This document contains questions and answers regarding a federal contract opportunity for a clean room project. The U.S. Army Engineer Research and Development Center is seeking a contractor to provide materials, equipment, and installation services to create a modular cleanroom at its Construction Engineering Research Laboratory facility in Champaign, Illinois. The cleanroom must meet ISO 5 standards for particle counts and have HEPA filtration, temperature and humidity control, and specialized sealed lighting fixtures. Required equipment includes chemical storage cabinets, benches with hoods, and eyewash/safety systems. Interested offerors must attend an optional site visit and submit responses by March 16, 2020. The acquisition is set aside for small businesses.

View the file

Other files

File Type Posted
RFQ(R).pdf PDF
B08.03 Clean Room Q&A.DOCX DOCX document
A02.12 Cleanroom layout v5.pptx PPTX presentation
RFQ.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Questions & Answers

Q: Can we use Al. wall panels with ESD compatible coating instead of Fiber Reinforced Plastic as described in tender?

A: No, Fiber Reinforced Plastic is a firm requirement

Q: Are there building drawings that can be provided? Specifically interested in 1) Plan View of area, 2) Cross View showing heights from building slab to overhead steel or obstructions above?

A: There is a layout document posted with the solicitation already. This is the only site related document that can be shared publically.

Q: Will you please share RFI Answers to questions that have been submitted on the project?

A: That information was posted in the prior Q&A

Q: Should we plan for the Cleanroom HVAC to be separate and stand-alone from the Building, or is there Chilled Water and Plant Steam to tie into?

A: No, the clean room will not be a stand-alone building. Yes, there is Chilled Water and a Plant Steam to tie into

Q: Classification Requirements (FS209E, EU, ISO, Other):

A: ISO 5

Q: Is the Shell or Host Building Existing or New Construction?

A: It is an existing building

Q: Is any Demolition Required, if so what and by whom?

A: No

Q: Describe the Shell or Host Building (Stories, Warehouse, etc.):

A: Warehouse in design

Q: What is the construction of the Shell or Host Building Walls?

A: Concrete block

Q: What is the construction of the Shell or Host Building Floors?

A: Concrete

Q: What is the location of the Cleanroom Area within the Shell or Host Building?

A: Centrally Located

Q: Are any of the Cleanroom Walls adjacent to exterior building walls-exposed to outdoors (if so provide sketch)?

A: No

Q: Can the Cleanroom Ceiling be supported from the existing Building Steelwork?

A: No

Q: Is the Cleanroom Project located in a Seismic Zone (if so please indicate)?

A: No

Q: Do any of the existing Building Columns interfere with the cleanroom layout (if so please provide sketch)?

A: No

Q: Does an Equipment Mezzanine exist (if not, is one required)?

A: No

Q: Is a new Independent Self Supported Steel Structure required for the cleanroom (if so, by whom)?

A: No

Q: What is the intended design location of the Cleanroom HVAC Equipment?

A: HVAC unit exterior to the building. Chilled water is available and preferred

Q: What is the Source and year-round Conditions of the Make-Up Air (MUA) (Outside or Inside)?

A: MUA will be supplied from inside air maintained at 68 F and ~50% humidity.

Q: What is the year-round Ambient Temperature and Humidity Conditions adjacent to and above the cleanroom?

A: 68 F and ~50% humidity; this is the requirement for the interior of the clean room

Q: Are any of the cleanroom areas classified as Bio-Hazardous (if so, please describe)?

A: No

Q: What is the HVAC Cooling Method (Chilled Water, Water Cooled DX, Air Cooled DX)?

A: Chilled Water is available

Q: Will the Cleanroom HVAC Controls be connected to a building management system (BMS) (if so, describe and by whom)?

A: The clean room must have its own HVAC.

Q: Will the Cleanroom Area require a Sprinkler System?

A: No

Q: Does a Sprinkler Main exist (if not, then it will be provided by whom)?

A: Yes – one is located above where the cleanroom will be installed

Q: Will the area above the Cleanroom Ceiling require sprinklers?

A: Currently sprinklers are already available.

Q: Will Smoke and Fire Alarms be required (if so, by whom)?

A: Yes

Q: What is the required Cleanroom HEPA/ULPA Filter ratings?

A: Filter system that can maintain ISO 5

Q: Describe the required Cleanroom Lights (Tear Drop, Flow-Thru Troffers, Lay-In, Top-Access, etc.):

A: Cleanroom lighting must consist of sealed fixtures, with the standard 70 foot candles of illumination. These specialized fixtures are designed for wash-down procedures and to prevent the exfiltration of air. The lighting in the photolithography room must be yellow-tinted to prevent unwanted exposure of photoresist to light of shorter wavelengths.

Q: What Light Ballasts are required?

A: Please see above answer

Q: Are any special type of light fixture required?

A: Please see above answer

Q: Is other than 1P-120V required for the Cleanroom Lighting?

A: No Q: Is other than 60HZ require?

A: No

Q: If not white light, describe the color and wave length:

A: Yellow-tinted light to prevent unwanted exposure of photoresist.

Q: Are colored lamps or lamp shields preferred?

A: Yes

Q: Light levels will be measured at 30" AFF unless otherwise specified.

A: 70 foot candles of illumination

Q: Are any 3P Outlets required in the cleanroom (if so, by whom)?

A: Need one 208 V receptacle

Q: What type of Door Interlocks will be used for the Cleanroom Doors (Traffic Lights, Magnetics, Shoot Bolts), please provide Interlocking sequence?

A: Cleanroom doors must have good performance at outside face, flat, high structural strength, corrosion resistance, no dust, easy to clean.

Q: What type of Cleanroom Telephones and/or Intercoms are required (provide type, location and quantity)?

A: Government-issued phone will be installed and used.

Q: What is the Type and Quantity of Process Exhaust (Acid, Solvent, General)?

A: Acid/Base, Solvents (acetone, methanol, photoresist, isopropanol)

Q: What chemicals and/or gasses are used within the cleanroom (Type, Concentration, Amount, Container)?

A: Developers from the bottles for SU-8 and AZ photoresist, SUMA from the bottle cleaning solution, solvents, Nitrogen, Argon, and Oxygen.

Q: Please indicate the required level of Certification:

A: ISO 5

Q: Particle Counts:

A: >100,000 particles (0.1um) per sq meter

Q: HEPA Filter Integrity Test:

A: Yes

Q: Temperature:

A: 68 F +- 2 F

Q: Humidity:

A: 50% +- 10% relative humidity

Q: Light:

A: Cleanroom lighting must consist of sealed fixtures, with the standard 70 foot candles of illumination. These specialized fixtures are designed for wash-down procedures and to prevent the exfiltration of air. The lighting in the photolithography room must be yellow-tinted to prevent unwanted exposure of photoresist to light of shorter wavelengths.

Q: Is Third Party Testing Required (if so by whom and for which tests)?

A: No

Q: Who is providing and Validation Services (what services and by whom)?

A: Vendor

Q: Are the Cleanroom Installers to be Union members?

A: Davis Bacon Act terms and conditions are not included in this award as it is not considered construction

Q: Are there any Bonding requirements?

A: Davis Bacon Act terms and conditions are not included in this award as it is not considered construction

Q: Are any Permits or Fees required (if so, by whom)?

A: See prior Q&A regarding permitting questions

Q: Is any Ancillary Cleanroom Equipment to be included (if so, what and by whom)?

A: Solvent bench hood with bench, Acid/base bench with hood, stainless steel benches, one stainless steel bench with wheels, eye wash/safety shower systems, corrosive chemical storage cabinet, storage cabinet, storage shelving.

Q: Is there an Architect Firm already involved with this cleanroom project (if so, who is the contact)?

A: No

Q: Is there an Engineering Firm already involved with this cleanroom project (if so, who is the contact)?

A: No

Q: Is there a Cleanroom Consulting Firm already involved with this cleanroom project (if so, who is the contact)?

A: No

Q: Is there a Validation Consulting Firm already involved with this cleanroom project (if so, who is the contact)?

A: No

Q: Is there a General Contracting Firm already involved with this cleanroom project (if so, who is the contact)?

A: No

Q: Is there a Mechanical Contracting Firm already involved with this cleanroom project (if so, who is the contact)?

A: No

Q: Is there an Electrical Contracting Firm already involved with this cleanroom project (if so, who is the contact)?

A: No

Q: Is there a High Purity Process Contracting Firm already involved with this cleanroom project (if so, who is the contact)?

A: No