This federal contract opportunity solicitation is for the design/build renovation of HPW Building 441 at Wright-Patterson Air Force Base in Ohio. The estimated construction cost is between $10-25 million, with a NAICS code of 236220 and size standard of $39.5 million. This is a 100% total small business set-aside solicitation issued by the Department of the Army Corps of Engineers Louisville District. Interested vendors must register at beta.SAM.gov to download the solicitation, as faxed, telephoned or mailed requests will not be accepted. The solicitation details the required design/build renovation services and provides response and award date information.

View the file

Other files

Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

LOUISVILLE DISTRICT

US Army Corps of Engineers ®

WRIGHT PATTERSON AIR FORCE BASE

REPAIR FSD-1 INTERIOR, EXTERIOR, AND HVAC

FACILITY 20441

CONTRACT NO.:

ISSUE DATE.:

FA8601-13-D0003

JULY 2020

PROJECT #ZHTV 160073

A DVANCED

E NGINEERING

C ONSULTANTS

Mechanical | Electrical | Plumbing | Fire Protection 1405 Dublin Road Tel: (614) 486-4778 Columbus, Ohio 43215 Fax: (614) 486-4082

P2 #476238

W912QR20B0021SOLICITATION NO.:

S O

LI

C

IT

A

TI

O

N N

O

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

TI

O

N

1 3 5

C

7 9

A

M A

R K

IS

S

U E

D A

TE

S

IZ

E

S U

B M

IT

TE

D B

Y

C O

N

TR

A C

T N

O

SHEET ID

D A

TE

US Army Corps of Engineers

U .S

. A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

LO

U

IS

V

IL

LE

, K Y

LO

U

IS

V

IL

LE

D

IS

TR

IC

T

W R

IG

H

T P

A

TT

E R

S O

N A

FB

R

E P

A

IR

F S

D -1

IN

TE

R

IO

R , E

X

TE

R

IO

R , A

N D

H V

A C

FA

C

IL

IT

Y

(Z H

TV

B

D

E

F

G

2 4 6 8 10

JU

LY

W

2Q R

B

FA

-1

3- D

A D

V A

N C

E D

E N

G

IN

E E

R

IN

G C

O N

S U

LT

A

N

TS

M ec ha ni ca l |

E le ct ric al

Pl um bi ng

Fi re P ro te ct io n

D ub lin

R oa d Te l:

(6

) 4

-4

C ol um bu s, O hi o

Fa x:

(6

) 4

-4

UNCLASSIFIED//FOR OFFICIAL USE ONLY - PROPERTY OF THE US GOVERNMENT, LIMITED REPRODUCTION AND DISSEMINATION TO MINIMUM REQUIRED TO BID AND CONSTRUCT THE PROJECT

UNCLASSIFIED//FOR OFFICIAL USE ONLY - PROPERTY OF THE US GOVERNMENT, LIMITED REPRODUCTION AND DISSEMINATION TO MINIMUM REQUIRED TO BID AND CONSTRUCT THE PROJECT

H

P

N O

CERTIFIED FINAL

07/17/2020

G E

N E

R A

L C

O V

E R

P A

G E

G-001

G .L

E

IT

C H

K .F

IE

LD

S

K .F

IE

LD

S

CERTIFIED FINAL

ARIMS: 200A Disposition: Maintain for 15yrs after construction

31 July 2020

W912QR20B0021

W

2Q R

B0

1-

1. COORDINATE ALL WORK THROUGH THE GOVERNMENT CONTRACTING

OFFICER.

2. ANY NEW TYPES OF HAZARDOUS MATERIALS TO BE USED, AND THE

WASTES THAT MAY BE GENERATED AS A RESULT OF THAT USE NEED

TO BE CONSIDERED IN CONSTRUCTION. IF APPROPRIATE, DEDICATED

SPACE FOR STORAGE OF HAZARDOUS MATERIALS AND WASTE NEED

TO BE PROVIDED. IN ADDITION PROPER COORDINATION IS NEEDED

WITH 88 CEG/CEIEC. QUESTIONS CONCERNING THE REQUIREMENTS

FOR STORAGE AND DISPOSAL OF ANY HAZARDOUS MATERIALS CAN

BE ADDRESSED BY THE 88 CEG/CEIEC HAZARDOUS MATERIALS PM,

MIKE VAUGHN, (937-257-8028 OR MICHAEL.VAUGHN.3@US.AF.MIL) OR

88 CEG/CEIEC HAZARDOUS WASTE PM, GARY SELBY (937-257-3349 OR

GARY.SELBY@US.AF.MIL).

3. BECAUSE IT IS NOT POSSIBLE TO DEFINITELY KNOW THE LOCATION OF

ALL POTENTIAL ASBESTOS CONTAINING MATERIALS (ACM) WITHIN A

FACILITY, FOR INSTANCE ACM FIRE WALLS OR ACM FLOOR TILE, THE

CONTRACTOR PERFORMING THIS WORK SHALL COMPLY WITH ALL

RELEVANT PARTS OF 29 CFR 1910.1001 AND/OR 29 CFR 1926.1101 AS

MAY BE APPLICABLE. A LIMITED ASBESTOS AND LEAD-BASED PAINT

SURVEY WAS PERFORMED ON 12 JUN 2017. THIS REPORT CAN BE

FOUND IN THE PROJECT SPECIFICATIONS. IDENTIFIED AREAS ARE

NOTED ON THE DRAWINGS. IF ADDITIONAL SUSPECT

ASBESTOS-CONTAINING MATERIAL IS FOUND THE CONTRACTOR SHALL

STOP WORK IMMEDIATELY AND NOTIFY THE CONTRACTING OFFICER.

4. CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE HIS OWN

TELEPHONE AND COMPUTER CONNECTIONS FOR HIS CONSTRUCTION

TRAILER ON SITE.

5. THE MAJORITY OF THE BUILDING WILL BE VACANT BUT SMALL

PORTIONS WILL REMAIN PARTIALLY OCCUPIED. CONTRACTOR SHALL

COORDINATE ALL ACTIVITIES REQUIRED IN BASE OCCUPIED AREAS

WITH THE GOVERNMENT PROJECT MANAGER, CONTRACTING OFFICER,

AND BUILDING SECURITY OPERATIONS OFFICER.

6. CONTRACTOR SHALL REQUEST AND RECEIVE PERMISSION PRIOR TO

ANY UTILITY OUTAGE A MINIMUM OF 2 WEEKS PRIOR TO OUTAGE.

7. CONTRACTOR SHALL KEEP CONSTRUCTION SITE CLEAN AT ALL TIMES.

8. SOIL DISTURBANCE DURING THIS PROJECT, INCLUDING EQUIPMENT

STAGING AREAS, WILL REQUIRE EROSION CONTROL MEASURES. FOR

PROJECTS THAT DISTURB LESS THAN AN ACRE OF SOIL, AN EROSION

CONTROL PLAN IS REQUIRED PRIOR TO DISTURBANCE. FOR

PROJECTS THAT DISTURB MORE THAN AN ACRE, A NOTICE OF INTENT

(NOI) MUST BE APPROVED BY THE OHIO EPA PRIOR TO ANY SOIL BEING

DISTURBED AS WELL AS A STORM WATER POLLUTION PREVENTION

PLAN (SWPPP) APPROVED BY 88 CEG/CEIEA. THE CONSTRUCTION

CONTRACTOR SHALL PREPARE AND SUBMIT THE SWPPP AND DRAFT

NOI TO THE CONTRACTING OFFICER'S REPRESENTATIVE TO BE

FORWARDED TO ENVIRONMENTAL MANAGEMENT, 88 CEG/CEIEA, FOR

REVIEW. ONCE THE SWPPP AND DRAFT NOI HAVE BEEN APPROVED BY

THE COR AND ENVIRONMENTAL MANAGEMENT, THE CONTRACTOR

SHALL PREPARE AND FORWARD THE FINAL NOI TO THE OHIO EPA.

PLEASE CONTACT AND 88 CEG/CEIEA WATER PM, KAREN BEASON, BY

EMAIL AT KAREN.BEASON@US.AF.MIL OR BY PHONE AT (937) 257-5899

FOR ADDITIONAL INFORMATION.

9. ANY FIRE SUPPRESSION EQUIPMENT CONTAINING IONIZING

RADIOACTIVE MATERIAL (SMOKE DETECTORS) AND ANY EMERGENCY

EXIT SIGNS CONTAINING IONIZING RADIOACTIVE MATERIAL SHALL BE

TURNED INTO 88 AMDS/SGPB. COORDINATE THIS TURN-IN WITH

WPAFB 88 AMDS/SGPB RADIATION SAFETY OFFICER AT 937-255-6815.

10. ALL METAL AND WIRING SHALL BE RECYCLED AT THE WPAFB BASE

RECYCLING CENTER. THE WPAFB RECYCLING CENTER IS AVAILABLE

FOR CONTRACTOR USE TO REDUCE WASTE DISPOSAL. ALL

RECYCLABLE METAL IS TO BE RECYCLED THROUGH THE BASE

RECYCLING CENTER. ALL RECYCLING MUST BE ACCOMPLISHED IN

ACCORDANCE WITH WPAFB SPECIFICATION SECTION 01 02 20.

CONTACT WPAFB RECYCLING PROGRAM MANAGER AT 937-257-5060 TO

CONFIRM WHAT MATERIALS ARE RECYCLABLE AND TO COORDINATE

TURN-IN. THE CONTRACTOR SHALL SUBMIT A QUARTERLY SUMMARY

REPORT TO THE GOVERNMENT CONTRACT REPRESENTATIVE IAW

WPAFB SPECIFICATION SECTION 01 02 20 STATING (1) THE COST TO

RECYCLE AND THE TONNAGE OF CONSTRUCTION AND DEMOLITION

MATERIALS RECYCLED, (2) THE COST TO DIVERT/REUSE THE TONNAGE

OF CONSTRUCTION AND DEMOLITION MATERIALS DIVERTED/REUSE, (3)

THE COST TO MULCH AND THE TONNAGE AND COST OF

CONSTRUCTION AND DEMOLITION MATERIALS MULCHED, (4) THE COST

FOR WASTE-TO-ENERGY AND THE TONNAGE OF CONSTRUCTION AND

DEMOLITION MATERIALS CONVERTED FROM WASTE-TO-ENERGY, (5)

THE COST TO LANDFILL AND THE TONNAGE OF CONSTRUCTION AND

DEMOLITION MATERIALS LAND-FILLED, (6) THE COST TO INCINERATE

AND THE TONNAGE OF CONSTRUCTION AND DEMOLITION MATERIALS

INCINERATED, AND (7) EXPLANATION OF THE DIVERSION RATE IF LESS

THAN 60%. THE QUARTERLY SUMMARY REPORTS SHALL BE RECEIVED

ON APRIL 7, JULY 7, OCTOBER 7, AND JANUARY 7 COVERING THE

THREE MONTHS PRIOR. THE QUARTERLY SUMMARY REPORTS SHALL

BE ON THE WPAFB DIVERSION FORM. FOR ADDITIONAL INFORMATION

CONTACT THE RECYCLING PM, DAVE DALTON, AT 937-257-5060 OR

DAVID.DALTON.2@US.AF.MIL.

11. TURN-IN ALL MERCURY CONTAINING DEVICES, SWITCHES AND

THERMOSTATS TO 88 CEG/CEIE IN ACCORDANCE WITH WPAFB

SPECIFICATION SECTION 01 02 20 FOR RECYCLING.

12. TURN-IN ALL MERCURY CONTAINING LAMPS TO 88 CEG/CEIE IN

ACCORDANCE WITH WPAFB SPECIFICATION SECTION 01 02 20.

13. TURN-IN ALL PCB CONTAINING LIGHT BALLAST TO 88 CEG/CEIE IN

ACCORDANCE WITH WPAFB SPECIFICATION SECTION 01 02 20.

14. REMOVE AND DISPOSE OF ANY ASBESTOS CONTAINING MATERIAL IN

ACCORDANCE WITH WPAFB SPECIFICATION SECTION 01 02 20.

15. ANY LEAD CONTAINING PAINT CONTROL MEASURES SHALL BE

PERFORMED IN ACCORDANCE WITH WPAFB SPECIFICATION 01 02 20.

16. RECOVER AND RECLAIM ANY REFRIGERANT IN ACCORDANCE WITH

WPAFB SPECIFICATION SECTION 02 09 10.

17. NO ASBESTOS-CONTAINING MATERIAL SHALL BE INSTALLED DURING

THIS PROJECT.

18. ALL WINDOW AND DOOR FRAME CAULKING AND GLAZING WILL BE

TREATED AS CONTAINING ASBESTOS UNLESS TESTING PROVES IT TO

BE ASBESTOS FREE.

19. THE GENERATION OF FUGITIVE EMISSIONS MUST BE KEPT TO A

MINIMUM USING APPROVED DUST SUPPRESSION METHODS SUCH AS

WATER SPRAYS ON AREAS OF HIGH DUST GENERATION. FOR

ADDITIONAL INFORMATION PLEASE CONTACT 88 CEG/CEIE AIR PM

CHRIS TUMBUSCH (937-257-2455 OR

CHRISTOPHER.TUMBUSCH@US.AF.MIL).

20. 30 DAYS PRIOR TO THE START OF WORK, THE CONTRACTOR SHALL

TAKE A REPRESENTATIVE SAMPLE OF THE HVAC SYSTEM WATER TO

DETERMINE WHETHER IT CAN BE DRAINED DIRECTLY INTO THE

SANITARY SEWER. ANALYZE THE WATER TO DETERMINE THE TOTAL

LEVEL OF EACH OF THE FOLLOWING: CADMIUM, CHROMIUM, COPPER,

CYANIDE, LEAD, MERCURY, MOLYBDENUM, NICKEL, SILVER, ZINC AND

SULFIDE. THE LAB PERFORMING THE ANALYSIS MUST BE CERTIFIED

BY OHIO EPA TO ANALYZE FOR THESE PARAMETERS. PROVIDE A

COPY OF THE LAB'S REPORT TO THE CONTRACTING OFFICER, WHO

WILL IN TURN FORWARD IT TO 88 CEG/CEIEA FOR A DETERMINATION

ON THE WASTEWATER DISPOSAL METHOD.

21. UTILITIES HAVE BEEN PRIVATIZED AT WRIGHT PATTERSON AIR FORCE

BASE. CONNECTION TO WATER, SANITARY, AND NATURAL GAS

INFRASTRUCTURE MUST BE COORDINATED WITH THE APPROPRIATE

UTILITY OWNER.

22. THERE WILL BE NO WORK ACCOMPLISHED ON ALL FEDERAL HOLIDAYS.

(NEW YEAR'S DAY, MLK DAY, PRESIDENT'S DAY, MEMORIAL DAY,

INDEPENDENCE DAY, LABOR DAY, COLUMBUS DAY, VETERANS DAY,

THANKSGIVING, AND CHRISTMAS DAY).

23. DEMOLITION OF LOAD-BEARING WALLS OR STRUCTURAL

COMPONENTS REQUIRE NOTIFICATION OF DEMOLITION AND

RENOVATION TO THE REGIONAL AIR POLLUTION AND CONTROL

AGENCY (RAPCA) A MINIMUM OF 10 WORK DAYS PRIOR TO BEGINNING

CONSTRUCTION.

24. IF ANY DRINKING WATER MAINS ARE BEING EXTENDED, UPSIZED, OR

NEW MAINS ARE BEING INSTALLED, A PLANS APPROVAL MAY BE

REQUIRED FROM THE OHIO EPA PRIOR TO BEGINNING MAIN

INSTALLATION. THE CONSTRUCTION CONTRACTOR SHALL PREPARE

AND SUBMIT A DRAFT PLANS APPROVAL PACKAGE TO THE

CONTRACTING OFFICER'S REPRESENTATIVE, INCLUDING A CHECK FOR

ANY APPLICABLE OHIO EPA FEES, FOR REVIEW AND PROCESSING BY

ENVIRONMENTAL MANAGEMENT, 88 CEG/CEIEA. ENVIRONMENTAL

MANAGEMENT SHALL ENDORSE THE PACKAGE AS THE UTILITY OWNER

AND SHALL SUBMIT IT TO OHIO EPA. PLEASE CONTACT THE 88

CEG/CEIEA WATER PM, KAREN BEASON, BY EMAIL AT

KAREN.BEASON@US.AF.MIL OR BY PHONE AT 937-257-5899 FOR

ADDITIONAL INFORMATION.

25. IF ANY SANITARY SEWER MAINS ARE BEING EXTENDED, UPSIZED OR

NEW MAINS ARE BEING INSTALLED A PERMIT TO INSTALL (PTI) MAY BE

REQUIRED FROM THE OHIO EPA PRIOR TO BEGINNING MAIN

INSTALLATION. THE CONSTRUCTION CONTRACTOR SHALL PREPARE

AND SUBMIT A DRAFT PTI PACKAGE TO THE CONTRACTING OFFICER'S

REPRESENTATIVE, INCLUDING A CHECK FOR ANY APPLICABLE OHIO

EPA FEES, FOR REVIEW AND PROCESSING BY ENVIRONMENTAL

MANAGEMENT, 88 CEG/CEIEA. ENVIRONMENTAL MANAGEMENT SHALL

ENDORSE THE PACKAGE AS THE UTILITY OWNER AND SHALL SUBMIT IT

TO OHIO EPA. PLEASE CONTACT THE 88 CEG/CEIEA WATER PM, KAREN

BEASON, BY EMAIL AT KAREN.BEASON@US.AF.MIL OR BY PHONE AT

937-257-5899 FOR ADDITIONAL INFORMATION.

26. IF ANY REFRIGERANT-CONTAINING EQUIPMENT SCHEDULED FOR NEW

INSTALLATION, INCLUDING WATER COOLERS, THEY MUST UTILIZE AN

HFC REFRIGERANT. CFC AND HCFC REFRIGERANTS ARE NOT

AUTHORIZED FOR NEW EQUIPMENT INSTALLATIONS. FOR ADDITIONAL

INFORMATION PLEASE CONTACT THE 88 CEG/CEIEA AIR PM CHRIS

TUMBUSCH. CHRIS CAN BE REACHED AT 937-257-2455 OR BY EMAIL AT

CHRISTOPHER.TUMBUSCH@US.AF.MIL.

27. IF AN EMERGENCY GENERATOR OR BOILER WILL BE INSTALLED, AN

AIR SOURCE PERMIT MAY BE REQUIRED FOR THE GENERATOR AND

POSSIBLY THE FUEL TANK. FOR ADDITIONAL INFORMATION PLEASE

CONTACT THE 88 CEG/CEIEA AIR PM CHRIS TUMBUSCH. CHRIS CAN BE

REACHED AT 937-257-2455 OR BY EMAIL AT

CHRISTOPHER.TUMBUSCH@US.AF.MIL.

28. ANY TRANSFORMERS, SWITCH GEAR, OR ELECTRICAL PANELS

CONTAINING OIL SCHEDULED FOR REMOVAL MUST HAVE THE

EQUIPMENT OIL VERIFIED TO BE NON PCB-CONTAINING PRIOR TO

TURN-IN. 88 CEG/CEIE MAINTAINS A BASE-WIDE PCB DATA-BASE FOR

OIL CONTAINING EQUIPMENT. IF THE EQUIPMENT CANNOT BE

LOCATED IN THE DATA-BASE THE OIL FROM EACH INDIVIDUAL PIECE

OF EQUIPMENT MUST BE SAMPLED FOR PCB. PLEASE CONTACT THE

88 CEG/CEIEC USED OIL TECHNICIAN BOB JARUSIEWIC BY EMAIL AT

ROBERT.JARUSIEWIC@US.AF.MIL OR BY PHONE AT 937-257-2889 FOR

ADDITIONAL INFORMATION.

29. STORM WATER INNOVATIVE DESIGN MEASURES MUST BE

INCORPORATED INTO THE DESIGN IAW SECTION 438 OF THE ENERGY

INDEPENDENCE AND SECURITY ACT (EISA) IF THE PROJECT HAS A

FOOTPRINT THAT EXCEEDS 5000 SQ FT. PLEASE CONTACT THE 88

CEG/CEIEA WATER PM KAREN BEASON BY EMAIL AT

KAREN.BEASON@US.AF.MIL OR BY PHONE AT 937-257-5899 FOR

ADDITIONAL INFORMATION.

30. A CRANE PLAN SUBMITTAL IS REQUIRED FOR GOVERNMENT

APPROVAL. THE CRANE PLAN SHALL INCLUDE THE CRANE LOCATION,

HEIGHT, DATES OF USE AND POINT OF CONTACT. PLEASE NOTE THAT

AN FAA FORM 7460-1 WILL BE REQUIRED IF CRANE IS OVER 200FT AND

THESE DOCUMENTS MAY TAKE 60 DAYS OR MORE TO PROCESS.

31. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH WPAFB

SPECIFICATION SECTION 01 02 20.

32. CONTRACTORS ARE FREE TO USE ANY PRODUCT WHICH MEETS THE

GOVERNMENT'S MINIMUM REQUIREMENTS AND NOT IN CONFLICT WITH

OTHER CONTRACT PROVISIONS. UNLESS INDICATED OTHERWISE ON

THE PLANS OR SPECIFICATIONS (E.G. SOLE-SOURCE), ALL LISTED

MANUFACTURERS ARE THE BASIS OF DESIGN. FOR THESE BASIS OF

DESIGN PRODUCTS, OTHER MANUFACTURERS MAY BE SUBSTITUTED

AS LONG AS THE STANDARD OF QUALITY AND CHARACTERISTICS OF

THE SUBSTITUTED MANUFACTURER MEET OR EXCEED THE STANDARD

OF QUALITY AND CHARACTERISTICS OF THE BASIS OF DESIGN.

G-001 COVER PAGE

G-002 GENERAL NOTES AND SHEET INDEX

G-003 SEQUENCING GENERAL NOTES

G-101 BASEMENT FLOOR PLAN - SEQUENCE 1

G-102 FIRST FLOOR PLAN - SEQUENCE 1

G-103 SECOND FLOOR PLAN - SEQUENCE 1

G-104 ROOF/PENTHOUSE PLAN - SEQUENCE 1

G-105 BASEMENT FLOOR PLAN - SEQUENCE 2

G-106 FIRST FLOOR PLAN - SEQUENCE 2

G-107 BASEMENT FLOOR PLAN - SEQUENCE 3

G-108 FIRST FLOOR PLAN - SEQUENCE 3

G-109 SECOND FLOOR PLAN - SEQUENCE 3

G-110 ROOF/PENTHOUSE PLAN - SEQUENCE 3

G-111 FIRST FLOOR PLAN - SEQUENCE 4

G-112 FIRST FLOOR PLAN - SEQUENCE 5

G-113 SECOND FLOOR PLAN - SEQUENCE 5

G-114 SECOND FLOOR PLAN - SEQUENCE 6

G-115 BASEMENT FLOOR PLAN - UTILITY COORDINATION

G-116 FIRST FLOOR PLAN - UTILITY COORDINATION

G-117 SECOND FLOOR PLAN - UTILITY COORDINATION

G-301 SECTIONS - UTILITY COORDINATION

GI101 BASEMENT FLOOR PLAN - LIFE SAFETY

GI102 FIRST FLOOR PLAN - LIFE SAFETY

GI103 SECOND FLOOR PLAN - LIFE SAFETY

H-101 BASEMENT PLAN - HAZARDOUS MATERIAL ABATEMENT PLAN

H-102 BASEMENT PLAN - HAZARDOUS MATERIAL ABATEMENT PLAN

H-103 PARTIAL FIRST FLOOR HAZARDOUS MATERIAL ABATEMENT PLAN

H-104 PARTIAL FIRST FLOOR HAZARDOUS MATERIAL ABATEMENT PLAN

H-105 SECOND FLOOR HAZARDOUS MATERIAL ABATEMENT PLAN

H-106 SECOND FLOOR HAZARDOUS MATERIAL ABATEMENT PLAN

H-107 ROOF HAZARDOUS MATERIAL ABATEMENT PLAN

C-001 GENERAL NOTES AND LEGEND

GC101 LOCATION MAP AND HAUL ROUTE

V-101 EXISTING CONDITIONS & DEMOLITION PLAN

C-101 CIVIL SITE PLAN

C-102 CIVIL SITE PLAN

C-501 CIVIL DETAILS

C-502 CIVIL DETAILS

S-001 GENERAL STRUCTURAL NOTES

S-002 GENERAL STRUCTURAL NOTES

S-401 NEW ADDITION FOUNDATION PLAN & EQUIPMENT PAD PLAN

S-402 NEW ADDITION ROOF FRAMING PLAN

S-411 NEW CANOPY FOUNDATION PLAN

S-412 NEW CANOPY FRAMING PLAN

S-501 FOUNDATION DETAILS

S-502 FRAMING DETAILS

S-511 CANOPY FOUNDATION DETAILS

S-512 CANOPY FRAMING DETAILS

S-601 STRUCTURAL TYPICAL DETAILS

S-602 STRUCTURAL TYPICAL DETAILS

A-001 GENERAL NOTES, ABBREVIATIONS, & SYMBOLS

AD101 BASEMENT DEMOLITION PLAN

AD102 FIRST FLOOR DEMOLITION PLAN

AD103 SECOND FLOOR DEMOLITION PLAN

AD104 ROOF/PENTHOUSE DEMOLITION PLAN

AD111 BASEMENT CEILING DEMOLITION PLAN

AD112 FIRST FLOOR CEILING DEMOLITION PLAN

AD113 SECOND FLOOR CEILING DEMOLITION PLAN

A-101 BASEMENT FLOOR PLAN

A-102 FIRST FLOOR PLAN

A-103 SECOND FLOOR PLAN

A-104 ROOF/PENTHOUSE PLAN

A-111 BASEMENT CEILING PLAN

A-112 FIRST FLOOR CEILING PLAN

A-113 SECOND FLOOR CEILING PLAN

A-201 ELEVATIONS

A-202 ELEVATIONS

A-301 WALL SECTIONS

A-302 SECTION DETAILS

A-303 SECTION DETAILS

A-401 ENLARGED PLANS & ELEVATIONS - MECHANICAL ROOM

A-402 ENLARGED PLANS - COURTYARDS

A-403 ENLARGED PLANS & ELEVATIONS - RESTROOMS

A-404 ENLARGED PLANS & ELEVATIONS - RESTROOMS

A-405 ENLARGED PLANS & ELEVATIONS - RESTROOMS

A-501 CANOPY SECTIONS

A-502 CANOPY SECTIONS

A-503 CANOPY SECTIONS

A-601 DOOR SCHEDULES AND DETAILS

A-602 WINDOW SCHEDULES AND DETAILS

A-603 PARTITION TYPES

A-701 STAIR PLANS & SECTIONS

A-702 STAIR PLANS & SECTIONS

A-703 STAIR PLANS & SECTIONS

A-704 STAIR PLANS & SECTIONS

A-709 STAIR SECTIONS & DETAILS

A-901 ELEVATIONS & PERSPECTIVES

I-101 BASEMENT EXISTING FURNITURE PLAN

I-102 FIRST FLOOR EXISTING FURNITURE PLAN

I-103 SECOND FLOOR NEW AND EXISTING FURNITURE PLAN

I-111 BASEMENT FINISH PLAN

I-112 FIRST FLOOR FINISH PLAN

I-113 SECOND FLOOR FINISH PLAN

I-201 BASEMENT SIGNAGE PLAN

I-202 FIRST FLOOR SIGNAGE PLAN

I-203 SECOND FLOOR SIGNAGE PLAN

I-204 SIGNAGE TYPICALS & SCHEDULE

I-401 ENLARGED FURNITURE PLANS

I-402 ENLARGED PANEL PLAN

I-403 ENLARGED FINISH PLAN AND DETAILS

I-601 FINISH SCHEDULE

F-001 GENERAL INFORMATION - FIRE PROTECTION

FD101 BASEMENT FLOOR PLAN - FIRE PROTECTION - DEMOLITION

FD102 FIRST FLOOR PLAN - FIRE PROTECTION - DEMOLITION

FD103 SECOND FLOOR PLAN - FIRE PROTECTION - DEMOLITION

FD104 ROOF/PENTHOUSE PLAN - FIRE PROTECTION - DEMOLITION

F-101 BASEMENT FLOOR PLAN - FIRE PROTECTION

F-102 FIRST FLOOR PLAN - FIRE PROTECTION

F-103 SECOND FLOOR PLAN - FIRE PROTECTION

F-104 ROOF/PENTHOUSE PLAN - FIRE PROTECTION

F-501 DETAILS - FIRE PROTECTION

FA001 GENERAL INFORMATION - FIRE ALARM

FA101 BASEMENT FLOOR PLAN WEST - FIRE ALARM

FA102 BASEMENT FLOOR PLAN EAST - FIRE ALARM

FA111 FIRST FLOOR PLAN WEST - FIRE ALARM

FA112 FIRST FLOOR PLAN EAST - FIRE ALARM

FA121 SECOND FLOOR PLAN WEST - FIRE ALARM

FA122 SECOND FLOOR PLAN EAST - FIRE ALARM

FA131 ROOF/PENTHOUSE PLAN WEST - FIRE ALARM

FA132 ROOF/PENTHOUSE PLAN EAST - FIRE ALARM

FA431 ENLARGED PENTHOUSE PLAN - FIRE ALARM

FA501 DETAILS - FIRE ALARM

FA502 DETAILS - FIRE ALARM

P-001 GENERAL INFORMATION - PLUMBING

P-101 BASEMENT PLAN - PLUMBING

P-102 FIRST FLOOR PLAN - PLUMBING

P-103 SECOND FLOOR PLAN - PLUMBING

P-104 ROOF/PENTHOUSE PLAN - PLUMBING

P-301 DIAGRAMS - PLUMBING

P-601 DETAILS AND SCHEDULES - PLUMBING

M-001 GENERAL INFORMATION - MECHANICAL

MD101 BASEMENT FLOOR PLAN WEST - HVAC - DEMOLITION

MD102 BASEMENT FLOOR PLAN EAST - HVAC - DEMOLITION

MD103 BASEMENT FLOOR PLAN WEST - HVAC PIPING - DEMOLITION

MD104 BASEMENT FLOOR PLAN EAST - HVAC PIPING - DEMOLITION

MD111 FIRST FLOOR PLAN WEST - HVAC - DEMOLITION

MD112 FIRST FLOOR PLAN EAST - HVAC - DEMOLITION

MD113 FIRST FLOOR PLAN WEST - HVAC PIPING - DEMOLITION

MD114 FIRST FLOOR PLAN EAST - HVAC PIPING - DEMOLITION

MD121 SECOND FLOOR PLAN WEST - HVAC - DEMOLITION

MD122 SECOND FLOOR PLAN EAST - HVAC - DEMOLITION

MD123 SECOND FLOOR PLAN WEST - HVAC PIPING - DEMOLITION

MD133 ROOF/PENTHOUSE PLAN WEST - HVAC PIPING - DEMOLITION

MD134 ROOF/PENTHOUSE PLAN EAST - HVAC PIPING - DEMOLITION

MD411 ENLARGED FIRST FLOOR PLANS - MECHANICAL - DEMOLITION

MD421 ENLARGED SECOND FLOOR PLANS - MECHANICAL - DEMOLITION

MD431 ENLARGED PENTHOUSE PLAN - HVAC - DEMOLITION

MD432 ENLARGED PENTHOUSE PLAN - HVAC PIPING - DEMOLITION

MH101 BASEMENT FLOOR PLAN WEST - HVAC

MH102 BASEMENT FLOOR PLAN EAST - HVAC

MH111 FIRST FLOOR PLAN WEST - HVAC

MH112 FIRST FLOOR PLAN EAST - HVAC

MH121 SECOND FLOOR PLAN WEST - HVAC

MH122 SECOND FLOOR PLAN EAST - HVAC

MP101 BASEMENT FLOOR PLAN WEST - HVAC PIPING

MP102 BASEMENT FLOOR PLAN EAST - HVAC PIPING

MP111 FIRST FLOOR PLAN WEST - HVAC PIPING

MP112 FIRST FLOOR PLAN EAST - HVAC PIPING

MP121 SECOND FLOOR PLAN WEST - HVAC PIPING

MP122 SECOND FLOOR PLAN EAST - HVAC PIPING

MP131 ROOF/PENTHOUSE PLAN WEST - HVAC PIPING

MP132 ROOF/PENTHOUSE PLAN EAST - HVAC PIPING

M-301 SECTIONS - MECHANICAL

M-411 ENLARGED FIRST FLOOR PLANS - MECHANICAL

M-421 ENLARGED SECOND FLOOR PLANS - MECHANICAL

M-431 ENLARGED PENTHOUSE PLAN - HVAC

M-432 ENLARGED PENTHOUSE PLAN - HVAC PIPING

M-501 DETAILS - MECHANICAL

M-502 DETAILS - MECHANICAL

M-503 DETAILS - MECHANICAL

M-504 DETAILS - MECHANICAL

M-601 SCHEDULES - MECHANICAL

M-602 SCHEDULES - MECHANICAL

M-603 SCHEDULES - MECHANICAL

M-604 SCHEDULES - MECHANICAL

M-701 CONTROLS - MECHANICAL

M-702 CONTROLS - MECHANICAL

M-703 CONTROLS - MECHANICAL

M-704 CONTROLS - MECHANICAL

M-705 CONTROLS - MECHANICAL

M-706 CONTROLS - MECHANICAL

M-707 CONTROLS - MECHANICAL

M-708 CONTROLS - MECHANICAL

M-709 CONTROLS - MECHANICAL

M-710 CONTROLS - MECHANICAL

M-711 CONTROLS - MECHANICAL

M-712 CONTROLS - MECHANICAL

M-713 CONTROLS - MECHANICAL

M-714 CONTROLS - MECHANICAL

M-715 CONTROLS - MECHANICAL

M-716 CONTROLS - MECHANICAL

M-717 CONTROLS - MECHANICAL

M-718 CONTROLS - MECHANICAL

M-719 CONTROLS - MECHANICAL

M-720 CONTROLS - MECHANICAL

M-721 CONTROLS - MECHANICAL

M-722 CONTROLS - MECHANICAL

M-723 CONTROLS - MECHANICAL

M-724 CONTROLS - MECHANICAL

M-725 CONTROLS - MECHANICAL

M-726 CONTROLS - MECHANICAL

M-727 CONTROLS - MECHANICAL

M-728 CONTROLS - MECHANICAL

M-729 CONTROLS - MECHANICAL

M-730 CONTROLS - MECHANICAL

M-731 CONTROLS - MECHANICAL

M-732 CONTROLS - MECHANICAL

M-801 DIAGRAMS - MECHANICAL

M-802 DIAGRAMS - MECHANICAL

M-803 DIAGRAMS - MECHANICAL

M-804 DIAGRAMS - MECHANICAL

M-805 DIAGRAMS - MECHANICAL

M-806 DIAGRAMS - MECHANICAL

E-001 GENERAL INFORMATION - ELECTRICAL

ED101 BASEMENT FLOOR PLAN WEST - ELECTRICAL - DEMOLITION

ED102 BASEMENT FLOOR PLAN EAST - ELECTRICAL - DEMOLITION

ED111 FIRST FLOOR PLAN WEST - ELECTRICAL - DEMOLITION

ED112 FIRST FLOOR PLAN EAST - ELECTRICAL - DEMOLITION

ED121 SECOND FLOOR PLAN WEST - ELECTRICAL - DEMOLITION

ED122 SECOND FLOOR PLAN EAST - ELECTRICAL - DEMOLITION

ED411 ENLARGED FIRST FLOOR PLAN - ELECTRICAL - DEMOLITION

ED431 ENLARGED PENTHOUSE PLAN - ELECTRICAL - DEMOLITION

ED501 DETAILS - ELECTRICAL - DEMOLITION

ED701 DIAGRAMS - DEMOLITION

ED702 DIAGRAMS - DEMOLITION

EG131 ROOF/PENTHOUSE PLAN - LIGHTNING PROTECTION

EL101 BASEMENT FLOOR PLAN WEST - LIGHTING

EL102 BASEMENT FLOOR PLAN EAST - LIGHTING

EL111 FIRST FLOOR PLAN WEST - LIGHTING

EL112 FIRST FLOOR PLAN EAST - LIGHTING

EL121 SECOND FLOOR PLAN WEST - LIGHTING

EL122 SECOND FLOOR PLAN EAST - LIGHTING

EP101 BASEMENT FLOOR PLAN WEST - POWER

EP102 BASEMENT FLOOR PLAN EAST - POWER

EP111 FIRST FLOOR PLAN WEST - POWER

EP112 FIRST FLOOR PLAN EAST - POWER

EP121 SECOND FLOOR PLAN WEST - POWER

EP122 SECOND FLOOR PLAN EAST - POWER

E-401 ENLARGED PLANS - ELECTRICAL

E-411 ENLARGED FIRST FLOOR PLANS - ELECTRICAL

E-431 ENLARGED PENTHOUSE PLAN - ELECTRICAL

E-501 DETAILS - ELECTRICAL

E-502 DETAILS - ELECTRICAL

E-601 SCHEDULES - ELECTRICAL

E-602 SCHEDULES - ELECTRICAL

E-603 SCHEDULES - ELECTRICAL

E-604 SCHEDULES - ELECTRICAL

E-605 SCHEDULES - ELECTRICAL

E-606 SCHEDULES - ELECTRICAL

E-607 SCHEDULES - ELECTRICAL

E-701 DIAGRAMS - ELECTRICAL

E-702 DIAGRAMS - ELECTRICAL

E-703 DIAGRAMS - ELECTRICAL

E-704 DIAGRAMS - ELECTRICAL

T-001 GENERAL INFORMATION - TELECOMMUNICATIONS

TS101 SITE PLAN - TELECOMMUNICATIONS

TD101 BASEMENT FLOOR PLAN WEST - TELECOMMUNICATIONS - DEMOLITION

TD102 BASEMENT FLOOR PLAN EAST - TELECOMMUNICATIONS - DEMOLITION

TD111 FIRST FLOOR PLAN WEST - TELECOMMUNICATIONS - DEMOLITION

TD112 FIRST FLOOR PLAN EAST - TELECOMMUNICATIONS - DEMOLITION

TD121 SECOND FLOOR PLAN WEST - TELECOMMUNICATIONS - DEMOLITION

TD122 SECOND FLOOR PLAN EAST - TELECOMMUNICATIONS - DEMOLITION

TD701 DIAGRAMS - TELECOMMUNICATIONS - DEMOLITION

T-101 BASEMENT FLOOR PLAN WEST - TELECOMMUNICATIONS

T-102 BASEMENT FLOOR PLAN EAST - TELECOMMUNICATIONS

T-111 FIRST FLOOR PLAN WEST - TELECOMMUNICATIONS

T-112 FIRST FLOOR PLAN EAST - TELECOMMUNICATIONS

T-121 SECOND FLOOR PLAN WEST - TELECOMMUNICATIONS

T-122 SECOND FLOOR PLAN EAST - TELECOMMUNICATIONS

T-401 ENLARGED PLANS - TELECOMMUNICATIONS

T-501 DETAILS - TELECOMMUNICATIONS

T-502 DETAILS - TELECOMMUNICATIONS

T-701 DIAGRAMS - TELECOMMUNICATIONS

GENERAL NOTESSHEET INDEX

S O

LI

C

IT

A

TI

O

N N

O

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

TI

O

N

1 3 5

C

7 9

A

M A

R K

IS

S

U E

D A

TE

S

IZ

E

S U

B M

IT

TE

D B

Y

C O

N

TR

A C

T N

O

SHEET ID

D A

TE

US Army Corps of Engineers

U .S

. A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

LO

U

IS

V

IL

LE

, K Y

LO

U

IS

V

IL

LE

D

IS

TR

IC

T

W R

IG

H

T P

A

TT

E R

S O

N A

FB

R

E P

A

IR

F S

D -1

IN

TE

R

IO

R , E

X

TE

R

IO

R , A

N D

H V

A C

FA

C

IL

IT

Y

(Z H

TV

B

D

E

F

G

2 4 6 8 10

JU

LY

W

2Q R

B

FA

-1

3- D

A D

V A

N C

E D

E N

G

IN

E E

R

IN

G C

O N

S U

LT

A

N

TS

M ec ha ni ca l |

E le ct ric al

Pl um bi ng

Fi re P ro te ct io n

D ub lin

R oa d Te l:

(6

) 4

-4

C ol um bu s, O hi o

Fa x:

(6

) 4

-4

UNCLASSIFIED//FOR OFFICIAL USE ONLY - PROPERTY OF THE US GOVERNMENT, LIMITED REPRODUCTION AND DISSEMINATION TO MINIMUM REQUIRED TO BID AND CONSTRUCT THE PROJECT

UNCLASSIFIED//FOR OFFICIAL USE ONLY - PROPERTY OF THE US GOVERNMENT, LIMITED REPRODUCTION AND DISSEMINATION TO MINIMUM REQUIRED TO BID AND CONSTRUCT THE PROJECT

H

P

N O

CORRECTED FINAL

07/17/2020

G E

N E

R A

L G

E N

E R

A L

N O

TE

S

A N

D S

H E

E T

IN

D

E X

G-002

G . L

E

IT

C H

K . F

IE

LD

S

K . F

IE

LD

S

CERTIFIED FINAL

ARIMS: 200A Disposition: Maintain for 15yrs after construction

W

2Q R

B0

1-

1. THESE NOTES APPLY TO ALL PROPOSED SEQUENCING SHEETS

2. THE UPGRADE AND REPLACEMENT HVAC SYSTEMS SHALL OCCUR IN

SEVERAL SEQUENCES SO THAT SELECT LABS CAN REMAIN

OPERATIONAL DURING CONSTRUCTION. ONLY LIMITED NUMBERS OF

AIR HANDLING UNITS (AHU'S) AND SUBSYSTEMS WILL BE PERMITTED

TO BE SHUTDOWN AT ANY GIVEN TIME FOR SHORT DURATIONS

DURING THE CONSTRUCTION TO MAINTAIN BUILDING FUNCTIONALITY.

3. THIS PROPOSED SEQUENCE OUTLINES A PLAN OF CONSTRUCTION

STAGING AND IS INTENDED FOR THE USE OF THE SUCCESSFUL

CONTRACTOR AS A STARTING POINT FOR THE DETAILED PLANNING

AND COORDINATION OF THE WORK SCHEDULE AND PROCESS

REQUIRED WITH THE CONTRACTING OFFICER'S REPRESENTATIVE.

4. STAGING SHALL ALLOW THE BUILDING TO BE MAXIMALLY FUNCTIONAL

THROUGHOUT CONSTRUCTION.

5. CONTRACTOR SHALL BE RESPONSIBLE FOR DETAILING AND

COORDINATING THE STAGING, WORK PROCESS AND SCHEDULING

WITH THE CONTRACTING OFFICER'S REPRESENTATIVE. A DETAILED

METHOD OF PROCEDURE WILL BE REQUIRED FOR EACH PART OF THE

DEMOLITION AND CONSTRUCTION.

6. CONTRACTOR MAY EXECUTE TASKS CONCURRENTLY AS THE

DETAILED PLANNING, SCHEDULING AND COORDINATION OF ALL

DISCIPLINES ALLOWS.

7. THE GOVERNMENT HAS IDENTIFIED NINE LAB FACILITIES THAT WILL

NEED TO REMAIN OPERATIONAL DURING CONSTRUCTION. THESE LAB

FACILITIES WILL BE THE DRIVING FACTOR BEHIND THE SEQUENCING

PLAN TO MINIMIZE DISRUPTION TO THE USER'S MISSION. THE NINE

LAB FACILITIES THAT WERE IDENTIFIED ARE:

7.1. SHARC

7.2. BAMLAB

7.3. VERITAS

7.4. VOCRES

7.5. ALF

7.6. MIRE

7.7. AAC

7.8. BATMAN

7.9. REAT

8. ALL OFFICE PERSONNEL WILL BE DISPLACED FROM BUILDING 441 TO A

TEMPORARY SWING SPACE. ONLY A FEW LAB STAFF WILL REMAIN IN

THE BUILDING DURING THE CONSTRUCTION.

9. THE ALF AND VERITAS LABS WILL REQUIRE TEMPORARY COOLING

DURING CONSTRUCTION TO MAINTAIN A SPACE RELATIVE HUMIDITY

OF NO MORE THAT 55%.

10. OUTAGES TO THE LAB FACILITIES MUST BE COORDINATED WITH THE

COR A MINIMUM OF FOUR WEEKS IN ADVANCE.

11. CONTRACTOR SHALL MAINTAIN A MINIMUM OF TWO PATHS OF EGRESS

DURING CONSTRUCTION.

12. CONTRACTOR SHALL COORDINATE WITH COR FOR LAB MOBILE DATA

CART REQUIREMENTS.

GENERAL NOTES

S O

LI

C

IT

A

TI

O

N N

O

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

TI

O

N

1 3 5

C

7 9

A

M A

R K

IS

S

U E

D A

TE

S

IZ

E

S U

B M

IT

TE

D B

Y

C O

N

TR

A C

T N

O

SHEET ID

D A

TE

US Army Corps of Engineers

U .S

. A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

LO

U

IS

V

IL

LE

, K Y

LO

U

IS

V

IL

LE

D

IS

TR

IC

T

W R

IG

H

T P

A

TT

E R

S O

N A

FB

R

E P

A

IR

F S

D -1

IN

TE

R

IO

R , E

X

TE

R

IO

R , A

N D

H V

A C

FA

C

IL

IT

Y

(Z H

TV

B

D

E

F

G

2 4 6 8 10

JU

LY

W

2Q R

B

FA

-1

3- D

A D V A N C E D

E N

G

IN

E E

R

IN

G C

O N

S U

LT

A

N

TS

M ec ha ni ca l |

E le ct ric al

Pl um bi ng

Fi re P ro te ct io n

D ub lin

R oa d Te l:

(6

) 4

-4

C ol um bu s, O hi o

Fa x:

(6

) 4

-4

UNCLASSIFIED//FOR OFFICIAL USE ONLY - PROPERTY OF THE US GOVERNMENT, LIMITED REPRODUCTION AND DISSEMINATION TO MINIMUM REQUIRED TO BID AND CONSTRUCT THE PROJECT

UNCLASSIFIED//FOR OFFICIAL USE ONLY - PROPERTY OF THE US GOVERNMENT, LIMITED REPRODUCTION AND DISSEMINATION TO MINIMUM REQUIRED TO BID AND CONSTRUCT THE PROJECT

H

P

N O

CORRECTED FINAL

07/17/2020

G E

N E

R A

L G

E N

E R

A L

N O

TE

S

G-003

G . L

E

IT

C H

K . F

IE

LD

S

K . F

IE

LD

S

CERTIFIED FINAL

a3 a2a1b6 b7 b8 b9b5.1b5b4b2b1 aF aE aD aC aB aA bB bA.2 bA.1 bAbA bC bD bE bF bG bH bJ bK bL bM bN bA.3

E.9

E.1

EX1 1.0 2.0

UP

UP

UP

BAMLAB

0-111

VERITAS

0-114A

FABRICATION

SHOP

0-117

MECH

0-118

STORAGE

0-117A

OFFICE

0-124

LAB

0-120

LAB

0-120B

LAB

0-120A

ELEVATOR

0E1

MENS

0-012

OFFICE

0-119A

OFFICE

0-119B

OFFICE

0-119

LAB

0-126B

LAB

0-126C

LAB

0-126A

STAIR C

0S2

VOCRES

0-116A

MECH

0-902

STORAGE

0-112

SHARC

0-108

0-113

BREAK ROOM

0-103

JAN.

0-904

CORRIDOR

0-906

STORAGE

0-107

LAB

0-102

COMM

0-115A

OFFICE

0-106

LAB

0-110

WOMENS

0-011

VERITAS

CONTROL

0-114

LISTENING LAB

0-101

CONFERENCE

ROOM

0-104

STORAGE

0-104ASHARC CONTROL

0-109

LAB

0-110A

VESTIBULE

0-903

STAIR A

0S4

OFFICE

0-105

VOCRES

CONTROL

0-116

OFFICE

0-125

CORRIDOR

0-905

SOFTWARE

DEVELOPMENT

LAB

0-123

STAIR B

0S1CORRIDOR

0-901

OFFICE

0-119C

LISTENING LAB

0-126

EEG LAB

0-122

VIRTUAL AUDIO

LAB

0-121

LAB

0-121A

ELEC

0-115

4' 8' 16'03/32"=1'-0"A1

BASEMENT FLOOR PLAN - SEQUENCE 1

SEQUENCE OF CONSTRUCTION

A. SEQUENCE ONE:

ALL WORK ASSOCIATED WITH THIS SEQUENCE SHALL BE COMPLETED IN NO MORE

THAN 270 DAYS.

A.A. LABS:

A.A.A. CONTRACTOR WILL NOT HAVE ACCESS TO ALL LAB FACILITIES DURING

THIS CONSTRUCTION SEQUENCE.

A.B. HVAC:

A.B.A. CHILLED WATER PIPING:

A.B.A.A. ROUTE NEW CHW PIPING FROM MECHANICAL ROOM ADDITION TO

PENTHOUSE MECHANICAL ROOMS. TERMINATE CHW PIPING MAINS

IN INTERIOR OF PENTHOUSE MECHANICAL ROOMS WITH VALVED

TAPS FOR FUTURE CONNECTION DURING OTHER SEQUENCES.

A.B.B. HOT WATER PIPING:

A.B.B.A. ROUTE NEW HW PIPING FROM MECHANICAL ROOM ADDITION TO

PENTHOUSE MECHANICAL ROOMS. TERMINATE HW PIPING MAINS

IN INTERIOR OF PENTHOUSE MECHANICAL ROOMS WITH VALVED

TAPS FOR FUTURE CONNECTION DURING OTHER SEQUENCES.

A.B.C. AC-5 AND AC-10:

A.B.C.A. REPLACE AC-5 IN FAB SHOP 0-117 WITH NEW CHW/HW AIR

HANDLING UNIT. REPLACE ASSOCIATED CHW PIPING WITH NEW

PIPING FROM SEQUENCE ONE SYSTEM. ROUTE NEW HW FROM

SEQUENCE ONE SYSTEM. DEMOLISH ALL ASSOCIATED STEAM AND

CONDENSATE PIPING.

A.B.C.B. REPLACE DUCT SYSTEM WITH NEW DUCT SYSTEM.

A.B.C.C. REPLACE AC-10 IN BASEMENT MECHANICAL ROOM 0-118.

COORDINATE REPLACEMENT WITH ELECTRICAL (MECHANICAL

ROOM HOUSES THE 400 HZ AND 28 VOLT DC GENERATORS).

A.D. FIRE ALARM:

A.D.A. PROVIDE TEMPORARY WALL MOUNTED SMOKE DETECTORS IN LABS

AND LAB CONTROL ROOMS, DETECTORS MUST BE BETWEEN 4" AND 12"

FROM THE CEILING AFTER THE EXISTING CEILING GRID HAS BEEN

REMOVED.

A.D.B. PROVIDE FIXED TEMPERATURE HEAT DETECTORS ONLY AND NOT RATE

OF RISE DETECTORS.

A.D.C. HEAT DETECTORS SHALL BE LOCATED IN CORRIDORS AND OTHER

AREAS OF THE BUILDING. ON THE SECOND FLOOR LOCATE HEAT

DETECTORS IN CORRIDORS AND REMOVE ALL DOORS FROM THEIR

HINGES TO COMMUNICATE AREAS.

A.D.D. CONTRACTOR SHALL PROVIDE A PLAN FOR PROTECTION TO THE FIRE

DEPARTMENT FOR REVIEW AND COORDINATION OF SMOKE AND HEAT

DETECTOR LOCATIONS.

A.D.E. NOTIFICATION SHALL BE REQUIRED IN THE LABS DURING

CONSTRUCTION (TEMPORARY SYSTEM).

A.D.F. PROVIDE TEMPORARY SMOKE DETECTOR SERVING THE ALF LAB,

LOCATE DETECTOR OUTSIDE OF THE LAB DOOR.

A.D.C. PROVIDE TEMPORARY SMOKE DETECTOR SERVING THE REAT LAB,

LOCATE DETECTOR OUTSIDE OF THE LAB DOOR.

A.E. EGRESS:

A.E.A. PROVIDE TEMPORARY EXIT AND EMERGENCY EGRESS LIGHTING WITH

90 MINUTE BATTERY BACKUP FOR BUILDING EGRESS, COORDINATE

LOCATIONS WITH THE AHJ.

SEQUENCE 1

S O

LI

C

IT

A

TI

O

N N

O

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

TI

O

N

1 3 5

C

7 9

A

M A

R K

IS

S

U E

D A

TE

S

IZ

E

S U

B M

IT

TE

D B

Y

C O

N

TR

A C

T N

O

SHEET ID

D A

TE

US Army Corps of Engineers

U .S

. A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

LO

U

IS

V

IL

LE

, K Y

LO

U

IS

V

IL

LE

D

IS

TR

IC

T

W R

IG

H

T P

A

TT

E R

S O

N A

FB

R

E P

A

IR

F S

D -1

IN

TE

R

IO

R , E

X

TE

R

IO

R , A

N D

H V

A C

FA

C

IL

IT

Y

(Z H

TV

B

D

E

F

G

2 4 6 8 10

JU

LY

W

2Q R

B

FA

-1

3- D

A D V A N C E D

E N

G

IN

E E

R

IN

G C

O N

S U

LT

A

N

TS

M ec ha ni ca l |

E le ct ric al

Pl um bi ng

Fi re P ro te ct io n

D ub lin

R oa d Te l:

(6

) 4

-4

C ol um bu s, O hi o

Fa x:

(6

) 4

-4

NORTH

UNCLASSIFIED//FOR OFFICIAL USE ONLY - PROPERTY OF THE US GOVERNMENT, LIMITED REPRODUCTION AND DISSEMINATION TO MINIMUM REQUIRED TO BID AND CONSTRUCT THE PROJECT

UNCLASSIFIED//FOR OFFICIAL USE ONLY - PROPERTY OF THE US GOVERNMENT, LIMITED REPRODUCTION AND DISSEMINATION TO MINIMUM REQUIRED TO BID AND CONSTRUCT THE PROJECT

H

P

N O

CORRECTED FINAL

07/17/2020

S E

Q U

E N

C E

B

A S

E M

E N

T

FL

O O

R P

LA

N

G-101

J.

L

E E

K . F

IE

LD

S

E . L

E H

M A

N a2a1b6 b7 b8 b9b5b4 aE aD aC aB aA bAbA bC bD bE bF bG bH bJ bK bL bM bN bA.3

E.9

E.1

EX1 1.0 2.0 a3b1

DN

UP

DN

UP

DN

DN UP

ALF

1-010

MIRE

1-008A

STAGING

1-009

CORRIDOR

1-904

AAC

1-008D

REAT

1-008E

LAB

1-008B

MECH

1-006

CONTROL

1-008

WOMENS

1-007

STAIR B

1S1

STAIR C

1S2

CONFERENCE

1-004

STORAGE

1-004AOFFICE

1-003C

OFFICE

1-003B

OFFICE

1-003A

OFFICE

1-003

OFFICE

1-005

OFFICE

1-005A

STORAGE

1-012

STORAGE

1-011

OFFICE

1-017

OFFICE

1-013

OFFICE

1-015

COMM

1-014A

STORAGE

1-019A

KITCHENETTE

1-106

MECH

1-901

STORAGE

1-020A

OFFICE

1-018C

STORAGE

1-018B

LOBBY

1-902

CONFERENCE

ROOM

1-019

WOMENS

1-R02

STAIR A

1S4

STAIR D

1S3

MENS

1-R01

OFFICE

1-018A

OFFICE

1-018

ENTRY

1-900

CONFERENCE

1-020

ELEC

1-014

CORRIDOR

1-903

CONTROL

1-008C

1-016

MENS

1-016A

SHOWER

4' 8' 16'03/32"=1'-0"A1

FIRST FLOOR PLAN - SEQUENCE 1

SEQUENCE OF CONSTRUCTION

A. SEQUENCE ONE:

ALL WORK ASSOCIATED WITH THIS SEQUENCE SHALL BE COMPLETED IN NO MORE

THAN 270 DAYS.

A.A. EXTERIOR:

A.A.A. NEW RAMPS TO BE INSTALLED.

A.B. LABS:

A.B.A. CONTRACTOR WILL NOT HAVE ACCESS TO ALL LAB FACILITIES DURING

THIS CONSTRUCTION SEQUENCE.

A.C. HVAC:

A.C.A. COOLING PLANT:

A.C.A.A. PROVIDE NEW CHILLERS AND ASSOCIATED EQUIPMENT IN NEW

MECHANICAL ROOM.

A.C.A.B. ROUTE NEW CHW PIPING FROM MECHANICAL ROOM ADDITION TO

PENTHOUSE MECHANICAL ROOMS. TERMINATE CHW PIPING MAINS

IN INTERIOR OF PENTHOUSE MECHANICAL ROOMS WITH VALVED

TAPS FOR FUTURE CONNECTION DURING OTHER SEQUENCES.

A.C.B. HEATING PLANT:

A.C.B.A. PROVIDE NEW BOILERS AND ASSOCIATED EQUIPMENT IN NEW

MECHANICAL ROOM.

A.C.B.B. ROUTE NEW HW PIPING FROM MECHANICAL ROOM ADDITION TO

PENTHOUSE MECHANICAL ROOMS. TERMINATE HW PIPING MAINS

IN INTERIOR OF PENTHOUSE MECHANICAL ROOMS WITH VALVED

TAPS FOR FUTURE CONNECTION DURING OTHER SEQUENCES.

A.D. ELECTRICAL:

A.D.A. AC-5 AND AC-10:

A.D.A.A. DISCONNECT FEEDS FROM THE PP-1C TO AC-5 AND SOURCE TO

AC10.

A.D.A.B. PROVIDE ELECTRICAL FEEDS FROM PANEL PP-1C TO NEW AC-5

AND SOURCE TO AC-10.

A.D.B. SWITCHBOARDS:

A.D.B.A. ADD FUSING AND A POWER FEED FROM SPARE SWITCH IN SPACE

10 OF SWITCHBOARD PDC-A IN THE SECOND FLOOR

A.E. FIRE ALARM:

A.E.A. PROVIDE TEMPORARY WALL MOUNTED DETECTORS IN ENTRY LOBBY,

DETECTORS MUST BE BETWEEN 4" AND 12" FROM THE CEILING AFTER

THE EXISTING CEILING GRID HAS BEEN REMOVED.

A.E.B. PROVIDE FIXED TEMPERATURE HEAT DETECTORS ONLY AND NOT RATE

OR RISE DETECTORS.

A.E.C. HEAT DETECTORS SHALL BE LOCATED IN CORRIDORS AND OTHER

AREAS OF THE BUILDING. ON THE SECOND FLOOR LOCATE HEAT

DETECTORS IN CORRIDORS AND REMOVE ALL DOORS FROM THIER

HINGES TO COMMUNICATE AREAS.

A.E.D. CONTRACTOR SHALL PROVIDE A PLAN FOR PROTECTION TO THE FIRE

DEPARTMENT FOR REVIEW AND COORDINATION OF SMOKE AND HEAT

DETECTOR LOCATIONS.

A.E.E. NOTIFICATION SHALL BE REQUIRED IN THE LABS DURING

CONSTRUCTION (TEMPORARY SYSTEM).

A.E.F. PROVIDE TEMPORARY SMOKE DETECTOR SERVING THE ALF LAB,

LOCATE DETECTOR OUTSIDE THE LAB DOOR.

A.E.G. PROVIDE TEMPORARY SMOKE DETECTOR SERVING THE REAT LAB,

LOCATE DETECTOR OUTSIDE THE LAB DOOR.

A.F. ARCHITECTURAL:

A.F.A. CONSTRUCT MECHANICAL ROOM ADDITION.

A.F.B. REWORK FRONT ENTRY RAMP.

A.G. EGRESS:

A.G.A. PROVIDE TEMPORARY EXIT AND EMERGENCY EGRESS LIGHTING WITH

90 MINUTE BATTERY BACKUP FOR BUILDING EGRESS, COORDINATE

LOCATIONS WITH THE AHJ.

SEQUENCE 1

SEQUENCE 1

SEQUENCE 1

S O

LI

C

IT

A

TI

O

N N

O

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

TI

O

N

1 3 5

C

7 9

A

M A

R K

IS

S

U E

D A

TE

S

IZ

E

S U

B M

IT

TE

D B

Y

C O

N

TR

A C

T N

O

SHEET ID

D A

TE

US Army Corps of Engineers

U .S

. A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

LO

U

IS

V

IL

LE

, K Y

LO

U

IS

V

IL

LE

D

IS

TR

IC

T

W R

IG

H

T P

A

TT

E R

S O

N A

FB

R

E P

A

IR

F S

D -1

IN

TE

R

IO

R , E

X

TE

R

IO

R , A

N D

H V

A C

FA

C

IL

IT

Y

(Z H

TV

B

D

E

F

G

2 4 6 8 10

JU

LY

W

2Q R

B

FA

-1

3- D

A D V A N C E D

E N

G

IN

E E

R

IN

G C

O N

S U

LT

A

N

TS

M ec ha ni ca l |

E le ct ric al

Pl um bi ng

Fi re P ro te ct io n

D ub lin

R oa d Te l:

(6

) 4

-4

C ol um bu s, O hi o

Fa x:

(6

) 4

-4

NORTH

UNCLASSIFIED//FOR OFFICIAL USE ONLY - PROPERTY OF THE US GOVERNMENT, LIMITED REPRODUCTION AND DISSEMINATION TO MINIMUM REQUIRED TO BID AND CONSTRUCT THE PROJECT

UNCLASSIFIED//FOR OFFICIAL USE ONLY - PROPERTY OF THE US GOVERNMENT, LIMITED REPRODUCTION AND DISSEMINATION TO MINIMUM REQUIRED TO BID AND CONSTRUCT THE PROJECT

H

P

N O

CORRECTED FINAL

07/17/2020

S E

Q U

E N

C E

FI

R S

T

FL

O O

R P

LA

N

G-102

J.

L

E E

K . F

IE

LD

S

E . L

E H

M A a2a1b6 b7 b8 b9b5.1b5b4b2 aE aD aC aB aA bB bA.2 bA.1 bAbA bC bD bE bF bG bH bJ bK bL bM bN bA.3

E.9

E.1

EX1 1.0 2.0 a3b1

DN

DN

DN

MENS

2-020B

STORAGE

2-903

STAIR B

2S1

MECH

2-904

STAIR D

2S3

STAIR C

2S2

COMM

2-116C

STORAGE

2-116

JANITOR

2-118

OFFICE

2-115B

STAIR A

2S4

KITCHENETTE

2-107B

STORAGE

2-107A

OFFICE

2-008

OFFICE

2-007

OFFICE

2-006

OFFICE

2-004

OFFICE

2-001

OFFICE

2-002

OFFICE

2-003

OFFICE

2-016

OFFICE

2-100

OFFICE

2-117B

CORRIDOR

2-117G

OFFICE

2-117

CLOSET

2-117H

CORRIDOR

2-901

OFFICE

2-115C

OFFICE

2-115D

OFFICE

2-117E STORAGE

2-117F

CONFERENCE

ROOM

2-107

OFFICE

2-115

OFFICE

2-101

OFFICE

2-102

OFFICE

2-103

OFFICE

2-117D STORAGE

2-104

OFFICE

2-117C

WOMENS

2-020A

OFFICE

2-117A

ELEC

2-116B

ALF

1-010

CORRIDOR

2-905

OFFICE

2-023B

OFFICE

2-023 OFFICE

2-023C

OFFICE

2-023D

OFFICE

2-023E

CORRIDOR

2-902

4' 8' 16'03/32"=1'-0"A1

SECOND FLOOR PLAN - SEQUENCE 1

SEQUENCE 1

SEQUENCE OF CONSTRUCTION

A. SEQUENCE ONE:

ALL WORK ASSOCIATED WITH THIS SEQUENCE SHALL BE COMPLETED IN NO MORE

THAN 270 DAYS.

A.A. LABS:

A.A.A. CONTRACTOR WILL NOT HAVE ACCESS TO ALL LAB FACILITIES DURING

THIS CONSTRUCTION SEQUENCE.

A.B. HVAC:

A.B.A. CHILLED WATER PIPING:

A.B.A.A. ROUTE NEW CHW PIPING FROM MECHANICAL ROOM ADDITION TO

PENTHOUSE MECHANICAL ROOMS. TERMINATE CHW PIPING MAINS

IN INTERIOR OF PENTHOUSE MECHANICAL ROOMS WITH VALVED

TAPS FOR FUTURE CONNECTION DURING OTHER SEQUENCES.

A.B.B. HOT WATER PIPING:

A.B.B.A. ROUTE NEW HW PIPING FROM MECHANICAL ROOM ADDITION TO

PENTHOUSE MECHANICAL ROOMS. TERMINATE HW PIPING MAINS

IN INTERIOR OF PENTHOUSE MECHANICAL ROOMS WITH VALVED

TAPS FOR FUTURE CONNECTION DURING OTHER SEQUENCES.

A.B.C. PROVIDE DDC FRONT END COMMUNICATIONS IN MECHANICAL ROOM

2-904 TO COMMUNICATE WITH THE WPAFB SYSTEM.

A.C. FIRE ALARM:

A.C.A. PROVIDE TEMPORARY WALL MOUNTED DETECTORS IN ENTRY LOBBY,

DETECTORS MUST BE BETWEEN 4" AND 12" FROM THE CEILING AFTER

THE EXISTING CEILING GRID HAS BEEN REMOVED.

A.C.B. PROVIDE FIXED TEMPERATURE HEAT DETECTORS ONLY AND NOT RATE

OR RISE DETECTORS.

A.C.C. HEAT DETECTORS SHALL BE LOCATED IN CORRIDORS AND OTHER

AREAS OF THE BUILDING. ON THE SECOND FLOOR LOCATE HEAT

DETECTORS IN CORRIDORS AND REMOVE ALL DOORS FROM THIER

HINGES TO COMMUNICATE AREAS.

A.C.D. CONTRACTOR SHALL PROVIDE A PLAN FOR PROTECTION TO THE FIRE

DEPARTMENT FOR REVIEW AND COORDINATION OF SMOKE AND HEAT

DETECTOR LOCATIONS.

A.C.E. NOTIFICATION SHALL BE REQUIRED IN THE LABS DURING

CONSTRUCTION (TEMPORARY SYSTEM).

A.D. EGRESS:

A.D.A. PROVIDE TEMPORARY EXIT AND EMERGENCY EGRESS LIGHTING WITH

90 MINUTE BATTERY BACKUP FOR BUILDING EGRESS, COORDINATE

LOCATIONS WITH THE AHJ.

S O

LI

C

IT

A

TI

O

N N

O

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

TI

O

N

1 3 5

C

7 9

A

M A

R K

IS

S

U E

D A

TE

S

IZ

E

S U

B M

IT

TE

D B

Y

C O

N

TR

A C

T N

O

SHEET ID

D A

TE

US Army Corps of Engineers

U .S

. A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

LO

U

IS

V

IL

LE

, K Y

LO

U

IS

V

IL

LE

D

IS

TR

IC

T

W R

IG

H

T P

A

TT

E R

S O

N A

FB

R

E P

A

IR

F S

D -1

IN

TE

R

IO

R , E

X

TE

R

IO

R , A

N D

H V

A C

FA

C

IL

IT

Y

(Z H

TV

B

D

E

F

G

2 4 6 8 10

JU

LY

W

2Q R

B

FA

-1

3- D

A D V A N C E D

E N

G

IN

E E

R

IN

G C

O N

S U

LT

A

N

TS

M ec ha ni ca l |

E le ct ric al

Pl um bi ng

Fi re P ro te ct io n

D ub lin

R oa d Te l:

(6

) 4

-4

C ol um bu s, O hi o

Fa x:

(6

) 4

-4

NORTH

UNCLASSIFIED//FOR OFFICIAL USE ONLY - PROPERTY OF THE US GOVERNMENT, LIMITED REPRODUCTION AND DISSEMINATION TO MINIMUM REQUIRED TO BID AND CONSTRUCT THE PROJECT

UNCLASSIFIED//FOR OFFICIAL USE ONLY - PROPERTY OF THE US GOVERNMENT, LIMITED REPRODUCTION AND DISSEMINATION TO MINIMUM REQUIRED TO BID AND CONSTRUCT THE PROJECT

H

P

N O

CORRECTED FINAL

07/17/2020

S E

Q U

E N

C E

S

E C

O N

D F

LO

O

R P

LA

N

G-103

J.

L

E E

K . F

IE

LD

S

E . L

E H

M A aE aD aC aB aA bB bA.2 bA.1 bA bC bD bE bF bG bH bJ bK bL bM bN bA.3

E.9

E.1

EX1 1.0 2.0 a3b1

PENTHOUSE

3-100

PENTHOUSE

3-101

4' 8' 16'03/32"=1'-0"A1

ROOF/PENTHOUSE PLAN - SEQUENCE 1

SEQUENCE 1

SEQUENCE 1

SEQUENCE OF CONSTRUCTION

A. SEQUENCE ONE:

ALL WORK ASSOCIATED WITH THIS SEQUENCE SHALL BE COMPLETED IN NO MORE

THAN 270 DAYS.

A.A. LABS:

A.A.A. CONTRACTOR WILL NOT HAVE ACCESS TO ALL LAB FACILITIES DURING

THIS CONSTRUCTION SEQUENCE.

A.B. HVAC:

A.B.A. CHILLED WATER PIPING:

A.B.A.A. ROUTE NEW CHW PIPING FROM MECHANICAL ROOM ADDITION TO

PENTHOUSE MECHANICAL ROOMS. TERMINATE CHW PIPING MAINS

IN INTERIOR OF PENTHOUSE MECHANICAL ROOMS WITH VALVED

TAPS FOR FUTURE CONNECTION DURING OTHER SEQUENCES.

A.B.B. HOT WATER PIPING:

A.B.B.A. ROUTE NEW HW PIPING FROM MECHANICAL ROOM ADDITION TO

PENTHOUSE MECHANICAL ROOMS. TERMINATE HW PIPING MAINS

IN INTERIOR OF PENTHOUSE MECHANICAL ROOMS WITH VALVED

TAPS FOR FUTURE CONNECTION DURING OTHER SEQUENCES.

S O

LI

C

IT

A

TI

O

N N

O

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

TI

O

N

1 3 5

C

7 9

A

M A

R K

IS

S

U E

D A

TE

S

IZ

E

S U

B M

IT

TE

D B

Y

C O

N

TR

A C

T N

O

SHEET ID

D A

TE

US Army Corps of Engineers

U .S

. A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

LO

U

IS

V

IL

LE

, K Y

LO

U

IS

V

IL

LE

D

IS

TR

IC

T

W R

IG

H

T P

A

TT

E R

S O

N A

FB

R

E P

A

IR

F S

D -1

IN

TE

R

IO

R , E

X

TE

R

IO

R , A

N D

H V

A C

FA

C

IL

IT

Y

(Z H

TV

B

D

E

F

G

2 4 6 8 10

JU

LY

W

2Q R

B

FA

-1

3- D

A D V A N C E D

E N

G

IN

E E

R

IN

G C

O N

S U

LT

A

N

TS

M ec ha ni ca l |

E le ct ric al

Pl um bi ng

Fi re P ro te ct io n

D ub lin

R oa d Te l:

(6

) 4

-4

C ol um bu s, O hi o

Fa x:

(6

) 4

-4

NORTH

UNCLASSIFIED//FOR OFFICIAL USE ONLY - PROPERTY OF THE US GOVERNMENT, LIMITED REPRODUCTION AND DISSEMINATION TO MINIMUM REQUIRED TO BID AND CONSTRUCT THE PROJECT

UNCLASSIFIED//FOR OFFICIAL USE ONLY - PROPERTY OF THE US GOVERNMENT, LIMITED REPRODUCTION AND DISSEMINATION TO MINIMUM REQUIRED TO BID AND CONSTRUCT THE PROJECT

H

P

N O

CORRECTED FINAL

07/17/2020

S E

Q U

E N

C E

R

O O

F/ P

E N

TH

O

U S

E P

LA

N

G-104

J.

L

E E

K . F

IE

LD

S

E . L

E H

M A aE aD aC aB aA bB bA.2 bA.1 bAbA bC bD bE bF bG bH bJ bK bL bM bN bA.3

E.9

E.1

EX1 1.0 2.0

UP

UP

UP

BAMLAB

0-111

VERITAS

0-114A

FABRICATION

SHOP

0-117

MECH

0-118

STORAGE

0-117A

OFFICE

0-124

LAB

0-120

LAB

0-120B

LAB

0-120A

ELEVATOR

0E1

MENS

0-012

OFFICE

0-119A

OFFICE

0-119B

OFFICE

0-119

LAB

0-126B

LAB

0-126C

LAB

0-126A

STAIR C

0S2

VOCRES

0-116A

MECH

0-902

STORAGE

0-112

SHARC

0-108

0-113

BREAK ROOM

0-103

JAN.

0-904

CORRIDOR

0-906

STORAGE

0-107

LAB

0-102

COMM

0-115A

OFFICE

0-106

LAB

0-110

WOMENS

0-011

VERITAS

CONTROL

0-114

LISTENING LAB

0-101

CONFERENCE

ROOM

0-104

STORAGE

0-104ASHARC CONTROL

0-109

LAB

0-110A

VESTIBULE

0-903

STAIR A

0S4

OFFICE

0-105

VOCRES

CONTROL

0-116

OFFICE

0-125

CORRIDOR

0-905

SOFTWARE

DEVELOPMENT

LAB

0-123

STAIR B

0S1CORRIDOR

0-901

OFFICE

0-119C

LISTENING LAB

0-126

EEG LAB

0-122

VIRTUAL AUDIO

LAB

0-121

LAB

0-121A

ELEC

0-115

4' 8' 16'03/32"=1'-0"A1

BASEMENT FLOOR PLAN - SEQUENCE 2

SEQUENCE 2

S W

SEQUENCE OF CONSTRUCTION

A. SEQUENCE TWO:

ALL WORK ASSOCIATED WITH THIS SEQUENCE SHALL BE COMPLETED IN NO MORE

THAN 120 DAYS.

A.A. CORRIDOR:

A.A.A. TEMPORARY BARRIER SHALL BE CONSTRUCTED ALONG COLUMN LINE

b6 IN THE SOUTH CORRIDOR 0-901.

A.A.B. CORRIDOR SHALL BE KEPT CLEAR OF DEBRIS DURING CONSTRUCTION.

A.A.C. REFER TO SECTIONS FOR SEQUENCE OF WORK IN CORRIDORS.

A.B. LABS:

A.B.A. CONTRACTOR WILL HAVE ACCESS TO LAB FACILITIES VOCRES AND

BATMAN (0-120) DURING THIS CONSTRUCTION SEQUENCE.

A.C. HVAC:

A.C.C. AC-3:

A.C.C.A. REPLACE DUCT SYSTEM WITH DISTRIBUTED VARIABLE AIR VOLUME

(VAV) DUCT SYSTEM.

A.C.C.B. ROUTE NEW HW PIPING FROM SEQUENCE ONE PIPING MAINS TO

VAV REHEAT COILS.

A.C.C.C. PIPING WORK IN CORRIDOR 0-901 SHALL REMAIN AT A MINIMUM TO

AVOID DISTURBANCE OF ADJACENT SPACES.

A.D. ELECTRICAL:

A.D.A. PANELS:

A.D.A.A. DISCONNECT THE FEED FROM SWITCHBOARD MCC-A TO PANELS

LL-1B, 3C (LPA), LPB, LPC, LPD, PP-5 AND THE SIREN COMPRESSOR.

REPLACE THE INTERNAL BUS-WORK FOR PANELS PP-10, PP-11 AND

PP-12.

A.D.B. SWITCHBOARDS:

A.D.B.A. PROVIDE FEEDS FROM SWITCHBOARD PDC-A TO NEW HVAC

DEVICES AC-3, AND RF-3. PROVIDE FEEDS FROM SWITCHBOARDS

PDC-C AND PDC-E TO LOADS INDICATED ON THE ONE-LINE

DIAGRAM. PROVIDE A TEMPORARY FEED FROM PDC-E TO PANEL

LPC ON THE SECOND FLOOR.

A.D.C. LIGHTING:

A.D.C.A. THE EAST BASEMENT WILL BE A CONSTRUCTION ZONE. PROVIDE

LED TYPE TEMPORARY CONSTRUCTION LIGHT STRINGS IN THE

BASEMENT CORRIDOR. PROVIDE FEEDER FROM 277VAC PANEL

LPE, CIRCUIT 9 TO THIS STRING. PROVIDE BATTERY BACKED

EMERGENCY LIGHT/EXIT SIGN COMBINATIONS ON THE STRING TO

INDICATE THE EGRESS PATH PER THE LIFE SAFETY DIAGRAMS.

THE CORRIDOR LIGHTING LEVEL SHALL BE AT LEAST 5

FOOT-CANDLES.

A.D.C.B. PROVIDE BATTERY BACKED LIGHTING IN THE VOCRES CONTROL

ROOM. PROVIDE FEEDER FROM 277VAC PANEL LPE, CIRCUIT 9 TO

THIS LIGHTING. THE CORRIDOR LIGHTING LEVEL SHALL BE AT

LEAST 5 FOOT-CANDLES.

A.E. FIRE ALARM:

A.E.A. PROVIDE FIXED TEMPERATURE HEAT DETECTORS ONLY AND NOT RATE

OR RISE DETECTORS.

A.E.B. HEAT DETECTORS SHALL BE LOCATED IN CORRIDORS AND OTHER

AREAS OF THE BUILDING. ON THE SECOND FLOOR LOCATE HEAT

DETECTORS IN CORRIDORS AND REMOVE ALL DOORS FROM THIER

HINGES TO COMMUNICATE AREAS.

A.E.C. CONTRACTOR SHALL PROVIDE A PLAN FOR PROTECTION TO THE FIRE

DEPARTMENT FOR REVIEW AND COORDINATION OF SMOKE AND HEAT

DETECTOR LOCATIONS.

A.E.D. NOTIFICATION SHALL BE REQUIRED IN THE LABS DURING

CONSTRUCTION (TEMPORARY SYSTEM).

A.E.E. PROVIDE TEMPORARY SMOKE DETECTOR SERVING THE ALF LAB,

LOCATE DETECTOR OUTSIDE THE LAB DOOR.

A.E.F. PROVIDE TEMPORARY SMOKE DETECTOR SERVING THE REAT LAB,

LOCATE DETECTOR OUTSIDE THE LAB DOOR.

A.F. EGRESS:

A.F.A. PROVIDE TEMPORARY EXIT AND EMERGENCY EGRESS LIGHTING WITH

90 MINUTE BATTERY BACKUP FOR BUILDING EGRESS, COORDINATE

LOCATIONS WITH THE AHJ.

S O

LI

C

IT

A

TI

O

N N

O

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

TI

O

N

1 3 5

C

7 9

A

M A

R K

IS

S

U E

D A

TE

S

IZ

E

S U

B M

IT

TE

D B

Y

C O

N

TR

A C

T N

O

SHEET ID

D A

TE

US Army Corps of Engineers

U .S

. A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

LO

U

IS

V

IL

LE

, K Y

LO

U

IS

V

IL

LE

D

IS

TR

IC

T

W R

IG

H

T P

A

TT

E R

S O

N A

FB

R

E P

A

IR

F S

D -1

IN

TE

R

IO

R , E

X

TE

R

IO

R , A

N D

H V

A C

FA

C

IL

IT

Y

(Z H

TV

B

D

E

F

G

2 4 6 8 10

JU

LY

W

2Q R

B

FA

-1

3- D

A D V A N C E D

E N

G

IN

E E

R

IN

G C

O N

S U

LT

A

N

TS

M ec ha ni ca l |

E le ct ric al

Pl um bi ng

Fi re P ro te ct io n

D ub lin

R oa d Te l:

(6

) 4

-4

C ol um bu s, O hi o

Fa x:

(6

) 4

-4

NORTH

UNCLASSIFIED//FOR OFFICIAL USE ONLY - PROPERTY OF THE US GOVERNMENT, LIMITED REPRODUCTION AND DISSEMINATION TO MINIMUM REQUIRED TO BID AND CONSTRUCT THE PROJECT

UNCLASSIFIED//FOR OFFICIAL USE ONLY - PROPERTY OF THE US GOVERNMENT, LIMITED REPRODUCTION AND DISSEMINATION TO MINIMUM REQUIRED TO BID AND CONSTRUCT THE PROJECT

H

P

N O

CORRECTED FINAL

07/17/2020

S E

Q U

E N

C E

B

A S

E M

E N

T

FL

O O

R P

LA

N

G-105

J.

L

E E

K . F

IE

LD

S

E . L

E H

M A aE aD aC aB aA bAbA bC bD bE bF bG bH bJ bK bL bM bN bA.3

E.9

E.1

EX1 1.0 2.0 a3b1

DN

UP

DN

UP

DN

DN UP

ALF

1-010

MIRE

1-008A

STAGING

1-009

CORRIDOR

1-904

AAC

1-008D

REAT

1-008E

LAB

1-008B

MECH

1-006

CONTROL

1-008

WOMENS

1-007

STAIR B

1S1

STAIR C

1S2

CONFERENCE

1-004

STORAGE

1-004AOFFICE

1-003C

OFFICE

1-003B

OFFICE

1-003A

OFFICE

1-003

OFFICE

1-005

OFFICE

1-005A

STORAGE

1-012

STORAGE

1-011

OFFICE

1-017

OFFICE

1-013

OFFICE

1-015

COMM

1-014A

STORAGE

1-019A

KITCHENETTE

1-106

MECH

1-901

STORAGE

1-020A

OFFICE

1-018C

STORAGE

1-018B

LOBBY

1-902

CONFERENCE

ROOM

1-019

WOMENS

1-R02

STAIR A

1S4

STAIR D

1S3

MENS

1-R01

OFFICE

1-018A

OFFICE

1-018

ENTRY

1-900

CONFERENCE

1-020

ELEC

1-014

CORRIDOR

1-903

CONTROL

1-008C

1-016

MENS

1-016A

SHOWER

4' 8' 16'03/32"=1'-0"A1

FIRST FLOOR PLAN - SEQUENCE 2

SEQUENCE 2

SEQUENCE OF CONSTRUCTION

A. SEQUENCE TWO:

ALL WORK ASSOCIATED WITH THIS SEQUENCE SHALL BE COMPLETED IN NO MORE

THAN 120 DAYS.

A.A. CORRIDOR:

A.A.A. TEMPORARY BARRIER SHALL BE CONSTRUCTED ALONG COLUMN LINE

b6 IN THE SOUTH CORRIDOR 0-901.

A.A.B. CORRIDOR SHALL BE KEPT CLEAR OF DEBRIS DURING CONSTRUCTION.

A.A.C. REFER TO SECTIONS FOR SEQUENCE OF WORK IN CORRIDORS.

A.B. LABS:

A.B.A. CONTRACTOR WILL HAVE ACCESS TO LAB FACILITIES VOCRES AND

BATMAN (0-120) DURING THIS CONSTRUCTION SEQUENCE.

A.C. HVAC:

A.C.A. AC-3:

A.C.A.A. REPLACE AC-3 IN MECHANICAL ROOM 1-006 WITH NEW CHW/HW AIR

HANDLING UNIT. REPLACE ASSOCIATED CHW PIPING WITH NEW

PIPING FROM SEQUENCE ONE SYSTEM. ROUTE NEW HW FROM

SEQUENCE ONE SYSTEM. DEMOLISH ALL ASSOCIATED STEAM

PIPING.

A.D. ELECTRICAL:

A.D.A. PANELS:

A.D.A.A. OPEN THE SWITCH AND DISCONNECT THE FEED FROM

SWITCHBOARD MCC-A TO PANEL PPJ. REPLACE THE INTERNAL

BUS-WORK FOR THIS PANEL. RE-FEED THIS PANEL FROM SPARE

FUSED SWITCH 5 IN SWITCHBOARD PDP-A.

A.D.A.B. OPEN THE SWITCH AND DISCONNECT THE FEED FROM

SWITCHBOARD MCC-A TO PANELS PP2, PP-4 AND ROOM 211 AH.

THIS EQUIPMENT IS NO LONGER USED.

A.D.A.C. OPEN THE SWITCH AND DISCONNECT THE FEED FROM

SWITCHBOARD MCC-A TO PANEL PP-1C. REPLACE THE INTERNAL

BUS-WORK FOR PANELS PP-1C, 1-400 AND THE BASEMENT DC

PANEL.

A.D.A.D. DISCONNECT FEEDS FROM SWITCHBOARD PDC-A TO EXISTING AIR

HANDLING UNIT AC-4, FAN RF-4 AND CONDENSER #4.

A.D.A.E. OPEN THE SWITCHES AND DISCONNECT THE FEEDS FROM

SWITCHBOARD MCC-A TO THE 45KVA TRANSFORMER AND

DISCONNECT SWITCH FOR PANEL CP-1B. DISCONNECT THE FEED

FROM SWITCHBOARD MCC-A TO THE DISCONNECT AND 75KVA

TRANSFORMER FOR PANEL PP-100. TEMPORARILY RELOCATE THE

TRANSFORMERS AND DISCONNECT SWITCHES WHILE THE AIR

HANDLER AH-4 DUCT WORK IS REMOVED.

A.D.A.F. DISCONNECT THE FEEDS FROM PANEL PDP-1 TO THE

TRANSFORMER T-24, THE SIREN COMPRESSOR AND PANELS PP-10,

PP-11, PP-12 AND HP-1. DISCONNECT THE FEED WIRING FROM

MCC-A TO PANEL PDP-1. SINCE THE PDP-1 FEED IS TIED DIRECTLY

TO THE BUS-WORK FOR MCC-A (AND NOT THROUGH AN ISOLATING

BREAKER), THE MCC-A SWITCHBOARD WILL NEED TO BE SHUT

DOWN FOR THIS WORK. REMOVE PANEL PDP-1 ON THE STAIRWAY.

A.D.A.G. DISCONNECT FEEDS FROM PANEL PP-1 TO AIR CONDITIONER #3,

CHILLERS AND CONDENSER LOADS. DISCONNECT THE FEED FROM

SWITCHBOARD MCC-A TO PANEL PP-1. REMOVE PANEL PP-1.

A.D.B. SWITCHBOARDS:

A.D.B.A. AFTER AC-4 IS REMOVED, THE LOUVER OPENING ON THE WALL IS

AVAILABLE FOR REMOVING ELECTRICAL EQUIPMENT. DISCONNECT

THE ELECTRICAL FEED FROM SWITCHBOARD PDC-A TO

SWITCHBOARD MCC-A. REMOVE SWITCHBOARD MCC-A.

A.D.B.B. PROVIDE NEW SWITCHBOARD PDC-C IN THE FIRST FLOOR

ELECTRICAL ROOM. PROVIDE A FEED FROM SWITCHBOARD PDC-A

TO SWITCHBOARD PDC-C. USE THE SAME SWITCH THAT MCC-A

WAS CONNECTED TO. REPLACE FUSES AS REQUIRED.

A.D.B.C. PROVIDE NEW SWITCHBOARD PDC-E IN THE FIRST FLOOR

ELECTRICAL ROOM. PROVIDE A FEED FROM A SPARE FUSED

SWITCH ON SWITCHBOARD PDP-A TO SWITCHBOARD PDC-E.

A.D.B.D. RE-INSTALL THE TRANSFORMERS AND DISCONNECT SWITCHES

FOR PANELS PP-100 AND CP1-1B. PROVIDE FEEDS TO THESE

CIRCUITS. UPON COMPLETION OF THESE STEPS, THE LABS CAN BE

OPERATIONAL.

A.E. FIRE ALARM:

A.E.A. PROVIDE TEMPORARY WALL MOUNTED DETECTORS IN ENTRY LOBBY,

DETECTORS MUST BE BETWEEN 4" AND 12" FROM THE CEILING AFTER

THE EXISTING CEILING GRID HAS BEEN REMOVED.

A.E.B. PROVIDE FIXED TEMPERATURE HEAT DETECTORS ONLY AND NOT RATE

OR RISE DETECTORS.

A.E.C. HEAT DETECTORS SHALL BE LOCATED IN CORRIDORS AND OTHER

AREAS OF THE BUILDING. ON THE SECOND FLOOR LOCATE HEAT

DETECTORS IN CORRIDORS AND REMOVE ALL DOORS FROM THIER

HINGES TO COMMUNICATE AREAS.

A.E.D. CONTRACTOR SHALL PROVIDE A PLAN FOR PROTECTION TO THE FIRE

DEPARTMENT FOR REVIEW AND COORDINATION OF SMOKE AND HEAT

DETECTOR LOCATIONS.

A.E.E. NOTIFICATION SHALL BE REQUIRED IN THE LABS DURING

CONSTRUCTION (TEMPORARY SYSTEM).

A.E.F. PROVIDE TEMPORARY SMOKE DETECTOR SERVING THE ALF LAB,

LOCATE DETECTOR OUTSIDE THE LAB DOOR.

A.E.G. PROVIDE TEMPORARY SMOKE DETECTOR SERVING THE REAT LAB,

LOCATE DETECTOR OUTSIDE THE LAB DOOR.

A.F. EGRESS:

A.F.A. PROVIDE TEMPORARY EXIT AND EMERGENCY EGRESS LIGHTING WITH

90 MINUTE BATTERY BACKUP FOR BUILDING EGRESS, COORDINATE

LOCATIONS WITH THE AHJ.

S O

LI

C

IT

A

TI

O

N N

O

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

TI

O

N

1 3 5

C

7 9

A

M A

R K

IS

S

U E

D A

TE

S

IZ

E

S U

B M

IT

TE

D B

Y

C O

N

TR

A C

T N

O

SHEET ID

D A

TE

US Army Corps of Engineers

U .S

. A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

LO

U

IS

V

IL

LE

, K Y

LO

U

IS

V

IL

LE

D

IS

TR

IC

T

W R

IG

H

T P

A

TT

E R

S O

N A

FB

R

E P

A

IR

F S

D -1

IN

TE

R

IO

R , E

X

TE

R

IO

R , A

N D

H V

A C

FA

C

IL

IT

Y

(Z H

TV

B

D

E

F

G

2 4 6 8 10

JU

LY

W

2Q R

B

FA

-1

3- D

A D V A N C E D

E N

G

IN

E E

R

IN

G C

O N

S U

LT

A

N

TS

M ec ha ni ca l |

E le ct ric al

Pl um bi ng

Fi re P ro te ct io n

D ub lin

R oa d Te l:

(6

) 4

-4

C ol um bu s, O hi o

Fa x:

(6

) 4

-4

NORTH

UNCLASSIFIED//FOR OFFICIAL USE ONLY - PROPERTY OF THE US GOVERNMENT, LIMITED REPRODUCTION AND DISSEMINATION TO MINIMUM REQUIRED TO BID AND CONSTRUCT THE PROJECT

UNCLASSIFIED//FOR OFFICIAL USE ONLY - PROPERTY OF THE US GOVERNMENT, LIMITED REPRODUCTION AND DISSEMINATION TO MINIMUM REQUIRED TO BID AND CONSTRUCT THE PROJECT

H

P

N O

CORRECTED FINAL

07/17/2020

S E

Q U

E N

C E

FI

R S

T

FL

O O

R P

LA

N

G-106

J.

L

E E

K . F

IE

LD

S

E . L

E H

M A aE aD aC aB aA bB bA.2 bA.1 bAbA bC bD bE bF bG bH bJ bK bL bM bN bA.3

E.9

E.1

EX1 1.0 2.0

UP

UP

UP

BAMLAB

0-111

VERITAS

0-114A

FABRICATION

SHOP

0-117

MECH

0-118

STORAGE

0-117A

OFFICE

0-124

LAB

0-120

LAB

0-120B

LAB

0-120A

ELEVATOR

0E1

MENS

0-012

OFFICE

0-119A

OFFICE

0-119B

OFFICE

0-119

LAB

0-126B

LAB

0-126C

LAB

0-126A

STAIR C

0S2

VOCRES

0-116A

MECH

0-902

STORAGE

0-112

SHARC

0-108

0-113

BREAK ROOM

0-103

JAN.

0-904

CORRIDOR

0-906

STORAGE

0-107

LAB

0-102

COMM

0-115A

OFFICE

0-106

LAB

0-110

WOMENS

0-011

VERITAS

CONTROL

0-114

LISTENING…

This is the start of the file's text. The full file is on GovTribe.