Request For Information (RFI) receipts and answers as of 4th day of August, year 2017.
RFI #18
| Question : |
| “The specification for interstitial line type, is it (closed cell or fiberglass)? Thickness (1 or 2 inches )? , and inner duct (perforated or solid)? is not in the specifications. Please advise.” |
Regarding Specification: 233113 – Metal Ducts Plan Note #17 on Sheet M1.01
| Response : |
| Replace Note 17 on Sheet M1.01 with “Supply and Return Duct work of fan cool units 5 & 6 are not insulated.” |