Add-Alter_B720_-_Addendum_1_Spec_28_31_76.pdf
PDF 106 KB Posted
- Attached to
- Add-Alter Squadron Operations Building 720 Federal contract opportunity
- Solicitation number
- W912L7-19-B-5001
About this file
Add-Alter B720 - Addendum 1 Spec 28 31 76
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Bid_Opening_Attendance_Roster.pdf | ||
| 19B5001_Abstract_of_Bids.pdf | ||
| W912L7-19-B-5001_QA__8-9.pdf | ||
| W912L7-19-B-5001_QA__1-7.pdf | ||
| Add-Alter_B720_-_Addendum_1_Drawings.pdf | ||
| W912L7-19-B-5001-001-Add-Alter_SQ_OPs_B720_Solicitation_Amnd_1.pdf | ||
| Preproposal_Minutes-Slides-Signin_Sheet.pdf | ||
| J&A-ALC_1.pdf | ||
| Add-Alter_B720_-__Addendum_1_Spec_21_13_18.00_10.pdf | ||
| 11_-_BKTZ172003_Drawings_Package_3.pdf | ||
| 10_-_BKTZ172003_Specifications_Package_1.pdf | ||
| 10_-_BKTZ172003_Specifications_Package_3.pdf | ||
| 11_-_BKTZ172003_Drawings_Package_2.pdf | ||
| 11_-_B720_Geotechnical_Report.pdf | ||
| W912L719B5001_Add-Alter_Sq_Ops_B720_Draft_Solicitation_05-31-2019.pdf | ||
| 10_-_BKTZ172003_Specifications_Package_2.pdf | ||
| 11_-_BKTZ172003_Drawings_Package_1.pdf |
Show all 17
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CH2M-HDR JV - Add/Alter B720 Squad Ops Project: BKTZ172003 Nashville IAP, TN - TNANG Addendum No. 1
SECTION 28 31 76
INTERIOR FIRE ALARM AND MASS NOTIFICATION SYSTEM
08/11
PART 1 GENERAL
1.1 RELATED SECTIONS
Section 26 00 00.00 20 BASIC ELECTRICAL MATERIALS AND METHODS, applies to this section, with the additions and modifications specified herein. In addition, refer to the following sections for related work and coordination:
Section 23 00 00 AIR SUPPLY, DISTRIBUTION, VENTILATION, AND EXHAUST
SYSTEMS
Section 21 13 13.00 10 WET PIPE SPRINKLER SYSTEM, FIRE PROTECTION Section 21 13 18.00 10 PREACTION AND DELUGE SPRINKLER SYSTEMS, FIRE
PROTECTION
Section 21 22 00.00 40 CLEAN AGENT FIRE EXTINGUISHING SYSTEMS
1.2 SUMMARY
1.2.1 Scope
a. This work includes completion of design and modifying the existing fire alarm and mass notification system as described herein and on the contract drawings for the building 720 addition and renovations.
Include in the system wiring, raceways, pull boxes, terminal cabinets, outlet and mounting boxes, control equipment, alarm, and supervisory signal initiating devices, alarm notification appliances, and other accessories and miscellaneous items required for a complete operating system even though each item is not specifically mentioned or described. Provide systems complete and ready for operation.
b. Provide equipment, materials, installation, workmanship, inspection, and testing in strict accordance with the required provisions of NFPA 72, ISO 7240-16, IEC 60268-16, except as modified herein. The system layout on the drawings show the intent of coverage and are shown in suggested locations. Submit plan view drawing showing device locations, terminal cabinet locations, junction boxes, other related equipment, conduit routing, wire counts, circuit identification in each conduit, and circuit layouts for all floors. Drawings shall comply with the requirements of NFPA 170. Final quantity, system layout, and coordination are the responsibility of the Contractor.
1.3 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ACOUSTICAL SOCIETY OF AMERICA (ASA)
ASA S3.2 (2009; R 2014) Method for Measuring the Intelligibility of Speech Over Communication Systems (ASA 85)
SECTION 28 31 76 Page 1 June 10, 2019
FM GLOBAL (FM)
FM APP GUIDE (updated on-line) Approval Guide http://www.approvalguide.com/
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE C62.41.1 (2002; R 2008) Guide on the Surges Environment in Low-Voltage (1000 V and Less) AC Power Circuits
IEEE C62.41.2 (2002) Recommended Practice on Characterization of Surges in Low-Voltage (1000 V and Less) AC Power Circuits
INTERNATIONAL ELECTROTECHNICAL COMMISSION (IEC)
IEC 60268-16 (2003; ED 4.0) Sound System Equipment - Part 16: Objective Rating Of Speech Intelligibility By Speech Transmission Index
INTERNATIONAL ORGANIZATION FOR STANDARDIZATION (ISO)
ISO 7240-16 (2007) Fire Detection And Alarm Systems — Part 16: Sound System Control And Indicating Equipment
ISO 7240-19 (2007) Fire Detection and Alarm Systems — Part 19: Design, Installation, Commissioning and Service of Sound Systems for Emergency Purposes
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 170 (2018) Standard for Fire Safety and Emergency Symbols
NFPA 70 (2017; ERTA 1-2 2017; TIA 17-1; TIA 17-2;
TIA 17-3; TIA 17-4; TIA 17-5; TIA 17-6;
TIA 17-7; TIA 17-8; TIA 17-9; TIA 17-10;
TIA 17-11; TIA 17-12; TIA 17-13; TIA
17-14) National Electrical Code
NFPA 72 (2016) National Fire Alarm and Signaling Code
NFPA 90A (2018) Standard for the Installation of Air Conditioning and Ventilating Systems
U.S. DEPARTMENT OF DEFENSE (DOD)
UFC 3-601-02 (2010) Operations and Maintenance:
Inspection, Testing, and Maintenance of Fire Protection Systems
UNDERWRITERS LABORATORIES (UL)
UL 1480 (2016; Reprint Sep 2017) UL Standard for
SECTION 28 31 76 Page 2
Safety Speakers for Fire Alarm and Signaling Systems, Including Accessories
UL 1638 (2016; Reprint Sep 2017) UL Standard for Safety Visible Signaling Devices for Fire Alarm and Signaling Systems, Including Accessories
UL 1971 (2002; Reprint Oct 2008) Signaling Devices for the Hearing Impaired
UL 2017 (2008; Reprint Jan 2016) General-Purpose Signaling Devices and Systems
UL 268 (2016; Reprint Jul 2016) UL Standard for Safety Smoke Detectors for Fire Alarm Systems
UL 464 (2016; Reprint Sep 2017) UL Standard for Safety Audible Signaling Devices for Fire Alarm and Signaling Systems, Including Accessories
UL 864 (2014) Standard for Control Units and Accessories for Fire Alarm Systems
UL Electrical Constructn (2012) Electrical Construction Equipment Directory
UL Fire Prot Dir (2012) Fire Protection Equipment Directory
1.4 DEFINITIONS
Wherever mentioned in this specification or on the drawings, the equipment, devices, and functions shall be defined as follows:
1.4.1 Interface Device
An addressable device that interconnects hard wired systems or devices to an analog/addressable system.
1.4.2 Remote Fire Alarm and Mass Notification Control Unit
A control panel, electronically remote from the fire alarm and mass notification control panel, that receives inputs from automatic and manual fire alarm devices; may supply power to detection devices and interface devices; may provide transfer of power to the notification appliances; may provide transfer of condition to relays or devices connected to the control unit; and reports to and receives signals from the fire alarm control panel.
1.4.3 Fire Alarm Control Unit and Mass Notification Autonomous Control Unit
(FMCP)
A master control panel having the features of a fire alarm and mass notification control unit and fire alarm and mass notification control units are interconnected. The panel has central processing, memory, input and output terminals, and LCD, LED Display units.
SECTION 28 31 76 Page 3
1.4.4 Local Operating Console (LOC)
A unit designed to allow emergency responders and/or building occupants to operate the MNS including delivery or recorded and/or live messages, initiate strobe and textural visible appliance operation and other relayed functions.
1.4.5 Terminal Cabinet
A steel cabinet with locking, hinge-mounted door that terminal strips are securely mounted.
1.5 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submittals with an "S" are for inclusion in the Sustainability eNotebook. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Instructions; G
Wiring Diagrams; G
System Layout; G
System Operation; G
Notification Appliances; G
Amplifiers; G
SD-03 Product Data
Technical Data And Computer Software; G
Terminal Cabinets; G
Manual Stations; G
Smoke Sensors; G
Notification Appliances; G
Addressable Interface Devices; G
Amplifiers; G
SD-06 Test Reports
Field Quality Control
Testing Procedures; G
Smoke Sensor Testing Procedures; G
SECTION 28 31 76 Page 4
SD-07 Certificates
Installer
Fire Protection Engineer
Formal Inspection and Tests
Final Testing
SD-09 Manufacturer's Field Reports
System Operation; G
Fire Alarm/Mass Notification System
SD-10 Operation and Maintenance Data
Operation and Maintenance (O&M) Instructions; G
Instruction of Government Employees; G
SD-11 Closeout Submittals
As-Built Drawings
1.6 QUALITY ASSURANCE
Equipment and devices shall be compatible and operable with existing station fire alarm system and shall not impair reliability or operational functions of existing supervising station fire alarm system. The supervising equipment is existing and consists of the following brands and models: supervising station control panel Fike Cheetah EST, Simplex, and Monaco.
a. Interpret reference to "authority having jurisdiction" to mean the Contracting Offices Designated Representative (COR).
b. The recommended practices stated in the manufacturer's literature or documentation shall be considered as mandatory requirements.
c. Devices and equipment for fire alarm service must be listed by UL Fire Prot Dir or approved by FM APP GUIDE.
1.6.1 Qualifications
1.6.1.1 Design Services
Installations requiring completion of installation drawings and specification or modifications of fire detection, fire alarm, mass notification system, fire suppression systems or mass notification systems shall require the services and review of a fire protection engineer. For the purposes of meeting this requirement, a qualified engineer is defined as an individual meeting one of the following conditions:
a. A registered professional engineer having a Bachelor of Science or Masters of Science Degree in Fire Protection Engineering from an accredited university engineering program, plus a minimum of four years work experience in fire protection engineering.
SECTION 28 31 76 Page 5
b. A registered professional engineer (P.E.) in fire protection engineering.
c. Registered Professional Engineer with verification of experience and at least five years of current experience in the design of the fire protection and detection systems.
1.6.1.2 Supervisor
NICET Fire Alarm Technicians to perform the installation of the system. A NICET Level IV Fire Alarm Technician shall supervise the installation of the fire alarm system/mass notification system. The Fire Alarm technicians supervising the installation of equipment shall be factory trained in the installation, adjustment, testing, and operation of the equipment specified herein and on the Drawings.
1.6.1.3 Technician
Fire Alarm Technicians with a minimum of four years of experience utilized to install and terminate fire alarm/mass notification devices, cabinets and panels. The Fire Alarm technicians installing the equipment shall be factory trained in the installation, adjustment, testing, and operation of the equipment specified herein and on the Drawings.
1.6.1.4 Installer
NICET Level II technician to assist in the installation of fire alarm/mass notification devices, cabinets and panels. An electrician shall be allowed to install wire, cable, conduit and backboxes for the fire alarm system/mass notification system. The Fire Alarm installer shall be factory trained in the installation, adjustment, testing, and operation of the equipment specified herein and on the drawings.
1.6.1.5 Test Personnel
Fire Alarm Technicians with a minimum of eight years of experience and certified as a NICET Level IV shall be utilized to test and certify the installation of the fire alarm/mass notification devices, cabinets and panels. The Fire Alarm technicians testing the equipment shall be factory trained in the installation, adjustment, testing, and operation of the equipment specified herein and on the Drawings.
1.6.1.6 Manufacturer's Representative
The design shall be prepared by a licensed fire protection engineer. The fire alarm and mass notification equipment manufacturer's representative shall be present for the connection of wiring to the control panel. The Manufacturer's Representative shall be an employee of the manufacturer with necessary technical training on the system being installed and certified as a NICET Level IV.
1.6.1.7 Manufacturer
Components shall be of current design, compatible with existing devices, and shall be in regular and recurrent production at the time of installation. Provide design, materials, and devices for a protected premises fire alarm system, complete, conforming to NFPA 72, except as otherwise or additionally specified herein.
SECTION 28 31 76 Page 6
1.6.2 Regulatory Requirements
1.6.2.1 Requirements for Fire Protection Service
Equipment and material shall have been tested by UL and listed in UL Fire Prot Dir or approved by FM and listed in FM APP GUIDE. Where the terms "listed" or "approved" appear in this specification, they shall mean listed in UL Fire Prot Dir or FM APP GUIDE. The omission of these terms under the description of any item of equipment described shall not be construed as waiving this requirement. All listings or approval by testing laboratories shall be from an existing ANSI or UL published standard.
1.6.2.2 Fire Alarm/Mass Notification System
Furnish equipment that is compatible with existing Fike Cheetah releasing panel and Simplex EST fire alarm control panel equipment and devices, and is UL listed, FM approved, or listed by a nationally recognized testing laboratory for the intended use. All listings by testing laboratories shall be from an existing ANSI or UL published standard. Submit a unique identifier for each device, including the control panel and initiating and indicating devices, with an indication of test results, and signature of the factory-trained technician of the control panel manufacturer and equipment installer. With reports on preliminary tests, include printer information. Include the NFPA 72 Record of Completion and NFPA 72 Inspection and Testing Form, with the appropriate test reports.
1.6.2.3 Fire alarm Testing Services or Laboratories
construct fire alarm and fire detection equipment in accordance with UL Fire Prot Dir, UL Electrical Constructn, or FM APP GUIDE.
1.7 DELIVERY, STORAGE, AND HANDLING
Protect equipment delivered and placed in storage from the weather, humidity, and temperature variation, dirt and dust, and other contaminants.
PART 2 PRODUCTS
2.1 MATERIALS AND EQUIPMENT
Submit annotated catalog data as required in the paragraph SUBMITTAL, in table format on the drawings, showing manufacturer's name, model, voltage, and catalog numbers for equipment and components. Submitted shop drawings shall not be smaller than ISO A1. Also provide UL or FM listing cards for equipment provided.
2.1.1 Standard Products
Provide materials, equipment, and devices that have been tested by a nationally recognized testing laboratory, such as UL or FM Approvals, LLC (FM), and listed or approved for fire protection service when so required by NFPA 72 or this specification. Select material from one manufacturer, compatible with existing equipment and devices, where possible, and not a combination of manufacturers, for any particular classification of materials. Material and equipment shall be the standard products of a manufacturer regularly engaged in the manufacture of the products for at least 5 years prior to bid opening.
SECTION 28 31 76 Page 7
2.1.2 Keys
Keys and locks for equipment shall be identical. Provide not less than six keys of each type required. Master all keys and locks to a single key as required by the Installation Fire Department.
2.2 GENERAL PRODUCT REQUIREMENT
All fire alarm and mass notification equipment shall be listed for use under the applicable reference standards. Interfacing of Listed UL 864 or similar approved industry listing with Mass Notification Panels listed to UL 2017 shall be done in a laboratory listed configuration, if the software programming features cannot provide a listed interface control. If a field modification is needed, such as adding equipment like relays, the manufacturer of the existing panel shall provide the installing contractor for review and confirmation by the installing contractor. As part of the submittal documents, provide this information.
2.3 SYSTEM OPERATION
The existing system shall be activated into the alarm mode by actuation of any alarm initiating device. The system shall remain in the alarm mode until the initiating device is reset and the control panel is reset and restored to normal. The system may be placed in the alarm mode by local microphones, LOC, or remotely from authorized locations/users.
Submit a complete description of the system operation in matrix format on the drawings. Submit a complete list of new device addresses and corresponding messages.
2.3.1 Alarm Initiating Devices and Notification Appliances (Visual, Voice, Textural)
a. Connect alarm initiating devices to existing initiating device circuits (IDC) Class "A" to signal line circuits (SLC) Class "A" and installed in accordance with NFPA 72.
b. Connect alarm notification appliances and speakers to existing notification appliance circuits (NAC) Class "A.
c. The system shall operate in the alarm mode upon actuation of any alarm initiating device or a mass notification signal. The system shall remain in the alarm mode until initiating device(s) or mass notification signal is/are reset and the existing control panel is manually reset and restored to normal. Audible, and visual appliances and systems shall comply with NFPA 72 and as specified herein. Fire alarm system/mass notification system components requiring power, except for the control panel power supply, shall operate on 24 Volts dc.
2.3.2 Functions and Operating Features
The system shall provide the following functions and operating features:
a. The existing FACP shall provide power, annunciation, supervision, and control for the system. Addressable systems shall be microcomputer (microprocessor or microcontroller) based with a minimum word size of eight bits with sufficient memory to perform as specified.
b. For Class "A" circuits with conductor lengths of 3m (10 feet) or less, SECTION 28 31 76 Page 8 the conductors shall be permitted to be installed in the same raceway in accordance with NFPA 72.
c. Provide notification appliance circuits. The visual alarm notification appliances shall have the flash rates synchronized as required by
NFPA 72.
d. Provide an audible and visual trouble signal to activate upon a single break or open condition, or ground fault (or short circuit). The trouble signal shall also operate upon loss of primary power (AC) supply, absence of a battery supply, low battery voltage, or removal of alarm or supervisory panel modules. Provide a trouble alarm silence feature that shall silence the audible trouble signal, without affecting the visual indicator. After the system returns to normal operating conditions, the trouble signal shall again sound until the trouble is acknowledged. A smoke sensor in the process of being verified for the actual presence of smoke shall not initiate a trouble condition.
e. Alarm, supervisory, and/or trouble signals shall be automatically transmitted to the fire department.
f. Alarm functions shall override trouble or supervisory functions.
Supervisory functions shall override trouble functions.
g. The existing system shall be capable of being programmed from the panels keyboard. Programmed information shall be stored in non-volatile memory.
h. The existing system shall be capable of operating, supervising, and/or monitoring both addressable and non-addressable alarm and supervisory devices.
i. There shall be no limit, other than maximum system capacity, as to the number of existing/new addressable devices, that may be in alarm simultaneously.
j. Where the existing fire alarm/mass notification system is responsible for initiating an action in another emergency control device or system, such as an HVAC system releasing panel, the addressable fire alarm relay shall be within 3 feet of the emergency control device.
k. An alarm signal shall automatically initiate the following functions:
(1) Transmission of an alarm signal to the fire department.
(2) Visual indication of the device operated on the control panel
(FACP/MNCP).
(3) Continuous actuation of all alarm notification appliances.
(4) Recording of the event via electronically in the history log of the fire control system unit.
(5) Operation of a duct smoke sensor shall shut down the appropriate air handler in accordance with NFPA 90A in addition to other requirements of this paragraph and as allowed by NFPA 72.
(6) Operation of Very Early Warning Smoke Detection System level 3
SECTION 28 31 76 Page 9 shall release the FM-200 fire extinguishing system after a 30 second time delay.
l. A supervisory signal shall automatically initiate the following functions:
(1) Visual indication of the device operated on the FACP and sound the audible alarm at the respective panel.
(2) Transmission of a supervisory signal to the fire department.
(3) Recording of the event electronically in the history log of the control unit.
m. A trouble condition shall automatically initiate the following functions:
(1) Visual indication of the system trouble on the FACP and sound the audible alarm at the respective panel.
(2) Transmission of a trouble signal to the fire department.
(3) Recording of the event in the history log of the control unit.
n. The maximum permissible elapsed time between the actuation of an initiating device and its indication at the FACP is 10 seconds.
o. The maximum elapsed time between the occurrence of the trouble condition and its indication at the FACP is 200 seconds.
2.4 SYSTEM MONITORING
2.4.1 Valves
Each valve affecting the proper operation of a FM-200 system whether supplied under this contract or existing, shall be electrically monitored to ensure its proper position.
2.4.2 Independent Fire Detection System
Each new independent smoke detection subsystem, and releasing system (e.g.
FM-200) shall be monitored both for the presence of an alarm condition and for a trouble condition. Provide each monitored condition with a separate address.
2.5 MASS NOTIFICATION SYSTEM FUNCTIONS
2.5.1 Notification Appliance Network
The existing audible notification appliance network consists of speakers located to provide intelligible instructions at all locations in the building. The Mass Notification System announcements shall take priority over all other audible announcements of the system including the output of the fire alarm system in a normal or alarm state. When a mass notification announcement is activated during a fire alarm, all fire alarm system functions shall continue in an alarm state except for the output signals of the fire alarm audible and visual notification appliances.
SECTION 28 31 76 Page 10
2.5.2 Strobes
Provide strobes to alert hearing-impaired occupants.
2.5.3 Text Displays
LED text displays (textural visible appliances) for hearing impaired occupants. The textual displays shall be programmable and shall display the same content of the voice message being played. The signs shall be able to provide a minimum of 4 inch high letters and be located in high traffic areas easily seen by building occupants. The system shall interface with the Programmable sign controller to activate the proper message.
2.5.4 Voice Notification
An existing autonomous voice notification control unit is used to monitor and control the notification appliance network and provide consoles for local operation. Using an existing console, personnel in the building can initiate delivery of pre-recorded voice messages, provide live voice messages and instructions, and initiate visual strobe and optional textual message notification appliances. The existing autonomous voice notification control unit will temporarily override audible fire alarm notification while delivering Mass Notification messages to ensure they are intelligible.
2.6 OVERVOLTAGE AND SURGE PROTECTION
2.6.1 Signaling Line Circuit Surge Protection
For systems having circuits located outdoors, communications equipment shall be protected against surges induced on any signaling line circuit and shall comply with the applicable requirements of IEEE C62.41.1 and IEEE C62.41.2. Cables and conductors, that serve as communications links, shall have surge protection circuits installed at each end that meet the following waveform(s):
a. A 10 microsecond by 1000 microsecond waveform with a peak voltage of 1500 volts and a peak current of 60 amperes.
b. An 8 microsecond by 20 microsecond waveform with a peak voltage of 1000 volts and a peak current of 500 amperes. Protection shall be provided at the equipment. Additional triple electrode gas surge protectors, rated for the application, shall be installed on each wireline circuit within 3 feet of the building cable entrance. Fuses shall not be used for surge protection.
2.6.2 Sensor Wiring Surge Protection
Digital and analog inputs and outputs shall be protected against surges induced by sensor wiring installed outdoors and as shown. The inputs and outputs shall be tested with the following waveforms:
a. A 10 by 1000 microsecond waveform with a peak voltage of 1500 volts and a peak current of 60 amperes.
b. An 8 by 20 microsecond waveform with a peak voltage of 1000 volts and a peak current of 500 amperes. Fuses shall not be used for surge protection.
SECTION 28 31 76 Page 11
2.7 ADDRESSABLE INTERFACE DEVICES
The initiating device being monitored shall be configured as a Class "A" initiating device circuits. The system shall be capable of defining any module as an alarm module and report alarm trouble, loss of polling, or as a supervisory module, and reporting supervisory short, supervisory open or loss of polling such as independent smoke detection systems, relays for output function actuation, etc. The module shall be UL or FM listed as compatible with the existing control panel. The monitor module shall provide address setting means compatible with the existing control panel's SLC supervision and store an internal identifying code. Monitor module shall contain an integral LED that flashes each time the monitor module is polled and is visible through the device cover plate. Pull stations with a monitor module in a common backbox are not required to have an LED.
2.8 ADDRESSABLE CONTROL MODULE
The control module shall be capable of operating as a relay (dry contact form C) for interfacing the existing control panel with other systems. The module shall be UL or FM listed as compatible with the control panel. The indicating device or the external load being controlled shall be configured as a Class "B" notification appliance circuits. The system shall be capable of supervising, audible, visual and dry contact circuits. The control module shall have both an input and output address. The supervision shall detect a short on the supervised circuit and shall prevent power from being applied to the circuit. The control module shall provide address setting means compatible with the existing control panel's SLC supervision and store an internal identifying code. The control module shall contain an integral LED that flashes each time the control module is polled and is visible through the device cover plate. Control Modules shall be located in environmental areas that reflect the conditions to which they were listed.
2.9 ISOLATION MODULES
Provide isolation modules to subdivide each signaling line circuit into groups of not more than 20 addressable devices between adjacent isolation modules.
2.10 SMOKE SENSORS
2.10.1 Photoelectric Smoke Sensors
Provide addressable photoelectric smoke sensors as follows:
a. Provide analog/addressable photoelectric smoke sensors utilizing the photoelectric light scattering principle for operation in accordance with UL 268. Smoke sensors shall be listed for use with the existing fire alarm control panel.
b. Provide self-restoring type sensors that do not require any readjustment after actuation at the existing FACP to restore them to normal operation. Sensors shall be UL listed as smoke-automatic fire sensors.
c. Components shall be rust and corrosion resistant. Vibration shall have no effect on the sensor's operation. Protect the detection chamber with a fine mesh metallic screen that prevents the entrance of insects
SECTION 28 31 76 Page 12 or airborne materials. The screen shall not inhibit the movement of smoke particles into the chamber.
d. Provide twist lock bases for the sensors. The sensors shall maintain contact with their bases without the use of springs. Provide companion mounting base with screw terminals for each conductor. Terminate field wiring on the screw terminals. The sensor shall have a visual indicator to show actuation.
e. The sensor address shall identify the particular unit, its location within the system, and its sensitivity setting. Sensors shall be of the low voltage type rated for use on a 24 VDC system.
f. An operator at the existing control panel, having a proper access level, shall have the capability to manually access the following information for each initiating device.
(1) Primary status
(2) Device type
(3) Present average value
(4) Present sensitivity selected
(5) Sensor range (normal, dirty, etc.)
2.10.2 Duct Smoke Sensors
Duct-mounted photoelectric smoke detectors shall be furnished and installed where indicated and in accordance with NFPA 90A. Units shall consist of a smoke detector as specified in paragraph Photoelectric Detectors, mounted in a special housing fitted with duct sampling tubes, and mounted in a weather-proof metal housing. Detector circuitry shall be mounted in a metallic enclosure exterior to the duct. (It is not permitted to cut the duct insulation to install the duct detector directly on the duct).
Detectors shall have a manual reset. Detectors shall be rated for air velocities that include air flows between 500 and 4000 fpm. Detectors shall be powered from the fire alarm panel.
a. Sampling tubes shall run the full width of the duct. The duct detector package shall conform to the requirements of NFPA 90A, UL 268A, and shall be UL listed for use in air-handling systems. The control functions, operation, reset, and bypass shall be controlled from the fire alarm control panel.
b. Lights to indicate the operation and alarm condition; and the test and reset buttons shall be visible and accessible with the unit installed and the cover in place. Remote indicators shall be provided where required by NFPA 72 and these shall be provided with test and reset switches.
c. Remote lamps and switches as well as the affected fan units shall be properly identified in etched plastic placards. Detectors shall provide for control of auxiliary contacts that provide control, interlock, and shutdown functions. Auxiliary contacts provide for this function shall be located within 3 feet of the controlled circuit or appliance. The detectors shall be supplied by the fire alarm system manufacturer to ensure complete system compatibility.
SECTION 28 31 76 Page 13
2.10.3 Air Sampling Smoke Detectors
Air sampling detectors (ASD) are very early warning smoke detection (VEWSD) devices used to detect what may be the beginning of a fire. The detector uses a series of perforated pipes in the protected area to continuously draw smoke into the sampling chamber. Once in the sampling chamber the air is sampled by mass scattering of light or laser particle counting to determine if there is possibly a fire in the protected area. These units shall be programmable in multiple levels to indicate detection of particles that are not normally present, to indicate the presence of particles that could be produced by a fire and to indicate the presence of particles of the proper size and quantity to indicate that a fire conditions exists.
a. Description: The system shall consist of a highly sensitive laser-based smoke detector, aspirator, and filter. The detection unit shall include a scanning valve mechanism to identify the sampling pipe carrying smoke. The system shall be modular, with each detector monitored by a display featuring LEDs and a sounder. The system shall be configured by a programmer that is either integral to the system, portable or PC based. The system shall allow programming of four smoke threshold alarm levels per pipe (sector), time delays, faults including airflow, detector, power, filter and network as well as an indication of the urgency of the fault, and seven configurable relay outputs for remote indication of alarm and fault conditions. The system shall consist of an air sampling pipe network to transport air to the detection system, supported by calculations from a computer-based design modeling tool. Equipment shall include intelligent remote displays and a high-level interface with the FACP.
b. Performance Requirements: The system shall be tested and approved to cover up to 5,000 square feet and shall be approved to provide very early smoke detection and provide four output levels corresponding to Alert, Action, Fire 1 and Fire 2 per pipe (sector). These levels shall be programmable and able to be set at sensitivities ranging from 0.0015
- 6 percent obscuration/ft. The system shall provide staged airflow faults.
c. Detector Assembly: The detector, filter, aspirator, and relay outputs shall be housed in a mounting box and shall be arranged in such a way that air is drawn from the fire risk and a sample passed through the dual stage filter and detector by the aspirator. The detection unit shall include a scanning valve mechanism to identify the sampling pipe carrying smoke. The valve mechanism shall be integrated into the detector, begin to sample each pipe individually upon detection of smoke, be used to identify the level of smoke in each pipe, be used to indicate in which pipe sector an alarm was first detected, operate upon manual activation of the scan button on the display, and be automatically tested daily to ensure uninterrupted protection. The system shall utilize the principle of sampling all sectors simultaneously. When a scan smoke level is reached, an automatic sequence shall be initiated to sample each sector individually. If an alarm threshold level is reached, a "First Alarm Sector" is indicated and signaled. The unit shall then continue its sequence monitoring until the smoke level signal reduces below the scan level. The detector shall have four independent field programmable smoke alarm thresholds per pipe (sector) and a programmable scan time delay. The detector shall incorporate facilities to transmit faults including detector, air flow, filter, system, zone, network, and power. The
SECTION 28 31 76 Page 14 detector shall have four in-line sample pipe inlets and must contain a flow sensor for each pipe inlet. The filter must be a two-stage disposable filter cartridge. The first stage shall be capable of filtering particles in excess of 20 microns from the air sample. The second stage shall be ultra-fine, removing more than 99 percent of containment particles of 0.3 microns or larger, to provide a clean air barrier around the detector's optics to prevent contamination and increase service life. The aspirator shall be a purpose-designed rotary vane air pump. The system shall be capable of allowing for multiple sampling pipe runs up to 200 feet in total (4 pipe runs per detector), with a transport time of 60 seconds maximum or as codes dictate. The assembly must contain relays for alarm and fault conditions. The relays shall be software programmable to the required functions. Remote relays shall be configured to replicate those on the detector. The assembly shall be able to be surface mounted to a wall or recessed in the wall cavity. The assembly shall have built-in event and smoke logging. The system shall store smoke levels, alarm conditions, operator actions, and faults. The date and time of each event shall be recorded. Each detector (zone) shall be capable of storing up to 18,000 events and shall not require the presence of a display in order to do so.
d. Display: A detector display module may be located within the detector. Each display shall provide a 20-segment bar graph display, four independent high intensity alarm indicators (Alert, Action, Fire 1, and Fire 2) corresponding to the four alarm thresholds of the indicated sector, alarm threshold indicators for Alert, Action, and Fire 1, LED indication that the First Alarm Sector is established, LED indication of which pipe(s) is carrying smoke, detector fault and airflow fault indicators, and LED indicators for each fault category.
A remotely mounted display shall be equipped with fault conditions.
e. Sampling Pipe: The sampling pipe shall be smooth bore and sized according to the transport calculations. The pipe material shall be suitable for the environment in which it is installed. All joints in the sampling pipe must be air tight and made by using solvent cement, except at entry to the detector. The pipe shall be identified as "Aspirating Smoke Detector Pipe" (or similar wording) along its entire length at regular intervals not exceeding the manufacturer's recommendation or that of local codes and standards. The far end of each trunk or branch pipe shall be fitted with an end cap and drilled with a hole appropriately sized to achieve the performance as specified and as calculated by the system design.
f. Air sampling detection system shall be powered from the FARP.
2.10.4 Smoke Sensor Testing
Smoke sensors shall be tested in accordance with NFPA 72 and manufacturer's recommended calibrated test method. Submit smoke sensor testing procedures for approval. In addition to the NFPA 72 requirements, smoke detector sensitivity shall be tested during the preliminary tests.
2.11 ASD VEWSD SECONDARY POWER SUPPLY
Provide for ASD VEWSD system operation in the event of primary power source failure. Transfer from normal to auxiliary (secondary) power or restoration from auxiliary to normal power shall be automatic and shall not cause transmission of a false alarm.
SECTION 28 31 76 Page 15
2.11.1 Batteries
Provide sealed, maintenance-free, sealed lead acid batteries as the source for emergency power to the ASD VEWSD system . Batteries shall contain suspended electrolyte. The battery system shall be maintained in a fully charged condition by means of a solid state battery charger. Provide an automatic transfer switch to transfer the load to the batteries in the event of the failure of primary power.
2.11.1.1 Capacity
Battery size shall be the greater of the following two capacities.
a. Sufficient capacity to operate the ASD VEWSD system under supervisory and trouble conditions, including audible trouble signal devices for 48 hours and audible and visual signal devices under alarm conditions for an additional 15 minutes.
2.11.1.2 Battery Power Calculations
a. Verify that battery capacity exceeds supervisory and alarm power requirements.
(1) Substantiate the battery calculations for alarm, alert, and supervisory power requirements. Include ampere-hour requirements for each system component and each component, and compliance with
UL 864.
(2) Provide complete battery calculations for both the alarm, alert, and supervisory power requirements. Submit ampere-hour requirements for each system component with the calculations.
(3) A voltage drop calculation to indicate that sufficient voltage is available for proper operation of the system and all components, at the minimum rated voltage of the system operating on batteries.
b. For battery calculations use the following assumptions: Assume a starting voltage of 24 VDC for starting the calculations to size the batteries. Calculate the required Amp-Hours for the specified standby time, and then calculate the required Amp-Hours for the specified alarm time. Calculate the nominal battery voltage after operation on batteries for the specified time period. Using this voltage perform a voltage drop calculation for circuit containing device and/or appliances remote from the power sources.
2.11.2 Battery Chargers
Provide a solid state, fully automatic, variable charging rate battery charger. The charger shall be capable of providing 120 percent of the connected system load and shall maintain the batteries at full charge. In the event the batteries are fully discharged (20.4 Volts dc), the charger shall recharge the batteries back to 95 percent of full charge within 48 hours after a single discharge cycle as described in paragraph CAPACITY above. Provide pilot light to indicate when batteries are manually placed on a high rate of charge as part of the unit assembly if a high rate switch is provided.
SECTION 28 31 76 Page 16
2.12 FIRE ALARM CONTROL UNIT AND MASS NOTIFICATION CONTROL UNIT (FMCP)
2.12.1 Remote LCD Text Display
An LCD text display shall be provided at locations as shown on the drawings. The size shall not exceed 16 inches length by 3 inches deep with a height necessary to meet the requirements of Chapter 24 of NFPA 72). The text display shall as a minimum meet the following requirements:
a. Two lines of information for high priority messaging.
b. Minimum of 20 characters per line (40 total) displayed.
c. Text shall be no less than height requirements in Table 24.4.2.20.14.5 of NFPA 72 and color/contrast requirements of 24.4.2.20 of NFPA 72.
d. 32K character memory.
e. Display shall be wall or ceiling mounted.
f. Mounting brackets for a convenient wall/cubicle mount.
g. During non-emergency periods, display date and time.
h. All programming shall be accomplished from the existing Mass Notification network. No user programming shall be required.
An LCD text display shall be provided at locations as shown on the drawings. The LCD text display shall spell out the words "EVACUATE" and "ANNOUNCEMENT" and the remainder of the emergency instructions. The design of LCD text display shall be such that it cannot be read when not illuminated.
2.13 AMPLIFIERS, PREAMPLIFIERS, TONE GENERATORS
Any amplifiers, preamplifiers, tone generators, digitalized voice generators, and other hardware necessary for a complete, operational, textual audible circuit conforming to NFPA 72 shall be housed in a remote FMCP, terminal cabinet, or in the FMCP. Submit data to indicate that the amplifiers have sufficient capacity to simultaneously drive all notification speakers at the maximum rating plus 50 percent spare capacity. Annotate data for each circuit on the drawings.
2.13.1 Operation
The system shall automatically operate and control all building speakers.
2.13.2 Construction
Amplifiers shall utilize computer grade solid state components and shall be provided with output protection devices sufficient to protect the amplifier against any transient up to 10 times the highest rated voltage in the system.
2.13.3 Inputs
Equip each system with separate inputs for the tone generator, digitalized voice driver and panel mounted microphone.
SECTION 28 31 76 Page 17
2.13.4 Protection Circuits
Each amplifier shall be constantly supervised for any condition that could render the amplifier inoperable at its maximum output. Failure of any component shall cause automatic transfer to a designated backup amplifier, illumination of a visual "amplifier trouble" indicator on the control panel, appropriate logging of the condition on the system printer, and other actions for trouble conditions as specified.
2.14 MANUAL STATIONS
Provide metal or plastic, semi-flush mounted, double action, addressable manual stations, that are not subject to operation by jarring or vibration. Stations shall be equipped with screw terminals for each conductor. Stations that require the replacement of any portion of the device after activation are not permitted (e.g. Glass rods). Stations shall be finished in fire-engine red with molded raised white lettering operating instructions of contrasting color. The use of a key or wrench shall be required to reset the station. Manual stations shall be mounted at 44 inches. Stations shall have a separate screw terminal for each conductor. Stations shall have a clear plastic safety cover that must be lifted to operate the manual station.
2.15 NOTIFICATION APPLIANCES
2.15.1 Fire Alarm/Mass Notification Speakers
Audible appliances shall conform to the applicable requirements of UL 464.
Appliances shall be connected into notification appliance circuits.
Surface mounted audible appliances shall be painted red. Recessed audible appliances shall be installed with a grill that is painted red.
a. Speakers shall conform to the applicable requirements of UL 1480.
Speakers shall have six different sound output levels and operate with audio line input levels of 70.7 VRMs and 25 VRMs, by means of selectable tap settings. Tap settings shall include taps of 1/8, 1/4, 1/2, 1, and 2 watts. Speakers shall incorporate a high efficiency speaker for maximum output at minimum power across a frequency range of 150 Hz to 10,000 Hz, and shall have a sealed back construction.
Speakers shall be capable of installation on standard 4-inch square electrical boxes. Where speakers and strobes are provided in the same location, they may be combined into a single wall or ceiling mounted unit. All inputs shall be polarized for compatibility with standard reverse polarity supervision of circuit wiring via the existing FACP.
b. Provide speaker mounting plates constructed of cold rolled steel having a minimum thickness of 16 gauge or molded high impact plastic and equipped with mounting holes and other openings as needed for a complete installation. Fabrication marks and holes shall be ground and finished to provide a smooth and neat appearance for each plate. Each plate shall be primed and painted.
c. Speakers shall utilize screw terminals for termination of all field wiring.
2.15.2 Visual Notification Appliances
Visual notification appliances shall conform to the applicable requirements of UL 1971 and conform to the Architectural Barriers Act (ABA). Colored
SECTION 28 31 76 Page 18 lens, such as amber, shall comply with UL 1638. The manufacturer shall have the color lens tested to the full UL 1971 polar plotting criteria, voltage drop, and temperature rise as stated in 1971. Fire Alarm Notification Appliances shall have clear high intensity optic lens, xenon flash tubes, and be marked "Fire" in red letters. Fire Alarm/Mass Notification Appliances shall have amber high intensity optic lens, xenon flash tubes, and output white light and be marked "ALERT" in red letters.
The light pattern shall be disbursed so that it is visible above and below the strobe and from a 90-degree angle on both sides of the strobe. Strobe flash rate shall be 1 flash per second and a minimum of 15 candela (actual output after derating for tinted lens) based on the UL 1971 test. Strobe shall be surface mounted. Where more than two appliances are located in the same room or corridor or field of view, provide synchronized operation. Devices shall use screw terminals for all field wiring.
2.16 WIRING
Provide wiring materials under this section as specified in Section 26 20 00 INTERIOR DISTRIBUTION SYSTEM with the additions and modifications specified herein. NFPA 70 accepted fire alarm cables that do not require the use of raceways except as modified herein are permitted.
2.16.1 Alarm Wiring
The SLC wiring shall be solid copper cable in accordance with the manufacturers requirements. Copper signaling line circuits and initiating device circuit field wiring shall be No. 14 AWG size twisted and shielded solid conductors at a minimum. Visual notification appliance circuit conductors, that contain audible alarm appliances, shall be solid copper No. 14 AWG size conductors at a minimum. Speaker circuits shall be copper No. 16 AWG size twisted and shielded conductors at a minimum. Wire size shall be sufficient to prevent voltage drop problems. Circuits operating at 24 VDC shall not operate at less than the UL listed voltages for the sensors and/or appliances. Power wiring, operating at 120 VAC minimum, shall be a minimum No. 12 AWG solid copper having similar insulation.
Acceptable power-limited cables are FPL, FPLR or FPLP as appropriate with red colored covering. Nonpower-limited cables shall comply with NFPA 70.
PART 3 EXECUTION
3.1 INSTALLATION OF FIRE ALARM INITIATING DEVICES AND NOTIFICATION
APPLIANCES
3.1.1 Manual Stations:
Locate manual stations as required by NFPA 72 and as indicated on drawings. Mount stations so that their operating handles are 4 feet above the finished floor. Mount stations so they are located no farther than 5 feet from the exit door they serve, measured horizontally.
3.1.2 Notification Appliance Devices
Locate notification appliance devices as required by NFPA 72. Mount assemblies on walls as required by NFPA 72 and to meet the intelligibility requirements. Ceiling mounted speakers shall conform to NFPA 72.
3.1.3 Smoke Sensors
Locate sensors as required by NFPA 72 and their listings on a 4 inch
SECTION 28 31 76 Page 19 mounting box. Locate smoke sensors on the ceiling. Install heat sensors not less than 4 inches from a side wall to the near edge. Smoke sensors are permitted to be on the wall no lower than 12 inches from the ceiling with no minimum distance from the ceiling. In raised floor spaces, install the smoke sensors to protect 225 square feet per sensor. Install smoke sensors no closer than 5 feet from air handling supply outlets.
3.2 SYSTEM FIELD WIRING
3.2.1 Wiring within Cabinets, Enclosures, and Boxes
Provide wiring installed in a neat and workmanlike manner and installed parallel with or at right angles to the sides and back of any box, enclosure, or cabinet. Conductors that are terminated, spliced, or otherwise interrupted in any enclosure, cabinet, mounting, or junction box shall be connected to screw-type terminal blocks. Mark each terminal in accordance with the wiring diagrams of the system. The use of wire nuts or similar devices is prohibited. Conform wiring to NFPA 70.
Indicate the following in the wiring diagrams.
a. Point-to-point wiring diagrams showing the points of connection and terminals used for electrical field connections in the system, including interconnections between the equipment or systems that are supervised or controlled by the system. Diagrams shall show connections from field devices to the existing FACP and remote fire alarm control units, initiating circuits, switches, relays and terminals.
b. Complete riser diagrams indicating the wiring sequence of devices and their connections to the control equipment. Include a color code schedule for the wiring. Include floor plans showing the locations of devices and equipment.
3.2.2 Terminal Cabinets
Provide a terminal cabinet and where indicated on the drawings. Terminal size shall be appropriate for the size of the wiring to be connected.
Conductor terminations shall be labeled and a drawing containing conductors, their labels, their circuits, and their interconnection shall be permanently mounted in the terminal cabinet. Minimum size is 8 inches by 8 inches. Only screw-type terminals are permitted.
3.2.3 Alarm Wiring
Voltages shall not be…