Electrical_Systems_Combined_Drawings.pdf
PDF 2 MB Posted
- Attached to
- Repair Electrical Transformers Federal contract opportunity
- Solicitation number
- W912JB19B5009
About this file
Electrical Systems Combined Drawings
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Out of scope JA II (003).pdf | ||
| W912JB19B5009_Amendment_0001a.pdf | ||
| Specifications_-_Project_Manual_-_4.pdf | ||
| Specifications_-_Project_Manual_-_2.pdf | ||
| Specifications_-_Project_Manual_-_1.pdf | ||
| W912JB19B5009_Repair_Electrical_Transformers.pdf | ||
| Specifications_-_Project_Manual_-_3.pdf | ||
| Selfridge_ANGB_Vetting_Access_Request_Form.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
List of Drawings
Selfridge Air National
Guard Base
SANG Design and Repair of
Electrical Systems: Buildings 36, South of 45, 860 and 1400
Harrison Township, Michigan
PROJECT NO. 2016-01842-000
ELECTRICAL
Rev 1
March 26, 2019
Construction Document
SANG PROJECT NO. VGLZ 162010
VOLUME 1
N O
R T
H -S
O U
T H
IN
S
T R
U M
E N
T R
U N
W A
Y N
O R
T H
-S O
U T
H
IN
S T
R U
M E
N T
R U
N W
A Y
TAXIWAY "A"
SHEET NO:
SHEET TITLE:
PROJECT NUMBER:
COPYRIGHT © 2016
DATE ISSUE
26913 NORTHWESTERN HWY
SUITE 200
SOUTHFIELD, MICHIGAN
48033 | USA
(T) 248 262 1500
WWW.HED.DESIGN
2016-01842-000
Selfridge Air
National Guard
Base
SANG Design and Repair of
Electrical Systems: Buildings 36, South of 45, 860 and 1400
Harrison Township, MI 48045
SANG Project No.: 162010
E-001
Electrical Symbols, General
Notes, Overall Site Plan &
Sheet Index
11-02-16 Preliminary (35%) Submittal
PROJECT GENERAL NOTES:
1. ALL WORK TO CONFORM TO THE REQUIREMENTS OF THE LOCAL, STATE CODES, AND GOVERNMENT BASE CODES AND
STANDARDS. COORDINATE WITH SPECIFICATIONS, DIVISION 1.
2. ALL NEW EQUIPMENT PROVIDED FOR THIS PROJECT SHALL BE IN ACCORDANCE WITH THE "BUY AMERICA ACT" REFER TO
DIVISION 1 SPECIFICATIONS FOR ADDITIONAL INFORMATION.
3. THE ELECTRICAL CONTRACTOR SHALL COORDINATE ALL EXCAVATION WITH GOVERNMENT UTILITIES GROUP AND OBTAIN
A "DIG" PERMIT PRIOR TO ANY EXCAVATION.
4. FOR WORK REQUIRED IN THE AIRFIELD THE CONTRACTOR SHALL PROVIDE A NON-DISTRUCTIVE FORM OF EXCAVATION
AND COORDINATE WITH THE BASE UTILITIES AND "DIG" PERMIT FOR LOCATIONS OF EXISTING UNDERGROUND UTILITIES
INCLUDING AIRFIELD DRAINAGE SYSTEM. PERFORM EXCAVATION AS REQUIRED TO AVOID DAMAGE TO UTILITIES AND
AIRFIELD DRAINAGE SYSTEM. WHERE THE DRAINAGE SYSTEM OR OTHER UTILITIES ARE DAMAGED THEY SHALL BE
REPAIRED TO ITS ORIGINAL CONDITION WITHOUT ADDITIONAL COST TO THE PROJECT, WHERE RE-WORK IS REQUIRED TO
ACCOMMODATE THE NEW INSTALLATION THE CONTRACTOR SHALL RE-ROUT AND RE-CONNECT WITH LIKE MATERIALS TO
MAINTAIN THE INTEGRITY OF THE SYSTEMS BEING RE-ROUTED.
5. WHERE REQUIRED THE E.C. SHALL PROVIDE ALL EQUIPMENT NECESSARY TO REMOVE [PUMP] WATER FROM EXISTING
MANHOLES AS REQUIRED TO COMPLETE THE WORK INDICATED ON THE DOCUMENTS AND IN THE SPECIFICATIONS.
COORDINATE WORK [MANHOLE PUMP /DRAIN, ETC.] WITH GOVERNMENT PRIOR TO THE START OF WORK.
6. WHERE REQUIRED THE CONTRACTOR SHALL PROVIDE TEMPORARY SUPPORT FOR EXISTING UTILITIES REQUIRED TO
REMAIN IN SERVICE THOUGHT THE PROJECT / SCOPE OF WORK TO ACCOMMODATE THE NEW UNDERGROUND
INSTALLATIONS. COORDINATE SUPPORT TYPE / METHOD WITH THE TYPE AND SIZE OF SERVICE AS REQUIRED.
7. THE OWNER'S NORMAL OPERATIONS WILL BE CONTINUED DURING CONSTRUCTION. THE CONSTRUCTION SHALL NOT
INTERFERE WITH THESE OPERATIONS IN ANY WAY WITHOUT THE OWNER'S CONSENT. ANY SHUTDOWNS REQUIRED
SHALL BE COORDINATED WITH THE OWNERS REPRESENTATIVE PRIOR TO THE INTERRUPTION OF THE SERVICE, AND
SHALL BE SUBMITTED IN WRITING MIN. TWO [2] WEEKS IN ADVANCE AND SHALL INCLUDING THE SERVICE BEING
INTERPRETED, AND THE EXPECTED DURATION OF THE OUTAGE. THE CONTRACTOR SHALL COMPLY WITH ALL OF THE
GOVERNMENTS REQUIREMENTS AT NO ADDITIONAL COST TO THE PROJECT.
8. IT SHALL BE THE CONTRACTORS RESPONSIBILITY TO VISIT THE SITE AND FAMILIARIZE HIMSELF/HERSELF WITH ALL
EXISTING CONDITIONS. THE CONTRACTOR SHALL TAKE ALL NECESSARY FIELD MEASUREMENTS AND OTHERWISE
VERIFY ALL DIMENSIONS AND EXISTING CONSTRUCTION CONDITIONS INDICATED AND/OR SHOWN ON THE DRAWINGS.
SHOULD ANY ERROR OR INCONSISTENCE EXIST, THE CONTRACTOR SHALL NOT PROCEED WITH THE WORK AFFECTED
THEREBY UNTIL REPORTING THE SAME TO THE GOVERNMENT AND THE OWNERS REPRESENTATIVE FOR CLARIFICATION
AND/OR CORRECTION. THE CONTRACTOR SHALL VERIFY THE EXISTENCE, LOCATION AND ELEVATION OF ALL
UNDERGROUND UTILITIES IN WORK AREAS PRIOR TO PROCEEDING WITH CONSTRUCTION. ALL DISCREPANCIES SHALL BE
DOCUMENTED AND FORWARDED TO GOVERNMENT AND OWNERS REPRESENTATIVE FOR ACTION.
9. ALL EXISTING CONSTRUCTION AND SURFACES WHICH ARE TO REMAIN BUT ARE AFFECTED BY THE WORK UNDER THIS
CONTRACT SHALL BE RESTORED AND REFINISHED TO MATCH THE CONSTRUCTION, FINISH AND ALIGNMENT OF THE
EXISTING ADJACENT CONSTRUCTION AND FINISHES.
10. THE LOCATIONS AND ELEVATIONS OF EXISTING UNDERGROUND UTILITIES WHERE INDICATED ON THE DRAWINGS ARE
ONLY APPROXIMATE. NO GUARANTEE IS EITHER EXPRESSED OR IMPLIED AS TO THE COMPLETENESS OR ACCURACY
THEREOF. THE CONTRACTOR SHALL BE EXCLUSIVELY RESPONSIBLE FOR DETERMINING THE EXACT UTILITY LOCATIONS
TYPE OF SERVICE (PRIMARY, COMMUNICATIONS, CCTV, STORM, ETC.) AND ELEVATIONS PRIOR TO THE START OF
CONSTRUCTION. NOTE NOT ALL UNDERGROUND UTILITIES ARE SHOWN.
11. IN LOCATIONS OF EXISTING UTILITIES THE CONTRACTOR SHALL HAND DIG OR UTILIZE A NON -DESTRUCTIVE FORM OF
EXCAVATION, TO UNCOVER, BACKFILL AND DETERMINE THE EXACT LOCATION OF THE UNDERGROUND UTILITIES. THE
CONTRACTOR IS RESPONSIBLE FOR ALL DAMAGES CAUSED TO ANY EXISTING UTILITIES DURING EXCAVATION, AND
SHALL RESTORE DAMAGED SERVICES AT NO ADDITIONAL COST TO THE OWNER.
12. SLOPE ALL UNDERGROUND CONDUITS AWAY FROM BUILDING PENETRATIONS TO MANHOLES / HANDHOLES.
13. ALL UNDERGROUND CONDUIT / DUCT BANKS MUST BE CONCRETE ENCASED UTILIZE RIGID METAL CONDUIT FOR ALL
HORIZONTAL RADIUS BENDS AND AT EQUIPMENT PAD CONDUIT STUB UP LOCATIONS [VERTICAL RISERS] PROVIDE
INSULATED GROUNDING BUSHINGS ON ALL EQUIPMENT CONDUIT STUB UPS. PROVIDE WITH #4/0 GRD. CONDUCTOR TO
ASSOCIATED EQUIPMENT GROUND BUS.
14. THE CONTRACTOR SHALL COORDINATE EXACT LOCATIONS OF OUTDOOR ENCLOSURES AND ASSOCIATED EQUIPMENT
PADS.
15. RELEVANT DIMENSIONS AND ELEVATIONS FOR EQUIPMENT INSTALLATIONS SHALL BE VERIFIED AGAINST
MANUFACTURERS CERTIFIED EQUIPMENT DRAWINGS
16. CONTRACTOR SHALL PROVIDE TEMPORARY POWER FOR EACH LOCATING AS INDICATED, OR WHERE REQUESTED BY
OWNERS' REPRESENTATIVE.
17. DO NOT SCALE DRAWINGS TO DETERMINE SIZES AND DIMENSIONS. USE FIGURED DIMENSIONS ONLY.
18. NEW WORK SHALL ALIGN WITH AND MATCH EXISTING WORK UNLESS NOTED OTHERWISE.
19. COORDINATE IDENTIFICATION AND REMOVAL OF HAZARDOUS MATERIALS WITH THE GOVERNMENT.
PROJECT DEMOLITION NOTES:
1. THE OWNER'S NORMAL OPERATIONS WILL BE CONTINUED DURING DEMOLITION. DEMOLITION
CONTRACTOR SHALL NOT INTERFERE WITH THESE OPERATIONS IN ANY WAY WITHOUT THE
OWNER'S CONSENT.
2. PROVIDE TEMPORARY BARRICADES AND OTHER FORMS OF PROTECTION TO PROTECT OWNER'S
PERSONNEL, AND GENERAL PUBLIC FROM INJURY DUE TO SELECTIVE DEMOLITION AND NEW
WORK INSTALLATION.
3. PROTECT FROM DAMAGE EXISTING FINISH WORK THAT IS TO REMAIN IN PLACE AND BECOME
EXPOSED DURING DEMOLITION OPERATIONS.
4. PRIOR TO CUTTING / EXCAVATION OF EXISTING CONSTRUCTION, LOCATE AND IDENTIFY SERVICES
TO REMAIN IN OPERATION, UNDOCUMENTED CONDITIONS, UTILITIES, ETC. THAT MUST REMAIN IN
OPERATION DURING THE DEMOLITION WORK.
5. MAINTAIN EXISTING UTILITIES INDICATED TO REMAIN IN SERVICE AND PROTECT THEM AGAINST
DAMAGE DURING DEMOLITION OPERATIONS. DO NOT INTERRUPT UTILITIES SERVING OCCUPIED
OR IN-USE FACILITIES, EXCEPT WHEN AUTHORIZED IN WRITING BY THE OWNER.
6. PROVIDE SHORING, BRACING AND ANY OTHER MEANS REQUIRED TO PROTECT AND MAINTAIN THE
SAFETY, INTEGRITY AND STABILITY OF ALL EXISTING AND NEW CONSTRUCTION.
7. DEMOLITION OF ANY EXISTING CONSTRUCTION SHALL INCLUDE WHAT IS NECESSARY AND
REQUIRED TO ACCOMMODATE THE REQUIREMENTS OF NEW CONSTRUCTION. REFER TO THE
APPROPRIATE DRAWINGS AS TO THE EXTENT OF EXISTING CONSTRUCTION TO REMAIN.
8. ALL DEMOLITION SHALL COMPLY WITH APPLICABLE LOCAL CODES AND STATE CODES,
ORDINANCES AND GOVERNMENT REQUIREMENTS.
9. THE E.C. SHALL COORDINATE REMOVAL AND DISPOSAL OF EXISTING LIQUID FILLED
TRANSFORMERS WITH THE GOVERNMENT'S REPRESENTATIVE. EXISTING TRANSFORMERS SHALL
BE DISCONNECTED REMOVED AND DISPOSED BY THE CONTRACTOR EXCEPT WHERE NOTED ON
THE DRAWINGS.
10. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
SOUTH OF 45
BLDG. 45
EP-104
N.T.S.
OVERALL SITE PLAN
N
SHEET INDEX
SHEET
NUMBER
DESCRIPTION
E-001
ELECTRICAL SYMBOLS, GENERAL NOTES, OVERALL SITE PLAN & SHEET INDEX
EP-101
HANGER 36 DEMOLITION, NEW WORK PLANS AND ONE-LINE DIAGRAMS
EP-102
BUILDING 860 DEMOLITION, NEW WORK PLANS AND ONE-LINE DIAGRAMS
EP-103
BUILDING 1400 DEMOLITION, NEW WORK PLANS AND ONE-LINE DIAGRAMS
EP-104
SWITCHYARD SOUTH OF 45 DEMOLITION, NEW WORK PLANS AND ONE-LINE DIAGRAMS
EP-105
BORDER PATROL DEMOLITION, NEW WORK PLANS AND ONE-LINE DIAGRAMS
BLDG. 1400
EP-103
BLDG. 860
EP-102
BLDG. 36
EP-101
BORDER PATROL
EP-105
12-28-16 Preliminary (65%) Submittal
02-22-17 Pre-Final (95%) Submittal
04-28-17 Final (100%) Submittal
03-26-19 Rev 1
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text
EASEMENT
AutoCAD SHX Text
EASEMENT
AutoCAD SHX Text E
AutoCAD SHX Text
EASEMENT
AutoCAD SHX Text
AutoCAD SHX Text
RANGE
AutoCAD SHX Text
DRIVING
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
PAPI
AutoCAD SHX Text
LOCALIZER
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text w
AutoCAD SHX Text w
AutoCAD SHX Text
SOUTH PERIMETER RD
AutoCAD SHX Text
IRWIN ROAD
AutoCAD SHX Text
IRWIN ROAD
AutoCAD SHX Text
NORTH RIVER ROAD
AutoCAD SHX Text
SOUTH PERIMETER RD
AutoCAD SHX Text
SCHOOLHOUSE RD
AutoCAD SHX Text
E. JOY BLVD
AutoCAD SHX Text
BUNKER RD
AutoCAD SHX Text
NORTH PERIMETER ROAD
AutoCAD SHX Text
SUGARBUSH RD
AutoCAD SHX Text
SCHILLING ST.
AutoCAD SHX Text
DOOLITTLE DR
AutoCAD SHX Text
MULBERRY ST.
AutoCAD SHX Text
AMMO RD
AutoCAD SHX Text
NORTH PERIMETER ROAD
AutoCAD SHX Text
ANDERSEN
AutoCAD SHX Text
ELLSWORTH ST.
AutoCAD SHX Text
ALTUS ST.
AutoCAD SHX Text
CARSWELL ST.
AutoCAD SHX Text
CASTLE AVE.
AutoCAD SHX Text
PLATTSBURG ST.
AutoCAD SHX Text
CASTLE AVE
AutoCAD SHX Text
WEST
AutoCAD SHX Text
RAMP
AutoCAD SHX Text
STABLES RD.
AutoCAD SHX Text
TO AND FROM
AutoCAD SHX Text
I-94 & GRATIOT
AutoCAD SHX Text
ROSSO HWY
AutoCAD SHX Text
ROSSO HWY
AutoCAD SHX Text
FALCON DR.
AutoCAD SHX Text
DOOLITTLE DR
AutoCAD SHX Text
DOOLITTLE DR.
AutoCAD SHX Text
NIKE ROAD
AutoCAD SHX Text
ANCHOR BAY / LAKE ST CLAIR
AutoCAD SHX Text
EAST RAMP
AutoCAD SHX Text
WOOTEN ST
AutoCAD SHX Text
ROULOTT
AutoCAD SHX Text
MITCHELL ST
AutoCAD SHX Text
SELFRIDGE AVE
AutoCAD SHX Text
ASH ST
AutoCAD SHX Text
WILLOW ST
AutoCAD SHX Text
RAILROAD AVE
AutoCAD SHX Text
MAPLE ST
AutoCAD SHX Text
OAK ST
AutoCAD SHX Text
SUPPLY ST
AutoCAD SHX Text
GEORGE AVE
AutoCAD SHX Text
WAKE ST
AutoCAD SHX Text
BIRCH ST
AutoCAD SHX Text
WAGNER ST
AutoCAD SHX Text
MITCHELL ST.
AutoCAD SHX Text
GEORGE AVE
AutoCAD SHX Text
WILBUR WRIGHT BLVD
AutoCAD SHX Text
SUPERIOR ST.
AutoCAD SHX Text
STRAUBLE
AutoCAD SHX Text
GEN. ANDREWS DR.
AutoCAD SHX Text
HURON ST.
AutoCAD SHX Text
GEORGE AVE.
AutoCAD SHX Text
SKEEL
AutoCAD SHX Text
BOYLE
AutoCAD SHX Text
SKEEL
AutoCAD SHX Text
WOLD AVE.
AutoCAD SHX Text
BOYLE
AutoCAD SHX Text
LAKE ST
AutoCAD SHX Text
HURON ST.
AutoCAD SHX Text
LAKE ST.
AutoCAD SHX Text
LUFBERRY ST
AutoCAD SHX Text
KEITH AVE
AutoCAD SHX Text
KELLY
AutoCAD SHX Text
TAXIWAY 'A'
AutoCAD SHX Text NORTH-SOUTH INSTRUMENT RUNWAY 9000'x150' N 1%%D 29' 10" E
AutoCAD SHX Text
CLINTON
AutoCAD SHX Text
RIVER
AutoCAD SHX Text
PAPI
AutoCAD SHX Text
TAXIWAY 'D'
AutoCAD SHX Text
TAXIWAY 'C'
AutoCAD SHX Text
TAXIWAY 'C'
AutoCAD SHX Text
TAXIWAY 'B'
AutoCAD SHX Text
TAXIWAY 'B'
AutoCAD SHX Text
TAXIWAY 'H'
AutoCAD SHX Text
TAXIWAY 'C'
AutoCAD SHX Text
TAXIWAY 'J'
AutoCAD SHX Text
CONTROL TOWER
AutoCAD SHX Text
TAXIWAY 'G'
AutoCAD SHX Text
TAXIWAY 'M'
AutoCAD SHX Text
TAXIWAY 'L'
AutoCAD SHX Text
TAXIWAY 'B'
AutoCAD SHX Text
TAXIWAY 'K'
AutoCAD SHX Text
TAXIWAY 'A'
AutoCAD SHX Text W
AutoCAD SHX Text
TAXIWAY 'F'
AutoCAD SHX Text W
AutoCAD SHX Text W
AutoCAD SHX Text W
AutoCAD SHX Text W
AutoCAD SHX Text W
AutoCAD SHX Text W
AutoCAD SHX Text
SOUTH PERIMETER RD
AutoCAD SHX Text
CLINTON
AutoCAD SHX Text
RIVER
AutoCAD SHX Text
TAXIWAY 'A'
AutoCAD SHX Text W
AutoCAD SHX Text
FISH POND ROAD
AutoCAD SHX Text
JOHNSON ST.
AutoCAD SHX Text
JEFFERSON AVE.
AutoCAD SHX Text
RECREATION DR
AutoCAD SHX Text
MAIN GATE
AutoCAD SHX Text
WILLOW ST
AutoCAD SHX Text
AC
AutoCAD SHX Text
AC
AutoCAD SHX Text H.C.
AutoCAD SHX Text H.C.
AutoCAD SHX Text
16 SPACES @ 9'-0"
AutoCAD SHX Text
7 SPACES @ 9'-0", 2 H.C. @ 12'-0"
AutoCAD SHX Text
4 SPACES @ 9'-0"
AutoCAD SHX Text
N. PERIMETER RD
AutoCAD SHX Text
ASHAU VALLEY DR
AutoCAD SHX Text
PARTRIDGE CT
AutoCAD SHX Text
WURTSMITH
AutoCAD SHX Text
SPAATZ CT
AutoCAD SHX Text
WHITEHEAD CT
AutoCAD SHX Text
BRETT DR
AutoCAD SHX Text
BRIAN DR.
AutoCAD SHX Text
ARNOLD CIRCLE
AutoCAD SHX Text
ARNOLD CIRCLE
AutoCAD SHX Text
SPAATZ CT
AutoCAD SHX Text
COPYRIGHT 1999 - FIREHOUSE DESIGNS
AutoCAD SHX Text
JEFFERSON AVE
AutoCAD SHX Text
DOOLITTLE DR
AutoCAD SHX Text
SUPPLY ST
AutoCAD SHX Text
MITCHELL ST
AutoCAD SHX Text
LUKE AVE
AutoCAD SHX Text
GEORGE AVE
AutoCAD SHX Text
JP8
AutoCAD SHX Text
JP8
AutoCAD SHX Text
CB
AutoCAD SHX Text
CB
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CO
AutoCAD SHX Text
CB
AutoCAD SHX Text
CB
AutoCAD SHX Text
CB
AutoCAD SHX Text
CB
AutoCAD SHX Text
CB
AutoCAD SHX Text
CB
AutoCAD SHX Text
CB
AutoCAD SHX Text
CB
AutoCAD SHX Text
CB
AutoCAD SHX Text
CB
AutoCAD SHX Text
CB
AutoCAD SHX Text
CB
AutoCAD SHX Text
CB
AutoCAD SHX Text
CB
AutoCAD SHX Text
CB
AutoCAD SHX Text
CB
AutoCAD SHX Text
CB
AutoCAD SHX Text 2+00
AutoCAD SHX Text 4+00
AutoCAD SHX Text 6+00
AutoCAD SHX Text 2+00
AutoCAD SHX Text 4+00
AutoCAD SHX Text 6+00
AutoCAD SHX Text 8+00
AutoCAD SHX Text 10+00
AutoCAD SHX Text 8+00
AutoCAD SHX Text 6+00
AutoCAD SHX Text 4+00
AutoCAD SHX Text 2+00
AutoCAD SHX Text 10+00
208Y/120V
SEC.#1
208Y/120V
SEC.#2
208Y/120V
SEC.#3
480Y/277V
SEC.#1
480Y/277V
SEC.#2
480Y/277V
SEC.#3
FFFFFF
FFFFFF
F
F
208Y/120V
SEC.#1
208Y/120V
SEC.#2
208Y/120V
SEC.#3
480Y/277V
SEC.#1
480Y/277V
SEC.#2
480Y/277V
SEC.#3
FFFFFF
FFFFFF
F
F
MAIN
INCOMING
LUG
SECTION
AUX.
COMPARTMENT
[L.A.] / P/T'S
LOAD BREAK
SWITCH
BLDG. 36
52-36-1
LOAD BREAK
SWITCH
BLDG. 36
52-36-2
G
G
G G
G
G
G
G
G
G
G
G
G
G
G
G
GG
G
G
SHEET NO:
SHEET TITLE:
PROJECT NUMBER:
COPYRIGHT © 2016
DATE ISSUE
26913 NORTHWESTERN HWY
SUITE 200
SOUTHFIELD, MICHIGAN
48033 | USA
(T) 248 262 1500
WWW.HED.DESIGN
2016-01842-000
Selfridge Air
National Guard
Base
SANG Design and Repair of
Electrical Systems: Buildings 36, South of 45, 860 and 1400
Harrison Township, MI 48045
SANG Project No.: 162010
EP-101
Hanger 36 Demolition, New
Work Plans and One-Line
Diagrams
N.T.S.
HANGER 36 SITE PLAN
HANGER No.36
N
SCALE:
" = 1'-0"
HANGER 36 PRIMARY SERVICE - DEMOLITION
SCALE:
" = 1'-0"
HANGER 36 PRIMARY SERVICE NEW WORK
N.T.S
HANGER 36 DEMOLITION - ONE LINE DIAGRAM
ØA
TO EXIST. 4.8kV FUSED CUT OUT
ØB ØC
[3] @ 100kVA
4.8kV - 208Y/120V-3Ø, 4W
TO BE REMOVED
EXIST.
SECONDARY
CONDUCTORS
[ACTIVE]
EXIST.
SECONDARY
CONDUCTORS
[ABANDONED]
ØA
TO EXIST. 4.8kV FUSED CUT OUT
ØB ØC
[3] @ 100kVA
4.8kV - 480Y/277V-3Ø, 4W
TO BE REMOVED
EXIST. PAD MOUNTED
TRANSFORMER 4.8kV -
480Y/277V-3Ø, 4W - TO BE
DISCONNECTED FOR REMOVAL
BY OTHERS [SANG]
COORDINATE REMOVAL AFTER
DISCONNECTION WITH THE
OWNERS REPRESENTATIVE.
3Ø TO EXIST. 4.8kV
FUSED CUT OUT
Δ
Y
EXIST. SECONDARY
CONDUCTORS TO BLDG.
480Y/277V SERVICE
[ACTIVE]
N.T.S
HANGER 36 NEW WORK - ONE LINE DIAGRAM
NEW PAD MOUNTED TRANSFORMER HVT-36-1
AND ASSOCIATED EQUIPMENT PAD. REFER
TO TRANSFORMER PAD DETAIL THIS SHEET
EXISTING SECONDARY CONDUITS AND CONDUCTORS. LOCATE
TRANSFORMER SECONDARY TERMINATION SECTION OVER
EXISTING CONDUITS. FOR RE-CONENCTION TO EXISTING
SECONDARY CONDUCTORS.
EXISTING SECONDARY
CONDUITS TO BLDG. 36
NEW HVT-36-1 4.8kV PRIMARY FEEDER
NEW HVT-36-2 4.8kV PRIMARY FEEDER
EXISTING SECONDARY
CONDUITS TO BLDG. 36
2-4"C. IN CONCRETE ENCASED DUCT BANK [SEE DETAIL
THIS SHEET] TO EXISTING PRIMARY CONDUITS REVISED
CONDUIT ROUTE DURING DEMOLITION.
EXISTING BUILDING 36 TRANSFORMER YARD
EXISTING ELECTRICAL MANHOLE
EXISTING FENCE
NEW PAD MOUNTED TRANSFORMER HVT-36-2
AND ASSOCIATED EQUIPMENT PAD. REFER
TO TRANSFORMER PAD DETAIL THIS SHEET
EXISTING SECONDARY CONDUITS AND CONDUCTORS. LOCATE
TRANSFORMER SECONDARY TERMINATION SECTION OVER
EXISTING CONDUITS. FOR RE-CONENCTION TO EXISTING
SECONDARY CONDUCTORS.
BARE Cu. COUNTERPOISE GROUND
RING [TYP.]
"x10' Cu. GROUND ROD [TYP.]
NEW 15kV EQUIPMENT AND CONCRETE PAD
SEE EQUIPMENT PAD DETAIL THIS SHEET
6'-0" [MIN]
EXISTING SECONDARY
CONDUITS TO BLDG. 36
EXISTING SECONDARY
CONDUITS TO BLDG. 36
EXISTING FENCE AND ASSOCIATED
FOUNDATIONS TO BE REMOVED.
EXISTING SECONDARY [208Y/120V] CONDUITS [3] W\
WEATHER-HEADS. EXISTING CONDUITS AND CONDUCTORS TO
BE RE-WORKED TO ACCOMMODATE THE NEW INSTALLATION.
EXISTING CONCRETE PAD TO BE REMOVED
EXISTING UNI-STRUT / PIPE SUPPORT RACK TO BE
REMOVED COMPLETE [TYP.]
EXISTING 4.8kV PILC CABLE [CURRENTLY ABANDONED] TO BE
REMOVED COMPLETE BY THE CONTRACTOR. EC TO
COORDINATE EXISTING CABLE REMOVAL WITH SANG BASE
OPERATIONS AND RESTORE ALL DISTURBED SURFACES TO
MATCH THEIR EXISTING CONDITION.
EXISTING SINGLE PHASE POLE TYPE TRANSFORMER ON CONCRETE
PAD TO BE REMOVED [TYP. FOR SIX].
EXISTING ABANDONED "POTHEAD" TO BE DISCONNECTED AND REMOVED
EXISTING FUSED CUT-OUT SWITCHES ON UNI-STRUT / PIPE
SUPPORT RACKS TO BE REMOVED COMPLETE [TYP.]
EXISTING DISC. TO BE
REMOVED COMPLETE
EXISTING DISC. TO BE
REMOVED COMPLETE
EXISTING PAD MOUNTED
TRANSFORMER [480Y/277V]
TO BE DISCONNECTED FOR
REMOVAL BY OTHERS.
EXISTING SECONDARY [480Y/277V] CONDUITS [2] W\
WEATHER-HEADS. EXISTING CONDUITS AND CONDUCTORS TO
BE RE-WORKED TO ACCOMMODATE THE NEW INSTALLATION.
EXISTING 4.8kV PRIMARY CONDUCTORS TO BE
REMOVED TO ADJACENT MANHOLE.
4.8kV PRIMARY CONDUIT STUBS [2].
50E 50E
LA
PT
RP
HVT-36-1; 300kVA
4.8/13.2kV- 208Y/120V-3Ø, 4W
OUTDOOR LIQUID FILLED
Δ
4"C. W \3-1/C-15kV-#2AWG-Cu.W\ Cu. TAPE SHIELD AND 133%
EPR INSULATION & 1#4 600V GRD. W\GREEN INSULATION
4"C. W\3-1/C-15kV-#2AWG-Cu.W\ Cu. TAPE SHIELD AND 133%
EPR INSULATION & 1#4 600V GRD. W\GREEN INSULATION
Y
HVT-36-2; 300kVA
4.8/13.2kV- 480Y/277V-3Ø, 4W
OUTDOOR LIQUID FILLED
Δ
Y
NEW OUTDOOR W.P. METAL ENCLOSED
SWITCHGEAR LINEUP [15kV SW.GEAR BLDG. 36]
15kV-600A-40kA
K
K
K
K kA
600AS
[52-36]
[2]-4"C, [1-ACTICE; 1-SPARE] W/3-1/C-15kV-
AWG Cu. W/ Cu. TAPE
SHIELD AND 133% EPR INSULATION & 1#4 600VGRD. W/GREEN
INSULATION
PROVIDE PROVISIONS FOR FUTURE
BUS EXTENSION [TYP.]
[TYP.]
[TYP.]
[TYP.]
[TYP.]
[TYP.]
[TYP.]
EXIST.
CONDUIT AND
CONDUCTORS
KEY NOTES:
I.D. DESCRIPTION
PROVIDE NON DISCONNECT TYPE FUSE HOLDER FOR USE WITH
EXPULSION TYPE FUSES [SIZES AS INDICATED] REFER TO
SPECIFICATION SECTION 261300.02 FUSES.
PROVIDE OUTDOOR STRESS CONE ASSEMBLIES COMPLETE
FOR TERMINATIONS TO OUTDOOR SWITCHGEAR. REFER TO
SPECIFICATION SECTION 260513 TERMINATIONS.
PROVIDE KIRK KEY INTERLOCK BETWEEN THE SWITCH AND
THE FUSE COMPARTMENT. THE FUSE COMPARTMENT DOOR
SHALL REQUIRE THE SWITCH TO BE OPENED FOR THE KEY TO
BE RELEASED TO ALLOW ACCESS TO THE DE-ENERGIZED FUSE
COMPARTMENT.
PROVIDE SWITCHGEAR P.T. WITH 120/240V-1Ø SECONDARY
AND NEMA 12/3R RECEPTACLE PANEL FOR CONNECTION TO
SWITCHGEAR ACCESSORIES. REFER TO SECTION 261300.02
MEDIUM VOLTAGE METAL ENCLOSED SWITCHGEAR.
PROVIDE LIGHTNING / SURGE ARRESTORS. REFER TO SECTION
261300.02 MEDIUM VOLTAGE METAL ENCLOSED SWITCHGEAR.
PROVIDE TRANSFORMER PRIMARY CONNECTIONS WITH DEAD
FRONT LOAD-BREAK TYPE ELBOWS. REFER TO 261200 PAD
MOUNTED OIL FILLED TRANSFORMERS AND 260513
MEDIUM-VOLTAGE CABLE AND ACCESSORIES.
PROVIDE OUTDOOR PAD MOUNTED LIQUID FILLED [VEGETABLE
OIL] TRANSFORMER WITH A 4.8kV DUAL WOUND PRIMARY AND
SINGLE TAP 13.2kV PRIMARY [FUTURE PRIMARY SERVICE
VOLTAGE] WITH RATINGS AS INDICATED ON THE DRAWINGS.
REFER TO SPECIFICATION SECTION 261200 PAD MOUNTED OIL
FILLED TRANSFORMERS.
PROVIDE TRANSFORMER SECONDARY CONNECTIONS
UTILIZING STANDARD NEMA 2-HOLE TERMINATION PAD. REFER
TO 261200 PAD MOUNTED OIL FILLED TRANSFORMERS AND
260519 WIRES AND CABLES [600 VOLTS AND BELOW].
NEW 15kV OUTDOOR MEDIUM VOLTAGE METAL ENCLOSED
SWITCHGEAR REFER TO SPECIFICATION SECTION 261300.02
FOR ALL REQUIREMENTS ASSOCIATED WITH NEW
SWITCHGEAR LINE-UP'S.
1'-5"
5" 6" 5"
SCALE:
NEW ELECTRICAL
DUCT BANK DETAIL
N.T.S.
10"
#4 (2-PIECE) TIE
@48" O.C.
NON-METALLIC DUCT
SPACER 60" O.C.
CONCRETE ENCASEMENT
#4/0 GROUND CONDUCTOR
4" DUCT
#5 BAR (TYP. FOR 4)
PROVIDE UNDERGROUND DETECTABLE WARNING TAPE
(CONTINUOUS) 12" BELOW GRADE [MAX.]
NEW 15Kv FEEDER [4.8kV OPERATING VOLTAGE]
TO HANGER 36 ELECTRICAL EQUIPMENT
* PROVIDE NYLON PULL STRINGS IN ALL SPARE
CONDUITS
36" BELOW GRADE
42"
[MIN]
6"Ø CONCRETE
[TYP.]
6 1/2"
1 1/2"
1 1/2"
BARS
1'-6" 1'
3"
6"6"1'
3"
2"
2"
2"
1"
5'-2"
6'-2"
6"
1'-7"
2'-5"
4'-10"
PRI. SEC.
No.2 [TYP.]
@ 6" O.C.
No.2 BOTTOM
LAYER ONLY
SCALE:
TRANSFORMER PAD DETAIL
N.T.S.
NOTE: CONCRETE MIX 6 BAGS PER YARD, MINIMUM COMPRESSIVE
STRENGTH 3500PSI @ 28 DAYS.
COORDINATE CONDUIT WINDOWS [LOCATION AND SIZE] WITH
APPROVED EQUIPMENT MANUFACTURER SUBMITTALS.
SCALE: N.T.S.
EQUIPMENT PAD DETAIL
GRADE
6"
1" CHAMFER
ELECT. EQUIP.
4" [TYP.]
8"
48"
[MIN.]
10"
[TYP.]
2#4BARS CONTINUOUS
[TOP / MID / BOTTOM]
#4 BARS @ 12" O.C. EACH WAY
RIGID - PVC CONDUIT ADAPTER
[WHERE APPLICABLE]
1 1/2" MAX.
PROVIDE THREADED INSULATED
GROUNDING BUSHING ON RGS
CONDUIT STUB WITH #4/0GRD. TO
EQUIPMENT GROUND BUS.
PROVIDE NON-FROST SUSCEPTIBLE
COMPACTED FILL
GENERAL ELECTRICAL NOTES:
1. REFER TO SHEET E-001 PROJECT GENERAL NOTES AND PROJECT
SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
2. E.C. TO COORDINATE WITH OWNERS REPRESENTATIVE IF POWER IS
REQUIRED TO BE MAINTAINED THROUGHOUT DURATION OF THE OUTAGE. E.C.
TO PROVIDE TEMPORARY GENERATORS AS REQUIRED TO MEET THE OWNERS
REQUIREMENTS.
3. WHERE EXISTING EXTERIOR CABLES ARE INDICATED TO BE RE-USED IN NEW
WORK, THE E.C. SHALL PROTECT ALL CABLES FROM DAMAGE AND WEATHER
THOUGHT THE DURATION OF THE WORK.
4. PRIOR TO RE-TERMIANTION OF ANY EXISTING MEDIUM VOLTAGE CABLE
[<600V] THE CABLE SHALL BE ISOLATED AT EACH END AND TESTES PER THE
SPECIFICATIONS TO VERIFY CABLE INTEGRITY PRIOR TO RE-ENERGIZTAION.
TEST REPORTS SHALL BE SUBMITTED TO THE OWNER AND ENGINEER FOR
REVIEW.
5. PRIOR TO RE-TERMINATION OF ANY EXISTING LOW VOLTAGE CABLES [>600V]
THE CABLES SHALL BE ISOLATED AT EACH END AND TESTED PER THE
SPECIFICATIONS TO VERIFY CABLE INTEGRITY PRIOR TO RE-ENERGIZTAION.
TEST REPORTS SHALL BE SUBMITTED TO THE OWNER AND ENGINEER FOR
REVIEW.
6. WHERE NEW PAD MOUNTED TRANSFORMERS ARE INSTALLED THE E.C. SHALL
VERIFY EXISTING SYSTEM GROUNDING ARRANGEMENT [N-G CONNECTION AT
TRANSFORMER OR S.E. PANEL] WITH EXISTING EQUIPMENT AND REMOVE /
MAINTAIN SYSTEM BONDING JUMPER IN NEW PAD MOUNTED TRANSFORMER
SECONDARY TERMINATION SECTION AS REQUIRED.
600AS
[52-36-1]
600AS
[52-36-2]
36" MIN. TOP
OF CONDUIT
OR DUCT
BANK
11-02-16 Preliminary (35%) Submittal
R O
A D
W A
Y
R O
A D
W A
Y
NN
12-28-16 Preliminary (65%) Submittal
TO S&C PRIMARY SWITCH No.35 [LOCATED AT STREET CORNER] NOTE SHARED PRIMARY
FEEDER WITH BUILDING 39. E.C. TO COORDINATE WITH THE GOVERNMENT DURATION OF
PRIMARY SYSTEM OUTAGE AND PROVISIONS FOR TEMPORARY POWER FOR BUILDING #39 AS
REQUIRED. THE CONTRACTOR SHALL PROVIDE TEMPORARY POWER AS REQUIRED BY
GOVERNMENT. COORDINATE SHUTDOWNS, DURATIONS, ETC.
RGS CONDUIT
SWEEP [30" MIN.]
U/G PRIMARY TO
BLDG. 35
02-22-17 Pre-Final (95%) Submittal
04-28-17 Final (100%) Submittal
BARE Cu. GROUND FROM GROUND ROD THRU. 1" PVC
CONDUIT SLEEVE TO 15kV EQUIPMENT GROUND BUS
[TYP. FOR 3]
03-26-19 Rev 1
208Y/120V
SEC.#2
208Y/120V
SEC.#3
F F
F F
F
F
G
Y
V
S E
C
Y
V
S E
C
Y
V
S E
C
F F
F F
F
F
G
LOAD BREAK
SWITCH
BLDG. 860
52-860-2
MAIN
INCOMING
SECTION
AUX.
COMPARTMENT
[L.A.] / P/T'S
LOAD BREAK
SWITCH
BLDG. 860
52-860-1
F
G
G
G
G
G
G
G
G
G
SHEET NO:
SHEET TITLE:
PROJECT NUMBER:
COPYRIGHT © 2016
DATE ISSUE
26913 NORTHWESTERN HWY
SUITE 200
SOUTHFIELD, MICHIGAN
48033 | USA
(T) 248 262 1500
WWW.HED.DESIGN
2016-01842-000
Selfridge Air
National Guard
Base
SANG Design and Repair of
Electrical Systems: Buildings 36, South of 45, 860 and 1400
Harrison Township, MI 48045
SANG Project No.: 162010
EP-102
Building 860 Demolition, New
Work Plans and One-Line
Diagrams
N.T.S.
BLDG. 860 SITE PLAN
N
SCALE:
" = 1'-0"
BLDG. 860 PRIMARY SERVICE - DEMOLITION
SCALE:
" = 1'-0"
BLDG. 860 PRIMARY SERVICE NEW WORK
N.T.S
BLDG. 860 DEMOLITION - ONE LINE DIAGRAM
ØA ØB ØC
[3] @ 15kVA
4.8kV - 208Y/120V-3Ø, 4W
TO BE REMOVED
EXIST. SECONDARY CONDUCTORS
TO S.E. DISC. [INDOOR] VIA CONDUIT AND
WIRE-WAY TO BE REMOVED COMPLETE.
N.T.S
BLDG. 860 NEW WORK - ONE LINE DIAGRAM
TAXIWAY "A"
EXISTING BUILDING 860
EXISTING ELECT. MANHOLE
EXISTING BUILDING 860; 4.8kV PRIMARY
FEEDER TO BE REVISED / REWORKED REFER
TO DEMOLITION AND NEW WORK PLAN THIS
SHEET [TOTAL LENGTH APPROX. 250']
FROM 4.8Kv SITE SWITCHGEAR
4.8kV CIRCUIT TO NEXT STRUCTURE
EXIST. SINGLE PHASE PAD MOUNTED
AIR-SHOW TRANSFORMER
LOOP FEED FROM AIR-SHOW TRANSFORMER TO NEXT
AIR SHOW SINGLE PHASE TRANSFORMER
EXIST. 4.8kV AIR CRAFT LIGHTING
CABLE FROM EXIST. EXPOSED
FUSED CUTOUTS TO EXISTING
SINGLE PHASE PAD MOUNT AIR
SHOW LIGHTING TRANSFORMER
EXISTING 4.8kV PRIMARY FROM EXISTING MANHOLE TO BUILDING
860 OUTDOOR 4.8kV EQUIPMENT TO BE DISCONNECTED BACK TO
NEW HANDHOLE FOR EXTENSION TO NEW EQUIPMENT
EXISTING SPLICE TO 4.8kV CIRCUIT IN EXISTING
MANHOLE SEE PARTIAL SITE PLAN THIS SHEET
EXISTING CONDUCTOR TAP OF EXISTING 4.8kV
CIRCUIT FOR AIR SHOW TRANSFORMERS
xxE
600AS
[52-860-1]
NEW OUTDOOR W.P. METAL ENCLOSED
SWITCHGEAR LINEUP [15kV SW.GEAR BLDG. 860]
15kV-600A-40kA
K
K
10E
600AS
[52-860-2]
K
K
HVT-860; 45kVA
4.8/13.2kV- 208Y/120V-3Ø, 4W
OUTDOOR LIQUID FILLED
Δ
Y
4"C. W\ 3-1/C-15kV-#2AWG-Cu.W\ Cu. TAPE SHIELD AND 133%
EPR INSULATION & 1#4 600V GRD. W\GREEN INSULATION
2"C. - W\4#
&1#6GRD.
NEW 4#
&1#6GRD. IN EXIST. CONDUIT & WIREWAY TO
EXISTING S.E. DISCONNECT
EXTEND EXIST. CONDUIT TO ACCOMMODATE
NEW TRANSFORMER INSTALLATION.
LA
kA
PT
RP
PROVIDE PROVISIONS FOR FUTURE
BUS EXTENSION [TYP.]
3-1/C-15kV-#2AWG-Cu.W\ Cu. TAPE SHIELD AND 133% EPR
INSULATION & 1#4 600V GRD. W\GREEN INSULATION
EXIST. FROM ADJACENT MANHOLE
NEW HANDHOLE [HH-860-1]
600AS
[52-860]
[TYP.]
[TYP.]
[TYP.]
5 4
[TYP.]
[TYP.]
[TYP.]
EXISTING FUSED CUT-OUTS TO BE
REMOVED COMPLETE [TYP.]
PROVIDE MOGUL CONDUIT "LB" [2"RGS CONTRACTOR TO CONFIRM] ON
EXISTING CONDUIT STUB THRU EXTERIOR WALL FOR TRANSITION TO U/G
CONDUIT FOR NEW TRANSFORMER SECONDARY CONDUCTORS
2"C.[RGS] W\4#1/0 &1#6GRD. Cu. TO EXISTING BUILDING 860
S.E. DISC. SW. THRU EXISTING WIREWAY
EXIST. S.E. DISC. SW. ABOVE WIREWAY
EXISTING BLDG. 860 NEW PAD
MOUNTED TRANSFORMER HVT-860
NEW CONCRETE EQUIPMENT PAD
NEW OUTDOOR 15Kv
EQUIPMENT
NEW 4" RGS. CONDUIT FOR
HVT-860-1 PRIMARY
NEW 4" SCHED. 40 PVC
CONCRETE ENCASED 36" BELOW
GRADE. CONDUIT FOR AIR SHOW
4.8kV CIRCUIT [BY OTHERS]
PROVIDE 4"SCHED. 40 CONDUIT
STUB FOR USE BY OTHERS
NEW PRE-CAST CONCRETE HANDHOLE [HH-860-1]
E.C. TO SPLICE EXISTING CABLE TO NEW FOR
EXTENSION TO NEW OUTDOOR LINEUP.
HH-860-1 EXISTING BLDG. 860 4.8kV. FEEDER. E.C. TO
INTERCEPT EXISTING CABLES / CONDUIT AND
INTERCEPT FOR EXTENSION TO NEW OUTDOOR
EQUIPMENT.
PROVIDE NEW 2-CELL CONCRETE DUCT BANK FOR NEW
BLDG. 860 4.8kV FEEDER SEE DETAIL THIS SHEET.
EXIST. S.E. DISC. SW. ABOVE WIREWAY
EXIST. WIREWAY
EXISTING CONCRETE PAD TO BE REMOVED
EXISTING WIREWAY ON UNI-STRUT / PIPE SUPPORTS WITH
EXISTING SECONDARY CONDUCTORS TO BE REMOVED.
EXISTING SINGLE PHASE POLE TYPE TRANSFORMER ON CONCRETE
PAD TO BE REMOVED.
EXISTING FENCE AND ASSOCIATED FOUNDATIONS TO BE REMOVED.
EXISTING U/G 4.8kV FEEDER TO BE REMOVED / MODIFIED TO
ACCOMMODATE THE NEW INSTALLATION
EXISTING FUSED CUT-OUTS AND
ASSOCIATED UNI-STRUT / PIPE
SUPPORTS, CONDUCTORS, INSULATORS,
ETC. TO BE REMOVED COMPLETE.
EXISTING ABANDONED CONCRETE FOUNDATIONS
TO BE REMOVED COMPLETE [TYP. FOR 4]
EXISTING U/G 4.8kV FEEDER TO BE MODIFIED TO
ACCOMMODATE NEW WORK.
REMOVE EXISTING SECTION OF 4.8kV
FEEDER TO ACCOMMODATE NEW WORK.
EXISTING AIR-SHOW 4.8kV FEEDER AND CONDUIT STUB FROM EXIST.
FUSED CUT-OUT SWITCHES TO BE REMOVED. EXISTING U/G FEEDER TO
BE RE-WORKED TO ACCOMMODATE NEW EQUIPMENT INSTALLATION.
GRD. BAR IN HAND HOLE
"x10' Cu. GROUND ROD [TYP.]
BARE Cu. COUNTERPOISE GROUND RING
BARE Cu. GROUND FROM GROUND ROD THRU. 1" PVC CONDUIT
SLEEVE TO 15kV EQUIPMENT GROUND BUS [TYP. FOR 3]
BARE Cu. GROUND FROM GROUND
ROD THRU. 1" PVC CONDUIT SLEEVE TO
PAD MOUNTED TRANSFORMER GROUND
LUG. E.C. TO COORDINATION LOCATION
OF GROUND LUG WITH APPROVED
EQUIPMENT SUBMITTALS.
EXISTING EXPOSED CONDUIT FROM WIREWAY TO BUILDING
WIREWAY / S.E. DISCONNECT.
EXISTING BUILDING 860 EXISTING BUILDING 860
HANDHOLE DETAIL
SCALE:N.T.S.
PLAN VIEW
(W/OUT FRAME & COVER)
SECTION VIEW
6"
5'-0"
4'-0"
6"
6"
5'-0"
4'-0" 6"
3'-3"
5"
6"
3'-0"
6"
1'-0"
1'-3"2'-6" 1'-3"
EJIW #1580 HD FRAME &
36"Ø COVER WITH
"ELECTRICAL" LETTERING
"Ø THREADED,
EMBEDDED INSERTS
(TYP. 6 EACH WALL)
4'-0"
12"x3" DEEP SUMP DISH
WITH 4" DRAIN.
HOT DIPPED GALV. STEEL
"Ø ROLLED STEEL U-BOLT
PULLING IRON (TYP. 4)
30"x15" KNOCKOUT WINDOW (TYP. EACH WALL)
3/4"x10' COPPER GROUND
ROD (TYP.)
1'-5"
5" 6" 5"
SCALE:
NEW ELECTRICAL
DUCT BANK DETAIL
N.T.S.
10"
#4 (2-PIECE) TIE
@48" O.C.
NON-METALLIC DUCT
SPACER 60" O.C.
CONCRETE ENCASEMENT
#4/0 GROUND CONDUCTOR
4" DUCT
#5 BAR (TYP. FOR 4)
PROVIDE UNDERGROUND DETECTABLE WARNING TAPE
(CONTINUOUS) 12" BELOW GRADE
* PROVIDE NYLON PULL STRINGS IN ALL SPARE
CONDUITS
36" BELOW GRADE
BLDG. 36 ONE-LINE DIAGRAM KEY NOTES:
I.D. DESCRIPTION
PROVIDE NON DISCONNECT TYPE FUSE HOLDER FOR USE WITH EXPULSION TYPE
FUSES [SIZES AS INDICATED] REFER TO SPECIFICATION SECTION 261300.02 FUSES.
PROVIDE OUTDOOR STRESS CONE ASSEMBLIES COMPLETE FOR TERMINATIONS
TO OUTDOOR SWITCHGEAR. REFER TO SPECIFICATION SECTION 260513
TERMINATIONS.
PROVIDE KIRK KEY INTERLOCK BETWEEN THE SWITCH AND THE FUSE
COMPARTMENT. THE FUSE COMPARTMENT DOOR SHALL REQUIRE THE SWITCH TO
BE OPENED FOR THE KEY TO BE RELEASED TO ALLOW ACCESS TO THE
DE-ENERGIZED FUSE COMPARTMENT.
PROVIDE SWITCHGEAR P.T. WITH 120/240V-1Ø SECONDARY AND NEMA 12/3R
RECEPTACLE PANEL FOR CONNECTION TO SWITCHGEAR ACCESSORIES. REFER
TO SECTION 261300.02 MEDIUM VOLTAGE METAL ENCLOSED SWITCHGEAR.
PROVIDE LIGHTNING / SURGE ARRESTORS. REFER TO SECTION 261300.02 MEDIUM
VOLTAGE METAL ENCLOSED SWITCHGEAR.
PROVIDE TRANSFORMER PRIMARY CONNECTIONS WITH DEAD FRONT
LOAD-BREAK TYPE ELBOWS. REFER TO 261200 PAD MOUNTED OIL FILLED
TRANSFORMERS AND 260513 MEDIUM-VOLTAGE CABLE AND ACCESSORIES.
PROVIDE OUTDOOR PAD MOUNTED LIQUID FILLED [VEGETABLE OIL]
TRANSFORMER WITH A DUAL WOUND 4.8kV PRIMARY AND SINGLE TAP 13.2kV
PRIMARY [FUTURE PRIMARY SERVICE VOLTAGE] WITH RATINGS AS INDICATED ON
THE DRAWINGS. REFER TO SPECIFICATION SECTION 261200 PAD MOUNTED OIL
FILLED TRANSFORMERS.
PROVIDE TRANSFORMER SECONDARY CONNECTIONS UTILIZING STANDARD NEMA
2-HOLE TERMINATION PAD. REFER TO 261200 PAD MOUNTED OIL FILLED
TRANSFORMERS AND 260519 WIRES AND CABLES [600 VOLTS AND BELOW].
NEW 15kV OUTDOOR MEDIUM VOLTAGE METAL ENCLOSED SWITCHGEAR REFER
TO SPECIFICATION SECTION 261300.02 FOR ALL REQUIREMENTS ASSOCIATED
WITH NEW SWITCHGEAR LINE-UP'S.
PROVIDE SPLICE OF EXISTING TO NEW CONDUCTORS.
SCALE: N.T.S.
EQUIPMENT PAD DETAIL
GRADE
6"
1" CHAMFER
ELECT. EQUIP.
4" [TYP.]
8"
48"
[MIN.]
10"
[TYP.]
2#4BARS CONTINUOUS
[TOP / MID / BOTTOM]
#4 BARS @ 12" O.C. EACH WAY
RIGID - PVC CONDUIT ADAPTER
[WHERE APPLICABLE]
1 1/2" MAX.
PROVIDE THREADED INSULATED
GROUNDING BUSHING ON RGS
CONDUIT STUB WITH #4/0GRD. TO
EQUIPMENT GROUND BUS.
PROVIDE NON-FROST SUSCEPTIBLE
COMPACTED FILL
GENERAL ELECTRICAL NOTES:
1. REFER TO SHEET E-001 PROJECT GENERAL NOTES AND PROJECT
SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
2. E.C. TO COORDINATE WITH OWNERS REPRESENTATIVE IF POWER IS
REQUIRED TO BE MAINTAINED THROUGHOUT DURATION OF THE OUTAGE. E.C.
TO PROVIDE TEMPORARY GENERATORS AS REQUIRED TO MEET THE OWNERS
REQUIREMENTS.
3. WHERE EXISTING EXTERIOR CABLES ARE INDICATED TO BE RE-USED IN NEW
WORK, THE E.C. SHALL PROTECT ALL CABLES FROM DAMAGE AND WEATHER
THOUGHT THE DURATION OF THE WORK.
4. PRIOR TO RE-TERMINATION OF ANY EXISTING MEDIUM VOLTAGE CABLE
[<600V] THE CABLE SHALL BE ISOLATED AT EACH END AND TESTES PER THE
SPECIFICATIONS TO VERIFY CABLE INTEGRITY PRIOR TO RE-ENERGIZTAION.
TEST REPORTS SHALL BE SUBMITTED TO THE OWNER AND ENGINEER FOR
REVIEW.
5. PRIOR TO RE-TERMINATION OF ANY EXISTING LOW VOLTAGE CABLES [>600V]
THE CABLES SHALL BE ISOLATED AT EACH END AND TESTED PER THE
SPECIFICATIONS TO VERIFY CABLE INTEGRITY PRIOR TO RE-ENERGIZTAION.
TEST REPORTS SHALL BE SUBMITTED TO THE OWNER AND ENGINEER FOR
REVIEW.
6. WHERE NEW PAD MOUNTED TRANSFORMERS ARE INSTALLED THE E.C. SHALL
VERIFY EXISTING SYSTEM GROUNDING ARRANGEMENT [N-G CONNECTION AT
TRANSFORMER OR S.E. PANEL] WITH EXISTING EQUIPMENT AND REMOVE /
MAINTAIN SYSTEM BONDING JUMPER IN NEW PAD MOUNTED TRANSFORMER
SECONDARY TERMINATION SECTION.
36" MIN. TOP
OF CONDUIT
OR DUCT
BANK
11-02-16 Preliminary (35%) Submittal
NN
12-28-16 Preliminary (65%) Submittal
HATCHING INDICATES AREA OF EXCAVATION. CONTRACTOR TO
DETERMINE FINAL LIMITS OF EXCAVATION PRIOR TO START OF WORK.
CAUTION DURING EXCAVATION AND BACKFILL CONTRACTOR TO BE
AWARE OF AIRFIELD UNDERGROUND DRAINAGE SYSTEM, COORDINATE
ALL WORK WITH SELFRIDGE UTILITIES GROUP PRIOR TO EXCAVATION AND
PROVIDE SUPPORT WHERE REQUIRED FOR DRAINAGE SYSTEM THROUGH
INSTALLATION. WHERE REQUIRED PROVED RE-ROUTE OF DRAINAGE
SYSTEM PIPING WITH LIKE MATERIALS TO ACCOMMODATE THE NEW
INSTALLATION.
RGS CONDUIT
SWEEP [30" MIN.]
4"C. STUB & CAP
FUTURE
[PROVIDED BY OTHERS]
02-22-17 Pre-Final (95%) Submittal
NEW 15Kv FEEDER [4.8kV OPERATING VOLTAGE]
TO BUILDING 860 ELECTRICAL EQUIPMENT
04-28-17 Final (100%) Submittal
03-26-19 Rev 1
208Y/120V
SEC.#2
208Y/120V
SEC.#3
FF F
M
208Y/120V
SEC.#1
208Y/120V
SEC.#2
208Y/120V
SEC.#3
FF F
M
I N
C O
M I N
G
S E
C T
I O
N
M L O
C
P T
L A
S
L O
A D
B
R E
A K
S W
I T
C H
B L D
G
G
G
G
G
G G
M
SHEET NO:
SHEET TITLE:
PROJECT NUMBER:
COPYRIGHT © 2016
DATE ISSUE
26913 NORTHWESTERN HWY
SUITE 200
SOUTHFIELD, MICHIGAN
48033 | USA
(T) 248 262 1500
WWW.HED.DESIGN
2016-01842-000
Selfridge Air
National Guard
Base
SANG Design and Repair of
Electrical Systems: Buildings 36, South of 45, 860 and 1400
Harrison Township, MI 48045
SANG Project No.: 162010
EP-103
Building 1400 Demolition, New Work Plans and
One-Line Diagrams
N.T.S.
BLDG. 1400 SITE PLAN
BUILDING 1400
N
SCALE:
" = 1'-0"
BLDG. 1400 PRIMARY SERVICE - DEMOLITION
SCALE:
" = 1'-0"
BLDG. 1400 PRIMARY SERVICE NEW WORK
N.T.S
BLDG. 1400 DEMOLITION - ONE LINE DIAGRAM
ØA ØB ØC
[3] @ 25kVA
4.8kV - 208Y/120V-3Ø, 4W
TO BE REMOVED
EXIST.
SECONDARY
CONDUCTORS
[ACTIVE]
N.T.S
BLDG. 1400 NEW WORK - ONE LINE DIAGRAM
EXISTING BUILDING 1400 TRANSFORMER YARD
"x10' Cu. GROUND ROD [TYP.]
EXISTING FENCE AND ASSOCIATED
FOUNDATIONS TO BE REMOVED.
EXIST. ABANDONED 4.8kV PRIMARY
CONDUIT STUBS [2], REMOVE TO A
SUITABLE LOCATION BEYOND THE NEW
EQUIPMENT AND ABANDONED IN
PLACE.
KEY NOTES:
I.D. DESCRIPTION
PROVIDE NON DISCONNECT TYPE FUSE HOLDER FOR USE WITH EXPULSION TYPE
FUSES [SIZES AS INDICATED] REFER TO SPECIFICATION SECTION 261300.02 FUSES.
PROVIDE OUTDOOR STRESS CONE ASSEMBLIES COMPLETE FOR TERMINATIONS
TO OUTDOOR SWITCHGEAR. REFER TO SPECIFICATION SECTION 260513
TERMINATIONS.
PROVIDE KIRK KEY INTERLOCK BETWEEN THE SWITCH AND THE FUSE
COMPARTMENT. THE FUSE COMPARTMENT DOOR SHALL REQUIRE THE SWITCH
TO BE OPENED FOR THE KEY TO BE RELEASED TO ALLOW ACCESS TO THE
DE-ENERGIZED FUSE COMPARTMENT.
PROVIDE SWITCHGEAR P.T. WITH 120/240V-1Ø SECONDARY AND NEMA 12/3R
RECEPTACLE PANEL FOR CONNECTION TO SWITCHGEAR ACCESSORIES. REFER
TO SECTION 261300.02 MEDIUM VOLTAGE METAL ENCLOSED SWITCHGEAR.
PROVIDE LIGHTNING / SURGE ARRESTORS. REFER TO SECTION 261300.02 MEDIUM
VOLTAGE METAL ENCLOSED SWITCHGEAR.
PROVIDE TRANSFORMER PRIMARY CONNECTIONS WITH DEAD FRONT
LOAD-BREAK TYPE ELBOWS. REFER TO 261200 PAD MOUNTED OIL FILLED
TRANSFORMERS AND 260513 MEDIUM-VOLTAGE CABLE AND ACCESSORIES.
PROVIDE OUTDOOR PAD MOUNTED LIQUID FILLED [VEGETABLE OIL]
TRANSFORMER WITH A 4.8kV DUAL WOUND PRIMARY AND SINGLE TAP 13.2kV
PRIMARY [FUTURE PRIMARY SERVICE VOLTAGE] WITH RATINGS AS INDICATED ON
THE DRAWINGS. REFER TO SPECIFICATION SECTION 261200 PAD MOUNTED OIL
FILLED TRANSFORMERS.
PROVIDE TRANSFORMER SECONDARY CONNECTIONS UTILIZING STANDARD NEMA
2-HOLE TERMINATION PAD. REFER TO 261200 PAD MOUNTED OIL FILLED
TRANSFORMERS AND 260519 WIRES AND CABLES [600 VOLTS AND BELOW].
NEW 15kV OUTDOOR MEDIUM VOLTAGE METAL ENCLOSED SWITCHGEAR REFER
TO SPECIFICATION SECTION 261300.02 FOR ALL REQUIREMENTS ASSOCIATED
WITH NEW SWITCHGEAR LINE-UP'S.
REMOVE EXISTING STRESS CONES AND PROVIDE NEW STRESS CONE FOR NEW
SW. GEAR TERMINATION. SEE GENERAL NOTE #4.
EXISTING CONCRETE PAD TO
BE REMOVED
EXISTING SINGLE PHASE POLE TYPE TRANSFORMER ON
CONCRETE PAD TO BE REMOVED [TYP. FOR THREE].
EXISTING SECONDARY [208Y/120V] CONDUIT STUBS [2] W\
WEATHER-HEADS. EXISTING CONDUCTORS TO BE REMOVED
COMPLETE, REMOVE EXISTING CONDUIT ELBOWS TO BELOW GRADE
FOR EXTENSION TO NEW PAD MOUNTED TRANSFORMER SEE NEW
WORK PLAN THIS SHEET.
EXISTING S.E. PANELBOARD
EXISTING UTILITY METER ON UNI-STRUT SUPPORT WITH
EXPOSED C/T'S INSTALLED ON TRANSFORMER SECONDARY
CONDUCTORS. REMOVE METER. C/T'S AND ASSOCIATED
WIRING COMPLETE FOR RE-INSTALALTION ON NEW PAD
MOUNTED TRANSFORMER.
EXISTING UNI-STRUT / PIPE SUPPORT RACK TO BE
REMOVED COMPLETE [TYP.]
EXISTING FUSED CUT-OUT SWITCHES ON UNI-STRUT / PIPE
SUPPORT RACKS TO BE REMOVED COMPLETE [TYP.]
EXISTING 4.8kV PRIMARY FEEDER UNDERGROUND TO PVC CONDUIT STUB. DISCONNECT AND
REMOVE EXISTING PRIMARY TERMINATION. PROTECT EXISTING CABLE AND TERMINATION
AGAINST DAMAGE FOR RE-USE IN NEW WORK.
EXIST. 4.8kV PRIMARY FEEDER TO ADJACENT CABLE POLE FUSED CUT-OUT SWITCH
EXISTING S.E. PANELBOARD
EXIST. 4.8kV PRIMARY FEEDER TO ADJACENT CABLE POLE FUSED CUT-OUT SWITCH
NEW PAD MOUNTED TRANSFORMER
HVT-1400
BARE Cu. COUNTERPOISE GROUND
RING [TYP.]
2-4"C. CONCRETE ENCASED SECONDARY DUCT BANK [SEE
DETAIL THIS SHEET] EXTEND EXISTING CONDUITS AND
CONNECTED TO NEW DUCT BANK FOR NEW CABLE
INSTALLATION.
EXISTING CONDUITS FROM EXIST. BLDG. 1400 S.E. PANEL
CONNECT TO NEW CONDUITS FROM NEW PAD MOUNTED
TRANSFORMER.
NEW CONCRETE EQUIPMENT PAD FOR NEW
15kV EQUIPMENT AND PAD MOUNTED
TRANSFORMER.
BARE Cu. GRD. THRU 1" PVC SLEEVE TO TRANSFORMER GROUND PAD. COORDINATE
LOCATION OF GROUND PAD WITH APPROVED EQUIPMENT SUBMITTALS [TYP. FOR 2].
BUILDING 1400
BUILDING 1400
BARE Cu. GRD. THRU 1" PVC SLEEVE TO NEW
15kV SW. GEAR GROUND BAR [TYP. FOR 2].
4"C. FOR NEW HVT-1400 PRIMARY FEEDER
PROVIDE NEW 4" PVC SCHED. 40 CONDUIT CONCRETE ENCASED, EXTEND EXISTING
CONDUIT AND RE-INSTALL EXISTING 4.8kV FEEDER TO NEW 15Kv SW. GEAR
EXISTING FUSED CUT-OUTS ON
EXISTING CABLE POLE.
EXISTING 4.8kV PRIMARY FROM EXISTING CABLE POLE FUSED
CUT-OUTS, U/G TO BUILDING 1400 OUTDOOR 4.8kV EQUIPMENT.
DISCONNECT EXISTING FEEDER AND PROTECT AGAINST DAMAGE
FOR RE-TERMINATION TO NEW EQUIPMENT.
EXISTING O/H 4.8kV CIRCUIT
13E
600AS
[52-1400-1]
NEW OUTDOOR W.P. METAL ENCLOSED
SWITCHGEAR LINEUP [15kV SW.GEAR BLDG. 1400]
15kV-600A-40kA
K
K
HVT-1400; 75kVA
4.8/13.2kV- 208Y/120V-3Ø, 4W
OUTDOOR LIQUID FILLED
Δ
Y
4"C. W\3-1/C-15kV-#2AWG-Cu.W\ Cu. TAPE SHIELD AND 133% EPR
INSULATION & 1#4 600V GRD. W\GREEN INSULATION
W\4#4/0&1#4GRD.
[2] EXIST. 4"C. EXTEND TO NEW CONDUITS RE-USE ONE [1]
CONDUIT FOR NEW CONDUCTORS TO EXIST. PANEL. WITH ONE
SPARE.
EXTEND [2] EXIST. CONDUIT TO CONDUIT DUCT BANK FOR
INSTALLATION OF NEW SECONDARY CONDUCTORS.
EXIST. BLDG. 1400 ELECT. DISTRIBUTION [PANEL]
LA
kA
PT
RP
EXIST. 4.8kV PRIMARY CABLE
PROVIDE PROVISIONS FOR FUTURE
BUS EXTENSION [TYP.]
[TYP.]
[TYP.]
[TYP.]
[TYP.]
[TYP.]
[TYP.]
EXISTING FUSED CUT-OUTS ON EXISTING CABLE POLE.
EXISTING O/H 4.8kV CIRCUIT
NEW CONDUIT WITH EXIST. CABLE.
1'-5"
5" 6" 5"
SCALE:
NEW ELECTRICAL
DUCT BANK DETAIL
N.T.S.
10"
#4 (2-PIECE) TIE
@48" O.C.
NON-METALLIC DUCT
SPACER 60" O.C.
CONCRETE ENCASEMENT
4" DUCT
#5 BAR (TYP. FOR 4)
PROVIDE UNDERGROUND DETECTABLE
WARNING TAPE (CONTINUOUS) 12" BELOW
GRADE
NEW 208Y/120V FEEDER TO BLDG.
1400 EXIST. ELECT. PANEL
* PROVIDE NYLON PULL STRINGS IN ALL SPARE
CONDUITS
36" BELOW GRADE
EXISTING CABLE POLE W\ EXIST.
BUILDING 1400 CUT-OUT'S
EXIST. O/H 4.8kV CIRCUIT
GENERAL ELECTRICAL NOTES:
1. REFER TO SHEET E-001 PROJECT GENERAL NOTES AND PROJECT
SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
2. E.C. TO COORDINATE WITH OWNERS REPRESENTATIVE IF POWER IS
REQUIRED TO BE MAINTAINED THROUGHOUT DURATION OF THE OUTAGE. E.C.
TO PROVIDE TEMPORARY GENERATORS AS REQUIRED TO MEET THE OWNERS
REQUIREMENTS.
3. WHERE EXISTING EXTERIOR CABLES ARE INDICATED TO BE RE-USED IN NEW
WORK, THE E.C. SHALL PROTECT ALL CABLES FROM DAMAGE AND WEATHER
THOUGHT THE DURATION OF THE WORK.
4. PRIOR TO RE-TERMINATION OF ANY EXISTING MEDIUM VOLTAGE CABLE
[<600V] THE CABLE SHALL BE ISOLATED AT EACH END AND TESTES PER THE
SPECIFICATIONS TO VERIFY CABLE INTEGRITY PRIOR TO RE-ENERGIZTAION.
TEST REPORTS SHALL BE SUBMITTED TO THE OWNER AND ENGINEER FOR
REVIEW.
5. PRIOR TO RE-TERMINATION OF ANY EXISTING LOW VOLTAGE CABLES [>600V]
THE CABLES SHALL BE ISOLATED AT EACH END AND TESTED PER THE
SPECIFICATIONS TO VERIFY CABLE INTEGRITY PRIOR TO RE-ENERGIZTAION.
TEST REPORTS SHALL BE SUBMITTED TO THE OWNER AND ENGINEER FOR
REVIEW.
6. WHERE NEW PAD MOUNTED TRANSFORMERS ARE INSTALLED THE E.C. SHALL
VERIFY EXISTING SYSTEM GROUNDING ARRANGEMENT [N-G CONNECTION AT
TRANSFORMER OR S.E. PANEL] WITH EXISTING EQUIPMENT AND REMOVE /
MAINTAIN SYSTEM BONDING JUMPER IN NEW PAD MOUNTED TRANSFORMER
SECONDARY TERMINATION SECTION.
SCALE: N.T.S.
EQUIPMENT PAD DETAIL
GRADE
6"
1" CHAMFER
ELECT. EQUIP.
4" [TYP.]
8"
48"
[MIN.]
10"
[TYP.]
2#4BARS CONTINUOUS
[TOP / MID / BOTTOM]
#4 BARS @ 12" O.C. EACH WAY
RIGID - PVC CONDUIT ADAPTER
[WHERE APPLICABLE]
1 1/2" MAX.
PROVIDE THREADED INSULATED GROUNDING
BUSHING ON RGS CONDUIT STUB WITH
#4/0GRD. TO EQUIPMENT GROUND BUS.
PROVIDE NON-FROST SUSCEPTIBLE
COMPACTED FILL
RE-INSTALL EXISTING [SANG] METER ON THE EXTERIOR OF THE NEW PAD MOUNTED
TRANSFORMER SECONDARY TERMINATION SECTION. RE-INSTALL EXISTING C/T'S ON
NEW SECONDARY CONDUCTORS.
36" MIN. TOP
OF CONDUIT
OR DUCT
BANK
EXIST. BLDG. 1400 U/G ELECT. SERVICE
E.C. TO VERIFY EXACT ROUTING
11-02-16 Preliminary (35%) Submittal
N N
12-28-16 Preliminary (65%) Submittal
RGS CONDUIT
SWEEP [30" MIN.]
02-22-17 Pre-Final (95%) Submittal
04-28-17 Final (100%) Submittal
03-26-19 Rev 1
AutoCAD SHX Text
FF F
FF F
F
F
F
FF F
FF F
F
F
F
L O
B
E
A K
S W
I T
C H
S
W
Y A
S
G
G
I N
C O
M I N
G
S E
C T
I O
N
C P
T
L A
S
G R
D
D
E T
G
G
G G
SHEET NO:
SHEET TITLE:
PROJECT NUMBER:
COPYRIGHT © 2016
DATE ISSUE
26913 NORTHWESTERN HWY
SUITE 200
SOUTHFIELD, MICHIGAN
48033 | USA
(T) 248 262 1500
WWW.HED.DESIGN
2016-01842-000
Selfridge Air
National Guard
Base
SANG Design and Repair of
Electrical Systems: Buildings 36, South of 45, 860 and 1400
Harrison Township, MI 48045
SANG Project No.: 162010
EP-104
Switchyard South of Bldg. 45
West of Foxtrot Taxiway
Demolition, New Work Plans and One-Line Diagrams
N.T.S.
SWITCHYARD SITE PLAN
BUILDING 45/46
N
SCALE:
" = 1'-0"
SWITCHYARD - DEMOLITION
N.T.S
SWITCHYARD DEMOLITION - ONE LINE DIAGRAM
KEY NOTES:
I.D. DESCRIPTION
PROVIDE NON DISCONNECT TYPE FUSE HOLDER FOR USE WITH EXPULSION TYPE
FUSES [SIZES AS INDICATED] REFER TO SPECIFICATION SECTION 261300.02 FUSES.
PROVIDE OUTDOOR STRESS CONE ASSEMBLIES COMPLETE FOR TERMINATIONS
TO OUTDOOR SWITCHGEAR. REFER TO SPECIFICATION SECTION 260513
TERMINATIONS.
PROVIDE KIRK KEY INTERLOCK BETWEEN THE SWITCH AND THE FUSE
COMPARTMENT. THE FUSE COMPARTMENT DOOR SHALL REQUIRE THE SWITCH
TO BE OPENED FOR THE KEY TO BE RELEASED TO ALLOW ACCESS TO THE
DE-ENERGIZED FUSE COMPARTMENT.
PROVIDE SWITCHGEAR P.T. WITH 120/240V-1Ø SECONDARY AND NEMA 12/3R
RECEPTACLE PANEL FOR CONNECTION TO SWITCHGEAR ACCESSORIES. REFER
TO SECTION 261300.02 MEDIUM VOLTAGE METAL ENCLOSED SWITCHGEAR.
PROVIDE LIGHTNING / SURGE ARRESTORS. REFER TO SECTION 261300.02 MEDIUM
VOLTAGE METAL ENCLOSED SWITCHGEAR.
NEW 15kV OUTDOOR MEDIUM VOLTAGE METAL ENCLOSED SWITCHGEAR REFER
TO SPECIFICATION SECTION 261300.02 FOR ALL REQUIREMENTS ASSOCIATED
WITH NEW SWITCHGEAR LINE-UP'S.
REMOVE EXISTING STRESS CONES AND PROVIDE NEW STRESS CONE FOR NEW
SW. GEAR TERMINATION. SEE GENERAL NOTE #4.
EXISTING FENCE AND ASSOCIATED
FOUNDATIONS TO BE REMOVED.
EXISTING CONDUITS
[1-ACTIVE; 1-USED / ABANDONED]
EXISTING CONCRETE PAD TO BE
REMOVED
EXISTING UNI-STRUT / PIPE SUPPORT RACK WITH
FUSED CUT-OUT'S INSULATORS, ETC. TO BE
REMOVED COMPLETE
EXISTING UNI-STRUT / PIPE SUPPORT RACK WITH
FUSED CUT-OUT'S INSULATORS, ETC. TO BE
REMOVED COMPLETE
EXIST. CONDUIT STUB. FROM EAST
RAMP SITE LIGHTING TRANSFORMER /
HANGER 35 / SW-36 LOOP FEED
EXISTING 4.8kV CIRCUIT.
FROM EAST RAMP.
U/G 4.8kV CABLE TO STRUT MOUNTED FUSED
CUTOUTS. E.C. TO DISCONNECT EXIST STRESS
CONES AND PROTECT AGAINST DAMAGE FOR
RE-TERMINATION IN NEW WORK.
U/G EAST RAMP SITE LIGHTING
TRANSFORMER LOOP FEED FROM
BLDG. 35. SW-36.
EXIST. 4.8kV CABLE
EXIST. FENCED SWITCH
YARD S. OR 45 W. OF GOLF
EXIST. CONDUIT U/G
ALL EXISTING SWITCHYARD
EQUIPMENT TO BE REMOVED
COMPLETE
NEW HANDHOLE, E.C. TO RE-WORK EXISTING CONDUIT
TO NEW HANDHOLE FOR EXTENSION TO NEW 15kV
SWITCHGEAR. SEE HANDHOLE DETAIL THIS SHEET.
EXISTING 4.8kV CIRCUIT.
FROM EAST RAMP.
RE-WORK / REVISE EXIST. CONDUIT AND PLACE NEW
SW. GEAR INCOMING SECTION OVER EXISTING
CONDUIT. CONDUIT SHALL NOT EXCEED 3" ABOVE NEW
EQUIPMENT PAD.
"x10' Cu. GROUND ROD [TYP.]
BARE Cu. COUNTERPOISE GROUND
RING [TYP.]
BARE Cu. GRD. THRU 1" PVC SLEEVE TO
EQ. GROUND BUS [TYP. FOR 2]
NEW 4"C. FROM NEW HANDHOLE TO NEW
SWITCHGEAR LOAD BREAK SWITCH FOR
EXTENSION OF EXISTING 4.8kV CKT.
100E
600AS
[52-S45-1]
LA
3-1/C-15kV-#2AWG-Cu.W\ Cu. TAPE SHIELD AND 133%
INSULATION & 1#4 600V GRD. W\GREEN INSULATION
NEW OUTDOOR W.P. METAL ENCLOSED
SWITCHGEAR LINEUP [15kV SW.GEAR S. BLDG. 45]
15kV-600A-40kA
K
K kA
PT
RP
EXIST. FEEDER
NEW HANDHOLE [HH-S45-1]
EXIST. 4.8kV CIRCUIT FROM EAST RAMP
SITE LIGHTING TRANSFORMER.
600AS
[52-S45]
[TYP.]
[TYP.]
[TYP.]
5 4
HANDHOLE DETAIL
SCALE:N.T.S.
PLAN VIEW
(W/OUT FRAME & COVER)
SECTION VIEW
6"
5'-0"
4'-0"
6"
6"
5'-0"
4'-0" 6"
3'-3"
5"
6"
3'-0"
6"
1'-0"
1'-3"2'-6"1'-3"
EJIW #1580 HD FRAME &
36"Ø COVER WITH
"ELECTRICAL" LETTERING
"Ø THREADED,
EMBEDDED INSERTS
(TYP. 6 EACH WALL)
4'-0"
12"x3" DEEP SUMP DISH
WITH 4" DRAIN.
HOT DIPPED GALV. STEEL
"Ø ROLLED STEEL U-BOLT
PULLING IRON (TYP. 4)
30"x15" KNOCKOUT WINDOW (TYP. EACH WALL)
3/4"x10' COPPER GROUND
ROD (TYP.)
EXISTING SWITCH YARD
EAST
RAMP
T A
X I W
Y
G
G
O L F
SCALE: N.T.S.
EQUIPMENT PAD DETAIL
GRADE
6"
1" CHAMFER
ELECT. EQUIP.
4" [TYP.]
8"
48"
[MIN.]
10"
[TYP.]
2#4BARS CONTINUOUS
[TOP / MID / BOTTOM]
#4 BARS @ 12" O.C. EACH WAY
RIGID - PVC CONDUIT ADAPTER
[WHERE APPLICABLE]
1 1/2" MAX.
PROVIDE THREADED INSULATED GROUNDING
BUSHING ON RGS CONDUIT STUB WITH #4/0GRD.
TO EQUIPMENT GROUND BUS.
PROVIDE NON-FROST SUSCEPTIBLE
COMPACTED FILL
GENERAL ELECTRICAL NOTES:
1. REFER TO SHEET E-001 PROJECT GENERAL NOTES AND PROJECT
SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
2. E.C. TO COORDINATE WITH OWNERS REPRESENTATIVE IF POWER IS
REQUIRED TO BE MAINTAINED THROUGHOUT DURATION OF THE OUTAGE. E.C.
TO PROVIDE TEMPORARY GENERATORS AS REQUIRED TO MEET THE OWNERS
REQUIREMENTS.
3. WHERE EXISTING EXTERIOR CABLES ARE INDICATED TO BE RE-USED IN NEW
WORK, THE E.C. SHALL PROTECT ALL CABLES FROM DAMAGE AND WEATHER
THOUGHT THE DURATION OF THE WORK.
4. PRIOR TO RE-TERMINATION OF ANY EXISTING MEDIUM VOLTAGE CABLE
[<600V] THE CABLE SHALL BE ISOLATED AT EACH END AND TESTES PER THE
SPECIFICATIONS TO VERIFY CABLE INTEGRITY PRIOR TO RE-ENERGIZTAION.
TEST REPORTS SHALL BE SUBMITTED TO THE OWNER AND ENGINEER FOR
REVIEW.
5. PRIOR TO RE-TERMINATION OF ANY EXISTING LOW VOLTAGE CABLES [>600V]
THE CABLES SHALL BE ISOLATED AT EACH END AND TESTED PER THE
SPECIFICATIONS TO VERIFY CABLE INTEGRITY PRIOR TO RE-ENERGIZTAION.
TEST REPORTS SHALL BE SUBMITTED TO THE OWNER AND ENGINEER FOR
REVIEW.
6. WHERE NEW PAD MOUNTED TRANSFORMERS ARE INSTALLED THE E.C. SHALL
VERIFY EXISTING SYSTEM GROUNDING ARRANGEMENT [N-G CONNECTION AT
TRANSFORMER OR S.E. PANEL] WITH EXISTING EQUIPMENT AND REMOVE /
MAINTAIN SYSTEM BONDING JUMPER IN NEW PAD MOUNTED TRANSFORMER
SECONDARY TERMINATION SECTION.
7. THIS AREA TO BE FULLY CONTAINED FOR SOIL EROSION REFER TO VOLUME 2
REFERENCE DRAWINGS CG-001, C-001 & 002 FOR ADDITIONAL CRITERIA.
N.T.S
SWITCHYARD NEW WORK - ONE LINE DIAGRAM
SCALE:
" = 1'-0"
SWITCHYARD - NEW WORK
11-02-16 Preliminary (35%) Submittal
NN
APPROX.
300'
12-28-16 Preliminary (65%) Submittal
HATCHING INDICATES AREA OF EXCAVATION. CONTRACTOR TO
DETERMINE FINAL LIMITS OF EXCAVATION PRIOR TO START OF WORK.
CAUTION DURING EXCAVATION AND BACKFILL CONTRACTOR TO BE
AWARE OF AIRFIELD UNDERGROUND DRAINAGE SYSTEM, COORDINATE
ALL WORK WITH SELFRIDGE UTILITIES GROUP PRIOR TO EXCAVATION AND
PROVIDE SUPPORT WHERE REQUIRED FOR DRAINAGE SYSTEM THROUGH
INSTALLATION. WHERE REQUIRED PROVED RE-ROUTE OF DRAINAGE
SYSTEM PIPING WITH LIKE MATERIALS TO ACCOMMODATE THE NEW
INSTALLATION.
RGS CONDUIT
SWEEP [30" MIN.]
02-22-17 Pre-Final (95%) Submittal
04-28-17 Final (100%) Submittal
03-26-19 Rev 1
AutoCAD SHX Text
AutoCAD SHX Text
JP8
JP8
208Y/120V
SEC.#2
208Y/120V
SEC.#3
F
208Y/120V
SEC.#1
208Y/120V
SEC.#2
208Y/120V
SEC.#3
F
F
INCOMING
SECTION
MLO / CPT /
L.A.'S
LOAD BREAK
SWITCH
BLDG.
52-BP-1
G
G
G
G
G
G
2-4"C. SPARE
HVT-BP
G
SHEET NO:
SHEET TITLE:
PROJECT NUMBER:
COPYRIGHT © 2016
DATE ISSUE
26913 NORTHWESTERN HWY
SUITE 200
SOUTHFIELD, MICHIGAN
48033 | USA
(T) 248 262 1500
WWW.HED.DESIGN
2016-01842-000
Selfridge Air
National Guard
Base
SANG Design and Repair of
Electrical Systems: Buildings 36, South of 45, 860 and 1400
Harrison Township, MI 48045
SANG Project No.: 162010
EP-105
Border Patrol - Demolition, New Work Plans and
One-Line Diagrams
N.T.S.
BORDER PATROL - SITE PLAN
N
SCALE:
" = 1'-0"
BORDER PATROL - DEMOLITION
N.T.S
BORDER PATROL DEMOLITION - ONE LINE DIAGRAM
50E
600AS
[52-BP-1]
3-1/C-15kV-#2AWG-Cu.W\ Cu. TAPE SHIELD AND 133%
INSULATION & 1#4 600V GRD. W\GREEN INSULATION
NEW OUTDOOR W.P. METAL ENCLOSED SWITCHGEAR
LINEUP [15kV SW.GEAR - BORDER PATROL]
15kV-600A-40kA
K
K kA
RP
NEW 4.8kV CIRCUIT; 3-1/C-15kV-#2AWG-Cu.W\ Cu. TAPE
SHIELD AND 133% EPR INSULATION PROVIDE RIGID METAL
CONDUIT RISER AT EXISTING POLE.
[TYP.]
[TYP.]
[TYP.]
S
P
E
R
I M
E
T
E
GENERAL ELECTRICAL NOTES:
1. REFER TO SHEET E-001 PROJECT GENERAL NOTES AND PROJECT
SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
2. E.C. TO COORDINATE WITH OWNERS REPRESENTATIVE IF POWER IS
REQUIRED TO BE MAINTAINED THROUGHOUT DURATION OF THE OUTAGE. E.C.
TO PROVIDE TEMPORARY GENERATORS AS REQUIRED TO MEET THE OWNERS
REQUIREMENTS.
3. WHERE EXISTING EXTERIOR CABLES ARE INDICATED TO BE RE-USED IN NEW
WORK, THE E.C. SHALL PROTECT ALL CABLES FROM DAMAGE AND WEATHER
THOUGHT THE DURATION OF THE WORK.
4. PRIOR TO RE-TERMINATION OF ANY EXISTING MEDIUM VOLTAGE CABLE
[<600V] THE CABLE SHALL BE ISOLATED AT EACH END AND TESTES PER THE
SPECIFICATIONS TO VERIFY CABLE INTEGRITY PRIOR TO RE-ENERGIZTAION.
TEST REPORTS SHALL BE SUBMITTED TO THE OWNER AND ENGINEER FOR
REVIEW.
5. PRIOR TO RE-TERMINATION OF ANY EXISTING LOW VOLTAGE CABLES [>600V]
THE CABLES SHALL BE ISOLATED AT EACH END AND TESTED PER THE
SPECIFICATIONS TO VERIFY CABLE INTEGRITY PRIOR TO RE-ENERGIZTAION.
TEST REPORTS SHALL BE SUBMITTED TO THE OWNER AND ENGINEER FOR
REVIEW.
6. WHERE NEW PAD MOUNTED TRANSFORMERS ARE INSTALLED THE E.C. SHALL
VERIFY EXISTING SYSTEM GROUNDING ARRANGEMENT [N-G CONNECTION AT
TRANSFORMER OR S.E. PANEL] WITH EXISTING EQUIPMENT AND REMOVE /
MAINTAIN SYSTEM BONDING JUMPER IN NEW PAD MOUNTED TRANSFORMER
SECONDARY TERMINATION SECTION.
N.T.S
BORDER PATROL NEW WORK - ONE LINE DIAGRAM
SCALE:
" = 1'-0"
BORDER PATROL - NEW WORK
12-28-16 Preliminary (65%) Submittal
NN
EXISTING "H" FRAME TRANSFORMER PLATFORM
BETWEEN TWO EXISTING UTILITY POLES
EXISTING UTILITY / POWER POLE
TYPICAL FOR TWO [2] W/ 4.8kV
OVERHEAD LINES
EXISTING PLATFORM BETWEEN UTILITY /
POWER POLES [+/- 15' ABOVE GRADE]
WITH THREE POLE TOP STYLE
TRANSFORMERS. TRANSFORMERS AND
PLATFORM…