This document provides details for a federal contract opportunity to construct a high-bay aircraft maintenance hangar at Westover Air Reserve Base in Massachusetts. The proposed project includes demolishing an existing building and constructing a new hangar with a reinforced concrete foundation and floor slab, masonry exterior walls for the office area and metal sandwich panels for the hangar area. The project also includes electrically operated hangar doors, a structural steel frame, an architecturally compatible roof, fire protection and alarm systems, utilities, secure and non-secure communications, site improvements, and other necessary support. The contract duration is estimated at 730 calendar days with an estimated cost range of $25-100 million. The solicitation number is W912QR20R0059 and was issued by the Department of the Army Corps of Engineers Engineering District Louisville. The NAICS code is 236220.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Solicitation For Regional ISO Maintenance Hangar Westover Air Reserve Base, MA
P2: 472183
Design Bid Build
Specifications Vol. 3 of 4 Certified Final Submittal
11 August 2020
W912QR20R0059
ARIMS: 200A
Disposition: Maintain for 15yrs after construction
W912QR20R0059-0001
This page was intentionally left blank for duplex printing.
Westover Air Reserve Base, MA
Project Number: YTPM099001B P2#: 472183
Certified Final Submittal Specifications
Volume III
July 2020
BMcD PN 109519
Louisville District
Westover Air Reserve Base, MA
Project Number: YTPM099001B
P2#: 472183
July 2020 Burns & McDonnell 9400 Ward Parkway
Kansas City, MO 64114
CERTIFICATION PAGE
CIVIL STRUCTURAL ARCHITECTURAL
FIRE PROTECTION MECHANICAL ELECTRICAL
07/31/2020
07/31/2020 07/31/2020
07/31/2020
C5: 109519; ISO HANGAR
Westover AFRB, MA
109519
PROJECT TABLE OF CONTENTS Page 1
PROJECT TABLE OF CONTENTS
VOLUME I of IV
DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS
00 80 00.00 06 SPECIAL PROVISIONS
DIVISION 01 - GENERAL REQUIREMENTS
01 32 01.00 06 PROJECT SCHEDULE
01 33 00.00 06 SUBMITTAL PROCEDURES
01 33 29.00 06 SUSTAINABILITY REPORTING
01 35 26.00 06 GOVERNMENT SAFETY REQUIREMENTS
01 42 00 SOURCES FOR REFERENCE PUBLICATIONS
01 45 00.15 10 RESIDENT MANAGEMENT SYSTEM CONTRACTOR MODE (RMS CM)
01 45 04.10 06 CONTRACTOR QUALITY CONTROL
01 45 35 SPECIAL INSPECTIONS
01 46 00.00 06 TOTAL BUILDING COMMISSIONING (CONTRACTOR CxA)
01 50 00 TEMPORARY CONSTRUCTION FACILITIES AND CONTROLS
01 57 19.00 06 TEMPORARY ENVIRONMENTAL CONTROLS AND PERMITS
01 74 19 CONSTRUCTION AND DEMOLITION WASTE MANAGEMENT
01 78 23 OPERATION AND MAINTENANCE DATA
DIVISION 02 - EXISTING CONDITIONS
02 41 00 DEMOLITION
02 61 13 EXCAVATION AND HANDLING OF CONTAMINATED MATERIAL
02 81 00 TRANSPORTATION AND DISPOSAL OF HAZARDOUS MATERIALS
02 82 00 ASBESTOS REMEDIATION
02 83 13.00 06 LEAD IN CONSTRUCTION
DIVISION 03 - CONCRETE
03 11 13.00 10 STRUCTURAL CAST-IN-PLACE CONCRETE FORMING
03 15 00.00 10 CONCRETE ACCESSORIES
03 20 00.00 10 CONCRETE REINFORCING
03 30 00.00 10 CAST-IN-PLACE CONCRETE
03 35 00.00 10 CONCRETE FINISHING
03 39 00.00 10 CONCRETE CURING
DIVISION 04 - MASONRY
04 20 00 UNIT MASONRY
DIVISION 05 - METALS
05 05 23.16 STRUCTURAL WELDING
05 12 00 STRUCTURAL STEEL
05 21 00 STEEL JOIST FRAMING
05 30 00 STEEL DECKS
05 40 00 COLD-FORMED METAL FRAMING
05 50 13 MISCELLANEOUS METAL FABRICATIONS
05 51 33 METAL LADDERS
05 52 00 METAL RAILINGS
DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES
06 10 00 ROUGH CARPENTRY
06 41 16.00 10 PLASTIC-LAMINATE-CLAD ARCHITECTURAL CABINETS
PROJECT TABLE OF CONTENTS Page 2
06 61 16 SOLID SURFACING FABRICATIONS
VOLUME II of IV
DIVISION 07 - THERMAL AND MOISTURE PROTECTION
07 05 23 PRESSURE TESTING AN AIR BARRIER SYSTEM FOR AIR TIGHTNESS
07 11 13 BITUMINOUS DAMPPROOFING
07 21 13 BOARD AND BLOCK INSULATION
07 21 16 MINERAL FIBER BLANKET INSULATION
07 22 00 ROOF AND DECK INSULATION
07 27 10.00 10 BUILDING AIR BARRIER SYSTEM
07 27 19.01 SELF-ADHERING AIR BARRIERS
07 27 26 FLUID-APPLIED MEMBRANE AIR BARRIERS
07 42 13 METAL WALL PANELS
07 42 63 FABRICATED WALL PANEL ASSEMBLIES
07 60 00 FLASHING AND SHEET METAL
07 61 14.00 20 STEEL STANDING SEAM ROOFING
07 72 13 PREFABRICATED ROOF CURBS
07 84 00 FIRESTOPPING
07 92 00.00 06 JOINT SEALANTS
07 95 00 EXPANSION CONTROL
DIVISION 08 - OPENINGS
08 11 13 STEEL DOORS AND FRAMES
08 33 13 COILING COUNTER DOORS
08 34 16.10 STEEL SLIDING HANGAR DOORS
08 34 19.10 20 ROLLING SERVICE AND FIRE DOORS
08 41 13 ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS
08 51 13 ALUMINUM WINDOWS
08 71 00 DOOR HARDWARE
08 81 00 GLAZING
08 91 00 METAL WALL LOUVERS
DIVISION 09 - FINISHES
09 06 00 SCHEDULES FOR FINISHES
09 22 00 SUPPORTS FOR PLASTER AND GYPSUM BOARD
09 29 00 GYPSUM BOARD
09 51 00 ACOUSTICAL CEILINGS
09 65 00 RESILIENT FLOORING
09 67 23.16 FUEL RESISTIVE RESINOUS FLOORING, 5-COAT SYSTEM
09 68 00 CARPETING
09 90 00 PAINTS AND COATINGS
09 97 13.27 EXTERIOR COATING OF STEEL STRUCTURES
DIVISION 10 - SPECIALTIES
10 14 00.10 EXTERIOR SIGNAGE
10 14 00.20 INTERIOR SIGNAGE
10 14 53 TRAFFIC SIGNAGE
10 21 13 TOILET COMPARTMENTS
10 22 13 WIRE MESH PARTITIONS
10 26 00 WALL AND DOOR PROTECTION
10 28 13 TOILET ACCESSORIES
10 51 13 METAL LOCKERS
PROJECT TABLE OF CONTENTS Page 3
DIVISION 11 - EQUIPMENT
11 01 50 RIGID RAIL FALL PROTECTION SYSTEMS
DIVISION 12 - FURNISHINGS
12 21 00 WINDOW BLINDS
12 36 00 COUNTERTOPS
12 50 00.13 10 FURNITURE AND FURNITURE INSTALLATION
12 59 00 SYSTEMS FURNITURE
DIVISION 13 - SPECIAL CONSTRUCTION
13 34 20 PRE-ENGINEERED METAL FUELING CANOPIES
DIVISION 21 - FIRE SUPPRESSION
21 13 13.00 10 WET PIPE SPRINKLER SYSTEMS, FIRE PROTECTION
21 13 18.00 10 PREACTION SPRINKLER SYSTEMS, FIRE PROTECTION
21 13 25.00 10 HIGH EXPANSION FOAM (HI EX. HEF) FIRE PROTECTION SYSTEM
21 30 00 FIRE PUMPS
DIVISION 22 - PLUMBING
22 00 00 PLUMBING, GENERAL PURPOSE
22 05 48.00 20 MECHANICAL SOUND, VIBRATION, AND SEISMIC CONTROL
DIVISION 23 - HEATING, VENTILATING, AND AIR CONDITIONING (HVAC)
23 00 00 AIR SUPPLY, DISTRIBUTION, VENTILATION, AND EXHAUST SYSTEMS
23 03 00.00 20 BASIC MECHANICAL MATERIALS AND METHODS
23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC
23 07 00 THERMAL INSULATION FOR MECHANICAL SYSTEMS
23 09 00 INSTRUMENTATION AND CONTROL FOR HVAC
23 09 13 INSTRUMENTATION AND CONTROL DEVICES FOR HVAC
23 09 23.02 BACNET DIRECT DIGITAL CONTROL FOR HVAC AND OTHER BUILDING
CONTROL SYSTEMS
23 11 25 FACILITY GAS PIPING
23 21 23 HYDRONIC PUMPS
23 23 00 REFRIGERANT PIPING
23 52 00 HEATING BOILERS
23 64 26 HEATING WATER PIPING SYSTEMS
23 81 00 DECENTRALIZED UNITARY HVAC EQUIPMENT
23 82 00.00 20 TERMINAL HEATING UNITS
VOLUME III of IV
DIVISION 25 - INTEGRATED AUTOMATION
25 10 10 UTILITY MONITORING AND CONTROL SYSTEM (UMCS) FRONT END
AND INTEGRATION
DIVISION 26 - ELECTRICAL
26 00 00.00 20 BASIC ELECTRICAL MATERIALS AND METHODS
26 08 00 APPARATUS INSPECTION AND TESTING
26 20 00 INTERIOR DISTRIBUTION SYSTEM
26 24 13 SWITCHBOARDS
26 28 01.00 10 COORDINATED POWER SYSTEM PROTECTION
PROJECT TABLE OF CONTENTS Page 4
26 29 23 VARIABLE FREQUENCY DRIVE SYSTEMS UNDER 600 VOLTS
26 35 43 400-HERTZ (HZ) SOLID STATE FREQUENCY CONVERTER
26 41 00 LIGHTNING PROTECTION SYSTEM
26 51 00 INTERIOR LIGHTING
26 56 00 EXTERIOR LIGHTING
DIVISION 27 - COMMUNICATIONS
27 10 00 BUILDING TELECOMMUNICATIONS CABLING SYSTEM
DIVISION 28 - ELECTRONIC SAFETY AND SECURITY
28 31 76 INTERIOR FIRE ALARM AND MASS NOTIFICATION SYSTEM
DIVISION 31 - EARTHWORK
31 00 00.00 06 EARTHWORK
31 11 00 CLEARING AND GRUBBING
31 31 16.13 CHEMICAL TERMITE CONTROL
DIVISION 32 - EXTERIOR IMPROVEMENTS
32 01 11.51 PAINT REMOVAL FROM AIRFIELD PAVEMENTS
32 01 16.71 COLD MILLING ASPHALT PAVING
32 01 19 FIELD MOLDED SEALANTS FOR SEALING JOINTS PAVEMENTS
32 11 23 GRADED CRUSHED AGGREGATE AND AGGREGATE BASE COURSES
32 12 13 BITUMINOUS TACK AND PRIME COATS
32 12 15.13 ASPHALT PAVING FOR AIRFIELDS
32 12 16 HOT-MIX ASPHALT (HMA) FOR ROADS
32 13 13.06 PORTLAND CEMENT CONCRETE PAVEMENT FOR ROADS AND SITE
FACILITIES
32 13 14.13 CONCRETE PAVING FOR AIRFIELDS AND OTHER HEAVY DUTY
PAVEMENTS
32 16 19 CONCRETE CURBS, GUTTERS AND SIDEWALKS
32 17 23 PAVEMENT MARKINGS
32 31 13.53 HIGH-SECURITY CHAIN LINK FENCES AND GATES
32 92 19 SEEDING
DIVISION 33 - UTILITIES
33 11 00 WATER UTILITY DISTRIBUTION PIPING
33 30 00 SANITARY SEWERAGE
33 40 00 STORM DRAINAGE UTILITIES
33 51 15 NATURAL-GAS / LIQUID PETROLEUM GAS DISTRIBUTION
33 52 10 FUEL SYSTEMS PIPING (SERVICE STATION)
33 52 23.15 POL SERVICE PIPING WELDING
33 71 02 UNDERGROUND ELECTRICAL DISTRIBUTION
33 82 00 TELECOMMUNICATIONS OUTSIDE PLANT (OSP)
DIVISION 41 - MATERIAL PROCESSING AND HANDLING EQUIPMENT
41 22 13.15 BRIDGE CRANES, OVERHEAD ELECTRIC, UNDER RUNNING
DIVISION 46 - WATER AND WASTEWATER EQUIPMENT
46 25 14 COALESCING OIL-WATER SEPARATORS
PROJECT TABLE OF CONTENTS Page 5
VOLUME IV of IV
APPENDIX A DRAFT SWPPP
APPENDIX B ENVIRONMENTAL REPORTS
APPENDIX C BUILDING 2426 PROJECT REFERENCE DOCUMENTS
APPENDIX D OWNER'S PROJECT REQUIREMENTS DOCUMENT
APPENDIX E BASIS OF DESIGN Cx
-- End of Project Table of Contents --
C5: 109519; ISO HANGAR 109519
SECTION 25 10 10
UTILITY MONITORING AND CONTROL SYSTEM (UMCS) FRONT END AND INTEGRATION
11/15
PART 1 GENERAL
1.1 SUMMARY
Provide a Utility Monitoring and Control System (UMCS) which performs supervisory monitoring and supervisory control of building control systems and utility control systems using: ASHRAE 135 (BACnet) Tridium Niagara N4 per base standards. Integrate ASHRAE 135 (BACnet) field control systems installed per Section 23 09 23.02 BACNET DIRECT DIGITAL CONTROL FOR HVAC AND OTHER BUILDING CONTROL SYSTEMS as specified.
1.1.1 System Requirements
Provide a UMCS as specified and indicated, and in accordance with the following characteristics:
1.1.1.1 General System Requirements
a. The system performs supervisory monitoring and control functions including but not limited to Scheduling, Alarm Handling, Trending, Overrides, Report Generation, and Electrical Demand Limiting as specified.
b. The system includes a Graphical User Interface which allows for graphical navigation between systems, graphical representations of systems, access to real-time data for systems, ability to override points in a system, and access to all supervisory monitoring and control functions.
c. All software used by the UMCS and all software used to install and configure the UMCS is licensed to and delivered to the installation.
d. All necessary documentation, configuration information, configuration tools, programs, drivers, and other software is licensed to and otherwise remains with the Government such that the Government or their agents are able to repair, replace, upgrade, and expand the system without subsequent or future dependence on the Contractor.
Software licenses must not require periodic fees and must be valid in perpetuity.
e. Provide sufficient documentation and data, including rights to documentation and data, such that the Government or their agents can execute work to repair, replace, upgrade, and expand the system without subsequent or future dependence on the Contractor.
f. The UMCS interfaces directly to ASHRAE 135, CEA-709.1-D , MODBUS Protocol , MODBUS TCP/IP, OPC DA, and Niagara Framework field control systems as specified and may interface to field control systems using other protocols via an M&C Software protocol driver or a Gateway.
g. For UMCS systems with Monitoring and Control Software functionality
SECTION 25 10 10 Page 1 implemented in Monitoring and Control (M&C) Controller Hardware, provide sufficient additional controller hardware to support the full capacity requirements as specified.
1.1.1.2 BACnet Requirements
a. The UMCS must be capable of future communication using ASHRAE 135 Annex J over the Government furnished IP network as specified.
b. All communication between the UMCS and ASHRAE 135 field control networks must be via the ASHRAE 135 protocol.
c. All communication between the M&C Software and the field control system devices must be via standard ASHRAE 135 services other than PrivateTransfer and ConfirmedPrivateTransfer except as follows:
(1) PrivateTransfer and ConfirmedPrivateTransfer may be used for device configuration and device programming.
(2) PrivateTransfer and ConfirmedPrivateTransfer may be used for communication between the M&C Software and the field control system if and only if both the M&C Software and the field control system devices automatically (without requiring reconfiguration) revert to the use of other standard ASHRAE 135 services when one of the components is modified or replaced.
1.1.2 General Cybersecurity Requirements
Address cybersecurity in accordance with AF ETL 11-1 .
1.1.3 Symbols, Definition and Abbreviations
Use symbols, definitions, and engineering unit abbreviations indicated in the Contract Drawings for displays, submittals, and reports. For symbols, definitions and abbreviations not in the Contract Drawings use terms conforming at a minimum to IEEE Stds Dictionary and the ASHRAE FUN IP , as applicable.
1.1.4 System Units and Accuracy
Use English (inch-pound) units for displays, print-outs, and calculations. Perform calculations with an accuracy of at least three significant figures. For displays and printouts present values to at least three significant figures.
1.1.5 Data Packages/Submittals Requirements
Technical data packages consisting of computer software and technical data (meaning technical data which relates to computer software) which are specifically identified in this Project and which may be defined/required in other Specifications must be delivered strictly in accordance with the Contract Clauses and in accordance with the Contract Data Requirements List, DD Form 1423. Data delivered must be identified by reference to the particular Specification Paragraph against which it is furnished. All submittals not specified as technical data packages are considered Shop Drawings under the Federal Acquisition Regulation Supplement (FARS) and must contain no proprietary information and must be delivered with unrestricted rights.
SECTION 25 10 10 Page 2
1.2 REFERENCES
The publications listed below form a part of this Specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)
ANSI INCITS 154 (1988; R 2004) Office Machines and Supplies - Alphanumeric Machines - Keyboard Arrangement
AMERICAN SOCIETY OF HEATING, REFRIGERATING AND AIR-CONDITIONING
ENGINEERS (ASHRAE)
ASHRAE 135 (2016; INT 1 2016; ERTA 1 2016) BACnet—A Data Communication Protocol for Building Automation and Control Networks
ASHRAE FUN IP (2017) Fundamentals Handbook, I-P Edition
CONSUMER ELECTRONICS ASSOCIATION (CEA)
CEA-709.1-D (2014) Control Network Protocol Specification
CEA-852-C (2014) Tunneling Component Network Protocols Over Internet Protocol Channels
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE 1815 (2015; CORR 2016) Exchanging Information Between Networks Implementing IEC 61850 and IEEE Std 1815 Distributed Network Protocol (DNP3)
IEEE 802.11 WARNING: Text in tags exceeds the maximum length of 300 characters
IEEE C62.41 (1991; R 1995) Recommended Practice on Surge Voltages in Low-Voltage AC Power Circuits
IEEE Stds Dictionary (2009) IEEE Standards Dictionary: Glossary of Terms & Definitions
INTERNET ENGINEERING TASK FORCE (IETF)
IETF RFC 7465 (2015) Prohibiting RC4 Cipher Suites
RFC 821 (2001) Simple Mail Transfer Protocol (SMTP)
LONMARK INTERNATIONAL (LonMark)
LonMark Interoperability Guide (2005) LonMark Application-Layer Interoperability Guide and LonMark Layer 1-6 Interoperability Guide; Version 3.4
LonMark SNVT List (2014) LonMark SNVT Master List; Version 15
SECTION 25 10 10 Page 3
LonMark XIF Guide (2001) LonMark External Interface File Reference Guide; Revision 4.402
MODBUS ORGANIZATION, INC (MODBUS)
MODBUS Protocol (2012) Modbus Application Protocol Specification; Version 1.1b3
MODBUS TCP/IP (2006) Modbus Messaging on TCP/IP Implementation Guide; Version V1.0b
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
NEMA 250 (2014) Enclosures for Electrical Equipment (1000 Volts Maximum)
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 262 (2015) Standard method of Test for Flame Travel and Smoke of Wires and Cables for Use in Air-Handling Spaces
NFPA 70 (2017; ERTA 1-2 2017; TIA 17-1; TIA 17-2;
TIA 17-3; TIA 17-4; TIA 17-5; TIA 17-6;
TIA 17-7; TIA 17-8; TIA 17-9; TIA 17-10;
TIA 17-11; TIA 17-12; TIA 17-13; TIA
17-14; TIA 17-15; TIA 17-16; TIA 17-17 )
National Electrical Code
OPC FOUNDATION (OPC)
OPC DA (Ver 3.0; Errata) OPC Data Access (DA)
TELECOMMUNICATIONS INDUSTRY ASSOCIATION (TIA)
TIA-568-C.1 (2009; Add 2 2011; Add 1 2012) Commercial Building Telecommunications Cabling Standard
TIA-606 (2017c) Administration Standard for the Telecommunications Infrastructure
TIA-607 (2011b) Generic Telecommunications Bonding and Grounding (Earthing) for Customer Premises
TRIDIUM, INC (TRIDIUM)
Niagara Framework (2012) NiagaraAX User's Guide
Tridium Open NiCS (2005) Understanding the NiagaraAX Compatibility Statement (NiCS)
U.S. AIR FORCE (USAF)
AF ETL 11-1 (2011) Civil Engineer Industrial Control System Information Assurance Compliance
SECTION 25 10 10 Page 4
U.S. FEDERAL COMMUNICATIONS COMMISSION (FCC)
FCC EMC (2002) FCC Electromagnetic Compliance Requirements
FCC Part 15 Radio Frequency Devices (47 CFR 15)
UNDERWRITERS LABORATORIES (UL)
UL 1778 (2014; Reprint Sep 2017) UL Standard for Safety Uninterruptible Power Systems
UL 60950 (2000; Reprint Oct 2007) Safety of Information Technology Equipment
1.3 DEFINITIONS
The following list of definitions may contain terms not found elsewhere in this Section but are included here for completeness. Some terms are followed with a protocol reference in parenthesis indicating to which protocol the term and definition applies. Inclusion of protocol-specific definitions does not create a requirement to support that protocol, nor does it relax any requirements to support specific protocols as indicated elsewhere in this Section."
1.3.1 Alarm Generation
The process of comparing a point value (the point being alarmed) with a pre-defined alarm condition (e.g., a High Limit) and performing some action based on the result of the comparison.
1.3.2 Alarm Handling
See Alarm Routing.
1.3.3 Alarm Routing
Alarm routing is M&C software functionality that starts with a notification that an alarm exists (typically as the output of an Alarm Generation process) and sends a specific message to a specific alarm recipient or device.
1.3.4 BACnet (BACnet)
The term BACnet is used in two ways. First meaning the BACnet Protocol Standard - the communication requirements as defined by ASHRAE 135 including all annexes and addenda. The second to refer to the overall technology related to the ASHRAE 135 protocol.
1.3.5 BACnet Advanced Application Controller (B-AAC)(BACnet)
A hardware device BTL Listed as a B-AAC. A control device which contains BIBBs in support of scheduling and alarming but otherwise has limited resources relative to a B-BC. It may be intended for specific applications and supports some degree of programmability.
1.3.6 BACnet Advanced Operator Workstation (B-AWS)(BACnet)
Monitoring and Control (M&C) Software BTL Listed as an Advanced Operator
SECTION 25 10 10 Page 5
Workstation and includes the ability to manage scheduling, alarming, and trending in an open manner. The B-AWS is the advanced operator's window into a BACnet system. It is primarily used to monitor the performance of a system and to modify parameters that affect the operation of a system.
1.3.7 BACnet Application Specific Controller (B-ASC)(BACnet)
A hardware device BTL Listed as a B-ASC. A controller with limited resources relative to a B-AAC. It is intended for use in a specific application and supports limited programmability.
1.3.8 BACnet Building Controller (B-BC)(BACnet)
A hardware device BTL Listed as a B-BC. A general-purpose, field-programmable device capable of carrying out a variety of building automation and control tasks including control and monitoring via direct digital control (DDC) of specific systems and data storage for trend information, time schedules, and alarm data. Like the other BTL Listed controller types (B-AAC, B-ASC, etc.) a B-BC device is required to support the server ("B") side of the ReadProperty and WriteProperty services, but unlike the other controller types it is also required to support the client ("A") side of these services. Communication between controllers requires that one of them support the client side and the other support the server side, so a B-BC is often used when communication between controllers is needed.
1.3.9 BACnet Internetwork (BACnet)
Two or more BACnet networks connected with BACnet routers. In a BACnet Internetwork, there exists only one message path between devices.
1.3.10 BACnet Interoperability Building Blocks (BIBBs) (BACnet)
A BIBB is a collection of one or more BACnet services intended to define a higher level of interoperability. BIBBs are combined to build the BACnet functional requirements for a device in a Specification. Some BIBBs define additional requirements (beyond requiring support for specific services) in order to achieve a level of interoperability. For example, the BIBB DS-V-A (Data Sharing-View-A), which would typically be used by an M&C client, not only requires the client to support the ReadProperty Service, but also provides a list of data types (Object / Properties) which the client must be able to interpret and display for the user.
1.3.11 BACnet Operator Display (B-OD)(BACnet)
A hardware device BTL Listed as a B-OD. A basic operator interface with limited capabilities relative to a B-OWS. It is not intended to perform direct digital control. The B-OD profile could be used for wall-mounted LCD devices, displays affixed to BACnet devices; hand-held terminals or other very simple user interfaces.
1.3.12 BACnet Operator Workstation (B-OWS)(BACnet)
Monitoring and Control (M&C) Software BTL Listed as a B-OWS. An operator interface with limited capabilities relative to a B-AWS. The B-OWS is used for monitoring and basic control of a system, but differs from a B-AWS in that it does not support configuration activities, nor does it provide advanced troubleshooting capabilities.
SECTION 25 10 10 Page 6
1.3.13 BACnet Smart Actuator (B-SA)(BACnet)
A hardware device BTL Listed as a B-SA. A simple control output device with limited resources; it is intended for specific applications.
1.3.14 BACnet Smart Sensor (B-SS)(BACnet)
A hardware device BTL Listed as a B-SS. A simple sensing device with very limited resources.
1.3.15 BACnet Testing Laboratories (BTL)(BACnet)
Established by BACnet International to support compliance testing and interoperability testing activities and consists of BTL Manager and the BTL Working Group (BTL-WG). BTL also publishes Implementation Guidelines.
1.3.16 BACnet Testing Laboratories (BTL) Listed (BACnet)
A device that has been certified by BACnet® Testing Laboratory. Devices may be certified to a specific device profile, in which case the certification indicates that the device supports the required capabilities for that profile, or may be certified as "other".
1.3.17 Binary
A two-state system or signal; for example one where an "ON" condition is represented by a high signal level and an "OFF" condition is represented by a low signal level. 'Digital' is sometimes used interchangeably with 'binary'.
1.3.18 Broadcast
Unlike most messages, which are intended for a specific recipient device, a broadcast message is intended for all devices on the network.
1.3.19 Building Control Network (BCN)
The network used by the Building Control System. Typically the BCN is a BACnet ASHRAE 135 network installed by the Building Control System Contractor.
1.3.20 Building Control System (BCS)
One type of Field Control System. A control system for building electrical and mechanical systems, typically HVAC (including central plants) and lighting. A BCS generally uses Direct Digital Control (DDC) Hardware and generally does NOT include its own local front end.
1.3.21 Building Point of Connection (BPOC)
A FPOC for a Building Control System. (This term is being phased out of use in preference for FPOC but is still used in some Specifications and criteria. When it was used, it typically referred to a piece of control hardware. The current FPOC definition typically refers instead to IT hardware.)
1.3.22 Commandable (BACnet)
A point (Object) is commandable if its Present_Value Property is writable
SECTION 25 10 10 Page 7 and it supports the optional Priority_Array Property. This functionality is useful for Overrides.
1.3.23 Control Logic Diagram
A graphical representation of control logic for multiple processes that make up a system.
1.3.24 Device Object (BACnet)
Every BACnet device requires one Device Object, whose properties represent the network visible properties of that device. Every Device Object requires a unique Object_Identifier number on the BACnet internetwork.
This number is often referred to as the device instance or device ID.
1.3.25 Field Point Of Connection (FPOC)
The FPOC is part of the UMCS IP network and acts as the point of connection between the UMCS IP Network and the field control IP network.
The FPOC is an IT device such as a switch, IP router, or firewall, typically managed by the Site IT staff. (Note that the field control IP network may consist of a single IP device, or that integration may require installation of a field control network IP device.)
1.3.26 Field Control Network
The network used by a field control system.
1.3.27 Field Control System (FCS)
A building control system or utility control system.
1.3.28 Fox Protocol (Niagara Framework)
The protocol used for communication between components in the Niagara Framework. By default, Fox uses TCP port 1911.
1.3.29 Gateway
A device that translates from one protocol to another. Devices that change only the transport mechanism of the protocol - "translating" from LonWorks over TP/FT-10 to LonWorks over IP for example - are not gateways as the underlying protocol (data format) does not change. Gateways are also called Communications Bridges or Protocol Translators.
1.3.30 Internetwork (BACnet)
See BACnet Internetwork.
1.3.31 JACE (Niagara Framework)
Java Application Control Engine. See Niagara Framework Supervisory Gateway.
1.3.32 Modbus
A basic protocol for control network communications generally used in utility control systems. The Modbus protocol standard is maintained by The Modbus Organization.
SECTION 25 10 10 Page 8
1.3.33 Master-Slave/Token Passing (MS/TP)(BACnet)
Data link protocol as defined by the BACnet standard. Multiple speeds (data rates) are permitted by the BACnet MS/TP standard.
1.3.34 Monitoring and Control (M&C) Software
The UMCS 'front end' software which performs supervisory functions such as alarm handling, scheduling, and data logging and provides a user interface for monitoring the system and configuring these functions.
1.3.35 Network (BACnet)
In BACnet, a portion of the control internetwork consisting of one or more segments of the same media connected by repeaters. Networks are separated by routers.
1.3.36 Niagara Framework
A set of hardware and software specifications for building and utility control owned by Tridium Inc., and licensed to multiple vendors. The Framework consists of front end (M&C) software, web based clients, field level control hardware, and engineering tools. While the Niagara Framework is not adopted by a recognized standards body and does not use an open licensing model, it is sufficiently well-supported by multiple HVAC vendors to be considered a de-facto Open Standard.
1.3.37 Niagara Framework Supervisory Gateway (Niagara Framework)
DDC Hardware component of the Niagara Framework. A typical Niagara architecture has Niagara specific supervisory gateways at the IP level and other (non-Niagara specific) controllers on field networks (TP/FT-10, MS/TP, etc.) beneath the Niagara supervisory gateways. The Niagara specific controllers function as a gateway between the Niagara framework protocol (Fox) and the field network beneath. These supervisory gateways may also be used as general purpose controllers and also have the capability to provide a web-browser based user interface.
Note that different vendors refer to this component by different names.
The most common name is "JACE"; other names include "EC-BOS", "FX-40", and
"UNC".
1.3.38 Object (BACnet)
A BACnet Object. The concept of organizing BACnet information into standard components with various associated Properties. Examples include Analog Input objects and Binary Output objects.
1.3.39 Override
To change the value of a point outside of the normal sequence of operation where this change has priority over the sequence. An override can be accomplished in one of two ways: The point itself may be Commandable and written to with a priority or there may be a separate point on the controller for the express purpose of implementing the override.
Typically this override is from the Utility Monitoring and Control System (UMCS) Monitoring and Control (M&C) Software. Note that this definition
SECTION 25 10 10 Page 9 is not standard throughout industry.
1.3.40 Point, Calculated
A value within the M&C Software that is not a network point but has been calculated by logic within the software based on the value of network points or other calculated points. Calculated points are sometimes called virtual points or internal points.
1.3.41 Point, Network
A value that the M&C Software reads from or writes to a field control network.
1.3.42 Polling
A requested transmission of data between devices, rather than an unrequested transmission such as Change-Of-Value (COV) or Binding where data is automatically transmitted under certain conditions.
1.3.43 Property (BACnet)
A BACnet Property - a data element associated with an Object. Different Objects have different Properties, for example an Analog Input Object has a Present_Value Property (which provides the value of the underlying hardware analog input), a High_Limit Property (which contains a high limit for alarming), as well as other properties.
1.3.44 Protocol Implementation Conformance Statement (PICS)(BACnet)
A document, created by the manufacturer of a device, which describes which potions of the BACnet standard are implemented by a given device.
1.3.45 Repeater
A device that connects two control network segments and retransmits all information received on one side onto the other.
1.3.46 Router (BACnet)
A device that connects two or more BACnet networks and controls traffic between the networks by retransmitting signals received from one network onto another based on the signal destination. Routers are used to subdivide an internetwork and to control bandwidth usage.
1.3.47 Segment
A 'single' section of a control network that contains no repeaters or routers. There is generally a limit on the number of devices on a segment, and this limit is dependent on the topology/media and device type. For example, a TP/FT-10 segment with locally powered devices is limited to 64 devices, and a BACnet MS/TP segment is limited to 32 devices.
1.3.48 Service (BACnet)
A BACnet Service. A defined method for sending a specific type of data between devices. Services are always defined in a Client-Server manner, with a Client initiating a Service request and a Server Executing the Service. Some examples are ReadProperty (a client requests a data value
SECTION 25 10 10 Page 10 from a server), WriteProperty (a client writes a data value to a server), and CreateObject (a client requests that a server create a new object within the server device).
1.3.49 Standard BACnet Object/Property/Service (BACnet)
BACnet Objects, Properties, or Services that are standard Objects, Properties, or Services enumerated and defined in ASHRAE 135. Clause 23 of ASHRAE 135 defines methods to extend ASHRAE 135 to non-standard or proprietary information. Standard BACnet Objects/Properties/Services specifically exclude any vendor specific extensions.
1.3.50 Supervisory Controller
A controller implementing a combination of supervisory logic (global control strategies or optimization strategies), scheduling, alarming, event management, trending, web services or network management. Note this is defined by use; many supervisory controllers have the capability to also directly control equipment.
1.3.51 Supervisory Gateway
A device that is both a supervisory controller and a gateway.
1.3.52 UMCS Network
An IP network connecting multiple field control systems to the Monitoring and Control Software using one or more of: LonWorks ( CEA-709.1-D and CEA-852-C ), BACnet ( ASHRAE 135 Annex J), MODBUS Protocol , MODBUS TCP/IP, or OPC DA.
1.3.53 Utility Control System (UCS)
One type of field control system. Used for control of utility systems such as an electrical substation, sanitary sewer lift station, water pump station, etc. Building controls are excluded from a UCS, however it is possible to have a Utility Control System and a Building Control System in the same facility, and for those systems to share components such as the FPOC. A UCS may include its own local front-end.
1.4 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor Quality Control approval. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government.
Submittals with an "S" are for inclusion in the Sustainability eNotebook, in conformance to Section 01 33 29.00 06 SUSTAINABILITY REPORTING. Submit the following in accordance with Section 01 33 00.00 06 SUBMITTAL PROCEDURES and TABLE 1: PROJECT SEQUENCING:
SD-02 Shop Drawings
UMCS Contractor Design Drawings; G
UMCS Contractor Design Drawings as a single complete package: 2 hard copies and 2 copies on CDROM. Submit hardcopy Drawings on ISO A1 34 by 22 inches and A3 17 by 11 inches sheets, and Electronic Drawings in both PDF and AutoCAD format.
SECTION 25 10 10 Page 11
Draft As-Built Drawings; G
Draft As-Built Drawings as a single complete package: 2 hard copies and 2 copies on CDROM. Submit hardcopy Drawings must on ISO A1 34 by 22 inches and A3 17 by 11 inches sheets, and Electronic Drawings in both PDF and AutoCAD format.
Final As-Built Drawings; G
Final As-Built Drawings as a single complete package: 2 hard copies and 2 copies on CDROM. Submit hardcopy Drawings on ISO A1 34 by 22 inches and A3 17 by 11 inches sheets, and Electronic Drawings in both PDF and AutoCAD format.
SD-03 Product Data
Product Data Sheets; G
Computer Software; G
The most recent versions of all computer software provided under this Specification delivered as a Technical Data Package. Submit the user manuals for all software delivered for this Project with the software.
Enclosure Keys
SD-05 Design Data
UMCS IP Network Bandwidth Usage Estimate; G
Four copies of the UMCS IP Network Bandwidth Usage Estimate.
SD-06 Test Reports
Pre-Construction QC Checklist; G
Four copies of the Pre-Construction QC Checklist.
Post-Construction QC Checklist; G
Four copies of the Post-Construction QC Checklist.
Existing Conditions Report; G
Four copies of the Existing Conditions Report.
Start-Up and Start-Up Testing Report; G
Four copies of the Start-Up and Start-Up Testing Report. The Start-Up and Testing report may be submitted as a Technical Data Package.
PVT Phase I Procedures; G
Four copies of the PVT Phase I Procedures. The PVT Procedures may be submitted as a Technical Data Package.
SECTION 25 10 10 Page 12
PVT Phase I Report; G
Four copies of the PVT Phase I Report. The PVT Phase I Report may be submitted as a Technical Data Package.
PVT Phase II Report; G
Four copies of the PVT Phase II Report. The PVT Phase II Report may be submitted as a Technical Data Package.
SD-10 Operation and Maintenance Data
Operation and Maintenance (O&M) Instructions; G
Four bound O&M Instructions and 6 copies of the Instructions in PDF format on optical disc. Index and tab bound instructions.
Submit instructions in PDF form as a single PDF file, or as multiple PDF files with a PDF file table of contents containing links to the other files. O&M Instructions may be submitted as a Technical Data Package.
Preventive Maintenance Work Plan; G
Four copies of the Preventive Maintenance Work Plan. The Preventive Maintenance Work Plan may be submitted as a Technical Data Package.
Basic Training Documentation; G
Training manuals for Basic Training delivered for each trainee on the Course Attendance List with two additional copies delivered for archival at the Project Site. Submit two copies of the Course Attendance List with the archival copies. The Basic Training Documentation may be submitted as a Technical Data Package.
Advanced Training Documentation; G
One set of training manuals delivered for each trainee on the Course Attendance List with two additional copies delivered for archival at the Project Site. Submit two copies of the Course Attendance List with the archival copies. The Advanced Training Documentation may be submitted as a Technical Data Package.
Refresher Training Documentation; G
One set of training manuals delivered for each trainee on the Course Attendance List with two additional copies delivered for archival at the Project Site. Submit two copies of the Course Attendance List with the archival copies. The Refresher Training Documentation may be submitted as a Technical Data Package.
SD-11 Closeout Submittals
Closeout QC Checklist; G
Four copies of the Closeout QC Checklist.
SECTION 25 10 10 Page 13
1.5 PROJECT SEQUENCING
TABLE I: PROJECT SEQUENCING specifies the sequencing of submittals as specified in Paragraph "Submittals" (denoted by an 'S' in the 'TYPE' column) and activities as specified in PART 3 EXECUTION (denoted by an 'E' in the 'TYPE' column).
1.5.1 Sequencing for Submittals
The sequencing specified for submittals is the deadline by which the submittal must be initially submitted to the Government. Following submission there will be a Government review period as specified in Section 01 33 00.00 06 SUBMITTAL PROCEDURES. If the submittal is not accepted by the Government, revise the submittal and resubmit it to the Government within 14 days of notification that the submittal has been rejected. Upon re-submittal there will be an additional Government review period. If the submittal is not accepted the process repeats until the submittal is accepted by the Government.
1.5.2 Sequencing for Activities
The sequencing specified for activities indicates the earliest the activity may begin.
1.5.3 Abbreviations
In TABLE I the abbreviation AAO is used for 'after approval of' and 'ACO' is used for 'after completion of'.
TABLE I. PROJECT SEQUENCING
ITEM TYPE DESCRIPTION SEQUENCING
(START OF ACTIVITY or
DEADLINE FOR SUBMITTAL)
1 Notice to proceed
2 S Existing Conditions Report after #1
3 S Design Drawings after #1
4 S Product Data Sheets after #1
5 S UMCS IP Network Bandwidth Usage Estimate after #1
6 S Pre-construction QC Checklist after #1
7 E Install UMCS AAO #2 thru #6
SECTION 25 10 10 Page 14
TABLE I. PROJECT SEQUENCING
ITEM TYPE DESCRIPTION SEQUENCING
(START OF ACTIVITY or
DEADLINE FOR SUBMITTAL)
8 E Start-Up and Start-Up Testing ACO #7
9 S Post-Construction QC Checklist ACO #8
10 S Computer Software ACO #8
11 S Start-Up and Start-Up Testing Report
ACO #8
12 S Draft As-Built Drawings ACO #8
13 S PVT Phase I Procedures before scheduled start of #14 and
AAO #11
14 E PVT Phase I AAO #13 and #12
15 S PVT Phase I Report ACO #14
16 S Preventive Maintenance Work Plan AAO #11
17 S O&M Instructions AAO #11
18 S Basic Training Documentation AAO #11 and before scheduled start of #19
19 E Basic Training (PVT Phase II) AAO #16, #17, and #18
20 S PVT Phase II Report ACO #19
21 S Final As-Built Drawings AAO #20
22 S Advanced Training Documentation before schedule start of #23 and
AAO #18
23 E Advanced Training ACO #19, AAO #22, and no later than 60 days ACO #19
24 S Refresher Training Documentation before #25 and AAO #18 and #22
25 E Refresher Training ACO #19 and AAO #24
SECTION 25 10 10 Page 15
TABLE I. PROJECT SEQUENCING
ITEM TYPE DESCRIPTION SEQUENCING
(START OF ACTIVITY or
DEADLINE FOR SUBMITTAL)
26 S Closeout QC Checklist ACO #23
Note: Temperature Controls Contractor shall provide proposed Project Sequencing Schedule.
1.6 QUALITY CONTROL (QC) CHECKLISTS
The Contractor's Chief Quality Control (QC) Representative must complete the QC Checklist in APPENDIX A, and must submit the Pre-Construction QC Checklist, Post-Construction QC Checklist, and Closeout QC Checklist as specified. The QC Representative must verify each item in the Checklist and initial in the provided area to indicate that the requirement has been met. The QC Representative must sign and date the Checklist prior to submission to the Government.
The APPENDIX A QC Checklist is available as an editable file at http://www.wbdg.org/FFC/NAVGRAPH/graphtoc.pdf .
1.7 OPERATION AND MAINTENANCE (O&M) INSTRUCTIONS
Provide UMCS Operation and Maintenance Instructions which include:
a. Procedures for the UMCS system start-up, operation, and shut-down.
b. Final As-Built Drawings.
c. Routine maintenance checklist, arranged in a columnar format: The first column listing all installed devices, the second column stating the maintenance activity or stating that no maintenance required, the third column stating the frequency of the maintenance activity, and the fourth column providing any additional comments or reference.
d. Qualified service organization list including points of contact with phone numbers.
e. Start-Up and Start-Up Testing Report.
f. Performance Verification Test (PVT) Procedures and Reports.
PART 2 PRODUCTS
2.1 EQUIPMENT REQUIREMENTS
2.1.1 Product Certifications
For computing devices, as defined in FCC Part 15 , supplied as part of the UMCS provide devices which are certified to comply with the requirements of Class B computing devices.
SECTION 25 10 10 Page 16
2.1.2 Product Sourcing
For units of the same type of equipment, provide products of a single manufacturer. For each major component of equipment provide equipment with the manufacturer's name and the model and serial number in a conspicuous place. For materials and equipment, provide new standard unmodified products of a manufacturer regularly engaged in the manufacturing of such products.
2.1.3 General Requirements
Provide components that meet the following requirements:
a. Portions of the data communications equipment system installed in unconditioned spaces must operate properly in an environment with ambient temperatures between 32 and 120 degrees F and ambient relative humidity between 10 percent and 90 percent non-condensing.
b. Components must accept 100 to 125 volts AC (Vac), 60 Hz, single phase, three wire with a three-pronged, dedicated circuit outlet or be provided with a transformer to meet the component's power requirements.
c. The equipment must meet the requirements of NFPA 70 , UL 60950 , NFPA 262 , FCC EMC, and FCC Part 15 .
2.1.4 Nameplates
Provide nameplates of laminated plastic identifying the function, network address, if applicable, and identifier of the device. Laminated plastic must be at least 0.125 inch thick, white with black center core.
Nameplates must be a minimum of 1 by 3 inch with minimum 0.25 inch high engraved block lettering.
2.1.5 Product Data Sheets
For all products (equipment) specified in PART 2 and supplied under this Contract, submit copies of all manufacturer catalog cuts and Specification sheets to indicate conformance to product requirements. For M&C Software also include the PICS verifying BTL Listing as a B-AWS.
2.2 CONTROL HARDWARE
2.2.1 Control Protocol Routers
2.2.1.1 BACnet/IP Router
Provide BACnet/IP Routers which perform layer 3 routing of ASHRAE 135 packets over an IP network in accordance with ASHRAE 135 Annex J and Clause 6. The router must provide the appropriate connection to the IP network and connections to a ASHRAE 135 MS/TP, or other ASHRAE 135 network. Devices used as BACnet/IP Routers must be BTL Listed and must support the Network Management-Router Configuration-B (NM-RC-B) BIBB.
2.2.2 Monitoring and Control (M&C) Controller Hardware
Provide Monitoring and Control (M&C) Controller Hardware which is a microprocessor-based direct digital control hardware and which communicates over the UMCS IP network using one of:
SECTION 25 10 10 Page 17
a. CEA-709.1-D in accordance with CEA-852-C and using only Standard Network Variable Types (SNVTs) as defined by the LonMark SNVT List.
b. ASHRAE 135 in accordance with ASHRAE 135 Annex J and using only Standard ASHRAE 135 services.
Monitoring and Control (M&C) Controller Hardware must either meet the requirements of the LonMark Interoperability Guide or be BTL Listed.
2.2.3 BACnet Supervisory Controller Hardware
Provide BACnet Supervisory Controller Hardware which is direct digital control hardware and which:
a. Is BTL Listed.
b. Communicates using ASHRAE 135 over an IP network in accordance with ASHRAE 135 Annex J.
c. Has a configurable Object_Name Property.
d. Supports the following BIBBS.
(1) DS-RP-B (Data Sharing–Read Property–B) BIBB for Objects requiring read access from the M&C Software.
(2) DS-WP-B (Data Sharing–Write Property–B) BIBB for Objects requiring write access from the M&C Software.
(3) SCHED-E-B (Scheduling-External-B).
(4) AE-N-I-B (Alarm and Event-Notification Internal-B).
(5) AE-ACK-B (Alarm and Event-ACK-B).
(6) T-VMT-I-B (Trending-Viewing and Modifying Trends-Internal-B).
(7) T-ATR-B (Trending-Automated Trend Retrieval-B).
e. Has a Writeable Recipient_List Property of the Notification Class Object.
2.2.4 Control Protocol Gateways
Provide Control Protocol Gateways which perform bi-directional protocol translation between two of the following protocols, or between one of the following protocols and another protocol: CEA-709.1-D , ASHRAE 135, MODBUS Protocol , MODBUS TCP/IP, and OPC DA. Provide Control Protocol Gateways which also meet the following requirements.
a. Gateways must have two or more separate network connections, each appropriate for the protocol and media used. A single network connection must not be used for both protocols.
b. Gateways must be capable of being installed, configured, and programmed through the use of instructions in the manual supplied by the Contractor.
c. Provide and license to the Government all software required for
SECTION 25 10 10 Page 18 gateway configuration.
d. Gateways must retain their configuration after a power loss of an indefinite time, and must automatically return to their pre-power loss state once power is restored.
e. Gateways must provide capacity for mapping all required points as indicated plus an additional 10 percent between the two protocols it uses.
f. Gateways must, in addition, meet all requirements specified (in the following subparagraphs) for each of the two protocols it translates.
2.2.4.1 Gateway for CEA-709.1
For a gateways using CEA-709.1-D provide gateways which meet the following requirements in addition to the requirements for all gateways:
a. It must allow bi-directional mapping of data in the Gateway to Standard Network Variable Types (SNVTs) according to the LonMark SNVT List .
b. Gateways communicating CEA-709.1-D over an IP network must communicate in accordance with CEA-852-C .
c. It must allow of its standard network variables (SNVTs) and support transmitting data using the "min, max, and delta" (throttling and heartbeat) methodology.
d. It must provide the ability to label SNVTs.
e. It must supply a LonMark external interface file (XIF) as defined in the LonMark XIF Guide for use with LNS tools and utilities.
f. It must have a "service pin" which, when pressed, will cause the Gateway to broadcast its 48-bit NodeID and ProgramID over the network.
g. It must provide a configurable self-documenting string.
2.2.4.2 Gateway for ASHRAE 135
For gateways using ASHRAE 135 provide gateways which meets the following requirements in addition to the requirements for all gateways:
a. It must allow bi-directional mapping of data in the Gateway to Standard Objects as defined in ASHRAE 135.
b. All ASHRAE 135 Objects must have a configurable Object_Name Property.
c. It must be BTL Listed.
d. Gateways communicating ASHRAE 135 over an IP network must communicate in accordance with ASHRAE 135 Annex J.
e. Gateways communicating ASHRAE 135 to a field control systems must support the DS-RP-A (Data Sharing–Read Property–A) BIBB and the DS-WP-A (Data Sharing–Write Property–A) BIBB.
f. Gateways communicating ASHRAE 135 to the M&C Software or to a BACnet
SECTION 25 10 10 Page 19
Supervisory Controller must support the DS-RP-B (Data Sharing–Read Property–B) BIBB for Objects requiring read access from the M&C Software and the DS-WP-B (Data Sharing–Write Property–B) BIBB for Objects requiring write access from the M&C Software.
2.2.4.3 Gateway for Modbus
For gateways that use MODBUS Protocol / MODBUS TCP/IP provide gateways that meet the requirements specified for all gateways and which allow bi-directional mapping of data in the Gateway to MODBUS Protocol / MODBUS TCP/IP registers using the four standard Modbus register types (Discrete Input, Coil, Input Register, and Holding Register). Gateways communicating MODBUS Protocol / MODBUS TCP/IP to the M&C Software must communicate via MODBUS Protocol / MODBUS TCP/IP over TCP/IP.
2.2.4.4 Gateway for OPC
For gateways that use OPC DA, provide gateways that meet the requirements specified for all gateways and which allow bi-directional mapping of data in the Gateway using OPC DA tags and which communicate over an IP network in accordance with OPC DA.
2.2.4.5 Gateway for DNP3
For gateways that use DNP3, provide gateways that meet the requirements specified for all gateways and which allow bi-directional mapping of data in the Gateway to DNP3 object groups and variations as defined by IEEE 1815 .
Gateways communicating DNP3 over an IP network must communicate in accordance with the LAN/WAN Networking volume of IEEE 1815 .
2.2.4.6 Niagara Framework Supervisory Gateway
Niagara Framework Supervisory Gateway Hardware must:
a. Be direct digital control hardware.
b. Have an unrestricted interoperability license and a Niagara Compatibility Statement (NiCS) that follows the Tridium Open NiCS Specification.
c. Manage communications between a field control network and the Niagara Framework Monitoring and Control Software and between itself and other Niagara Framework Supervisory Gateways. Niagara Framework Supervisory Gateway Hardware must use Fox protocol for communication with other Niagara Framework Components.
d. Be fully programmable using the Niagara Framework Engineering Tool and support the following:
(1) Time synchronization, Calendar, and Scheduling using Niagara Scheduling Objects
(2) Alarm generation and routing using the Niagara Alarm Service
(3) Trending using the Niagara History Service and Niagara Trend Log Objects
(4) Integration of field control networks using the Niagara Framework Engineering Tool
SECTION 25 10 10 Page 20
(5) Configuration of integrated field control system using the Niagara Framework Engineering Tool when supported by the field control system
e. Meet the following minimum hardware requirements:
(1) {AIR FORCE or ARMY or SERVICE GENERIC} {NAVY} {/NAVY} One{NAVY} {/NAVY} {/AIR FORCE or ARMY or SERVICE GENERIC} {NAVY} {AIR FORCE or ARMY or SERVICE GENERIC}{/AIR FORCE or ARMY or SERVICE GENERIC} Two{AIR FORCE or ARMY or SERVICE GENERIC} {/AIR FORCE or ARMY or SERVICE GENERIC}{/NAVY} 10/100…