The solicitation number is W912QR24R0046 for the "ARCENT Readiness Training Center Microgrid Project - Camp Buehring, Kuwait". The intent is to select a single contractor to provide construction services for a microgrid installation. The Government will evaluate proposals and award a firm fixed price contract to the responsible offeror representing the best value. The project involves a 1.5 MW/1.5 MWhr battery energy storage system (BESS), a 700 kW solar PV system, a 1.5 MW generator, and associated electrical equipment and infrastructure. The one-line diagram provides details on the major electrical components, ratings, and interconnections. The U.S. Army Corps of Engineers, Louisville District is the procuring agency for this opportunity.
View the file
Other files
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A1
SCALE: N.T.S.
ELECTRICAL ONE-LINE DIAGRAM
DIRECT BURIAL
& 35mm2 GND
3-300mm2 (MV 105) BOX (SB)
SECTIONALIZING
EXISTING
95mm2 GEC
& 150mm2 GND)
5 SETS OF (4-300mm2
POI SEE NOTE 4
95mm2 GEC
CONDUCTOR
GROUNDING
SUPPLY SIDE
8 AND 9
SEE NOTE
& 150mm2 GND
4-300mm2
C A
M P
B U
E H
R
IN
G
K U
W A
IT
E R
C
IP
F Y
Z O
N E
S O
L A
R P
V a n d
.5
M W
/1 .5
M W
H R
B E
S S
I N
S T
A L
L A
T
IO
N
M
IC
R O
G R
ID
P
R O
J E
C T
K
W
B R
IA
N
R
J O
H N
S O
N
P .E
T .L
.C
-5
M O
H A
M M
E D
M A
A R
O O
F
P .E
B .R
.J
J A
N U
A R
Y
C E
R T
IF
IE
D F
IN
A
L
D
IS
T R
IC
T
K
U W
A
IT
T R
A N
S A
T L
A N
T
IC
E X
P E
D
IT
IO
N
A R
Y
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
D A
T E
DISTRICT
EXPEDITIONARY
TRANSATLANTIC
of Engineers
US Army Corps
A N
S I
D
P R
O J E
C T
N O
F
IL
E N
A M
E
C K
D B
Y
D E
S C
R
IP
T
IO
N M
A R
K A
P P
R
F
IL
E N
U M
B E
R
S I Z
E
S U
B M
IT
T
E D
B Y
P L
O T
S C
A L
E P
L O
T D
A T
E
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
C O
N T
R A
C T
N O
IDENTIFICATION
SHEET
D A
T E
A P
P R
D E
S
IG
N E
D B
Y
D W
N B
Y
R
Q
P
N
M
L
K
J
H
G
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
W X
X X
X X
-X X
-X -X
X X
E-601
O N
E -L
IN
E
D
IA
G R
A M
E L
E C
T R
IC
A
L
N .T
.S
100% RATED
3P, GFP
1800AT
2000AF
PROPOSED MSB 415/240V, 6000A, 3PH, 4W, 100 kAIC
GFP
3P
4000AT
4000AF
1.5 MW GENERATOR
PROPOSED
3P
300 AT
300 AF
GFP
3P
4000AT
4000AF
PROPOSED AC COMBINER SWITCHBOARD 415/240V, 4W, 4000A, 3PH, 100kAIC
3P
200 AT
200 AF
3P
300 AT
300 AF
3P
150 AT
200 AF
3P
150 AT
200 AF
3P
200 AT
200 AF
RATED
100%
3P, GRP
2500 AT
2500 AF
INVERTER
1500KW
LITHIUM-ION
BATTERY STORAGE
& 185mm2 GND)
7 SETS OF (4-240mm2
& 16mm2 GND
4/C-95mm2
& 16mm2 GND
4/C-50mm2
& 16mm2 GND
4/C-50mm2
& 25mm2 GND
4/C-150mm2
& 16mm2 GND
4/C-50mm2
(4- 400mm2 + 240mm2 GND)
8 SETS OF
SECONDARY SIDE.
FAULT AMPS AT
42k AVAILABLE
COMPACT SUBSTATION
COMBINED TRANSFORMER
5% IMPEDANCE
11kV-415/240V, PROPOSED 1500kVA
NEMA 4 450 KVA 50HZ TO 60 HZ FREQUENCY CONVERTER. 5.
SWITCHBOARD.
TO CIRCUIT BREAKER AT THE END OF THE BUS OF THE MSB
LOADSIDE CONNECTION: CONTRACTOR TO INTERCONNECT 4.
SIDE INTERCONNECTION.
NATIONAL ELECTRIC CODE (NEC), SECTION 705.12, LOAD
COMPLY WITH ALL RELEVANT SECTIONS OF THE 2020
NEW SWITCHGEAR, SWITCHBOARD, AND INVERTERS SHALL 3.
RATED NEMA 4.
ALL NEW EXTERIOR ELECTRICAL ENCLOSURES SHALL BE 2.
EQUIPMENT.
PT'S, CT'S AND OTHER REQUIRED SYSTEM CONTROLS
CONTRACTOR SHALL PROVIDE ALL NEW METERS, RELAYS, 1.
NOTES
SHALL BE RATED NEMA 4.
ALL NEW EXTERIOR ELECTRICAL ENCLOSURES 10.
DEMAND LOADS OVER PV AND BESS CAPACITY.
GENERATOR WHEN ISLANDING MODE ACTIVATED AND
CIRCUIT BREAKER CONTROL SHALL ENERGIZE THE 9.
MEANS.
BESS ISLANDING CONTROLLER OR BE OTHER CONTROL
ISLANDING MODE INITIATED. TO BE CONTROLLED BY
UPSTREAM MAIN CIRCUIT BREAKERS OPEN WHEN
BREAKERS. CIRCUIT BREAKERS TO CLOSE WHEN
SYNCHING CAPABLE AND CONTROLLED CIRCUIT 8.
CONTROLLED BY ISLANDING CONTROLLER.
CONTROL BREAKER (GRID DISCONNECT) TO BE 7.
AND AC SIDE OF THE INVERTER(S).
APPLY SPDs (SURGE PROTECTION DEVICE) ON THE DC 6.
3P
200A
3P
(N)
MTS
100A
G17
(E)
MTS
200A
(N)
MTS
100A
G15
(N)
MTS
100A
G14
(N)
MTS
100A
G13
(N)
MTS
800A
G12
(N)
MTS
100A
G11
(N)
MTS
800A
G10
(N)
MTS
100A
G8
(N)
MTS
100A
G9
(N)
MTS
400A
G7
(N)
MTS
800A
G6
(N)
MTS
200A
G5
(N)
MTS
200A
G4
(N)
MTS
200A
G3
(N)
MTS
200A
G2
(E)
MTS
400A
G1
(N)
MTS
100A
G18
3P
3P
3P
3P
3P
3P
3P
3P
3P
3P
3P
3P
3P
3P
3P
3P
3P
(SEE NOTE 5)
CONVERTER
FREQ.
LOADS FEEDRE SCHEDULE
INVERTER
150KW
INVERTER
75KW
INVERTER
150KW
INVERTER
75KW
INVERTER
75KW
INVERTER
100KW
RATED
100%
RATED
100%
NEEDED.
CHARGED AT NIGHT BY CAMP POWER IF
SYSTEM DURING THE DAY. BESS COULD BE
BESS SHALL BE CHARGED BY THE PV SOLAR d.
LOAD HOURS AND/OR AS NEEDED.
SHAVING AND DISCHARGE DURING PEAK
THE BESS SHALL UTILIZED FOR PEAK c.
LOAD DURING DAYLIGHT HOURS.
THE PV SOLAR SYSTEM SHALL SUPPORT THE b.
POWER SOURCE
CAMP'S POWER SHALL BE THE PRIMARY a.
POWER.
<=80% OF MICRO-GRID'S GENERATING
GENERATOR TO SHUT DOWN IF THE LOAD IS f.
MODE.
SHALL ENERGIZED DURING ISLANDING
THE GENERATOR AND THE MICROGRID e.
SYSTEM OPERATION
240M<L
169M<L
201M<L
203M<L
403M<L
285M<L
20M<L
RVTT BUILDING B606 BUILDING B610 BUILDING B608 BUILDING B611CARPORT - 1
L
M
V D
.8
G16
L
M
V D
.9
L
M
V D
.1
L
M
V D
.2
L
M
V D
.9
L
M
V D
.5
L
M
V D
.1
L
M
V D
.6
L
M
V D
.2
L
M
V D
.4
L
M
V D
.2
L
M
V D
.8
L
M
V D
.5
L
M
V D
.7
L
M
V D
.1
L
M
V D
.5
L
M
V D
.3
L
M
V D
.2
RATED
3P, 100%
1800AT
2000AF
4-300mm2+35mm2 GND IN 1-103 C
4-95mm2+16mm2 GND
4-50mm2+16mm2 GND
2 SET (4-185mm2+70mm2 GND)
4-150mm2+25mm2 GND
4-35mm2+10mm2 GND
4-70mm2+25mm2 GND
GFPE
GFPE
DIRECT BURIAL
DIRECT BURIAL
DIRECT BURIAL
DIRECT BURIALDIRECT BURIALDIRECT BURIALDIRECT BURIAL
DIRECT BURIALDIRECT BURIAL
& 25mm2 GND
4/C-150mm2
DIRECT BURIAL
& 25mm2 GND
4/C-150mm2
DIRECT BURIAL
& 25mm2 GND
4/C-150mm2
INVERTER
100KW
CARPORT - 2 & 3