About this file

This solicitation requests proposals for the construction of an addition and renovation to an existing base supply facility located at the 148th Fighter Wing of the Duluth Air National Guard Base in Minnesota. Services required include construction project management, site work, demolition, interior reconfiguration, replacement of mechanical, electrical and plumbing systems, and restoration of brick facade and standing seam metal roof to match existing building. The project magnitude is between $5-10 million and must be completed within 540 days of notice to proceed. The NAICS code is 236220 for commercial and institutional building construction. This is a small business set-aside solicitation issued by the US Property and Fiscal Office for Minnesota on behalf of the Department of the Army Minnesota Army National Guard. The pre-proposal conference is scheduled for October 7th and proposals are due October 29th. The source selection will be based on best value past performance and price factors without discussions.

View the file

Other files for this federal contract opportunity

Other files attached to B222 Renovation and Addition, newest first.
File Type Posted
Addendum 09.doc DOC document
B 08 W912LM20R1003 Amendment 01 B222 Renovation and Addition.pdf PDF
Addendum 08.doc DOC document
Q and A Addendum 07 27Oct2020 08 71 00.pdf PDF
Q and A Addendum 07 27Oct2020 08 51 13.pdf PDF
Addendum 07.doc DOC document
Q and A Addendum 07 27Oct2020 08 81 00.pdf PDF
Q and A Addendum 07 27Oct2020 102554_ - Sheet - AD010 - GROUND FLOOR DEMOLITION PLAN.pdf PDF
Q and A Addendum 07 27Oct2020 08 11 13.pdf PDF
Q and A Addendum 07_Structural.pdf PDF
Q and A Addendum 07 27Oct2020 102554_ - Sheet - A-353 - SECTION DETAILS.pdf PDF
B222_2007_ExistingWindowInformation.pdf PDF
222-1976-Original Construction.pdf PDF
222-1984-84005-Addition to Engine Shop.pdf PDF
B222_2007_Renovation.pdf PDF
Q and A Addendum 05 09 29 00 26OCT20.pdf PDF
Addendum 05 and 06.doc DOC document
Q and A Addendum 05 08 33 13 26OCT20.pdf PDF
Q and A Addendum 03 Architecture.pdf PDF
Addendum 03 and 04.doc DOC document
Q and A Addendum 01_02 (08 71 00).pdf PDF
Q and A Addendum 01_02 (07 27 10.00 10).pdf PDF
Addendum 01 and 02.doc DOC document
Q and A Addendum 01_02 (07 05 23).pdf PDF
Q and A Addendum 01_02 (08 81 00).pdf PDF
Q and A Addendum 01_02 (14 21 23).pdf PDF
Preproposal Conference.pdf PDF
MATOC Preproposal Conference.pdf PDF
B222 Site visit.pdf PDF
B 04 DB Wage Det 28 Sep.pdf PDF
EXHIBIT_C_-_Reference_Questionnaire_Package NEW Ld.docx DOCX document
EXHIBIT A Ld.doc DOC document
148FW Form 66.pdf PDF
EXHIBIT B Ld.doc DOC document
B 08 W912LM20R1003 B222 Renovation and Addition.pdf PDF
Exhibit D_Letter of Commitment Ld.docx DOCX document
Show all 36

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the state of Minnesota.

KEVIN O. WATSON, PE

DATE: 01/03/20 LIC. NO. 51801

date detailed checkeddesigned ofsheet sheets project contract rev.drawing file

no. date descriptionby ckd

1 1312111098765432

I

H

G

F

E

D

C

B

A

B222 RENOVATION AND ADAL

US NATIONAL GUARD BUREAU

MN ANG, 148TH FIGHTER WING

DULUTH, MINNESOTA

8201 NORMAN CENTER DR.

BLOOMINGTON, MN 55437

763-277-4676

102554

C

102554_E_CENTRAL

E-701

PANELBOARD SCHEDULES

12/20/19

K. WATSON C. KLOS

A. ALLEN

DEMAND WITH EXPANSION: 26 A

TOTAL ESTIMATED DEMAN... 22 A

TOTAL CONNECTED... 22 A

TOTAL ESTIMATED DEMAN... 18053 VA

TOTAL CONNECTED LOAD: 18053 VA

PANEL TOTALS

TOTAL LOAD: 4496 VA 5110 VA 8447 VA

41 20 1 SPARE 0 0 -- SPACE -- -- 42

39 20 1 SPARE 0 0 -- SPACE -- -- 40

37 20 1 SPARE 0 0 -- SPACE -- -- 38

35 20 1 SPARE 0 0 -- SPACE -- -- 36

33 20 1 SPARE 0 0 -- SPACE -- -- 34

31 20 1 SPARE 0 0 -- SPACE -- -- 32

29 20 1 SPARE 0 0 -- SPACE -- -- 30

27 20 1 SPARE 0 0 -- SPACE -- -- 28

25 20 1 SPARE 0 0 -- SPACE -- -- 26

23 -- -- -- -- 1795 0 SPARE 1 20 24

21 -- -- -- -- 1798 0 SPARE 1 20 22

19 40 3 LIGHTING INVERTER SEE ONE-LINE 1777 0 SPARE 1 20 20

17 20 1 WEAPONS VAULT/ REST RM... 2#12, #12G., 3/4'' C. 2190 0 SPARE 1 20 18

15 20 1 EXTERIOR LTG - SOUTH 2#12, #12G., 3/4'' C. 214 0 SPARE 1 20 16

13 20 1 WEST ADMIN AREA LTG 2#12, #12G., 3/4'' C. 1979 0 SPARE 1 20 14

11 20 1 TMO AREA LTG 2#10, #10G. 3/4" C. 2244 0 SPARE 1 20 12

9 20 1 WEST WAREHOUSE AREA LTG 2#12, #12G., 3/4'' C. 1216 0 SPARE 1 20 10

7 0 SPARE 1 20 8

5 -- -- -- -- 2218 0 SPARE 1 20 6

3 -- -- -- -- 1882 0 SPARE 1 20 4

1 60 3 HP-1B SEE ONE-LINE 740 0 SPARE 1 20 2

# B... P LOAD SERVED WIRE / GROUND /... A B C WIRE / GROUND / CONDUIT LOAD SERVED P B... #

NOTES:

ENCLOSURE: NEMA 1 MCB RATING: 125 A

MOUNTING: SURFACE WIRES: 4 MAINS RATING: 100 A

SUPPLY FROM: MDB PHASE: 3 MAINS TYPE: MCB

LOCATION: ELECTRICAL ROOM 119 VOLTAGE: 480Y/277V A.I.C. RATING: 22K AIC RMS SYMMETRICAL

PANELBOARD: HP1A

DEMAND WITH EXPANSION: 139 A

TOTAL ESTIMATED DEMAN... 116 A

TOTAL CONNECTED... 124 A

TOTAL ESTIMATED DEMAN... 96594 VA

TOTAL CONNECTED LOAD: 103480 VA

PANEL TOTALS

TOTAL LOAD: 35055 VA 36809 VA 31616 VA

41 -- -- -- -- 0 0 -- SPACE -- -- 42

39 -- -- -- -- 0 0 -- SPACE -- -- 40

37 20 3 SPARE 0 0 -- SPACE -- -- 38

35 -- -- -- -- 0 0 -- SPACE -- -- 36

33 -- -- -- -- 0 0 -- SPACE -- -- 34

31 20 3 SPARE 0 0 -- SPACE -- -- 32

29 -- -- -- -- 0 0 -- SPACE -- -- 30

27 -- -- -- -- 0 0 -- SPACE -- -- 28

25 20 3 SPARE 0 0 -- SPACE -- -- 26

23 -- -- -- -- 7202 0 -- -- -- -- 24

21 -- -- -- -- 7202 0 -- -- -- -- 22

19 40 3 CU-1 3#8, #10G., 3/4'' C. 7202 0 SPARE 3 60 20

17 -- -- -- -- 13833 0 -- -- -- -- 18

15 -- -- -- -- 14913 0 -- -- -- -- 16

13 100 3 HP2B SEE ONE-LINE 13993 0 SPARE 3 60 14

11 -- -- -- -- 1256 0 -- -- -- -- 12

9 -- -- -- -- 2609 0 -- -- -- -- 10

7 30 3 LP-2 VIA T-2 SEE ONE-LINE 2049 0 SPARE 3 30 8

5 -- -- -- -- 9325 0 -- -- -- -- 6

3 -- -- -- -- 12085 0 -- -- -- -- 4

1 100 3 HP-2A SEE ONE-LINE 11811 0 SPARE 3 30 2

# B... P LOAD SERVED WIRE / GROUND /... A B C WIRE / GROUND / CONDUIT LOAD SERVED P B... #

NOTES:

ENCLOSURE: NEMA 1 MCB RATING: 225 A

MOUNTING: SURFACE WIRES: 4 MAINS RATING: 225 A

SUPPLY FROM: MDB PHASE: 3 MAINS TYPE: MCB

LOCATION: ELECTRICAL ROOM 119 VOLTAGE: 480Y/277V A.I.C. RATING: 22K AIC RMS SYMMETRICAL

PANELBOARD: HP2

DEMAND WITH EXPANSION: 345 A

TOTAL ESTIMATED DEMAND CURRENT: 287 A

TOTAL CONNECTED CURRENT: 343 A

TOTAL ESTIMATED DEMAND LOAD: 238949 VA

TOTAL CONNECTED LOAD: 285395 VA

SWITCHBOARD TOTALS

12 SPACE -- -- -- -- 0 VA --

11 SPACE -- -- -- -- 0 VA --

10 SPARE 1 100 A -- 0 VA

9 SPARE 1 125 A -- 0 VA

8 SPARE 1 200 A -- 0 VA

7 EEWH-1 SEE ONE-LINE 3 175 A 250 A 10800 VA

6 ELEVATOR SEE ONE-LINE 3 30 A 125 A 16620 VA

5 LP3 VIA T3 SEE ONE-LINE 3 125 A 125 A 80000 VA

4 HP2 SEE ONE-LINE 3 225 A 250 A 103480 VA

3 HP1A SEE ONE-LINE 3 125 A 125 A 18053 VA

2 SPD SEE ONE-LINE 3 30 A -- 0 VA

1 EHP1 SEE ONE-LINE 3 200 A 250 A 56442 VA

CKT LOAD NAME DESIGN WIRE AND CONDUIT POLES

TRIP

RATING

FRAME

SIZE

LOAD COMMENTS

NOTES:

ENCLOSURE: NEMA 1 MCB RATING: 600 A

MOUNTING: FLOOR WIRES: 4 MAINS RATING: 600 A

SUPPLY FROM: PHASES: 3 MAINS TYPE: MDB

LOCATION: ELECTRICAL ROOM 119 VOLTAGE: 480Y/277V A.I.C. RATING: 22K AIC RMS SYMMETRICAL

SWITCHBOARD: MDB

DEMAND WITH EXPANSION: 7 A

TOTAL ESTIMATED DEMAN... 6 A

TOTAL CONNECTED... 6 A

TOTAL ESTIMATED DEMAN... 4840 VA

TOTAL CONNECTED LOAD: 4840 VA

PANEL TOTALS

TOTAL LOAD: 740 VA 1882 VA 2218 VA

41 20 1 SPARE 0 0 -- SPACE -- -- 42

39 20 1 SPARE 0 0 -- SPACE -- -- 40

37 20 1 SPARE 0 0 -- SPACE -- -- 38

35 20 1 SPARE 0 0 -- SPACE -- -- 36

33 20 1 SPARE 0 0 -- SPACE -- -- 34

31 20 1 SPARE 0 0 -- SPACE -- -- 32

29 20 1 SPARE 0 0 -- SPACE -- -- 30

27 20 1 SPARE 0 0 -- SPACE -- -- 28

25 20 1 SPARE 0 0 -- SPACE -- -- 26

23 20 1 SPARE 0 0 SPARE 1 20 24

21 20 1 SPARE 0 0 SPARE 1 20 22

19 20 1 SPARE 0 0 SPARE 1 20 20

17 20 1 SPARE 0 0 SPARE 1 20 18

15 20 1 SPARE 0 0 SPARE 1 20 16

13 20 1 SPARE 0 0 SPARE 1 20 14

11 20 1 EAST WAREHOUSE 2#12, #12G., 3/4'' C. 2218 0 SPARE 1 20 12

9 20 1 EAST DEPLOYMENT AREA 2#12, #12G., 3/4'' C. 1583 0 SPARE 1 20 10

7 20 1 EAST ADMIN AREA LTG 2#12, #12G., 3/4'' C. 10 0 SPARE 1 20 8

5 20 1 SPARE 0 0 SPARE 1 20 6

3 20 1 EXTERIOR LTG - NORTH 2#12, #12G., 3/4'' C. 299 0 SPARE 1 20 4

1 20 1 EAST ADMIN AREA LTG 2#12, #12G., 3/4'' C. 730 0 SPARE 1 20 2

# B... P LOAD SERVED WIRE / GROUND /... A B C WIRE / GROUND / CONDUIT LOAD SERVED P B... #

NOTES:

ENCLOSURE: NEMA 1 MCB RATING: 125 A

MOUNTING: SURFACE WIRES: 4 MAINS RATING: 60 A

SUPPLY FROM: HP1A PHASE: 3 MAINS TYPE: MCB

LOCATION: WAREHOUSE 130 VOLTAGE: 480Y/277V A.I.C. RATING: 10K AIC RMS SYMMETRICAL

PANELBOARD: HP1B

SERVICE TRANSFORMER

A 08/01/19 KOW CGK TYPE B-2 SUBMITTAL

B 01/03/20 KOW CGK TYPE B-3 SUBMITTAL

C 10/15/20 KOW CGK ADDENDUM 01

C

C

C

C

C

10/15/20 by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the state of Minnesota.

KEVIN O. WATSON, PE

DATE: 01/03/20 LIC. NO. 51801

date detailed checkeddesigned ofsheet sheets project contract rev.drawing file

no. date descriptionby ckd

1 1312111098765432

I

H

G

F

E

D

C

B

A

B222 RENOVATION AND ADAL

US NATIONAL GUARD BUREAU

MN ANG, 148TH FIGHTER WING

DULUTH, MINNESOTA

8201 NORMAN CENTER DR.

BLOOMINGTON, MN 55437

763-277-4676

102554

C

102554_E_CENTRAL

E-702

PANELBOARD SCHEDULES

12/20/19

K. WATSON C. KLOS

A. ALLEN

DEMAND WITH EXPANSION: 45 A

TOTAL ESTIMATED DEMAN... 38 A

TOTAL CONNECTED... 40 A

TOTAL ESTIMATED DEMAN... 31320 VA

TOTAL CONNECTED LOAD: 33220 VA

PANEL TOTALS

TOTAL LOAD: 11811 VA 12085 VA 9325 VA

41 0 -- SPACE -- -- 42

39 0 -- SPACE -- -- 40

37 0 -- SPACE -- -- 38

35 -- -- -- -- 60 0 -- SPACE -- -- 36

33 -- -- -- -- 60 0 -- SPACE -- -- 34

31 20 3 ELECTRIC FORKLIFT RECEPT 3#12, #12G., 3/4'' C. 60 0 -- SPACE -- -- 32

29 -- -- -- -- 388 0 -- SPACE -- -- 30

27 -- -- -- -- 388 0 -- SPACE -- -- 28

25 15 3 EF-3 3#12, #12G., 3/4'' C. 388 0 -- SPACE -- -- 26

23 -- -- -- -- 467 0 SPARE 1 20 24

21 -- -- -- -- 467 0 SPARE 1 20 22

19 15 3 EEWH-2 EYEWASH 3#12, #12G., 3/4'' C. 467 0 SPARE 1 20 20

17 -- -- -- -- 1385 0 SPARE 1 20 18

15 -- -- -- -- 1385 0 SPARE 1 20 16

13 15 3 ATO-3 3#12, #12G., 3/4'' C. 1385 0 SPARE 1 20 14

11 -- -- -- -- 1385 0 SPARE 1 20 12

9 -- -- -- -- 1385 0 SPARE 1 20 10

7 15 3 ATO-2 3#12, #12G., 3/4'' C. 1385 0 SPARE 1 20 8

5 -- -- -- -- 5640 0 SPARE 1 20 6

3 -- -- -- -- 8400 0 SPARE 1 20 4

1 50 3 LP-2A VIA T-2A 3#12, #12G., 3/4'' C. 8126 0 SPARE 1 20 2

# B... P LOAD SERVED WIRE / GROUND /... A B C WIRE / GROUND / CONDUIT LOAD SERVED P B... #

NOTES:

ENCLOSURE: NEMA 1 MCB RATING: 225 A

MOUNTING: SURFACE WIRES: 4 MAINS RATING: 100 A

SUPPLY FROM: HP2 PHASE: 3 MAINS TYPE: MCB

LOCATION: WAREHOUSE 113 VOLTAGE: 480Y/277V A.I.C. RATING: 14K AIC RMS SYMMETRICAL

PANELBOARD: HP2A

DEMAND WITH EXPANSION: 62 A

TOTAL ESTIMATED DEMAN... 51 A

TOTAL CONNECTED... 51 A

TOTAL ESTIMATED DEMAN... 42740 VA

TOTAL CONNECTED LOAD: 42740 VA

PANEL TOTALS

TOTAL LOAD: 13993 VA 14913 VA 13833 VA

41 -- -- -- -- 1333 0 -- SPACE -- -- 42

39 -- -- -- -- 1333 0 -- SPACE -- -- 40

37 15 3 EWH-1 NIPR 202 3#12, #12G., 3/4'' C. 1333 0 -- SPACE -- -- 38

35 -- -- -- -- 467 0 -- SPACE -- -- 36

33 -- -- -- -- 467 0 -- SPACE -- -- 34

31 15 3 EEWH-2 EYEWASH - RM 130 3#12, #12G., 3/4'' C. 467 0 -- SPACE -- -- 32

29 -- -- -- -- 467 0 -- SPACE -- -- 30

27 -- -- -- -- 467 0 -- SPACE -- -- 28

25 15 3 EEWH-2 EYEWASH - RM 130 3#12, #12G., 3/4'' C. 467 0 -- SPACE -- -- 26

23 -- -- -- -- 3667 0 SPARE 1 20 24

21 -- -- -- -- 3667 0 SPARE 1 20 22

19 30 3 AC-1 WAREHOUSE 130 3#10, #10G., 3/4'' C. 3667 0 SPARE 1 20 20

17 -- -- -- -- 3324 0 SPARE 1 20 18

15 -- -- -- -- 3324 0 SPARE 1 20 16

13 15 3 RECEPTACLE WAREHOUSE 130 3#12, #12G., 3/4'' C. 3324 0 SPARE 1 20 14

11 -- -- -- -- 2360 0 SPARE 1 20 12

9 -- -- -- -- 3440 0 SPARE 1 20 10

7 50 3 LP-2B VIA T-2B SEE ONE-LINE 2520 0 SPARE 1 20 8

5 -- -- -- -- 2216 0 SPARE 1 20 6

3 -- -- -- -- 2216 0 SPARE 1 20 4

1 15 3 ATO-1 3#12, #12G., 3/4'' C. 2216 0 SPARE 1 20 2

# B... P LOAD SERVED WIRE / GROUND /... A B C WIRE / GROUND / CONDUIT LOAD SERVED P B... #

NOTES:

ENCLOSURE: NEMA 1 MCB RATING: 225 A

MOUNTING: SURFACE WIRES: 4 MAINS RATING: 100 A

SUPPLY FROM: HP2 PHASE: 3 MAINS TYPE: MCB

LOCATION: WAREHOUSE 130 VOLTAGE: 480Y/277V A.I.C. RATING: 14K AIC RMS SYMMETRICAL

PANELBOARD: HP2B

DEMAND WITH EXPANSION: 20 A

TOTAL ESTIMATED DEMAN... 16 A

TOTAL CONNECTED... 16 A

TOTAL ESTIMATED DEMAN... 5914 VA

TOTAL CONNECTED LOAD: 5914 VA

PANEL TOTALS

TOTAL LOAD: 2049 VA 2609 VA 1256 VA

41 20 1 SPARE 0 0 -- SPACE -- -- 42

39 20 1 SPARE 0 0 -- SPACE -- -- 40

37 20 1 SPARE 0 0 -- SPACE -- -- 38

35 20 1 SPARE 0 0 -- SPACE -- -- 36

33 20 1 SPARE 0 0 -- SPACE -- -- 34

31 20 1 SPARE 0 0 -- SPACE -- -- 32

29 20 1 SPARE 0 0 -- SPACE -- -- 30

27 20 1 SPARE 0 0 -- SPACE -- -- 28

25 20 1 SPARE 0 0 -- SPACE -- -- 26

23 20 1 SPARE 0 0 -- SPACE -- -- 24

21 20 1 SPARE 0 0 SPARE 1 20 22

19 20 1 MOTORIZED DAMPERS MECH... 2#12, #12G., 3/4'' C. 180 0 SPARE 1 20 20

17 20 1 MOTORIZED DAMPERS POWER... 2#12, #12G., 3/4'' C. 360 0 SPARE 1 20 18

15 20 1 OH DOOR RM 121 2#12, #12G., 3/4'' C. 1000 0 SPARE 1 20 16

13 20 1 EF-6 2#12, #12G., 3/4'' C. 360 0 SPARE 1 20 14

11 20 1 EF-4 MECH RM 203 2#12, #12 G., 3/4" C. 696 0 SPARE 1 20 12

9 20 1 VAV - 5, 6, 11 2#12, #12G., 3/4'' C. 300 0 SPARE 1 20 10

7 20 1 VAV - 3 & 4 2#10, #10G., 3/4'' C. 200 0 SPARE 1 20 8

5 20 1 VAV - 1 & 2 2#12, #12G., 3/4'' C. 200 0 SPARE 1 20 6

3 -- -- -- -- 1309 0 SPARE 1 20 4

1 20 2 ACCU-1, CRU-1 2#12, #12G., 3/4'' C. 1309 0 SPARE 1 20 2

# B... P LOAD SERVED WIRE / GROUND /... A B C WIRE / GROUND / CONDUIT LOAD SERVED P B... #

NOTES:

ENCLOSURE: NEMA 1 MCB RATING: 225 A

MOUNTING: SURFACE WIRES: 4 MAINS RATING: 100 A

SUPPLY FROM: T2 PHASE: 3 MAINS TYPE: MCB

LOCATION: ELECTRICAL ROOM 119 VOLTAGE: 208Y/120V A.I.C. RATING: 10K AIC RMS SYMMETRICAL

PANELBOARD: LP2

DEMAND WITH EXPANSION: 68 A

TOTAL ESTIMATED DEMAN... 57 A

TOTAL CONNECTED... 62 A

TOTAL ESTIMATED DEMAN... 20356 VA

TOTAL CONNECTED LOAD: 22166 VA

PANEL TOTALS

TOTAL LOAD: 8126 VA 8400 VA 5640 VA

41 0 -- SPACE -- -- 42

39 0 -- SPACE -- -- 40

37 0 -- SPACE -- -- 38

35 20 1 RECEPTACLE ROOF 2#12, #12 G., 3/4" C. 540 0 -- SPACE -- -- 36

33 30 1 RECEPTACLE WAREHOUSE 113 2#10, #10G., 3/4'' C. 2400 0 -- SPACE -- -- 34

31 30 1 RECEPTACLE WAREHOUSE 113 2#10, #10G., 3/4'' C. 2400 0 -- SPACE -- -- 32

29 20 1 MOTORIZED DAMPERS POWER... 2#12, #12G., 3/4'' C. 180 0 -- SPACE -- -- 30

27 20 1 MOTORIZED DAMPERS POWER... 2#12, #12G., 3/4'' C. 360 0 -- SPACE -- -- 28

25 20 1 DWHP-1 JANITOR 123 2#12, #12G., 3/4'' C. 270 0 -- SPACE -- -- 26

23 30 1 DRYER RM 113 2#12, #12G., 3/4'' C. 2400 0 SPARE 1 20 24

21 -- -- -- -- 2400 0 SPARE 1 20 22

19 30 2 SPEC. RECEPT E WAREHOUSE... 2#10, #10G., 3/4'' C. 2400 0 SPARE 1 20 20

17 20 1 OH DOOR 137A DEPLOYMENT... 2#12, #12 G., 3/4" C. 1080 0 SPARE 1 20 18

15 20 1 WASHER RM 113 2#12, #12G., 3/4'' C. 1080 0 SPARE 1 20 16

13 20 1 OH-113B 2#12, #12G., 3/4'' C. 1080 0 SPARE 1 20 14

11 20 1 MOTORIZED DAMPERS... 2#12, #12G., 3/4'' C. 360 0 SPARE 1 20 12

9 20 1 HSF-1 2#12, #12G., 3/4'' C. 1080 0 SPARE 1 20 10

7 20 1 VAV - 7 & 8 2#12, #12 G., 3/4" C. 200 0 SPARE 1 20 8

5 20 1 GWH-1 2#12, #12 G., 3/4" C. 1080 0 SPARE 1 20 6

3 20 1 GIH-1 2#12, #12 G., 3/4" C. 1080 0 SPARE 1 20 4

1 20 1 EF- 2, 5, & 7 2#12, #12 G., 3/4" C. 1776 0 SPARE 1 20 2

# B... P LOAD SERVED WIRE / GROUND /... A B C WIRE / GROUND / CONDUIT LOAD SERVED P B... #

NOTES:

ENCLOSURE: NEMA 1 MCB RATING: 225 A

MOUNTING: SURFACE WIRES: 4 MAINS RATING: 100 A

SUPPLY FROM: T2A PHASE: 3 MAINS TYPE: MCB

LOCATION: WAREHOUSE 113 VOLTAGE: 208Y/120V A.I.C. RATING: 10K AIC RMS SYMMETRICAL

PANELBOARD: LP2A

A 08/01/19 KOW CGK TYPE B-2 SUBMITTAL

B 01/03/20 KOW CGK TYPE B-3 SUBMITTAL

C 10/15/20 KOW CGK ADDENDUM 01

C

C

C by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the state of Minnesota.

KEVIN O. WATSON, PE

DATE: 01/03/20 LIC. NO. 51801

date detailed checkeddesigned ofsheet sheets project contract rev.drawing file

no. date descriptionby ckd

1 1312111098765432

I

H

G

F

E

D

C

B

A

B222 RENOVATION AND ADAL

US NATIONAL GUARD BUREAU

MN ANG, 148TH FIGHTER WING

DULUTH, MINNESOTA

8201 NORMAN CENTER DR.

BLOOMINGTON, MN 55437

763-277-4676

102554

C

102554_E_CENTRAL

E-703

PANELBOARD SCHEDULES

12/20/19

K. WATSON C. KLOS

A. ALLEN

DEMAND WITH EXPANSION: 53 A

TOTAL ESTIMATED DEMAN... 44 A

TOTAL CONNECTED... 57 A

TOTAL ESTIMATED DEMAN... 15980 VA

TOTAL CONNECTED LOAD: 20460 VA

PANEL TOTALS

TOTAL LOAD: 6410 VA 6900 VA 7150 VA

41 20 1 ICE MACHINE BREAK ROOM 115 2#12, #12G., 3/4'' C. 1500 0 SPARE 1 20 42

39 20 1 REFRIGERATOR BREAK ROOM... 2#12, #12G., 3/4'' C. 1500 0 SPARE 1 20 40

37 -- -- -- -- 90 0 SPARE 1 20 38

35 20 2 RANGE BREAK ROOM 115 2#12, #12G., 3/4'' C. 90 0 SPARE 1 20 36

33 20 1 RECEPT BREAK ROOM 115 2#12, #12G., 3/4'' C. 1080 0 SPARE 1 20 34

31 20 1 DISPOSAL BREAK ROOM 115 2#12, #12G., 3/4'' C. 1500 0 SPARE 1 20 32

29 20 1 MICROWAVE BREAK ROOM 115 2#12, #12G., 3/4'' C. 1500 0 SPARE 1 20 30

27 20 1 RECEPT 114, 115 2#12, #12G., 3/4'' C. 900 0 SPARE 1 20 28

25 20 1 RECEPT 114, 115 2#12, #12G., 3/4'' C. 1080 0 SPARE 1 20 26

23 20 1 OH DOOR 114 2#12, #12G., 3/4'' C. 1000 0 SPARE 1 20 24

21 20 1 RECEPT ORDERLY 112 2#12, #12G., 3/4'' C. 900 0 SPARE 1 20 22

19 20 1 RECEPT ORDERLY 112 2#12, #12G., 3/4'' C. 900 0 SPARE 1 20 20

17 20 1 RECEPT 107,109,111 2#12, #12G., 3/4'' C. 1260 0 SPARE 1 20 18

15 20 1 RECEPT 107, 109, 111 2#12, #12G., 3/4'' C. 1080 0 SPARE 1 20 16

13 20 1 RECEPT 108, 110 2#12, #12G., 3/4'' C. 900 0 SPARE 1 20 14

11 20 1 RECEPT 108, 110 2#12, #12G., 3/4'' C. 900 0 SPARE 1 20 12

9 20 1 RECEPT 103, 106 2#12, #12G., 3/4'' C. 720 0 SPARE 1 20 10

7 20 1 RECEPT 103, 106 2#12, #12G., 3/4'' C. 720 0 SPARE 1 20 8

5 20 1 RECEPT 104, 105 2#12, #12G., 3/4'' C. 900 0 SPARE 1 20 6

3 20 1 RECEPT 104, 105 2#12, #12G., 3/4'' C. 720 0 SPARE 1 20 4

1 20 1 RECEPT CORR 102 2#12, #12G., 3/4'' C. 720 500 2#12, #12G., 1'' C. LIFT STATION PUMP 1 20 2

# B... P LOAD SERVED WIRE / GROUND /... A B C WIRE / GROUND / CONDUIT LOAD SERVED P B... #

ELECTRONIC GRADE PANELBOARD WITH REMOTE SPD, ISOLATED GROUND BUS AND 200% NEUTRAL

NOTES:

ENCLOSURE: NEMA 1 MCB RATING: 225 A

MOUNTING: RECESSED WIRES: 4 MAINS RATING: 100 A

SUPPLY FROM: LP3 PHASE: 3 MAINS TYPE: MCB

LOCATION: Space 48 VOLTAGE: 208Y/120V A.I.C. RATING: 10K AIC RMS SYMMETRICAL

PANELBOARD: LP3A

DEMAND WITH EXPANSION: 175 A

TOTAL ESTIMATED DEMAN... 146 A

TOTAL CONNECTED... 222 A

TOTAL ESTIMATED DEMAN... 52590 VA

TOTAL CONNECTED LOAD: 80000 VA

PANEL TOTALS

TOTAL LOAD: 26480 VA 26210 VA 27310 VA

41 20 1 SPARE 0 0 SPARE 1 20 42

39 20 1 SPARE 0 0 SPARE 1 20 40

37 20 1 SPARE 0 0 SPARE 1 20 38

35 20 1 CUH-1, CUH-2 3#12, #12G., 3/4'' C. 3000 2400 -- -- -- -- 36

33 20 1 SOUTH TV CONF ROOM 117 3#12, #12G., 3/4'' C. 360 3120 -- -- -- -- 34

31 20 1 NORTH TV CONF ROOM 117 3#12, #12G., 3/4'' C. 360 3120 SEE ONE-LINE LTR (COMM RM) 3 60 32

29 20 1 RECEPT JANITOR 123 2#12, #12G., 3/4'' C. 180 0 -- -- -- -- 30

27 20 1 RECEPT ELEC ROOM 119 2#12, #12G., 3/4'' C. 720 1200 -- -- -- -- 28

25 20 1 FLOORBOX CONF ROOM 117 2#12, #12G., 3/4'' C. 1080 1200 SEE ONE-LINE LFP 3 60 26

23 20 1 FLOORBOX CONF ROOM 117 2#12, #12G., 3/4'' C. 1080 2700 -- -- -- -- 24

21 20 1 DEHUMIDIFIER VAULT 121 2#12, #12G., 3/4'' C. 500 2880 -- -- -- -- 22

19 20 1 RECEPT CONF ROOM 117 2#12, #12G., 3/4'' C. 900 3420 SEE ONE-LINE LP3D 3 100 20

17 20 1 RECEPT CONF ROOM 117 2#12, #12G., 3/4'' C. 900 3600 -- -- -- -- 18

15 20 1 RECEPT CONF ROOM 117 2#12, #12G., 3/4'' C. 900 2610 -- -- -- -- 16

13 20 1 RECEPT WEAPONS VAULT 121 2#12, #12G., 3/4'' C. 720 2610 SEE ONE-LINE LP3C 3 100 14

11 20 1 RECEPT WEAPONS VAULT 121 2#12, #12G., 3/4'' C. 720 5040 -- -- -- -- 12

9 20 1 RECEPT WOMEN'S RR 124 2#12, #12G., 3/4'' C. 720 5220 -- -- -- -- 10

7 20 1 RECEPT MEN'S RR 126 2#10, #10G., 3/4'' C. 720 5040 SEE ONE-LINE LP3B 3 100 8

5 20 1 RECEPT STORAGE 115.1 2#12, #12G., 3/4'' C. 540 7150 -- -- -- -- 6

3 20 1 RECEPT CORR 122 2#12, #12G., 3/4'' C. 1080 6900 -- -- -- -- 4

1 20 1 RECEPT CORR 122 2#12, #12G., 3/4'' C. 900 6410 SEE ONE-LINE LP3A 3 100 2

# B... P LOAD SERVED WIRE / GROUND /... A B C WIRE / GROUND / CONDUIT LOAD SERVED P B... #

ELECTRONIC GRADE PANELBOARD WITH REMOTE SPD, ISOLATED GROUND BUS AND 200% NEUTRAL

NOTES:

ENCLOSURE: NEMA 1 MCB RATING: 225 A

MOUNTING: SURFACE WIRES: 4 MAINS RATING: 225 A

SUPPLY FROM: T3 PHASE: 3 MAINS TYPE: MCB

LOCATION: ELECTRICAL ROOM 119 VOLTAGE: 208Y/120V A.I.C. RATING: 10K AIC RMS SYMMETRICAL

PANELBOARD: LP3

DEMAND WITH EXPANSION: 28 A

TOTAL ESTIMATED DEMAN... 23 A

TOTAL CONNECTED... 23 A

TOTAL ESTIMATED DEMAN... 8320 VA

TOTAL CONNECTED LOAD: 8320 VA

PANEL TOTALS

TOTAL LOAD: 2520 VA 3440 VA 2360 VA

41 20 1 SPARE 0 0 -- SPACE -- -- 42

39 20 1 SPARE 0 0 -- SPACE -- -- 40

37 20 1 SPARE 0 0 -- SPACE -- -- 38

35 20 1 SPARE 0 0 -- SPACE -- -- 36

33 20 1 SPARE 0 0 -- SPACE -- -- 34

31 20 1 SPARE 0 0 -- SPACE -- -- 32

29 20 1 SPARE 0 0 -- SPACE -- -- 30

27 20 1 SPARE 0 0 -- SPACE -- -- 28

25 20 1 SPARE 0 0 -- SPACE -- -- 26

23 20 1 OH DOOR RM 137 2#12, #12 G., 3/4" C. 1080 0 SPARE 1 20 24

21 20 1 OH DOOR WAREHOUSE 130 2#12, #12G., 3/4'' C. 1080 0 SPARE 1 20 22

19 20 1 SPARE 0 0 SPARE 1 20 20

17 20 1 SPARE 0 0 SPARE 1 20 18

15 20 1 OH DOOR WAREHOUSE 130 2#12, #12 G., 3/4" C. 1080 0 SPARE 1 20 16

13 20 1 OH DOOR DEPLOYMENT... 2#12, #12G., 3/4'' C. 1080 0 SPARE 1 20 14

11 20 1 VAV - 12 & 13 2#12, #12 G., 3/4" C. 200 0 SPARE 1 20 12

9 20 1 VAV - 9 & 10 2#12, #12G., 3/4'' C. 200 0 SPARE 1 20 10

7 20 1 GIH-4 2#12, #12 G., 3/4" C. 1080 0 SPARE 1 20 8

5 20 1 GIH-3 2#12, #12G., 3/4'' C. 1080 0 SPARE 1 20 6

3 20 1 GIH-2 2#12, #12 G., 3/4" C. 1080 0 SPARE 1 20 4

1 20 1 MOTORIZED DAMPERS POWER... 2#12, #12 G., 3/4" C. 360 0 SPARE 1 20 2

# B... P LOAD SERVED WIRE / GROUND /... A B C WIRE / GROUND / CONDUIT LOAD SERVED P B... #

NOTES:

ENCLOSURE: NEMA 1 MCB RATING: 225 A

MOUNTING: SURFACE WIRES: 4 MAINS RATING: 100 A

SUPPLY FROM: T2B PHASE: 3 MAINS TYPE: MCB

LOCATION: WAREHOUSE 130 VOLTAGE: 208Y/120V A.I.C. RATING: 10K AIC RMS SYMMETRICAL

PANELBOARD: LP2B

DEMAND WITH EXPANSION: 44 A

TOTAL ESTIMATED DEMAN... 37 A

TOTAL CONNECTED... 42 A

TOTAL ESTIMATED DEMAN... 13280 VA

TOTAL CONNECTED LOAD: 15300 VA

PANEL TOTALS

TOTAL LOAD: 5040 VA 5220 VA 5040 VA

41 20 1 SPARE 0 0 SPARE 1 20 42

39 20 1 SPARE 0 0 SPARE 1 20 40

37 20 1 SPARE 0 0 SPARE 1 20 38

35 20 1 RECEPT 113, 128, 129 2#10, #10G., 3/4'' C. 1080 0 SPARE 1 20 36

33 20 1 RECEPT 128, 129 2#12, #12G., 3/4'' C. 720 0 SPARE 1 20 34

31 20 1 SPARE 0 0 SPARE 1 20 32

29 20 1 RECEPT WAREHOUSE 113 2#12, #12G., 3/4'' C. 360 0 SPARE 1 20 30

27 20 1 RECEPT WAREHOUSE 113 2#12, #12G., 3/4'' C. 360 0 SPARE 1 20 28

25 20 1 RECEPTACLE WAREHOUSE 113 2#12, #12G., 3/4'' C. 1080 0 SPARE 1 20 26

23 20 1 RECEPTACLE WAREHOUSE 113 2#10, #10G., 3/4'' C. 1080 0 SPARE 1 20 24

21 20 1 RECEPTACLE WAREHOUSE 113 2#10, #10G., 3/4'' C. 1080 0 SPARE 1 20 22

19 20 1 RECEPTACLE WAREHOUSE 113 2#10, #10G., 3/4'' C. 900 0 SPARE 1 20 20

17 20 1 RECEPTACLE WOOD SHOP 139 2#10, #10G., 3/4'' C. 720 0 SPARE 1 20 18

15 20 1 RECEPT WOOD SHOP 139 2#10, #10G., 3/4'' C. 900 0 SPARE 1 20 16

13 20 1 RECEPT TMO 138 2#12, #12G., 3/4'' C. 720 0 SPARE 1 20 14

11 20 1 RECEPT TMO 138 2#12, #12G., 3/4'' C. 900 0 SPARE 1 20 12

9 20 1 RECEPT TMO 138 2#12, #12G., 3/4'' C. 900 0 SPARE 1 20 10

7 20 1 RECEPT DEPLOYMENT 137 2#10, #10G., 3/4'' C. 1080 0 SPARE 1 20 8

5 20 1 RECEPT DEPLOYMENT 137 2#10, #10G., 3/4'' C. 720 180 2#10, #10G., 3/4'' C. POWER WOOD SHOP 139 1 20 6

3 20 1 RECEPTACLE DEPLOYMENT... 2#10, #10G., 3/4'' C. 1080 180 2#10, #10G., 3/4'' C. POWER WOOD SHOP 139 1 20 4

1 20 1 RECEPT DEPLOYMENT 137 2#10, #10G., 3/4'' C. 1080 180 2#10, #10G., 3/4'' C. POWER WOOD SHOP 139 1 20 2

# B... P LOAD SERVED WIRE / GROUND /... A B C WIRE / GROUND / CONDUIT LOAD SERVED P B... #

ELECTRONIC GRADE PANELBOARD WITH REMOTE SPD, ISOLATED GROUND BUS AND 200% NEUTRAL

NOTES:

ENCLOSURE: NEMA 1 MCB RATING: 225 A

MOUNTING: SURFACE WIRES: 4 MAINS RATING: 100 A

SUPPLY FROM: LP3 PHASE: 3 MAINS TYPE: MCB

LOCATION: WAREHOUSE 113 VOLTAGE: 208Y/120V A.I.C. RATING: 10K AIC RMS SYMMETRICAL

PANELBOARD: LP3B

A 08/01/19 KOW CGK TYPE B-2 SUBMITTAL

B 01/03/20 KOW CGK TYPE B-3 SUBMITTAL

C 10/15/20 KOW CGK ADDENDUM 01

C

C by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the state of Minnesota.

KEVIN O. WATSON, PE

DATE: 01/03/20 LIC. NO. 51801

date detailed checkeddesigned ofsheet sheets project contract rev.drawing file

no. date descriptionby ckd

1 1312111098765432

I

H

G

F

E

D

C

B

A

B222 RENOVATION AND ADAL

US NATIONAL GUARD BUREAU

MN ANG, 148TH FIGHTER WING

DULUTH, MINNESOTA

8201 NORMAN CENTER DR.

BLOOMINGTON, MN 55437

763-277-4676

102554

C

102554_E_CENTRAL

E-705

PANELBOARD SCHEDULES

12/20/19

K. WATSON C. KLOS

A. ALLEN

DEMAND WITH EXPANSION: 81 A

TOTAL ESTIMATED DEMAN... 67 A

TOTAL CONNECTED... 68 A

TOTAL ESTIMATED DEMAN... 56042 VA

TOTAL CONNECTED LOAD: 56442 VA

PANEL TOTALS

TOTAL LOAD: 18248 VA 19317 VA 18878 VA

41 20 1 SPARE 0 0 -- SPACE -- -- 42

39 20 1 SPARE 0 0 -- SPACE -- -- 40

37 20 1 SPARE 0 0 -- SPACE -- -- 38

35 20 1 SPARE 0 0 -- SPACE -- -- 36

33 20 1 SPARE 0 0 -- SPACE -- -- 34

31 20 1 SPARE 0 0 -- SPACE -- -- 32

29 -- -- -- -- 2105 0 -- SPACE -- -- 30

27 -- -- -- -- 2105 0 -- SPACE -- -- 28

25 20 3 HWP-2 GAS RISER ROOM 128 3#12, #12G., 3/4'' C. 2105 0 -- SPACE -- -- 26

23 -- -- -- -- 2105 0 SPARE 1 20 24

21 -- -- -- -- 2105 0 SPARE 1 20 22

19 20 3 HWP-1 GAS RISER ROOM 128 3#12, #12G., 3/4'' C. 2105 0 SPARE 1 20 20

17 20 1 WEST 2ND FLR LTG 2#12, #12G., 3/4'' C. 363 0 SPARE 1 20 18

15 20 1 EAST 2ND FLR LTG 2#12, #12G., 3/4'' C. 554 0 SPARE 1 20 16

13 20 1 LIGHTING 2#12, #12G., 3/4'' C. 33 0 SPARE 1 20 14

11 -- -- -- -- 6025 0 SPARE 1 20 12

9 -- -- -- -- 6025 0 SPARE 1 20 10

7 20 3 AHU-1 3#10, #10G., 3/4'' C. 6025 0 SPARE 1 20 8

5 -- -- -- -- 8280 0 SPARE 1 20 6

3 -- -- -- -- 8528 0 SPARE 1 20 4

1 50 3 PANEL ELP1 VIA ET1 SEE ONE-LINE 7980 0 SPARE 1 20 2

# B... P LOAD SERVED WIRE / GROUND /... A B C WIRE / GROUND / CONDUIT LOAD SERVED P B... #

NOTES:

ENCLOSURE: NEMA 1 MCB RATING: 225 A

MOUNTING: SURFACE WIRES: 4 MAINS RATING: 100 A

SUPPLY FROM: MDB PHASE: 3 MAINS TYPE: MCB

LOCATION: ELECTRICAL ROOM 119 VOLTAGE: 480Y/277V A.I.C. RATING: 14,000 RMS SYMMETRICAL

PANELBOARD: EHP1

DEMAND WITH EXPANSION: 81 A

TOTAL ESTIMATED DEMAN... 68 A

TOTAL CONNECTED... 69 A

TOTAL ESTIMATED DEMAN... 24388 VA

TOTAL CONNECTED LOAD: 24788 VA

PANEL TOTALS

TOTAL LOAD: 7980 VA 8528 VA 8280 VA

41 20 1 UH-3 2#12, #12 G., 3/4" C. 360 0 -- SPACE -- -- 42

39 20 1 UH-1, UH-2, EF-1 2#12, #12G., 3/4'' C. 1248 0 -- SPACE -- -- 40

37 20 1 HWB-2 2#12, #12G., 3/4'' C. 720 0 -- SPACE -- -- 38

35 20 1 HWB-1 2#12, #12G., 3/4'' C. 720 0 -- SPACE -- -- 36

33 20 1 RECEPTACLE NIPR 202 2#12, #12G., 3/4'' C. 1500 0 -- SPACE -- -- 34

31 20 1 RECEPT SIPR 201 2#12, #12G., 3/4'' C. 1080 0 -- SPACE -- -- 32

29 20 1 RECEPT SIPR 201 2#12, #12G., 3/4'' C. 1080 0 -- SPACE -- -- 30

27 20 1 RECEPT SIPR 201 2#12, #12G., 3/4'' C. 360 0 -- SPACE -- -- 28

25 20 1 RECEPT SIPR 201 2#12, #12G., 3/4'' C. 1080 0 -- SPACE -- -- 26

23 20 1 RECEPT SIPR 201 2#12, #12G., 3/4'' C. 720 0 SPARE 1 20 24

21 20 1 RECEPT SIPR 201 2#12, #12G., 3/4'' C. 720 0 SPARE 1 20 22

19 20 1 RECEPT NIPR 202 2#12, #12G., 3/4'' C. 1080 0 SPARE 1 20 20

17 20 1 RECEPT NIPR 202 2#12, #12G., 3/4'' C. 1080 1080 2#12, #12G., 3/4'' C. ELEVATOR CAB LIGHTS 1 20 18

15 20 1 RECEPT NIPR 202 2#12, #12G., 3/4'' C. 900 1080 2#12, #12G., 3/4'' C. ELEVATOR CB SHUNT TRIP 1 20 16

13 20 1 RECEPT NIPR 202 2#12, #12G., 3/4'' C. 720 360 2#12, #12G., 3/4'' C. JBOX COMM 118 1 20 14

11 20 1 RECEPT NIPR 202 2#12, #12G., 3/4'' C. 1080 1080 2#12, #12G., 3/4'' C. ELEVATOR CB SHUNT TRIP 1 20 12

9 20 1 RECEPT NIPR 202 2#12, #12G., 3/4'' C. 1500 360 2#12, #12G., 3/4'' C. DAMPERS HVAC MECH ROOM... 1 60 10

7 20 1 RECEPT MECH ROOM 203 2#10, #10G., 3/4'' C. 720 360 2#12, #12G., 3/4'' C. UH-7 1 20 8

5 20 1 RECEPT MECH ROOM 203 2#10, #10G., 3/4'' C. 720 360 2#12, #12G., 3/4'' C. UH-6 ELECTRICAL ROOM 119 1 20 6

3 20 1 DDC PANEL 2#12, #12G., 3/4'' C. 500 360 2#12, #12G., 3/4'' C. UH-5 WEAPONS VAULT 121 1 20 4

1 20 1 RECEPTACLE NIPR 202 2#12, #12G., 3/4'' C. 1500 360 2#12, #12G., 3/4'' C. HVAC WOOD SHOP 139 1 20 2

# B... P LOAD SERVED WIRE / GROUND /... A B C WIRE / GROUND / CONDUIT LOAD SERVED P B... #

NOTES:

ENCLOSURE: NEMA 1 MCB RATING: 225 A

MOUNTING: SURFACE WIRES: 4 MAINS RATING: 100 A

SUPPLY FROM: ET1 PHASE: 3 MAINS TYPE: MCB

LOCATION: WAREHOUSE 130 VOLTAGE: 208Y/120V A.I.C. RATING: 10,000 RMS SYMMETRICAL

PANELBOARD: ELP1

DEMAND WITH EXPANSION: 29 A

TOTAL ESTIMATED DEMAN... 24 A

TOTAL CONNECTED... 24 A

TOTAL ESTIMATED DEMAN... 8640 VA

TOTAL CONNECTED LOAD: 8640 VA

PANEL TOTALS

TOTAL LOAD: 3120 VA 3120 VA 2400 VA

41 20 1 SPARE 0 0 -- SPACE -- -- 42

39 20 1 SPARE 0 0 -- SPACE -- -- 40

37 20 1 SPARE 0 0 -- SPACE -- -- 38

35 20 1 SPARE 0 0 -- SPACE -- -- 36

33 20 1 SPARE 0 0 -- SPACE -- -- 34

31 20 1 SPARE 0 0 -- SPACE -- -- 32

29 20 1 SPARE 0 0 -- SPACE -- -- 30

27 20 1 SPARE 0 0 -- SPACE -- -- 28

25 20 1 SPARE 0 0 -- SPACE -- -- 26

23 20 1 SPARE 0 0 -- SPACE -- -- 24

21 20 1 SPARE 0 0 -- SPACE -- -- 22

19 20 1 SPARE 0 0 -- SPACE -- -- 20

17 20 1 SPARE 0 0 -- SPACE -- -- 18

15 20 1 RECEPT COMM 118 2#12, #12G., 3/4'' C. 720 0 -- SPACE -- -- 16

13 20 1 RECEPT COMM 118 2#12, #12G., 3/4'' C. 720 0 -- SPACE -- -- 14

11 20 1 RECEPT COMM 118 2#12, #12G., 3/4'' C. 1200 0 -- SPACE -- -- 12

9 20 1 RECEPT COMM 118 2#12, #12G., 3/4'' C. 1200 0 -- SPACE -- -- 10

7 20 1 RECEPT COMM 118 2#12, #12G., 3/4'' C. 1200 0 -- SPACE -- -- 8

5 20 1 RECEPT COMM 118 2#12, #12G., 3/4'' C. 1200 0 -- SPACE -- -- 6

3 20 1 RECEPT COMM 118 2#12, #12G., 3/4'' C. 1200 0 -- SPACE -- -- 4

1 20 1 RECEPT COMM 118 2#12, #12G., 3/4'' C. 1200 0 -- SPACE -- -- 2

# B... P LOAD SERVED WIRE / GROUND /... A B C WIRE / GROUND / CONDUIT LOAD SERVED P B... #

NOTES:

ENCLOSURE: NEMA 1 MCB RATING: 60 A

MOUNTING: SURFACE WIRES: 4 MAINS RATING: 100 A

SUPPLY FROM: LP3 PHASE: 3 MAINS TYPE: MCB

LOCATION: COMM 118 VOLTAGE: 208Y/120V A.I.C. RATING: 10K AIC RMS SYMMETRICAL

PANELBOARD: LTR

A 08/01/19 KOW CGK TYPE B-2 SUBMITTAL

B 01/03/20 KOW CGK TYPE B-3 SUBMITTAL

C 10/15/20 KOW CGK ADDENDUM 01

C

C

C

102554_E_Central_absantos - Sheet - E-701 - PANELBOARD SCHEDULES
102554_E_Central_absantos - Sheet - E-702 - PANELBOARD SCHEDULES
102554_E_Central_absantos - Sheet - E-703 - PANELBOARD SCHEDULES
102554_E_Central_absantos - Sheet - E-705 - PANELBOARD SCHEDULES

File details come from the government source that posted it. Updated .