This federal contract opportunity solicitation is for the design, construction, and delivery of new transient training barracks at Fort McCoy, Wisconsin. The estimated construction cost is between $10-25 million. The NAICS code is 236220 for commercial and institutional building construction. The size determination is $39.5 million. This is an unrestricted full and open competition requiring price evaluation for HUBZone small businesses. No award will be made until funds are appropriated. Interested parties must register in the System for Award Management at sam.gov, which is free of charge. A pre-bid site visit is available and the terms bid and proposal may be used interchangeably. Technical questions must be submitted through the Bidder Inquiry system at projnet.org by the specified due date.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Solicitation For Transient Training Barracks Ft McCoy Wisconsin
P2: 476377
Design-Bid-Build
Specifications Volume 2 of 2 Div 10 - 33
CERTIFIED FINAL
07 August 2020
W912QR20R0027
ARIMS: 200A
Disposition: Maintain for 15yrs after completion of project
W912QR20R0027_Specs_Vol2-0000
P2 476377 TRANSIENT TRAINING BARRACKS
Ft. McCoy, WI
PROJECT TABLE OF CONTENTS
DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS
00 80 00.00 06 SPECIAL PROVISIONS
DIVISION 01 - GENERAL REQUIREMENTS
01 32 01.00 06 PROJECT SCHEDULE
01 33 00.00 06 SUBMITTAL PROCEDURES
01 33 29.00 06 SUSTAINABILITY REPORTING
01 35 26.00 06 GOVERNMENT SAFETY REQUIREMENTS
01 42 00 SOURCES FOR REFERENCE PUBLICATIONS
01 45 04.10 06 CONTRACTOR QUALITY CONTROL
01 45 35 SPECIAL INSPECTIONS
01 50 00 TEMPORARY CONSTRUCTION FACILITIES AND CONTROLS
01 57 19.00 06 TEMPORARY ENVIRONMENTAL CONTROLS AND PERMITS
01 74 19 CONSTRUCTION AND DEMOLITION WASTE MANAGEMENT
01 78 23 OPERATION AND MAINTENANCE DATA
01 91 00.15 TOTAL BUILDING COMMISSIONING
DIVISION 02 - EXISTING CONDITIONS
02 41 00 DEMOLITION
DIVISION 03 - CONCRETE
03 11 13.00 10 STRUCTURAL CAST-IN-PLACE CONCRETE FORMING
03 15 00.00 10 CONCRETE ACCESSORIES
03 20 00.00 10 CONCRETE REINFORCING
03 30 00.00 10 CAST-IN-PLACE CONCRETE
03 35 00.00 10 CONCRETE FINISHING
03 39 00.00 10 CONCRETE CURING
DIVISION 04 - MASONRY
04 20 00 MASONRY
04 21 13.13 NONBEARING MASONRY VENEER/STEEL STUD WALLS
04 72 00.00 48 CAST STONE
DIVISION 05 - METALS
05 12 00 STRUCTURAL STEEL
05 21 00 STEEL JOIST FRAMING
05 30 00 STEEL DECKS
05 40 00 COLD-FORMED METAL FRAMING
05 50 13 MISCELLANEOUS METAL FABRICATIONS
05 51 00 METAL STAIRS
05 52 00 METAL RAILINGS
DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES
06 10 00 ROUGH CARPENTRY
06 61 16 SOLID SURFACING FABRICATIONS
DIVISION 07 - THERMAL AND MOISTURE PROTECTION
07 05 23 PRESSURE TESTING AN AIR BARRIER SYSTEM FOR AIR TIGHTNESS
07 13 53 ELASTOMERIC SHEET WATERPROOFING
PROJECT TABLE OF CONTENTS Page 1
CERTIFIED FINAL
07 21 13 BOARD INSULATION
07 21 19 SPRAY POLYURETHANE FOAM (SPF) INSULATION
07 27 10.00 10 BUILDING AIR BARRIER SYSTEM
07 27 19.01 SELF-ADHERING AIR BARRIERS
07 27 26 FLUID-APPLIED MEMBRANE AIR BARRIERS
07 41 13 METAL ROOF PANELS, UNDERLAYMENTS, AND VENTILATED NAIL BASE
07 42 13 METAL WALL PANELS
07 60 00 FLASHING AND SHEET METAL
07 84 00 FIRESTOPPING
07 92 00 JOINT SEALANTS
DIVISION 08 - OPENINGS
08 11 13 STEEL DOORS AND FRAMES
08 11 16 ALUMINUM DOORS AND FRAMES (ALUMINUM STOREFRONTS)
08 51 13 ALUMINUM WINDOWS
08 71 00 DOOR HARDWARE
08 81 00 GLAZING
08 91 00 METAL WALL LOUVERS
DIVISION 09 - FINISHES
09 22 00 SUPPORTS FOR GYPSUM BOARD
09 29 00 GYPSUM BOARD
09 30 10 CERAMIC, QUARRY, AND GLASS TILING
09 51 00 ACOUSTICAL CEILINGS
09 65 00 RESILIENT FLOORING
09 90 00 PAINTS AND COATINGS
DIVISION 10 - SPECIALTIES
10 14 00.20 INTERIOR SIGNAGE
10 21 13 TOILET COMPARTMENTS
10 26 00 WALL AND DOOR PROTECTION
10 28 00.00 48 TOILET AND SHOWER ACCESSORIES
DIVISION 12 - FURNISHINGS
12 21 00 WINDOW BLINDS
DIVISION 14 - CONVEYING EQUIPMENT
14 24 23 HYDRAULIC PASSENGER ELEVATORS
DIVISION 21 - FIRE SUPPRESSION
21 13 13.00 10 WET PIPE SPRINKLER SYSTEM, FIRE PROTECTION
DIVISION 22 - PLUMBING
22 00 00 PLUMBING, GENERAL PURPOSE
DIVISION 23 - HEATING, VENTILATING, AND AIR CONDITIONING (HVAC)
23 00 00 AIR SUPPLY, DISTRIBUTION, VENTILATION, AND EXHAUST SYSTEMS
23 03 00.00 20 BASIC MECHANICAL MATERIALS AND METHODS
23 05 93.00 06 TESTING, ADJUSTING, AND BALANCING (TAB) OF HVAC
23 07 00 THERMAL INSULATION FOR MECHANICAL SYSTEMS
23 09 00 INSTRUMENTATION AND CONTROL FOR HVAC
PROJECT TABLE OF CONTENTS Page 2
23 09 13 INSTRUMENTATION AND CONTROL DEVICES FOR HVAC
23 09 23.02 BACNET DIRECT DIGITAL CONTROL FOR HVAC AND OTHER BUILDING
CONTROL SYSTEMS
23 11 25 FACILITY GAS PIPING
23 52 00 HEATING BOILERS
23 64 26 HOT WATER PIPING SYSTEMS
23 81 00 DECENTRALIZED UNITARY HVAC EQUIPMENT
23 82 19.00 40 FAN COIL UNITS
DIVISION 26 - ELECTRICAL
26 00 00.00 20 BASIC ELECTRICAL MATERIALS AND METHODS
26 08 00 APPARATUS INSPECTION AND TESTING
26 20 00 INTERIOR DISTRIBUTION SYSTEM
26 24 13 SWITCHBOARDS
26 28 01.00 10 COORDINATED POWER SYSTEM PROTECTION
26 29 23 VARIABLE FREQUENCY DRIVE SYSTEMS UNDER 600 VOLTS
26 41 00 LIGHTNING PROTECTION SYSTEM
26 51 00 INTERIOR LIGHTING
26 56 00 EXTERIOR LIGHTING
DIVISION 27 - COMMUNICATIONS
27 05 14.00 10 CABLE TELEVISION PREMISES DISTRIBUTION SYSTEM
27 10 00 BUILDING TELECOMMUNICATIONS CABLING SYSTEM
DIVISION 28 - ELECTRONIC SAFETY AND SECURITY
28 31 76 INTERIOR FIRE ALARM AND MASS NOTIFICATION SYSTEM
DIVISION 31 - EARTHWORK
31 00 00.00 06 EARTHWORK
31 05 22.00 06 GEOTEXTILES USED AS FILTERS
31 11 00 CLEARING AND GRUBBING
31 21 13 RADON MITIGATION
DIVISION 32 - EXTERIOR IMPROVEMENTS
32 11 23 AGGREGATE BASE COURSE
32 16 19 CONCRETE CURBS, GUTTERS AND SIDEWALKS
32 17 23 PAVEMENT MARKINGS
32 92 19 SEEDING
32 92 23 SODDING
DIVISION 33 - UTILITIES
33 11 00 WATER UTILITY DISTRIBUTION PIPING
33 30 00 SANITARY SEWERAGE
33 40 00 STORM DRAINAGE UTILITIES
33 51 15 NATURAL-GAS / LIQUID PETROLEUM GAS DISTRIBUTION
33 71 02 UNDERGROUND ELECTRICAL DISTRIBUTION
33 82 00 TELECOMMUNICATIONS OUTSIDE PLANT (OSP)
-- End of Project Table of Contents --
PROJECT TABLE OF CONTENTS Page 3
SECTION TABLE OF CONTENTS
DIVISION 10 - SPECIALTIES
SECTION 10 14 00.20
INTERIOR SIGNAGE
08/17
PART 1 GENERAL
1.1 REFERENCES
1.2 SUBMITTALS
1.3 QUALITY ASSURANCE
1.3.1 Samples
1.3.2 Detail Drawings
1.4 DELIVERY, STORAGE, AND HANDLING
1.5 WARRANTY
PART 2 PRODUCTS
2.1 STANDARD PRODUCTS
2.2 ROOM IDENTIFICATION/DIRECTIONAL SIGNAGE SYSTEM
2.2.1 Standard Room Signs
2.2.2 Changeable Message Strip Signs
2.2.3 Type of Mounting For Signs
2.2.4 Graphics
2.2.4.1 First Surface Copy Direct Print or Silkscreened
(Non-Tactile)
2.2.5 Character Proportions and Heights
2.2.6 Tactile Letters, Symbols and Braille
2.3 STAIR SIGNAGE
2.4 ALUMINUM ALLOY PRODUCTS
2.5 ANODIC COATING
2.6 ORGANIC COATING
2.7 FABRICATION AND MANUFACTURE
2.7.1 Factory Workmanship
2.7.2 Dissimilar Materials
2.8 COLOR, FINISH, AND CONTRAST
2.9 TYPEFACE
PART 3 EXECUTION
3.1 INSTALLATION
3.1.1 Anchorage
3.1.2 Protection and Cleaning
-- End of Section Table of Contents --
SECTION 10 14 00.20 Page 1
SECTION 10 14 00.20
INTERIOR SIGNAGE
08/17
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by basic designation only.
ALUMINUM ASSOCIATION (AA)
AA DAF45 (2003; Reaffirmed 2009) Designation System for Aluminum Finishes
AA PK-1 (2015) Pink Sheets: Designations and Chemical Composition Limits for Aluminum Alloys in the Form of Castings & Ingot
AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA)
AAMA 2604 (2017a) Voluntary Specification, Performance Requirements and Test Procedures for High Performance Organic Coatings on Aluminum Extrusions and Panels
AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)
ANSI Z97.1 (2015) Safety Glazing Materials Used in Buildings - Safety Performance Specifications and Methods of Test
AMERICAN WELDING SOCIETY (AWS)
AWS D1.2/D1.2M (2014) Structural Welding Code - Aluminum
ASTM INTERNATIONAL (ASTM)
ASTM B209 (2014) Standard Specification for Aluminum and Aluminum-Alloy Sheet and Plate
ASTM B221 (2014) Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes
INTERNATIONAL CODE COUNCIL (ICC)
ICC A117.1 COMM (2017) Standard And Commentary Accessible and Usable Buildings and Facilities
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 101 (2018; TIA 18-1; TIA 18-2; TIA 18-3) Life
SECTION 10 14 00.20 Page 2
Safety Code
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
36 CFR 1191 Americans with Disabilities Act (ADA) Accessibility Guidelines for Buildings and Facilities; Architectural Barriers Act (ABA) Accessibility Guidelines
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submittals with an "S" are for inclusion in the Sustainability eNotebook, in conformance to Section 01 33 29 SUSTAINABILITY REPORTING. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Detail Drawings; G , RO
SD-03 Product Data
Installation; G , RO
Warranty; G , RO
SD-04 Samples
Interior Signage; G , RO
Software; G , RO
SD-10 Operation and Maintenance Data
Approved Manufacturer's Instructions; G , RO
Protection and Cleaning; G , RO
1.3 QUALITY ASSURANCE
1.3.1 Samples
Submit interior signage samples of each of the following sign types showing typical quality, workmanship and color: Directional sign, Standard Room sign, Changeable message strip sign, . The samples may be installed in the work, provided each sample is identified and location recorded.
1.3.2 Detail Drawings
Submit detail drawings showing elevations of each type of sign, dimensions, details and methods of mounting or anchoring, mounting height, shape and thickness of materials, and details of construction. Include a schedule showing the location, each sign type, and message.
SECTION 10 14 00.20 Page 3
1.4 DELIVERY, STORAGE, AND HANDLING
Materials must be packaged to prevent damage and deterioration during shipment, handling, storage and installation. Product must be delivered to the jobsite in manufacturer's original packaging and stored in a clean, dry area in accordance with manufacturer's instructions.
1.5 WARRANTY
Warrant the interior signage for a period of 2 year against defective workmanship and material. Warranties must be signed by the authorized representative of the manufacturer. Submit warranty accompanied by the document authenticating the signer as an authorized representative of the guarantor. Guarantee that the signage products and the installation are free from any defects in material and workmanship from the date of delivery.
PART 2 PRODUCTS
2.1 STANDARD PRODUCTS
Signs, plaques, directories, and dimensional letters must be the standard product of a manufacturer regularly engaged in the manufacture of such products that essentially duplicate signs that have been in satisfactory use at least 2 years prior to bid opening. Obtain signage from a single manufacturer with edges and corners of finished letterforms and graphics true and clean.
2.2 ROOM IDENTIFICATION/DIRECTIONAL SIGNAGE SYSTEM
2.2.1 Standard Room Signs
Signs must consist of acrylic plastic 0.080 inch thickness minimum conforming to ANSI Z97.1 and must conform to the following:
a. Frames must be aluminum , flat
b. End caps must be aluminum with square style corners.
c. Units must be frameless. Corners of signs must be squared .
2.2.2 Changeable Message Strip Signs
Changeable message strip signs must be of same construction as standard room signs to include a clear sleeve that will accept a paper or plastic insert identifying changeable text. The insert must be prepared typeset message mounted on paper card stock . Furnish one suction device to assist in removing face sheet.
2.2.3 Type of Mounting For Signs
Provide extruded aluminum brackets for hanging, projecting, and double-sided signs. Mounting for framed, hanging, and projecting signs must be by mechanical fasteners. Surface mounted signs must be mounted with countersunk mounting holes in plaques and mounting screws fabricated from materials that are not corrosive to sign material and mounting surface.
2.2.4 Graphics
Signage graphics for modular signs must conform to the following:
SECTION 10 14 00.20 Page 4
2.2.4.1 First Surface Copy Direct Print or Silkscreened (Non-Tactile)
Message may be applied to panel using the silkscreen process. Silkscreened images must be executed with photo screens prepared from original art.
Handcut screens will not be accepted. Original art is defined as artwork that is a first generation reproduction of the specified art. Edges and corners must be clean.
2.2.5 Character Proportions and Heights
Letters and numbers on signs conform to 36 CFR 1191 .
2.2.6 Tactile Letters, Symbols and Braille
Raised letters and numbers on signs must conform to 36 CFR 1191 .
2.3 STAIR SIGNAGE
Provide signs on stairs serving three or more stories with special signage within the enclosure at each floor landing conforming to NFPA 101 .
Indicate the floor level, the terminus of the top and bottom of the stair enclosure, and the identification of the stair enclosure. Also, state the floor level of, and the direction to, exit discharge. Locate the signage inside the enclosure in a position that is visible when the door is in the open or closed position and install in conformance with 36 CFR 1191 . The floor level designation must also be tactile in accordance with
ICC A117.1 COMM .
2.4 ALUMINUM ALLOY PRODUCTS
Aluminum extrusions must be at least 1/8 inch thick, and aluminum plate or sheet must be at least 0.0508 inch thick. Extrusions must conform to ASTM B221; plate and sheet must conform to ASTM B209. Where anodic coatings are specified, alloy must conform to AA PK-1 alloy designation
514.0. Exposed anodized aluminum finishes must be as shown. Welding for aluminum products must conform to AWS D1.2/D1.2M .
2.5 ANODIC COATING
Anodized finish must conform to AA DAF45 as follows:
a. Clear (natural) designation AA-M10-C22-A31, Architectural Class II 0.4 mil or thicker.
b. Integral color anodized designation AA-M10-C22-A32, Architectural Class
0.4 to 0.7 mil.
c. Electrolytically deposited color-anodized designation AA-M10-C22-A34, Architectural Class II 0.4 to 0.7 mil.
2.6 ORGANIC COATING
Organic coating must conform to AAMA 2604, with total dry film thickness not less than 1.2 mils.
SECTION 10 14 00.20 Page 5
2.7 FABRICATION AND MANUFACTURE
2.7.1 Factory Workmanship
Holes for bolts and screws must be drilled or punched. Drilling and punching must produce clean, true lines and surfaces. Exposed surfaces of work must have a smooth finish and exposed riveting must be flush.
Fastenings must be concealed where practicable.
2.7.2 Dissimilar Materials
Where dissimilar metals are in contact, the surfaces will be protected to prevent galvanic or corrosive action.
2.8 COLOR, FINISH, AND CONTRAST
Color must be as indicated . Finish of all signs must be eggshell, matte, or other non-glare finish as required in handicapped-accessible buildings.
2.9 TYPEFACE
ADA-ABA compliant font for Room Signs.
PART 3 EXECUTION
3.1 INSTALLATION
Signs must be installed plumb and true and in accordance with approved manufacturer's instructions at locations shown on the detail drawings .
Submit six copies of operating instructions outlining the step-by-step procedures required for system operation. The instructions must include simplified diagrams for the system as installed, the manufacturer's name, model number, service manual, parts list, and brief description of all equipment and their basic operating features. Each set must be permanently bound and must have a hard cover. The following identification must be inscribed on the covers: the words "OPERATING AND MAINTENANCE INSTRUCTIONS", name and location of the facility, name of the Contractor, and contract number. Mounting height and mounting location must conform to 36 CFR 1191 . Required blocking must be installed. Signs on doors or other surfaces must not be installed until finishes on such surfaces have been installed. Signs installed on glass surfaces must be installed with matching blank back-up plates in accordance with manufacturer's instructions.
Do not install items that show visual evidence of biological growth.
3.1.1 Anchorage
Anchorage must be in accordance with approved manufacturer's instructions.
Anchorage not otherwise specified or shown must include slotted inserts, expansion shields, and powder-driven fasteners when approved for concrete;
toggle bolts and through bolts for masonry; machine carriage bolts for steel; lag bolts and screws for wood. Exposed anchor and fastener materials must be compatible with metal to which applied and must have matching color and finish.
a. Signs mounted to painted gypsum board surfaces must be removable for painting maintenance.
SECTION 10 14 00.20 Page 6
b. Mount signs mounted to lay-in ceiling grids with clip connections to ceiling tees.
c. Install signs mounted on metal surfaces with magnetic tape.
d. Install signs mounted on fabric surfaces with hook and loop tape or pin mount.
3.1.2 Protection and Cleaning
Protect the work against damage during construction. Hardware and electrical equipment must be adjusted for proper operation. Glass, frames, and other sign surfaces must be cleaned at completion of sign installation in accordance with the manufacturer's approved instructions and the requirements of Section 01 78 23 OPERATION AND MAINTENANCE DATA, Package
1. Submit six copies of maintenance instructions listing routine procedures, repairs, and guides.
-- End of Section --
SECTION 10 14 00.20 Page 7
SECTION TABLE OF CONTENTS
DIVISION 10 - SPECIALTIES
SECTION 10 21 13
TOILET COMPARTMENTS
08/17
PART 1 GENERAL
1.1 REFERENCES
1.2 SUBMITTALS
1.3 CERTIFICATIONS
1.3.1 Indoor Air Quality
1.3.1.1 Laminated Plastic and Solid Phenolic Products
1.4 REGULATORY REQUIREMENTS
1.5 DELIVERY, STORAGE, AND HANDLING
1.6 WARRANTY
PART 2 PRODUCTS
2.1 SYSTEM REQUIREMENTS
2.2 MATERIALS
2.2.1 Galvanized Steel Sheet
2.2.2 Sound-Deadening Cores
2.2.3 Anchoring Devices and Fasteners
2.2.4 Brackets
2.2.5 Hardware and Fittings
2.2.5.1 General Requirements
2.2.5.2 Finishes
2.2.6 Door Hardware
2.2.6.1 Hinges
2.2.6.2 Latch and Pull
2.2.6.3 Coat Hooks
2.3 PARTITION PANELS AND DOORS
2.3.1 Toilet Enclosures
2.3.2 Urinal Screens
2.4 FLOOR-ANCHORED PARTITIONS
2.5 PILASTER SHOES
2.6 HARDWARE
2.7 COLORS AND FINISHES
2.7.1 Colors
2.7.2 Finishes No.4 and No. 5
PART 3 EXECUTION
3.1 PREPARATION
3.2 METAL PARTITION FABRICATION
3.3 INSTALLATION
3.4 CEILING-HUNG PARTITIONS
3.5 FLOOR-ANCHORED PARTITIONS
3.6 OVERHEAD-BRACED PARTITIONS
3.7 FINAL ADJUSTMENT
3.8 CLEANING
SECTION 10 21 13 Page 1
-- End of Section Table of Contents --
SECTION 10 21 13 Page 2
SECTION 10 21 13
TOILET COMPARTMENTS
08/17
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ALUMINUM ASSOCIATION (AA)
AA DAF45 (2003; Reaffirmed 2009) Designation System for Aluminum Finishes
ASTM INTERNATIONAL (ASTM)
ASTM A123/A123M (2017) Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products
ASTM A167 (2011) Standard Specification for Stainless and Heat-Resisting Chromium-Nickel Steel Plate, Sheet, and Strip
ASTM A336/A336M (2018) Standard Specification for Alloy Steel Forgings for Pressure and High-Temperature Parts
ASTM A385/A385M (2017) Standard Practice for Providing High-Quality Zinc Coatings (Hot-Dip)
ASTM A653/A653M (2017) Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM B221 (2014) Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes
ASTM B36/B36M (2013) Standard Specification for Brass Plate, Sheet, Strip, and Rolled Bar
ASTM B456 (2017) Standard Specification for Electrodeposited Coatings of Copper Plus Nickel Plus Chromium and Nickel Plus Chromium
ASTM B86 (2013) Standard Specification for Zinc and Zinc-Aluminum (ZA) Alloy Foundry and Die Castings
SECTION 10 21 13 Page 3
ASTM D6386 (2016) Standard Practice for Preparation of Zinc (Hot-Dip Galvanized) Coated Iron and Steel Product and Hardware Surfaces for Painting
CALIFORNIA DEPARTMENT OF PUBLIC HEALTH (CDPH)
CDPH SECTION 01350 (2010; Version 1.1) Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources using Environmental Chambers
INTERNATIONAL CODE COUNCIL (ICC)
ICC A117.1 COMM (2017) Standard And Commentary Accessible and Usable Buildings and Facilities
SCIENTIFIC CERTIFICATION SYSTEMS (SCS)
SCS SCS Global Services (SCS) Indoor Advantage
SOCIETY OF AUTOMOTIVE ENGINEERS INTERNATIONAL (SAE)
SAE AMS2460 (2013; Rev A) Plating, Chromium
U.S. GENERAL SERVICES ADMINISTRATION (GSA)
CID A-A-60003 (Basic) Partitions, Toilet, Complete
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
36 CFR 1191 Americans with Disabilities Act (ADA) Accessibility Guidelines for Buildings and Facilities; Architectural Barriers Act (ABA) Accessibility Guidelines
UNDERWRITERS LABORATORIES (UL)
UL 2818 (2013) GREENGUARD Certification Program For Chemical Emissions For Building Materials, Finishes And Furnishings
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submittals with an "S" are for inclusion in the Sustainability eNotebook, in conformance to Section 01 33 29 SUSTAINABILITY REPORTING. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Fabrication Drawings
Installation Drawings; G RO
SECTION 10 21 13 Page 4
SD-03 Product Data
Cleaning and Maintenance Instructions
Colors And Finishes
Galvanized Steel Sheet
Sound-Deadening Cores
Anchoring Devices and Fasteners
Hardware and Fittings
Brackets
Door Hardware
Pilaster Shoes
Finishes; G, AE
SD-04 Samples
Colors and Finishes; G , AE
Hardware and Fittings
Anchoring Devices and Fasteners
SD-07 Certificates
Warranty
SD-11 Closeout Submittals
1.3 CERTIFICATIONS
1.3.1 Indoor Air Quality
1.3.1.1 Laminated Plastic and Solid Phenolic Products
Provide products certified to meet indoor air quality requirements by UL 2818 (Greenguard) Gold, SCS Global Services Indoor Advantage Gold or provide certification or validation by other third-party program that products meet the requirements of this Section. Provide current product certification documentation from certification body. When product does not have certification, provide validation that product meets the indoor air quality product requirements cited herein.
SECTION 10 21 13 Page 5
1.4 REGULATORY REQUIREMENTS
Conform to ICC A117.1 COMM code for access for the handicapped operation of toilet compartment door and hardware.
1.5 DELIVERY, STORAGE, AND HANDLING
Deliver materials in the manufacturer's original unopened packages with the brand, item identification, and project reference clearly marked. Store components in a dry location that is adequately ventilated; free from dust, water, other contaminants, and damage during delivery, storage, and construction.
1.6 WARRANTY
Provide certification or warranties that toilet partitions will be free of defects in materials, fabrication, finish, and installation and will remain so for a period of not less than 25 years after completion.
PART 2 PRODUCTS
2.1 SYSTEM REQUIREMENTS
Provide a complete and usable toilet partition system, including toilet enclosures, room entrance screens, urinal screens, system of panels, hardware, and support components. Furnish the partition system from a single manufacturer, with a standard product as shown in the most recent catalog data. Submit Fabrication Drawings for metal toilet partitions and urinal screens consisting of fabrication and assembly details to be performed in the factory. Submit manufacturer's Cleaning and Maintenance Instructions with Fabrication Drawings for review.
2.2 MATERIALS
2.2.1 Galvanized Steel Sheet
Provide galvanized steel sheet cold-rolled, stretcher-level, commercial quality material, conforming to ASTM A653/A653M . Conform surface preparation of material for painting to ASTM D6386, Method A.
2.2.2 Sound-Deadening Cores
Provide sound deadening consisting of treated kraft paper honeycomb cores with a cell size of not more than 1 inch. Resin-material content must weigh not less than 11 percent of the finished core weight. Expanded cores must be faced on both sides with kraft paper.
2.2.3 Anchoring Devices and Fasteners
Provide steel anchoring devices and fasteners hot-dipped galvanized after fabrication, in conformance with ASTM A385/A385M and ASTM A123/A123M .
Conceal all galvanized anchoring devices.
2.2.4 Brackets
Wall brackets must be two-ear panel brackets, T-style, 1-inch stock.
Provide stirrup style panel-to-pilaster brackets.
SECTION 10 21 13 Page 6
2.2.5 Hardware and Fittings
2.2.5.1 General Requirements
Conform hardware for the toilet partition system to CID A-A-60003 for the specified type and style of partitions. Provide hardware finish highly resistant to alkalis, urine, and other common toilet room acids. Comply latching devices and hinges for handicap compartments with 36 CFR 1191 ;
provide stainless steel devices and hinges with door latches that operate without either tight grasping or twisting of the wrist of the operator.
Submit three samples of each item, including anchoring devices and fasteners. Approved hardware samples may be installed in the work if properly identified.
Material Conformance Standard
Cold-rolled sheet steel ASTM A336/A336M, commercial quality
Zinc-base alloy ASTM B86, Alloy AC41-A
Brass ASTM B36/B36M, Alloy C26800
Aluminum ASTM B221
Corrosion-resistant steel ASTM A167, Type 304
2.2.5.2 Finishes
a. Chrome plating must conform to ASTM B456.
b. Finish must conform to SAE AMS2460, Class I, Type III.
c. Aluminum must have a clear anodic coating conforming to AA DAF45.
d. Corrosion-resistant steel must have a No. 4 finish.
e. Exposed fasteners must match the hardware and fittings.
2.2.6 Door Hardware
2.2.6.1 Hinges
Hinges must be adjustable to hold in-swinging doors open at any angle up to 90 degrees and outswinging doors to 10 degrees. Provide self-lubricating hinges with the indicated swing. Hinges must be the cutout-insert type.
2.2.6.2 Latch and Pull
Latch and pull must be a combination rubber-faced door strike and keeper equipped with emergency access.
2.2.6.3 Coat Hooks
Coat hooks must be combination units with hooks and rubber tipped pins.
SECTION 10 21 13 Page 7
2.3 PARTITION PANELS AND DOORS
Fabricate partition panels and doors not less than 1 inch thick with face sheets not less than 0.0396 inch thick.
Provide solid polyethylene toilet partitions and screens with recycled content of 30 percent minimum. Provide data identifying percentage of recycled content for plastic, solid polyethylene partitions and screens.
Provide laminated plastic and solid phenolic toilet partitions and urinal screens to meet the emissions requirements of CDPH SECTION 01350 (use the office or classroom requirements, regardless of space type). Provide certification or validation of indoor air quality for laminated plastic partitions and screens.
2.3.1 Toilet Enclosures
Provide and conform toilet enclosures to CID A-A-60003 , Type I, Style B, floor mounted . Furnish width, length, and height of toilet enclosures as shown. Provide a width of 1 inch. Finish surface of panels must be solid polyethylene, Finish 5; water resistant; graffiti resistant; non-absorbent; .
Reinforce panels indicated to receive toilet paper holders or grab bars for mounting of the items required. Provide grab bars to withstand a bending stress, shear stress, shear force, and a tensile force induced by 250 lbf.
Grab bars must not rotate within their fittings.
2.3.2 Urinal Screens
Provide and conform urinal screens to CID A-A-60003 , Type III, Style B, wall mounted . Provide finish for surface of screens as solid polyethylene, Finish 5; water resistant; graffiti resistant; non-absorbent; .
Furnish width and height of urinal screens as shown. Provide thickness of 1 inch. Secure wall hung urinal screens with a minimum of three wall stirrup brackets. Fabricate screens from the same types of panels and pilasters as the toilet partitions. Use corrosion-resistant stainless steel fittings and fasteners.
2.4 FLOOR-ANCHORED PARTITIONS
Pilasters must be not less than 1-1/4 inch thick with face sheets not less than 0.0635 inch thick. Provide anchoring device at the bottom of the pilaster consisting of a steel bar not less than 1/2 by 7/8 inch welded to the reinforced face sheets and having not less than two 3/8 inch round anchorage devices for securing to the floor slab. Provide anchorage devices complete with threaded rods, expansion shields, lock washers, and leveling-adjustment nuts. Trim piece at the floor must be 3 inch high and fabricated from not less than 0.030 inch thick corrosion-resistant stainless steel.
2.5 PILASTER SHOES
Provide shoes at pilasters to conceal floor-mounted anchorage. Pilaster shoes must be stainless steel . Height must be 3 inches.
2.6 HARDWARE
Provide hardware for the toilet partition system that conforms to CID A-A-60003 for the specified type and style of partitions. Provide hardware pre-drilled by manufacturer. Use a hardware finish that is highly
SECTION 10 21 13 Page 8 resistant to alkalis, urine, and other common toilet room acids. Hardware includes: chrome plated non ferrous cast pivot hinges, gravity type, adjustable for door close positioning; nylon bearings; chrome plated aluminum door latch; door strike and keeper with rubber bumper; and cast alloy chrome plated coat hook and bumper, . Provide latching devices and hinges for handicap compartments complying with 36 CFR 1191 and stainless steel door latches that operate without either tight grasping or twisting of the wrist of the operator. Use stainless steel, tamper proof type screws and bolts. Wall mounting brackets must be continuous, full height, stainless steel , in accordance with toilet compartment manufacturer's instructions.
2.7 COLORS AND FINISHES
2.7.1 Colors
Provide manufacturer's standard color charts for color of finishes for toilet partition system components. Submit three samples showing a finished edge on two adjacent sides and core construction, each not less than 12-inch square
2.7.2 Finishes No.4 and No. 5
Provide solid plastic fabricated of polymer resins (polyethylene) formed under high pressure rendering a single component section not less than one inch thick. Colors must extend throughout the panel thickness. Provide exposed finish surfaces: smooth, waterproof, non-absorbent, and resistant to staining and marking with pens, pencils, or other writing devices.
Solid plastic partitions must not show any sign of deterioration when immersed in the following chemicals and maintained at a temperature of 80 degrees F for a minimum of 30 days:
Acetic Acid (80 percent) Hydrochloric Acid (40 percent)
Acetone Hydrogen Peroxide (30 percent)
Ammonia (liquid) Isopropyl Alcohol
Ammonia Phosphate Lactic Acid (25 percent)
Bleach (12 percent) Lime Sulfur
Borax Nicotine
Brine Potassium Bromide
Caustic Soda Soaps
Chlorine Water Sodium Bicarbonate
Citric Acid Trisodium Phosphate
Copper Chloride Urea; Urine
SECTION 10 21 13 Page 9
Core Oils Vinegar
PART 3 EXECUTION
3.1 PREPARATION
Take field measurements prior to the preparation of drawing and fabrication to ensure proper fits. Verify that field measurements, surfaces, substrates and conditions are as required, and ready to receive work.
Verify correct spacing of plumbing fixtures. Verify correct location of built in framing, anchorage, and bracing. Report in writing to Contracting Officer prevailing conditions that will adversely affect satisfactory execution of the work of this section. Do not proceed with work until unsatisfactory conditions have been corrected.
3.2 METAL PARTITION FABRICATION
a. Fabricate metal Partition Panels, doors, screens, and pilasters required for the project from galvanized-steel face sheets with formed edges. Face sheets must be pressure-laminated to the sound-deadening core with edges sealed with a continuous locking strip and corners mitered and welded. Ground all welds smooth. Provide concealed reinforcement for installation of hardware, fittings, and accessories.
Surface of face sheets must be smooth and free from wave, warp, or buckle.
b. Before application of an enamel coating system, solvent-clean galvanized-steel surfaces to remove processing compounds, oils, and other contaminants harmful to coating-system adhesion. After cleaning,coat the surfaces with a metal-pretreatment phosphate coating. After pretreatment, finish exposed galvanized-steel surfaces with a baked-enamel coating system as specified.
c. Provide an enamel coating system consisting of a factory-applied baked acrylic enamel coating system. Coating system must be a durable, washable, stain-resistant, mar-resistant finish.
3.3 INSTALLATION
Do not install items that show visual evidence of biological growth.
Install partitions rigid, straight, plumb, and level, with the panels centered between the fixtures. Provide a panel clearance of not more than 1/2 inch and secure the panels to walls and pilasters with not less than two wall brackets attached near the top and bottom of the panel. Locate wall brackets so that holes for wall bolts occur in masonry or tile joints. Secure Panels to pilasters with brackets matching the wall brackets. Provide for adjustment due to minor floor variations. Locate head rail joints at pilaster center lines. Install adjacent components for consistency of line and plane. Equip each door with hinges, one door latch, and one coat hook and bumper. Align hardware to uniform clearance at vertical edges of doors.
a. Secure panels to hollow plastered walls with toggle bolts using not less than 1/4-20 screws of the length required for the wall thickness.
Toggle bolts must have a load-carrying strength of not less than 600 pounds per anchor.
b. Secure panels to ceramic tile on hollow plastered walls or hollow
SECTION 10 21 13 Page 10 concrete-masonry walls with toggle bolts using not less than 1/4-20 screws of the length required for the wall thickness. Toggle bolts must have a load-carrying strength of not less than 600 pounds per anchor.
c. Secure panels to solid masonry or concrete with lead or brass expansion shields designed for use with not less than 1/4-20 screws, with a shield length of not less than 1-1/2 inch. Expansion shields must have a load-carrying strength of not less than 600 pounds per anchor.
d. Submit Installation Drawings for metal toilet partitions and urinal screens showing plans, elevations, details of construction, hardware, reinforcing and blocking, fittings, mountings and escutcheons.
Indicate on drawings the type of partition, location, mounting height, cutouts, and reinforcement required for toilet-room accessories.
3.4 CEILING-HUNG PARTITIONS
Secure pilasters to the structural support above with the anchorage device specified. Make all leveling devices readily accessible for leveling, plumbing, and tightening the installation. Level the bottoms of doors with bottoms of pilasters when doors are in a closed position.
3.5 FLOOR-ANCHORED PARTITIONS
Secure pilasters to the floor with the anchorage device specified. Make all leveling devices readily accessible for leveling, plumbing, and tightening the installation. Level tops of doors with tops of pilasters when doors are in a closed position. Expansion shields must have a minimum 2-inch penetration into the concrete slab.
3.6 OVERHEAD-BRACED PARTITIONS
Secure pilasters to the floor with the anchorage device specified. Make all leveling devices readily accessible for leveling, plumbing, and tightening the installation. Secure overhead brace to the pilaster face with not less than two fasteners per face. Expansion shields must have a minimum 2-inch penetration into the concrete slab. Make tops of doors parallel with the overhead brace when doors are in a closed position.
3.7 FINAL ADJUSTMENT
After completion of the installation, make final adjustments to the pilaster-leveling devices, door hardware, and other working parts of the partition assembly. Doors must have a uniform vertical edge clearance of approximately 3/16 inch and must rest open at approximately 30 degrees when unlatched.
3.8 CLEANING
Baked enamel finish must be touched up with the same color of paint that was used for the finish. Clean all surfaces of the work, and adjacent surfaces soiled as a result of the work, in an approved manner compliant with the manufacturer's recommended cleaning and protection from damage procedures until accepted. Remove all equipment, tools, surplus materials, and work debris from the site.
-- End of Section --
SECTION 10 21 13 Page 11
SECTION TABLE OF CONTENTS
DIVISION 10 - SPECIALTIES
SECTION 10 26 00
WALL AND DOOR PROTECTION
08/17
PART 1 GENERAL
1.1 REFERENCES
1.2 SUBMITTALS
1.3 CERTIFICATIONS
1.3.1 Indoor Air Quality
1.3.1.1 Wall Covering/Panels
1.3.1.2 Adhesives and Sealants
1.4 DELIVERY, STORAGE, AND HANDLING
1.5 WARRANTY
PART 2 PRODUCTS
2.1 STANDARD PRODUCTS
2.1.1 Resilient Material
2.1.1.1 Minimum Impact Resistance
2.1.1.2 Fire Rating
2.1.1.3 Integral Color
2.1.1.4 Chemical and Stain Resistance
2.1.1.5 Fungal and Bacterial Resistance
2.2 CORNER GUARDS
2.2.1 Resilient Corner Guards
2.2.2 Stainless Steel Corner Guards
2.3 TRIM, FASTENERS AND ANCHORS
2.4 FINISH
2.4.1 Stainless Steel Finish
2.4.2 Resilient Material Finish
2.5 ADHESIVES
2.6 COLOR
PART 3 EXECUTION
3.1 INSTALLATION
3.1.1 Corner Guards and Wall Guards (Bumper Guards)
3.1.2 Door, Door Frame Protectors, and Wall Panels
3.1.3 Stainless Steel Guards
-- End of Section Table of Contents --
SECTION 10 26 00 Page 1
SECTION 10 26 00
WALL AND DOOR PROTECTION
08/17
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM A240/A240M (2017) Standard Specification for Chromium and Chromium-Nickel Stainless Steel Plate, Sheet, and Strip for Pressure Vessels and for General Applications
ASTM B221 (2014) Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes
ASTM D256 (2010) Determining the Izod Pendulum Impact Resistance of Plastics
ASTM D543 (2014) Standard Practices for Evaluating the Resistance of Plastics to Chemical Reagents
ASTM D635 (2014) Standard Test Method for Rate of Burning and/or Extent and Time of Burning of Self-Supporting Plastics in a Horizontal Position
ASTM E84 (2018) Standard Test Method for Surface Burning Characteristics of Building Materials
ASTM G21 (2015) Standard Practice for Determining Resistance of Synthetic Polymeric Materials to Fungi
CALIFORNIA DEPARTMENT OF PUBLIC HEALTH (CDPH)
CDPH SECTION 01350 (2010; Version 1.1) Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources using Environmental Chambers
GREEN SEAL (GS)
GS-36 (2013) Adhesives for Commercial Use
SECTION 10 26 00 Page 2
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 80 (2016; TIA 16-1) Standard for Fire Doors and Other Opening Protectives
SCIENTIFIC CERTIFICATION SYSTEMS (SCS)
SCS SCS Global Services (SCS) Indoor Advantage
SOCIETY OF AUTOMOTIVE ENGINEERS INTERNATIONAL (SAE)
SAE J1545 (2005; R 2014) Instrumental Color Difference Measurement for Exterior Finishes, Textiles and Colored Trim
SOUTH COAST AIR QUALITY MANAGEMENT DISTRICT (SCAQMD)
SCAQMD Rule 1168 (2017) Adhesive and Sealant Applications
UNDERWRITERS LABORATORIES (UL)
UL 2818 (2013) GREENGUARD Certification Program For Chemical Emissions For Building Materials, Finishes And Furnishings
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submittals with an "S" are for inclusion in the Sustainability eNotebook, in conformance to Section 01 33 29 SUSTAINABILITY REPORTING. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Corner Guards; G , RO
Wall Guards (Bumper Guards); G , RO
Door Protectors; G , RO
Wall Covering/Panels; G , RO
SD-03 Product Data
Corner Guards; G , RO
Wall Guards (Bumper Guards); G , RO
Door Protectors; G , RO
Wall Covering/Panels; G
SD-04 Samples
Finish; G , RO
SECTION 10 26 00 Page 3
SD-06 Test Reports
Corner Guards
Wall Guards (Bumper Guards)
Door Protectors
Wall Covering/Panels
SD-07 Certificates
Corner Guards
Wall Guards (Bumper Guards)
Door Protectors
Indoor air quality for adhesives; S
1.3 CERTIFICATIONS
1.3.1 Indoor Air Quality
1.3.1.1 Wall Covering/Panels
Provide sheet and high impact resistant resilient materials certified to meet indoor air quality requirements by UL 2818 (Greenguard) Gold, SCS Global Services Indoor Advantage Gold or provide certification or validation by other third-party program that products meet the requirements of this section. Provide current product certification documentation from certification body. When product does not have certification, provide validation that product meets the indoor air quality product requirements cited herein.
1.3.1.2 Adhesives and Sealants
Provide products certified to meet indoor air quality requirements by UL 2818 (Greenguard) Gold, SCS Global Services Indoor Advantage Gold or provide certification or validation by other third-party program that products meet the requirements of this section. Provide current product certification documentation from certification body When product does not have certification, provide validation that product meets the indoor air quality product requirements cited herein..
1.4 DELIVERY, STORAGE, AND HANDLING
Deliver materials to the project site in manufacturer's original unopened containers with seals unbroken and labels and trademarks intact. Keep materials dry, protected from weather and damage, and stored under cover.
Materials must be stored at approximately 70 degrees F for at least 48 hours prior to installation.
1.5 WARRANTY
Provide manufacturer's standard performance guarantees or warranties that extend beyond a 1 year period.
SECTION 10 26 00 Page 4
PART 2 PRODUCTS
2.1 STANDARD PRODUCTS
To the maximum extent possible, corner guards, door and door frame protectors, wall guards (bumper guards), wall panels and wall covering must be the standard products of a single manufacturer and must be furnished as detailed. Drawings show general configuration of products required, and items differing in minor details from those shown will be acceptable.
2.1.1 Resilient Material
Provide resilient material consisting of high impact resistant extruded acrylic vinyl, polyvinyl chloride, or injection molded thermal plastic conforming to the following:
2.1.1.1 Minimum Impact Resistance
Minimum impact resistance must be 18 ft-lbs/sq. inch when tested in accordance with ASTM D256, (Izod impact, ft-lbs per sq inch notched).
2.1.1.2 Fire Rating
Fire rating must be Class 1 when tested in accordance with ASTM E84, having a maximum flame spread of 25 and a smoke developed rating of 450 or less.
Material must be rated self extinguishing when tested in accordance with ASTM D635. Material must be labeled and tested by an approved nationally known testing laboratory. Resilient material used for protection on fire rated doors and frames must be listed by the testing laboratory performing the tests. Resilient material installed on fire rated wood/steel door and frame assemblies must have been tested on similar type assemblies. Test results of material tested on any other combination of door/frame assembly will not be acceptable.
2.1.1.3 Integral Color
Colored components must have integral color and must be matched in accordance with SAE J1545 to within plus or minus 1.0 on the CIE-LCH scales.
2.1.1.4 Chemical and Stain Resistance
Materials must be resistant to chemicals and stains reagents in accordance with ASTM D543.
2.1.1.5 Fungal and Bacterial Resistance
Materials must be resistant to fungi and bacteria in accordance with ASTM G21, as applicable.
2.2 CORNER GUARDS
2.2.1 Resilient Corner Guards
Corner guard units must be surface mounted type, radius formed to profile shown. Corner guards must extend from floor to ceiling. Mounting hardware, cushions, and base plates must be furnished. Assembly must consist of a snap-on corner guard formed from high impact resistant resilient material, mounted on a continuous aluminum retainer. Extruded aluminum retainer must conform to ASTM B221, alloy 6063, temper T5 or T6. Provide aluminum
SECTION 10 26 00 Page 5 components that contain a minimum of 35 percent recycled content. Provide data identifying percentage of recycled content for aluminum component of corner guards. Flush mounted type guards must act as a stop for adjacent wall finish material. Factory fabricated end closure caps must be furnished for top and bottom of surface mounted corner guards. Flush mounted corner guards installed in fire rated wall must maintain the rating of the wall. Insulating materials that are an integral part of the corner guard system must be provided by the manufacturer of the corner guard system. Exposed metal portions of fire rated assemblies must have a paintable surface.
2.2.2 Stainless Steel Corner Guards
Stainless steel corner guards must be fabricated of 18 gauge thick material conforming to ASTM A240/A240M , type 302 or 304. Provide stainless steel base material that contains a minimum of 60 percent recycled content.
Provide data identifying percentage of recycled content for steel component of corner guards. Corner guards must be 6'-0" feet high. Corner guard must be formed to dimensions shown.
2.3 TRIM, FASTENERS AND ANCHORS
Provide vinyl trim, fasteners and anchors for each specific installation as shown.
2.4 FINISH
Submit three samples indicating color and texture of materials requiring color and finish.
2.4.1 Stainless Steel Finish
Finish for stainless steel must be in accordance with ASTM A240/A240M , Type 302 or 304 , finish number 4.
2.4.2 Resilient Material Finish
Finish for resilient material must be embossed velour texture with colors in accordance with SAE J1545 .
2.5 ADHESIVES
Adhesive for resilient material must be in accordance with manufacturers recommendations. Provide sealants and non-aerosol adhesive products used on the interior of the building (defined as inside of the weatherproofing system) that meet either emissions requirements of CDPH SECTION 01350 (limit requirements for either office or classroom spaces regardless of space type) the VOC content requirements of SCAQMD Rule 1168 , or VOC content requirements of GS-36. Provide certification or validation of indoor air quality for adhesives.
2.6 COLOR
Color must be as indicated.
SECTION 10 26 00 Page 6
PART 3 EXECUTION
3.1 INSTALLATION
Do not install items that show visual evidence of biological growth.
3.1.1 Corner Guards and Wall Guards (Bumper Guards)
Material must be mounted at location indicated in accordance with manufacturer's recommendations.
3.1.2 Door, Door Frame Protectors, and Wall Panels
Surfaces to receive protection must be clean, smooth, and free of obstructions. Protectors must be installed after frames are in place, but prior to hanging of doors, in accordance with manufacturer's specific instructions. Adhesives must be applied in controlled environment in accordance with manufacturer's recommendations. Protection for fire doors and frames must be installed in accordance with NFPA 80 .
3.1.3 Stainless Steel Guards
a. Mount guards on external corners of interior walls, partitions and columns as in accordance with manufacturer's recommendations.
b. Where corner guards are installed on walls, partitions or columns finished with plaster or ceramic tile, anchor corner guards as indicated . Coat back surfaces of corner guards, where shown, with a non-flammable, sound deadening material. Corner guards must overlap finish plaster surfaces.
c. Where corner guards are installed on exposed structural glazed facing tile units or masonry wall, partitions or columns, anchor corner guards as indicated . Grout spaces solid between guards and backing with portland cement and sand mortar.
d. Where corner guards are installed on gypsum board, clean surfaces and anchor guards with a neoprene solvent-type contact adhesive specifically manufactured for use on gypsum board construction. Remove excess adhesive from the guard edges and allow to cure undisturbed for 24 hours.
e. For wall guards, space brackets at no more than 3 feet on centers and anchor to the wall in accordance with the manufacturer's installation instructions.
-- End of Section --
SECTION 10 26 00 Page 7
SECTION TABLE OF CONTENTS
DIVISION 10 - SPECIALTIES
SECTION 10 28 00.00 48
TOILET AND SHOWER ACCESSORIES
04/06
PART 1 GENERAL
1.1 SUBMITTALS
1.2 REGULATORY REQUIREMENTS
1.3 FIELD MEASUREMENTS
1.4 COORDINATION
1.5 WARRANTY
1.6 DELIVERY, STORAGE, AND HANDLING
PART 2 PRODUCTS
2.1 MAUFACTURED UNITS
2.1.1 Anchors and Fasteneers
2.1.2 Stainless Steel Sheet:
2.1.3 Adhesive:
2.1.4 Expansion Shields:
2.2 FABRICATION
2.3 KEYING
2.4 FINISHES
2.4.1 Galvanizing:
2.4.2 Shop Primed Ferrous Metals:
2.4.3 Stainless Steel:
2.4.4 Back Painting Components:
PART 3 EXECUTION
3.1 EXAMINATION
3.2 PREPARATION
3.3 INSTALLATION
3.4 SCHEDULE
3.4.1 A1, Mop and Broom Holder
3.4.2 A2, Stainless Steel Framed Mirror
3.4.3 A11-b, Surface Mounted Multi-Roll Toilet Tissue Dispenser w/
Utility Shelf - B2840 Rolls Side-By-Side w/ Shelf above.
3.4.4 A11-c, Surface-Mounted Napkin Disposal
3.4.5 A13, Stainless Steel Utility Hook (TP on drawings):
3.4.6 A15, Recessed Soap Holder and Bar
3.4.7 A16, Heavy-Duty Shower Curtain Rod with Concealed Mounting
3.4.8 A17, Stainless Steel Curtain Hook
3.4.9 A18, Opaque White Vinyl Shower Curtain
3.4.10 A21-b, Stainmless Steel Framed Mirror
3.4.11 A22-d, Surface-Mounted Paper Towel Dispenser
-- End of Section Table of Contents --
SECTION 10 28 00.00 48 Page 1
SECTION 10 28 00.00 48
TOILET AND SHOWER ACCESSORIES
04/06
PART 1 GENERAL
1.1 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. The following shall be submitted in accordance with Section 013 30 00.00 06 SUBMITTAL PROCEDURES:
Acceptable Manufacturer Products;
Manufacturers products listed in this specification are referenced to establish a standard of quality. When the specific product listed is submitted by the Contractor, that submittal will be considered For Information Only. When an equal to that named in this specification is submitted, it shall be for Government Approval (G). The following manufacturer products are specifically mentioned in this specification:
American Specialties Inc.