x x x x x x x x x x x x x x x x

21'

END OF BASE BID

MATCH LINE.

ROOF LINE

WALL LINE

186'±

6' OFF FENCE

74' OFF FENCE

16"Ø

PEDESTAL

M

I N

B

E L O

W

F I N

I S

H E

D

G

R A

D E

1" RADIUS

AS REQ'D FOR PROTECTION

FROM VEHICLES

16"Ø DRILLED CONCRETE PEDESTAL INSTALLED AS

SHOWN; HOLE TO BE BORED INTO NATIVE MATERIAL

& CONCRETE CAST AGAINST UNDISTURBED SOIL

BELOW ORIGINAL GROUND LINE

CONCRETE TO BE f'c = 3500 psi, 6% AIR, 4" SLUMP

3" CLEAR TYP. BETWEEN ALL

REBAR & LIMITS OF CONC

#3 TIES @ 12" o.c. TYPICAL

(6 Ea.) #5 VERTICAL BARS

EVENLY SPACED AS SHOWN

LIGHT POLE TO BE

CENTERED AS SHOWN

LIGHT POLE & BASE PLATE BY OTHERS -

ANCHOR BOLT LAYOUT & THREAD

PROJECTION PER POLE MANUFACTURER

ANCHOR BOLTS (VERIFY W/ LIGHT MFG.

PRIOR TO CONSTRUCTION)

ADJUSTABLE BRACKET DARK

BRONZE COLOR.(SEE DETAIL E-2/2

INSTALL 12' X 5" SQUARE

ALUMINUM LIGHT POLE .BRONZE

COLOR. (SEE DETAIL E-2/1

AREA LIGHT

& POLE PEDESTAL

NTS E-1/1

AC PAVER - SEE PLAN

TRAFFIC RATED VAULT

1" CONDUITS. WATER

TIGHT CONNECTION.

18" MIN

NEW AND EXISTING HMAC,

CONCRETE, & GRAVEL PAVING AREAS -

CDF 200 PSI @ 28 DAYS (SLURRY MIX)

-OR-

3/4"-0 CRUSHED AGGREGATE COMPACTED

TO 95% MAXIMUM DENSITY PER AASHTO T-99

SOIL AREAS -

3/4- BACKFILL COMPACTED TO 95% Max.

DENSITY PER AASHTO T-99

± 6" TYP

COMMON UTILITY

TRENCH SECTION

NTS

± 4" TYP (IF REQ'D)

SAND OR 3/4"-0

BEDDING (AS

REQ'D)

M

I N

C

O V

E R

UNDISTURBED

NATIVE

INSTALL LOCATOR TAPE

12" ABOVE UTILITY (TYP)

COORDINATE INSTALLATION OF BURIED

UTILITIES WITH APPLICABLE UTILITY

PROVIDER PRIOR TO CONSTRUCTION.

NEW CONDUIT1" PIPING

PER PLAN.

173rd CE Squadron.

Oregon Air National Guard.

221 Wagner St Suite 16.

Kingsley Field

Klamath Falls OR.

REPAIR FACILITY 404

PARKING LOT

E-1

NOTES

CONFIRM THE THAT

PARKING LOT LIGHT

SCHEDULED FOR DEMO

IS ON END OF CIRCUIT

FOR RAMP AREA LIGHT.

TERMINATE POWER

SUPPLYING (E) LIGHT.

DEMO (E) LIGHTS AND

POLE.

USE (E) PANEL.(N) 20

AMP 208 2 POLE

BREAKER. W/PHOTO

CELL AND LIGHTING

CONTROL RELAY.

AREA LIGHT CONDUITS

2 EACH 1" #8 WIRE. 1

CONDUIT WILL BE USED

AS A SPARE.CONNECT

TO EXISTING CONDUITS

MARKED AT FENCE LINE

DETAIL E-1/2

TRAFFIC RATED VAULT

24"X15"X12".

PARKING LOT AREA

LIGHT / POLES AND

PEDESTAL. DETAIL E1/1,

E2/1,E2/2.

(N) 1" CONDUIT. WIRE

PER MANUFACTURES

REQUIREMENTS. TO

SUPPLY POWER FOR

(N) 14' WIDE X 7' TALL

TILT-WAY GATE.

(CONTRACTOR TO

CONFIRM LOCATION SO

THAT GATE CLEARS

BUILDING OVERHANG)

DETAIL E1/2.

INSTALL (N) GROUND

LOOP. CONNECT

CONTROLS.

KJAQ132250

5/2/2016

1 1/2"=50'

NAME#X MM/DD