This document contains a federal contract opportunity notice and related technical drawings. The U.S. Army Corps of Engineers, St. Louis District is seeking firms for the rehabilitation of miter gates at the National Aeronautics and Space Administration's John C. Stennis Space Center in Mississippi. The goal is to rehabilitate the upper and lower miter gates to maintain marine access to the NASA test facility. Work will include blasting and painting gates, replacing timber fenders, rubber seals, and structural members, removing and reinstalling the cathodic protection system, and rehabilitating hydraulic cylinders. Firms must furnish all equipment, labor, services, materials and complete specified work, minimizing lock closure duration. The solicitation is expected to issue on May 21, 2021 via the System for Award Management website. The estimated value is between $5-10 million. Responses are due as specified in the solicitation.

View the file

Other files

Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DRAWING NO.AUTHORITY

ERONAUTICS AND

DMINISTRATION

PACE

ATIONAL

DESCRIPTION

REVISIONS

SYM

SIGNATURES

ZONE

DATE

APPROVED

SSC, MS 39529-6000

SPACE CENTER

JOHN C. STENNIS

DATE

CADD P/N:

A

B

NOTES:

1. EXISTING ANODES: COMPOSITION ASTM B-265, TITANIUM/GRADE2, DIAMETER

0.75", LENGTH 20". TOTAL IS 368 ANODES.

REPLACEMENT ANODES: TITANIUM ASTM GRADE 1 SUBSTRATE

TUBULAR ANODE WITH MIXED METAL OXIDE COATING. DIAMETER 1.0",

LENGTH 19.7". TOTAL IS 368 ANODES.

UPPER MITER GATES (2 EACH) UPSTREAM AND DOWNSTREAM SIDES

FOUR ANODES PER STRING WITH EIGHT ANODE STRINGS PER A GATE

PER SIDE.

LOWER MITER GATE (2 EACH) UPSTREAM SIDE NINE ANODES PER

STRING WITH EIGHT ANODE STRING PER A GATE PER SIDE.

LOWER MITER GATE (2) EACH DOWNSTREAM SIDE, SIX ANODES PER

STRING WITH EIGHT ANODE STRINGS PER A GATE PER SIDE.

2. EXISTING ANODES LEAD WIRES: # 8 AWG, 7 STRAND COPPER CONDUCTORS

WITH 7/64" THICK HIGH MOLECULAR POLYETHYLENE (HMWPE) INSULATED

LEADS. REPLACEMENT ANODES LEAD WIRES #8 AWG, 7 STRAND COPPER

CONDUCTORS WITH .020" HALAR INSULATION THICKNESS (INNER LAYER) AND

.065" HIGH MOLECULAR POLYETHYLENE (HMWPE) THICKNESS (OUTER

LAYER).

3. CONDUCT STRUCTURE TO WATER POTENTIAL MEASUREMENTS WITH

REFERENCE TO COPPER - COPPER SULFATE CELL AT THE POINTS INDICATED

BY "X" ON BOTH THE EAST AND WEST GATES. ADJUST RECTIFIER OUTPUT TO

HAVE POTENTIAL MEASUREMENT NOT HIGHER THAN -0.85 VOLT.

4. REPLACE EXISTING RECTIFIER AND ANODE STRINGS.

BUILDING 2311 BUILDING 2310

A

B

REPLACEMENT RECTIFIER 1

460 VAC, 3 PHASE

30 VDC, 50 AMP

REPLACEMENT RECTIFIER 4

460 VAC, 3 PHASE

30 VDC, 50 AMP

REPLACEMENT RECTIFIER 2

460 VAC, 3 PHASE

30 VDC, 50 AMP

REPLACEMENT RECTIFIER 3

460 VAC, 3 PHASE

30 VDC, 50 AMP

REPLACE EXISTING ANODE

AND ATTACHMENT CABLE

STRAIGHT CONNECTOR

WITH NEOPRENE BUSHING

EMCS

EMCS

MBC422

ELPRO 905U WIRELESS

MULTI I/O NODE

EMCS HARDWIRE

& 24 VAC SUPPLY

ELPRO 915U WIRELESS

MULTI I/O GATEWAY

EMCS

ELPRO 915U WIRELESS

MULTI I/O GATEWAY

EMCS

ELPRO 915U WIRELESS

MULTI I/O GATEWAY

EMCS

ELPRO 915U WIRELESS

MULTI I/O GATEWAY

EMCS

MBC421

EMCS HARDWIRE

& 24 VAC SUPPLY

ELPRO 905U WIRELESS

MULTI I/O NODE