090255FinalDwgs_032610.pdf
PDF 10 MB Posted
- Attached to
- Multiple Award Task Order Contract (MATOC) Federal contract opportunity
- Solicitation number
- W912LM-10-R-0003
About this file
Final Drawings
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Duluth MATOC Q A - 5-20.doc | DOC document | |
| 090255Addendum_051810 | — | |
| W912LM-10-R-0003-0002 - Duluth MATOC Amendment.doc | DOC document | |
| M102A _Addendum051810.pdf | ||
| Duluth MATOC Q A - 5-18.doc | DOC document | |
| 04 2000 Unit Masonry.pdf | ||
| W912LM-10-R-0003-0001 - Duluth MATOC Amendment.doc | DOC document | |
| Site Visit Roster - Duluth.pdf | ||
| Duluth Pre-Proposal Slides.ppt | PPT presentation | |
| W912LM-10-R-0003 - Duluth MATOC Solicitation.doc | DOC document | |
| 2010 - MATOC EXHIBITS A-D F and G Jan 09.doc | DOC document | |
| 090255FinalSpec_032910.pdf | ||
| MATOC EXHIBIT E.doc | DOC document |
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TE LE .
223 255
230 240
VIPER STREET
PH
AN
TO
M DR
IVE
249248
WING STORAGE
ALERT
CREW
PH
AN
TO
M
DR
IV
E
INVADER STREET
MUS
TA
NG
DR
IVE
SCORPION DRIVE
VOODOO STREET
RA
MP
LOCATION MAP
Minnesota Air National Guard
DULUTH, MINNESOTA
FMKM 932052
REPLACE CENTRAL
HEAT PLANT
MATERIALSCONTACTS
ARCHITECT
LHB, INC.
21 WEST SUPERIOR STREET, SUITE 500
DULUTH, MN 55802
PHONE: (218) 727-8446, FAX: (218) 727-8456
CONTACT: CYNTHIA POIRIER
E-MAIL: cynthia.poirier@LHBCORP.COM
CIVIL ENGINEER
LHB, INC.
CONTACT: DAN SHAW
STRUCTURAL ENGINEER
LHB, INC.
CONTACT: ALAN VORDERBRUGGEN
ELECTRICAL
LHB, INC.
CONTACT: LOYD HEIMBRUCH
MECHANICAL ENGINEER
FOSTER JACOBS & JOHNSON, INC.
345 CANAL PARK DRIVE, SUITE 200
DULUTH, MN 55802
PHONE: (218) 722-3060, FAX: (218) 722-1931
CONTACT: JIM JOHNSON
E-MAIL: jimj@FJJ.COM
CONTRACTING OFFICER'S
REPRESENTATIVE
148th FIGHTER WING
MINNESOTA AIR NATIONAL GUARD
OFFICE OF THE BASE CIVIL ENGINEER
PHONE: (218) 788-7290, FAX: (218) 788-7338
CONTACT: CAPT. RYAN KASPARI
BASE CIVIL ENGINEER
E-MAIL: ryan.kaspari@mndulu.ang.af.mil
REFERENCE INDICATORS DRAWING INDEX
ABBREVIATIONS
A
AB
AC
ACBD
ACT
ADDM
ADJ
ADJ
ADJ
AFF
AHU
ALT
ALUM
AP
APPROX
ARCH
AWT
Absolute Acoustic Acoustic Board Acoustical Ceiling Tile Addendum Adjacent Adjoining Adjustable Above Finished Floor Air Handling Unit Alternate Aluminum Access Panel Approximate Architect Acousical Wall Treatment
BB
BD
BITUM
BLDG
BLK
BLKG
BM
BMU
BOT
BRG
BUR
Bulletin Board Board Bituminous Building Block Blocking Bench Mark, Beam Burnished Masonry Unit Bottom Bearing Built-Up Roofing
CAB
CB
CI
CJ
CT
CEM
CEMPLAS
CHBD
CG
CL
CLG
CLR
CMU
CO/COR
COL
COMP
CONC
CONF
CONT
CONTR
CPT
CSG
CUH
Cabinet Catch Basin Cast Iron Control Joint Ceramic Tile Cement Cement Plaster Chalk Board Corner Guard Center Line Ceiling Clear Concrete Masonry Unit Contracting Officer (Rep) Column Composition Concrete Conference Continuous Contractor Carpet Casing Cabinet Unit Heater
D
DBL
DEMO
DET
DF
DIA
DIM
DISP
DN
DR
DR
DS
DT
DW
DWG
Depth Double Demolition Detail Drinking Fountain Diameter Dimension Dispenser Down Door Drain Down Spout Drain Tile Dishwasher Drawing
E
EA
EF
EFIS
EJ
EL
ELEC
ELEV
ENCL
EQ
EW
EWC
EXP
EXPMATL
EXT
EXIST
East Each Each Face Exterior Finish Insulation System Expansion Joint Elevation Electrical Elevator Enclosure Equal Each Way Elec. Water Cooler Expansion, Exposed Expansion Material Exterior Existing
FD
FDTN
FE
FEC
FIN
FLR
FP
FR
FT
FTG
FWC
Floor Drain Foundation Fire Extinguisher Fire Extinguisher Cabinet Finish Floor Fireproofing Frame Foot Footing Fabric Wall Covering
GA
GALV
GB
GEN
GI
GL
GLU LAM
GYP
Gage Galvanized Grab Bar General Galvanized Iron Glass Glued Laminated Wood Gypsum
HC
HD
HDBD
HDW
HDWD
HNDRL
HM
HORIZ
HT
Hollow Core Hand Dryer Hardboard Hardware Hardwood Handrail Hollow Metal Horizontal Height
ID
INSUL
INT
JAN
JST
JT
Inside Diameter Insulation Interior Janitor Joist Joint
LAV
LF
LINO
LKR
LOC
MATL
MAX
MECH
MET/MTL
MEZZ
MFR
MH
MK BD
MIN
MIRR
MISC
MO
MR
MTG
Lavatory Linear Feet (Foot) Linoleum Locker Location, Locate
Material Maximum Mechanical Metal Mezzanine Manufacturer Manhole Marker Board Minimum, Minute Mirror Miscillaneous Masonry Opening Mosure Resistant Mounting
N
NA
NIC
NTS
NO
North Not Applicable Not In Contract Not To Scale Number
OC
OD
OFF
OPNG
OPP
OH
ORIG
On Center Outside Diameter Office Opening Opposite Overhead Original
PC
PBD
PERF
PL
PLAS
PLAM
PLYWD
PREFIN
PTD
PTH
PT
QT
R
RAD
RB
RD
REC
REF
REINF
REQD
RESIL
RM
RO
RS
RTF
S
SAT
SC
SCHED
SECT
SD
SGD
SGT
SHTHG
SIM
SND
SPEC
SQ FT
SS
STL
STOR
STRUCT
SUSP
SV
Portland Cement Partical Board Perforated Plate Plaster Plastic Laminate Plywood Prefinished Paper Towel Dispenser Paper Towel Holder Paint
Quarry Tile
Riser, Radius, Range Radiator Resilient Base
Roof Drain Recessed Refigerator Reinforced Required Resilient Room Rough Opening Rough Sawn Rubber Tile Flooring
South Suspended Acoustical Tile Solid Core Schedule Section Soap Dispenser Sliding Glass Door Structural Glazed Tile Sheathing Similar Sanitary Napkin Dispenser Specification Square Foot Stainless Steel Steel Storage Structural Suspended Sheet Vinyl
T
TB
TD
TEL
TEMP
TER
TKBD
T&G
TPD
TYP
UNEX
UNFIN
UNO
UR
VB
VCT
VERT
VIF
VWC
W W/ W/O
WC
WD
WDW
WGL
WH
WWM
WI
Tread, Toilet Towel Bar Towel Dispenser Telephone Tempered Terrazo Tack Board Tongue and Groove Toilet Paper Dispenser Typical
Unexcavated Unfinished Unless Noted Otherwise Urnial
Vinyl Base Vinyl Composition Tile Vertical Verify In Field Vinyl Wall Covering
West With Without Water Closet Wood Window Wire Glass Water Heater Welded Wire Mesh Wrought Iron
At Angle Channel Center Line Flow Line Plate Feet Inches Number Smoke Square Round, Diameter
CL
FL
PL
O
SYMBOL CHARACTERS
W, X, Y, Z
V
U
T
S
R
Q
PH
I, J, K
L
M
N
O
D
E
F
G
C
B
GENERAL NOTES
PLYWOOD
WOOD BLOCKING
FACE BRICK
CONCRETE BLOCK
CONCRETE BLOCK (LARGE SCALE)
METAL/METAL STUD PARTITION
BATT INSULATION
EXTERIOR RIGID INSULATION
RIGID INSULATION (LARGE SCALE)
GYPSUM BOARD OR PLASTER
EXISTING (DETAILS/SECTIONS)
THE GENERAL CONTRACTOR, ASSOCIATED SUBCONTRACTORS AND ALL OF THEIR
SUBORDINATES SHALL FAMILIARIZE THEMSELVES WITH ALL INFORMATION LOCATED WITHIN
THE MASTER LEGEND REGARDLESS OF TRADE INVOLVED PRIOR TO CONSTRUCTION.
1. ALL WORK SHALL BE PERFORMED IN STRICT CONFORMANCE WITH LAWS, ORDINANCES,
RULES AND REGULATIONS OF GOVERNMENT AUTHORITEIS HAVING JURISDICTIONS.
2.
BEFORE COMMENCEMENT OF WORK, THE CONTRACTOR AND ASSOCIATED
SUBCONTRACTORS SHALL VERIFY ALL DIMENSIONS, CONDITIONS SHOWN IN THE
CONTRACT DOCUMENTS, AND EXISTING CONDITIONS PRIOR TO BIDDING. ANY
DEVIATIONS, DISCREPANCIES, AND/OR CONFLICTS SHALL BE REPORTED IN
WRITING.
3. DO NOT SCALE: DIMENSIONS GOVERN, LARGE SCALE DETAILS GOVERN OVER
SMALL SCALE.
4. THE CONTRACTING OFFICER SHALL CONDUCT A FIELD INSPECTION OF THE
PARTITION LAYOUT AT THE JOB SITE BEFORE THE WORK IS COMMENCED.
5. REFERENCES IN THE SPECIFICATIONS TO EQUIPMENT, MATERIAL, ARTICLES OR
PROCESSES BY BRAND NAME, TRADE NAME, MAKE OR CATALOG NUMBER, SHALL
BE REGARDED AS ESTABLISHING A STANDARD OF QUALITY AND SHALL NOT BE
CONSTRUED AS LIMITING COMPETITION THE CONTRACTOR MAY AT ITS OPINION,
USE ANY EQUIPMENT, MATERIAL, ARTICLE, OR PROCESS THAT IN THE JUDGEMENT
OF THE CONTRACTING OFFICER, IS EQUAL TO THAT NAMED IN THE
SPECIFICATIONS, UNLESS OTHERWISE SPECIFICALLY PROVIDED IN THIS
CONTRACT.
6. CONTRACTOR SHALL PERFORM HIGH QUALITY WORK. MATERIALS INSTALLED TO
UNIFORM ACCURATE FIT SO THEY MEET WITH NEAT, STRAIGHT LINES, FREE OF
OPEN SEAMS OR OVERLAPS. INSTALL EXPOSED MATERIALS APPROPRIATELY
LEVEL, PLUMB AND AT ACCURATE RIGHT ANGLES, OR FLUSH WITH ADJOINING
MATERIALS. WORK OF EACH TRADE SHALL MEET OR EXCEED ALL NATIONAL
STANDARDS PUBLISHED BY THE TRADE.
7. CONTRACTOR SHALL ARRANGE TO ACCOMMODATE "NOT IN CONTRACT" WORK.
WHEN INFORMATION IS INADEQUATE, REQUEST FURTHER INSTRUCTIONS BEFORE
PROCESSING.
8. CONTRACTOR SHALL TAKE CARE TO PROTECT NEWLY INSTALLED MATERIALS.
9. PRIOR TO FINAL INSPECTION OF AND ACCEPTANCE OF THIS PROJECT, THE
CONTRACTOR SHALL HAVE PROJECT AREA FREE FROM ALL CONSTRUCTION DEBRIS,
SCRAPS, MATERIAL, AND EQUIPMENT.
10. CONTRACTOR SHALL PATCH AND REPAIR ANY AND ALL FLOORS, WALLS, BASE,
CEILING, ETC. IN A WORKMANSHIP-LIKE MANNER TO MATCH THE SURROUNDING
SURFACE AREAS WHERE THERE IS DAMAGE BECAUSE OF REMOVAL OR
REPLACEMENT OF EXISTING CONSTRUCTION.
11. ALL ACTIVE TELEPHONE AND LOW VOLTAGE LINES IN PLENUM SPACES ABOVE THE
CEILING SHALL BE IN CONDUIT OR CABLE TRAY AND SUSPENDED FROM THE
BUILDING STRUCTURE. NO LINES SHALL BE ALLOWED TO REST ON THE CEILING
GRID STRUCTURE.
12. FIRE CAULK ALL PENETRATIONS THROUGH RATED WALL ASSEMBLIES THAT OCCUR
AS A RESULT OF THIS CONSTRUCTION.
13. IF NON-IDENTIFIED, POTENTIALLY HAZARDOUS MATERIAL IS ENCOUNTERED, DO NOT
DISTURB. CONTACT OWNER IMMEDIATELY TO ARRANGE FOR REMOVAL BY OWNER
(NIC).
14. REPLACE DAMAGED SOD/SOIL DUE TO CONSTRUCTION RELATED ACTIVITIES WITH
BLACK DIRT AND NEW SOD TO ACHIEVE A UNIFORM SURFACE AND APPEARANCE.
15. REFER TO SPEC SECTION 01230 FOR BID OPTIONS.
RCP Reflected Ceiling Plan
ROOM NAME
MATERIAL INDICATOR
SIZE INDICATOR
SUB TYPE IDENTIFIER
LAYERS OF GYP BD/ COVERING INDICATOR
ELEVATION INDICATOR
WALL/ PARTITION TYPE
DOOR TAG
WINDOW/ LOUVER TAG
INTERIOR ELEVATION REFERENCE
EXTERIOR ELEVATION REFERENCE
BUILDING SECTION REFERENCE
SECTION REFERENCE
REFERENCE TAG
REVISION NUMBER
KEYNOTES
ROOM NAME/ NUMBER101A
DETAIL NUMBER
SHEET NUMBER
G0.01
A5.11
L000
101A.1
M3 1A
POINT REFERENCED
ELEVATION
A3.01
A5.03
FILE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT TITLE:
COPYRIGHT 2010 BY LHB, INC. ALL RIGHTS RESERVED
http://www.LHBcorp.com
I HEREBY CERTIFY that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of Minnesota.
Signature:
Typed or Printed Name:
Date: Reg. No.:
21 W. Superior Street Suite 500 Duluth, MN 55802
TEL 218/727-8446
FAX 218/727-8456
DULUTH MINNEAPOLIS
THIS SQUARE APPEARS 1/2"x1/2" ON FULL SIZE SHEETS
CLIENT:
DULUTH, MINNESOTA
FMKM 932052
03/26/10 TYPE B FINAL SUBMITTAL
REPLACE
CENTRAL HEAT
PLANT
148th FIGHTER WING
MINNESOTA AIR
NATIONAL GUARD
C :\R ev it
Lo ca l F ile s\
B
LD
G
A
C en tra l_ M
M B.
rv t
3/
/2
:3 4:
A
M
BNL/MMH
CIP
090255 G0.01
PROJECT TITLE SHEET
03/26/10
CYNTHIA POIRER
22021
090255 Bldg 231.rvt
SHEET
NUMBER SHEET NAME
G0.01 PROJECT TITLE SHEET
C0.00 CIVIL NOTES, LEGEND AND LOCATION MAP
C1.01 EROSION CONTROL AND DEMOLITION PLAN
C1.02 EROSION CONTROL AND DEMOLITION PLAN
C1.03 EROSION CONTROL AND DEMOLITION PLAN
C2.01 UTILITY PLAN
C2.02 UTILITY PLAN
C3.01 CONSTRUCTION DETAILS
A1.01 BUILDING 230 DEMOLITION PLAN AND NOTES
A2.00 BLDG 250, 255, 436 FLOOR PLANS
A2.01 BUILDING 231 FLOOR PLAN & ELEVATIONS
A2.02 BUILDING 240 FLOOR PLAN & ELEVATIONS
A2.10 ROOF PLANS AND DETAILS
A2.11 DOOR SCHEDULE AND DETAILS
S1.00 BUILDING 231 NOTES, PLANS, AND DETAILS
S1.01 BUILDING 240 NOTES, PLANS, AND DETAILS
M1.01 BUILDING 231 MECHANICAL PLANS
M1.02 BUILDING 240 MECHANICAL PLANS
M1.03 BUILDING 250 MECHANICAL PLANS
M1.04 BUILDING 255 MECHANICAL PLANS
M1.05 BUILDING 436 MECHANICAL PLANS
E0.01 ELECTRICAL SYMBOLS AND ABBREVIATIONS
E1.01 ELECTRICAL SITE DEMOLITION PLAN
E1.02 ELECTRICAL SITE PLAN
E2.01 BUILDING 231 ELECTRICAL PLANS
E2.02 BUILDING 240 ELECTRICAL PLANS
E2.03 BUILDING 250 ELECTRICAL PLANS
E2.04 BUILDING 255 ELECTRICAL PLANS
E2.05 BUILDING 436 ELECTRICAL PLANS
E8.01 ELECTRICAL SCHEDULES
BUILDING 255
BUILDING 250
BUILDING 231
BUILDING 240
BUILDING 230
BUILDING 436
No Date Revision
C0.00
C1.01
C1.02
C1.03
C2.01
A
C3.01
C2.02
C3.01
A1.01
MECHANICAL ROOM
EXHAUST
FAN ON
ROOF,
REFER TO
4/A2.00
MECH
ROOM
MECHANICAL ROOM
EXHAUST
FAN ON
ROOF,
REFER TO
4/A2.00
REMOVE DOOR
AND FRAME.
INFILL DOOR
OPENING W/ CMU
TO MATCH
EXISTING, FINISH
AS NOTED.
PT.2
RB
PT.1
RB
1 2
A
B
NOTE:
PLANS ARE FOR REFERENCE
ONLY. REFER TO MECH AND
ELEC FOR WORK DONE IN
THESE AREAS.
M
IN
EQUIPMENT
SHEET METAL FLASHING
2x4 STUDS @ 16" O.C.
1/2" CDX PLYWD. SHEATH.
REINFORCED MEMBRANE STRIP
EXISTING ROOF MEMBRANE, CUT
AS NECESSARY AT OPENING
EXISTING ROOF ASSEMBLY
CONTINUOUS SEALANT
MEMBRANE FLASHING RUN UP AND
OVER CURB
L4X4X1/4" TYP
NOTE: MECHANICAL EQUIPMENT SHALL BE PLACED TO BEAR ON TWO
JOISTS MINIMUM. SEE ARCH FOR CURB & ROOF DETAILS.
L6X4X3/8"
PLACE
BETWEEN
FLUTES
VERIFY SIZE & LOCATION
OF OPENING W/MECH
FILE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT TITLE:
COPYRIGHT 2010 BY LHB, INC. ALL RIGHTS RESERVED
http://www.LHBcorp.com
I HEREBY CERTIFY that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of Minnesota.
Signature:
Typed or Printed Name:
Date: Reg. No.:
21 W. Superior Street Suite 500 Duluth, MN 55802
TEL 218/727-8446
FAX 218/727-8456
DULUTH MINNEAPOLIS
THIS SQUARE APPEARS 1/2"x1/2" ON FULL SIZE SHEETS
CLIENT:
DULUTH, MINNESOTA
FMKM 932052
03/26/10 TYPE B FINAL SUBMITTAL
REPLACE
CENTRAL HEAT
PLANT
148th FIGHTER WING
MINNESOTA AIR
NATIONAL GUARD
C R e v it L o c a l F ile s \0
B
L D
G
A
C e n tr a l_ b n lia n .r v t
/2
/2
:2 :3
P
M
BNL/MMH
CIP
090255
A2.00
BLDG 250, 255, 436
FLOOR PLANS
03/26/10
CYNTHIA POIRER
22021
090255 Bldg 231.rvt
1/16" = 1'-0"1
BUILDING 250 PARTIAL FLOOR PLAN
1/16" = 1'-0"2
BUILDING 255 FLOOR PLAN
1/16" = 1'-0"3
BUILDING 436 FLOOR PLAN
3" = 1'-0"4
EQUIPMENT CURB
1" = 1'-0"6
TYPICAL MECHANICAL OPENING
FD
A2.01
A2.01
A2.01
A2.10
A2.01
EXISTING PIT
TO BE REMOVED,
SEE STRUCTURAL
100'-0"
100'-0"
1 2 3 4 5 6 7 8 9 10
MECH
ADDITION EXISTING
A2.10
14' - 6"
231A
MECH
A2.11
A2.11
MODIFY GUTTER AND
RELOCATE EXISTING
DOWNSPOUT AS REQUIRED
MF2
SEALED CONCRETE FINISH
NOTE: REFER TO
DRAWINGS AND
SPECIFICATIONS FOR
FINISHES.
F.E.
BRACKET
LEVEL 1
100' - 0"
PREFINISHED METAL TRIM
METAL PANEL SIDING
0.25
LEVEL 1
100' - 0"
A2.10
METAL PANEL SIDING
EPDM ROOF
3' - 0"
LOUVER,
SEE MECH.
LEVEL 1
100' - 0"
METAL PANEL
SIDING
PREFINISHED METAL TRIM
0.25
EPDM ROOF
FILE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT TITLE:
COPYRIGHT 2010 BY LHB, INC. ALL RIGHTS RESERVED
http://www.LHBcorp.com
I HEREBY CERTIFY that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of Minnesota.
Signature:
Typed or Printed Name:
Date: Reg. No.:
21 W. Superior Street Suite 500 Duluth, MN 55802
TEL 218/727-8446
FAX 218/727-8456
DULUTH MINNEAPOLIS
THIS SQUARE APPEARS 1/2"x1/2" ON FULL SIZE SHEETS
CLIENT:
DULUTH, MINNESOTA
FMKM 932052
03/26/10 TYPE B FINAL SUBMITTAL
REPLACE
CENTRAL HEAT
PLANT
148th FIGHTER WING
MINNESOTA AIR
NATIONAL GUARD
C R e v it L o c a l F ile s \0
B
L D
G
A
C e n tr a l_ b n lia n .r v t
/2
/2
:1 :5
P
M
BNL/MMH
CIP
090255
A2.01
BUILDING 231 FLOOR
PLAN & ELEVATIONS
03/26/10
CYNTHIA POIRER
22021
090255 Bldg 231.rvt
1/8" = 1'-0"1
OVERALL BUILDING 231 PLAN
1/4" = 1'-0"2
ENLARGED PLAN - 231 ADDITION
1/4" = 1'-0"5
EAST ELEVATION - 231 ADDITION
1/4" = 1'-0"4
SOUTH ELEVATION - 231 ADDITION
1/4" = 1'-0"3
WEST ELEVATION - ADDITION
A2.024
A2.02
A2.02
A2.02
A2.02
REMOVE EXISTING SHED
EXISTING
BLDG
ADDITION
A2.02
10' - 0" 3' - 0"
5' - 4"
1' - 0"
A2.02
MECH
0A
RECESSED
SLAB AREA
MF2
A2.11
SIM
A2.11
SIM
OVERHANG
ABOVE
SEALED
CONCRETE
FINISH
NOTE: REFER TO
SPECIFICATION FOR FINISH
SCHEDULES
F.E. BRACKETLEVEL 1
100' - 0"
METAL PANEL SIDING
PREFINISHED METAL TRIM
EPDM ROOFING
3' - 0"
LEVEL 1
100' - 0"
A2.02
METAL PANEL SIDING
LEVEL 1
100' - 0"
METAL PANEL SIDING
PREFINISHED METAL TRIM
0.25
EPDM ROOFING
3' - 0"
LEVEL 1
100' - 0"
MECH
ROOF SYSTEM:
EPDM ON 7/16" FIBERBOARD
4" POLYISO INSULATION
VAPOR BARRIER
METAL DECK FRAMING
WALL SYSTEM:
METAL PANEL, AIR BARRIER
1/2" GYP SHEATHING
6" STUD FRAMING W/ BATT INSULATION
3/4" FIRE RATED PLYWOOD
RECESSED SLAB AREA
A2.11
A2.10
A2.10
SIM
JOIST BRG.
108'-0"108'-2 1/2"
JOIST BRG.
PAINT EXPOSED
STRUCTURE AND WALLS.
REFER TO 09 9000 FOR
SCHEDULE
SHED TO BE DEMOLISHED
FILE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT TITLE:
COPYRIGHT 2010 BY LHB, INC. ALL RIGHTS RESERVED
http://www.LHBcorp.com
I HEREBY CERTIFY that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of Minnesota.
Signature:
Typed or Printed Name:
Date: Reg. No.:
21 W. Superior Street Suite 500 Duluth, MN 55802
TEL 218/727-8446
FAX 218/727-8456
DULUTH MINNEAPOLIS
THIS SQUARE APPEARS 1/2"x1/2" ON FULL SIZE SHEETS
CLIENT:
DULUTH, MINNESOTA
FMKM 932052
03/26/10 TYPE B FINAL SUBMITTAL
REPLACE
CENTRAL HEAT
PLANT
148th FIGHTER WING
MINNESOTA AIR
NATIONAL GUARD
C R e v it L o c a l F ile s \0
B
L D
G
A
C e n tr a l_ b n lia n .r v t
/2
/2
:2 :2
P
M
BNL/MMH
CIP
090255
A2.02
BUILDING 240 PLAN AND
ELEVATIONS
03/23/10
CYNTHIA POIRER
22021
090255 BLDG 240.rvt
1/8" = 1'-0"1
OVERALL BUILDING 240 PLAN
1/4" = 1'-0"2
ENLARGED PLAN - 240 ADDITION
1/4" = 1'-0"5
WEST ELEVATION - 240 ADDITION
1/4" = 1'-0"4
NORTH ELEVATION - 240 ADDITION
1/4" = 1'-0"3
EAST ELEVATION - 240 ADDITION
1/4" = 1'-0"6
SECTION
1/4" = 1'-0"7
PHOTO OF SHED TO BE DEMOLISHED
LEVEL 1
100' - 0"
MECH
A2.10
A2.10
5ROOF SYSTEM #1:
- EPDM
- 7/16" PROTECTION BOARD
- 4" POLYISOCYANURATE INSULATION R25
- VAPOR BARRIER
- 1 1/2" METAL DECK
WALL SYSTEM:
METAL PANEL, AIR
BARRIER
1/2" GYP SHEATHING
6" STUD FRAMING W/ BATT
INSULATION
3/4" FIRE RATED PLYWOOD
109' - 2"
JOIST BRG.
109' - 6"
JOIST BRG.
A2.11
PAINT EXPOSED
STRUCTURE AND
WALLS, TYP
NOTE: REFER TO SPECIFICATION 09 9000
FOR PAINT FINISH SCHEDULE
RB, TYP.
CONTINUOUS SEALANT
TERMINATION BAR
AND FASTNER
EPDM ROOF
MEMBRANE, RUN UP
WALL A MIN. OF 8"
EPDM ROOF MEMBRANE
EXISTING CONSTRUCTION
METAL COUNTER FLASHING
M
IN
ROOF JOIST - REFER TO STRUCTURAL
METAL DECK
VAPOR BARRIER
4" POLYISO INSULATION
7/16" PROTECTION BOARD
EPDM ROOFING
3/4" FIRE RATED PLYWOOD
PAINTED, TYP TO DECK
6" METAL STUDS WITH
BATT INSULATION
PREFINISHED
METAL GUTTER
METAL WALL
PANEL
AIR BARRIER
1/2" GYP
SHEATHING
VAPOR BARRIER
FILL VOID WITH
BATT INSULATION
A2.10
WOOD
BLOCKING
ROOF JOIST - REFER TO STRUCTURAL
METAL DECK
VAPOR BARRIER
4" POLYISO INSULATION
7/16" PROTECTION BOARD
EPDM ROOFING
3/4" FIRE RATED PLYWOOD,
PAINTED, TYP. TO DECK
6" METAL STUDS, FILL WITH
BATT INSULATION
PREFINISHED
ROOF EDGE
METAL WALL
PANEL
AIR BARRIER
1/2" GYP
SHEATHING
VAPOR BARRIER
FILL VOID WITH
BATT INSULATION
A2.10
WOOD
BLOCKING
VENT STACK
ROOF SYSTEM #1
EXISTING ROOF
SLOPE DOWN
1/4" = 1'-0"
A2.10
A2.10
A2.10
O V
E R
H A
N G
A2.10
EDGE OF
BUILDING
BELOW
M
IN
.1
M
IN
6" MIN.
FILL VOID W/ BATT INSUL.
FIELD MEMBRANE
PREFABRICATED FLASHING
MEMBRANE W/ DRAWBAND
SEALANT AS REQ'D
SEALANT
PIPE FLASHING W/ DRAWBAND
T Y
P
R O
O F
A S
S E
M B
L Y
PIPE 1/2" MIN.
6 1/2" MAX.
STAINLESS STEEL
CLAMPING RING
PRE-MOLDED PIPE
FLASHING
MEMBRANE ROOFING
ROOF SYSTEM #1 EDGE OF
BUILDING
BELOW
EXISTING ROOF
OVERHANG
3' - 0"
SLOPE DOWN
1/4" = 1'-0" 9
A2.10
A2.10
A2.10
3' - 0" OVERHANG SLOPE DOWN
1/4" = 1'-0"
JOIST BRG
108'-0"
ROOF JOIST - REFER TO
STRUCTURAL
METAL DECK
VAPOR BARRIER
4" POLYISO INSULATION
7/16" PROTECTION BOARD
EPDM ROOFING
3/4" FIRE RATED PLYWOOD TO DECK
6" METAL STUDS
PREFINISHED
METAL GUTTER
METAL WALL PANEL
AIR BARRIER
1/2" GYP SHEATHING
CONTINUE TO DECK
VAPOR BARRIER
PREFINISHED METAL
SOFFIT PANEL
PREFINISHED METAL
FASCIA WITH DRIP
FLASHING AND
KEEPER STRIP
3/4" PLYWOOD
A2.10
WOOD BLOCKING
PREFINISHED METAL FASCIA
COVER
EPDM ROOFING, WRAP
DOWN FACE OF WALL
TERMINATION BAR
SEALANT
CONTINUOUS SEALANT
EPDM ROOFING, RUN DOWN FACE OF WALL
CONTINUOUS FLASHING
PREFINISHED METAL GUTTER
FILE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT TITLE:
COPYRIGHT 2010 BY LHB, INC. ALL RIGHTS RESERVED
http://www.LHBcorp.com
I HEREBY CERTIFY that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of Minnesota.
Signature:
Typed or Printed Name:
Date: Reg. No.:
21 W. Superior Street Suite 500 Duluth, MN 55802
TEL 218/727-8446
FAX 218/727-8456
DULUTH MINNEAPOLIS
THIS SQUARE APPEARS 1/2"x1/2" ON FULL SIZE SHEETS
CLIENT:
DULUTH, MINNESOTA
FMKM 932052
03/26/10 TYPE B FINAL SUBMITTAL
REPLACE
CENTRAL HEAT
PLANT
148th FIGHTER WING
MINNESOTA AIR
NATIONAL GUARD
C R e v it L o c a l F ile s \0
B
L D
G
A
C e n tr a l_ b n lia n .r v t
/2
/2
:1 :3
P
M
BNL/MMH
CIP
090255
A2.10
ROOF PLANS AND
DETAILS
03/26/10
CYNTHIA POIRER
22021
090255 Bldg 231.rvt
1/4" = 1'-0"1
SECTION BLDG 231
1 1/2" = 1'-0"5
DETAIL AT CONNECTION TO EXISTING ROOF
1 1/2" = 1'-0"6
DETAIL AT ROOF EAVE
1 1/2" = 1'-0"7
DETAIL AT ROOF RAKE
1/4" = 1'-0"2
ROOF PLAN - BLDG 231
3" = 1'-0"8
HOT STACK DETAIL
3" = 1'-0"4
VENT STACK FLASHING (TYP.)
1/4" = 1'-0"3
ROOF PLAN - BLDG 240
1 1/2" = 1'-0"9
DETAIL @ OVERHANG
6" = 1'-0"10
ENLARGED DETAIL AT ROOF RAKE
6" = 1'-0"11
ENLARGED DETAIL AT ROOF EAVE
No Date Revision
NOTE:
REFER TO DETAILS 4
AND 8/A2.10 FOR
PENETRATION
DETAILS. REFER TO
MECHANICAL FOR
LOCATIONS.
METAL WALL PANEL
AIR BARRIER
1/2" GYP
SHEATHING
PREFINISHED
HEAD FLASHING
6" METAL STUDS
@ 16" O.C.
3/4" FIRE RATED
PLYWOOD
BATT
INSULATION
SEALANT,
BOTH SIDES
BOX HEADER
SEE STRUCT.
METAL WALL PANEL
AIR BARRIER
1/2" GYP
SHEATHING
6" METAL STUDS
@ 16" O.C.
3/4" FIRE RATED
PLYWOOD
SEALANT, BOTH SIDES
SEE
SCHEDULE
S E
E S
C H
E D
U L
E
D-10
FLUSH
2" 2"
S E
E S
C H
E D
U L
E
SEE
SCHEDULE
F-10
METAL PANEL
AIR BARRIER
1/2" GYP
SHEATHING
6" METAL STUDS @
16" O.C. O.C. W/ R20
BATT INSULATION
3/4" FIRE RATED
PLYWOOD
2 1/2" METAL
STUDS @ 16" O.C.
VAPOR BARRIER
EXISTING
CONSTRUCTION
SEALANT
METAL PANEL
AIR BARRIER
1/2" GYP
SHEATHING
6" METAL STUDS @ 16" O.C.
W/ R20 BATT INSULATION
3/4" FIRE RATED PLYWOOD
2 1/2" METAL STUDS @ 16" O.C.
SEALANT
ALIGN NEW WALL
WITH EXISTING WALL
CONSTRUCTION
VAPOR
BARRIER
THICKENED EDGE CONC SLAB
(SEE STRUCTURAL)
INSULATED HM DOOR AND FRAME
THERMAL BREAK SADDLE THRESHOLD
1/2" THERMAL
BREAK
1 LAYER FIRE RATED PLYWOOD EXPOSED FACE
MF2
EXPOSED FACE
2 1/2" MET STUD @ 16" OC.
EXISTING OR OTHERWISE
SCHEDULED
CONSTRUCTION WHERE
APPLICABLE
3/4" FIRE RATED PLYWOOD
3 1/4"
METAL PANEL
AIR BARRIER
1/2" GYP
SHEATHING
6" METAL STUDS
@ 16" O.C. O.C. W/ R20
BATT INSULATION
3/4" FIRE RATED
PLYWOOD
SEALANT
VAPOR
BARRIER
THICKENED EDGE CONC SLAB
(SEE STRUCTURAL)(2) LAYERS RIGID
INSULATION (SEE
STRUCTURAL)
GRADE LINE
3/4" FIRE RATED PLYWOOD
PREFINISHED
GALVANIZED
INSULATION
PROTECTION
METAL WALL PANEL
AIR
INFILTRATION
BARRIER
1 1/2" GYP
SHEATHING
VAPOR BARRIER
6" METAL STUDS O.C.
W/ R20 BATT INSULATION
RUBBER BASE, TYP.
VAPOR BARRIER
FILE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT TITLE:
COPYRIGHT 2010 BY LHB, INC. ALL RIGHTS RESERVED
http://www.LHBcorp.com
I HEREBY CERTIFY that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of Minnesota.
Signature:
Typed or Printed Name:
Date: Reg. No.:
21 W. Superior Street Suite 500 Duluth, MN 55802
TEL 218/727-8446
FAX 218/727-8456
DULUTH MINNEAPOLIS
THIS SQUARE APPEARS 1/2"x1/2" ON FULL SIZE SHEETS
CLIENT:
DULUTH, MINNESOTA
FMKM 932052
03/26/10 TYPE B FINAL SUBMITTAL
REPLACE
CENTRAL HEAT
PLANT
148th FIGHTER WING
MINNESOTA AIR
NATIONAL GUARD
C R e v it L o c a l F ile s \0
B
L D
G
A
C e n tr a l_ b n lia n .r v t
/2
/2
:2 :0
P
M
BNL/MMH
CIP
090255
A2.11
DOOR SCHEDULE AND
DETAILS
03/26/10
CYNTHIA POIRER
22021
090255 Bldg 231.rvt
DOOR AND FRAME SCHEDULE
DOOR
NUMBER
DOOR FRAME DETAIL
GLAZING
FIRE
RATING
HDWR
GROUP COMMENTS
LEAF
QTY WIDTH HEIGHT MATL TYPE MATL TYPE HEAD JAMB SILL
LEVEL 1
231A 2 5' - 0" 7' - 0" HM D10 HM F10 3/A2.11 2/A2.11 7/A2.11 --- --- 1 CARD READER
240A 2 5' - 0" 7' - 0" HM D10 HM F10 3/A2.11 2/A2.11 7/A2.11 --- --- 1 CARD READER
LEVEL 1: 2
Grand total: 2
3" = 1'-0"3
DOOR HEAD
3" = 1'-0"2
DOOR JAMB
1/4" = 1'-0"1
DOOR AND FRAME TYPES
3" = 1'-0"5
PLAN DETAIL
3" = 1'-0"4
PLAN DETAIL AT CORNER
1" = 1'-0"7
SILL DETAIL
1 1/2" = 1'-0"6
WALL TYPE MF2
1 1/2" = 1'-0"8
WALL PENETRATION PLAN DETAIL
1" = 1'-0"9
WALL BASE DETAIL
SLAB EDGE
4369 [14'-4"]
S L A
B E
D G
E
F /E
X W
A L L
127 [5"] CONC SLAB REINF.
W/ 6X6-W2.9XW2.9 WWF
T/SLAB = 30480 [100'-0"]
600S137-43 STUDS
@ 24" O.C., ALIGN
STUDS W/JOISTS
EXIST WALL
DEMO EXIST PUMP PIT
IN ITS ENTIRETY
S1.00
(3) 16 [#5] X 610 [24"]
DWL, DRILL & ADHESIVE
INTO EX FND WALL, 152
[6"] EMBED., TYP
DRAINTILE, CONNECT
TO EXISTING SYSTEM (IF
PRESENT) OR ROUTE
TO WEST, SEE CIVIL
1219 [4'-0"]
INSULATION
LINE
S1.00
FLOOR DRAIN, SUMP &
HOUSEKEEPING PADS -
SEE MECH
1.5B 22 GA
METAL DECK
SLOPE 6.4 [1/4"]:305 [12"]
5 SPS. @ 610 [24"] O.C.
1000S162-68
BLOCKING IN FIRST
JOIST SPACE @ 1219
[48"] O.C. MAX.
54 [16 GA] CONT.
RUNNER B/S
EXIST WALL
S1.00
S1.00
600S137-43 BOX
HEADER
W/STIFFENERS
JST BRG ELEV =
33274 [109'-2"]
JST BRG ELEV =
33376 [109'-6"]
1000S162-68 BLOCKING EA SIDE
OF STACK PENETRATION
356 [14'] STACK PENETRATION
CENTERED BETWEEN JOISTS
NOTE: ATTACH 1ST
STUD TO EX WALL W/
HILTI KWIK-CON II 3/16X1
3/4 HEX-HEAD/WASHER
ANCHORS. (3) ANCHORS
@ 3" O.C. @ T/ STUD,
THEN 24" O.C.
THEREAFTER (TYP.)
JOIST BRIDGING
@ MIDSPAN
1' - 6" 1' - 6"1' - 0"
1000S162-68 JOISTS
S1.00
DRAIN TILE
F/STUD
51 [2"]
457 [1'-6"]
M A
X
1219 [4'-0"]
SUITABLE
SUBGRADE
COMPACTED
NFS FILL
(2) LAYERS 51 [2"]
EXTRUDED POLYSTYRENE,
STAGGER JOINTS
(2) 16 [#5] , TOP & BOTT
10 [#3] TIES @ 610 [24"] O.C.
SEE PLAN
FOR SLAB
METAL PANEL - SEE ARCH
SLOPE 6.4 [1/4"] : 305 [12"] MIN.
EDGE OF SLAB
SEE PLAN
VAPOR
RETARDER
CONT.
RUNNER
METAL DECK
ROOF JOIST
METAL STUD
JBE VARIES
SEE PLAN
METAL DECK
ROOF JOIST
METAL STUD
BLOCKING
ROOF JOIST
JBE
SEE PLAN
GENERAL DESIGN AND CONSTRUCTION NOTES
A. BUILDING CODE
1. 2007 MINNESOTA STATE BUILDING CODE (MSBC).
2. 2006 INTERNATIONAL BUILDING CODE (IBC).
B. DESIGN LIVE LOADS
1. WIND LOAD: 90 MPH (3 SEC. GUST), EXPOSURE C,
IMPORTANCE FACTOR 1.15
2. SEISMIC LOAD: NOT APPLICABLE (MSBC).
3. ROOF LIVE LOAD: 20 PSF
4. ROOF SNOW LOAD: 60 PSF GROUND SNOW PLUS SNOW ACCUMULATION
PER IBC AND ASCE 7-05.
a. FLAT ROOF SNOW LOAD, Pf = 46.2 PSF
b. SNOW EXPOSURE FACTOR, Ce = 1.0
c. SNOW IMPORTANCE FACTOR, I = 1.1
d. THERMAL FACTOR, Ct = 1.0
C. FOOTINGS AND FOUNDATION
1. SOIL DESIGN PRESUMPTIVE NET ALLOWABLE BEARING CAPACITY IS
2000 PSF IN ACCORDANCE WITH IBC TABLE 1804.2. SOIL CONDITIONS
SHALL BE VERIFIED BY A LICENSED GEOTECHNICAL ENGINEER.
2. FOUNDATIONS SHALL BEAR ON UNDISTURBED, UNFROZEN SUBGRADE,
EXCEPT WHERE COMPACTED SUBGRADE OR FILL IS OTHERWISE
SPECIFIED, OR FOUNDATIONS BEAR ON ROCK.
3. SEE DRAWINGS FOR DRAIN TILE LOCATIONS.
D. CONSTRUCTION NOTES
1. ALL DIMENSIONS INVOLVING COORDINATION OF NEW WORK WITH EXISTING
CONSTRUCTION SHALL BE FIELD-CHECKED BY THE CONTRACTOR AND
FURNISHED TO THE SUBCONTRACTORS PRIOR TO FABRICATION OF ANY
WORK. THE VERIFIED DIMENSIONS SHALL APPEAR AND BE NOTED ON THE
SHOP DRAWINGS SUBMITTED.
2. THE CONTRACTOR IS RESPONSIBLE FOR THE PROTECTION OF EXISTING
BUILDINGS, UTILITIES, STREETS, ETC. DURING CONSTRUCTION. CONTRACTOR
IS RESPONSIBLE FOR DESIGN AND INSTALLATION OF ALL NECESSARY
TEMPORARY BRACING.
3. ANY HOLES CUT IN NEW OR EXISTING CONSTRUCTION THAT ARE NOT
DETAILED ON THE STRUCTURAL DRAWINGS SHALL BE REVIEWED WITH THE
STRUCTURAL ENGINEER. COORDINATE ALL HOLES AND PENETRATIONS WITH
OTHER DISCIPLINES.
4. THE STRUCTURE SHALL BE ADEQUATELY BRACED AND SHORED DURING
ERECTION AGAINST WIND AND ERECTION LOADS. STRUCTURAL MEMBERS
ARE DESIGNED FOR IN-PLACE LOADS.
5. THE CONTRACTOR SHALL NOTIFY THE ENGINEER IMMEDIATELY OF
DISCREPANCIES FOUND BETWEEN CONSTRUCTION DOCUMENTS AND ACTUAL
FIELD CONDITIONS.
E. SPECIAL INSPECTIONS AND TESTING
1. SEE PROJECT "SPECIAL STRUCTURAL TESTING AND INSPECTION SUMMARY
SCHEDULE".
B. CONCRETE NOTES
1. PERFORM WORK IN ACCORDANCE WITH ACI-301-05 AND ACI 318-05.
2. CONCRETE CLEAR COVER OVER REINFORCING STEEL SHALL MEET THE
REQUIREMENTS OF ACI 318-05.
3. PROVIDE A 3/4" CHAMFER ON ALL EXPOSED CONCRETE CORNERS UNLESS
NOTED OTHERWISE.
4. PROVIDE LAP SPLICES AT ALL CORNERS AND INTERSECTIONS, SAME
SIZE AND SPACING AS HORIZONTAL REINFORCING.
5. PROVIDE SUPPORTS AND SPACERS FOR ALL REINFORCING, INCLUDING WWF.
6. SEE ARCHITECTURAL PLANS FOR DEPRESSED AND SLOPED AREAS IN
FLOORS NOT SHOWN ON STRUCTURAL DRAWINGS.
7. CONSOLIDATE ALL CONCRETE, INCLUDING SLABS, BY VIBRATING.
8. ALL CONCRETE SHOWN SHALL BE REINFORCED. PLANS, SECTIONS AND
DETAILS SHOWN WITHOUT REINFORCEMENT ARE INTENDED TO SHOW
DIMENSIONS AND DETAILS OF CONSTRUCTION ONLY. REINFORCEMENT OF
THESE SECTIONS SHALL BE PROVIDED IN ACCORDANCE WITH THE
DETAILS SHOWING REINFORCEMENT.
9. LAP SPLICES 40 BAR DIAMETERS (MIN.) UNLESS NOTED OTHERWISE.
10. MIX DESIGNS SHALL INCORPORATE ADMIXTURES AS APPROPRIATE FOR
ENVIRONMENTAL CONDITIONS.
11. COORDINATE GROUNDING REQUIREMENTS BETWEEN FOUNDATION
CONSTRUCTION AND ELECTRICAL WORK.
12. ALL REINFORCING SHALL BE DETAILED, FABRICATED & PLACED IN
ACCORDANCE WITH CRSI "MANUAL OF STANDARD PRACTICE".
13. SUBMIT DESCRIPTION OF PLANNED PROTECTIVE MEASURES FOR HOT OR
COLD WEATHER CONCRETING.
CAST-IN-PLACE CONCRETE
2. REINFORCING PROPERTIES:
ALL BARS UNLESS NOTED OTHERWISE:
TIES & STIRRUPS:
WELDED WIRE FABRIC (SMOOTH, SHEETS):
WELDABLE REINFORCEMENT:
EPOXY COATING:
3. CHAIRS AND BOLSTERS SHALL BE PLASTIC OR EPOXY COATED.
4. IF CONCRETE SUPPORT BLOCKS ARE USED, THEIR STRENGTH SHALL BE
EQUAL OR GREATER THAN THAT OF THE CONCRETE BEING PLACED.
f'c (PSI)
28 DAYS
4,000 4,000 4,500
MAX.
SLUMP
INCHES
MAX
AGGR.
3/4" 3/4" 3/4"
ENTR.
AIR (%)
0*
MAX.
W/C 0.45 0.45 0.45
FY (PSI)
60,000 60,000 65,000 60,000
N/A
ASTM
A615 A615 A185 A706 A775
A. MATERIAL PROPERTIES
1. CONCRETE PROPERTIES:
GRADE BEAMS:
INT. SLAB ON GRADE (NW):. .
EXT. CONCRETE FOR STOOPS
* USE 6%±1.5% ENTRAINED AIR IF EXTERIOR CONCRETE
14. PROVIDE 6X6 - W2.9XW2.9 WWF FOR ALL SLABS ON GRADE U.N.O.
15. CONCRETE SLABS ON GRADE SHALL BE PLACED ON A 4" SAND CUSHION.
INSTALL VAPOR RETARDER UNDER ALL SLABS. INSTALL THE VAPOR
RETARDER DIRECTLY BELOW THE SLAB.
16. THE FOLLOWING MINIMUM CONCRETE COVER SHALL BE PROVIDED FOR
REINFORCEMENT:
CONCRETE CAST AGAINST &
PERMANENTLY EXPOSED TO EARTH:
CONCRETE EXPOSED TO EARTH OR WEATHER:
#6 THRU #11 BARS:
#5 & SMALLER BARS:
CONCRETE NOT EXPOSED TO WEATHER
OR IN CONTACT WITH GROUND:
SLABS AND WALLS:
BEAMS AND COLUMNS:
17. HOUSEKEEPING PADS SHALL BE 102 [4"] CONCRETE WITH 13 [#4] BARS AT
305 [12") ON CENTER EACH WAY UNLESS NOTED OTHERWISE.
MINIMUM
COVER (IN.)
1 1/2
3/4 1 1/2
COLD-FORMED STEEL
A. LIGHT GAUGE FRAMING SHALL BE DESIGNED AND CONSTRUCTED IN
ACCORDANCE WITH 2001 AISI SPECIFICATIONS WITH 2004 SUPPLEMENT AND
2002 AISI DESIGN MANUAL.
B. STUD AND JOIST DESIGNATION AND RELATED ACCESSORIES ON THE DRAWINGS
ARE FOR UNIMAST, INC. OTHER MANUFACTURERS SHALL FURNISH ELEMENTS
OF EQUAL OR GREATER SECTION PROPERTIES AND MATERIAL STRENGTHS
(STUDS: Fy = 40,000 PSI, TRACK: Fy = 33,000 PSI).
C. ALL CONNECTIONS ARE THE RESPONSIBILITY OF THE SUPPLIER.
D. ALL FRAMING MATERIALS SHALL BE CUT SQUARE, ERECTED LEVEL AND PLUMB
AND SHALL BE INSTALLED PER MANUFACTURER INSTRUCTIONS.
E. PROVIDE INSULATION EQUAL TO THAT SPECIFIED ELSEWHERE AT ALL DOUBLED
JAMB STUDS AND HEADERS NOT ACCESSIBLE LATER.
F. SPLICES ARE NOT PERMITTED IN COMPONENTS OTHER THAN TRACKS.
G. LOAD BEARING STUDS SHALL BE INSTALLED WITH ENDS FULLY INSERTED INTO
RUNNER TRACKS AND SHALL BE ATTACHED TO BOTH FLANGES OF UPPER AND
LOWER TRACKS.
H. PROVIDE HORIZONTAL STRAP BRACING OR BLOCKING PER MANUFACTURER
RECOMMENDATIONS AT NOT MORE THAN 48" VERTICAL SPACING.
SLOPE 6.4 [1/4"] : 305 [12"] MIN.
EDGE OF SLAB
SEE PLAN
SEE 3/S1.00 FOR NOTES
[1 /2
SAND
203 [8"] CONC SLAB
REINF W/13 [#4] @
305 [12"] O.C. E/W
16 [#5] X 610 [24"]
EPOXY-COATED DWL @
305 [12"] O.C., DRILL &
ADHESIVE, 6" EMBED.
(3) SIDES
1219 [4'-0"]
19 [3/4"] CHAMFER
(NO CHAMFER
WHERE STOOP
ABUTS SIDEWALK)
13 [1/2"] E.J. MAT'L 152 [6"]
FASTENER NOTES
A. FASTENERS ARE BASED ON HILTI NORTH AMERICA. (1-800-879-8000,
www.US.HILTI.COM) UNLESS NOTED OTHERWISE.
B. SUBSTITUTIONS WILL BE CONSIDERED PROVIDED CONTRACTOR SUPPLIES DATA
WHICH SHOWS EQUIVALENT FASTENER CAPACITY. EMBEDMENT DEPTH,
FASTENER SPACING AND EDGE DISTANCES MUST BE CONSIDERED.
C. FASTENER TYPES:
ADHESIVE ANCHOR IN HOLLOW CMU: . . . . . HY20 W/SCREEN TUBE
ADHESIVE ANCHOR IN GROUTED CMU: . . . . HY150 MAX W/HAS-E ROD
ADHESIVE ANCHOR IN CONCRETE: . . . . . . . RE500SD W/HAS ROD
EXPANSION ANCHOR IN CONCRETE: . . . . . . KWIK BOLT TZ
EXPANSION ANCHOR IN SOLID
GROUT CMU:. . . . . . . . . . . . . . . . . . . . . . . . . KWIK BOLT III
SLEEVE ANCHOR: . . . . . . . . . . . . . . . . . . . . . . HLC SLEEVE ANCHOR
CONCRETE SCREW ANCHOR: . . . . . . . . . . . . KWIK-CON III
METAL DECK
METAL STUD
ROOF JOIST
SOLID BLOCKING
CONT. RUNNER
JBE
SEE PLAN
FILE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT TITLE:
COPYRIGHT 2010 BY LHB, INC. ALL RIGHTS RESERVED
http://www.LHBcorp.com
21 W. Superior Street Suite 500 Duluth, MN 55802
TEL 218/727-8446
FAX 218/727-8456
DULUTH MINNEAPOLIS
I HEREBY CERTIFY that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the State of Minnesota.
Signature:
Typed or Printed Name:
Date: Reg. No.:
THIS SQUARE APPEARS 1/2"x1/2" ON FULL SIZE SHEETS
CLIENT:
DULUTH, MINNESOTA
FMKM 932052
03/26/10 TYPE B FINAL SUBMITTAL
REPLACE
CENTRAL HEAT
PLANT
148th FIGHTER WING
MINNESOTA AIR
NATIONAL GUARD
C R e v it P ro je c ts
\0 B
L D
G
\D
R H
-0 B
L D
G
S
C e n tr a l.
rv t
/2
/2
:3
:5
A
M
CLG
AJV
090255
S1.00
BLDG 231
NOTES, PLANS
& DETAILS
03/26/10
1/4" = 1'-0"
PLAN - SLAB & FOUNDATION, BOILER ROOM ADDITION
1/4" = 1'-0"
PLAN - ROOF FRAMING, BOILER ROOM ADDITION
3/4" = 1'-0"
SLAB EDGE DETAIL
1" = 1'-0"
ROOF EDGE DETAIL
1" = 1'-0"
ROOF EDGE DETAIL
3/4" = 1'-0"
STOOP DETAIL
NORTH NORTH
1" = 1'-0"
ROOF EDGE DETAIL
No Date Revision
ALAN J. VORDERBRUGGEN
20969
127 [5"] CONC SLAB REINF.
W/ 6X6-W2.9XW2.9 WWF
T/SLAB = 2540 [100'-0"]
600S137-43 STUDS
@ [610] 24" O.C., ALIGN STUDS
W/JOISTS
EXIST WALL
(3) 16 [#5] X 610 [24"] DWL,
DRILL & ADHESIVE INTO
EX FND WALL, 152 [6"]
EMBED., TYP
DRAINTILE, CONNECT TO
EXISTING SYSTEM (IF
PRESENT) OR ROUTE TO
NORTH, SEE CIVIL
INSULATION LINE
F /E
X W
A L L
SLAB EDGE
2997 [9'-10"]
S L A
B E
D G
E
254 [10"]
1626 [5'-4"]
S1.01
S1.01
FLOOR DRAIN, SUMP
& HOUSEKEEPING
PAD - SEE MECH
DEMO EXIST SHED AND
FND IN THEIR ENTIRETY
DEPRESSED
SLAB - SEE
MECH
V .I .F
V.I.F.
762 [2'-6"]7
S1.01
1.5B 22 GA
METAL DECK
SLOPE 6.4 [1/4"]:305 [12"]
54 [16 GA] CONT.
RUNNER B/S
EXIST WALL
600S137-43 BOX
HEADER W/STIFFENERS
610 [24"] O.C.
1000S162-68 JOISTS @
JST BRG ELEV =
32918 [108'-0"]
JST BRG ELEV =
3982 [108'-2 1/2"]
VENT BOILER THRU
WALL BETWEEN
STUDS.
NOTE: ATTACH 1ST STUD TO
EX WALL W/ HILTI KWIK-CON II
3/16X1 3/4 HEX-HEAD/WASHER
ANCHORS. (3) ANCHORS @ 3"
O.C. @ T/ STUD, THEN 24" O.C.
THEREAFTER (TYP.)
914 [3'-0"]914 [3'-0"]
S1.01
S1.01
1000S162-68 JOISTS
@ 610 [24"] O.C.
DECK SPAN
DIRECTION
JOIST BRIDGING
@ MIDSPAN
DRAIN TILE
F/STUD
51 [2"]
457 [1'-6"]
M A
X
1219 [4'-0"]
SUITABLE
SUBGRADE
COMPACTED
NFS FILL
(2) LAYERS 51 [2"]
EXTRUDED POLYSTYRENE,
STAGGER JOINTS
(2) 16 [#5] , TOP & BOTT
10 [#3] TIES @ 610 [24"] O.C.
SEE PLAN
FOR SLAB
METAL PANEL - SEE ARCH
SLOPE 6.4 [1/4"] : 305 [12"] MIN.
EDGE OF SLAB
SEE PLAN
VAPOR
RETARDER
SLOPE 6.4 [1/4"] : 305 [12"] MIN.
EDGE OF SLAB
SEE PLAN
SEE 3/S1.01 FOR NOTES
/2
SAND
203 [8"] CONC SLAB
REINF W/13 [#4] @ 305
[12"] O.C. E/W
16 [#5] X 610 [24"] EPOXY-
COATED DWL @ 305 [12"]
O.C., DRILL & ADHESIVE,
152 [6"] EMBED.
(3) SIDES
1219 [4'-0"]
19 [3/4"]
CHAMFER
13 [1/2"] E.J. MAT'L
152 [6"]
CONT.
RUNNER
METAL DECK
ROOF JOIST
METAL STUD
JBE VARIES
SEE PLAN
METAL DECK
ROOF JOIST
METAL STUD
ROOF JOIST
JBE
SEE PLAN
CONT. RUNNER
SOLID BLOCKING
SEE PLAN FOR SLAB
VAPOR
RETARDER
VERIFY IN FIELD
V E
R
IF
Y I N
F
IE
L D
B/ GRADE
BEAM BEYOND
13 [#4] @ 406 [16"] O.C.
GENERAL DESIGN AND CONSTRUCTION NOTES
A. BUILDING CODE
1. 2007 MINNESOTA STATE BUILDING CODE (MSBC).
2. 2006 INTERNATIONAL BUILDING CODE (IBC).
B. DESIGN LIVE LOADS
1. WIND LOAD: 90 MPH (3 SEC. GUST), EXPOSURE C,
IMPORTANCE FACTOR 1.15
2. SEISMIC LOAD: NOT APPLICABLE (MSBC).
3. ROOF LIVE LOAD: 20 PSF
4. ROOF SNOW LOAD: 60 PSF GROUND SNOW PLUS SNOW ACCUMULATION
PER IBC AND ASCE 7-05.
a. FLAT ROOF SNOW LOAD, Pf = 46.2 PSF
b. SNOW EXPOSURE FACTOR, Ce = 1.0
c. SNOW IMPORTANCE FACTOR, I = 1.1
d. THERMAL FACTOR, Ct = 1.0
C. FOOTINGS AND FOUNDATION
1. SOIL DESIGN PRESUMPTIVE NET ALLOWABLE BEARING CAPACITY IS
2000 PSF IN ACCORDANCE WITH IBC TABLE 1804.2. SOIL CONDITIONS
SHALL BE VERIFIED BY A LICENSED GEOTECHNICAL ENGINEER.
2. FOUNDATIONS SHALL BEAR ON UNDISTURBED, UNFROZEN SUBGRADE,
EXCEPT WHERE COMPACTED SUBGRADE OR FILL IS OTHERWISE
SPECIFIED, OR FOUNDATIONS BEAR ON ROCK.
3. SEE DRAWINGS FOR DRAIN TILE LOCATIONS.
D. CONSTRUCTION NOTES
1. ALL DIMENSIONS INVOLVING COORDINATION OF NEW WORK WITH EXISTING
CONSTRUCTION SHALL BE FIELD-CHECKED BY THE CONTRACTOR AND
FURNISHED TO THE SUBCONTRACTORS PRIOR TO FABRICATION OF ANY
WORK. THE VERIFIED DIMENSIONS SHALL APPEAR AND BE NOTED ON THE
SHOP DRAWINGS SUBMITTED.
2. THE CONTRACTOR IS RESPONSIBLE FOR THE PROTECTION OF EXISTING
BUILDINGS, UTILITIES, STREETS, ETC. DURING CONSTRUCTION. CONTRACTOR
IS RESPONSIBLE FOR DESIGN AND INSTALLATION OF ALL NECESSARY
TEMPORARY BRACING.
3. ANY HOLES CUT IN NEW OR EXISTING CONSTRUCTION THAT ARE NOT
DETAILED ON THE STRUCTURAL DRAWINGS SHALL BE REVIEWED WITH THE
STRUCTURAL ENGINEER. COORDINATE ALL HOLES AND PENETRATIONS WITH
OTHER DISCIPLINES.
4. THE STRUCTURE SHALL BE ADEQUATELY BRACED AND SHORED DURING
ERECTION AGAINST WIND AND ERECTION LOADS. STRUCTURAL MEMBERS
ARE DESIGNED FOR IN-PLACE LOADS.
5. THE CONTRACTOR SHALL NOTIFY THE ENGINEER IMMEDIATELY OF
DISCREPANCIES FOUND BETWEEN CONSTRUCTION DOCUMENTS AND ACTUAL
FIELD CONDITIONS.
E. SPECIAL INSPECTIONS AND TESTING
1. SEE PROJECT "SPECIAL STRUCTURAL TESTING AND INSPECTION SUMMARY
SCHEDULE".
COLD-FORMED STEEL
A. LIGHT GAUGE FRAMING SHALL BE DESIGNED AND CONSTRUCTED IN
ACCORDANCE WITH 2001 AISI SPECIFICATIONS WITH 2004 SUPPLEMENT AND
2002 AISI DESIGN MANUAL.
B. STUD AND JOIST DESIGNATION AND RELATED ACCESSORIES ON THE DRAWINGS
ARE FOR UNIMAST, INC. OTHER MANUFACTURERS SHALL FURNISH ELEMENTS
OF EQUAL OR GREATER SECTION PROPERTIES AND MATERIAL STRENGTHS
(STUDS: Fy = 40,000 PSI, TRACK: Fy = 33,000 PSI).
C. ALL CONNECTIONS ARE THE RESPONSIBILITY OF THE SUPPLIER.
D. ALL FRAMING MATERIALS SHALL BE CUT SQUARE, ERECTED LEVEL AND PLUMB
AND SHALL BE INSTALLED PER MANUFACTURER INSTRUCTIONS.
E. PROVIDE INSULATION EQUAL TO THAT SPECIFIED ELSEWHERE AT ALL DOUBLED
JAMB STUDS AND HEADERS NOT ACCESSIBLE LATER.
F. SPLICES ARE NOT PERMITTED IN COMPONENTS OTHER THAN TRACKS.
G. LOAD BEARING STUDS SHALL BE INSTALLED WITH ENDS FULLY INSERTED INTO
RUNNER TRACKS AND SHALL BE ATTACHED TO BOTH FLANGES OF UPPER AND
LOWER TRACKS.
H. PROVIDE HORIZONTAL STRAP BRACING OR BLOCKING PER MANUFACTURER
RECOMMENDATIONS AT NOT MORE THAN 48" VERTICAL SPACING.
B. CONCRETE NOTES
1. PERFORM WORK IN ACCORDANCE WITH ACI-301-05 AND ACI 318-05.
2. CONCRETE CLEAR COVER OVER REINFORCING STEEL SHALL MEET THE
REQUIREMENTS OF ACI 318-05.
3. PROVIDE A 3/4" CHAMFER ON ALL EXPOSED CONCRETE CORNERS UNLESS
NOTED OTHERWISE.
4. PROVIDE LAP SPLICES AT ALL CORNERS AND INTERSECTIONS, SAME
SIZE AND SPACING AS HORIZONTAL REINFORCING.
5. PROVIDE SUPPORTS AND SPACERS FOR ALL REINFORCING, INCLUDING WWF.
6. SEE ARCHITECTURAL PLANS FOR DEPRESSED AND SLOPED AREAS IN
FLOORS NOT SHOWN ON STRUCTURAL DRAWINGS.
7. CONSOLIDATE ALL CONCRETE, INCLUDING SLABS, BY VIBRATING.
8. ALL CONCRETE SHOWN SHALL BE REINFORCED. PLANS, SECTIONS AND
DETAILS SHOWN WITHOUT REINFORCEMENT ARE INTENDED TO SHOW
DIMENSIONS AND DETAILS OF CONSTRUCTION ONLY. REINFORCEMENT OF
THESE SECTIONS SHALL BE PROVIDED IN ACCORDANCE WITH THE
DETAILS SHOWING REINFORCEMENT.
9. LAP SPLICES 40 BAR DIAMETERS (MIN.) UNLESS NOTED OTHERWISE.
10. MIX DESIGNS SHALL INCORPORATE ADMIXTURES AS APPROPRIATE FOR
ENVIRONMENTAL CONDITIONS.
11. COORDINATE GROUNDING REQUIREMENTS BETWEEN FOUNDATION
CONSTRUCTION AND ELECTRICAL WORK.
12. ALL REINFORCING SHALL BE DETAILED, FABRICATED & PLACED IN
ACCORDANCE WITH CRSI "MANUAL OF STANDARD PRACTICE".
13. SUBMIT DESCRIPTION OF PLANNED PROTECTIVE MEASURES FOR HOT OR
COLD WEATHER CONCRETING.
CAST-IN-PLACE CONCRETE
2. REINFORCING PROPERTIES:
ALL BARS UNLESS NOTED OTHERWISE:
TIES & STIRRUPS:
WELDED WIRE FABRIC (SMOOTH, SHEETS):
WELDABLE REINFORCEMENT:
EPOXY COATING:
3. CHAIRS AND BOLSTERS SHALL BE PLASTIC OR EPOXY COATED.
4. IF CONCRETE SUPPORT BLOCKS ARE USED, THEIR STRENGTH SHALL BE
EQUAL OR GREATER THAN THAT OF THE CONCRETE BEING PLACED.
f'c (PSI)
28 DAYS
4,000 4,000 4,500
MAX.
SLUMP
INCHES
MAX
AGGR.
3/4" 3/4" 3/4"
ENTR.
AIR (%)
0*
MAX.
W/C 0.45 0.45 0.45
FY (PSI)
60,000 60,000 65,000 60,000
N/A
ASTM
A615 A615 A185 A706 A775
A. MATERIAL PROPERTIES
1. CONCRETE PROPERTIES:
GRADE BEAMS:
INT. SLAB ON GRADE (NW):. .
EXT. CONCRETE FOR STOOPS
* USE 6%±1.5% ENTRAINED AIR IF EXTERIOR CONCRETE
14. PROVIDE 6X6 - W2.9XW2.9 WWF FOR ALL SLABS ON GRADE U.N.O.
15. CONCRETE SLABS ON GRADE SHALL BE PLACED ON A 4" SAND CUSHION.
INSTALL VAPOR RETARDER UNDER ALL SLABS. INSTALL THE VAPOR
RETARDER DIRECTLY BELOW THE SLAB.
16. THE FOLLOWING MINIMUM CONCRETE COVER SHALL BE PROVIDED FOR
REINFORCEMENT:
CONCRETE CAST AGAINST &
PERMANENTLY EXPOSED TO EARTH:
CONCRETE EXPOSED TO EARTH OR WEATHER:
#6 THRU #11 BARS:
#5 & SMALLER BARS:
CONCRETE NOT EXPOSED TO WEATHER
OR IN CONTACT WITH GROUND:
SLABS AND WALLS:
BEAMS AND COLUMNS:
17. HOUSEKEEPING PADS SHALL BE 102 [4"] CONCRETE WITH 13 [#4] BARS AT
305 [12") ON CENTER EACH WAY UNLESS NOTED OTHERWISE.
MINIMUM
COVER (IN.)
1 1/2
3/4 1 1/2
FASTENER NOTES
A. FASTENERS ARE BASED ON HILTI NORTH AMERICA. (1-800-879-8000,
www.US.HILTI.COM) UNLESS NOTED OTHERWISE.
B. SUBSTITUTIONS WILL BE CONSIDERED PROVIDED CONTRACTOR SUPPLIES DATA
WHICH SHOWS EQUIVALENT FASTENER CAPACITY. EMBEDMENT DEPTH,
FASTENER SPACING AND EDGE DISTANCES MUST BE CONSIDERED.
C. FASTENER TYPES:
ADHESIVE ANCHOR IN HOLLOW CMU: . . . . . HY20 W/SCREEN TUBE
ADHESIVE ANCHOR IN GROUTED CMU: . . . . HY150 MAX W/HAS-E ROD
ADHESIVE ANCHOR IN CONCRETE: . . . . . . . RE500SD W/HAS ROD
EXPANSION ANCHOR IN CONCRETE: . . . . . . KWIK BOLT TZ
EXPANSION ANCHOR IN SOLID
GROUT CMU:. . . . . . . . . . . . . . . . . . . . . . . . . KWIK BOLT III
SLEEVE ANCHOR: . . . . . . . . . . . . . . . . . . . . . . HLC SLEEVE ANCHOR
CONCRETE SCREW ANCHOR: . . . . . . . . . . . . KWIK-CON III
FILE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT TITLE:
COPYRIGHT 2010 BY LHB, INC. ALL RIGHTS RESERVED
http://www.LHBcorp.com
21 W. Superior Street Suite 500 Duluth, MN 55802
TEL 218/727-8446
FAX 218/727-8456
DULUTH MINNEAPOLIS
I HEREBY CERTIFY that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the State of Minnesota.
Signature:
Typed or Printed Name:
Date: Reg. No.:
THIS SQUARE APPEARS 1/2"x1/2" ON FULL SIZE SHEETS
CLIENT:
DULUTH, MINNESOTA
FMKM 932052
03/26/10 TYPE B FINAL SUBMITTAL
REPLACE
CENTRAL HEAT
PLANT
148th FIGHTER WING
MINNESOTA AIR
NATIONAL GUARD
C R e v it P ro je c ts
\0 B
L D
G
\D
R H
-0 B
L D
G
S
C e n tr a l.
rv t
/2
/2
:3
:4
A
M
CLG
AJV
090255
S1.01
BLDG 240
NOTES, PLANS
& DETAILS
03/26/10
1/4" = 1'-0"
PLAN - SLAB & FOUNDATION, BOILER ROOM ADDITION 1/4" = 1'-0"
PLAN - ROOF FRAMING, BOILER ROOM ADDITION
3/4" = 1'-0"
SLAB EDGE DETAIL
3/4" = 1'-0"
STOOP DETAIL
1" = 1'-0"
ROOF EDGE DETAIL
1" = 1'-0"
ROOF EDGE DETAIL
NORTH
NORTH
1/2" = 1'-0"
SECTION @ DEPRESSED SLAB
No Date Revision
ALAN J. VORDERBRUGGEN
20969
FAX (218) 722-1931
Email: mail@fjj.com
(218) 722-3060
DULUTH, MN 55802
345 CANAL PARK DRIVE
SUITE 200
BOILER SCHEDULEPUMP SCHEDULE
UNIT HEATER SCHEDULE
(218) 722-3060
DULUTH, MN 55802
345 CANAL PARK DRIVE
SUITE 200
BOILER SCHEDULE
PUMP SCHEDULE
UNIT HEATER SCHEDULE (HOT WATER)
Keyed Notes:
Email: mail@fjj.com
(218) 722-3060
DULUTH, MN 55802
345 CANAL PARK DRIVE
SUITE 200
BOILER SCHEDULE
FAN SCHEDULE
(218) 722-3060
DULUTH, MN 55802
345 CANAL PARK DRIVE
SUITE 200
BOILER SCHEDULE COIL SCHEDULE
FAN SCHEDULE
(218) 722-3060
DULUTH, MN 55802
345 CANAL PARK DRIVE
SUITE 200
1P 1 POLE (2P, 3P, 4P, ETC.)
A AMPERE
AC ABOVE COUNTER OR AIR
CONDITIONER
ACLG ABOVE CEILING
ADO AUTOMATIC DOOR OPENER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFI ARC FAULT CIRCUIT
INERUPTER
AHU AIR HANDLING UNIT
AL ALUMINUM ALT ALTERNATE
AMP AMPERE
AMPL AMPLIFIER
ANNUN ANNUNCIATOR
APPROX APPROXIMATELY
AQ-STAT AQUASTAT
ARCH ARCHITECT, ARCHITECTURAL
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AV AUDIO VISUAL
AWG AMERICAN WIRE GAUGE
BATT BATTERY
BD BOARD
BLDG BUILDING
BMS BUILDING MANAGEMENT
SYSTEM
C CONDUIT
CAB CABINET
CATV CABLE TELEVISION
CB CIRCUIT BREAKER
CCTV CLOSED CIRCUIT TELEVISION
CKT CIRCUIT
CLG CEILING
COMB COMBINATION
CMPR COMPRESSOR
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUATION OR
CONTINUOUS
CONTR CONTRACTOR
CONV CONVECTOR
CP CIRCULATING PUMP
CRT CATHODE-RAY TUBE
CT CURRENT TRANSFORMER
CTR CENTER
CU COPPER
DCP DOMESTIC WATER
CIRCULATING PUMP
DEPT DEPARTMENT
DET DETAIL
DIA DIAMETER
DISC DISCONNECT
DIST DISTRIBUTION
DN DOWN
DPR DAMPER
DS SAFETY DISCONNECT SWITCH
DT DOUBLE THROW
DWG DRAWING
EC ELECTRICAL CONTRACTOR
ELEC ELECTRIC, ELECTRICAL
ELEV ELEVATOR
EM EMERGENCY
EMS ENERGY MANAGEMENT SYSTEM
EMT ELECTRICAL METALLIC TUBING
EP ELECTRIC PNEUMATIC
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EXIST EXISTING
EXH EXHAUST
EXP EXPLOSION PROOF
FA FIRE ALARM
FABP FIRE ALARM BOOSTER POWER
SUPPLY PANEL
FACP FIRE ALARM CONTROL PANEL
FCU FAN COIL UNIT
FIXT FIXTURE
FLR FLOOR
FLUOR FLUORESCENT
FU FUSE
FUDS FUSED SAFETY DISCONNECT
SWITCH
GA GAUGE
GAL GALLON
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERATOR
GFI GROUND FAULT CIRCUIT
INTERRUPTER
GFP GROUND FAULT PROTECTOR
GND GROUND
GRS GALVANIZED RIGID STEEL
(CONDUIT)
GYP BD GYPSUM BOARD
HOA HANDS-OFF-AUTOMATIC
SWITCH
HORIZ HORIZONTAL
HP HORSEPOWER
HPF HIGH POWER FACTOR
HT HEIGHT
HTG HEATING
HTR HEATER
HV HIGH VOLTAGE
HWP HYDRONIC WATER PUMP
IC INTERRUPTING CAPACITY
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
INCAND INCANDESCENT
IR INFRARED
I/W INTERLOCK WITH
J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT-AMPERE
KVAR KILOVOLT-AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
LOC LOCATE OR LOCATION
LT LIGHT
LTG LIGHTING
LTNG LIGHTNING
LV LOW VOLTAGE
MAX MAXIMUM
MAG.S MAGNETIC STARTER
M/C MOMENTARY CONTACT
MC MECHANICAL CONTRACTOR
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDC MAIN DISTRIBUTION CENTER
MDP MAIN DISTRIBUTION PANEL
MFR MANUFACTURER
MFS MAIN FUSED DISCONNECT
SWITCH
MH MANHOLE
MIC MICROPHONE
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MMS MANUAL MOTOR STARTER
MOA MULTIOUTLET ASSEMBLY
MSP MOTOR STARTER PANELBOARD
MSBD MAIN SWITCHBOARD
MT MOUNT
MT.C EMPTY CONDUIT
MTS MANUAL TRANSFER SWITCH
MTR MOTOR, MOTORIZED
N.C. NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURER'S
ASSOCIATION
NFDS NON-FUSED SAFETY
DISCONNECT SWITCH
NIC NOT IN CONTRACT
NL NIGHT LIGHT
N.O. NORMALLY OPEN
NPF NORMAL POWER FACTOR
NTS NOT TO SCALE
OH OVERHEAD
OL OVERLOADS
PA PUBLIC ADDRESS
PB PULL BOX OR PUSHBUTTON
PE PNEUMATIC ELECTRIX
PED PEDESTAL PF POWER FACTOR
PH PHASE
PNL PANEL
PP POWER POLE
PR PAIR
PRI PRIMARY
PROJ PROJECTION
PRV POWER ROOF VENTILATOR
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE
(CONDUIT)
PWR POWER
QUAN QUANITY
RCPT RECEPTACLE
REQD REQUIRED
RSC RIGID STEEL CONDUIT
RTU ROOF TOP UNIT
SC SURFACE CONDUIT
SEC SECONDARY
SHT SHEET
SIM SIMILAR
S/N SOLID NEUTRAL
SPEC SPECIFICATION
SPKR SPEAKER
SP SPARE
SR SURFACE RACEWAY
SS STAINLESS STEEL
SSW SELECTOR SWITCH
S/S STOP/START PUSHBUTTONS
STA STATION
STD STANDARD
SURF SURFACE MOUNTED
SW SWITCH
SWBD SWITCHBOARD
SYM SYMMECTRICAL SYS SYTEM
TEL TELEPHONE
TERM TERMINAL
TL TWIST LOCK
TR TAMPER RESISTANT
T-STAT THERMOSTAT
TTC TELEPHONE TERMINAL
CABINET
TV TELEVISION
TVTC TELEVISION TERMINAL
CABINET
TYP TYPICAL
UE UNDERGROUND ELECTRICAL
UG UNDERGROUND
UH UNIT HEATER
UT UNDERGROUND TELEPHONE
UV UNIT VENTILATOR OR
ULTRAVIOLET
V VOLT
VA VOLT-AMPERES
VDT VIDEO DISPLAY TERMINAL
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VOL VOLUME
W WATT
W/ WITH
WG WIRE GUARD
WH WATER HEATER
W/O WITHOUT
WP WEATHERPROOF
XFMR TRANSFORMER
XFR TRANSFER
ANGLE
@ AT
' FEET
" INCHES
# NUMBER
Ø PHASE
C CENTER LINE
P PLATE
L L
ELECTRICAL ABBREVIATIONS LIST
FIRE PROTECTION REQUIREMENTS
A. PENETRATIONS IN WALLS REQUIRING PROTECTED OPENINGS MUST BE FIRESTOPPED WITH AN
APPROVED MATERIAL.
1. CONDUITS MAY PENETRATE WALLS OR PARTITIONS, PROVIDED THEY ARE FIRE-STOPPED.
2. OPENINGS FOR STEEL ELECTRICAL BOXES NOT EXCEEDING 16 SQUARE INCHES ARE
PERMITTED PROVIDED OPENINGS DO NOT AGGREGATE MORE THAN 100 SQUARE INCHES
FOR ANY 100 SQUARE FEET OF WALL OR PARTITION.
3. OUTLET BOXES ON OPPOSITE SIDES OF WALLS OR PARTITIONS MUST BE SEPARATED
BY A HORIZONTAL DISTANCE OF 24 INCHES.
B. LIGHT FIXTURES AND OTHER APPARATUS SUPPORTED BY THE ACOUSTICAL CEILING GRID
MUST MEET THE REQUIREMENTS OF NEC SECTION 410.16, MEANS OF SUPPORT.
C. RECESSED LIGHTING FIXTURES INSTALLED IN FIRE RATED CEILING ASSEMBLIES SHALL BE
FIRE RATED FIXTURES BEARING THE UL FIRE RATED LABEL. FIXTURES SHALL BE
INSTALLED IN ACCORDANCE WITH THE UL FIRE RESISTANCE DIRECTORY, AND SHALL
INCLUDE A FIRE RATED ENCLOSURE INSTALLED OVER THE FIXTURE THAT MEETS THE
REQUIREMENTS OF THE UL FIRE RESISTANCE DIRECTORY.
SPECIFIC CODE NOTES
SYSTEM DESIGNATION
EQUIPMENT DESIGNATION
UNINTERUPTABLE POWER SOURCE
ISOLATED GROUND
EMERGENCY
POWER CONDITIONED
NORMAL
C
UPS
IG
LP4N-102
E N
PANEL NO.
FLOOR OF STRUCTURE
LOW VOLTAGE 1Ø3W. 120/208
LOW VOLTAGE 1Ø3W. 120/240
LOW VOLTAGE 3Ø4W. 120/208
HIGH VOLTAGE 3Ø4W. 277/480
EQUIPMENT DESIGNATION
SYSTEMS DESIGNATION
LP1
LP2
LP4
HP4
CODE
CODE
HP3HIGH VOLTAGE 3Ø3W. 480
LP3LOW VOLTAGE 3Ø3W. 208
HIGH VOLTAGE 1Ø3W. 277/480 HP1
PANELBOARD IDENTIFICATION
A. ALL CONDUCTORS OPERATING AT 50 VOLTS OR GREATER SHALL BE IN RACEWAY. ALL
RACEWAY WITHIN THE STRUCTURE ABOVE THE FLOOR SLAB SHALL BE METAL. RACEWAY
BELOW THE FLOOR SLAB AND UNDERGROUND RACEWAY OUTSIDE THE STRUCTURE SHALL BE
PVC.
B.
C.
ALL LOW VOLTAGE CABLES OR CONDUCTORS OPERATING AT LESS THAN 50 VOLTS SHALL
BE IN METAL RACEWAY. LOW VOLTAGE CABLES MAY BE RUN IN CABLE TRAY WHERE
NOTED.
COORDINATE LOCATIONS OF DEVICES WITH ARCHITECTURAL ELEVATIONS AND DETAILS.
ARCHITECTURAL ELEVATIONS AND DETAILS TAKE PRECEDENCE OVER LOCATIONS SHOWN ON
ELECTRICAL DRAWINGS.
D. WHERE CONNECTED TO A 20A. BRANCH CIRCUIT SUPPLYING AN INDIVIDUAL RECEPTACLE
(SIMPLEX OR DUPLEX), THE RECEPTACLE SHALL BE RATED AT 20A.
CONTRACTOR SHALL BE RESPONSIBLE FOR WIRING ALL ELECTRICAL ITEMS SHOWN ON THE
DRAWINGS, EXCEPT ITEMS LISTED IN NOTE F.
F. TELEPHONE OUTLETS AND DATA OUTLETS SHALL CONSIST OF BACK BOX WITH CONDUIT
STUBBED ABOVE THE ACCESSIBLE CEILING.
G. FURNISH AND INSTALL CONDUIT FROM BACK BOXES FOR THE FOLLOWING DEVICES TO THE CABLE
TRAY OR MDF, VERIFY LOCATIONS.
3/4"C TELEPHONE OUTLETS
3/4"C INFORMATION OUTLETS
GENERAL ELECTRICAL NOTES
E.
ELECTRICAL DRAWINGS
SR
SYMBOL
LV
UE
EX
UMVE
OHE
OHT
*** DISTANCE TO HIGHEST OPERABLE PART OF EQUIPMENT
72"** CIRCUIT BREAKER PANEL
ALL DISTANCES ARE TO CENTER OF DEVICE OR EQUIPMENT UNLESS OTHERWISE NOTED. DEVICES INDICATED AT 48" MAY NOT BE INSTALLED WITH ANY OPERABLE PART HIGHER THAN 48". DEVICES MAY BE INSTALLED IN CONCRETE MASONRY UNITS WITH THE TOP OF THE DEVICE AT 48".
* DISTANCE ABOVE TOP OF DOOR FRAME
PER SCHED WALL HEATER (TYPE DENOTED)
** DISTANCE TO TOP OF EQUIPMENT OR DEVICE
PER SCHED D1
H2
HATCHED SYMBOL INDICATES REMOVED
HAND OR HAIR DRYER (TYPE DENOTED)
DASHED SYMBOL INDICATES EXISTING
SOLENOID VALVE
AS NOTED
AS NOTED
48"
48"
PER SCHED
48"
AS NOTED
H
T
H1
TC
AS NOTED
72"**
72"**
PS
IRSO
FS
R
72"**
72"**
72"**
48"
72"**
72"**
72"**
72"**
SF-1
T1
BUS DUCT WITH PLUG UN DISCONNECT (FUSED)
LIGHT LEVEL SENSOR - TYPE DENOTED
TIME CONTROL SWITCH (TIME SWITCH)
BASEBOARD HEATER (TYPE DENOTED)
HUMIDISTAT
THERMOSTAT
PHOTOCELL
ENCLOSED CIRCUIT BREAKER
PRESSURE SWITCH
RELAY
48"
84"
AS NOTED
84"
COMB. MOTOR STARTER (NON-FUSED)
MAG. MOTOR STARTER OR CONTACTOR
SAFETY DISC. SW. (FUSED)
SAFETY DISC. SW. (NON-FUSED)
COMB. MOTOR STARTER (FUSED)
MANUAL MTR. STR. (W/OVERLOADS)
POWER OR DISTRIBUTION PANEL
MOTOR (SEE SCHEDULE)
TRANSFORMER (TYPE DENOTED)
DAMPER MOTOR
SPECIAL CABINET (TYPE DENOTED)
48"***
18"
18"
18"
J
DESCRIPTION
WALL MOUNTED FLOODLIGHT (TYPE DENOTED)
SURFACE INCANDESCENT LIGHT (TYPE DENOTED)
POLE MOUNTED LIGHT (TYPE DENOTED)
RECESSED LIGHT (TYPE DENOTED)
SURFACE H.I.D. LIGHT (TYPE DENOTED)
EXIT SIGN (TYPE DENOTED)
SUSPENDED OR PENDANT LIGHT (TYPE DENOTED)
TRACK AND TRACK LIGHT (TYPES DENOTED)
SURFACE FLUORESCENT LIGHT (TYPE DENOTED)
FLUORESCENT STRIP LIGHT (TYPE DENOTED)
EMERGENCY BATTERY LIGHT (TYPE DENOTED)
RECESSED FLUORESCENT LIGHT (TYPE DENOTED)
POLE MOUNTED FLOODLIGHT (TYPE DENOTED)PER SCHED
PER SCHED
AS NOTED
12"*
96"
P2P1
T1S1S1
E E
EM
H
ST1
BB
G
AA
R
AS NOTED
HT AFF
AS NOTED
SYMBOL
A
C
B
D
AS NOTED
AS NOTED
J J
84" A
P
HT AFF
18"
18"
SYMBOL
A
GROUND CONNECTION - EXOTHERMIC WELD
GROUND CONNECTION TO STEEL OR STRUCTURE
STATIC GROUND RECEPTACLE (TYPE DENOTED)
SPECIAL CONNECTION (SEE SCHEDULE)
SPECIAL RECEPT. OR CONN. (SEE SCHEDULE)
JUNCTION BOX
PULL BOX
GROUND ROD (PLAN VIEW)
LIGHTNING PROTECTION AIR TERMINAL
SURGERY SERVICE COLUMN
CLOCK (TYPE DENOTED)
POWER POLE (OPEN OFFICE STYLE)
MULTIOUTLET ASSEMBLY (TYPE DENOTED)
MULTIOUTLET ASSEMBLY (TYPE DENOTED)
DESCRIPTION HT AFF
GAS DETECTOR (TYPE DENOTED)
FLEXIBLE CONDUIT OR FIXTURE WHIP
12"*
PROJECTOR CONTROL OUTLET
CCTV CAMERA WITH PAN/TILT DRIVE
**** DISTANCE BELOW CEILING
WEATHERHEAD
ANTENNA
CCTV CAMERA
***** DISTANCE TO BOTTOM OF DEVICE
NURSE CALL MASTER STATION
NURSE CALL DOME LIGHT (2 LAMP)
NURSE CALL ANNUNCIATOR PANEL
NURSE CALL EQUIPMENT CABINET
NCM
144"*
EQUIPOTENTIAL GROUND OUTLET
X-RAY FILM VIEWER (SEE SPECIFICATIONS)
DOOR SIGNAL - APT. UNIT
SPEAKER (WALL OR CEILING MT.)
SURFACE MT…
This is the start of the file's text. The full file is on GovTribe.