This document contains questions and answers regarding Amendment #0004 to repair the generator at Building #73 at Fort Leavenworth, Kansas. The opportunity involves installing new louvers on the generator enclosure measuring 114 inches wide and 82 inches high. The louvers must be ducted to intake for the generator. The enclosure wall is 2 inches thick. Pictures are provided showing the unit heater and natural gas filter system specifications. No further details are provided on the products or services required for the opportunity.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
W91QF4-23-Q-0054
RSC Generator, Bldg. #73, FORT LEAVENWORTH, KANSAS
Questions & Answers
Q1. Question: Do you have the Unit Heater information?
A1. Answer: Please see pictures below.
Q2. Question: What size of Louvers and the dimensions?
A2. Answer: The opening in the Generator Enclosure is 114” wide, 82” high.
Q3. Question: Do the Lovers need to be ducted to the intake/exhaust of the generator?
A3. Answer: Intake.
Q4. Question: What type of wall are they cutting the Louvers into?
A4. Answer: The Enclosure wall is 2 ¾” Thick
Q5. Question: Are there Specs on the Natural Gas filter system?
A5. Answer: Please see pictures below.