER THIS DESIGN

CONCURRENT NATURAL GAS CONVERSION PROJECT PACKAGES MAY

HEATING SYSTEMS WITH DPW PRIOR TO THE START OF CONSTRUCTION.

AND OIL) BURNERS FOR HEATING HOT WATER AND DOMESTIC HOT WATER

THE CONTRACTOR SHALL COORDINATE THE USAGE OF DUAL FUEL (GAS

SPRINKLER WORK

REPAIR AND MAINTENANCE WORK

HVAC SYSTEM

1.

2.

1.

2.

3. REPAIR BY REPLACEMENT EXISTING BACK FLOW PREVENTER (BFP) AND PRESSURE REDUCING VALVE (PRV) ASSEMBLY, INCLUDING PIPE

SUPPORTS AND HOSE BIBB WITH NEW.

1. REPAIR BY REPLACEMENT OF EXISTING FIRE PROTECTION SYSTEM WITH NEW WET TYPE SPRINKLER SYSTEM AND ASSOCIATED PIPING WITH NEW.

REPAIR BY REPLACEMENT OF EXISTING DETERIORATED ELECTRIC UNIT HEATER WITH NEW.

REPAIR BY REPLACEMENT OF EXISTING DETERIORATED ELECTRIC WATER COOLER WITH NEW.

REPAIR BY REPLACEMENT OF EXISTING DETERIORATED ALL COLD WATER PIPING WITH NEW.

GENERAL NOTES AND SCOPE OF WORK

REPAIR BY REPLACEMENT OF EXISTING DETERIORATED HEATING BOILER, AIR COOLED CONDENSING UNIT, AIR HANDLING UNIT AND DUCT

PLUMBING SYSTEM

WITH SPLIT TYPE HEAT PUMP UNITS INCLUDING CONC. PAD, ENERGY RECOVERY VENTILATIONS, DUCTWORK AND DIFFUSERS WITH NEW.

BLDG NO. 261

REPAIR TRANSIENT LIVING QUARTER,

M-3

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

M E C H A N I C A L E Q U I P M E N T S C H E D U L E

R E M A R KD E S C R I P T I O NITEM NO QTY.

EWC

ELECTRIC WATER COOLER

MOTOR : 1/5 HP, 115 V, 1 PH, 60 HZ.

FLOOR MOUNTED TYPE, MECHANICALLY

CAPACITY : 8.0 GPH, 80 DEG.F. TO 50 DEG.F.

& COMPRESSOR SHALL CONFORM TO ARISTANDARD 1010.

MECH RM (123)

HORIZONTAL

REMARKS

HP

1/20

VOLT/PH/HZRPMLPS

EAT

1,550256.210

(DEG C)

EWT

(KW)

HEATING

CAPACITY

LPS

82.12.3 0.05

(DEG C)

TYPESERVICE

DISCHARGE TYPE

Q'TYITEM NO

FAN CAPACITY

UH

ELECTRIC UNIT HEATER

HPU

BE INSTALLED AS PER MANUFACTURER RECOMMENDATIONS.

WITH 7 DAY PROGRAMMABLE MOD # PQRCVSL0208V/60Hz/ 300.2 R-410A4-WAY CASSETTE TYPE, Q'TY

COOLING CAP

TYPE

HEATING CAP

ITEM NO

INDOOR SPLIT SYSTEM HEAT PUMP UNIT

(BTU/H ) (BTU/H)

REFRIGERANT

TYPE

FAN CAPACITY

AMPS VOLT/PH/HZ

21,500

POWER

INPUT(W)

SERVICE REMARKS

19,100

AIR CAP

BEDROOM (101, 102, 201

AND 202)

1PH

1. ALL HEAT PUMP UNITS REFRIGERANT PIPING SHALL

2. WALL MOUNTED TEMPERATURE CONTROLLER

DUCT LESS CABINET

(CFM)

3. FOR CASSATTE TYPE UNITS, MFG SHALL PROVIDE AIR DEFLECTOR PLATE

4. BUILT-IN CONDENSATE DRAIN PUMP

5. CASSETTE COVER MODEL PDC-TH1.

6. LG MODEL ARNU183TQC4 OR APPROVED EQUAL

TOTAL

COOLING CAP

(BTU/H)

Q'TY SERVICEITEM NO

TOTAL

HEATING CAP

(BTU/H)

OHPU

POWER SUPPLY

TYPE

TYPE

OUTDOOR HEAT

PUMP UNIT

QTY POWER(A) QTY POWER(A)

COMPRESSOR SUPPLY FAN

VOLT/PH/HZ

TYPE

AIR CAP.

(CFM)

3 3 PROPELLER 17,600

MCA MOP

REFRIGERANT

TYPE

HEATING CAPACITY SHALL BE BASED ON 8 DEG C

208/3/60 R410A

REMARKS

BE INSTALLED AS PER MANUFACTURER RECOMMENDATIONS.

OUTDOOR SPLIT SYSTEM HEAT PUMP UNIT

1ST, 2ND FLOOR HPU

MUILT V TYPE

216,000 14.01 15.87243,000 48.8 25.3

HSS DC SCROLL (B) /19.0

(A)17.0/19.0

4.0/6.0

1. ALL HEAT PUMP UNITS REFRIGERANT PIPING SHALL

2. COOLING CAPACITY SHALL BE BASED ON 35 DEG C

3. SIMILAR TO LG MODEL ARUN216BTE4 OR APPROVED EQUAL

ERV 590 208V/60Hz/1PH470AIR TO AIR HEAT EXCHANGER

CROSS FLOW TYPE

Q'TY TYPE

AIR CAPACITY

ITEM NO VOLT/PH/HZ

ENERGY RECOVERY VENTILATION

REMARKS

(CFM)

POWER INPUT

(W)

SERVICE

3.44

RATED AMPS

(A)

BEDROOM (101, 102, 201

AND 202)

LG MULTI V MODEL ARVU063ZEA2 OR APPROVED EQUAL

AIR COOLED WITH AIR COOLED CONDENSER

MECHANICAL EQUIPMENT SCHEDULE

208/1/60

BLDG NO. 261

REPAIR TRANSIENT LIVING QUARTER,

WARRIOR BASECHU, HC

107387

MECHANICAL

(KW)

INPUT

POWER

(KW)

INPUT

POWER

M-4

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

MECHANICAL

T T

TH

TC

M

SCALE : 1: 50

MECH

RC T

S

M4

EXISTING 1ST FLOOR REMOVAL PLAN

CONC. PAD AND PIPING TO BE REMOVED

EXST. ALL DUCT TO BE REMOVED(TYP)

EXST. ALL EQUIPMENTS AND DUCT & HVAC, PLUMBING

AND OIL PIPING TO BE REMOVED IN MECH ROOM

EXST. SUMP AND FUEL OIL PIPING

TO BE REMOVED

EXISTING 1ST FLOOR REMOVAL PLAN

TURN-IN TO SUPPLY DIVISION

(SEWER AND VENT PIPING TO BE REMAINE)

BEDROOM

BEDROOM

ROOM

MECH

FEB FEB

BLDG NO. 261

REPAIR TRANSIENT LIVING QUARTER,

M-5

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

MECHANICAL

T

EXST. ALL DUCT TO BE REMOVED(TYP)

SCALE : 1: 50M5

EXISTING 2ND FLOOR REMOVAL PLAN

EXST. SMOKE STACK TO BE REMOVED

EXISTING 2ND FLOOR REMOVAL PLAN

EXST. ALL DUCT TO BE REMOVED(TYP)

BEDROOM

BEDROOM

FEBFEB

BLDG NO. 261

REPAIR TRANSIENT LIVING QUARTER,

M-6

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

MECHANICAL

SCALE : 1: 50M6

EAOA EAOA

ROUND PAN DIFFUSER

S.A Q : 196 CFM

ø420×ø250 (ND:ø250)

ARVU063ZEA2

ROUND PAN DIFFUSER

R.A Q : 295 CFM

ø420×ø250 (ND:ø250)

ARVU063ZEA2

ROUND PAN DIFFUSER

R.A Q : 295 CFM

ø420×ø250 (ND:ø250)

ARVU063ZEA2

ROUND PAN DIFFUSER

S.A Q : 196 CFM

ø420×ø250 (ND:ø250)

ARVU063ZEA2

R A

S A

E A

O A

R A

S A

E A

O A

ERV

ERV

1ST FLOOR HVAC PLAN(ENERGY RECOVERY VENTILATION)

1.

NOTES:

CONTRACTOR SHALL VERIFY EXACT LOCATION, SIZE AND DIRECTION

2.

OF DUCT IN FIELD(TYP)

VENTILATION SYSTEM IN MECH. ROOM.

CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR ENERGY RECOVERY

(ENERGY RECOVERY VENTILATION)

1ST FLOOR HVAC PLAN

FEB FEB

BLDG NO. 261

REPAIR TRANSIENT LIVING QUARTER,

WARRIOR BASECHU, HC

107387

MECH ROOM

BEDROOM

BEDROOM

M-7

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

MECHANICAL

BEDROOM

BEDROOM

EAOA EAOA

ERV

ROUND PAN DIFFUSER

R.A Q : 196 CFM

ø420×ø250 (ND:ø250)

ARVU063ZEA2

ROUND PAN DIFFUSER

S.A Q : 196 CFM

ø420×ø250 (ND:ø250)

ARVU063ZEA2

ROUND PAN DIFFUSER

R.A Q : 196 CFM

ø420×ø250 (ND:ø250)

ARVU063ZEA2

ROUND PAN DIFFUSER

S.A Q : 196 CFM

ø420×ø250 (ND:ø250)

R A

S A

E A

O A

R A

S A

E A

O A

ERV

SCALE : 1: 50M7

2ND FLOOR HVAC PLAN(ENERGY RECOVERY VENTILATION)

1.

NOTES:

CONTRACTOR SHALL VERIFY EXACT LOCATION, SIZE AND DIRECTION

2.

OF DUCT IN FIELD(TYP)

VENTILATION SYSTEM IN MECH. ROOM.

CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR ENERGY RECOVERY

(ENERGY RECOVERY VENTILATION)

2ND FLOOR HVAC PLAN

FEBFEB

BLDG NO. 261

REPAIR TRANSIENT LIVING QUARTER,

M-8

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

MECHANICAL

HPU

HPU

HPU

HPU

HPU

HPU

HPU

HPU

HPU

HPU

OHPU

OHPU

EUH

CONC. PAD

SCALE : 1: 50M8

1ST FLOOR HVAC PLAN(HEAT PUMP)

1.

NOTES:

CONTRACTOR SHALL VERIFY EXACT LOCATION, SIZE AND DIRECTION

2.

OF HEAT PUMP AND PIPING IN FIELD(TYP)

CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR HEAT PUMP AND

PIPING IN MECH. ROOM.

1ST FLOOR HVAC PLAN

(HEAT PUMP)

FEB FEB

BLDG NO. 261

REPAIR TRANSIENT LIVING QUARTER,

M-9

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

MECHANICAL

BEDROOM

BEDROOM

HPU

HPU

HPU

HPU

HPU

HPU

HPU

HPU

HPU

HPU

HPU

HPU

SCALE : 1: 50M9

2ND FLOOR HVAC PLAN(HEAT PUMP)

1.

NOTES:

CONTRACTOR SHALL VERIFY EXACT LOCATION, SIZE AND DIRECTION

2.

OF HEAT PUMP AND PIPING IN FIELD(TYP)

CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR HEAT PUMP AND

PIPING IN MECH. ROOM.

2ND FLOOR HVAC PLAN

(HEAT PUMP)

FEBFEB

BLDG NO. 261

REPAIR TRANSIENT LIVING QUARTER,

M-10

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

MECHANICAL

MECH

FIRST FLOOR SECOND FLOOR

POC

WATER PIPE.

25mm DOMESTIC COLD

M16-

M16-

SCALE : 1: 50

EWC

EWC

CW

CW

M10

PLUMBING PIPING PLANS

1.

NOTES:

CONTRACTOR SHALL VERIFY EXACT LOCATION, SIZE AND DIRECTION

2.

OF CW, SEWER AND VENT PIPING IN FIELD(TYP)

(COLD WATER PIPING, SEWER AND VENT PIPING)

CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR PLUMBING PIPING

PRIOR TO COLD, SEWER, VENT PIPING INSTALLATION.

PLUMBING PIPING PLANS AND NOTES

PREVENTER ASSEMBLY WITH NEW

REPLACE EXISTING BACK-FLOW

REDUCING VALVE WITH NEW

REPLACE EXISTING PRESURE

MAIN PIPE TO BE REMAINED

EXISTING 50mm SEWER

BLDG NO. 261

REPAIR TRANSIENT LIVING QUARTER,

M-11

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

MECHANICAL

INDICATING BUTTERFLY

OS & Y

KEY OPERATED

LEGEND & ABBREVIATION

SP MAIN SUPPLY SPRINKLER

UPRIGHT SPRINKLER(K=5.6)

CUTTING POINT

CAP

NON-RISING STEM

TAMPER DETECTION SWITCH

CHECK

WALL MOUNTED TEST HEADER

CONNECTION, TOP

ELBOW, 90

ELBOW, TURNED UP

ELBOW, TURNED DOWN

TEE

TEE, OUTLET UP

TEE, OUTLET DOWN

CONNECTION, BOTTOM

RISER

GATE, NORMALLY CLOSED

GLOBE

DIAPHRAGM

GATE

GATE, NORMALLY OPEN

SWING GATE CHECK

TYPICALTYP.

NO

EXST EXISTING

ABBREVIATIONS

MAX MAXIMUM

MIN MINIMUM

DRAIN PIPED NUMBER

DRAWINGDWG

CONN

CONT

CONNECTION

RM ROOM

W/ WITH

W/O WITHOUT

SCH SCHEDULE

ALARM CHECK VALVE

FIRE DEPARTMENT CONNECTION

(2-WAY SHOWN)

AN APPLIANCE WITHIN THE ENCLOSURE AND DEAD ENDS IN THE ENCLOSURE.

OR DUCT SHALL PENETRATE ANY STAIR OR EXIT PASSAGEWAY ENCLOSURE UNLESS IT SERVES

8. ALL PIPING, SANITARY, VENT, WASTE, PLUMBING, OTHER PIPING, POWER OR CONTROL CIRCUTS,

3. PROVIDE EARTHQUAKE PROTECTION (SWAY BRACING), END OF BRANCH LINE AND SEISMIC

BRACING CALCULATION IN ACCORDANCE WITH NFPA 13 REQUIREMENTS; SPRINKLERS

WITH O-RINGS ARE NOT PERMITTED.

4. FIRE PROTECTION PLANS SHOWN ARE USED FOR COST ESTIMATE PURPOSE ONLY.

5. CONTRACTOR SHALL SUBMIT HYDRAULIC CALCULATIONS AS REQUIRED BY NFPA 13 CHAPTER

22-"PLANS AND CALCULATIONS" PRIOR TO SPRINKLER PIPING INSTALLATION. THE

CONTRACTOR SHALL CONFORM TO THE SYMBOLS INDICATED IN NFPA 170 TO DEVELOP THE

AS-BUILT DRAWINGS FOR THIS PROJECT.

6. PROVIDE MINIMUM 1M X 2M SPACE FOR EACH FIRE SPRINKLER RISER FOR INSTALLATION

AND MAINTENANCE. TEST DRAINS ARE NOT TO BE TERMINATED AT WALL SINKS OR FLOOR

DRAINS, BUT MUST TERMINATE TO THE BUILDING EXTERIOR. SPRINKLER RISERS SHALL NOT

7. ALL AUTOMATIC SPRINKLER DRAIN VALVES FOR FIRE DEPARTMENT CONNECTIONS SHALL BE

INSTALLED IN THE HORIZONTAL POSITION.

WATER SUPPLY AND THE SPRINKLER SYSTEM DEMAND.

ENTIRE FACILITY. A MINIMUM 10% SAFETY FACTOR IS REQUIRED BETWEEN THE AVAILABLE

SHOPDRAWINGS. AUTOMATIC SPRINKLER PROTECTION SYSTEM IS REQUIRED TO PROTECT THIS

THE HYDRANT LOCATIONS, FLOW TESTS, AND DATE SHALL BE INDICATED ON THE

ON NFPA 291 REQUIREMENTS AND UTILIZE THIS DATA TO DESIGN THE SPRINKLER SYSTEM.

2. THE CONTRACTOR SHALL CONDUCT WATER SUPPLY HYDRANT TEST FOR THIS PROJECT BASED

LISTED AND FM APPROVED IN ACCORDANCE WITH NFPA 13 AND THE PROJECT SPECIFICATION.

CEILING PANELS, LIGHTING FIXTURES, AND HVAC AIR DEVICES. ALL EQUIPMENT SHALL BE UL

EQUIPMENT LISTINGS. CONTRACTOR SHALL COORDINATE SPRINKLER HEADS LOCATIONS WITH,

SHALL BE IN ACCORDANCE WITH APPLICABLE CODES, MANUFACTURER'S RECOMMENDATIONS, AND

INSTALLATION. THE EQUIPMENT SHOWN ARE SUGGESTED LOCATIONS HOWEVER FINAL LAYOUT

NFPA 13 AND SPECIFICATION REQUIREMENTS AND SUBMIT FOR APPROVAL PRIOR TO

CONTRACTOR SHALL SUBMIT A COMPLETE FIRE SPRINKLER SYSTEM SHOPDRAWINGS BASED ON

PERFORMANCE BASED WHICH MEANS CONCEPTUAL REQUIREMENT ONLY. THE SPRINKLER

TO FULLY PROTECT THIS FACILITY. THE FIRE SPRINKLER SYSTEM SHOWN THESE DRAWING IS

1. THE CONTRACTOR SHALL PROVIDE AND INSTALL AN AUTOMATIC WET PIPE SPRINKLER SYSTEM

AUTOMATIC FIRE SUPPRESSION(S) GENERAL NOTES:

INDEX OF DRAWING, LEGEND &

SUPPRESSION GENERAL NOTES

ABBREVIATION AND AUTOMATIC FIRE

BLDG NO. 261

REPAIR TRANSIENT LIVING QUARTER,

M-12

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

MECHANICAL

UPRIGHT TYPE SPRINKLER HEAD

SCALE : 1: 50M12

1ST FLOOR FIRE PROTECTION PIPING PLAN

1ST FLOOR FIRE PROTECTION PIPING PLAN

1.

NOTES:

2.

CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR H-SHAPE TO SUPPORTED

SPRINKLER PIPING.

THE H-SHAPE SHALL BE INSTALLED RIGHT ABOVE THE SPRINKLER PIPING.

BLDG NO. 261

REPAIR TRANSIENT LIVING QUARTER,

WARRIOR BASECHU, HC

107387

150 150 150

UPRIGHT TYPE SPRINKLER HEAD

15mm QUICK RESPONSE

UPRIGHT TYPE SPRINKLER HEAD

20mm QUICK RESPONSE

SEE

T

S P (W

M15-

SEE

M15-

SEE

M14-

FEB FEB

ROOM

MECH

BEDROOM

BEDROOM

100 100

100100100100100 100

M-13

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

MECHANICAL

SCALE : 1: 50M13

2ND FLOOR FIRE PROTECTION PIPING PLAN

2ND FLOOR FIRE PROTECTION PIPING PLAN

BLDG NO. 261

REPAIR TRANSIENT LIVING QUARTER,

WARRIOR BASECHU, HC

107387

UPRIGHT TYPE SPRINKLER HEAD

15mm QUICK RESPONSE

SP

(W

T

FEBFEB

BEDROOM

BEDROOM

25 3

100 100

M-14

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

MECHANICAL

(5.6)

115K-FACTOR OF

SPRINKLER NOZZLE

MIN. 2.4 M (8 FT)

MAX. 4.6 M (15 FT)

MECH ROOMBED ROOM

OCCUPANCY

HC-2 HAZARD

ORDINARY TEMPERATURE RATING

(57°C-77°C / 135°F-170°F)

OCCUPANCY

HC-1 HAZARD

60 MIN.

140 SM (1500 SF)

950 LPM (250 GPM)

QUICK RESPONSE

4.1 LPM/SM (0.10 GPM/SF)

WET SPRINKLER

INTERMEDIATE TEMPERATURE RATING

(79°C-107°C / 175°F-220°F)

60 MIN.

MIN. 1.8 M (6 FT)

230 SM (2500 SF)

MAX. 4.6 M (15 FT)

950 LPM (250 GPM)

12.07 SM (130 SF)

QUICK RESPONSE

8.2 LPM/SM (0.20 GPM/SF)

WET SPRINKLER

- RESIDUAL FLOW : 3112 LPM (822 GPM)

- WATER FLOW TEST DATE : MAR. 11. 2016

- RESIDUAL PRESSURE : 2.28 BAR (33 PSI)

WATER SUPPLY INFORMATION*

APPLICATION AREA

DESIGN AREA

HOSE STREAM

DURATION OF SUPPLY

DESIGN DENSITY

FIRE PROTECTION REQUIREMENTS

HAZARD

DESCRIPTION

SPRINKLER TEMPERATURE

RATING*

MAX. & MIN. SPACE OF

BETWEEN SPRINKLERS

MAX. COVERAGE PER

SPRINKLER TYPE

SPRINKLER

TYPE OF SYSTEM

(8.0)

- STATIC PRESSURE : 2.62 BAR (38 PSI)

THIS DWG.

KEY PLAN

REFER TO PARA 4-2.3.1, UFC 3-600-01(1. MAR. 2013, CHANGE 3)**

20.90 SM (225 SF)

N.O

N.O

N .C

N .O

BACKFLOW PREVENTER

ALARM CHECK VALVE

HOSE HEADER CONNECTION

FIRE DEPARTMENT CONNECTION

OS&Y GATE VALVE

CHECK VALVE

MECH

N.O.N.O.

TEST HOSE HEADER

FIRE DEPARTMENT CONNECTION

SPARE SPRINKLER HEAD CABINET

BACKFLOW PREVENTER

100mm CHECK VALVE

100mm GATE VALVE

(WITH TAMPER SWITCH)

(WITH TAMPER SWITCH)

SCALE : 1: 50M14

MECH ROOM FIRE PROTECTION PIPING PARTIAL PLAN

- M14

MECH ROOM FIRE PROTECTION PIPING ISOMETRIC DIAGRAM

NOT TO SCALE

MECH ROOM FIRE PROTECTION PIPING

PARTIAL PLAN & ISOMETRIC DIAGRAM

AND FIRE PROTECTION REQUIREMENTS

FOR CONT.

SEE CIVIL DWG

BLDG NO. 261

REPAIR TRANSIENT LIVING QUARTER,

WARRIOR BASECHU, HC

107387

ALARM CHECK VALVE

GATE VALVE

M-15

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

MECHANICAL

DETAILS-1

BLDG NO. 261

REPAIR TRANSIENT LIVING QUARTER,

WARRIOR BASECHU, HC

107387

TEST HEADER FOR BACKFLOW

PREVENTER FLOW TEST

PRESSURE GAUGE(2-REQUIRED)

DESCRIPTION

WATER MOTOR ALARM GONG

TAMPER SWITCH

MAIN DRAIN VALVE

RETARDING CHAMBER

OS&Y GATE VALVE

PRESSURE SWITCH

FIRE DEPARTMENT CONNECTION

W/TAMPER SWITCH

LOCAL ALARM SHUTOFF VALVE

AUTO BALL DRIP VALVE

WATER MOTOR ALARM DRAIN

CHECK VALVE

DOUBLE CHECK TYPE BACKFLOW

PREVENTER

15 STRAINER

ITEM

MAIN DRAIN5

PRESSURE RELIEF VALVE

N.O.

6 17

N.O.

N .O

MAX.

610MM

PIPE SUPPORT

MAX.

610MM

TO SPRINKLER MAIN

GL.

FL.

TO DRAIN

4-WAY BRACING

PER NFPA 13

N .O

FLEXIBLE COUPLING

4N .C

MIN.

300MM

AG

UG

S A

M E

S

F .D .C m m m m (M

IM

.4

M A

X .1

S A

IN

D R

A

IN

(M A

X m m

S A

A

IN

S A

A

IN

ALARM CHECK VALVE

PIPE SLEEVE

SEALANT

NOT TO SCALEM15

MAIN RISER DETAIL

PIPE HANGER

BACK-FLOW PREVENTER

REDUCED PRESSURE

STRAINER

(TYP OF 3)

GATE VALVE

GLOBE VALVE

UNION (TYP)

CW TO SYSTEM

PET COCK (TYP OF 2)

REDUCING TEE (TYP)

REDUCER

(TYP OF 2)

GAUGE

PRESSURE

VALVE

REDUCING

PRESSURE

(TYP OF 2)

TAPPING

GAUGE

M-16

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

MECHANICAL

NOT TO SCALE

BACKFLOW PREVENTER & PRESSURE REDUCING STATION

M16 - NOT TO SCALEM16

ACTUAL EQUIPMENT SIZE6" 6"

CONC. PAD DETAIL

EXST CONC FLOOR

1/ 2" THK EXPANSION JOINT ( TYP )

CROSS WAY ( TOP & BOTTOM )

#4 STL BAR @ 10" OC

CONC PAD

"B" "B"

S E C T I O N "B" - "B"

P L A N

A C

T U

A L

E

Q U

IP

M E

N T

S

IZ

E

ACTUAL EQUIPMENT SIZE

6"

6"

6" 6"

EQUIPMENT UNIT

TEE DRAINGE PATTERN

AS REQ'D

PIPE SLEEVE

NOTE : WATER COOLER SHELL BE STATIONARY

WATER COOLER

ELECTRIC

BUBBLER

P-TRAP

- NOT TO SCALEM16

3 ELECTRIC WATER COOLER

DETAILS-2

BLDG NO. 261

REPAIR TRANSIENT LIVING QUARTER,

Bldg# S-261,WB(Final)-M1
Bldg# S-261,WB(Final)-M2
Bldg# S-261,WB(Final)-M3
Bldg# S-261,WB(Final)-M4
Bldg# S-261,WB(Final)-M5
Bldg# S-261,WB(Final)-M6
Bldg# S-261,WB(Final)-M7
Bldg# S-261,WB(Final)-M8
Bldg# S-261,WB(Final)-M9
Bldg# S-261,WB(Final)-M10
Bldg# S-261,WB(Final)-M11
Bldg# S-261,WB(Final)-M12
Bldg# S-261,WB(Final)-M13
Bldg# S-261,WB(Final)-M14
Bldg# S-261,WB(Final)-M15
Bldg# S-261,WB(Final)-M16