This document package includes plans and specifications for the renovation of HPW Building 441 at Wright-Patterson Air Force Base in Ohio. The project involves interior, exterior, HVAC, and fire protection system upgrades. Key details include a construction budget between $10-25 million, a NAICS code of 236220 for commercial and institutional building construction, and a 100% small business set-aside. The solicitation will be available exclusively on beta.SAM.gov. Plans include first floor fire alarm layout, details, schedules for mechanical equipment, and a general information sheet noting design standards and existing conditions. Specifications cover fire alarm and mass notification systems installation.

View the file

Other files

Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

LINE TYPE LEGEND

EXISTING TO REMAIN

EXISTING TO BE REMOVED

NEW WORK

ACCEPTANCE TESTING NOTES:

A. AUDIBILITY REQUIREMENTS AS DEFINED IN NFPA 72 SHALL APPLY ONLY TO THE ALERT TONES

THAT PRECEDE OR FOLLOW VOICE MESSAGES, AND UNLESS NOTED OTHERWISE, SHALL UTILIZE

THE AMBIENT SOUND PRESSURE LEVELS AS LISTED IN TABLE A.18.4.3 OF NFPA 72 FOR TESTING

PURPOSES.

A.A. 55 DBA (BUISNESS OCCUPANCIES) SHALL BE USED FOR ALL NON- MECHANICAL TYPE

SPACES.

A.B. 85 DBA SHALL BE USED FOR MECHANICAL ROOMS UNLESS SPECIFICALLY NOTED OTHERWISE

ON THE FLOOR PLANS.

B. INTELLIGIBILITY REQUIREMENTS SHALL BE AS DEFINED IN UFC 4-021-01. ALL OCCUPIED SPACES

SHALL HAVE A CIS VALUE OF .8 MINIMUM, UNLESS SPECIFICALLY NOTED OTHERWISE ON THE

FLOOR PLANS.

SPEAKER ONLY (80" AFF TO BOTTOM OF DEVICE) - WP =

WEATHER PROOF - 'C' = CEILING MOUNTED

SPEAKER STROBE DEVICE W/"ALERT" DESIGNATION "C"

INDICATES CEILING MOUNTED, "W" INDICATES

WALL MTD. (80" AFF TO BOTOM OF DEVICE)

STROBE ONLY DEVICE - "C" = CEILING DEVICE

SMOKE DETECTOR WITH AUX. CONTACTS (CEILING

MOUNTED)

FIRE ALARM / MASS NOTIFICATION CONTROL PANEL

FIRE ALARM MANUAL PULL STATION (44" TO HANDLE

OF DEVICE)

KB FIRE PROTECTION SECURE KEY BOX (48" AFF TO

TOP OF BOX)

FMCP

MASS NOTIFICATION DOCUMENTATION CABINET, 48"

AFF TO BOTTOM OF CABINET

FIRE ALARM/MASS NOTIFICATION

SYSTEM SYMBOLS

M FIRE ALARM ADDRESSABLE RELAY MODULE

FAAP

FIRE ALARM REMOTE ANNUNCIATOR PANEL ( 48"

AFF TO BOTTOM OF PANEL.)

T

PV

WATER FLOW SWITCH

WATER TAMPER SWITCH

POST INDICATOR VALVE

F

S

HEAT DETECTOR

WF

S

CARBON MONOXIDE DETECTORCO

PS PRESSURE SWITCH

ABBREVIATIONS

CD CANDELA

dB DECIBELS

WP WEATHER PROOF

DUCT SMOKE DETECTOR

S

FIRE ALARM/MASS NOTIFICATION

SYSTEM SYMBOLS CONT.

LOC LOCAL OPERATOR CONSOLE (LOC)

FIRE ALARM MINIPLPEX TRANSPONDER PANEL ,

(48" AFF TO BOTTOM OF PANEL)

MTP

F FIRE ALARM BELL, 120 VOLT

FIRE ALARM HVAC SHUTDOWN RELAYR

ADDRESSIBLE INPUT - OUTPUT MODULEAIO

RI FIRE ALARM REMOTE INDICATOR

EMERGENCY TEXTUAL VISIBLE APPLIANCE

CARBON MONOXIDE DETECTOR

CO

ET

GENERAL FIRE ALARM NOTES:

1. EXISTING FIRE ALARM SYSTEM SHALL REMAIN OPERATIONAL DURING CONSTRUCTION.

CONTRACTOR SHALL PLAN WORK TO MINIMIZE ANY REQUIRED OUTAGES, AND SHALL PROVIDE

A FIRE WATCH AS REQUIRED. COORDINATE SCHEDULING OF OUTAGES WITH CONTRACTING

OFFICERS REPRESENTATIVE. THE CONTRACTOR SHALL BE RESPONSIBLE FOR FIRE

PROTECTION DURING CONSTRUCTION IN ACCORDANCE WITH NFPA 241 AND THE LATEST

VERSION OF USACE SAFETY AND HEALTH REQUIREMENTS MANUAL, EM 385-1-1, IN EFFECT ON

DATE OF THE SOLICITATION.

2. EXISTING FIRE ALARM SYSTEM IS A SIMPLEX 4100ES SYSTEM. EXISTING TO REMAIN NODE

PANELS SHALL REMAIN AS IS. ANY NEW DEVICES ADDED TO THE SYSTEM SHALL BE 100 %

COMPATIBLE WITH EXISTING SIMPLEX SYSTEM.

3. MAINTAIN CONTINUITY OF ALL DEVICES OUTSIDE SCOPE OF WORK AREA. PROVIDE JUNCTION

BOXES AND OTHER DEVICES NECESSARY WHERE NEEDED TO MAINTAIN CONTINUITY OF

EXISTING CIRCUITS.

4. REMOVE EXISTING FIRE ALARM NOTIFICATION DEVICES AS INDICATED ON THE DRAWINGS.

INCLUDING ASSOCIATED WIRING AND EQUIPMENT BACK TO SOURCE OR NEAREST DEVICE THAT

IS TO REMAIN.

5. UNLESS NOTED OTHERWISE, SURFACE MOUNTED BOXES AND WIREWAYS THAT ARE RENDERED

EMPTY AFTER DEMOLITION SHALL BE REMOVED COMPLETE. CONTRACTOR SHALL PATCH,

REPAIR AND PAINT EXISTING WALLS TO LIKE NEW CONDITION. PROVIDE BLANK COVERS ON ANY

EXISTING SURFACE MOUNTED BOXES THAT ARE REQUIRED TO REMAIN. PAINTING OF WALLS

SHALL INCLUDE FLOOR TO CEILING, CORNER TO CORNER OF AREA AFFECTED.

6. PROVIDE STEEL BLANK COVERS FOR FLUSH MOUNTED BACKBOXES AFTER REMOVAL OF

EXISTING DEVICES. COVERS SHALL BE PAINTED TO MATCH EXISTING WALLS. BOXES LOCATED

IN WALLS THAT HAVE EXISTING WALL COVERINGS (WALLPAPER, ETC.) SHALL BE PROVIDED WITH

STAINLESS STEEL BLANK COVERPLATES.

7. REMOVE EXISTING RACEWAYS THAT ARE NOT BEING REUSED BACK TO NEAREST JUNCTION

BOX, EXCEPT THOSE NOTED ON PLANS.

8. CEILING TILES DAMAGED BY THE CONTRACTOR SHALL BE REPLACED BY THE CONTRACTOR AND

SHALL MATCH EXISTING. TILES SHALL BE REPLACED BEFORE COMPLETION OF WORK IN AN

AREA.

9. THE DESIGN AND INSTALLATION OF THE SYSTEM CONTROL UNIT SHALL MEET THE

REQUIREMENTS OF NFPA 72, EXCEPT AS MODIFIED BY THE SPECIFICATIONS OR THE CONTRACT

DRAWINGS. ANY CONFLICTS BETWEEN THE DRAWINGS AND SPECIFICATIONS, AND NFPA 72

SHALL BE BROUGHT TO THE ATTENTION OF THE CONTRACTING OFFICER FOR RESOLUTION. IN

ALL CASES THE MOST STRINGENT REQUIREMENT SHALL APPLY.

10. PORTIONS OF THE FACILITY THAT REQUIRE ISOLATION DEVICES MAY HAVE ACCESS

RESTRICTIONS. SPECIAL ACCESS ARRANGEMENTS MAY BE REQUIRED. CONTRACTOR SHALL

COORDINATE WORK IN THESE AREAS WITH CONTRACTING OFFICERS REPRESENTATIVE. WORK

SHALL BE STAGED AND PERFORMED TO MINIMIZE THE NUMBER OF VISITS TO EACH OF THESE

AREAS.

11. FIRE STOPPING SHALL BE PROVIDED FOR ALL PENETRATIONS OF WALLS THAT GO FROM FLOOR

TO DECK.

S O

LI

C

IT

A

TI

O

N N

O

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

TI

O

N

1 3 5

C

7 9

A

M A

R K

IS

S

U E

D A

TE

S

IZ

E

S U

B M

IT

TE

D B

Y

C O

N

TR

A C

T N

O

SHEET ID

D A

TE

US Army Corps of Engineers

U .S

. A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

LO

U

IS

V

IL

LE

, K Y

LO

U

IS

V

IL

LE

D

IS

TR

IC

T

A M

E N

D M

E N

T

/1 9/

W R

IG

H

T P

A

TT

E R

S O

N A

FB

R

E P

A

IR

F S

D -1

IN

TE

R

IO

R , E

X

TE

R

IO

R , A

N D

H V

A C

FA

C

IL

IT

Y

(Z H

TV

B

D

E

F

G

2 4 6 8 10

JU

LY

W

2Q R

B

FA

-1

3- D

A D

V A

N C

E D

E N

G

IN

E E

R

IN

G C

O N

S U

LT

A

N

TS

M ec ha ni ca l |

E le ct ric al

Pl um bi ng

Fi re P ro te ct io n

D ub lin

R oa d Te l:

(6

) 4

-4

C ol um bu s, O hi o

Fa x:

(6

) 4

-4

UNCLASSIFIED//FOR OFFICIAL USE ONLY - PROPERTY OF THE US GOVERNMENT, LIMITED REPRODUCTION AND DISSEMINATION TO MINIMUM REQUIRED TO BID AND CONSTRUCT THE PROJECT

UNCLASSIFIED//FOR OFFICIAL USE ONLY - PROPERTY OF THE US GOVERNMENT, LIMITED REPRODUCTION AND DISSEMINATION TO MINIMUM REQUIRED TO BID AND CONSTRUCT THE PROJECT

H

P

N O

CERTIFIED FINAL

07/17/2020

FI

R

E A

LA

R

M G

E N

E R

A L

IN

FO

R M

A

TI

O N

FA001

J.

L

E E

K .F

IE

LD

S

M . R

IC

E

W

2Q R

B0

1P la ns

-0 ab6 b7b5b4 bA bC bD bE bF bG bH bJ bK bL bM bN bA.3

EX1 1.0 2.0b1

DN

S

S

OFFICE

1-017

OFFICE

1-013

OFFICE

1-015

COMM

1-014A

STORAGE

1-019A

KITCHENETTE

1-106

OFFICE

1-018C

STORAGE

1-018B

LOBBY

1-902

CONFERENCE

ROOM

1-019

WOMENS

1-R02

STAIR A

1S4 MENS

1-R01

OFFICE

1-018A

OFFICE

1-018

ENTRY

1-900

CONFERENCE

1-020

ELEC

1-014

CORRIDOR

1-903

1-016

MENS

1-016A

SHOWER

01/8"=1'-0" 4' 8' 16'A1 FIRST FLOOR PLAN - WEST - FIRE ALARM

(E)PANEL FACP

FA

C

P

S

C

C

C

C

F

W

C

C

C

C

LO

C

W

W

W

W

KB

S

C

C

C

TWF

C

S C

S

C

C

C

S C

C

C

S

C

S

C

C

S

C

S

C

S C

S

GENERAL SHEET NOTES:

1. ACTUAL CANDELA AND DECIBEL SETTINGS SHALL BE BASED ON

FINAL DESIGN AS SUBMITTED IN SHOP DRAWINGS. REFER TO

SPECIFICATIONS.

2. REFER TO SPECIFICATIONS, SCHEDULES AND DETAILS FOR

ADDITIONAL REQUIREMENTS.

3. ALL CONDUITS/CONDUCTORS SHALL BE CONCEALED UNLESS

NOTED OTHERWISE ON PLANS.

4. COORDINATE DEVICE INSTALLATIONS, MOUNTING HEIGHTS,

CONDUIT, CABLE ROUTING ETC. WITH EXISTING STRUCTURES AND

OTHER TRADES PRIOR TO COMMENCEMENT OF WORK.

5. FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO

COMMENCEMENT OF WORK.

6. SEAL ALL PENETRATIONS OF WALLS/FLOORS MOISTURE TIGHT,

PROVIDE FIRE SEALS FOR RATED WALLS AND CEILINGS.

7. ALL EXTERIOR FIRE ALARM / MASS NOTIFICATION SPEAKERS SHOWN

SHALL HAVE A MINIMUM DECIBEL RATING OF 81 UNLESS NOTED

OTHERWISE BASED ON A SPEAKER TAPPED AT A 7.5 WATT AND

MEASURED AT 10'.

WP

ET

SHEET KEYNOTES:

1. EXISTING TO REMAIN FIRE ALARM CONTROL PANEL, SIMPLEX

4100ES SERIES.

2. PROVIDE WALL MOUNTED DOCUMENTATION CABINET FOR FIRE

ALARM MASS NOTIFICATION SYSTEM. PROVIDE LABEL ON PANEL

THAT READS "SYSTEM RECORD DOCUMENTS".

3. PROVIDE FIRE ALARM CONNECTION TO SECURE KEY BOX TAMPER

SWITCH. THIS BOX SHALL BE A KNOX BOX INSTALLED BETWEEN 48

AND 60 INCHES AFF, THE PROCUREMENT AND KEYING OF THE KNOX

BOX SHALL BE COORDINATED WITH THE WPAFB FIRE DEPARTMENT.

4. MUSHROOM HEAD TYPE MAINTAINED POSITION EMERGENCY HVAC

SHUT DOWN BUTTON.

5. PROVIDE A RELAY THAT WILL CHANGE STATE WHEN THE LOC

MICROPHONE IS USED. CONTACTS OFF THIS RELAY WILL SERVE TO

DISCONNECT ALL SPEAKERS WITHIN A 30 FOOT RADIUS OF THE

ASSOCIATED LOC PANEL TO PREVENT FEEDBACK. SELECT THE

RELAY WITH RATINGS COMPATIBLE WITH THE LOC CONTROL

CIRCUITRY AND SPEAKER LOADS.

S O

LI

C

IT

A

TI

O

N N

O

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

TI

O

N

1 3 5

C

7 9

A

M A

R K

IS

S

U E

D A

TE

S

IZ

E

S U

B M

IT

TE

D B

Y

C O

N

TR

A C

T N

O

SHEET ID

D A

TE

US Army Corps of Engineers

U .S

. A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

LO

U

IS

V

IL

LE

, K Y

LO

U

IS

V

IL

LE

D

IS

TR

IC

T

A M

E N

D M

E N

T

/1 9/

W R

IG

H

T P

A

TT

E R

S O

N A

FB

R

E P

A

IR

F S

D -1

IN

TE

R

IO

R , E

X

TE

R

IO

R , A

N D

H V

A C

FA

C

IL

IT

Y

(Z H

TV

B

D

E

F

G

2 4 6 8 10

JU

LY

W

2Q R

B

FA

-1

3- D

A D

V A

N C

E D

E N

G

IN

E E

R

IN

G C

O N

S U

LT

A

N

TS

M ec ha ni ca l |

E le ct ric al

Pl um bi ng

Fi re P ro te ct io n

D ub lin

R oa d Te l:

(6

) 4

-4

C ol um bu s, O hi o

Fa x:

(6

) 4

-4

NORTH

UNCLASSIFIED//FOR OFFICIAL USE ONLY - PROPERTY OF THE US GOVERNMENT, LIMITED REPRODUCTION AND DISSEMINATION TO MINIMUM REQUIRED TO BID AND CONSTRUCT THE PROJECT

UNCLASSIFIED//FOR OFFICIAL USE ONLY - PROPERTY OF THE US GOVERNMENT, LIMITED REPRODUCTION AND DISSEMINATION TO MINIMUM REQUIRED TO BID AND CONSTRUCT THE PROJECT

H

SCALE:

KEY PLAN

NTS

P

N O

CERTIFIED FINAL

07/17/2020

FI

R

E A

LA

R

M W

E S

T

FI

R S

T

FL

O O

R P

LA

N

FA111

J.

L

E E

K . F

IE

LD

S

M . R

IC

E

W

2Q R

B0

1P la ns

-0

NTSA3 OPERATION MATRIX - FIRE ALARM / MASS NOTIFICATION SYSTEM

WATER FLOW INDICATOR

TR

OUBLE

IN

DIC

ATO

R F

OR F

IR

E A

LA

RM IN

TE

RRUPTE

D F

OR M

NS A

NNOUNCEMENT

G

ALA

RM IN

DIC

ATO

R A

UDIO

VIS

UAL

SUPERVIS

ORY IN

DIC

ATO

R A

UDIO

VIS

UAL

TR

OUBLE

IN

DIC

ATO

R A

UDIO

VIS

UAL

BA C D E F

ACTI

VATE

S

PEAKER / S

TR

OBES T

HROUGHOUT

BUILD

IN

G

MJH I K L PN O Q R S

MANUAL PULL STATION

DUCT SMOKE DETECTOR FOR UNIT SHUTDOWN

FIRE ALARMS AAUT V W X Y DDBB CC EE

FIRE SUPPRESSION VALVE TAMPER SWITCH

GBA C D E F MJH I K L PN O Q R S

TRANSRECEIVER DOOR TAMPER SWITCH

SUPERVISORY UT V W X Y

FIRE ALARM NOTIFICATION ACTIVATION

GBA C D E F MJH I K L PN O Q R SMASS NOTIFICATION SYSTEM (MNS) UT V W X Y

REQUIRED ACTIONCONTROL UNIT

ANNUNCIATION

FIRE ALARM NOTIFICATION ACTIVATION

GBA C D E F MJH I K L PN O Q R S

PRERECORDED VOICE MESSAGE # ACTIVATED

MASS NOTIFICATION SYSTEM (MNS) UT V W X Y

(TYPICAL FOR EACH OF THE EIGHT BUTTONS)

LIVE MESSAGE FROM BASE SYSTEM

LIVE VOICE ANNOUNCEMENT ACTIVATED AT LOC

SMOKE DETECTOR / HEAT DETECTOR

DIS

PLA

Y C

ORRECT

LO

CATI

ON / C

ONDIT

IO

N IN

P

LA

IN

E

NGLIS

H

RECORD E

VENTS

IN

S

YSTE

MS LO

G

NOTIFICATION SUPPLEMENTARY FUNCTIONS

TR

ANSMIT

T

ROUBLE

S

IG

NAL B

ETW

EEN B

UILD

IN

G F

IR

E A

LA

RM S

YSTE

M A

ND B

ASE S

YSTE

M

TR

ANSMIT

S

IG

NAL B

ETW

EEN B

UILD

IN

G M

ASS N

OTI

FI

CATI

ON S

YSTE

M A

ND B

ASE S

YSTE

M

SHUT

DOW

N H

VAC U

NIT

FF GG HH II JJ KK LLZ

AA DDBB CC EE FF GG HH II JJ KK LLZ

AA DDBB CC EE FF GG HH II JJ KK LLZ

FACP AC POWER FAILURE

GBA C D E F MJH I K L PN O Q R S

FACP LOW BATTERY

TROUBLE SIGNALS UT V W X Y

AA DDBB CC EE FF GG HH II JJ KK LLZ

OPEN CIRCUIT / SHORT CIRCUIT

GROUND FAULT

TEST MODE

06ELEVATOR LOBBY SMOKE DETECTOR 1ST. FLOOR

GENERAL SHEET NOTES:

1. ALL WIRING SHALL BE RUN AS CLASS B'.

2. RISER DIAGRAM IS SCHEMATIC IN NATURE AND MAY VARY

DEPENDING ON FIRE ALARM PANEL MANUFACTURER.

RECALL

E

LE

VATO

R T O P

RIM

ARY F

LO

OR

ELEVATOR LOBBY SMOKE DETECTOR BASEMENT

RECALL

E

LE

VATO

R T O A

LT

ERNATE

F

LO

OR

NTSE1 DIAGRAM - FIRE ALARM / MNS SYSTEM RISER

120VAC

FS

C C

HVAC

SHUT

DOWN

M

F

S S

S

C C

HVAC

SHUT

DOWN

M

F

S S

S

HVAC

SHUT

DOWN

M

F

S S

S

HVAC

SHUT

DOWN

M

SURGE

ARRESTOR

(TYP)

07ELEVATOR LOBBY SMOKE DETECTOR 2ND. FLOOR

KEY

BOX

F PV

M M MM

DELAY

EGRESS

DOORS

WF

M

PS

LOC

C C C S S

SHELTER

IN PLACE

SEVERE

WEATHER

CUSTOM

MESSAGE 4

CUSTOM

MESSAGE 5

CUSTOM

MESSAGE 6

CUSTOM

MESSAGE 7

CUSTOM

MESSAGE 8

(TYP)

EMERGENCY

HVAC

SHUTDOWN

ET

ET

ET

CO

CO

BASEMENT

1ST. FLOOR

LOC LOC LOC

2ND. FLOOR

08PREACTION DRY PIPE SYSTEM ANECHOIC CHAMBER, BASEMENT

2 TWISTED

PAIR

COPPER

SIGNAL T0

BASE FIRE

DEPARTMENT

C/O DETECTOR

TR

ANSMIT

A

LA

RM S

IG

NAL B

ETW

EEN B

UILD

IN

G F

IR

E A

LA

RM A

ND B

ASE S

YSTE

M

AIO AIO

ELEV

SHUNT

TRIP

ELEV

RECALL

SHUT

DOW

N E

LE

VATO

R V

IA

S

HUNT

TR

IP

D

IS

CONNECT

SW

IT

CH

SHEET KEYNOTES:

1. EXISTING TO REMAIN SIMPLEX 4100ES FIRE ALARM CONTROL

PANEL. EXISTING TO REMAIN FA/MASS NOTIFICATION CIRCUITS ON

FIRST FLOOR WEST SHALL REMAIN, ALL OTHER DEVICES SHALL BE

REMOVED. SEE FIRE ALARM/MASS NOTIFICATION RISER THIS

SHEET.

2. PROVIDE FIRE ALARM WIRING AND RACEWAYS AS REQUIRED FOR

NEW SIGNAL, NAC , POWER AND SHUTDOWN CIRCUITS.

EXISTING

FACP

SIMPLEX

4100ES

S O

LI

C

IT

A

TI

O

N N

O

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

TI

O

N

1 3 5

C

7 9

A

M A

R K

IS

S

U E

D A

TE

S

IZ

E

S U

B M

IT

TE

D B

Y

C O

N

TR

A C

T N

O

SHEET ID

D A

TE

US Army Corps of Engineers

U .S

. A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

LO

U

IS

V

IL

LE

, K Y

LO

U

IS

V

IL

LE

D

IS

TR

IC

T

A M

E N

D M

E N

T

/1 9/

W R

IG

H

T P

A

TT

E R

S O

N A

FB

R

E P

A

IR

F S

D -1

IN

TE

R

IO

R , E

X

TE

R

IO

R , A

N D

H V

A C

FA

C

IL

IT

Y

(Z H

TV

B

D

E

F

G

2 4 6 8 10

JU

LY

W

2Q R

B

FA

-1

3- D

A D

V A

N C

E D

E N

G

IN

E E

R

IN

G C

O N

S U

LT

A

N

TS

M ec ha ni ca l |

E le ct ric al

Pl um bi ng

Fi re P ro te ct io n

D ub lin

R oa d Te l:

(6

) 4

-4

C ol um bu s, O hi o

Fa x:

(6

) 4

-4

UNCLASSIFIED//FOR OFFICIAL USE ONLY - PROPERTY OF THE US GOVERNMENT, LIMITED REPRODUCTION AND DISSEMINATION TO MINIMUM REQUIRED TO BID AND CONSTRUCT THE PROJECT

UNCLASSIFIED//FOR OFFICIAL USE ONLY - PROPERTY OF THE US GOVERNMENT, LIMITED REPRODUCTION AND DISSEMINATION TO MINIMUM REQUIRED TO BID AND CONSTRUCT THE PROJECT

H

P

N O

CERTIFIED FINAL

07/17/2020

FI

R

E A

LA

R

M D

E

TA

IL

S

FA501

J.

L

E E

K . F

IE

LD

S

M . R

IC

E

W

2Q R

B0

1P la ns

-0

PUMP SCHEDULE

HWP-1 HHW 70 45 62 1-1/4 7.0 1800 2 460 / 3

NOTES:

1. INSTALL PUMP PER MANUFACTURER'S RECOMMENDATIONS.

2. PUMP SHALL BE NON OVERLOADING UNDER THE ENTIRE RANGE OF PERFORMANCE CURVE.

3. PUMP MOTOR SHALL BE INVERTER DUTY RATED.

4. VFD SHALL BE FIELD PROVIDED.

5. PROVIDE WITH SUCTION DIFFUSER.

6. PROVIDE WITH NON-FUSED DISCONNECT SWITCH.

UNIT DATA

TAG FUNCTION TYPE GPM

FT.

HD.

EFF. %

SUCTION

SIZE (IN)

MOTOR DATA

REMARKSDISCHARGE

SIZE (IN)

IMPELLER

DIAMETER (IN)

RPM HP V / PH

HWP-2

CHWP-1 CHILLED

WATER

CHWP-2 CHILLED

WATER

TAG SERVICE TYPE

ELECTRIC

B-1 HHW

GAS-FIRED

CONDENSING

1250 4" 120/1

AMPS

REMARKS

ALL

CAPACITY (MBH)

INPUT OUTPUT

EQUIPMENT CONNECTIONS

HWS GAS (IN) VENT (IN) AIR (IN)

1-1/2" 8"Ø 6"Ø

NOTES:

1. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.

2. PROVIDE BOILER WITH MANUFACTURER'S LOCAL CONTROLS. BOILER CONTROLS SHALL BE BACNET COMPATIBLE. CONTRACTOR SHALL INTERFACE CONTROLS WITH FACILITY BAS.

3. PROVIDE WITH CONDENSATE NEUTRALIZATION KIT.

4. HEATING OUTPUT (MBH) AND GPM BASED ON DESIGN ENTERING WATER TEMPERATURE AND TEMPERATURE RISE.

5. ELECTRICAL CONTRACTOR TO PROVIDE DISCONNECT SWITCH.

6. MANUFACTURER TO PROVIDE STAINLESS STEEL VENT TERMINATION KIT FOR FLUE AND INTAKE.

7. PROVIDE WITH MOTORIZED ISOLATION VALVES.

BOILER SCHEDULE

B-2 HHW

GAS-FIRED

CONDENSING

V / PH

GPM

EWT

LWT

HEAD LOSS

(" W.G.)

12.3

HWR

4"

FAN SCHEDULE

RF-03

NOTES:

1. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.

2. PROVIDE WITH INVERTER DUTY RATED MOTOR.

3. PROVIDE WITH HANGING SPRING ISOLATOR.

4. PROVIDE WITH MOTOR COVER.

5. PROVIDE WITH MOUNTING RAILS.

6. PROVIDE WITH EASY ACCESS DOOR.

7. VFD SHALL BE FIELD PROVIDED.

8. PROVIDE WITH ROOF CURB.

UNIT DATA

TAG SERVICE SIZE (IN) FUNCTION FAN

TYPE

WHEEL

TYPE

TIP SPEED

FPM

E.S.P.

IN W.G.

CFM TYPE OF

DRIVE

HP VOLTS PHASE

MOTOR DATA

REMARKSTYPE OF

CONTROL

INLET

SOUND

DB

1.6

FLA

END

SUCTION

110 69 2-1/2 2

END

SUCTION

END

SUCTION

120/1 ALL120 140

RF-06 0.75 5,700 942 3 694.8

RF-07 INLINE 0.5 6,150 614 2 623.4

RF-08 0.75 6,400 557 1.5 613

RF-09 1.5 2,500 1,530 1.5 673

RF-10 0.8 1,650 1,082 0.5 591.1

AHU-06

AHU-07

AHU-08

AHU-09

AHU-10

RETURN

RETURN

RETURN

RETURN

RETURN

AHU-03

BI = BACKWARD INCLINED

RPM

INLINE 3

441 COMPLEX ALL

MINIMUM DESIGN

CAPACITY (TONS)

NO OF

COMP.

NO. OF

PASSES

MCA (A) MOP (A)E.W.T.

(°F)

L.W.T.

(°F)

W.P.D.

FT. HD.

NOTES:

1. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.

2. SHIP CHILLER WITH N2 HOLDING CHARGE.

3. PROVIDE ELECTROMETRIC ISOLATION PADS.

4. PROVIDE UNIT WITH CONTACTS FOR REMOTE ENABLE/DISABLE.

5. PROVIDE NON-FUSED DISCONNECT SWITCH.

6. PROVIDE WITH CONTACTS FOR CONNECTS WITH ALARM CONTACTS.

7. PROVIDE FACTORY INSTALLED ELECTRONIC FLOW SWITCH.

8. PROVIDE WITH CONTACTS FOR REMOTE RESET OF CHILLED WATER SETPOINT.

9. CHILLER MUST BE MANUFACTURED BY TRANE PER JUSTIFICATION AND APPROVAL.

IPLV

(KW/TON)

DESIGN

GPM

441 COMPLEX

TAG

CH-1

CH-2

SERVICE MODEL

UNIT DATA

2 0.857 111 57 42 8.69 2

REFRIG

R-134A 20.6 25

OUTDOOR CONDENSER DATA

MCA

131 175

MOCP VOLTS

UNIT ELECTRICAL DATA

460 3

PHASE REMARKS

INDOOR EVAPORATOR DATA

COMPRESSOR CHILLER SCHEDULE

TAG

ACC-1

V / PH

460/3

1312.3

NO. OF FANS

TAG

UNIT DATA

EXPANSION TANK SCHEDULE

FUNCTION

REMARKS

TYPE

TANK VOLUME

ET-1 HHW

(GALLONS)

ACCEPTANCE VOLUME

(GALLONS)

AIR CHARGE PRESSURE

(PSIG)

BLADDER 26 11 23

TAG

UNIT DATA

AIR SEPARATOR SCHEDULE

FUNCTION

REMARKS

TYPE

AS-1 HHW COALESCING 140 1.5 3

GPM MAX PD. FT WG. SIZE (IN)

AS-2 CWS/CWR 220 1.5 4

ET-2 CHWS/CHWR BLADDER 10 10 23

UNIT HEATER SCHEDULE

UH-1

UH-2

PENTHOUSE 3-100 PROP. 60.2

30.9

1,340

140 120 6.0

3.1

1.0

0.4

1/8

1/12

ALL

NOTES:

1. PROVIDE FAN GUARD.

2. PROVIDE REMOTE THERMOSTAT.

3. PROVIDE MANUAL TOGGLE SWITCH STARTER.

UNIT DATA

TAG SERVICE TYPE MBH

AIR DATA

CFM GPM

MOTOR DATA

REMARKSE.W.T.

(°F) L.W.T.

(°F)

W.P.D.

FT. HD.

WATER DATA

HP VOLTS PHASE

PENTHOUSE 3-101 PROP. 140 120 ALL

1250 4" 1-1/2" 8"Ø 6"Ø1150 125 4"

RF-02 RETURN 1.0 3,600 797 BELT 0.75 460 3 57 ALLBI 4,461AHU-02 INLINE VFD

4,450

4,904

6,045

4,744

6,711

INLINE

INLINE

INLINE

VFD

VFD

VFD

VFD

VFD

BI

BI

BI

BI

BELT

BELT

BELT

BELT

BELTBI

ELECTRIC WALL HEATER SCHEDULE

UNIT DATA

TAG LOCATION TYPE

CAPACITY

VOLT/PH AMPS MEANS OF

CONTROL

REMARKS

ECH-1 VERTICAL SURFACE

MOUNTED 5 480/3 7STAIR D 1S3 ALL

NOTES:

1. OFF-WHITE BAKED ENAMEL FINISH.

2. PROVIDE WITH INTEGRAL DISCONNECT.

3. PROVIDE WITH INTEGRAL THERMOSTAT.

KW

INTEGRAL

STAT

ECH-2 VERTICAL SURFACE

MOUNTED 5 480/3 7STAIR B 1S1 INTEGRAL

STAT

ECH-3 VERTICAL SURFACE

MOUNTED 5 480/3 7STAIR C 1S2 INTEGRAL

STAT

ECH-4 VERTICAL SURFACE

MOUNTED 5 480/3 7STAIR A 0S4 INTEGRAL

STAT

RF-05 0.5 7,250 552 BELT 3 3 674.8AHU-05 5,201RETURN BIINLINE 460VFD

ALL

ALL

ALL

ALL

ALL

ALL

ALL

ALL

ALL

ALL

UH-3 45.6 1120 4.5 0.6 1/12 115 1HYDRONIC MECH

ROOM PROP. 140 120 ALL

EF-1 0.5 1,600 1,538 0.5 66-RMS EXHAUST 15,238DOWNBLAST 115START/STOP DIRECTBI 1,8

ELECTRIC UNIT HEATER SCHEDULE

UNIT DATA

TAG LOCATION TYPE CFM

CAPACITY

VOLT/PH AMPS MEANS OF

CONTROL

REMARKS

EUH-1 350 3 208/1 14.5MECH 1-901 ALL

NOTES:

1. PROVIDE WITH INTEGRAL DISCONNECT.

2. PROVIDE WITH INTEGRAL THERMOSTAT.

3. PROVIDE WITH SUPPORT BRACKET. REFER TO MECHANICAL DETAILS FOR ADDITIONAL SUPPORT INFORMATION.

KW

INTEGRAL

STAT

ALL69 2 0.857 111 57 42 8.69 2 R-134A 20.6 25131 175 460 3 ACC-1 460/36

0.75 7,150 552 BELT 3 3 674.85,201RETURN BIINLINE 460VFD ALL

HHW 70 62 1-1/4 7.0 2

END

SUCTION ALL

8.5 1800 5 ALL

CHWP-3 CHILLED

WATER

END

SUCTION 110

HWP-3 HHW 70 62 1-1/4 7.0 2

END

SUCTION ALL

460 / 3

460 / 3

460 / 3

1-1/2

1-1/2

1-1/2

69 2-1/2 2 8.5 1800 5 ALL460 / 3

69 2-1/2 2 8.5 1800 5 ALL460 / 3

HORIZONTAL

HUNG

COALESCING

BASIS OF DESIGN: TRANE

RTUD 120

RTUD 120

S O

LI

C

IT

A

TI

O

N N

O

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

TI

O

N

1 3 5

C

7 9

A

M A

R K

IS

S

U E

D A

TE

S

IZ

E

S U

B M

IT

TE

D B

Y

C O

N

TR

A C

T N

O

SHEET ID

D A

TE

US Army Corps of Engineers

U .S

. A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

LO

U

IS

V

IL

LE

, K Y

LO

U

IS

V

IL

LE

D

IS

TR

IC

T

A M

E N

D M

E N

T

/1 9/

W R

IG

H

T P

A

TT

E R

S O

N A

FB

R

E P

A

IR

F S

D -1

IN

TE

R

IO

R , E

X

TE

R

IO

R , A

N D

H V

A C

FA

C

IL

IT

Y

(Z H

TV

B

D

E

F

G

2 4 6 8 10

JU

LY

W

2Q R

B

FA

-1

3- D

A D

V A

N C

E D

E N

G

IN

E E

R

IN

G C

O N

S U

LT

A

N

TS

M ec ha ni ca l |

E le ct ric al

Pl um bi ng

Fi re P ro te ct io n

D ub lin

R oa d Te l:

(6

) 4

-4

C ol um bu s, O hi o

Fa x:

(6

) 4

-4

UNCLASSIFIED//FOR OFFICIAL USE ONLY - PROPERTY OF THE US GOVERNMENT, LIMITED REPRODUCTION AND DISSEMINATION TO MINIMUM REQUIRED TO BID AND CONSTRUCT THE PROJECT

UNCLASSIFIED//FOR OFFICIAL USE ONLY - PROPERTY OF THE US GOVERNMENT, LIMITED REPRODUCTION AND DISSEMINATION TO MINIMUM REQUIRED TO BID AND CONSTRUCT THE PROJECT

H

P

N O

CERTIFIED FINAL

07/17/2020

M E

C H

A N

IC

A

L S

C H

E D

U

LE

S

M-603

G .L

E

IT

C H

K .F

IE

LD

S

E .L

A R

U E

W

2Q R

B0

1P la ns

-0

FA001
FA111
FA501
M-603