This document contains technical specifications and drawings for a liquid preservation system and transformer. The U.S. Army Corps of Engineers is soliciting bids for the Old Hickory Power Plant GSU Transformer Installation project in Hendersonville, Tennessee. The solicitation is a firm fixed price construction contract to incorporate revised specifications and drawings provided in the attachments. Bidders must submit a completed security form to access the secured plans and specifications. The project involves installation of a 150 MVA transformer rated for 60Hz at 13.2/161/152.95kV. Additional details include ONAN/ONAF cooling, an eight year manufacturer date, copper windings, and liquid preservation system operating pressures up to 5 psi positive and 0.5 psi positive.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
N A
M E
D
ATE
REV.NO.
O R
D
ER
N O
CLIENT:
SC
ALE
SH
EET
SH
SU
BST.FO
R R
EPL.BY
O
R
IG
IN
R ating Plate
DO 90 000 / 150E
LS41413 A2
US ARM
Y CO
RPS O
F ENG
INEERS / USA
1:1
DESIGN
CHECK
NO.
R
EVISIO
N
DESIG.
RELEASE
RELEASE
DATE-NAM
E
DESIG.
DESIG.
DESIG.
RELEASE
RELEASE
RELEASE
SER
IAL N
O
We reserve all rights in this document and in the information contained therein
N 009082
210318
N 009082101-102
G . Anzinger
210322 210322
Project: O ld H ickory Pow er Plant
C ustom er: Yellow stone Electric C o.
End U ser: U S Arm y C orps of Engineers
M .G etzinger M
.G etzinger
1LS41413 A2
-2
210520 AG
210521 H
A
Liquid preservation system inform ation
211004 AG
211004 H
A
Liquid level changing inform ation
211214 AG
211215 H
A
H V BIL SIL level
As-Built.
220210 AG
220210 H
A
AS-BU
ILT.
AS-BUILT
Connection
Type Number of specification Rated frequency Winding / Insulation level
Rated power
Rated current
De-energized tap-changer
Rated current
Hz kV
MVA
V
A
Type
A
Type of cooling
Serial number Date of manu-facture Kind Connection symbol
Impedance voltage at rated current referred to power
DETC Serial number Insulation level kVA s kV
Three-phase Transformer
Rated voltage
Voltage V Current APosi-tion
High-voltage Terminal: H3 - H2 - H1 - H0
Low-voltage Terminal: X1 - X2 - X3
13 200
LS41413 A2-3
ABB - DTW Double Deck
1 015
1 169 050
165 025
161 000
156 975
152 950
DO 90 000 / 150E
60 ONAN / ONAF - 65C
N009082101
11 / 2021
YN / d1
75 000
BIL 650 AC 275
169 050/GrdY 97 601
161 000/GrdY 92 953
152 950/GrdY 88 306
13 200
IEEE C57.12.00
BIL 650 BSL 540 AC 170 -
BIL 150 AC 50
A - D
4 374
B - D
B - E
C - E
C - F
3 280
ONAN ONAF
HV/
75 / 100
269 / 359
! ATTENTION !
Do not operate de-energized tap-changer when transformer is energized!
Step-up
Siemens Energy Austria GmbH - Linz
Total mass
Transportation mass excl. oil
Untanking mass lbs lbs lbs
Max. ambient temperature 40°C
Mass of tank and fittings lbs
Mass of core and coil lbs
Contains no PCB's as determined by the use of ASTM D 4059
3 limb core type Material of HV, LV winding: copper
Quantity of insulating oil - tank: 8 418 gallons / radiators: 289 gallons / Total: 8 707 gallons 8 518 *) gallons
Instruction manual number: 2036-00/96Goverment´s contract number: W912P520C0013 Seismic level: IEEE 693 - moderate
Tank pressure: positive 14.5 psiTank, radiators and piping are designed for full vacuum.
140 571
50 265
Mass of total insulating oil lbs
Short-circuit Duration max.
H / X
7.39
7.46
7.57
1ZUA21228408
LV / BIL 110 AC 34
75 / 100
3 280 / 4 374
Type of insulating fluid: ASTM D3487 Type II Mineral Oil
X/R Ratio 1 57.6
285 278 *)
212 291 *)
61 915 *)
168 720 *)
*) Measured values during manufacture
Mass of insualtion mat. lbs 8 047
Liquid level below top surface of the highest point of the highest manhole flange at 25°C 360 mm (14.17 in). Liquid level changes 23.75 mm (0.935 in) per 10 °C change in liquid temperature
Sheet 1
Transformer is reconnectable to 69 kV
Operating pressures of liquid preservation system max. +5.0 psi positive and min. +0.5 psi positive