Q and A Addendum 01_02 (102554_Elec_PanelboardSchedules_Add01).pdf
PDF 528 KB Posted
- Attached to
- B222 Renovation and Addition Federal contract opportunity
- Solicitation number
- W912LM20R1003
About this file
This solicitation requests proposals for the construction of an addition and renovation to an existing base supply facility located at the 148th Fighter Wing of the Duluth Air National Guard Base in Minnesota. Services required include construction project management, site work, demolition, interior reconfiguration, replacement of mechanical, electrical and plumbing systems, and restoration of brick facade and standing seam metal roof to match existing building. The project magnitude is between $5-10 million and must be completed within 540 days of notice to proceed. The NAICS code is 236220 for commercial and institutional building construction. This is a small business set-aside solicitation issued by the US Property and Fiscal Office for Minnesota on behalf of the Department of the Army Minnesota Army National Guard. The pre-proposal conference is scheduled for October 7th and proposals are due October 29th. The source selection will be based on best value past performance and price factors without discussions.
View the file
Other files for this federal contract opportunity
Show all 36
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the state of Minnesota.
KEVIN O. WATSON, PE
DATE: 01/03/20 LIC. NO. 51801
date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
no. date descriptionby ckd
1 1312111098765432
I
H
G
F
E
D
C
B
A
B222 RENOVATION AND ADAL
US NATIONAL GUARD BUREAU
MN ANG, 148TH FIGHTER WING
DULUTH, MINNESOTA
8201 NORMAN CENTER DR.
BLOOMINGTON, MN 55437
763-277-4676
102554
C
102554_E_CENTRAL
E-701
PANELBOARD SCHEDULES
12/20/19
K. WATSON C. KLOS
A. ALLEN
DEMAND WITH EXPANSION: 26 A
TOTAL ESTIMATED DEMAN... 22 A
TOTAL CONNECTED... 22 A
TOTAL ESTIMATED DEMAN... 18053 VA
TOTAL CONNECTED LOAD: 18053 VA
PANEL TOTALS
TOTAL LOAD: 4496 VA 5110 VA 8447 VA
41 20 1 SPARE 0 0 -- SPACE -- -- 42
39 20 1 SPARE 0 0 -- SPACE -- -- 40
37 20 1 SPARE 0 0 -- SPACE -- -- 38
35 20 1 SPARE 0 0 -- SPACE -- -- 36
33 20 1 SPARE 0 0 -- SPACE -- -- 34
31 20 1 SPARE 0 0 -- SPACE -- -- 32
29 20 1 SPARE 0 0 -- SPACE -- -- 30
27 20 1 SPARE 0 0 -- SPACE -- -- 28
25 20 1 SPARE 0 0 -- SPACE -- -- 26
23 -- -- -- -- 1795 0 SPARE 1 20 24
21 -- -- -- -- 1798 0 SPARE 1 20 22
19 40 3 LIGHTING INVERTER SEE ONE-LINE 1777 0 SPARE 1 20 20
17 20 1 WEAPONS VAULT/ REST RM... 2#12, #12G., 3/4'' C. 2190 0 SPARE 1 20 18
15 20 1 EXTERIOR LTG - SOUTH 2#12, #12G., 3/4'' C. 214 0 SPARE 1 20 16
13 20 1 WEST ADMIN AREA LTG 2#12, #12G., 3/4'' C. 1979 0 SPARE 1 20 14
11 20 1 TMO AREA LTG 2#10, #10G. 3/4" C. 2244 0 SPARE 1 20 12
9 20 1 WEST WAREHOUSE AREA LTG 2#12, #12G., 3/4'' C. 1216 0 SPARE 1 20 10
7 0 SPARE 1 20 8
5 -- -- -- -- 2218 0 SPARE 1 20 6
3 -- -- -- -- 1882 0 SPARE 1 20 4
1 60 3 HP-1B SEE ONE-LINE 740 0 SPARE 1 20 2
# B... P LOAD SERVED WIRE / GROUND /... A B C WIRE / GROUND / CONDUIT LOAD SERVED P B... #
NOTES:
ENCLOSURE: NEMA 1 MCB RATING: 125 A
MOUNTING: SURFACE WIRES: 4 MAINS RATING: 100 A
SUPPLY FROM: MDB PHASE: 3 MAINS TYPE: MCB
LOCATION: ELECTRICAL ROOM 119 VOLTAGE: 480Y/277V A.I.C. RATING: 22K AIC RMS SYMMETRICAL
PANELBOARD: HP1A
DEMAND WITH EXPANSION: 139 A
TOTAL ESTIMATED DEMAN... 116 A
TOTAL CONNECTED... 124 A
TOTAL ESTIMATED DEMAN... 96594 VA
TOTAL CONNECTED LOAD: 103480 VA
PANEL TOTALS
TOTAL LOAD: 35055 VA 36809 VA 31616 VA
41 -- -- -- -- 0 0 -- SPACE -- -- 42
39 -- -- -- -- 0 0 -- SPACE -- -- 40
37 20 3 SPARE 0 0 -- SPACE -- -- 38
35 -- -- -- -- 0 0 -- SPACE -- -- 36
33 -- -- -- -- 0 0 -- SPACE -- -- 34
31 20 3 SPARE 0 0 -- SPACE -- -- 32
29 -- -- -- -- 0 0 -- SPACE -- -- 30
27 -- -- -- -- 0 0 -- SPACE -- -- 28
25 20 3 SPARE 0 0 -- SPACE -- -- 26
23 -- -- -- -- 7202 0 -- -- -- -- 24
21 -- -- -- -- 7202 0 -- -- -- -- 22
19 40 3 CU-1 3#8, #10G., 3/4'' C. 7202 0 SPARE 3 60 20
17 -- -- -- -- 13833 0 -- -- -- -- 18
15 -- -- -- -- 14913 0 -- -- -- -- 16
13 100 3 HP2B SEE ONE-LINE 13993 0 SPARE 3 60 14
11 -- -- -- -- 1256 0 -- -- -- -- 12
9 -- -- -- -- 2609 0 -- -- -- -- 10
7 30 3 LP-2 VIA T-2 SEE ONE-LINE 2049 0 SPARE 3 30 8
5 -- -- -- -- 9325 0 -- -- -- -- 6
3 -- -- -- -- 12085 0 -- -- -- -- 4
1 100 3 HP-2A SEE ONE-LINE 11811 0 SPARE 3 30 2
# B... P LOAD SERVED WIRE / GROUND /... A B C WIRE / GROUND / CONDUIT LOAD SERVED P B... #
NOTES:
ENCLOSURE: NEMA 1 MCB RATING: 225 A
MOUNTING: SURFACE WIRES: 4 MAINS RATING: 225 A
SUPPLY FROM: MDB PHASE: 3 MAINS TYPE: MCB
LOCATION: ELECTRICAL ROOM 119 VOLTAGE: 480Y/277V A.I.C. RATING: 22K AIC RMS SYMMETRICAL
PANELBOARD: HP2
DEMAND WITH EXPANSION: 345 A
TOTAL ESTIMATED DEMAND CURRENT: 287 A
TOTAL CONNECTED CURRENT: 343 A
TOTAL ESTIMATED DEMAND LOAD: 238949 VA
TOTAL CONNECTED LOAD: 285395 VA
SWITCHBOARD TOTALS
12 SPACE -- -- -- -- 0 VA --
11 SPACE -- -- -- -- 0 VA --
10 SPARE 1 100 A -- 0 VA
9 SPARE 1 125 A -- 0 VA
8 SPARE 1 200 A -- 0 VA
7 EEWH-1 SEE ONE-LINE 3 175 A 250 A 10800 VA
6 ELEVATOR SEE ONE-LINE 3 30 A 125 A 16620 VA
5 LP3 VIA T3 SEE ONE-LINE 3 125 A 125 A 80000 VA
4 HP2 SEE ONE-LINE 3 225 A 250 A 103480 VA
3 HP1A SEE ONE-LINE 3 125 A 125 A 18053 VA
2 SPD SEE ONE-LINE 3 30 A -- 0 VA
1 EHP1 SEE ONE-LINE 3 200 A 250 A 56442 VA
CKT LOAD NAME DESIGN WIRE AND CONDUIT POLES
TRIP
RATING
FRAME
SIZE
LOAD COMMENTS
NOTES:
ENCLOSURE: NEMA 1 MCB RATING: 600 A
MOUNTING: FLOOR WIRES: 4 MAINS RATING: 600 A
SUPPLY FROM: PHASES: 3 MAINS TYPE: MDB
LOCATION: ELECTRICAL ROOM 119 VOLTAGE: 480Y/277V A.I.C. RATING: 22K AIC RMS SYMMETRICAL
SWITCHBOARD: MDB
DEMAND WITH EXPANSION: 7 A
TOTAL ESTIMATED DEMAN... 6 A
TOTAL CONNECTED... 6 A
TOTAL ESTIMATED DEMAN... 4840 VA
TOTAL CONNECTED LOAD: 4840 VA
PANEL TOTALS
TOTAL LOAD: 740 VA 1882 VA 2218 VA
41 20 1 SPARE 0 0 -- SPACE -- -- 42
39 20 1 SPARE 0 0 -- SPACE -- -- 40
37 20 1 SPARE 0 0 -- SPACE -- -- 38
35 20 1 SPARE 0 0 -- SPACE -- -- 36
33 20 1 SPARE 0 0 -- SPACE -- -- 34
31 20 1 SPARE 0 0 -- SPACE -- -- 32
29 20 1 SPARE 0 0 -- SPACE -- -- 30
27 20 1 SPARE 0 0 -- SPACE -- -- 28
25 20 1 SPARE 0 0 -- SPACE -- -- 26
23 20 1 SPARE 0 0 SPARE 1 20 24
21 20 1 SPARE 0 0 SPARE 1 20 22
19 20 1 SPARE 0 0 SPARE 1 20 20
17 20 1 SPARE 0 0 SPARE 1 20 18
15 20 1 SPARE 0 0 SPARE 1 20 16
13 20 1 SPARE 0 0 SPARE 1 20 14
11 20 1 EAST WAREHOUSE 2#12, #12G., 3/4'' C. 2218 0 SPARE 1 20 12
9 20 1 EAST DEPLOYMENT AREA 2#12, #12G., 3/4'' C. 1583 0 SPARE 1 20 10
7 20 1 EAST ADMIN AREA LTG 2#12, #12G., 3/4'' C. 10 0 SPARE 1 20 8
5 20 1 SPARE 0 0 SPARE 1 20 6
3 20 1 EXTERIOR LTG - NORTH 2#12, #12G., 3/4'' C. 299 0 SPARE 1 20 4
1 20 1 EAST ADMIN AREA LTG 2#12, #12G., 3/4'' C. 730 0 SPARE 1 20 2
# B... P LOAD SERVED WIRE / GROUND /... A B C WIRE / GROUND / CONDUIT LOAD SERVED P B... #
NOTES:
ENCLOSURE: NEMA 1 MCB RATING: 125 A
MOUNTING: SURFACE WIRES: 4 MAINS RATING: 60 A
SUPPLY FROM: HP1A PHASE: 3 MAINS TYPE: MCB
LOCATION: WAREHOUSE 130 VOLTAGE: 480Y/277V A.I.C. RATING: 10K AIC RMS SYMMETRICAL
PANELBOARD: HP1B
SERVICE TRANSFORMER
A 08/01/19 KOW CGK TYPE B-2 SUBMITTAL
B 01/03/20 KOW CGK TYPE B-3 SUBMITTAL
C 10/15/20 KOW CGK ADDENDUM 01
C
C
C
C
C
10/15/20 by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the state of Minnesota.
KEVIN O. WATSON, PE
DATE: 01/03/20 LIC. NO. 51801
date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
no. date descriptionby ckd
1 1312111098765432
I
H
G
F
E
D
C
B
A
B222 RENOVATION AND ADAL
US NATIONAL GUARD BUREAU
MN ANG, 148TH FIGHTER WING
DULUTH, MINNESOTA
8201 NORMAN CENTER DR.
BLOOMINGTON, MN 55437
763-277-4676
102554
C
102554_E_CENTRAL
E-702
PANELBOARD SCHEDULES
12/20/19
K. WATSON C. KLOS
A. ALLEN
DEMAND WITH EXPANSION: 45 A
TOTAL ESTIMATED DEMAN... 38 A
TOTAL CONNECTED... 40 A
TOTAL ESTIMATED DEMAN... 31320 VA
TOTAL CONNECTED LOAD: 33220 VA
PANEL TOTALS
TOTAL LOAD: 11811 VA 12085 VA 9325 VA
41 0 -- SPACE -- -- 42
39 0 -- SPACE -- -- 40
37 0 -- SPACE -- -- 38
35 -- -- -- -- 60 0 -- SPACE -- -- 36
33 -- -- -- -- 60 0 -- SPACE -- -- 34
31 20 3 ELECTRIC FORKLIFT RECEPT 3#12, #12G., 3/4'' C. 60 0 -- SPACE -- -- 32
29 -- -- -- -- 388 0 -- SPACE -- -- 30
27 -- -- -- -- 388 0 -- SPACE -- -- 28
25 15 3 EF-3 3#12, #12G., 3/4'' C. 388 0 -- SPACE -- -- 26
23 -- -- -- -- 467 0 SPARE 1 20 24
21 -- -- -- -- 467 0 SPARE 1 20 22
19 15 3 EEWH-2 EYEWASH 3#12, #12G., 3/4'' C. 467 0 SPARE 1 20 20
17 -- -- -- -- 1385 0 SPARE 1 20 18
15 -- -- -- -- 1385 0 SPARE 1 20 16
13 15 3 ATO-3 3#12, #12G., 3/4'' C. 1385 0 SPARE 1 20 14
11 -- -- -- -- 1385 0 SPARE 1 20 12
9 -- -- -- -- 1385 0 SPARE 1 20 10
7 15 3 ATO-2 3#12, #12G., 3/4'' C. 1385 0 SPARE 1 20 8
5 -- -- -- -- 5640 0 SPARE 1 20 6
3 -- -- -- -- 8400 0 SPARE 1 20 4
1 50 3 LP-2A VIA T-2A 3#12, #12G., 3/4'' C. 8126 0 SPARE 1 20 2
# B... P LOAD SERVED WIRE / GROUND /... A B C WIRE / GROUND / CONDUIT LOAD SERVED P B... #
NOTES:
ENCLOSURE: NEMA 1 MCB RATING: 225 A
MOUNTING: SURFACE WIRES: 4 MAINS RATING: 100 A
SUPPLY FROM: HP2 PHASE: 3 MAINS TYPE: MCB
LOCATION: WAREHOUSE 113 VOLTAGE: 480Y/277V A.I.C. RATING: 14K AIC RMS SYMMETRICAL
PANELBOARD: HP2A
DEMAND WITH EXPANSION: 62 A
TOTAL ESTIMATED DEMAN... 51 A
TOTAL CONNECTED... 51 A
TOTAL ESTIMATED DEMAN... 42740 VA
TOTAL CONNECTED LOAD: 42740 VA
PANEL TOTALS
TOTAL LOAD: 13993 VA 14913 VA 13833 VA
41 -- -- -- -- 1333 0 -- SPACE -- -- 42
39 -- -- -- -- 1333 0 -- SPACE -- -- 40
37 15 3 EWH-1 NIPR 202 3#12, #12G., 3/4'' C. 1333 0 -- SPACE -- -- 38
35 -- -- -- -- 467 0 -- SPACE -- -- 36
33 -- -- -- -- 467 0 -- SPACE -- -- 34
31 15 3 EEWH-2 EYEWASH - RM 130 3#12, #12G., 3/4'' C. 467 0 -- SPACE -- -- 32
29 -- -- -- -- 467 0 -- SPACE -- -- 30
27 -- -- -- -- 467 0 -- SPACE -- -- 28
25 15 3 EEWH-2 EYEWASH - RM 130 3#12, #12G., 3/4'' C. 467 0 -- SPACE -- -- 26
23 -- -- -- -- 3667 0 SPARE 1 20 24
21 -- -- -- -- 3667 0 SPARE 1 20 22
19 30 3 AC-1 WAREHOUSE 130 3#10, #10G., 3/4'' C. 3667 0 SPARE 1 20 20
17 -- -- -- -- 3324 0 SPARE 1 20 18
15 -- -- -- -- 3324 0 SPARE 1 20 16
13 15 3 RECEPTACLE WAREHOUSE 130 3#12, #12G., 3/4'' C. 3324 0 SPARE 1 20 14
11 -- -- -- -- 2360 0 SPARE 1 20 12
9 -- -- -- -- 3440 0 SPARE 1 20 10
7 50 3 LP-2B VIA T-2B SEE ONE-LINE 2520 0 SPARE 1 20 8
5 -- -- -- -- 2216 0 SPARE 1 20 6
3 -- -- -- -- 2216 0 SPARE 1 20 4
1 15 3 ATO-1 3#12, #12G., 3/4'' C. 2216 0 SPARE 1 20 2
# B... P LOAD SERVED WIRE / GROUND /... A B C WIRE / GROUND / CONDUIT LOAD SERVED P B... #
NOTES:
ENCLOSURE: NEMA 1 MCB RATING: 225 A
MOUNTING: SURFACE WIRES: 4 MAINS RATING: 100 A
SUPPLY FROM: HP2 PHASE: 3 MAINS TYPE: MCB
LOCATION: WAREHOUSE 130 VOLTAGE: 480Y/277V A.I.C. RATING: 14K AIC RMS SYMMETRICAL
PANELBOARD: HP2B
DEMAND WITH EXPANSION: 20 A
TOTAL ESTIMATED DEMAN... 16 A
TOTAL CONNECTED... 16 A
TOTAL ESTIMATED DEMAN... 5914 VA
TOTAL CONNECTED LOAD: 5914 VA
PANEL TOTALS
TOTAL LOAD: 2049 VA 2609 VA 1256 VA
41 20 1 SPARE 0 0 -- SPACE -- -- 42
39 20 1 SPARE 0 0 -- SPACE -- -- 40
37 20 1 SPARE 0 0 -- SPACE -- -- 38
35 20 1 SPARE 0 0 -- SPACE -- -- 36
33 20 1 SPARE 0 0 -- SPACE -- -- 34
31 20 1 SPARE 0 0 -- SPACE -- -- 32
29 20 1 SPARE 0 0 -- SPACE -- -- 30
27 20 1 SPARE 0 0 -- SPACE -- -- 28
25 20 1 SPARE 0 0 -- SPACE -- -- 26
23 20 1 SPARE 0 0 -- SPACE -- -- 24
21 20 1 SPARE 0 0 SPARE 1 20 22
19 20 1 MOTORIZED DAMPERS MECH... 2#12, #12G., 3/4'' C. 180 0 SPARE 1 20 20
17 20 1 MOTORIZED DAMPERS POWER... 2#12, #12G., 3/4'' C. 360 0 SPARE 1 20 18
15 20 1 OH DOOR RM 121 2#12, #12G., 3/4'' C. 1000 0 SPARE 1 20 16
13 20 1 EF-6 2#12, #12G., 3/4'' C. 360 0 SPARE 1 20 14
11 20 1 EF-4 MECH RM 203 2#12, #12 G., 3/4" C. 696 0 SPARE 1 20 12
9 20 1 VAV - 5, 6, 11 2#12, #12G., 3/4'' C. 300 0 SPARE 1 20 10
7 20 1 VAV - 3 & 4 2#10, #10G., 3/4'' C. 200 0 SPARE 1 20 8
5 20 1 VAV - 1 & 2 2#12, #12G., 3/4'' C. 200 0 SPARE 1 20 6
3 -- -- -- -- 1309 0 SPARE 1 20 4
1 20 2 ACCU-1, CRU-1 2#12, #12G., 3/4'' C. 1309 0 SPARE 1 20 2
# B... P LOAD SERVED WIRE / GROUND /... A B C WIRE / GROUND / CONDUIT LOAD SERVED P B... #
NOTES:
ENCLOSURE: NEMA 1 MCB RATING: 225 A
MOUNTING: SURFACE WIRES: 4 MAINS RATING: 100 A
SUPPLY FROM: T2 PHASE: 3 MAINS TYPE: MCB
LOCATION: ELECTRICAL ROOM 119 VOLTAGE: 208Y/120V A.I.C. RATING: 10K AIC RMS SYMMETRICAL
PANELBOARD: LP2
DEMAND WITH EXPANSION: 68 A
TOTAL ESTIMATED DEMAN... 57 A
TOTAL CONNECTED... 62 A
TOTAL ESTIMATED DEMAN... 20356 VA
TOTAL CONNECTED LOAD: 22166 VA
PANEL TOTALS
TOTAL LOAD: 8126 VA 8400 VA 5640 VA
41 0 -- SPACE -- -- 42
39 0 -- SPACE -- -- 40
37 0 -- SPACE -- -- 38
35 20 1 RECEPTACLE ROOF 2#12, #12 G., 3/4" C. 540 0 -- SPACE -- -- 36
33 30 1 RECEPTACLE WAREHOUSE 113 2#10, #10G., 3/4'' C. 2400 0 -- SPACE -- -- 34
31 30 1 RECEPTACLE WAREHOUSE 113 2#10, #10G., 3/4'' C. 2400 0 -- SPACE -- -- 32
29 20 1 MOTORIZED DAMPERS POWER... 2#12, #12G., 3/4'' C. 180 0 -- SPACE -- -- 30
27 20 1 MOTORIZED DAMPERS POWER... 2#12, #12G., 3/4'' C. 360 0 -- SPACE -- -- 28
25 20 1 DWHP-1 JANITOR 123 2#12, #12G., 3/4'' C. 270 0 -- SPACE -- -- 26
23 30 1 DRYER RM 113 2#12, #12G., 3/4'' C. 2400 0 SPARE 1 20 24
21 -- -- -- -- 2400 0 SPARE 1 20 22
19 30 2 SPEC. RECEPT E WAREHOUSE... 2#10, #10G., 3/4'' C. 2400 0 SPARE 1 20 20
17 20 1 OH DOOR 137A DEPLOYMENT... 2#12, #12 G., 3/4" C. 1080 0 SPARE 1 20 18
15 20 1 WASHER RM 113 2#12, #12G., 3/4'' C. 1080 0 SPARE 1 20 16
13 20 1 OH-113B 2#12, #12G., 3/4'' C. 1080 0 SPARE 1 20 14
11 20 1 MOTORIZED DAMPERS... 2#12, #12G., 3/4'' C. 360 0 SPARE 1 20 12
9 20 1 HSF-1 2#12, #12G., 3/4'' C. 1080 0 SPARE 1 20 10
7 20 1 VAV - 7 & 8 2#12, #12 G., 3/4" C. 200 0 SPARE 1 20 8
5 20 1 GWH-1 2#12, #12 G., 3/4" C. 1080 0 SPARE 1 20 6
3 20 1 GIH-1 2#12, #12 G., 3/4" C. 1080 0 SPARE 1 20 4
1 20 1 EF- 2, 5, & 7 2#12, #12 G., 3/4" C. 1776 0 SPARE 1 20 2
# B... P LOAD SERVED WIRE / GROUND /... A B C WIRE / GROUND / CONDUIT LOAD SERVED P B... #
NOTES:
ENCLOSURE: NEMA 1 MCB RATING: 225 A
MOUNTING: SURFACE WIRES: 4 MAINS RATING: 100 A
SUPPLY FROM: T2A PHASE: 3 MAINS TYPE: MCB
LOCATION: WAREHOUSE 113 VOLTAGE: 208Y/120V A.I.C. RATING: 10K AIC RMS SYMMETRICAL
PANELBOARD: LP2A
A 08/01/19 KOW CGK TYPE B-2 SUBMITTAL
B 01/03/20 KOW CGK TYPE B-3 SUBMITTAL
C 10/15/20 KOW CGK ADDENDUM 01
C
C
C by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the state of Minnesota.
KEVIN O. WATSON, PE
DATE: 01/03/20 LIC. NO. 51801
date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
no. date descriptionby ckd
1 1312111098765432
I
H
G
F
E
D
C
B
A
B222 RENOVATION AND ADAL
US NATIONAL GUARD BUREAU
MN ANG, 148TH FIGHTER WING
DULUTH, MINNESOTA
8201 NORMAN CENTER DR.
BLOOMINGTON, MN 55437
763-277-4676
102554
C
102554_E_CENTRAL
E-703
PANELBOARD SCHEDULES
12/20/19
K. WATSON C. KLOS
A. ALLEN
DEMAND WITH EXPANSION: 53 A
TOTAL ESTIMATED DEMAN... 44 A
TOTAL CONNECTED... 57 A
TOTAL ESTIMATED DEMAN... 15980 VA
TOTAL CONNECTED LOAD: 20460 VA
PANEL TOTALS
TOTAL LOAD: 6410 VA 6900 VA 7150 VA
41 20 1 ICE MACHINE BREAK ROOM 115 2#12, #12G., 3/4'' C. 1500 0 SPARE 1 20 42
39 20 1 REFRIGERATOR BREAK ROOM... 2#12, #12G., 3/4'' C. 1500 0 SPARE 1 20 40
37 -- -- -- -- 90 0 SPARE 1 20 38
35 20 2 RANGE BREAK ROOM 115 2#12, #12G., 3/4'' C. 90 0 SPARE 1 20 36
33 20 1 RECEPT BREAK ROOM 115 2#12, #12G., 3/4'' C. 1080 0 SPARE 1 20 34
31 20 1 DISPOSAL BREAK ROOM 115 2#12, #12G., 3/4'' C. 1500 0 SPARE 1 20 32
29 20 1 MICROWAVE BREAK ROOM 115 2#12, #12G., 3/4'' C. 1500 0 SPARE 1 20 30
27 20 1 RECEPT 114, 115 2#12, #12G., 3/4'' C. 900 0 SPARE 1 20 28
25 20 1 RECEPT 114, 115 2#12, #12G., 3/4'' C. 1080 0 SPARE 1 20 26
23 20 1 OH DOOR 114 2#12, #12G., 3/4'' C. 1000 0 SPARE 1 20 24
21 20 1 RECEPT ORDERLY 112 2#12, #12G., 3/4'' C. 900 0 SPARE 1 20 22
19 20 1 RECEPT ORDERLY 112 2#12, #12G., 3/4'' C. 900 0 SPARE 1 20 20
17 20 1 RECEPT 107,109,111 2#12, #12G., 3/4'' C. 1260 0 SPARE 1 20 18
15 20 1 RECEPT 107, 109, 111 2#12, #12G., 3/4'' C. 1080 0 SPARE 1 20 16
13 20 1 RECEPT 108, 110 2#12, #12G., 3/4'' C. 900 0 SPARE 1 20 14
11 20 1 RECEPT 108, 110 2#12, #12G., 3/4'' C. 900 0 SPARE 1 20 12
9 20 1 RECEPT 103, 106 2#12, #12G., 3/4'' C. 720 0 SPARE 1 20 10
7 20 1 RECEPT 103, 106 2#12, #12G., 3/4'' C. 720 0 SPARE 1 20 8
5 20 1 RECEPT 104, 105 2#12, #12G., 3/4'' C. 900 0 SPARE 1 20 6
3 20 1 RECEPT 104, 105 2#12, #12G., 3/4'' C. 720 0 SPARE 1 20 4
1 20 1 RECEPT CORR 102 2#12, #12G., 3/4'' C. 720 500 2#12, #12G., 1'' C. LIFT STATION PUMP 1 20 2
# B... P LOAD SERVED WIRE / GROUND /... A B C WIRE / GROUND / CONDUIT LOAD SERVED P B... #
ELECTRONIC GRADE PANELBOARD WITH REMOTE SPD, ISOLATED GROUND BUS AND 200% NEUTRAL
NOTES:
ENCLOSURE: NEMA 1 MCB RATING: 225 A
MOUNTING: RECESSED WIRES: 4 MAINS RATING: 100 A
SUPPLY FROM: LP3 PHASE: 3 MAINS TYPE: MCB
LOCATION: Space 48 VOLTAGE: 208Y/120V A.I.C. RATING: 10K AIC RMS SYMMETRICAL
PANELBOARD: LP3A
DEMAND WITH EXPANSION: 175 A
TOTAL ESTIMATED DEMAN... 146 A
TOTAL CONNECTED... 222 A
TOTAL ESTIMATED DEMAN... 52590 VA
TOTAL CONNECTED LOAD: 80000 VA
PANEL TOTALS
TOTAL LOAD: 26480 VA 26210 VA 27310 VA
41 20 1 SPARE 0 0 SPARE 1 20 42
39 20 1 SPARE 0 0 SPARE 1 20 40
37 20 1 SPARE 0 0 SPARE 1 20 38
35 20 1 CUH-1, CUH-2 3#12, #12G., 3/4'' C. 3000 2400 -- -- -- -- 36
33 20 1 SOUTH TV CONF ROOM 117 3#12, #12G., 3/4'' C. 360 3120 -- -- -- -- 34
31 20 1 NORTH TV CONF ROOM 117 3#12, #12G., 3/4'' C. 360 3120 SEE ONE-LINE LTR (COMM RM) 3 60 32
29 20 1 RECEPT JANITOR 123 2#12, #12G., 3/4'' C. 180 0 -- -- -- -- 30
27 20 1 RECEPT ELEC ROOM 119 2#12, #12G., 3/4'' C. 720 1200 -- -- -- -- 28
25 20 1 FLOORBOX CONF ROOM 117 2#12, #12G., 3/4'' C. 1080 1200 SEE ONE-LINE LFP 3 60 26
23 20 1 FLOORBOX CONF ROOM 117 2#12, #12G., 3/4'' C. 1080 2700 -- -- -- -- 24
21 20 1 DEHUMIDIFIER VAULT 121 2#12, #12G., 3/4'' C. 500 2880 -- -- -- -- 22
19 20 1 RECEPT CONF ROOM 117 2#12, #12G., 3/4'' C. 900 3420 SEE ONE-LINE LP3D 3 100 20
17 20 1 RECEPT CONF ROOM 117 2#12, #12G., 3/4'' C. 900 3600 -- -- -- -- 18
15 20 1 RECEPT CONF ROOM 117 2#12, #12G., 3/4'' C. 900 2610 -- -- -- -- 16
13 20 1 RECEPT WEAPONS VAULT 121 2#12, #12G., 3/4'' C. 720 2610 SEE ONE-LINE LP3C 3 100 14
11 20 1 RECEPT WEAPONS VAULT 121 2#12, #12G., 3/4'' C. 720 5040 -- -- -- -- 12
9 20 1 RECEPT WOMEN'S RR 124 2#12, #12G., 3/4'' C. 720 5220 -- -- -- -- 10
7 20 1 RECEPT MEN'S RR 126 2#10, #10G., 3/4'' C. 720 5040 SEE ONE-LINE LP3B 3 100 8
5 20 1 RECEPT STORAGE 115.1 2#12, #12G., 3/4'' C. 540 7150 -- -- -- -- 6
3 20 1 RECEPT CORR 122 2#12, #12G., 3/4'' C. 1080 6900 -- -- -- -- 4
1 20 1 RECEPT CORR 122 2#12, #12G., 3/4'' C. 900 6410 SEE ONE-LINE LP3A 3 100 2
# B... P LOAD SERVED WIRE / GROUND /... A B C WIRE / GROUND / CONDUIT LOAD SERVED P B... #
ELECTRONIC GRADE PANELBOARD WITH REMOTE SPD, ISOLATED GROUND BUS AND 200% NEUTRAL
NOTES:
ENCLOSURE: NEMA 1 MCB RATING: 225 A
MOUNTING: SURFACE WIRES: 4 MAINS RATING: 225 A
SUPPLY FROM: T3 PHASE: 3 MAINS TYPE: MCB
LOCATION: ELECTRICAL ROOM 119 VOLTAGE: 208Y/120V A.I.C. RATING: 10K AIC RMS SYMMETRICAL
PANELBOARD: LP3
DEMAND WITH EXPANSION: 28 A
TOTAL ESTIMATED DEMAN... 23 A
TOTAL CONNECTED... 23 A
TOTAL ESTIMATED DEMAN... 8320 VA
TOTAL CONNECTED LOAD: 8320 VA
PANEL TOTALS
TOTAL LOAD: 2520 VA 3440 VA 2360 VA
41 20 1 SPARE 0 0 -- SPACE -- -- 42
39 20 1 SPARE 0 0 -- SPACE -- -- 40
37 20 1 SPARE 0 0 -- SPACE -- -- 38
35 20 1 SPARE 0 0 -- SPACE -- -- 36
33 20 1 SPARE 0 0 -- SPACE -- -- 34
31 20 1 SPARE 0 0 -- SPACE -- -- 32
29 20 1 SPARE 0 0 -- SPACE -- -- 30
27 20 1 SPARE 0 0 -- SPACE -- -- 28
25 20 1 SPARE 0 0 -- SPACE -- -- 26
23 20 1 OH DOOR RM 137 2#12, #12 G., 3/4" C. 1080 0 SPARE 1 20 24
21 20 1 OH DOOR WAREHOUSE 130 2#12, #12G., 3/4'' C. 1080 0 SPARE 1 20 22
19 20 1 SPARE 0 0 SPARE 1 20 20
17 20 1 SPARE 0 0 SPARE 1 20 18
15 20 1 OH DOOR WAREHOUSE 130 2#12, #12 G., 3/4" C. 1080 0 SPARE 1 20 16
13 20 1 OH DOOR DEPLOYMENT... 2#12, #12G., 3/4'' C. 1080 0 SPARE 1 20 14
11 20 1 VAV - 12 & 13 2#12, #12 G., 3/4" C. 200 0 SPARE 1 20 12
9 20 1 VAV - 9 & 10 2#12, #12G., 3/4'' C. 200 0 SPARE 1 20 10
7 20 1 GIH-4 2#12, #12 G., 3/4" C. 1080 0 SPARE 1 20 8
5 20 1 GIH-3 2#12, #12G., 3/4'' C. 1080 0 SPARE 1 20 6
3 20 1 GIH-2 2#12, #12 G., 3/4" C. 1080 0 SPARE 1 20 4
1 20 1 MOTORIZED DAMPERS POWER... 2#12, #12 G., 3/4" C. 360 0 SPARE 1 20 2
# B... P LOAD SERVED WIRE / GROUND /... A B C WIRE / GROUND / CONDUIT LOAD SERVED P B... #
NOTES:
ENCLOSURE: NEMA 1 MCB RATING: 225 A
MOUNTING: SURFACE WIRES: 4 MAINS RATING: 100 A
SUPPLY FROM: T2B PHASE: 3 MAINS TYPE: MCB
LOCATION: WAREHOUSE 130 VOLTAGE: 208Y/120V A.I.C. RATING: 10K AIC RMS SYMMETRICAL
PANELBOARD: LP2B
DEMAND WITH EXPANSION: 44 A
TOTAL ESTIMATED DEMAN... 37 A
TOTAL CONNECTED... 42 A
TOTAL ESTIMATED DEMAN... 13280 VA
TOTAL CONNECTED LOAD: 15300 VA
PANEL TOTALS
TOTAL LOAD: 5040 VA 5220 VA 5040 VA
41 20 1 SPARE 0 0 SPARE 1 20 42
39 20 1 SPARE 0 0 SPARE 1 20 40
37 20 1 SPARE 0 0 SPARE 1 20 38
35 20 1 RECEPT 113, 128, 129 2#10, #10G., 3/4'' C. 1080 0 SPARE 1 20 36
33 20 1 RECEPT 128, 129 2#12, #12G., 3/4'' C. 720 0 SPARE 1 20 34
31 20 1 SPARE 0 0 SPARE 1 20 32
29 20 1 RECEPT WAREHOUSE 113 2#12, #12G., 3/4'' C. 360 0 SPARE 1 20 30
27 20 1 RECEPT WAREHOUSE 113 2#12, #12G., 3/4'' C. 360 0 SPARE 1 20 28
25 20 1 RECEPTACLE WAREHOUSE 113 2#12, #12G., 3/4'' C. 1080 0 SPARE 1 20 26
23 20 1 RECEPTACLE WAREHOUSE 113 2#10, #10G., 3/4'' C. 1080 0 SPARE 1 20 24
21 20 1 RECEPTACLE WAREHOUSE 113 2#10, #10G., 3/4'' C. 1080 0 SPARE 1 20 22
19 20 1 RECEPTACLE WAREHOUSE 113 2#10, #10G., 3/4'' C. 900 0 SPARE 1 20 20
17 20 1 RECEPTACLE WOOD SHOP 139 2#10, #10G., 3/4'' C. 720 0 SPARE 1 20 18
15 20 1 RECEPT WOOD SHOP 139 2#10, #10G., 3/4'' C. 900 0 SPARE 1 20 16
13 20 1 RECEPT TMO 138 2#12, #12G., 3/4'' C. 720 0 SPARE 1 20 14
11 20 1 RECEPT TMO 138 2#12, #12G., 3/4'' C. 900 0 SPARE 1 20 12
9 20 1 RECEPT TMO 138 2#12, #12G., 3/4'' C. 900 0 SPARE 1 20 10
7 20 1 RECEPT DEPLOYMENT 137 2#10, #10G., 3/4'' C. 1080 0 SPARE 1 20 8
5 20 1 RECEPT DEPLOYMENT 137 2#10, #10G., 3/4'' C. 720 180 2#10, #10G., 3/4'' C. POWER WOOD SHOP 139 1 20 6
3 20 1 RECEPTACLE DEPLOYMENT... 2#10, #10G., 3/4'' C. 1080 180 2#10, #10G., 3/4'' C. POWER WOOD SHOP 139 1 20 4
1 20 1 RECEPT DEPLOYMENT 137 2#10, #10G., 3/4'' C. 1080 180 2#10, #10G., 3/4'' C. POWER WOOD SHOP 139 1 20 2
# B... P LOAD SERVED WIRE / GROUND /... A B C WIRE / GROUND / CONDUIT LOAD SERVED P B... #
ELECTRONIC GRADE PANELBOARD WITH REMOTE SPD, ISOLATED GROUND BUS AND 200% NEUTRAL
NOTES:
ENCLOSURE: NEMA 1 MCB RATING: 225 A
MOUNTING: SURFACE WIRES: 4 MAINS RATING: 100 A
SUPPLY FROM: LP3 PHASE: 3 MAINS TYPE: MCB
LOCATION: WAREHOUSE 113 VOLTAGE: 208Y/120V A.I.C. RATING: 10K AIC RMS SYMMETRICAL
PANELBOARD: LP3B
A 08/01/19 KOW CGK TYPE B-2 SUBMITTAL
B 01/03/20 KOW CGK TYPE B-3 SUBMITTAL
C 10/15/20 KOW CGK ADDENDUM 01
C
C by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the state of Minnesota.
KEVIN O. WATSON, PE
DATE: 01/03/20 LIC. NO. 51801
date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
no. date descriptionby ckd
1 1312111098765432
I
H
G
F
E
D
C
B
A
B222 RENOVATION AND ADAL
US NATIONAL GUARD BUREAU
MN ANG, 148TH FIGHTER WING
DULUTH, MINNESOTA
8201 NORMAN CENTER DR.
BLOOMINGTON, MN 55437
763-277-4676
102554
C
102554_E_CENTRAL
E-705
PANELBOARD SCHEDULES
12/20/19
K. WATSON C. KLOS
A. ALLEN
DEMAND WITH EXPANSION: 81 A
TOTAL ESTIMATED DEMAN... 67 A
TOTAL CONNECTED... 68 A
TOTAL ESTIMATED DEMAN... 56042 VA
TOTAL CONNECTED LOAD: 56442 VA
PANEL TOTALS
TOTAL LOAD: 18248 VA 19317 VA 18878 VA
41 20 1 SPARE 0 0 -- SPACE -- -- 42
39 20 1 SPARE 0 0 -- SPACE -- -- 40
37 20 1 SPARE 0 0 -- SPACE -- -- 38
35 20 1 SPARE 0 0 -- SPACE -- -- 36
33 20 1 SPARE 0 0 -- SPACE -- -- 34
31 20 1 SPARE 0 0 -- SPACE -- -- 32
29 -- -- -- -- 2105 0 -- SPACE -- -- 30
27 -- -- -- -- 2105 0 -- SPACE -- -- 28
25 20 3 HWP-2 GAS RISER ROOM 128 3#12, #12G., 3/4'' C. 2105 0 -- SPACE -- -- 26
23 -- -- -- -- 2105 0 SPARE 1 20 24
21 -- -- -- -- 2105 0 SPARE 1 20 22
19 20 3 HWP-1 GAS RISER ROOM 128 3#12, #12G., 3/4'' C. 2105 0 SPARE 1 20 20
17 20 1 WEST 2ND FLR LTG 2#12, #12G., 3/4'' C. 363 0 SPARE 1 20 18
15 20 1 EAST 2ND FLR LTG 2#12, #12G., 3/4'' C. 554 0 SPARE 1 20 16
13 20 1 LIGHTING 2#12, #12G., 3/4'' C. 33 0 SPARE 1 20 14
11 -- -- -- -- 6025 0 SPARE 1 20 12
9 -- -- -- -- 6025 0 SPARE 1 20 10
7 20 3 AHU-1 3#10, #10G., 3/4'' C. 6025 0 SPARE 1 20 8
5 -- -- -- -- 8280 0 SPARE 1 20 6
3 -- -- -- -- 8528 0 SPARE 1 20 4
1 50 3 PANEL ELP1 VIA ET1 SEE ONE-LINE 7980 0 SPARE 1 20 2
# B... P LOAD SERVED WIRE / GROUND /... A B C WIRE / GROUND / CONDUIT LOAD SERVED P B... #
NOTES:
ENCLOSURE: NEMA 1 MCB RATING: 225 A
MOUNTING: SURFACE WIRES: 4 MAINS RATING: 100 A
SUPPLY FROM: MDB PHASE: 3 MAINS TYPE: MCB
LOCATION: ELECTRICAL ROOM 119 VOLTAGE: 480Y/277V A.I.C. RATING: 14,000 RMS SYMMETRICAL
PANELBOARD: EHP1
DEMAND WITH EXPANSION: 81 A
TOTAL ESTIMATED DEMAN... 68 A
TOTAL CONNECTED... 69 A
TOTAL ESTIMATED DEMAN... 24388 VA
TOTAL CONNECTED LOAD: 24788 VA
PANEL TOTALS
TOTAL LOAD: 7980 VA 8528 VA 8280 VA
41 20 1 UH-3 2#12, #12 G., 3/4" C. 360 0 -- SPACE -- -- 42
39 20 1 UH-1, UH-2, EF-1 2#12, #12G., 3/4'' C. 1248 0 -- SPACE -- -- 40
37 20 1 HWB-2 2#12, #12G., 3/4'' C. 720 0 -- SPACE -- -- 38
35 20 1 HWB-1 2#12, #12G., 3/4'' C. 720 0 -- SPACE -- -- 36
33 20 1 RECEPTACLE NIPR 202 2#12, #12G., 3/4'' C. 1500 0 -- SPACE -- -- 34
31 20 1 RECEPT SIPR 201 2#12, #12G., 3/4'' C. 1080 0 -- SPACE -- -- 32
29 20 1 RECEPT SIPR 201 2#12, #12G., 3/4'' C. 1080 0 -- SPACE -- -- 30
27 20 1 RECEPT SIPR 201 2#12, #12G., 3/4'' C. 360 0 -- SPACE -- -- 28
25 20 1 RECEPT SIPR 201 2#12, #12G., 3/4'' C. 1080 0 -- SPACE -- -- 26
23 20 1 RECEPT SIPR 201 2#12, #12G., 3/4'' C. 720 0 SPARE 1 20 24
21 20 1 RECEPT SIPR 201 2#12, #12G., 3/4'' C. 720 0 SPARE 1 20 22
19 20 1 RECEPT NIPR 202 2#12, #12G., 3/4'' C. 1080 0 SPARE 1 20 20
17 20 1 RECEPT NIPR 202 2#12, #12G., 3/4'' C. 1080 1080 2#12, #12G., 3/4'' C. ELEVATOR CAB LIGHTS 1 20 18
15 20 1 RECEPT NIPR 202 2#12, #12G., 3/4'' C. 900 1080 2#12, #12G., 3/4'' C. ELEVATOR CB SHUNT TRIP 1 20 16
13 20 1 RECEPT NIPR 202 2#12, #12G., 3/4'' C. 720 360 2#12, #12G., 3/4'' C. JBOX COMM 118 1 20 14
11 20 1 RECEPT NIPR 202 2#12, #12G., 3/4'' C. 1080 1080 2#12, #12G., 3/4'' C. ELEVATOR CB SHUNT TRIP 1 20 12
9 20 1 RECEPT NIPR 202 2#12, #12G., 3/4'' C. 1500 360 2#12, #12G., 3/4'' C. DAMPERS HVAC MECH ROOM... 1 60 10
7 20 1 RECEPT MECH ROOM 203 2#10, #10G., 3/4'' C. 720 360 2#12, #12G., 3/4'' C. UH-7 1 20 8
5 20 1 RECEPT MECH ROOM 203 2#10, #10G., 3/4'' C. 720 360 2#12, #12G., 3/4'' C. UH-6 ELECTRICAL ROOM 119 1 20 6
3 20 1 DDC PANEL 2#12, #12G., 3/4'' C. 500 360 2#12, #12G., 3/4'' C. UH-5 WEAPONS VAULT 121 1 20 4
1 20 1 RECEPTACLE NIPR 202 2#12, #12G., 3/4'' C. 1500 360 2#12, #12G., 3/4'' C. HVAC WOOD SHOP 139 1 20 2
# B... P LOAD SERVED WIRE / GROUND /... A B C WIRE / GROUND / CONDUIT LOAD SERVED P B... #
NOTES:
ENCLOSURE: NEMA 1 MCB RATING: 225 A
MOUNTING: SURFACE WIRES: 4 MAINS RATING: 100 A
SUPPLY FROM: ET1 PHASE: 3 MAINS TYPE: MCB
LOCATION: WAREHOUSE 130 VOLTAGE: 208Y/120V A.I.C. RATING: 10,000 RMS SYMMETRICAL
PANELBOARD: ELP1
DEMAND WITH EXPANSION: 29 A
TOTAL ESTIMATED DEMAN... 24 A
TOTAL CONNECTED... 24 A
TOTAL ESTIMATED DEMAN... 8640 VA
TOTAL CONNECTED LOAD: 8640 VA
PANEL TOTALS
TOTAL LOAD: 3120 VA 3120 VA 2400 VA
41 20 1 SPARE 0 0 -- SPACE -- -- 42
39 20 1 SPARE 0 0 -- SPACE -- -- 40
37 20 1 SPARE 0 0 -- SPACE -- -- 38
35 20 1 SPARE 0 0 -- SPACE -- -- 36
33 20 1 SPARE 0 0 -- SPACE -- -- 34
31 20 1 SPARE 0 0 -- SPACE -- -- 32
29 20 1 SPARE 0 0 -- SPACE -- -- 30
27 20 1 SPARE 0 0 -- SPACE -- -- 28
25 20 1 SPARE 0 0 -- SPACE -- -- 26
23 20 1 SPARE 0 0 -- SPACE -- -- 24
21 20 1 SPARE 0 0 -- SPACE -- -- 22
19 20 1 SPARE 0 0 -- SPACE -- -- 20
17 20 1 SPARE 0 0 -- SPACE -- -- 18
15 20 1 RECEPT COMM 118 2#12, #12G., 3/4'' C. 720 0 -- SPACE -- -- 16
13 20 1 RECEPT COMM 118 2#12, #12G., 3/4'' C. 720 0 -- SPACE -- -- 14
11 20 1 RECEPT COMM 118 2#12, #12G., 3/4'' C. 1200 0 -- SPACE -- -- 12
9 20 1 RECEPT COMM 118 2#12, #12G., 3/4'' C. 1200 0 -- SPACE -- -- 10
7 20 1 RECEPT COMM 118 2#12, #12G., 3/4'' C. 1200 0 -- SPACE -- -- 8
5 20 1 RECEPT COMM 118 2#12, #12G., 3/4'' C. 1200 0 -- SPACE -- -- 6
3 20 1 RECEPT COMM 118 2#12, #12G., 3/4'' C. 1200 0 -- SPACE -- -- 4
1 20 1 RECEPT COMM 118 2#12, #12G., 3/4'' C. 1200 0 -- SPACE -- -- 2
# B... P LOAD SERVED WIRE / GROUND /... A B C WIRE / GROUND / CONDUIT LOAD SERVED P B... #
NOTES:
ENCLOSURE: NEMA 1 MCB RATING: 60 A
MOUNTING: SURFACE WIRES: 4 MAINS RATING: 100 A
SUPPLY FROM: LP3 PHASE: 3 MAINS TYPE: MCB
LOCATION: COMM 118 VOLTAGE: 208Y/120V A.I.C. RATING: 10K AIC RMS SYMMETRICAL
PANELBOARD: LTR
A 08/01/19 KOW CGK TYPE B-2 SUBMITTAL
B 01/03/20 KOW CGK TYPE B-3 SUBMITTAL
C 10/15/20 KOW CGK ADDENDUM 01
C
C
C
| 102554_E_Central_absantos - Sheet - E-701 - PANELBOARD SCHEDULES |
| 102554_E_Central_absantos - Sheet - E-702 - PANELBOARD SCHEDULES |
| 102554_E_Central_absantos - Sheet - E-703 - PANELBOARD SCHEDULES |
| 102554_E_Central_absantos - Sheet - E-705 - PANELBOARD SCHEDULES |
File details come from the government source that posted it. Updated .