W912P518B0005_DRAFT_TPlans_.pdf
PDF 44 MB Posted
- Attached to
- Downstream Lock Excavation Construction Federal contract opportunity
- Solicitation number
- W912P518B0005
About this file
DRAFT TECHNICAL PLANS ONLY W912P18B0005
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| KYL_Lock_Excavation201_May2018_Industry_Day_Part_2.pdf | ||
| KYL_Lock_Excavation201_May2018_Industry_Day_Part_1.pdf | ||
| KY_Lock_Industry_Day_Q&A.pdf | ||
| Attendance_Roster.pdf | ||
| W912P518B0005_DRAFT__TSpecs.pdf | ||
| W912P518B0005_DRAFT_TSpecs_Appendix_B_-_Forms_and_Attachments.pdf | ||
| W912P518B0005_DRAFT_TPlans_Maintenance_Bldg_95_BCOES.pdf | ||
| W912P518B0005_DRAFT_TSpecs_Appendix_A_-_Maintenance_Bldg.pdf | ||
| W912P518B0005_DRAFT_Solicitation_5-4-2018.pdf | ||
| Site_Visit_Form.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SCALE:
H
F
G
E
3 4 5 6
D
C
B
A
2 3 4 5 6
REV NO.TASK COMPLETED BY:
DO NOT ALTER MANUALLY
C.A.D. DRAWING
ISSUED BY:
R
TENNESSEE VALLEY AUTHORITY
FOSSIL AND HYDRO ENGINEERING
AUTOCAD R
DATE
PLOT FACTOR:
REVIEWED BY: APPROVED BY:
AS CONST
EXCEPT AS NOTED
NO.
REV.
DATE
R
R
DRWNDSGN CHKD RVWDSUPV APPD
PROJECT
ISSD
ID
F
CD
REV
DISCIPLINE
INTERFACE
E
7 8 9
D
C
B
A
SUBMITTED BY:
APPROVED BY:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
REVISION R CHIEF, ENGINEERING CONSTRUCTION DIVISION
US Army Corps of Engineers
Nashville District
P l o t
T i m e
P l
D a t e
F i l e
N m e
:5
:5
P M c u s e r s h e c x d e k d o c u m e n t s p w w o r k c e lr n d m s
N
.d g n
8C
C07
N_TVA
---MAMRFK-
INITIAL ISSUE
XX
CHIEF, CIVIL DESIGN BRANCH
CDH
NONE
BDS
BDS CDH NCB
SHEET 1 0F 2
CELRN
DOWNSTREAM LOCK EXCAVATION
BDS
BDS
KENTUCKY PROJECT
INDEX OF DRAWINGS
61N246-7
61N246-7
KENTUCKY LOCK ADDITION
DRAWING TITLEFILE NAME
GENERAL
DRAWING TITLEFILE NAME
ROCK EXCAVATION
OVERBURDEN EXCAVATION
GROUTING PROGRAM
EXISTING LANDWALL STABILIZATION MEASURES
GROUT CURTAIN, BASELINE PROFILE
COVER SHEET
GENERAL NOTES, LEGEND AND ABBREVIATIONS
PROJECT LOCATION PLAN
HORIZONTAL & VERTICAL CONTROL, SURVEY MONUMENT & BASELINES
EXISTING LOCK, ANCHOR PLAN VIEW, LAYOUT - LAND WALL61N241-18
61N241-19
61N241-20
61N241-21
61N241-22
61N241-23
61N241-24
61N241-25
61N241-31
61N241-33
EXISTING LOCK, ANCHOR LAYOUT, MONOLITH EL-11
EXISTING LOCK, ANCHOR LAYOUT, MONOLITH EL-12
EXISTING LOCK, ANCHOR LAYOUT, MONOLITH EL-13
EXISTING LOCK, ANCHOR LAYOUT, MONOLITH EL-14
EXISTING LOCK, ANCHOR LAYOUT, MONOLITH EL-15
EXISTING LOCK, ANCHOR LAYOUT, MONOLITH EL-16
EXISTING LOCK, ANCHOR LAYOUT, MONOLITH EL-22
EXISTING LOCK, ANCHOR LAYOUT, MONOLITH EL-24
EXISTING LOCK, ANCHOR LAYOUT, MONOLITH EL-25
EXISTING LOCK, ANCHOR DETAILS61N241-14A
61N246-7
61N247-70
61N247-71
61N247-73
61N247-74
61N241-34
61N241-26
10N400-1
10N400-2
10N400-3
10N400-4
10N400-5
10N400-6
10N400-7
10N400-8
10N400-9
10N400-10
10N400-11
10N400-12
10N400-13
10N400-14
10N400-15
10N400-16
10N400-17
10N400-18
10N400-19
10N400-20
10N400-21
10N400-22
10N400-23
10N400-24
10N400-25
BORING LOCATION PLAN
17N401-1
17N401-2
17N401-3
17N401-4
17N401-5
17N401-6
17N401-7
17N401-8
17N401-9
17N400-1
17N400-2
17N401-10
PLUMBING LEGEND
PLUMBING FLOOR PLAN - SANITARY
PLUMBING FLOOR PLAN - HOT & COLD WATER
PLUMBING FLOOR PLAN - COMPRESSED AIR
PLUMBING RISER - SOIL, WASTE & VENT
PLUMBING RISER - HOT & COLD WATER
PLUMBING RISER - COMPRESSED AIR
PLUMBING DETAILS
PLUMBING DETAILS
PLUMBING EQUIPMENT SCHEDULES
17N400-3
HVAC SCHEDULES
HVAC DETAILS
HVAC FLOOR PLAN
HVAC LEGEND
822N3060
822N3061
822N3062
822N3063
61N246-8 INDEX OF DRAWINGS, SHEET 2 OF 2
INDEX OF DRAWINGS, SHEET 1 OF 2
61N651-20
61N651-21
61N651-22
61N651-23
ROBERT F. KNOX MICHAEL A. MORRISON NICOLE C. BERGER
BENJAMIN L. ROHRBACH P.E.
VANESSA C. BATEMAN
61N_DLE_CVR
EXISTING LOCK, ANCHOR LAYOUT, MONOLITH EL-17
EXISTING LOCK, ANCHOR LAYOUT, MONOLITH EL-18
ROCK EXCAVATION PLAN
ROCK EXCAVATION PLAN, PHASE I
ROCK EXCAVATION PLAN, PHASE II
ROCK EXCAVATION PLAN, PHASE III
822N3064
822N3065
822N3066
822N3067
822N3068
822N3069
822N3070
822N3071
822N3072 BORING SECTIONS, SECTIONS AT 13+00B & 14+00B
BORING SECTIONS, SECTIONS AT 11+00B & 12+00B
BORING SECTIONS, SECTIONS AT 09+00B & 10+00B
BORING SECTIONS, SECTIONS AT 07+00B & 08+00B
BORING SECTIONS, SECTIONS AT 05+00B & 06+00B
GEOTECHNICAL LEGEND
PRESPLIT AND LINE DRILLING
FOUNDATIONS, APPROXIMATE TOP OF ROCK
EXCAVATION SECTIONS, SECTIONS AT 03+00B & 04+00B
EXCAVATION SECTIONS, SECTIONS AT 05+00B & 06+00B
EXCAVATION SECTIONS, SECTIONS AT 07+00B & 08+00B
EXCAVATION SECTIONS, SECTIONS AT 09+00B & 10+00B
EXCAVATION SECTIONS, SECTIONS AT 11+00B & 12+00B
EXCAVATION SECTIONS, SECTIONS AT 13+00B & 14+00B
61N651-24
61N651-25
61N651-26
61N651-27 EXCAVATION SECTIONS, SECTION AT 15+00B
61N651-28
61N651-29
61N651-30
61N651-31
61N651-32
61N651-33
61N651-34
GROUT CURTAIN, CROSS SECTIONS A-A THRU E-E
GROUT CURTAIN, GEOLOGIC PROFILE, B-LINE
GROUT CURTAIN, GEOLOGIC PROFILE, A-LINE
GROUT CURTAIN BASELINE
GROUT CURTAIN PLAN
TEMPORARY LOCK MAINTENANCE BUILDING
GENERAL
COVER SHEET
CONTROL POINT LOCATIONS
INDEX OF DRAWINGS
VICINITY AND LOCATION MAPS
CONTROL POINT DESCRIPTIONS
SOIL AND ROCK CLASSIFICATION
BORING TEST PIT LOGS
BORING TEST PIT LOGS
10N400-26
10N400-27
10N400-28
10N400-29
10N400-30
10N400-31
10N400-28A
10N400-32
10N400-33
10N400-34
10N400-35
10N400-36
10N400-37
10N400-38
10N400-39
10N400-40
10N400-41
10N400-42
10N400-43
10N400-44
10N400-45
10N400-46
10N400-47
10N400-48
10N400-49
10N400-50
10N400-51
10N400-52
10N400-53
10N400-54
10N400-55
10N400-56
10N400-57
10N400-58
10N400-59
EROSION CONTROL PLAN
EROSION CONTROL PLAN
EROSION CONTROL PLAN
EROSION CONTROL DETAILS
DEMOLITION PLAN
DEMOLITION PLAN
DEMOLITION PLAN
SITE PLAN
SITE PLAN
SITE DETAILS
SITE DETAILS
SITE DETAILS
GRADING PLAN
GRADING PLAN
SANITARY SEWER PROFILE
GRADING DETAILS
PAVEMENT DETAILS
PAVEMENT PLAN
UTILITY PLAN
UTILITY PLAN
UTILITY DETAILS
CIVIL
STRUCTURAL
ARCHITECTURAL
GENERAL STRUCTURAL NOTES, DESIGN LOADS & ABBREVIATIONS
SPECIAL INSPECTIONS
FOUNDATION PLAN
ROOF FRAMING PLAN
EXTERIOR ELEVATIONS
EXTERIOR ELEVATIONS
TYPICAL DETAILS
TYPICAL MASONRY DETAILS
3D REPRESENTATION
GENERAL NOTES, ABBREVIATIONS
SEALANT, MASONRY JOINTS & MISC. STANDARD DETAILS
FLOOR PLAN
ROOF PLAN
REFLECTED CEILING PLAN
BUILDING ELEVATIONS
BUILDING ELEVATIONS
BUILDING SECTIONS
WALL SECTIONS
WALL DETAILS
ENLARGED RESTROOM/STAIR PLANS, ELEVATIONS & DETAILS
ENLARGED STAIR DETAILS
ROOF DETAILS
MISCELLANEOUS DETAILS
PARTITION SCHEDULES & DETAILS
DOOR SCHEDULE AND TYPES
DOOR DETAILS
WINDOW TYPES
WINDOW DETAILS
DOOR SCHEDULE, FRAMES & TYPES
PERSPECTIVE VIEWS
DRAWING TITLEFILE NAME
TEMPORARY LOCK MAINTENANCE BUILDING
15N400-1
15N400-2
15N400-3
FIRE ALARM
15N400-4
15N400-5
15N400-6
15N400-7
15N400-8
15N400-9
15N400-10
15N400-11
15N400-12
15N400-13
15N400-14
15N400-15
FIRE ALARM PLAN
FIRE ALARM DETAILS
ELECTRICAL
LEGEND AND ABBREVIATIONS
LIGHTING PLAN
FIRST ELEVATION POWER PLAN
SECOND ELEVATION POWER PLAN
ELECTRICAL DETAILS
LIGHTING DETAILS
ONE-LINE DIAGRAM
PANEL SCHEDULES
LIGHTNING PROTECTION PLAN
LIGHTING PROTECTION DETAILS
GROUNDING DETAIL
TELECOMMUNICATION
TELECOMMUNICATIONS PLAN
TELECOMMUNICATIONS DETAILS
MECHANICAL
17N400-4
PLUMBING
17N401-11
PLUMBING FLOOR PLAN - RADON
61N247-75
61N247-76 MAJOR FEATURES OF WORK
16W220-6
16W220-15
16W220-2r1 ARCHITECTURAL. FLOOR PLAN
ARCHITECTURAL, ELEVATIONS AND BUILDING SECTIONS16W220-3r1
ARCHITECTURAL, WALL SECTIONS16W220-4r1
ARCHITECTURAL, WALL FRAMING
16W220-9r1 ARCHITECTURAL, MONORAIL, LADDER, AND HANDRAIL DETAILS
16W220-10r1 ARCHITECTURAL, FLOOR SLAB PLAN AND DETAILS
16W220-12r2 MECHANICAL, PIPING, HEATING & VENTILATING
16W220-13r4 MECHANICAL, PIPING, HEATING & VENTILATING
16W220-14r2 ELECTRICAL, POWER AND LIGHTING LAYOUT AND DETAILS
ARCHITECTURAL, STAIR PLAN & DETAILS
BOAT SHELTER
FIRST FLOOR PLAN
LEGEND AND ABBREVIATIONS
FLOOR PLAN
ELECTRICAL DETAILS
10N400-59A
10N400-59B
LIFE SAFETY
LIFE SAFETY CODE REVIEW
FIRST FLOOR - LIFE SAFETY PLAN
FOR INFORMATION ONLY
TEMPORARY LOCK MAINTENANCE BUILDING
10N400-1?
15N400-1?
15N400-2?
15N400-3?
GROUT CURTAIN HOLE DATA
822N3073 BORING SECTIONS, SECTIONS AT 15+00B & 16+00B
GEOLOGIC PROFILE, SPECIALIZED TREATMENT ZONES (STZ)
EXISTING BORINGS LOCATION, BORINGS PLAN
DOWNSTREAM COFFERDAM STABILIZATION MEASURES
MONOLITHS M-27C THROUGH M-28C, CONCRETE COFFERDAM
MONOLITHS M-30C THROUGH M-31C, CONCRETE COFFERDAM
MONOLITHS M-29C, CONCRETE COFFERDAM
61N241-45
61N241-47
61N241-49
61N241-32 EXISTING LOCK, ANCHOR LAYOUT, MONOLITH EL-23
61N247-72A CONSTRUCTION LIMITS PLAN, CURRENT CONTRACTS
61N247-76 SPLASH PAD DETAILS
61N247-72B CONSTRUCTION LIMITS PLAN, DOWNSTREAM LOCK EXCAVATION CONTRACT
DISPOSAL AREA "D", PLAN
DISPOSAL AREA "D", SECTIONS
COFFERDAM ANCHOR LAYOUT - ANCHOR PLACEMENT
MONOLITHS M-22C THROUGH M-24C, CONCRETE COFFERDAM
MONOLITHS M-25C THROUGH M-26C, CONCRETE COFFERDAM
61N241-40
61N241-41
61N241-43
CONCRETE
INDENTIFICATION NUMBER
DETAIL
IS SHOWN
WHICH THE DETAIL
DRAWING NUMBER ON
A
XXXXXXX
A
XXXXXXX
XXXXXXX
DRAINAGE SLOPE
D
R
T
CURVE DELTA ANGLE
CURVE RADIUS
CURVE TANGENT
PROFILE DESIGNATION
SHEET LOCATIONDESIGNATION
STATION OR OFFSET
STATION OR OFFSET
DIRECTION DESIGNATION
RIPRAP
AGGREGATE
DEMOLITION, EXCEPT WHEN NOTED
CLAY
COE
CMP
CLSM
CL
CFS
CB
BR
CORPS OF ENGINEERS
CORRUGATED METAL PIPE
CONTROLLED LOW-STRENGTH MATERIALS
CENTER LINE
CUBIC FEET PER SECOND
CONTROL BOX
BRIDGE
LW
LTG
LT
LS
LBS
L
KY
NORTH AMERICAN VERTICAL DATUM
NORTH
MINIMUM
MANHOLE
MANUFACTURER
MANUFACTURED
MECHANIC
MAXIMUM
MAINTENANCE
NAVD
N
MIN
MH
MFR
MFD
MECH
MAX
MAINT
PIEZOMETER
POINT OF VERTICAL TANGENT
POINT OF VERTICAL INTERSECTION
POLYVINYL CHLORIDE
POINT
PUBLIC SERVICE SAFETY
POUNDS PER SQUARE INCH
PROPOSED LOCK
PLUG
PZ
PVT
PVI
PVC
PT
PSS
PSI
PROP LOCK
PL
WKYRECC
W/
W
V:H
V
USC & GS
USACE
WEST KENTUCKY RURAL ELECTRIC COOPERATIVE CORPORATION
WITH
WEST
VERTICAL TO HORIZONTAL SLOPE
VERTICAL
UNITED STATES COAST AND GEODETIC SURVEY
UNITED STATES ARMY CORPS OF ENGINEERS
YR
XFMR
W
V
TRANS
TEL
SW
RECC
PWR
PH
NEMA 3R
KVA
KV
ETC
CONTR
COND
C
A
YEAR
TRANSFORMER
WATT
VOLT
TRANSFORMER
TELEPHONE
SWITCH
RURAL ELECTRIC COOPERATIVE CORPORATION
POWER
PHASE
NATIONAL ELECTRICAL MANUFACTURER ASSOCIATION 3 RATING
KILOVOLT-AMPERE
KILOVOLT
ELECTRICAL TRANSFORMER COMPONENTS
CONTROL
CONDUIT
CABLE
AMP
BM V
BM H
BLDG
AVE
ASTM-C
ASTM
APPROX
ACI
AC
AASHTO
BENCHMARK VERTICAL
BENCHMARK HORIZONTAL
BUILDING
AVERAGE
AMERICAN SOCIETY FOR TESTING MATERIALS-CONCRETE
AMERICAN SOCIETY FOR TESTING MATERIALS
APPROXIMATE
AMERICAN CONCRETE INSTITUTE
ACRES
AMERICAN ASSOCIATION OF STATE HIGHWAY AND TRANSPORTATION OFFICIALS
DOT
DOH
DIR
DIA
DEPT
DEG
D
CY
CU
CSB
CP
EXP
EXH
EXC
EX, EXIST
ENG
ELEV
EL
E
DWG
DS
DEPARTMENT OF TRANSPORTATION
DEPARTMENT OF HEALTH
DIRECTION
DIAMETER
DEPARTMENT
DEGREE
DIAMETER
CUBIC YARDS
CUBIC
CRUSHED STONE BASE
CONTROL POINT
EXPLORATORY HOLE
EXHAUST
EXCAVATION
EXISTING
ENGINEERING
ELEVATION
ELEVATION
EAST
DRAWING
DOWNSTREAM OF ORIGIN
LAND WALL
LIGHTING
LOW TENSION
LIFT STATION
POUNDS
LENGTH
KENTUCKY
NATIONAL GEODETIC VERTICAL DATUM
NUMBER
NOT TO SCALE
ON CENTER
OFFSET
PARKER KALON
PADUCAH AND LOUISVILLE
PERFORATED
NGVD
NO
NTS
OC
OFF
PK
P&L
PERF
U/S, US
TYP
TVA
TP
T/LOCK
STD
STA
UPSTREAM
TYPICAL
TENNESSEE VALLEY AUTHORITY
TURNING POINT
TOP OF LOCK
STANDARD
STATION
KYTC
JB
INV
I
HWY
HSE
HQ
HEX
HEI
HDPE
FT
FLD
KENTUCKY TRANSPORTATION CABINET
JUNCTION BOX
INVERT
INTERSTATE
HIGHWAY
HOUSE
HEADQUARTERS
HEXAGONAL
HANSON ENGINEERING INCORPORATED
HIGH DENSITY POLYETHYLENE
FEET
FIELD
SPEC
SDR
SCH
S
RR
REINF
RCP
R
Q
SPECIFICATION
STANDARD DIMENSION RATIO
SCHEDULE
SOUTH
RAILROAD
REINFORCED
REINFORCED CONCRETE PIPE
RIGHT OF ORIGIN, LOOKING DOWNSTREAM
DISCHARGE
ROCK
BORING SAMPLE
EXPLORATORY HOLE, PIEZOMETER
NTC NOT THIS CONTRACT
SCALE:
H
F
G
E
3 4 5 6
D
C
B
A
2 3 4 5 6
REV NO.TASK COMPLETED BY:
DO NOT ALTER MANUALLY
C.A.D. DRAWING
ISSUED BY:
R
TENNESSEE VALLEY AUTHORITY
FOSSIL AND HYDRO ENGINEERING
AUTOCAD R
DATE
PLOT FACTOR:
REVIEWED BY: APPROVED BY:
AS CONST
EXCEPT AS NOTED
NO.
REV.
DATE
R
R
DRWNDSGN CHKD RVWDSUPV APPD
PROJECT
ISSD
ID
F
CD
REV
DISCIPLINE
INTERFACE
E
7 8 9
D
C
B
A
US Army Corps of Engineers
Nashville District
SUBMITTED BY:
APPROVED BY:
P l m e
P l t e
F i m e
:5
:4 c u s e r s h e c x d e k d o c u m e n t s p w w o r k c e lr n d m s
N
.d g n
DESIGNED BY:
DRAWN BY:
CHECKED BY:
REVISION R CHIEF, ENGINEERING CONSTRUCTION DIVISION0
8C
C07
N_TVA
INITIAL ISSUE
XX
NONE
CHIEF, CIVIL DESIGN BRANCH
GENERAL NOTES,
LEGEND AND ABBREVIATIONS
INDENTIFICATION LETTER
SECTION
IS SHOWN
WHICH THE SECTION
DRAWING NUMBER ON
BDS
CDH
BDS CDH RFK MAM- NCB
CELRN
CURVE DATA
SECTION IDENTIFICATION
DETAIL IDENTIFICATION
ELECTRICAL ABBREVIATIONSABBREVIATIONS
CIVIL LEGEND
XXX X+XX X
A
XXX-XXX
XXX X+XX X
A
XXX-XXX
LOCK ADDITION
BDS
BDS
DOWNSTREAM LOCK EXCAVATION
KENTUCKY PROJECT
61N247-70
61N247-70
ROBERT F. KNOX MICHAEL A. MORRISON NICOLE C. BERGER
BENJAMIN L. ROHRBACH P.E.
VANESSA C. BATEMAN
P
P
P
P
P
P
IDENTIFIER
STRUCTURE
SEE NOTE 1
AT MAXIMUM SAG,
WIRE ELEVATION
DRAWING NUMBER
REFERENCE
411.0
415.0
413.0
490.0
490.0
490.0
490.0
LW-2666s2
LW-2284s1
LW-3068s1
LW-2986s1AA
LW-3395s1B
LW-5732s4A
LW-2171s1A
VOLTAGE
69 KV
69 KV
69 KV
161 KV
161 KV
161 KV
161 KV
STRUCTURE LOW CHORD ELEVATION
US 62/641 BRIDGE
I-24 BRIDGE
P&L RAILWAY BRIDGE
389.0
389.0
386.5
387.3RAILROAD & ACCESS BRIDGE
C B
C B
C B
C B
C B
C B
C B
C B
C B
C B
C B
C B
C B
C B
C B
CB 0200 100 200 400FT
SCALE: 1''= 200'
C B
C B
RI
PRAP
PAVED DITCH
0 4
PAVED DITCH
CEMETERY
RI
P
RAP
RI
P
RAP
RI
P
RAP
RI
P
RAP
RI
P
RAP
RI
P
RAP
RI
P
RAP
RI
P
RAP
RI
P
RAP
RI
P
RAP
BI
LLBOARD
RI
P
RAP
U .S
385 4
U .S
RI
P
RAP
RI
P
RAP
RI
P
RAP
RI
P
RAP
RI
P
RAP
RI
P
RAP
RI
P
RAP
U .S
U .S
HOPPER
RI
PRAP
RI
PRAP
RI
PRAP
RI
PRAP
RI
PRAP
RI
PRAP
W.E
5.1
W.E
6.1
RI
PRAP
RI
PRAP
RI
PRAP
RI
PRAP
RI
PRAP
8C
C07
N_TVA
---NCBMAMRFK-
INITIAL ISSUE
FLOW
SCALE:
H
F
G
E
3 4 5 6
D
C
B
A
2 3 4 5 6
REV NO.TASK COMPLETED BY:
DO NOT ALTER MANUALLY
C.A.D. DRAWING
ISSUED BY:
R
TENNESSEE VALLEY AUTHORITY
FOSSIL AND HYDRO ENGINEERING
AUTOCAD R
DATE
PLOT FACTOR:
REVIEWED BY: APPROVED BY:
AS CONST
EXCEPT AS NOTED
NO.
REV.
DATE
R
R
DRWNDSGN CHKD RVWDSUPV APPD
PROJECT
ISSD
ID
F
CD
REV
DISCIPLINE
INTERFACE
E
7 8 9
D
C
B
A
US Army Corps of Engineers
Nashville District
SUBMITTED BY:
APPROVED BY:
:5
:3 b a n e r
P l m e
P l t e
F i m e
DESIGNED BY:
DRAWN BY:
CHECKED BY:
REVISION R CHIEF, ENGINEERING CONSTRUCTION DIVISION
Z
1.3
RI
PRAP
RI
PRAP
RI
PRAP
RI
PRAP
RI
PRAP
RI
PRAP
E
N
E
N
320325
E
N
U .S
E
N
Z
0.
Z
8.
CB
CB
E
N
Z
8.
DENSE
VEGETATI
ON
0 3
BI
LLBOARD
U .S
E
N
Z
9.
E
Z
3.
Z
3.
OVERHEAD
PI
PES
TENNESSEE RIVER
KENTUCKY LAKE
NOTES:
BDS
DEK
LOCK ADDITION
GRAPHIC SCALE
BDS DEK
CHIEF, CIVIL DESIGN BRANCH
EXISTING KENTUCKY DAM
POWERHOUSE ISLAND
KENTUCKY LOCK, DAM
AND HYDRO PLANT,
LC
R E
L O
C A
T
U S
BOAT BASIN
MILE 22.4
THIS DRAWING
SEE NOTE 2 AND TABLE
TOWER RETAINING WALLS
EXISTING TRANSMISSION
1 2
4 5
6 7
C NEW 110' X 1200' LOCK
C EXISTING 110' X 600' LOCK
CELRN
1"= 200'
THESE FACILITIES.
PRIOR TO INITIATING ANY WORK ACTIVITIES IMPACTED BY
LINES ARE APPROXIMATE. CONTRACTOR SHALL FIELD VERIFY
2. LOCATION OF EXISTING TRANSMISSION TOWERS AND OVERHEAD
WITH EM-385-1-1.
DISTANCE FROM CONSTRUCTION EQUIPMENT IN ACCORDANCE
SHALL FIELD VERIFY ELEVATION AND MAINTAIN CLEAR
1. MAXIMUM SAG ELEVATIONS ARE APPROXIMATE. CONTRACTOR
RIVER CURRENT TRAINING DIKE
SMS
SMS
DOWNSTREAM LOCK EXCAVATION
KENTUCKY PROJECT
COFFERDAM
DOWNSTREAM CELLULAR
COFFERDAM
DOWNSTREAM CONCRETE
PROJECT LOCATION PLAN
ROBERT F. KNOX MICHAEL A. MORRISON NICOLE C. BERGER
BENJAMIN L. ROHRBACH P.E.
VANESSA C. BATEMAN
61N247-71
61N247-71
SEE DWG 61N247-74
DISPOSAL AREA "D"
TRANSMISSION LINE SAG ELEVATION
BRIDGE LOW CHORD ELEVATION
C
L O
C A
T
L
A I
L W
A Y
L
C B
C B
0100 50 100 200FT
SCALE: 1''= 100'
PAVED DITCH
C
EM
ET
ER
Y
R
IP
R
AP
R
IP
R
AP
R
IP
R
AP
R
IP
R
AP
R
IP
R
AP
R
IP
R
AP
R
IP
R
AP
B
IL
LB
O
AR
D
R
IP
R
AP
U .S
R
IP
R
AP
R
IP
R
AP
R
IP
R
AP
R
IP
R
AP
R
IP
R
AP
R
IP
R
AP
U .S
W .E
5.
.0
.9
.7
.1
.7
.3
.7
.9
.8
.93
.6
.6
FLOW
FLOW
S
B
NOTES:
H
F
G
E
3 4 5 6
D
C
B
A
2 3 4 5 6
REV NO.TASK COMPLETED BY:
DO NOT ALTER MANUALLY
C.A.D. DRAWING
ISSUED BY:
R
TENNESSEE VALLEY AUTHORITY
FOSSIL AND HYDRO ENGINEERING
AUTOCAD R
DATE
PLOT FACTOR:
REVIEWED BY: APPROVED BY:
AS CONST
EXCEPT AS NOTED
NO.
REV.
DATE
R
R
DRWNDSGN CHKD RVWDSUPV APPD
PROJECT
ISSD
ID
F
CD
REV
DISCIPLINE
INTERFACE
E
7 8 9
D
C
B
A
US Army Corps of Engineers
Nashville District
SUBMITTED BY:
APPROVED BY:
:5
:2 b a n e r
P l m e
P l t e
F i m e
DESIGNED BY:
DRAWN BY:
CHECKED BY:
REVISION R CHIEF, ENGINEERING CONSTRUCTION DIVISION0
C07
N_TVA
--NCBMAMRFK-
INITIAL ISSUE
SURVEY MONUMENT & BASELINES
BDS
DEK
LOCK ADDITION
BDS DEK
N
EXISTING KENTUCKY DAM
GRAPHIC SCALE
0 3
CHIEF, CIVIL DESIGN BRANCH
HORIZONTAL & VERTICAL CONTROL
N 54°16'48.6" E
PROJECT BASELINE
C EXISTING LOCKL
DOWNSTREAM CONCRETE COFFERDAM
L
OFS 2+15R
C FUTURE LOCK
BM-6
S
B
S
B
S
B
S
B
S T
A
B
S T
A
B
S T
A
B
S T
A
B
S T
A
B
S T
A
B
S T
A
B
S T
A
B
S T
A
B
S T
A
B
OFS 4+00R
OFS 3+00R
OFS 2+00R
OFS 1+00R
OFS 1+00L
OFS 2+00L
OFS 0+00
OFS XX+XXL - OFFSET STATIONING LEFT OF BASE LINE.
OFS XX+XXR - OFFSET STATIONING RIGHT OF BASE LINE.
STA XX+XXB - EXISTING LOCK CHAMBER DOWNSTREAM STATIONING.
STA XX+XXA - EXISTING LOCK CHAMBER UPSTREAM STATIONING.
LEGEND
PLAN
SCALE: 1"=100'
BM-4
BM-2 BM-1
BM-3
P
P
P
P
P P
P
P P P
P
PP
P P
P
6.
6.
9.
.8
.5
1.
.9
1.
P
P
P
P
P
P
P
P
P
P
P
P P P P P P
P
P
P
P
P
P
1.
1.
9.
.7
.1
.5
.9
.1
.6
.4
9.
.2
.7
.2
.7
.3
.4
9.
.1
9.
9.
.3
9.
9.
9.
.3
9.
9.
.1
.8
.1
.8
.1
.1
9.
.8
.8
.3
.1
.8
.1
.3
.1
.7
1.
.9
1.
1.
6 3
1.
.1
.1
.7
.2
.1
9.
P
P P
P
P
1.
1.
P
P
P
P
P
P
.7
.7
.3
.2
.7
.7
.9
.8
1.
1.
1.
1.
1.
1.
1.
1.
1.
1.
P
P
PPPPPPPPPPP
P
P P P P P P P P P P P
P3 1.
1.
1.
1.
1.
1.
1.
1.
2 3
1.
1.
1.
2 3
.3
.7
.6 3
.5
.4
.5
.4
.3
9.
.6
.5
.3
9.
P
P P P P P P P P P P P P P
P P
P
6.
.4
.6
6.
.7
6.
.5
6.
1.
1.
P
.3
BM-7
BM-8
2. VERTICAL CONTROL IS BASED ON VERTICAL DATUM NGVD 29.
NAD 83 (GEOID 03).
STATE PLANE COORDINATE SYSTEM, HORIZONTAL DATUM
1. HORIZONTAL CONTROL IS BASED ON KENTUCKY SOUTH
BM-4 1898391.528 905958.434 381.75 BRASS DISK IN CONCRETE
BM-2 1898486.597 906026.803 381.79 BRASS DISK IN CONCRETE
BM-1 1898162.550 906477.450 381.76 BRASS DISK IN CONCRETE
POINT NORTHING EASTING ELEVATION DESCRIPTION
HORIZONTAL AND VERTICAL CONTROL
BM-3 1898067.481 906409.097 381.79 BRASS DISK IN CONCRETE
BM-8 1899458.862 905360.596 349.05 BRASS DISK IN CONCRETE
STATION
STA. 0+15B, 58.53' R
BM-6 1898106.286 906455.431 - LOCK STATION ORIGIN POINT
BM-7 1899107.216 904608.401 342.39 BRASS DISK IN CONCRETE CURB
STA. 0+15B, 58.57' L
STA. 0+00 U/S & D/S
STA. 5+70B, 58.52' R
STA. 5+70B, 58.58' L
CELRN
1"= 100'
SMS
SMS
DOWNSTREAM LOCK EXCAVATION
TRAINING DIKE
RIVER CURRENT
GUARD CELLS
WALL
TIED Z-PILE
RETAINING WALLS
EXISTING TRANSMISSION TOWER
61N247-73
61N247-73
ROBERT F. KNOX MICHAEL A. MORRISON NICOLE C. BERGER
BENJAMIN L. ROHRBACH P.E.
L O
C A
T
I
L W
A Y
L O
C A
T
CELLULAR
DOWNSTREAM
KENTUCKY LAKE
R
IP
R
AP
POWERHOUSE ISLAND
SCALE: 1" = 20'-0"
STATION 3+00B
SCALE: 1" = 20'-0"
STATION 4+00B
400400
0+00 5+00 6+001+00 2+00 3+00 4+00
10'-0"
10'-0"
APPROXIMATE TOP OF ROCK
APPROXIMATE TOP OF ROCK
LOCK FLOOR EL 285.00
5'-0"
5'-0"
2'-6"
M-6VARIES L-6
CUTOFF WALL
LC NEW LOCK, 2+15R
EL 295.57
EL 287.00
EL 276.00
99'-0"
EL 388.00
EL 382.00EL 382.00
EL 340.00
EL 330.00
EL 320.00
EL 310.00
EL.305.50 +/-
EL 297.00
17'-5"+/-
EL 282.00
EL 276.00
35'-0"
EL.283.21 +/-
5+40
400400
400400
0+00 1+00 2+00 3+00 4+00 5+00
A P P
R O
X I
M A T E
T
O
F
C K
APPROXIMATE TOP OF ROCK
EXISTING SURFACE
EXISTING SURFACE
EXI
STI
NG
SURFACE
EL.283.21 +/-
EL 340.00
EL 382.00
EL 276.00
40'-0"
EL 330.00
M-97'-0"
VARIES
EL 276.00
LC NEW LOCK, 2+15R
EL-10
EL 303.00
EL 382.00
80'-0"
L-9
LOCK FLOOR EL 285.00
EL-13
FUTURE LAND WALL
INITIAL ISSUE
020 20 40FT
SCALE: 1''= 20'
GRAPHIC SCALE
CHIEF, CIVIL DESIGN BRANCH
VANESSA C. BATEMAN
BENJAMIN L. ROHRBACH P.E.
MICHAEL A. MORRISON NICOLE C. BERGER
SCALE:
H
F
G
E
3 4 5 6
D
C
B
A
2 3 4 5 6
REV NO.TASK COMPLETED BY:
DO NOT ALTER MANUALLY
C.A.D. DRAWING
ISSUED BY:
R
TENNESSEE VALLEY AUTHORITY
FOSSIL AND HYDRO ENGINEERING
AUTOCAD R
DATE
PLOT FACTOR:
REVIEWED BY: APPROVED BY:
AS CONST
EXCEPT AS NOTED
NO.
REV.
DATE
R
R
DRWNDSGN CHKD RVWDSUPV APPD
PROJECT
ISSD
ID
F
CD
REV
DISCIPLINE
INTERFACE
E
7 8 9
D
C
B
A
US Army Corps of Engineers
Nashville District
SUBMITTED BY:
APPROVED BY:
:5 b a n e r
P l m e
P l t e
F i m e
DESIGNED BY:
DRAWN BY:
CHECKED BY:
REVISION R CHIEF, ENGINEERING CONSTRUCTION DIVISION
ANSI E
1" = 20'
LOCK EXCAVATION
MSE
MSE
LOCK ADDITION
MSE MSE
SECTIONS AT 03+00 & 04+00B
61N651-21
ALD
ALD
61N651-21
EXCAVATION SECTIONS
ROBERT F. KNOX
1.5
NOTES:
LEGEND:
EXCAVATION GRADE
APPROXIMATE TOP OF ROCK
FUTURE LOCK MONOLITH
LOCATIONS.
3. SEE DRAWING 61N651-20 FOR CROSS SECTION
SEE DRAWING 822N3066.
AND DEVELOPED FROM EXPLORATORY BORINGS,
2. TOP OF ROCK ELEVATIONS ARE APPROXIMATE
1. ELEVATION IN FEET ABOVE MSL, NGVD29.
STATION 5+00B
SCALE: 1" = 20'-0"
STATION 6+00B
400400
400400
0+00 1+00 2+00 3+00 4+00 5+00
EXISTING SURFACE
APPROXIMATE TOP OF ROCK
A P P
R O
X I
M A
C K
EL.282.55 +/-
EL 340.00
EL 382.00
EL 276.00
40'-0"
M-11
EL 276.00
VARIES
LC NEW LOCK, 2+15R
EL-15
CONTROL
ROOM
SHOP
EL 303.00
EL 276.00
EL 382.00
80'-0"
L-11
LOCK FLOOR EL 285.00
L-13
FUTURE LAND WALL
ROADWAY
US EMBANKMENT
10'-0"
---MSE-
INITIAL ISSUE
KENTUCKY PROJECT
LOCK EXCAVATION
ALD
CHIEF, CIVIL DESIGN BRANCH
LOCK ADDITION
SCALE:
H
F
G
E
3 4 5 6
D
C
B
A
2 3 4 5 6
REV NO.TASK COMPLETED BY:
DO NOT ALTER MANUALLY
C.A.D. DRAWING
ISSUED BY:
R
TENNESSEE VALLEY AUTHORITY
FOSSIL AND HYDRO ENGINEERING
AUTOCAD R
DATE
PLOT FACTOR:
REVIEWED BY: APPROVED BY:
AS CONST
EXCEPT AS NOTED
NO.
REV.
DATE
R
R
DRWNDSGN CHKD RVWDSUPV APPD
PROJECT
ISSD
ID
F
CD
REV
DISCIPLINE
INTERFACE
E
7 8 9
D
C
B
A
US Army Corps of Engineers
Nashville District
SUBMITTED BY:
APPROVED BY:
:5
:1 c u s e r s h e c x d e k d o c u m e n t s p w w o r k c e lr n d m s
N .d g n
P l m e
P l t e
F i m e
DESIGNED BY:
DRAWN BY:
CHECKED BY:
REVISION R CHIEF, ENGINEERING CONSTRUCTION DIVISION
020 10 20 40FT
SCALE: 1''= 20'
MSE
MSE
61N651-22
61N651-22
MSE MSE
2018/01/12
SECTIONS AT 5+00B & 6+00B
EXCAVATION SECTIONS
1.5
400400
400400
0+00 1+00 2+00 3+00 4+00 5+00 5+40
EXISTING SURFACE
TOR
EL 340.00
M-13VARIES
EL 330.00
7'-0"
40'-0"
EL 276.00EL 276.00
LOCK FLOOR EL 285.00
EL 382.00
EL.282.35 +/-
EL 303.00
EL 276.00
EL 382.00
80'-0"
EXISTING SURFACE
10'-0"
LC NEW LOCK, 2+15R
EL-17
APPROXIMATE TOP OF ROCK
GRAPHIC SCALE
SEE NOTE 3
1.5
VANESSA C. BATEMAN
BENJAMIN L. ROHRBACH P.E.
MICHAEL A. MORRISON NICOLE C. BERGERROBERT F. KNOX
SEE NOTE 3
NOTES:
LEGEND:
EXCAVATION GRADE
APPROXIMATE TOP OF ROCK
FUTURE LOCK MONOLITH
LOCATIONS.
5. SEE DRAWING 61N651-20 FOR CROSS SECTION
AS CATCHMENT FOR OVERBURDEN SLOPE.
AT TOP OF ROCK FOR WORKER SAFETY AND
4. CONTRACTOR TO CONSTRUCT A 10 FT. BENCH
A BENCH TO PROVIDE SAFETY AND STABILITY.
CONTRACTOR MAY BE REQUIRED TO EXCAVATE
AND DOES NOT REQUIRE PRESPLITTING.
3. THIS IS NOT A FINAL EXCAVATION FACE
SEE DRAWING 822N3066.
AND DEVELOPED FROM EXPLORATORY BORINGS,
STATION 7+00B
SCALE: 1" = 20'-0"
STATION 8+00B
400400
400400
0+00 1+00 2+00 3+00 4+00 5+00 5+40
EXISTING SURFACE
LOCK FLOOR EL 285.00
EL 340.00
M-14
VARIES
EL 330.00
7'-0"
40'-0"
EL 382.00
EL.282.35 +/-
EL 303.00
EL 276.00
SECTION A-A
MONOLITH L-18
80'-0"
EL 382.00
L-18A
LC NEW LOCK, 2+15R
APPROXIMATE TOP OF ROCK
10'-0"
10'-0"
1.5
400400
400400
0+00 1+00 2+00 3+00 4+00 5+00
EL-16
EXISTING SURFACE
M-17VARIES
EL 320.00
7'-0"
EL 310.00
46'-0"
LOCK FLOOR EL 285.00
EL 382.00
EL 330.00
7'-0"
7'-0"
EL 303.00
EL 276.00
80'-0"
EL 382.00
L-20
LC NEW LOCK, 2+15R
EL-18A
APPROXIMATE TOP OF ROCK
APPROXIMATE TOP OF ROCK
10'-0"
10'-0"
SCALE: 1''= 20'
GRAPHIC SCALE
CHIEF, CIVIL DESIGN BRANCH
VANESSA C. BATEMAN
BENJAMIN L. ROHRBACH P.E.
MICHAEL A. MORRISON NICOLE C. BERGER
SCALE:
H
F
G
E
3 4 5 6
D
C
B
A
2 3 4 5 6
REV NO.TASK COMPLETED BY:
DO NOT ALTER MANUALLY
C.A.D. DRAWING
ISSUED BY:
R
TENNESSEE VALLEY AUTHORITY
FOSSIL AND HYDRO ENGINEERING
AUTOCAD R
DATE
PLOT FACTOR:
REVIEWED BY: APPROVED BY:
AS CONST
EXCEPT AS NOTED
NO.
REV.
DATE
R
R
DRWNDSGN CHKD RVWDSUPV APPD
PROJECT
ISSD
ID
F
CD
REV
DISCIPLINE
INTERFACE
E
7 8 9
D
C
B
A
US Army Corps of Engineers
Nashville District
SUBMITTED BY:
APPROVED BY:
:5
:0 b a n e r
P l m e
P l t e
F i m e
DESIGNED BY:
DRAWN BY:
LOCK EXCAVATION
MSE
MSE
LOCK ADDITION
MSE MSE
SECTIONS AT 07+00B & 08+00B
61N651-23
ALD
61N651-23
1.5
SEE NOTE 4
SEE NOTE 4
NOTES:
LEGEND:
EXCAVATION GRADE
APPROXIMATE TOP OF ROCK
FUTURE LOCK MONOLITH
LOCATIONS.
5. SEE DRAWING 61N651-20 FOR CROSS SECTION
A BENCH TO PROVIDE SAFETY AND STABILITY.
CONTRACTOR MAY BE REQUIRED TO EXCAVATE
AND DOES NOT REQUIRE PRESPLITTING.
4. THIS IS NOT A FINAL EXCAVATION FACE
AS CATCHMENT FOR OVERBURDEN SLOPE.
AT TOP OF ROCK FOR WORKER SAFETY AND
3. CONTRACTOR TO CONSTRUCT A 10 FT. BENCH
SEE DRAWING 822N3066.
AND DEVELOPED FROM EXPLORATORY BORINGS,
STATION 9+00B
STATION 10+00B
---MSE-
INITIAL ISSUE
KENTUCKY PROJECT
LOCK EXCAVATION
ALD
SCALE:
H
F
G
E
3 4 5 6
D
C
B
A
2 3 4 5 6
REV NO.TASK COMPLETED BY:
DO NOT ALTER MANUALLY
C.A.D. DRAWING
ISSUED BY:
R
TENNESSEE VALLEY AUTHORITY
FOSSIL AND HYDRO ENGINEERING
AUTOCAD R
DATE
PLOT FACTOR:
REVIEWED BY: APPROVED BY:
AS CONST
EXCEPT AS NOTED
NO.
REV.
DATE
R
R
DRWNDSGN CHKD RVWDSUPV APPD
PROJECT
ISSD
ID
F
CD
REV
DISCIPLINE
INTERFACE
E
7 8 9
D
C
B
A
US Army Corps of Engineers
Nashville District
SUBMITTED BY:
APPROVED BY:
:5 c u s e r s h e c x d e k d o c u m e n t s p w w o r k c e lr n d m s
N .d g n
P l m e
P l t e
F i m e
DESIGNED BY:
DRAWN BY:
CHECKED BY:
REVISION R CHIEF, ENGINEERING CONSTRUCTION DIVISION
MSE
61N651-24
61N651-24
SECTIONS AT 9+00B & 10+00B
2018/01/12
EXCAVATION SECTIONS
390390
390390
0+00 1+00 2+00 3+00 4+00 5+00
390390
390390
0+00 1+00 2+00 3+00 4+00 5+00
VARIES
LOCK FLOOR EL 285.00
EL 382.00
EL 330.00
M-19
EL 276.00
40'-0"
EL 320.00
7'-0"
EL 310.00
EL 300.00
7'-0"
7'-0" EL 303.00
EL 276.00
EL 382.00
80'-0"
L-19
EXISTING SURFACE
EL-22
LC NEW LOCK, 2+15R
APPROXI
MATE
TOP
OF
ROCK
40'-0"
EL 382.00
EL 330.00
EL 276.00
LOCK FLOOR EL 285.00
VARIES
EXI
STI
NG
SURFACE
W/
RI
P
RAP
EL 303.00
EL 276.00
EL 382.00
80'-0"
L-21
EL-25
LC NEW LOCK, 2+15R
M-21
APPROXIMATE TOP OF ROCK
APPROXIMATE TOP OF ROCK
EXCAVATION LIMITS
FUTURE MIDDLE WALL FUTURE LAND WALL
FUTURE MIDDLE WALL FUTURE LAND WALL
10'-0"
10'-0"
10'-0"
10'-0"
GRAPHIC SCALE
VANESSA C. BATEMAN
BENJAMIN L. ROHRBACH P.E.
MICHAEL A. MORRISON NICOLE C. BERGERROBERT F. KNOX
1.5
1.5
NOTES:
LEGEND:
EXCAVATION GRADE
APPROXIMATE TOP OF ROCK
FUTURE LOCK MONOLITH
LOCATIONS.
4. SEE DRAWING 61N651-20 FOR CROSS SECTION
AS CATCHMENT FOR OVERBURDEN SLOPE.
AT TOP OF ROCK FOR WORKER SAFETY AND
3. CONTRACTOR TO CONSTRUCT A 10 FT. BENCH
SEE DRAWING 822N3066.
AND DEVELOPED FROM EXPLORATORY BORINGS,
STATION 11+00B
STATION 12+00B
SCALE: 1" = 20'-0"
SCALE: 1" = 20'-0"
390390
390390
0+00 1+00 2+00 3+00 4+00 5+00
390390
390390
0+00 1+00 2+00 3+00 4+00 36'-0"
46'-6"
F
36'-0"
SCALE: 1''= 20'
GRAPHIC SCALE
CHIEF, CIVIL DESIGN BRANCH
VANESSA C. BATEMAN
BENJAMIN L. ROHRBACH P.E.
MICHAEL A. MORRISON NICOLE C. BERGER
SCALE:
H
F
G
E
3 4 5 6
D
C
B
A
2 3 4 5 6
REV NO.TASK COMPLETED BY:
DO NOT ALTER MANUALLY
C.A.D. DRAWING
ISSUED BY:
R
TENNESSEE VALLEY AUTHORITY
FOSSIL AND HYDRO ENGINEERING
AUTOCAD R
DATE
PLOT FACTOR:
REVIEWED BY: APPROVED BY:
AS CONST
EXCEPT AS NOTED
NO.
REV.
DATE
R
R
DRWNDSGN CHKD RVWDSUPV APPD
PROJECT
ISSD
ID
F
CD
REV
DISCIPLINE
INTERFACE
E
7 8 9
D
C
B
A
US Army Corps of Engineers
Nashville District
SUBMITTED BY:
APPROVED BY:
:5
:5
P
M b a n e r
P l m e
P l t e
F i m e
DESIGNED BY:
DRAWN BY:
LOCK EXCAVATION
MSE
MSE
LOCK ADDITION
MSE MSE
SECTIONS AT 11+00B & 12+00B
61N651-25
ALD
61N651-25
EXI
STI
NG
SURFACE
EL 303.00
EL 276.00
EL 382.00
L-23
75'-0"
HIGHEST LOCK FLOOR EL. 285.00
L
NAVIGATION CHANNEL
C EXISTING LOCK AND
EL. 343.50
F
M-23M-23C
LC NEW LOCK, 2+15R
EXCAVATION LINE
15'H X 19'W
CULVERT
EL.382
EL. 276
10'-0"
APPROXIMATE TOP OF ROCK
APPROXIMATE TOP OF ROCK
EL.382
EL. 276
EL.343.5
M-25
CONCRETE COFFERDAM
M-25C
EL 303.00
EL 276.00
EL 382.00
80'-0"
L-25
HIGHEST LOCK FLOOR EL. 285.00
EXIS
TING S
URFACE
LC NEW LOCK, 2+15R
10'-0"
APPROXIMATE TOP OF ROCK
A P P R
O X I
M A T E
T
R
O C
K
FUTURE MIDDLE WALL
FUTURE LAND WALL
FUTURE MIDDLE WALL FUTURE LAND WALL
#9 @ 12 E.W.
WALL ARMOR
FEATURES)
AND UNKNOWN ROCK
TO CONSTRUCTION
(LINE VARIES DUE
EXCAVATION LINE
EL. 280 +/-
EL. 284+/-
10'-0"
ROBERT F. KNOX
1.5
1.5
NOTES:
LEGEND:
FUTURE LOCK MONOLITH
COFFERDAM
EXISTING SEGMENTAL
EXCAVATION GRADE
APPROXIMATE TOP OF ROCK
LOCATIONS.
4. SEE DRAWING 61N651-20 FOR CROSS SECTION
AS CATCHMENT FOR OVERBURDEN SLOPE.
AT TOP OF ROCK FOR WORKER SAFETY AND
3. CONTRACTOR TO CONSTRUCT A 10 FT. BENCH
SEE DRAWING 822N3066.
AND DEVELOPED FROM EXPLORATORY BORINGS,
STATION 13+00B
STATION 14+00B
SCALE: 1" = 20'-0"
SCALE: 1" = 20'-0"
COFFERDAM
EXISTING SEGMENTAL
---MSE-
LOCK EXCAVATION
ALD
SCALE:
H
F
G
E
3 4 5 6
D
C
B
A
2 3 4 5 6
REV NO.TASK COMPLETED BY:
DO NOT ALTER MANUALLY
C.A.D. DRAWING
ISSUED BY:
R
TENNESSEE VALLEY AUTHORITY
FOSSIL AND HYDRO ENGINEERING
AUTOCAD R
DATE
PLOT FACTOR:
REVIEWED BY: APPROVED BY:
AS CONST
EXCEPT AS NOTED
NO.
REV.
DATE
R
R
DRWNDSGN CHKD RVWDSUPV APPD
PROJECT
ISSD
ID
F
CD
REV
DISCIPLINE
INTERFACE
E
7 8 9
D
C
B
A
US Army Corps of Engineers
Nashville District
SUBMITTED BY:
APPROVED BY:
:5 c u s e r s h e c x d e k d o c u m e n t s p w w o r k c e lr n d m s
N .d g n
P l m e
P l t e
F i m e
DESIGNED BY:
DRAWN BY:
CHECKED BY:
REVISION R CHIEF, ENGINEERING CONSTRUCTION DIVISION
ANSI F
61N651-26
61N651-26
SECTIONS AT 13+00B & 14+00B
MSE
MSE MSE
EXCAVATION SECTIONS
VANESSA C. BATEMAN
BENJAMIN L. ROHRBACH P.E.
MICHAEL A. MORRISON NICOLE C. BERGER
390390
390390
0+00 1+00 2+00 3+00 4+00 4+20
390390
390390
0+00 1+00 2+00 3+00 4+00 5+00
260 260
ROBERT F. KNOX
GRAPHIC SCALE
36'-0"
36'-0"
EL.382
EL.343.5
M-27M-27C
EL. 270
#9 @ 12 E.W.
#9 @ 12 E.W.
WALL ARMOR
EL 303.00
EL 276.00
EL 382.00
80'-0"
L-27
HIGHEST LOCK FLOOR EL. 285.00
EXISTING SURFACE
LC NEW LOCK, 2+15R
EL. 284+/-
APPROXI
MATE
TOP
OF
ROCK
APPROXIMATE TOP OF ROCK
FUTURE MIDDLE WALL FUTURE LAND WALL
EL.382
M-28M-28C
EL.343.5
EL. 270
#9 @ 12 E.W.
WALL ARMOR
EL 303.00
EL 276.00
EL 382.00
80'-0"
L-28
HIGHEST LOCK FLOOR EL. 285.00
EXISTING SURFACE
LC NEW LOCK, 2+15R
APPROXIMATE TOP OF ROCK
APPROXIMATE TOP OF ROCK
FUTURE MIDDLE WALL FUTURE LAND WALL
10'-0"
10'-0"
10'-0"
1.5
1.5
NOTES:
LEGEND:
FUTURE LOCK MONOLITH
APPROXIMATE TOP OF ROCK
EXCAVATION GRADE
LOCATIONS.
4. SEE DRAWING 61N651-20 FOR CROSS SECTION
AS CATCHMENT FOR OVERBURDEN SLOPE.
AT TOP OF ROCK FOR WORKER SAFETY AND
3. CONTRACTOR TO CONSTRUCT A 10 FT. BENCH
SEE DRAWING 822N3066.
AND DEVELOPED FROM EXPLORATORY BORINGS,
2. TOP OF ROCK ELEVATIONS ARE APPROXIMATE
EL. 284+/-
STATION 15+00B
350350
350350
0+00 1+00 2+00 3+00 4+00
5+00
EL.343.5
EL. 261
EL.345
35'-0"
EL.289.0
HIGHEST LOCK FLOOR EL. 285.00
SCALE: 1''= 20'
GRAPHIC SCALE
CHIEF, CIVIL DESIGN BRANCH
VANESSA C. BATEMAN
BENJAMIN L. ROHRBACH P.E.
MICHAEL A. MORRISON NICOLE C. BERGER
SCALE:
H
F
G
E
3 4 5 6
D
C
B
A
2 3 4 5 6
REV NO.TASK COMPLETED BY:
DO NOT ALTER MANUALLY
C.A.D. DRAWING
ISSUED BY:
R
TENNESSEE VALLEY AUTHORITY
FOSSIL AND HYDRO ENGINEERING
AUTOCAD R
DATE
PLOT FACTOR:
REVIEWED BY: APPROVED BY:
AS CONST
EXCEPT AS NOTED
NO.
REV.
DATE
R
R
DRWNDSGN CHKD RVWDSUPV APPD
PROJECT
ISSD
ID
F
CD
REV
DISCIPLINE
INTERFACE
E
7 8 9
D
C
B
A
US Army Corps of Engineers
Nashville District
SUBMITTED BY:
APPROVED BY:
:5 b a n e r
P l m e
P l t e
F i m e
DESIGNED BY:
DRAWN BY:
CHECKED BY:
EL. 284+/-
LOCK EXCAVATION
MSE
MSE
LOCK ADDITION
MSE MSE
61N651-27
ALD
61N651-27
EXCAVATION SECTION
SECTION AT 15+00B
M-31
M-31C
EL 303.00
EL 276.00
EL 382.00
80'-0"
L-31
EXISTING SURFACE
LC NEW LOCK, 2+15R
10'-0"
APPROXIMATE TOP OF ROCKAPPROXIMATE TOP OF ROCK
FUTURE MIDDLE WALL FUTURE LAND WALL
ROBERT F. KNOX
COFFERDAM
EXISTING SEGMENTAL
1.5
NOTES:
LEGEND:
FUTURE LOCK MONOLITH
APPROXIMATE TOP OF ROCK
EXCAVATION GRADE
LOCATIONS.
4. SEE DRAWING 61N651-20 FOR CROSS SECTION
AS CATCHMENT FOR OVERBURDEN SLOPE.
AT TOP OF ROCK FOR WORKER SAFETY AND
3. CONTRACTOR TO CONSTRUCT A 10 FT. BENCH
SEE DRAWING 822N3066.
AND DEVELOPED FROM EXPLORATORY BORINGS,
B
B
285 285
276 276
282 282
303303
EXCAVATION LIMITS
CL EXISTING LOCK
EL 25
EL 23
EL 24
EL 10EL 11EL 12EL 13EL 14EL 15EL 16EL 17EL 18AEL 18BEL 19EL 20EL 21EL 22 EL 2EL 3EL 4EL 5EL 6EL 7EL 8EL 9
.5
.1
L
OFFSET 2+15R
C FUTURE LOCK
OFFSET 1+75R
L-8 L-7 L-6 L-5 L-4
M-5 M-4
11A
2A
3A
FLOW
NOTES:
GRAPHIC SCALE
VANESSA C. BATEMAN
BENJAMIN L. ROHRBACH P.E.
MICHAEL A. MORRISON NICOLE C. BERGER
LEGEND:
WITH ELEVATION
EXCAVATION LIMITS
1. COORDINATES IN KENTUCKY STATE PLANE,
NAD 83 (FT.) DATUM.
2. ELEVATION IN FEET ABOVE MSL, NGVD29.
3.
CONDTIONS ENCOUNTERED.
AND MAY VARY BASED ON ACTUAL
EXCAVATION LIMITS ARE APPROXIMATE
INITIAL ISSUE
1" = 50'
MSE ALD MSE
822N3060
822N3060
MSE
ALD
2018/02/08
H
F
G
E
3 4 5 6
D
C
B
A
2 3 4 5 6
REV NO.TASK COMPLETED BY:
DO NOT ALTER MANUALLY
C.A.D. DRAWING
ISSUED BY:
R
TENNESSEE VALLEY AUTHORITY
FOSSIL AND HYDRO ENGINEERING
AUTOCAD R
DATE
PLOT FACTOR:
REVIEWED BY: APPROVED BY:
AS CONST
EXCEPT AS NOTED
NO.
REV.
DATE
R
R
DRWNDSGN CHKD RVWDSUPV APPD
PROJECT
ISSD
ID
F
CD
REV
DISCIPLINE
INTERFACE
E
7 8 9
D
C
B
A
US Army Corps of Engineers
Nashville District
SUBMITTED BY:
APPROVED BY:
:4 c u s e r s h e c x d e k d o c u m e n t s p w w o r k c e lr n d m s
N .d g n
P l m e
P l t e
F i m e
DESIGNED BY:
DRAWN BY:
CHECKED BY:
REVISION R CHIEF, ENGINEERING CONSTRUCTION DIVISION
050 25 50 100FT
SCALE: 1''= 50'
ROCK EXCAVATION PLAN
B
B
B
FLOW
LC EXISTING LOCK
S T
A
B
S
B
S
B
S T
A
B
S T
A
B
S T
A
B
S T
A
B
S T
A
B
S T
A
B
S T
A
B
S
B
S
B
S
B
S
A
S
S
B
S
B
S
B
S
B
B
B
B
B
B
B
S T
A
S T
A
B
S T
A
S T
A
S T
A
S T
A
S T
A
S T
A
S T
A
S T
A
S T
A
B
B
B
B
B
B
B
N
C B
C B
B
B
CL EXISTING LOCK
EL 25
EL 23
EL 24
EL 10EL 11EL 12EL 13EL 14EL 15EL 16EL 17EL 18AEL 18BEL 19EL 20EL 21EL 22 EL 2EL 3EL 4EL 5EL 6EL 7EL 8EL 9
L
OFFSET 2+15R
C FUTURE LOCK
L-8 L-7 L-6 L-5 L-4
M-5 M-4
11A
2A
3A
FLOW
NOTES:
GRAPHIC SCALE
VANESSA C. BATEMAN
BENJAMIN L. ROHRBACH P.E.
MICHAEL A. MORRISON NICOLE C. BERGER
LEGEND:
WITH ELEVATION
EXCAVATION LIMITS
ELEVATION IN FEET ABOVE MSL, NGVD29.2.
COORDINATES IN KENTUCKY STATE PLANE, 1.
H
F
G
E
3 4 5 6
D
C
B
A
2 3 4 5 6
REV NO.TASK COMPLETED BY:
DO NOT ALTER MANUALLY
C.A.D. DRAWING
ISSUED BY:
R
TENNESSEE VALLEY AUTHORITY
FOSSIL AND HYDRO ENGINEERING
AUTOCAD R
DATE
PLOT FACTOR:
REVIEWED BY: APPROVED BY:
AS CONST
EXCEPT AS NOTED
NO.
REV.
DATE
R
R
DRWNDSGN CHKD RVWDSUPV APPD
PROJECT
ISSD
ID
F
CD
REV
DISCIPLINE
INTERFACE
E
7 8 9
D
C
B
A
US Army Corps of Engineers
Nashville District
SUBMITTED BY:
APPROVED BY:
:4 c u s e r s h e c x d e k d o c u m e n t s p w w o r k c e lr n d m s
N .d g n
P l m e
P l t e
F i m e
DESIGNED BY:
DRAWN BY:
CHECKED BY:
REVISION R CHIEF, ENGINEERING CONSTRUCTION DIVISION
050 25 50 100FT
SCALE: 1''= 50'
PHASE I
822N3061
822N3061
MSE
ALD
MSE
ROCK EXCAVATION PLAN
B
B
B
B
B
FLOW
LC EXISTING LOCK
S T
A
B
S
B
S
B
S T
A
B
S T
A
B
S T
A
B
S T
A
B
S T
A
B
S T
A
B
S T
A
B
S
B
S
B
S
B
S
A
S
S
B
S
B
S
B
S
B
B
B
B
B
B
B
S T
A
S T
A
B
S T
A
S T
A
S T
A
S T
A
S T
A
S T
A
S T
A
S T
A
S T
A
B
B
B
B
B
B
B
N
C B
B
B
CL EXISTING LOCK
EL 25
EL 23
EL 24
EL 10EL 11EL 12EL 13EL 14EL 15EL 16EL 17EL 18AEL 18BEL 19EL 20EL 21EL 22 EL 2EL 3EL 4EL 5EL 6EL 7EL 8EL 9
L
OFFSET 2+15R
C FUTURE LOCK
L-8 L-7 L-6 L-5 L-4
M-5 M-4
11A
2A
3A
FLOW
NOTES:
GRAPHIC SCALE
VANESSA C. BATEMAN
BENJAMIN L. ROHRBACH P.E.
MICHAEL A. MORRISON NICOLE C. BERGER
LEGEND:
WITH ELEVATION
H
F
G
E
3 4 5 6
D
C
B
A
2 3 4 5 6
REV NO.TASK COMPLETED BY:
DO NOT ALTER MANUALLY
C.A.D. DRAWING
ISSUED BY:
R
TENNESSEE VALLEY AUTHORITY
FOSSIL AND HYDRO ENGINEERING
AUTOCAD R
DATE
PLOT FACTOR:
REVIEWED BY: APPROVED BY:
AS CONST
EXCEPT AS NOTED
NO.
REV.
DATE
R
R
DRWNDSGN CHKD RVWDSUPV APPD
PROJECT
ISSD
ID
F
CD
REV
DISCIPLINE
INTERFACE
E
7 8 9
D
C
B
A
US Army Corps of Engineers
Nashville District
SUBMITTED BY:
APPROVED BY:
:4 c u s e r s h e c x d e k d o c u m e n t s p w w o r k c e lr n d m s
N .d g n
P l m e
P l t e
F i m e
DESIGNED BY:
DRAWN BY:
CHECKED BY:
REVISION R CHIEF, ENGINEERING CONSTRUCTION DIVISION
PHASE II
822N3062
822N3062
MSE
ALD
MSE
ROCK EXCAVATION PLAN
B
B
B
B
B
FLOW
LC EXISTING LOCK
S T
A
B
S
B
S
B
S T
A
B
S T
A
B
S T
A
B
S T
A
B
S T
A
B
S T
A
B
S T
A
B
S
B
S
B
S
B
S
A
S
S
B
S
B
S
B
S
B
B
B
B
B
B
B
S T
A
S T
A
B
S T
A
S T
A
S T
A
S T
A
S T
A
S T
A
S T
A
S T
A
S T
A
B
B
B
B
B
B
B
N
C B
C B
B
B
282282
CL EXISTING LOCK
EL 25
EL 23
EL 24
EL 10EL 11EL 12EL 13EL 14EL 15EL 16EL 17EL 18AEL 18BEL 19EL 20EL 21EL 22 EL 2EL 3EL 4EL 5EL 6EL 7EL 8EL 9
L
OFFSET 2+15R
C FUTURE LOCK
L-8 L-7 L-6 L-5 L-4
M-5 M-4
11A
2A
3A
FLOW
NOTES:
GRAPHIC SCALE
VANESSA C. BATEMAN
BENJAMIN L. ROHRBACH P.E.
MICHAEL A. MORRISON NICOLE C. BERGER
LEGEND:
WITH ELEVATION
H
F
G
E
3 4 5 6
D
C
B
A
2 3 4 5 6
REV NO.TASK COMPLETED BY:
DO NOT ALTER MANUALLY
C.A.D. DRAWING
ISSUED BY:
R
TENNESSEE VALLEY AUTHORITY
FOSSIL AND HYDRO ENGINEERING
AUTOCAD R
DATE
PLOT FACTOR:
REVIEWED BY: APPROVED BY:
AS CONST
EXCEPT AS NOTED
NO.
REV.
DATE
R
R
DRWNDSGN CHKD RVWDSUPV APPD
PROJECT
ISSD
ID
F
CD
REV
DISCIPLINE
INTERFACE
E
7 8 9
D
C
B
A
US Army Corps of Engineers
Nashville District
SUBMITTED BY:
APPROVED BY:
:4 c u s e r s h e c x d e k d o c u m e n t s p w w o r k c e lr n d m s
N .d g n
P l m e
P l t e
F i m e
DESIGNED BY:
DRAWN BY:
CHECKED BY:
REVISION R CHIEF, ENGINEERING CONSTRUCTION DIVISION
PHASE III
822N3063
822N3063
MSE
ALD
MSE
ROCK EXCAVATION PLAN
B
B
B
B
B
FLOW
LC EXISTING LOCK
S T
A
B
S
B
S
B
S T
A
B
S T
A
B
S T
A
B
S T
A
B
S T
A
B
S T
A
B
S T
A
B
S
B
S
B
S
B
S
A
S
S
B
S
B
S
B
S
B
B
B
B
B
B
B
S T
A
S T
A
B
S T
A
S T
A
S T
A
S T
A
S T
A
S T
A
S T
A
S T
A
S T
A
B
B
B
B
B
B
B
N
C B
B
B
PRESPLIT LINES
LINE DRILLING
CL EXISTING LOCK
EL 25
EL 23
EL 24
EL 10EL 11EL 12EL 13EL 14EL 15EL 16EL 17EL 18AEL 18BEL 19EL 20EL 21EL 22 EL 2EL 3EL 4EL 5EL 6EL 7EL 8EL 9
.1
L
OFFSET 2+15R
C FUTURE LOCK
SEE NOTE 3
L-8 L-7 L-6 L-5 L-4
M-5 M-4
11A
2A
3A
FLOW
VANESSA C. BATEMAN
BENJAMIN L. ROHRBACH P.E.
MICHAEL A. MORRISON NICOLE C. BERGER
LEGEND:
NOTES:
GRAPHIC SCALE
3. EXPECTED LOW TOP OF ROCK
4.
THAN 90 DEGREES.
INSIDE CORNERS THAT ARE EQUAL TO OR LESS
AND FIVE (5) FEET ON EITHER SIDE OF
THAT ARE EQUAL TO OR LESS THAN 120 DEGREES,
FEET ON EITHER SIDE OF OUTSIDE CORNERS
LINE DRILLING SHALL BE PERFORMED TEN (10)
H
F
G
E
3 4 5 6
D
C
B
A
2 3 4 5 6
REV NO.TASK COMPLETED BY:
DO NOT ALTER MANUALLY
C.A.D. DRAWING
ISSUED BY:
R
TENNESSEE VALLEY AUTHORITY
FOSSIL AND HYDRO ENGINEERING
AUTOCAD R
DATE
PLOT FACTOR:
REVIEWED BY: APPROVED BY:
AS CONST
EXCEPT AS NOTED
NO.
REV.
DATE
R
R
DRWNDSGN CHKD RVWDSUPV APPD
PROJECT
ISSD
ID
F
CD
REV
DISCIPLINE
INTERFACE
E
7 8 9
D
C
B
A
US Army Corps of Engineers
Nashville District
SUBMITTED BY:
APPROVED BY:
:4 c u s e r s h e c x d e k d o c u m e n t s p w w o r k c e lr n d m s
N .d g n
P l m e
P l t e
F i m e
DESIGNED BY:
DRAWN BY:
CHECKED BY:
REVISION R CHIEF, ENGINEERING CONSTRUCTION DIVISION
822N3064
822N3064
MSE
ALD
MSE
PRESPLIT AND LINE DRILLING
STA. 13+50
PRESPLIT LINE
STA. 13+17
PRESPLIT LINE
B
B
B
B
B
FLOW
LC EXISTING LOCK
S T
A
B
S
B
S
B
S T
A
B
S T
A
B
S T
A
B
S T
A
B
S T
A
B
S T
A
B
S T
A
B
S
B
S
B
S
B
S
A
S
S
B
S
B
S
B
S
B
B
B
B
B
B
B
S T
A
S T
A
B
S T
A
S T
A
S T
A
S T
A
S T
A
S T
A
S T
A
S T
A
S T
A
B
130'
CENTERLINE OF FUTURE LOCK
PRESPLIT LINE OFFSET FROM
140'
CENTERLINE OF FUTURE LOCK
PRESPLIT LINE OFFSET FROM
130'
PRESPLIT LINE OFFSET FROM
140'
CENTERLINE OF FUTURE LOCK
PRESPLIT LINE OFFSET FROM
50'
CENTERLINE OF FUTURE LOCK
PRESPLIT LINE OFFSET FROM
B
B
B
B
B
B
N
STA. 14+04
PRESPLIT LINE
STA. 13+42
PRESPLIT LINE
50'
CENTERLINE OF FUTURE LOCK
PRESPLIT LINE OFFSET FROM
119'
PRESPLIT LINE OFFSET FROM
55'
CENTERLINE OF FUTURE LOCK
PRESPLIT LINE OFFSET FROM
C B
Standard Penetration & CoredDC
Auger HoleA
Standard Penetration
C
C
Vertical Core Hole
Angle Core Hole
DESCRIPTIONSYMBOLLETTER
Cone PenetrometerCPT
VANESSA C. BATEMAN
BENJAMIN L. ROHRBACH P.E.
MICHAEL A. MORRISON NICOLE C. BERGERROBERT F. KNOX
and if sticky, the specimen should be spread out in a thin layer and allowed to lose some moisture by evaporation. Then the specimen is rolled out by hand on a smooth surface or between the palms into a thread about one-eighth inch in diameter. The thread is then folded and rolled repeatedly. During the manipulation the moisture content is gradually reduced is reached.
continued until the lump crumbles.
The tougher the thread near the plastic limit and the stiffer the lump when it finally crumbles, the more potent is the colloidal clay fraction in the soil. Weakness of the thread at the plastic limit and quick loss of coherence of the lump below the plastic limit indicate either which occur below the A-line.
Highly organic clays have a very weak and spongy feel at the plastic limit.
After removing particles larger than the No. 40 sieve size, a specimen of soil about one-halfAfter removing particles larger then No. 40 sieve size, prepare a pat of water if necessary to make the soil soft but not sticky.
Place the pat in the open palm of one hand and shake horizontally, reaction consists of the appearance of water on the surface of the pat sample is squeezed between the fingers, the water and gloss disappear from the surface, the pat stiffens, and finally it cracks or crumbles.
The rapidity of appearance of water during shaking and of its disap-pearance during squeezing assist in identifying the character of the fines in a soil.
Very fine clean sands give the quickest and most distinct reaction
Adopted by Corps of Engineers and Bureau of Reclamation, January 1952.
striking vigorously against the other hand several times. A positive which changes to a livery consistency and becomes glossy. When the whereas a plastic clay has no reaction. Inorganic silts, such as a typical
(1) Boundary classifications. Soils possessing characteristics of two groups are designated by combinations of group symbols. For example GW-GC, well-graded gravel-sand mixture with clay binder.
FIELD IDENTIFICATION PROCEDURES FOR FINE-GRAINED SOIL OR FRACTIONS
crumbling between the fingers. This strength is a measure contained in the soil. The dry strength increases with of the character and quantity of the colloidal fraction
After removing particles larger than No. 40 sieve size, mold a necessary. Allow the pat to dry completely by oven, sun, strength. Silty fine sands and silts have about the same slight dry strength, but can be distinguished by the feel when powdering the dried specimen. Fine sand feels gritty feel of flour.
High dry strength is characteristic for clays of the CH group.
A typical inorganic silt possesses only very slight dry whereas a typical silt has the smooth
GW
GP
GM
GC
SW
SP
SM
SC
Well-graded gravels, gravel-sand mixtures, little or no fines.
Poorly-graded gravels, gravel-sand mixtures, little or no fines.
Clayey gravels, gravel-sand-clay mixtures
Well-graded sands, gravelly sands, little or no fines.
Poorly-graded sands, gravelly sands, little or no fines.
Silty sands, sand-silt mixtures.
Clayey sands, sand-clay mixtures.
Typical Names Group
Symbols Major Divisions
1 2 3 4
C o a r s e g r a in e d
S o il s
S a n d s
G r a v e ls
M o r e t h a n h a lf o f c o a r s e f r a c t io n M o r e t h a n h a lf o f c o a r s e f r a c t io n
F o r v is u a l c la s s if ic a t io n t h e in s iz m y b e u s e d a s e q u iv a le n t t o
C le n
G r a v e ls
L it t le o r n o f in e s
G r a v ls w it h
F in e s
A p p r e c ia b le a m o u n t o f f in e s
C le a n
S a n d s
L it t le f in e s
S a n d s w it h
F in e s
A p p r e c ia b le a m o u n t o f f in e s
Field Identification Procedures
(Excluding particles larger than 3 inches and basing fractions on estimated weights)
Wide range in grain sizes and substantial amounts
Predominantly one size or a range of sizes with some intermediate sizes missing
Nonplastic fines or fines with low plasticity (for
Plastic fines (for identification procedures see CL below)
Wide range in grain size and substantial amounts
Predominantly one size or a range of sizes with some intermediate sizes missing
Nonplastic fines or fines with low plasticity (for
Plastic fines (for identification procedures see
CL below).
Identification Procedures on Fraction Smaller than NO. 40 Sieve Size identification procedures see ML below).
of all intermediate particle sizes.
identification procedures see ML below).
of all intermediate particle sizes
Silty gravels, gravel-sand-silt mixtures
Information Required for
Describing Soils
For undisturbed soils add information on drainage characteristics and hardness of the coarse grains;
pertinent descriptive information, Example:
cementation, moisture conditions and local or geologic name and other and symbol in parentheses.
angular gravel particles 1/2-inch well-compacted and moist in place;
alluvial sand; (SM).
maximum size; rounded and subangular
Give typical name; indicate approximate stratification, degree of compactness percentages of sand and gravel, max.
Silty sand, gravelly; about 20% hard, sand grains coarse to fine; about 15% size, angularity, surface condition, D e t e r m in e p e r c e n t a g e s o f g r a v e l a n d s a n d f r g a in s iz e c u r v e s ie v e s iz e c o a r s e g r a in e d s o il s a r e c la s s if ie d a s f o ll o w s
L e s s t h a n
M o r e t h a n t o
G W
G P
S W
S P
G M
G C
S M
S C
B o r d e r li n e c a s e s r e q u ir in g u s e o f d u a l s y m b o ls
U s e g r a in s iz e c u r v e in id e n t if y in g t h e f r a c t io n s a s g iv e n u n d e r f ie ld id e n t if ic a t io n
Laboratory Classification
Criteria
Atterberg limits above "A" line with PI greater than 7
Atterberg limits below "A" line Limits plotting in hatched zone with
PI between 4 and 7 are borderline cases requiring use of dual symbols.
or PI less than 4
Not meeting all gradation requirements for SW x10
D
D
D60 u
D C =
D
Cc Between 1 and 3
Atterberg limits below "A" line or PI less than 4
Atterberg limits above "A" line with PI greater than 7
Not meeting all gradation requirements for GW
Above "A" line with
PI between 4 and 7 are borderline cases requiring use of dual symbols.
x10
D
D
D60 u
D C = Greater than 6
D
Cc Between 1 and 3
Greater than 4
0 10 20 30 40 50 60 70 80 90 100
CL-ML
CL
CH
OH
MH
ML
Toughness and Dry Strength Increase with Increasing Plasticity Index
A- Lin e
P L
A S
T
IC
IT
Y
IN
D E
X
LIQUID LIMIT
PLASTICITY CHART
For laboratory classification of fine-grained soils
Comparing Soils at Equal Liquid Limit
Dry Strength
(Crushing characteristics)
Dilatancy
(Reaction to shaking)
Toughness
(Consistency near PL)
None to slight Quick to slow None
Medium to high None to very slow Medium
Slight to medium Slow Slight
Slight to medium Slow to none Slight to medium
High to very high None High
None to very slow Slight to medium
Readily identified by color, odor, spongy feel and frequently by fibrous texture.
Example:
For undisturbed soils add information on structure, stratification, consistency in undisturbed and remolded states, moisture and drainage condition.
character of plasticity, amount and maximum size of coarse grains, color geologic name, and other pertinent in parentheses.
in wet condition, odor if any, local or small percentage of fine sand, Give typical name, indicate degree and descriptive information, and symbol
Clayey silt, brown, slightly plastic, numerous vertical root holes, firm and dry in place, loess, (ML).
F in e g r a in e d
S o il s
S il t s a la y s
L iq u id li m it g r e a t e r t h a n
ML
CL
OL
MH
CH
OH
PtHighly Organic Soils Peat and other highly organic soils.
Organic clays of medium to high plasticity organic silts.
Organic silts and organic silty clays of low plasticity.
Inorganic clays of low to medium plasticity, or lean clays.
clayey silts with slight plasticity.
Medium to high
Inorganic silts and very fine sands, rock flour, silty or clayey fine sands or
Organic silts, micaceous or diatomaceous fine sandy or silty soils, elastic silts.
Inorganic clays of high plasticity, fat clays.
gravelly clays, sandy clays, silty clays, S il t s a la y s
L iq u id li m it le s s t h a n
U N I F I E D S O I L C L A S S I F I C A T I O N (Including Identification and Description)
M o r e t h a n h a lf f t e r ia l is la r g e r t h s ie v e s iz e is la r g e r t h s ie v e s iz e is s m a ll e r t h s ie v e s iz e t h s ie v e s iz e
M o r e t h a n h a lf f t e r ia l is s m a ll e r t h s ie v e s iz e
T h s ie v e s iz e is a b o u t t h e s m a ll e s t p a r t ic le v is ib le t o t h e n a k e d e y e
D e p e n d in g o n p e r c e n t a g e o f f in e s f r a c t io n s m a ll e r t h nonplastic fines with low dry strength;
moist soil with a volume of about one-half cubic inch. Add enough rock flour, show a moderately quick reaction.
DILATANCY (Reaction to shaking)
DRY STRENGTH (Crushing characteristics) screening is not intended, simply remove by hand the coarse particles that interfere with the tests.
pat of soil to the consistency of putty, adding water if or air drying, and then test its strength by breaking and
These procedures are to be performed on the minus No. 40 sieve size particles, approximately in. For field classification purposes
After the thread crumbles, the pieces should be lumped together and a slight kneading action inorganic clay of low plasticity, or materials such as kaolin-type clays and organic clays and the specimen stiffens, finally loses its plasticity, and crumbles when the plastic limit inch cube in size, is molded to the consistency of putty. If too dry, water must be added
TOUGHNESS (Consistency near plastic limit)
(2) All sieve sizes on this chart are U.S. standard.
increasiny plasticity.
accum at accumulated
A B B R E V I A T I O N S sd sdy sh shy si sis siy sl slcs slick sml sand sandy shale shaly silt siltstone silty slight, slightly siliceous slickenside small scat scattered ln lo ls lt med mic min mod mot mss mst mtl mtx nod
NR
num
OB
occ ool op org lense loose limestone light medium micaceous mineralized, -ization moderate, moderately mottling, mottled massive moist material matrix nodule no recovery numerous overburden (unclassified) occasional, -ally oolite, oolitic open,opened organic part pbl petro
PI
pit
PL
pl pla pln pwdr prob pt
PT
ptg qtz rec partially pebble petroleum, petroliferous plasticity index pit, pitted, pitting plastic limit plastic platy plane powder, powdered probable, probably paper-thin pressure test parting quartz recovered
LL liquid limit el est excl extr f fe fld fm fos frac frag fri fsl gen glau gr gra grad grn grt gvl gyp elevation estimate,-ed excluding extremely fine, finely iron filled formation fossil, fossiliferous fracture fragment friable fissle generally glauconite, -itic gray grain, grained gradational green grout gravel, gravelly gypsum h/a hd hem hld hor imbdd incl intbdd intlam irr jt l/a lam
LC
LDW
lea lg lig lim high angle hard hematite healed horizontal imbedded including interbed, interbedded interlaminated irregular, irregularly joint low angle lamina, -ae, -ated lost core lost drill water leached large lignitic limonite
DWR drill water retained drv drive bky bl bld
BOH
blocky black boulder bottom of hole br brec brk c cal calc brown brecciated broken coarse calcite calcareous carb cav cbl
CD
cem
CH
cht circl cl cly cmtd col conc congl crm d dis dk dmp dol carbonaceous cavity cobble corrected depth cement core in hole chert circulation clay clayey cemented columnar concrete conglomerate crumbly dense disseminated dark damp dolomite, dolomitic drl drilling
BK back alt ang approx argil bbl bdd bdr bifur angular alternating approximate, -mately argillaceous barrel bedded, bedding bedrock bifurcating
AH ahead rk rnd
RQD
sat rock round rock quality designation saturated
REF refusal so soln soft solution, -tioned, -tioning ss st stf strg styl stylc sur ti
TR
sandstone stain, -ed, -ing stiff stringer stylolite stylolitic surface tight top of rock tr
UL
unacct var v vert vgy w/ wea wht
WL
WT
x-bdd xl xln yel trace unaccountable loss unaccountable variable very vertical vuggy with weathered white water level water table cross-bedded crystal crystalline yellow
SPT std. penetration test smpl sample
* When using as the plural form add "s"
A BLOW COUNT OF HIGHER THAN 50 BLOWS PER HALF FOOT IS NORMALLY DEFINED AS REFUSAL FOR
IS DEFINED AS THE POINT BEYOND WHICH FURTHER PENETRATION WAS IMPRACTICABLE WITH THE
EXPLORATION METHOD USED.
BE DETERMINED BY SEPARATE OBSERVATIONS. WATER LEVEL READINGS WERE NOT TAKEN ON EVERY
HOLE FOR VARIOUS REASONS. THE ABSENCE OF A READING DOES NOT INDICATE THE ABSENCE OF
GROUNDWATER.
WHEREVER THE METHOD OF EXPLORATION PRECLUDED THE POSSIBILITY OF RECOVERING SAMPLES
SOME OF THE EXPLORATORY BORINGS ARE PROJECTED ON THE SOIL AND ROCK PROFILES.
1.
2.
3.
4.
5.
6.
GENERAL NOTES
STANDARD PENETRATION HOLES. FOR ALL OTHER HOLES DRILLED THROUGH OVERBURDEN, REFUSAL
ABOVE ROCK, SUITABLE FOR EXAMINATION OR TESTS, THE MATERIAL IS DENOTED AS OVERBURDEN.
FOR DISTANCES, SEE PLANS OF EXPLORATION.
WATER ELEVATIONS INDICATED ( ) IN CORE (C), DENSION (U), DRIVE SAMPLED (D), AUGER (A), AND
ACTUAL LEVEL OF GROUNDWATER ON ANY DATE OTHER THAN THAT SHOWN ON THE LOGS MUST
GROUNDWATER LEVELS WILL VARY IN ACCORDANCE WITH RAINFALL AND STREAM STAGES, THEREFORE
RQD IS A MEASURE OF THE ROCK QUALITY. ALL LENGTHS OF CORE RECOVERED OVER 4 INCHES
IN LENGTH ARE ADDED THEN DIVIDED BY THE TOTAL LENGTH OF CORE WHICH SHOULD HAVE
BEEN RECOVERED AND EXPRESSED AS A PERCENTAGE.
ALL ELEVATIONS ARE IN FEET AND REFER TO NATIONAL GEODETIC VERTICAL DATUM (NGVD).
7.
WASHBORINGS (WB) MAY HAVE BEEN INFLUENCED BY TRAPPEDDRILLING FLUID OR AN INSUFFICIENT
PASSAGE OF TIME TO PERMIT BORING TO REFLECT ACTUALGROUND WATER ELEVATION.
Parting
Band
Thin Bed
Medium Bed
Thick Bed
Massive
< 0.02'
0.02' - 0.2'
0.2' - 0.5'
0.5' - 1.0'
1.0' - 2.0'
> 2.0'
TERMS FOR THICKNESS
OF BEDDING
Very soft or plastic
Soft
Moderately hard
Can be indented easily with thumb
Can be scratched with fingernail
Can be scratched easily with knife;
cannot be scratched with fingernail
Hard
Very hard
Difficult to scratch with knife
Cannot be scratched with knife
SCALE OF HARDNESS
TERMS FOR HARDNESS OF BEDROCK
DESCRIPTION
LEGEND FOR BORING TYPE
SHOWN ON EXPLORATION PLANS
HOLE NUMBER AND TYPE
LEGEND FOR LOGS OF BORINGS AND
SUBSURFACE PROFILES AND SECTIONS
BOTTOM OF HOLE ELEVATION
GENERAL BEDROCK DESCRIPTION
weathered solution channels occur along joints and bedding planes.
FORT PAYNE FORMATION LIMESTONE: Thin bedded to massive, hard to very hard, dark gray to black, fine-to medium-grained limestone, with numerous lenses and nodules of very hard, black chert. In core samples, chert is found to comprise about 30% of the total. Numerous weathered solution channels occur along joints and bedding planes.
to medium-grained limestone, occasional lenses and nodules of very hard, black chert. Numerous
WARSAW FORMATION LIMESTONE: Thin bedded to massive, hard to very hard, medium to dark gray, fine-
SUFACE…