x x x x x x x x x x x x x x x x
21'
END OF BASE BID
MATCH LINE.
ROOF LINE
WALL LINE
186'±
6' OFF FENCE
74' OFF FENCE
16"Ø
PEDESTAL
M
I N
B
E L O
W
F I N
I S
H E
D
G
R A
D E
1" RADIUS
AS REQ'D FOR PROTECTION
FROM VEHICLES
16"Ø DRILLED CONCRETE PEDESTAL INSTALLED AS
SHOWN; HOLE TO BE BORED INTO NATIVE MATERIAL
& CONCRETE CAST AGAINST UNDISTURBED SOIL
BELOW ORIGINAL GROUND LINE
CONCRETE TO BE f'c = 3500 psi, 6% AIR, 4" SLUMP
3" CLEAR TYP. BETWEEN ALL
REBAR & LIMITS OF CONC
#3 TIES @ 12" o.c. TYPICAL
(6 Ea.) #5 VERTICAL BARS
EVENLY SPACED AS SHOWN
LIGHT POLE TO BE
CENTERED AS SHOWN
LIGHT POLE & BASE PLATE BY OTHERS -
ANCHOR BOLT LAYOUT & THREAD
PROJECTION PER POLE MANUFACTURER
ANCHOR BOLTS (VERIFY W/ LIGHT MFG.
PRIOR TO CONSTRUCTION)
ADJUSTABLE BRACKET DARK
BRONZE COLOR.(SEE DETAIL E-2/2
INSTALL 12' X 5" SQUARE
ALUMINUM LIGHT POLE .BRONZE
COLOR. (SEE DETAIL E-2/1
AREA LIGHT
& POLE PEDESTAL
NTS E-1/1
AC PAVER - SEE PLAN
TRAFFIC RATED VAULT
1" CONDUITS. WATER
TIGHT CONNECTION.
18" MIN
NEW AND EXISTING HMAC,
CONCRETE, & GRAVEL PAVING AREAS -
CDF 200 PSI @ 28 DAYS (SLURRY MIX)
-OR-
3/4"-0 CRUSHED AGGREGATE COMPACTED
TO 95% MAXIMUM DENSITY PER AASHTO T-99
SOIL AREAS -
3/4- BACKFILL COMPACTED TO 95% Max.
DENSITY PER AASHTO T-99
± 6" TYP
COMMON UTILITY
TRENCH SECTION
NTS
± 4" TYP (IF REQ'D)
SAND OR 3/4"-0
BEDDING (AS
REQ'D)
M
I N
C
O V
E R
UNDISTURBED
NATIVE
INSTALL LOCATOR TAPE
12" ABOVE UTILITY (TYP)
COORDINATE INSTALLATION OF BURIED
UTILITIES WITH APPLICABLE UTILITY
PROVIDER PRIOR TO CONSTRUCTION.
NEW CONDUIT1" PIPING
PER PLAN.
173rd CE Squadron.
Oregon Air National Guard.
221 Wagner St Suite 16.
Kingsley Field
Klamath Falls OR.
REPAIR FACILITY 404
PARKING LOT
E-1
NOTES
CONFIRM THE THAT
PARKING LOT LIGHT
SCHEDULED FOR DEMO
IS ON END OF CIRCUIT
FOR RAMP AREA LIGHT.
TERMINATE POWER
SUPPLYING (E) LIGHT.
DEMO (E) LIGHTS AND
POLE.
USE (E) PANEL.(N) 20
AMP 208 2 POLE
BREAKER. W/PHOTO
CELL AND LIGHTING
CONTROL RELAY.
AREA LIGHT CONDUITS
2 EACH 1" #8 WIRE. 1
CONDUIT WILL BE USED
AS A SPARE.CONNECT
TO EXISTING CONDUITS
MARKED AT FENCE LINE
DETAIL E-1/2
TRAFFIC RATED VAULT
24"X15"X12".
PARKING LOT AREA
LIGHT / POLES AND
PEDESTAL. DETAIL E1/1,
E2/1,E2/2.
(N) 1" CONDUIT. WIRE
PER MANUFACTURES
REQUIREMENTS. TO
SUPPLY POWER FOR
(N) 14' WIDE X 7' TALL
TILT-WAY GATE.
(CONTRACTOR TO
CONFIRM LOCATION SO
THAT GATE CLEARS
BUILDING OVERHANG)
DETAIL E1/2.
INSTALL (N) GROUND
LOOP. CONNECT
CONTROLS.
KJAQ132250