127th WING

WELLNESS

CENTER

BUILDING 168

RENOVATION

http://www.AECOM.com

27777 Franklin Road, Suite 2000

Southfield, MI 48034

United States

P: 248 204 5900 F: 248 204 5901

TITLE SHEET

T100

SELFRIDGE ANG BASE MAPLOCATION MAP

BLDG. 168

BASE

SELFRIDGE AIR NATIONAL GUARD BASE

PROJECT NUMBER: VGLZ 162028

CONTRACT NUMBER: W912JB-D-4005-0015

FEBRUARY 13, 2018

100% FINAL SUBMITTAL

DRAWING INDEX

RENOVATE - BUILDING 168

THE 127th WING, MICHIGAN AIR NATIONAL GUARD

CODE SUMMARY

APPLICABLE CODES AND STANDARDS

2012 INTERNATIONAL BUILDING CODE (IBC)

UNITED FACILITIES CRITERIA (UFC)

T100 TITLE SHEET

ARCHITECTURAL

AD01 FIRST FLOOR DEMOLITION PLAN

A101 FIRST FLOOR PLAN

A103 FIRST FLOOR REFLECTED CEILING PLAN

A200 DOOR AND ROOM FINISH SCHEDULES

A301 SECTIONS AND DETAILS

MECHANICAL

M000 MECHANICAL SYMBOLS AND ABBREVIATIONS

M101 FIRST FLOOR PLAN - MECHANICAL DEMO

M201 FIRST FLOOR - MECHANICAL NEW

M501 MECHANICAL - DETAILS & SCHEDULES

P101 FIRST FLOOR PLAN - PLUMBING DEMO

P201 FIRST FLOOR PLAN - PLUMBING NEW

ELECTRICAL

E000 ELECTRICAL SYMBOL LIST & LIGHTING FIXTURE LEGEND

ED01 FIRST FLOOR ELECTRICAL DEMOLITION PLAN

E101 FIRST FLOOR LIGHTING PLAN

E201 FIRST FLOOR ELECTRICAL POWER & SPECIAL SYSTEMS PLAN

E300 PARTIAL ONE LINE DIAGRAM

EX.RTU-1

EX.RTU-2

10.2 10.2 9.6

6.1

6.1

6.1

23 2323

8.1 8.18.1

8.18.1 8.18.18.1

8.1

12.1

22.1 22.1

8.1

22.1

4.1 4.1

4.1

4.1

4.1

EXIST. PORTION OF

TO WALL REMAIN

15'-4"

9.7

6.1

8.1

8.1

8.1

8.1

8.18.1

6.1

9.1

4.1

4.1

4.1

4.1

12.1

8.2

8.2

8.2

8.2

9.1 8.18.1

9.1

9.1

9.1

5'-2" 3'-4"

4" 3'-

4"

OPTION # 2 -

OPTION # 1 - LINE

DENOTES LIMITS OF CARPET

REMOVAL ( 1050 sq.ft. +/- )

21'-0"

'-3

9.3

9.3

9.4

9.7

8.1

9.7

4.1

127th WING

WELLNESS

CENTER

BUILDING 168

RENOVATION

http://www.AECOM.com

27777 Franklin Road, Suite 2000

Southfield, MI 48034

United States

P: 248 204 5900 F: 248 204 5901

FIRST FLOOR

DEMOLITION

PLAN

AD01

NORTH

FIRST FLOOR DEMOLITION PLAN

REMOVE EXISTING MASONRY WALL - TO BOTTOM OF ROOF SLAB AND PREP FOR CONCRETE INFILL

AFTER ASBESTOS ABATEMENT, REMOVE STEPS, PLATFORM AND FRAMING. PREP FOR NEW FLOOR FINISH

REMOVE DOOR AND FRAME

REMOVE EXISTING STEEL FRAMED WINDOW UNIT - REFER TO ASBESTOS / LEAD DISCOVERY NOTES ON

THIS SHEET.

REMOVE PARTITION - VERIFY EXACT CONSTRUCTION IN FIELD. SALVAGE 50 sq. ft. OF HARDWOOD PANELS

FROM THE EAST WALL OF THE NAVE FOR RE-USE.

REMOVE PLASTER BULKHEAD AND FRAMING

REMOVE LAY-IN CEILING PANELS IN THIS ROOM - METAL GRID SUSPENSION SYSTEM TO REMAIN

REMOVE CERAMIC/PORCELAIN FLOOR TILE AND MUD BED IN THIS ROOM. CONCRETE SLAB BELOW TO

REMAIN. PREP FOR NEW CONCRETE TOPPING AND FLOOR FINISH.

REMOVE CARPET AND WALL BASE IN THIS ROOM. - PREP SURFACES FOR NEW WORK

REMOVE TOILET PARTITIONS

REMOVE COUNTER TOP/CASEWORK

REMOVE PLUMBING FIXTURES - REFER TO MECHANICAL DRAWINGS

REMOVE ASBESTOS FLOORING - REFER ASBESTOS ABATEMENT NOTES (THIS SHEET)

REMOVE EXISTING CERAMIC TILE AND CONCRETE FLOOR SLAB - PREP FOR NEW WORK

4.1

6.1

8.1

8.2

9.1

9.3

9.4

9.6

9.7

10.2

12.1

22.1

DEMOLITION KEY NOTES

EXISTING PARTITION TO BE REMOVED

EXISTING DOOR TO REMAIN - REFER TO DOOR SCHEDULE FOR ADDITIONAL

INFORMATION

EXISTING DOOR AND FRAME TO BE REMOVED - REFER TO DEMOLITION NOTES

FOR ADDITIONAL INFORMATION

DEMOLITION PLAN LEGEND

EXISTING PARTITION TO REMAIN

1. IF SUSPECTED ASBESTOS CONTAINING BUILDING MATERIAL (ACBM) IS ENCOUNTERED, WORK IN THE IMMEDIATE VICINITY MUST STOP AND THE OWNERS CONTRACTING OFFICER SHALL BE NOTIFIED. AFTER CONSULTATION WITH BASE PERSONNEL, THE OWNERS CONTRACTING OFFICER WILL DIRECT FURTHER ACTION TO BE TAKEN. WORK SHOULD PROCEED UNINTERRUPTED IN UNAFFECTED AREAS OF THE PROJECT.

2. BASED ON THE AGE OF THE BUILDINGS AT SELFRIDGE ANG BASE, THERE IS THE POTENTIAL FOR THE PRESENCE OF LEAD ON PAINTED SURFACES. BEST MANAGEMENT PRACTICES MUST BE EMPLOYED TO MINIMIZE DUST AND ADEQUATELY PROTECT WORKERS FROM LEAD BASED PAINT (LBP) EXPOSURE IN

ACCORDANCE WITH OSHA AND MIOSHA STANDARDS.

3. IF ASBESTOS AND/OR LEAD IS SUSPECTED IT SHOULD BE TESTED FOR. IF EITHER ASBESTOS AND/OR LEAD

IS FOUND, FOLLOW APPLICABLE OSHA GUIDELINES FOR REMEDIATION.

4. REFER TO SPECIFICATIONS. APPENDIX NO. 1 : ASBESTOS INSPECTION REPORT USAG-M OMA BUILDING

NO.168 AND APPENDIX NO.2 : 168 LEAD INVESTIGATION REPORT - LEAD BASED PAINT

1. CONTRACTOR SHALL INCLUDE THE ABATEMENT OF ALL ASBESTOS CONTAINING BUILDING MATERIALS

(ACBM) IN THEIR BID.

2. ASBESTOS ABATED IN THE COURSE OF THIS PROJECT MUST BE PROPERLY COLLECTED, CONTAINERIZED AND DISPOSED OF IN A LANDFILL LICENSED TO ACCEPT ASBESTOS WASTE. ALL ASBESTOS DISPOSAL MANIFESTS MUST BE COORDINATED WITH, AND SIGNED BY, 127TH WING ENVIRONMENTAL MANAGEMENT

OFFICE PERSONNEL.

3. CONTRACTOR SHALL UTILIZE SELFRIDGE ANG BASE (SANGB) FORM 23 FOR TRACKING HAZARDOUS

MATERIALS AND SANGB FORM 72 FOR SOLID WASTE TRACKING AND DIVERSION.

4. CONTRACTOR SHALL ASSUME THE PRESENCE OF ASBESTOS CONTAINING FLOOR TILE (9" X 9") AND TILE

MASTIC UNDER ALL FLOORING NOTED FOR DEMOLITION.

5. CONTRACTOR SHALL ASSUME THE PRESENCE OF ASBESTOS CONTAINING INSULATION ON PLUMBING AND MECHANICAL PIPING NOTED FOR DEMOLITION AND/OR ALTERATION. REFER TO MECHANICAL AND PLUMBING

DRAWINGS FOR ADDITIONAL INFORMATION.

1. REFER TO GENERAL NOTES ON SHEET AD101 FOR DEMOLITION AND NEW WORK REQUIREMENTS.

2. REFER TO ARCHITECTURAL, MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL DEMOLITION

INFORMATION.

3. ALL DEMOLITION SHALL BE CARRIED OUT IN A SAFE MANNER AND IN STRICT ACCORDANCE WITH OSHA /

MIOSHA REGULATIONS.

4. DEMOLITION CONTRACTOR TO COORDINATE AND REVIEW ALL CONSTRUCTION DOCUMENTS AND

DETERMINE THE EXTENT OF DEMOLITION WORK AND BECOME FAMILIAR WITH THEM THOROUGHLY BEFORE PERFORMING ANY DEMOLITION WORK. BY THE ACT OF STARTING DEMOLITION, THE CONTRACTOR WILL BE DEEMED TO HAVE COMPLIED WITH THE FOREGOING, TO HAVE ACCEPTED SUCH CONDITIONS, AND TO HAVE

MADE THE NECESSARY ALLOWANCES IN HIS BID.

5. ANY ITEMS LEFT IN DEMOLITION AREAS WILL BECOME THE PROPERTY OF DEMOLITION CONTRACTOR FOR

HIS OFF-SITE DISPOSAL AT THE CONTRACTOR'S EXPENSE UNLESS NOTED OTHERWISE.

6. GENERAL CONTRACTOR TO COORDINATE COMMENCEMENT OF DEMOLITION WORK WITH OWNER

REPRESENTATIVE.

7. PATCH AND REPAIR ALL OPENINGS IN EXISTING GYPSUM BOARD WALLS CREATED BY REMOVAL OR INSTALLATION OF ELECTRICAL OUTLETS, DATA DROPS, OR SWITCHES. REFER TO ELECTRICAL PLANS FOR

LOCATIONS.

DEMOLITION GENERAL REQUIREMENTSASBESTOS ABATEMENT NOTESASBESTOS/LEAD DISCOVERY NOTES

ASBESTOS FLOORING TO BE ABATED - SEE ABATEMENT NOTES THIS SHEET

EXISTING FLOORING AND CONRETE SLAB AND RAMPS TO BE REMOVED - PREP FOR

NEW CONCRETE.

REMOVE CERAMIC/PORCELAIN FLOOR TILE AND MUD BED IN THIS AREA. CONCRETE

SLAB BELOW TO REMAIN. PREP FOR NEW MUD BED AND CERAMIC TILE.

RE

LO

CA

TE

D

FR

ID

G.

/F

RZ

FAMILY READINESS

ENTRANCE

SARC ENTRANCE

CHAPLAIN, STUDENT

FLIGHT AND LECTURE

HALL ENTRANCE

SHELVING

N.I.C.

EX.RTU-1

EX.RTU-2

5'- 0"

2'- 8"

1'- 3"

2'- 6"

1'- 3"

6" 3'-

4"

6"

8'-9"6"1'-0"6"8'-9" 8"10"

20'-2"

4'-9" 10'-0" 4'-9"

35'-0"

'-2

8"

V.

I.F

CL

R.

M.

O.

M.O.

1'-2" 5'-0" 7'-9" 14'-5" 7'-5" 10'-5"

9'- 1"

8'- 9"

EQUAL EQUAL 8'-7"

V.I.F.

3'-1"

2'-0" 3'-4"

1'-

" 5'-

6'- 5"

PROVIDE NEW BULLNOSED

CMU AT END OF REMAINING

WALL

15'-4"

1'-5"

2'-3"

15'-0"

6'- 0"

8"

DW (NIC)

2'- 6"

CARPET ACCENT

INCL. IN BASE BID

2'-6"

CTR. TOP

6" CHASE BEHIND BASE

CABINETS TYP.

2'-0"

EXISTING COLUMNS - PROVIDE

NEW HARDWOOD ENCLOSURE

- MATCH EXISTING

OPTION # 2 - PROVIDE

NEW CARPET ON NEW

CONCRETE SLAB

6 3'- 4"

110111112113

116117

S1

F1

S2

S2

C3

C1

C1

C2

S4

6'- 0"

V

IF

W / 1

M

UL

LIO

N

6'- 0"

V

IF

W / 1

M

UL

LIO

N

6'- 0"

V

IF

W / 1

M

UL

LIO

N

9'- 0"

V

IF

W / 2

M

UL

LIO

NS

B.F.

44'-0"

TABLE &

CHAIRS - NIC

TABLES &

CHAIRS - NIC

F.D.F.D.

SHELF

MOP RACK

S.S.

A301

A301

RANGE

NIC

6 5 A301 A301

USE SALVAGED HARDWOOD

WOOD PANELS FROM THE

NAVE DEMOLITION TO FINISH

THIS SIDE OF INFILLE - MATCH

EXISTING ADJACENT SURFACE 8

T.2 T.1

BOILER RM.

DIRECTOR OF

PSYCH. HEALTH

CONFERENCE RM. /

COMPUTER LAB

KITCHENETTE

VOLUNTEER

STORAGE

CHAPLAIN 1

CHAPLAIN

ASSISTANTS (3)

TOILET

VESTIBULE

MEN'S TOILET

WOMEN'S TOILET

MEN'S

TOILET

WOMEN'S

TOILET

I.T. CLOSET

VESTIBULE

STAIR

CHAPLAIN 2

CHAPLAIN 3

FAMILY READINESS

MULTI-PURPOSE ROOM

109LECTURE HALL

CORRIDOR

CO

RR

ID

OR

FAMILY READINESS

OFFICE

STAGE

AREA DEFENSE

COUNSEL

SARC

COUNSELING

SARC

OFFICE

SARC

WAITING

FAMILY READINESS

ASSISTANT

FAMILY READINESS

YELLOW RIBBON

TOUCH-DOWN

OFFICE

STUDENT FLIGHT

CLASSROOM

J.C.

VOLUNTEER

STORAGE

AIRMEN'S

LOUNGE

CHAPLAIN, STUDENT

FLIGHT AND LECTURE

HALL ENTRANCE

4'-6" HIGH KNEE WALL

TO MATCH EXISTING

WAINSCOT -

BENCHES TYP.

4'-6" 14'-6" 6'-0" 14'-6" 4'-6"

CARPET

1050 sq. ft. +/-

EXISTING COLUMNS

2'- 5"

A301

AIRMEN'S

LOUNGE

OPTION # 1

REMOVE EXISTING CARPET IN THE AREA SHOWN (SEE SHT. AD01). PROVIDE NEW

4'-6" HIGH PARTITIONS WITH BENCHES AS SHOWN ABOVE.

CONCRETE FLOOR TOPPING. TOP OF CONCRETE TO BE FLUSH WITH ADJACENT SURFACE.

DEPTH 3" +/- TYP.

CONCRETE FLOOR INFILL. TOP OF CONCRETE TO BE FLUSH WITH ADJACENT SURFACE . DEPTH

TO MATCH EXISTING ( 6" )

CONCRETE FLOOR TOPPING (INFILL RECESS LEFT BY CERAMIC TILE AND MUD BED REMOVAL).

TOP OF CONCRETE TO BE FLUSH WITH ADJACENT SURFACES, PROVIDE A DRY, CLEAN AND

SMOOTH SURFACE FOR INSTALLATION OF RESILIENT FLOOR PER MANUFACTURERS

SPECIFICATIONS.

NEW SOUND CONTROL WINDOW - SEE DETAIL # 3 A/301

INFILL EXISTING WALL OPENING, PROVIDE SOUND ATTENUATION INSULATION IN EXISTING AND

NEW PARTITION CONSTRUCTION.

PROVIDE NEW WALL AND BASE CABINETS, COUNTERTOP AND BACKSPLASH. SEE ELEVATIONS

AND DETAILS ON SHEET A301

PROVIDE 6" CONCRETE FLOOR SLAB.- RECESS SLAB TO ALLOW FOR NEW CERAMIC TILE AND

'MUD' BASE (COORDINATE W/ TILE CONTRACTOR) SLOPE TO FLOOR DRAINS.

PROVIDE NEW 30"X30" CEILING ACCESS PANEL (ABOVE) MODEL NO.

T1 & T2, PROVIDE NEW TOILET ROOM SIGNAGE - SEE DETAILS ON SHEET A301

T

FLOOR PLAN KEY NOTES

1. DO NOT SCALE DRAWINGS

2. ALL DIMENSIONS ARE NOMINAL, U.N.O.

3. VERIFY ALL CONDITIONS AND DIMENSIONS IN FIELD PRIOR TO START OF WORK.

4. ALL DIMENSIONS SHOWN AS EXISTING SHALL BE FIELD VERIFIED BY CONTRACTOR PRIOR TO

DEMOLITION. VERIFY ALL DEMOLITION WORK W/ NEW CONSTRUCTION AND INSTALLATION

DRAWINGS PRIOR TO BEGINNING CONSTRUCTION.

5. DOCUMENTS ARE BASED UPON OWNER'S RECORD DRAWINGS. NOTIFY ARCHITECT OF

DISCREPANCIES OR CONDITIONS REQUIRING SUPPLEMENTAL INSTRUCTION PRIOR TO

CONTINUATION OF WORK.

6. ALL WORK TO ADHERE TO ALL STATE, LOCAL CODES.

7. ADJOINING SPACES TO REMAIN OCCUPIED DURING CONSTRUCTION. PROTECT AND ALLOW TO

REMAIN FUNCTIONAL.

9. CONTRACTOR TO MAINTAIN ALL EGRESS PATHS CODE COMPLIANT DURING DURATION OF

CONSTRUCTION ACTIVITIES.

10. CONTRACTOR TO INSTALL TEMPORARY PARTITIONS AND DUST CONTROLS TO ADEQUATELY

SEAL OFF CONSTRUCTION ACTIVITIES FROM ADJACENT SPACES THAT ARE TO REMAIN

OCCUPIED.

11. CONTRACTOR TO COORDINATE ALL UTILITY SHUT DOWNS THAT WILL IMPACT ADJACENT

OCCUPIED SPACES WITH OWNER REPRESENTATIVE.

12. CONTRACTOR TO COORDINATE LOCATION OF MATERIAL STAGING AREAS WITH OWNER

REPRESENTATIVE AND ALLOWABLE INGRESS/EGRESS PATH FOR MOVING CONSTRUCTION

MATERIALS AND DEBRIS.

13. PROTECT ALL EXISTING WALLS, FLOORS, CEILINGS, ETC. THAT ARE TO REMAIN FOR THE

DURATION OF CONSTRUCTION. CONTRACTOR TO PATCH AND REPAIR ANY DAMAGED PORTIONS

OF THE EXISTING AREAS AS REQUIRED TO MATCH ADJACENT EXISTING CONDITIONS AND AS

REQUIRED TO INSTALL NEW EQUIPMENT, MATERIALS OR FINISHES.

14. ALL SURFACES DISTURBED DUE TO DEMOLITION/REMODELING ARE TO BE PATCHED TO MATCH

ADJACENT SURFACES AND PREPARED TO RECEIVE NEW FINISHES.

15. FILL-IN ANY CHASE OPENINGS, PENETRATIONS IN WALLS AND FLOORS DUE TO REMOVAL OF

ELEMENTS.

16. PROVIDE 16GA. x 8"W SHEET METAL WALL REINFORCING AS REQUIRED AT WALL MOUNTED

EQUIPMENT, SHELVES, COAT HOOKS, DOOR WALL BUMPERS, ETC.

17. SEE SHEET A301 FOR ADULT RESTROOM BARRIER FREE STANDARD ELEVATIONS

EXISTING PARTITION TO REMAIN

NEW PARTITION: 5/8" GYPSUM BOARD BOTH SIDES 3-5/8" METAL STUDS

AT 16" O.C. EXTEND PARTITION CONSTRUCTION UP TO EXISTING CEILING

SEE TYPICAL SLIP TRACK DETAIL ON SHEET A200.

PARTITION LEGEND

NEW PARTITION: 5/8" GYPSUM BOARD BOTH SIDES 3-5/8" METAL

STUDS AT 16" O.C. WITH 3" SOUND ATTENUATION INSULATION.

EXTEND PARTITION CONSTRUCTION UP TO EXISTING CEILING ABOVE.

PROVIDE ACOUSTICAL SEALANT AT BASE OF WALL & TOP OF WALL.

NEW FURRING ON EXISTING CONSTRUCTION: 5/8" GYPSUM BOARD ON

1 5/8" METAL FURRING AT 16" O.C. - EXTEND CONSTRUCTION UP TO 6"

ABOVE CEILING.

PLANMARK DESCRIPTION

NEW CHASE: 5/8" GYPSUM BOARD ONE SIDE 3-5/8" METAL STUDS AT

16" O.C. WITH 3" SOUND ATTENUATION INSULATION. EXTEND

CONSTRUCTION UP TO UNDERSIDE OF FLOOR DECK ABOVE. PROVIDE

ACOUSTICAL SEALANT AT BASE OF WALL AND TOP OF WALL.

NEW CMU INFILL @ EXISTING WALL OPENING (TOOTH-IN CMU) - MATCH

EXISTING WALL THICKNESS. PREP & FINISH TO MATCH EXISTING.

PROVIDE NEW WALL INFILL (FLUSH W/ EXISTING): 5/8" GYPSUM BOARD ON

EACH SIDE OF STUD FRAMING AT 16" O.C. WITH SOUND ATTENUATION -

TAPE AND FINISH PERIMETER JOINT FLUSH W/ EXISTING ADJACENT

SURFACES.

S4

C2

S3

S2

S1

F1

127th WING

WELLNESS

CENTER

BUILDING 168

RENOVATION

http://www.AECOM.com

27777 Franklin Road, Suite 2000

Southfield, MI 48034

United States

P: 248 204 5900 F: 248 204 5901

FIRST FLOOR

PLAN

A101

NORTH

FIRST FLOOR PLAN

GENERAL NOTES

NORTH

PROJECT

AREA

BLDG #168

SITE PLAN

NEW CMU WALL UP TO UNDERSIDE OF DECK ABOVE. PROVIDE

ACOUSTICAL SEALANT AT TOP OF WALL. SEE PLAN FOR THICKNESS

C1

(PART OF OPTION # 1 ) - 5/8" GYPSUM BOARD ON EACH SIDE OF STUD

FRAMING AT 16" O.C. - UP TO 4'-6" A.F.F. - PROVIDE 1X6 HARDWOOD CAP

AT TOP OF WALL (PART OF OPTION # 1 )

S5

TOILET RM.

ACCESSORY NOTES

1 MIRROR

PAPER TOWEL DISPENSER / DISPOSAL UNIT

TOILET PAPER HOLDER

GRAB BARS

SOAP DISPENSER

SANITARY NAPKIN DISPENSER / DISP. UNIT

C3 NEW CMU WALL UP TO UNDERSIDE OF DECK ABOVE. PROVIDE

ACOUSTICAL SEALANT AT TOP OF WALL. SEE PLAN FOR THICKNESS

SARC ENTRANCE

CHAPLAIN, STUDENT

FLIGHT AND LECTURE

HALL ENTRANCE

EX.RTU-1

EX.RTU-2

8'-9"6"1'-0"6"8'-9"8"

20'-2"

5'-5" 10'-0" 4'-9"

35'-0"

'-2

8"

V.

I.F

M.O.

1'-2" 5'-0" 7'-9" 14'-5" 7'-5" 10'-5"

6'- 5"

9'-1 1/4" 9'-1 1/4" 8'-7" V.I.F.3'-1"

BOILER RM.

DIRECTOR OF

PSYCH. HEALTH

CONFERENCE RM. /

COMPUTER LAB

KITCHENETTE

VOLUNTEER

STORAGE

CHAPLAIN 1

CHAPLAIN

ASSISTANTS (3)

TOILET

VESTIBULE

MEN'S TOILET

WOMEN'S TOILET

MEN'S

TOILET

WOMEN'S

TOILET

I.T. CLOSET

VESTIBULE

STAIR

CHAPLAIN 2

CHAPLAIN 3

FAMILY READINESS

MULTI-PURPOSE ROOM

109LECTURE HALL

CORRIDOR

CO

RR

ID

OR

FAMILY READINESS

OFFICE

STAGE

AREA DEFENSE

COUNSEL

SARC

COUNSELING

SARC

OFFICE

SARC

WAITING

FAMILY READINESS

ASSISTANT

FAMILY READINESS

YELLOW RIBBON

TOUCH-DOWN

OFFICE

STUDENT FLIGHT

CLASSROOM

J.C.

VOLUNTEER

STORAGE

STUDENT FLIGHT

LOUNGE

EXISTING CEILING

ACCESS PANEL

A103

PROVIDE NEW

30"x30" CEILING

ACCESS PANEL

MODEL #

PROVIDE NEW CEILING PANELS

(IN EXISTING GRID)

PROVIDE NEW

SUSPENDED GYP.

BD. CLG. INFILL -

MATCH EXISTING

CEILING

PROVIDE NEW

SUSPENDED GYP. BD.

CLG. INFILL - MATCH

EXISTING CEILING

127th WING

WELLNESS

CENTER

BUILDING 168

RENOVATION

http://www.AECOM.com

27777 Franklin Road, Suite 2000

Southfield, MI 48034

United States

P: 248 204 5900 F: 248 204 5901

FIRST FLOOR

REFLECTED

CEILING PLAN

A103

REFLECTED CEILING PLAN LEGEND

EXISTING CEILING TO REMAIN

2'-0" X 2'-0" LAY-IN ACOUSTICAL CEILING PANEL IN SUSPENDED

METAL GRID SYSTEM

SUSPENDED GYPSUM BOARD CEILING SYSTEM

2'-0" X 2'-0" LAY-IN LIGHT FIXTURE - SEE ELECTRICAL DRAWINGS

PENDANT MOUNT LIGHT FIXTURE - SEE ELECTRICAL DRAWINGS

LIGHT FIXTURE - SEE ELECTRICAL DRAWINGS

SURFACE MOUNTED LIGHT FIXTURE - SEE ELECTRICAL DRAWINGS

SUPPLY AIR DIFFUSER - SEE MECHANICAL DRAWINGS

RETURN AIR / EXHAUST GRILLE - SEE MECHANICAL DRAWINGS

EXISTING WOOD PANELING

ON WOOD FRAMINGFRAMING

PROVIDE NEW HARDWOOD

TRIM - FINISH TO MATCH

EXISTING

8'-9" A.F.F.

PROVIDE NEW HARDWOOD

TRIM AND WOOD BLOCKING 3"

1 1 /2"

6"

EXISTING PARTITION

PANELING AND FRAMING

TO BE REMOVED UP TO

8'-9" A.F.F.

V.I.F.

BALCONY FLR.

ELEV = 10'-6"

SECTION AT BALCONY

A103

2'-0" X 4'-0" RECESSED LIGHT FIXTURE - SEE ELECTRICAL

DRAWINGS

NORTH

1st FOOR REFLECTED CEILING PLAN

3'- 0"

2'- 0"

3'-

0" CWT1

CWT2

CWT3

CWT4

TYPICAL TOILET ROOM

TILE PATTERN ELEVATION

A200

6"

2'-0"

8"

TYP.

8"

FULL TILE PCTB1

2"

NON-STRUCTURAL

METAL FRAMING

SOUND ATTENUATION

BLANKETS SEE WALL

TYPES FOR LOCATIONS

REFER TO ROOM FINISH

SCHEDULE FOR WALL

FINISH. - TYP.

GYPSUM BOARD

JOINT SEALANT, EA. SIDE - TYP.

HOLLOW METAL DOOR

FRAME

NOTE : SEE PLANS AND FLOOR

PLAN LEGEND FOR WALL

CONSTRUCTION.

SEE DOOR

SCHEDULE

A200

HEAD SIMILAR

A200

EXISTING CMU (TYPICAL)

5 3/4"

H.M. FRAME W/ MIN. 3

ANCHORS PER JAMB

TYP. (FILL W/ GROUT).

3/8

H.M. FRAME W/ MIN. 3

ANCHORS PER JAMB

TYP. (FILL W/ GROUT).

SEALANT AND BACKER

ROD AT PERIMETER

BOTH SIDES

SEALANT AND BACKER

ROD AT PERIMETER

BOTH SIDESEXISTING CMU (TYPICAL)

2"

SE

E

DO

OR

SC

HE

DU

LE

3/8"

PARTITION AS

SCHEDULED

SLIP TRACK AT HEAD TO

ACCOMMODATE FLOOR

DEFLECTION

NOTE:

1. DO NOT ANCHOR VERTICAL

STUDS TO TOP RUNNER.

ALLOW FOR STRUCTURAL

SLAB DEFLECTION.

UNDERSIDE OF STRUCT.

ACOUSTIC SEALANT TYPICAL

BOTH SIDES

1" C

LE

AR

SCALE: 1 1/2" = 1'-0"

TYPICAL SLIP TRACK DETAIL

127th WING

WELLNESS

CENTER

BUILDING 168

RENOVATION

http://www.AECOM.com

27777 Franklin Road, Suite 2000

Southfield, MI 48034

United States

P: 248 204 5900 F: 248 204 5901

DOOR AND

ROOM FINISH

SCHEDULE

A200

DOOR SCHEDULE

DOOR FRAME DETAILS

HARDWARE SET NOTES

NO. ROOM NAME

TYPE SIZE MATERIAL MATERIAL TYPE HEAD JAMB

102 SARC

COUNSELING B 3'-0" X 7'-0" WOOD HM 1 2/A200 2/A200 2

104 AREA DEFENSE

COUNSEL B 3'-0" x 7'-0" WOOD HM 1 2/A200 2/A200 2

105 VOLUNTEER

STORAGE A (2) 2'-6" x 7'-0" WOOD HM 1 2/A200 2/A200 1

FAMILY

READINESS

YELLOW RIBBON

A 3'-0" x 7'-0" WOOD HM 1 2/A200 2/A200 2

FAMILY

READINESS

MULTI-PURPOSE

B 3'-0" x 7'-0" WOOD HM 1 2/A200 2/A200 2

110 TOUCHDOWN

OFFICE B 3'-0" x 7'-0" WOOD HM 1 2/A200 2/A200 2

111 VOLUNTEER

STORAGE A 3'-0" x 7'-0" WOOD HM 1 2/A200 2/A200 1

CONFERENCE

ROOM /

COMPUTER LAB

B 3'-0" x 7'-0" WOOD HM 1 2/A200 2/A200 2 PROVIDE DOOR SEALS

REESE DS78A & 370A

113 JANITORS

CLOSET D 3'-0" x 7'-0" WOOD HM 1 1

114 KITCHENETTE B 3'-0" x 7'-0" WOOD HM 1 2/A200 2/A200 5

115 I.T. CLOSET EXISTING TO REMAIN - PROVIDE CIPHER LOCK -

KABA 5021-BWL-26D

116 WOMEN'S A 3'-0" x 7'-0" WOOD HM 1 4/A301 4/A301 3

117 MEN'S A 3'-0" X 7'-0" WOOD HM 1 4/A301 4/A301 3

118 CORRIDOR C 3'-0" x 7'-0" WOOD HM 1 3/A200 3/A200 4

121 CHAPLAIN 1 EXISTING TO REMAIN - - - PROVIDE DOOR SEALS

REESE DS78A & 370A

122 CHAPLAIN 1 EXISTING TO REMAIN - PROVIDE DOOR SEALS

REESE DS78A & 370A

123 CHAPLAIN 1 EXISTING TO REMAIN - PROVIDE DOOR SEALS

REESE DS78A & 370A

124 CHAPLAIN 1 EXISTING TO REMAIN - PROVIDE DOOR SEALS

REESE DS78A & 370A

6"

6" 6"TEMPERED GLASS (T)

DOOR TYPES

A

FLUSH DOOR

B

FLUSH DOOR W/ NARROW LITE

FRAME TYPES

6"

6"

TEMPERED

GLASS (T)

D

FLUSH DOOR W/ LOUVER

C

FLUSH DOOR W/ HALF LITE

6"

ROOM FINISH SCHEDULE

ROOM

NO. ROOM NAME

FLOOR WALL CEILING

REMARKSFLOOR BASE ALL NORTH SOUTH EAST WEST MTL/FIN/HT

101 SARC WAITING EX RB1 PT1 EX/EX/ 9'-0" 8

102 SARC COUNSELING EX RB1 PT1 EX/EX/ 9'-0" 8

103 SARC OFFICE EX EX EX/EX/ 9'-0"

104 AREA DEFENSE COUNSEL EX EX PT1 EX/EX/ 9'-0" 8, 12

105 VOLUNTEER STORAGE EX RB1 PT1 GYP / PT3 / 7'-0"

106 FAM. READINESS OFFICE EX EX EX EX/EX/ 9'-0"

107 FAM. READINESS ASSISTANT CPT1 RB1 PT1 ACP1/ - / 9'-0" 8, 12

108 FAM. READINESS YELLOW

RIBBON CPT1 RB1 PT1 ACP1/ - / 9'-0" 8, 12

109 FAM. READINESS

MULTI-PURPOSE ROOM ROOM. EX EX - PT1 EX/EX/ 12'-0" 8, 13

110 TOUCH-DOWN OFFICE CPT1 RB1 PT1 ACP1/ - / 9'-0"

111 VOLUNTEER STORAGE RF1 RB1 PT1 ACP1/ - / 9'-0"

112 CONF. ROOM COMPUTER LAB CPT1 RB1 PT1 ACP1/ - / 9'-0"

113 JANITOR CLOSET SC1 RB1 PT1 PT1 FRP1/PT1 FRP1/PT1 GYP / PT3 / 9'-0" 9

114 KITCHENETTE RF2 RB1 PT1 EX / PT3 / 8'-9" 1, 6, 10

115 I.T. CLOSET RF1 RB1 PT1 EX / PT1/ 9'-0"

116 WOMEN'S TOILET PCT1 PCTB1 CWT1/2/3/4 GYP / PT3 / 9'-0" 1, 4, 6

117 MEN'S TOILET PCT1 PCTB1 CWT1/2/3/4 GYP / PT3 / 9'-0" 1, 4, 6

118 CORRIDOR CPT1 RB1 PT1 ACP1/-/ 9'-0" 14, 15

119 STUDENT FLIGHT CLASSROOM CPT1 RB1 PT1 PT2 PT1 PT1 ACP1/ - / 9'-0"

120 CORRIDOR CPT1 RB1 - EX/EX/ 9'-0" 11

121 CHAPLAIN 1 EX EX EX EX/EX/ 9'-0" 7

122 CHAPLAIN 1 EX EX EX EX/EX/ 9'-0" 7

123 CHAPLAIN 1 EX EX EX EX/EX/ 9'-0" 7

124 CHAPLAIN ASSISTANTS (3) EX EX EX EX/EX/ 9'-0" 7

125 VESTIBULE EX EX EX EX/EX/ 9'-0"

126 STAIR EX EX EX EX / EX / VARIES

127 MEN'S TOILET EX EX EX EX/EX/ 9'-0"

128 WOMEN'S TOILET EX EX EX EX/EX/ 9'-0"

129 AIRMEN'S LOUNGE EX EX EX EX / EX / VARIES 5

130 LECTURE HALL EX EX EX EX / EX / VARIES 5

131 STAGE EX EX EX EX / EX / VARIES

132 BOILER ROOM EX EX EX EX/EX/ 9'-0"

133 DIRECTOR OF PSYCH. HEALTH CPT1 RB1 PT1 ACP1 / - / 8'-0" 14

134 TOILET EX EX EX EX/EX/ 9'-0"

135 VESTIBULE EX EX EX EX/EX/ 9'-0"

GENERAL FINISH NOTES

A ALL FINISHES SHALL BE PROVIDED AS SPECIFIED - NO SUBSTITUTIONS, UNLESS

NOTED OTHERWISE

B DISCREPANCIES IN FINISH DESIGNATIONS, COLOR NUMBERS AND/OR

DESCRIPTIONS MUST BE BROUGHT TO THE ATTENTION OF THE ARCHITECT FOR

RESOLUTION PRIOR TO ORDER, FABRICATION AND/OR INSTALLATION.

C ANY NOTE REFERRING TO "MATCH EXISTING" REQUIRES EXISTING FINISHES AND

FINISH DETAILS TO BE REPLICATED IN FULL UPON COMPLETION OF WORK IN THE

GIVEN AREA.

D WIREWAYS, ACCESS PANELS, GRILLES, FIRE EXTINGUISHES CABINETS,

ELECTRICAL PANELS, MECHANICAL DEVICES, ETC SHALL BE FINISHED TO MATCH

THE ADJACENT SURFACE.

E LAMINATE CABINET INTERIORS: WHITE

F MPI GLOSS LEVEL2 ON WALLS & CEILINGS (EGGSHELL)

MPI GLOSS LEVEL5 ON TRIM, FRAMES, DOORS, WINDOWS (SEMI-GLOSS)

G USE TR2 BETWEEN CPT1 AND EXISTING VCT, AND BETWEEN CPT1 AND RF1

H USE TR1 BETWEEN CPT1 AND PCT1

I USE TR3 BETWEEN PCT1 AND RF1

J ALL HOLLOW METAL DOOR FRAMES TO BE PAINTED PT1

ROOM FINISH SCHEDULE - REMARKS

1 FLOOR TILE TO BE INSTALLED WITH 1/3 OFFSET

2 CABINETS: PL1

3 COUNTERS: PL2

4 REFER TO TILE PATTERN ELEVATION FOR TOILET ROOM WALL TILE

5 REFER TO OPTION #1 PLAN ON SHEET A101 FOR ADDITIONAL INFORMATION.

6 GROUT

GR1: FLOOR TILE

GR2: WALL TILE

7 PROVIDE NEW HARDWOOD SILL AND TRIM SEE DETAIL ON DRAWING A301.

8 PATCH AND REPAIR EXISTING FINISHES AS REQUIRED

9 FRP TO 4'-0" AFF

10 EXISTING GLAZED BLOCK TO REMAIN. PROTECT FOR DURATION OF

CONSTRUCTION. PAINT GYP BOARD PORTION OF WALLS IN THIS SPACE PER

ROOM FINISH SCHEDULE.

11 FINISHES IN THIS AREA ARE PART OF OPTION #2

12 PAINT NEW AREAS TO MATCH EXISTING.

13 PAINT E WALL TO MATCH EXISTING.

14 CEILING PANELS ONLY, EXISTING GRID TO REMAIN

15 PCT1 AND PCTB1 AT MENS AND WOMENS TOILET ALCOVE.

MATERIAL LIST

ABBREV MANUFACTURER PATTERN COLOR PRODUCT NO. SIZE REMARKS

ACOUSTICAL CEILING PANELS

ACP1 ARMSTRONG CIRRUS WHITE 534 24"X24" 15/16" GRID

CARPET

CPT1 SHAW LINEWEIGHT INK - 13496 5T114 18" X 36" ASHLAR INSTALLATION

CERAMIC WALL TILE

CWT1 MEDITERRANEA TOUCH SUN GLOW 12" X 24"

CWT2 AMERICAN OLEAN BRIGHT & MATTE 91 - BRIGHT BISCUIT 6" X 6"

CWT3 AMERICAN OLEAN BRIGHT & MATTE 38 - BRIGHT MUSHROOM 6" x 6"

CWT4 AMERICAN OLEAN BRIGHT & MATTE 81 - BRIGHT SUMMER RAIN 6" x 6"

FLOOR ACCESSORIES

TR1 SCHLUTER SCHIENE STAINLESS STEEL E 125 TRANSITION STRIP

TR2 JOHNSONITE DARK BROWN CTA-XX-HT

TR3 SCHLUTER RENO-U STAINLESS STEEL EU 125

GROUT

GR1 TEC POWER GROUT LIGHT PEWTER 927 FLOOR

GR2 TEC POWER GROUT BIRCH 903 WALL

FIBERGLASS REINFORCED PLASTIC PANELS

FRP1 MARLITE STANDARD FRP IVORY P 140 4' X 8' X 3/32"

USE WITH COORDINATING PVC TRIM PIECES AT EDGES

AND SEAMS

PAINT

PT1 SHERWIN WILLIAMS DOVER WHITE SW 6385 GENERAL PAINT

PT2 SHERWIN WILLIAMS TONY TAUPE SW 7038 NEUTRAL ACCENT

PT3 SHERWIN WILLIAMS EXTRA WHITE SW 7006 CEILING

PLASTIC LAMINATE

PL1 NEVAMAR VOUS SERENE VS5002T

PL2 WILSONART FORGED STEEL 4995-60

PORCELAIN COVE BASE

PCTB1 FLORIM USA BASALTINE NUT 6" X 12" COVE BASE

PORCELAIN TILE

PCT1 FLORIM USA BASALTINE NUT 12" X 12" MOSAIC

RESILIENT BASE

RB1 JOHNSONITE STANDARD COVE RUBBER 44 - DARK BROWN 4" H

RESILIENT FLOOR

RF1 JOHNSONITE IQ GRANIT SD SIDEWALK GRTSD-R-726 6'-6" WIDE ROLL USE COORDINATING WELD ROD

RF2 JOHNSONITE ACCENT CONCRETE DARK GREY 25001 6'-6" WIDE ROLL USE COORDINATING WELD ROD

SEALED CONCRETE

SC1

1'- 3"

1'-1"

1'- 3"

1'-6"

MICROWAVE N.I.C.

2'-6"

PLASTING LAMINATE DOOR WITH

SELF CLOSING HINGES

DOOR PULL- MOUNT CENTERLINE

1-1/2" FROM DOOR EDGE

3MM PVC EDGE BANDING -

TYP AT EXPOSED EDGES

PLASTIC LAMINATE ON 3/4"

COUNTERTOP AND BACKSPLASH

TYP. CABINET SECTION

A301

3"

4" 6 1

/2"

3'- 0"

1 1 /2"

PLASTIC LAMINATE AT TOE

KICK TO MATCH CABINET

(TYPICAL)

NOTE:

2" RADIUSED CORNERS AT OPEN

COUNTER ENDS (TYP)

EXISTING CEILING SYSTEM

4"

NOTE:

P.LAM. ON ALL

EXPOSED SURFACES

DETAIL AT MICROWAVE

A301

1'- 6"

2'- 6"

1'- 6"

2'- 6"

1'-1"

DOOR PULL - MOUNT

CENTERLINE 1 1/2" FROM EDGE

OF DOOR

PLASTIC LAMINATE CLAD

CABINET DOOR (FINISH ALL

SIDES) WITH SELF-CLOSING

CONCEALED HINGES

3/4" PLASTIC LAMINATE CLAD

ADJUSTABLE SHELF

3/4" PLASTIC LAMINATE CLAD

ADJUSTABLE SHELF

3/4" PLASTIC LAMINATE CLAD

TOP, BOTTOM AND SIDES

3'- 0"

6" PIPE CHASE TYP.

EXISTING MASONRY WALL

EXISTING CEILING

1'- 4"

1'- 4"

SEALANT AT PERIMETER TYP.

MICROWAVE SHELF

1 1/2" GROMMET FOR

MICROWAVE CORD

1" FILLER PANEL

1'-6" 2'-0" 3'-3"

MIN. CLEAR

2'-0"

1" FILLER PANEL

2'-6"

1'-3" 2'-0" 2'-0" 2'-0" 1'-6" 1'-1"

1" FILLER PANEL3" FILLER PANEL

3'- 0"

1'- 6"

1'- 3"

COFFEE

MAKER

N.I.C.

A301

TYP

KITCHEN 114 SOUTH ELEVATION

A301

RANGE, N.I.C. - CONTRACTOR TO

VERIFY CLEAR SPACE REQUIRED

A301

TYP

6" CHASE TYP.

1'-3"

1'- 3"

MICROWAVE, N.I.C.

3'- 0"

2'-6"

2" FILLER PANEL

2'-0" 3'-0" 2'-6" 2'-3"

2'-0" MIN CLEAR INSIDE

1'-1"

1" FILLER PANEL

2'-0" 6'-0 1/2" 3'-0"

1'- 6"

2'- 6"

KITCHEN 114 WEST ELEVATION

A301

DISHWASHER, N.I.C.

V.I.F.

6" CHASE TYP.

EXISTING WINDOW

TO REMAIN

2"

OR

60" MIN.

CLEAR

" M

AX

36" MIN.

CLEAR

"M

AX

" M

AX

16"-18"

"-1

9"

42" MIN.

12" MAX.

NO

TE

"-1

9"

25" MAX.

" M

AX

NOTE 1

" M

AX

" M

IN

" M

AX

"-3

6"

24" MIN. 12" MIN.

"-3

6"

ALT. LOCATION

9" M

IN

39" - 41"

7 1 1/2" MIN. CLR. BELOW

GRAB BAR, SEE NOTE

2.

12" MIN. CLR. SEE NOTE 2.

1. DISPENSER OUTLET ABOVE THE GRAB BAR SHALL

BE 24" MIN. & 36" MAX. FROM REAR WALL.

BELOW THE GRAB BAR, DISPENSER OUTLET SHALL BE

24" MIN. & 42" MAX. FROM REAR WALL.

2. NO PART OF ANY ACCESSORY SHALL BE WITHIN A

ZONE 12" ABOVE AND 1 12" BELOW THE GRAB BAR.

EXCEPTION: RECESSED DISPENSERS EXTENDING NO

MORE THAN 14" BEYOND FACE OF WALL MAY CROSS

THIS ZONE. NO PORTION OF A RECESSED DISPENSER

SHALL BE BEHIND THE GRAB BAR ITSELF.

3. OUTLET OF DISPENSER SHALL BE 18" MIN. AND 48"

MAX. ABOVE FLOOR.

*WITH MAX. 0.5" REACH DEPTH. REFER TO

ICC A117.1-2009TABLE 603.6 FOR OTHER

REACH DEPTH CONDITIONS

54" MIN.

ADULT RESTROOM BARRIER FREE STANDARD ELEVATIONS

(REFER TO PLANS FOR ACTUAL LAYOUT)

5/8" GYP. BD. ON BOTH SIDES OF

3 5/8" METAL STUDS AT 16" O.C.,

W/ 3" ACOUSTIC BATT INSULATION

HOLLOW METAL DOOR FRAME -

FILL WITH GROUT (TYP). - SEE

DOOR SCHEDULE

BASE - SEE ROOM FINISH

SCHEDULE (TYP)

5/8" GPDW ON METAL FRAMING

(TYPICAL)

8'- 0"

DETAIL AT STORAGE RM. 105

A101

2x4 STUDS AT 16" O.C., HARDWOOD BASE & SHOE - FINISH

TO MATCH EXISTING WOOD

TRIM (TYP)

1'-6"

5/8" HARDWOOD VENEER PLYWOOD

- FINISH TO MATCH EXISTING WOOD

TRIM (TYP)

V.I.F.

4'- 6"

5/8" HARDWOOD VENEER PLYWOOD -

FINISH TO MATCH EXISTING WOOD

TRIM (TYP)

3/4" HARDWOOD COVE MOULDING -

FINISH TO MATCH EXISTING WOOD

TRIM (TYP)

2 1/4" x 3/4" HARDWOOD EDGE

MOULDING W/ 1/2" RAD. - FINISH

TO MATCH EXIST. WOOD TRIM (TYP)

HARDWOOD CAP W/ 1/2" RADIUS -

FINISH TO MATCH EXISTING WOOD

TRIM (TYP)

1'- 8"

1 1 /2"

5 3/4"

2x4 WOOD FRAMING AT 16" O.C., WALL - BENCH DETAIL

A101 OPTION # 1

9"9"

T.2T.1

NOTE: MOUNT SIGN @ LOCATION SHOWN

ON FLR. PLAN (BRAILLE @ 60" A.F.F. MAX.)

OF TEXT, BRAILLE & SYMBOLS

6"

3/4

MEN

WOMEN

6" 3/4

1" RAISED TEXT

OF TEXT, BRAILLE & SYMBOLS

3/4" RAISED TEXT

BRAILLE DOTS

NOTE: MOUNT SIGN @ LOCATION SHOWN

ON FLR. PLAN (BRAILLE @ 60" A.F.F. MAX.)

127th WING

WELLNESS

CENTER

BUILDING 168

RENOVATION

http://www.AECOM.com

27777 Franklin Road, Suite 2000

Southfield, MI 48034

United States

P: 248 204 5900 F: 248 204 5901

SECTIONS

AND DETAILS

A301

EXISTING CEILING AND

WOOD TRIM TO REMAIN

SOUND CONTROL WINDOWS,

GLASS & ALUMINUM FRAME

UNITS (TYP.)

SEALANT AND BACKER

ROD - EA. SIDE AT

PERIMETER (TYP)

PROVIDE NEW 1x10

HARDWOOD SILL - FINISH

TO MATCH EXISTING

PROVIDE NEW 1 x 6

HARDWOOD TRIM

FINISH TO MATCH

EXISTING

EXISTING ACOUSTIC

LAY-IN CEILING, GRID

AND WOOD TRIM TO

REMAIN

EXISTING HARDWOOD

TRIM AND WOOD

BLOCKING TO REMAIN

EXISTING MASONRY

SILL TO REMAIN

PAINT EXPOSED WOOD

TRIM. - MATCH EXISTING

4'- 1"

FI

EL

D

VE

RI

FY

EXISTING MASONRY TO

REMAIN

SECTION AT WINDOW

A101

5 3/4"

3/8"

2" 3/8

6" CMU (TYPICAL)

BOND BEAM LINTEL -

W/ 6" BEARING EA. SIDE

OF OPENING TYP.

SEALANT AND BACKER

ROD AT PERIMETER

BOTH SIDES

SE

E

DO

OR

SC

HE

DU

LE

H.M.

5 3/4"

VERTICAL REINFORCING -

# 5 VERTICAL AT EA. JAMB

- GROUT CORE SOLID

BULLNOSE CMU

TYPICAL

H.M. FRAME W/ MIN. 3

TIES PER JAMB TYP.

(FILL W/ GROUT).

SE

E

DO

OR

SC

HE

DU

LE

2"

3/8

3/8"

H.M. FRAME W/ MIN. 3

TIES PER JAMB TYP.

(FILL W/ GROUT).

VERTICAL REINFORCING -

# 5 VERTICAL AT EA. JAMB

- GROUT CORE SOLID

SEALANT AND BACKER

ROD AT PERIMETER

BOTH SIDES

SEALANT AND BACKER

ROD AT PERIMETER

BOTH SIDES

HEAD JAMB

CMU DOOR DETAILS

A200

SIGNAGE DETAILS

SIGNAGE NOTES

1 PROVIDE PRODUCTS "UNICOR 2/90 MODULAR SIGN SYSTEMS" OR APROVED EQUAL

1.1 ALL SIGNAGE FINISHES TO MATCH EXISTING SIGNAGE. AND TO BE FREE OF FADING, PEELING OR CRACKING.

1.2 ALL SIGNS TO BE INSTALLED LEVEL, WITH THE GUIDELINES OF THE AMERICANS WITH DISABILITIES ACT (ADA) AS APPLICABLE.

1.3 INSTALL WALL SIGNS WITH 3M 5952 VHB TAPE.

CENTER

BUILDING 168

RENOVATION

http://www.AECOM.com

27777 Franklin Road, Suite 2000

Southfield, MI 48034

United States

P: 248 204 5900 F: 248 204 5901

MECHANICAL

SYMBOL AND

ABBREVIATIONS

M000

R OR D

R OR D INCLINE RISE OR DROP IN

DIRECTION OF AIR FLOW

90° RADIUS ELBOW UP. USE

90° ELBOW W/ TURNING VANES

WHEN RADIUS DOES NOT FIT

90° RADIUS ELBOW DOWN. USE

90° ELBOW W/ TURNING VANES

WHEN RADIUS DOES NOT FIT

OSA DUCT

DUCT SECTION-SUPPLY AIR/

DUCT SECTION-RETURN AIR/

EXHAUST AIR DUCT

FLEXIBLE CONNECTOR

FLEXIBLE DUCT

FC

FC

FD

VD

BDD

BDD

VD

FD FIRE DAMPER

VOLUME DAMPER

BACKDRAFT DAMPER

MOTORIZED DAMPER

SIZE 4

SUPPLY CEILING DIFFUSER

REGISTER(GRILLE)

CEILING EXHAUST AND RETURN AIR

SIZE 4

SUPPLY GRILLE OR REGISTER

SIZE 4

DOOR LOUVER

DDC CONTROLLER

HUMIDISTAT

DUCT SMOKE DETECTOR

TEMPERATURE SENSOR

BUILDING EMERGENCY

AIR DISTRIBUTION SHUT OFF

E

SP

S

SD

H

T

DL

DDC

AHU

AS

B

CH

EF

ET

P WATER PUMP

EXPANSION TANK

EXHAUST FAN

CHEMICAL POT FEEDER

BOILER

AIR SEPARATOR

AIR HANDLING UNIT

A

AFF

AMB

AP

ARCH

AVG

A/C

BAS

BDD

BOD

BTUH

CC

CD

CFM

CG

C.L.

CLG

COMP

COEF

CONC

CONT

CP

CV

D

DB

dB

DDC

DEFL DEFLECTION

DIRECT DIGITAL CONTROL

DECIBELS

DRY BULB

DRAIN

CONSTANT VOLUME

CONTROL PANEL

CONTINUATION

CONCRETE

COMPRESSOR

COEFFICIENT

CEILING

CENTER LINE

CEILING GRILLE

CUBIC FEET PER MINUTE

CEILING DIFFUSER

COOLING COIL

BRITISH THERMAL UNIT/HR

BOTTOM OF DUCT

BACK DRAFT DAMPER

BUILDING AUTOMATION SYSTEM

AIR CHANGE

AVERAGE

ARCHITECT

ACCESS PANEL

AMBIENT

AMPERE

ABOVE FINISHED FLOOR

DIA

DIFF

DL

DN

DWG

DX

EA

ea

EAT

EF-XX

EG

ELEC.

ENT

EWT

EXH

EX.

FA

FD

FC

FLA

FLR

FPM

FSD

FT

GA

HDPE

GAGE or GAUGE

FOOT

FIRE SMOKE DAMPER

FEET PER MINUTE

FLOOR

FULL LOAD AMP

FIRE DAMPER

FLEXIBLE CONNECTION

FREE AREA

EXISTING

EXHAUST

ENTERING WATER TEMPERATURE

ENTERING

ELECTRICAL

EXHAUST GRILLE

ENTERING AIR TEMPERATURE

EXHAUST FAN

EXHAUST AIR

EACH

DIRECT EXPANSION

DRAWING

DOWN

DOOR LOUVER

DIFFERENCE

DIAMETER

INSIDE DIAMETER

INCH

INCH OF WATER GAUGE

ID

IN

INWG

KILOWATT

KILOWATT HOUR

KW

KWH

LEAVING AIR TEMPERATURE

POUND

LOCKED ROTOR AMPERES

MAXIMUM

MINIMUM CURRENT AMPERES

MOTOR CONTROL CENTER

MOTORIZED DAMPER

MINIMUM

NOISE CRITERIA

NORMALLY CLOSED

NOT IN CONTRACT

NORMALLY OPEN

NOT TO SCALE

NOT APPLICABLE

OUTSIDE AIR

OPENING

PRESSURE DROP

PHASE

LAT

LB

LRA

LWT

MAX

MCA

MCC

MD

MIN

NC

N C

NIC

N O

NTS

N/A

OA

OPNG

PD

PH

LEAVING WATER TEMPERATURE

IPLV INTEGRATED PART LOAD VALUE

HERTZHZ

ROOM

RETURN AIR

RATED LOAD AMPS

REVOLUTIONS PER MINUTE

RETURN AIR REGISTER

SUPPLY AIR

SUPPLY AIR GRILLE

STATIC PRESSURE

SPECIFICATION

SUPPLY AIR REGISTER

STAINLESS STEEL

TRANSFER DUCT

TEMPERATURE

TRANSFER GRILLE

THERMOSTAT

TYPICAL

UP THRU ROOF

VOLT

VOLUME DAMPER

RA

RH

RLA

RM

RPM

RR

SA

SG

SP

SPEC

SR

SS

TD

TEMP

TG

T STAT

TYP

UTR

V

VD

WATT

WITH

WET BULB

WATER COLUMN

WATER GAUGE

WEIGHT

W

W/

WB

WC

WG

WT

SF SQUARE FEET

YEARYR

HOSE END CONNECTION

CAP

BLIND FLANGE

UNION, FLANGED

UNION, SCREWED

COUPLING, JOINT

FLEXIBLE CONNECTOR

ANCHOR POINT

GUIDE

DRAIN LINE

HOT WATER SUPPLY

HOT WATER RETURN

D

HWR

HWS

HPR

HPS

CHECK VALVE

TEE, OUTLET DOWN

TEE, OUTLET UP

PIPE TURNING UP

BALL VALVE

BUTTERFLY VALVE

PIPE TURNING DOWN

CONNECTION, TOP

CONNECTION, BOTTOM

EXPANSION LOOP

STRAINER,W/ BLOWOFF

AND HOSE CONN.

AIR VENT, AUTOMATIC

RELIEF VALVE

PRESSURE REDUCING VALVE

THREE WAY CONTROL VALVE

TWO WAY CONTROL VALVE

AIR VENT, MANUAL

PRESSURE/TEMPERATURE TAP

FLOW SWITCH

THERMOMETER

PRESSURE GAUGE & GAUGE COCK

INCREASER, REDUCER

CALIBRATED BALL VALVE

W/ PRESSURE PORTS

DUCT STATIC PRESSURE SENSOR

ISOLATION VALVE

(BALL, GATE, OR BUTTERFLY)

HOA HAND-OFF-AUTO SWITCH

HIGH DENSITY POLYPROPYLENE

AC AIR CONDITIONING UNIT

SM SHEET METAL

AFS AIR FLOW MEASURING STATION

M

M

MD-XX

MD-XX

DEGREEDEG

DEGREE FAHRENHEIT°F

ROOM THERMOSTAT

RETURN/EXHAUST GRILLE OR

REGISTER SIZE 4

MAKE-UP AIR UNIT

SF

HPGR

HPGS

DT DAY TANK

SB

SB SECURITY BARS

CO2 CO2 SENSOR

FOR

FOS

FUEL OIL RETURN

FUEL OIL SUPPLY

VAV VARIABLE AIR VOLUME

ACC AIR COOLED CONDENSER

UH UNIT HEATER

PROPYLENE GLYCOLPG

BT BUFFER TANK

CHILLER

FCU FAN COIL UNIT

MAU

SUPPLY FANS

CF

HV HEATING & VENTILATION UNIT

CCEC CLOSED CIRCUIT

EVAPORATIVE COOLER

600x300 600x300

300 DIA

300 DIA

600x300(L) 600x300(L)

600 DIA (L) 600 DIA (L)

LINED RECTANGULAR DUCT. NUMBER

INDICATES CLEAR INSIDE DIMENSION

LINED ROUND DUCT. NUMBER

INDICATES CLEAR INSIDE DIMENSION

(24x12)

(12)

ROUND DUCT. NUMBER INDICATES

DUCT DIAMETER. IP UNITS IN

BRACKETS (TYPICAL)

(24)

(24x12)

RECTANGULAR DUCT. SIZE IN MM.

FIRST NUMBER INDICATES SIDE IN

VIEW, SECOND NUMBER INDICATES

SIDE IN DEPTH. IP UNITS IN

BRACKETS (TYPICAL)

RS

RL

REFRIGERANT LIQUID LINE

REFRIGERANT SUCTION LINE

HEAT PUMP LOOP SUPPLY

HEAT PUMP LOOP RETURN

HEAT PUMP GLYCOL SUPPLY

HEAT PUMP GLYCOL RETURN

SB SECURITY BARS

CABINET UNIT HEATERCUH

A. ALL DIMENSIONS ARE SI UNLESS OTHERWISE NOTED IN BRACKETS

B. ALL DUCT DIMENSIONS ARE INSIDE CLEAR.

C. VERIFY AND COORDINATE EQUIPMENT LAYOUT, SIZE, AND CONNECTING SERVICES WITH

EQUIPMENT ACTUALLY SELECTED FOR INSTALLATION.

D. DO NOT SCALE DUCTWORK AND EQUIPMENT FOR SIZE.

E. COORDINATE ENTIRE INSTALLATION OF THE HVAC SYSTEMS WITH THE WORK OF ALL OTHER

TRADES PRIOR TO ANY FABRICATION OR INSTALLATION.

F. COORDINATE EXACT LOCATION AND SIZES OF REQUIRED OPENINGS AND SUPPORTS FOR

FURNISHED EQUIPMENT WITH THE GENERAL CONTRACTOR.

G. ALL EQUIPMENT SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE EQUIPMENT

MANUFACTURER'S REQUIREMENTS.

H. PROVIDE ALL FITTINGS, TRANSITIONS, DAMPERS, VALVES, AND OTHER DEVICES REQUIRED

FOR COMPLETE WORKABLE INSTALLATION.

I. ALL EQUIPMENT, DUCTS, PIPING, AND OTHER DEVICES OR MATERIAL EXPOSED TO THE

WEATHER SHALL BE COMPLETELY WEATHERPROOF.

J. ALL VALVES, CONTROLS, DAMPERS, FANS, ETC. SHALL BE INSTALLED IN ACCESSIBLE

LOCATION. PROVIDE ADEQUATELY SIZED ACCESS DOOR OR PANELS WHERE REQUIRED.

K. THE LOCATION OF CEILING AIR INLETS AND OUTLETS SHALL BE IN ACCORDANCE WITH

MECHANICAL DRAWINGS.

L. PROVIDE VALVED DRAINS AT LOW POINTS AND MANUAL AIR VENTS AT HIGH POINTS OF ALL

HYDRONIC SYSTEMS.

M. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL LABOR REQUIRED TO INSTALL

COMPLETE AND OPERABLE MECHANICAL SYSTEMS AS INDICATED ON THE DRAWINGS, AS

SPECIFIED AND AS REQUIRED BY CODE.

N. CONTRACT DOCUMENT DRAWINGS FOR MECHANICAL WORK ARE DIAGRAMMATIC AND ARE

INTENDED TO CONVEY SCOPE AND GENERAL ARRANGEMENT ONLY.

O. POWER TO MOTORIZED DAMPERS SHALL BE BY DIV. 23 CONTRACTOR.

P. PROVIDE VIBRATION ISOLATORS FOR ALL PIPING SUPPORTS CONNECTED TO AND WITHIN 50

FEET OF ISOLATED EQUIPMENT IN ACCESSIBLE LOCATIONS (EXCEPT WHERE BASE ELBOW

SUPPORTS AND ANCHOR POINTS) THROUGHOUT MECHANICAL EQUIPMENT ROOMS.

Q. LOCATE ALL TEMPERATURE, PRESSURE, AND FLOW MEASURING DEVICES IN ACCESSIBLE

LOCATIONS WITH STRAIGHT SECTION OF PIPE OR DUCT UP- OR DOWN STREAM AS

RECOMMENDED BY MANUFACTURER FOR GOOD ACCURACY.

R. ALL CONTROL WIRING SHALL COMPLY WITH THE NATIONAL ELECTRICAL CODE AND

SPECIFICATIONS.

S. CONCRETE HOUSEKEEPING PADS TO SUIT MECHANICAL EQUIPMENT SHALL BE SIZED BY A

MECHANICAL CONTRACTOR.

T. FOR TYPICAL DETAILS SEE MECHANICAL SHEETS.

U. PROVIDE SUFFICIENT CLEARANCE FOR AHU'S, AND AC'S COIL/PULL AND IN FRONT OF

ACCESS DOORS/PANELS FILTER.

V. PER ANTI-TERRORISM FORCE PROTECTION GUIDELINES, ALL OVERHEAD UTILITIES, MOUNTED

FIXTURES EQUIPMENT AND FEATURES WEIGHTING 31 POUNDS OR MORE SHALL BE BRACED

TO RESIST 0.5 TIMES THE COMPONENT WEIGHT IN ANY DIRECTION AND 1.5 TIMES THE

COMPONENT WEIGHT IN THE DOWNWARD DIRECTION. THIS STANDARD DOES NOT PRECLUDE

THE NEED TO DESIGN ATTACHMENTS AND BRACING TO RESIST FORCES REQUIRED BY

OTHER CRITERIA SUCH AS WIND, SEISMIC, OR SNOW LOADING.

W. 120V POWER FROM ELECTRICAL PANELS TO DDC CONTROLLERS, ALARM PANELS AND OTHER

DDC EQUIPMENT SHALL BE BY DIV. 23 CONTRACTOR.

X. DUCTWORK LAYOUT IS DIAGRAMMATIC ONLY. IN THE PROCESS TO COORDINATE THE DUCT

INSTALLATION WITH OTHER TRADES, THE CONTRACTOR MAY REARRANGE THE DUCTWORK

DOWNSTREAM OF AHU EQUIPMENT FOR AN OPTIMAL LAYOUT. THE FOLLOWING RULES SHALL

BE FOLLOWED:

1. MAXIMUM OF 5FT OF FLEXIBLE DUCT SHALL BE USED. SEE TYPICAL DETAILS ON

MECHANICAL DRAWINGS.

2. DUCT SIZE FOR THE TOTAL FLOW THROUGH THE BRANCH SHALL BE AS FOLLOW:

0 – 40 CFM 4-INCH 425 - 660 CFM 12-INCH

45 - 70 CFM 5-INCH 665 - 1000 CFM 14-INCH

75 - 110 CFM 6-INCH 1005 – 1500 CFM 16-INCH

115 – 230 CFM 8-INCH 1550 – 2000 CFM 18-INCH

235 - 420 CFM 10-INCH 2005 – 2600 CFM 20-INCH

Y. DUCTS SHALL NOT BE REINFORCED WITH TIE RODS OR OTHER INTERNAL REINFORCEMENT

EXCEPT FOR DUCT DIMENSIONS GREATER THAN 85 INCH AND STATIC PRESSURE IN EXCESS

OF 6 INCHES WG, AS REQUIRED BY SMACNA HVAC DUCT CONSTRUCTION STANDARDS METAL

AND FLEXIBLE, THIRD EDITION.

AIR FLOW QUANTITY: L/S (CFM)

AIR FLOW QUANTITY: L/S (CFM)

AIR FLOW QUANTITY: L/S (CFM)

AIR FLOW QUANTITY: L/S (CFM)

CD-4

115 (250)

CG-4

260 (550)

SR-4

455 (955)

RG-4

305 (635)

MICHIGAN MECHANICAL CODEMMC

VAV VARIABLE AIR VOLUME BOX

RELATIVE HUMIDITY

HW CIRCULATION PUMP

PC

PUMPED CONDENSATE

DETAILDET

HP HORSE POWER

HEATING, VENTILATING

AND AIR CONDITIONING

HVAC

MAXIMUM FUSE SIZEMFS

WSHP WATER SOURCE HEAT PUMP

SD SUPPLY DIFFUSER

RETURN GRILLERG

127th WING

WELLNESS

CENTER

BUILDING 168

RENOVATION

http://www.AECOM.com

27777 Franklin Road, Suite 2000

Southfield, MI 48034

United States

P: 248 204 5900 F: 248 204 5901

FIRST FLOOR

PLAN -

MECHANICAL

M101

DEMO

PROJECT

AREA

BLDG #168

DEMOLITION KEYED NOTES:

DEMOLISH EXISTING SUPPLY AIR REGISTER IN CEILING AND ASSOCIATED BRANCH/FLEX DUCT

VOLUME DAMPER AND ACCESSORIES.

DEMOLISH ABANDONED THERMOSTAT AN ASSOCIATED CONTROLS.

DEMOLISH CAPPED RETURN AIR GRILLES IN CEILING AND ASSOCIATED BRANCH/FLEX DUCT

AND ACCESSORIES.

DEMOLISH EXISTING 72"x18" CEILING AIR GRILLES AND ASSOCIATED ACCESSORIES.

EXISTING AIR-COOLED CONDENSER UNIT SHALL REMAIN IN USE. DISCONNECT REFRIGERANT

LINES FOR RE-ROUTING.

DISCONNECT AND SALVAGE EX. UNIT AND ASSOCIATED WIRING, CONTROLS AND ACCESSORIES

FOR RELOCATION.

EXISTING SERVER SHALL BE RELOCATED (BY OTHERS).

DEMOLISH EXISTING FIN TUBE / CONVECTOR UNIT AND ASSOCIATED PIPING, VALVES AND

CONTROLS. SEE GENERAL NOTE # 5 FOR ANY ASBESTOS WORK.

EXISTING FIN TUBE SHALL BE ABANDONED IN PLACE.

DEMOLISH EXISTING KITCHEN EXHAUST HOOD AND ASSOCIATED SUPPORTS, DUCTWORK,

EXHAUST FAN AND CONTROLS. SEE GENERAL NOTE # 5 FOR ANY ASBESTOS WORK.

DEMOLISH EXISTING DISHWASHER EXHAUST HOOD AND ASSOCIATED SUPPORTS, DUCTWORK

AND CONTROLS. SEE GENERAL NOTE # 5 FOR ANY ASBESTOS WORK.

EXISTING WALL MOUNTED EXHAUST VENT SHALL REMAIN FOR RESUE.

DISCONNECT AND SALVAGE EXISTING SUPPLY AND/OR RETURN DIFFUSERS IN CEILING FOR

REUSE AND RELOCATION.

DEMOLISH EXISTING BRANCH DUCT TO EXTENT SHOWN AND CAP FOR REUSE.

DISCONNECT EXISTING SPACE TEMPERATURE SENSOR AND ASSOCIATED WIRING FOR

RELOCATION.

EXISTING TO REMAIN FOR REUSE.

GENERAL NOTES:

1. DO NOT SCALE DRAWINGS.

2. ALL DIMENSIONS ARE IN NOMINAL BRITISH IMPERIAL UNITS.

3. DOCUMENTS ARE BASED UPON OWNER'S RECORD DRAWINGS. NOTIFY ARCHITECT OF

DISCREPANCIES OR CONDITIONS REQUIRING SUPPLEMENTAL INSTRUCTION PRIOR TO

CONTINUATION OF WORK.

4. VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS IN FIELD PRIOR TO START OF WORK.

5. REFER TO ASBESTOS ABATEMENT AND DISCOVERY NOTES ON DRAWING AD01 FOR EXTENT

OF RESPONSIBILITY FOR REMOVAL OF ASBESTOS CONTAINING MATERIALS. THE

CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFICATION OF EXTENT OF ASBESTOS

ABATEMENT REQUIRED FOR BID.

6. ALL EXISTING HVAC SYSTEMS SHALL BE VERIFIED FOR PROPER REUSE CONDITION. ALL

EXISTING DUCTWORK AND CEILING GRILLES TO REMAIN IN USE SHALL BE CLEANED

THOROUGHLY FROM DUST AND STAINS.

7. PATCH ALL FLOOR, WALL, AND CEILING OPENINGS CREATED BY DEMOLITION WORK. PAINT

AND PATCH TO MATCH EXISTING.

8. PRIOR TO PERFORMING WORK THAT REQUIRED INTERRUPTION OF SERVICE TO THE

BUILDING, NOTIFY GENERAL CONTRACTOR AND OWNER IN WRITING 5 WORKING DAYS PRIOR

TO PERFORMING WORK. NO WORK THAT INTERFERES WITH THE OPERATION OF THE FACILITY

SHALL BE PERFORMED WITHOUT WRITTEN APPROVAL OF GENERAL CONTRACTOR AND

OWNER.

9. ALL WORK SHALL COMPLY WITH LOCAL CODES, STANDARDS, MANUFACTURERS

RECOMMENDATIONS AND ANG DESIGN POLICIES ANGTEL-15-01, ANGTEL-15-01-04,

ANGTEL-15-01-05, ETC.

M

127th WING

WELLNESS

CENTER

BUILDING 168

RENOVATION

http://www.AECOM.com

27777 Franklin Road, Suite 2000

Southfield, MI 48034

United States

P: 248 204 5900 F: 248 204 5901

FIRST FLOOR

PLAN -

M201

NEW

PROJECT

AREA

BLDG #168

NEW WORK KEYED NOTES:

EXISTING DIFFUSER TO REMAIN. BALANCE TO SUPPLY AIR VOLUME (CFM) SHOWN. TYPICAL

FOR ALL EXISTING SHOWN

PROVIDE NEW RETURN AIR CEILING GRILLE AND CONNECT TO EXISTING RETURN AIR MAIN

WITH ASSOCIATED FLEX DUCT AND VOLUME DAMPER, AS SHOWN. BALANCE TO AIR VOLUME

(CFM) SHOWN.

PROVIDE NEW SUPPLY AIR CEILING DIFFUSER AND CONNECT TO EXISTING SUPPLY AIR MAIN

WITH ASSOCIATED FLEX DUCT AND VOLUME DAMPER, AS SHOWN. BALANCE TO AIR VOLUME

(CFM) SHOWN.

RECONNECT EXISTING AIR COOLED CONDENSER REFRIGERANT GAS AND LIQUID LINES TO

RELOCATED EXISTING INDOOR COOLING UNIT (EX.AC). ROUTE LINES FROM OUTSIDE

THROUGH NEW CHASE TO CONNECT TO UNIT.

RELOCATE EXISTING AC UNIT WITH ASSOCIATED SPACE THERMOSTAT AND INSTALL IN NEW

LOCATION SHOWN. RECONNECT TO EXISTING OUTDOOR CONDENSING UNIT (SEE NOTE 4).

EXTEND CONDENSATE DRAIN LINE AS NEEDED.

PROVIDE NEW INLINE TYPE CENTRIFUGAL EXHAUST FAN (EF-1) WITH ASSOCIATED BACK

DRAFT DAMPER, CONTROLS AND ACCESSORIES. MOUNT NEW FAN ABOVE CEILING SPACE

AND COORDINATE WITH EXISTING SYSTEMS. SUPPORT FAN FROM EXISTING BUILDING

STRUCTURE USING SPRING ISOLATORS. CONNECT NEW FAN TO EXISTING EXHAUST DUCT

AND AIR DISCHARGE AIR WALL VENT LOCATED ABOVE KITCHEN AREA. NEW EXHAUST FAN

OPERATION SHALL BE INTERLOCKED WITH EX. RTU-2 RUN SCHEDULE. CONNECT NEW EF-1

TO EXISTING BUILDING ALC DDC PANEL (LGR 250) LOCATED IN BOILER ROOM (FIELD VERIFY

PANEL LOCATION).

PROVIDE NEW MOTORIZED DAMPER AND ACTUATOR FOR EXHAUST AIR AND INSTALL ON

NEW DUCT THAT CONNECTS TO EXISTING EXHAUST DISCHARGE DUCT. FIELD VERIFY

EXISTING DUCT AND SIZE ABOVE THE CEILING. INTERLOCK DAMPER OPERATION WITH NEW

EXHAUST FAN EF-1.

PROVIDE NEW EXHAUST DUCT AND CEILING GRILLE IN LOCATION SHOWN WITH ASSOCIATED

VOLUME DAMPER AND SUPPORTS. BALANCE NEW EXHAUST GRILLE TO AIR VOLUME (CFM)

SHOWN.

RELOCATE EXISTING SUPPLY AND/OR RETURN CEILING DIFFUSER OR GRILLES TO LOCATION

SHOWN. PROVIDE NEW FLEX DUCT (UNLESS PLENUM RETURN) AND RECONNECT EXISTING

SUPPLY AND/OR RETURN DIFFUSER TO EXISTING DUCT. BALANCE RELOCATED EXISTING

DIFFUSER TO AIR VOLUME (CFM) SHOWN.

RELOCATE EXISTING ROOM TEMPERATURE SENSOR TO NEW LOCATION SHOWN. EXTEND

CONTROL WIRING AS NEEDED. FIELD VERIFY.

PROVIDE NEW SUPPLY AIR CEILING DIFFUSER IN CORRIDOR 118 AND CONNECT TO EXISTING

SUPPLY AIR MAIN. PROVIDE WITH ASSOCIATED FLEX DUCT, VOLUME DAMPER AND FIRE

DAMPER, AS SHOWN. BALANCE TO AIR VOLUME (CFM) SHOWN.

RELOCATE EXISTING ROOM TEMPERATURE THERMOSTAT TO NEW LOCATION SHOWN.

EXTEND CONTROL WIRING AS NEEDED. FIELD VERIFY.

GENERAL NOTES:

1. DO NOT SCALE DRAWINGS.

2. ALL DIMENSIONS ARE IN NOMINAL BRITISH IMPERIAL UNITS.

3. DOCUMENTS ARE BASED UPON OWNER'S RECORD DRAWINGS. NOTIFY ARCHITECT OF

DISCREPANCIES OR CONDITIONS REQUIRING SUPPLEMENTAL INSTRUCTION PRIOR TO

CONTINUATION OF WORK.

4. VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS IN FIELD PRIOR TO START OF WORK.

5. REFER TO ASBESTOS ABATEMENT AND DISCOVERY NOTES ON DRAWING AD01 FOR EXTENT

OF RESPONSIBILITY FOR REMOVAL OF ASBESTOS CONTAINING MATERIALS. THE

CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFICATION OF EXTENT OF ASBESTOS

ABATEMENT REQUIRED FOR BID.

6. ALL EXISTING HVAC SYSTEMS SHALL BE VERIFIED FOR PROPER REUSE CONDITION. ALL

EXISTING DUCTWORK AND CEILING GRILLES TO REMAIN IN USE SHALL BE PROFESSIONALLY

CLEANED AND FLUSHED THOROUGHLY FROM DUST, DEBRIS AND STAINS.

7. INSTALL NEW HVAC EQUIPMENT WITH ADEQUATE CLEARANCE SPACE, FOR ACCESS AND

MAINTENANCE, AS REQUIRED PER ANG-ETL POLICIES, UFC STANDARDS AND

MANUFACTURERS REQUIREMENTS.

8. ALL EXISTING AND NEW SUPPLY, RETURN AND EXHAUST DIFFUSERS AND GRILLES SHALL BE

AIR BALANCED PER AIR VOLUME (CFM) VALUES SHOWN ON DRAWING.

9. REFER TO ELECTRICAL DRAWINGS FOR ADDITIONAL HVAC EQUIPMENT INFORMATION.

10. PRIOR TO PERFORMING WORK THAT REQUIRED INTERRUPTION OF SERVICE TO THE

BUILDING, NOTIFY GENERAL CONTRACTOR AND OWNER IN WRITING 5 WORKING DAYS PRIOR

TO PERFORMING WORK. NO WORK THAT INTERFERES WITH THE OPERATION OF THE FACILITY

SHALL BE PERFORMED WITHOUT WRITTEN APPROVAL OF GENERAL CONTRACTOR AND

OWNER.

11. ALL WORK SHALL COMPLY WITH LOCAL CODES, STANDARDS, MANUFACTURERS

CENTER

BUILDING 168

RENOVATION

http://www.AECOM.com

27777 Franklin Road, Suite 2000

Southfield, MI 48034

United States

P: 248 204 5900 F: 248 204 5901

MECHANICAL -

M501

SCHEDULES

DESCRIPTIONTAG

ROUGH-IN SIZES

W * *

NOTES/

ACCESSORIESHW CW V

MOP BASIN FLOOR-MOUNTED MOLDED STONE MOP BASIN, WALL-MOUNTED SERVICE FAUCET WITH

INTEGRAL VACUUM BREAKER, PAIL HOOK AND WALL BRACKET, RUBBER HOSE AND MOP HANGER.

FIXTURE: FIAT MSB 2424 MOLDED STONE

FAUCET: CHICAGO FAUCET 540-LD8975WXFABCP

HOSE AND BRACKET: FIAT 832AA

MOP HANGER:

MS-1 3"

LAV-1 1 12" 1

2"1 12" 1

2" A, B, DLAVATORY:

AMERICAN STANDARD LUCERNE MODEL 0355.012 (OR EQUAL), ADA COMPLIANT, WALL-MOUNTED

WHITEVITREOUS CHINA, FRONT OVERFLOW, FAUCET LEDGE, SPLASH SHIELDS, OVERALL SIZE: 20 12"x 18 14" x

6 12" DEEP. PROVIDE WITH CONCEALED ARMS SUPPORT.

FLAT GRID STRAINER w/ 1-14" TAILPIECE OFFSET DRAIN, P-TRAP CHROME PLATED BRASS.

TRUE-BRO UNDERSINK LAV GUARD FOR UTILITIES.

FAUCET - CHICAGO MODEL 2200-4E2805ABCP, LOW FLOW, 0.5 GPM, SINGLE LEVER, DECK-MOUNTED, VANDAL-PROOF, CHROME-PLATED, PRESSURE COMPENSATING, WITH 4 3 4" CAST SPOUT WITH LAMINAR

FLOW OUTLET, INLETS WITH STAINLESS STEEL SUPPLIES WITH 3 8" COMPRESSION FITTING.

THERMOSTATIC/PRESSURE BALANCING MIXING VALVE - POWERS E480T/P, ASSE 1016

1 12"1 12" A, C, D1 2"1

2"

SK-1

DOUBLE-COMPARTMENT SINK, TOP-MOUNTED, 18 GAUGE 304 STAINLESS STEEL, ADA COMPLIANT, 6-12" BOWL DEPTH & (4) 1-1/2" FAUCET HOLES ON 4" CENTERS FOR FAUCET AND SPRAY HOSE. PROVIDE WITH PERFECT DRAINS & STRAINERS, CHROME PLATED BRASS P-TRAP W/ CLEAN-OUT PLUG, AND SUPPLIES

AND ESCUTCHEON PLATES.

MANUFACTURER: ELKAY - MODEL LRAD332165PD3, OR EQUAL.

FAUCET: CENTERSET, DECK-MOUNTED, ARC SPOUT, 4" LEVER HANDLES, CHROME PLATED BRASS, 4"

FAUCET HOLES CENTERS.

MANUFACTURER: ELKAY MODEL LKD24898BHC, OR EQUAL.

FIXTURES TO BE FURNISHED AND INSTALLED IN ACCORDANCE TO THE LATEST EDITION OF THE "BARRIER

FREE DESIGN" REQUIREMENTS OF THE STATE'S CONSTRUCTION CODE.

D

A

B

3/8"C.P. SUPPLY ASSEMBLIES WITH 1/2 x 3/8 LOOSE ANGLE KEY STOPS AND ESCUTCHEON PLATES

1-1/4 x 1-1/2 17 GA. CHROME PLATED TUBULAR BRASS P-TRAP W/ CLEANOUT PLUG & ESCUTCHEON PLATE.

PROVIDE PER MANUFACTURER SHOWN OR APPROVED EQUAL.

UNLESS OTHERWISE SHOWN ON DRAWINGS.

D

C 1-1/2" 17 GA. CHROME PLATED TUBULAR BRASS P-TRAP W/ CLEANOUT PLUG & ESCUTCHEON PLATE.

1"4" 2"WC-1 WATER CLOSET:

AMERICAN STANDARD, MODEL MADERA 3461.001 (OR EQUAL), ADA COMPLIANT, FLOOR-MOUNTED, HIGH EFFICIENCY 1.1 TO 1.6 GPF, WHITE VITREOUS CHINA, ELONGATED BOWL, 1-12" TOP SPUD WITH

ADJUSTABLE CARRIER.

OLSONITE MODEL 9555CT SOLID PLASTIC SEAT, OPEN FRONT SEAT (LESS COVER).

FLUSH VALVE - AMERICAN STANDARD MODEL 6047-121.002 MANUAL FLOWISE, 1.28 GPF, 1-12" TOP SPUD WITH SECURING NUT, 1" I.P.S. WATER INLET, CAST BRASS VALVE AND COVER WITH CHROME-PLATED FINISH, VANDAL RESISTANT, BACK-FLOW PREVENTION, VACUUM BREAKER ,AND ESCUTCHEON PLATE.

- D

WALL-MOUNTED WATER COOLER:

-SELF-CONTAINED, HEAVY-DUTY, VANDAL-RESISTANT WATER COOLER.

14 GA STAINLESS STEEL WELDED CONSTRUCTION, TEMPER-RESISTANT & CURVED PROFILE FOR

SAFETY.

-VANDAL-RESISTANT FRONT PUSHBUTTON ACTIVATION.

-VANDAL-RESISTANT STREAMSAVER BUBBLER AND INTEGRAL DRAIN IN BASIN.

-LOUVERED SCREENS WITH HOLES SIZED TO PREVENT EASY TEMPERING.

-DELIVERS 8 GPH OF 50°F WATER AT 90°F AMBIENT AND 80°F INLET WATER.

-ELECTRICAL: 115V/60 Hz, 4.0 FULL LOAD AMPS, 370 WATTS.

-COMPRESSOR: HERMETICALLY-SEALED, RECIPROCATING TYPE, SINGLE PHASE, SEALED-IN LIFETIME

LUBRICATION.

-CONDENSER: FAN-COOLED. FAN MOTOR PERMANENTLY LUBRICATED.

-COOLING UNIT: COMBINATION TUBE-TANK TYPE. COPPER TUBING WITH STAINLESS STEEL TANK.

FULLY INSULATED.

-REFRIGERANT: R134a CONTROLLED BY CALIBRATED CAPILLARY TUBE.

-INCLUDED WATERSENTRY VII 1500-GALLON CAPACITY FILTER

-MEET ADA GUIDLINES AND CERTIFIED TO NSF/ANSI 42, 53, 61 AND 372.

-CERTIFIED TO UL399 AND CAN/CSA 22.2 NO. 120.

-MEETS FEDERAL AND STATE LOW-LEAD REQUIREMENTS

-ACCEPTABLE MANUFACTURERS: ELKAY (LVRCHD8S), HAWS, OASIS, OR EQUAL TO MEET BUY

AMERICAN ACT.

-INSTALL ALL CONTROLS BETWEEN 38" AND 48" ABOVE FINISHED FLOOR IN COMPLIANCE WITH LATEST ADA STANDARDS. MAXIMUM FLOW TO BE 1.75 GPM IN COMPLIANCE WITH ENERGY POLICY ACT OF 1992 AND ASME/ANSI STANDARD A112.18.1M. SET TEMPERATURE LIMIT STOP TO 110°F DISCHARGE.

DESCRIPTIONTAG

ROUGH-IN SIZES

W * *

NOTES/

ACCESSORIESHW CW V

REMARKSMARK SERVICE TYPE MODEL CFM RPM

(HP)

BHP

(LBS)

WEIGHT

@ 5'

SONE

NOISE MOTOR

VOLT PHASE POWER

(HP)(PH)(V)

EF-1 KITCHEN CEILING SPACE EXHAUST BSQ-80-5 625 0.75 2164 0.43 20 79 208 3 1

2 1, 2, 3, 4, 5, 6, 7, 8

MOUNTING

SUSPENDED

LOCATION ESP

IN. WG

INLINE

CENTRIFUGAL

REMARKS:

1. MANUFACTURER IS GREENHECK OR APPROVED EQUAL.

2. PROVIDE WITH UNIT-MOUNTED DISCONNECT.

3. PROVIDE WITH HANGING SPRING ISOLATOR SUPPORTS.

4. PROVIDE WITH BACKDRAFT DAMPER.

5. MOUNT ABOVE CEILING AND ATTACH TO BUILDING STRUCTURE.

6. FAN TO INTERLOCK AND RUN WITH EX. RTU-2 OPERATION.

7. INTERLOCK WITH MOTORIZED DAMPER.

8. PROVIDE WITH MATCHING MOTOR COVER AND BELT GUARD.

9. PROVIDE WITH 1" FIBERGLASS DUCT LINER ON FAN HOUSING AND MOTOR COVER.

RECTANGULAR

SUPPLY DUCT

CEILING DIFFUSER CONNECTION

AIR FLOW

AIR FLOW

15° MAX

30° MAX

15° MAX

15° MAX

15° MAX

30° MAX

DUCT TRANSITION SCHEMATIC

DUCT SUPPORTS

SHEET METAL DUCTWORK CONSTRUCTION DETAILS

TYPICAL SUPPLY DUCT TAKEOFF DETAIL TYPICAL EXHAUST OR RETURN BRANCH DUCT DETAILIN-LINE FAN MOUNTING DETAIL

1 12" 1 12" 1 2"

-WALL-MOUNTED, VITREOUS CHINA, SIPHON JET WITH 3/4" TOP SPUD, ANTI-BACKSLASH WALL AND

EXTENDED RIM.

-ACCEPTABLE MANUFACTURER: KOHLER, DEXTER URINAL MODEL K-5016-ET, OR EQUAL.

-PROVIDE WITH MANUAL FLUSH VALVE, TOP-MOUNTED, EXPOSED, CHROME PLATED, 0.5 GPF, 3 4" I.P.S.

WATER CONNECTION, BACK-FLOW PROTECTION, VANDAL RESISTANT, ADA COMPLIANT, DIAPHRAGM TYPE.

-PROVIDE WITH COMPATIBLE WALL SUPPORTS.

UR-1

FD-1 FLOOR DRAIN:

ZURN MODEL ZN-415-3NH-5BZ: CAST IRON BODY, FLANGE, FLASHING RING, BOTTOM OUTLET, 6" DIAMETER

NICKEL BRONZE STRAINER. PROVIDE WITH 12" TRAP PRIMER CONNECTION.

2" 1 12" 3 4"

3"

1 12" 1 2"1

2"

2"

127th WING

WELLNESS

CENTER

BUILDING 168

RENOVATION

http://www.AECOM.com

27777 Franklin Road, Suite 2000

Southfield, MI 48034

United States

P: 248 204 5900 F: 248 204 5901

FIRST FLOOR

PLAN -

PLUMBING

P101

DEMO

PROJECT

AREA

BLDG #168

DEMOLITION KEYED NOTES:

DEMOLISH EXISTING PLUMBING FIXTURE AND DISCONNECT DOMESTIC WATER, SAN AND VENT

PIPING BACK AT MAINS TO EXTENT SHOWN.

EXISTING CW AND HW PIPING TO REMAIN. CAPPED UNUSED PIPING AT WALL OR BACK AT MAINS

IF ACCESSIBLE.

REMOVE EXISTING FRIDGE AND DISCONNECT EXISTING WATER LINE, IF ANY, BACK AT MAIN.

TURN EXISTING FRIDGE BACK TO OWNER.

DEMOLISH EXISTING ICE MAKER AND DISCONNECT EXISTING WATER LINE AND FILTER BACK AT

MAIN. TURN EXISTING ICE MAKER BACK TO OWNER.

EXISTING DISHWASHER TO REMAIN IN USE. VERIFY EXISTING WATER AND DRAIN FOR PROPER

CONDITION AND REPAIR ANY LEAK.

DEMOLISH EXISTING CW, HW AND HWR PIPING CONNECTIONS ROUTED FROM PIPING TRENCH

AND CAP.

EXISTING MAIN VENT PIPE THROUGH ROOF SHALL REMAIN. CAP IF UNUSED.

DISCONNECT EXISTING WATER LINE FROM DEMOLISHED SINK AND…