Spec_W912PL-12-R-0003V3.pdf
PDF 5 MB Posted
- Solicitation number
- W912PL-12-R-0003
About this file
VOLUME 3 of 3 - TECHNICAL SPECIFICATIONS FOR ADJACENT FY12 F-35 ADAL AIRCRAFT MAINTENANCE UNIT
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Am5_W912PL-12-R-0003.pdf | ||
| Am4_W912PL-12-R-0003.pdf | ||
| Squad Ops AMU Attendance List.pdf | ||
| Am3_W912PL-12-R-0003.pdf | ||
| Am2_W912PL-12-R-0003.pdf | ||
| Am1_W912PL-12-R-0003.pdf | ||
| SPL012-11.pdf | ||
| SPL012-12.pdf | ||
| SPL012-10REVISED.pdf | ||
| SPL012-9.pdf | ||
| SPL12-10.pdf | ||
| SPL012-12.pdf | ||
| SPL012-11.pdf | ||
| SPL012-9.pdf | ||
| Spec_W912PL-12-R-0003V2.pdf | ||
| Drawings_W912PL12R0003_SQ_OPS_VOL_2 .pdf | ||
| Spec_W912PL-12-R-0003V1.pdf | ||
| Drawings_W912PL12R0003_ADAL AMU.pdf | ||
| Drawings_W912PL12R0003_SQ_OPS_VOL_1.pdf |
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
For the best experience, open this PDF portfolio in Acrobat 9 or Adobe Reader 9, or later.
Get Adobe Reader Now!
http://www.adobe.com/go/reader
SECTION 09 06 90
COLOR SCHEDULE
PART 1 GENERAL
1.1 SYSTEM DESCRIPTION
This section covers only the color of the exterior and interior materials and products that are exposed to view in the finished construction. The word "color", as used herein, includes surface color and pattern.
Requirements for quality and method of installation are covered in other appropriate sections of the specifications. Specific locations where the various materials are required are shown on the drawings. Items not designated for color in this section may be specified in other sections.
When color is not designated for items, propose a color for approval.
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-04 Samples
Color Schedule; G
PART 2 PRODUCTS
2.1 REFERENCE TO MANUFACTURER'S COLOR
Where color is shown as being specific to one manufacturer, an equivalent color by another manufacturer may be submitted for approval. Manufacturers and materials specified are not intended to limit the selection of equal colors from other manufacturers.
2.2 COLOR SCHEDULE
The color schedule lists the colors, patterns and textures required for exterior and interior finishes, including both factory applied and field applied colors. Submit 4 sets of color boards, 120 days after the Contractor is given Notice to proceed, complying with the following requirements:
a. Color boards shall reflect all actual finish textures, patterns, and colors required for this contract.
b. Materials shall be labeled with the finish type, manufacturer's name, pattern, and color reference.
c. Samples shall be on size 8-1/2- by 11-inch boards with a maximum spread of size 11 by 17 inches for foldouts.
d. Samples for this color board are required in addition to samples
09 06 90-1 requested in other specification sections.
e. Color boards shall be submitted to the following addresses: Base Architect, COE Representative and A/E.
2.2.1 Exterior Walls
Exterior wall colors shall apply to exterior wall surfaces including recesses at entrances and projecting vestibules. Conduit shall be painted to closely match the adjacent surface color. Wall color shall be provided to match the colors listed below.
2.2.1.1 Concrete Masonry Units
CODE SPEC MFG PROD. # STYLE COLOR NAME
CMU-1 04 20 00 Trenwyth Ind
Trendstone Split Face Durango
CMU-2 04 20 00 Trenwyth Ind
Trendstone Plus
Filled/ Polished
Durango
2.2.1.2 Paint
Match adjacent materials.
2.2.1.3 Metal Wall Panels, Hardware, and Associated Trim
MPS-1 07 42 63 Dri-Design - - Match Benjamin Moore
Barrista AF-175
MPS-2 07 42 63 Centria - - Cambridge White #995
2.2.1.4 Precast Concrete
PC-1 03 33 00 Continental Cast Stone
Precast Concrete
- #1104
2.2.1.5 Glass and Glazing
GLZ 08 81 00 PPG Idea S
Solarban 70XL Solar Gray
2.2.1.6 Insulated Translucent Wall Panel (TWP)
TWP-1 08 45 23.00 48 Kalwall - - White
09 06 90-2
2.2.2 Exterior Trim
Exterior trim shall be provided to match the colors listed below.
2.2.2.1 Steel Doors and Door Frames
2.2.2.2 Steel Windows (Mullion, Muntin, Sash, Trim, and Sill)
MFG PROD. # COLOR NAME
PPG Idea Scapes UC106704XL Platinum
2.2.2.3 Aluminum Doors and Door Frames
Kawneer - Clear Anodized Aluminum
2.2.2.4 Aluminum Windows (Mullion, Muntin, Sash, Trim, and Sill)
Kawneer - Clear Anodized Aluminum
2.2.2.5 Fascia
Match MPS-2 (reference Specification 07 42 63).
2.2.2.6 Soffits and Ceilings
2.2.2.7 Overhangs
2.2.2.8 Downspouts, Gutters, Louvers, and Flashings
Match MPS-1 (reference Specification 07 60 00).
2.2.2.9 Coping
2.2.2.10 Precast Concrete Caps and Sills
PC-1 03 33 00 Continental Cast Stone
Precast Concrete
- #1104
2.2.2.11 Caulking and Sealants
Match adjacent materials (reference Specification 07 92 00).
09 06 90-3
2.2.2.12 Control Joints
2.2.2.13 Signage
Match existing base exterior signage (reference Specification 10 14 01).
2.2.3 Exterior Roof
Roof color shall apply to exterior roof surfaces including sheet metal flashings and copings, mechanical units, roof trim, pipes, conduits, electrical appurtenances, and similar items. Provide roof color to match the colors listed below.
2.2.3.1 Metal
MPS-2 07 61 14.00 20 Centria - - Cambridge White #995
2.2.3.2 Penetrations
Shall match roof in color.
2.2.4 Interior Floor Finishes
Provide flooring materials to match the colors listed below.
2.2.4.1 Carpet Tile
CODE SPEC MFG PROD. STYLE COLOR NAME
CPT-1 09 68 00 Shaw
Contract Group
59598 Overlay Tile 18 by 36 Fluid 95504
CPT-2 09 68 00 Shaw Contract Group
59550 Site Lines 24 inches by 24 inches
Unmarked Trail 38760
2.2.4.2 Walk Off Mat
Mat 12 48 13.13 C/S Group Pedigrid Carpet Tread Insert
#7325 Wrought Iron, Aluminum Trim
2.2.4.3 Terrazzo, Poured Epoxy (TT)
TT-1 09 66 23 Terroxy Resin
20% Glass/80% Marble TM-HS-04
09 06 90-4
2.2.4.4 Resilient Floor Tile (RF)
RF-1 09 65 00 Johnsonite RT-SQ Roundel-Raised Square
#48 Grey
2.2.4.5 Concrete Sealed
Reference Specification 09 90 00.
2.2.5 Interior Base Finishes
Provide base materials to match the colors listed below.
2.2.5.1 Resilient Base and Moldings
NOTE: Rubber Base is intended to match wall paint finish.
RB-1 09 65 00 Johnsonite 21 4 inch toed 21 Platinum
RB-2 09 65 00 Johnsonite 285 4 inch toed 285 Morning Light
RB-3 09 65 00 Johnsonite 151 4 inch toed 151 Iguana
RB-4 09 65 00 Johnsonite 71 4 inch toed 71 Storm Cloud
2.2.6 Interior Wall Finishes
Interior wall color shall apply to the entire wall surface, including reveals, vertical furred spaces, grilles, diffusers, electrical and access panels, and piping and conduit adjacent to wall surfaces unless otherwise specified. Items not specified in other paragraphs shall be painted to match adjacent wall surface. Provide wall materials to match the colors listed below.
2.2.6.1 Paint
EP/P-1 09 90 00 Sherwin Williams
SW7135 Egg Shell Twinkle
EP/P-2 09 90 00 Sherwin
SW6126 Egg Shell Navajo White
EP/P-3 09 90 00 Sherwin
SW6197 Egg Shell Aloof Gray
EP/P-4 09 90 00 Sherwin
SW6128 Egg Shell Blonde
P-5 09 90 00 Sherwin
SW7733 Egg Shell Bamboo Shoot
09 06 90-5
P-6 09 90 00 Sherwin
SW 6250 Egg Shell Granite Peak
P-7 09 90 00 PPG Idea Scapes
Notes:
1. EP indicates epoxy paint for water areas; P indicates latex paint, except P-7, which is a metallic paint finish for all interior door frames.
2. Paints located in high traffic areas shall be high performance architecture finishes such as Scrub Tough paint from Scuff Masters or approved equal.
2.2.6.2 Ceramic Tile
CWT-1 09 30 00 - 709 Matte 4-1/4 inch tile
Architectural Gray
PT-1 09 30 00 Dal Tile PN9B Plaza Nova 12- by 24-inch
Grey Fog
PT-2 09 30 00 Dal Tile PN94 Plaza Nova 4- by
White Magic
PT-3 09 30 00 Dal Tile PN99 Plaza Nova 4- by
Black Shadow
Note: Install Accent Band of either PT-2 or PT-3 (See Room Finish Schedule). Install pattern shall be brick method. Field Tile (PT-1) shall be aligned.
2.2.6.3 Ceramic Tile Grout (GRT-2)
GRT-2 09 30 00 Laticrete #7B - Sterling Silver
2.2.6.4 Board Formed Concrete (BFC-1)
Reference Specification 03 33 00.
2.2.7 Interior Ceiling Finishes
Ceiling colors shall apply to ceiling surfaces including soffits, furred down areas, grilles, diffusers, registers, and access panels. Ceiling color shall also apply to joist, underside of roof deck, and conduit and piping where joists and deck are exposed and required to be painted.
Provide ceiling materials to match the colors listed below.
09 06 90-6
2.2.7.1 Acoustical Tile and Grid
ACT-1 09 51 00 Armstrong Ceilings
Dune #1775 Beveled Tegular Ceiling Tile 24 by 24 inches
White
ACT-2 09 51 00 Armstrong
#607 Cerma Guard w/ Humiguard Max ceiling tile 24 inches used with SG-2 suspension system
SG-1 09 51 00 Armstrong
#7501 9/16 inch suprafine
SG-2 09 51 00 Armstrong
#7301 15/16 inch prelude White
2.2.7.2 Paint
P-1 09 90 00 Sherwin
SW 7135 Egg Shell Twinkle
Note: All gypsum board ceilings shall be painted P-1 unless otherwise noted on Room Finish Plan.
2.2.7.3 Structural Framing
Paint exposed framing as indicated on architectural plans.
2.2.8 Interior Trim
Provide interior trim to match the colors listed below.
2.2.8.1 Steel Doors
Paint to match adjacent material.
2.2.8.2 Steel Door Frames
Paint to match paint finish P-7, reference paragraph 2.2.6.1 Paint.
2.2.8.3 Aluminum Doors and Door Frames
Clear, anodized aluminum.
2.2.8.4 Aluminum Windows
Clear, anodized aluminum.
09 06 90-7
2.2.8.5 Wood Doors
Stain to match Haworth Retro Walnut #VR-W31, walnut.
2.2.8.6 Wood Stain
Stain to match architectural sample.
WD-1 08 14 00 Haworth VR-W31 Walnut Retro Walnut
2.2.8.7 Window Sills
SS-1 Corian; Color: Dove.
2.2.8.8 Fire Extinguisher Cabinets
Stainless steel, brushed.
2.2.8.9 Exposed Ductwork
P-1 09 90 00 Sherwin
SW7135 Egg Shell Twinkle
2.2.8.10 Benches
Stain to match WD-1.
2.2.9 Interior Window Treatment
Provide window treatments to match the colors listed below.
2.2.9.1 Window Shades
WS-1 12 24 13 Mechoshade Thermoveil 1300 Series;
5 percent open
#1301 White
WS-2 12 24 13 Mechoshade Thermoveil Blackout
1300 Series 0100 Series
#1301 White #0102 Alabaster
2.2.10 Interior Miscellaneous
Provide miscellaneous items to match the colors listed below.
2.2.10.1 Toilet Partitions and Urinal Screens (TP-1)
TP-1 10 21 13 Accurate #3 Stainless Steel Diamond Pattern
Brushed Stainless Steel
09 06 90-8
2.2.10.2 Plastic Laminate
HPL-2 06 41 16.00 01 Wilsonart 7943-07 High Pressure Laminate
Columbian Walnut
2.2.10.3 Solid Surfacing Material
SS-1 06 61 16 Corian 7925-38 - Dove
SS-2 06 61 16 Corian 7923-07 Terra Collection Whisper
2.2.10.4 Casework
Reference architectural drawings for designated casework finishes.
2.2.10.5 Signage Message Color
Black (excluding handicapped signage, which shall be white for contrast).
2.2.10.6 Signage Background Color
a. Background Plate: Same finish as HPL-1 found in paragraph 2.2.10.2.
b. Front Plate Background: LM101 Satin Silver.
2.2.10.7 Interior Letter Forms
MFG PROD. # STYLE COLOR NAME
Take Form Stud Mounted
Letters Metabold 1/4 inch thick aluminum
Black
2.2.10.8 Acoustical Wall Panels:
AWP-1 09 83 13 DeCoustics 1-inch AP Panel
Square edge system with no
See below for fabric finish on
AWP-1
- 09 83 13 Maharam 90 1881 Count Shade #005
2.2.10.9 Wall Switch Handles and Standard Receptacle Bodies
White.
2.2.10.10 Electrical Device Cover Plates
Stainless.
09 06 90-9
2.2.10.11 Electrical Panels
Match adjacent surface.
2.3 PLACEMENT SCHEDULE
Placement of color shall be in accordance with the room finish schedule, elevations and wall finish placement plans.
PART 3 EXECUTION (Not Applicable)
-- End of Section --
09 06 90-10
COLOR SCHEDULE
PART 1 GENERAL
1.1 SYSTEM DESCRIPTION
1.2 SUBMITTALS
PART 2 PRODUCTS
2.1 REFERENCE TO MANUFACTURER'S COLOR
2.2 COLOR SCHEDULE
2.2.1 Exterior Walls
2.2.1.1 Concrete Masonry Units
2.2.1.2 Paint
2.2.1.3 Metal Wall Panels, Hardware, and Associated Trim
2.2.1.4 Precast Concrete
2.2.1.5 Glass and Glazing
2.2.1.6 Insulated Translucent Wall Panel TWP
2.2.2 Exterior Trim
2.2.2.1 Steel Doors and Door Frames
2.2.2.2 Steel Windows Mullion, Muntin, Sash, Trim, and Sill
2.2.2.3 Aluminum Doors and Door Frames
2.2.2.4 Aluminum Windows Mullion, Muntin, Sash, Trim, and Sill
2.2.2.5 Fascia
2.2.2.6 Soffits and Ceilings
2.2.2.7 Overhangs
2.2.2.8 Downspouts, Gutters, Louvers, and Flashings
2.2.2.9 Coping
2.2.2.10 Precast Concrete Caps and Sills
2.2.2.11 Caulking and Sealants
2.2.2.12 Control Joints
2.2.2.13 Signage
2.2.3 Exterior Roof
2.2.3.1 Metal
2.2.3.2 Penetrations
2.2.4 Interior Floor Finishes
2.2.4.1 Carpet Tile
2.2.4.2 Walk Off Mat
2.2.4.3 Terrazzo, Poured Epoxy TT
2.2.4.4 Resilient Floor Tile RF
2.2.4.5 Concrete Sealed
2.2.5 Interior Base Finishes
2.2.5.1 Resilient Base and Moldings
2.2.6 Interior Wall Finishes
2.2.6.1 Paint
2.2.6.2 Ceramic Tile
2.2.6.3 Ceramic Tile Grout GRT-2
2.2.6.4 Board Formed Concrete BFC-1
2.2.7 Interior Ceiling Finishes
2.2.7.1 Acoustical Tile and Grid
2.2.7.2 Paint
2.2.7.3 Structural Framing
2.2.8 Interior Trim
2.2.8.1 Steel Doors
2.2.8.2 Steel Door Frames
2.2.8.3 Aluminum Doors and Door Frames
2.2.8.4 Aluminum Windows
2.2.8.5 Wood Doors
2.2.8.6 Wood Stain
2.2.8.7 Window Sills
2.2.8.8 Fire Extinguisher Cabinets
2.2.8.9 Exposed Ductwork
2.2.8.10 Benches
2.2.9 Interior Window Treatment
2.2.9.1 Window Shades
2.2.10 Interior Miscellaneous
2.2.10.1 Toilet Partitions and Urinal Screens TP-1
2.2.10.2 Plastic Laminate
2.2.10.3 Solid Surfacing Material
2.2.10.4 Casework
2.2.10.5 Signage Message Color
2.2.10.6 Signage Background Color
2.2.10.7 Interior Letter Forms
2.2.10.8 Acoustical Wall Panels:
2.2.10.9 Wall Switch Handles and Standard Receptacle Bodies
2.2.10.10 Electrical Device Cover Plates
2.2.10.11 Electrical Panels
2.3 PLACEMENT SCHEDULE
PART 3 EXECUTION Not Applicable
SECTION 09 22 00
SUPPORTS FOR PLASTER AND GYPSUM BOARD
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM A 463/A 463M (2010) Standard Specification for Steel Sheet, Aluminum-Coated, by the Hot-Dip Process
ASTM A 653/A 653M (2011) Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM C 645 (2009a) Nonstructural Steel Framing Members
ASTM C 754 (2009a) Installation of Steel Framing Members to Receive Screw-Attached Gypsum Panel Products
ASTM C 841 (2003; R 2008e1) Installation of Interior Lathing and Furring
ASTM C 847 (2010) Standard Specification for Metal Lath
NATIONAL ASSOCIATION OF ARCHITECTURAL METAL MANUFACTURERS (NAAMM)
NAAMM ML/SFA 920 (2009) Metal Lathing and Furring
UNDERWRITERS LABORATORIES (UL)
UL Fire Resistance (2011) Fire Resistance Directory
U.S. GREEN BUILDING COUNCIL (USGBC)
LEED (2009) Leadership in Energy and Environmental Design(tm) Green Building Rating System for New Construction
(LEED-NC)
LEED Reference Guide (2009) LEED-NC Reference Guide for New Construction submittals not having a "G" designation are for Contractor Quality Control
09 22 00-1 approval. Submit the following in accordance with Section 01 33 00
SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Metal support systems; G
Submit for the erection of metal framing, furring, and ceiling suspension systems. Indicate materials, sizes, thicknesses, and fastenings.
SD-03 Product Data
Local/Regional Materials; (LEED)
Submit documentation in accordance with Leadership in Energy and
Environmental Design TM Green Building Rating System for New Construction, USGBC-LEED-NC 2009. Indicate distance between materials, or products extracted, harvested or recovered as well as the manufacturing facility and the project site. Indicate distance of raw material origin from the project site. Indicate relative dollar value of local/regional materials to total dollar value of products included on project.
Recycled Content; (LEED)
Environmental Design TM Green Building Rating System for New Construction, USGBC-LEED-NC 2009. Indicate percentage of post-consumer and pre-consumer recycled content per unit of product. Indicate relative dollar value of recycled content products to total dollar value of products included in project.
Adhesives; (LEED)
Paints & Coatings; (LEED)
Submit manufacturer's product data in accordance with Leadership in Energy and Environmental Design TM Green Building Rating System for New Construction, USGBC-LEED-NC 2009. Indicate VOC content.
Submit LEED documentation relative to low emitting materials credit in accordance with LEED Reference Guide. Include in LEED Documentation Notebook.
SD-11 Closeout Submittals
Provide LEED Documentation Notebook information. The Contractor shall prepare a comprehensive notebook documenting compliance for each LEED Credit as identified in Section 01 33 29 LEED (TM) Documentation.
1.3 DELIVERY, STORAGE, AND HANDLING
Deliver materials to the job site and store in ventilated dry locations.
Storage area shall permit easy access for inspection and handling. If materials are stored outdoors, stack materials off the ground, supported on a level platform, and fully protected from the weather. Handle materials carefully to prevent damage. Remove damaged items and provide new items.
09 22 00-2
1.4 SUSTAINABLE DESIGN REQUIREMENTS
1.4.1 LEED Rating
Section 01 33 29 LEED (TM) DOCUMENTATION identifies the LEED Credit Items that are designed for otherwise required for this Project. Refer to the LEED Reference Guide for additional information regarding LEED (TM) Documentation requirements.
1.4.2 Local/Regional Materials
Use materials or products extracted, harvested or recovered as well as manufactured within a 500 mile radius from the project site. See Section 01 33 29 LEED (TM) Documentation for cumulative total local material requirements.
2.1 MATERIALS - GENERAL
2.1.1 Recycled Content
See Section 01 33 29 LEED (TM) DOCUMENTATION for cumulative total recycled content requirements.
2.1.2 Adhesives
Adhesives must meet the requirements of USGBC-LEED-NC 2009 low emitting materials credit.
2.1.3 Sealants
Sealants must meet the requirements of USGBC-LEED-NC 2009 low emitting
2.1.4 Paints & Coatings
Paints & Coatings must meet the requirements of USGBC-LEED-NC 2009 low emitting materials credit.
2.2 MATERIALS
Provide steel materials for metal support systems with galvanized coating ASTM A 653/A 653M, G-60; aluminum coating ASTM A 463/A 463M, T1-25; or a 55-percent aluminum-zinc coating.
2.2.1 Materials for Attachment of Lath
2.2.1.1 Suspended and Furred Ceiling Systems and Wall Furring
ASTM C 841 and ASTM C 847.
2.2.1.2 Non-loadbearing Wall Framing
NAAMM ML/SFA 920.
09 22 00-3
2.2.2 Materials for Attachment of Gypsum Wallboard
2.2.2.1 Suspended and Furred Ceiling Systems
ASTM C 645.
2.2.2.2 Nonload-Bearing Wall Framing and Furring
ASTM C 645, but not thinner than 0.0179 inch thickness, with 0.0329 inch minimum thickness supporting wall hung items such as cabinetwork, equipment and fixtures.
2.2.2.3 Furring Structural Steel Columns
ASTM C 645. Steel (furring) clips and support angles listed in UL Fire Resistance may be provided in lieu of steel studs for erection of gypsum wallboard around structural steel columns.
2.2.2.4 Z-Furring Channels with Wall Insulation
Not lighter than 26 gage galvanized steel, Z-shaped, with 1-1/4 inch and 3/4 inch flanges and depth as required by the insulation thickness provided.
PART 3 EXECUTION
3.1 INSTALLATION
3.1.1 Systems for Attachment of Lath
3.1.1.1 Suspended and Furred Ceiling Systems and Wall Furring
ASTM C 841, except as indicated otherwise.
3.1.1.2 Non-loadbearing Wall Framing
NAAMM ML/SFA 920, except provide framing members 16 inches o.c. unless indicated otherwise.
3.1.2 Systems for Attachment of Gypsum Wallboard
3.1.2.1 Suspended and Furred Ceiling Systems
ASTM C 754, except provide framing members 16 inches o.c. unless indicated otherwise.
3.1.2.2 Non-loadbearing Wall Framing and Furring
ASTM C 754, except as indicated otherwise.
3.1.2.3 Furring Structural Steel Columns
Install studs or galvanized steel clips and support angles for erection of gypsum wallboard around structural steel columns in accordance with the UL Fire Resistance, design number(s) indicated on drawings.
3.1.2.4 Z-Furring Channels with Wall Insulation
Install Z-furring channels vertically spaced not more than 24 inches o.c.
Locate Z-furring channels at interior and exterior corners in accordance
09 22 00-4 with manufacturer's printed erection instructions. Fasten furring channels to masonry walls with powder-driven fasteners through narrow flange of channel. Space fasteners not more than 24 inches o.c.
3.2 ERECTION TOLERANCES
Provide framing members which will be covered by finish materials such as wallboard, plaster, or ceramic tile set in a mortar setting bed, within the following limits:
a. Layout of walls and partitions: 1/4 inch from intended position;
b. Plates and runners: 1/4 inch in 8 feet from a straight line;
c. Studs: 1/4 inch in 8 feet out of plumb, not cumulative; and
d. Face of framing members: 1/4 inch in 8 feet from a true plane.
Provide framing members which will be covered by ceramic tile set in dry-set mortar, latex-portland cement mortar, or organic adhesive within the following limits:
a. Layout of walls and partitions: 1/4 inch from intended position;
b. Plates and runners: 1/8 inch in 8 feet from a straight line;
c. Studs: 1/8 inch in 8 feet out of plumb, not cumulative; and
d. Face of framing members: 1/8 inch in 8 feet from a true plane.
09 22 00-5
SUPPORTS FOR PLASTER AND GYPSUM BOARD
PART 1 GENERAL
1.1 REFERENCES
1.2 SUBMITTALS
1.3 DELIVERY, STORAGE, AND HANDLING
1.4 SUSTAINABLE DESIGN REQUIREMENTS
1.4.1 LEED Rating
1.4.2 Local/Regional Materials
PART 2 PRODUCTS
2.1 MATERIALS - GENERAL
2.1.1 Recycled Content
2.1.2 Adhesives
2.1.3 Sealants
2.1.4 Paints & Coatings
2.2 MATERIALS
2.2.1 Materials for Attachment of Lath
2.2.1.1 Suspended and Furred Ceiling Systems and Wall Furring
2.2.1.2 Non-loadbearing Wall Framing
2.2.2 Materials for Attachment of Gypsum Wallboard
2.2.2.1 Suspended and Furred Ceiling Systems
2.2.2.2 Nonload-Bearing Wall Framing and Furring
2.2.2.3 Furring Structural Steel Columns
2.2.2.4 Z-Furring Channels with Wall Insulation
PART 3 EXECUTION
3.1 INSTALLATION
3.1.1 Systems for Attachment of Lath
3.1.1.1 Suspended and Furred Ceiling Systems and Wall Furring
3.1.1.2 Non-loadbearing Wall Framing
3.1.2 Systems for Attachment of Gypsum Wallboard
3.1.2.1 Suspended and Furred Ceiling Systems
3.1.2.2 Non-loadbearing Wall Framing and Furring
3.1.2.3 Furring Structural Steel Columns
3.1.2.4 Z-Furring Channels with Wall Insulation
3.2 ERECTION TOLERANCES
SECTION 09 29 00
GYPSUM BOARD
AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)
ANSI A108.11 (1992; Reaffirmed 2005) Specifications for Interior Installation of Cementitious Backer Units
ANSI A108/A118/A136.1 (2009) American National Standards for the Installation of Ceramic Tile
ASTM C 1002 (2007) Standard Specification for Steel Self-Piercing Tapping Screws for the Application of Gypsum Panel Products or Metal Plaster Bases to Wood Studs or Steel Studs
ASTM C 1177/C 1177M (2008) Standard Specification for Glass Mat Gypsum Substrate for Use as Sheathing
ASTM C 1178/C 1178M (2008) Standard Specification for Glass Mat Water-Resistant Gypsum Backing Panel
ASTM C 1396/C 1396M (2009a) Standard Specification for Gypsum Board
ASTM C 475/C 475M (2002; R 2007) Joint Compound and Joint Tape for Finishing Gypsum Board
ASTM C 840 (2008) Application and Finishing of Gypsum Board
ASTM C 954 (2010) Steel Drill Screws for the Application of Gypsum Panel Products or Metal Plaster Bases to Steel Studs from
0.033 in. (0.84 mm) to 0.112 in. (2.84 mm) in Thickness
ASTM C 1177/C 1177M (2008) Standard Specification for Glass Mat Gypsum Substrate for Use as Sheathing
ASTM D 1149 (2007) Standard Test Method for Rubber Deterioration - Surface Ozone Cracking in a Chamber
09 29 00-1
ASTM D 412 (2006ae2) Standard Test Methods for Vulcanized Rubber and Thermoplastic Elastomers - Tension
ASTM D 624 (2000; R 2007) Tear Strength of Conventional Vulcanized Rubber and Thermoplastic Elastomers
GYPSUM ASSOCIATION (GA)
GA 214 (2007) Recommended Levels of Gypsum Board Finish
GA 216 (2010) Application and Finishing of Gypsum Panel Products
GA 253 (2007) Application of Gypsum Sheathing
LEED Reference Guide (2009) LEED-NC Reference Guide for New Construction
Cementitious backer units
Glass Mat Water-Resistant Gypsum Tile Backing Board
Water-Resistant Gypsum Backing Board
Glass Mat Covered or Reinforced Gypsum Sheathing
Glass Mat Covered or Reinforced Gypsum Sheathing Sealant
Accessories
Submit for each type of gypsum board and for cementitious backer units.
Certification
Gypsum Board; (LEED)
09 29 00-2
Submit documentation indicating percentage of post-industrial and post-consumer recycled content per unit of product. Indicate relative dollar value of recycled content products to total dollar value of products included in project.
Joint Treatment Materials
Submit manufacturer's product data, indicating VOC content.
Environmental DesignTM Green Building Rating System for New Construction, USGBC-LEED-NC 2009. Indicate distance between materials, or products extracted, harvested or recovered as well as the manufacturing facility and the project site. Indicate distance of raw material origin from the project site. Indicate relative dollar value of local/regional materials to total dollar value of products included on project.
Recycled content; (LEED)
Environmental DesignTM Green Building Rating System for New Construction, USGBC-LEED-NC 2009. Indicate percentage of post-consumer and pre-consumer recycled content per unit of product. Indicate relative dollar value of recycled content products to total dollar value of products included in project.
Adhesives, Paints & Coatings; LEED
Submit manufacturer's product data in accordance with Leadership in Energy and Environmental DesignTM Green Building Rating System for New Construction, USGBC-LEED-NC 2009. Indicate VOC content.
Submit LEED documentation relative to low emitting materials
SD-07 Certificates
Asbestos Free Materials; G
Certify that gypsum board types, gypsum backing board types, cementitious backer units, and joint treating materials do not contain asbestos.
SD-08 Manufacturer's Instructions
Material Safety Data Sheets
SD-10 Operation and Maintenance Data
Manufacturer maintenance instructions
Waste Management
09 29 00-3
LEED (TM) Documentation; (LEED)
Provide LEED Documentation Notebook information. The Contractor shall prepare a comprehensive notebook documenting compliance for each LEED Credit as identified in Section 01 33 29 LEED (TM) Documentation.
1.3 DELIVERY, STORAGE, AND HANDLING
1.3.1 Delivery
Deliver materials in the original packages, containers, or bundles with each bearing the brand name, applicable standard designation, and name of manufacturer, or supplier.
1.3.2 Storage
Keep materials dry by storing inside a sheltered building. Where necessary to store gypsum board and cementitious backer units outside, store off the ground, properly supported on a level platform, and protected from direct exposure to rain, snow, sunlight, and other extreme weather conditions.
Provide adequate ventilation to prevent condensation. Store per manufacturer's recommendations for allowable temperature and humidity range. Gypsum wallboard shall not be stored with materials which have high emissions of volatile organic compounds (VOCs) or other contaminants. Do not store panels near materials that may offgas or emit harmful fumes, such as kerosene heaters, fresh paint, or adhesives.
1.3.3 Handling
Neatly stack gypsum board and cementitious backer units flat to prevent sagging or damage to the edges, ends, and surfaces.
1.4 ENVIRONMENTAL CONDITIONS
1.4.1 Temperature
Maintain a uniform temperature of not less than 50 degrees F in the structure for at least 48 hours prior to, during, and following the application of gypsum board, cementitious backer units, and joint treatment materials, or the bonding of adhesives.
1.4.2 Exposure to Weather
Protect gypsum board and cementitious backer unit products from direct exposure to rain, snow, sunlight, and other extreme weather conditions.
1.4.3 Temporary Ventilation
Provide temporary ventilation for work of this section.
1.5 SUSTAINABLE DESIGN REQUIREMENTS
1.5.1 LEED Rating
Section 01 33 29 LEED (TM) Documentation identifies the LEED Credit Items
09 29 00-4 that are designed for otherwise required for this Project. Refer to the LEED Reference Guide for additional information regarding LEED (TM) Documentation requirements.
1.5.2 Local/Regional Materials
Use materials or products extracted, harvested, or recovered, as well as manufactured, within a 500 mile radius from the project site. See Section 01 33 29 LEED(TM) DOCUMENTATION for cumulative total local material requirements.
1.6 QUALIFICATIONS
Furnish type of gypsum board work specialized by the installer with a minimum of 3 years of documented successful experience.
1.7 SCHEDULING
The gypsum wallboard shall be taped, spackled and primed before the installation of the highly-emitting materials.
2.1 MATERIALS -GENERAL
2.1.1 Recycled Content
See Section 01 33 29 LEED (TM) DOCUMENTATION for cumulative total recycled content requirements.
2.1.2 Adhesives, Paints & Coatings
Adhesives must meet the requirements of USGBC-LEED-NC 2009 low emitting
Paints & Coatings must meet the requirements of USGBC-LEED-NC 2009 low emitting materials credit.
2.2 MATERIALS
Conform to specifications, standards and requirements specified. Provide gypsum board types, gypsum backing board types, cementitious backing units, and joint treating materials manufactured from asbestos free materials only. Submit Material Safety Data Sheets and manufacturer maintenance instructions for gypsum materials including adhesives.
2.2.1 Gypsum Board
ASTM C 1396/C 1396M. Gypsum board shall contain a minimum of 5 percent post-consumer recycled content, or a minimum of 20 percent post-industrial recycled content. Paper facings shall contain 100 percent post-consumer recycled paper content. Gypsum cores shall contain a minimum of 95 percent post-industrial recycled gypsum content. See Section 01 33 29 LEED(tm) DOCUMENTATION for cumulative total recycled content requirements. Gypsum board may contain post-consumer or post-industrial recycled content.
2.2.1.1 Regular
48 inch wide in thickness indicated on Drawings, tapered and featured
09 29 00-5 edges.
2.2.1.2 Foil-Backed
48 inch wide, 5/8 inch thick, tapered and featured edges.
2.2.1.3 Type X (Special Fire-Resistant)
48 inch wide,thickness as indicated on Drawings, tapered and featured edges.
2.2.2 Gypsum Backing Board
ASTM C 1396/C 1396M, gypsum backing board shall be used as a base in a multilayer system.
2.2.2.1 Regular
48 inch wide,thickness as indicated on Drawings, square edges.
2.2.2.2 Foil-Backed
48 inch wide, 5/8 inch thick, square edges.
2.2.2.3 Type X (Special Fire-Resistant)
2.2.3 Regular Water-Resistant Gypsum Backing Board
ASTM C 1396/C 1396M
2.2.3.1 Regular
48 inch wide,thickness as indicated on Drawings, tapered edges.
2.2.3.2 Type X (Special Fire-Resistant)
48 inch wide,thickness as indicated on Drawings, tapered edges.
2.2.4 Glass Mat Water-Resistant Gypsum Tile Backing Board
ASTM C 1178/C 1178M
2.2.4.1 Regular
48 inch wide, thickness as indicated on Drawings, square edges.
2.2.4.2 Type X (Special Fire-Resistant)
2.2.5 Glass Mat Covered or Reinforced Gypsum Sheathing
Exceeds physical properties of ASTM C 1396/C 1396M and ASTM C 1177/C 1177M.
Provide 1/2 inch, gypsum sheathing. Provide gypsum board of with a noncombustible water-resistant core, with glass mat surfaces embedded to the gypsum core or reinforcing embedded throughout the gypsum core. Warrant gypsum sheathing board for at least twelve months against delamination due to direct weather exposure. Provide continuous, asphalt impregnated, 09 29 00-6 building felt to cover exterior face of sheathing. Seal all joints, seams, and penetrations with compatible sealant.
2.2.5.1 Glass Mat Covered or Reinforced Gypsum Sheathing Sealant
Provide sealant compatible with gypsum sheathing, rubber washers for masonry veneer anchors, and other associated cavity wall components such as anchors and through wall flashing. Provide sealants for gypsum sheathing board edge seams and veneer anchor penetrations recommended by the gypsum sheathing manufacturer and have the following performance requirements:
a. ASTM D 412: Tensile Strength, 80 psi
b. ASTM D 412: Ultimate Tensile Strength (maximum elongation), 170 psi
c. ASTM D 624: Tear Strength, dieB, 27 ppi
d. ASTM D 1149: Joint Movement Capability after 14 Days cure, plus or minus 50 percent.
2.2.6 Cementitious Backer Units
ANSI A108/A118/A136.1.
2.2.7 Joint Treatment Materials
ASTM C 475/C 475M. Use all purpose joint and texturing compound containing inert fillers and natural binders, including lime compound. Pre-mixed compounds shall be free of antifreeze, vinyl adhesives, preservatives, biocides and other slow releasing compounds.
2.2.7.1 Embedding Compound
Specifically formulated and manufactured for use in embedding tape at gypsum board joints and compatible with tape, substrate and fasteners.
2.2.7.2 Finishing or Topping Compound
Specifically formulated and manufactured for use as a finishing compound.
2.2.7.3 All-Purpose Compound
Specifically formulated and manufactured to serve as both a taping and a finishing compound and compatible with tape, substrate and fasteners.
2.2.7.4 Setting or Hardening Type Compound
Specifically formulated and manufactured for use with fiber glass mesh tape.
2.2.7.5 Joint Tape
Use cross-laminated, tapered edge, reinforced paper, or fiber glass mesh tape recommended by the manufacturer.
2.2.8 Fasteners
2.2.8.1 Screws
ASTM C 1002, Type "G", Type "S" or Type "W" steel drill screws for fastening gypsum board to gypsum board, wood framing members and steel framing members less than 0.033 inch thick. ASTM C 954 steel drill screws for fastening gypsum board to steel framing members 0.033 to 0.112 inch
09 29 00-7 thick. Provide cementitious backer unit screws with a polymer coating.
2.2.9 Shaftwall Liner Panel
ASTM C 1396/C 1396M. Conform to the UL Fire Resistance for the Design Numbers(s) indicated for shaftwall liner panels. Manufacture liner panel for cavity shaftwall system, with water-resistant paper faces, bevel edges, single lengths to fit required conditions, 1" thick, by 24" wide.
2.2.10 Accessories
ASTM C 1396/C 1396M. Fabricate from corrosion protected steel or plastic designed for intended use. Accessories manufactured with paper flanges are not acceptable. Flanges shall be free of dirt, grease, and other materials that may adversely affect bond of joint treatment. Provide prefinished or job decorated materials.
a. Exposed decorative reveal moldings shall be constructed of aluminum extruded alloy 6063 T5 with chemical conversion coating. Profiles and locations of each shall be as indicated on the drawings and finishes are listed in Specification 09 06 90 COLOR SCHEDULE. Basis of design products listed below are from Fry reglet Architectural Metals Co.
Refer to specification Section 09 06 90 COLOR SCHEDULE for color and finish information.
(1) MR-1 Reveal Molding 1/4 inch deep x 1/4 inch high non-vented product #DRM-25-25.
(2) MR-2 Reveal Molding 5/8 inch deep x 1/2 inch high non-vented product #DRM-625-50.
(3) MR3 Reveal Molding 5/8 inch deep x 12 inch high non-vented product
#DRM-625-100.
2.2.11 Water
Provide clean, fresh, and potable water.
3.1 EXAMINATION
3.1.1 Framing and Furring
Verify that framing and furring are securely attached and of sizes and spacing to provide a suitable substrate to receive gypsum board and cementitious backer units. Verify that all blocking, headers and supports are in place to support plumbing fixtures and to receive soap dishes, grab bars, towel racks, and similar items. Do not proceed with work until framing and furring are acceptable for application of gypsum board and cementitious backer units.
3.1.2 Gypsum Board
Verify that surfaces of gypsum board to be bonded with an adhesive are free of dust, dirt, grease, and any other foreign matter. Do not proceed with work until surfaces are acceptable for application of gypsum board with adhesive.
09 29 00-8
3.2 APPLICATION OF GYPSUM BOARD
Apply gypsum board to framing and furring members in accordance with ASTM C 840 or GA 216 and the requirements specified. Apply gypsum board with separate panels in moderate contact; do not force in place. Stagger end joints of adjoining panels. Neatly fit abutting end and edge joints.
Use gypsum board of maximum practical length; select panel sizes to minimize waste. Cut out gypsum board to make neat, close, and tight joints around openings. In vertical application of gypsum board, provide panels in lengths required to reach full height of vertical surfaces in one continuous piece. Lay out panels to minimize waste; reuse cutoffs whenever feasible. Surfaces of gypsum board and substrate members may not be bonded together with an adhesive. Treat edges of cutouts for plumbing pipes, screwheads, and joints with water-resistant compound as recommended by the gypsum board manufacturer. Minimize framing by floating corners with single studs and drywall clips. Install 5/8 inch gypsum or 1/2 inch ceiling board over framing at 24 inches on center. Provide type of gypsum board for use in each system specified herein as indicated.
3.2.1 Application of Gypsum Board to Steel Framing and Furring
Apply in accordance with ASTM C 840, System VIII or GA 216.
3.2.2 Gypsum Board for Wall Tile or Tile Base Applied with Adhesive
In dry areas (areas other than tubs, shower enclosures, saunas, steam rooms, gang shower rooms), apply glass mat water-resistant gypsum tile backing board in accordance with ASTM C 840, System X or GA 216.
3.2.3 Exterior Application
Apply exterior gypsum board (such as at soffits) in accordance with ASTM C 840, System XI or GA 216.
3.2.4 Glass Mat Covered or Fiber Reinforced Gypsum Sheathing
Apply gypsum sheathing in accordance to gypsum association publications GA 253. Follow gypsum sheathing manufacturer's requirements of design details for joints and fasteners and be properly installed to protect the substrate from moisture intrusion. Do not leave exposed surfaces of the gypsum sheathing beyond the manufacturer's recommendation without a weather barrier cladding. Provide vapor retarder with .01 perm rating over sheathing surface in shingle fashion with edges and ends lapped a minimum of 6 inch. Property flash the openings. Seal all joints, seams, and penetrations with a compatible silicone sealant.
3.2.5 Control Joints
Install expansion and contraction joints in ceilings and walls in accordance with ASTM C 840, System XIII or GA 216. Fill control joints between studs in fire-rated construction with firesafing insulation to match the fire-rating of construction.
3.2.6 Application of Foil-Backed Gypsum Board
Apply foil-backed gypsum board in accordance with ASTM C 840, System XIV or
GA 216.
09 29 00-9
3.3 APPLICATION OF CEMENTITIOUS BACKER UNITS
3.3.1 Application
In wet areas (tubs, shower enclosures, saunas, steam rooms, gang shower rooms), apply cementitious backer units in accordance with ANSI A108.11.
Place a 15 lb asphalt impregnated, continuous felt paper membrane behind cementitious backer units, between backer units and studs or base layer of gypsum board. Place membrane with a minimum 6 inch overlap of sheets laid shingle style.
3.3.2 Joint Treatment
ANSI A108.11.
3.4 FINISHING OF GYPSUM BOARD
Tape and finish gypsum board in accordance with ASTM C 840, GA 214 and GA 216. Finish plenum areas above ceilings to Level 1 in accordance with GA 214. Finish water resistant gypsum backing board, ASTM C 1396/C 1396M, to receive ceramic tile to Level 2 in accordance with GA 214. Finish walls and ceilings to receive a heavy-grade wall covering or heave textured finish before painting to Level 3 in accordance with GA 214. Finish walls and ceilings without critical lighting to receive egg shell paints, light textures, or wall coverings to Level 4 in accordance with GA 214. Finish gypsum board walls with the graphic murals on them to Level 5 in accordance with GA 214. Provide joint, fastener depression, and corner treatment.
Tool joints as smoothly as possible to minimize sanding and dust. Do not use fiber glass mesh tape with conventional drying type joint compounds;
use setting or hardening type compounds only. Provide treatment for water-resistant gypsum board as recommended by the gypsum board manufacturer. Protect workers, building occupants, and HVAC systems from gypsum dust.
3.4.1 Uniform Surface
Finish gypsum wall surface in accordance to GA 214 Level 4 unless noted otherwise.
3.5 SEALING
Seal openings around pipes, fixtures, and other items projecting through gypsum board and cementitious backer units as specified in Section 07 92 00 JOINT SEALANTS Apply material with exposed surface flush with gypsum board or cementitious backer units.
3.5.1 Sealing for Glass Mat or Reinforced Gypsum Board Sheathing
Apply silicone sealant in a 3/8 inch bead to all joints and trowel flat.
Apply enough of the same sealant to all fasteners penetrating through the glass mat gypsum board surface to completely cover the penetration when troweled flat. Do not place construction and materials behind sheathing until a visual inspection of sealed joints during daylight hours has been completed by Contracting Officer.
3.6 FIRE-RESISTANT ASSEMBLIES
Wherever fire-rated construction is indicated, provide materials and application methods, including types and spacing of fasteners, wall and
09 29 00-10 ceiling framing in accordance with the specifications contained in UL Fire Resistance for the Design Number(s) indicated. Joints of fire-rated gypsum board enclosures shall be closed and sealed in accordance with UL test requirements or GA requirements. Seal penetrations through rated partitions and ceilings tight in accordance with tested systems.
3.7 PATCHING
Patch surface defects in gypsum board to a smooth, uniform appearance, ready to receive finishes.
3.8 SHAFTWALL FRAMING
Install the shaftwall system in accordance with the system manufacturer's published instructions. Coordinate bucks, anchors, blocking and other items placed in or behind shaftwall framing with electrical and mechanical work. Patch or replace fireproofing materials which are damaged or removed during shaftwall construction.
3.9 WASTE MANAGEMENT
As specified in Waste Management Plan and as follows. Separate clean waste gypsum products from contaminants. Do not include wood, plastic, metal, asphalt-impregnated gypsum board, or any gypsum board coated with glass fiber, vinyl, decorative paper, or other finish. Place in designated area and protect from moisture and contamination. Coordinate with Section 32 05 33 LANDSCAPE ESTABLISHMENT to identify requirements for gypsum soil amendment and to prepare scrap gypsum board for use as soil amendment.
Identify manufacturer's policy for collection or return of remaining construction scrap, unused material, and packaging material. Institute demolition and construction recycling to take advantage of manufacturer's programs. When such a service is not available, seek local recyclers to reclaim the materials.
09 29 00-11
GYPSUM BOARD
PART 1 GENERAL
1.1 REFERENCES
1.2 SUBMITTALS
1.3 DELIVERY, STORAGE, AND HANDLING
1.3.1 Delivery
1.3.2 Storage
1.3.3 Handling
1.4 ENVIRONMENTAL CONDITIONS
1.4.1 Temperature
1.4.2 Exposure to Weather
1.4.3 Temporary Ventilation
1.5 SUSTAINABLE DESIGN REQUIREMENTS
1.5.1 LEED Rating
1.5.2 Local/Regional Materials
1.6 QUALIFICATIONS
1.7 SCHEDULING
PART 2 PRODUCTS
2.1 MATERIALS -GENERAL
2.1.1 Recycled Content
2.1.2 Adhesives, Paints & Coatings
2.2 MATERIALS
2.2.1 Gypsum Board
2.2.1.1 Regular
2.2.1.2 Foil-Backed
2.2.1.3 Type X Special Fire-Resistant
2.2.2 Gypsum Backing Board
2.2.2.1 Regular
2.2.2.2 Foil-Backed
2.2.2.3 Type X Special Fire-Resistant
2.2.3 Regular Water-Resistant Gypsum Backing Board
2.2.3.1 Regular
2.2.3.2 Type X Special Fire-Resistant
2.2.4 Glass Mat Water-Resistant Gypsum Tile Backing Board
2.2.4.1 Regular
2.2.4.2 Type X Special Fire-Resistant
2.2.5 Glass Mat Covered or Reinforced Gypsum Sheathing
2.2.5.1 Glass Mat Covered or Reinforced Gypsum Sheathing Sealant
2.2.6 Cementitious Backer Units
2.2.7 Joint Treatment Materials
2.2.7.1 Embedding Compound
2.2.7.2 Finishing or Topping Compound
2.2.7.3 All-Purpose Compound
2.2.7.4 Setting or Hardening Type Compound
2.2.7.5 Joint Tape
2.2.8 Fasteners
2.2.8.1 Screws
2.2.9 Shaftwall Liner Panel
2.2.10 Accessories
2.2.11 Water
PART 3 EXECUTION
3.1 EXAMINATION
3.1.1 Framing and Furring
3.1.2 Gypsum Board
3.2 APPLICATION OF GYPSUM BOARD
3.2.1 Application of Gypsum Board to Steel Framing and Furring
3.2.2 Gypsum Board for Wall Tile or Tile Base Applied with Adhesive
3.2.3 Exterior Application
3.2.4 Glass Mat Covered or Fiber Reinforced Gypsum Sheathing
3.2.5 Control Joints
3.2.6 Application of Foil-Backed Gypsum Board
3.3 APPLICATION OF CEMENTITIOUS BACKER UNITS
3.3.1 Application
3.3.2 Joint Treatment
3.4 FINISHING OF GYPSUM BOARD
3.4.1 Uniform Surface
3.5 SEALING
3.5.1 Sealing for Glass Mat or Reinforced Gypsum Board Sheathing
3.6 FIRE-RESISTANT ASSEMBLIES
3.7 PATCHING
3.8 SHAFTWALL FRAMING
3.9 WASTE MANAGEMENT
SECTION 09 30 00
CERAMIC TILE, PORCELAIN TILE, AND PAVER TILE
ASTM C 373 (1988; R 2006) Water Absorption, Bulk Density, Apparent Porosity, and Apparent Specific Gravity of Fired Whiteware Products
ASTM C 482 (2002; R 2009) Bond Strength of Ceramic Tile to Portland Cement
ASTM C 501 (1984; R 2009) Relative Resistance to Wear of Unglazed Ceramic Tile by the Taber Abraser
ASTM C 648 (2004; R 2009) Breaking Strength of Ceramic Tile
ASTM D 226/D 226M (2009) Standard Specification for Asphalt-Saturated Organic Felt Used in Roofing and Waterproofing
ASTM D 4068 (2009) Chlorinated Polyethylene Sheeting for Concealed Water-Containment Membrane
BAY AREA AIR QUALITY MANAGEMENT DISTRICT (Bay Area AQMD)
Bay Area AQMD Rule 8-51 (1992; R 2001) Adhesive and Sealant
GREEN SEAL (GS)
GS-36 (2000) Commercial Adhesives
GREENGUARD ENVIRONMENTAL INSTITUTE (GEI)
GEI Greenguard Standards for Low Emitting
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 99 (2005; TIA 05-1; TIA 05-2; TIA 05-3;
Errata 05-1) Standard for Health Care Facilities
09 30 00-1
SCIENTIFIC CERTIFICATION SYSTEMS (SCS)
SCS Scientific Certification Systems (SCS)Indoor Advantage
SOUTH COAST AIR QUALITY MANAGEMENT DISTRICT (SCAQMD)
SCAQMD Rule 1168 (1989; R 2005) Adhesive and Sealant Applications
TILE COUNCIL OF NORTH AMERICA (TCNA)
TCA Hdbk (2007) Handbook for Ceramic Tile Installation
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
36 CFR 1191 Americans with Disabilities Act (ADA) Accessibility Guidelines for Buildings and Facilities
1.2 SYSTEM DESCRIPTION
1.2.1 General Requirements
Close space, in which tile is being set, to traffic and other work. Keep closed until tile is firmly set. Do not walk or work on newly tiled floors without using kneeling boards or equivalent protection of the tiled surface. Keep traffic off horizontal portland cement mortar installations for at least 72 hours. Keep all traffic off epoxy installed floors for at least 40 hours after grouting, and heavy traffic off for at least 7 days, unless otherwise specifically authorized by manufacturer. For materials like Tile, Accessories, and marble Thresholds submit Samples of sufficient size to show color range, pattern, type and joints.
1.2.2 Local/Regional Materials
See Section 01 33 29 LEED(tm) DOCUMENTATION for cumulative total local material requirements. Tile materials may be locally available. Submit documentation indicating distance between manufacturing facility and the project site and also the distance of raw material origin from the project site. For Tile indicate percentage of post-industrial and post-consumer recycled content per unit of product. Indicate relative dollar value of recycled content products to total dollar value of products included in project. Submit LEED documentation relative to local/regional materials
1.2.3 Sustainable Design Certification
Product shall be third party certified by GEI Greenguard Indoor Air Quality Certified, SCS Scientific Certification Systems Indoor Advantage or equal.
09 30 00-2
Certification shall be performed annually and shall be current.
1.3 SUBMITTALS
Detail Drawings; G
Tile; G
Mortar, Grout, and Adhesive; (LEED); G
Tile; (LEED)
Grout; G
SD-06 Test Reports
Testing; G
Mortar, Grout, and Adhesive; G
Tile; (LEED)
1.4 QUALITY ASSURANCE
Dimension and draw detail drawings at a minimum scale of 1/4 inch = 1 foot.
Include drawings of pattern at inside corners, outside corners, termination points and location of all equipment items such as thermostats, switch plates, mirrors and toilet accessories mounted on surface. Submit drawings showing tile pattern elevations.
09 30 00-3
1.5 DELIVERY, STORAGE, AND HANDLING
Deliver materials to the project site in manufacturer's original unopened containers with seals unbroken and labels and hallmarks intact. Protect materials from weather, and store them under cover in accordance with manufacturer's printed instructions.
1.6 ENVIRONMENTAL REQUIREMENTS
Do not perform ceramic tile work unless the substrate and ambient temperature is at least 50 degrees F and rising. Maintain temperature above 50 degrees F while the work is being performed and for at least 7 days after completion of the work. When temporary heaters are used, ventilate the area to the outside to avoid carbon dioxide damage to new tilework.
1.7 WARRANTY
Provide manufacturer's standard performance guarantees or warranties that extend beyond a 1-year period.
1.8 EXTRA MATERIALS
Supply an extra two percent of each type tile used in clean and marked cartons.
2.1 TILE
Conform to TCA Hdbk for standard grade tile. Provide grade sealed containers. Mark seals with the marks on the signed master grade certificate. Provide an impact resistant tile with a minimum floor breaking strength for wall tile of 90 pound in accordance with ASTM C 648.
Provide a 0.50 maximum percent water absorption in accordance with ASTM C 373. Coordinate the color with Section 09 06 90 COLOR SCHEDULE.
See Section 01 33 29 LEED(tm) DOCUMENTATION for cumulative total recycled content requirements. Tile may contain post-consumer or post-industrial recycled content. Submit manufacturer's catalog data and preprinted installation and cleaning instructions plus a master grade certificate for tile. Indicate VOC content.
2.1.1 Porcelain Tile (PT-1)
Furnish an unglazed porcelain tile and trim with the color extending uniformly through the body of the tile. Provide a nominal size of 12 by 24 by 5/16 inch thick. Criteria for tile to meet or exceed is as follows:
Abrasive wear in accordance with ASTM C 501 and bonding strength in accordance with ASTM C 482. Comply with 36 CFR 1191 for coefficient of friction for interior tiled floors. Coordinate color with Section 09 06 90
COLOR SCHEDULE.
2.1.2 Glazed Wall Tile
Provide glazed wall tile with cushioned edges and trim edged with lead-free matte finish. Provide tile 4-1/4 by 4-1/4 inch. Coordinate color with Section 09 06 90 COLOR SCHEDULE.
09 30 00-4
2.1.3 Porcelain Tile: (PT-2/3)
Furnish glazed porcelain tiles with the color extending uniformly through the body of the tile. Provide nominal sizes of 4 by 24 inches (PT-2/3).
Criteria for tile to…
This is the start of the file's text. The full file is on GovTribe.