W912QR25RA052_Specs_Vol2-0000.pdf

PDF 34 MB Posted

Attached to
Construction and Repair of Substation A, JMTC, Rock Island, IL
Solicitation number
W912QR25RA052
Issued by

About this file

This document is a detailed specification section (Section 26 20 00) for Interior Distribution System electrical work. The specification covers the technical requirements for electrical distribution system components, including conduits, wiring, cables, panels, switches, receptacles, and grounding equipment for a federal construction project at Rock Island Arsenal, Illinois.

Key technical requirements include using copper conductors with specific insulation types, color coding standards, and performance specifications for electrical components. The specification mandates that all materials must be listed by Underwriters Laboratories (UL), comply with National Electrical Code (NFPA 70), and meet specific standards for installation, testing, and quality control. The document provides comprehensive guidelines for selecting, installing, and testing electrical distribution system equipment, with detailed requirements for conductor types, wire management, grounding methods, and equipment installation practices. Specific attention is given to safety, reliability, and proper electrical system configuration to ensure optimal performance and compliance with federal electrical standards.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Solicitation For

JTMC – SUBSTATION A REPAIR

ROCK ISLAND ARSENAL, IL

P2: 518820

Design-Bid-Build

Specifications - Vol 2 of 2 (Div 26-40) Certified Final Design

08 August 2025

W912QR25RA052

RRS-A: 200A Disposition: Maintain for 15 yrs after construction.

W912QR25RA052_Specs_Vol2-0000

P2 # 518820 JMTC Substation A Repair

Rock Island Arsenal, IL

PROJECT SPECIFICATIONS

Project Lead, Robert Winkler P.E.

Sections covered by this seal

00 80 00.00 06

01 10 00

01 11 00

01 14 00

01 32 01.00 06

01 33 00

01 35 26.00 06

01 42 00

01 45 00.15 10

01 45 04.10 06

01 45 35

01 50 00

01 57 19.00 06

01 74 19

01 78 23

02 41 00

Architectural, Jennifer Rinde

Olson

Sections covered by this seal

06 10 00

07 21 13

07 27 10

07 27 19.01

07 27 26

07 41 63

07 42 63

07 60 00

07 92 00

08 11 13

08 71 00

08 81 00

09 29 00

09 90 00

Structural, Nathan J. Pierson, P.E.

Sections covered by this seal

03 30 00

03 42 13.00 10

05 50 20

05 05 23.16

05 40 00

05 50 15

05 52 00

13 48 73

Electrical, Nathan C. Veen, P.E.

Sections covered by this seal

26 05 48

26 05 73

26 08 00

26 12 19

26 13 13

26 20 00

26 27 13.10 30

26 33 53

26 41 00

26 51 00

26 56 00

33 71 02

081-007658

PIERSON

NATHAN J.

S

TATE OFILLIN

OI

S

L

IC

E N S E

D

STRUCTURAL

EN

G

IN

E E

R

P2 #518820 JMTC Substation A Repair

PROJECT TABLE OF CONTENTS Page 1

Certified Final Submittal

PROJECT TABLE OF CONTENTS

DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS

00 10 00 PRICE BREAKOUT SCHEDULE

00 80 00.00 06 CHG 1: 06/23 SPECIAL PROVISIONS

DIVISION 01 - GENERAL REQUIREMENTS

01 11 00 SUMMARY OF WORK

01 14 00 CHG 3: 08/24 WORK RESTRICTIONS

01 32 01.00 06 PROJECT SCHEDULE

01 33 00 CHG 4: 02/21 SUBMITTAL PROCEDURES

01 35 26.00 06 GOVERNMENT SAFETY REQUIREMENTS

01 42 00 SOURCES FOR REFERENCE PUBLICATIONS

01 45 00.15 10 11/23 RESIDENT MANAGEMENT SYSTEM CONTRACTOR

MODE(RMS CM)

01 45 04.10 06 CONTRACTOR QUALITY CONTROL

01 45 35 11/20 SPECIAL INSPECTIONS

01 50 00 CHG 2: 08/24 TEMPORARY CONSTRUCTION FACILITIES AND

CONTROLS

01 57 19.00 06 04/20 TEMPORARY ENVIRONMENTAL CONTROLS AND

PERMITS

01 74 19 CHG 3: 11/21 CONSTRUCTION WASTE MANAGEMENT AND

DISPOSAL

01 78 23 05/23 OPERATION AND MAINTENANCE DATA

01 91 00.15 10 CHG 2: 11/23 POWER SYSTEMS COMMISSIONING

01 91 00.15 CHG 2: 11/23 COMMISSIONING

01 91 19 05/23 BUILDING ENCLOSURE COMMISSIONING

DIVISION 02 - EXISTING CONDITIONS

02 41 00 08/22 DEMOLITION

DIVISION 03 - CONCRETE

03 30 00 CHG 8: 05/24 CAST-IN-PLACE CONCRETE

03 42 13.00 10 PLANT-PRECAST CONCRETE PRODUCTS FOR

BELOW GRADE CONSTRUCTION

DIVISION 05 - METALS

05 05 20 05/22 POST-INSTALLED CONCRETE AND MASONRY

ANCHORS

05 05 23.16 08/18 STRUCTURAL WELDING

05 40 00 CHG 1: 08/18 COLD-FORMED METAL FRAMING

05 50 15 CIVIL WORKS FABRICATIONS

05 52 00 08/23 METAL RAILINGS

PROJECT TABLE OF CONTENTS Page 2

Certified Final Submittal

DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES

06 10 00 CHG 2: 11/18 ROUGH CARPENTRY

DIVISION 07 - THERMAL AND MOISTURE PROTECTION

07 21 13 08/23 BOARD AND BLOCK INSULATION

07 27 10 08/23 BUILDING AIR BARRIER SYSTEM

07 27 19.01 CHG 1: 08/24 SELF-ADHERING AIR BARRIERS

07 27 26 08/23 FLUID-APPLIED MEMBRANE AIR BARRIERS

07 41 63 11/16 FABRICATED ROOF PANEL ASSEMBLIES

07 42 63 CHG 4: 08/20 FABRICATED WALL PANEL ASSEMBLIES

07 60 00 08/23 FLASHING AND SHEET METAL

07 92 00 08/23 JOINT SEALANTS

DIVISION 08 - OPENINGS

08 11 13 08/20 STEEL DOORS AND FRAMES

08 71 00 CHG 4: 02/22 DOOR HARDWARE

08 81 00 GLAZING

DIVISION 09 - FINISHES

09 29 00 08/24 GYPSUM BOARD

09 90 00 02/21 PAINTS AND COATINGS

DIVISION 13 - SPECIAL CONSTRUCTION

13 48 73 05/22 SEISMIC CONTROL FOR MISCELLANEOUS

EQUIPMENT

DIVISION 22 - PLUMBING

22 00 00 05/24 PLUMBING, GENERAL PURPOSE

DIVISION 23 - HEATING, VENTILATING, AND AIR CONDITIONING (HVAC)

23 03 00.00 20 CHG 3: 08/18 BASIC MECHANICAL MATERIALS AND

METHODS

23 05 48.19 CHG 2: 08/20 SEISMIC BRACING FOR HVAC

23 05 93 11/15 TESTING, ADJUSTING, AND BALANCING FOR

HVAC

23 08 00 CHG 1: 08/24 COMMISSIONING OF MECHANICAL AND

PLUMBING SYSTEMS

23 35 19.00 20 CHG 2: 08/18 INDUSTRIAL VENTILATION AND EXHAUST

23 81 00 05/24 DECENTRALIZED UNITARY HVAC EQUIPMENT

PROJECT TABLE OF CONTENTS Page 3

Certified Final Submittal

DIVISION 25 - INTEGRATED AUTOMATION

25 05 11.01 CYBERSECURITY FOR FIRE ALARM CONTROL

SYSTEMS

25 05 11.02 CYBERSECURITY FOR SMART METER

CONTROL SYSTEMS

DIVISION 26 - ELECTRICAL

26 05 48 11/23 SEISMIC PROTECTION FOR ELECTRICAL

EQUIPMENT

26 05 73 08/23 POWER SYSTEM STUDIES

26 08 00 11/22 APPARATUS INSPECTION AND TESTING

26 12 19 05/24 PAD-MOUNTED, LIQUID-FILLED,

MEDIUM-VOLTAGE TRANSFORMERS

26 13 13 11/21 METAL-CLAD SWITCHGEAR

26 20 00 08/23 INTERIOR DISTRIBUTION SYSTEM

26 27 13.10 30 CHG 2: 08/18 ELECTRIC METERS

26 33 53 05/19 STATIC UNINTERRUPTIBLE POWER SUPPLY

(UPS)

26 41 00 08/23 LIGHTNING PROTECTION SYSTEM

26 51 00 05/20 CHG 2: 11/21 INTERIOR LIGHTING

26 56 00 08/21 EXTERIOR LIGHTING

DIVISION 28 - ELECTRONIC SAFETY AND SECURITY

28 31 70 08/20 INTERIOR FIRE ALARM SYSTEM, ADDRESSABLE

DIVISION 31 - EARTHWORK

31 00 00.00 06 05/24 EARTHWORK

31 11 00 11/18 CLEARING AND GRUBBING

DIVISION 32 - EXTERIOR IMPROVEMENTS

32 15 00 05/17 AGGREGATE SURFACING

DIVISION 33 - UTILITIES

33 71 02 08/21 UNDERGROUND ELECTRICAL DISTRIBUTION

33 82 00 04/06 TELECOMMUNICATIONS OUTSIDE PLANT(OSP)

DIVISION 34 - TRANSPORTATION

34 11 00 04/08 RAILROAD TRACK AND ACCESSORIES

DIVISION 40 - PROCESS INTERCONNECTIONS

40 60 00 05/20 PROCESS CONTROL

PROJECT TABLE OF CONTENTS Page 4 Certified Final Submittal

Appendix A – GEOTECHNICAL REPORT

Appendix B – COAL FILE SAMPLE LOCATIONS

Appendix C – HAZMAT SURVEY

Appendix D - Hydrographs

-- End of Project Table of Contents –

SECTION 26 20 00

INTERIOR DISTRIBUTION SYSTEM

08/23

PART 1 GENERAL

1.1 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.

ASTM INTERNATIONAL (ASTM)

ASTM B1 (2013) Standard Specification for Hard-Drawn Copper Wire

ASTM B8 (2023) Standard Specification for Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard, or Soft

ASTM D709 (2017) Standard Specification for Laminated Thermosetting Materials

INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)

IEEE 81 (2012) Guide for Measuring Earth Resistivity, Ground Impedance, and Earth Surface Potentials of a Ground System

IEEE Stds Dictionary (2009) IEEE Standards Dictionary: Glossary of Terms & Definitions

INTERNATIONAL ELECTRICAL TESTING ASSOCIATION (NETA)

NETA ATS (2021) Standard for Acceptance Testing Specifications for Electrical Power Equipment and Systems

NATIONAL ELECTRICAL CONTRACTORS ASSOCIATION (NECA)

NECA NEIS 1 (2015) Standard for Good Workmanship in Electrical Construction

NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)

ANSI C80.1 (2020) American National Standard for Electrical Rigid Steel Conduit (ERSC)

ANSI C80.3 (2020) American National Standard for Electrical Metallic Tubing (EMT)

ANSI C80.5 (2020) American National Standard for Electrical Rigid Aluminum Conduit

NEMA 250 (2020) Enclosures for Electrical Equipment (1000 Volts Maximum)

SECTION 26 20 00 Page 1

CERTIFIED FINAL DESIGN SUBMITTAL

NEMA BU 1.1 (2010) General Instructions for Proper Handling, Installation, Operation and Maintenance of Busway Rated 600 V or Less

NEMA FU 1 (2012) Low Voltage Cartridge Fuses

NEMA ICS 1 (2022) Standard for Industrial Control and Systems: General Requirements

NEMA ICS 6 (1993; R 2016) Industrial Control and Systems: Enclosures

NEMA KS 1 (2013) Enclosed and Miscellaneous Distribution Equipment Switches (600 V Maximum)

NEMA RN 1 (2005; R 2013) Polyvinyl-Chloride (PVC) Externally Coated Galvanized Rigid Steel Conduit and Intermediate Metal Conduit

NEMA ST 20 (2014) Dry-Type Transformers for General Applications

NEMA TC 2 (2020) Standard for Electrical Polyvinyl Chloride (PVC) Conduit

NEMA TC 3 (2021) Polyvinyl Chloride (PVC) Fittings for Use With Rigid PVC Conduit and Tubing

NEMA VE 2 (2018; ERTA 1-2 2018) Cable Tray Installation Guidelines

NEMA WD 1 (1999; R 2020) Standard for General Color Requirements for Wiring Devices

NEMA WD 6 (2021) Wiring Devices Dimensions Specifications

NEMA Z535.4 (2023) Product Safety Signs and Labels

NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

NFPA 70 (2023; ERTA 7 2023; TIA 23-15) National Electrical Code

NFPA 70E (2024) Standard for Electrical Safety in the Workplace

NFPA 780 (2023) Standard for the Installation of Lightning Protection Systems

TELECOMMUNICATIONS INDUSTRY ASSOCIATION (TIA)

TIA-569 (2019e; Add 1 2022) Telecommunications Pathways and Spaces

TIA-607 (2019d) Generic Telecommunications Bonding and Grounding (Earthing) for Customer

SECTION 26 20 00 Page 2

Premises

U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)

29 CFR 1910.147 The Control of Hazardous Energy (Lock Out/Tag Out)

29 CFR 1910.303 Electrical, General

UNDERWRITERS LABORATORIES (UL)

UL 1 (2005; Reprint Jan 2022) UL Standard for Safety Flexible Metal Conduit

UL 4 (2004; Reprint Mar 2021) UL Standard for Safety Armored Cable

UL 5 (2016; Reprint Jul 2022) UL Standard for Safety Surface Metal Raceways and Fittings

UL 6 (2022) UL Standard for Safety Electrical Rigid Metal Conduit-Steel

UL 6A (2008; Reprint Mar 2021) UL Standard for Safety Electrical Rigid Metal Conduit - Aluminum, Red Brass, and Stainless Steel

UL 20 (2018; Reprint May 2023) UL Standard for Safety General-Use Snap Switches

UL 44 (2018; Reprint May 2021) UL Standard for Safety Thermoset-Insulated Wires and Cables

UL 50 (2024) UL Standard for Safety Enclosures for Electrical Equipment, Non-Environmental Considerations

UL 67 (2018; Reprint Aug 2023) UL Standard for Safety Panelboards

UL 83 (2017; Reprint Mar 2020) UL Standard for Safety Thermoplastic-Insulated Wires and Cables

UL 248-4 (2010; Reprint Apr 2019) Low-Voltage Fuses

- Part 4: Class CC Fuses

UL 248-8 (2011; Reprint Aug 2020) Low-Voltage Fuses

- Part 8: Class J Fuses

UL 248-10 (2011; Reprint Aug 2020) Low-Voltage Fuses

- Part 10: Class L Fuses

UL 248-12 (2011; Reprint Aug 2020) Low Voltage Fuses

- Part 12: Class R Fuses

UL 248-15 (2018) Low-Voltage Fuses - Part 15: Class T Fuses

SECTION 26 20 00 Page 3

UL 360 (2013; Reprint Jan 2024) UL Standard for Safety Liquid-Tight Flexible Metal Conduit

UL 467 (2022) UL Standard for Safety Grounding and Bonding Equipment

UL 486A-486B (2018; Reprint Jul 2023) UL Standard for Safety Wire Connectors

UL 486C (2018; Reprint May 2021) UL Standard for Safety Splicing Wire Connectors

UL 489 (2016; Rev 2019) UL Standard for Safety Molded-Case Circuit Breakers, Molded-Case Switches and Circuit-Breaker Enclosures

UL 498 (2017; Reprint May 2023) UL Standard for Safety Attachment Plugs and Receptacles

UL 510 (2020; Dec 2022) UL Standard for Safety Polyvinyl Chloride, Polyethylene and Rubber Insulating Tape

UL 514A (2013; Reprint Jun 2022) UL Standard for Safety Metallic Outlet Boxes

UL 514B (2012; Reprint Mar 2024) UL Standard for Safety Conduit, Tubing and Cable Fittings

UL 514C (2014; Reprint Feb 2020) UL Standard for Safety Nonmetallic Outlet Boxes, Flush-Device Boxes, and Covers

UL 651 (2011; Reprint May 2022) UL Standard for Safety Schedule 40, 80, Type EB and A Rigid PVC Conduit and Fittings

UL 719 (2015; Reprint Nov 2023) UL Standard for Safety Nonmetallic-Sheathed Cables

UL 797 (2007; Reprint Apr 2023) UL Standard for Safety Electrical Metallic Tubing -- Steel

UL 817 (2015; Reprint May 2023) UL Standard for Safety Cord Sets and Power-Supply Cords

UL 857 (2009; Reprint Apr 2021) UL Standard for Safety Busways

UL 870 (2016; Reprint Nov 2023) UL Standard for Safety Wireways, Auxiliary Gutters, and Associated Fittings

UL 943 (2016; Reprint Sep 2023) UL Standard for Safety Ground-Fault Circuit-Interrupters

UL 1242 (2006; Reprint Apr 2022) UL Standard for Safety Electrical Intermediate Metal Conduit -- Steel

SECTION 26 20 00 Page 4

UL 1449 (2021; Reprint Dec 2022) UL Standard for Safety Surge Protective Devices

UL 1569 (2018) UL Standard for Safety Metal-Clad Cables

UL 1660 (2019; Reprint Jan 2022) Liquid-Tight Flexible Nonmetallic Conduit

UL 1699 (2017; Reprint Feb 2022) UL Standard for Safety Arc-Fault Circuit-Interrupters

UL 4248-1 (2022) UL Standard for Safety Fuseholders

- Part 1: General Requirements

UL 4248-12 (2018; Reprint Feb 2022) UL Standard for Safety Fuseholders - Part 12: Class R

1.2 DEFINITIONS

Unless otherwise specified or indicated, electrical and electronics terms used in these specifications, and on the drawings, are as defined in IEEE Stds Dictionary .

1.3 RELATED REQUIREMENTS

Section 25 05 11.01 CYBERSECURITY FOR FIRE AND MASS NOTIFICATION CONTROL SYSTEMS applies to this section, with the additions and modifications specified herein.

1.4 SUBMITTALS

Government approval is required for submittals with a "G" classification.

Submittals not having a "G" classification are for information only. When used, a code following the "G" classification identifies the office that will review the submittal for the Government. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:

SD-02 Shop Drawings

Panelboards; G, AE

Transformers; G, AE

Busway; G, AE

Cable Trays; G, AE

Wireways; G, AE

Marking Strips Drawings; G, AE

SD-03 Product Data

Receptacles; G, AE

Circuit Breakers; G Switches; G , AE

SECTION 26 20 00 Page 5

Transformers; G, AE

Surge Protective Devices; G, AE

Cable Trays; G, AE

SD-05 Design Data

Cable Tray Design; G, AE

SD-06 Test Reports

600-volt Wiring Test; G, AE

Grounding System Test; G, AE

Transformer Tests; G, AE

Ground-fault Receptacle Test; G, AE

Arc-fault Receptacle Test; G, AE

SD-07 Certificates

Fuses; G

SD-09 Manufacturer's Field Reports

Transformer Factory Tests

SD-10 Operation and Maintenance Data

Electrical Systems, Data Package 5; G, AE

1.5 QUALITY ASSURANCE

1.5.1 Fuses

Submit coordination data as specified in paragraph, FUSES of this section.

1.5.2 Regulatory Requirements

In each of the publications referred to herein, consider the advisory provisions to be mandatory, as though the word, "must" had been substituted for "should" wherever it appears. Interpret references in these publications to the "authority having jurisdiction," or words of similar meaning, to mean the Contracting Officer. Provide equipment, materials, installation, and workmanship in accordance with NFPA 70 unless more stringent requirements are specified or indicated. NECA NEIS 1 shall be considered the minimum standard for workmanship.

1.5.3 Standard Products

Provide materials and equipment that are products of manufacturers regularly engaged in the production of such products which are of equal material, design and workmanship and:

a. Have been in satisfactory commercial or industrial use for 2 years prior to bid opening including applications of equipment and materials

SECTION 26 20 00 Page 6 under similar circumstances and of similar size

b. Have been on sale on the commercial market through advertisements, manufacturers' catalogs, or brochures during the 2-year period

c. Where two or more items of the same class of equipment are required, provide products of a single manufacturer; however, the component parts of the item need not be the products of the same manufacturer unless stated in this section.

1.5.3.1 Alternative Qualifications

Products having less than a 2-year field service record will be acceptable if a certified record of satisfactory field operation for not less than 6000 hours, exclusive of the manufacturers' factory or laboratory tests, is furnished.

1.5.3.2 Material and Equipment Manufacturing Date

Products manufactured more than 3 years prior to date of delivery to site are not acceptable.

1.6 MAINTENANCE

1.6.1 Electrical Systems

Submit operation and maintenance data in accordance with Section 01 78 23, OPERATION AND MAINTENANCE DATA and as specified herein. Submit operation and maintenance manuals for electrical systems that provide basic data relating to the design, operation, and maintenance of the electrical distribution system for the building. Include the following:

a. Single line diagram of the "as-built" building electrical system

b. Schematic diagram of electrical control system(other than HVAC, covered elsewhere)

c. Manufacturers'operating and maintenance manuals on active electrical equipment.

1.7 WARRANTY

Provide equipment items supported by service organizations that are reasonably convenient to the equipment installation in order to render satisfactory service to the equipment on a regular and emergency basis during the warranty period of the contract.

1.8 SEISMIC REQUIREMENTS

Provide seismic details conforming to Section 26 05 48 SEISMIC PROTECTION

FOR ELECTRICAL EQUIPMENT.

PART 2 PRODUCTS

2.1 MATERIALS AND EQUIPMENT

As a minimum, meet requirements of UL, where UL standards are established for those items, and requirements of NFPA 70 for all materials, equipment, and devices.

SECTION 26 20 00 Page 7

2.2 CONDUIT AND FITTINGS

Conform to the following:

2.2.1 Rigid Metallic Conduit

2.2.1.1 Rigid, Threaded Zinc-Coated Steel Conduit

ANSI C80.1 , UL 6 .

2.2.1.2 Rigid Aluminum Conduit

ANSI C80.5 , UL 6A .

2.2.2 Rigid Nonmetallic Conduit

PVC Type EPC-40, and EPC-80 in accordance with NEMA TC 2, UL 651 .

2.2.3 Intermediate Metal Conduit(IMC)

UL 1242 , zinc-coated steel only.

2.2.4 Electrical, Zinc-Coated Steel Metallic Tubing(EMT)

UL 797 , ANSI C80.3 .

2.2.5 Plastic-Coated Rigid Steel and IMC Conduit

NEMA RN 1, Type 40( 40 mils thick).

2.2.6 Flexible Metal Conduit

UL 1 , limited to 6 feet.

2.2.6.1 Liquid-Tight Flexible Metal Conduit, Steel

UL 360 , limited to 6 feet.

2.2.7 Fittings for Metal Conduit, EMT, and Flexible Metal Conduit

UL 514B . Ferrous fittings: cadmium- or zinc-coated in accordance with

UL 514B .

2.2.7.1 Fittings for Rigid Metal Conduit and IMC

Threaded-type. Split couplings unacceptable.

2.2.7.2 Fittings for EMT

Die Cast compression type.

2.2.8 Fittings for Rigid Nonmetallic Conduit

NEMA TC 3 for PVC, and UL 514B .

2.2.9 Liquid-Tight Flexible Nonmetallic Conduit

UL 1660 .

SECTION 26 20 00 Page 8

2.3 SURFACE RACEWAY

2.3.1 Surface Metal Raceway

UL 5 , two-piece painted steel, totally enclosed, snap-cover type. Provide multiple outlet-type raceway with grounding-type receptacle where indicated. Provide receptacles as specified herein, spaced a minimum of one every 18 inches. Wire alternate receptacles on different circuits.

2.4 BUSWAY

NEMA BU 1.1 , UL 857 . Provide the following:

a. Buses: copper

b. Busways: rated 15,000 volts, 3,000 continuous current amperes, three-phase, four-wire, and include integral or internal ground bus

c. Short circuit rating: 40,000 root mean square(rms)symmetrical amperes minimum

d. Busway systems: suitable for use indoors. Fixed support system

e. Enclosures: metallic

f. Hardware: plated or otherwise protected to resist corrosion

g. Joints: one-bolt type with through-bolts, which can be checked for tightness without de-energizing system

h. Maximum hot spot temperature rise at any point in busway at continuous rated load: do not exceed 55 degrees C above maximum ambient temperature of 40 degrees C in any position

i. Internal barriers to prevent movement of superheated gases

j. Coordinate proper voltage phasing of entire bus duct system, for example where busway interfaces with transformers, switchgear, switchboards, motor control centers, and other system components.

2.5 CABLE TRAYS

NEMA VE 2. Provide the following:

Submit cable tray design, including dimensional layout, load and seismic calculations, and fill calculations. Dimensional layout includes cable spacings, cable tray splices, and supports. Fill calculations include an index of cables for each section and identification of the lb/ft, cross sectional area, and insulation voltage class for each cable.

a. Cable trays: form a wireway system, with a nominal6 inch depth. Cable tray is to have a span/load class designation of 20C per NEMA VE 2.

b. Cable trays: constructed of aluminum.

c. Cable trays: include splice and end plates, dropouts, and miscellaneous hardware.

SECTION 26 20 00 Page 9

d. Edges, fittings, and hardware: finished free from burrs and sharp edges.

e. Fittings: ensure not less than load-carrying ability of straight tray sections and have manufacturer's minimum standard radius.

f. Radius of bends: 24 inches.

2.5.1 Ladder-Type Cable Trays

Provide of nominal 12, 18, 24, 30, 36 inch width with maximum rung spacing of 9 inches. Cable tray must be suitable for use as an equipment grounding conductor.

2.6 OUTLET BOXES AND COVERS

UL 514A , cadmium - or zinc-coated, if ferrous metal. UL 514C , if nonmetallic.

2.6.1 Outlet Boxes for Telecommunications System

Provide the following:

a. Standard type 4 inches square by 2 1/8 inches deep.

2.7 CABINETS, JUNCTION BOXES, AND PULL BOXES

UL 50 ; volume greater than 100 cubic inches, NEMA Type 1 enclosure; sheet steel, hot-dip, zinc-coated. Where exposed to wet, damp, or corrosive environments, NEMA Type 3R.

2.8 WIRES AND CABLES

Provide wires and cables in accordance applicable requirements of NFPA 70 and UL for type of insulation, jacket, and conductor specified or indicated. Do not use wires and cables manufactured more than 24 months prior to date of delivery to site.

2.8.1 Conductors

Provide the following:

a. Conductor sizes and capacities shown are based on copper, unless indicated otherwise

b. Conductors No.8 AWG and larger diameter: stranded

c. Conductors No.10 AWG and smaller diameter: solid

d. Conductors for remote control, alarm, and signal circuits, classes 1, 2, and 3: stranded unless specifically indicated otherwise

e. All conductors: copper.

2.8.1.1 Minimum Conductor Sizes

Provide minimum conductor size in accordance with the following:

a. Branch circuits: No. 12 AWG

SECTION 26 20 00 Page 10

b. Class 1 remote-control and signal circuits: No.14 AWG

c. Class 2 low-energy, remote-control and signal circuits: No.16 AWG

d. Class 3 low-energy, remote-control, alarm and signal circuits: No.22

AWG.

2.8.2 Color Coding

Provide color coding for service, feeder, branch, control, and signaling circuit conductors.

2.8.2.1 Ground and Neutral Conductors

Provide color coding of ground and neutral conductors as follows:

a. Grounding conductors: Green

b. Neutral conductors: White

c. Exception, where neutrals of more than one system are installed in same raceway or box, other neutrals color coding: white with a different colored(not green)stripe for each.

2.8.2.2 Ungrounded Conductors

Provide color coding of ungrounded conductors in different voltage systems as follows:

a. 208/120 volt, three-phase

(1) Phase A - black

(2) Phase B - red

(3) Phase C - blue

b. 480/277 volt, three-phase

(1) Phase A - brown

(2) Phase B - orange

(3) Phase C - yellow

c. 120/240 volt, single phase: Black and red

2.8.3 Insulation

Unless specified or indicated otherwise or required by NFPA 70 , provide power and lighting wires rated for 600-volts, Type THWN/THHN conforming to UL 83 or Type XHHW conforming to UL 44 , except that grounding wire may be type TW conforming to UL 83 ; remote-control and signal circuits: Type TW or TF, conforming to UL 83 . Where equipment or devices require 90-degree Centigrade(C)conductors, provide only conductors with 90-degree C insulation or better.

SECTION 26 20 00 Page 11

2.8.4 Bonding Conductors

ASTM B1, solid bare copper wire for sizes No. 8 AWG and smaller diameter;

ASTM B8, Class B, stranded bare copper wire for sizes No.6 AWG and larger diameter.

2.8.4.1 Telecommunications Bonding Backbone(TBB)

Provide a copper conductor TBB in accordance with TIA-607 with No. 6 AWG minimum size, and sized at 2 kcmil per linear foot of conductor length up to a maximum size of 750 kcmil. Provide insulated TBB with insulation as specified in the paragraph INSULATION and meeting the fire ratings of its pathway.

2.8.4.2 Bonding Conductor for Telecommunications

Provide a copper conductor Bonding Conductor for Telecommunications between the telecommunications main grounding busbar(PBB)and the electrical service ground in accordance with TIA-607 . Size the bonding conductor for telecommunications the same as the TBB.

2.8.5 Nonmetallic Sheathed Cable

UL 719 , Type NM or NMC.

2.8.6 Metal-Clad Cable

UL 1569 ; NFPA 70 , Type MC cable.

2.8.7 Armored Cable

UL 4 ; NFPA 70 , Type AC cable.

2.8.8 Cable Tray Cable or Power Limited Tray Cable

UL listed; type TC or PLTC.

2.8.9 Cord Sets and Power-Supply Cords

UL 817 .

2.9 SPLICES AND TERMINATION COMPONENTS

UL 486A-486B for wire connectors and UL 510 for insulating tapes.

Connectors for No.10 AWG and smaller diameter wires: insulated, pressure-type in accordance with UL 486A-486B or UL 486C (twist-on splicing connector). Provide solderless terminal lugs on stranded conductors.

2.10 DEVICE PLATES

Provide the following:

a. UL listed, one-piece device plates for outlets to suit the devices installed

b. For metal outlet boxes, plates on unfinished walls: zinc-coated sheet steel or cast metal having round or beveled edges

c. For nonmetallic boxes and fittings, other suitable plates may be

SECTION 26 20 00 Page 12 provided

d. Plates on finished walls: satin finish stainless steel or brushed-finish aluminum, minimum 0.03 inch thick

e. Screws: machine-type with countersunk heads in color to match finish of plate

f. Sectional type device plates are not be permitted

g. Plates installed in wet locations: gasketed and UL listed for "wet locations."

2.11 SWITCHES

2.11.1 Toggle Switches

NEMA WD 1, UL 20 , single pole, three-way, totally enclosed with bodies of thermoplastic or thermoset plastic and mounting strap with grounding screw. Include the following:

a. Handles: white thermoplastic

b. Wiring terminals: screw-type, side-wired

c. Contacts: silver-cadmium and contact arm - one-piece copper alloy

d. Switches: rated quiet-type ac only, 120/277 volts, with current rating and number of poles indicated.

2.11.2 Switch with Red Pilot Handle

NEMA WD 1. Provide the following:

a. Pilot lights that are integrally constructed as a part of the switch's handle

b. Pilot light color: red and illuminate whenever the switch is closed or "on"

c. Pilot lighted switch: rated 20 amps and 120 volts or 277 volts, as indicated

d. The circuit's neutral conductor to each switch with a pilot light.

2.11.3 Disconnect Switches

NEMA KS 1. Provide heavy duty-type switches where indicated, where switches are rated higher than 240 volts, and for double-throw switches.

Utilize Class R fuseholders and fuses for fused switches, unless indicated otherwise. Provide horsepower rated for switches serving as the motor-disconnect means. Provide switches in NEMA enclosure as indicated per NEMA ICS 6 .

2.12 FUSES

NEMA FU 1. Provide complete set of fuses for each fusible switch.

Coordinate time-current characteristics curves of fuses serving motors or connected in series with circuit breakers for proper operation. Submit

SECTION 26 20 00 Page 13 coordination data for approval. Provide fuses with a voltage rating not less than circuit voltage.

2.12.1 Fuseholders

Provide in accordance with UL 4248-1 .

2.12.2 Cartridge Fuses, Current Limiting Type(Class R)

UL 248-12 , Class. Provide only Class R associated fuseholders in accordance with UL 4248-12 .

2.12.3 Cartridge Fuses, High-Interrupting Capacity, Current Limiting Type (Classes J, L, and CC)

UL 248-8 , UL 248-10 , UL 248-4 , Class J for zero to 600 amperes, Class L for 601 to 6,000 amperes, and Class CC for zero to 30 amperes.

2.12.4 Cartridge Fuses, Current Limiting Type(Class T)

UL 248-15 , Class T for zero to 1,200 amperes, 300 volts; and zero to 800 amperes, 600 volts.

2.13 RECEPTACLES

Provide the following:

a. UL 498 , general purpose specification grade,grounding-type.

Residential grade receptacles are not acceptable

b. Ratings and configurations: as indicated

c. Bodies: white as per NEMA WD 1

d. Face and body: thermoplastic supported on a metal mounting strap

e. Dimensional requirements: per NEMA WD 6

f. Screw-type, side-wired wiring terminals or of the solderless pressure type having suitable conductor-release arrangement

g. Grounding pole connected to mounting strap

h. The receptacle: containing triple-wipe power contacts and double or triple-wipe ground contacts.

2.13.1 Weatherproof Receptacles

Provide receptacles, UL listed for use in "wet locations" with integral GFCI protection. Include cast metal box with gasketed, hinged, lockable and weatherproof while-in-use, die-cast metal/aluminum extra-duty rated hood.

2.13.2 Ground-Fault Circuit Interrupter Receptacles

UL 943 , duplex type for mounting in standard outlet box. Provide device capable of detecting current leak when the current to ground is 6 milliamperes or higher, and tripping per requirements of UL 943 for Class A ground-fault circuit interrupter devices. Provide screw-type, side-wired

SECTION 26 20 00 Page 14 wiring terminals or pre-wired(pigtail)leads.

2.14 PANELBOARDS

Provide panelboards in accordance with the following:

2.14.1 Enclosure

Provide panelboard enclosure in accordance with the following:

a. UL 50

b. Cabinets: painted in accordance with paragraph FIELD APPLIED PAINTING

c. Front edges of cabinets: form-flanged or fitted with structural shapes welded or riveted to the sheet steel, for supporting the panelboard front

d. All cabinets: fabricated such that no part of any surface on the finished cabinet deviates from a true plane by more than 1/8 inch

e. Holes: provided in the back of indoor surface-mounted cabinets, with outside spacers and inside stiffeners, for mounting the cabinets with a 1/2 inch clear space between the back of the cabinet and the wall surface

f. Flush doors: mounted on hinges that expose only the hinge roll to view when the door is closed

g. Each door: fitted with a combined catch and lock latch

h. Keys: two provided with each lock, with all locks keyed alike

i. Finished-head cap screws: provided for mounting the panelboard fronts on the cabinets.

2.14.2 Panelboard Buses

Support bus bars on bases independent of circuit breakers. Design main buses and back pans so that breakers may be changed without machining, drilling, or tapping. Provide isolated neutral bus in each panel for connection of circuit neutral conductors. Provide separate ground bus identified as equipment grounding bus per UL 67 for connecting grounding conductors; bond to steel cabinet.

2.14.3 Circuit Breakers

UL 489 , thermal magnetic-type having a minimum short-circuit current rating equal to the short-circuit current rating of the panelboard in which the circuit breaker will be mounted. Breaker terminals: UL listed as suitable for type of conductor provided. Series rated circuit breakers and plug-in circuit breakers are unacceptable.

2.14.3.1 Multipole Breakers

Provide common trip-type with single operating handle. Design breaker such that overload in one pole automatically causes all poles to open. Maintain phase sequence throughout each panel so that any three adjacent breaker poles are connected to Phases A, B, and C, respectively.

SECTION 26 20 00 Page 15

2.14.3.2 Circuit Breaker With Ground-Fault Circuit Interrupter

UL 943 and NFPA 70 . Provide with auto-monitoring(self-test)and lockout features, "push-to-test" button, visible indication of tripped condition, and ability to detect and trip when current imbalance is 6 milliamperes or higher per requirements of UL 943 for Class A ground-fault circuit interrupter devices.

2.14.3.3 Arc-Fault Circuit Interrupters

UL 489 , UL 1699 and NFPA 70 . Molded case circuit breakers: rated as indicated. Provide with "push-to-test" button.

2.15 TRANSFORMERS

Provide transformers in accordance with the following:

a. NEMA ST 20 , general purpose, dry-type, self-cooled, ventilated

b. Provide transformers in NEMA 1 enclosure

c. Taps for transformers 15 kVA and larger: Two 2.5 percent taps Full Capacity Above Nominal(FCAN)and two 2.5 percent taps Full Capacity Below Nominal(FCBN)

d. Transformer insulation system:

(1) 220 degrees C insulation system for transformers 15 kVA and greater, with temperature rise not exceeding 115 degrees C under full-rated load in maximum ambient of 40 degrees C

(2) 180 degrees C insulation for transformers rated 10 kVA and less, with temperature rise not exceeding 80 degrees C under full-rated load in maximum ambient of 40 degrees C.

2.16 LOCKOUT REQUIREMENTS

Provide circuit breakers, disconnecting means, and other devices that are electrical energy-isolating capable of being locked out for machines and other equipment to prevent unexpected startup or release of stored energy in accordance with 29 CFR 1910.147 , NFPA 70E and 29 CFR 1910.303 . Comply with requirements of Division 23, "Heating, Ventilating, and Air Conditioning(HVAC)for mechanical isolation of machines and other equipment.

2.17 TELECOMMUNICATIONS SYSTEM

Provide system of telecommunications wire-supporting structures(pathway), including: outlet boxes, conduits with pull wires and other accessories for telecommunications outlets and pathway in accordance with TIA-569 and as specified herein.

2.18 GROUNDING AND BONDING EQUIPMENT

2.18.1 Ground Rods

UL 467 . Ground rods: cone pointed copper-clad steel solid copper stainless steel, with minimum diameter of 3/4 inch and minimum length 10 feet.

Sectional type rods may be used for rods 20 feet or longer.

SECTION 26 20 00 Page 16

2.18.2 Ground Bus

Copper ground bus: provided in the electrical equipment rooms as indicated.

2.19 MANUFACTURER'S NAMEPLATE

Provide on each item of equipment a nameplate bearing the manufacturer's name, address, model number, and serial number securely affixed in a conspicuous place; the nameplate of the distributing agent will not be acceptable.

2.20 FIELD FABRICATED NAMEPLATES

Provide field fabricated nameplates in accordance with the following:

a. ASTM D709

b. Provide laminated plastic nameplates for each equipment enclosure, relay, switch, and device; as specified or as indicated on the drawings

c. Each nameplate inscription: identify the function and, when applicable, the position

d. Nameplates: melamine plastic, 0.125 inch thick, white with black center core

e. Surface: matte finish. Corners: square. Accurately align lettering and engrave into the core

f. Minimum size of nameplates: one by 2.5 inches

g. Lettering size and style: a minimum of 0.25 inch high normal block style.

2.21 WARNING SIGNS

Provide warning signs for flash protection in accordance with NFPA 70E and NEMA Z535.4 for switchboards, panelboards, industrial control panels, and motor control centers that are in other than dwelling occupancies and are likely to require examination, adjustment, servicing, or maintenance while energized. Provide field installed signs to warn qualified persons of potential electric arc flash hazards when warning signs are not provided by the manufacturer. Provide marking that is clearly visible to qualified persons before examination, adjustment, servicing, or maintenance of the equipment.

2.22 WIREWAYS

UL 870 . Material: steel epoxy painted 16 gauge for heights and depths up to 6 by 6 inches, and 14 gauge for heights and depths up to 12 by 12 inches.

Provide in length required for the application with hinged-cover NEMA 1 enclosure per NEMA ICS 6 .

2.23 SURGE PROTECTIVE DEVICES

Provide parallel type surge protective devices(SPD)which comply with UL 1449 at panelboards. Provide surge protectors in a NEMA enclosure per NEMA ICS 6 . Do not install SPD inside a panelboard or switchboard

SECTION 26 20 00 Page 17 enclosure.SPD must have the same short-circuit current rating as the protected equipment and must not be installed at a point of system where the available fault current is in excess of that rating. Use Type 1 or Type 2 SPD and connect on the load side of a dedicated circuit breaker.

Submit performance and characteristic curves.

Provide the following modes of protection:

FOR SINGLE PHASE AND THREE PHASE WYE CONNECTED SYSTEMS-

Phase to phase ( L-L ) Each phase to neutral ( L-N ) Neutral to ground ( N-G ) Phase to ground ( L-G )

SPDs at the service entrance: provide with a minimum surge current rating of 80,000 amperes for L-L mode minimum and 40,000 amperes for other modes (L-N, L-G, and N-G).

Provide SPDs per NFPA 780 for the lightning protection system.

Maximum L-N, and N-G Voltage Protection Rating:

700V for 208Y/120V, three phase system 1,200V for 480Y/277V, three phase system

Maximum L-G Protection Rating:

700V for 208Y/120V, three phase system 1,200V for 480Y/277V, three phase system

Maximum L-L Voltage Protection Rating:

1,200V for 208Y/120V, three phase system 1,800V for 480Y/277V, three phase system

The minimum MCOV(Maximum Continuous Operating Voltage)rating for L-N and L-G modes of operation: 120 percent of nominal voltage for 240 volts and below; 115 percent of nominal voltage above 240 volts to 480 volts.

2.24 FACTORY APPLIED FINISH

Provide factory-applied finish on electrical equipment in accordance with the following:

a. NEMA 250 corrosion-resistance test and the additional requirements as specified herein

b. Interior and exterior steel surfaces of equipment enclosures:

thoroughly cleaned followed by a rust-inhibitive phosphatizing or equivalent treatment prior to painting

c. Exterior surfaces: free from holes, seams, dents, weld marks, loose scale or other imperfections

d. Interior surfaces: receive not less than one coat of corrosion-resisting paint in accordance with the manufacturer's standard practice

e. Exterior surfaces: primed, filled where necessary, and given not less than two coats baked enamel with semigloss finish

f. Equipment located indoors: ANSI Light Gray, and equipment located

SECTION 26 20 00 Page 18 outdoors: ANSI Light Gray

g. Provide manufacturer's coatings for touch-up work and as specified in paragraph FIELD APPLIED PAINTING.

2.25 SOURCE QUALITY CONTROL

2.25.1 Transformer Factory Tests

Submittal: include routine NEMA ST 20 transformer test results on each transformer and also provide the results of NEMA "design" and "prototype" tests that were made on transformers electrically and mechanically equal to those specified.

2.26 COORDINATED POWER SYSTEM PROTECTION

Prepare analyses as specified in Section 26 05 73 POWER SYSTEM STUDIES.

PART 3 EXECUTION

3.1 INSTALLATION

Electrical installations, including weatherproof and hazardous locations and ducts, plenums and other air-handling spaces: conform to requirements of NFPA 70 and to requirements specified herein.

3.1.1 Underground Service

Underground service conductors and associated conduit: continuous from service entrance equipment to outdoor power system connection.

3.1.2 Wiring Methods

Provide insulated conductors installed in rigid steel conduit, IMC, rigid nonmetallic conduit, or EMT, except where specifically indicated or specified otherwise or required by NFPA 70 to be installed otherwise.

Grounding conductor: separate from electrical system neutral conductor.

Provide insulated green equipment grounding conductor for circuit(s) installed in conduit and raceways. Minimum conduit size: 1/2 inch in diameter for low voltage lighting and power circuits. Vertical distribution in multiple story buildings: made with metal conduit in fire-rated shafts, with metal conduit extending through shafts for minimum distance of 6 inches.

3.1.2.1 Pull Wire

Install pull wires in empty conduits. Pull wire: plastic having minimum 200-pound force tensile strength. Leave minimum 36 inches of slack at each end of pull wire.

3.1.2.2 Metal-Clad Cable

Install in accordance with NFPA 70 , Type MC cable.

3.1.2.3 Armored Cable

Install in accordance with NFPA 70 , Type AC cable.

SECTION 26 20 00 Page 19

3.1.2.4 Flat Conductor Cable

Install in accordance with NFPA 70 , Type FCC cable.

3.1.3 Conduit Installation

Unless indicated otherwise, conceal conduit under floor slabs and within finished walls, ceilings, and floors. Keep conduit minimum 6 inches away from parallel runs of flues and steam or hot water pipes. Install conduit parallel with or at right angles to ceilings, walls, and structural members where located above accessible ceilings and where conduit will be visible after completion of project.

3.1.3.1 Restrictions Applicable to Aluminum Conduit

a. Do not install underground or encase in concrete or masonry.

b. Do not use brass or bronze fittings.

c. Do not use when the enclosed conductors must be shielded from the effects of High-altitude Electromagnetic Pulse(HEMP).

3.1.3.2 Restrictions Applicable to EMT

a. Do not install underground.

b. Do not encase in concrete, mortar, grout, or other cementitious materials.

c. Do not use in areas subject to physical damage including but not limited to equipment rooms where moving or replacing equipment could physically damage the EMT.

d. Do not use in hazardous areas.

e. Do not use outdoors.

f. Do not use in fire pump rooms.

g. Do not use when the enclosed conductors must be shielded from the effects of High-altitude Electromagnetic Pulse(HEMP).

3.1.3.3 Restrictions Applicable to Nonmetallic Conduit

a. PVC Schedule 40.

(1) Do not use where subject to physical damage, including but not limited to, mechanical equipment rooms, electrical equipment rooms, fire pump rooms, and where restrictions are applying to both PVC Schedule 40 and PVC Schedule 80.

(2) Do not use above grade, except where allowed in this section for rising through floor slab or indicated otherwise.

b. PVC Schedule 80.

(1) Do not use where subject to physical damage, including but not limited to, hospitals, power plant, missile magazines, and other such areas.

SECTION 26 20 00 Page 20

(2) Do not use in hazardous(classified)areas.

(3) Do not use in penetrating fire-rated walls or partitions, or fire-rated floors.

3.1.3.4 Restrictions Applicable to Flexible Conduit

Use only as specified in paragraph FLEXIBLE CONNECTIONS. Do not use when the enclosed conductors must be shielded from the effects of High-altitude Electromagnetic Pulse(HEMP).

3.1.3.5 Underground Conduit

Plastic-coated rigid steel; plastic-coated steel IMC; PVC, Type EPC-40; or fiberglass. Convert nonmetallic conduit, other than PVC Schedule 40 or 80, to plastic-coated rigid, or IMC, steel conduit before rising through floor slab. Plastic coating: extend minimum 6 inches above floor.

3.1.3.6 Conduit for Circuits Rated Greater Than 600 Volts

Rigid metal conduit or IMC only.

3.1.3.7 Conduit Through Floor Slabs

Where conduits rise through floor slabs, do not allow curved portion of bends to be visible above finished slab. Where conduit rises through slab-on grade, seal all electrical penetrations to address radon mitigation and prevent infiltration of air, insects, and vermin.

3.1.3.8 Stub-Ups

Provide conduits stubbed up through concrete floor for connection to free-standing equipment with adjustable top or coupling threaded inside for plugs, set flush with finished floor. Extend conductors to equipment in rigid steel conduit, except that flexible metal conduit may be used 6 inches above floor. Where no equipment connections are made, install screwdriver-operated threaded flush plugs in conduit end.

3.1.3.9 Conduit Support

Support conduit by pipe straps, wall brackets, threaded rod conduit hangers, or ceiling trapeze. Plastic cable ties are not acceptable. Fasten by wood screws to wood; by toggle bolts on hollow masonry units; by concrete inserts or expansion bolts on concrete or brick; and by machine screws, welded threaded studs, or spring-tension clamps on steel work.

Threaded C-clamps may be used on rigid steel conduit only. Do not weld conduits or pipe straps to steel structures. Do not exceed one-fourth proof test load for load applied to fasteners. Provide vibration resistant and shock-resistant fasteners attached to concrete ceiling. Do not cut main reinforcing bars for any holes cut to depth of more than 1 1/2 inches in reinforced concrete beams or to depth of more than 3/4 inch in concrete joints. Fill unused holes. In partitions of light steel construction, use sheet metal screws. In suspended-ceiling construction, run conduit above ceiling. Do not support conduit by ceiling support system. Conduit and box systems: supported independently of both(a)tie wires supporting ceiling grid system, and(b)ceiling grid system into which ceiling panels are placed. Do not share supporting means between electrical raceways and mechanical piping or ducts. Identify independent conduit support in both

SECTION 26 20 00 Page 21 fire and non-fire rated assemblies per NFPA 70 . Coordinate installation with above-ceiling mechanical systems to assure maximum accessibility to all systems. Spring-steel fasteners may be used for lighting branch circuit conduit supports in suspended ceilings in dry locations expansion fitting that maintains conduit electrical continuity by bonding jumpers or other means. For conduits greater than 2 1/2 inches inside diameter, provide supports to resist forces of 0.5 times the equipment weight in any direction and 1.5 times the equipment weight in the downward direction.

3.1.3.10 Directional Changes in Conduit Runs

Make changes in direction of runs with symmetrical bends or cast-metal fittings. Make field-made bends and offsets with hickey or conduit-bending machine. Do not install crushed or deformed conduits. Avoid trapped conduits. Prevent plaster, dirt, or trash from lodging in conduits, boxes, fittings, and equipment during construction. Free clogged conduits of obstructions.

3.1.3.11 Locknuts and Bushings

Fasten conduits to sheet metal boxes and cabinets with two locknuts where required by NFPA 70 , where insulated bushings are used, and where bushings cannot be brought into firm contact with the box; otherwise, use at least minimum single locknut and bushing. Provide locknuts with sharp edges for digging into wall of metal enclosures. Install bushings on ends of conduits, and provide insulating type where required by NFPA 70 .

3.1.3.12 Flexible Connections

Provide flexible steel conduit between 3 and 6 feet in length for recessed and semirecessed lighting fixtures. Install flexible conduit to allow 20 percent slack. Minimum flexible steel conduit size: 1/2 inch diameter.

Provide separate ground conductor across flexible connections. Plastic cable ties are not acceptable as a support method.

3.1.3.13 Telecommunications and Signal System Pathway

Install telecommunications pathway in accordance with TIA-569 .

3.1.4 Busway Installation

Comply at minimum with NFPA 70 . Install busways parallel with or at right angles to ceilings, walls, and structural members. Support busways at 5 foot maximum intervals, and brace to prevent lateral movement. Provide fixed type hinges on risers; spring-type are unacceptable. Provide flanges where busway makes penetrations through walls and floors, and seal to maintain smoke and fire ratings. Provide waterproof curb where busway riser passes through floor. Seal gaps with fire-rated foam and caulk.

Provide expansion joints, but only where bus duct crosses building expansion joints. Provide supports to resist forces of 0.5 times the equipment weight in any direction and 1.5 times the equipment weight in the downward direction.

3.1.5 Cable Tray Installation

Install and ground in accordance with NFPA 70 . Install cable trays parallel with or at right angles to ceilings, walls, and structural members. Cable tray and tray supports must not partially nor completely obstruct access to the room. Support in accordance with NEMA VE 2 and with

SECTION 26 20 00 Page 22 manufacturer recommendations but at not more than 6 foot intervals.

Adjacent cable tray sections: bonded together by connector plates of an identical type as the cable tray sections. For grounding of cable tray system provide No. 2 AWG bare copper wire throughout cable tray system, and bond to each section, except use No. 1/0 aluminum wire if cable tray is aluminum. Terminate cable trays 10 inches from both sides of smoke and fire partitions. Install conductors run through smoke and fire partitions in 4 inch rigid steel conduits with grounding bushings, extending 12 inches beyond each side of partitions. Seal conduit on both ends to maintain smoke and fire ratings of partitions. Provide supports to resist forces of

0.5 times the equipment weight in any direction and 1.5 times the equipment weight in the downward direction.

3.1.6 Boxes, Outlets, and Supports

Provide boxes in wiring and raceway systems wherever required for pulling of wires, making connections, and mounting of devices or fixtures. Boxes for metallic raceways: cast-metal, hub-type when located in wet locations, when surface mounted on outside of exterior surfaces, when surface mounted on interior walls exposed up to 7 feet above floors and walkways, and when specifically indicated. Boxes in other locations: sheet steel, except that aluminum boxes may be used with aluminum conduit, and nonmetallic boxes may be used with nonmetallic sheathed cable conduit system. Provide each box with volume required by NFPA 70 for number of conductors enclosed in box. Boxes for mounting lighting fixtures: minimum 4 inches square, or octagonal, except that smaller boxes may be installed as required by fixture configurations, as approved. Boxes for use in masonry-block or tile walls: square-cornered, tile-type, or standard boxes having square-cornered, tile-type covers. Provide gaskets for cast-metal boxes installed in wet locations and boxes installed flush with outside of exterior surfaces. Provide separate boxes for flush or recessed fixtures when required by fixture terminal operating temperature; provide readily removable fixtures for access to boxes unless ceiling access panels are provided. Support boxes and pendants for surface-mounted fixtures on suspended ceilings independently of ceiling supports. Fasten boxes and supports with wood screws on wood, with bolts and expansion shields on concrete or brick, with toggle bolts on hollow masonry units, and with machine screws or welded studs on steel. In open overhead spaces, cast boxes threaded to raceways need not be separately supported except where used for fixture support; support sheet metal boxes directly from building structure or by bar hangers. Where bar hangers are used, attach bar to raceways on opposite sides of box and support raceway with approved-type fastener maximum 24 inches from box. When penetrating reinforced concrete members, avoid cutting reinforcing steel.

3.1.6.1 Boxes

Boxes for use with raceway systems: minimum 1 1/2 inches deep, except where shallower boxes required by structural conditions are approved.

Boxes for other than lighting fixture outlets: minimum 4 inches square, except that 4 by 2 inch boxes may be used where only one raceway enters outlet.

3.1.6.1.1 Wall-Mounted Telecommunications Outlet Box

Provide double gang electrical boxes, minimum standard size 4-11/16 inches square and 2-1/8 inches deep with plaster ring for connection of single gang faceplate.

This is the start of the file's text. The full file is on GovTribe.