This file contains specifications (Volume 2 of 2) for a design-bid-build construction project to build a Vertical Skills Instruction Facility at Joint Base McGuire-Dix-Lakehurst, NJ. The specifications detail requirements for Divisions 10-33, covering specialties, furnishings, special construction, mechanical/electrical systems, and site work.
Key specifications include requirements for interior signage (Section 10 14 00.20), toilet compartments and accessories (10 21 13, 10 28 13), wall/door protection (10 26 00), fire extinguishers (10 44 16), window treatments (12 21 00, 12 24 13), and metal building systems (13 34 19). Detailed requirements are provided for materials, fabrication, finishes, installation, and testing of components like room signs, toilet partitions, grab bars, paper towel dispensers, corner guards, window blinds, and structural steel. The specifications emphasize durability, ADA compliance, sustainability, and integration with other building systems. Warranty periods generally range from 1-10 years depending on the component. The document provides comprehensive technical requirements that contractors must follow during construction of the facility.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Solicitation For Vertical Skills Instruction Facility Joint Base McGuire-Dix-Lakehurst, NJ
P2: 479787
Design-Bid-Build
Specifications - Vol 2 of 2(Div 10 - 33) Certified Final Design
10 December 2024
W912QR25R0014
ARIMS: 200A
Disposition: Maintain for 15yrs after construction
W912QR25R0014_Specs_Vol2-0000
P2: 479787 Vertical Skills Instruction Facility Joint Base McGuire-Dix-Lakehurst, NJ
Certified Final
Plumbing
DOCUMENT PROJECT Page 1
PROJECT TABLE OF CONTENTS
DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS
00 10 00 00 SOLICITATION CONTRACT FORM
00 80 00.00 06 04/21 SPECIAL PROVISIONS
00 80 00.01 06 ATTACHMENTS
DIVISION 01 - GENERAL REQUIREMENTS
01 14 00 11/11, CHG 14: 02/22 WORK RESTRICTIONS
01 32 01.00 06 10/23 PROJECT SCHEDULE
01 33 00 08/18, CHG 4: 02/21 SUBMITTAL PROCEDURES
01 33 29.00 06 11/17 SUSTAINABILITY REPORTING
01 35 26.00 06 GOVERNMENT SAFETY REQUIREMENTS
01 42 00 02/19 SOURCES FOR REFERENCE PUBLICATIONS
01 45 00.15 10 11/16, CHG 2: 08/19 RESIDENT MANAGEMENT SYSTEM CONTRACTOR
MODE (RMS CM)
01 45 04.10 06 CONTRACTOR QUALITY CONTROL
01 45 35 11/20 SPECIAL INSPECTIONS
01 46 00.00 06 04/20 TOTAL BUILDING COMMISSIONING
01 50 00 11/20, CHG 1: 08/21 TEMPORARY CONSTRUCTION FACILITIES AND
CONTROLS
01 57 19.00 06 04/20 TEMPORARY ENVIRONMENTAL CONTROLS AND
PERMITS
01 74 19 02/19, CHG 3: 11/21 CONSTRUCTION WASTE MANAGEMENT AND
DISPOSAL
01 78 23 08/15, CHG 2: 08/21 OPERATION AND MAINTENANCE DATA
DIVISION 02 - EXISTING CONDITIONS
02 41 00 08/22 DEMOLITION
02 82 00 11/18 ASBESTOS REMEDIATION
DIVISION 03 - CONCRETE
03 30 00 02/19, CHG 7: 02/24 CAST-IN-PLACE CONCRETE
DIVISION 04 - MASONRY
04 20 00 11/15, CHG 2: 05/19 UNIT MASONRY
DIVISION 05 - METALS
05 40 00 05/15, CHG 1: 08/18 COLD-FORMED METAL FRAMING
05 50 13 05/17, CHG 1: 08/18 MISCELLANEOUS METAL FABRICATIONS
DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES
06 10 00 08/16, CHG 2: 11/18 ROUGH CARPENTRY
06 41 16.00 10 08/10, CHG 1: 11/18 PLASTIC-LAMINATE-CLAD ARCHITECTURAL
CABINETS
06 61 16 08/20 SOLID SURFACING FABRICATIONS
06 73 01 08/23 FIBERGLASS REINFORCED PLASTIC (FRP)
GRATING
DIVISION 07 - THERMAL AND MOISTURE PROTECTION
07 11 13 08/23 BITUMINOUS DAMPPROOFING
07 21 13 08/23 BOARD AND BLOCK INSULATION
DOCUMENT PROJECT Page 2
07 27 10 08/23 BUILDING AIR BARRIER SYSTEM
07 27 19.01 08/23 SELF-ADHERING AIR BARRIERS
07 41 14.00 48 10/10 STRUCTURAL STANDING SEAM METAL ROOFING
SYSTEM (HYDROSTATIC-HS-SSSMRS)
07 62 00.00 48 10/10 FLASHING AND SHEET METAL
07 84 00 05/10, CHG 1: 08/13 FIRESTOPPING
07 92 00.00 48 10/10 JOINT SEALANTS
DIVISION 08 - OPENINGS
08 11 13 08/20 STEEL DOORS AND FRAMES
08 31 00 05/17, CHG 1: 08/18 ACCESS DOORS AND PANELS
08 33 23 08/20, CHG 1: 02/22 OVERHEAD COILING DOORS
08 41 13 08/18 ALUMINUM-FRAMED ENTRANCES AND
STOREFRONTS
08 51 13 05/19 ALUMINUM WINDOWS
08 71 00 02/16, CHG 4: 02/22 DOOR HARDWARE
08 81 00 05/19 GLAZING
08 91 00 08/20 METAL WALL LOUVERS
DIVISION 09 - FINISHES
09 22 00 02/10, CHG 2: 08/18 SUPPORTS FOR PLASTER AND GYPSUM BOARD
09 29 00 08/16, CHG 4: 02/20 GYPSUM BOARD
09 30 10 08/20 CERAMIC, QUARRY, AND GLASS TILING
09 51 00 08/20 ACOUSTICAL CEILINGS
09 62 38 08/17, CHG 1: 08/18 STATIC-CONTROL FLOORING
09 65 00 08/10, CHG 3: 08/18 RESILIENT FLOORING
09 68 00 11/17, CHG 2: 08/20 CARPETING
09 90 00 02/21 PAINTS AND COATINGS
DIVISION 10 - SPECIALTIES
10 14 00.20 08/17 INTERIOR SIGNAGE
10 21 13 08/20 TOILET COMPARTMENTS
10 26 00 08/20 WALL AND DOOR PROTECTION
10 28 13 08/20 TOILET ACCESSORIES
10 44 16 11/19 FIRE EXTINGUISHERS
10 90 00.00 48 04/06 MISCELLANEOUS SPECIALTIES (PARTIAL
OMAR FUNDED)
DIVISION 12 - FURNISHINGS
12 21 00 08/17, CHG 2: 11/18 WINDOW BLINDS
12 24 13 08/20 ROLLER WINDOW SHADES
DIVISION 13 - SPECIAL CONSTRUCTION
13 34 19 08/20, CHG 1: 02/21 METAL BUILDING SYSTEMS
DIVISION 21 - FIRE SUPPRESSION
21 13 13 08/20 WET PIPE SPRINKLER SYSTEMS, FIRE
PROTECTION
DIVISION 22 - PLUMBING
22 00 00 11/15, CHG 4: 05/21 PLUMBING, GENERAL PURPOSE
DOCUMENT PROJECT Page 3
DIVISION 23 - HEATING, VENTILATING, AND AIR CONDITIONING (HVAC)
23 05 93 11/15 TESTING, ADJUSTING, AND BALANCING FOR
HVAC
23 07 00 02/13, CHG 7: 05/20 THERMAL INSULATION FOR MECHANICAL
SYSTEMS
23 09 00 02/19, CHG 3: 05/21 INSTRUMENTATION AND CONTROL FOR HVAC
23 09 13 11/15, CHG 2: 05/21 INSTRUMENTATION AND CONTROL DEVICES
FOR HVAC
23 09 23.02 02/19, CHG 1: 02/20 BACNET DIRECT DIGITAL CONTROL FOR HVAC
AND OTHER BUILDING CONTROL SYSTEMS
23 11 20 05/20 FACILITY GAS PIPING
23 23 00 08/21 REFRIGERANT PIPING
23 30 00 05/20, CHG 1: 02/22 HVAC AIR DISTRIBUTION
23 80 20.00 10 05/20 GAS-FIRED HEATING EQUIPMENT
23 83 00.00 20 04/06 ELECTRIC SPACE HEATING EQUIPMENT
DIVISION 25 - INTEGRATED AUTOMATION
25 05 11.01 11/17 CYBERSECURITY FOR FACILITY-HVAC
RELATED CONTROL SYSTEMS
25 05 11.02 05/21, CHG 1: 08/23 CYBERSECURITY FOR FIRE ALARM LIFE
SAFETY FACILITY-RELATED CONTROL SYSTEMS
25 05 11.03 05/21, CHG 1: 08/23 CYBERSECURITY FOR ELECTRICAL
FACILITY-RELATED CONTROL SYSTEMS
DIVISION 26 - ELECTRICAL
26 05 73 08/23 POWER SYSTEM STUDIES
26 08 00 11/22 APPARATUS INSPECTION AND TESTING
26 20 00 08/23 INTERIOR DISTRIBUTION SYSTEM
26 29 23 02/20, CHG 1: 05/21 ADJUSTABLE SPEED DRIVE (ASD) SYSTEMS
26 41 00
08/23
UNDER 600 VOLTS
LIGHTNING PROTECTION SYSTEM
26 51 00 05/20, CHG 2: 11/21 INTERIOR LIGHTING
26 56 00 08/21 EXTERIOR LIGHTING
DIVISION 27 - COMMUNICATIONS
27 05 28.36 48 04/20 CABLE TRAYS FOR COMMUNICATIONS SYSTEMS
27 10 00.00 48 10/20 BUILDING TELECOMMUNICATIONS CABLING
SYSTEM
DIVISION 28 - ELECTRONIC SAFETY AND SECURITY
28 31 76 08/20 INTERIOR FIRE ALARM AND MASS
NOTIFICATION SYSTEM, ADDRESSABLE
DIVISION 31 - EARTHWORK
31 00 00.00 06 07/18 EARTHWORK
DIVISION 32 - EXTERIOR IMPROVEMENTS
32 01 17.61 05/17 SEALING CRACKS IN ASPHALT PAVING
32 11 20 08/17 AGGREGATE BASE COURSE
32 12 13 05/17 BITUMINOUS TACK AND PRIME COATS
32 12 16.16 11/20 ROAD-MIX ASPHALT PAVING
32 12 36.13 05/17 ASPHALTIC SEAL AND FOG COATS
DOCUMENT PROJECT Page 4
32 16 19 05/18 CONCRETE CURBS AND SIDEWALKS
32 17 23 08/16, CHG 5: 11/18 PAVEMENT MARKINGS
32 31 13.53 11/21 HIGH-SECURITY FENCES (CHAIN LINK AND
ORNAMENTAL) AND GATES
DIVISION 33 - UTILITIES
33 11 00 02/18, CHG 1: 02/22 WATER UTILITY DISTRIBUTION PIPING
33 30 00 05/18 SANITARY SEWERAGE
33 40 00 11/21 STORMWATER UTILITIES
33 71 02 08/21 UNDERGROUND ELECTRICAL DISTRIBUTION
33 82 00.00 48 04/20 TELECOMMUNICATIONS OUTSIDE PLANT (OSP)
-- End of Project Table of Contents --
SECTION 10 14 00.20
INTERIOR SIGNAGE
08/17
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by basic designation only.
ALUMINUM ASSOCIATION (AA)
AA DAF45 (2003; Reaffirmed 2009) Designation System for Aluminum Finishes
AA PK-1 (2015) Pink Sheets: Designations and Chemical Composition Limits for Aluminum Alloys in the Form of Castings & Ingot
AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA)
AAMA 2604 (2017a) Voluntary Specification, Performance Requirements and Test Procedures for High Performance Organic Coatings on Aluminum Extrusions and Panels
AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)
ANSI Z97.1 (2015) Safety Glazing Materials Used in Buildings - Safety Performance Specifications and Methods of Test
AMERICAN WELDING SOCIETY (AWS)
AWS D1.2/D1.2M (2014; Errata 1 2014; Errata 2 2020) Structural Welding Code - Aluminum
ASTM INTERNATIONAL (ASTM)
ASTM B209 (2014) Standard Specification for Aluminum and Aluminum-Alloy Sheet and Plate
ASTM B221 (2021) Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
36 CFR 1191 Americans with Disabilities Act (ADA) Accessibility Guidelines for Buildings and Facilities; Architectural Barriers Act (ABA) Accessibility Guidelines
SECTION 10 14 00.20 Page 1
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submittals with an "S" are for inclusion in the Sustainability eNotebook, in conformance to Section 01 33 29.00 06 SUSTAINABILITY REPORTING. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Detail Drawings ; G
SD-03 Product Data
Installation ; G
Warranty ; G
SD-04 Samples
Interior Signage ; G
Software ; G
SD-10 Operation and Maintenance Data
Approved Manufacturer's Instructions ; G
Protection and Cleaning ; G
1.3 EXTRA MATERIALS
Provide 5 extra frames and extra stock of the following: Type D and F.
Provide paper inserts and one copy of the software for user produced signs and inserts after project completion.
1.4 QUALITY ASSURANCE
1.4.1 Samples
Submit interior signage samples of each of the following sign types showing typical quality, workmanship and color: Directional sign, Standard Room sign, Changeable message strip sign. The samples may be installed in the work, provided each sample is identified and location recorded.
1.4.2 Detail Drawings
Submit detail drawings showing elevations of each type of sign, dimensions, details and methods of mounting or anchoring, mounting height, shape and thickness of materials, and details of construction. Include a schedule showing the location, each sign type, and message.
1.5 DELIVERY, STORAGE, AND HANDLING
Materials must be packaged to prevent damage and deterioration during shipment, handling, storage and installation. Product must be delivered
SECTION 10 14 00.20 Page 2 to the jobsite in manufacturer's original packaging and stored in a clean, dry area in accordance with manufacturer's instructions.
1.6 WARRANTY
Warrant the interior signage for a period of 2 years against defective workmanship and material. Warranties must be signed by the authorized representative of the manufacturer. Submit warranty accompanied by the document authenticating the signer as an authorized representative of the guarantor. Guarantee that the signage products and the installation are free from any defects in material and workmanship from the date of delivery.
PART 2 PRODUCTS
2.1 STANDARD PRODUCTS
Signs, plaques, directories, and dimensional letters must be the standard product of a manufacturer regularly engaged in the manufacture of such products that essentially duplicate signs that have been in satisfactory use at least 2 years prior to bid opening. Obtain signage from a single manufacturer with edges and corners of finished letterforms and graphics true and clean.
2.2 ROOM IDENTIFICATION/DIRECTIONAL SIGNAGE SYSTEM
2.2.1 Standard Room Signs
Signs must consist of acrylic plastic 0.080 inch thickness minimum conforming to ANSI Z97.1 and must conform to the following:
a. Frames must be molded acrylic, flat or radius.
b. End caps must be aluminum or molded acrylic with round or square style corners.
2.2.2 Changeable Message Strip Signs
Changeable message strip signs must be of same construction as standard room signs to include a clear sleeve that will accept a paper or plastic insert identifying changeable text. The insert must be prepared die-cut vinyl letters applied to 0.015 inch rigid vinyl film or typeset message mounted on paper card stock. Provide paper/vinyl filmstrips and software for creating text and symbols for computers identified by owner for Owner production of paper inserts after project completion.
2.2.3 Type of Mounting For Signs
Provide extruded aluminum brackets for hanging, projecting, and double-sided signs. Mounting for framed, hanging, and projecting signs must be by mechanical fasteners. Surface mounted signs must be mounted with 1/16 inch thick closed cell vinyl foam with adhesive backing.
Adhesive must be transparent, long aging, high tech formulation on two sides of the vinyl foam, fabricated from materials that are not corrosive to sign material and mounting surface.
2.2.4 Graphics
Signage graphics for modular signs must conform to the following:
SECTION 10 14 00.20 Page 3
2.2.4.1 Surface Applied Photopolymer
Integral graphics and Braille achieved by photomechanical stratification processes. Photopolymer used for ADA compliant graphics must be of the type that has a minimum durometer reading of 90. Tactile graphics must be raised 1/32 inch from the first surface of plaque by photomechanical stratification process.
2.2.5 Character Proportions and Heights
Letters and numbers on signs conform to 36 CFR 1191 .
2.2.6 Tactile Letters, Symbols and Braille
Raised letters and numbers on signs must conform to 36 CFR 1191 .
2.3 BUILDING DIRECTORIES
Building directories must be lobby directories or floor directories, and must be provided with a changeable directory listing consisting of the areas, offices and personnel located within the facility. Dimensions, details, and materials of sign and message content must be as shown on the drawings.
2.3.1 Header Panel
Header panel must be acrylic with raised acrylic letters.
2.3.2 Fabrication
Extruded aluminum frames and trim must be assembled with corners reinforced and mitered to a hairline fit, with no exposed fasteners.
2.3.3 Non-Illuminated Unit
Directory must consist of a non-illuminated unit with vinyl or screen printed lettering on plastic film held in interchangeable plastic carriers. Design of unit must be as shown in the drawings.
2.3.3.1 Message Strips
Message strips must be updatable by user. Letters and numbers must be provided in accordance with the drawings.
2.4 DIMENSIONAL BUILDING LETTERS
2.4.1 Fabrication
Letters must be cast. Letters must be aluminum or bronze. Package letters for protection until installation.
2.4.2 Size
Letter size must be as indicated.
2.4.3 Finish
Provide baked enamel finish. Finishes to match base standards.
SECTION 10 14 00.20 Page 4
2.4.4 Mounting
Steel U-bracket, cap screws, and expansion bolts of number and size recommended by manufacturer, must be supplied for concealed anchorage.
Letters which project from the mounting surface must have stud spacer sleeves. Letters, studs, and sleeves must be of the same material.
Templates for mounting must be supplied.
2.5 PRESSURE SENSITIVE LETTERS
2.5.1 Fabrication
Ensure that vinyl letter edges and corners of finished letterforms and graphics are true and clean. Do not use letterforms and graphics with rounded positive or negative corners, nicked, cut, or ragged edges.
2.5.2 Size
Letter size: as indicated.
2.6 ALUMINUM ALLOY PRODUCTS
Aluminum extrusions must be at least 1/8 inch thick, and aluminum plate or sheet must be at least 0.0508 inch thick. Extrusions must conform to ASTM B221; plate and sheet must conform to ASTM B209. Where anodic coatings are specified, alloy must conform to AA PK-1 alloy designation
514.0. Exposed anodized aluminum finishes must be as shown. Welding for aluminum products must conform to AWS D1.2/D1.2M .
2.7 ANODIC COATING
Anodized finish must conform to AA DAF45 as follows:
a. Clear (natural) designation AA-M10-C22-A31, Architectural Class II 0.4 mil or thicker.
b. Integral color anodized designation AA-M10-C22-A32, Architectural Class
0.4 to 0.7 mil .
c. Electrolytically deposited color-anodized designation AA-M10-C22-A34, Architectural Class II 0.4 to 0.7 mil .
2.8 ORGANIC COATING
Organic coating must conform to AAMA 2604, with total dry film thickness not less than 1.2 mils .
2.9 FABRICATION AND MANUFACTURE
2.9.1 Factory Workmanship
Holes for bolts and screws must be drilled or punched. Drilling and punching must produce clean, true lines and surfaces. Exposed surfaces of work must have a smooth finish and exposed riveting must be flush.
Fastenings must be concealed where practicable.
SECTION 10 14 00.20 Page 5
2.9.2 Dissimilar Materials
Where dissimilar metals are in contact, the surfaces will be protected to prevent galvanic or corrosive action.
2.10 COLOR, FINISH, AND CONTRAST
Color must be as indicated on construction drawings. Finish of all signs must be eggshell, matte, or other non-glare finish as required in handicapped-accessible buildings.
2.11 TYPEFACE
ADA-ABA compliant font for Room Signs.
PART 3 EXECUTION
3.1 INSTALLATION
Signs must be installed plumb and true and in accordance with approved manufacturer's instructions at locations shown on the construction drawings. Submit three copies of operating instructions outlining the step-by-step procedures required for system operation. The instructions must include simplified diagrams for the system as installed, the manufacturer's name, model number, service manual, parts list, and brief description of all equipment and their basic operating features. Each set must be permanently bound and must have a hard cover. The following identification must be inscribed on the covers: the words "OPERATING AND MAINTENANCE INSTRUCTIONS", name and location of the facility, name of the Contractor, and contract number. Mounting height and mounting location must conform to 36 CFR 1191 . Required blocking must be installed. Signs on doors or other surfaces must not be installed until finishes on such surfaces have been installed. Signs installed on glass surfaces must be installed with matching blank back-up plates in accordance with manufacturer's instructions.
Do not install items that show visual evidence of biological growth.
3.1.1 Anchorage
Anchorage must be in accordance with approved manufacturer's instructions. In high humidity interior spaces (for example, bathrooms, locker rooms, pools, trainers) and unconditioned spaces, use corrosion-resistant anchors/fasteners or with approval by the manufacturer, waterproof silicone adhesive. Anchorage not otherwise specified or shown must include slotted inserts, expansion shields, and powder-driven fasteners when approved for concrete; toggle bolts and through bolts for masonry; machine carriage bolts for steel; lag bolts and screws for wood. Exposed anchor and fastener materials must be compatible with metal to which applied and must have matching color and finish. At interior applications in heavy traffic areas, firmly attach signage to structure walls with tamper-proof fasteners.
a. Signs mounted to painted gypsum board surfaces must be removable for painting maintenance.
b. Mount signs mounted to lay-in ceiling grids with clip connections to ceiling tees.
SECTION 10 14 00.20 Page 6
c. Install signs mounted on metal surfaces with magnetic tape.
d. Install signs mounted on fabric surfaces with hook and loop tape or pin mount.
3.1.2 Protection and Cleaning
Protect the work against damage during construction. Hardware and electrical equipment must be adjusted for proper operation. Glass, frames, and other sign surfaces must be cleaned at completion of sign installation in accordance with the manufacturer's approved instructions and the requirements of Section 01 78 23 OPERATION AND MAINTENANCE DATA, Package 1. Submit three copies of maintenance instructions listing routine procedures, repairs, and guides.
-- End of Section --
SECTION 10 14 00.20 Page 7
SECTION 10 21 13
TOILET COMPARTMENTS
08/20
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ALUMINUM ASSOCIATION (AA)
AA DAF45 (2003; Reaffirmed 2009) Designation System for Aluminum Finishes
ASTM INTERNATIONAL (ASTM)
ASTM A123/A123M (2017) Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products
ASTM A167 (2011) Standard Specification for Stainless and Heat-Resisting Chromium-Nickel Steel Plate, Sheet, and Strip
ASTM A336/A336M (2021) Standard Specification for Alloy Steel Forgings for Pressure and High-Temperature Parts
ASTM A385/A385M (2020) Standard Practice for Providing High-Quality Zinc Coatings (Hot-Dip)
ASTM B36/B36M (2018) Standard Specification for Brass Plate, Sheet, Strip, and Rolled Bar
ASTM B86 (2018; E 2021) Standard Specification for Zinc and Zinc-Aluminum (ZA) Alloy Foundry and Die Castings
ASTM B221 (2021) Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes
ASTM B456 (2017) Standard Specification for Electrodeposited Coatings of Copper Plus Nickel Plus Chromium and Nickel Plus Chromium
INTERNATIONAL CODE COUNCIL (ICC)
ICC A117.1 (2017) Standard And Commentary Accessible and Usable Buildings and Facilities
SECTION 10 21 13 Page 1
SCIENTIFIC CERTIFICATION SYSTEMS (SCS)
SCS SCS Global Services (SCS) Indoor Advantage
U.S. GENERAL SERVICES ADMINISTRATION (GSA)
CID A-A-60003 (Basic; Notice 1) Partitions, Toilet, Complete
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
36 CFR 1191 Americans with Disabilities Act (ADA) Accessibility Guidelines for Buildings and Facilities; Architectural Barriers Act (ABA) Accessibility Guidelines
UNDERWRITERS LABORATORIES (UL)
UL 2818 (2022) GREENGUARD Certification Program For Chemical Emissions For Building Materials, Finishes And Furnishings
1.2 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for information only. When used, a code following the "G" classification identifies the office that will review the submittal for the Government.
Submit the following in accordance with Section 01 33 00 SUBMITTAL
PROCEDURES:
SD-02 Shop Drawings
Fabrication Drawings
Installation Drawings ; G
SD-03 Product Data
Cleaning and Maintenance Instructions
Colors And Finishes
Anchoring Devices and Fasteners
Hardware and Fittings
Brackets
Door Hardware
Pilaster Shoes
Finishes ; G
SD-04 Samples
Colors and Finishes ; G
SECTION 10 21 13 Page 2
Hardware and Fittings
Anchoring Devices and Fasteners
SD-07 Certificates
Warranty
1.3 CERTIFICATIONS
1.3.1 Indoor Air Quality
1.3.1.1 Laminated Plastic and Solid Phenolic Products
Provide products certified to meet indoor air quality requirements by UL 2818 (Greenguard) Gold, SCS Global Services Indoor Advantage Gold or provide certification or validation by other third-party program that products meet the requirements of this Section. Provide current product certification documentation from certification body.
1.4 REGULATORY REQUIREMENTS
Comply with to ICC A117.1 code for access for the handicapped operation of toilet compartment door and hardware.
1.5 DELIVERY, STORAGE, AND HANDLING
Deliver materials in the manufacturer's original unopened packages with the brand, item identification, and project reference clearly marked.
Store components in a dry location that is adequately ventilated; free from dust, water, other contaminants, and damage during delivery, storage, and construction.
1.6 WARRANTY
Provide manufacturer's warranty to repair or replace defective materials and workmanship for a period of one year from date of final acceptance of the work.
PART 2 PRODUCTS
2.1 SYSTEM REQUIREMENTS
Provide a complete and usable toilet partition system, including toilet enclosures, room entrance screens, urinal screens, system of panels, hardware, and support components. Furnish the partition system from a single manufacturer, with a standard product as shown in the most recent catalog data. Submit Fabrication Drawings for toilet partitions and urinal screens consisting of fabrication and assembly details to be performed in the factory. Submit manufacturer's Cleaning and Maintenance Instructions in accordance with Section 01 78 23 OPERATIONS AND
MAINTENANCE DATA.
2.2 MATERIALS
2.2.1 Solid Polyethylene Panels (Finish 5)
Provide high density polyethylene (HDPE) suitable for exposed application.
SECTION 10 21 13 Page 3
Waterproof, non-absorbent and graffiti resistant textured surface with a Flame Spread Index of 75 or less, and a Smoke Developed Index of 450 or less.
2.2.2 Anchoring Devices and Fasteners
Provide steel anchoring devices and fasteners hot-dipped galvanized after fabrication, in conformance with ASTM A385/A385M and ASTM A123/A123M .
Conceal all galvanized anchoring devices.
2.2.3 Brackets
Provide two-ear panel wall brackets, T-style, 1 inch stock. Provide stirrup style panel-to-pilaster brackets.
2.2.4 Hardware and Fittings
2.2.4.1 General Requirements
Provide hardware for the toilet partition system that complies with CID A-A-60003 for the specified type and style of partitions. Provide hardware finish highly resistant to alkalis, urine, and other common toilet room acids. Comply with 36 CFR 1191 of latching devices and hinges for handicap compartments; provide chrome-plated steel devices and hinges with door latches that operate without either tight grasping or twisting of the wrist of the operator. Submit three samples of each item, including anchoring devices and fasteners. Approved hardware samples may be installed in the work if properly identified.
Material Conformance Standard
Cold-rolled sheet steel ASTM A336/A336M , commercial quality
Zinc-base alloy ASTM B86, Alloy AC41-A
Brass ASTM B36/B36M, Alloy C26800
Aluminum ASTM B221
Corrosion-resistant steel ASTM A167, Type 302
2.2.4.2 Finishes
a. Provide chrome plating that complies with ASTM B456.
b. Provide exposed fasteners that match the hardware and fittings.
2.2.5 Door Hardware
2.2.5.1 Hinges
Provide adjustable hinges to hold in-swinging doors open at any angle up to 90 degrees and outswinging doors up to 10 degrees. Provide self-lubricating hinges with the indicated swing. Provide hinges that have the following type of return movement:
SECTION 10 21 13 Page 4
a. Gravity return movement
2.2.5.2 Latch and Pull
Provide latch and pull that is a combination rubber-faced door strike and keeper equipped with emergency access.
2.2.5.3 Coat Hooks
Provide coat hooks that are combination units with hooks and rubber tipped pins.
2.3 PARTITION PANELS AND DOORS
Fabricate partition panels, and pilasters of materials and construction listed:
Provide plastic (HDPE) partition panels, doors and pilasters not less than 1 inch thick.
Provide solid polyethylene toilet partitions and screens with recycled content of 30 percent minimum.
2.3.1 Toilet Enclosures
Provide toilet enclosures that comply with CID A-A-60003 , Type I, Style C, overhead braced . Furnish width, length, and height of toilet enclosures as shown. Finish surface of panels are solid polyethylene (Finish 5);
water resistant; graffiti resistant; non-absorbent radius beveled edges.
Reinforce panels indicated to receive toilet paper holders or grab bars for mounting of the items required, and provide cut outs for through partition toilet accessories. Provide grab bars to withstand a bending stress, shear stress, shear force, and a tensile force induced by 250 lbf .
Grab bars cannot rotate within their fittings.
2.4 OVERHEAD-BRACED PARTITIONS
Provide pilasters in sizes indicated that are manufacturer's standard corrosion-resistant supports, leveling mechanism, and anchors at pilasters to suit floor conditions. Provide shoes at pilasters to conceal supports and leveling mechanism. Provide anchoring device at the bottom of the pilaster consisting of a channel-shaped floor stirrup fabricated from not less than 0.0635 inch thick material and a leveling bolt. Secure the stirrup to the pilaster with not less than a 3/16 inch bolt and nut after the pilaster is leveled. Secure the stirrup to the floor with not less than two lead expansion shields and sheetmetal screws. Fabricate overhead brace from a continuous extruded aluminum tube not less than 1 inch wide by 1-1/2 inch high, 0.125 inch wall thickness. Finish is AA-C22A31 in accordance with AA DAF45. Set and secure brace into the top of each pilaster. Provide shoes at pilasters to conceal supports and leveling mechanism.
2.5 PILASTER SHOES
Provide shoes at pilasters to conceal floor-mounted anchorage. Provide stainless steel pilaster shoes. Height is a minimum 3 inches .
SECTION 10 21 13 Page 5
2.6 HARDWARE
Provide hardware for the toilet partition system that complies with CID A-A-60003 for the specified type and style of partitions. Provide hardware pre-drilled by manufacturer. Use a hardware finish that is highly resistant to alkalis, urine, and other common toilet room acids.
Hardware includes: chrome plated nonferrous cast pivot hinges, gravity type, adjustable for door close positioning; nylon bearings; chrome plated aluminum door latch; door strike and keeper with rubber bumper; and cast alloy chrome plated coat hook and bumper, . Provide latching devices and hinges for handicap compartments complying with 36 CFR 1191 and chrome-plated steel door latches that operate without either tight grasping or twisting of the wrist of the operator.
2.7 COLORS AND FINISHES
2.7.1 Colors
Provide color as indicated; colors listed are not intended to limit the selection of equal colors from other manufacturers.
Submit three samples showing color and a finished edge on two adjacent sides and core construction, each not less than 12 inch square.
2.7.2 Finishes
2.7.2.1 Finishes No. 4, No 4A and No. 5
Provide manufacturer's standard solid polyethylene (Finish 5) formed under high pressure rendering a single component section not less than 1 inch thick. Colors extend throughout the panel thickness.
PART 3 EXECUTION
3.1 PREPARATION
Take field measurements prior to the preparation of drawing and fabrication to ensure proper fits. Verify that field measurements, surfaces, substrates and conditions are as required, and ready to receive work. Verify correct spacing of plumbing fixtures. Verify correct location of built in framing, anchorage, and bracing. Report in writing to Contracting Officer prevailing conditions that adversely affect satisfactory execution of the work of this section. Do not proceed with work until unsatisfactory conditions have been corrected.
3.2 INSTALLATION
Do not install items that show visual evidence of biological growth.
Install partitions rigid, straight, plumb, and level, with the panels centered between the fixtures. Provide a panel clearance of not more than 1/2 inch and secure the panels to walls and pilasters with continuous full height wall brackets. Locate wall brackets so that holes for wall bolts occur in masonry or tile joints. Secure panels to pilasters with brackets matching the wall brackets. Provide for adjustment due to minor floor variations. Locate head rail joints at pilaster center lines. Install adjacent components for consistency of line and plane. Equip each door with hinges, one door latch, and one coat hook and bumper. Align hardware to uniform clearance at vertical edges of doors.
SECTION 10 21 13 Page 6
a. Secure panels to hollow plastered walls with toggle bolts using not less than 1/4-20 screws of the length required for the wall thickness. Provide toggle bolts with a load-carrying strength of not less than 600 pounds per anchor.
b. Secure panels to ceramic tile on hollow plastered walls or hollow concrete-masonry walls with toggle bolts using not less than 1/4-20 screws of the length required for the wall thickness. Provide toggle bolts with a load-carrying strength of not less than 600 pounds per anchor.
c. Secure panels to solid masonry or concrete with lead or brass expansion shields designed for use with not less than 1/4-20 screws, with a shield length of not less than 1-1/2 inches . Provide expansion shields with a load-carrying strength of not less than 600 pounds per anchor.
d. Submit Installation Drawings for toilet partitions, room entrance screens, and urinal screens showing plans, elevations, details of construction, hardware, reinforcing and blocking, fittings, mountings and escutcheons. Indicate on drawings the type of partition, location, mounting height, cutouts, and reinforcement required for toilet-room accessories.
3.3 OVERHEAD-BRACED PARTITIONS
Secure pilasters to the floor with the anchorage device specified. Make all leveling devices readily accessible for leveling, plumbing, and tightening the installation. Secure overhead brace to the pilaster face with not less than two fasteners per face. Expansion shields have a minimum 2 inch penetration into the concrete slab. Make tops of doors parallel with the overhead brace when doors are in a closed position.
3.4 FINAL ADJUSTMENT
After completion of the installation, make final adjustments to the pilaster-leveling devices, door hardware, and other working parts of the partition assembly. Doors have a uniform vertical edge clearance of approximately 3/16 inch and rest open at approximately 30 degrees when unlatched.
3.5 CLEANING
Touch up baked enamel and powder coat finish with the same color of paint that was used for the finish. Clean all surfaces and adjacent surfaces soiled as a result of the work, in an approved manner compliant with the manufacturer's recommended cleaning and protection from damage procedures until accepted. Remove all equipment, tools, surplus materials, and work debris from the site.
-- End of Section --
SECTION 10 21 13 Page 7
SECTION 10 26 00
WALL AND DOOR PROTECTION
08/20
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ALUMINUM ASSOCIATION (AA)
AA DAF45 (2003; Reaffirmed 2009) Designation System for Aluminum Finishes
ASTM INTERNATIONAL (ASTM)
ASTM A167 (2011) Standard Specification for Stainless and Heat-Resisting Chromium-Nickel Steel Plate, Sheet, and Strip
ASTM B221 (2021) Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes
ASTM D256 (2010; R 2018) Standard Test Methods for Determining the Izod Pendulum Impact Resistance of Plastics
ASTM D543 (2020) Standard Practices for Evaluating the Resistance of Plastics to Chemical Reagents
ASTM D635 (2018) Standard Test Method for Rate of Burning and/or Extent and Time of Burning of Plastics in a Horizontal Position
ASTM E84 (2023) Standard Test Method for Surface Burning Characteristics of Building Materials
ASTM G21 (2015; R 2021; E 2021) Standard Practice for Determining Resistance of Synthetic Polymeric Materials to Fungi
CALIFORNIA DEPARTMENT OF PUBLIC HEALTH (CDPH)
CDPH SECTION 01350 (2017; Version 1.2) Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources using Environmental Chambers
SECTION 10 26 00 Page 1
GREEN SEAL (GS)
GS-36 (2013) Adhesives for Commercial Use
SCIENTIFIC CERTIFICATION SYSTEMS (SCS)
SCS SCS Global Services (SCS) Indoor Advantage
SOCIETY OF AUTOMOTIVE ENGINEERS INTERNATIONAL (SAE)
SAE J1545 (2005; R 2014) Instrumental Color Difference Measurement for Exterior Finishes, Textiles and Colored Trim
SOUTH COAST AIR QUALITY MANAGEMENT DISTRICT (SCAQMD)
SCAQMD Rule 1168 (2017) Adhesive and Sealant Applications
UNDERWRITERS LABORATORIES (UL)
UL 2818 (2022) GREENGUARD Certification Program For Chemical Emissions For Building Materials, Finishes And Furnishings
1.2 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for information only. When used, a code following the "G" classification identifies the office that will review the submittal for the Government.
Submit the following in accordance with Section 01 33 00 SUBMITTAL
PROCEDURES:
SD-02 Shop Drawings
Corner Guards ; G
Wall Guards (Bumper Guards) ; G
SD-03 Product Data
Corner Guards ; G
Wall Guards ; G
Recycled content for aluminum component of corner guards ; S
Recycled content for steel component of corner guards ; S
Recycled content for aluminum component of wall guards, Combination Handrail/Wall guard and handrails ; S
SD-04 Samples
Finish ; G
SD-06 Test Reports
Corner Guards
SECTION 10 26 00 Page 2
Wall Guards
SD-07 Certificates
Corner Guards
Wall Guards
Indoor air quality for adhesives ; S
1.3 CERTIFICATIONS
1.3.1 Indoor Air Quality
1.3.1.1 Wall Covering and Panels
Provide sheet and high impact resistant resilient materials certified to meet indoor air quality requirements by UL 2818 (Greenguard) Gold, SCS Global Services Indoor Advantage Gold or provide certification or validation by other third-party program that products meet the requirements of this section. Provide current product certification documentation from certification body.
1.3.1.2 Adhesives and Sealants
Provide products certified to meet indoor air quality requirements by UL 2818 (Greenguard) Gold, SCS Global Services Indoor Advantage Gold or provide certification or validation by other third-party program that products meet the requirements of this section. Provide current product certification documentation from certification body. When product does not have certification, provide validation that product meets the indoor air quality product requirements cited herein.
1.4 DELIVERY, STORAGE, AND HANDLING
Deliver materials to the project site in manufacturer's original unopened containers with seals unbroken and labels and trademarks intact. Keep materials dry, protected from weather and damage, and stored under cover.
Store materials at approximately 70 degrees F for at least 48 hours prior to installation.
1.5 WARRANTY
Provide manufacturer's warranty to repair or replace defective materials and workmanship for a 1 year period of one year from date of final acceptance of the work.
PART 2 PRODUCTS
2.1 STANDARD PRODUCTS
To the maximum extent possible, provide wall and door protection items that are standard products of a single manufacturer and furnished as detailed. Drawings show general configuration of products required, and items differing in minor details from those shown are acceptable.
Submit detailed shop drawings of each wall and door protection item indicated. Include elevations, dimensions, clearances, details of
SECTION 10 26 00 Page 3 construction and anchorage, and details of joints and connections.
Submit manufacturers' descriptive product data for each wall and door protection item indicated. Include manufacturers' literature, finishes, profiles and thicknesses of materials.
Submit manufacturers' operations and maintenance data for each wall and door protection item indicated in accordance with Section 01 78 23
OPERATIONS AND MAINTENANCE DATA.
2.1.1 Resilient Material
Provide resilient material consisting of high impact resistant extruded acrylic vinyl, polyvinyl chloride, or injection molded thermal plastic conforming to the following:
2.1.1.1 Minimum Impact Resistance
Minimum impact resistance must be 18 ft-lbs/sq. inch when tested in accordance with ASTM D256, (Izod impact, ft-lbs per sq inch notched).
2.1.1.2 Fire Resistance Rating
Provide the following surface burning characteristics when tested and labeled in accordance with ASTM E84 by a qualified testing agency:
maximum flame spread of 25 and a smoke developed rating of 450 or less.
Provide material rated as self extinguishing when tested in accordance with ASTM D635. Provide resilient material used for protection on fire rated doors and frames listed by the qualified testing agency performing the tests. Provide resilient material installed on fire rated wood/steel door and frame assemblies tested on similar type assemblies. Test results of material tested on any other combination of door/frame assembly are not acceptable.
2.1.1.3 Integral Color
Provide colored components having integral color and matched in accordance with SAE J1545 to within plus or minus 1.0 on the CIE-LCH scales.
2.1.1.4 Chemical and Stain Resistance
Provide materials resistant to chemicals and stains reagents in accordance with ASTM D543.
2.1.1.5 Fungal and Bacterial Resistance
Provide materials resistant to fungi and bacteria in accordance with ASTM G21, as applicable.
2.2 CORNER GUARDS
2.2.1 Resilient Corner Guards
Provide surface mounted corner guards, radius formed to profile shown.
Corner guard height as indicated on the construction drawings. Furnish mounting hardware, cushions, and base plates. Provide assembly consisting of a snap-on corner guard formed from high impact resistant resilient material, mounted on a continuous aluminum retainer. Extruded aluminum retainer conforms to ASTM B221, alloy 6063, temper T5 or T6. Provide
SECTION 10 26 00 Page 4 aluminum components that contain a minimum of 35 percent recycled content. Provide data identifying percentage of recycled content for aluminum component of corner guards . Flush mounted type guards act as a stop for adjacent wall finish material. Furnish factory fabricated end closure caps for top and bottom of surface mounted corner guards. Provide flush mounted corner guards installed in fire rated wall that maintain the rating of the wall. Manufacturer to provide insulating materials that are an integral part of the corner guard system. Provide exposed metal portions of fire rated assemblies with a paintable surface.
2.2.2 Stainless Steel Corner Guards
Provide stainless steel base material that contains a minimum of 60 percent recycled content. Provide data identifying percentage of recycled content for steel component of corner guards . Fabricate stainless steel base material of 20 gauge thick material conforming to ASTM A167, type 430 or 304. Corner guard height as indicated on the construction drawings.
Form corner guard to dimensions shown.
2.3 WALL GUARDS
Provide product with prefabricated end closure caps, inside and outside corners, concealed splices, cushions, mounting hardware and other accessories standard with the manufacturer. Extruded continuous aluminum retainers must conform to ASTM B221, alloy 6063, temper T5 or T6. Provide aluminum components that contain a minimum of 35 percent recycled content. Provide data identifying percentage of recycled content for aluminum component of wall guards, combination handrail/wall guard and handrails . Field adjust all end caps and corners to assure close alignment.
2.3.1 Wall Guards, Combination Handrail/Wall Guards and Handrails
Wall guards, combination handrail/wall guards, and handrails must be provided with prefabricated end closure caps, inside and outside corners, concealed splices, cushions, mounting hardware and other accessories standard with the manufacturer. Extruded aluminum retainers must conform to ASTM B221, alloy 6063, temper T5 or T6. Provide aluminum components that contain a minimum of 35 percent recycled content. Provide data identifying percentage of recycled content for aluminum component of wall guards, combination handrail/wall guard and handrails. End caps and corners must be field adjustable to assure close alignment with handrails and wall guards. Wall guards must have profile as shown on drawings.
2.4 TRIM, FASTENERS AND ANCHORS
Provide vinyl trim, fasteners and anchors for each specific installation as indicated.
2.5 FINISH
Submit samples indicating color and texture of materials requiring color and finish.
2.5.1 Aluminum Finish
Provide aluminum finish accordance with AA DAF45; exposed aluminum with designation AA-C22A31 chemically etched medium matte, with clear anodic coating . Provide Class II architectural coating that is 0.4 mil thick.
SECTION 10 26 00 Page 5
Provide concealed aluminum with mill finish as fabricated, uniform in natural color and free from surface blemishes.
2.5.2 Stainless Steel Finish
Provide stainless steel finish in accordance with ASTM A167, Type 302 or 304, finish number 4.
2.5.3 Resilient Material Finish
Provide resilient material finish of embossed velour stipple texture with colors in accordance with SAE J1545 .
2.6 ADHESIVES
Provide adhesive for resilient material in accordance with manufacturers recommendations. Provide sealants and non-aerosol adhesive products used on the interior of the building (defined as inside of the weatherproofing system) that meet either emissions requirements of CDPH SECTION 01350 (limit requirements for either office or classroom spaces regardless of space type) the VOC content requirements of SCAQMD Rule 1168 , or VOC content requirements of GS-36. Provide certification of indoor air quality for adhesives .
2.7 COLOR
Color must be as indicated.
PART 3 EXECUTION
3.1 INSTALLATION
Do not install items that show visual evidence of biological growth.
Install items on surfaces that are clean, smooth, and free of obstructions.
3.1.1 Corner Guards and Wall Guards (Bumper Guards)
a. Mount guards as indicated and in accordance with manufacturer's written installation instructions.
b. For wall guards, space brackets at no more than 3 feet on centers and anchor to the wall in accordance with the manufacturer's written installation instructions.
3.1.1.1 Stainless Steel Guards
a. Mount guards as indicated and in accordance with manufacturer's recommendations.
b. Where corner guards are installed on gypsum board, clean surfaces and anchor guards with a neoprene solvent-type contact adhesive specifically manufactured for use on gypsum board construction.
Remove excess adhesive from the guard edges and allow to cure undisturbed for 24 hours.
c. For wall guards, space brackets at no more than 3 feet on center and anchor to the wall in accordance with the manufacturer's installation instructions.
SECTION 10 26 00 Page 6
-- End of Section --
SECTION 10 26 00 Page 7
SECTION 10 28 13
TOILET ACCESSORIES
08/20
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
U.S. DEPARTMENT OF DEFENSE (DOD)
MIL-STD-1691 (1994; Rev F) Construction and Material Schedule for Military Medical and Dental Facilities
1.2 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for information only. When used, a code following the "G" classification identifies the office that will review the submittal for the Government.
Submit the following in accordance with Section 01 33 00 SUBMITTAL
PROCEDURES:
SD-02 Shop Drawings
Product Schedule ; G
Submit product Schedule indicating types, quantities, sizes, and installation locations by room for each toilet accessory item required. Identify locations using room designations indicated on the drawings.
SD-03 Product Data
Recycled content for stainless steel toilet accessories ; S
Item A5082 Dispenser, Paper Towel, Sensor, Hands Free; G
Item A5109 Grab Bar, 1-1/4 inch Dia., SS, 2 Wall, W/C Accessible; G
Item A5135 Shelf, Utility W/ Mop/Broom Holders, SS, Surf Mntd; G
Item A5200 Dispenser, Toilet Tissue, SS, 2-Roll, Surface Mntd; G
Submit catalog numbers, literature, data sheets, construction details, profiles, anchoring and mounting requirements ,including cutouts in other work and substrate preparation, and other pertinent data for each toilet accessory item to evaluate function, materials, dimensions and appearance.
SD-10 Operation and Maintenance Data
SECTION 10 28 13 Page 1
Item A5082 Dispenser, Paper Towel, Sensor, Hands Free; G
Item A5109 Grab Bar, 1-1/4 inch Dia., SS, 2 Wall, W/C Accessible; G
Item A5135 Shelf, Utility W/ Mop/Broom Holders, SS, Surf Mntd; G
Item A5200 Dispenser, Toilet Tissue, SS, 2-Roll, Surface Mntd; G
Submit Data Package 1 for each toilet accessory item in accordance with Section 01 78 23 OPERATIONS AND MAINTENANCE DATA.
1.3 DELIVERY, STORAGE, AND HANDLING
Wrap toilet accessories for shipment and storage, then deliver to the jobsite in manufacturer's original packaging, and store in a clean, dry area protected from construction damage and vandalism.
1.4 WARRANTY
Provide manufacturer's warranty to repair or replace defective materials and workmanship for a period of one year from date of final acceptance of the work..
PART 2 PRODUCTS
2.1 ACCESSORY ITEMS
Provide toilet accessories where indicated in accordance with Contractor-provided product schedule . Conform to the requirements for accessory items specified herein which are based on MIL-STD-1691 Joint Schedule Numbers (JSN). Provide each accessory item complete with the necessary mounting plates of sturdy construction with corrosion resistant surface.
Provide stainless steel products listed herein manufactured from materials containing a minimum of 50 percent recycled content. Provide data identifying percentage of recycled content for stainless steel toilet accessories .
2.1.1 Anchors and Fasteners
Provide corrosion-resistant anchors and fasteners capable of developing a restraining force commensurate with the strength of the accessory to be mounted and suited for use with the supporting construction. Provide tamperproof design exposed fasteners with finish to match the accessory.
Provide fasteners proposed for use for each type of wall construction and mounting.
2.1.2 Finishes
Except where noted otherwise, provide the following finishes on metal:
Metal Finish
Stainless steel No. 4 satin finish
SECTION 10 28 13 Page 2
Metal Finish
Carbon steel, copper alloy, and brass Chromium plated, bright
2.1.3 Item A5082 Dispenser, Paper Towel, Sensor, Hands Free
Surface mounted paper towel dispenser with hands free operation. Unit made of high impact plastic in a dark translucent color. Unit has the capacity of one standard 8 inch wide by 8 inch diameter 800 ft roll with optional paper length settings. Unit is battery operated by four "D" size alkaline batteries, and have low battery indicator light, or optional AC power adapter. Unit has keyed lock.
Approximate size: 12 inches wide by 15 inches high by 10 inches deep.
2.1.4 Item A5109 Grab Bar, 1-1/4 Inch Diameter, SS, 2 Wall, W/C Accessible
Grab bar of 1-1/4 inch diameter satin finish stainless steel with peened gripping surface for use in toilet stall/room. Snap-on flange covers for concealed mounting are stainless steel and equipped with two screw holes for attachment to wall. Grab bars designed to meet and exceed ADA requirements for structural strength. Grab bars designed to withstand loads of 900 pounds when properly installed. Clearance from wall to grab bar is 1-1/2 inches to meet ADA and ANSI codes.
2.1.5 Item A5135 Shelf, Utility W/ Mop/Broom Holders, SS, Surf Mounted
Surface mounted mop/broom holder with shelf made of 18 gauge stainless steel with all exposed surfaces in satin finish. Unit has shelf 8 inches deep with shelf support brackets of satin finish stainless steel welded to mounting base, and a minimum of 3 hooks/3 holders. Mop holders have spring-loaded rubber cams and hold mop or broom handle with a diameter between 5/8 inch and 1 inch .
Approximate size: 36 inches wide by 8 inches deep.
2.1.6 Item A5200 Dispenser, Toilet Tissue, SS, 2-Roll, Surface Mounted
Concealed surface mounted, double roll, toilet tissue dispenser of stainless steel. Unit holds and dispenses two standard 5-1/4 inch diameter rolls of toilet tissue.